Unrestricted © Siemens 2019
www.siemens.com/sinamics-g120xUnrestricted © Siemens 2019
SINAMICS G120XFunkce, výbava, vlastnosti
TIA na dosah 1/2019
Unrestricted © Siemens 2019
G120X a Digitalizace
APP:
Analyze My
Drives
in-cloud
in-line
in-m
achine
SINAMICS connect
G120X
data
G120X can…
ServicesProduction
execution
Production
engineering
Production
planning
Product
design
Machine
services
Machine
operation
Machine
commissioning
Machine
engineering
Machine
concept
NX MCD, SIZER, E-
Plan
DT Configurator, SIZE, SAM (webserver),
IOP-2
SAM (webserver),
IOP-2
IOP-2, SAM
(webserver), Analyze
MyDrives
TIA Portal (GSD),
SINAMICS Web
server, IOP-2
TIA Portal (GSD),
SINAMICS Web
server, IOP-2
TIA Portal (GSD), IOP-2,
SINAMICS Web server,
Analyze MyDrives
Page 5
• ... simply be connected to the cloud
• ... visualize important operating states
• ... show the need for service → AMD
Up to 8
drives
RS2321
2 w
ire
PT
P
2 w
ire
2 w
ire
PT
P
PT
P
1 RS232: SUB-D 9pol
Unrestricted © Siemens 2019
Page 6
G120X a SINAMICS Connect
Wiring example
Pin Signal Use
1 DCD Data Carrier
detect
2 RxD Received data
3 TxD Transmited data
4 DTR Data terminal
ready
5 M Ground (GND)
6 DSR Data set ready
7 RTS Request to send
8 CTS Clear to send
9 RI Incoming call
RS232: SUB-D 9pol (female) SINAMICS Connect
SINAMICS
G120X
SINAMICS
Connect
TX1
RX1
M
PE1
SINAMICS G120X SINAMICS Connect
Pin 2 TX1
Pin 3 RX1
Pin 5 M
Pin 5 PE1
Unrestricted © Siemens 2019
G120X
Technická data
FSA
FSB,FSC
STO terminals
G120X
Safety Integrated STO SIL 3 HW
Memory card (SD card) Yes
Real-time Clock Yes
BOP-2 Yes
IOP-2 Yes
WEBSERVER (SAM) Yes
Motor support incl. 3rd party IE4
• Switching frequency (2) 4kHz to 16Khz
(with derating)
• Asynchronous
• V/f control linear, parabolic
• Sensorless vector mode
• Reluctance motor (Siemens, 3rd party1 )
• Permanent magnet1
Page 7
Product data overview
1 Please contact your local Siemens partner
Unrestricted © Siemens 2019
G120X
Ochrana měniče lakováním 3C2 / 3C33
Page 8
Environment parameters
IEC 60721-3-3Units
Class
3C2 3C3
Mean Max Mean Max
Sea salt mg/m3 Salt mist
Sulphur dioxide mg/m3 0.3 1 5 10
Hydrogen sulphide mg/m3 0.1 0.5 3 10
Chlorine mg/m3 0.1 0.3 0.3 1
Hydrogen chloride mg/m3 0.1 0.5 1 5
Hydrogen fluoride mg/m3 0.01 0.03 0.1 2
Ammonia mg/m3 1 3 10 35
Ozone mg/m3 0.05 0.1 0.1 0.3
Nitrogen Oxides mg/m3 0.5 1 3 9
1 The values refer to a temperature of 20°C and a pressure of 101.3 kPa2 Mean values are expected long-term values. Maximum values are limit or peak values, occurring over a period of time no longer than 30min/day3 In preparation
• FSA ... FSG:
Protected
according to 3C3
to EN 60721-3-3
• FSH/FSJ:
Protected
according to 3C2
according to EN
60721-3-3
Unrestricted © Siemens 2019
G120X
IP20: Montáž & rozměry
Side-by-side mounting until 50°C1 ambient temperature
Frame
size
Power
range
(kW)
380-480V
Width
mm (inch)
Height mm (inch)Depth incl.
CU
mm (inch)
w/o
screening
plate
With
screening
plate
FSA 0.75 – 3 73 (2.9) 232 (9.1) 329.8 (13) 209 (8.2)
FSB 4 – 7.5 100 (3.9) 275 (10.8) 383 (15.1) 209 (8.2)
FSC 11 – 15 140 (5.5) 295 (11.6) 423 (16.7) 209 (8.2)
FSD 18.5 – 37 200 (7.9) 472 (18.5) 625 (24.6) 239 (9.4)
FSE 45 – 55 275 (10.8) 551 (21.7) 850 (33.5) 239 (9.4)
FSF 75 – 132 305 (12) 709 (27.9) 969 (38.1) 360 (14.2)
FSG 160 – 250 305 (12) 999 (39.3) 1255 (49.4) 360 (14.2)
FSH 315 – 400 548 (21.6) 1695 (66.3) - 393 (15.5)
FSJ 450 - 560 801 (31.5) 1621 (63.8) - 393 (15.5)
IP20
Page 9
Minimum spacing at the front: 100mm
FSA – FSG: Side-by-Side mounting without space between drives
FSH – FSJ: requires 30mm distance between drives
Clearance distance: mm (inch)
FSA-C: A= 80 (3); B= 100 (4); FSD-G: A= 300 (12), B= 350 (14);
FSH-J: A= 200 (12); B: 250 (8)
1 FSA,B,C: 50mm between each other when ambient temperature >50°C
Unrestricted © Siemens 2019
G120X
IP20: Zapojení měniče
Wiring example Interface
Page 10
PROFINET connections
FS B FS A…C
MotorLine supply
Unrestricted © Siemens 2019
G120X
KIT - stříška IP21, rozměry a instalace
IP21 KIT dimensions Side-by-Side1 mounting without space
between the converters
Page 11
FS E FS F FS G
Frame
sizeClearance
A
mm
(inch)
B
mm
(inch)
C
mm
(inch)
D
mm
(inch)
Ø
mm
(inch)
FSA42 (1.7) 25 (1) 92 (3.6) 54 (2.1) 306 (12)
5.5
(0.2)
FSB63 (2.5) 25 (1) 120 (4.7) 80 (3.1) 306 (12)
5.5
(0.2)
FSC94 (3.7) 25 (1) 160 (6.3) 118 (4.6) 306 (12)
5.5
(0.2)
FSD 300 (37.1) 28 (1.1) 218 (8.6) 170 (6.7) 323 (12.7) 6 (0.2)
FSE 300 (37.1) 28 (1.1) 293 (11.5) 230 (9.1) 323 (12.7) 6 (0.2)
FSF 300 (37.1) 28 (1.1) 323 (12.7) 270 (10.6) 323 (12.7) 6 (0.2)
FSG300 (37.1) 28 (1.1) 323 (12.7) 270 (10.6) 323 (12.7) 6 (0.2)
IP21 top cover on the control cabinet panel using two M5 screws
(tightening torque: 6 Nm (53.1 lbf.in)
1 Until 50°C, then 50mm between each other
Unrestricted © Siemens 2019
G120X
KIT – Push Through IP20, instalace a rozměry
IP20 PT KIT
Page 12
Note: degree of protection for PT parts
Outside the cabinet is IP20
FS A-C FS D-GFrame
size
Width
mm (inch)
Height mm (inch)Depth
mm (inch)
H - with
screening
plate
H1- w/o
screening
plate
T1 T2
FSA 126 (5) 390 (15.4) 300 (11.8) 160 (6.3) 57 (2.2)
FSB 153 (6) 450 (17.7) 345 (13.6) 153 (6) 66 (2.6)
FSC 191 (7.5) 473 (18.6) 361 (14.2) 154 (6.1) 65 (2.5)
FSD 271 (10.6) 647 (25.5) 514 (20.2) 142 (5.6) 98 (3.9)
FSE 360 (14.2) 773 (30.4) 600 (23.6) 145 (5.7) 93 (3.7)
FSF 396 (15.6) 1003 (39.5) 749 (29.5) 185 (7.3) 185 (7.3)
FSG384 (15.1) 1275 (50.2) 1026 (40.4) 184 (7.2) 188 (7.4)
Drilling dimensions can be found within the operation instructions.
Unrestricted © Siemens 2019
G120X a ovládací panely
IOP-2 a BOP-2
Page 13
• Easy commissioning of standard applications via various
assistants
• Knowledge of parameter structure not necessary
• Serial commissioning through clone function
• Diagnosis due to clear text display, usable on-site
• Integrated support function to troubleshoot errors
• Simplified Update of languages, assistants and FW via USB
• Commissioning wizard
• 2-line display with text display
• Diagnostics for parameter display without auxiliary function
• Serial commissioning through clone function
• Key operation with menu structure
• Door mounting available
Intelligent operator panel (IOP-2) Basic operator panel (BOP-2
Enhances the interface & communication capabilitiesIntelligent commissioning & configuration tool
Unrestricted © Siemens 2019
Feature / function Benefits
During commissioning, only the
necessary data must be entered. All
other data will get a default setting.
Accelerated commissioning. It is no longer
necessary to go through all setup screens.
The system tells the user via the status
icons , , , which "data" is
missing or needs to be checked.
Targeted user guidance allows quick and
easy commissioning. Configuration data
which hast to be checked or entered will
be marked.
Free access to configuration data No sequential process (step by step)
anymore.
Access to all important configuration data
For most applications, it is no longer
necessary to leave the setup. A
subsequent access to the parameter list
for further configurations is no longer
necessary.
IOP-2 FW2.3
Nový koncept pro uvedení do provozu
Page 14 IOP - Bernd Lerp
Unrestricted © Siemens 2019
IOP-2 FW2.3
Quick Startup
Language,
Date/ Time
settings
OKOK
OKOK2s OK
Coming from Setup MenuInitial start-up
Page 15 IOP - Bernd Lerp
OK
Unrestricted © Siemens 2019
IOP-2 FW2.3
Advanced Startup
Language,
Date/ Time
settings
OK2sOK ESC OK
OK OK OK OK
OK
From Setup Menu
Page 16 IOP - Bernd Lerp
Unrestricted © Siemens 2019
G120X a SAM (Smart Access Module)
Webserver a Wi-Fi modul
SAM: Smart-Access-Module
Mobile Device View(Additional WLAN Access Point required)
Page 17
Up to 50m
• A faster commissioning mode is presented for the G120X to
fulfill branch application setup (Pump, Fan, Heavy-duty)
• In parallel, the classic quick commission is kept for the rest of
the G120 family
Smart Access Module (SAM)
Faster commissioning with improved setup
Unrestricted © Siemens 2019
Page 18
SAM (Smart Access Module)
Nově přepracované nastavení pro uvedení do provozu
Application
selection
Motor
data
I/O
configuration
Important
(key) parameters
Motor
ID
Config. Is
Finished
The new G120X SAM’ commissioning mode enables a faster P&F setup solution
Prefilled standard Preselected standard
macro
Prefilled
Unrestricted © Siemens 2019
G120X
Režimy řízení motoru
Page 19
Motor control
V/f characteristic
• Parabolic v/f characteristic for square law torque at
radial pumps, radial and axial fans, and radial
compressors with low dynamic requirements
• Linear v/f characteristic for constant torque at positive
displacement pumps and compressors with low
dynamic requirements
• Flux reduction via ECO mode
Flux current control• Simple control with field orientation enables stable
operation under varying load
Sensorless vector mode
• Field orientated control mode for demanding drives
with speed control and higher dynamic requirements
• Optimized control modes for synchronous reluctance
motors and permanent magnet motors1
• Stable operation together with large motors
1 It needs APC pre-approval
Unrestricted © Siemens 2019
G120X
Ochranné funkce
Page 20
Protective functions
Converter
• Over/under voltage and phase loss
• Overcurrent, overload i2t
• Over temperature of control unit and power module
• Broken wire monitoring of the analog inputs
• Monitoring of 3 external faults/warnings
Motor
• Temperature monitoring with and without temperature sensor
• Speed monitoring, blocking and stalling monitoring
Drive
• Torque monitoring for dry run protection or belt monitoring
• Protection against frost, condensation, cavitation
Communication • Detection of missing telegrams, bus interruption
Fault buffer
• Buffer for 8 fault cases with each 8 faults incl. fault value and time stamp
• Buffer for 56 warnings incl. warning value and time stamp
G120X
Protection
Unrestricted © Siemens 2019
G120X
Základní funkce
Page 21
Basic functionality
set point selection
• Analog value 0 – 10V / 0/4 – 20mA with broken wire
monitoring
• Fixed speed values direct or binary coded
• Motorized potentiometer
• Communication interface
• PID controller for process values
set point channel• Minimum speed, maximum speed, ramp generator with
smoothening
Control and feedback• Control word and status word according PROFIdrive
profile
Data sets
• 3 control data sets, to be switched during operation, for
local/remote operation or manual/automatic mode
• 3 motor data sets for different motors and control modes
Selectable macros• Simple configuration of the terminals by selectable
macros
Unrestricted © Siemens 2019
Řízení čerpadel
Speciální funkce a ochrana pohonu
Function Benefits
• Multi-pump1 control
• Allows the use of several smaller
pumps, instead of one large pump
• Soft start with a ramp-up speed
• Enables option to switch off pumps
simultaneously or using reverse
sequence
• Pipe filling mode
• Smooth water flow speed control on
empty pipes
• Protection against hammer effect
• Deragging mode
• Self-ability to clear clogs on the
pump’s impellers before operation
• Reduced maintenance efforts
G120XSoftware
features
Pump control
1 Multi-pump control function is supported for same power rating pumps until <30kW
G120X: 2 pumps (+2 with I/O extension module)/ G120XA: up to 4 pumpsPage 22
Unrestricted © Siemens 2019
Multi-pump control
Řízení několika čerpadel
3AC
Page 23
1 Multi-pump control function is supported for same power rating pumps until <30kW
G120X: 2 pumps (+2 with I/O extension module coming on 12/2019)
Feature/ Function
Allows the of use several smaller pumps, which
can be switched in and out as required, instead of
one large pump
Control up to 2 (4 with ext. module) pumps by
integrated PID controller, using:
• Pump switchover
• Stop mode
• Service mode
Related parameters: p29520 … p29549
Unrestricted © Siemens 2019
Multi-pump control - Pump switchover
Přepínání čerpadel podle motohodin
Feature / Function
With pump switchover enabled, the inverter
monitors the operation status of all running
pumps:
1) If the continuous operating hours of the pump
in inverter operation exceed the threshold,
the inverter switches off the pump and then
switches in an idle pump to keep constant
output power
2) If the continuous operating hours of a pump in
line operation exceed the threshold, the
inverter first switches off the pump, switches
out the inverter-controlled pump to line
operation, and then switches in an idle
pump to run in inverter operation to keep
constant output power
3AC
Pump1 Pump2 Pump3 Pump4
10 hours 10 hours 10 hours 10 hours
Page 24
p29522 = 0: next pump according fixed sequence
p29522 = 1: next pump according op. hours.
Unrestricted © Siemens 2019
Multi-pump control - Stop mode
Okamžité a postupné zastavení čerpadel
Feature / Function
Two stop modes are available as follows:
Normal stop
• Set p2370 = 0, All pumps running in line
operation are switched off simultaneously as
soon as the stop command is received.
• The pump in inverter operation stops under the
control of the inverter.
Sequence stop
• Set p2370 = 1, The pumps running in line
operation stop one by one in the reverse
sequence in which they are switched on. There is
a delay time (p29537) between every pump stop.
• The pump in inverter operation stops under the
control of the inverter after the other pumps are
switched off.
3AC
Stop 1 Stop 2 Stop 3 Stop 4
Page 25
Unrestricted © Siemens 2019
Multi-pump control - Service mode
Servisní mód = oprava nebo odstavení čerpadla
Feature / Function
When a pump is in service mode, the inverter locks
the corresponding relay allowing to perform
troubleshooting of the pump without
interrupting the operation of other pumps.
3AC
Run 2 Run 3 Run 4
Page 26
Related parameters: p29540 … p29544
Unrestricted © Siemens 2019
Page 27
Multi-pump control
Kaskádové řízení čerpadel
Feature/ Function
Consists of the speed-controlled main motor
and up to three other motors that are
switched-on or off via contactors or motor
starters, depending on:
• A fixed arrangement
• The operating hours
The PID deviation serves as the input signal
for activating the other motors. The contactors
or motor starters are switched by the drive's
digital outputs.
Usability: applications that require between 1 and
4 motors to be run at the same time depending on
load, so that e.g. highly variable pressure ratios or
flow volumes can be corrected
Related parameters: p2200 … p23872 pumps (+2 with I/O extension module)
Unrestricted © Siemens 2019
Pipe filling
Operation
Pipe filling mode
Mód pro napouštění potrubí
Feature / Function
After each power-up, pipe filling mode allows the
inverter fills the pipe slowly to avoid hammer
effect to the pipe.
If the pipe filling is interrupted (for example, fault
occurs), the function continues after the inverter is
recovered
2 filling modes are available:
• Time mode
• Pressure mode + PID
Output
TimeValve open
Page 28
Related parameters: p29610 … p29615
Unrestricted © Siemens 2019
Deragging mode
Uvolnění zablokovaného čerpadla = povely vpřed/vzad
Feature / Function
The deragging function is used to clean any
clogs/ obstructions on the pump impeller, pipes
or valves.
This function consists on running the motor
forward and on reverse to clean the impeller.
Deragging mode can be enabled after power-up,
for every run or with an input signal.
(p29591).
Time
Speed
Page 29
Related parameters: p29590 … p29598
Unrestricted © Siemens 2019
Řízení ventilátorů
Funkce pro udržení chodu a informace o pohonu
Function Benefits
• Flying restart
• Attempts to catch the running load and
automatically restart the inverter
after power restore
• Automatic restart • Allows to automatically acknowledge
all faults
• Skip frequency bands
• Up to 4 parametrizable frequencies
can be skipped
• Real-time clock and
timer
• Allows day/night switch-over of room
temperature
• Includes summer/winter clock
change
• Faults and alarms are provided with a
time stamp
G120XSoftware
features
Fan control
Page 30
Unrestricted © Siemens 2019
Flying restart
Letmý start = synchronizace na otáčející se motor
Feature / Function
After the ON command, the "flying restart" function
initially synchronizes the inverter output frequency
to the motor speed and then accelerates the motor
up to the set point.
Typical applications:
• Synchronization on a fan rotating even after
power failure
• The fan impeller is driven by the air flow
• Search current and search speed are adjustable.
• Searching also in the negative direction of
rotation (fan rotates in the reverse direction)
Auto flying restart pump
and fan
Page 31
Unrestricted © Siemens 2019
Page 32
Automatic restart increases availability
Automatický restart po poruchovém hlášení
Feature/ Function
Includes two functionalities after a fault that allow
to:
• Automatically acknowledge all faults
• Automatically switch-on the motor again.
Events recognized as power failure:
• Fault F30003 (undervoltage in the DC link), after
line voltage has been briefly interrupted.
• After all power supplies have been
interrupted and all the energy storage devices in
the inverter have discharged to such a level that
the inverter electronics fail.
Automatic Restart (AR)
No AR
p1210 =0(default)
Auto ack.
faults
No auto switch on
motor
p1210= 1
Auto ack. faults
if ON/OFF =1
Auto switch on
motor
After power failure
p1210=4
After power
failure & faults
p1210=6
No auto ack. faults
Autoswitch on
motor
After power failure
p1210=14 p1210=16
After power
failure & faults
Auto ack.
faults
Auto switch on
motor
p1210= 26
Unrestricted © Siemens 2019
Skip frequency bands
Rezonanční otáčky a jejich odblokování
Feature / Function
Speed bands exist in the set point channel to
prevent unwanted motor speeds.
The drive traverses through the set skip frequency
bands on the ramp function up / down generator,
but permanent operation in the set skip frequency
bands is not possible. This prevents an unwanted
speed from being permanently pending.
Advantages:
• Avoidance of resonance in the mechanical
system (e.g. pipelines / vent ducts)
• Reduced material fatigue
• Reduced noise pollution
• 4 skip frequency bands with mean speed and
bandwidth parameterizable
Page 33
Unrestricted © Siemens 2019
Real-time clock
Hodiny reálného času – formát den:měsíc:rok
Page 34
Feature / Function
The real-time clock is a hardware clock in a chip,
which consists of a counter and a watch crystal as
the clock generator.
An energy accumulator is located in the device, so
that the clock does not stop when the device is
turned off.
It comprises the clock time in a 24 hour format
and the date in the "day, month, year" format.
It must be set once during commissioning. After
a power supply interruption, the real time clock
continues to run for approx. 5 days.
Faults and alarms are provided with a time stamp
based on the real-time clock. This allows their clear
relation with other activities in the production process,
which may be related to the faults or have not them
caused at all.
Real-time clock module Time
stamp
Unrestricted © Siemens 2019
Timer functionality
Zapínání a vypínání měniče podle časového intervalu
Feature / Function
The timer function, along with the real time clock
in the inverter, offers the option of controlling when
signals are switched on and off.
Examples:
• Day/night switching of a temperature control
• Switching a process control from weekday to
weekend.
Page 35
Operating principle and functional diagram of a timer
switch
Unrestricted © Siemens 2019
Regulace pohonu se speciálními požadavky
Function Benefits
• Keep running mode
• Maximized operation time by avoiding
common issues w/o manual
intervention
• Personalized protection measures,
such as:
• Reduced PWM frequency, speed
and output current
• Auto flying restart of P&F
• Kinetic buffering to skip
interruption
• PID controller • Increased flexibility to regulate
processes (levels, pressures, etc.)
• Dual ramp function
• Optimized pump operation
• Shorter start/stop time
• Minimizes wearing of the pump
• Multiple speed set points • Up to 16 fixed frequency settings that
enable multi-speed operation
G120XSoftware
features
Set point Op.
Page 36PWM: Pulse Width Modulation
Unrestricted © Siemens 2019
Keep running mode
Zajištění chodu měniče v nepříznivých provozních podmínkách
Feature / Function
Enables all possible functions to keep the
inverter away from faults and from tripping, by
applying configurable measures like:
• Reduction of the output speed and PWM
frequency to avoid over-temperature and
overload problems
• Catching running load and automatically
restarting the inverter after power disruption
(switches on drive while motor is running)
• Using kinetic energy from the load to skip short
time power interruption
Overheat
Overload
Low-voltage
Power interruption
Reduce PWM frequency
Reduce speed
Reduce output current
Auto flying restart pump
and fan
Kinetic buffering to skip
interruption
Page 37
PWM: Pulse Width Modulation
Related parameters: p29630; p0290, p1210…p1240
Unrestricted © Siemens 2019
PID controller
Regulace na nulovou odchylku
Feature / Function
The PID enables simple process control such
as line pressure, fill level, temperature, flow,
tension control or load balancing.
• The technology controller is implemented as a
PID controller (controller with proportional,
integral, and derivative action)
• Set point are specified via analog value, fixed set
points, motorized potentiometer, fieldbus
• The P, I and D components can be set
separately „
• The “I” component can be locked when the
control output is limited „
• Display and entry of set point and actual values
in technological dimensions
Page 38
Block diagram of a PID technology control
Control mechanism on a closed
loop feedback
Example: Technology controller as a level controller
Unrestricted © Siemens 2019
Dual ramp mode
Dvě časové rampy pro jeden regulační cykl
Feature / Function
The dual ramp function allows the user to
parameterize the inverter so that it can switch
from one ramp rate to another when ramping
up or down to a set point.
As a result, the inverter can be started
smoothly and stopped quickly.
No-return valve
Quick
startingFast
stopping
Time
Speed
Page 39
Related parameters: p29570…p29580
Unrestricted © Siemens 2019
Multiple speed set points
16 pevných (přednastavených) otáček
Feature / Function
This function can be used to specify preset
speed frequency set points.
The fixed set points are defined in parameters
and selected via binector inputs.
The digital inputs or the corresponding bits in the
PROFINET telegram, for instance, can be used
for external control here.
Both the individual fixed set points as well as the
effective fixed set point are available via a
connector output for further interconnection
(e.g. with connector input p1070 CI: Main set
point).
This function helps in implementing very simple
applications in which it should be switched only
between a few dedicated speeds.
Page 40
Up to 16 fixed frequency settings that
enable multi-speed operation
Unrestricted © Siemens 2019
Úspora energie a redukce ztrát v pohonu
Function Benefits
• Eco mode
• Ensures best performance and lowest
losses on low dynamic loads (P&F)
• Optimizes output voltage to reduce
the load’s energy consumption
• Hibernation mode
• Allows automatic pump switch off
(sleep mode) and wakeup by fixed set
point or offset
• Saves energy, reduces mechanical
wear and noise
• Bypass
• Switches the motor between inverter
and line operation to reduce energy
consumption
• Energy/ flow calculator • Calculates the energy saving and flow
values without the external meters
• Support of PMSM + SRM • Operation of high efficiency motors to
ensure more energy saving
G120XSoftware
features
Energy saving
Page 41
PMSM: Permanent Magnet Synchronous Motor
SRM: Synchronous Reluctance Motor
Unrestricted © Siemens 2019
ECO mód – úspora energie
Snížení odběru proudu motoru
Feature / Function
• Economy mode works by slightly changing the
output voltage (via excitation current) either up
or down in order to find the minimum input power.
• Allows energy saving during low dynamic load,
such as pump and fan applications without
knowledge of the characteristic curve.
• If the load is changed, the control can adapt to
normal dynamic control to give the best
performance.
Speed
Voltage
ECOWithout
ECO
Speed
Voltage
Energy
saving
100%
80%
Page 42
Related parameters: p1300
Unrestricted © Siemens 2019
Hibernační mód v režimu PID
Chytré řešení pro úsporu energie
Feature / Function
PID with hibernation allows to switch the pumps
to sleep mode when the drives are only being
deployed temporarily (by fixed set point or if the
offset is smaller than the setting) to avoid wasting
energy by:
• Frequently starting and stopping the pump during
low-load period causing increased pipe pressure
and energy waste.
• High pressure in the pipes that can cause
increased water loss even when the demand is
low.
Sleep
Wake up
ZZ
Z
Energy
SavingOperating Operating
f
T
Page 43
Unrestricted © Siemens 2019
Page 44
Bypass mód
Přepínání motoru měnič/síť s cílem snížit spotřebu
Feature / Function
When induction motors connected to a converter
are frequently operated in the rated motor speed
range, unnecessary losses are incurred.
In Bypass mode it is possible to "bypass" the
inverter electrically as soon as the motor
frequently operates close to its rated speed.
This helps to avoid inverter losses and increase
overall efficiency.
Bypass function is only supported on induction motors up to <30 kW
Unrestricted © Siemens 2019
Kalkulátor spotřeby energie / průtoku
Odhadování průtoku čerpadla bez snímače průtoku
podle spotřeby energie
Feature / Function
• Without having a power meter or flow meter, the
G120X can estimate the energy saving from
the flow characteristic associated with a
mechanical flow control and the measured
electric power that is drawn.
• The calculation is suitable for centrifugal pumps,
fans, radial and axial compressors, for instance.
To set the characteristic, it is required from the
pump manufacturer:
• The flow characteristic associated with 5
selected speeds.
• At constant speed, the power drawn associated
with 5 flow rates, corresponds to the line
frequency and mechanical throttling of the flow
rate.
Energy meter
Flow meter
3AC 1000111 00110001
110010 10000 01011000
Page 45
Unrestricted © Siemens 2019
Podpora motorů s vysokou účinností
Feature / Function
G120X supports motors with IE2, IE3,IE4
SynRM (Siemens, 3rd party1) and PMSM1
Uses Sensorless vector control that allows to lower
the output with higher performance
With higher performance motors it is possible to
achieve greater energy savings in comparison
with traditional solution
Life
tim
e c
ost
Operating time
Break even point
Low efficiency
motors
Page 46
1 Please contact your Siemens partnerPMSM: Permanent Magnet Synchronous Motor
SRM: Synchronous Reluctance Motor
Unrestricted © Siemens 2019
Systémy ochrany pohonu a personálu
Function Benefits
• Frost protection If temp.
falls below threshold
• Turns the motor automatically to avoid
freezing and motor damage
• Condensation protection
via DC current
• Keeps the motor warm to prevent
condensation
• Cavitation detection
• Sends status and protects the pump
by tripping or sending alarms to reduce
the maintenance efforts
• Pump blockage,
pipe leakage and
dry running protection
• Monitors the output torque and speed
range to avoid abnormal situations,
extending the lifetime of the pumps
• No load, torque
and rotation monitoring
(with sensor)
• Indicates load’s power interruptions
• Monitors torque/speed to know
gearbox and fan belts status
• Fire mode (ESM)
• Keeps fans working without controller
to extend ventilation and survival time
on critical situations
G120XSoftware
features
Protection
Page 47
Unrestricted © Siemens 2019
Ochrana pro kondenzaci a zamrznutí
Feature / Function
Condensation protection:
Motors in a humid and cold environment can
develop condensation which could cause motor
failure.
This problem can be avoided by slightly
increasing the temperature of motor surface by
applying a DC current to keep the motor warm to
prevent condensation.
Frost protection:
The water frozen inside of a pump can cause
damage. The slow movement of the impeller
while it’s not being operated or when the
surrounding temperature falls below a threshold
can prevent damage.
Page 48
(humid air → condensed water)
Related parameters: p29622.. p29624
Unrestricted © Siemens 2019
Kavitační ochrana
Zabránění „korozi“ čerpadla
Feature / Function
The impeller from the pump can be damaged by
little bubbles which are generated by the pressure
gap when the pump is running at high speed and
the water can not be supplied as required.
The cavitation protection generates a warning
when cavitation pressure thresholds are
reached. If the inverter gets no feedback from the
pump transducer, it will trip to prevent cavitation
damage.
Warning
Stop
Ava
ilab
le h
ea
d o
f w
ate
r
Requ
ire
d h
ea
d o
f w
ate
r
Page 49
Cavitation is the formation of vapor cavities in a liquid,
small liquid-free zones ("bubbles" or "voids")
Related parameters: p29625.. p29627
Unrestricted © Siemens 2019
Ochrana čerpadla proti:
blokaci, úniku kapaliny, chodu naprázdno
Feature / Function
The inverter can keep track of the speed,
current and the torque of the motor to
determine abnormal load situations:
• Insufficient torque can indicate leakage or dry-
running
• Excessive torque (and current) together with
low speed can indicate machine blockage
• Insufficient motor current indicates that the
power transmission from the motor to the load is
interrupted (no load)
Torque
Speed
Warning
Stop
Page 50
Blocked
Dry run
Leakage
Unrestricted © Siemens 2019
Mód HOŘÍ
Essential Service Mode (ESM)
Feature / Function
During Fire mode, the inverter attempts to
operate the motor for as long as possible
(ignoring the OFF signal) despite irregular
ambient conditions to improve the air circulation
and survival time on critical situations
ON
set point
Keep fans working to give the
pressure in the stair well to
force the fireproof door close to
reduce the spread of fire and
smoke
Fire
door
The pump system also can use
ESM to keep fire-fighting
system running
Page 51
Unrestricted © Siemens 2019
G120X
Délka kabelů k motoru bez externího příslušenství
Maximum permissible motor cable length (screened / non screened)
Frame size A B C D E F G H J
SINAMICS G120X 3AC200V
Unfiltered 200/300 200/300 200/300 200/300 200/300 300/450 300/450 150/200 150/200
SINAMICS G120X 3AC400V
Unfiltered 200/300 200/300 200/300 200/300 200/300 300/450 300/450 150/200 150/200
Category C3 acc. EN61800-3 200/- 200/- 200/- 200/- 200/- 200/- 200/- 150/- 150/-
Category C2 acc. EN61800-3 150/- 150/- 150/- 150/- 150/- 150/- 150/- - -
Category C1 acc. EN61800-3
(IP55)50/- 50/- 50/- 50/- 50/- 50/- - - -
SINAMICS G120X 3AC690V
Unfiltered - - - 200/300 200/300 300/450 300/450 150/200 150/200
Category C3 acc. EN61800-3 - - - 200/- 200/- 150/- 150/- 150/- 150/-
Category C2 acc. EN61800-3 - - - 100/- 100/- - - - -
*) To extend the cable length, two output reactors are necessary
Page 52
Unrestricted © Siemens 2019
G120X
Externí volitelné příslušenství na straně napájení
Line side components
AC chokes / DC chokes (line reactors)
AC and DC chokes are used to smooth voltage peaks or to bridge commutating dips. They
reduce the effects of harmonics on the inverter and the line supply.
• SINAMICS G120X FSH to HSJ require an AC choke
• SINAMICS G120X FSA to FSG have integrated DC chokes, an AC choke is not required
EMC filters (line filter)
EMC filters limit the high frequency conducted emissions of drive systems in the frequency
range of 150 kHz to 30 MHz and thus provide a contribution to electromagnetic compatibility
(EMC).
• Drives FSA to FSG with integrated filter class A fulfill the EMC requirements of the EN
61800-3 for the category C2.
• Drives FSH to FSJ has integrated filter and fulfill the EMC requirements of the EN 61800-3
for the category C3, C2 is reachable with a additional external filter.
• Drives (IP20) FSA to FSF can fulfill the EMC requirements of the EN 61800-3 category C1
by use of an unfiltered drive and an external side mounted Filter B1 to be ordered separately.
Page 53
1 Available on 12/2019
Line reactor
Line filter
Filter B (C1)
Unrestricted © Siemens 2019
G120X
Externí volitelné příslušenství na straně motoru
Load side components
Output reactor
Output reactors reduce the voltage stress on the motor windings. At the same time, the
capacitive charging/discharging currents, which place an additional load on the power
unit when long motor cables are used, are reduced. Especially in case of IT networks, an
output choke ensures that in the event of a fault the inverter does not switch off by the rapid
current increase with overcurrent
Dv/dt filter
Dv/dt filter plus VPL (Voltage Peak Limiter) limit the voltage rate-of-rise dv/dt and the
typical voltage peaks according to the limit value curve to IEC/TS 60034-17
Sinusoidal filter
A sinusoidal filter limits the rate of rise of voltage and the capacitive
charging/discharging currents that usually occur with inverter operation. The sinusoidal
filter at the inverter output supplies almost perfect sinusoidal voltages at the motor so
that standard motors can be used without special cables.
Page 54
Sinusoidal filter
dv/dt filters
compact plus VPL
output reactor
dv/dt filters plus VPL
Unrestricted © Siemens 2019
G120X
Silová elektronika
Topology SINAMICS G120X
Design
The power electronic consist of
• a 6 pulse rectifier with diodes
• an integrated dc choke
• a DC link circuit with electrolytic capacitors
• a pulse inverter with IGBTs for the motor control
Advantages
• The integrated dc choke limits the height of the charging
current, further on the harmonic currents are limited in a way as
with a converter with a 4% ac choke
• The power factor amounts to almost 0.9, so that only little
reactive power is received
Output voltage
Output voltage approx. 96% (HO), 96% (LO)
Output power
• The output current is constant in a way that hp values according
NEC at 3 AC 480V are met
EMC
• THDi = 39.4%, PWHDi = 33.9%
• Compliance with EN61000-3-12 for a RSC > 120
• Compliance with category C2 acc. EN 61800-3 for a cable length
of 150m
Page 55
THDi : total harmonic distortion
PWHDi: partial weighted harmonic distortion
RSC: short circuit ratio
Unrestricted © Siemens 2019
SINAMICS G120X
DC tlumivka zabudovaná v měniči
THC/Iref = 90.7%
PWHC/Iref = 37%
Cos phi = 0.99
λ = 0.73
THC/Iref = 50.5%
PWHC/Iref = 20.1%
Cos phi = 0.98
λ = 0.87
THC/Iref = 39.4%
PWHC/Iref = 33.9%
Cos phi = 0.99
λ = 0.92
Without choke With AC choke With DC choke
Reduction of harmonics on the line side
Cos phi = offset factor
λ = power factor
Page 56
THC = total harmonic current 2 ≤ n ≤ 40
PWHC = partial weighted harmonic current 14 ≤ n ≤ 40
Unrestricted © Siemens 2019
G120X a SIZER V3.19
Page 57