Training Booklet SINAMICS G120P Answers for infrastructure and cities.

SinamicS G120P• SINAMICS G120 CU230P-2 HVAC / BT • Motor (0.12 kW) • SINAMICS PC Connection Kit-2 • Basic Operator Panel BOP-2 • Intelligent Operator Panel IOP-2 • Screening

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

  • Training Booklet

    SinamicS G120P

    Answers for infrastructure and cities.

  • 2

    System configuration required for commissioning STARTER software

    • Processorwithmin.1GHz(dualcorerecommended)• 1024MBRAM(2048MBrecommended)• 3GBfreeHDDspace• Graphicscard(min.256MBmemoryrecommended)• Screenresolution:1024x768pixels• InternetExplorerV6.0orhigher• Operatingsystems: Microsoft®Windows™XP(ServicePack2orlater) Microsoft®Windows™7

  • 3

    ThetrainingbookletisacomfortableandeasytounderstandintroductiontotheSINAMICSG120Pvariablespeeddrive.

    SinamicS G120PTraining Booklet

  • 4

    Materials and tools

    Thecomponentslistedbelowarepresentedinthisbooklet.Totestyourknowledgeontheactualproduct,youhavethechoicebetweenorderingthefollowingalternatives:

    Training case

    Product

    • SINAMICSG120Pcase*

    Order No.

    A5E03828108

    Single components

    Product

    • SINAMICSG120PM230FSA0.55kW

    • SINAMICSG120CU230P-2HVAC/BT

    • Motor(0.12kW)

    • SINAMICSPCConnectionKit-2

    • BasicOperatorPanelBOP-2

    • IntelligentOperatorPanelIOP-2

    • ScreeningKit2

    Order No.

    6SL3210-1NE11-7UL0

    6SL32436BB301HA2

    1LA7060-4AB10

    6SL3255-0AA00-2CA0

    6SL3255-0AA00-4CA1

    6SL3255-0AA00-4JA0

    6SL3264-1EA00-0FA0

    Optional components

    Product

    • IOP-2/BOP-2doormountingkit

    Order No.

    6SL3256-0AP00-0JA0

    You will also need the following equipment:

    • PC/PGwithUSBinterface• Switches–commerciallyavailable*• Potentiometer–commerciallyavailable*• VariousM4screwsandnuts(lengthdependsoninstallationlocation)withsuitablescrewdriver/

    wrench–commerciallyavailable*

    *Thetrainingcaseisacompletedemostationincludingamotor,thepowermoduleofthevariablespeeddrive,switches,lightsanda230Vpowersupplyconnection.

  • 5

    Safety instructions

    Validity

    Theseinstructionsapplytothefollowingvariablespeeddrive:

    Product

    SINAMICSG120P

    Prerequisites

    YouareproficientinworkingwiththeMicrosoft®Windows™operatingsystem.Youhaveagoodunderstandingoftheprinciplesofelectronicsandelectricalengineering.

    Warning

    Dangerouscurrentsandvoltages!Theequipmentcontainsdangerousvoltagesandcontrolspotentiallydangerousrotatingmechanicalparts.Non-compliancewiththewarningsorfailuretofollowtheinstructionscontainedinthedocu-mentationcanresultinlossoflife,severepersonalinjuryorseriousdamagetoproperty.

    Takeparticularnoticeofthegeneralandregionalinstallationandsafetyregulationsregardingworkondangerousvoltageinstallations(e.g.EN50178)aswellastherelevantregulationsregardingthecorrectuseoftoolsandpersonalprotectiveequipment(PPE).

    Qualified personnel

    Thedevice/systemmayonlybesetupandusedinconjunctionwiththisdocumentation.Onlyquali-fiedpersonnelmaycommissionandoperatethisequipment.Withinthecontextofthesafetynotesinthisdocumentation,qualifiedpersonsaredefinedaspersonswhoareauthorizedtocommission,groundandlabeldevices,systemsandcircuitsinaccordancewithestablishedsafetypracticesandstandards.

    Liability disclaimer

    DependingonthefirmwareandsoftwareversionoftheControlUnit,operatorpanelandSTARTER,themasks,symbolsandmenusmaydiffer.Wehavereviewedthecontentsofthispublicationtoensureconsistencywiththehardwareandsoftwaredescribed.Sincedeviationscannotbeentirelyruledout,wecannotguaranteefullconsistency.However,theinformationinthispublicationisreviewedregularlyandanynecessarycorrectionsareincludedinsubsequenteditions.

  • 6

    Welcome to the SinamicS G120P Tutorial for First Time Users. This tutorial will help you to simply and quickly get to know the variable speed drive. We’ll take you step by step through installation, setting parameters and initial commissioning. We recommend that you work through all of the chapters.

  • 7

    Variable speed drive SINAMICS G120P 08 – 29

    1.1Components PowerModule 12

    ControlUnit 13

    OperatorPanel2(BOP-2/IOP-2) 14

    1.2Mountingandwiring PowerModule 15

    ControlUnit 18

    WiringthecontrolterminalsintheCU230P-2 20

    Wiringexamples 21

    OperatorPanels(BOP-2/IOP-2) 28

    Operator Panels BOP-2 and IOP-2 30 – 63

    2.1Basicfunctions TheBOP-2display 32

    Menustructure 33

    2.2WorkingwiththeBOP-2 Parameterlist/Operatingmode 34

    Functionbuttons 37

    2.3Quickcommissioning Resettingthevariablespeeddrive 38

    Settingthecontrolmode/Selectinglinefrequency 39

    Enteringmotordata 40

    Specifyingapplicationparameters 41

    Savingandrestoringdata 44

    2.4IntelligentOperatorPanel Thedevice 45

    WorkingwiththeIOP-2 47

    Basiccommissioning 49

    Outputsettings 56

    TrendView 58

    Accessingthediagnostics 62

    STARTER software and PC 64 – 91

    3.1Mountingandpreparation CreatingaSTARTERproject 68

    STARTERuserinterface 71

    Loadingvariablespeeddrivedata 72

    3.2Parameterization Configurationwizard 76

    3.3Applicationcases Activatingemergencyoperation 81

    ParameterizingthePIDcharacteristic 82

    Savingdata 85

    Restoringfactorysettings 88

    Appendix Download overview 93

  • 8

    This chapter introduces the low-voltage SinamicS G120P variable speed drive. You will learn about the main components, its structure and obtain some practical tips about assembling and wiring of the frequency variable speed drive.

    1

  • 9

    Variable speed drive family

    SinamicS G120P3 AC 400 V 0,37 kW – 90 kW (IP55)3 AC 400 V 0,37 kW – 75 kW (IP20)

  • 10

    1.1 components TheSINAMICSG120Pvariablespeeddrivehasamodulardesign.Itcomprisesthreebasiccomponents:

    1 2ThePowerModulesuppliespowertothemotor TheControlUnitcontrolsandmonitorsthePowerModule

    VariablespeeddrivefamilySINAMICSG120P: Components

  • 11

    3 +TheBasicOperatorPanel(BOP-2)ortheIntelligentOperatorPanel(IOP-2)areusedtooperateandmonitorthevariablespeeddrive

    Withacomputer,aUSBcableandtheSTARTERcommissioningsoftwareyoucanalsosetparameters,operateandmonitorthevariablespeeddrive

    EachControlUnitcanbefreelycombinedwitheachPowerModule.

    NOTE

  • 12

    1

    2

    3

    4

    5

    Power ModuleThedeviceisavailableinseveralsizesanddegreesofprotection.Ithasapowerrangeextendingfrom0.37kWupto90kW(75kWforIP20).ThepowermodulesareavailableinbothIP20andIP55.

    IP20

    IP55

    Pleasechecktheratingplatetomakesurethatthepowermodulealsomeetsyourrequire-mentspecifications.

    NOTE

    Ratingplate

    Powerconnectors

    Motorconnectors

    PEterminals

    Equipotentialbonding

    2

    2

    4

    4 3

    3

    VariablespeeddrivefamilySINAMICSG120P: Components

    32

    1

    1

    5

  • 13

    1

    2

    33

    16

    66

    4

    2

    59

    9

    8

    9

    7

    4

    5

    6

    7

    8

    9

    10

    Control UnitTherearevariousdesignsfortheControlUnit.Theydifferprimarilyintermsofdifferentfieldbusinter-faces.ThistutorialwillusetheexampleoftheCU230P-2HVAC/BTControlUnit.ItoffersModbusRTU,BACnetMS/TPandUSSasfieldbusinterfaces.

    AlwaysusetheCUscreeningkitinordertoensureoptimalpotentialequalization,fixingandscreeningofallbusandsignalcables.

    NOTE

    Ratingplate

    DIPswitchforanaloginputs

    DIPswitchforfieldbusaddress

    InterfacefortheOperatorPanel(BOP-2orIOP-2)

    StatusLEDs

    Terminalsfordigitalandanaloginputsandoutputs

    USBinterfaceforSTARTER

    InterfacetothePowerModule

    Fasteningclips

    RS485connectorforfieldbus

    10

  • 14

    Basic Operator Panel 2 (BOP-2)ThebasicinputanddisplaydeviceisusedtooperateandsetparametersforthevariablespeeddriveafterbeingconnectedtotheControlUnit.Itisoperatedbypressingthebuttonsandcanbeusedtosimplycommissionavariablespeeddrivethankstothemenupromptingandthe2-linedisplay.TheBOP-2canstoreonesetofparametersandcanbeusedtoclone.

    Intelligent Operator Panel (IOP-2)TheIntelligentOperatorPanelmanagesthesamefunctionsastheBOP-2butaddsseveralmoreoptions.Theintegratedapplicationwizards,fullgraphicaldiagnosticoverviewsandplaintextsignificantlyincreasetheusability.TheIOP-2canstoreupto16parametersettingsandisthusveryconvenientforseriescommissioning.

    1

    3

    4

    1

    2

    3

    26

    6

    5 5

    4

    1

    1

    66

    55

    4 4

    3 3

    2 2

    BOP-2 IOP-2Sevenoperatingbuttons

    Display

    Releasecatch

    Threadedinsertsfordoormounting

    RS232connector

    Productratinglabel

    Graphicdisplay

    Navigationwheel

    Fiveoperatingbuttons

    USBconnection(forfirmwareandlanguagepackupdates)

    RS232connector

    Productratinglabel

    VariablespeeddrivefamilySINAMICSG120P: Components

  • 15

    Mounting the Power Module in the control cabinetPleaserefertothedrillingpatternprovidedwiththePowerModuleforthecorrectdrillingcentersandclearancedistancesaboveandbelowthePowerModule.ThePowerModulescanbemountedsidebyside.However,a1mmgapisrecommendedtosimplifyinstallation.

    1.2 mounting and wiringBeforestarting,checktoensurethefollowingconditionshavebeenmet:• Allrequiredcomponents,toolsandsmallpartsareavailable• Allrequiredcablesandconductorshavebeenrouted/installedinaccordancewithspecifications• Allminimumclearancesarecompliedwith

    Themotorandvariablespeeddrivemustbeselectedsothattheymatcheachother.Thisisalsothecaseinourexample.Further,thedatafromtheratingplateofthemotorareimportantwheninitiallycommis-sioningthevariablespeeddrive.

    NOTE

    The 5 safety regulations when working on a VSD must be strictly observed

    • Disconnect• Lockoutagainstunintentionalrestart• Verifythatitreallyisinano-voltagecondition• Groundandshortcircuit• Coverorpartitionoffanyadjacentliveparts

    Exampleofdrillingpattern

    36.5mm(1.44")

    62.3mm(2.45")

    6m

    m(

    0.2

    3")

    18

    6m

    m(

    7.3

    2")

  • 16

    Connecting the Power Module to the motorDependingontherequiredEMCclass,differentcablelengthlimitsareapplicablefortheconnectionbetweenthePowerModuleandmotor.Alwaysuseshieldedcables.Iflongercablesareneeded,makesurethatasine-wavefilterisused.

    Wiring the Power Module (motor cable)

    • ConnecttheequipotentialbondingconductortothePowerModule(onlyforIP55.ForIP20ensurethatthecabinetisconnectedtotheequipotentialbondingconductorandthatthemetalheatsinkisproperlyconnectedtotherearofthecabinet)

    • ConnectthephasesandthegroundconductortoterminalsU2,V2,W2andPE.Makesurethatthecableisproperlyshielded.ForIP55devicesuseanEMCgland,routethescreenthroughthecableglandandconnectitinsidethehousing

    1

    2

    ThemotorandPowerModulearenowconnected.

    Wiring the motor

    • Unscrewthecoveroftheterminalboxonthemotor(theinsidecoverofSiemens’motors illustratesthewiringforstarandthedeltaconnections)• Removethejumperbarsfromtheconnectingblockandloosenthescrews• Placethejumperbarsontheterminalblockandscrewthemintoplace(dependingonthe typeofconnectionsrequired–starordelta–inthisexample,astarconnectionisshown)• InsertthecablesfromthePowerModulethroughtheopeningoftheterminalboxtothemotor• ConnectthePEconnectionfirst• Introducethephaseconductorsintotheconnectionsaccordingtothephaseassignment• Replacetheterminalboxcoverandensurethatitissecuredwiththefourscrews,tightenedtothe requiredtorque• UseanEMCcableglandonthemotoraswellandmakesurethatthecableisproperlyshielded

    insidethecablegland

    3

    Theelectricalwiringisnowcomplete.

    Wiring the power supply

    • ConnectthephasesandtheearthconductortotheterminalclampsL1,L2,L3andPE4

    VariablespeeddrivefamilySINAMICSG120P: Mounting and wiring

  • 17

    Motorcablesaresourcesofinter-ference.Thismeansthatyoumustuseshieldedcablesinordertomeetthecorrespondingelec-tromagneticcompatibilityspecifi-cations.Thecablelengthsthatareactuallypossibledependonthefollowing:‒Operatingenvironment‒Variablespeeddrivebeingused‒Reactorsandfiltersused‒Shieldedorunshieldedcable

    InordertomeetClassA/C2elec-tromagneticcompatibilityrequi-rements,youneedapowermodulewithintegratedfilterandashieldedcable(max.length:25meters).TomeetClassB/C1,aPowerModulewithFilterBhastobeused(IP55max.25m,IP20max.50m).Astarconnectionisshownintheexample.Theratingplateprovidesinformationaboutthecorrectcircuitdata:e.g.230/400V∆/YmeansthatyouoperatethemotorinaYconnectionwitha400Vlinesupply.

    NOTE

    4 2

    1

    3

    3

  • 18

    Attaching the Control UnitAttachtheControlUnittothebottomofthePowerModuleusingthefasteningclipsandthenpresstheupperedgeoftheControlUnitontothePowerModuleuntilthelockingdevicesnapsintoplace.Theterminalcoverhastobeopenedbeforewiringthecontrolterminals.

    General procedure for wiring using the cage clamp mechanism

    • Slidethewireintotheterminalopening• Theinnerclampopensslightlyandholdsthewiretightlyintoplace

    Thewireisnowfirmlyattached.

    • Toreleasethewiregentlypressascrewdriverontothelever• Removethewire• Withdrawthescrewdriverfromtheterminal

    VariablespeeddrivefamilySINAMICSG120P: Mounting and wiring

    WiringexampleofCU230-P-2

  • 19

    Wiring the control terminals in the CU230P-2TheCU230P-2comeswithanextensiverangeofI/O.6digitalinputs,3digitaloutputs,4analoginputs–2ofthoseforLG-Ni1000orPt1000sensorsand2analogoutputsarestandard.

    Inthefactorysettings,someoftheI/Oarepreconfiguredtoaddresscommonrequirements(seediagrammonthenextpage).

    TheCU230P-2hasamacroparameter(p0015),whichautomaticallyconfiguresthedrivetoaddresscom-monapplications.Usingthismacro,I/Oandfunctionsareautomaticallyconfiguredaswellassomecommonparametersinsomemacros.WhencarryingoutthebasiccommissioningofthedrivewitheitherSTARTER,BOP-2ortheIOP-2,youcanselectthemacromostsuitableforyourparticularapplication.Afteradrivehasbeensetupyou,canselectanothermacroatanytimebysimplyactivatingthecom-missioningmode(P0010=1)andthenselecttherequiredmacroinP0015.Aftercommissioninghasbeencompleted,youcanresetP0010to0.

    AlwaysensurethatallsignalandbuscablesareshieldedattheControlUnitusingtheshieldingkit.Signalandbuscablesmustberoutedthemaximumpossibledis-tanceawayfrompowerandmotorcables,andcrossthemonlyata90°angle.

    NOTE

    Your G120P with FW 4.6 comes with the following HVAC-specific macros

      12:StandardI/Owithanalogsetpoint(factorysetting)101:Generalpurposeapplication103:PumpdeltaPcontrol104:Stairwaypressurization(ESM)105:Pressure-controlledsupplyfan106:Coolingtowerfan(activetemp.sensor)+hibernationmode107:Coolingtowerfan(LG-Ni1000temp.sensor)+hibernationmode108:USSfieldbus109:ModbusRTUfieldbus110:BACnetMS/TPfieldbus

  • 20

    18 DO 0 NC19 DO 0 NO20 DO 0 COM

    23 DO 2 NC24 DO 2 NO25 DO 2 COM

    Wiring the control terminals in the CU230P-2

    VariablespeeddrivefamilySINAMICSG120P: Mounting and wiring

    1 +10V OUT2 GND 3 AI 0+

    An

    alo

    gin

    / ou

    t

    4 AI 0-12 AO 0+13 GND21 DO 1 NO22 DO 1 COM14 T1 MOTOR15 T2 MOTOR9 +24V OUT

    28 GND

    Dig

    ital

    in / o

    ut

    69 DI COM5 DI 06 DI 17 DI 28 DI 3

    16 DI 417 DI 5

    31 +24V IN32 GND IN–

    35 +10V OUT36 GND50 AI 2+/NI1000

    An

    alo

    gin

    / ou

    t

    51 GND52 AI 3+/NI100053 GND––––

    10 AI 1+

    An

    alo

    gin

    / ou

    t

    11 AI 1-26 AO 1+27 GND

  • 21

    Standard I/O with analog setpoint (factory setting)

    DIP switch for AI0 and AI1 (terminals

    3/4 and 10/11)

    Fault

    Output current (0..20 mA)

    Operation

    Alarm

    Speed (0..20 mA)

    Control system 0-10V

    ON / OFF

    AcknowledgeReverse

    GND / DI COM

  • VariablespeeddrivefamilySINAMICSG120P: Mounting and wiring

    General purpose application• Macro101• Setpointviaa0...10Vsignal• Analogsetpointcanbeoverriddenwith4fixedspeeds• Flyingrestartandautomaticrestartareactivated• Essentialservicemode(intheeventoffire)

    DIP switch for AI0 and AI1 (terminals

    3/4 and 10/11)

    Fault

    Output current (0..20 mA)

    Operation

    Enable second VSD

    GND / DI COM

    Speed (0..20 mA)

    PTC A / PTC B

    ON / OFF

    Fix speed 3Fix speed 2Fix speed 1ESM activationExternal fault

    22

    Control system 0-10V

  • 23

    Pump delta P control • Macro103• DifferentialpressureiscontrolledbytheintegratedPIDcontroller• Flyingrestartandautomaticrestartareactivated

    DIP switch for AI0 and AI1 (terminals

    3/4 and 10/11)

    Fault

    Output current (0..20 mA)

    Operation

    Alarm

    Speed (0..20 mA)

    PTC A / PTC B

    Pressure sensor 0-10 V, e.g. QBE64-DP4

    ON / OFF

    GND / DI COM

  • VariablespeeddrivefamilySINAMICSG120P: Mounting and wiring

    DIP switch for AI0 and AI1 (terminals

    3/4 and 10/11)

    Fault

    Alarm

    Speed (0..20 mA)

    Output current (0..20 mA)

    PTC A / PTC B

    ESM activationOperation

    Pressure sensor 0-10 V, e.g. QBM66.201

    GND / DI COM

    Stairway pressurization (ESM)• Macro104• Centralfirealarmsystemstartsthefan• Pressurecontrol,e.g.inastairwell,inordertokeepescaperoutesclear• Flyingrestartandautomaticrestartareactivated

    24

  • 25

    Pressure-controlled supply fan + ESM fixed speed• Macro105• PressureintheairductisregulatedbytheintegratedPIDcontroller• Flyingrestartandautomaticrestartareactivated• Essentialservicemode(intheeventoffire)withfixedspeed

    DIP switch for AI0 and AI1 (terminals

    3/4 and 10/11)

    Fault

    Output current (0..20 mA)

    Operation

    Alarm

    Speed (0..20 mA)

    PTC A / PTC B

    ESM activation

    ON / OFF

    Pressure sensor 0-10 V, e.g. QBM66.202

    GND / DI COM

  • VariablespeeddrivefamilySINAMICSG120P: Mounting and wiring

    Cooling tower fan (active temp. sensor) + hibernation mode• Macro106• Controlofthecoolingtowerfanbasedonthetemperatureofthecoolingwater• Hibernation• Temperaturesensor0–10VatAI0• Flyingrestartandautomaticrestartareactivated

    DIP switch for AI0 and AI1 (terminals

    3/4 and 10/11)

    Fault

    Output current (0..20 mA)

    Operation

    Alarm

    Speed (0..20 mA)

    PTC A / PTC B

    ON / OFF

    Temperature sensor 0-10 V, e.g.

    QAE2164.010

    GND / DI COM

    26

  • 27

    NI1000 DIP switch AI2

    (terminals 50/51)

    Fault

    Output current (0..20 mA)

    Operation

    Alarm

    Speed (0..20 mA)

    PTC A / PTC B

    ON / OFF

    Temperature sensor LG-Ni1000,

    e.g. QAP22

    GND / DI COM

    Cooling tower fan ( LG-Ni1000 temp. sensor) + hibernation mode• Macro107• Controlofthecoolingtowerfanbasedonthetemperatureofthecoolingwater• TemperaturesensorLG-Ni1000atAI3• Hibernation• Flyingrestartandautomaticrestartareactivated

  • 28

    Mounting the operator panels (BOP-2 or IOP-2)

    • PlacethebottomedgeoftheIOP-2/BOP-2intothelowerrecessoftheControlUnithousing• PushtheIOP-2/BOP-2towardtheControlUnituntilthecatchclicksintoplace

    1

    2

    2

    1

    VariablespeeddrivefamilySINAMICSG120P: Mounting and wiring

  • 29

    Mounting the IOP-2 or BOP-2 in a cabinet doorTheoperatorpanelistheinputanddisplayinstrumentforcontrollingthevariablespeeddrive.Itisusedinstand-aloneoperation,i.e.,locally,onthedevice,integratedinthecabinetdoororashandheldversionforseriescommissioning(IOP-2).

    Doorpanel

    Seal

    Doormountingbracket

    Screws

    D-typeretainingscrews

    MountingtheIOP-2IdenticalmountingfortheBOP-2

    43

    1

    2

    5

    1

    2

    3

    4

    5

    Congratulations!Yourvariablespeeddriveisnowreadyforoperation.Afterinstallationhasbeencompleted,thevariablespeeddriveparametersmustbeset,i.e.,youmustenterthespecificcharacteristicsoftheconnectedmotorintothevariablespeeddrive.

  • 30

    in this section, you will learn more about how to use the operator panels to locally control the variable speed drive. You will learn how to use the Basic Opera-tor Panel 2 (BOP-2) to set up parameters for the variable speed drive and the connected motor, and how to operate the variable speed drive with the BOP-2. Then, you will learn how to best use the intelligent Operator Panel (iOP-2).

    2

  • 31

    Basic Operator Panel (BOP-2) intelligent Operator Panel (iOP-2)

  • 32

    Menubarindicatestheselectedmenufunction(seepage27)

    Providesinformationabouttheselectedfunctionalityordisplaystheactualvalue

    Displaysthevalues

    OperatorPanelsBOP-2andIOP-2: Basic functions

    Inthistutorial,weintroduceanapplicationthatisbasedon“V/fcontrolforaparaboliccharacteris-tic”.ThiscontrolmethodistypicallyappliedinHVACapplications.Werecommendthatyouworkthroughtheexamplewehavepresentedhereinordertofamiliarizeyourselfwithsettingupparametersforavariablespeeddrive.

    NOTE

    2.1 Basic functionsTheoperatorpanelistheinputanddisplayinstrumentforcontrollingthevariablespeeddrive.Itisusedinstand-aloneoperation,i.e.,locally,onthedevice,integratedinthecabinetdoororremotelycon-nectedwithaserialcable(max.5m).

    The BOP-2 display

    TheBOP-2isusedtocommission,diagnose(troubleshoot)anddisplaythestatusofthevariablespeeddrive.Upto2statusvaluescanbesimultaneouslyandcontinuouslymonitored.Itfeaturessimplenavigationusingatransparentandwell-structuredmenuandclearlyassignedoperatorkeys.

    1 2

    1

    2

    3

    3

  • 33

    MONITORING

    Theactualstatusofthevariablespeeddrive/motorsystemisdisplayed

    CONTROL

    Setpoint,jogandreversemodecanbeactivated

    DIAGNOSTICS

    Faultsandalarmscanbeacknowledged,historyandstatusisdisplayed

    PARAMETER

    Parametervaluescanbeviewedandchanged

    SETUP

    Basiccommissioningofthevariablespeeddrivecanbeperformed

    EXTRAS

    AdditionalfunctionssuchassavingandcopyingdatasetsintoandfromtheBOP-2canbeperformed

    1

    1

    4

    2

    5

    3

    62

    3

    4

    5

    6

    Menu structure

    Whenmovingthemenubartothefollowingmenufunction,thefollowingapplies:

  • 34 OperatorPanelsBOP-2andIOP-2: Working with BOP-2

    ESCkey–takesyoubacktothepreviousscreen

    Upkey–changesselection

    Downkey–changesselection

    OKkey–confirmsselection

    OFFkey–stopsthemotorinthemanualmode

    HAND/AUTOkey–switchesthecommandsourcebetweenHANDandAUTOmode

    ON/RUNkey–startsthemotorinthemanualmode

    2.2 Working with the BOP-2TheBOP-2isequippedwithsevenbuttons.ForsetupandparameterizationonlytheUPandDOWN,OKandESCbuttonsarerelevant.TheON,OFFandHAND/AUTOkeysareneededforlocaloperation.

    1

    4 7

    6

    5

    4

    3

    1

    2

    2

    3

    5 6 7

  • 35

    • PressUPtoaccessthenextparameter• Inthiscase,P3appears(Pmeansthatyoucanchangethevalueofthisparameter)• PressOKtoedittheparameter• UsetheUPandDOWNbuttonstoadjustthevalue• ConfirmthevaluebypressingOK

    Operating mode

    • PressESCtoenterthemenuselection• UsetheUPandDOWNbuttonstomovethemenubartoPARAMSandpressOK• PressOKtoselectthestandardlevel

    Parameter listTobetterunderstandthefunctionalityofthebuttons,youshouldbeacquaintedwiththeoperatingmode:TheBasicOperatorPanelgivesyouaccesstoaparameterlist.Theparametersareassignedstoredvaluesthatcontroltheoperationofthemotor.However,notallthenumbersareassigned.

    Thefirstparameternumberthatappearsisdisplayedontheleftsideofthescreen:r2(rstandsforreadonlyandmeansthatyoucanonlyreadthisvaluebutcannotchangeit).Theparametervalueoftheselectednumberisshownontheright-handside.

    Exa

    mp

    le

    Ifyouwanttochangeanyparam-eterusingtheparameterlist,youarerequestedtochooseafilterlevel(StandardorExpert).Thestandardlevellimitstheavailableparameters,thuslimitingtheriskofdangerousparametersettings.TheExpertLevelallowsyoutoaccessallparameters.

    NOTE

    Exa

    mp

    le

    ESC

    ESC

    OK

    OK

    OK

    OK

  • 36 OperatorPanelsBOP-2andIOP-2: Working with BOP-2

    Example of index parameters

    • PressingOKtakesyouto[00]• UPtakesyouto[01],DOWNbackto[00]• Selectanindexnumberofyourchoice• PressOKagaintoedittheindex• Thevaluestartsflashing• AdjustthevaluebypressingUPorDOWN• ConfirmbypressingOK

    Someparametershavemorethanoneassociatedvalue.Inthiscase,pressingOKdoesnottakeyoudirectlytothevalue,buttoanindexthatisdisplayedinbrackets[00]abovetheactualvalue.

    Exa

    mp

    le

    OKOKOK

    Acompletelistofallparameterscanbefoundinthe“ParameterManual:ControlUnits–CU230P-2”asadownloadat:http://support.automation. siemens.com/WW/view/de/70985339/0/enIfyouwanttoadjustanyblink-ing/activevaluedigitbydigit(usingtheUPorDOWNbuttonmightjusttaketoolong),youcanalwayspresstheOKbuttonformorethantwoseconds.Afterreleasingthebutton,youcancontinuouslychangeanysingledigitbyusingthebuttonsOK(movetonextdigit),ESC(movetopreviousdigit),UP(increasevalue),andDOWN(decreasevalue).

    NOTE

  • 37

    Function buttons

    Youcanoperatethemotorusingthefunctionbuttons.TheHAND/AUTObuttonchangesthecommandsourcebetweentheBOP-2(HAND)andfieldbusorterminal(AUTO).AsymbolofahandappearsonthescreentoindicatethattheHANDmodeisactive.

    • IntheHANDmode,theONandOFFbuttonsareenabled• IntheAUTOmode,theONandOFFbuttonsaredisabled• IftheHANDmodeisactive,pressingtheHAND/AUTObuttonwillswitchthevariablespeeddrive

    totheAUTOmode• IftheAUTOmodeisactive,pressingtheHAND/AUTObuttonwillswitchthevariablespeeddrive

    totheHANDmode• ChangingfromtheHANDtotheAUTOmodeispossiblewhilethemotorisrunning

    Adetailedlistofthefaultandalarmmessagescanbefoundinthe“ParameterManual:ControlUnits–CU230P2”asadownloadat:http://support.automation.siemens.com/WW/view/en/49946106

    NOTE

    Screen icons

    TheBOP-2displaysanumberoficonsattheleft-handsideofthedisplaytoindicatetheactualstateofthevariablespeeddrive.

    • Commandsource,auto/hand

    • Variablespeeddrivestatus,operational

    • JOG

    • Fault/alarmsactive

    JOG

  • 38

    Starting quick commissioning

    • PressESCtoenterthemenuselection• UseUPandDOWNtomovethemenubartoSETUPandpressOK• Thescreenwillautomaticallydisplaythenextparameterinthecommissioningsequence

    Resetting the variable speed drive

    • PressOKwhiletheBOP-2showsRESET• PressUPorDOWNtochangethevaluetoYES• PressOKandwaituntiltheBUSYsymboldisappears• Allvalueshavenowbeenresettothefactorysetting

    OperatorPanelsBOP-2andIOP-2: Quick commissioning

    Anystepofthecommissioningwizardcanbeskippedbypress-ingtheDOWNbutton.YoucangobackonestepbypressingtheUPbutton.ByconfirmingonestepwithOK,thescreenwillautomaticallydisplaythenextparameterinthecommissioningsequence.

    NOTE

    2.3 Quick commissioningThefollowingdescriptionsshowhowtosetupthedriveusingthequickcommissioningwizard,whichisintegratedintheBOP-2.

    Quickcommissioningnowstarts.Itwillhelpyoutosetalloftherelevantparametersstepbystep.Parametersthatarenotrelevantwillbeskippedautomatically.Thisallowsyoutoadjustthefactorysettingsofyourvariablespeeddrivetotherequirementsofyourmotor.

    OKOK

    ESC OK

  • 39

    Setting the control mode (P1300)

    Inourexampleitisassumedthatyourvariablespeeddriveandthemotorarenew.Asaresult,aseriesofpreparatorystepsarerequired,e.g.selectingthecontrolmode.Thisisindicatedbytheparameternumber1300.‘V/fcontrolwithparaboliccharacteristiccurve’isdefinedbythefactorysetting.

    • PressOKtomodifytheparametervalueCTRLMOD• Theupperlineshowsthecontrolmodeassociatedwiththeactualparametervaluebelow• Choose“V/fcontrolforaparaboliccharacteristicandECO”valuebypressingUPorDOWN• Observehowthecontrolmodenameintheupperrowchangesaccordingly• PressOKifthedesiredcontrolmodeisdisplayed

    Selecting the line frequency (P100)

    Thenextparametersequencesetsthelinefrequencyoftheregioninwhichthemotorisbeingused.Inourexample,thisisEurope.

    • PressOKtomodifytheparametervalueEURUSA• Set0forEurope(50Hz)(1representstheUSlinefrequencyof60Hz)• ConfirmthevaluebypressingOK• Thescreenwillautomaticallydisplaythenextparameterinthecommissioningsequence

    Theapplicablelinefrequencycanalsobefoundonyourmotorratingplate(seechapter“Enter-ingmotordata”).

    NOTE

    OKOK

    OKOK

  • 40 OperatorPanelsBOP-2andIOP-2: Quick commissioning

    Ifyouwanttoadjustanyflash-ingvaluedigitbydigit(usingtheUPandDOWNbuttonmighttaketoolong)continuouslypresstheOKbuttonforlongerthantwoseconds.Afterreleasingthebut-ton,youcanchangeeachsingledigitbyusingthebuttonsOK(movetonextdigit),ESC(movetopreviousdigit),UP(increasevalue)andDOWN(decreasevalue).

    NOTE

    12

    34

    5

    1

    3

    2

    4

    5

    P304=MOTVOLT=motorvoltage

    P100=EURUSA=standardIECorNEMA

    P305=MOTCURR=motorratedcurrent

    P307=MOTPOW=motorratedpower

    P311=MOTRPM=motorratedspeed

    P308=MOTCOSPHI=RatedMotorpowerfactor

    Thelinefrequencyhasbeensetalreadyinthebeginningofquickcommissioning(seepage37).

    Entering motor data

    Inthenextstep,thevariablespeeddriveisadjustedtothemotor.Themotordatacanbefoundonthemotorratingplate.Pleasesetthevaluesaccordingtotheratingplate.

    • PressOKtoeditthemotorvoltagestoredunderP304• Thepresetmotorvoltageof400voltsisdisplayed• KeepthevalueandconfirmbypressingOK

    OKOK

    6

    6

  • 41

    Activating pre-defined settings (P15) e.g. for command and setpoint source

    • PressOKtoactivatemacroparameterizationMAcPAr• Macro12(StdASP)isdisplayed,itdeterminesDI0forthecommandsourceandthe analoginput0forthesetpointsource• LeavethevalueandconfirmbypressingOK

    ThevariablespeeddrivecannowbeswitchedonusingdigitalinputDI0.AI0(0-10V)isselectedasthesetpointsource.

    Motor data identificationAfterenteringthemotordata,thewizardrequeststhatthemotordataidentificationisactivated.Thisisrecommendedforaverificationandoptimizationofthedatathatyouhaveentered.Themotordataidentificationinitiatesa“measurement”oftheconnectedmotor.Intheprocess,thedatapreviouslycal-culatedinthevariablespeeddrivearecomparedtotheactualmotordataandadaptedtooneanother.

    Specifying application parameters using Macro ParameterInthenextstep,pre-definedsettingsforthevariablespeeddriveinterfacescanbeactivated.Thisisstoredinparameternumber15andindicatedbyMAcPArformacroparameterization.Forexample,thevariablespeeddriveoffersdifferentpre-definedmacrosforsettingthecommandandsetpointsources(seePage20/27).

    Activating motor data identification (P1900)

    • PressOKtoconfirmMOTID• Changethedisplayedvalueto1bypressingUP

    Motordataidentificationonlystartsafterthebasiccommissioningsequencehasbeencompletedandthemotorisswitchedonthefirsttime!

    OK

    OK OK

    Themotordataidentificationcantakeseveralminutes.Donotinterrupttheprocess.

  • 42 OperatorPanelsBOP-2andIOP-2: Quick commissioning

    Thevaluesaredisplayedinseconds.Inbothcases,thetimesindicatedshouldnotbetooshort,asthismightresultinanalarm.Theramptimesareonlyvalidinnormaloperation.IfthedriveusesPIDcontrol,thePID-specificsettingshavepriority.AnexampleforaPIDsetupisprovidedinChapter->Starter.

    Minimum motor speed, ramp-up and ramp-down time (P1080)

    • SettheminimummotorspeedunderparameterMINRPM• PressOK(parameterMINRPM)• ChangethevaluebypressingUPorDOWN• PressOKtoconfirm

    Changingthevaluedigitbydigitispossiblebycontinuouslypres-singtheOKbuttonformorethan2seconds.Afterreleasingthebutton,eachsingledigitcanbechangedbyusingtheOK(movetonextdigit),ESC(movetopre-viousdigit),UP(increasevalue)andDOWN(decreasevalue)but-tons.Refertothe“ParameterManual:ControlUnits–CU230P-2”foradescriptionofthecontrolmodesandtheircorrespondingparame-tersettingsat:http://support.automation.siemens.com/WW/view/en/49946106 G120PrequirestheminimumspeedtobesetinrpmandnotinHz.Youcanusethe“SINAMICSSupport”appavailableforiPhoneandAndroidtoconvertHzintorpmforyourmotor.Theminimumspeedmustbeenteredasafrac-tionofthesynchronousmotorspeedifV/fcontrolisselected.

    NOTE

    OK OK

    • Settheramp-uptimeunderparameterRAMPUPfortheacceleratingtimetomaximumfrequency(P1120)

    • Settheramp-downtimeunderparameterRAMPDWNforthetimeuntilstandstillisreached(P1121)

    OK OK

    OK OK

  • 43

    Completing quick commissioning

    • PressOKwhiletheBOP-2displaysFINISH• SelectYESandpressOKagain

    Thevariablespeeddriveisnowoptimallyparameterizedforyourparticularapplicationandmotorspecifications.Motordataidentificationshouldnowberuntocompletecommissioning.Thiscanbedonebyswitchingonthemotor.Presently,thecommandsourceissettodigitalinputDI0.StartthemotorbyenergizingDI0.

    OK OK

    Motor data identification

    • StartthemotormanuallybyusingdigitalinputDI0• Themeasuringprocessissetinmotion.Thiscantakeseveralminutes–donotinterruptthisprocess• Themotorisswitchedoffwhentheprocesshasbeencompleted• BOP-2indicatesthatthemeasuredvaluesarenowbeingconvertedintodata

    Afterthemotordataidentifica-tionhasbeenperformed,switchthemotoroffandonagaininordertostartnormaloperation(usingDI0).

    NOTE

  • 44

    TheBasicOperatorPanel2canalsobeusedtomakeavarietyofotheradjustmentstoyourapplication.PleasenotethatanoverviewoftheparameternumberscanbefoundintheOperatingInstructions:ControlUnitsCU230P-2.

    Saving parameter sets from the variable speed drive to the BOP-2

    • NavigatewiththemenubartothefunctionEXTRAS• PressOK• PushtheDOWNbuttonuntilTOBOPappears• PressOK

    Copying parameter sets from the BOP-2 to the variable speed drive

    • NavigatetothemenuEXTRAS• PressOK• PushtheDOWNbuttonuntilFROMBOPappears• PressOK• Disconnectfromthelinesupplyandreconnect,sothatthedownloadbecomeseffective

    Saving and restoring dataSavingdataindifferentlocationisimportant.TheEXTRASfunctionallowsloadingparameterdatafromthevariablespeeddrivememorytotheBOP-2andviceversa.

    TheBOP-2canbemountedorremovedatanytime,evendur-ingoperation.Thedeviceisnotnecessaryforongoingoperation.

    NOTE

    OKOK

    OKOK

    OperatorPanelsBOP-2andIOP-2: Quick commissioning

  • 45

    2.4 intelligent Operator PanelWiththeIntelligentOperatorPanel,youcansetthevariablespeeddriveparameters,putthevariablespeeddriveintooperation,monitormotoroperationandgetvaluableinformationaboutfaultsandalarms.Allthesefunctionscanbeaccessedwithoutexpertknowledge.Themainadvantagesareasfollows:

    Fast commissioning without expert knowledge

    • Simplecommissioningofstandardapplicationsusingapplication-specificwizards, knowledgeoftheparameterstructureisnotnecessary• Usercustomizedparameterlistswithreducedparametersets• Fastseriescommissioningofdevicesusingtheclonefunctionandthepossibilitytosaveupto 16parametersets• Commissioningwithoutdocumentationbyusingtheintegratedhelpfunction

    Minimized maintenance times

    • Diagnosticswithplaintextdisplay• Simpleupdateoflanguages,applicationwizardsandfirmwareusingthe integratedUSBconnection• Integratedclearplainhelpfunctiontoreadfaultmessagesandresolvethecauseslocally

    High usability, intuitive handling

    • Direct,manualcontrolofthedrive–simpleswitchingfrommanualtoautomaticoperation• Intuitivemenunavigationusingaselectionwheel• Graphicaldisplayfore.g.statusvaluesinvertical-barcharts(forexamplepressureorflowrate)

    ortrendgraphs• Statusdisplaywithfreelyselectableunits–displayofreal,physicalvalues

    Flexible use

    • Availablefordirectmountingonthecontrolunit,doormountingorremoteusewithaserialcable(max.5m)

    • Simpleandfastmechanicalmountingandelectricalconnectioninadoor• Thehandhelddevicecanbeusedforawidevarietyofvariablespeeddrives• Multiplelanguagesintegratedasstandard–morecanbedownloadedviaUSB

  • 46

    1 2 3

    OperatorPanelsBOP-2andIOP-2: Intelligent Operator Panel

    The deviceTheIOP-2isamenu-drivendevice.Ithasthreemainfunctiongroups:

    1

    2

    3

    The display

    Allofthenecessaryinformationisdisplayedinplaintextoriconsinauser-friendlyfashion.Theiconsaredisplayedatthetopright-handedgeofthedisplay.Theyindicatevariousvariablespeeddrivestates.

    • Commandsourceauto/hand

    • Variablespeeddrivestatusready/operating

    • Fault

    • Alarmactive

    • IndicatesalldataiscurrentlysavedtoRAM.

    Ifpoweristerminatedalldataislost.

    [Wizards]Assistyouinsettingupstandardapplications

    [Control]Allowsyoutochangethesetpointvalues,activatethedirectionofrotationreversalandchangetotheJOGmode

    [Menu]Allowsyoutoaccessallpossiblefunctions

  • 47

    Working with the IOP-2TheIOP-2ismainlyoperatedusingtheselectionwheel.Thefiveadditionalbuttonsmakeitpossibletodisplaycertainvaluesortotogglebetweenthemanualandautomaticmodes.Thebuttonsareasfollows:ON,OFF,ESC,INFOandHAND/AUTO.

    TurningchangestheselectionPressingconfirmstheselection

    Startsthemotorinthemanualmode

    Stopsthemotorinthemanualmode

    Takesyoubacktothepreviousscreen

    Displaysadditionalinformation

    SwitchesthecommandsourcebetweentheHANDandAUTOmodes

    TheHAND/AUTOfunctionoper-atesinexactlythesamewayastheoneimplementedintheBOP-2.AfterstartingthemotorwiththeONbutton,youcanchangethesetpointspeedbynavigatingtoCONTROL/SETPOINTandturningthewheel(clockwisetoincreasespeed,counter-clockwisetodecreasespeed).

    NOTE

    1

    1

    2

    23 6

    4 5

    3

    4

    5

    6

  • 48

    Basic commissioning

    • Select“Wizards”byturningthewheel• Navigateto“Basiccommissioning”• ConfirmbypressingOK

    The wizardsSeveralwizardsareavailablethatallowyoutosetupvariousfunctionsandcommissionthevariablespeeddrive.Theynavigateyouinteractivelythroughtheparameterizationofstandardapplications.Thewizardsareaccessedfromthewizardsmenu,atthebottomleftofthestatusscreen.

    • AlwaysusethewheeltoselectanoptionandpressOKtoconfirm• PressESCtomovebackonestep• PressINFOtoreadcontext-sensitivehelpinformation

    Nowthewizardwillguideyouthroughseveralstepsbypresentinganumberofscreenswhereyoucanchoosethenecessaryoptionsandvalues.Ourexampleshowsastandardconfiguration.

    Wizards Basic commissioningOK OKOK OK

    OperatorPanelsBOP-2andIOP-2: Intelligent Operator Panel

    AfterselectingWizardsorwhenadvancingwiththeIOP-2,some-timesaspecificloadingtimeisrequired.Ifthescreendoesnotimmediatelychange,donotpressanyadditionalbuttonsasthismightcausetheIOP-2toadvancetoofar.Atthetopofthescreen,youcanseenumbersthatindicatethepresentstepofthewizardthatyouarein.Forexample,2/28meansthatyouareinstep2of28.

    NOTE

  • 49

    Basic commissioning

    Restoring factory settings

    • Choose“Yes”• ConfirmbypressingOK

    YesOK OK

    Control mode

    • Selecttherequiredcontrolmodebyturningthewheel• Inourexample:“V/fforaParabolicCharacteristicandECOMode”• PressOK

    V/f for a Parabolic Characteristic and ECO ModeOK OK

    Motor data

    • Refertotheratingplateofyourmotor• Select“Europe50Hz,kW”or“N.America60Hz”accordingyourlinesupplyandmotor• PressOK

    50 Hz, kWOK OK

    Motor type

    • Selecttheappropriatemotortype• Refertotheratingplateofyourmotororconsultthemotormanual(alsoseePage40)• Inourexample:“Inductionmotor”• PressOK

    Induction motorOK OK

  • 50

    Motor characteristics

    • Choosetheappropriatevalue• Valuedependsonthecharacteristicyouwanttouse.87Hzshouldnotbeusedwithoutfirst

    contactingthemotorsupplier.• Inourexample:“50Hz”• PressOK

    50 HzOK OK

    Motor connections

    • Anoteisdisplayedthatpromptsyoutoenterthemotordataaccordingtothemotorratingplate• PressOKtocontinue

    OK

    Entering detailed motor data

    • Youarenowpromptedtoenter50Hzmotordata• PressOKtocontinue

    OK

    OperatorPanelsBOP-2andIOP-2: Intelligent Operator Panel

  • 51

    Motor current

    • Entertheappropriatemotorcurrent• Inourexample:“0.42A”• Turnthewheeltoselecttheappropriatenumbers• PressOKtoconfirmthenumber

    0.42 AOK OK

    Power rating

    • Entertheappropriatepowerrating• Inourexample:“0.12kW”• Turnthewheeltoselecttheappropriatenumbers• PressOKtoconfirmthenumber

    0.12 kWOK OK

    Motor voltage

    • Entertheappropriatemotorvoltage• Inourexample:“400V”• Turnthewheeltoselecttheappropriatenumbers• PresstheOKbuttontoconfirmthedigitandjumptothenextdigit• Pleasenote,thatyouhavetoconfirmeachdigitindividually

    00400 VOK OK

    OK OK

    00400 V

    00000 V 00000 V 00000 V

    Wheneditingparametersorsearchvaluesthereisachoicetoeditindividualdigitsoranentirevalue.WithalongpressoftheOKbutton(>3sec)itwilltogglebetweenthetwodifferentvalueeditingmodes.

    NOTE

  • 52

    Rated motor speed

    • Entertheappropriateratedmotorspeed(pleaseseethemotorratingplateonpage40)• Inourexample:“1350rpm”• Turnthewheeltoselecttheappropriatenumbers• PressOKtoconfirmthenumber

    1350 rpmOK OK

    Activating motor data identification

    • Motoridentificationisrecommendedforverificationandoptimizationofallmotordata• Ifitissafechoosemotor“dataidentificationatstandstill”• Motordataidentificationwillbeperformedwhenthemotorisswitchedon• PressOKtoconfirm

    ID standstillOK OK

    OperatorPanelsBOP-2andIOP-2: Intelligent Operator Panel

    Current limit

    • Thedrivesuggestsacurrentlimitwithfactor1.5oftheratedmotorcurrent.Adjustthisvalueifneeded.

    x 1.5OK OK

    Motor cos phi

    • Enterthecorrectmotorcosphiaccordingtothemotorratingplate

    0.75OK OK

  • 53

    Encoder type

    • Inourexample:encodertypeisnotapplicable• PressOK

    OK

    Encoder parameters

    • Inourexample:allparameterswillbesettodefault• PressOKtocontinue

    OK

    Command and setpoint sources

    • Commandandsetpointsourcesareautomaticallydeterminedusingpresetmacros• MacroparametersarestoredinP015• Selecttheappropriatemacroaccordingtoyourwiring• Inourexample:“standardmacrowithanalogsetpointandtheONcommandonthedigitalinput0”• PressOKtocontinue

    Standard IO with analog setpointOK OK

    Minimum speed

    • Entertheappropriateminimumspeed• Werecommendthat20%ofthesynchronousspeedisselected• Inourexample:“300rpm”(ratedspeedis1350rpm,andsynchronousspeedis1500rpm)• Turnthewheeltoselecttheappropriatenumbers• PressOKtoconfirmthenumber

    300 rpmOK OK

  • 54

    Ramp up

    • Entertheappropriateramp-uptime• Ramp-downtimedependsonthemotorsize• Inourexample:“30s”• Turnthewheeltoselecttheappropriatenumbers• PressOKtoconfirmthenumber

    30 sOK OK

    Ramp down

    • Entertheappropriateramp-downtime• Ramp-downtimedependsonthemotorsize• Inourexample:“30s”• Turnthewheeltoselecttheappropriatenumbers• PressOKtoconfirmthenumber

    30 sOK OK

    Summary of settings

    • Reviewallsettingsbyscrollingthroughthelist• EachsettingcanstillbechangedbyselectingandpressingOK• Press“Esc”ifyouwanttogoback• Select“Continue”andpressOKtoconfirmallsettings

    ContinueOK OK

    OperatorPanelsBOP-2andIOP-2: Intelligent Operator Panel

    Motor temperature sensor

    • Ifthereisamotortemperaturesensorconnectedtoyourdevice,choosethecorrecttypeofsensor.

    Type...OK OK

  • 55

    Saving settings

    • Select“Save”andpressOK

    SaveOK OK

    Saving

    • ThesettingsaresavedtotheEEPROMmemoryofthevariablespeeddrive• Pleasewaituntiltheprocesshasbeencompleted• PressOKtocontinue

    OK

    Completing basic commissioning

    • Thedisplayremindsyouthatyouhaveselectedmotordataidentification• PressOKtocompletebasiccommissioning• Thestatusscreenisdisplayed• Atthetoprightasmallwarningsymbolstillremindsyouthatyouhaveselectedmotordata identification• Switchonthemotor• Motordataidentificationisperformed

    OK

    If“CancelWizard”isselected,allchangeswillbecancelledandthestatusscreenwillreturntothelastsetstatusscreensettings.Afterthemotordataidentifica-tionhasbeenperformed,switchthemotoroffandonagaininordertostartnormaloperation(usingDI0).

    NOTE

    Duringthemotordataidentificationyouwillhearapeepingsound.Theidentificationprocesscantakeuptofiveminutes.Afterthemotordataidentificationhasbeencompletedyourmotorandvariablespeeddriveareconfigured.

  • 56 OperatorPanelsBOP-2andIOP-2: Intelligent Operator Panel

    Output settingsTwobargraphswithtwodifferentvaluescanbedisplayedonthestatusscreen.Bothgraphscanbechangedsothatotherphysicalvaluesaredisplayed.Aneasy-to-usewizardguidesyouthroughtherele-vantsteps.

    Navigating to the status screen wizard

    • Goto“Menu”andpressOK• Select“Extras”andconfirmwithOK• Select“Statusscreenwizard”

    OK OK

    OK

    OK OK

    OK

    Extras

    Status screen wizard

    Menu

    Changing the top or bottom bar that is displayed

    • Select“Bargraph”tochangeitsvalues• PressOK• Selectthescreenposition• Inourexample:SelectthetopbarandpressOK

    OK OKOK OKBar graph Top

  • 57

    Summary of the setting

    • Alistofallchangesisdisplayed• Reviewthesettingchanges• Select“Continue”andpressOK• Savethesettings

    OK OKOK OKContinue Save

    Selecting new values

    • Choosetherequiredparameter• Inourexample:“r0024frequencyoutput”• PressOK• Selecttheappropriateunit• Inourexample:“Hz(Hertz)”• PressOK• Selectthenumberofdigitstobedisplayed• Inourexample:“2”• PressOK

    OK OKOK OKr0024 frequency output Hz (Hertz)

    OK OK2

    Aftersavinghasbeencompletedthestatusscreenopensandthechangesaredisplayedimmediately.Inourexampleyoucannowmonitorthemotorspeed,inHertz(andnotinrpm).

  • 58 OperatorPanelsBOP-2andIOP-2: Intelligent Operator Panel

    Trend ViewTheTrendViewisapowerfulfeaturefordiagnosticsandoptimization.TheTrendViewallowsselectedparameterstobegraphicallydisplayedwithrespecttotime,forexample,motorfrequencyandoutputcurrent.Thismeansthattheselectedparameterscanbegraphicallymonitoredoveracertaintimeperiod.Thegraphcanbeconfiguredaccordingtoyourneeds.

    Configuring the Trend View

    • Choose“TrendView”topresentdata• PressOK• Firstchoose“Y-axisleft”• PressOKtochangethesettingtoY-axisleft

    OK OKOK OKTrend View Y-axis left

    Navigating to the status screen wizard

    • Goto“Menu”andpressOK• Select“Extras”andconfirmwithOK• Select“Statusscreenwizard”

    OK

    OK OKStatus screen wizard

    Menu OKOK OKExtras

  • 59

    Changing the Y-axis left

    • Selecttherequiredparametervalues• Inourexample:“r0024frequencyoutput”• PressOK• Selecttherequiredunit• Inourexample:“Hz(Hertz)”• Selecttherequirednumberofunitdigits• Inourexample:“2”• Determinemaximumvalue• Determineminimumvalue• Inourexample:rangingfrom“0to50Hz”• PressOKtocontinue

    OK OKOK OKr0024 frequency output

    OK OKMin value: 0

    Hz (Hertz)

    OK OKYes

    OK OK2 OK OKMax value: +50

  • 60

    Changing the Y-axis right

    • IfrequiredtheY-axisrightcanalsobeconfigured• Select“Yes”andpressOK• Choosetherequiredoutputparameter• Inourexample:“r0025voltageoutput”• PressOK• Selecttherequiredunit• Inourexample:“Volts”• PressOK• Selecttherequirednumberofunitdigits• Inourexample:“0”• Determinemaximumvalue• Determineminimumvalue• Inourexample:rangingfrom“0to400V”• PressOK

    OK OKOK OKYes

    OK OK0

    OK OKOK OKMax value: 0400 Min value: 0

    r0025 voltage output

    OK OKVolts

    OperatorPanelsBOP-2andIOP-2: Intelligent Operator Panel

  • 61

    Defining the displayed time period and completing the configuration

    • SettherequiredtimeperiodfortheTrendView• “Hours”,“minutes”and“seconds”areindividuallyselected• PressOKtojumpfromhourstominutes/seconds• Turnthewheeltochangethenumberofhours/minutes/seconds• Inourexample:“2minutes”• PressOKtocontinue• Asummaryofsettingsisdisplayed• Reviewoffallsettings• Select“Continue”andpressOK• Select“Save”tocompletetheconfiguration

    Theconfigurationprocessiscompletedbysavingallofthesettings.Thescreenwillautomaticallyreturntothestatusscreen.Theconfiguredgraphisimmediatelydisplayed.Nowswitchonthemotortoseehowthegraphdisplaysselectedmotorparameters(e.g.motorcurrent,motorfrequency).Youwillseehowthemotoracceleratesaccordingtotheramp-uptimethatyouconfigured.Changethemotorspeedtoseehowthegraphchanges.

    2minutesisagoodtimeperiodforaquickanalysis.24hoursisrecommendedforlong-termmonitoring.

    NOTE

    OK

    OK OK

    OK

    Hours Minutes

    Save

    OK OK2

    OK OKContinueOKSeconds

  • 62

    Accessing the diagnosticsIfyouwanttofindoutwhichinputandoutputdevicesareconnectedtothevariablespeeddrive,simplynavigatetothediagnosticsmenuandselecttheI/Ostatus.Thisoptiondisplaysalistofthedigitalandanaloginputsandoutputsofthevariablespeeddrive.Inaddition,youcanmonitortheircurrentstatus.Thisisaninformationscreenonlyandcannotbechanged.

    TheINFObutton–alwayspro-videsyouwithmorein-depthinformationaboutthepresentlyhighlightedselectedsteporfeature.

    NOTE

    Reading the I/O status

    • Usethewheeltoselect“Menu”• ConfirmbypressingOK• Select“Diagnostics”• ConfirmbypressingOK• Choose“I/OStatus”• ConfirmbypressingOK• Choose“StatusDigitalInputs”• ConfirmbypressingOK

    YoucannowseeaclearlyarrangedoverviewofalloftheconnectedI/Oincludingtheirstatus.

    OK OK

    OK

    OK OK

    OK

    Diagnostics

    I/O Status

    Menu

    OK OKStatus Digital Inputs

    OperatorPanelsBOP-2andIOP-2: Intelligent Operator Panel

  • 63

    Ifyouwanttofindoutaboutpreviousfaultsandalarms,pleasenavigatebackonelevelandselect“History”.Thiswilldis-playalistofallpreviousfaultsandalarmsincludingthetimethattheyoccurred.

    NOTE

    Obtaining information on active faults

    • Usethewheeltoselect“Menu”• ConfirmbypressingOK• Choose“Diagnostics”• ConfirmbypressingOK• Select“ActiveFaults/Alarms”

    Allactivefaultmessagesthathavenotyetbeenacknowledgedarenowdisplayed.Youcanselecteachone,andpressINFOtoobtainmoreinformation.

    Younowknowhowtousetheoperatorpanelstosettheparametersonyourvariablespeeddriveandcommissionit.AnotheroptionforsettingtheparametersistouseyourPCoraSIMATICprogrammingdevice.Thismethodisclearerandmoreconvenient,butrequiressomewhatmorepreparationtime.

    OK OK

    OK

    OK OK

    OK

    Menu Diagnostics

    Active Faults/Alarms

  • 64

    in the next step, you will learn how to connect your Pc or PG to the variable speed drive and how to set parameters using the STaRTER software.

    3

  • 65

    STaRTER software and Pc

  • 66 STARTERsoftwareandPC: Mounting and preparation

    3.1 mounting and preparationTheoptionalPCConnectionKit2isrequiredtosetuptheparametersusingaPC.Thekitconsistsoftwocomponents.

    1 2Connectingcable STARTERsoftwareonDVD

  • 67

    Hardware preparation

    • InserttheSTARTERDVDintoyourDVDdrive• InstalltheSTARTERsoftwarebyfollowingthesetupwizard• ConnecttheUSBcabletotheControlUnit• ConnecttheotherendtotheUSBportofyourPC

    ThelatestversionofSTARTERcanalsobedownloadedat:http://support.automation. siemens.com/WW/view/en/26233208

    NOTE

    YoumustinstalltheUSBdriverifyouareconnectingthevariablespeeddriveandPCtogetherforthefirsttime.Windows7automaticallyinstallsthedriver;forolderWindowsversions,youmustconfirmtheautomaticinstallation.

  • 68

    Creating a STARTER project

    Aftertheinstallationhasbeencompleted,switchonthevariablespeeddrivepowersupplyandstartthepro-gram.Theprojectwizardopensautomatically.Thewizardwillhelpyoucreateyourfirstprojectinfoursteps.

    Introduction:Select“Finddriveunitsonline”1

    STARTERsoftwareandPC: Mounting and preparation

    1

    STARTERsoftwarereadingstep-by-stepinstructionsareprovidedonthefollowingpages.

  • 69

    Creatinganewproject(Step1):Givetheprojectanameandclick“Next”toaccess

    PG/PCSetinterface(Step2):Checkthat“DEVICE”issetasaccesspoint.Ifnot,click“Accesspoint”andset“DEVICE”inthedialogbox

    Checkthat“S7USB”issetasinterface.Ifnot,click“PG/PC”

    Openthedropdownmenuandselect“AccesspointoftheApplication”

    Choosethecommand“Device(STARTER,SCOUT)-->toS7USB”

    Inthelowersectioncalled“InterfaceParameterAssignedUsed”select“S7USB”

    ClosewithOKandclick“Next”

    3

    4

    2

    5

    6

    7

    8

    7

    8

    56

    2

    3

    4

  • 70

    Insertdriveunits(Step3):Theidentifiedvariablespeeddriveisdisplayed,click“Next”

    Summary(Step4):Checkthesummary

    Closetheprojectwizardbyclicking“Complete”11

    10

    9

    10

    STARTERsoftwareandPC: Mounting and preparation

    ThevariablespeeddriveisnowintegratedintotheprojecttreeandtheparameterscanbesetusingtheSTARTERsoftware.

    9

    11

  • 71

    STARTER user interface

    Projecttree

    Programmenu

    Toolbarwithspecialfeatures

    Icon“Connecttoselectedtargetdevices”

    Connectionmode

    Workarea

    1

    1

    4

    2

    2

    5

    5

    6

    3

    3

    4

    6

  • 72 STARTERsoftwareandPC: Mounting and preparation

    Loading variable speed drive data

    Beforeyoucanloadtheactualvariablespeeddrive’sdataintoyourproject,anonlineconnectionbetweenthePCandthevariablespeeddrivehastobeestablished.

    Clicktheicon“Connecttoselectedtargetdevices”inthetoolbarandawindowappears

    Settheaccesspointto“DEVICE”andplaceacheckmarknexttothevariablespeeddrivenameandclickOKAconnectionisnowestablished

    Anonline/offlinecomparisonisdisplayed,click“LoadHWconfigurationtoPG”andclosethewindow

    1

    2

    3

    1

    2

    3

  • 73

    ThevariablespeeddrivedataisnowloadedintotheprojectandanonlineconnectionbetweenPCandvariablespeeddriveisestablished.

    Thebluehighlighted“Offlinemode”changestotheyellowhighlighted“Onlinemode”

    Theworkbenchareaopens

    4

    5

    Workbench area

    Theareaprovidesadditionalinformationsuchasalarms,thetargetsystemoutputandthediagnosticsoverview.Italsostoresadditionaloperatingfeatures.

    4

    5

  • 74 STARTERsoftwareandPC: Parameterization

    3.2 Parameterization Youcannowbegintoparameterizeyourvariablespeeddrive.

    Double-clickonthevariablespeeddriveiconintheprojecttree

    Clickon“LoadCPU/driveUnittoPG”inthetoolbarandconfirmtheloadingprocessThedatasetisloaded

    1

    2

    1

    2

    2

  • 75

    Opentheprojecttreeanddouble-click“Configuration”under“ControlUnit”

    Click“Wizard...”intheworkareaandfollowthewizard’sinstructions

    3

    3

    4

    IfnoControlUnitappearsintheprojecttree,justgoofflineandgoonlineagain.Inmostcasesthisresolvestheproblem.Werecommendthatourexampleisparameterizedintheonlinemode.

    NOTE

    4

  • 76

    Configuration wizard

    Theconfigurationwizardguidesyoustepbystepthroughthefollowingparameters:

    • Controlstructure• Defaultsofthesetpointandcommandsources• Drivesetting• Motor• Motordata• Drivefunctions• Importantparameters• Calculationofthemotordata• Summary

    Youmovetothenextconfigurationstepbypressing“Next”.

    STARTERsoftwareandPC: Parameterization

    1 2

  • 77

    Startbysettingthecontrolstructure:V/fwithparaboliccharacteristic

    Definethecommandandsetpointsource:Keepthedefaultsettings

    Selectthedrivesettings:Keeptheidentifieddrivepropertiesandclick“Next”

    Selectthemotortype:Inductionmotor

    Enterthemotorratingplatedata

    1

    2

    4

    5

    3

    Fornon-Siemensmotors,pleaseenterthemotorratingplatedata.

    NOTE

    3 4 5

  • 78

    Definedrivefunctions:Select“Identifymotordataatstandstill”formotordataidentification

    Enterimportantparameters• Minimumspeed:300rpm• Maximumspeed:1500rpm• Ramp-uptime:10s• Ramp-downtime:30s• OFF3-ramp-downtimeemergencyshutdown:30s

    Choose“Calculatemotordataonly”inthenextstep

    6

    7

    8

    STARTERsoftwareandPC: Parameterization

    6

    7

  • 79

    Afterclicking“Next”,youwillreceiveasummaryofalltheparametervaluesthathavebeenentered.Thesummarycanbeinsertedintoatextfilebypressingthe“Copytexttoclipboard”button.Finallyselect“CopyRAMtoROM”tosavetheparameterizationinthevariablespeeddrivesEEPROMmemoryandclosethewindowbyclickingfinish.

    8

  • 80 STARTERsoftwareandPC: Application cases

    3.3 application cases Intheeventofafire,theG120Pcanautomaticallyswitchovertotheessentialservicemode(ESM),ensur-ingthatthesystemignoresallexternalfaultsandalarms.Thegoalistomaintainanoverpressurecondi-tionthroughventilationaslongaspossiblesothatescaperoutesarekeptfreeofsmokeanddoorscanstillbeeasilyopened.Thisexampleshowsyouhowtoparameterizeapressure-controlledventilationcombinedwithESMoperationusingtheSTARTERsoftware.

    Inourexample,theventilationisoperatedbyaproportional-inte-gral-derivativecontroller(PID).

    NOTE

    Wiring example

    DIP switch for AI0 and AI1 (terminals

    3/4 and 10/11)

    Fault

    Output current (0..20 mA)

    Operation

    Alarm

    Speed (0..20 mA)

    PTC A / PTC B

    ESM Activation

    ON / OFF

    Pressure sensor 0-10 V, e.g. QBM66.202

    GND / DI COM

  • 81

    Activating emergency operation

    Choose“Functions”intheprojecttree

    Double-click“Emergencyoperation”Emergencyoperationopensintheworkarea

    Starttheparameterizationbyclickingonthebluebinectorbuttonnextto“Activateemergencyoperation”Alistofrelevantparametersopens

    Selectparameterr722forDI5correspondingtothewiringexample(seewiringexample)ClosethewindowwithOK

    Definethesetpointsourcebyopeningthedrop-downmenuSelect“Fixedspeedsetpoint(p1015)”

    Enterfixedsetpoint:1500rpm

    1

    1

    2

    2

    4

    4

    5

    5

    6

    6

    3

    3

  • 82 STARTERsoftwareandPC: Application cases

    Parameterizing the PID characteristic

    Access“Technologycontroller”intheprojecttree

    Select“TechnologyPIDcontroller”ThePIDcontrolleropensintheworkarea

    Starttheparameterizationbyclickingonthebluebinectorbuttonnextto“PIDcontrolleractivation”Awindowwithrelevantparameteropens

    Select1foractivationandclickOK

    DefinethesetpointsourcebyclickingintheappropriatefieldAwindowwithrelevantparametersopensChooseP2201forfixedvalue1andclickOK

    1

    1

    2

    2

    4

    4

    5

    5

    6

    3

    3

  • 83

    5

    6

    3

    DefinetheactualvaluesourcebyclickingintheappropriatefieldAwindowwiththerelevantparametersopensSelectanaloginput1whichissavedinr755[1]andclickOK

    Setthesmoothingtimefortheactualvalue(P2265)byclickingtheappropriatefieldEnter10s

    Defineramp-up/ramp-downtimebyclickingintheappropriatefieldAwindowopensEnter30sforbothvaluesandclosethewindow

    6

    7

    7

    8 10

    8

    9

    Theramp-upandramp-downtimessetduringbasiccommissioningdonotapplytothePIDcontrols.Itisimportantthattheramp-upandramp-downtimesandsmoothingtimesaresetinthePIDwindow.

    NOTE

  • 84 STARTERsoftwareandPC: Application cases

    PIDcontrolparameterscanalsobeadjusted,ifrequired,byclickingtheappropriatebuttonAwindowwithdetailedparametersopenNochangesarenecessaryinourexampleClosethewindowbyclickingCLOSE

    Checktheoutputlimitsbyclickingon“Limitationactive”anddefinearamp-up/ramp-downtimeof30s.ClosethewindowbyclickingCLOSE

    9

    9

    10

    10

  • 85

    Saving data

    Apowerfailuremaymeanthatparametersettingsarelost.STARTERoffersvariouspossibilitiesforbackingupyourparametersettings.

    Doubleclickthe“Drivenavigator”intheprojecttree

    Select“Commissioning”intheworkarea

    1

    2

    1

    2

  • 86

    Select“Savedataindrive(RAMtoROM)”tostoretheparametersettingsinthevariablespeeddriveEEPROMmemory

    STARTERsoftwareandPC: Application cases

    3

    3

  • 87

    Becauseyouhaveworkedintheonlinemode,nodatawhatsoeverhasbeenstoredinyourprojectonthecomputer.

    Click“Savedatatoproject”tosavetheparametersettinginyourproject

    Youcouldnowdisconnecttheonlineconnectiontothevariablespeeddrivebyclickingthe“Disconnectfromtargetsystem”icon.Inourexample,pleasestayonlinetorestorethevariablespeeddrivetoitsfactorysettings.

    4

    4

  • 88 STARTERsoftwareandPC: Application cases

    Restoring factory settings

    Resettingyourvariablespeeddrivetofactorysettingsmightbehelpfulifyouhaveexperiencedanyproblemsduringparameterization.

    Double-clickthe“Drivenavigator”

    Select“Commissioning”

    1

    2

    1

    2

  • 89

    3

    Select“Factorysettings”

    Thesecuritypromptthatisnowdisplayedletsyouknowthatallsettingsyouhavemadewillbereset.Usingthecheckbox(“SavefactorysettingstoROM”)query,youwilloverwritethecurrentsettingsalsointhenon-volatileEEPROMofthevariablespeeddrive.

    3

  • 90 STARTERsoftwareandPC: Application cases

    Click“OK”torestoreallvariablespeeddrivesettingstothefactorysettingThefactorysettingsarerestored

    4

    4

    5

  • 91

    Click“Close”tocompletetheprocess

    Click“Disconnectfromtargetsystem”tofinallycompletetheprocess

    YounowknowhowtouseSTARTERtoeasilyandclearlyinsertyourvariablespeeddriveintoaproject,setitsparameters,andcommissionit.Pleasemakesurethatyoualwaysremembertosavetheparameterdatatothevariablespeeddriveandinthesoftwarebeforeexitingaproject.

    5

    6

    6

  • 92

  • 93

    congratulations! You have mastered the SinamicS G120P Training Booklet. Thank you for your time and efforts. We hope that this tutorial addressed all of your questions and was useful to you. more detailed information can be found online at www.siemens.com/G120P.

  • notes

  • notes

  • www.siemens.com/G120P

    Theinformationinthisdocumentcontainsgeneraldescriptionsoftechnicaloptionsavailable,whichdonotalwayshavetobepresentinindividualcases.Therequiredfeaturesshouldthereforebespecifiedineachindividualcaseatthetimeofclosingthecontract.

    ©SiemensSwitzerlandLtd,2013•Orderno.0-92326-en•0,61311

    SiemensSwitzerlandLtdInfrastructure&CitiesSectorBuildingTechnologiesDivisionInternationalHeadquartersGubelstrasse226301ZugSwitzerlandTel+41417242424

    SiemensBuildingTechnologiesInfrastructure&CitiesSectorBrunelHouseSirWilliamSiemensSquare,FrimleyCamberleySurrey,GU168QDUnitedKingdomTel+441276696000

    SiemensLtdInfrastructure&CitiesSectorBuildingTechnologiesDivision22/F,AIAKowloonTower,LandmarkEast100HowMingStreetKwunTong,HongKongTel+85228707888