Simulation of Block Ice Formation With Varying Brine Temperatures

Embed Size (px)

Citation preview

  • 8/8/2019 Simulation of Block Ice Formation With Varying Brine Temperatures

    1/7

    ENETT2550-019

    1/7

    323-25 2550

    Simulation of Block Ice Formation with Varying Brine Temperatures

    Arsanchai Sukkuea and Kuntinee Maneeratana*

    Department of Mechanical Engineering, Faculty of Engineering, Chulalongkorn University, Bangkok 10330 Thailand

    Tel: 0-2218-6610, Fax: 0-2252-2889, E-mail: [email protected], [email protected]

    Abstract

    This paper simulates the formation of block ice with real

    brine temperature changes by the finite volume method. The

    mathematical model is based upon the explicit heat conduction

    equation with the fixed gridand latent heat source approaches.

    With hourly brine temperature measurements, 3 different types of

    variations linear interpolation, constant average and step are

    considered in the 1D and 3D simulations. The main results are

    temperature profiles, ice/water fraction and internal energy loss.

    The test cases with linear interpolation show that results have

    similar overall characteristics to the simulation with constant brine

    temperature, but with distinctive temperature variations in the

    frozen regions. When the brine temperature variation is changed

    to the step approximation, the results differ slightly from the linear

    interpolation and may possibly be used for further approximation.

    1. Introduction

    Ice factories produce block ice for consumption, fishing and

    frozen food businesses. Such factories consume huge amount of

    electricity in the manufacturing process. A factory in Samut

    Sakhon Province can be considered as a typical large ice

    manufacturer in Thailand. The block ice section contains two

    14.5172-m brine pools, each containing 2,600 ice moulds

    (Figure 1). Ice blocks, weighting around 150-160 kg each, are

    ready for sale in 40 to 70-hours cycles. As the factory sells ice

    blocks to customers sporadically, substantial savings can be

    made by increasing equipment efficiencies as well as optimizing

    operating conditions to reduce ice oversupply and electricity cost

    [1].

    In order to effectively control operating conditions, it is

    crucial to accurately predict the ice formation within the moulds.

    Even though there are many parameters affecting the rates of

    block ice formation, such as the brine temperature, brine level,

    size of block ice as well as losses, etc. The first obvious choice

    for operation control is the brine temperature which only involves

    the refrigeration system, does not affect the product sizes and

    requires relatively low investment and development.

    The factory operates 20 hours every day from 0:00-20:00 hr.

    During this period, evaporator piping and fans keep the brine

    water temperature within 2 to 12C range (Figure 2). From the

    measurements at two opposite ends of a pool, denoted Tb1 and

    Tb2, it was found that the brine temperatures were almost uniform,

    especially when compared to the average brine temperatures Tb.

    It was also observed that the brine temperature increased

    significantly outside operating hours.

    Figure 1 An ice factory floor (left) and a set of ice moulds (right).

    time t, hr

    0 24 48 72 96 120

    brine

    tempera

    ture,

    C

    -12

    -10

    -8

    -6

    -4

    -2

    0

    2

    Tb

    TbT

    b1T

    bT

    b2

    Figure 2 Hourly brine temperatures during 1-5 Oct 2004 period

    [2]. The Tb is averaged from measurements Tb1 and Tb2 at two

    opposite pool ends.

    A cost effective and quick method of predicting the ice

    formation rate is the numerical computation. The final objective of

    this research is to develop a cheap computational program that

  • 8/8/2019 Simulation of Block Ice Formation With Varying Brine Temperatures

    2/7

    ENETT2550-019

    2/7

    can predict the ice formation with sufficient accuracy, leading to a

    better plant control for energy saving, increased efficiency and

    profitability [1].

    During solidification, the liquid/solid front, which releases

    massive latent heat, continuously moves through the domain.

    The ice formation, characterised by isothermal phase change

    under constant freezing temperature and abrupt property

    discontinuity, is highly non-linear and exact solutions of the

    mathematical models are extremely difficult to obtain. Thus, the

    numerical simulations are popularly employed instead.

    The overall literature survey on such numerical simulation

    was provided in [3]. The numerical procedures can be

    categorized as combinations of two main models, grid and latent

    heat representations. The grid consideration may be further

    divided into front tracking and fixed grid approaches while the

    latent heat is represented by either the temperature-based or the

    enthalpy-based methods. By comparing combinations of these

    approaches for the finite volume (FV) simulation in a previous

    study [3], the fixed grid and the modified fictitious heat schemes

    is chosen such that the latent heat increment is calculated from

    the fictitious temperature in the freezing region and then the

    temperature fields are adjusted.

    In addition, appropriate transient and interface

    approximations must be selected. From available numerical

    techniques, 4 temporal schemes explicit, fully implicit, Crank-

    Nicolson and pseudo-implicit [4] and 3 interface conductivity

    approximations arithmetic, harmonic means and solid

    conductivity are considered and used for 1D and 2D test cases

    [3]. The papers conclude that the best practical choices are the

    explicit temporal scheme for least computational expense and the

    solid interface approximation, which slightly overestimates the

    conductivity as the freezing front progresses across the saturated

    cells.

    This paper expands the previous studies [3-4] using real-life

    brine temperatures for 1D and 3D test cases. As the steel mould

    is made from 1.5 to 5.5-mm-thick steel plate of which the heat

    conductivity is much higher than ice, the brine temperature is

    used as the prescribed temperature of the domain.

    In addition, it was found in a previous study [4] that the

    highly non-linear, transient 3D simulations uses up a lot of

    memory and CPU as well as takes a very long time such that

    they usually took roughly 2 days to run the program on a

    personal computer. Thus, real-time, on-site simulations for each

    block ice are not economically appropriate. Besides, there is no

    need to predict the formation rate at an extremely high accuracy

    as some extra supply availability are built into the plant control in

    case of unexpected customer demands. Thus, the second

    objective of this paper is to study the simulation results in order to

    identifying a simple brine temperature variation that can be used

    in the rough estimation of ice formation rates by tabulated data

    for on-site control.

    2. Mathematical Model and Simulation

    The energy conservation and Fouriers law of heat

    conduction are employed as the mathematical model.

    ( )i i

    H Tkt x x

    =

    , (1)

    where H, t, T, kand xiare enthalpy, time, temperature, thermal

    conductivity and coordinates. The enthalpy His calculated from:

    if ,ref

    T

    S FT

    H c dT T T =

  • 8/8/2019 Simulation of Block Ice Formation With Varying Brine Temperatures

    3/7

    ENETT2550-019

    3/7

    where ri is the position vector and the superscript denotes the

    location of the property. The gradient vector ( )Pix at cell Pis

    calculated by ensuring a least square fit of through P and

    neighbouring nodes Qfas:

    3 31 1

    ( )( )

    ( ) ( )

    ff f P Q f nb nbi jP

    f ff fi

    d d d

    d x d

    = =

    =

    , (5)

    where = ff Q P

    i i id r r is the distance vector between Pand Q

    f. For

    the conductivity k at cell faces, the solid value Sk are used as

    recommended in [3-4]. The diffusion flux through the face f into

    an adjacent node Qf

    is approximated using the orthogonal

    correction method as:

    ( ) ( )f fQ P

    f f f f f i ii f f f

    i i

    S dT T T T k dS k S

    x d x S d

    +

    . (6)

    With the explicit scheme, the equation (3) becomes:

    ,0

    0 ,0

    1 1

    ( )( ) ( ) ( )( )

    fP n n

    P Q f

    i if f i

    cV S T S T T k T k S d

    t d x d

    = =

    . (7)

    By assembling equation (7) for all cells with initial and boundary

    conditions, a system of simultaneous equations =[ ] [ ] [ ] A T b is

    formed with nodal temperature [ ]T as unknowns.

    Before a new time step, the phase status of a cell is

    checked. If the node is liquid and the nodal temperature PT

    drops lower than the freezing temperature FT , it becomes

    saturated. The node is tagged and the temperature is then

    reassigned to FT . The latent heat incrementPQ is calculated

    from the fictit ious sensible heat such that ( )P P PFQ c T T V = .

    TheP

    Q is added to the accumulated latent heatP

    Q for

    subsequent time steps until the PQ equals the total latent heat

    PLV of the control volume. At this stage, the control volume

    becomes solid, the tag on the cell is removed and the latent heat

    increment is no longer calculated (Figure 4).

    Input data

    Data initilisation

    Start time increment loop

    Start solution loop

    Check phase status of each nodeand specify appropriate properties

    Formulate & solve the energy equation

    For saturated nodes, calculated latent heatfrom fictitious sensible heat

    Prescribed number of time step is reached

    stop

    NO

    Figure 4 Explicit solution algorithm.

    3. 1D Case Study

    A 0.135-m-long domain of water (shaded area in Figure 5)

    with unit square cross section is initially at temperature

    = 40 Ci

    T . Then, the boundary temperature at = 0.135 mx is

    suddenly lowered to the brine temperature Tb (Figure 2) while the

    other boundary condition at = 0x is symmetry plane. The

    freezing occurs at 0 CFT = with 338 kJ/kgL = while other

    properties are shown in Table 1. The domain is discretised into

    50 uniform cells and = 1 st which satisfy both the explicit time

    step restriction of < 2( ) /2t c x k and the 1-cell-deep freezing

    front requirement [3].

    Table 1 Material properties of water and ice [3].

    Property Water Ice

    (W/m K)k 0.556 2.220

    (kJ/kg K)c 4.226 1.762

    3(kg/m ) 1000 1000*

    *Approximate to the water value to ensure mass conservation

    bT

    = 40 Ci

    T

    0.27 m

    x

    symmetry plane

    bT

    a monitoring node

    Figure 5 1D problem descriptions.

    As the brine temperatures are measured on the hour and the

    hourly data is used in the plant control [1], the appropriate

    estimation of brine temperatures during the hour must be first

    considered.

    3.1 Linear Interpolation of Brine Temperature

    With linear interpolation of hourly brine temperatures in

    Figure 2, the boundary condition can be considered a fairly close

    approximation of the real brine temperature and can be used as

    the base case. It takes 77.3 hours before all water are frozen.

    Figure 6 shows the temperature profiles at various time instants

    while Figure 7 displays the temperature changes with time at

    monitoring nodes distributed throughout the domain (Figure 5),

    the estimated ice thickness from the calculated latent energy [4]

    and associated rate as well as the internal energy and cooling

    load. The energy loss at an instant time t is obtained from the

    difference between the current and initial internal energy values.

    The results exhibit many characteristics of the simulation

    with constant brine temperature [4]. The rate of heat transfer is

    predominantly controlled by the position of the freezing front.

    Liquid cells cool down slowly; once a control volume is frozen, its

    temperature drops rapidly such that the temperature gradient in

    the ice is almost linear and the freezing of the next cell starts

    shortly afterwards (Figure 6). The freezing front advances at a

    slowing rate and exhibits similar characteristics to the decreasing

    cooling load. The rate of ice formation or thickness changes is

    still exhibit the cyclic numerical errors from the fixed grid scheme

    because the front has to wait for a short interval before a new

  • 8/8/2019 Simulation of Block Ice Formation With Varying Brine Temperatures

    4/7

    ENETT2550-019

    4/7

    node starts to freeze as the front progresses from one control

    volume to the next [4].

    Due to the varying values of the brine temperature, nodal

    temperatures fluctuate with the brine temperature. From Figure 7,

    this fluctuation can be seen to diffuse deeply into the domain.

    The temperature variation is particularly pronounced in the frozen

    region but is reduced with increasing distances from the

    boundary. This variation also triggers some small amount of heat

    transfer into the domain through the boundary when the brine

    temperature increases. In short, the brine temperature cycles can

    be observed in both the ice thickness and energy plots.

    positionx, m

    0.000 0.025 0.050 0.075 0.100 0.125

    tempe

    ratureT

    ,C

    -10

    0

    10

    20

    30

    401 hr

    10 hr

    20 hr

    40 hr

    80 hr

    Figure 6 1D case study 1: Temperature distributions.

    tempera

    tureT

    ,C

    -10

    0

    10

    20

    30

    40

    increasingx

    ice

    thicknesss,

    m

    0.000

    0.025

    0.050

    0.075

    0.100

    0.125

    ch

    angera

    teds/dt,mm

    /hr

    -5

    0

    5

    10

    15

    20

    25

    time t, hr

    0 20 40 60 80

    energy

    lossU

    ,MJ/m

    2

    0

    20

    40

    60

    80

    coo

    ling

    loa

    ddU/dt,kW/m

    2

    0

    2

    4

    6

    8

    thickness

    thickness

    change rate

    energy loss

    cooling load

    Figure 7 1D case study 1: Temperatures at monitored nodes

    (Figure 5), ice thickness and energy plots.

    3.2 Constant Average Brine Temperature

    As it takes 77.3 hours for fully freezing all water when the

    brine temperature variation is linearly interpolated, the averaged

    brine temperature over 78 hours of -5.996C is used for the next

    comparison (Figure 8). When the average brine temperature is

    used, only the result characteristics of problems with constant

    boundary temperature [4] are obtained with many differences due

    to the brine temperature variations. The time taken for the water

    to be fully frozen is slightly shorter at 76.8 hours. The difference

    in ice thickness is quite large when compared with results from

    the interpolated brine temperature simulation. The difference in

    energy loss is also significant.

    These differences make the use of average brine

    temperature an inappropriate approximation even though its use

    would greatly simplify the plant controls. Thus the step brine

    temperature is considered next.

    tempera

    tureT

    ,C

    -10

    0

    10

    20

    30

    40

    increasingx

    thickness

    difference,

    %

    -20

    0

    20

    40

    60

    80

    100

    ice

    thickness

    differe

    nce,

    mm

    -6

    -4

    -2

    0

    2

    4

    6

    time t, hr

    0 20 40 60 80

    los

    sdifference,

    %

    -5

    0

    5

    10

    15

    energyloss

    difference,

    MJ/m

    2

    -2.0

    -1.0

    0.0

    1.0

    2.0

    savg

    sinterp

    100(savg

    sinterp

    )/sinterp

    100(Uavg

    Uinterp

    )/Uinterp

    Uavg

    Uinterp

    Figure 8 1D case study 2: Temperatures at monitored nodes as

    well as ice thickness and energy plots as compared against the

    linear interpolation case study 1.

    3.3 Step Brine Temperature

    If the step values, in which the brine temperature is kept

    constant during the hour and jumps to the next measured value,

    are used instead of the linear interpolation of hourly brine

    temperatures, the results such as temperature distributions and

    ice thickness, etc. are still similar but with more stepping

  • 8/8/2019 Simulation of Block Ice Formation With Varying Brine Temperatures

    5/7

    ENETT2550-019

    5/7

    shapes (Figure 9). It takes 77.5 hours to fully freeze all water.

    The difference in ice thickness is small when compared with the

    results from interpolated brine temperature and fall within the -

    0.592 0.900 mm range with the average and SD values of -

    0.010 mm and 0.310 mm. If the percentage difference in ice

    thickness is considered, the difference is within the range of -6.87

    1.614% but with the average and SD values of -0.115% and

    0.761% during the 80-hours period. The differences in internal

    energy losses are also acceptable when compared with the

    results from interpolated brine temperature. The differences fall

    within the -0.230 0.309 MJ/m2

    range with the average and SD

    values of -0.014 MJ/m2

    and 0.117 MJ/m2. If the percentage

    difference in loss internal energy is considered, the difference is

    within the range of -2.862 0.757% but with the average and SD

    values of -0.080% and 0.383% only.

    tempera

    tureT

    ,C

    -10

    0

    10

    20

    30

    40

    increasingx

    thickness

    diffe

    rence,

    %

    -6

    -4

    -2

    0

    2

    4

    ice

    thickness

    difference,

    mm

    -1.0

    -0.5

    0.0

    0.5

    1.0

    1.5

    2.0

    time t, hr

    0 20 40 60 80

    loss

    difference,

    %

    -3

    -2

    -1

    0

    1

    energy

    loss

    difference,

    MJ/m

    2

    -0.50

    -0.25

    0.00

    0.25

    0.50

    sstep

    sinterp

    100(sstep

    sinterp

    )/sinterp

    100(Ustep

    Uinterp

    )/Uinterp

    Ustep

    Uinterp

    Figure 9 1D case study 3: Temperatures at monitored nodes as

    well as ice thickness and energy plots as compared against the

    linear interpolation case study 1.

    4. 3D Case Study

    The developed program [4] is employed to study the freezing

    process in industrial ice block manufacturing with the actual size

    of ice block shown in Figure 10a. Initially, temperature of water is

    = 40 CiT throughout. The boundary conditions on the top end

    is assumed to be = 0 CbT . Due to symmetry, only one-fourth of

    the total area is modelled. The discretised domain consists of 26

    13 120 cells while 10 st = which satisfy the combined cell

    size/time step restrictions [4].

    4.1 Linear Interpolation of Brine Temperature

    With linear interpolation of hourly brine temperatures in

    Figure 2, the boundary condition can be considered a close

    approximation of the real brine temperature and used as the

    reference case. It takes just under 89.5 hours before all water are

    frozen.

    0.52 m

    1.2 m

    0.27 m0.56 m

    a

    b

    c

    d

    e

    a) block geometry b) monitored cells

    Figure 10 Geometry and domain of ice block.

    Selected locations in the ice block are monitored (Figure

    10b) and the temperatures and ice fractions at these cells are

    shown in Figure 11. It is noted that the values at cells b and care

    similar with only small delays for c, indicating that the side

    freezing fronts dominates the solidification process while the

    freezing front from the bottom exerts much less influences.

    Although the uppermost-centre node d experiences a sharp

    temperature drop early on, it still remains unfrozen until the last

    moments due to the fact that the ambient temperature is not

    sufficiently low to properly induce an effective freezing process.

    Coupled with the fact that it takes more than 10 hours longer for

    the domain to be fully frozen when compared to the 1D test case,

    the importance of the ambient temperature on the determination

    of overall freezing duration is clearly demonstrated.

    For overall results, the loss of internal energy and fraction of

    ice in the block are displayed. The characteristic fluctuations of

    results with the brine temperature variations are clearly observed.

    4.2 Average Brine Temperature

    As previous, the averaged brine temperature over 90 hours

    of -6.46C is used for the next comparison. It takes just under

    88.5 hours before all water are frozen in keeping with the trend in

    1D simulations. As in the 1D case, the differences in water

    fraction and energy loss are quite large when compared with the

    results from interpolated brine temperature changes as shown in

    Figure 12.

  • 8/8/2019 Simulation of Block Ice Formation With Varying Brine Temperatures

    6/7

    ENETT2550-019

    6/7

    te

    mpera

    tureT

    ,C

    -10

    0

    10

    20

    30

    40

    pt a

    ce

    llwa

    ter

    frac

    tion

    0.00

    0.25

    0.50

    0.75

    1.00

    time t, hr

    0 20 40 60 80

    totalenergy

    lossU

    ,M

    J

    0

    5

    10

    15

    20

    25

    totalwa

    ter

    frac

    tionf

    0.0

    0.2

    0.4

    0.6

    0.8

    1.0

    energy loss

    water fraction

    pt e

    pt b

    pt d

    pt e

    pt a pt b

    pt d

    pt c

    pt c

    Figure 11 3D case study 1: Temperature & ice fraction at

    monitoringcells as well as total energy loss and water fraction.

    te

    mpera

    tureT

    ,C

    -10

    0

    10

    20

    30

    40

    pt a

    ce

    llwa

    ter

    frac

    tion

    difference,

    %

    0

    20

    40

    60

    80

    100

    time t, hr

    0 20 40 60 80

    energy

    loss

    difference,

    MJ

    -1.25

    -1.00

    -0.75

    -0.50

    -0.25

    0.00

    0.25

    0.50

    totalfrac

    tion

    difference

    ,%

    -6

    -4

    -2

    0

    2

    4

    6

    8

    pt e

    pt b

    pt d

    pt e

    pt a

    pt b pt d

    pt c

    pt c

    100(favg

    finterp

    )

    Uavg

    Uinterp

    100(favg

    finterp

    )

    Figure 12 3D case study 2: Temperature & ice fraction at

    monitoringcells as well as total energy loss and water fraction.

    4.3 Step Brine Temperature

    If the step values are used instead of the linear interpolation

    of hourly brine temperatures, the overall results are quite similar

    even though some differences in some individual cells are

    comparatively larger than others (Figure 13). The difference in

    total water fraction is small when compared with the results from

    interpolated brine temperature such that the differences fall within

    the -0.531 0.678% range with the average and SD values of -

    0.001% and 0.221% or in the order of 1/10th compared to the

    constant brine temperature simulation (Figure 12). For the totalinternal energy loss, the differences fall within the -0.106 0.093

    MJ range with the average and SD of -0.002 MJ and 0.038 MJ,

    respectively.

    5. Conclusion

    The ice formation simulation with real hourly brine

    temperatures by the finite volume method with the fixed grid and

    the latent heat by fictitious sensible heat schemes is successfully

    performed for 1D and 3D test cases. Three different temperature

    estimations between the hours are considered the linear

    interpolation, constant average and step values. The linear

    interpolation best emulates the real changes but requires more

    detailed analyses for on-site plant control. The average brine

    temperature, while is able to predict the overall trend, can not

    capture the variations within the domain during the freezing

    period. Hence, it is not suitable for further uses in the real

    optimisation of plant operating conditions. The results from the

    step approximation differ slightly from those of linear interpolation

    and can probably be used for the existing hourly plant control [1]

    instead.

    The future works includes the analyses of simulated data for

    better ice formation approximation which is in immediate demandfor the plant control as the current approximation method by

    tabulate energy loss data [1] was found the overestimate the

    number of ready-for-sell ice blocks by some 200 to 400 blocks

    out of the total number of 2600 [5]. Later, the programs should be

    used to study effects of various parameters, such as the brine

    and ambient temperatures, brine level, mould thickness and sizes

    on the ice formation rate so that a more efficient plant control and

    design can be formulated and obtained.

  • 8/8/2019 Simulation of Block Ice Formation With Varying Brine Temperatures

    7/7

    ENETT2550-019

    7/7

    te

    mpera

    tureT

    ,C

    -10

    0

    10

    20

    30

    40

    pt a

    ce

    llwa

    ter

    frac

    tion

    difference,

    %

    -10.0

    -7.5

    -5.0

    -2.5

    0.0

    2.5

    5.0

    time t, hr

    0 20 40 60 80

    energy

    loss

    difference,

    MJ

    -0.20

    -0.15

    -0.10

    -0.05

    0.00

    0.05

    0.10

    totalfrac

    tion

    difference

    ,%

    -0.6

    -0.4

    -0.2

    0.0

    0.2

    0.4

    0.6

    0.8

    pt e

    pt b

    pt d

    pt e

    pt apt b

    pt d

    pt c

    pt c

    100(fstep

    finterp

    )

    UstepUinterp

    100(fstep

    finterp

    )

    Figure 13 3D case study 3: Temperature & ice fraction at

    monitoringcells as well as total energy loss and water fraction.

    6. Acknowledgements

    Special thanks are due to Dr. Naebboon Hoonchareon and

    Miss Thitima Lertpiya from the Department of Electrical

    Engineering, Chulalongkorn University as well as the Siam

    Scholars Co., Ltd., Bangkok.

    References

    1. Lertpiya, T. Energy Management System for Block-Ice

    Factory using TOD and TOU Tariff, M. Eng. Thesis,

    Department of Electrical Engineering, Faculty of

    Engineering, Chulalongkorn University, 2005.

    2. Hoonchareon, N. and Lertpiya, T. Private Communication,

    2004.

    3. Prapainop, R. and Maneeratana, K. Simulation of ice

    formation by the finite volume method, Songklanakarin

    Journal of Science and Technology, vol. 26, no. 1, pp. 55-

    70, 2004.

    4. Meneeratana, K. Simulation of ice formation by the

    unstructured finite volume method, Proceedings of the 1st

    E-NETT Conference. Ambassador City Jomtien, Chonburi,

    code ECB02, pp. 211-216, 11-13 May 2005.

    5. Hoonchareon, N. Private Communication, 2007.