View
223
Download
0
Embed Size (px)
Citation preview
8/8/2019 Simulation of Block Ice Formation With Varying Brine Temperatures
1/7
ENETT2550-019
1/7
323-25 2550
Simulation of Block Ice Formation with Varying Brine Temperatures
Arsanchai Sukkuea and Kuntinee Maneeratana*
Department of Mechanical Engineering, Faculty of Engineering, Chulalongkorn University, Bangkok 10330 Thailand
Tel: 0-2218-6610, Fax: 0-2252-2889, E-mail: [email protected], [email protected]
Abstract
This paper simulates the formation of block ice with real
brine temperature changes by the finite volume method. The
mathematical model is based upon the explicit heat conduction
equation with the fixed gridand latent heat source approaches.
With hourly brine temperature measurements, 3 different types of
variations linear interpolation, constant average and step are
considered in the 1D and 3D simulations. The main results are
temperature profiles, ice/water fraction and internal energy loss.
The test cases with linear interpolation show that results have
similar overall characteristics to the simulation with constant brine
temperature, but with distinctive temperature variations in the
frozen regions. When the brine temperature variation is changed
to the step approximation, the results differ slightly from the linear
interpolation and may possibly be used for further approximation.
1. Introduction
Ice factories produce block ice for consumption, fishing and
frozen food businesses. Such factories consume huge amount of
electricity in the manufacturing process. A factory in Samut
Sakhon Province can be considered as a typical large ice
manufacturer in Thailand. The block ice section contains two
14.5172-m brine pools, each containing 2,600 ice moulds
(Figure 1). Ice blocks, weighting around 150-160 kg each, are
ready for sale in 40 to 70-hours cycles. As the factory sells ice
blocks to customers sporadically, substantial savings can be
made by increasing equipment efficiencies as well as optimizing
operating conditions to reduce ice oversupply and electricity cost
[1].
In order to effectively control operating conditions, it is
crucial to accurately predict the ice formation within the moulds.
Even though there are many parameters affecting the rates of
block ice formation, such as the brine temperature, brine level,
size of block ice as well as losses, etc. The first obvious choice
for operation control is the brine temperature which only involves
the refrigeration system, does not affect the product sizes and
requires relatively low investment and development.
The factory operates 20 hours every day from 0:00-20:00 hr.
During this period, evaporator piping and fans keep the brine
water temperature within 2 to 12C range (Figure 2). From the
measurements at two opposite ends of a pool, denoted Tb1 and
Tb2, it was found that the brine temperatures were almost uniform,
especially when compared to the average brine temperatures Tb.
It was also observed that the brine temperature increased
significantly outside operating hours.
Figure 1 An ice factory floor (left) and a set of ice moulds (right).
time t, hr
0 24 48 72 96 120
brine
tempera
ture,
C
-12
-10
-8
-6
-4
-2
0
2
Tb
TbT
b1T
bT
b2
Figure 2 Hourly brine temperatures during 1-5 Oct 2004 period
[2]. The Tb is averaged from measurements Tb1 and Tb2 at two
opposite pool ends.
A cost effective and quick method of predicting the ice
formation rate is the numerical computation. The final objective of
this research is to develop a cheap computational program that
8/8/2019 Simulation of Block Ice Formation With Varying Brine Temperatures
2/7
ENETT2550-019
2/7
can predict the ice formation with sufficient accuracy, leading to a
better plant control for energy saving, increased efficiency and
profitability [1].
During solidification, the liquid/solid front, which releases
massive latent heat, continuously moves through the domain.
The ice formation, characterised by isothermal phase change
under constant freezing temperature and abrupt property
discontinuity, is highly non-linear and exact solutions of the
mathematical models are extremely difficult to obtain. Thus, the
numerical simulations are popularly employed instead.
The overall literature survey on such numerical simulation
was provided in [3]. The numerical procedures can be
categorized as combinations of two main models, grid and latent
heat representations. The grid consideration may be further
divided into front tracking and fixed grid approaches while the
latent heat is represented by either the temperature-based or the
enthalpy-based methods. By comparing combinations of these
approaches for the finite volume (FV) simulation in a previous
study [3], the fixed grid and the modified fictitious heat schemes
is chosen such that the latent heat increment is calculated from
the fictitious temperature in the freezing region and then the
temperature fields are adjusted.
In addition, appropriate transient and interface
approximations must be selected. From available numerical
techniques, 4 temporal schemes explicit, fully implicit, Crank-
Nicolson and pseudo-implicit [4] and 3 interface conductivity
approximations arithmetic, harmonic means and solid
conductivity are considered and used for 1D and 2D test cases
[3]. The papers conclude that the best practical choices are the
explicit temporal scheme for least computational expense and the
solid interface approximation, which slightly overestimates the
conductivity as the freezing front progresses across the saturated
cells.
This paper expands the previous studies [3-4] using real-life
brine temperatures for 1D and 3D test cases. As the steel mould
is made from 1.5 to 5.5-mm-thick steel plate of which the heat
conductivity is much higher than ice, the brine temperature is
used as the prescribed temperature of the domain.
In addition, it was found in a previous study [4] that the
highly non-linear, transient 3D simulations uses up a lot of
memory and CPU as well as takes a very long time such that
they usually took roughly 2 days to run the program on a
personal computer. Thus, real-time, on-site simulations for each
block ice are not economically appropriate. Besides, there is no
need to predict the formation rate at an extremely high accuracy
as some extra supply availability are built into the plant control in
case of unexpected customer demands. Thus, the second
objective of this paper is to study the simulation results in order to
identifying a simple brine temperature variation that can be used
in the rough estimation of ice formation rates by tabulated data
for on-site control.
2. Mathematical Model and Simulation
The energy conservation and Fouriers law of heat
conduction are employed as the mathematical model.
( )i i
H Tkt x x
=
, (1)
where H, t, T, kand xiare enthalpy, time, temperature, thermal
conductivity and coordinates. The enthalpy His calculated from:
if ,ref
T
S FT
H c dT T T =
8/8/2019 Simulation of Block Ice Formation With Varying Brine Temperatures
3/7
ENETT2550-019
3/7
where ri is the position vector and the superscript denotes the
location of the property. The gradient vector ( )Pix at cell Pis
calculated by ensuring a least square fit of through P and
neighbouring nodes Qfas:
3 31 1
( )( )
( ) ( )
ff f P Q f nb nbi jP
f ff fi
d d d
d x d
= =
=
, (5)
where = ff Q P
i i id r r is the distance vector between Pand Q
f. For
the conductivity k at cell faces, the solid value Sk are used as
recommended in [3-4]. The diffusion flux through the face f into
an adjacent node Qf
is approximated using the orthogonal
correction method as:
( ) ( )f fQ P
f f f f f i ii f f f
i i
S dT T T T k dS k S
x d x S d
+
. (6)
With the explicit scheme, the equation (3) becomes:
,0
0 ,0
1 1
( )( ) ( ) ( )( )
fP n n
P Q f
i if f i
cV S T S T T k T k S d
t d x d
= =
. (7)
By assembling equation (7) for all cells with initial and boundary
conditions, a system of simultaneous equations =[ ] [ ] [ ] A T b is
formed with nodal temperature [ ]T as unknowns.
Before a new time step, the phase status of a cell is
checked. If the node is liquid and the nodal temperature PT
drops lower than the freezing temperature FT , it becomes
saturated. The node is tagged and the temperature is then
reassigned to FT . The latent heat incrementPQ is calculated
from the fictit ious sensible heat such that ( )P P PFQ c T T V = .
TheP
Q is added to the accumulated latent heatP
Q for
subsequent time steps until the PQ equals the total latent heat
PLV of the control volume. At this stage, the control volume
becomes solid, the tag on the cell is removed and the latent heat
increment is no longer calculated (Figure 4).
Input data
Data initilisation
Start time increment loop
Start solution loop
Check phase status of each nodeand specify appropriate properties
Formulate & solve the energy equation
For saturated nodes, calculated latent heatfrom fictitious sensible heat
Prescribed number of time step is reached
stop
NO
Figure 4 Explicit solution algorithm.
3. 1D Case Study
A 0.135-m-long domain of water (shaded area in Figure 5)
with unit square cross section is initially at temperature
= 40 Ci
T . Then, the boundary temperature at = 0.135 mx is
suddenly lowered to the brine temperature Tb (Figure 2) while the
other boundary condition at = 0x is symmetry plane. The
freezing occurs at 0 CFT = with 338 kJ/kgL = while other
properties are shown in Table 1. The domain is discretised into
50 uniform cells and = 1 st which satisfy both the explicit time
step restriction of < 2( ) /2t c x k and the 1-cell-deep freezing
front requirement [3].
Table 1 Material properties of water and ice [3].
Property Water Ice
(W/m K)k 0.556 2.220
(kJ/kg K)c 4.226 1.762
3(kg/m ) 1000 1000*
*Approximate to the water value to ensure mass conservation
bT
= 40 Ci
T
0.27 m
x
symmetry plane
bT
a monitoring node
Figure 5 1D problem descriptions.
As the brine temperatures are measured on the hour and the
hourly data is used in the plant control [1], the appropriate
estimation of brine temperatures during the hour must be first
considered.
3.1 Linear Interpolation of Brine Temperature
With linear interpolation of hourly brine temperatures in
Figure 2, the boundary condition can be considered a fairly close
approximation of the real brine temperature and can be used as
the base case. It takes 77.3 hours before all water are frozen.
Figure 6 shows the temperature profiles at various time instants
while Figure 7 displays the temperature changes with time at
monitoring nodes distributed throughout the domain (Figure 5),
the estimated ice thickness from the calculated latent energy [4]
and associated rate as well as the internal energy and cooling
load. The energy loss at an instant time t is obtained from the
difference between the current and initial internal energy values.
The results exhibit many characteristics of the simulation
with constant brine temperature [4]. The rate of heat transfer is
predominantly controlled by the position of the freezing front.
Liquid cells cool down slowly; once a control volume is frozen, its
temperature drops rapidly such that the temperature gradient in
the ice is almost linear and the freezing of the next cell starts
shortly afterwards (Figure 6). The freezing front advances at a
slowing rate and exhibits similar characteristics to the decreasing
cooling load. The rate of ice formation or thickness changes is
still exhibit the cyclic numerical errors from the fixed grid scheme
because the front has to wait for a short interval before a new
8/8/2019 Simulation of Block Ice Formation With Varying Brine Temperatures
4/7
ENETT2550-019
4/7
node starts to freeze as the front progresses from one control
volume to the next [4].
Due to the varying values of the brine temperature, nodal
temperatures fluctuate with the brine temperature. From Figure 7,
this fluctuation can be seen to diffuse deeply into the domain.
The temperature variation is particularly pronounced in the frozen
region but is reduced with increasing distances from the
boundary. This variation also triggers some small amount of heat
transfer into the domain through the boundary when the brine
temperature increases. In short, the brine temperature cycles can
be observed in both the ice thickness and energy plots.
positionx, m
0.000 0.025 0.050 0.075 0.100 0.125
tempe
ratureT
,C
-10
0
10
20
30
401 hr
10 hr
20 hr
40 hr
80 hr
Figure 6 1D case study 1: Temperature distributions.
tempera
tureT
,C
-10
0
10
20
30
40
increasingx
ice
thicknesss,
m
0.000
0.025
0.050
0.075
0.100
0.125
ch
angera
teds/dt,mm
/hr
-5
0
5
10
15
20
25
time t, hr
0 20 40 60 80
energy
lossU
,MJ/m
2
0
20
40
60
80
coo
ling
loa
ddU/dt,kW/m
2
0
2
4
6
8
thickness
thickness
change rate
energy loss
cooling load
Figure 7 1D case study 1: Temperatures at monitored nodes
(Figure 5), ice thickness and energy plots.
3.2 Constant Average Brine Temperature
As it takes 77.3 hours for fully freezing all water when the
brine temperature variation is linearly interpolated, the averaged
brine temperature over 78 hours of -5.996C is used for the next
comparison (Figure 8). When the average brine temperature is
used, only the result characteristics of problems with constant
boundary temperature [4] are obtained with many differences due
to the brine temperature variations. The time taken for the water
to be fully frozen is slightly shorter at 76.8 hours. The difference
in ice thickness is quite large when compared with results from
the interpolated brine temperature simulation. The difference in
energy loss is also significant.
These differences make the use of average brine
temperature an inappropriate approximation even though its use
would greatly simplify the plant controls. Thus the step brine
temperature is considered next.
tempera
tureT
,C
-10
0
10
20
30
40
increasingx
thickness
difference,
%
-20
0
20
40
60
80
100
ice
thickness
differe
nce,
mm
-6
-4
-2
0
2
4
6
time t, hr
0 20 40 60 80
los
sdifference,
%
-5
0
5
10
15
energyloss
difference,
MJ/m
2
-2.0
-1.0
0.0
1.0
2.0
savg
sinterp
100(savg
sinterp
)/sinterp
100(Uavg
Uinterp
)/Uinterp
Uavg
Uinterp
Figure 8 1D case study 2: Temperatures at monitored nodes as
well as ice thickness and energy plots as compared against the
linear interpolation case study 1.
3.3 Step Brine Temperature
If the step values, in which the brine temperature is kept
constant during the hour and jumps to the next measured value,
are used instead of the linear interpolation of hourly brine
temperatures, the results such as temperature distributions and
ice thickness, etc. are still similar but with more stepping
8/8/2019 Simulation of Block Ice Formation With Varying Brine Temperatures
5/7
ENETT2550-019
5/7
shapes (Figure 9). It takes 77.5 hours to fully freeze all water.
The difference in ice thickness is small when compared with the
results from interpolated brine temperature and fall within the -
0.592 0.900 mm range with the average and SD values of -
0.010 mm and 0.310 mm. If the percentage difference in ice
thickness is considered, the difference is within the range of -6.87
1.614% but with the average and SD values of -0.115% and
0.761% during the 80-hours period. The differences in internal
energy losses are also acceptable when compared with the
results from interpolated brine temperature. The differences fall
within the -0.230 0.309 MJ/m2
range with the average and SD
values of -0.014 MJ/m2
and 0.117 MJ/m2. If the percentage
difference in loss internal energy is considered, the difference is
within the range of -2.862 0.757% but with the average and SD
values of -0.080% and 0.383% only.
tempera
tureT
,C
-10
0
10
20
30
40
increasingx
thickness
diffe
rence,
%
-6
-4
-2
0
2
4
ice
thickness
difference,
mm
-1.0
-0.5
0.0
0.5
1.0
1.5
2.0
time t, hr
0 20 40 60 80
loss
difference,
%
-3
-2
-1
0
1
energy
loss
difference,
MJ/m
2
-0.50
-0.25
0.00
0.25
0.50
sstep
sinterp
100(sstep
sinterp
)/sinterp
100(Ustep
Uinterp
)/Uinterp
Ustep
Uinterp
Figure 9 1D case study 3: Temperatures at monitored nodes as
well as ice thickness and energy plots as compared against the
linear interpolation case study 1.
4. 3D Case Study
The developed program [4] is employed to study the freezing
process in industrial ice block manufacturing with the actual size
of ice block shown in Figure 10a. Initially, temperature of water is
= 40 CiT throughout. The boundary conditions on the top end
is assumed to be = 0 CbT . Due to symmetry, only one-fourth of
the total area is modelled. The discretised domain consists of 26
13 120 cells while 10 st = which satisfy the combined cell
size/time step restrictions [4].
4.1 Linear Interpolation of Brine Temperature
With linear interpolation of hourly brine temperatures in
Figure 2, the boundary condition can be considered a close
approximation of the real brine temperature and used as the
reference case. It takes just under 89.5 hours before all water are
frozen.
0.52 m
1.2 m
0.27 m0.56 m
a
b
c
d
e
a) block geometry b) monitored cells
Figure 10 Geometry and domain of ice block.
Selected locations in the ice block are monitored (Figure
10b) and the temperatures and ice fractions at these cells are
shown in Figure 11. It is noted that the values at cells b and care
similar with only small delays for c, indicating that the side
freezing fronts dominates the solidification process while the
freezing front from the bottom exerts much less influences.
Although the uppermost-centre node d experiences a sharp
temperature drop early on, it still remains unfrozen until the last
moments due to the fact that the ambient temperature is not
sufficiently low to properly induce an effective freezing process.
Coupled with the fact that it takes more than 10 hours longer for
the domain to be fully frozen when compared to the 1D test case,
the importance of the ambient temperature on the determination
of overall freezing duration is clearly demonstrated.
For overall results, the loss of internal energy and fraction of
ice in the block are displayed. The characteristic fluctuations of
results with the brine temperature variations are clearly observed.
4.2 Average Brine Temperature
As previous, the averaged brine temperature over 90 hours
of -6.46C is used for the next comparison. It takes just under
88.5 hours before all water are frozen in keeping with the trend in
1D simulations. As in the 1D case, the differences in water
fraction and energy loss are quite large when compared with the
results from interpolated brine temperature changes as shown in
Figure 12.
8/8/2019 Simulation of Block Ice Formation With Varying Brine Temperatures
6/7
ENETT2550-019
6/7
te
mpera
tureT
,C
-10
0
10
20
30
40
pt a
ce
llwa
ter
frac
tion
0.00
0.25
0.50
0.75
1.00
time t, hr
0 20 40 60 80
totalenergy
lossU
,M
J
0
5
10
15
20
25
totalwa
ter
frac
tionf
0.0
0.2
0.4
0.6
0.8
1.0
energy loss
water fraction
pt e
pt b
pt d
pt e
pt a pt b
pt d
pt c
pt c
Figure 11 3D case study 1: Temperature & ice fraction at
monitoringcells as well as total energy loss and water fraction.
te
mpera
tureT
,C
-10
0
10
20
30
40
pt a
ce
llwa
ter
frac
tion
difference,
%
0
20
40
60
80
100
time t, hr
0 20 40 60 80
energy
loss
difference,
MJ
-1.25
-1.00
-0.75
-0.50
-0.25
0.00
0.25
0.50
totalfrac
tion
difference
,%
-6
-4
-2
0
2
4
6
8
pt e
pt b
pt d
pt e
pt a
pt b pt d
pt c
pt c
100(favg
finterp
)
Uavg
Uinterp
100(favg
finterp
)
Figure 12 3D case study 2: Temperature & ice fraction at
monitoringcells as well as total energy loss and water fraction.
4.3 Step Brine Temperature
If the step values are used instead of the linear interpolation
of hourly brine temperatures, the overall results are quite similar
even though some differences in some individual cells are
comparatively larger than others (Figure 13). The difference in
total water fraction is small when compared with the results from
interpolated brine temperature such that the differences fall within
the -0.531 0.678% range with the average and SD values of -
0.001% and 0.221% or in the order of 1/10th compared to the
constant brine temperature simulation (Figure 12). For the totalinternal energy loss, the differences fall within the -0.106 0.093
MJ range with the average and SD of -0.002 MJ and 0.038 MJ,
respectively.
5. Conclusion
The ice formation simulation with real hourly brine
temperatures by the finite volume method with the fixed grid and
the latent heat by fictitious sensible heat schemes is successfully
performed for 1D and 3D test cases. Three different temperature
estimations between the hours are considered the linear
interpolation, constant average and step values. The linear
interpolation best emulates the real changes but requires more
detailed analyses for on-site plant control. The average brine
temperature, while is able to predict the overall trend, can not
capture the variations within the domain during the freezing
period. Hence, it is not suitable for further uses in the real
optimisation of plant operating conditions. The results from the
step approximation differ slightly from those of linear interpolation
and can probably be used for the existing hourly plant control [1]
instead.
The future works includes the analyses of simulated data for
better ice formation approximation which is in immediate demandfor the plant control as the current approximation method by
tabulate energy loss data [1] was found the overestimate the
number of ready-for-sell ice blocks by some 200 to 400 blocks
out of the total number of 2600 [5]. Later, the programs should be
used to study effects of various parameters, such as the brine
and ambient temperatures, brine level, mould thickness and sizes
on the ice formation rate so that a more efficient plant control and
design can be formulated and obtained.
8/8/2019 Simulation of Block Ice Formation With Varying Brine Temperatures
7/7
ENETT2550-019
7/7
te
mpera
tureT
,C
-10
0
10
20
30
40
pt a
ce
llwa
ter
frac
tion
difference,
%
-10.0
-7.5
-5.0
-2.5
0.0
2.5
5.0
time t, hr
0 20 40 60 80
energy
loss
difference,
MJ
-0.20
-0.15
-0.10
-0.05
0.00
0.05
0.10
totalfrac
tion
difference
,%
-0.6
-0.4
-0.2
0.0
0.2
0.4
0.6
0.8
pt e
pt b
pt d
pt e
pt apt b
pt d
pt c
pt c
100(fstep
finterp
)
UstepUinterp
100(fstep
finterp
)
Figure 13 3D case study 3: Temperature & ice fraction at
monitoringcells as well as total energy loss and water fraction.
6. Acknowledgements
Special thanks are due to Dr. Naebboon Hoonchareon and
Miss Thitima Lertpiya from the Department of Electrical
Engineering, Chulalongkorn University as well as the Siam
Scholars Co., Ltd., Bangkok.
References
1. Lertpiya, T. Energy Management System for Block-Ice
Factory using TOD and TOU Tariff, M. Eng. Thesis,
Department of Electrical Engineering, Faculty of
Engineering, Chulalongkorn University, 2005.
2. Hoonchareon, N. and Lertpiya, T. Private Communication,
2004.
3. Prapainop, R. and Maneeratana, K. Simulation of ice
formation by the finite volume method, Songklanakarin
Journal of Science and Technology, vol. 26, no. 1, pp. 55-
70, 2004.
4. Meneeratana, K. Simulation of ice formation by the
unstructured finite volume method, Proceedings of the 1st
E-NETT Conference. Ambassador City Jomtien, Chonburi,
code ECB02, pp. 211-216, 11-13 May 2005.
5. Hoonchareon, N. Private Communication, 2007.