APPLICATION
Fresh air introduction, heating and/or cooling. Installation indoors or outdoors. Floor or ceiling setting up (sizes 08 to 38). Handled air temperature: -25 to +40°C.
RANGE
7 one-piece casing sizes 08 / 18 / 28 / 38 / 48 / 88 / 120. Airflow from 200 to 12 000 m3/h. 8 models:
3 operating modes: variable airflow (VAV), constant airflow (CAV), constant pressure (COP).
Configurations:
Sizes 08 to 38 indoor or outdoor units- EXD : right hand access and connections,- EXG : left hand access and connections.
Sizes 48 to 120 outdoor unit with mounted roof :- EXD : right hand access and connections,- EXG : left hand access and connections.
Sizes 48 to 120 indoor unit without roof :- D : right hand access and connections,- G : left hand access and connections.
CORRIGO control specific to VIM. RS485 ModBus communication port and TCP/IP BacNet IP port. ETD offset touch control.
Inverted assembly for ceiling fixing, possible for all configurations of sizes 08 to 38.
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
KSDR ECOWATT® 48 TO 120
KSDR ECOWATT® 08 TO 38
APCAir inlet and outlet
G4, M5 or F7 cartridge filters
MSDZM0 and M1 Circularflexible sleeve
REEV/LFDamper piloted by actuator
ACCESSORIES FOR SIZES 08 TO 38
ACCESSORIES FOR SIZES 48 TO 120
NE
W
CVFRemote controlOn/Off + variation
SCO2 AAmbient measurement sensor
SPRD BDifferential pressure sensor
TGRAmbient sensor
ELECTRICAL ACCESSORIES
CORRIGO control with Modbus/BACnet communication
Coils fitted within the AHU
Backward plug fan
50 mm double skin panel
Low-consumption EC Motor
2018
BMSModbusBACnet
REINFORCEDinsulation SÉLECTION
software
UVNR - variable EC Motor OPTAIR® CTA
Electrical Hotwater
Coldwater
Reversible water
Direct expansion
Glycol water coil
EI
EC
EF
ER
ECF
EX
EG
EGC
Each water coil is delivered with a 3 ways valve for sizes 08 to 38.
CDRAntifrost or fire damper, can be motorized
M5, M5+F7 or M5+F9 mini pleat filters
KSDR BCCCircularconnection flange
VTVS Motorized 3 ways valve
KSDR BRCRectangular connectionflange
KSDR CHHorizontal raincap withbird guard
MSCERectangular flexible sleeve
SIPH - EUAZStandard or ball syphons
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr | 2
| Sim
ple fl
ow
AHU
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
DESCRIPTION
Construction
Self-supporting structure made of 50 mm double skin panels. Mineral rock wool insulation with a thickness of 50 mm and density
of 40 kg/m3, - Heat conductivity: 0.037 W/(m.k) (20/80°C). - Fire rating A1 according to the standard EN 13 501.1.
Galvanised steel backward plug fans for sizes 08 to 38, aluminium backward plug fans for sizes 48 to 120, with built-in EC Motor.
Fitted and connected switch. Right or left hand access and connection sides according to air circu-
lation direction.
Construction sizes 08 to 38
Inside and outside finish of Z275 galvanised steel. Construction in line, connection by circular flanges with category D
seals. Standard G4 filter, M5 or F7 HEP (High Energy Performance) optional
filter. 4 holders/retaining brackets provided. Access cover secured when the unit is attached upside down.
Construction sizes 48 to 120
Unit delivered with 100mm feet. Construction in line, connection by rectangular flanges. Standard mini-pleat M5 filter, M5 + F7 HEP or M5 + F9 HEP (High
Energy Performance) mini-pleat optional filters.. Grain-effect exterior finishes made of RAL7024 dark grey pre-lac-
quered galvanised steel ; RC3 corrosion-resistant, RUV3 ultravio-
let resistant, according to EN 10169.
Interior finishes of Z275 galvanised steel.
Roof mounted in EX version. KSDR 120 : damper integrated into the unit between filtration and coil,
for coil antifrost function or CH 38 ERP French fire regulation compli-ance. Optional damper for EI models.
Control
Mounted/connected CORRIGO control, integrated into the unit with offset touch control, allowing 3 operating modes:
AIRFLOW ADJUSTMENT ADVISED APPLICATIONS
VAV - VARIABLE AIRFLOW MODE
Fan speed variation
- Airfl ow function of a 0-10 V signal coming from the extraction, remote control, an external sensor (CO2, temperature, hygrometry, etc.) or a remote control (M/A + variation).
- Fresh air counterbalance according to kitchen extraction,- Single-zone installations which require the fan to be adapted according to the occupation.
CAV - CONSTANT AIRFLOW MODE
Fan speeds defi ned according to a precise airfl ow
- Manual entry (m3/h) of 2 airfl ow setting points such as 0-LS-HS. Manual operation or by time slot.- Viewing of values on the display, manual switching, by clock or external contact.
- Installations that require the control of one or more precise airfl ows.
COP - CONSTANT PRESSURE MODE
Automatic variation of the fan speed to maintain a constant pressure
- Constant pressure value measured by an external sensor (optional) located in the supply duct network.
- Multi-zone installations connected to a modulation of terminal airfl ows.
Motorisation
Backward plug fan connected to an EC Motor. Single or three phases motor with heat protection managed electron-
ically, by 0-10V control or ModBus: - KSDR 08/18: Single phase 230V (200-277V), 50/60Hz, IP44, category B. - KSDR 28: Single phase 230V (200-277V), 50/60Hz, IP54, category B. - KSDR 38: Three phases 400V (380-480V), 50/60Hz, IP54, category B. - KSDR 48: Three phases 400V, 50/60Hz, IP54, category B. - KSDR 88/120: Three phases 400V, 50/60Hz, IP54, category F.
Electrical heaters (EI models)
304L stainless steel resistance. Overheat control: automatic resetting at 75°C, manual resetting at
120°C. Proportional control by static relay for the 1st stage followed by se-
quencing for the subsequent stages. Electrical load relief control possible on 1 or 2 stages (sizes 48 to 120).
Heating/reversible water coils (Models EC / ER / ECF / EGC)
2, 3 or 4 rows coils, depending on the model, with copper tubes and aluminium fins, in a galvanised steel frame; threaded coil headers.
Right or left hand connection in the air direction. Anti-freeze protection by contact sensor. Coil(s) mounted on slide rail which is accessible by a side hatch. Stainless steel drip tray and droplet separator if reversible. Motorised 3 ways valve (24V) proportional with 0-10V signal provided,
optionally for sizes 48/88/120, not fitted.
Cooling water coils (EF/ECF models)
3 or 4 rows coils, depending on the model, with copper tubes, alumin-ium fins on a galvanised steel frame; threaded coil headers.
Right or left hand connection in the air direction Coil(s) mounted on slide rail which is accessible by a side hatch. Stainless steel drip tray and droplet separator. Motorised 3 ways valve (24V) proportional with 0-10V signal provided,
optionally for sizes 48/88/120, not fitted.
Direct expansion coil (EX) - (sizes 48 to 120)
Coil with 2 or 3 rows to run in evaporation or condensation mode. Copper tubes and collectors, aluminium fins in a galvanised steel
frame. Stainless steel drip tray and droplet separator.
Glycol water coils (EG/EGC models) (1 coil provided) - (sizes 48 to
120)
6 rows coils, with copper tubes, thick aluminium fins in a galvanised steel frame ; threaded coil headers.
Right or left hand connection in the air direction. Coil(s) mounted on slide rail which is accessible by a side hatch. Optional motorised 3 ways valve (24V) proportional with 0-10V signal,
not fitted. The EGC model has an additional heating coil (EC model).
NE
W
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr |3
| Sim
ple fl
ow
AHU
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
NE
W
KSDR ECOWATT WITH CORRIGO control EI EC EF ER ECF EX EGMAIN ITEMS- Main safety switch fi tted on control cabinet outer face
- Controller and terminal block fi tted within the unit and accessible from the cabinet outer face
- TGK3 PT1000 fresh air temperature sensor
- TGK3 PT1000 supply air temperature sensor
- TGA1 PT1000 (EC - ER - ECF) anti-freeze temperature sensor
- THCO "CHANGEOVER" sensor to be installed at the water coil inlet (ER)
- TGK3 PT1000 extract air or TGR5 PT1000 ambient air temperature sensor
- Motorized 3 ways valve(s) - proportional 0-10V provided, not fi tted A A A A
- Filter clogging check pressure switch
FUNCTIONSAirfl ow adjustment and display
- Constant or fi xed airfl ow (CAV mode), up to 2 diff erent airfl ow setting points
- Variable airfl ow according to an external 0-10V signal, from the remote control or from an off set control (VAV mode)
- Airfl ow management according to time slots (clock)
- BOOST function by external contact
- STOP function by external contact
Control of internal water coils- Power control by 3 ways valve activation C B
Control of internal electrical coils - Proportional control of the electrical heater power
Control of an external electrical heater (accessory) - Proportional control of the electrical heater power by a 0 - 10V signal
- Fresh air damper (accessory) actuator control
Controls and Safety- Filter clogging signal
- Temperature sensor fault signal
- Fan fault signal
- Signal that the setting point is not reached (Airfl ow, Pressure, T°)
- Fire alarm from a contact related to the external fi re detection system
- Controller and remote control communication fault signal
- Water coil freezing risk check (valve opening, stop if water temperature goes below 7°C in heating mode).
- Alarm history
COMMUNICATION- Remote control with touch graphic display (ETD)
- MODBUS RTU in standard mode (RS485)
- BACNET IP on TCP/IP port
- Web server application on TCP/IP port
Included, Optional
(A) valves optional for sizes 48-88-120.
(B) Glycol water coil taken into account :The control can manage the circulation pump of the glycol water coil :- all or nothing (without the use of a by-pass valve in the circuit),- all or nothing with control of the by-pass valve,- at a variable speed without a by-pass valve.
(C) Direct expansion coil taken into account :The control of the direct expansion coil must be managed by the direct expansion unit, coordinated by a 0-10V signal proportional to a warm or cold need.The Corrigo controller has a signal input for DX group defrosting, to stop the ventilation in this case.
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr | 4
| Sim
ple fl
ow
AHU
KSDR ECOWATT® 08 to 38 with water coil (EC, EF, ER, ECF)
KSDR ECOWATT® 08 to 38 with electrical heater (EI)
OVERVIEW OF ELECTRONIC CONTROL
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
NE
W
S1 Supply air delivery T° sensor
S4 Fresh air T° sensor
R Corrigo controller
Pr1/2 Overheat control (manu/auto)
M1 Motor fan
M5 Fresh air damper (accessory)
Fl1 Fresh air filter
DP1 Fresh air filter pressure switch
DP3 Airflow measurement
DP5 Differential pressure sensor (COP mode accessory)
Bat1 Electrical heater
Triac Power adjustment
ETD Touch console to control the KSDR
S1 Supply air T° sensor
S4 Fresh air T° sensor
R Corrigo controller
Pr10 Anti-freeze sensor
S20 Changeover thermostat
M1 Motor fan
M5 Fresh air damper (accessory)
M6 Motorized valve
M7 Motorized valve
Fl1 Fresh air filter
DP1 Fresh air filter pressure switch
DP3 Airflow measurement
DP5 Differential pressure probe (COP mode accessory)
Coil1 Rev. water/heating coil
Coil2 Cooling coil
ETD Touch console to control the KSDR
Triac
ETD GTCou
S1S4
M1
DP5Pr2Pr1
Bat1
DP1 DP3
Fl1
R
Liaison d'usine
Liaison à réaliser
par le client
M5
Factory settings
To be achieved by
the customer
OU
Bat2Bat1
M6
M7
R ETD GTCou
M5 S1S4
M1
DP5DP1 DP3
Fl1
Liaison d'usine
Liaison à réaliser
par le client
Pr10M5 S1
Bat1
S4
M1
M6
S20 DP5
R
DP1 DP3
Fl1
ETD GTCou
Liaison d'usine
Liaison à réaliser
par le client
Pr10
Factory settings
To be achieved by
the customer
Factory settings
To be achieved by
the customer
OR
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr |5
| Sim
ple fl
ow
AHU
KSDR ECOWATT® 48 to 120 with water coil (EC, EF, ER, ECF)
KSDR ECOWATT® 48 to 120 with electrical heater (EI)
OVERVIEW OF ELECTRONIC CONTROL
S1 Supply air T° sensor
S4 Fresh air T° sensor
R Corrigo controller
Pr1/2 Overheat control (manu/auto)
M1 Motor fan
M5 Fresh air damper (accessory)
Fl1 Fresh air pre-filter
FI2 Fresh air filter
DP2 Fresh air filter pressure switch
DP1 Fresh air pre-filter pressure switch
DP3 Airflow measurement
DP5 Differential pressure sensor (COP mode accessory)
Coil1 Electrical heater
Triac Power adjustment
ETD Touch console to control the KSDR
S1 Supply air T° sensor
S4 Fresh air T° sensor
R Corrigo controller
Pr10 Anti-freeze sensor
S20 Changeover thermostat
M1 Motor fan
M5 Fresh air damper (accessory)
M6 Motorized valve (accessory)
M7 Motorized valve (accessory)
Fl1 Fresh air pre-filter
FI2 Fresh air filter
DP1 Fresh air pre-filter pressure switch
DP2 Fresh air filter pressure switch
DP3 Airflow measurement
DP5 Differential pressure probe (COP mode accessory)
Coil1 Rev. water/heating coil
Coil2 Cooling coil
ETD Touch console to control the KSDR
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
NE
W
S1S4
M1
DP5Pr2Pr1
Bat1
Triac
DP1 DP3
Fl1
R
Liaison d'usineLiaison à réaliser par le client
ETD GTCou
DP2
Fl2
Factory settings
To be achieved by
the customer
M5 S1S4
M1
DP5
R
DP1 DP3
Fl1
ETD GTCou
Liaison d'usine
Liaison à réaliser par le client
DP2
Fl2
Pr10
Bat1
M6
S20
Bat2Bat1
Pr10
M6
M7
R ETD GTCou
M5 S1S4
M1
DP5DP3
Fl1
DP1 DP2
Fl2
Liaison d'usine
Liaison à réaliser par le client
Factory settings
To be achieved by
the customer
Factory settings
To be achieved by
the customer
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr | 6
| Sim
ple fl
ow
AHU
OVERVIEW OF ELECTRONIC CONTROL
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
NE
W
KSDR ECOWATT® 48 to 120 with glycol water coil (EG)
KSDR ECOWATT® 48 to 120 with direct expansion coil (EX)
S1 Supply air T° sensor
S4 Fresh air T° sensor
R Corrigo controller
M1 Motor fan
M5 Fresh air damper (accessory)
Fl1 Fresh air pre-filter
FI2 Fresh air filter
DP1 Fresh air pre-filter pressure switch
DP2 Fresh air filter pressure switch
DX Direct expansion coil
DP3 Airflow measurement
DP5 Differential pressure sensor (COP mode accessory)
ETD Touch console to control the KSDR
S1 Supply air T° sensor
S4 Fresh air T° sensor
R Corrigo controller
M1 Motor fan
M5 Fresh air damper (accessory)
Fl1 Fresh air pre-filter
FI2 Fresh air filter
DP1 Fresh air pre-filter pressure switch
DP2 Fresh air filter pressure switch
EG Glycol water exchanger
M6 3 ways valve (if used, as an accessory)
C Circulator (if used)
DP3 Airflow measurement
DP5 Pressure sensor
ETD Touch console to control the KSDR
Liaison d'usineLiaison à réaliser par le client
M5 S1
Bat4
S4
M1
DP5
R
DP1 DP3
Fl1
ETD GTCou
DP2
Fl2
DX
Factory settings
To be achieved by
the customer
Liaison d'usineLiaison à réaliser par le client
R
M5 S1S4
M1
DP5DP1 DP3
Fl1
ETD GTCou
DP2
Fl2
Pr10
M6
EG
CFactory settings
To be achieved by
the customer
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr |7
| Sim
ple fl
ow
AHU
Model with EI electrical heaterRight hand access and connection
Model with EC heating, EF cooling orER reversible water coilRight hand access and connection
Model with heating + cooling coils ECFRight hand access and connection
R
BØ D
Ø12
F
G
A
E
C
OVERALL SIZE (IN MM)
SizesUnit Fixings Water coil Weight (Kg)
A B C Ø D E R F G H J K L N P EI EC, EF or ER ECF
KSDR 08 820 520 370 250 190 695 840 540 85 210 400 52 437 582 55 58 67
KSDR 18 1120 670 600 355 275 845 1140 690 105 390 675 52 565 740 99 104 127
KSDR 28 1120 670 600 400 265 845 1140 690 105 390 675 52 565 740 103 115 131
KSDR 38 1120 670 600 400 265 845 1140 690 105 390 675 52 565 740 112 121 140
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
NE
W
KSDR ECOWATT® 08 to 38
C
E
K LA
H J
Raccordement condensats Ø14(version réversible)
1 vanne 3 voies+ moteur : fournisnon montés
F
Ø 1''
Ø D
B
Ø 12
R
G
Drain tray connection Ø14(reversible type)
One 3 ways valvewith motor providednon fi tted
J B
R
H
L
L
A
F
N
P
E
CG ØD
Ø1''
Ø12
Raccordement condensats Ø14
2 vannes 3 voies+ moteurs : fournisnon montés
Drain tray connection Ø14
Two 3 ways valvesprovided not fi tted
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr | 8
| Sim
ple fl
ow
AHU
L
J
K
NM
OVERALL SIZE (IN MM)
Sizes J K L M N48 1975 1175 1020 90 90
88 2210 1485 1270 150 150
120 2400 1485 1580 150 150
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
NE
W
KSDR ECOWATT® 48Indoor model
KSDR ECOWATT® 48 to 120Outdoor model
E
A
J
F
CK
D I
M8(*)
G BH
KSDR ECOWATT® 88 to 120 Indoor model
E
A
F
JCK
D I
M8(*)
G BH
Sizes A B C D E F G (except EI) G (EI) H I J K
48 1715 1000 800 620 925 100 100 65 840 650 150 869
88 1950 1315 1100 810 1165 100 100 65 1140 850 135 1284
120 2400 1315 1100 1100 1465 100 100 65 1140 1188 135 1284
(*): 6 rivet nuts for sizes 88 and 120.
L
HS
P
Sizes H L S P48 734 890 108 530
88 1006 1190 107 644
120 1220 1187 included 692
CH-CHR 48 to 120Rain hood
G4 + M5 filtersFC M5
Mixing
section
CM
Main proof
hood
CH
MSSZ and BCCor BRC
G4 + F7 filtersFC F7
G4 + F7 filters
+ active coal
FCA
Damper
CDRBAC*
Casing
adaptation
flange
KSTA galva accessories 25mm
BAC*
Casing
adaptation
flange
Air flow
Sound
attenuator
SIL
Elec. heater
casing
EL
BCC or BRC and
MSSZ or MSDZ
Damper
CDR
KSTA galva accessories 25mm
CONFIGURATION
KSDR ECOWATT® 48 and 88
* BAC 48 or BAC 88 : double skin glavanized steel flange 25mm, provided with 2 feet to level the KSTA casing.
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr |9
| Sim
ple fl
ow
AHU
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200
Qv (m3/h)0
100
200
300
400
500
600
700Pabs (W)
0
100
200
300
400
500
600
700P
t (Pa)
5 10 15 20
10V
6V
8V
4V
5 10 15 20 25 30
15 20 25 30 40 50 60
10 20 30 40 50 60 80 100
10 20 30 40 50 60
20 40 60 80 100 110
10 20 30 40 50 60 80
2626
30
27
32
31
33
32
34
ΔP G4 filter
ΔP M5 filter
ΔP F7 filter
ΔP electric heater
ΔP heating coil
ΔP cooling coil
ΔP reversible coil
P (P )
KSDR ECOWATT® 18
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
NE
W
According to ISO 5801 standard, with 1,2 kg/m3 air density.
For electric heaters, water coils and filters pressure drops, refer to characteristics.
Acoustic pressure level measured in hemispherical free field, on a reflecting surface, with the micro place 4m from the sound source. Discharge connected, Lp in dB (A).
To calculate the acoustic pressure Lp by octave band, add the corrections indicated in the table below to the pressure level read.
AIR AND ACOUSTIC CHARACTERISTICS
0 2000 4000 6000 8000 10000 12000 14000
Qv (m3/h)0
200
400
600
800
1000
1200
1400
1600
1800
2000Pt (Pa)
88 120
4808 18 28
38
0 100 200 300 400 500 600 700 800 900 1000 1100
Qv (m3/h)0
50
100
150
200
250Pabs (W)
0
100
200
300
400
500P
t (Pa)
10 20 30
ΔP G4 filter
10V
6V
8V
4V
10 20 30 40
ΔP M5 filter
30 40 50 60 70 80 100
ΔP F7 filter
10 20 30 40 50 60 70 80
ΔP electric heater
10 20 30 40 50 60 70
ΔP heating coil
70 110 140 170
ΔP cooling coil
20 30 40 50 60 80 100 120 150
ΔP reversible coil
28
31
28
37
28
31
37
33
39
P (P )
KSDR ECOWATT® 08
PPtPt (((PPP ))a)
KSDR ECOWATT® range
CorrectionFrequency in Hz
63 125 250 500 1000 2000 4000 8000
Lp (4m) dB(A) 17 8 0 -5 -6 -12 -16 -21
SFP =P P = absorbed power in W; Q
v = airflow in m3/s; SFP = W/m3.s-1
SFP classifications see page 1531Qv
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr | 10
| Sim
ple fl
ow
AHU
According to ISO 5801 standard, with 1,2 kg/m3 air density.
For electric heaters, water coils and filters pressure drops, refer to characteristics.
Acoustic pressure level measured in hemispherical free field, on a reflecting surface, with the micro place 4m from the sound source. Discharge connected, Lp in dB (A).
To calculate the acoustic pressure Lp by octave band, add the corrections indicated in the table below to the pressure level read.
AIR AND ACOUSTIC CHARACTERISTICS
0 500 1000 1500 2000 2500 3000 3500
Q v (m3/h)
0
100
200
300
400
500
600
700
800
900P abs (W)
0
100
200
300
400
500
600
700
800
900P
t (Pa)
5 10 15 20 25 30 40 50 60
10V
6V
8V
4V
5 10 15 20 25 30 40 50 60 70 80
20 30 40 60 80 100 120
10 20 30 40 60 80 100 120
20 30 40 60 80 100 120
40 60 80 110 130 160
20 30 40 60 80 100 140 180
26 26
30
35
31
27
36
32
37
ΔP G4 filter
ΔP M5 filter
ΔP F7 filter
ΔP electric heater
ΔP heating coil
ΔP cooling coil
ΔP reversible coil
PPPPPt(((((PPPPP )a)a)a)a)
KSDR ECOWATT® 28
0 500 1000 1500 2000 2500 3000 3500 4000 4500
Qv (m3/h)0
100
200
300
400
500
600
700
800
900
1000Pabs (W)
0
100
200
300
400
500
600
700
800
900
1000P
t (Pa)
5 10 15 20 30 40 50 60 80 100
10V
6V
8V
4V
10 15 20 30 40 50 60 80 100 120
40 60 80 100 120 140 160
10 20 40 60 80 100 120 150 200
20 30 40 50 60 80 100 130
40 80 110 130 200
20 40 60 80 100 120 150 200
2929
33
30
38
3435
39
40
ΔP G4 filter
ΔP M5 filter
ΔP F7 filter
ΔP electric heater
ΔP heating coil
ΔP cooling coil
ΔP reversible coil
PPPPt((((PPPP ))a)a)
KSDR ECOWATT® 38
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500
Q v (m3/h)0
200
400
600
800
1000
1200
1400
1600
1800P abs (W)
0
100
200
300
400
500
600
700
800
900P t (P a)
10V
6V
8V
4V
ΔP M5 filter
10 20 30 40 50 60ΔP F7, F9 = F7 x 1.7 filter
20 30 40 50 60 70ΔP electric heater
10 20 30 40 50 60 70 80 90 110ΔP heating coil
10 20 30 40 50 60 70ΔP cooling coil
20 30 40 50 60 70 80 100 120 150ΔP cooling coil
10 20 30 40 50 60 70 80 100ΔP glycol water coil
40 60 80 100 130
PPPP t (P(P(P(P ))a)a)
KSDR ECOWATT® 48
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
NE
W
Q v (m3/h)
P abs (W)P t (P a)
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 100000
300
600900
1200
15001800
21002400
2700
3000
33003600
0
100200
300
400500
600700800
900
1000
11001200
10V
6V
8V
4V
10 20 30 40 50
PdC M5 filter
20 30 40 50 60 70
ΔP F7, F9 = F7 x 1.7 filter
20 30 40 50 60
ΔP electric heater
10 20 30 40 50 60
20 40 60 80 100 120 140
10 20 30 40 50 60 70 80 90ΔP glycol water coil
130110806040
ΔP heating coil
ΔP cooling coil
ΔP reversible coil
PPPP t (P(P(P(P ))a)a)
KSDR ECOWATT® 88
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr |11
| Sim
ple fl
ow
AHU
Water pressure drop of heating and reversible coils
KSDR ECOWATT® 08 to 38
Water pressure drop of cooling coils
KSDR ECOWATT® 08 to 38
AIR AND ACOUSTIC CHARACTERISTICS
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
NE
W
0 2000 4000 6000 8000 10000 12000 14000
Q v (m3/h)0
600
1200
1800
2400
3000
3600
4200
4800
5400
6000P abs (W)
0
200
400
600
800
1000
1200
1400
1600
1800
2000P t (P a)
10V
6V
8V
4V
10 20 30 40 50 60 70
20 30 40 50 60 70
20 30 40 50 60
10 20 30 40 50
20 30 40 50 70 90
10 20 30 40 50 60 70
1301006040
ΔP M5 filter
ΔP F7, F9 = F7 x 1.7 filter
ΔP electric heater
ΔP heating coil
ΔP cooling coil
ΔP reversible coil
ΔP glycol water coil
ΔP 6 rows cooling coil
20015010070
PPPPP tt ((P(P(P(P(P ))a)a)a)a)
KSDR ECOWATT® 120
KSDR ECOWATT® 48 to 120
KSDR ECOWATT® 48 to 120
0 2000 4000 6000 8000 10000 12000 14000 16000 180000
5
10
15
20
25
30
35
40
BAT 3
R 88
BAT 2R 120
BAT 3
R 48
BAT 4R 88BAT 3R 120
BAT 6
R 48
BAT 6
R 88
BAT 6R 120
Qv eau (l/h)
ΔP eau (kPa)
BAT 4
R 48
Qv water (l/h)
ΔP water (kPa)
0 2000 4000 6000 8000 10000 12000 140000
5
10
15
20
25
30
35
40
BAT 120 3R
BAT 88 4RBA
T 48 4
R BAT 120 6R
Qv eau (l/h)
ΔP eau (kPa)ΔP water (kPa)
Qv water (l/h)
According to ISO 5801 standard, with 1,2 kg/m3 air density.
For electric heaters, water coils and filters pressure drops, refer to characteristics.
Acoustic pressure level measured in hemispherical free field, on a reflecting surface, with the micro place 4m from the sound source. Discharge connected, Lp in dB (A).
To calculate the acoustic pressure Lp by octave band, add the corrections indicated in the table below to the pressure level read.
0 250 500 750 1000 1250 1500
Q v eau (l/h)0
5
10
15
20
25
30ΔPeau (kPa)
BAT EF 08
BAT EF 18/28/38
ΔP water (kPa)
Qv water (l/h)
CC 08
CC 18/28/38
0 500 1000 1500 2000Qv eau (l/h)
0
5
10
15ΔPeau (kPa)
BAT EC/ER 18/28/38
BAT EC/ER 08
ΔP water (kPa)
Qv water (l/h)
HC/RC 18/28/38
HC/RC 08
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr | 12
| Sim
ple fl
ow
AHU
TECHNICAL CHARACTERISTICS
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
NE
W
ModelFan Electric heater Complete unit
Max. speed(tr/min)
Frequency(Hz)
Voltage(V)
Max. p. absorbed (W)
Intensity(A)
Voltage(V)
P. absorbed (W)
No. of heatersand power
Intensity(A)
Voltage(V)
Total P(kW)
Intensity(A)
KSDR 08 EI 1 phase 2 649 50/60 1 Ph. 230V 193 1,5 Mono 230V 6 000 2x3kW 26,1 1 Ph. 230V 7 29
KSDR 08 EI 3 phases 2 649 50/60 1 Ph. 230V 193 1,5 3 Ph. 400V + N 9 000 3x3kW 13 3 Ph. 400V + N 10 15
KSDR 08 EC-EF-ER-ECF 2 649 50/60 1 Ph. 230V 193 1,5 - - - - 1 Ph. 230V 0,2 2
KSDR 18 EI 2 850 50/60 1 Ph. 230V 415 1,8 3 Ph. 400V + N 15 000 3x5kW 21,7 3 Ph. 400V + N 16 25
KSDR 18 EI 2 850 50/60 1 Ph. 230V 415 1,8 3 Ph. 400V + N 9 000 3x3kW 13 3 Ph. 400V + N 10 16
KSDR 18 EC-EF-ER-ECF 2 850 50/60 1 Ph. 230V 415 1,8 - - - - 1 Ph. 230V 0,4 2
KSDR 28 EI 2 800 50/60 1 Ph. 230V 715 3,1 3 Ph. 400V + N 24 000 3x3kW + 3x5kW 34,6 3 Ph. 400V + N 26 40
KSDR 28 EI 2 800 50/60 1 Ph. 230V 715 3,1 3 Ph. 400V + N 9 000 3x3kW 13 3 Ph. 400V + N 10 17
KSDR 28 EI 2 800 50/60 1 Ph. 230V 715 3,1 3 Ph. 400V + N 15 000 3x5kW 21,7 3 Ph. 400V + N 17 26
KSDR 28 EC-EF-ER-ECF 2 800 50/60 1 Ph. 230V 715 3,1 - - - - 1 Ph. 230V 1 3
KSDR 38 EI 2 580 50/60 3 Ph. 400V + N 1 000 1,63 3 Ph. 400V + N 30 000 6x5kW 43,3 3 Ph. 400V + N 33 47
KSDR 38 EI 2 580 50/60 3 Ph. 400V + N 1 000 1,63 3 Ph. 400V + N 15 000 3x5kW 21,7 3 Ph. 400V + N 17 24
KSDR 38 EC-EF-ER-ECF 2 580 50/60 3 Ph. 400V + N 1 000 1,63 - - - - 3 Ph. 400V + N 1 2
KSDR 48 EI 2 140 50/60 3 Ph. 400V 1 000 1,7 3 Ph. 400V 45 000 15x3kW 65 3 Ph. 400V 48 70
KSDR 48 EI 2 140 50/60 3 Ph. 400V 1 000 1,7 3 Ph. 400V 9 000 3x3kW 13 3 Ph. 400V 11 15
KSDR 48 EI 2 140 50/60 3 Ph. 400V 1 000 1,7 3 Ph. 400V 27 000 9x3kW 39 3 Ph. 400V 30 43
KSDR 48 EC-EF-ER-ECF-EX-EG-EGC 2 140 50/60 3 Ph. 400V 1 000 1,7 - - - - 3 Ph. 400V 1,2 2
KSDR 88 EI 2 040 50/60 3 Ph. 400V 2 730 4,2 3 Ph. 400V 90 000 18x5kW 129,9 3 Ph. 400V 97 141
KSDR 88 EI 2 040 50/60 3 Ph. 400V 2 730 4,2 3 Ph. 400V 30 000 6x5kW 43,3 3 Ph. 400V 34 50
KSDR 88 EI 2 040 50/60 3 Ph. 400V 2 730 4,2 3 Ph. 400V 60 000 12x5kW 86,6 3 Ph. 400V 66 95
KSDR 88 EC-EF-ER-ECF-EX-EG-EGC 2 040 50/60 3 Ph. 400V 2 730 4,2 - - - - 3 Ph. 400V 3 4,5
KSDR 120 EI 1 500 50/60 3 Ph. 400V 5 700 9 3 Ph. 400V 105 000 21x5kW 151,6 3 Ph. 400V 116 169
KSDR 120 EI 1 500 50/60 3 Ph. 400V 5 700 9 3 Ph. 400V 45 000 9x5kW 65 3 Ph. 400V 53 78
KSDR 120 EI 1 500 50/60 3 Ph. 400V 5 700 9 3 Ph. 400V 75 000 15x5kW 108,3 3 Ph. 400V 85 123
KSDR 120 EC-EF-ER-ECF-EX-EG-EGC 1 500 50/60 3 Ph. 400V 5 700 9 - - - - 3 Ph. 400V 6 9
ModelWeight (Kg)
EI EC/EF/ER ECF EX EG EGCKSDR 48 278 233 258 237 255 275
KSDR 88 417 350 387 356 383 413
KSDR 120 696 583 646 593 638 688
Electrical characteristics
Fluid coil headers
Weight
Sizes/Confi gurationsCoil header diameters (inches)
48 88 120EC 1" 1"1/4 2"
EF 1" 1"1/2 2"
ER 1" 2" 2"
Sizes/Confi gurationsCoil header diameters (inches)
48 88 120EG 3/4" 1" 2"
EX (liq./gaz) 35/42 mm 28/42 mm 28/42 mm
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr |13
| Sim
ple fl
ow
AHU
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
NE
W
KSDR ECOWATT® 08 to 38 with EC heating orER reversible water coilCharacteristics of coils with 90/70° hot water
Other water specification on demand.
Air input T° (°C)
KSDR ECOWATT® 08-10°C 0°C 10°C 15°C
Airfl ow(m3/h)
P (kW)
Air output T° (°C)
Water fl ow (l/h)
P (kW)
Air output T° (°C)
Water fl ow (l/h)
P (kW)
Air output T° (°C)
Water fl ow (l/h)
P (kW)
Air output T° (°C)
Water fl ow (l/h)
300 5.9 48 260 5.2 52 231 4.6 55 201 4.2 57 186
350 6.6 46 292 5.9 50 259 5.1 53 225 4.7 55 209
400 7.3 44 323 6.5 48 286 5.6 52 249 5.2 54 230
450 8.0 43 351 7.1 47 311 6.1 51 271 5.7 53 250
500 8.6 41 379 7.6 45 336 6.6 49 292 6.1 51 270
550 9.2 40 405 8.1 44 359 7.1 48 312 6.5 50 289
600 9.8 38 431 8.6 43 381 7.5 47 331 6.9 49 306
650 10.3 37 455 9.1 42 403 7.9 46 350 7.3 49 324
700 10.9 36 479 9.6 41 424 8.3 45 368 7.7 48 340
750 11.4 35 502 10.1 40 444 8.7 45 386 8.1 47 356
800 11.9 34 524 10.5 39 463 9.1 44 402 8.4 46 372
850 12.4 33 545 10.9 38 482 9.5 43 419 8.8 46 387
900 12.8 32 566 11.3 37 501 9.9 43 435 9.1 45 401
Power correction coeffi cient
Water specifi cation80/60 50/40
0.86 0.55
TECHNICAL CHARACTERISTICS
Air input T° (°C)
KSDR ECOWATT® 18/28/38-10°C 0°C 10°C 15°C
Airfl ow(m3/h)
P (kW)
Air output T° (°C)
Water fl ow (l/h)
P (kW)
Air output T° (°C)
Water fl ow (l/h)
P (kW)
Air output T° (°C)
Water fl ow (l/h)
P (kW)
Air output T° (°C)
Water fl ow (l/h)
500 13.0 67 579 11.6 69 517 10.2 70 453 9.5 71 421
600 15.0 64 668 13.4 66 596 11.8 68 522 10.9 68 485
700 17.0 62 753 15.1 64 671 13.2 66 588 12.3 67 546
800 18.8 59 833 16.7 62 742 14.6 64 650 13.6 65 604
900 20.5 57 910 18.3 59 810 16.0 62 710 14.8 63 659
1000 21.4 54 943 19.0 56 838 16.6 59 732 15.4 61 679
1200 24.6 51 1085 21.8 54 963 19.1 57 841 17.7 59 779
1400 27.6 49 1217 24.5 52 1081 21.4 55 943 19.8 57 873
1600 30.4 47 1342 27.0 50 1191 23.6 54 1039 21.8 56 963
1800 33.1 45 1461 29.4 49 1296 25.6 52 1130 23.7 54 1047
2000 35.7 43 1575 31.7 47 1396 27.6 51 1217 25.6 53 1127
2200 38.2 42 1683 33.8 46 1492 29.5 50 1300 27.3 52 1203
2400 40.5 40 1786 35.9 44 1584 31.3 49 1380 29.0 51 1277
2600 42.8 39 1886 37.9 43 1672 33.0 48 1456 30.6 50 1348
2800 44.9 38 1982 39.8 42 1756 34.7 47 1530 32.1 49 1415
3000 47.1 37 2075 41.7 41 1839 36.3 46 1601 33.6 48 1481
3200 49.1 36 2164 43.5 40 1918 37.8 45 1669 35.0 48 1544
3400 51 35 2251 45.2 40 1994 39.3 44 1735 36.4 47 1605
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr | 14
| Sim
ple fl
ow
AHU
KSDR ECOWATT® 08 with EF cooling coilCharacteristics of coils with 7/12° cold water Other water specification on demand.
Air input T° (°C)
KSDR ECOWATT® 0825°C and 50% RH 27°C and 50% RH 32°C and 50% RH
Airfl ow (m3/h) P (kW) Air output T° (°C) Water fl ow (l/h) P (kW) Air output T° (°C) Water fl ow (l/h) P (kW) Air output T° (°C) Water fl ow (l/h)
300 1.51 13.17 259 1.84 13.94 315 2.92 15.43 501
350 1.7 13.46 292 2.07 14.22 356 3.29 15.86 565
400 1.88 13.71 323 2.31 14.43 397 3.64 16.23 626
450 2.05 13.94 352 2.53 14.67 434 3.98 16.57 684
500 2.21 14.15 380 2.73 14.92 468 4.3 16.88 739
550 2.37 14.35 406 2.92 15.14 502 4.61 17.16 793
600 2.52 14.52 433 3.1 15.35 533 4.91 17.41 844
650 2.68 14.64 461 3.28 15.53 564 5.19 17.66 892
Air input T° (°C)
KSDR ECOWATT® 18/28/3825°C and 50% 27°C and 50% 32°C and 50%
Airfl ow (m3/h) P (kW) Air output T° (°C) Water fl ow (l/h) P (kW) Air output T° (°C) Water fl ow (l/h) P (kW) Air output T° (°C) Water fl ow (l/h)
500 1.82 15.01 312 2.09 16.25 359 3.71 17.92 638
600 2.02 15.58 348 2.31 16.81 397 4.29 18.36 737
700 2.21 16.06 379 2.58 17.05 444 4.77 18.82 821
800 2.38 16.45 409 2.89 17.20 496 5.24 19.21 890
900 2.53 16.81 435 3.36 17.18 576 5.64 19.61 969
1000 2.80 16.83 481 3.84 17.10 659 6.01 19.96 1033
1200 3.72 16.3 638 4.43 17.42 761 6.71 20.55 1153
1400 4.27 16.44 733 4.95 17.75 850 7.33 21.05 1260
1600 4.71 16.71 809 5.39 18.07 926 7.90 21.45 1358
1800 5.10 16.97 876 5.79 18.36 995 8.43 21.82 1449
2000 5.47 17.21 940 6.17 18.62 1060 8.94 22.13 1537
Air inlet Water specifi cation5° - 10° C 6° - 11° C 8° - 13° C
Power correction coeffi cient
25° C and 50% RH 1.2 1.1 0.9
27° C and 50% RH 1.18 1.08 0.9
32° C and 50% RH 1.12 1.06 0.9
Air inletWater specifi cation
5° - 10° C 6° - 11° C 8° - 13° C
Power correction coeffi cient
25° C and 50% RH 1.2 1.1 0.9
27° C and 50% RH 1.18 1.08 0.9
32° C and 50% RH 1.12 1.06 0.9
Air input T° (°C)
KSDR ECOWATT® 0825°C and 50% 27°C and 50% 32°C and 50%
Airfl ow (m3/h) P (kW) Air output T° (°C) Water fl ow (l/h) P (kW) Air output T° (°C) Water fl ow (l/h) P (kW) Air output T° (°C) Water fl ow (l/h)
300 0.80 17.38 137 0.94 18.49 161 1.31 22.10 225
350 0.86 17.81 148 1.01 18.97 174 1.47 22.41 252
400 0.95 18.05 164 1.09 19.38 187 1.76 22.36 302
450 1.01 18.44 174 1.15 19.73 198 1.96 22.51 337
500 1.07 18.77 183 1.21 20.04 208 2.12 22.72 365
550 1.12 19.06 192 1.27 20.32 217 2.26 22.95 388
600 1.17 19.33 200 1.35 20.43 233 2.38 23.16 409
650 1.21 19.56 208 1.46 20.46 251 2.50 23.35 429
700 1.25 19.78 215 1.60 20.38 275 2.61 23.54 448
KSDR ECOWATT® 08 to 38 with ER reversible water coilCharacteristics of coils with 7/12° cold water
Other water specification on demand.
TECHNICAL CHARACTERISTICS
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
NE
W
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr |15
| Sim
ple fl
ow
AHU
Air input T° (°C)
KSDR ECOWATT® 18/28/3825°C and 50% RH 27°C and 50% RH 32°C and 50% RH
Airfl ow (m3/h) P (kW) Air output T° (°C) Water fl ow (l/h) P (kW) Air output T° (°C) Water fl ow (l/h) P (kW) Air output T° (°C) Water fl ow (l/h)
500 2.77 12.36 475 3.4 12.94 584 5.38 14.08 924
600 3.24 12.58 557 3.95 13.26 679 6.25 14.53 1074
700 3.68 12.82 631 4.47 13.54 768 7.09 14.91 1218
800 4.08 13.06 701 4.97 13.79 854 7.9 15.23 1358
900 4.47 13.28 767 5.44 14.04 935 8.66 15.56 1488
1000 4.85 13.45 834 5.98 14.12 1027 9.41 15.84 1617
1100 5.22 13.63 897 6.43 14.32 1104 10.13 16.1 1740
1200 5.57 13.8 957 6.86 14.51 1178 10.82 16.35 1859
1300 5.9 13.96 1014 7.26 14.7 1247 11.49 16.58 1974
1400 6.23 14.11 1070 7.68 14.86 1319 12.13 16.79 2084
1500 6.54 14.25 1124 8.08 15.01 1388 12.75 17 2192
1600 6.86 14.37 1178 8.45 15.16 1452 13.38 17.18 2299
1700 7.15 14.5 1228 8.81 15.31 1514 13.96 17.37 2399
1800 7.49 14.56 1287 9.18 15.45 1577 14.55 17.53 2500
1900 7.78 14.69 1336 9.53 15.57 1638 15.12 17.69 2599
2000 8.08 14.79 1338 9.88 15.69 1697 15.66 17.86 2692
TECHNICAL CHARACTERISTICS
KSDR ECOWATT® 18 to 38 with EF cooling coilCharacteristics of coils with 7/12° cold water
Other water specification on demand.
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
NE
W
KSDR ECOWATT® 48 to 88 with EC, EGC or ER heating coilCharacteristics of coils with 90/70° hot water
Other water specification on demand.
Power correction coeffi cient
Water specifi cation80/60 50/40
0.88 0.6
Air inlet T°*-5°C +5°C 15°C +20°C
0.94 0.83 0.72 0.65
* Corrections in relation to the power with the air at -10°C
Air input T° (°C)
KSDR ECOWATT® 48 - 3 rows - EC KSDR ECOWATT®48 - 4 rows - ER-10°C 0°C 10°C -10°C 0°C 10°C
Airfl ow(m3/h)
P(kW)
Air output T° (°C)
Water fl ow (l/h)
P(kW)
Air output T° (°C)
Water fl ow (l/h)
P(kW)
Air output T° (°C)
Water fl ow (l/h)
P(kW)
Air output T° (°C)
Water fl ow (l/h)
P(kW)
Air output T° (°C)
Water fl ow (l/h)
P(kW)
Air output T° (°C)
Water fl ow (l/h)
2000 45 57 2007 40 60 1780 35 62 1553 52 67 2287 46 68 2037 40 70 1785
2500 53 53 2335 47 55 2071 41 58 1805 61 63 2716 55 65 2419 48 67 2119
3000 59 49 2633 53 52 2334 46 55 2033 70 60 3117 63 62 2774 55 64 2429
3500 65 46 2904 58 49 2573 50 53 2241 79 57 3491 70 59 3108 61 62 2721
4000 71 43 3154 63 47 2794 55 51 2432 87 54 3847 77 57 3423 68 60 2996
4500 76 40 3386 68 45 2999 59 49 2609 94 52 4184 84 55 3723 73 58 3258
5000 81 38 3603 72 43 3191 63 47 2776 101 50 4504 90 54 4008 79 57 3506
Air input T° (°C)
KSDR ECOWATT® 88 - 3 rows - EC KSDR ECOWATT® 88 - 4 rows - ER-10°C 0°C 10°C -10°C 0°C 10°C
Airfl ow(m3/h)
P(kW)
Air output T° (°C)
Water fl ow (l/h)
P(kW)
Air output T° (°C)
Water fl ow (l/h)
P(kW)
Air output T° (°C)
Water fl ow (l/h)
P(kW)
Air output T° (°C)
Water fl ow (l/h)
P(kW)
Air output T° (°C)
Water fl ow (l/h)
P(kW)
Air output T° (°C)
Water fl ow (l/h)
3000 58 47 1711 51 50 1496 43 53 1279 81 70 3592 72 71 3197 63 72 2800
4000 70 42 2072 61 45 1810 52 49 1545 102 65 4509 90 67 4010 79 69 3508
5000 81 38 2389 70 42 2085 60 46 1778 121 62 5349 107 64 4757 94 66 4159
6000 90 35 2671 79 39 2330 67 43 1985 138 58 6134 123 61 5452 107 63 4766
7000 99 32 2929 86 37 2553 73 41 2173 155 56 6870 138 58 6105 120 61 5333
8000 107 30 3164 93 35 2758 79 39 2345 170 53 7566 151 56 6722 132 59 5869
9000 114 28 3383 100 33 2946 85 38 2505 185 51 8227 165 54 7306 144 57 6378
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr | 16
| Sim
ple fl
ow
AHU
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
NE
W
TECHNICAL CHARACTERISTICS
T°(°C)
KSDR ECOWATT® 120 - 2 rows - EC-10°C/90% 0°C/90% 10°C/90%
Airfl ow(m3/h)
P(kW)
Air output T° (°C)
Air pressure drop (Pa)
Water fl ow (l/h)
P(kW)
Air output T° (°C)
Air pressure drop (Pa)
Water fl ow (l/h)
P(kW)
Air output T° (°C)
Air pressure drop (Pa)
Water fl ow (l/h)
4000 85.7 53.4 6.2 3806 76.4 56.2 6.4 3392 67.0 59.0 6.6 2975
6000 116.0 47.2 12.7 5153 103.25 50.7 13.1 4586 90.5 54.1 13.5 4018
8000 142.6 42.8 21.1 6335 126.9 46.8 21.7 5636 111.1 50.6 22.4 4934
10000 166.5 39.3 31.3 7398 148.05 43.7 32.1 6576 129.6 47.9 33.1 5755
12000 188.4 36.5 43.1 8370 167.5 41.2 44.3 7440 146.4 45.7 45.7 6504
T°(°C)
KSDR ECOWATT® 120 - 3 rows - ER-10°C/90% 0°C/90% 10°C/90%
Airfl ow(m3/h)
P(kW)
Air output T° (°C)
Air pressure drop (Pa)
Water fl ow (l/h)
P(kW)
Air output T° (°C)
Air pressure drop (Pa)
Water fl ow (l/h)
P(kW)
Air output T° (°C)
Air pressure drop (Pa)
Water fl ow (l/h)
4000 109.5 70.9 9.8 4863 97.8 72.0 10 4345 86.2 73.0 10.2 3830
6000 151.7 64.7 20 6736 135.4 66.4 20.4 6012 119.2 68.0 20.9 5293
8000 189.4 60 33.1 8413 169.0 62.2 33.9 7507 148.6 64.3 34.8 6603
10000 223.9 56.2 49 9944 199.6 58.8 50.2 8867 175.5 61.3 51.6 7794
12000 255.7 53.0 67.6 11357 227.9 56.0 69.3 10125 200.2 58.8 71.2 8894
KSDR ECOWATT® 120 with EC, EGC or ER heating coilCharacteristics of coils with 90/70° hot water
Other water specification demand.
KSDR ECOWATT® with ER reversible water coilCharacteristics of coils with 7/12° cold water
Other water specification on demand.
Air input T° (°C)
KSDR ECOWATT® 4825°C and 50% 27°C and 50% 32°C and 50%
Airfl ow(m3/h)
P(kW)
T° output T° (°C)
Water fl ow (l/h)
P(kW)
T° output T° (°C)
Water fl ow (l/h)
P(kW)
T° output T° (°C)
Water fl ow (l/h)
2000 7 15 1257 11 15 1821 18 17 3020
2500 10 15 1717 13 16 2151 20 17 3489
3000 12 15 1996 14 16 2479 23 18 3911
3500 13 15 2279 16 16 2728 25 19 4298
4000 15 16 2494 17 17 2964 27 19 4648
4500 16 16 2692 19 17 3186 29 20 4980
5000 17 16 2880 20 17 3408 31 20 5285
Air input T° (°C)
KSDR ECOWATT® 8825°C and 50% 27°C and 50% 32°C and 50%
Airfl ow(m3/h)
P(kW)
T° output T° (°C)
Water fl ow (l/h)
P(kW)
T° output T° (°C)
Water fl ow (l/h)
P(kW)
T° output T° (°C)
Water fl ow (l/h)
3000 11 15 1858 13 16 2210 26 16 4466
4000 13 16 2187 15 17 2572 33 17 5747
5000 14 17 2450 17 18 2865 39 18 6681
6000 16 17 2687 18 18 3140 44 19 7487
7000 17 18 2898 28 17 4851 48 19 8219
8000 18 18 3086 32 17 5492 52 20 8889
9000 27 17 4651 35 17 5987 55 20 9509
Power correction coeffi cient
Air inletWater specifi cation
5-10°C 6-11°C 8-13°C
25°C and 50% RH 1.2 1.1 0.91
27°C and 50% RH 1.18 1.09 0.92
32°C and 50% RH 1.16 1.08 0.91
KSDR ECOWATT® with EF cooling coilCharacteristics of coils with 7/12° cold water
Other water specification on demand.
Air input T° (°C)
KSDR ECOWATT® 4825°C and 50% 27°C and 50% 32°C and 50%
Airfl ow(m3/h)
P(kW)
T° output T° (°C)
Water fl ow (l/h)
P(kW)
T° output T° (°C)
Water fl ow (l/h)
P(kW)
T° output T° (°C)
Water fl ow (l/h)
2000 10 13 1740 12 14 2126 20 15 3398
2500 12 13 2034 14 14 2460 23 16 3941
3000 13 14 2291 16 15 2814 26 17 4436
3500 15 14 2538 18 15 3115 28 17 4884
4000 16 15 2769 20 16 3387 31 18 5295
4500 18 15 3048 21 16 3638 33 18 5684
5000 19 15 3272 23 16 3886 35 19 6045
Air input T° (°C)
KSDR ECOWATT® 8825°C and 50% 27°C and 50% 32°C and 50%
Airfl ow(m3/h)
P(kW)
T° output T° (°C)
Water fl ow (l/h)
P(kW)
T° output T° (°C)
Water fl ow (l/h)
P(kW)
T° output T° (°C)
Water fl ow (l/h)
3000 17 12 2868 21 13 3539 33 14 5610
4000 21 13 3540 25 13 4302 40 15 6853
5000 24 13 4130 29 14 4975 46 16 7957
6000 27 14 4644 32 15 5576 52 17 8936
7000 30 14 5137 37 15 6312 57 17 9855
8000 33 15 5600 40 15 6850 62 18 10697
9000 36 15 6166 43 16 7372 67 18 11476
AIR T
REAT
MEN
T
| VIM Catalogue 2017 | Instructions, Reports, EC declarations... available at www.vim.fr |17
| Sim
ple fl
ow
AHU
KSDR ECOWATT® with EF cooling coilCharacteristics of coils with 7/12° cold water
Other water specification on demand.
KSDR ECOWATT® with EX direct expansion coilHeating or cooling at R410a
TECHNICAL CHARACTERISTICS
SIMPLE FLOW AHU
KSDR ECOWATT®COMPACT - BACKWARD IMPELLER - EC MOTOR< 12 000 M3/H
NE
W
T°(°C)
Cold coil with 3 rows25°C/50 28°C/50 32°C 40%
Airfl ow(m3/h)
P(kW)
Air output T°(°C)
Water fl ow(l/h)
P(kW)
Air output T°(°C)
Water fl ow(l/h)
P(kW)
Air output T°(°C)
Water fl ow(l/h)
4000 13.1 15.8 2246 19.9 16.7 3410 25.2 17.0 4318
6000 20.8 15.8 3577 27.6 17.2 4738 33.1 18.3 5686
8000 25.6 16.3 4384 33.4 18.0 5735 39.9 19.2 6847
10000 31.2 16.4 5350 38.6 18.5 6619 45.9 20.0 7868
12000 35.14 16.9 6028 43.3 19.0 7432 51.2 20.6 8782
T°(°C)
Cold coil with 6 rows (*)24°C/50% 28°C/50% 32°C/40%
Airfl ow(m3/h)
P(kW)
Air output T°(°C)
Water fl ow(l/h)
P(kW)
Air output T°(°C)
Water fl ow(l/h)
P(kW)
Air output T°(°C)
Water fl ow(l/h)
6000 36.6 10.2 5,236 55.3 10.7 7,902 63.3 10.9 9,049
8000 46.1 10.6 6,584 68.8 11.5 9,829 78.8 11.7 11,269
10000 55.2 11.0 7,885 81.1 12.1 11,589 93.1 12.4 13,309
12000 63.3 11.4 9,052 92.5 12.7 13,217 106.5 13.1 15,215
(*) choose the KSDR 120 EG with optional chilled water
Size T° and %RHfresh air
Airfl ow(m3/h)
T° and RH%air outlet
Cold power(kW)
Δ Pa on air(Pa)
Coil volume(dm3)
Circuitnumber
Connection Ø(mm)
48 32°C 40% 4,800 20°C 73% 24 166 5 1 22/35
88 32°C 40% 8,800 22°C 66% 36 110 7 1 28/35
120 32°C 40% 12,000 22°C 66% 50 111 10 1 28/42
Fresh air -10°C 90% Extracted air 30°C 70% Extracted air 20°C 50% Water/air characteristics
SizeAirfl ow(m3/h)
Coil outlet T°(C)
Coil outlet % RH
Restored power (kW)
Effi ciency(%)
Coil outlet T°(C)
Coil outlet % RH
Restored power (kW)
Effi ciency(%)
Pressure drop on fresh air
(Pa)
Water fl ow(l/h)
Pressure drop on water
(kPa)
Coil connection
Ø (”)
48
4800 15.4 14.4 41.3 63.7 3.6 32.2 22.0 45.3 132 1860 50 3/4"
4200 16.0 13.9 36.9 65.0 3.8 31.5 19.6 46.1 106 1,815 49 3/4"
3600 12.7 147.2 27.6 56.8 3.4 32.6 16.3 44.7 80 1,100 16 3/4"
3000 14.8 15.0 25.1 61.9 4.5 30.3 14.7 48.2 57 1,100 17 3/4"
2400 17.1 12.9 22.0 67.8 5.7 27.8 12.7 52.2 39 1,100 16 3/4"
88
8800 16 13.8 77.2 65.0 4.3 30.7 42.4 47.5 134 3180 50 1"
7700 17.7 12.5 71.9 69.1 5.1 28.8 39.2 50.3 106 3,115 48 1"
6600 14.5 15.3 54.6 61.2 4.1 30.9 31.4 47 81 2,100 22 1"
5500 17.4 12.7 50.8 68.4 5.2 28.7 28.2 50.5 59 2,100 22 1"
4400 13.5 16.3 34.9 58.8 6.0 27.1 23.8 53.3 40 1,100 11 1"
120
12000 9.4 21.4 78.8 48.6 1.5 37.4 46.7 38.4 130 5,100 13 1 1/4"
10000 9.8 20.8 66.9 49.5 2.4 34.8 41.97 41.5 95 4,100 10 1 1/4"
8000 11.4 18.8 57.8 53.5 3.4 32.7 36.1 44.5 64 3,100 11 1 1/4"
6000 12.7 17.2 46.0 56.7 4.99 29.1 30.4 50 39 2,100 11 1 1/4"
KSDR ECOWATT® with EG glycol water coil
Use of the glycol water coil with a second coil of the same frontal sur-face area (10 rows with optimised circuits and fin pitches), installed at the air extraction unit of the building. The circulation loop is controlled by the CORRIGO of the KSDR.
Heat transfer fluid : glycol water with 30% ethylene glycol in volume.
Other water specification on demand.