7/23/2019 siemens plc Firmware Updation http://slidepdf.com/reader/full/siemens-plc-firmware-updation 1/3 Description FW update firmware version V4.5.x Updating firmware in RUN is possible as of this firmware version. An update is only possible from one version to the next, for example, from V4.5.5 to V4.5. !or information, refer to the respe"tive update des"ription and the !ault#tolerant systems $%# 4&&' system manual under (Updating the firmware without a memory "ard( and (!irmware update in RUN mode(.  Description: Difference of the operating system update compared to the remaining S7 4!! "#$s  After the a"tual firmware update, the self#test is started on the fault#tolerant system) this may ta*e several minutes. +his time depends on the load memory si-e of the inserted memory "ard and the "onfiguration of the wor* memory.  Description of rep%acement scenario /oth 01Us must have the same firmware version in an $%#4&&'. 2f one 01U of your $%#4&&' fails, order a new 01U with the same order number. 2t will be delivered with the latest firmware version. +his firmware version may be higher than the firmware version of the 01U being repla"ed. 2n this "ase, you must downgrade the new 01U to the older firmware version. 3ou have two options for the downgrade 1. using the memory card (see description …..) 2. using the online functionality as described below: Add the new CP to your automation system. !o not connect the "ber#optic cables yet. $elect this CP in %& Con"g or in $'A'C anager. *+ecute the menu command ,P-C pdate "rmware,. he ,pdate "rmware, dialog bo+ opens. %ere you select the "rmware "le with the same /ersion as that of the pre/ious CP. pload this "le to the CP. he new CP now has the same "rmware /ersion as the one it replaces. 0ow connect the "ber#optic cables.  ransfer the system to the edundant operating state by starting the CP.  es"ription of the operating system update with a memory "ard Re6uirements for "reating an operating system update "ard $ memory card 3lash 4 5 (order number 6*$ 782#19P#AA) or greater $*P with product /ersion ;<.1 or higher Programming de/ice or PC with e+ternal prommer for programming the memory card  

siemens plc Firmware Updation

Embed Size (px)

Citation preview

Page 1: siemens plc Firmware Updation

7/23/2019 siemens plc Firmware Updation

http://slidepdf.com/reader/full/siemens-plc-firmware-updation 1/3

Description FW update firmware version V4.5.x

Updating firmware in RUN is possible as of this firmware version. An update is only possiblefrom one version to the next, for example, from V4.5.5 to V4.5.!or information, refer to the respe"tive update des"ription and the !ault#tolerant systems $%#4&&' system manual under (Updating the firmware without a memory "ard( and (!irmware

update in RUN mode(.

 

Description: Difference of the operating system update compared to the remaining S74!! "#$s

 After the a"tual firmware update, the self#test is started on the fault#tolerant system) this mayta*e several minutes. +his time depends on the load memory si-e of the inserted memory "ardand the "onfiguration of the wor* memory.

 

Description of rep%acement scenario

/oth 01Us must have the same firmware version in an $%#4&&'. 2f one 01U of your $%#4&&'fails, order a new 01U with the same order number. 2t will be delivered with the latest firmwareversion. +his firmware version may be higher than the firmware version of the 01U beingrepla"ed. 2n this "ase, you must downgrade the new 01U to the older firmware version.

3ou have two options for the downgrade

1. using the memory card(see description …..)

2. using the online functionality as described below:• Add the new CP to your automation system.•

!o not connect the "ber#optic cables yet.• $elect this CP in %& Con"g or in $'A'C anager.• *+ecute the menu command ,P-C pdate "rmware,. he ,pdate

"rmware, dialog bo+ opens. %ere you select the "rmware "le with the same/ersion as that of the pre/ious CP.

• pload this "le to the CP. he new CP now has the same "rmware /ersionas the one it replaces.

• 0ow connect the "ber#optic cables.•  ransfer the system to the edundant operating state by starting the CP.

 

es"ription of the operating system update with a memory "ard

Re6uirements for "reating an operating system update "ard

• $ memory card• 3lash 4 5 (order number 6*$ 782#19P#AA) or greater• $*P with product /ersion ;<.1 or higher• Programming de/ice or PC with e+ternal prommer for programming the

memory card

 

Page 2: siemens plc Firmware Updation

7/23/2019 siemens plc Firmware Updation

http://slidepdf.com/reader/full/siemens-plc-firmware-updation 2/3

1ro"edure for "reating an operating system update "ard using $+71 %

• !ownload the re=uired CP "le• n>ip the "le with a double#clic? on the "le name• !elete the memory card with: ,3ile@!elete@$ emory Card, in $imatic

anager.• Program the operating system by selecting the following in $imatic anager:

,P-C@pdate A$ $,B select the target directory and start the programmingprocess by opening the "le CP%!.P!.

•  he operating system update card is programmed when the standard mousepointer appears again.

 

8eneral pro"edure for an operating system update

• Power 33 at the power supply (P$) of the rac? in which the CP is installed.• 'nsert the prepared operating system update card into the CP.

• Power 0 at the power supply of the rac? in which the CP is installed.•  he operating system is transferred from the memory card to the internal

3-A$% *P.• !uring this transferB all the -*!s on the CP are lit ('03B *D3B 3C*B C$B

0B $P). he operating system update ta?es about 2 minutes and iscompleted when the $P -*! on the CP Eashes slowly F memory resetre=uest from the system.0'C*:

 he self#test is started immediately after the update and can ta?e se/eralminutesB depending on the memory con"guration.

• Power 33 at the power supply and possible insertion of the memory cardintended for the operation.

• Power 0 at the power supply. he CP automatically performs a memory reset and is then operationalimmediately.

• $et the time after the successful operating system update.

 

Description of the operating system update in &$'

 As a general rule, any firmware update in RUN "an only be from one firmware version to thenext higher firmware version. A downgrade is not possible in RUN. $ee also the notes on therespe"tive version#spe"ifi" des"ription.

1ro"edure for automati" firmware update

'nitial situation: 5oth CPs are in redundant operation. edundant operation

1. 3or CP access protection with password: $elect a CP of the fault#tolerantsystem in $'A'C anager and select the menu command P-C Accessauthori>ation $etup. *nter the CP access password.

2. $elect one of the two CPs either /ia $imatic anager # ProGect or %&Con"g. !o not use the menu command ,Accessible nodes, in $imatic anager.

Page 3: siemens plc Firmware Updation

7/23/2019 siemens plc Firmware Updation

http://slidepdf.com/reader/full/siemens-plc-firmware-updation 3/3

<. $elect the menu command ,P-C pdate "rmware,A wi>ard is started that can automatically update the "rmware on both CPs.

+he "omplete update des"ription and alternative solutions are des"ribed in the !ault#tolerant$%#4&& ' $ystems system manual under (!irmware update in RUN mode(.

Link:

https://support.industry.siemens.com/cs/document/109474703/download-

operating-system-updates-4!h-cpu41"-3h-cpu414-4h-cpu414-4h-pg-

cpu417-4h-#dti$0%pnid$13&"&%lc$en-''