Upload
kly-nguyen
View
278
Download
15
Tags:
Embed Size (px)
Citation preview
MICROMASTER 440 0.12 kW - 250 kW
Operating Instructions Issue 10/06
User Documentation 6SE6400-5AW00-0BP0
MICROMASTER 440 Documentation
Getting Started Guide
Is for quick commissioning with SDP and BOP.
Operating Instructions
Gives information about features of the MICROMASTER 440, Installation, Commissioning, Control modes, System Parameter structure, Troubleshooting, Specifications and available options of the MICROMASTER 440.
Parameter List
The Parameter List contains the description of all Parameters structured in functional order and a detailed description. The Parameter list also includes a series of function plans.
Catalogues
In the catalogue you will find all the necessary information to select an appropriate inverter, as well as filters, chokes, operator panels and communication options.
MICROMASTER 440 0.12 kW - 250 kW
Operating Instructions User Documentation
Issue 10/06
Valid for Issue 10/06
Inverter Type Software Version MICROMASTER 440 2.1 0.12 kW - 250 kW
Overview 1
Installation 2
Functions 3
Troubleshooting 4
Specifications 5
Options 6
Electro-Magnetic Compatibility
7
Appendices
ABCDEFG
Index
MICROMASTER 440 Operating Instructions 4 6SE6400-5AW00-0BP0
Further information can be obtained from Internet website:
http://www.siemens.de/micromaster Approved Siemens Quality for Software and Training is to DIN ISO 9001, Reg. No. 2160-01 The reproduction, transmission or use of this document, or its contents is not permitted unless authorized in writing. Offenders will be liable for damages. All rights including rights created by patent grant or registration of a utility model or design are reserved. © Siemens AG 2001 – 2005, 2006. All Rights Reserved. MICROMASTER® is a registered trademark of Siemens
Other functions not described in this document may be available. However, this fact shall not constitute an obligation to supply such functions with a new control, or when servicing. We have checked that the contents of this document correspond to the hardware and software described. There may be discrepancies nevertheless, and no guarantee can be given that they are completely identical. The information contained in this document is reviewed regularly and any necessary changes will be included in the next edition. We welcome suggestions for improvement. Siemens handbooks are printed on chlorine-free paper that has been produced from managed sustainable forests. No solvents have been used in the printing or binding process. Document subject to change without prior notice.
Order number: 6SE6400-5AW00-0BP0
Siemens-Aktiengesellschaft
Issue 10/06 Foreword
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 5
Foreword
User Documentation
WARNING
Before installing and commissioning the inverter, you must read all safety instructions and warnings carefully including all the warning labels attached to the equipment. Make sure that the warning labels are kept in a legible condition and replace missing or damaged labels.
Information is also available from:
Regional Contacts Please get in touch with your contact for Technical Support in your Region for questions about services, prices and conditions of Technical Support.
Central Technical Support The competent consulting service for technical issues with a broad range of requirements-based services around our products and systems.
Europe / Africa Tel: +49 (0) 180 5050 222 Fax: +49 (0) 180 5050 223 Email: [email protected]
America Tel: +1 423 262 2522 Fax: +1 423 262 2589 Email: [email protected]
Asia / Pazific Tel: +86 1064 757 575 Fax: +86 1064 747 474 Email: [email protected]
Online Service & Support The comprehensive, generally available information system over the Internet, from product support to service & support to the support tools in the shop. http://www.siemens.com/automation/service&support
Contact address Should any questions or problems arise while reading this manual, please contact the Siemens office concerned using the form provided at the back this manual.
Definitions and Warnings Issue 10/06
MICROMASTER 440 Operating Instructions 6 6SE6400-5AW00-0BP0
Definitions and Warnings
DANGER indicates an immanently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION used with the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in a property damage.
NOTICE indicates a potential situation which, if not avoided, may result in an undesirable result or state.
NOTE
For the purpose of this documentation, "Note" indicates important information relating to the product or highlights part of the documentation for special attention.
Qualified personnel
For the purpose of this Instruction Manual and product labels, a "Qualified person" is someone who is familiar with the installation, mounting, start-up and operation of the equipment and the hazards involved. He or she must have the following qualifications: 1. Trained and authorized to energize, de-energize, clear, ground and tag circuits
and equipment in accordance with established safety procedures. 2. Trained in the proper care and use of protective equipment in accordance with
established safety procedures. 3. Trained in rendering first aid.
♦ PE – Protective Earth uses circuit protective conductors sized for short circuits where the voltage will not rise in excess of 50 Volts. This connection is normally used to ground the inverter.
♦ - Is the ground connection where the reference voltage can be the same as the Earth voltage. This connection is normally used to ground the motor.
Use for intended purpose only The equipment may be used only for the application stated in the manual and only in conjunction with devices and components recommended and authorized by Siemens.
Issue 10/06 Safety Instructions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 7
Safety Instructions
The following Warnings, Cautions and Notes are provided for your safety and as a means of preventing damage to the product or components in the machines connected. This section lists Warnings, Cautions and Notes, which apply generally when handling MICROMASTER 440 Inverters, classified as General, Transport & Storage, Commissioning, Operation, Repair and Dismantling & Disposal.
Specific Warnings, Cautions and Notes that apply to particular activities are listed at the beginning of the relevant chapters and are repeated or supplemented at critical points throughout these sections.
Please read the information carefully, since it is provided for your personal safety and will also help prolong the service life of your MICROMASTER 440 Inverter and the equipment you connect to it.
General
WARNING This equipment contains dangerous voltages and controls potentially
dangerous rotating mechanical parts. Non-compliance with Warnings or failure to follow the instructions contained in this manual can result in loss of life, severe personal injury or serious damage to property.
Only suitable qualified personnel should work on this equipment, and only after becoming familiar with all safety notices, installation, operation and maintenance procedures contained in this manual. The successful and safe operation of this equipment is dependent upon its proper handling, installation, operation and maintenance.
Risk of electric shock. The DC link capacitors remain charged for five minutes after power has been removed. It is not permissible to open the equipment until 5 minutes after the power has been removed. The following terminals can carry dangerous voltages even if the inverter is inoperative: ♦ the power supply L/L1, N/L2, L3 resp. U1/L1, V1/L2, W1/L3 ♦ the motor terminals U, V, W resp. U2, V2, W2 ♦ and depending on the frame size the terminals DC+/B+, DC-, B-, DC/R+
resp. DCPS, DCNS, DCPA, DCNA HP ratings are based on the Siemens 1LA motors and are given for
guidance only; they do not necessarily comply with UL or NEMA HP ratings.
CAUTION Children and the general public must be prevented from accessing or
approaching the equipment! This equipment may only be used for the purpose specified by the
manufacturer. Unauthorized modifications and the use of spare parts and accessories that are not sold or recommended by the manufacturer of the equipment can cause fires, electric shocks and injuries.
Safety Instructions Issue 10/06
MICROMASTER 440 Operating Instructions 8 6SE6400-5AW00-0BP0
NOTICE Keep these operating instructions within easy reach of the equipment and
make them available to all users Whenever measuring or testing has to be performed on live equipment, the
regulations of Safety Code BGV A2 must be observed, in particular §8 “Permissible Deviations when Working on Live Parts”. Suitable electronic tools should be used.
Before installing and commissioning, please read these safety instructions and warnings carefully and all the warning labels attached to the equipment. Make sure that the warning labels are kept in a legible condition and replace missing or damaged labels.
Transport & Storage
WARNING Correct transport, storage, erection and mounting, as well as careful operation and maintenance are essential for proper and safe operation of the equipment.
CAUTION Protect the inverter against physical shocks and vibration during transport and storage. Also be sure to protect it against water (rainfall) and excessive temperatures (see Table 4-1).
Commissioning
WARNING Work on the device/system by unqualified personnel or failure to comply with
warnings can result in severe personal injury or serious damage to material. Only suitably qualified personnel trained in the setup, installation, commissioning and operation of the product should carry out work on the device/system.
Only permanently-wired input power connections are allowed. This equipment must be grounded (IEC 536 Class 1, NEC and other applicable standards).
Only type B ELCBs should be used with FSA to FSF. Machines with a three-phase power supply, fitted with EMC filters, must not be connected to a supply via an ELCB (Earth Leakage Circuit-Breaker - see DIN VDE 0160, section 5.5.2 and EN50178 section 5.2.11.1).
The following terminals can carry dangerous voltages even if the inverter is inoperative: ♦ the power supply L/L1, N/L2, L3 resp. U1/L1, V1/L2, W1/L3 ♦ the motor terminals U, V, W resp. U2, V2, W2 ♦ and depending on the frame size the terminals DC+/B+, DC-, B-, DC/R+
resp. DCPS, DCNS, DCPA, DCNA This equipment must not be used as an ‘emergency stop mechanism’ (see EN
60204, 9.2.5.4)
CAUTION The connection of power, motor and control cables to the inverter must be carried out as shown in Fig. 2-11 on page 44, to prevent inductive and capacitive interference from affecting the correct functioning of the inverter.
Issue 10/06 Safety Instructions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 9
Operation
WARNING MICROMASTERS operate at high voltages. When operating electrical devices, it is impossible to avoid applying
hazardous voltages to certain parts of the equipment. Emergency Stop facilities according to EN 60204 IEC 204 (VDE 0113) must
remain operative in all operating modes of the control equipment. Any disengagement of the Emergency Stop facility must not lead to uncontrolled or undefined restart. Certain parameter settings may cause the inverter to restart automatically after an input power failure (e.g. automatic restart).
Wherever faults occurring in the control equipment can lead to substantial material damage or even grievous bodily injury (i.e. potentially dangerous faults), additional external precautions must be taken or facilities provided to ensure or enforce safe operation, even when a fault occurs (e.g. independent limit switches, mechanical interlocks, etc.).
Motor parameters must be accurately configured for motor overload protection to operate correctly.
This equipment is capable of providing internal motor overload protection in accordance with UL508C section 42. Refer to P0610 and P0335, i2t is ON by default. Motor overload protection can also be provided using an external PTC or KTY84.
This equipment is suitable for use in a circuit capable of delivering not more than 10,000 (Frame Sizes A to C) or 42,000 (Frame Sizes D to GX) symmetrical amperes (rms), for a maximum voltage of 230 V / 460 V / 575 V when protected by an H, J or K type fuse, a circuit breaker or self-protected combination motor controller (for more details see Appendix F).
This equipment must not be used as an ‘emergency stop mechanism’ (see EN 60204, 9.2.5.4)
Repair
WARNING Repairs on equipment may only be carried out by Siemens Service, by repair
centers authorized by Siemens or by authorized personnel who are thoroughly acquainted with all the warnings and operating procedures contained in this manual.
Any defective parts or components must be replaced using parts contained in the relevant spare parts list.
Disconnect the power supply before opening the equipment for access.
Dismantling & Disposal
CAUTION The inverter’s packaging is re-usable. Retain the packaging for future use. Easy-to-release screw and snap connectors allow you to break the unit down
into its component parts. You can then re-cycle these component parts, dispose of them in accordance with local requirements or return them to the manufacturer.
Electrostatic Sensitive Devices (ESD) Issue 10/06
MICROMASTER 440 Operating Instructions 10 6SE6400-5AW00-0BP0
Electrostatic Sensitive Devices (ESD)
The device contains components which can be destroyed by electrostatic discharge. These components can be easily destroyed if not carefully handled. Before opening the cabinet/enclosure in which the device is located, you must electrically discharge your body and apply the appropriate ESDS protective measures. The cabinet/enclosure should be appropriately labeled.
If you have to handle electronic boards, please observe the following:
• Electronic boards should only be touched when absolutely necessary.
• The human body must be electrically discharged before touching an electronic board.
• Boards must not come into contact with highly insulating materials - e.g. plastic parts, insulated desktops, articles of clothing manufactured from man-made fibers.
• Boards must only be placed on conductive surfaces.
• Boards and components should only be stored and transported in conductive packaging (e.g. metalized plastic boxes or metal containers).
• If the packing material is not conductive, the boards must be wrapped with a conductive packaging material, e.g. conductive foam rubber or household aluminium foil.
The necessary ESD protective measures are clearly shown again in the following diagram: • a = Conductive floor surface • b = ESD table • c = ESD shoes
• d = ESD overall • e = ESD chain • f = Cubicle ground connection
Sitting
a
b
e
d
c
d
ac
db
c a
e
ff f f f
Standing Standing / Sitting
Issue 10/06 Table of Contents
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 11
Table of Contents
1 Overview ................................................................................................................ 17 1.1 The MICROMASTER 440....................................................................................... 18 1.2 Features.................................................................................................................. 19
2 Installation ............................................................................................................. 21 2.1 Installation after a Period of Storage ...................................................................... 23 2.2 Ambient operating conditions ................................................................................. 24 2.3 Mechanical installation............................................................................................ 26 2.4 Electrical installation ............................................................................................... 33
3 Functions............................................................................................................... 47 3.1 Parameters ............................................................................................................. 51 3.2 Operator panels for MICROMASTER..................................................................... 70 3.3 Block diagram ......................................................................................................... 74 3.4 Factory setting ........................................................................................................ 75 3.5 Commissioning ....................................................................................................... 77 3.6 Inputs / outputs ..................................................................................................... 135 3.7 Communications ................................................................................................... 144 3.8 Fixed frequencies (FF).......................................................................................... 167 3.9 Motorized potentiometer (MOP) ........................................................................... 170 3.10 JOG....................................................................................................................... 172 3.11 PID controller (technological controller)................................................................ 173 3.12 Setpoint channel ................................................................................................... 181 3.13 Free function blocks (FFB) ................................................................................... 191 3.14 Motor holding brake (MHB)................................................................................... 196 3.15 Electronic brakes .................................................................................................. 202 3.16 Automatic restart................................................................................................... 211 3.17 Flying restart ......................................................................................................... 213 3.18 Closed-loop Vdc control........................................................................................ 215 3.19 Positioning down ramp ......................................................................................... 219 3.20 Monitoring functions / messages .......................................................................... 221 3.21 Thermal motor protection and overload responses .............................................. 227 3.22 Power module protection ...................................................................................... 232 3.23 Open-loop/closed-loop control technique ............................................................. 235
4 Troubleshooting.................................................................................................. 257 4.1 Troubleshooting with the SDP .............................................................................. 258 4.2 Troubleshooting with the BOP.............................................................................. 259
Table of Contents Issue 10/06
MICROMASTER 440 Operating Instructions 12 6SE6400-5AW00-0BP0
4.3 Fault messages..................................................................................................... 260 4.4 Alarm Messages ................................................................................................... 260
5 MICROMASTER 440 specifications................................................................... 261
6 Options ................................................................................................................ 273 6.1 Inverter-independent options ................................................................................ 273 6.2 Inverter-dependent options................................................................................... 274
7 Electro-magnetic compatibility (EMC).............................................................. 275 7.1 Electro-magnetic compatibility .............................................................................. 276
Appendices .............................................................................................................................. 281
A Changing the Operator Panel ............................................................................ 281
B Removing Front Covers ..................................................................................... 282 B.1 Removing Front Covers. Frame Sizes A .............................................................. 282 B.2 Removing Front Covers. Frame Sizes B and C ................................................... 283 B.3 Removing Front Covers. Frame Sizes D and E ................................................... 284 B.4 Removing Front Covers. Frame Size F ................................................................ 285 B.5 Removing Front Covers. Frame Sizes FX and GX.............................................. 286
C Removing the I/O Board..................................................................................... 287
D Removing ‘Y’ Cap ............................................................................................... 288 D.1 Removing ‘Y’ Cap. Frame Size A ......................................................................... 288 D.2 Removing ‘Y’ Cap. Frame Sizes B and C............................................................. 289 D.3 Removing ‘Y’ Cap. Frame Sizes D and E............................................................. 290 D.4 Removing ‘Y’ Cap. Frame Size F ......................................................................... 291 D.5 Removing ‘Y’ Cap. Frame Size FX....................................................................... 292 D.6 Removing ‘Y’ Cap. Frame Size GX ...................................................................... 293
E Removing fan ...................................................................................................... 294 E.1 Removing fan. Frame Size A................................................................................ 294 E.2 Removing fan. Frame Sizes B and C ................................................................... 295 E.3 Removing fan. Frame Size D and E ..................................................................... 296 E.4 Removing fan. Frame Size F ................................................................................ 297 E.5 Removing fan. Frame Size F with filter................................................................. 298 E.6 Removing fan. Frame Sizes FX and GX .............................................................. 299
F Short circuit current rating (SCCR)................................................................... 300
G Standards ............................................................................................................ 301
H List of Abbreviations .......................................................................................... 302
Index .............................................................................................................................. 305
Issue 10/06 Table of Contents
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 13
List of Illustrations Fig. 2-1 Forming ................................................................................................................................ 23 Fig. 2-2 Ambient operating temperature ............................................................................................ 24 Fig. 2-3 Installation altitude................................................................................................................ 24 Fig. 2-4 Drill pattern for MICROMASTER 440 ................................................................................... 27 Fig. 2-5 Installation dimensions for MICROMASTER 440 Frame size FX ......................................... 28 Fig. 2-6 Installation dimensions for MICROMASTER 440 Frame size GX ........................................ 29 Fig. 2-7 Options for the electronic box............................................................................................... 32 Fig. 2-8 MICROMASTER 440 Connection Terminals........................................................................ 37 Fig. 2-9 MICROMASTER 440 connection drawing – frame size FX.................................................. 38 Fig. 2-10 MICROMASTER 440 connection drawing - frame size GX.................................................. 39 Fig. 2-11 Motor and Power Connections ............................................................................................. 40 Fig. 2-12 Adaptation of fan voltage...................................................................................................... 41 Fig. 2-13 Control terminals of MICROMASTER 440............................................................................ 42 Fig. 2-14 Wiring Guidelines to Minimize the Effects of EMI ................................................................. 44 Fig. 3-1 Parameter types ................................................................................................................... 51 Fig. 3-2 Header line for parameter P0305 ......................................................................................... 55 Fig. 3-3 Parameter grouping / access................................................................................................ 56 Fig. 3-4 Binectors .............................................................................................................................. 60 Fig. 3-5 Connectors ........................................................................................................................... 61 Fig. 3-6 BICO connections (examples).............................................................................................. 62 Fig. 3-7 Example: Changeover from motor 1 to motor 2.................................................................... 63 Fig. 3-8 Example: Changing-over between the control and setpoint (frequency) source................... 63 Fig. 3-9 Copying from CDS ............................................................................................................... 65 Fig. 3-10 Changing-over CDS ............................................................................................................. 65 Fig. 3-11 Copying from DDS ............................................................................................................... 66 Fig. 3-12 Changing-over DDS ............................................................................................................. 67 Fig. 3-13 Normalization / de-normalization .......................................................................................... 69 Fig. 3-14 Operator panels.................................................................................................................... 70 Fig. 3-15 Operator panel keys ............................................................................................................. 72 Fig. 3-16 Changing parameters using the BOP................................................................................... 73 Fig. 3-17 MICROMASTER 440 – block diagram ................................................................................. 74 Fig. 3-18 Status Display Panel (SDP).................................................................................................. 75 Fig. 3-19 Recommended wiring for the factory setting ........................................................................ 76 Fig. 3-20 Procedure when commissioning........................................................................................... 77 Fig. 3-21 DIP switch to change-over between 50/60 Hz...................................................................... 79 Fig. 3-22 Mode of operation of the DIP50/60 switch in conjunction with P0100 .................................. 79 Fig. 3-23 Motor terminal box................................................................................................................ 80 Fig. 3-24 Star / delta circuit configurations .......................................................................................... 81 Fig. 3-25 V/f characteristic................................................................................................................... 82 Fig. 3-26 Equivalent circuit diagram (ECD) ......................................................................................... 91 Fig. 3-27 Magnetizing characteristic .................................................................................................... 92 Fig. 3-28 Upread / download using AOP and PC Tools..................................................................... 132 Fig. 3-29 Digital inputs....................................................................................................................... 135 Fig. 3-30 Digital outputs..................................................................................................................... 138 Fig. 3-31 DIP switch and P0756 for ADC current / voltage input ....................................................... 140
Table of Contents Issue 10/06
MICROMASTER 440 Operating Instructions 14 6SE6400-5AW00-0BP0
Fig. 3-32 Connection example for ADC voltage / current input.......................................................... 141 Fig. 3-33 ADC channel ...................................................................................................................... 141 Fig. 3-34 Signal output through the D/A converter channel ............................................................... 142 Fig. 3-35 D/A converter channel ........................................................................................................ 142 Fig. 3-36 Serial communication interfaces - BOP link and COM link ................................................. 144 Fig. 3-37 Cycle times......................................................................................................................... 147 Fig. 3-38 Serial linking of MICROMASTER (slaves) with a higher-level computer (master).............. 148 Fig. 3-39 Telegram structure ............................................................................................................. 149 Fig. 3-40 Assignment of the address byte (ADR) .............................................................................. 150 Fig. 3-41 Circulating list (Example of configuration) .......................................................................... 151 Fig. 3-42 Cycle time........................................................................................................................... 151 Fig. 3-43 Transmit sequence............................................................................................................. 152 Fig. 3-44 USS bus topology............................................................................................................... 153 Fig. 3-45 Telegram structure ............................................................................................................. 155 Fig. 3-46 Structure of the PKW and PZD areas................................................................................. 155 Fig. 3-47 Connecting the USS bus cable........................................................................................... 164 Fig. 3-48 Connecting the RS485 terminator ...................................................................................... 165 Fig. 3-49 Example for directly selecting FF1 via DIN1 and FF2 via DIN2.......................................... 168 Fig. 3-50 Example for selecting FF1 via DIN1 and FF2 via DIN2 using the binary-coded method .... 169 Fig. 3-51 Motorized potentiometer..................................................................................................... 170 Fig. 3-52 JOG counter-clockwise and JOG clockwise ....................................................................... 172 Fig. 3-53 Structure of the technology controller ................................................................................. 174 Fig. 3-54 Structure of the technological controller (PID controller) .................................................... 175 Fig. 3-55 PID controller...................................................................................................................... 176 Fig. 3-56 Example to directly select the PID fixed frequency of fixed frequency 1 via DIN1.............. 178 Fig. 3-57 PID dancer roll control ........................................................................................................ 179 Fig. 3-58 Structure of the closed-loop PID-dancer roll control ........................................................... 180 Fig. 3-59 Setpoint channel................................................................................................................. 181 Fig. 3-60 Summation ......................................................................................................................... 182 Fig. 3-61 Modifying the frequency setpoint ........................................................................................ 182 Fig. 3-62 Ramp-function generator.................................................................................................... 183 Fig. 3-63 Rounding off after an OFF1 command ............................................................................... 184 Fig. 3-64 OFF1 .................................................................................................................................. 186 Fig. 3-65 OFF2 .................................................................................................................................. 187 Fig. 3-66 OFF3 .................................................................................................................................. 188 Fig. 3-67 Changing-over using the BICO parameters P0810 and P0811 .......................................... 189 Fig. 3-68 Motor holding brake after ON / OFF1 ................................................................................. 196 Fig. 3-69 Motor holding brake after OFF2 ......................................................................................... 197 Fig. 3-70 Direct motor holding brake connection ............................................................................... 200 Fig. 3-71 Indirect motor holding brake connection............................................................................. 201 Fig. 3-72 Inter-dependency of the electronic brakes.......................................................................... 202 Fig. 3-73 DC braking after OFF1 / OFF3 ........................................................................................... 203 Fig. 3-74 DC braking after external selection .................................................................................... 204 Fig. 3-75 Compound braking ............................................................................................................. 205 Fig. 3-76 Connecting the chopper (braking) resistor.......................................................................... 207 Fig. 3-77 Mode of operation of the dynamic braking.......................................................................... 207
Issue 10/06 Table of Contents
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 15
Fig. 3-78 Load duty cycle – chopper resistors (MICROMASTER Catalog DA51.2)........................... 208 Fig. 3-79 Increasing the level of braking energy which can be absorbed .......................................... 209 Fig. 3-80 Chopper load duty cycle ..................................................................................................... 209 Fig. 3-81 Automatic restarts .............................................................................................................. 211 Fig. 3-82 Flying restart....................................................................................................................... 214 Fig. 3-83 Vdc_max controller............................................................................................................. 216 Fig. 3-84 Kinetic buffering (Vdc_min controller)................................................................................. 218 Fig. 3-85 Positioning down ramp ....................................................................................................... 219 Fig. 3-86 Rotary or linear axis............................................................................................................ 220 Fig. 3-87 Shaft drive with flat belts..................................................................................................... 223 Fig. 3-88 Load torque monitoring (P2181 = 1)................................................................................... 223 Fig. 3-89 Frequency/torque tolerance bandwidth .............................................................................. 224 Fig. 3-90 Load torque characteristic with minimum permissible load................................................. 225 Fig. 3-91 Load torque characteristic with maximum permissible load................................................ 225 Fig. 3-92 Load torque characteristic with minimum and maximum permissible load ......................... 226 Fig. 3-93 Thermal motor protection ................................................................................................... 228 Fig. 3-94 Connecting a temperature sensor to MICROMASTER....................................................... 230 Fig. 3-95 PTC characteristic for 1LG / 1LA motors ........................................................................... 231 Fig. 3-96 KTY84 characteristic for 1LG / 1LA motors ........................................................................ 231 Fig. 3-97 Operating ranges and characteristics of an induction motor when fed from a drive inverter236 Fig. 3-98 Slip compensation .............................................................................................................. 239 Fig. 3-99 Effect of V/f resonance damping ........................................................................................ 240 Fig. 3-100 Imax controller.................................................................................................................... 242 Fig. 3-101 Current Vector diagram in a steady-state condition............................................................ 243 Fig. 3-102 Changeover condition for SLVC ......................................................................................... 245 Fig. 3-103 Starting and passing-through 0 Hz in closed-loop controlled operation.............................. 246 Fig. 3-104 P0400 and DIP switch on the pulse encoder module ......................................................... 247 Fig. 3-105 Speed controller ................................................................................................................. 248 Fig. 3-106 Speed controller with pre-control........................................................................................ 250 Fig. 3-107 Speed controller with droop................................................................................................ 252 Fig. 3-108 Closed-loop speed/torque control....................................................................................... 253 Fig. 3-109 Torque limits....................................................................................................................... 255
List of Tables Table 2-1 Dimensions and Torques of MICROMASTER 440............................................................... 30 Table 3-1 Parameter attributes............................................................................................................. 52 Table 3-2 Parameter P0700 ................................................................................................................. 57 Table 3-3 Parameter P1000 ................................................................................................................. 58 Table 3-4 Parameter P0719 ................................................................................................................. 59 Table 3-5 Normalized interfaces........................................................................................................... 68 Table 3-6 Normalization functions ........................................................................................................ 68 Table 3-7 Pre-assignment of the digital inputs ..................................................................................... 75 Table 3-8 Example 1LA7060-4AB10 .................................................................................................... 82 Table 3-9 Possible settings for parameter P0340................................................................................. 88 Table 3-10 Calculated parameters ......................................................................................................... 89 Table 3-11 Parameters P0701 – P0706 ............................................................................................... 136
Table of Contents Issue 10/06
MICROMASTER 440 Operating Instructions 16 6SE6400-5AW00-0BP0
Table 3-12 Parameters P0731 – P0733 (frequently used functions / states)........................................ 138 Table 3-13 BOP link ............................................................................................................................. 145 Table 3-14 COM link............................................................................................................................. 145 Table 3-15 Minimum start intervals for various baud rates ................................................................... 152 Table 3-16 Structural data .................................................................................................................... 153 Table 3-17 Thermal and electrical characteristics ................................................................................ 154 Table 3-18 Max. number of nodes (devices) depending on the max. data transfer rate....................... 154 Table 3-19 Task IDs (master -> drive converter) .................................................................................. 158 Table 3-20 Response ID (converter -> master) .................................................................................... 159 Table 3-21 Fault numbers for the response ID "Request cannot be executed" .................................... 160 Table 3-22 Example for direct coding via digital inputs......................................................................... 167 Table 3-23 Example for binary coding via digital inputs........................................................................ 168 Table 3-24 Mode of operation of the MOP ........................................................................................... 171 Table 3-25 Selecting the motorized potentiometer ............................................................................... 171 Table 3-26 Correspondence between the parameters ......................................................................... 177 Table 3-27 Important parameters for the PID dancer roll control.......................................................... 180 Table 3-28 BICO parameters for ramp-function generator ................................................................... 185 Table 3-29 Examples for settings of parameter P0810......................................................................... 190 Table 3-30 Possible settings for parameters P0700 and P1000........................................................... 190 Table 3-31 Free function blocks ........................................................................................................... 191 Table 3-32 FFB priority table ................................................................................................................ 194 Table 3-33 Settings for parameter P1200............................................................................................. 213 Table 3-34 DC link undervoltage – shutdown threshold ....................................................................... 219 Table 3-35 Partial excerpt of monitoring functions / messages ............................................................ 222 Table 3-36 Thermal classes ................................................................................................................. 228 Table 3-37 General protection of the power components..................................................................... 232 Table 3-38 V/f characteristic (parameter P1300) .................................................................................. 236 Table 3-39 Voltage boost ..................................................................................................................... 238 Table 3-40 Vector control versions ....................................................................................................... 244 Table 4-1 Inverter conditions indicated by the LEDs on the SDP ....................................................... 258 Table 5-1 MICROMASTER 440 Performance Ratings ....................................................................... 262 Table 5-2 Dimensions, required cooling air flow and tightening torques for power terminals ............. 264 Table 5-3 Current reduction depending on pulse frequency............................................................... 265 Table 5-4 Data for braking resistors ................................................................................................... 266 Table 5-5 MICROMASTER 440 Specifications .................................................................................. 266 Table 7-1 Permissible harmonic current emissions ............................................................................ 277 Table 7-2 General industrial application ............................................................................................. 278 Table 7-3 With filter, for industrial applications ................................................................................... 278 Table 7-4 With filter, for residential, commercial and trade applications............................................. 279 Table 7-5 Compliance Table .............................................................................................................. 280
Issue 10/06 1 Overview
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 17
1 Overview
This Chapter contains: A summary of the major features of the MICROMASTER 440 range.
1.1 The MICROMASTER 440....................................................................................... 18 1.2 Features.................................................................................................................. 19
1 Overview Issue 10/06
MICROMASTER 440 Operating Instructions 18 6SE6400-5AW00-0BP0
1.1 The MICROMASTER 440 The MICROMASTER 440 are frequency inverters for speed and torque control of three-phase motors. The various models available cover the performance range from 120 W to 200 kW (for constant torque (CT), alternatively up to 250kW (for variable torque (VT)).
The inverters are microprocessor-controlled and use state-of-the-art Insulated Gate BipoIar Transistor (IGBT) technology. This makes them reliable and versatile. A special pulse-width modulation method with selectable Pulse frequency permits quiet motor operation. Comprehensive protective functions provide excellent inverter and motor protection.
With the factory default settings, the MICROMASTER 440 is suitable for many variable speed applications. Using the functionally grouped parameters, the MICROMASTER 440 can adapted to more demanding applications.
The MICROMASTER 440 can be used in both 'stand-alone' applications as well as being integrated into 'Automation Systems'.
Issue 10/06 1 Overview
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 19
1.2 Features
Main Characteristics Easy installation Easy commissioning Rugged EMC design Can be operated on IT line supplies Fast repeatable response time to control signals Comprehensive range of parameters enabling configuration for a wide range of
applications Simple cable connection Output relays Analog outputs (0 – 20 mA) 6 Isolated and switchable NPN/PNP digital inputs 2 Analog inputs:
♦ ADC1: 0 – 10 V, 0 – 20 mA and -10 to +10 V ♦ ADC2: 0 – 10 V, 0 – 20 mA
The 2 analog inputs can be used as the 7th and 8th digital inputs BICO technology Modular design for extremely flexible configuration High switching frequencies (drive inverter specific up to 16 kHz) for low-noise
motor operation Internal RS485 interface (port) Detailed status information and integrated message functions
1 Overview Issue 10/06
MICROMASTER 440 Operating Instructions 20 6SE6400-5AW00-0BP0
Performance Characteristics Vector Control
♦ Sensorless Vector Control (SLVC) ♦ Vector Control with encoder (VC)
V/f Control ♦ Flux Current Control (FCC) for improved dynamic response and motor
control ♦ Multi-point V/f characteristic
Automatic restart Flying restart Slip compensation Fast Current Limitation (FCL) for trip-free operation Motor holding brake Built-in DC injection brake Compound braking to improve braking performance Built-in braking chopper (Frame Sizes A to F) for resistor braking (dynamic
braking) Setpoint input via:
♦ Analog inputs ♦ Communication interface ♦ JOG function ♦ Motorized potentiometer ♦ Fixed frequencies
Ramp function generator ♦ With smoothing ♦ Without smoothing
Technology controller (PID) Parameter set switch-over
♦ Motor data sets (DDS) ♦ Command data sets and setpoint sources (CDS)
Free Function Blocks DC link voltage controller Kinetic Buffering Positioning Ramp down
Protection characteristics Overvoltage/undervoltage protection Overtemperature protection for the inverter Ground fault protection Short-circuit protection i2t thermal motor protection PTC/KTY84 for motor protection
Options Refer to Chapter 5
Issue 10/06 2 Installation
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 21
2 Installation
This Chapter contains: General data relating to installation Dimensions of Inverter Wiring guidelines to minimize the effects of EMI Details concerning electrical installation
2.1 Installation after a Period of Storage ...................................................................... 23 2.2 Ambient operating conditions ................................................................................. 24 2.3 Mechanical installation............................................................................................ 26 2.4 Electrical installation ............................................................................................... 33
2 Installation Issue 10/06
MICROMASTER 440 Operating Instructions 22 6SE6400-5AW00-0BP0
WARNING Work on the device/system by unqualified personnel or failure to comply with
warnings can result in severe personal injury or serious damage to material. Only suitably qualified personnel trained in the setup, installation, commissioning and operation of the product should carry out work on the device/system.
Only permanently-wired input power connections are allowed. This equipment must be grounded (IEC 536 Class 1, NEC and other applicable standards).
Only type B ELCBs should be used with FSA to FSF. Machines with a three-phase power supply, fitted with EMC filters, must not be connected to a supply via an ELCB (Earth Leakage Circuit-Breaker - see DIN VDE 0160, section 5.5.2 and EN50178 section 5.2.11.1).
The following terminals can carry dangerous voltages even if the inverter is inoperative: ♦ the power supply L/L1, N/L2, L3 resp. U1/L1, V1/L2, W1/L3 ♦ the motor terminals U, V, W resp. U2, V2, W2 ♦ and depending on the frame size the terminals DC+/B+, DC-, B-, DC/R+
resp. DCPS, DCNS, DCPA, DCNA Always wait 5 minutes to allow the unit to discharge after switching off before
carrying out any installation work. This equipment must not be used as an ‘emergency stop mechanism’ (see EN
60204, 9.2.5.4) The minimum size of the earth-bonding conductor must be equal to or greater
than the cross-section of the power supply cables. If the front cover (Frame Sizes FX and GX) has been removed, the fan impeller
is exposed. There is danger of injury when the fan is running.
CAUTION The connection of power, motor and control cables to the inverter must be carried out as shown in Fig. 2-11 on page 44, to prevent inductive and capacitive interference from affecting the correct functioning of the inverter.
Issue 10/06 2 Installation
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 23
2.1 Installation after a Period of Storage Following a prolonged period of storage, you must reform the capacitors in the inverter.
Frame Sizes A to F
100
50
75
0,5 1
[%]
2 4 6 8
Storage period less than 1 year:
Storage period 1 to 2 years:
Storage period 2 to 3 years:
Storage period 3 and more years:
No action necessary
Prior to energizing, connect tovoltage for one hour
Prior to energizing, formaccording to the curvePrior to energizing, formaccording to the curve
Voltage
Time t [h]
Fig. 2-1 Forming
Frame Sizes FX and GX Reforming the capacitors can be accomplished by applying 85% of the rated input voltage for at least 30 minutes without load.
2 Installation Issue 10/06
MICROMASTER 440 Operating Instructions 24 6SE6400-5AW00-0BP0
2.2 Ambient operating conditions
Temperature
Frame Sizes A to F: Frame Sizes FX and GX:
0 20 3010 40 [°C]Ambient temperature
50 55
95
100[%]
Permissible output current
90
85
450 20 3010 40 [°C]Ambient temperature
-10 50 60
constant torquevariable torque
75
50
25
100[%]
Permissible output current
Fig. 2-2 Ambient operating temperature
Humidity Range Relative air humidity ≤ 95 % Non-condensing
Altitude If the inverter is to be installed at an altitude > 1000 m or > 2000 m above sea level, derating will be required:
Permissible output current
Installation altitude in m above sea level
Permissible input voltage
80
100
0 1000 2000 3000 4000
%
Installation altitude in m above sea level
77
85
100
0 1000 2000 3000 4000
%
80
Frame SizesFX and GX
Frame SizesA to F
Fig. 2-3 Installation altitude
Shock and Vibration Do not drop the inverter or expose to sudden shock. Do not install the inverter in an area where it is likely to be exposed to constant vibration. Mechanical strength to EN 60721-33
Deflection: 0.075 mm (10 ... 58 Hz) Acceleration: 9.8 m/s2 (> 58 ... 200 Hz)
Electromagnetic Radiation Do not install the inverter near sources of electromagnetic radiation.
Issue 10/06 2 Installation
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 25
Atmospheric Pollution Do not install the inverter in an environment, which contains atmospheric pollutants such as dust, corrosive gases, etc.
Water Take care to site the inverter away from potential water hazards, e.g. do not install the inverter beneath pipes that are subject to condensation. Avoid installing the inverter where excessive humidity and condensation may occur.
Installation and cooling
CAUTION The inverters MUST NOT be mounted horizontally.
The inverters can be mounted without any clearance at either side. When mounting inverters one above the other, the specified environmental conditions must not be exceeded. Independent of this, these minimum distances must be observed.
Frame Size A, B, C above and below 100 mm Frame Size D, E above and below 300 mm Frame Size F above and below 350 mm Frame Size FX, GX above 250 mm
below 150 mm in front 40 mm (FX), 50 mm (GX) No equipment that could have a negative effect on the flow of cooling air should be installed in this area. Make sure that the cooling vents in the inverter are positioned correctly to allow free movement of air.
2 Installation Issue 10/06
MICROMASTER 440 Operating Instructions 26 6SE6400-5AW00-0BP0
2.3 Mechanical installation
WARNING To ensure the safe operation of the equipment, it must be installed and
commissioned by qualified personnel in full compliance with the warnings laid down in these operating instructions.
Take particular note of the general and regional installation and safety regulations regarding work on dangerous voltage installations (e.g. EN 50178), as well as the relevant regulations regarding the correct use of tools and personal protective equipment (PPE).
The mains input, DC and motor terminals, can carry dangerous voltages even if the inverter is inoperative; wait 5 minutes to allow the unit to discharge after switching off before carrying out any installation work.
The inverters can be mounted without any clearance at either side. When mounting inverters one above the other, the specified environmental conditions must not be exceeded. Independent of this, these minimum distances must be observed. • Frame Size A, B, C above and below 100 mm • Frame Size D, E above and below 300 mm • Frame Size F above and below 350 mm • Frame Size FX, GX above 250 mm
below 150 mm in front 40 mm (FX), 50 mm (GX)
If the front cover (Frame Sizes FX and GX) has been removed, the fan impeller is exposed. There is danger of injury when the fan is running.
IP20 protection is only against direct contact, always use these products within a protective cabinet.
4
Removing from transport pallet (only for frame sizes FX and GX) During transport, the inverter is fastened on the transport pallet with the aid of two iron brackets.
WARNING Note that the center of gravity of the inverter is not in the middle of the unit. When lifting the pallet, the unit can therefore suddenly change position and swing to the side. 1. Fasten the hoisting crane cable to the hoisting eyes on the inverter (2 eyes,
see Fig. 2-9 and Fig. 2-10). 2. Remove the two retaining bolts at the top of the front cover. 3. Unscrew the bolts in the iron brackets on the transport pallet and lift the
inverter off the pallet. 4. Once installation has been completed and the inverter connected, fasten the
two retaining bolts for the front cover at the bottom side of the door.
Issue 10/06 2 Installation
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 27
Frame Sizes A to F
160 mm6.30"
55 mm2.2"
Ø 4.5 mm0.17"
Ø 4.8 mm0.19"
174 mm6.85"
138 mm5.43"
Ø 5.5 mm0.22"
204 mm8.03"
174 mm6.85"
Frame Size A
Frame Size D Frame Size E Frame Size F
Frame Size B Frame Size C
Ø 17.5 mm0.68"
486 mm19.13"
235 mm9.25"
616.4 mm24.27"
810 mm31.89"
withfilter
1110 mm43.70"
Ø 17.5 mm0.68" Ø 15 mm
0.59"
235 mm9.25"
300 mm11.81"
Fig. 2-4 Drill pattern for MICROMASTER 440
2 Installation Issue 10/06
MICROMASTER 440 Operating Instructions 28 6SE6400-5AW00-0BP0
Frame Size FX
Fig. 2-5 Installation dimensions for MICROMASTER 440 Frame size FX
Issue 10/06 2 Installation
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 29
Frame Size GX
Fig. 2-6 Installation dimensions for MICROMASTER 440 Frame size GX
2 Installation Issue 10/06
MICROMASTER 440 Operating Instructions 30 6SE6400-5AW00-0BP0
Table 2-1 Dimensions and Torques of MICROMASTER 440
Frame-Size Overall Dimensions Fixing Method Tightening Torque mm 73 x 173 x 149
A Width x Height x Depth inch 2,87 x 6,81 x 5,87
2 M4 Bolts 4 M4 Nuts 4 M4 Washers or fitting on a standard rail
2,5 Nm with washers fitted
mm 149 x 202 x 172 B
Width x Height x Depth inch 5,87 x 7,95 x 6,77
4 M4 Bolts 4 M4 Nuts 4 M4 Washers
2,5 Nm with washers fitted
mm 185 x 245 x 195 C
Width x Height x Depth inch 7,28 x 9,65 x 7,68
4 M5 Bolts 4 M5 Nuts 4 M5 Washers
2,5 Nm with washers fitted
mm 275 x 520 x 245 D
Width x Height x Depth inch 10,82 x 20,47 x 9,65
4 M8 Bolts 4 M8 Nuts 4 M8 Washers
3,0 Nm with washers fitted
mm 275 x 650 x 245 E
Width x Height x Depth inch 10,82 x 25,59 x 9,65
4 M8 Bolts 4 M8 Nuts 4 M8 Washers
3,0 Nm with washers fitted
mm 350 x 850 mm x 320 height with filter 1150
F Width x Height x Depth inch 13,78 x 33,46 x 12,60
height with filter 45,28
4 M8 Bolts 4 M8 Nuts 4 M8 Washers
3,0 Nm with washers fitted
mm 326 x 1400 x 356 FX
Width x Height x Depth inch 12,80 x 55,12 x 12,83
6 M8 Bolts 6 M8 Nuts 6 M8 Washers
13 Nm +30 % with washers fitted
mm 326 x 1533 x 545 GX
Width x Height x Depth inch 12,80 x 60,35 x 21,46
6 M8 Bolts 6 M8 Nuts 6 M8 Washers
13 Nm +30 % with washers fitted
Issue 10/06 2 Installation
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 31
2.3.1 Mounting onto standard rail, Frame Size A
Mounting the inverter onto a 35 mm standard rail (EN 50022) 1. Locate the inverter on the mounting rail using
the upper rail latch
2. Using a flat blade screwdriver, press the release mechanism downwards and engage the inverter into the lower rail latch.
Removing the Inverter from the rail 1. To disengaged the release mechanism of the inverter, insert a screwdriver into
the release mechanism. 2. Apply a downward pressure and the lower rail latch will disengage. 3. Pull the inverter from the rail.
Upperrail latch
Lowerrail latch
Release Mechanism
2 Installation Issue 10/06
MICROMASTER 440 Operating Instructions 32 6SE6400-5AW00-0BP0
2.3.2 Installing communication options and/or pulse encoder evaluation module
Sizes A to F NOTE When installing the following options – PROFIBUS module, DeviceNet module, CANopen option module and/or pulses encoder evaluation module, the mounting depth of the drive inverter is increased! Please refer to the relevant Operating Instructions for the actual procedure.
Sizes FX and GX The front cover of the MICROMASTER 440 is designed so that the control module (normally the SDP) is almost flush with the opening in the front cover. If more than one option is to be installed in the electronic box, it is necessary to position the entire electronic box further to the rear
Installing the options
Remove the front cover: • Unscrew two screws at the bottom side of the front cover. • Lift front cover up and out.
Remove retaining screws on the electronic box. Screw on electronic box in correct installation position as shown in Fig. 2-7 Install additional options. Reinstall front cover.
Installation position 2
Installation position 2
Installation position 1
Installation position 1
Standard installation
Standard installation
Fig. 2-7 Options for the electronic box
Issue 10/06 2 Installation
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 33
2.4 Electrical installation
WARNING The inverter must always be grounded.
To ensure the safe operation of the equipment, it must be installed and commissioned by qualified personnel in full compliance with the warnings laid down in these operating instructions.
Take particular note of the general and regional installation and safety regulations regarding work on dangerous voltage installations (e.g. EN 50178), as well as the relevant regulations regarding the correct use of tools and personal protective gear.
Never use high voltage insulation test equipment on cables connected to the inverter.
The mains input, DC and motor terminals, can carry dangerous voltages even if the inverter is inoperative; wait 5 minutes to allow the unit to discharge after switching off before carrying out any installation work.
If the front cover (Frame Sizes FX and GX) has been removed, the fan impeller is exposed. There is danger of injury when the fan is running.
CAUTION The control, power supply and motor leads must be laid separately. Do not feed them through the same cable conduit/trunking.
2 Installation Issue 10/06
MICROMASTER 440 Operating Instructions 34 6SE6400-5AW00-0BP0
2.4.1 General
WARNING The inverter must always be grounded. If the inverter is not grounded correctly, extremely dangerous conditions may arise within the inverter which could prove potentially fatal.
Operation with ungrounded (IT) supplies Filtered The use of filtered MICROMASTER 4 drives on unearthed mains supplies is not permitted. Unfiltered In the case of non-grounded networks, the 'Y' capacitor of the device must be made ineffective. The procedure is described in Appendix D. If the MICROMASTER is to remain in operation in non-grounded networks when a ground fault occurs during the input or output phase, an output reactor must be installed.
Operation with Residual Current Device (Frame Sizes A to F) If an RCD (also referred to as ELCB or RCCB) is fitted, the MICROMASTER inverters will operate without nuisance tripping, provided that:
A type B RCD is used. The trip limit of the RCD is 300 mA. The neutral of the supply is grounded. Only one inverter is supplied from each RCD. The output cables are less than 50 m (screened) or 100 m (unscreened).
NOTE The residual current operated circuit-breakers used must provide protection against direct-current components in the fault current and must be suitable for briefly suppressing power pulse current peaks. It is recommended to protect the frequency inverter by fuse separately. The regulations of the individual country (e.g. VDE regulations in Germany) and the regional power suppliers must be observed!
Issue 10/06 2 Installation
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 35
2.4.2 Power and motor connections
WARNING The inverter must always be grounded. ♦ Isolate the mains electrical supply before making or changing connections to
the unit. ♦ Ensure that the inverter is configured for the correct supply voltage:
MICROMASTERS must not be connected to a higher voltage supply. ♦ When synchronous motors are connected or when coupling several motors in
parallel, the inverter must be operated with V/f control characteristic (P1300 = 0, 2 or 3).
CAUTION After connecting the power and motor cables to the proper terminals, make sure that the front covers have been replaced properly before supplying power to the unit!
NOTICE ♦ Ensure that the appropriate circuit-breakers/fuses with the specified current
rating are connected between the power supply and inverter (see chapter 5, Tables 5-5).
♦ Use Class 1 60/75 oC copper wire only (for UL compliance). For tightening torque see Table 5-2.
Operation with long cables All inverters will operate at full specification with cable lengths as follows:
Frame Sizes A to F FX and GX screened 50 m 100 m unscreened 100 m 150 m
Using the output chokes specified in catalogue DA 51.2, the following cable lengths are possible for the appropriate frame sizes:
Supply Voltage 200 V … 240 V ± 10%
380 V … 400 V ± 10 % 401 V … 480 V ± 10 % 500 V … 600 V ± 10%
Frame Sizes A … F A … B C D … F FX, GX A … C D … F FX, GX C D … Fscreened 200 m 150 m 200 m 200 m 300 m 100 m 200 m 300 m 100 m 200 m unscreened 300 m 225 m 300 m 300 m 450 m 150 m 300 m 450 m 150 m 300 m
CAUTION If using output chokes operation is only permissible with a pulse frequency of 4 kHz. Make shure that the automatic pulse frequency reductions are disabled. Coercing required parameter adjusting: P1800 = 4 kHz , P0290 = 0 or 1.
2 Installation Issue 10/06
MICROMASTER 440 Operating Instructions 36 6SE6400-5AW00-0BP0
Access to the power and motor terminals Access to the power supply and motor terminals is possible by removing the front covers (See Fig. 2-8 to Fig. 2-10). See also Appendix B. After removing the front covers and exposing the terminals, complete power and motor connections as shown in Fig. 2-11.
Connection of braking unit (only for framesize FX and GX) A passage opening for access to the intermediate circuit connections has been provided on the top side of the inverter. It is possible to connect an external braking unit (refer to Catalog DA65.11 or DA65.10) to these terminals. The position is shown in Fig. 2-9 and Fig. 2-10. The maximum cross section of connections is 50 mm², but only provided the crimped area of cable shoes on the equipment side is provided with a heat-shrinkable sleeve. This measure is important to ensure that air gaps and creep distances are observed.
Issue 10/06 2 Installation
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 37
Fig. 2-8 MICROMASTER 440 Connection Terminals
2 Installation Issue 10/06
MICROMASTER 440 Operating Instructions 38 6SE6400-5AW00-0BP0
Shield connectionMains cable PE
Hoisting eyes
Mains cablePhase U1/L1, V1/L2, W1/L3
Top adjustment rail
Bottom adjustment rail
Status Display Panel
Shield connectioncontrol leads
Transformer adaptionMotor cable
Phase U2, V2, W2Motor cable
PE Shield connection
Fan screws
Bottom retaining screw
Elektronic box
Top retaining screw
Connection toY-Capacitor
Fan fuses
Cable opening for mains conection
U1/L1, V1/L2, W1/L3
Fan
Cable opening DCPA, DCNAfor connection of anexternal braking unit
Connection DCPA, DCNAfor external braking unit
Connection for dv/dt filterDCPS, DCNS
Fig. 2-9 MICROMASTER 440 connection drawing – frame size FX
Issue 10/06 2 Installation
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 39
Cable opening formains conection
U1/L1, V1/L2, W1/L3
Shield connectionMains cable PE
Hoisting eyes
Cable opening DCPA, DCNAfor connection of anexternal braking unit
Mains cablePhase U1/L1, V1/L2, W1/L3
Top adjustment rail
Bottom adjustment rail
Status Display Panel
Shield connectioncontrol leads
Transformer adaptionMotor cable
Phase U2, V2, W2
Motor cable PE Shield connection
Fan screws
Bottom retaining screw
Elektronic box
Top retaining screw
Connection toY-Capacitor
Connection DCPA, DCNAfor external braking unit
Fan fuses
Fan
Connection for dv/dt filterDCPS, DCNS
Fig. 2-10 MICROMASTER 440 connection drawing - frame size GX
2 Installation Issue 10/06
MICROMASTER 440 Operating Instructions 40 6SE6400-5AW00-0BP0
Frame Sizes A to F
L2L1N
FuseContactor
OptionalFilter
PE
Optionalline choke MICROMASTER 1)
PE
L/L1
N/L2
U
V
W
Motor
L3 Single Phase
PE
L3L2L1
FuseContactor
OptionalFilter
PE
Optionalline choke MICROMASTER 1)
PE
L3
L2
L1
U
V
W
Motor
Three Phase
PE
1) with and without filter
Frame Sizes FX and GX
L3L2L1
FuseContactor
OptionalFilter
PE
Optionalline choke MICROMASTER
PE
L3
L2
L1
U
V
W
Motor
3)
2)
2) without filter 3) the commutation choke is to be earthed using the designated earthing point
Fig. 2-11 Motor and Power Connections
Issue 10/06 2 Installation
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 41
Adaptation of fan voltage (only for frame size FX and GX) A transformer is installed to adapt the existing line voltage to the fan voltage. It may be necessary to reconnect the transformer terminals on the primary side to coincide with the existing line power.
Connect according input voltage
0V 1L380V 1L400V 1L440V 1L480V -
Fig. 2-12 Adaptation of fan voltage
CAUTION If the terminals are not reconnected to the actually present line voltage, the fan fuses can blow.
Replacement for fan fuses Frame size Fuses (2 each) Recommended fuses FX (90 kW CT) 1 A / 600 V / slow-acting Cooper-Bussmann FNQ-R-1, 600 V
or comparable fuse
FX (110 kW CT) 2,5 A / 600 V / slow-acting Ferraz Gould Shawmut ATDR2-1/2, 600 V or comparable fuse
GX (132-200 kW CT) 4 A / 600 V / slow-acting Ferraz Gould Shawmut ATDR4, 600 V or comparable fuse
2 Installation Issue 10/06
MICROMASTER 440 Operating Instructions 42 6SE6400-5AW00-0BP0
2.4.3 Control terminals
Permitted cable diameters: 0.08 … 2.5 mm2 (AWG: 28 … 12)
Terminal Designation Function 1 − Output +10 V
2 − Output 0 V
3 ADC1+ Analog input 1 (+)
4 ADC1- Analog input 1 (-)
5 DIN1 Digital input 1
6 DIN2 Digital input 2
7 DIN3 Digital input 3
8 DIN4 Digital input 4
9 − Isolated output +24 V / max. 100 mA
10 ADC2+ Analog input 2 (+)
11 ADC2- Analog input 2 (-)
12 DAC1+ Analog output 1 (+)
13 DAC1- Analog output 1 (-)
14 PTCA Connection for PTC / KTY84
15 PTCB Connection for PTC / KTY84
16 DIN5 Digital input 5
17 DIN6 Digital input 6
18 DOUT1/NC Digital output 1 / NC contact
19 DOUT1/NO Digital output 1 / NO contact
20 DOUT1/COM Digital output 1 / Changeover contact
21 DOUT2/NO Digital output 2 / NO contact
22 DOUT2/COM Digital output 2 / Changeover contact
23 DOUT3/NC Digital output 3 / NC contact
24 DOUT3/NO Digital output 3 / NO contact
25 DOUT3/COM Digital output 3 / Changeover contact
26 DAC2+ Analog output 2 (+)
27 DAC2- Analog output 2 (-)
28 − Isolated output 0 V / max. 100 mA
29 P+ RS485 port
30 N− RS485 port
Fig. 2-13 Control terminals of MICROMASTER 440
A detailed description of the inputs and outputs is provided in Section 3.6.
Issue 10/06 2 Installation
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 43
2.4.4 Avoiding Electro-Magnetic Interference (EMI)
The inverters are designed to operate in an industrial environment where a high level of EMI can be expected. Usually, good installation practices will ensure safe and trouble-free operation. If you encounter problems, follow the guidelines stated below.
Action to Take Ensure that all equipment in the cubicle is well grounded using short, thick
grounding cable connected to a common star point or busbar Make sure that any control equipment (such as a PLC) connected to the
inverter is connected to the same ground or star point as the inverter via a short thick link.
Connect the return ground from the motors controlled by the inverters directly to the ground connection (PE) on the associated inverter
Flat conductors are preferred as they have lower impedance at higher frequencies
Terminate the ends of the cable neatly, ensuring that unscreened wires are as short as possible
Separate the control cables from the power cables as much as possible, using separate trunking, if necessary at 90º to each other.
Whenever possible, use screened leads for the connections to the control circuitry
Ensure that the contactors in the cubicle are suppressed, either with R-C suppressors for AC contactors or 'flywheel' diodes for DC contactors fitted to the coils. Varistor suppressors are also effective. This is important when the contactors are controlled from the inverter relay
Use screened or armored cables for the motor connections and ground the screen at both ends using the cable clamps
WARNING Safety regulations must not be compromised when installing inverters!
2 Installation Issue 10/06
MICROMASTER 440 Operating Instructions 44 6SE6400-5AW00-0BP0
2.4.5 Screening Methods
Frame Sizes A, B and C For frame sizes A, B and C the Gland Plate Kit is supplied as an option. It allows easy and efficient connection of the necessary screening. See the Gland Plate Installation Instructions contained on the Document CD-ROM, supplied with the MICROMASTER 440.
Screening without a Gland Plate Should a Gland Plate not be available, then the inverter can be screened using the methodology shown in Fig. 2-14.
1 Mains power input 2 Control cable 3 Motor cable 4 Footprint filter 5 Metal back plate 6 Use suitable clips to fix motor and control cable screens securely to metal back plate 7 Screening cables
Fig. 2-14 Wiring Guidelines to Minimize the Effects of EMI
Issue 10/06 2 Installation
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 45
Frame Sizes D and E The Gland Plate is factory fitted. If the installation conditions are restricted, the shield of the motor cable can also be attached outside the cabinet, as shown in Fig. 2-14, for example.Frame Sizes FX and GX
Frame size F The gland plate for the control cables is factory-fitted. Devices without filter: The shield of the motor cable must be attached outside the
cabinet, as shown in Fig. 2-14, for example. Devices with filter: The gland plate for the motor cable is factory-fitted.
Frame Sizes FX and GX Connect the wire shields to the shield connection points shown in the connection drawing (see Fig. 2-9 and Fig. 2-10) . Twist the shields of the motor cables and screw them to the PE connection for the motor cable.
When using an EMI filter, a power commutating choke is required. The wire shields should be fastened to the metallic mounting surface as close as possible to the components.
2 Installation Issue 10/06
MICROMASTER 440 Operating Instructions 46 6SE6400-5AW00-0BP0
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 47
3 Functions
This Section includes the following: Explanation of the MICROMASTER 440 parameters An overview of the parameter structure of MICROMASTER 440 A description of the display and operator control elements and communications A block diagram of MICROMASTER 440 An overview of the various ways of commissioning the MICROMASTER 440 A description of the inputs and outputs Possibilities of controlling (open-loop and closed-loop) the MICROMASTER 440 A description of the various functions of the MICROMASTER 440 and their
implementation Explanation and information on the protective functions
3.1 Parameters ............................................................................................................. 51 3.1.1 Setting / monitoring parameters and parameter attributes ..................................... 51 3.1.2 Interconnecting signals (BICO technology) ............................................................ 57 3.1.2.1 Selecting the command source P0700 / selecting the setpoint source P1000....... 57 3.1.2.2 Selection of command/frequency setpoint P0719 .................................................. 59 3.1.2.3 BICO technology..................................................................................................... 60 3.1.3 Data sets................................................................................................................. 63 3.1.4 Reference quantities ............................................................................................... 68 3.2 Operator panels for MICROMASTER..................................................................... 70 3.2.1 Description of the BOP (Basic Operator Panel) ..................................................... 70 3.2.2 Description of the AOP (Advanced Operator Panel) .............................................. 71 3.2.3 Keys and their functions on the operator panel (BOP / AOP) ................................ 72 3.2.4 Changing parameters using the operator panel ..................................................... 73 3.3 Block diagram ......................................................................................................... 74 3.4 Factory setting ........................................................................................................ 75 3.5 Commissioning ....................................................................................................... 77 3.5.1 50/60 Hz setting ...................................................................................................... 79 3.5.2 Motor circuit ............................................................................................................ 80 3.5.3 Quick commissioning.............................................................................................. 83 3.5.4 Calculating the motor / control data ........................................................................ 88 3.5.5 Motor data identification.......................................................................................... 91 3.5.6 Magnetizing current ................................................................................................ 95 3.5.7 Commissioning the application ............................................................................... 97 3.5.7.1 Serial Interface (USS)............................................................................................. 97 3.5.7.2 Selection of command source ................................................................................ 98 3.5.7.3 Digital input (DIN).................................................................................................... 98 3.5.7.4 Digital output (DOUT) ............................................................................................. 99 3.5.7.5 Selection of frequency setpoint............................................................................. 100 3.5.7.6 Analog input (ADC)............................................................................................... 101
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 48 6SE6400-5AW00-0BP0
3.5.7.7 Analog output (DAC)............................................................................................. 102 3.5.7.8 Motor potentiometer (MOP) .................................................................................. 103 3.5.7.9 Fixed frequency (FF)............................................................................................. 104 3.5.7.10 JOG....................................................................................................................... 105 3.5.7.11 Ramp function generator (RFG) ........................................................................... 106 3.5.7.12 Reference/limit frequencies .................................................................................. 107 3.5.7.13 Inverter protection................................................................................................. 108 3.5.7.14 Motor protection .................................................................................................... 108 3.5.7.15 Encoder................................................................................................................. 110 3.5.7.16 V/f control.............................................................................................................. 111 3.5.7.17 Field-orientated control ......................................................................................... 113 3.5.7.18 Converter-specific Functions ................................................................................ 118 3.5.7.19 Command and drive data set................................................................................ 127 3.5.7.20 Diagnostic parameters.......................................................................................... 130 3.5.7.21 End of commissioning........................................................................................... 131 3.5.8 Series commissioning........................................................................................... 132 3.5.9 Parameter reset to the factory setting................................................................... 133 3.6 Inputs / outputs ..................................................................................................... 135 3.6.1 Digital inputs (DIN)................................................................................................ 135 3.6.2 Digital outputs (DOUT) ......................................................................................... 138 3.6.3 Analog inputs (ADC) ............................................................................................. 140 3.6.4 Analog outputs (D/A converter) ............................................................................ 142 3.7 Communications ................................................................................................... 144 3.7.1 Universal serial interface (USS)............................................................................ 146 3.7.1.1 Protocol specification and bus structure............................................................... 148 3.7.1.2 The structure of net data....................................................................................... 155 3.7.1.3 USS bus configuration via COM link (RS485) ...................................................... 164 3.8 Fixed frequencies (FF).......................................................................................... 167 3.9 Motorized potentiometer (MOP) ........................................................................... 170 3.10 JOG....................................................................................................................... 172 3.11 PID controller (technological controller)................................................................ 173 3.11.1 Closed-loop PID control ........................................................................................ 175 3.11.1.1 PID motorized potentiometer (PID-MOP) ............................................................. 177 3.11.1.2 PID fixed setpoint (PID-FF)................................................................................... 178 3.11.1.3 PID dancer roll control .......................................................................................... 179 3.12 Setpoint channel ................................................................................................... 181 3.12.1 Summation and modification of the frequency setpoint (AFM)............................. 181 3.12.2 Ramp-function generator (RFG) ........................................................................... 183 3.12.3 OFF/braking functions .......................................................................................... 186 3.12.4 Manual / automatic operation ............................................................................... 189 3.13 Free function blocks (FFB) ................................................................................... 191 3.14 Motor holding brake (MHB)................................................................................... 196 3.15 Electronic brakes .................................................................................................. 202 3.15.1 DC braking ............................................................................................................ 202 3.15.2 Compound braking................................................................................................ 205 3.15.3 Dynamic braking ................................................................................................... 206 3.16 Automatic restart................................................................................................... 211 3.17 Flying restart ......................................................................................................... 213
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 49
3.18 Closed-loop Vdc control........................................................................................ 215 3.18.1 Vdc_max controller ............................................................................................... 215 3.18.2 Kinetic buffering (Vdc_min controller)................................................................... 218 3.19 Positioning down ramp ......................................................................................... 219 3.20 Monitoring functions / messages .......................................................................... 221 3.20.1 General monitoring functions / messages ............................................................ 221 3.20.2 Load torque monitoring......................................................................................... 223 3.21 Thermal motor protection and overload responses .............................................. 227 3.21.1 Thermal motor model............................................................................................ 229 3.21.2 Temperature sensor.............................................................................................. 230 3.22 Power module protection ...................................................................................... 232 3.22.1 General overload monitoring ................................................................................ 232 3.22.2 Thermal monitoring functions and overload responses........................................ 233 3.23 Open-loop/closed-loop control technique ............................................................. 235 3.23.1 V/f control.............................................................................................................. 235 3.23.1.1 Voltage boost ........................................................................................................ 237 3.23.1.2 Slip compensation................................................................................................. 239 3.23.1.3 V/f resonance damping......................................................................................... 240 3.23.1.4 V/f open-loop control with flux current control (FCC)............................................ 241 3.23.1.5 Current limiting (Imax controller)........................................................................... 242 3.23.2 Vector control........................................................................................................ 243 3.23.2.1 Vector control without speed encoder (SLVC) ..................................................... 245 3.23.2.2 Vector control with speed encoder (VC)............................................................... 247 3.23.2.3 Speed controller.................................................................................................... 248 3.23.2.4 Closed-loop torque control.................................................................................... 253 3.23.2.5 Limiting the torque setpoint................................................................................... 254
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 50 6SE6400-5AW00-0BP0
WARNING MICROMASTER drive inverters operate with high voltages. When electrical equipment is operated, then specific parts of this equipment are
at hazardous voltage levels. The following terminals can carry dangerous voltages even if the inverter is
inoperative: ♦ the power supply L/L1, N/L2, L3 resp. U1/L1, V1/L2, W1/L3 ♦ the motor terminals U, V, W resp. U2, V2, W2 ♦ and depending on the frame size the terminals DC+/B+, DC-, B-, DC/R+
resp. DCPS, DCNS, DCPA, DCNA Emergency switching-off devices in compliance with EN 60204 IEC 204 (VDE
0113) must remain functional in all operating modes of the control device. When the Emergency switching-off device is reset, then it is not permissible that the equipment runs-up again in an uncontrolled or undefined way.
In cases and situations where short-circuits in the control device can result in significant material damage or even severe bodily injury (i.e. potentially hazardous short-circuits), then additional external measures or devices/equipment must be provided in order to ensure or force operation without any potential hazards, even if a short-circuit occurs (e.g. independent limit switches, mechanical interlocks etc.).
Certain parameter settings can mean that the drive inverter automatically restarts after the power supply voltage fails and then returns.
The motor parameters must be precisely configured in order to ensure perfect motor overload protection.
The drive inverter provides internal motor overload protection according to UL508C, Section 42. I2t monitoring is enabled in the default setting (refer to P0610 and P0335). The motor overload protection can also be guaranteed using an external PTC or KTY84.
This equipment is suitable for use in a circuit capable of delivering not more than 10,000 (Frame Sizes A to C) or 42,000 (Frame Sizes D to GX) symmetrical amperes (rms), for a maximum voltage of 230 V / 460 V / 575 V when protected by an H, J or K type fuse, a circuit breaker or self-protected combination motor controller (for more details see Appendix F).
The drive unit may not be used as 'Emergency switching-off device' (refer to EN 60204, 9.2.5.4).
CAUTION Only qualified personnel may commission (start-up) the equipment. Safety measures and warnings must be always extremely carefully observed and fulfilled.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 51
3.1 Parameters
3.1.1 Setting / monitoring parameters and parameter attributes
The drive inverter is adapted to the particular application using the appropriate parameters. This means that each parameter is identified by a parameter number , parameter text and specific attributes (e.g. readable, can be written into, BICO attribute, group attribute etc.). Within any one particular drive system, the parameter number is unique. On the other hand, an attribute can be assigned a multiple number of times so that several parameters can have the same attribute.
For MICROMASTER, parameters can be accessed using the following operator units:
BOP (option) AOP (option) PC-based commissioning (start-up) tool "Drive Monitor" or "STARTER". These
PC-based tools are supplied on the CD-ROM.
The parameter types are the main differentiating feature of the parameters.
Parameter
"normal"Write-/Read parameters
Read (r....) Write/Read (P....)
BICO output BICO input"normal"Read parameters
Fig. 3-1 Parameter types
Setting parameters Parameters which can be written into and read – "P" parameters These are activated/de-activated in the individual functions or parameters directly influence the behavior of a function. The value of this parameter is saved in a non-volatile memory (EEPROM) as long as the appropriate option was selected (non-volatile data save). Otherwise, these values are saved in the non-volatile memory (RAM) of the processor, which are lost after power failure or power-off/power-on operations. Notation: P0927 setting parameter 927 P0748.1 setting parameter 748, bit 01 P0719[1] setting parameter 719 index 1 P0013[0...19] setting parameter 13 with 20 indices (indices 0 to 19) Abbreviated notation P0013[20] setting parameter 13 with 20 indices (indices 0 to 19)
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 52 6SE6400-5AW00-0BP0
Monitoring parameters These can only be read – "r" parameters These parameters are used to display internal quantities, for example states and actual values. These parameters are absolutely necessary, especially for diagnostics.
Notation: r0002 monitoring parameter 2 r0052.3 monitoring parameter 52, bit 03
r0947[2] monitoring parameter 947 index 2 r0964[0...4] monitoring parameter 964 with 5 indices (indices 0 to 4) Abbreviated notation r0964[5] monitoring parameter 964 with 5 indices (indices 0 to 4)
NOTE A parameter (e.g. P0013[20]) with x consecutive
elements (in this case: 20) is defined using an index. x is defined by the numerical index value. When transferred to a parameter this means that an indexed parameter can assume several values. The values are addressed via the parameter number including the index value (e.g. P0013[0], P0013[1], P0013[2], P0013[3], P0013[4], ...). Index parameters, for example, are used for:
Drive data sets Command data sets Sub-functions
In addition to the parameter number and parameter text, every setting and monitoring parameter has different attributes which are used to individually define the properties/characteristics of the parameter. The attributes are listed in the following Table which are used for MICROMASTER.
Table 3-1 Parameter attributes
Attribute group
Attribute Description
The data type of a parameter defines the maximum possible value range. 3 data types are used for MICROMASTER. They either represent an unsigned integer value (U16, U32) or a floating-point value (float). The value range is frequently restricted by a minimum, maximum value (min, max) or using drive inverter/motor quantities.
U16 Unsigned, integer value with a size of 16 bits, max. value range: 0 .... 65535
U32 Unsigned, integer value with a size of 32 bits max. value range: 0 .... 4294967295
Data types
Float A simple precise floating point value according to the IEEE standard format max. value range: -3.39e+38 – +3.39e+38
P0013[0]P0013[1]P0013[2]
P0013[18]P0013[19]
...
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 53
Attribute group
Attribute Description
The value range, which is specified as a result of the data type, is restricted/limited by the minimum, maximum value (min, max) and using drive inverter/motor quantities. Straightforward commissioning (start-up) is guaranteed in so much that the parameters have a default value. These values (min, def, max) are permanently saved in the drive inverter and cannot be changed by the user.
- No value entered (e.g.: "r parameter") Min Minimum value Def Default value
Value range
Max Maximum value For MICROMASTER, the units of a particular parameter involve the physical quantity
(e.g. m, s, A). Quantities are measurable properties/characteristics of physical objects, operations, states and are represented using characters of a formula (e.g. V = 9 V).
- No dimension % Percentage A Ampere V Volt
Ohm Ohm us Microseconds ms Milliseconds s Seconds
Hz Hertz kHz Kilohertz
1/min Revolutions per minute [RPM] m/s Meters per second Nm Newton meter W Watt kW Kilowatt Hp Horse power
kWh Kilowatt hours °C Degrees Celsius m Meter kg Kilograms
Unit
° Degrees (angular degrees) The access level is controlled using parameter P0003. In this case, only those
parameters are visible at the BOP or AOP, where the access level is less than or equal to the value assigned in parameter P0003. On the other hand, for DriveMonitor and STARTER, only access levels 0 and 4 are relevant. For example, parameters with access level 4 cannot be changed if the appropriate access level has not been set. The following access levels are implemented in the family of MICROMASTER drive units:
0 User-defined parameter list (refer to P0013) 1 Standard access to the most frequently used parameters 2 Extended access, e.g. to drive inverter I/O functions 3 Expert access only for experienced users 4 Service access only for authorized service/maintenance personnel – with password
protection.
Access level
As far as the ability to visualize the parameters is concerned, the group assignment of the individual parameters must be taken into account. Parameter P0004 is used for the control (refer to the Grouping).
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 54 6SE6400-5AW00-0BP0
Attribute group
Attribute Description
The parameters are sub-divided into groups according to their functionality. This increases the transparency and allows a parameter to be quickly searched for. Furthermore, parameter P0004 can be used to control the ability to be visualized for the BOP / AOP. Main parameter area:
ALWAYS 0 all parameters INVERTER 2 drive inverter parameters 0200 .... 0299
MOTOR 3 motor parameters 0300 .... 0399 and 0600 .... 0699
ENCODER 4 speed encoder 0400 .... 0499 TECH_APL 5 technical applications / units 0500 .... 0599
COMMANDS 7 control commands, digital I/O 0700 .... 0749 and 0800 .... 0899
TERMINAL 8 Analog inputs/outputs 0750 .... 0799 SETPOINT 10 Setpoint channel and ramp-function gen. 1000 .... 1199
FUNC 12 Drive inverter functions 1200 .... 1299 CONTROL 13 Motor open-loop/closed-loop control 1300 .... 1799
COMM 20 Communications 2000 .... 2099 ALARMS 21 Faults, warnings, monitoring functions" 2100 .... 2199
Grouping
TECH 22 Technological controller (PID controller) 2200 .... 2399 Description for Binector Input (BI), Binector Output (BO), Connector Input (CI),
Connector Output (CO) and Connector Output / Binector Output (CO/BO), refer to Section 3.1.2.3
BI Binector Input BO Binector Output CI Connector Input CO Connector Output
BICO
CO/BO Connector Output / Binector Output Description for the command data set (CDS) and drive data set (DDS) refer to Section
3.1.3 CDS Command data set
Data sets
DDS Drive data set "P" parameters can only be changed depending on the drive state. The parameter
value is not accepted if the instantaneous state is not listed in the parameter attribute "Change state". For instance, the commissioning (start-up) parameter P0010 with the attribute "CT" can only be changed in quick start-up "C" or ready "T" but not in run "U".
C Quick commissioning (start-up) U Operation (run)
Change state
T Ready This parameter attribute identifies as to whether the parameter is included in the quick
commissioning (start-up) (P0010 = 1). No The parameter is not included in the quick commissioning (start-up)
QC.
Yes The parameter is included in the quick commissioning (start-up) This attribute is only of importance in conjunction with a BOP. The "Immediate"
attribute indicates that this value is already accepted when scrolling (when changing the value with or ). Especially parameters which are used for optimization functions have this property (e.g. constant voltage boost P1310 or filter time constants). On the other hand, for parameters with the attribute "After actuation", the value is only accepted after first actuating the key . These include, for example, parameters where the parameter value can have different settings/meanings (e.g. selecting the frequency setpoint source P1000).
Immediately The value becomes valid by either scrolling with or
Active
After actuation
The value is only accepted by pressing
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 55
The attributes and groups are shown, in the parameter list, in the header line of the parameter. This is shown as an example in Fig. 3-2 using parameter P0305.
Rated motor current 0.01C A 3.2510000.0
01
P0305[3]CStat:P-Group:
Datatype: FloatActive:
Unit Def:Max:
Min:
GroupCStat
ActiveDatatypes
QuickComm.Unit
Value range
BICO (if available) Access level Index
MOTOR first confirm
Level:
QuickComm. Yes
Fig. 3-2 Header line for parameter P0305
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 56 6SE6400-5AW00-0BP0
The interrelationship between access level P0003 and the grouping P0004 is schematically shown in Fig. 3-3.
P0004 = 2
P0004 = 3
P0004 = 7
P0004 = 8P0004 = 10
P0004 = 12
P0004 = 13
P0004 = 20
P0004 = 21
P0004 = 22
P0004 = 0
P0004 = 2
P0004 = 2, P0003 = 1
P0004 = 2, P0003 = 2
P0004 = 2, P0003 = 4
P0004 = 2, P0003 = 3(no filter function)allows direct accessto the parameters.For BOP and AOPdepending on theselected access level
Parameters level 1concerning the inverter unit
Parameters level 1, 2 and 3concerning the inverter unit
Inverter Unit
Parameters level 1 and 2concerning the inverter unit
Parameters level 1, 2, 3 and 4concerning the inverter unit
Inverter Unit
Motor Data
PID Controller
Alarms, Warnings &Monitoring
Motor ControlP1300 ... P1799
Drive FeaturesP1200 ... P1299
Setpoint Channel &Ramp GeneratorP1000 ... P1199
Speed sensorP0400 ... P0499
Commands andDigital I/OP0700 ... P0749P0800 ... P0899
CommunicationP2000 ... P2099
P0004 = 5
P0004 = 4
TechnologyApplication / unitsP0400 ... P0499
Analogue I/OP0750 ... P0799
P0200 ... P0299
P0300 ... P0399P0600 ... P0699
P0003 = 1
P0003 = 2
P0003 = 3
P0003 = 4
P0003 = 1 2 3 4
StandardExtendedExpertService
User access level
Fig. 3-3 Parameter grouping / access
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 57
3.1.2 Interconnecting signals (BICO technology) A state-of-the-art drive unit must be able to interconnect internal and external signals (setpoint / actual values and control / status signal). This interconnection functionality must have a high degree of flexibility in order to be able to adapt the drive to new applications. Further, a high degree of usability is required, which also fulfills standard applications. This is the reason that within the MICROMASTER series of drive units, BICO technology (→ flexibility) and fast parameterization using parameters P0700 / P1000 (→ usability) or P0719 (→ combination P0700/P1000) have been introduced to be able to fulfill both of these requirements.
3.1.2.1 Selecting the command source P0700 / selecting the setpoint source P1000
The following parameters can be used to quickly interconnect setpoints and control signals:
P0700 "Selection of command source" P1000 "Selection of setpoint source"
These parameters are used to define via which interface the drive inverter receives the setpoint or the power-on/power-off command. The interfaces, listed in Table 3-2 can be selected for the command source P0700.
Table 3-2 Parameter P0700
Parameter values Significance / command source 0 Factory default
1 BOP (operator panel, refer to Section 3.2.1)
2 Terminal strip
4 USS on BOP link
5 USS on COM link
6 CB on COM link
The following internal or external sources / interfaces can be selected for the frequency setpoint source P1000. In addition to the main setpoint (1st position), a supplementary setpoint (2nd position) can be selected (refer to Table 3-3).
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 58 6SE6400-5AW00-0BP0
Table 3-3 Parameter P1000
Significance Parameter values
Main setpoint source Supplementary setpoint source 0 No main setpoint -
1 MOP setpoint (motorized potentiometer) -
2 Analog setpoint -
3 Fixed frequency -
4 USS on BOP link -
5 USS on COM link -
6 CB on COM link -
7 Analog setpoint 2 -
10 No main setpoint MOP setpoint
11 MOP setpoint MOP setpoint
12 Analog setpoint MOP setpoint
.. .. ..
.. .. ..
.. .. ..
77 Analog setpoint 2 Analog setpoint 2
NOTE Communications between the AOP and MICROMASTER are established using
the USS protocol. The AOP can be connected to both the BOP link (RS 232) as well as at the COM link interface (RS 485) of the drive inverter. If the AOP is to be used as command source or setpoint source then for parameter P0700 or P1000, either "USS on BOP link" or "USS on COM link" should be selected.
The complete list of all of the setting possibilities can be taken from the parameter list (refer to parameter list P1000).
Parameters P0700 and P1000 have the following default settings: a) P0700 = 2 (terminal strip) b) P1000 = 2 (analog setpoint) In this case, the selection of the command source is made independently of the selection of the frequency setpoint source. This means that the source to enter the setpoint does not have to match the source to enter the power-on/power-off com-mand (command source). This means, for example, that the setpoint (P1000 = 4) can be connected via an external device which is connected to the BOP link interface via USS and the control (ON/OFF command, etc.) is entered via digital inputs (terminals, P0700 = 2). CAUTION
When P0700 or P1000 are modified, then the frequency inverter also changes the subordinate BICO parameters (refer to the parameter list for P0700 or P1000 in the appropriate tables)
There is no prioritization (priority assignment) between direct BICO parameterization and P0700/P1000. The last modification is valid.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 59
3.1.2.2 Selection of command/frequency setpoint P0719 Parameter P0719 represents a combination of the functionalities of the two parameters P0700 and P1000. Here, it is possible to changeover the command source as well as also the frequency setpoint source via a parameter change. Contrary to P0700 and P1000, for parameter P0719, the subordinate (lower-level) BICO parameters are not changed. This characteristic/feature is especially used by PC tools in order to briefly retrieve the control authority for the drive without having to change the existing BICO parameterization. Parameter P0719 "Selection of command/frequency setpoint" comprises the command source (Cmd) and the frequency setpoint (setpoint).
Table 3-4 Parameter P0719
Significance Parameter values
Command source Setpoint source (frequency source) 0 Cmd=BICO parameter Setpoint = BICO parameter
1 Cmd=BICO parameter Setpoint = MOP setpoint
2 Cmd=BICO parameter Setpoint = Analog
3 Cmd=BICO parameter Setpoint = Fixed frequency
4 Cmd=BICO parameter Setpoint = USS BOP link
5 Cmd=BICO parameter Setpoint = USS COM link
6 Cmd=BICO parameter Setpoint = CB COM link
10 Cmd=BOP Setpoint = BICO Param
11 Cmd=BOP Setpoint = MOP setpoint
12 Cmd=BOP Setpoint = Analog
.. .. ..
.. .. ..
64 Cmd=CB COM link Setpoint = USS BOP link
66 Cmd=CB COM link Setpoint = USS COM link
NOTE
The complete list of all of the possible settings can be taken from the parameter list (refer to the parameter list, P0719).
Contrary to parameter P0700 and P1000, subordinate BICO parameters are not changed for parameter P0719. This characteristic/feature can be used during service if the control authority must be briefly and quickly re-assigned (e.g. selecting and executing the motor data identification routine using a PC-based tool).
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 60 6SE6400-5AW00-0BP0
3.1.2.3 BICO technology Using BICO technology (English: Binector Connector Technology), process data can be freely interconnected using the "standard" drive parameterization. In this case, all values which can be freely interconnected (e.g. frequency setpoint, frequency actual value, current actual value, etc.) can be defined as "Connectors" and all digital signals which can be freely interconnected (e.g. status of a digital input, ON/OFF, message function when a limit is violated etc.) can be defined as "Binectors". There are many input and output quantities as well as quantities within the closed-loop control which can be interconnected in a drive unit. It is possible to adapt the drive to the various requirements using BICO technology. A binector is a digital (binary) signal without any units and which can either have the value 0 or 1. Binectors always refer to functions whereby they are sub-divided into binector inputs and binector outputs (refer to Fig. 3-4). In this case, the binector input is always designated using a "P" parameter with attribute "BI" (e.g.: P0731 BI: Function, digital output 1), while the binector output is always represented using an "r" parameter with attribute "BO" (e.g.: r0751 BO: ADC status word). As can be seen from the examples above, the binector parameters have the following abbreviations in front of the parameter names:
BI Binector Input, signal receiver ("P" parameters) → The BI parameter can be interconnected with a binector output as source, by
entering the parameter number of the binector output (BO parameter) as value in the BI parameter (e.g.: Interconnecting the "BO" parameter r0751 with "BI" parameter P0731 → P0731 = 751).
BO Binector Output, signal source ("r" parameters) → The BO parameter can be used as source for BI parameters. For the
particular interconnection the BO parameter number must be entered into the BI parameter (e.g.: Interconnecting the "BO" parameter r0751 with "BI" parameter P0731 → P0731 = 751).
Abbreviation and symbol Name Function
BI Binector input (signal receiver)
Data flow
Pxxxx
BI: ...Function
BO Binector output
(signal source) Data flow
Functionrxxxx
BO: ...
Fig. 3-4 Binectors
A connector is a value (16 or 32 bit), which can include a normalized quantity (without dimension) as well as also a quantity with associated units. Connectors always refer to functions whereby they are sub-divided into connector inputs and connector outputs (refer to Fig. 3-5). Essentially the same as the binectors, the connector inputs are characterized by a "P" parameter with attribute "CI" (e.g.: P0771 CI: D/A converter); while the connector outputs are always represented using an "r" parameter with attribute "CO" (e.g.: r0021 CO: Smoothed output frequency).
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 61
As can be seen from the examples above, connector parameters have the following abbreviations in front of the parameter names:
CI Connector Input, signal sink ("P" parameters) → The CI parameter can be interconnected with a connector output as source,
by entering the parameter number of the connector output (CO parameter) as value in the CI parameter (e.g.: P0771 = 21).
CO Connector Output, signal source ("r" parameters) → The CO parameter can be used as source for CI parameters. For the
particular interconnection, the CO parameter number must be entered in the CI parameter (e.g.: P0771 = 21).
Further, MICROMASTER has "r" parameters where several binector outputs are combined in a word (e.g.: r0052 CO/BO: Status word 1). This feature reduces, on one hand, the number of parameters and simplifies parameterization via the serial interface (data transfer). This parameter is further characterized by the fact that it does not have any units and each bit represents a digital (binary) signal.
As can be seen from the examples of parameters, these combined parameters have the following abbreviation in front of the parameter names:
CO/BO Connector Output / Binector Output, signal source ("r" parameters)
→ CO/BO parameters can be used as source for CI parameters and BI parameters: a) In order to interconnect all of the CO/BO parameters, the parameter
number must be entered into the appropriate CI parameter (e.g.: P2016[0] = 52).
b) When interconnecting a single digital signal, in addition to the CO/BO parameter number, the bit number must also be entered into the BI parameter (e.g.: P0731 = 52.3)
Abbreviation and symbol Name Function
CI Connector input (signal receiver)
Data flow
Pxxxx
CI: ...Function
CO Connector output
(signal source) Data flow
Functionrxxxx
CO: ... COBO
Binector/connector output (signal source)
Data flow
Functionsrxxxx
CO/BO: ...
Fig. 3-5 Connectors
In order to interconnect two signals, a BICO setting parameter (signal receiver) must be assigned the required BICO monitoring parameter (signal source). A typical BICO interconnection is shown using the following examples (refer to Fig. 3-6).
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 62 6SE6400-5AW00-0BP0
Connector output (CO) ===> Connector input (CI)
CO/BO: Act. status word 1
FBr0755
P1070 = 755(755)
P1070
FBP0840 = 751.0
r0751 (751:0)
P0840 FB(751:0)
P0840
(751:0)P0840
P0731 = 52.3
P2051 = 52
P0731 FBP0731
(52:3)P0731
FBP2051(52)
FBr0052r0052
Binector output (BO) ===> Binector input (BI)
Connector output / Binector output (CO/BO)
BO: Status word of ADC
CO: Act. ADC after scal. [4000h]CI: Main setpoint
BI: ON/OFF1
CI: PZD to CB
BI: Function of digital output 1
Function
Function
Function
Function
Function
Function
Function
Fig. 3-6 BICO connections (examples)
NOTE BICO parameters with the CO, BO or CO/BO attributes can be used a multiple number of times.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 63
3.1.3 Data sets For many applications it is advantageous if several parameters can be simultaneously changed, during operation or in the ready state, using an external signal.
Examples: The drive inverter should be switched-over from motor 1 to motor 2.
MM4
M1
K1
M2
K2
Motor 1
Motor 2
Fig. 3-7 Example: Changeover from motor 1 to motor 2
The control source (e.g. terminal → BOP) or setpoint (frequency) source (e.g. ADC → MOP) should be changed-over using a terminal signal (e.g. DIN4) as function of an external event (e.g. the higher-level control unit fails). A typical example in this case is a mixer, which may not come to an uncontrolled stop when the control fails.
Control source: Terminal → BOP Setpoint (frequency source): ADC → MOP
DIN4
TerminalsSequence control
BOP
P0700[0] = 2
P0700[1] = 1
P0810 = 722.3
ADC Setpointchannel
MOP
0
1
P1000[0] = 2
P1000[1] = 1
Motorcontrol
0
1
Fig. 3-8 Example: Changing-over between the control and setpoint (frequency) source
This functionality can be elegantly implemented using indexed parameters (refer to Section 3.1.1). In this case, as far as the functionality is concerned, the parameters are combined to form groups / data sets and are indexed. By using indexing, several different settings can be saved for each parameter which can be activated by changing-over the data set (i.e. toggling between data sets).
The following data sets apply: CDS Command Data Set DDS Drive Data Set
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 64 6SE6400-5AW00-0BP0
3 independent settings are possible for each data set. These settings can be made using the index of the particular parameter: CDS1 ... CDS3 DDS1 ... DDS3 Those parameters (connector and binector inputs) which are used to control the drive and enter a setpoint, are assigned to the command data set (CDS). The signal sources for the control commands and setpoints are interconnected using BICO technology (refer to Section 3.1.2.3). In this case, the connector and binector inputs are assigned as signal sources corresponding to the connector and binector outputs. A command data set includes:
Command sources and binector inputs for control commands (digital signals) e.g.: ♦ Selects the command source P0700 ♦ ON/OFF1 P0840 ♦ OFF2 P0844 ♦ Enable JOG right P1055 ♦ Enable JOG left P1056
Setpoint sources and connector inputs for setpoints (analog signals) e.g.: ♦ Selection of frequency setpoint P1000 ♦ Selection of main setpoint P1070 ♦ Selection of additional setpoint P1075
The parameters, combined in a command data set, are designated with [x] in the parameter list in the index field. Index: Pxxxx[0] : 1st command data set (CDS) Pxxxx[1] : 2nd command data set (CDS) Pxxxx[2] : 3rd command data set (CDS)
NOTE A complete list of all of the CDS parameters can be taken from the parameter list. It is possible to parameterize up to three command data sets. This makes it easier to toggle between various pre-configured signal sources by selecting the appropriate command data set. A frequent application involves, for example, the ability to toggle between automatic and manual operation.
MICROMASTER has an integrated copy function which is used to transfer command data sets. This can be used to copy CDS parameters corresponding to the particular application. The copy operation is controlled with P0809 as follows (refer to Fig. 3-9): 1. P0809[0] = Number of the command data set which is to be copied (source) 2. P0809[1] = Number of the command data set into which data is to be copied
(target) 3. P0809[2] = 1 → Copying is started
Copying has been completed, if P0809[2] = 0.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 65
P0809[0] = 0P0809[1] = 2P0809[2] = 1
2. CDS 3. CDS
P0700P0701P0702P0703P0704.....P2253P2254P2264
..........
.....
[0] [1] [2]
1. CDS
1. CDS3. CDSStart copy
Fig. 3-9 Copying from CDS
The command data sets are changed-over using the BICO parameter P0810 and P0811, whereby the active command data set is displayed in parameter r0050 (refer to Fig. 3-10). Changeover is possible both in the "Read" as well as in the "Run" states.
t0
1
2
3
(0:0)
BI: CDS b0 loc/remP0810
(0:0)
BI: CDS bit 1P0811
t0
1
2
3
CO/BO: Act CtrlWd2
r0055r0055
CO/BO: Act CtrlWd1
r0054r0054
.15
.15
.15
.15
r0050CDS active
Selection of CDS
Switch-over timeaprox. 4 ms
Switch-over timeaprox. 4 ms
Fig. 3-10 Changing-over CDS
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 66 6SE6400-5AW00-0BP0
The drive data set (DDS) contains various setting parameters which are of significance for the open-loop and closed-loop control of a drive:
Motor and encoder data, e.g.: ♦ Select motor type P0300 ♦ Rated motor voltage P0304 ♦ Main inductance P0360 ♦ Select encoder type P0400
Various closed-loop control parameters, e.g.: ♦ Fixed frequency 1 P1001 ♦ Min. frequency P1080 ♦ Ramp-up time P1120 ♦ Control mode P1300
The parameters, combined in a drive data set, are designated with an [x] in the parameter list in the index field: Pxxxx[0] : 1st drive data set (DDS) Pxxxx[1] : 2nd drive data set (DDS) Pxxxx[2] : 3rd drive data set (DDS)
NOTE A complete list of all of the DDS parameters can be taken from the parameter list. It is possible to parameterize several drive data sets. This makes it easier to toggle between various drive configurations (control mode, control data, motors) by selecting the appropriate drive data set.
Just like the command data sets, it is possible to copy drive data sets within the MICROMASTER. P0819 is used to control the copy operation as follows: 1. P0819[0] = Number of the drive data set which is to be copied (source) 2. P0819[1] = Number of the drive data set into which data is to be copied
(target) 3. P0819[2] = 1 → Copying is started
Copying has been completed, if P0819[2] = 0.
P0819[0] = 0P0819[1] = 2P0819[2] = 1
2. DDS 3. DDS
P0005P0291P0300P0304P0305.....P2484P2487P2488
..........
.....
[0] [1] [2]
1. DDS
1. DDS3. DDSStart copy
Fig. 3-11 Copying from DDS
Drive data sets are changed-over using the BICO parameter P0820 and P0821 whereby the active drive data set is displayed in parameter r0051 (refer to Fig.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 67
3-12). Drive data sets can only be changed-over in the "Ready" state and this takes approx. 50 ms.
t0
1
2
3
(0:0)
BI: DDS bit 0P0820
(0:0)
BI: DDS bit 1P0821
t0
1
2
3
CO/BO: Act CtrlWd2
r0055r0055
CO/BO: Act CtrlWd2
r0055r0055
.04
.04
.05
.05
r0051[1]DDS active
Selection of DDS
aprox. 50 ms aprox. 50 msSwitch-over timeSwitch-over time
Drive running
Drive ready
t
Fig. 3-12 Changing-over DDS
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 68 6SE6400-5AW00-0BP0
3.1.4 Reference quantities Parameter range: P2000 – r2004
Physical quantities are normalized or de-normalized by the frequency inverter when data is output or is being entered. This conversion is undertaken by the particular interface using the reference quantities. The normalization / de-normalization is carried-out for the following interfaces:
Table 3-5 Normalized interfaces
Interafce 100 % Analog input Current input Voltage input
20 mA 10 V
Analog output Current output Voltage output
20 mA 10 V
USS 4000 h
CB 4000 h
Further, for a BICO connection, a normalization is carried-out if the connector output (CO) represents a physical quantity and the connector input (CI) a normalized (percentage) quantity (e.g. PID controller). De-normalization is carried-out if the inverse situation exists. This normalization / de-normalization should be carefully taken into consideration, especially for the free function blocks (FFBs). Reference quantities (normalization quantities) are intended to allow setpoint and actual value signals to be represented in a standard fashion (normalization / de-normalization of physical quantities such as setpoint and actual frequency). This also applies for permanently set parameters that are entered as a "percentage". A value of 100 % corresponds to a process data value PZD of 4000 h (USS or CB) – or a current / voltage value of 20 mA / 10 V (analog input / output). The following reference parameters and permanently saved reference values are available:
Table 3-6 Normalization functions
Parameter Designation Value (100 % / 4000 h) Units P2000 Reference frequency P2000 Hz
P2001 Reference voltage P2001 V
P2002 Reference current P2002 A
P2003 Reference torque P2003 Nm
r2004 Reference power π * P2000 * P2003 kW
- Reference speed P2000 * 60 / r0313 RPM
- Reference temperature 100 °C °C
- Reference energy 100 kWh kWh
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 69
Example Using the reference frequency P2000 as example, normalization / de-normalization is demonstrated via the serial interface "USS at BOP link". If the connection between two BICO parameters is closed (directly using the BICO parameters or indirectly using P0719 or P1000), that have different representation types (normalized representation (hex) or physical representation (Hz)), then in the frequency inverter, the following normalization is made to the target value:
P1070
y[Hz]
2000P4000[Hex]r2015[1] y[Hz] ⋅=
r2015[0][1][2][3]
P2016[0][1][2][3]
r0021
x[Hz] y[Hex]
x[Hex]
]Hex[4000P2000[Hz]r0021[Hz] y[Hex] ⋅=USS-PZD
BOP link
USS-PZDBOP link
Fig. 3-13 Normalization / de-normalization
Note Analog values are limited to 10 V or 20 mA. A maximum of 100 % referred to
the corresponding reference values can be output / entered as long as no DAC/ADC scaling is made (factory setting).
Setpoints and actual value signals via serial interface: ♦ When transferring using the PZD part, they are limited to the value 7FFF h.
This is the reason that the maximum value is 200 % referred to the reference value.
♦ When transferring data using the PKW part, they are transferred dependant on the data type and the units.
Parameter P1082 (max. frequency) limits the frequency in the frequency inverter independent of the reference frequency. When changing P1082 (factory setting: 50 Hz), this is the reason that P2000 should always be adapted (factory setting: 50 Hz). If, e.g. for a NEMA motor, the parameter is set to 60 Hz, and no changes are made regarding P2000, then the analog setpoint / actual value is limited to 100 % or a setpoint / actual value signal at 4000 h is limited to 50 Hz!
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 70 6SE6400-5AW00-0BP0
3.2 Operator panels for MICROMASTER MICROMASTER drive units can be optionally equipped with a BOP (Basic Operator Panel) or AOP (Advanced Operator Panel). The AOP distinguishes itself as a result of a plain text display which simplifies operator control, diagnostics as well as also commissioning (start-up).
BOP AOP
Fig. 3-14 Operator panels
3.2.1 Description of the BOP (Basic Operator Panel)
The BOP, available as option, allows drive inverter parameters to be accessed. In this case, the Status Display Panel (SDP) must be removed and the BOP either inserted or connected in the door of a cabinet using a special mounting kit (Operator panel door mounting set) (refer to the Attachment A).
Parameter values can be changed using the BOP. This allows the MICROMASTER drive unit to be set-up for a particular application. In addition to the keys (refer to Section 3.2.3), it includes a 5-digit LCD display on which the parameter numbers rxxxx and Pxxxx, parameter values, parameter units (e.g. [A], [V], [Hz], [s]), alarm Axxxx or fault messages Fxxxx as well as setpoints and actual values.
NOTE Contrary to the AOP, for the BOP, parameters do not have to be set or taken
into consideration when establishing the communications between the BOP and drive inverter.
A BOP does not have a local memory. This means that it is not possible to save a parameter set on the BOP.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 71
3.2.2 Description of the AOP (Advanced Operator Panel) An AOP (this is available as option) has the following additional functions with respect to a BOP:
Multi-language and multi-line plain text display Units are additionally displayed, such as [Nm], [°C], etc. Active parameters, fault messages, etc. are explained Diagnostics menu to support troubleshooting The main menu is directly called by simultaneously pressing keys Fn and P Timer with 3 switching operations per entry Up to 10 parameter sets can be downloaded / saved Communications between an AOP and MICROMASTER are realized using the
USS protocol. An AOP can be connected to the BOP link (RS 232) as well as to the COM link interface (RS 485) of the drive inverter.
Multi-point capable coupling to control (open-loop) and visualize up to 31 MICROMASTER drive inverters. The USS bus must, in this case, be configured and parameterized via the drive inverter terminals of the COM link interface.
Please refer to Sections 3.2.3, 3.2.4 and the AOP Manual for additional details.
NOTE Contrary to the BOP, for the AOP, the communications parameters of the
particular interface must be taken into account. When inserting / connecting to the drive inverter, the AOP automatically
changes the parameter P2012 (USS-PZD length) to 4 corresponding to the interface. COM link: P2012[0] BOP link: P2012[1]
For DriveMonitor, the default value for the USS-PZD length is set to 2. This results in a conflict if the AOP and the DriveMonitor are operated, alternating, at the same interface. Remedy: Increase the USS-PZD length to 4.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 72 6SE6400-5AW00-0BP0
3.2.3 Keys and their functions on the operator panel (BOP / AOP)
Operator panel/key
Function Effects
Status display The LCD indicates the settings which the drive inverter is presently using.
Start motor
The drive inverter is started by pressing the key. This key is de-activated in the default setting. Parameter P0700 or P0719 should be changed as follows to activate the key: BOP: P0700 = 1 or P0719 = 10 ... 16 AOP: P0700 = 4 or P0719 = 40 .... 46 on the BOP link P0700 = 5 or P0719 = 50 .... 56 on the COM link
Stop motor
OFF1 When this key is pressed, the motor comes to a standstill within the selected ramp-down time. It is de-activated in the default setting; to activate → refer to the "Start motor" key.
OFF2 The motor coasts down to a standstill by pressing the key twice (or pressing once for a longer period of time). This function is always activated.
Direction reversal
To reverse the direction of rotation of the motor, press this key. The opposing direction is displayed using the minus character (-) or by the flashing decimal point. In the default setting this function is de-activated; to activate it → refer to the "Start motor" key.
Jog
motor In the "Ready to power-on" state, when this key is pressed, the motor starts and rotates with the pre-set jog frequency. The motor stops when the key is released. When the motor is rotating, this key has no effect.
Functions
This key can be used to display additional information. If you press the key during operation, independent of the particular parameter, for two seconds, then the following data is displayed: 1. Voltage of the DC current link (designated by d – units V). 2. Output current (A) 3. Output frequency (Hz) 4. Output voltage (designated by o – units V). 5. The value, selected in P0005 (if P0005 is configured so that one of the
above pieces of data is displayed (1 to 4), then the associated value is not re-displayed).
The displays mentioned above are run-through one after the other by pressing again. Step function Starting from any parameter (rXXXX or PXXXX), if the key Fn is briefly pressed, then a jump is immediately made to r0000. You can then, when required, change an additional parameter. After returning to r0000, when key Fn is pressed, then the system returns to the starting point. Acknowledgement If alarm and fault messages are present, then these can be acknowledged by pressing key Fn.
Parameter
access Parameters can be accessed by pressing this key.
Increase value When this key is pressed, the displayed value is increased.
Reduce value When this key is pressed, the displayed value is decreased.
+
AOP menu Calls the AOP menu prompting (this is only available for AOP).
Fig. 3-15 Operator panel keys
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 73
3.2.4 Changing parameters using the operator panel The way that parameter P0719 can be changed will now be described; please use this description as a basis when setting all of the other parameters using the BOP.
Changing P0004 – parameter filter function
Step Result on the display
1 Press in order to access the parameter
2 Press until P0004 is displayed
3 Press in order to reach the parameter value level
4 Press or in order to obtain the required value
5 Press to acknowledge the value and to save the value
6 The user can only see the command parameters.
Changing an indexed parameter P0719 – selecting the command/frequency setpoint
Step Result on the display
1 Press in order to access the parameter
2 Press until P0719 is displayed
3 Press in order to reach the parameter value
4 Press in order to display the currently set value
5 Press or in order to obtain the required value
6 Press to acknowledge the value and to save the value
7 Press until r0000 is displayed
8 Press in order to return to the operating display (the display which the customer has defined)
Fig. 3-16 Changing parameters using the BOP
NOTE
The BOP sometimes display when changing parameter values. This means that the drive inverter is presently handling another higher-priority task.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 74 6SE6400-5AW00-0BP0
3.3 Block diagram
PE
1/3 AC 200 - 240 V3 AC 380 - 480 V3 AC 500 - 600 V
SI
PE L/L1, N/L2
L/L1, N/L2,L3
L1, L2, L3
=
3 ~
PE U,V,W
M
1 2
ADC1
ADC2
1 2
60 Hz
50 Hz
A/D
A/D
+10 V
0 V
0 - 20 mAmax. 500 Ω
NPN
PNP
CPU
RS485
D/A
D/A
DCNA
DCPA
B+/DC+
B-
DC-
~
=
ADC1+
ADC1-
ADC2+
ADC2-
DIN1
DIN2
DIN3
DIN4
DIN5
DIN6
PTCA
PTCB
DAC1+
DAC1-
DAC2+
DAC2-
P+
N-
COM
NC
NO
COM
NC
NO
COM
NO
1
2
3
4
10
11
5
6
7
8
16
17
9
28
14
15
12
13
26
27
29
30
20
18
19
25
23
24
22
21
0 - 20 mAmax. 500 Ω
≥ 4.7 kΩ
Output 0 Vmax. 100 mA(isolated)
or
MotorPTCKTY84
30 V DC / 5 A (resistive)250 V AC / 2 A (inductive)
Relay1
Relay2
Relay3
Frame sizesA to F
Frame sizesFX and GX
Output +24 Vmax. 100 mA(isolated)
0 - 20 mAcurrent0 - 10 Vvoltage
DIP switch(on I/O Board)
DIP switch(on Control Board)
Notused
Exte
rnal
bra
king
mod
ule
conn
ectio
n
Opt
o Is
olat
ion
or
or
CBOption
automatic
A/D
R
BOP link
COM link
Jog0
I
P
Fn
Hz150.00
BOP/AOP
RS232
5
6
7
8
16
17
28
DIN1
DIN2
DIN3
DIN4
DIN5
DIN6
External 24 V
24 V+_
DCNS
DCPS
Con
nect
ion
for
dv/d
t filt
er
Fig. 3-17 MICROMASTER 440 – block diagram
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 75
3.4 Factory setting The MICROMASTER drive unit is shipped from the plant with a Status Display Panel (SDP, refer to Fig. 3-18). The SDP has two LEDs on the front panel which display the operating state of the drive inverter (refer to Section 4.1). When MICROMASTER is shipped from the plant with the SDP functioning, it can be operated without any additional parameterization. In this case, the drive inverter default settings (which depend on the drive inverter type / size) match the following data of a 4-pole motor:
Rated motor power P0307 Rated motor voltage P0304 Rated motor current P0305 Rated motor frequency P0310
(We recommend a Siemens standard motor.)
Further, the following conditions must be fulfilled: Control (ON/OFF command) via digital inputs (refer to Table 3-7) Setpoint input via analog input 1 P1000 = 2 Induction motor P0300 = 1 Self-cooled motor P0335 = 0 Motor overload factor P0640 = 150 % Min. frequency P1080 = 0 Hz Max. frequency P1082 = 50 Hz Ramp-up time P1120 = 10 s Ramp-down time P1121 = 10 s Linear V/f characteristic P1300 = 0
Table 3-7 Pre-assignment of the digital inputs
Digital inputs Terminals Parameter Function Active Command source - P0700 = 2 Terminal strip Yes
Digital input 1 5 P0701 = 1 ON / OFF1 Yes
Digital input 2 6 P0702 = 12 Reversing Yes
Digital input 3 7 P0703 = 9 Fault acknowledge Yes
Digital input 4 8 P0704 = 15 Fixed setpoint (direct) No
Digital input 5 16 P0705 = 15 Fixed setpoint (direct) No
Digital input 6 17 P0706 = 15 Fixed setpoint (direct) No
Digital input 7 Via ADC1 P0707 = 0 Digital input disabled No
Digital input 8 Via ADC2 P0708 = 0 Digital input disabled No
Fig. 3-18 Status Display
Panel (SDP)
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 76 6SE6400-5AW00-0BP0
If the various prerequisites are fulfilled and the appropriate conditions present, then after the motor has been connected and the power connected, then the following is possible with the factory setting:
The motor can be started and stopped (via DIN1 with external switch) The direction of rotation can be reversed (via DIN2 with external switch) Faults reset (via DIN3 with external switch) A frequency setpoint can be entered (via ADC1 with external
potentiometer default setting of the ADC: Voltage input)
The frequency actual value can be output (via D/A converter, D/A converter output: current output)
The potentiometer and the external switches can be connected through the drive inverter internal power supply, as shown in Fig. 3-19.
Analog output
Pre-assignment of the digital inputs DIN1 to DIN3, refer to Table 3-7.
Fig. 3-19 Recommended wiring for the factory setting
If settings have to be made which go beyond the factory setting, then depending on the complexity of the application, when commissioning the drive system, the particular function description as well as the parameter list including function charts must be carefully taken into consideration.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 77
3.5 Commissioning A differentiation is made between the following scenarios when commissioning MICROMASTER:
50/60 Hz changeover Quick commissioning Motor data identification Calculating the motor / control data Series commissioning Commissioning the application
Start commissioning
Completeparameter list
of a commissioningavailable
?
End of commissioning
Quick commissioningSection 3.5.3
Is the momentof inertia of the motor
and load known?
Series commissioningSection 3.5.7
Motorequivalent
circuit diagram dataknown
?
Commissioning the applicationSection 3.5.6
P0341 = ?P0342 = ?P0344 = ?
P0340 = 1
yesno
yesno
yesno
Enter motor equivalentcircuit diagram data
Section 3.5.4
Motor data identificationSection 3.5.5
Carry-out checklist
NEMA motor60 Hz / hp ?Section 3.5.2
50/60 Hz settingSection 3.5.1
yes
no
Fig. 3-20 Procedure when commissioning
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 78 6SE6400-5AW00-0BP0
When commissioning, initially, a quick or series commissioning should be carried-out. The actual application should only be commissioned if the drive inverter – motor combination provides a satisfactory result.
If the drive is to be commissioned from a defined state, then the drive inverter can be reset to the initial state when it left the plant. This is done as follows:
Reset parameters to the factory setting
Check list The following check list should help you to commission MICROMASTER without any problems and to guarantee a high degree of availability:
When handling the drive unit, carefully observe all of the ESD measures. All of the screws must have been tightened up to their specified torque. All connectors / option modules must have been correctly inserted and locked /
screwed into place. The DC link pre-charging has been completed. All of the components are grounded/earthed at the points provided and all of the
shields have been connected. MICROMASTER drive units have been designed for defined mechanical,
climatic and electrical ambient conditions. It is not permissible that the specified limit values are exceeded in operation and when the drive units are being transported. The following must be especially carefully observed: ♦ Line supply conditions ♦ Pollutant stressing ♦ Gases which can have a negative impact on the function ♦ Ambient climatic conditions ♦ Storage / transport ♦ Shock stressing ♦ Vibration stressing ♦ Ambient temperature ♦ Installation altitude
In addition to carrying-out all of the installation work, an important prerequisite for successful commissioning is that the drive inverter is not disconnected from the line supply while being parameterized. If a line supply failure interrupts commissioning, then inconsistencies can occur regarding the parameterization. In this case, it is important that the commissioning is re-started (possibly reset and establish the original factory settings (refer to Section 3.5.9)).
NOTE When using output reactors, the pulse frequency may not be set higher than 4 kHz. The following parameter setting is mandatory when using an output reactor: P1800 = 4 kHz , P0290 = 0 or 1
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 79
3.5.1 50/60 Hz setting The frequency setting made in the factory can be adapted to the North American market, without requiring any parameterization using an operator panel or PC tool using the DIP50/60 switch (refer to Fig. 3-21) under the I/O board (refer to the Appendix C when removing the I/O board).
Rem
ove
I/O b
oard
DIP50/60
Fig. 3-21 DIP switch to change-over between 50/60 Hz
The switch determines the value of parameter P0100 corresponding to the following diagram (refer to Fig. 3-22). Besides P0100 = 2, after the power supply voltage has been switched-in, the DIP50/60 switch determines the 50/60 Hz setting (value of parameter P0100).
P0100 = 2?
P0100 = 0 P0100 = 2 P0100 = 1
P0100 = 2?
P0100 = 1?
yes
yes
no
no
yes
yes
nono
Quickcommissioning
P0010 = 1Powercycle
DIP2 = OFF?
Power in kWFrequency 50 Hz
Power in kWFrequency 60 Hz
Power in hpFrequency 60 Hz
Fig. 3-22 Mode of operation of the DIP50/60 switch in conjunction with P0100
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 80 6SE6400-5AW00-0BP0
By changing the setting of DIP50/60 switch, after the drive inverter has been powered-down/powered-up, the parameters for the rated motor frequency P0310, max. frequency P1082 and reference frequency P2000 are automatically pre-set. In addition, the rated motor parameters as well as all of the other parameters which depend on the rated motor parameters, are reset. The units of the power parameters are, depending on P0100, are either interpreted as kW value or hp value.
NOTE Switch DIP2(1) (refer to Fig. 3-21) under the I/O board has no function.
3.5.2 Motor circuit
In order to ensure a straightforward, successful commissioning, it is important that the circuit connection in the motor terminal box (refer to Fig. 3-23) matches the rated motor voltage entered in P0304 or the rated motor current P0305.
W2
U1
U2
V1
V2
W1
W2
U1
U2
V1
V2
W1
Delta connection
U1
V1W1
U1
V1W1
Star connection
IEC Motor
e.g.: Volts 230 V (Delta connection) / 400 V (Star connection)
NEMA Motor T1
T4T7
T3
T6T9
T8T5
T2
Volts U V W
T1-T7 T2-T8 T3-T9low T4-T5-T6
T1 T2 T3high
Connectedtogether Connection
T1-T7 T2-T8 T3-T9
Y YY
U V W
T1-T6-T7 T2-T4-T8 T3-T5-T9 -T1 T2 T3 T4-T7 T5-T8 T6-T9
∆ ∆∆
T1
T4T7
T2T5T8T3
T9T6
e.g.: Volts 230 V YY (low) / 460 V Y (high)
Volts
lowhigh
Connectedtogether Connection
Fig. 3-23 Motor terminal box
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 81
The following must be noted when entering the rating plate data or the ESB data:
The outer conductor voltage/phase-to-phase voltage (voltage U12 between outer conductors L1, L2) and the outer conductor current (phase current) I1 are always specified on the rating plate.
The rated motor voltage P0304 and the rated motor current P0305 must always be entered according to the motor circuit configuration (either delta/star circuit configuration).
If rated motor data that are available (P0304, P0305) are not consistent with the motor circuit configuration, then an appropriate conversion should be made which is then entered.
If equivalent circuit diagram data (P0350, P0354, P0356, P0358, P0360) is available, then these should be entered according to the motor circuit configuration. If there is no consistency between the motor circuit configuration and equivalent circuit diagram data, then the equivalent circuit diagram data should be converted and entered corresponding to the data on the rating plate (P0304, P0305).
I11
2
U12
3
U1N
I1N
ZN
Z Z
III 321 ==
U 3UUU 1Ν312312 ⋅===
Z2I
U1
12 ⋅=3
ZZ Y12,
∆12, =
U3
U Y12,1
∆12, =
I11
2
U12
3
I12
Z Z
Z
I31
III 1312312 ⋅===
UUU 312312 ==
I31
I Y1,∆1, =
Z32
IU
1
12 ⋅=
Fig. 3-24 Star / delta circuit configurations
NOTE The precise equivalent circuit diagram data are of extreme important regarding the stability of the closed-loop vector control and for the voltage boost applied to the V/f characteristic. Equivalent circuit diagram data can only be estimated from the rating plate data; this is the reason that equivalent circuit diagram data is either determined - using the motor data identification (refer to Chapter 0), or - is entered from a motor data sheet that may be available (refer to Chapter 0).
NOTE The MICROMASTER series of drive units is not available for 3-ph. 690 V AC.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 82 6SE6400-5AW00-0BP0
87 Hz characteristic When a motor with a delta circuit configuration (e. g. VN∆, motor = 230 V) is fed from a frequency inverter, where the rated voltage corresponds to the star circuit configuration (e.g. 400 V frequency inverter), then it is important to proceed as follows and observe the following:
The motor must have the appropriate voltage strength. Above the rated motor frequency, the iron losses in the motor increase over-
proportionally. This is the reason that above this frequency, the thermal motor torque should be reduced.
For the quick commissioning, the rating plate data for the delta circuit configuration should be entered or the rating plate must be appropriately converted.
The drive inverter must be designed for the higher current (delta circuit configuration).
The 87 Hz characteristic is independent of the control type and can therefore be used both for V/f control as well as for closed-loop vector control.
When using the 87 Hz characteristic, the mechanical motor limits must be taken into account (refer to Catalog M11).
For the 87 Hz characteristic, the ratio between the voltage and frequency (V/f characteristic) remain constant. This is the reason that the following relationships apply:
P = powerPUUP N∆
N∆
N1N1 ⋅=
fUUf N∆
N∆
N1N1 ⋅=
( ) nffn ∆N∆N1N1 pmin
s 60 +−
⎥⎦
⎤⎢⎣
⎡
=f
fN1fN∆
U
UN∆
UN1 f = frequencyn = speedp = pole pair No.
(400 V)
(230 V)
(50 Hz) (87 Hz)
Fig. 3-25 V/f characteristic
Table 3-8 Example 1LA7060-4AB10
Delta circuit configuration
87 Hz characteristic
Star circuit configuration
P0304 Rated motor voltage 230 V 400 V 400 V
P0305 Rated motor current 0.73 A 0.73 A 0.42 A
P0307 Rated motor power 120 W 207 W 120 W
P0308 Cos ϕ 0.75 0.75 0.75
P0310 Rated motor frequency 50 Hz 87 Hz 50 Hz
P0311 Rated motor speed 1350 RPM 2460 RPM 1350 RPM
P0314 Motor pole pairs 2 2 2
Contrary to the BOP, AOP operator panels or the commissioning program Drive-Monitor, the STARTER commissioning (start-up) program offers a mask-orientated quick commissioning, which is especially advantageous for users who are using MICROMASTER for the first time. On the other hand, BOP, AOP and DriveMonitor offer, in conjunction with the drive inverter, parameter-orientated quick commissio-ning where the user is navigated through the menu tree mentioned.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 83
3.5.3 Quick commissioning If there is still no appropriate parameter set for the drive, then a quick commissioning must be carried-out for the closed-loop Vector control and for the V/f control including a motor data identification routine. The following operator units can be used to carry-out quick commissioning:
BOP (option) AOP (option) PC Tools (with commissioning program STARTER, DriveMonitor)
When the quick commissioning is carried-out, the motor – drive inverter is basically commissioned; the following data must be obtained before quick commissioning is started:
Line supply frequency Motor rating plate data Command / setpoint sources Min. / max. frequency or ramp-up / ramp-down time Closed-loop control mode Motor data identification
Parameterizing the drive with BOP or AOP The frequency inverter is adapted to the motor using the quick commissioning function and important technological parameters are set. The quick commissioning shouldn't be carried-out if the rated motor data saved in the frequency inverter (4-pole 1LA Siemens motor, star circuit configuration frequency inverter (FU)-specific) match the rating plate data.
Parameters, designated with a * offer more setting possibilities than are actually listed here. Refer to the parameter list for additional setting possibilities.
NOTE Parameter P0308 or P0309 can only be viewed on the BOP or AOP if P0003 ≥
2. Depending on the setting of parameter P0100, either P0308 or P0309 is displayed.
The value entered into P0307 and all of the other power data – depending on P0100 – are either interpreted as kW or hp value.
Factory setting
P0003 = 3
User access level * 1 Standard: Allows access into most frequently used parameters 2 Extended: Allows extended access e.g. to inverter I/O functions 3 Expert (For expert use only)
Parameter filter * 0 All parameters 2 Inverter 3 Motor 4 Speed sensor
START
P0004 = 0 0
1
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 84 6SE6400-5AW00-0BP0
P0010 = 1
Commissioning parameter * 0 Ready 1 Quick commissioning 30 Factory setting (refer to Section 3.5.9) NOTE P0010 should be set to 1 in order to parameterize the data of the motor rating plate.
P0100 =...
P0100 = 1, 2 P0100 = 0
Europe/ North America (enters the line supply frequency) 0 Europe [kW], frequency default 50 Hz 1 North America [hp], frequency default 60 Hz 2 North America [kW], frequency default 60 Hz NOTE For P0100 = 0 or 1, the setting of switch DIP50/60 determines the value of P0100 (refer to Section 3.5.1). OFF = kW, 50 Hz ON = hp, 60 Hz
Inverter application (enters the required torque) 0 Constant torque (e.g. compressors, processing machines) 1 Variable torque (e.g. pumps, fans) NOTE This parameter is only effective for drive inverters ≥ 5.5 kW / 400 V
Select motor type 1 Asynchronous motor (induction motor) 2 Synchronous motor NOTE For P0300 = 2 (synchronous motor), only the V/f control types (P1300 < 20) are permitted.
P0304 =... P0304 =... Rated motor voltage (Nominal motor voltage [V] from rating plate) The rated motor voltage on the rating plate must be checked, regarding the star/delta circuit configuration to ensure that it matches with the circuit connection configured at the motor terminal board
P0305 =... P0305 =... Rated motor current (Nominal motor current [A] from rating plate)
P0307 =... P0307 =... Rated motor power (Nominal motor power [kW/hp] from rating plate) If P0100 = 0 or 2, value will be in kW. If P0100 = 1, value will be in in hp.
P0304
P0305P0307P0308 P0311
P0310
Example of a typical motor rating plate (data for a delta circuit configuration). The precise definition and explanation of this data is specified in DIN EN 60 034-1.
P0308 =...P0308 =... Rated motor cosPhi (Nominal motor power factor (cos ϕ) from rating plate) If the setting is 0, the value is automatically calculated P0100 = 1,2: P0308 no significance, no entry required.
P0309 =... P0309 =... Rated motor efficiency (Nominal motor efficiency in [%] from rating plate) Setting 0 causes internal calculation of value. P0100 = 0: P0309 no significance, no entry required.
1
0
P0300 =... P0300 =...
P0205 =... P0205 =...
0
0
FU-spec.
FU-spec.
FU-spec.
FU-spec.
FU-spec.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 85
P0310 =... Rated motor frequency (Nominal motor frequency in [Hz] from rating plate) Pole pair number recalculated automatically if parameter is changed.
P0311 =...
Rated motor speed (Nominal motor speed in [rpm] from rating plate) Setting 0 causes internal calculation of value. NOTE An entry must be made for closed-loop Vector control, V/f control with FCC and for slip compensation.
Motor magnetizing current (this is entered as a % referred to P0305) Motor magnetizing current as a % relative to P0305 (rated motor current). With P0320 = 0, the motor magnetizing current is calculated using P0340 = 1 or using P3900 = 1 - 3 (end of the quick commissioning) – and is displayed in parameter r0331.
P0335 =...
Motor cooling (Selects motor cooling system used) 0 Self-cooled: Using shaft mounted fan attached to motor 1 Force-cooled: Using separately powered cooling fan 2 Self-cooled and internal fan
3 Force-cooled and internal fan
P0640 =...
Motor overload factor (Motor overload factor in [%] relative to P0305) This defines the limit of the maximum output current as a % of the rated motor current (P0305). This parameter is set, using P0205 for constant torque, to 150 %, and for variable torque, to 110 %.
P0700 =...
Selection of command source (enters the command source) 0 Factory default setting 1 BOP (keypad) 2 Terminal 4 USS on BOP link 5 USS on COM link (control terminals 29 and 30) 6 CB on COM link (CB = communications module)
BOP
USSBOP link
USSCOM link
P0700 = 2
Terminals
CBCOM link
Sequence control
Setpointchannel
Motorcontrol
P0320 = ... 0.0
50.00 Hz
FU-spec.
0
150 %
2
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 86 6SE6400-5AW00-0BP0
P1000 =...
Selection of frequency setpoint * (enters the frequency setpoint source) 1 MOP setpoint 2 Analog setpoint 3 Fixed frequency 4 USS on BOP link 5 USS on COM link (control terminals 29 and 30) 6 CB on COM link (CB = communications module) 10 No main setpoint + MOP setpoint 11 MOP setpoint + MOP setpoint 12 Analog setpoint + MOP setpoint
... 76 CB on COM link + Analog setpoint 2 77 Analog setpoint 2 + Analog setpoint 2
MOP
ADC
FF
USSBOP link
USSCOM link
CBCOM link
ADC2
P1000 = 12
P1000 = 12
Sequence control
Mainsetpoint
Setpointchannel
Motorcontrol
Additonalsetpoint
P1080 =...
Min. frequency (enters the minimum motor frequency in Hz) Sets minimum motor frequency at which motor will run irrespective of frequency setpoint. The value set here is valid for both clockwise and anticlockwise rotation.
P1082 =...
Max. frequency (enters the maximum motor frequency in Hz) Sets maximum motor frequency at which motor will run irrespective of the frequency setpoint. The value set here is valid for both clockwise and anticlockwise rotation.
P1120 =...
Ramp-up time (enters the ramp-up time in s) Time taken for motor to accelerate from standstill up to maximum motor frequency (P1082) when no rounding is used. If a ramp-up time is parameterized which is too low, then this can result in alarm A0501 (current limit value) or the drive inverter being shutdown with fault F0001 (overcurrent).
P1121 =...
Ramp-down time (enters the deceleration time in s) Time taken for motor to decelerate from maximum motor frequency (P1082) down to standstill when no rounding is used. If the ramp-down time is parameterized toolow, then this can result in alarms A0501 (current limit value), A0502 (overvoltage limit value) or the drive inverter being powered-down with fault F0001 (overcurrent) or F0002 (overvoltage).
2
0.00 Hz
50.00 Hz
10.00 s
10.00 s
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 87
P1135 =...
OFF3 ramp-down time (enters the fast stop ramp-down time in s) Enters the time, for example, with which the motor should be braked from the maximum frequency P1082 down to standstill for an OFF3 command (fast stop). If the ramp-down time is parameterized too low, then this can result in alarms A0501 (current limit value), A0502 (overvoltage limit value) or the drive inverter being shutdown with fault F0001 (overcurrent) or F0002 (overvoltage).
P1300 =...
Control mode (enters the required control mode) 0 V/f with linear characteristic 1 V/f with FCC 2 V/f with parabolic characteristic 3 V/f with programmable characteristic 5 V/f for textile applications 6 V/f with FCC for textile applications 19 V/f control with independent voltage setpoint 20 Sensorless Vector control 21 Vector control with sensor 22 Sensorless Vector torque-control 23 Vector torque-control with sensor
Selection of torque setpoint * (enters the source for the torque setpoint) 0 No main setpoint 2 Analog setpoint
4 USS on BOP link 5 USS on COM link (control terminals 29 and 30) 6 CB on COM link (CB = communications module) 7 Analog setpoint 2
Select motor data identification * (refer to Section 0) 0 Disabled
Speed controller optimization * 0 Inhibited In order to optimize the speed controller, the closed-loop vector control (P1300 = 20 or 21) must be activated. After the optimization has been selected (P1960 = 1), Alarm A0542 is displayed.
End of quick commissioning (start of the motor calculation) 0 No quick commissioning (no motor calculations) 1 Motor calculation and reset of all of the other parameters, which are not
included in the quick commissioning (attribute "QC" = no), to the factory setting
2 Motor calculation and reset of the I/O settings to the factory setting 3 Only motor calculation. The other parameters are not reset. NOTE For P3900 = 1,2,3 → P0340 is internally set to 1 and the appropriate data calculated (refer to Section 3.5.4).
END
End of the quick commissioning/drive setting If additional functions must be implemented at the drive inverter, please use the Section "Commissioning the application" (refer to Section 3.5.7). We recommend this procedure for drives with a high dynamic response.
0 P1500 =...
0 P3900 = 1
P1910 = ...
P1960 = ...
0
0
5.00 s
0
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 88 6SE6400-5AW00-0BP0
WARNING The motor data identification routine (refer to Section 0) may not be used for loads which are potentially hazardous (e.g. suspended loads for crane applications). Before the motor data identification run is started, the potentially hazardous load must be carefully secured (e.g. by lowering the load to the floor or by clamping the load using the motor holding brake).
3.5.4 Calculating the motor / control data
The calculation of the internal motor / control data is initiated using parameter P0340 or indirectly using parameter P3900 (refer to Section 3.5.3) or P1910 (refer to Section 0). The functionality of parameter P0340 can, for example, be used if the equivalent circuit diagram data (refer to Fig. 3-26) or the moment of inertia is known. Possible settings for parameter P0340 are described in Table 3-9. Table 3-10 lists which parameters are calculated for the different settings.
Table 3-9 Possible settings for parameter P0340
Parameter Description P0340 = 0 No calculation is made
P0340 = 1 Starting from the rating plate parameters (P0300 - P0335) the motor equivalent circuit diagram parameters (P0350 - P0369) and the motor weight / moment of inertia (P0344, P0341) are determined. The V/f- / vector control parameters and reference quantities are then pre-assigned (this includes all calculations from P0340 = 2,3,4).
P0340 = 2 Starting from the rating plate parameters, the motor equivalent circuit diagram parameters (P0350 - P0369) are calculated (without any additional pre-assignments being made).
P0340 = 3 Starting from the motor equivalent circuit diagram parameters (P0350 - P0369) and motor weight / moment of inertia, moment of inertia ratio (P0344, P0341, P0342), the V/f- / vector control parameters are determined (contains all of the calculations from P0340 = 4).
P0340 = 4 Starting from the motor equivalent circuit diagram parameters (P0350 - P0369) and motor weight / moment of inertia, moment of inertia ratio (P0344, P0341, P0342), the vector control parameters are pre-assigned.
NOTE
When exiting the quick commissioning with P3900 > 0 (refer to Section 3.5.3), internally P0340 is set to 1 (complete parameterization).
For the motor data identification (refer to Section 0), after the measurement has been completed, internally P0340 is set to 3.
Equivalent circuit diagram data always refer to the star circuit configuration equivalent circuit diagram. If data for the delta equivalent circuit diagram are available, then this should first be converted into the star equivalent circuit diagram data before being entered.
If equivalent circuit diagram data (P0350, . . ., P0360) is available, then this must be entered according to the motor circuit configuration being used (a star circuit configuration requires star-type equivalent circuit diagram data). If there is no consistency between the motor circuit configuration and the equivalent circuit diagram data, then the equivalent circuit diagram data should be converted according to the motor circuit configuration actually being used (P0350∆ = P0350Y, etc.).
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 89
Table 3-10 Calculated parameters
P0341[3] Motor inertia [kg*m^2]
P0344[3] Motor weight
P1521[3] CO: Lower torque limit
P1531[3] Regenerative power limitation
P2002[3] Reference current
P2174[3] Torque threshold M_thresh
P2186[3] Lower torque threshold 1
P0342[3] Total/motor inertia ratio
P1520[3] CO: Upper torque limit
P1530[3] Motoring power limitation
P2000[3] Reference frequency
P2003[3] Reference torque
P2185[3] Upper torque threshold 1
P2187[3] Upper torque threshold 2
P0350[3] Stator resistance (line-to-line)
P0354[3] Rotor resistance
P0358[3] Rotor leakage inductance
P0362[3] Magnetizing curve flux 1
P0364[3] Magnetizing curve flux 3
P0366[3] Magnetizing curve imag 1
P0368[3] Magnetizing curve imag 3
P0352[3] Cable resistance
P0356[3] Stator leakage inductance
P0360[3] Main inductance
P0363[3] Magnetizing curve flux 2
P0365[3] Magnetizing curve flux 4
P0367[3] Magnetizing curve imag 2
P0369[3] Magnetizing curve imag 4P0625[3] Ambient motor temperature
P0346[3] Magnetization time
P1253[3] Vdc-controller output limitation
P0347[3] Demagnetization time
P1316[3] Boost end frequencyP1460[3] Gain speed controller
P1470[3] Gain speed controller (SLVC)
P1715[3] Gain current controller
P1764[3] Kp of n-adaption (SLVC)
P1462[3] Integral time speed controller
P1472[3] Integral time n-ctrl. (SLVC)
P1717[3] Integral time current controller
P1767[3] Tn of n-adaption (SLVC)
xxx
xx
xxx
xx
xxx
xx
xxx
xx
xxxx
xxx
xx
xxx
xxx
xx
xxxx
P0340 = 1
xxx
xx
xxx
xx
xxx
xx
P0340 = 2
xx
xxxx
xx
xx
xx
P0340 = 3
xx
xx
xx
xx
P0340 = 4
P2188[3] Lower torque threshold 2 xP2189[3] Upper torque threshold 3P2190[3] Lower torque threshold 3
xx
When calculating the motor / control data using P0340, there are different scenarios (refer to the following flowchart), which can be called-up as a function of the known data.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 90 6SE6400-5AW00-0BP0
Factory setting
Calculation of motor parameters This parameter is required during commissioning in order to optimize the operating behavior of the drive inverter. For the complete parameterization (P0340 = 1), in addition to the motor / control parameters, parameters are pre-assigned which refer to the rated motor data (e.g. torque limits and reference quantities for interface signals). A list of the parameters, which are calculated, depending on the setting of P0340, are included in the parameter list. 0 No calculation 1 Complete parameterization 2 Calculation of equivalent circuit data 3 Calculation of V/f and Vector control data 4 Calculation of controller settings only
no yes
Motor inertia [kgm2]
Total/motor inertia ratio
Motor weight (entered in kg)
no yes
Calculation of motor parameters 4 Calculates the controller setting (refer to parameter P0340)
Stator resistance (line-to-line) (entered in Ω) Stator resistance in Ω of the motor which is connected (from line-to-line). This parameter value also includes the cable resistance.
Rotor resistance (entered in Ω) Defines the rotor resistance of the motor equivalent diagram (phase value).
Stator leakage inductance (entered in mH) Defines the stator leakage inductance of the motor equivalent diagram (phase value).
Rotor leakage inductance (entered in mH) Defines the rotor leakage inductance of the motor equivalent diagram (phase value).
Main inductance (entered in mH) Defines the main (magnetizing) inductance of the motor equivalent diagram (phase value).
Calculation of motor parameters 3 Calculation of V/f and Vector control All of the parameters, dependent on the ECD data are calculated and, in addition, the controller settings (P0340 = 4).
The motor parameters have been calculated and it is now possible to return to the additional parameterization in the Section 3.5.7 "Commissioning the application".
P0342 = ...
P0344 = ...
P0341 = ...
P0354 = ...
P0356 = ...
P0358 = ...
P0360 = ...
P0340 = 3
Additional Cata-log and/or ECD data known ?
P0350 = ...
END
ECD data known ?
P0340 = 4
P0340 = 1
START
0
FU-spez.
FU-spez.
FU-spez.
0
FU-spez.
FU-spez.
FU-spez.
FU-spez.
FU-spez.
0
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 91
3.5.5 Motor data identification MICROMASTER has a measuring technique which is used to determine the motor parameters:
Equivalent circuit data (ECD, refer to Fig. 3-26) → P1910 = 1 Magnetizing characteristic (refer to Fig. 3-27) → P1910 = 3
For control-related reasons, we absolutely recommend that the motor data identification is carried-out as, starting from the rating plate data, it is only possible to estimate the equivalent circuit data, the motor cable resistance, the IGBT let-through voltage and the compensation of IGBT interlocking times. For example, the stator resistance is extremely important for the stability of the closed-loop Vector control and for the voltage boost for the V/f characteristic. The motor data identification routine should be executed, especially if long feeder cables or if third-party motors are being used.
If the motor data identification routine is being started for the first time, then the following data (refer to Fig. 3-26) is determined, starting from the rating plate data (rated [nominal] data) with P1910 = 1:
Equivalent circuit data Motor cable resistance IGBT on-state voltage and compensation of IGBT gating dead times
The rating plate data represent the initialization values for the identification. This is the reason that it is necessary to have correct and consistent input of the rating plate data when determining the data specified above (refer to Section 3.5.8).
Cable resistance0.0 ... 120.0 [Ohm]
P0352.D (0.0)
Stator leak.induct0.00001 ... 1000.00000
P0356.D (10.00000)
L?S
Rotor leak.induct.0.0 ... 1000.0
P0358.D (10.0)
L?R
LM
Main inductance0.0 ... 3000.0
P0360.D (10.0)
Rotor resistance0.0 ... 300.0 [Ohm]
P0354.D (10.0)
RR
On-state voltage0.0 ... 20.0 [V]
P1825 (1.4)
Gating dead time0.00 ... 3.50 [us]
P1828 (0.50)
MotorCableInverter
Stator res. (L2L)0.00001 ... 2000.00000 [Ohm]
P0350.D (4.00000)
C
R
Cable
Cable RS
CableP0350 = 2(R + RS)
Fig. 3-26 Equivalent circuit diagram (ECD)
In addition to the equivalent circuit data, the motor magnetizing characteristic (refer to Fig. 3-26) can be determined using the motor data identification (P1910 = 3). If the motor-drive inverter combination is operated in the field-weakening range, then this characteristic should be determined, especially when Vector control is being used. As a result of this magnetizing characteristic, MICROMASTER can, in the field-weakening range, more precisely calculate the current which is generating the field and in turn achieve a higher torque accuracy.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 92 6SE6400-5AW00-0BP0
0 P0366 P0367 100 % P0368 P0369 iµ [%]
P0362
P0363100 %P0364P0365
Φ [%]
r0331 [A]i [%]i µ
µ =
Fig. 3-27 Magnetizing characteristic
After selecting the motor data identification using parameter P1910, alarm A0541 is immediately generated. The motor identification routine is started by the ON command and different excitation signals are impressed in the motor (DC and AC voltages). This measurement is carried-out with the motor at a standstill and it takes, including the data calculation per selection (P1910 = 1.3) between 20 s ... 4 min. The identification time depends on the motor and increases with its size (this takes approx. 4 min for a 200 kW motor).
The motor data identification routine must be carried-out with the motor in the cold condition so that the motor resistance values saved can be assigned to the parameter of the ambient temperature P0625. Only then is correct temperature adaptation of the resistances possible during operation. The motor data identification routine operates with the results of the "Complete parameterization" P0340 = 1 or the motor equivalent diagram data which was last saved. The results become increasingly better the more times that the identification routine is executed (up to 3 times).
WARNING It is not permissible to carry-out the motor identification routine for loads which
are potentially hazardous (e.g. suspended loads for crane applications). Before starting the motor data identification routine, the potentially hazardous load must be secured (e.g. by lowering the load to the floor or clamping the load using the motor holding brake).
When starting the motor data identification routine, the rotor can move into a preferred position. This is more significant for larger motors.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 93
NOTE The equivalent circuit data (P0350, P0354, P0356, P0358, P0360), with the
exception of parameter P0350, should be entered as phase values. In this case, parameter P0350 (line-to-line value) corresponds to twice the phase value.
Equivalent circuit diagram data always refer to the star circuit configuration equivalent circuit diagram data. If data for the delta equivalent circuit diagram is available, then this data must be converted into the star equivalent circuit diagram data before being entered (refer to Section 0).
The motor cable resistance P0352 is defined as phase value During the motor identification routine, the stator resistance and the motor cable
resistance are determined and entered into parameter P0350. If a correction is made in parameter P0352, then MICROMASTER defines the motor cable resistance using the following relationship: P0352 = 0.2 * P0350.
If the motor cable resistance is known, then the value can be entered into parameter P0352 after the motor data identification. The stator resistance is appropriately reduced as a result of this entry and is therefore more precisely adapted to the actual application.
It is not necessary to lock the motor rotor for the motor data identification routine. However, if it is possible to lock the motor rotor during the identification routine (e.g. by closing the motor holding brake), then this should be used to determine the equivalent circuit diagram data.
The following formula can be applied to check the correctness of the motor rating plate data:
PN = √3 ∗ VN Υ∗ INΥ ∗ cosϕ ∗ η ≈ √3 ∗ VN ∆∗ IN∆ ∗ cosϕ ∗ η with PN rated motor power
VN Υ, VN ∆ rated motor voltage (star / delta) IN Υ, IN ∆ rated motor current (star / delta) cosϕ power factor η efficiency
Motor data identification routine
Factory setting
Ambient motor temperature (entered in °C) The motor ambient temperature is entered at the instant that motor data is being determined (factory setting: 20 °C).
yes no
The difference between the motor temperature and the motor ambient temperature P0625 must lie in the tolerance range of approx. ± 5 °C. If this is not the case, then the motor data identification routine can only be carried-out after the motor has cooled down.
START
P0625 = ? 20 °C
| Motor temp. - P0625| ≤ 5 °C ?
Allow the motor to cool down
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 94 6SE6400-5AW00-0BP0
Select motor data identification with P1910 = 1 p1910 = 1: Identifies the motor parameter with parameter change.
These are accepted and applied to the controller. When p1910 = 1 is selected, Alarm A0541 (motor data identification active) is output, and internally p0340 is set to 3.
Starts the motor data identification run with p1910 = 1 The measuring operation is initiated with the continuous (steady-state) ON command. The motor aligns itself and current flows through it. Diagnostics is possible using r0069 (CO: Phase current).
After the motor data identification routine has been completed, p1910 is reset (p1910 = 0, motor data identification routine inhibited) and Alarm A0541 is cleared (deleted).
In order to set the frequency converter into a defined state, an OFF1 command must be issued before the next step.
Select motor data identification with P1910 = 3 p1910 = 3: Identifies the saturation characteristic with parameter change. When p1910 = 3 is selected, Alarm A0541 (motor data identification active) is output and internally, p0340 is set to 2.
Starts the motor data identification run with P1910 = 3 The measuring operation must be started with a continuous ON command.
After the motor identification routine has been completed, p1910 is reset (p1910 = 0, motor data identification routine inhibited) and Alarm A0541 is cleared (deleted).
In order to set the frequency converter into a defined state, an OFF1 command must be issued before the next step.
If problems occur during the identification run, e.g. the current controller oscillates, then the rating plate data should be re-checked and an approximately correct magnetizing current P0320 entered. The motor data identification routine should then be re-started by calling P0340 = 1 (refer to Section 3.5.4).
P1910 = 1 0
A0541
ON
OFF1
P1910 = 3 0
A0541
ON
OFF1
END
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 95
3.5.6 Magnetizing current The value of the magnetizing current r0331/P0320 has a significant influence
on the closed-loop control. This cannot be measured at standstill. This means that the value is estimated for standard 4-pole 1LA7 SIEMENS standard using the automatic parameterization P0340=1 (P0320=0; result in r0331).
If the deviation of the magnetizing current is too high, then the values for the magnetizing reactance and those of the rotor resistance will not be able to be accurately determined.
Especially for third-party motors it is important that the magnetizing current that is determined, is carefully checked and if required, appropriately corrected.
The procedure to manually determine the magnetizing current and to re-calculate the equivalent circuit diagram data when the drive is operated with closed-loop vector control (P1300 = 20/21) is shown in the following.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 96 6SE6400-5AW00-0BP0
Quick commissioning routine Using the quick commissioning routine the frequency inverter is adapted to the motor and important technology parameters are set.
Motor data identification routine Using the motor data identification routine motor equivalent circuit diagram data is determined using a measuring technique.
Determing the magnetizing current In order to determine the magnetizing current (P0320/r0331), the motor should be accelerated up to approximately 80% of its rated speed under no-load operating conditions. In so doing, the following conditions must be carefully maintained:
− the vector control must be activated, P1300 = 20.21 − no field weakening (r0056.8 = 0) − flux setpoint, r1598 = 100 % − no efficiency optimization, P1580 = 0 %
No-load operation means that the motor is operated without a load (i.e. no coupled driven machine).
Under steady-state conditions, a current r0027 is obtained that approximately corresponds to the rated magnetizing current r0331. (the current is always less than the no-load current for a pure V/f control).
no yes
Measuring and entering the magnetizing current and therefore the associated new calculation of the equivalent circuit diagram data of the motor is an iterative procedure. It must be repeated at least 2-3 times until the following criteria are fulfilled:
− The more accurate the value of the magnetizing current that was entered, the better the flux setpoint (r1598=100%) matches the flux actual value (r0084=96..104%) of the observer model.
− The output Xm adaptation (r1787) of the observer model should be as low as possible. Good values lie between 1-5%. The less that the Xh adaptation of the observer must operate, the sensitivity of the motor parameters after power failures are that much less sensitive.
NOTE In order to display r0084 at the BOP/AOP, the LEVEL 4 parameters must be enabled using service parameter P3950=46.
Calculating P0320 Now, the new value can be entered in P0320 from the determined flux-generating current component r0029 by applying the following equation. P0320 = r0029 * 100 / P0305
Calculating the motor parameters The values of the motor equivalent circuit diagram data are calculated from the entered rating plate data. In addition, the parameters of the controls are pre-set (subsequently optimized) (P0340 = 3).
START
Quick commissioning
0
END
Motor data identificationdentif
Operation under no-load conditions
P0320 = ... 0
P0340 = 1
Criterium fulfilled ?
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 97
3.5.7 Commissioning the application After the motor – drive inverter combination was commissioned using the quick or series commissioning, in the following step parameters should be adapted and set according to the technological requirements. As an example, the following points should be considered:
Functional requirements of the drive inverter (e.g. closed-loop process control with PID controller)
Limit values Dynamic requirements Starting torques Load surge requirement Overload Diagnostics
If the application includes a function, which is not covered by the quick or series commissioning, then the following sections of the function description or the parameter list should be considered.
Adapting the drive inverter to the application The parameters designated with * offer more setting possibilities than are listed here. Refer to the parameter list for additional setting possibilities.
Factory setting
P0003 = 3
User access level * 1 Standard: Allows access into most frequently used parameters 2 Extended: Allows extended access e.g. to inverter I/O functions 3 Expert (For expert use only)
3.5.7.1 Serial Interface (USS)
P2010 =... USS baud rate Sets baud rate for USS communication.
P2011 =... USS address Sets unique address for inverter.
P2012 =... USS PZD length Defines the number of 16-bit words in PZD part of USS telegram.
P2013 =... USS PKW length Defines the number of 16-bit words in PKW part of USS telegram.
Possible Settings: 4 2400 Baud 5 4800 Baud 6 9600 Baud 7 19200 Baud 8 38400 Baud 9 57600 Baud 10 76800 Baud 11 93750 Baud 12 115200 Baud
START
1
6
0
2
127
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 98 6SE6400-5AW00-0BP0
3.5.7.2 Selection of command source
P0700 =...
Selection of command source Selects digital command source. 0 Factory fault setting 1 BOP (keypad) 2 Terminal 4 USS on BOP link 5 USS on COM link 6 CB on COM link
P0700 = 2Sequence control
Setpointchannel
Motorcontrol
BOP
USSBOP link
USSCOM link
Terminals
CBCOM link
3.5.7.3 Digital input (DIN)
Function digital input 1 Terminal 5 1 ON / OFF1
Function digital input 2 Terminal 6 12 Reverse
Function digital input 3 Terminal 7 9 Fault acknowledge
Function digital input 4 Terminal 8 15 Fixed setpoint (Direct selection)
Function digital input 5 Terminal 16 15 Fixed setpoint (Direct selection)
Function digital input 6 Terminal 17 15 Fixed setpoint (Direct selection)
Possible Settings: 0 Digital input disabled 1 ON / OFF1 2 ON + Reverse / OFF1 3 OFF2 – coast to standstill 4 OFF3 – quick ramp-down 9 Fault acknowledge 10 JOG right 11 JOG left 12 Reverse 13 MOP up (increase frequency) 14 MOP down (decrease frequency) 15 Fixed setpoint (Direct selection) 16 Fixed setpoint (Direct selection + ON) 17 Fixed setpoint (Binary coded selection + ON) 21 Local/remote 25 DC brake enable 29 External trip 33 Disable additional freq setpoint 99 Enable BICO parameterization
Function digital input 7 Via analog input, Terminal 3 0 Digital input disabled
Function digital input 8 Via analog input, Terminal 10 0 Digital input disabled
DIN8DIN7ON > 3,9 V, OFF < 1,7 V
12
1011
1234
Debounce time for digital inputs Defines debounce time (filtering time) used for digital inputs. 0 No debounce time 1 2.5 ms debounce time 2 8.2 ms debounce time 3 12.3 ms debounce time
PNP / NPN digital inputs Change-over (toggles) between high active (PNP) and low active (NPN). This applies to all digital inputs simultaneously. 0 NPN mode ==> low active 1 PNP mode ==> high active
15 P0706 = ...
15 P0705 = ...
1
12
9
15
P0701 = ...
P0703 = ...
P0702 = ...
P0704 = ...
3 P0724 = ...
P0725 = ... 1
0 P0707 = 0
0 P0708 = 0
2
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 99
DIN channel (e.g. DIN1 - PNP (P0725 = 1))
24 V T 0
&0
1
PNP/NPN DIN0 ... 1
P0725 (1)
0 V
24 VDebounce time: DIN
0 ... 3P0724 (3)
CO/BO: Bin.inp.valr0722r0722
.0
Kl.9P24 (PNP)Kl.280 V (NPN)
Pxxxx BI: ...
P0701
Function0
1
3.5.7.4 Digital output (DOUT)
BI: Function of digital output 1 * Defines source of digital output 1.
BI: Function of digital output 2 * Defines source of digital output 2.
BI: Function of digital output 3 * Defines source of digital output 3.
Invert digital output Defines high and low states of relay for a given function.
Common Settings: 52.0 Drive ready 0 52.1 Drive ready to run 0 52.2 Drive running 0 52.3 Drive fault active 0 52.4 OFF2 active 1 52.5 OFF3 active 1 52.6 Switch on inhibit active 0 52.7 Drive warning active 0 52.8 Deviation, setpoint / actual value 1 52.9 Control from PLC (PZD control) 0 52.A Maximum frequency reached 0 52.B Alarm: Motor current limiting 1 52.C Motor holding brake (MHB) active 0 52.D Motor overload 1 52.E Motor direction of rotation, clockwise 0 52.F Frequency inverter overload 1 53.0 DC brake active 0 .
(52:3)
BI: Fct. of DOUT 1P0731.C
-1
0
1
Invert DOUTs0 ... 7
P0748 (0) CO/BO: State DOUTs
r0747r0747
Kl.20
Kl.18
.0
Functionxxxx.y rxxxx.y
P0731 = xxxx.y
DOUT channel
Relay :DC 30 V / 5 AAC 250 V / 2 A
Kl.28
Kl.9
int. 24 Vmax. 100 mA
NO
COM
NC
Kl.19or
Text
max. opening / closing time5 / 10 ms
52.3
0
P0731 = ...
52.7
0.0
P0748 = ...
P0733 = ...
P0732 = ...
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 100 6SE6400-5AW00-0BP0
3.5.7.5 Selection of frequency setpoint
P1000 =...
Selection of frequency setpoint 0 No main setpoint 1 MOP setpoint 2 Analog setpoint 3 Fixed frequency 4 USS on BOP link 5 USS on COM link 6 CB on COM link 7 Analog setpoint 2 10 No main setpoint + MOP setpoint 11 MOP setpoint + MOP setpoint 12 Analog setpoint + MOP setpoint
... 76 CB on COM link + Analog setpoint 2 77 Analog setpoint 2 + Analog setpoint 2
NOTE In addition to the main setpoint, a supplementary setpoint can be entered using P1000
P1000 = 12 ? P1070 = 755P1070 CI: Main setpoint
r0755 CO: Act. ADC after scal. [4000h]
P1000 = 12 ? P1075 = 1050P1075 CI: Additional setpoint
r1050 CO: Act. Output freq. of the MOP
Example P1000 = 12 :
MOP
ADC
FF
USSBOP link
USSCOM link
CBCOM link
ADC2
P1000 = 12
P1000 = 12
Sequence control
Mainsetpoint
Setpointchannel
Motorcontrol
Additonalsetpoint
BI: Disable additional setpoint Deaktiviert den Zusatzsollwert (ZUSW).
CI: Additional setpoint Defines the source of the additional setpoint which is added to the main setpoint. Common settings: 755 Analog input setpoint 1024 Fixed frequency setpoint 1050 MOP setpoint
CI: Additional setpoint scaling Defines the source to scale the additional setpoint. Common settings: 1 Scaling of 1.0 (100 %) 755 Analog input setpoint 1024 Fixed frequency setpoint 1050 MOP setpoint
P1074 = ...
P1075 = ...
P1076 = ...
0:0
0:0
1:0
2
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 101
3.5.7.6 Analog input (ADC)
ADC type Defines the analog input type and activates the monitoring function of the analog input.
0 Unipolar voltage input (0 to +10 V) 1 Unipolar voltage input with monitoring (0 to 10 V) 2 Unipolar current input (0 to 20 mA) 3 Unipolar current input with monitoring (0 to 20 mA) 4 Bipolar voltage input (-10 to +10 V) NOTE For P0756 to P0760, the following applies: Index 0 : Analog input 1 (ADC1), terminals 3, 4 Index 1 : Analog input 2 (ADC2), terminals 10, 11
P0757 =... Value x1 of ADC scaling
P0758 =... Value y1 of ADC scaling This parameter represents the value of x1 as a % of P2000 (reference frequency).
P0759 =... Value x2 of ADC scaling
P0760 =... Value y2 of ADC scaling This parameter represents the value of x2 as a % of P2000 (reference frequency).
P0761 =... Width of ADC deadband Defines width of deadband on analog input.
ASPmax
100 %
10 V20 mA
V mAx100%
%
P0760
P0758
P0759
P0761 > 00 < P0758 < P0760 || 0 > P0758 > P0760
ASPmin
P0757P0761
P0757 = P0761
4000 h
Delay, ADC signal loss Defines the delay time between the loss of the analog setpoint and fault message F0080 being displayed.
KL4
KL3
DIP switch
AD
ADCtype
ADCscaling
P07
57P
0758
P07
59P
0760
ADCdeadzone
r0755 Pxxxx
r0752
P1000
ADC−
ADC+
r0754P0761P0753P0756
ADCtype
Setpoint
ADC channel
Wirebreakagesensing
P0756 P0761
r0751
F0080
r0722r0722.6
0
1 1.7 V
3.9 V P0707Pxxxx
Function
T 0
P0762
P0756 = ... 0
P0762 = ... 10 ms
0 V
0.0 %
10 V
100.0 %
0 V
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 102 6SE6400-5AW00-0BP0
3.5.7.7 Analog output (DAC)
CI: DAC Defines function of the 0 - 20 mA analog output. 21 CO: Output frequency (scaled according to P2000) 24 CO: Frequency inverter output frequency (scaled according to P2000) 25 CO: Output voltage (scaled according to P2001) 26 CO: DC link voltage (scaled according to P2001) 27 CO: Output current (scaled according to P2002) NOTE For P0771 to P0781, the following applies: Index 0 : Analog output 1 (DAC1), terminals 12, 13 Index 1 : Analog output 2 (DAC2), terminals 26, 27
P0773 =... Smooth time DAC Defines smoothing time [ms] for analog output signal. This parameter enables smoothing for DAC using a PT1 filter.
Permit absolute value Decides if the absolute value of the analog output is used. If enabled, this parameter will take the absolute value of the value to be outputed. If the value was originally negative then the corresponding bit in r0785 is set, otherwise it is cleared. 0 OFF 1 ON
DAC type Defines the analog output type. 0 Current output 1 Voltage output NOTE • P0776 changes the scaling of r0774 (0 – 20 mA ⇔ 0 – 10 V) • Scaling parameters P0778, P0780 and the dead zone are always entered in 0 – 20 mA For the DAC as voltage output, the DAC outputs must be terminated using a 500 Ω resistor
Value x1 of DAC scaling Defines the output characteristic value x1 as a %. This parameter represents the lowest analog value as a % of P200x (depending on the setting of P0771).
Value y1 of DAC scaling This parameter represents the value for x1 in mA.
Value x2 of DAC scaling Defines the output characteristic value x2 as a %. This parameter represents the lowest analog value as a % of P200x (depending on the setting of P0771).
20
P0780y2
P0778y1
P0777x1
P0779x2
100 %
mA
P0781
%
Value y2 of DAC scaling This parameter represents the value for x2 in mA.
Width of DAC deadband Sets width of deadband in [mA] for analog output.
21 P0771 = ...
P0776 = ... 0
0.0 %
0
100.0 %
P0777 = ...
P0778 = ...
P0779 = ...
20 P0780 = ...
0 P0781 = ...
2 ms
P0775 = ...
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 103
3.5.7.8 Motor potentiometer (MOP)
P1031 =...
Setpoint memory of the MOP Saves last motor potentiometer setpoint (MOP) that was active before OFF command or power down. 0 MOP setpoint will not be stored 1 MOP setpoint will be stored (P1040 is updated)
P1032 =...
Inhibit negative MOP setpoints 0 Neg. MOP setpoint is allowed 1 Neg. MOP setpoint inhibited
P1040 =... Setpoint of the MOP Determines setpoint for motor potentiometer control.
MOP ramp-up and ramp-down times are defined by the parameters P1120 and P1121.
Selection
DIN
BOP UP button
USS control wordr2032 Bit13
USS control wordr2032 Bit14
or
P0702 = 13(DIN2)
P0703 = 14(DIN3)
P0719 = 0, P0700 = 1, P1000 = 1
MOP up MOP down
P0719 = 1, P0700 = 2or
P0719 = 0, P0700 = 2, P1000 = 1
P0719 = 11
orP0719 = 0, P0700 = 4, P1000 = 1
P0719 = 41
DOWN button
Possible parameter settings for the selection of MOP:
USS onBOP link
USS control wordr2036 Bit13
USS control wordr2036 Bit14
orP0719 = 0, P0700 = 5, P1000 = 1
P0719 = 51USS onCOM link
CB control wordr2090 Bit13 r2090 Bit14
orP0719 = 0, P0700 = 6, P1000 = 1
P0719 = 61CB CB control word
0
1
5.00 Hz
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 104 6SE6400-5AW00-0BP0
3.5.7.9 Fixed frequency (FF)
Fixed frequency 1 Can be directly selected via DIN1 (P0701 = 15, 16)
Fixed frequency 2 Can be directly selected via DIN2 (P0702 = 15, 16)
Fixed frequency 3 Can be directly selected via DIN3 (P0703 = 15, 16)
Fixed frequency 4 Can be directly selected via DIN4 (P0704 = 15, 16)
Fixed frequency 5 Can be directly selected via DIN5 (P0705 = 15, 16)
Fixed frequency 6 Can be directly selected via DIN6 (P0706 = 15, 16)
Fixed frequency 7
Fixed frequency 8
Fixed frequency 9
Fixed frequency 10
Fixed frequency 11
Fixed frequency 12
Fixed frequency 13
Fixed frequency 14
Fixed frequency 15
When defining the function of the digital inputs (P0701 to P0703), three different types can be selected for fixed frequencies: 15 = Direct selection (binary-coded)
In this particular mode, the appropriate digital input always selects the associated fixed frequency, e.g.: Digital input 3 = selects fixed frequency 3. If several inputs are simultaneously active, then these are summed. An ON command is additionally required.
16 = Direct selection + ON command (binary-coded + On / Off1) In this mode, the fixed frequencies are selected as for 15, however these are combined with an ON command.
17 = Binary coded selection + ON command (BCD-coded + On/ Off1)
The BCD-coded operating mode is effective for digital inputs 1 to 3.
Fixed frequency code - Bit 0 Defines the selection method for fixed frequencies.
Fixed frequency code - Bit 1
Fixed frequency code - Bit 2
Fixed frequency code - Bit 3
1 Direct selection 2 Direct selection + ON command 3 Binary coded selection + ON command NOTE For settings 2 and 3, all parameters P1016 to P1019 must be set to the selected value so that the drive inverter accepts the ON command.
Fixed frequency code - Bit 4
Fixed frequency code - Bit 5
1 Direct selection 2 Direct selection + ON command
1
1
1
P1016 = ...
P1017 = ...
P1018 = ...
1 P1019 = ...
1 P1025 = ...
1 P1027 = ...
5.00 Hz
10.00 Hz
15.00 Hz
20.00 Hz
25.00 Hz
0.00 HzP1001 = ...
P1002 = ...
P1003 = ...
P1004 = ...
P1005 = ...
P1006 = ...
30.00 HzP1007 = ...
P1008 = ... 35.00 Hz
P1009 = ... 40.00 Hz
P1010 = ... 45.00 Hz
P1011 = ... 50.00 Hz
P1012 = ... 55.00 Hz
P1013 = ... 60.00 Hz
P1014 = ... 65.00 Hz
P1015 = ... 65.00 Hz
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 105
3.5.7.10 JOG
JOG frequency right Frequency in Hz when the motor is rotating clockwise in the jog mode.
JOG frequency left Frequency in Hz when the motor is rotating counter-clockwise in the jog mode.
JOG ramp-up time Ramp-up time in s from 0 to the maximum frequency (p1082). JOG ramp-up is limited by p1058 or p1059.
JOG ramp-down time Ramp-down time in s from the maximum frequency (p1082) to 0.
p1082(fmax)
p1058
tp1060 p1061
f
JOG
Tippen rechts
f
P1058
P1059
A0923 A0923P
1060
P10
60(0)
P1055
(0)P1056
"1"
"0"
"1"
"0"
t
t
t
P10
61DIN
BOP
USSBOP link
USSCOM link
CBCOM link
Tippen links
P1082
-P1082
P10
61
p1058 = ...
p1059 = ...
p1060 = ...
p1061 = ...
5.00 Hz
5.00 Hz
10.00 s
10.00 s
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 106 6SE6400-5AW00-0BP0
3.5.7.11 Ramp function generator (RFG)
Skip frequency 1 (entered in Hz) Defines skip frequency 1, which avoids effects of mechanical resonance and suppresses frequencies within +/- p1101 (skip frequency bandwidth).
Skip frequency 2
Skip frequency 3
Skip frequency 4
Skip frequency bandwidth (entered in Hz)
p1101
p1091fin
fout
Skip frequencybandwidth
Skip frequency
Ramp-up time (enters the accelerating time in s)
Ramp-down time (enters the deceleration time in s)
fp1082(fmax)
f1
tp1120 p1121
Rump-up initial rounding time (entered in s)
Ramp-up final rounding time (entered in s)
Rump-down initial rounding time (entered in s)
Ramp-down final rounding time (entered in s)
Rounding type 0 Continuous smoothing 1 Discontinuous smoothing
The rounding times are recommended as abrupt responses can be avoided therefore reducing stress and damage to the mechanical system. The ramp-up and ramp-down times are extended by the component of the rounding ramps.
OFF3 ramp-down time Defines ramp-down time from maximum frequency to standstill for OFF3 command.
2.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
p1091 = ...
p1092 = ...
p1093 = ...
p1094 = ...
p1101 = ...
p1120 = ...
p1121 = ...
p1130 = ...
p1131 = ...
p1132 = ...
p1133 = ...
p1134 = ...
p1135 = ...
10.00 s
10.00 s
0.00 s
0.00 s
0.00 s
0
5.00 s
0.00 s
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 107
3.5.7.12 Reference/limit frequencies
Min. frequency (entered in Hz) Sets minimum motor frequency [Hz] at which motor will run irrespective of frequency setpoint. If the setpoint falls below the value of p1080, then the output frequency is set to p1080 taking into account the sign.
Max. frequency (entered in Hz) Sets maximum motor frequency [Hz] at which motor will run irrespective of the frequency setpoint. If the setpoint exceeds the value p1082, then the output frequency is limited. The value set here is valid for both clockwise and anticlockwise rotation.
Reference frequency (entered in Hz) The reference frequency in Hertz corresponds to a value of 100 %. This setting should be changed if a maximum frequency of higher than 50 Hz is required. It is automatically changed to 60 Hz if the standard 60 Hz frequency was selected using p0100. NOTE This reference frequency effects the setpoint frequency as both the frequency setpoints via USS as well as via PROFIBUS (FB100) (4000H hex 100 % p2000) refer to this value.
Reference voltage (entered in V) The reference voltage in Volt (output voltage) corresponds to a value of 100 %. NOTE This setting should only be changed if it is necessary to output the voltage with a different scaling.
Reference current (entered in A) The reference current in Amps (output current) corresponds to a value of 100 %. Factory setting = 200 % of the rated motor current (P0305). NOTE This setting should only be changed if it is necessary to output the current with a different scaling.
Reference torque (entered in Nm) The reference torque in Nm corresponds to a value of 100 %. Factory setting = 200 % of the rated motor torque at a constant motor torque determined from the appropriate motor data. NOTE This setting should only be changed if it is necessary to output the torque with a different scaling.
1000 VP2001 = ...
0.10 A P2002 = ...
0.12 MnP2003 = ...
p2000 = ...
p1082 = ...
p1080 = ... 0.00 Hz
50.00 Hz
50.00 Hz
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 108 6SE6400-5AW00-0BP0
3.5.7.13 Inverter protection
Inverter overload reaction Selects reaction of inverter to an internal over-temperature. 0 Reduce output frequency 1 Trip (F0004 / F0005) 2 Reduce pulse frequency and output frequency 3 Reduce pulse frequency then trip (F0004)
A0504
A0505
A0506
F0004
F0005
Inverter overload reactionP0290
f_pulsecontrol
i_max control(U/f)
Current control(SLVC, VC)
r0036
r0037 Heat sinktemperature
P0292
IGBTtemperature
P0292
i2tP0294
Inverter monitoring
P0292 =...
Inverter temperature warning Defines the temperature difference (in ºC) between the Overtemperature trip threshold and the warning threshold of the inverter. The trip threshold is stored internally by the inverter and cannot be changed by the user.
Temperature MM440, Frame Size
110 °C
140 °C
95 °C
145 °C
A - C D - F
Input rectifier -
Cooling air -
Control board -
80 °C
145 °C
F600 V
-
-
-
-
-
-
88 °C
150 °C
FX95 kW
CT91 °C
150 °C
110 kWCT
75 °C
55 °C
75 °C
55 °C
65 °C 65 °C
80 °C
145 °C
GX132 kW
CT82 °C
147 °C
160 kWCT
75 °C
55 °C
75 °C
55 °C
65 °C 65 °C
88 °C
150 °C
200 kWCT
75 °C
50 °C
65 °C
IGBT
Heat sink
tripT = T - P0292Temperature warning threshold of inverter T_warn
Temperature shutdown threshold of inverter T_tripwarn
Delay, fan shutdown This defines the delay time in seconds between powering down the frequency inverter and then powering-down the fan. A setting of 0 means that the fan is immediately shut down (powered-down).
3.5.7.14 Motor protection
In addition to the thermal motor protection, the motor temperature is also included in the adaptation of the motor equivalent circuit diagram data. Especially for a high thermal motor load, this adaptation has a significant influence on the degree of stability of the closed-loop vector control. For MM440 the motor temperature can only be measured using a KTY84 sensor. For the parameter setting P0601 = 0,1, the motor temperature is calculated / estimated using the thermal motor model. If the frequency inverter is permanently supplied with an external 24V voltage, then the motor temperature is also tracked/corrected using the motor temperature time constant – even when the line supply voltage is switched-out.
0 s P0295 = ...
p0290 = ... 0
15 °C
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 109
A high thermal motor load and when the line supply is frequently switched-out/switched-in requires, for closed-loop vector control
− that a KTY84 sensor is used, or − an external 24V power supply voltage is connected
Motor cooling (Selects motor cooling system used) 0 Self-cooled: Using shaft mounted fan attached to motor 1 Force-cooled: Using separately powered cooling fan 2 Self-cooled and internal fan
3 Force-cooled and internal fan
Motor temperature sensor Selects the motor temperature sensor. 0 No sensor 1 PTC thermistor (PTC) 2 KTY84 When "no sensor" or "PTC thermistor (PTC)“ is selected, the motor temperature is determined on the basis of the value estimated by the thermal motor model.
r0631
ADC
5 V
Signalloss
detection
T1 = 4 s
2
1
No sensorPTCKTY
0
P0604
FaultF0015
&P0601 = 2
Thermalmotormodel
r0633
r0632
r0035
1≥Motortemp.
reaction
P0610P0601
Equivalentcircuit data
PV,mot
Power dissipation
V
ϑ
0
1
0
1
r0052Bit13
PTCKTY
Alarm threshold, motor overtemperature Defines the alarm threshold for the motor overtemperature protection. This threshold, where either a shutdown (trip) or Imax reduction is initiated (P0610) always lies 10 % above the alarm threshold.
ϑwarn :ϑtrip : Trip threshold (max. permissible temperature)
P0604 1.1 1.1 warntrip ⋅=⋅= ϑϑ Warning threshold (P0604)
The alarm threshold should be at least 40 °C greater than the ambient temperature P0625.P0604 ≥ P0625 + 40 °C
Inverter temperature reaction Defines reaction when motor temperature reaches warning threshold. 0 No reaction, warning only 1 Warning and Imax reduction (results in a lower output frequency) 2 Warning and trip (F0011)
Motor overload factor [%] Defines motor overload current limit in [%] relative to p0305 (rated motor current). Limited to maximum inverter current or to 400 % of rated motor current (p0305), whichever is the lower.
2
0 P0601 = ...
P0604 = ... 130.0 °C
P0610 = ...
0 P0335 = ...
p0640 = ... 150.0 %
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 110 6SE6400-5AW00-0BP0
3.5.7.15 Encoder
Select encoder type Selects the encoder type. 0 Inhibited 1 Single-track pulse encoder 2 Two-track pulse encoder The table shows the values of P0400 as a function of the number of tracks:
Parameter Terminal Track Encoder output
single endedP0400 = 1 A
differentialA
AN
A
B
A
AN
B
BN
differential
P0400 = 2 single ended
In order to guarantee reliable operation, the DIP switches on the encoder module must be set as follows depending on the encoder type (TTL, HTL) and encoder output:
Typedifferential
TTL
HTL
111111 010101
101010 000000
single ended
Output
(e.g.
(e.g.1XP8001-1)
1XP8001-2)
Encoder pulses per revolution Specifies the number of encoder pulses per revolution.
Reaction on speed signal loss Defines the calculation method. 0 No transition 1 Transition into SLVC
Allowed speed difference Parameter P0492 defines the frequency threshold for the loss of the encoder signal (fault F0090). CAUTION p0492 = 0 (no monitoring function): With p0492 = 0, the loss of the encoder signal at high frequency as well as at a low frequency is de-activated. As a result, the system does not monitor for the loss of the encoder signal.
P0494 =...
Delay speed loss reaction P0492 is used to detect the loss of the encoder signal at low frequencies. If the motor speed is less than the value of P0492, the loss of the encoder signal is determined using an appropriate algorithm. P0494 defines the delay time between detecting the loss of the speed signal and initiating the appropriate response. CAUTION p0494 = 0 (no monitoring function): With p0494 = 0, the loss of the encoder signal at low frequencies is de-activated. As a result, at these frequencies, a loss of the encoder signal is not detected (loss of the encoder signal at high frequency remains active as long as parameter p0492 > 0).
1024
0
10.00 Hz
10 ms
P0408 =...
P0491 =...
P0492 =...
0 P0400 =...
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 111
3.5.7.16 V/f control
P1300 =...
Control mode The control type is selected using this parameter. For the "V/f characteristic" control type, the ratio between the frequency inverter output voltage and the frequency inverter output frequency is defined. 0 V/f with linear 1 V/f with FCC 2 V/f with parabolic characteristic 3 V/f with programmable characteristic (→ P1320 – P1325)
P1310 =...
Continuous boost (entered in %) Voltage boost as a % relative to P0305 (rated motor current) and P0350 (stator resistance). P1310 is valid for all V/f versions (refer to P1300). At low output frequencies, the effective resistance values of the winding can no longer be neglected in order to maintain the motor flux.
f
Linear V/f
OFFON
t
t
f
P1310 active
t01
Validity rangeVmax
Vn(P0304)
VConBoost,100
0 fn(P0310)
f max(P1082)
V
fBoost,end(P1316)
Boost
Output voltage
actual V
Normal
V/f
(P13
00 =
0)
VConBoost,50
Boost voltage
P1311 =...
Acceleration boost (entered in %) Voltage boost for accelerating/braking as a % relative to P0305 and P0350. P1311 only results in a voltage boost when ramping-up/ramp-down and generates an additional torque for accelerating/braking. Contrary to parameter P1312, that is only active for the 1st acceleration operation after the ON command, P1311 is effective each time that the drive accelerates or brakes.
Vmax
Vn(P0304)
VAccBoost,100
0 fn(P0310)
fmax(P1082)
f
V
fBoost,end(P1316)
VAccBoost,50
Boost
U/f norm
al
(P1300 = 0)
V ist
Ausgangsspannung
OFFON
t
t
f
P1311 aktiv
t01
Boost-Spannung Gültigkeitsbereich
0
50.00 %
0.0 %
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 112 6SE6400-5AW00-0BP0
P1312 =...
Starting boost (entered in %) Voltage boost when starting (after an ON command) when using the linear or square-law V/f characteristic as a % relative to P0305 (rated motor current) or P0350 (stator resistance). The voltage boost remains active until 1) the setpoint is reached for the first time and 2) the setpoint is reduced to a value that is less than the instantaneous ramp-function
generator output.
P1320 =...
Programmable V/f freq. coord. 1 Sets V/f coordinates (P1320/1321 to P1324/1325) to define V/f characteristic.
P1321 =... Programmable. V/f volt. coord. 1
P1322 =... Programmable V/f freq. coord. 2
P1323 =... Programmable V/f volt. coord. 2
P1324 =... Programmable U/f Freq. coord. 3
P1325 =... Programmable V/f volt. coord. 3
]P0304[V100[%]
r0395[%]100[%]
P1310[%]P1310[V] ⋅⋅=
V
P1325
f1P1320
fmaxP1082
Vmaxr0071
VnP0304
P1323
P1321P1310
f00 Hz
f2P1322
f3P1324
fnP0310
f
Vmax = f(Vdc, Mmax)
Starting frequency for FCC (entered as a %) Defines the FCC starting frequency as a function of the rated motor frequency (P0310).
1333P100
P0310 fFCC ⋅=
( )%61333P100
P0310 f HysFCC +⋅=+
NOTE The constant voltage boost P1310 is continually decreased analog to switching-in FCC.
fFCCffFCC+Hys
FCC
V/fSw
itch-
over
Slip compensation (entered in %) Dynamically adjusts output frequency of inverter so that motor speed is kept constant independent of motor load.
ff
N
out
6 % 10 %
P1335
100 %
%Range of slip compensation :
P1338 =... Resonance damping gain V/f Defines resonance damping gain for V/f.
P1335 = ... 0.0 %
P1333 = ... 10.0 %
0.0 %
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.00
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 113
3.5.7.17 Field-orientated control
Limitations
Motor overload factor [%] Defines motor overload current limit in [%] relative to p0305 (rated motor current). Limited to maximum inverter current or to 400 % of rated motor current (p0305), whichever is the lower.
100 p0305
p0305) 4 (r0209, min p0640max ⋅⋅=
CO: Upper torque limit Specifies fixed value for upper torque limitation.
P1520 max
P1520 def r0333 1.5 ⋅=r0333 4 ⋅±=
CO: Lower torque limit Enters fixed value of lower torque limitation.
P1521max
P1521def r0333 1.5 ⋅−=r0333 4 ⋅±=
f 1 ~
Torque limitation
Resultanttorque limit
Powerlimitation
|fact
r1526r1527
Stalllimitation
p1530p1531
f 1 ~ 2
Constanttorque
fstallConstant
power
|
|M|
Stallpower
Motoring power limitation Defines fixed value for the max. permissiblemotoring active power.
P1530 def
P1530 max 0307P3 ⋅=0307P5.2 ⋅=
Regenerative power limitation Enters fixed value for the max. permissible regenerative active power
P1531max P0307 3- ⋅=P1531def P0307 2.5- ⋅=
M
f
f 2 P M
⋅π⋅=
Power limitation (motoring, regenerative)
p1530
p1531p1530
p1531
p0640 = ... 150.0 %
p1520 = ...
p1521 = ...
p1530 = ...
p1531 = ...
FC-spec.
FC-spec.
FC-spec.
FC-spec.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 114 6SE6400-5AW00-0BP0
Sensorless vector control (SLVC)
Control mode 20 Closed-loop Vector control – speed without encoder SLVC can provide excellent performance for the following types of application: • Applications which require high torque performance • Applications which require fast respond to shock loading • Applications which require torque holding while passing through 0 Hz • Applications which require very accurate speed holding • Applications which require motor pull out protection
Filter time for act. freq (SLVC) Sets time constant of PT1 filter to filter the frequency deviation of speed controller in operation mode SLVC (sensorless vector control). Decreasing the value leads to a higher dynamic of the speed regulation. Instability is seen if the value is to low (or to high). p1452 = 2 can be set for most applications.
Gain speed controller (SLVC) Enters gain of speed controller for sensorless vector control (SLVC).
Integral time n-ctrl. (SLVC) Enters integral time of speed controller for sensorless vector control (SLVC).
r1438r1084
–
Kp Tn
p1470 p1472
r0064
p1496 p0341 p0342
p1489p1488
p1452
Act. frequencyfrom observer model
r0063
r1170
–
Precontrol
Freq. setpointTorquesetpoint
Droop
150 ms
r1518p1492
r1490
0
1 0
r0079r1508
*)
*) only active, if pre-control is enabled (p1496 > 0)
Continuous torque boost (SLVC) Sets continuous torque boost in lower frequency range of SLVC (sensorless vector control). Value is entered in [%] relative to rated motor torque r0333. p1610 is only effective in the open-loop mode between 0 Hz and approx. ±p1755.
Acc. torque boost (SLVC) Sets acceleration torque boost in lower frequency range of SLVC (sensorless vector control). Value is entered in [%] relative to rated motor torque r0333. p1611 is only effective in the open-loop mode between 0 Hz and approx. ±p1755. In opposite to p1610 the acceleration torque boost p1611 is only in operation during acceleration/deceleration.
0 p1300=20
p1452 = ...
p1470 = ...
p1472 = ...
p1610 = ...
p1611 = ...
4 ms
3.0
400 ms
50.0 %
0.0 %
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 115
Control word of motor model This parameter controls the operation of the sensorless vector control (SLVC) at very low frequencies. This therefore includes the following conditions: Bit00 Start SLVC open loop 0 NO 1 YES (Operation directly after an ON command) Bit01 Zero crossing SLVC open loop 0 NO 1 YES (zero crossing)
f
t
p1755
Closed loop
Open loop
Start f
t
Closed loop
Open loop
Zero crossing
p1755
p1755
For most applications the setting of parameter p1750 = 0 gives the best result at low frequency.
Start-freq. motor model (SLVC) Enter the start frequency of sensorless vector control (SLVC), thereby SLVC switches over from open-loop to closed-loop at that frequency.
.
.
r0062
Speedcontroller
Pre-control
Torquelimitation
Currentcontroller
isq
−
open/closedloop
Flux setpointclosed loop
Flux setpointopen loop
isd
p1610
p1611
−
+
+
0
Act. outputvoltage
Act. outputfrequencyAct. frequency
Currentmeasurement
Act. angle
Observer modelclosed loop
Slip
Frequencysetpoint
iu
iwiv
p1452 p1470 p1472p1750/p1755
p1750 = ...
p1755 = ...
1
5.0 Hz
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 116 6SE6400-5AW00-0BP0
Vector control with encoder (VC)
• First step: Parameterizing the speed encoder (refer to Section 3.5.7.15)
• When commissioning Vector Control with encoder-feedback (VC), the drive should be configured for V/f mode (see p1300) first. Run the drive and compare r0061 with r0021 that should agree in: - sign - magnitude (with a deviation of only a few percent)
Only if both criteria are fulfilled, change p1300 and select VC (p1300 = 21/23).
• Encoder loss detection must be disabled (p0492 = 0) if torque is limited externally., e.g.: - closed-loop winder control - traversing / moving to a fixed endstop - when using a mechanical brake
Control mode 21 Vector control with sensor
Filter time for act. speed Sets time constant of PT1 filter to smooth actual speed of speed controller. Decreasing the value leads to a higher dynamic of the speed regulation. Instability is seen if the value is to low. p1442 = 2 can be set for most applications.
Gain speed controller Enters gain of speed controller.
Integral time speed controller Enters integral time of speed controller.
Precontrol
Freq. setpoint
r1438r1084
–
Kp Tn
p1460 p1462
r0064
Torquesetpoint
p1496 p0341 p0342
p1442
Act. frequencyfrom encoder
r0063
r1170
–
p1492
p1489p1488
Droop
r1490150 ms
r1518
0
1 0
r0079r1508
*) only active, if pre-control is enabled (p1496 > 0)
*)
p1300=21 0
4 ms
3.0
p1442 = ...
p1460 = ...
p1462 = ... 400 ms
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 117
Supplementary torque setpoint In the vector mode – with / without encoder – the speed controller can be
subordinate to a constant or variable supplementary torque. The supplementary setpoint can be used to advantage for hoisting gear with low
intrinsic friction when starting in the vertical direction. The supplementary torque setpoint must always be impressed in the hoisting (raising) direction (please observe the sign!). As a result of the supplementary torque, also when lowering, a slip is immediately established that has a stabilizing effect on the closed-loop control (there is no significant load sag).
The sign of the supplementary torque setpoint can be determined as follows in the commissioning phase with the appropriate care and taking into account all of the relevant safety regulations: Hoist (raise) a minimum load using the hoisting gear and read-out the sign from parameter r0079 (the sign of r0079 corresponds to the sign of the supplementary torque setpoint).
An empirical value of approx. 40 % of the rated motor torque r0333 has lead to good results for existing hoisting gear (carefully observe the sign!).
CI: Supplementary torque setpoint Selects the source of the supplementary torque setpoint.
Frequent settings: 2889 Fixed setpoint 1 as a % 2890 Fixed setpoint 2 as a % 755.0 Analog input 1 755.1 Analog input 2 2015. 2 USS (BOP link) 2018. 2 USS (COM link) 2050. 2 CB (e.g. PROFIBUS)
–Torquesetpoint
Droop
Act. frequency
– r1538 r1538
r1539 r1539
CI: Add. trq. setp
(0:0)P1511.C
Pre-control
Freq. setpoint
PISpeed
controller
SLVC:VC:
P1452P1442
P1470P1460
P1472P1462
Ti
Kp Tn
Ti Kp Tn
*)
*) only active, if pre-control is enabled (P1496 > 0)
r0079r1508r0063
r1170
r1515
r1518
P1511=... 0:0
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 118 6SE6400-5AW00-0BP0
3.5.7.18 Converter-specific Functions
Flying start
Flying start Starts inverter onto a spinning motor by rapidly changing the output frequency of the inverter until the actual motor speed has been found. 0 Flying start disabled 1 Flying start is always active, start in direction of setpoint 2 Flying start is active if power on, fault, OFF2, start in direction of setpoint 3 Flying start is active if fault, OFF2, start in direction of setpoint 4 Flying start is always active, only in direction of setpoint 5 Flying start is active if power on, fault, OFF2, only in direction of setpoint 6 Flying start is active if fault, OFF2, only in direction of setpoint
Motor-current: Flying start (entered in %) Defines search current used for flying start.
Search rate: Flying start (entered in %) Sets factor by which the output frequency changes during flying start to synchronize with turning motor.
Automatic restart
Automatic restart Configures automatic restart function. 0 Disabled 1 Trip reset after power on 2 Restart after mains blackout 3 Restart after mains brownout or fault 4 Restart after mains brownout 5 Restart after mains blackout and fault 6 Restart after mains brown/blackout or fault
0
100 %
100 %
p1200 = ...
p1202 = ...
p1203 = ?
p1210 = ... 1
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 119
Holding brake Series / commissioning for hazardous loads
− lower the load to the floor − when replacing the frequency inverter, prevent (inhibit) the frequency
inverter from controlling the motor holding brake (MHB) − secure the load or inhibit the motor holding brake control (so that the brake
cannot be controlled) and then – and only then – carry-out quick commissioning / parameter download using the PC-based tool (e.g. STARTER, AOP)
Parameterize the weight equalization for hoisting gear applications − magnetizing time P0346 greater than zero − min. frequency P1080 should approximately correspond to the motor slip
r0330 (P1080 ≈ r0330) − adapt the voltage boost to the load
a) V/f (P1300 = 0 ...3): P1310, P1311 b) SLVC (P1300 =20): P1610, P1611
It is not sufficient to just select the status signal r0052 bit 12 "motor holding brake active" in P0731 – P0733. In order to activate the motor holding brake, in addition, parameter P1215 must be set to 1.
It is not permissible to use the motor holding brake as operating brake. The reason for this is that the brake is generally only dimensioned/designed for a limited number of emergency braking operations.
The brake closing / opening times can be taken from the appropriate manual. The following typical values have been taken from Motor Catalog M11 2003/2004, Page 2/51:
Motor size Brake type Opening time [ms] Closing time [ms] 63 2LM8 005-1NAxx 25 56
71 2LM8 005-2NAxx 25 56
80 2LM8 010-3NAxx 26 70
90 2LM8 020-4NAxx 37 90
100 2LM8 040-5NAxx 43 140
112 2LM8 060-6NAxx 60 210
132 2LM8 100-7NAxx 50 270
160 2LM8 260-8NAxx 165 340
180 2LM8 315-0NAxx 152 410
200 225 2LM8 400-0NAxx 230 390
Holding brake enable Enables/disables holding brake function (MHB). 0 Motor holding brake disabled 1 Motor holding brake enabled NOTE The following must apply when controlling the brake relay via a digital output: P0731 = 52.C (= 52.12) (refer to Section 3.5.7.4 "Digital output (DOUT)").
0 P1215 =...
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 120 6SE6400-5AW00-0BP0
BI: Fct digital output 1 Defines the source for digital output 1.NOTE The brake relay can also be controlled from another digital output (if this is available) or using a distributed I/O module. Analog to DOUT 1, it should be guaranteed that the I/Os are controlled by the status bit “MHB active”.
Inverting digital outputs This parameter allows the signals to be output to be inverted.
Frequent settings: 52.0 Ready to power-up 0 Closed 52.1 Ready 0 Closed 52.2 Drive operational 0 Closed 52.3 Fault present 0 Closed 52.4 OFF2 active (present) 1 Closed 52.5 OFF3 active (present) 1 Closed 52.6 Power-on inhibit active (present) 0 Closed 52.7 Alarm active (present) 0 Closed 52.8 Deviation, setpoint/actual value 1 Closed 52.9 PZD / PLC control 0 Closed 52.A Maximum frequency reached 0 Closed 52.B Alarm: Motor current limit 1 Closed 52.C Motor holding brake active 0 Closed 52.D Motor overload 1 Closed 52.E Motor dir. of rotation, clockwise 0 Closed 52.F Frequency inverter overload 1 Closed 53.0 DC brake active 0 Closed 53.1 Actual freq. f_act > P2167 (f_off) 0 Closed : :
(52:3)
BI: Fct. of DOUT 1P0731.C
-1
0
1
Invert DOUTs0 ... 7
P0748 (0) CO/BO: State DOUTs
r0747r0747
Kl.20
Kl.18
.0
Functionxxxx.y rxxxx.y
P0731 = xxxx.y
DOUT channel
Relay :
DC 30 V / 5 AAC 250 V / 2 A Kl.28
Kl.9
int. 24 Vmax. 100 mA
NO
COM
NC
Kl.19or
Text
- max. opening / closing time5 / 10 ms
Holding brake release delay (entered in s) Defines the time interval during which the frequency inverter runs with the min. frequency p1080 after magnetizing, before the ramp-up starts. P1216 ≥ brake opening time + relay opening time
Holding time after ramp-down (entered in s) Defines time for which inverter runs at minimum frequency (p1080) after ramping down. P1217 ≥ brake closing time + relay closing time
p1217 = ... 1.0 s
p1216 = ... 1.0 s
0
52.3 P0731=52.C
P0748 = 0
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 121
Braking functions Priorities are assigned to the various braking functions. For instance, if a DC brake or a compound brake is activated, then this has a higher priority than the dynamic brake (resistance-type braking).
DC brakingP1233 > 0
?
yes
no
DC brakingenabled
Compoundbraking
P1236 > 0?
Compound brakingenabled
Dynamicbraking
P1237 > 0?
Dynamic brakingenabled disabled
no no
yes yes
DC-Bremse
BI: Enabling the DC brake This enables DC braking using a signal that was used from an external source. The function remains active as long as the external input signal is active. DC braking causes the motor to quickly stop by injecting a DC current
f
P0347
f*
i
t
t
t
1
0
f_act
DC braking
0
1
DC braking active
r0053Bit00
t
f_set
(0:0)P1230.CBI: Enable DC brk.
Note: DC brake can be applied in drive states r0002 = 1, 4, 5
P1232 =...
DC braking current (entered in %) Defines level of DC current in [%] relative to rated motor current (P0305).
P1230 = ...
100 %
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 122 6SE6400-5AW00-0BP0
P1233 =... Duration of DC braking (entered in s) Defines duration for which DC injection braking is to be active following an OFF1 or OFF3 command.
t
P1234
OFF1/OFF3
ON
t
t
f
P1233
1
tt
P0347
OFF2DC braking
OFF2
0
1
DC braking active
r0053Bit00
t
P1234
OFF1/OFF3
ON
t
t
f
OFF ramp
P1233
2
t
OFF2
tt
P0347
OFF2
OFF2DC braking
0
1
DC braking active
r0053Bit00
P1234 =... DC braking start frequency (entered in Hz) Sets the start frequency for the DC brake.
0 s
650 Hz
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 123
Compound braking
P1236 =...
Compound braking current (entered in %) Defines DC level superimposed on AC waveform after exceeding DC-link voltage threshold of compound braking. The value is entered in [%] relative to rated motor current (P0305). (see also Vdc controller ").
Compound braking switch-on level P0210213.1V21.13 U mainsDC_Comp
⋅⋅=⋅⋅=If P1254 = 0 :
1242r0.98 UDC_Comp
⋅=Compound braking switch-on levelotherwise :
f
i
t
t
f_act
f_set
P1236 = 0Without Compound braking
u
t
f
i
t
t
f_act
f_set
P1236 > 0With Compound braking
t
DC-link uDC-link
UDC_Comp
Dynamic braking
Dynamic braking Dynamic braking is activated using parameter P1237 – the nominal (rated) duty cycle as well as the switch-in duration of the braking resistor are also defined. 0 Inhibited 1 Load duty cycle 5 % 2 Load duty cycle 10 % 3 Load duty cycle 20 % 4 Load duty cycle 50 % 5 Load duty cycle 100 % Using the dynamic brake, the regenerative feedback energy is transferred to the external braking resistor using the chopper control (braking chopper); it is converted into thermal energy (heat) in this resistor. This dynamic braking allows the drive to be braked in a controlled fashion. This function is not available for sizes FX and GX.
Chopper resistor
Choppercontrol
B-
=~
~
B+
=
~
MM4
P1237 = ... 0
0 %
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 124 6SE6400-5AW00-0BP0
Vdc controller
P1240 =...
Configuration of Vdc controller Enables / disables Vdc controller. 0 Vdc controller disabled 1 Vdc-max controller enabled
P1254 =... Auto detect Vdc switch-on levels Enables/disables auto-detection of switch-on levels for Vdc control functionalities. 0 Disabled 1 Enabled t
t
f
1
-controller activeVDC_max
t
VDC
0r0056 Bit14
r1242
A0911
f
fact
set
PID controller
P2200 =...
BI: Enable PID controllerPID mode Allows user to enable/disable the PID controller. Setting to 1 enables the PID controller. Setting 1 automatically disables normal ramp times set in P1120 and P1121 and the normal frequency setpoints.
P2253 =... CI: PID setpoint Defines setpoint source for PID setpoint input.
P2254 =...
CI: PID trim source Selects trim source for PID setpoint. This signal is multiplied by the trim gain and added to the PID setpoint.
P2257 =... Ramp-up time for PID setpointSets the ramp-up time for the PID setpoint.
P2258 =... Ramp-down time for PID setpointSets ramp-down time for PID setpoint.
P2264 =... CI: PID feedback Selects the source of the PID feedback signal.
P2267 =... Max. value for PID feedbackSets the upper limit for the value of the feedback signal in [%]..
P2268 =... Min. value for PID feedbackSets lower limit for value of feedback signal in [%]..
P2280 =... PID proportional gain Allows user to set proportional gain for PID controller.
P2285 =... PID integral time Sets integral time constant for PID controller.
P2291 =... PID output upper limit Sets upper limit for PID controller output in [%].
1
1
0.0
0.0
0.0
1.00 s
1.00 s
755.0
100.00 %
0.00 %
3.000
0.000 s
100.00 %
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 125
P2292 =... PID output lower limit Sets lower limit for the PID controller output in [%].
PIDMOP
ADC
PIDSUM PIDPID
FF
USSBOP link
USSCOM link
CBCOM link
ADC2
P2254
P2253PIDRFG
PIDPT1
−∆PID
P2200
P2264 PIDPT1
PIDSCL
&
P2251
OutputPID
0
1
Motorcontrol
P22
57
P22
58
P22
61
P2271
P22
69
P22
70
P2265
P22
80
P22
85
0
Example:
Parameter Parameter text Example P2200 BI: Enable PID controller P2200 = 1.0 PID controller active P2253 CI: PID setpoint P2253 = 2224 PID-FF1 P2264 CI: PID feedback P2264 = 755 ADC P2267 Max. PID feedback P2267 Adapt to the application P2268 Min. PID feedback P2268 Adapt to the application P2280 PID proportional gain P2280 Determined by optimizing P2285 PID integral time P2285 Determined by optimizing P2291 PID output upper limit P2291 Adapt to the application P2292 PID output lower limit P2292 Adapt to the application
0.00 %
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 126 6SE6400-5AW00-0BP0
Free function blocks (FFB)
P2800 =...
Enable FFBs Parameter P2800 is used to activate all free function blocks (generally, P2800 is set to 1). Possible settings: 0 Inhibited 1 Enabled
P2801 =... Activate FFBs Parameter P2801 is used to individually enable (activate) the free function blocks P2801[0] to P2801[16] (P2801[x] > 0). Further, parameters P2801 and P2802 are used to define the chronological sequence of all of the function blocks. The table below indicates that the priority increases from left to right and from bottom to top. Possible settings: 0 Inactive 1 Level 1 2 Level 2 0 Level 3
Example: P2801[3] = 2, P2801[4] = 2, P2802[3] = 3, P2802[4] = 2 FFBs are calculated in the following sequence: P2802[3], P2801[3] , P2801[4], P2802[4] The active function blocks are calculated every 132 ms.
P2802 =...
Activate FFBs Parameter P2802 is used to individually enable (activate) the free function blocks P2802[0] to P2802[13] (P2802[x] > 0). Possible settings: 0 Inactive 1 Level 1 2 Level 2 1 Level 3
3210
P28
02 [1
3] C
MP
2P
2802
[12]
CM
P 1
P28
02 [1
1] D
IV 2
P28
02 [1
0] D
IV 1
P28
02 [9
] M
UL
2P
2802
[8]
MU
L 1
P28
02 [7
] S
UB
2P
2802
[6]
SU
B 1
P28
02 [5
] A
DD
2P
2802
[4]
AD
D 1
P28
02 [3
] T
imer
4P
2802
[2]
Tim
er 3
P28
02 [1
] T
imer
2P
2802
[0]
Tim
er 1
P28
01 [1
6] R
S-F
F 3
P28
01 [1
5] R
S-F
F 2
P28
01 [1
4] R
S-F
F 1
P28
01 [1
3] D
-FF
2P
2801
[12]
D-F
F 1
P28
01 [1
1] N
OT
3P
2801
[10]
NO
T 2
P28
01 [9
] N
OT
1P
2801
[8]
XO
R 3
P28
01 [7
] X
OR
2P
2801
[6]
XO
R 1
P28
01 [5
] O
R 3
P28
01 [4
] O
R 2
P28
01 [3
] O
R 1
P28
01 [2
] A
ND
3P
2801
[1]
AN
D 2
P28
01 [0
] A
ND
1LevelLevelLevelInactive
low high
Prio
rity
1
Priority 2
low
0
0.0
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 127
3.5.7.19 Command and drive data set
P0810 =...
Command data set CDS bit 0 (local / remote) Selects the command source in which bit 0 should be read-out to select a command data set (CDS).
t0
1
2
3
(0:0)
BI: CDS b0 loc/remP0810
(0:0)
BI: CDS bit 1P0811
t0
1
2
3
CO/BO: Act CtrlWd2
r0055r0055
CO/BO: Act CtrlWd1
r0054r0054
.15
.15
.15
.15
r0050Active CDS
Selecting CDS
approx. 4 ms approx. 4 ms
r0050CO: Active CDS
Changeover timeChangeover time
The currently active command data set (CDS) is displayed using parameter r0050:
r0055bit15
r0054bit15
1. CDS 0 0
2. CDS 0 1
3. CDS 1 0
3. CDS 1 1
r0050
0
1
2
2
SelectCDS
ActiveCDS
Most frequent settings: 722.0 = Digital input 1 (P0701 must be set to 99, BICO) 722.1 = Digital input 2 (P0702 must be set to 99, BICO) 722.2 = Digital input 3 (P0703 must be set to 99, BICO) 722.3 = Digital input 4 (P0704 must be set to 99, BICO) 722.4 = Digital input 5 (P0705 must be set to 99, BICO) 722.5 = Digital input 6 (P0706 must be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, P0707 must be set to 99) 722.7 = Digital input 8 (via analog input 2, P0708 must be set to 99)
Example for CDS changeover: CDS1: Command source via terminals and setpoint source via analog input (ADC) CDS2: Command source via BOP and setpoint source via MOP CDS changeover is realized using digital input 4 (DIN 4) Steps:
1. Carry-out commissioning for CDS1 (P0700[0] = 2 and P1000[0] = 2) 2. Connect P0810 (P0811 if required) to the CDS changeover source
(P0704[0] = 99, P0810 = 722.3) 3. Copy from CDS1 to CDS2 (P0809[0] = 0, P0809[1] = 1, P0809[2] = 2) 4. Adapt CDS2 parameters (P0700[1] = 1 and P1000[1] = 1)
0
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 128 6SE6400-5AW00-0BP0
DIN4
TerminalsSequence control
BOP
P0700[0] = 2
P0700[1] = 1
P0810 = 722.3
ADC Setpointchannel
MOP
0
1
P1000[0] = 2
P1000[1] = 1
Motorcontrol
0
1
Drive data set (DDS) bit 0 Selects the command source from which bit 0 should be read-out to select a drive data set.
t0
1
2
3
(0:0)
BI: DDS bit 0P0820
(0:0)
BI: DDS bit 1P0821
t0
1
2
3
CO/BO: Act CtrlWd2
r0055r0055
CO/BO: Act CtrlWd2
r0055r0055
.04
.04
.05
.05
r0051[1]Active DDS
Select DDS
approx. 50 ms approx. 50 msChangeover timeChangeover time
Operation
Ready
t
r0051 [2]CO: Active DDS
.01
The currently active drive data set (DDS) is displayed using parameter r0051[1]:
r0055bit05
r0054bit04
1. DDS 0 0
2. DDS 0 1
3. DDS 1 0
3. DDS 1 1
r0051 [0]
0
1
2
2
r0051 [1]
0
1
2
2
SelectDDS
ActiveDDS
Most frequent settings: 722.0 = Digital input 1 (P0701 must be set to 99, BICO) 722.1 = Digital input 2 (P0702 must be set to 99, BICO) 722.2 = Digital input 3 (P0703 must be set to 99, BICO) 722.3 = Digital input 4 (P0704 must be set to 99, BICO) 722.4 = Digital input 5 (P0705 must be set to 99, BICO) 722.5 = Digital input 6 (P0706 must be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, P0707 must be set to 99) 722.7 = Digital input 8 (via analog input 2, P0708 must be set to 99)
0 P0820 = ...
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 129
Example: 1. Commissioning steps with a motor:
− Carry-out commissioning at DDS1. − Connect P0820 (P0821 if required) to the DDS changeover source
(e.g. using DIN 4: P0704[0] = 99, P0820 = 722.3). − Copy DDS1 to DDS2 (P0819[0] = 0, P0819[1] = 1, P0819[2] = 2). − Adapt DDS2 parameters
(e.g. ramp-up / ramp-down times P1120[1] and P1121[1]).
DIN
ADC
P0820 = 722.3
SUMsetpoint
Sequence control
DIN4
AFM RFG Motorcontrol
0 1
P1120P1121
[0]DDS1
[1]DDS2
[2]DDS3
M
Gat
ing
unit
2. Commissioning steps with 2 motors (motor 1, motor 2): − Commission motor 1; adapt the remaining DDS1 parameters. − Connect P0820 (P0821 if required) to the DDS changeover source
(e.g. via DIN 4: P0704[0] = 99, P0820 = 722.3). − Changeover to DDS2 (check using r0051). − Commission motor 2; adapt the remaining DDS2 parameters.
MM4
M1
K1
M2
K2
Motor 1
Motor 2
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 130 6SE6400-5AW00-0BP0
3.5.7.20 Diagnostic parameters
r0035 CO: Motor temperature Displays the measured motor temperature in °C.
r0036 CO: Frequency inverter utilization Displays the frequency inverter utilization as a % referred to the overload. In so doing, the value is calculated using the I2t model. The I2t actual value relative to the maximum possible I2t value provides the level of utilization.
r0052 CO/BO: Act. status word 1 Displays the first active status word (ZSW) of the frequency inverter (bit format) and can be used to diagnose the inverter status.
r0054 CO/BO: Control word 1 Displays the first control word (STW) of the frequency inverter and can be used to display the active commands.
r0063 CO: Actual frequency Displays the actual frequency in Hz.
V/f
0
1,2
SLVC(observermodel)
Encoder
P0400
P1300
160 ms
Frequency actual values:
Smoothed freq. actual value
Frequency actual value
Freq.act.value fr. the encoder
21,23
20,22
<20
0
P1300 = 21,23 and P0400 = 0 --> F0090
P0408 60 r0313⋅
Smoothed speed act. value r0313
60
r0022
r0021
r0063
r0061
r1079 CO: Selected frequency setpoint Displays the selected frequency setpoint. The following frequency setpoints are displayed: r1078 total setpoint (HSW + ZUSW) P1058 JOG frequency, clockwise P1059 JOG frequency, counter-clockwise.
r1114 CO: Freq. setpoint after dir. ctrl. Displays the setpoint (reference) frequency in Hz after the function block to reverse the direction of rotation.
r1170 CO: : Frequency setpoint after RFG Displays the total frequency setpoint (reference value) in Hz after the ramp-function generator.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 131
3.5.7.21 End of commissioning
Transfer data from RAM to EEPROM 0 Inhibited 1 Start RAM->EEPROM All parameter changes are transferred from the RAM memory into the EEPROM memory and therefore saved in the MICROMASTER in a non-volatile fashion. NOTE When using a BOP or AOP, MICROMASTER automatically carries-out the RAM→EEPROM data save operation. If the parameterization is carried-out using the commissioning tools - STARTER or DriveMonitor – then data is not automatically saved in the EEPROM. Automatic RAM→EEPROM data save can be selected by pressing the appropriate selection button.
STARTER DriveMonitor
RAM → EEPROM Online-EEPROM
NOTE If P0971 is used to start data save from the RAM to EEPROM, then after the data has been transferred, the communications memory is re-initialized. This means that communications via USS as well as also via the CB board are interrupted for the time it takes to reset:
The connected PLC (e.g. SIMATIC S7) goes into stop The STARTER start-up program buffers the communications failure For the DriveMonitor start-up program, "NC" (not connected) or "drive busy" is
displayed. The "busy" text is displayed at the BOP operator panel
After reset has been completed, for the start-up programs STARTER and DriveMonitor and the BOP operator panel, communications are automatically re-established.
END
P0971 = 1 0
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 132 6SE6400-5AW00-0BP0
3.5.8 Series commissioning The parameter set can be read-out (upread) from the drive converter via the serial interface and saved on the hard disk / floppy disk or in a non-volatile memory (e.g. EEPROM) using the following
PC Tools (e.g. STARTER, DriveMonitor) or the Operator panel AOP
(please refer to Fig. 3-28). The interfaces of the drive inverter with USS protocol and the fieldbus interfaces (e.g. PROFIBUS) which can be used to transfer parameters, can be used as serial interface.
DriveMonitor
AOP
STARTER CB on COM link
USS on COM link
USS on BOP link
(PROFIBUS)
(RS485)
(RS232)
Parameter transmission from differentsources via download
MM4
* Option is absolutely required for the connection
1)
1) Option: Operator panel door mounting kit for single inverter control
5)*
2) Option: PC to inverter connection kit
3) Option: AOP door mounting kit for multiple inverter control (USS)
4) Option: RS232-RS485 Converter
3)*
2)*
2)*
4)*
4)*
CB
5) With PROFIBUS: SIMATIC NET With CANopen or DeviceNet: see user organisation
Fig. 3-28 Upread / download using AOP and PC Tools
If there is already an appropriate parameter set for the drive, which, for example, was created by either upreading or by programming offline, then this can be downloaded into the drive inverter. This means that it is possible to transfer the parameter set from drive inverter A to drive inverter B which, for identical applications (e.g. series machines, group drives) allows data to be copied and therefore in turn fast commissioning.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 133
WARNING For series commissioning, all of the communication interfaces as well as also
the digital and analog interfaces are re-initialized. This results in a brief communications failure or causes the digital outputs to switch.
Potentially hazardous loads must be carefully secured before starting a series commissioning.
Potentially hazardous loads can be secured as follows before starting series commissioning: ♦ Lower the load to the floor, or ♦ Clamp the load using the motor holding brake
(Caution: During series commissioning, MICROMASTER must be prevented from controlling the motor holding brake).
If the motor holding brake (refer to Section 3.14) is controlled by the MICROMASTER, then series commissioning may not be carried-out for potentially hazardous loads (e.g. suspended loads for crane applications).
3.5.9 Parameter reset to the factory setting
The factory setting is a defined initial state of all of the drive inverter parameters. The drive inverters are shipped from the factory in this state. The drive inverters have the following default settings:
Control via the digital inputs a) ON/OFF via DIN1 b) Direction of rotation reversal via DIN2 c) Fault acknowledgement via DIN3
Setpoint input via analog input 1 Signal output via the digital outputs
a) Fault active via DOUT 1 b) Warning active via DOUT 2
Actual frequency via the analog output The basic V/f characteristic is the control mode (P1300 = 0) Induction motor (P0300 = 1)
When appropriately connected-up and with the appropriate motor – drive inverter combination, MICROMASTER drive inverters are ready to run when shipped from the factory without requiring any additional parameterization. You can re-establish the initial state at any time by carrying-out a parameter reset to the factory setting. This undoes all of the parameter changes which were made since the drive inverter was supplied. This value is designated as "Def" in the parameter list.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 134 6SE6400-5AW00-0BP0
Reset to the factory setting
User access level 1 Access level, standard
Parameter filter 0 All parameters
Commissioning parameter 30 Factory setting
Factory reset 1 Parameter reset to the default values
The drive inverter carries-out a parameter reset (duration, approx. 10 s) and then automatically exits the reset menu and sets P0970 = 0 : Disabled P0010 = 0 : Ready
NOTE When resetting the parameters to the factory setting, the communications memory is re-initialized. This means that communications via USS as well as also via the CB board are interrupted for the time it takes to make the reset:
The connected PLC (e.g. SIMATIC S7) goes into stop The STARTER start-up program buffers the communications failure For the DriveMonitor start-up program, "NC" (not connected) or "drive busy" is
displayed. The "busy" text is displayed at the BOP operator panel
After reset has been completed, for the start-up programs STARTER and DriveMonitor or the BOP operator panel, communications are automatically re-established.
START
END
P0003 = 1
P0004 = 0
P0010 = 30
P0970 = 1
1
0
0
0
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 135
3.6 Inputs / outputs
3.6.1 Digital inputs (DIN)
Number: 6 + 2 Parameter range: r0722 – P0725 Function chart number: FP2000, FP2200 Features:
- cycle time: 2 ms - switch-on threshold: 10.6 V - switch-out threshold: 10.6 V - electrical features: electrically isolated, short-circuit proof
External control signals are required for a drive converter to be able to operate autonomously. These signals can be entered via a serial interface as well as also via digital inputs (refer to Fig. 3-29). MICROMASTER has 6 digital inputs which can be expanded to a total of 8 by using the 2 analog inputs. The digital inputs, as far as their assignment, can be freely programmed to create a function. Whereby, regarding the program, it is possible to directly assign the function via parameters P0701 - P0708 or to freely program the function using BICO technology.
DIN channel (e.g. DIN1 - PNP (P0725 = 1))
24 V T 0
&0
1
PNP/NPN DIN0 ... 1
P0725 (1)
0 V
24 VDebounce time: DIN
0 ... 3P0724 (3)
CO/BO: Bin.inp.valr0722r0722
.0
Kl.9P24 (PNP)Kl.280 V (NPN)
Pxxxx BI: ...
P0701
Function0
1
DIN channel (e.g. DIN1 - NPN (P0725 = 0))
24 V T 0
&0
1
PNP/NPN DIN0 ... 1
P0725 (1)
0 V
24 VDebounce time: DIN
0 ... 3P0724 (3)
CO/BO: Bin.inp.valr0722r0722
.0
Kl.9P24 (PNP)Kl.280 V (NPN)
Pxxxx BI: ...
P0701
Function0
1
Fig. 3-29 Digital inputs
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 136 6SE6400-5AW00-0BP0
Parameter P0725 is used to define as to whether digital inputs DIN1 - DIN6 are logical "1" when appropriately connected to 0 V or 24 V. The logical states of the digital inputs can be de-bounced using P0724 and read-out using parameter r0722 (BICO monitoring parameter). Further, this parameter is used to parameterize BICO for the digital inputs (refer to BICO parameterization in the following Section). P0701 – P0706 (digital inputs 1–6) or P0707 – P0708 (analog inputs 1-2) The possible settings of the individual inputs are listed in Table 3-11.
Table 3-11 Parameters P0701 – P0706
Parameter value Significance 0 Digital input disabled
1 ON / OFF1
2 ON+reverse / OFF1
3 OFF2 – coast to standstill
4 OFF3 – quick ramp-down
9 Fault acknowledge
10 JOG right
11 JOG left
12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
15 Fixed setpoint (direct selection)
16 Fixed setpoint (direct selection + ON)
17 Fixed setpoint (binary-coded selection + ON)
25 Enable DC braking
29 External trip
33 Disable additional frequency setpoint
99 Enable BICO parameterization
Example: An ON/OFF1 command should be realized using digital input DIN1.
P0700 = 2 Control enabled via terminal strip (digital inputs) P0701 = 1 ON/OFF1 via digital input 1 (DIN1)
NOTE If an analog input (refer to Fig. 3-33) has been configured as digital input, then the following limit values apply: < 1.7 V DC → "0" > 3.9 V DC → "1"
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 137
BICO parameterization If the setting 99 (BICO) is entered into parameters P0701 – P0708, then the BICO wiring is enabled for the appropriate digital input. The output parameter number of the function (parameter, included in the parameter text BO) should be entered into the command source (parameter which contains the code BI in the parameter text).
Example: An ON/OFF1 command should be realized using digital input DIN1.
P0700 = 2 Control enabled via digital inputs P0701 = 99 BICO enabled for DIN1 P0840 = 722.0 ON/OFF1 via DIN1
NOTE Only experienced users should use the BICO parameterization and for applications where the possibilities provided by P0701 – P0708 are no longer adequate.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 138 6SE6400-5AW00-0BP0
3.6.2 Digital outputs (DOUT) Number: 3 Parameter range: r0730 – P0748 Function chart number: FP2100 Features:
- cycle time: 1 ms
Binary states in the drive can be output via the digital outputs. As result of the fast cycle time, it is possible to control external devices and to display the state in real time. In order that higher powers can also be output, the internal signal (TTL level) is amplified using a relay (refer to Fig. 3-30).
Relay: - max. opening / closing time: 5 / 10 ms
- voltage / current 30 V DC / 5 A 250 V AC / 2 A
(52:3)
BI: Fct. of DOUT 1P0731.C
-1
0
1
Invert DOUTs0 ... 7
P0748 (0) CO/BO: State DOUTs
r0747r0747
NO
COM
NC
Kl.20
Kl.19
Kl.18
(52:7)
BI: Fct. of DOUT 2P0732.C
-1
0
2
Invert DOUTs0 ... 7
P0748 (0) CO/BO: State DOUTs
r0747r0747
NO
COMKl.22
Kl.21
(0:0)
BI: Fct. of DOUT 3P0733.C
-1
0
4
Invert DOUTs0 ... 7
P0748 (0) CO/BO: State DOUTs
r0747r0747
NO
COM
NC
Kl.25
Kl.24
Kl.23
.0
.1
.2
Fig. 3-30 Digital outputs
The states, which are to be output, are defined using the "BI" parameters P0731 (digital output 1), P0732 (digital output 2) and P0733 (digital output 3). For the definition, the "BO" parameter number or "CO/BO" parameter number and the bit number of the particular state should be entered into P0731 – P0733. Frequently used states including the parameter number and bit are shown in the following Table (refer to Table 3-12).
Table 3-12 Parameters P0731 – P0733 (frequently used functions / states)
Parameter value Significance 52.0 Drive ready
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 139
52.1 Drive ready to run
52.2 Drive running
52.3 Drive fault active
52.4 OFF2 active
52.5 OFF3 active
52.6 Switch-on inhibit active
52.7 Drive warning active
52.8 Deviation, setpoint / actual value
52.9 PZD control (Process Data Control)
52.A Maximum frequency reached
52.B Warning: Motor current limit
52.C Motor holding brake (MHB) active
52.D Motor overload
52.E Motor running direction right
52.F Inverter overload
53.0 DC brake active
53.1 Act. frequency f_act >= P2167 (f_off)
53.2 Act. frequency f_act > P1080 (f_min)
53.3 Act. current r0027 >= P2170
53.6 Act. frequency f_act >= setpoint
NOTE A complete list of all of the binary status parameters (refer to "CO/BO" parameters) can be taken from the parameter list.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 140 6SE6400-5AW00-0BP0
3.6.3 Analog inputs (ADC) Number: 2 Parameter range: P0750 – P0762 Function chart number: FP2200 Features:
- cycle time: 4 ms - resolution: 10 bits - accuracy: 1 % referred to 10 V / 20 mA - electrical features: incorrect polarity protection, short-circuit proof
Analog setpoints, actual values and control signals are read-into the drive inverter using the appropriate analog inputs and are converted into digital signals / values using the ADC converter. The setting as to whether the analog input is a voltage input (10 V) or a current input (20 mA) must be selected using the 2 switches DIP1(1,2) on the I/O board as well as also using parameter P0756 (refer to Fig. 3-31).
Possible settings of P0756: 0 Unipolar voltage input ( 0 to +10 V ) 1 Unipolar voltage input with monitoring (0 to 10 V ) 2 Unipolar current input (0 to 20 mA) 3 Unipolar current input with monitoring (0 to 20 mA) 4 Bipolar voltage input (-10 V to +10 V) only ADC1
Fig. 3-31 DIP switch and P0756 for ADC current / voltage input
NOTE The setting (analog input type) of P0756 must match that of switch DIP1(1,2) on
the I/O board. The bipolar voltage input is only possible with analog input 1 (ADC1).
Depending on the ADC type or source, the appropriate connection must be made. Using, as an example, the internal 10 V voltage source, a connection is shown as an example in the following diagram (refer to Fig. 3-32).
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 141
Voltage input
A
D
KL1 10 V
KL2 0 V
KL4 ADC−
KL3 ADC+> 4.7 kΩ
Current input
A
D
KL1 10 V
KL2 0 V
KL4 ADC−
KL3 ADC+
A
DKL11 ADC−
KL10 ADC+A
DKL11 ADC−
KL10 ADC+
0 ...20 mA
Fig. 3-32 Connection example for ADC voltage / current input
The ADC channel has several function units (filter, scaling, dead zone) (refer to Fig. 3-33).
KL
KL
DIP switch
AD
ADCtype
ADCscaling
P07
57P
0758
P07
59P
0760
ADCdead zone r0755 Pxxxx
r0752
Function
P1000
ADC?
ADC+
r0754
r0722r0722.x
P0761P0753P0756
0
1
ADCtype
Fig. 3-33 ADC channel
NOTE When the filter time constant P0753 (ADC-PT1) is increased, this smooths the ADC input signal therefore reducing the ripple. When this function is used within a control loop, this smoothing has a negative impact on the control behavior and immunity to noise (the dynamic performance deteriorates).
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 142 6SE6400-5AW00-0BP0
3.6.4 Analog outputs (D/A converter) Number: 2 Parameter range: r0770 – P0785 Function chart number: FP2300 Features: - cycle time: 4 ms - resolution: 10 bit - accuracy: 1 % referred to 20 mA
Setpoints, actual values and control signals inside the drive inverter are read-out via the D/A converter using these analog inputs. The digital signal is converted into an analog signal. All of the signals can be output via the D/A which contain the "CO" abbreviation in the parameter text (refer to list of all of the BICO parameters in the parameter list). Parameter P0771 defines, by assigning the parameter number, the quantity which is output as analog signal through the D/A converter channel (refer to Fig. 3-34). The smoothed output frequency is output, e.g. via the analog output, if P0771[0] = 21.
D/A conv.channel
D
AKL
KL
D/A conv.−
D/A conv.+r0755 Pxxxxrxxxx P0771
...
Function
r0020 CO: Freq. setpoint before RFGr0021 CO: Act. filtered frequencyr0024 CO: Act. filtered output freq.r0025 CO: Act. filtered output voltager0026 CO: Act. filtered DC-link volt.r0027 CO: Act. filtered output current
r0052 CO/BO: Act. status word 1r0053 CO/BO: Act. status word 2r0054 CO/BO: Act. control word 1...
0 ...
20
mA
Fig. 3-34 Signal output through the D/A converter channel
In order to adapt the signal, the D/A converter channel has several function units (filter, scaling, dead zone) which can be used to modify the digital signal before conversion (refer to Fig. 3-35).
Fig. 3-35 D/A converter channel
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 143
With parameter P0775 = 1, negative values can be avoided on the input side of the DAC channel. If this parameter is activated, the absolute value is always entered in the input of the DAC scaling (the DAC characteristic is mirrored on the Y axis). If the value was originally a negative one, the corresponding bit in r0785 is set for detection.
NOTE The analog outputs only provide current outputs (0 ... 20 mA). A 0 ... 10 V voltage signal can be generated by connecting a 500 Ohm resistor across the outputs. The voltage drop across the resistor can be read using parameter r0774 if the parameter P0776 is changed-over from current output (P0776 = 0) to voltage output (P0776 = 1). The D/A scaling parameters P0778, P0780 and the D/A converter dead zone must still be entered in mA (0 ... 20).
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 144 6SE6400-5AW00-0BP0
3.7 Communications Parameter range: P2009 – r2091 Function chart number: CB at COM link FP2700, FP2710 USS at COM link FP2600, FP2610 USS at BOP link FP2500, FP2510
MICROMASTER 440 has 2 serial communication interfaces which can be simultaneously used. These interfaces are designated as follows in the following text:
BOP link COM link
Different units, such as the BOP and AOP operator panels, PCs with the start-up software DriveMonitor and STARTER, interface modules for PROFIBUS DP, DeviceNet and CAN as well as programmable controls with communication processors can be connected at this interface (refer to Fig. 3-28).
* Option is absolutely required for the connection
BOP USSRS232
USSRS232
BOPDriveMonitor/
STARTER AOP
CB
BOP link
PROFIBUSboard
DeviceNetboard
CANboard
COM link
CB CB
USSRS485
AOP
USSRS485
DriveMonitor/STARTER
29 30
1) 1)3)*
1) Option: Operator panel door mounting kit for single inverter control
2)*
2) Option: PC to inverter connection kit
3) Option: AOP door mounting kit for multiple inverter control (USS)
4)*
4) Option: RS232-RS485 Converter
Fig. 3-36 Serial communication interfaces - BOP link and COM link
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 145
The BOP, a programming / operator unit (e.g. AOP, PC with DriveMonitor / STARTER) or a programmable control with communications processor can be connected via this BOP link. Data transfer between MICROMASTER and the programming / operator units is realized using the USS protocol via the RS232 interface (point-to-point data coupling). Communications between the BOP and MICROMASTER uses a optimized interface which takes into consideration the somewhat limited resources of the BOP. If the BOP is replaced by an USS unit (PC, AOP), then MICROMASTER automatically identifies the interface of the new unit. This is also true for the inverse replacement sequence. The BOP link interface can be adapted to the particular unit using the following parameters (refer to Table 3-13).
Table 3-13 BOP link
BOP link – interface BOP on BOP link USS on BOP link
No parameter P2009[1] P2010[1] P2011[1] P2012[1] P2013[1] P2014[1]
r2015 P2016
r2024[1] r2025[1] r2026[1] r2027[1] r2028[1] r2029[1] r2030[1] r2031[1] r2032 r2033
Communication modules (CB) such as PROFIBUS, DeviceNet, CANopen and also programming / operator units (e.g. PCs with the DriveMonitor / STARTER start-up software and AOP) as well as programmable controls with communication processor can be connected to the COM link. The plug connector allows the communication modules to be connected to MICROMASTER. On the other hand, the programming / operator units must be connected to the MICROMASTER through terminals 29/30. As for the BOP link, data is transferred between MICROMASTER and the programming / operator unit using the USS protocol. In so doing, for the COM link, the USS protocol is transferred via the bus-capable RS485 interface. Essentially the same as the BOP link, the COM link also automatically defines if a communications module is replaced with a USS unit (PC, AOP). The COM link can be adapted to the particular unit using the following parameters (refer to Table 3-14).
Table 3-14 COM link
COM link – interface CB on COM link USS on COM link
P2040 P2041 r2050 P2051
r2053 r2054 r2090 r2091
P2009[0] P2010[0] P2011[0] P2012[0] P2013[0] P2014[0]
r2018 P2019
r2024[0] r2025[0] r2026[0] r2027[0] r2028[0] r2029[0] r2030[0] r2031[0] r2036 r2037
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 146 6SE6400-5AW00-0BP0
NOTE A communications (CB) module as well as a programming / operator unit can
be simultaneously connected to the COM link interface via terminals 29/30 (USS). This is the reason that the communications module has priority over USS. In this case, the USS node (USS station) via the COM link is de-activated.
Contrary to PROFIBUS, the RS485 port (terminals 29/30) is not optically isolated (not floating). When installing the system, it must be ensured that EMC faults do not result in communication failures or damage to the RS485 drivers.
3.7.1 Universal serial interface (USS)
Parameter range: P2009 – r2037 Significance COM link BOP link USS basic setting USS baud rate P2010[0] P2010[1] USS address P2011[0] P2011[1] USS-PZD length P2012[0] P2012[1] USS-PKW length P2013[0] P2013[1]
PZD data Received data r2018[8] r2015[8] Received control word 1 r2036 r2032 Received control word 2 r2037 r2033 Sent data P2019[8] P2016[8] Sent status word 1 r0052 r0052 Sent status word 2 r0053 r0053
Alarms: --- Faults: F0071, F0072 Function chart number: FP2500, FP2510, FP2600, FP2610 Features: − electrical features: Not electrically isolated USS at the BOP link with PC- converter connecting set Not electrically isolated USS at COM link (terminals 29 /30) − cycle time (MM440): 8 ms (process data PZD) Background (parameter ID value PKW)
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 147
Baud rate + interval timeTelegram lengthNumber of nodes (slave)
Master
cycle,masterT
Slave(MICROMASTER)
cycle,USST cycle,slave(MM4)T
NOTE From the user’s perspective, the total cycle time between the master and slave is of significance. As shown in the diagram above, this time depends on several factors.
Fig. 3-37 Cycle times
Using the USS protocol, a user can establish a serial point-to-point data link and a serial bus data link between a higher-level master system and several slave systems. Master systems can be, for example, PLCs (e.g. SIMATIC S7-200) or PCs. MICROMASTER drive converters are always the slaves on the bus system. The USS protocol allows the user to implement both automation tasks with cyclical telegram traffic (→ a fixed telegram length is necessary) as well as visualization tasks. In this case, the protocol with variable telegram length is advantageous, as texts and parameter descriptions can be transferred in one telegram without chopping up the information.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 148 6SE6400-5AW00-0BP0
3.7.1.1 Protocol specification and bus structure The USS protocol has the following significant features:
Supports ♦ a multi-point-capable link, e.g. EIA RS 485 hardware or ♦ a point-to-point link, e.g. EIA RS 232
Master-slave access technique Single-master system Maximum 32 nodes (max. 31 slaves) Operation with variable or fixed telegram length Simple, reliable telegram frames The same bus mode of operation as with the PROFIBUS (DIN 19245 Part 1) Data interface to the basic unit according to PROFILE variable-speed drives.
This means that, when the USS is being used, information is transferred to the drive in the same way as with the PROFIBUS-DP.
Can be used for start-up, service and automation PC-based service tools (e.g. STARTER and DriveMonitor) Can be easily implemented in customized systems
Protocol specification The USS protocol defines an access technique according to the master-slave principle for communications via a serial bus. The point-to-point link is included as a sub-quantity. One master and a maximum of 31 slaves can be connected to the bus. The individual slaves are selected by the master using an address character in the telegram. A slave can never transmit without first being initiated by the master so that direct information transfer between individual slaves is not possible. The master function cannot be transferred (single-master system). The following illustration shows a bus configuration using drive technology as an example.
MICROMASTER
Higher-level computer
"Master"
MICROMASTER MICROMASTER MICROMASTER
"Slave""Slave""Slave""Slave"
Fig. 3-38 Serial linking of MICROMASTER (slaves) with a higher-level computer (master)
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 149
The telegram has the following structure: Each telegram begins with the start character STX (= 02 hex), followed by the
length information (LGE) and the address byte (ADR). The net characters then follow. The telegram is terminated by the BCC (Block Check Character).
For single-word data (16 bit) in the net data block (= net character block), the high byte (first character) is always sent and then the low byte (second character).
The same applies to double-word data: the high word is sent first followed by the low word.
The necessary settings / parameter assignments must be made both at the master as well as at the slave and can no longer be changed in bus operation.
The protocol does not identify tasks in the net characters. The contents of the net characters/data for the MICROMASTER drives is discussed in Section 3.7.1.2 "Structure of the net data".
n net characters
STX LGE ADR 1. 2. n BCC
Fig. 3-39 Telegram structure
Information is coded as follows:
Abbreviation Significance Size Explanation STX Start of text ASCII characters 02 hex
LGE Telegram length 1 byte Contains the telegram length
ADR Address 1 byte Contains the slave address and the telegram type (binary coded)
--- Net characters Each one byte Net data, contents are dependent on the request
BCC Block check character 1 byte Data security characters
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 150 6SE6400-5AW00-0BP0
In the address byte, information other than the node number is coded: The individual bits in the address byte are assigned as follows:
= 1: Broadcast, address bits (No. 0 to 4) are not evaluated= 0: No broadcast
7 6 5 4 3 2 1 0
STX LGE ADR 1. 2. n BCC
n net characters
Bit No.
Slave nodes No. 0 to 31
= 1: Mirror telegram= 0: No mirror telegram
= 1: Special telegram (for an explanation, see below)= 0: Standard; bits 0 to 6 are valid and must be evaluated
Fig. 3-40 Assignment of the address byte (ADR)
The master ensures cyclical telegram data transfer. The master addresses all of the slave nodes one after the other with a task telegram. The addressed nodes respond with a reply telegram. In accordance with the master-slave procedure, the slave, after receiving the task telegram, must send the reply telegram to the master before the master can address the next slave node. The sequence of the addressed slave nodes can be specified, for example, by entering the node numbers (ADR) in a circulating list (polling list) in the master. If it is necessary to address several slaves in a faster cycle than the other slaves, their node number can occur several times in the circulating list. A point-to-point link can be implemented by means of the circulating list, in which case only one node is entered into the circulating list.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 151
Example of configuration
1 3 57 21 0
0
1
3
5
0
7
21
1
3
5
0
1
0
1
7
21
Master
Circulating listin the master
MICROMASTER with the addresses 0, 1, 3, 5, 7 and 21
Nodes 0 and 1 are signalled twice as often as others
Fig. 3-41 Circulating list (Example of configuration)
The length of a cycle time is determined by the time needed for the sequential occurrence of data exchange with the individual nodes.
Cycle time
0 0 1 1 0 0 t
Telegram run time for reply from node 1
Reply delay time from node 1
Telegram run time for task for node 1
Processing time in the master
Fig. 3-42 Cycle time
Due to inconstant reply delay and processing times, the cycle time is not fixed. The STX start character (= 02 hexadecimal) by itself is not sufficient for the slaves to clearly identify the start of a telegram because the bit combination 02/hexadecimal can also occur in the net characters. For this reason, a no-character start interval of at least 2 character run-times before the STX is specified for the master. The start interval is part of the task telegram.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 152 6SE6400-5AW00-0BP0
Table 3-15 Minimum start intervals for various baud rates
Baud rate in bit/s Start interval in ms
2400 9,20 ms
4800 4,60 ms
9600 2,30 ms
19200 1,15 ms
38400 0,57 ms
57600 0,38 ms
76800 0,29 ms
93750 0,24 ms
115200 0,19 ms
Only an STX with a preceding start interval identifies the valid start of a telegram. Data is always transferred in accordance with the diagram illustrated below (half-duplex mode):
Master transmits
Startpause
STX LGE ADR 1. n BCC
STX LGE ADR 1. BCCBCC
STX
Slave transmits
Reply delaytime
Startpause
Fig. 3-43 Transmit sequence
The time interval between the last character of the task telegram (BCC) and the start of the reply telegram (STX) is known as the reply delay time. The maximum permissible reply delay time is 20 ms, but it must not be less than the start interval. If node x does not respond within the maximum permissible reply delay time, an error message is deposited in the master. The master than sends the telegram for the next slave node.
Bus structure The data transfer medium and the physical bus interface are essentially determined by what the bus system is used for. The physical interface of the USS protocol is based on the "Recommended Standard RS-485". For point-to-point links, a sub-quantity of EIA RS-232 (CCITT V.24) or TTY (20 mA current loop) can be used as the physical interface. The USS bus is based on a linear topology without branches. Both ends of the line terminate at a node. The maximum cable length (50 m) and therefore the maximum distance between the master and the last slave is limited by the characteristics of the cable, the ambient conditions and the data transfer rate [EIA Standard RS-422-A Dezember 1978, Appendix, Page 14] The number of nodes is limited to a maximum of 33 (1 master, 32 slaves).
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 153
Master
SlaveMaximum 32 slaves
First node Last node
SlaveSlave
Fig. 3-44 USS bus topology
The two ends of a bus line (first node and last node) must be terminated with bus terminating networks. (refer to Section 3.7.1.3). Point-to-point connections are handled just like bus connections. One node has the master function and the other has the slave function. Data is transferred in accordance with Standard EIA 485. RS 232 can be used for point-to-point links. Data transfer is always half-duplex − i.e. alternating between transmitting and receiving − and it must be controlled by the software. The half-duplex technique allows the same cables to be used for both data-transfer directions. This permits simple and inexpensive bus cabling, operation in environments subject to interference and a high data transfer rate. A shielded, twisted two-wire cable is used as the bus cable.
Table 3-16 Structural data
Conductor diameter 2 x ≈ 0,5 mm2
Conductor ≥ 16 x ≤0,2 mm
Lay ratio ≥ 20 twists / m
Overall shield Braided, tin-plated copper wire, diameter ∅ ≥ 1,1 mm2 85 % optical coverage
Overall diameter -∅ 5 mm
External sheath Depending on the requirements regarding flame retardation, deposits after burning etc.
NOTE
All information should only be considered as a recommendation. Deviations or different measures may be required depending on the particular
requirements, the specific application and the conditions on site.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 154 6SE6400-5AW00-0BP0
Table 3-17 Thermal and electrical characteristics
Cable resistance (20°C) ≤ 40 Ω/κµ
Insulation resistance (20°C) ≥ 200 MΩ/km
Operating voltage (20°C) ≥ 300 V
Test voltage (20°C) ≥ 1500 V
Temperature range -40 °C ≤T ≥80 °C
Load capability ≥ 5 A
Capacitance ≤ 120 pF/m
Mechanical characteristics
Single bending: ≤ 5 x outer diameter Repeated bending: ≤ 20 x outer diameter
Recommendations
Standard cable, without any special requirements: Two-core, flexible, shielded conductor in accordance with VDE 0812, with colored PVC sheath. PVC insulation resistant to oil, resistant to cold and petroleum products. Type: LiYCY 2 x 0,5 mm2 e.g. Fa. Metrofunk Kabel-Union GmbH, www.metrofunk.de
Postfach 41 01 09, 12111 Berlin Halogen-free cable (no hydrochloric acid is generated when the cable burns):
Halogen-free, highly flexible, resistant to extreme heat and cold. Sheath manufactured from a special ASS silicon-based composite. Type: ASS 1 x 2 x 0,5 mm2 e.g. Fa. Metrofunk Kabel-Union GmbH, www.metrofunk.de
Postfach 41 01 09, 12111 Berlin Recommended if halogen-free and silicon-free cables are required:
Type: BETAflam 145 C-flex. 2x0,5 mm2 e.g. Fa. Studer-Kabel-AG, http://www.studer-kabel.ch/
Herrenmattstrasse 20, CH 4658 Däniken
The total cable length of the USS connection may not exceed 50 m (max. cable length). The max. data transfer rate depends on the number of connected nodes (devices) as well as on the closed-loop control technique / function selection (processor utilization). Nominal values can be taken from the following table:
Table 3-18 Max. number of nodes (devices) depending on the max. data transfer rate
Max. data transfer rate Max. number of nodes (devices) V/f control Closed-loop vector control
9.6 kbit/s 32 32
19.2 kbit/s 32 32
38.4 kbit/s 32 7
93.7 kbit/s 32 -
115.2 kbit/s 32 -
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 155
NOTE If a higher baud rate or higher number of nodes is required, then the CB option boards (e.g. PROFIBUS, CAN) should be used to ensure disturbance-free operation.
3.7.1.2 The structure of net data
Information which, for example, a SIMATIC S7 control unit (= master) sends to a drive (= slave) or the drive sends to the control unit is placed in the net-data area of each telegram.
General structure of the net-data block The net-data block is divided into two areas:
the PKW (parameter ID value) range the PZD (process data) range
The structure of the net data in the USS-protocol telegram is shown below.
Protocol frame
Parameter ID value(parameter area)
STX LGE ADR(PKW) (PZD)
BCC
PKW: PZD: Process data(process-data area)
Process dataParameterNet data
Fig. 3-45 Telegram structure
The PKW area relates to the handling of the parameter ID value (PKW) interface. The PKW interface is not a physical interface but a mechanism which handles parameter transfer between two communication partners (e.g. control unit and drive). This involves, for example, reading and writing parameter values and reading parameter descriptions and associated texts. All tasks which are performed via the PKW interface essentially involve operator control and visualization, service and diagnosis.
The PZD area contains the signals required for the automation system: ♦ Control word(s) and setpoint(s) from the master to the slave ♦ Status word(s) and actual value(s) from the slave to the master.
PKW area
PKE IND PZD1 • • • PZD16
PZD area
PKW elements
variable length variable length
Fig. 3-46 Structure of the PKW and PZD areas
The two areas together make up the net data block. This structure applies to telegrams from the master to the slave and vice versa.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 156 6SE6400-5AW00-0BP0
PKW area With the help of the PKW mechanism, the following tasks can be performed via any serial interface with the USS protocol:
Reading and writing parameters Reading the description of a parameter
The PKW area can be varied. Depending on the requirements, the following lengths can be parameterized using parameter P2013:
3 words P2013 = 3 4 words P2013 = 4 variable word length P2013 = 127
The following is an example of a structure when access (write/read) is made to single-word (16 bit) parameter values. The PKW area must be permanently set to 3 words at the master and the slave. This setting is made during start-up and should not be altered any more during bus operation.
1st word 2nd word 3rd word
PKE IND PWE1
Parameter ID Index Parameter value 1 The following is an example of a structure when access (write/read) is made to double-word (32 bit) parameter values. Parameterization to a fixed length of 4 words applies to telegrams from the master to the slave and from the slave to the master.
1st word 2nd word 3rd word 4th word
PKE IND PWE1 PWE2
Parameter ID Index Parameter value (double word)
Telegram data transfer with variable telegram length (refer to the following example) means that the slave responds to a telegram from the master with a telegram whose length does not have to be the same length as the telegram from the master to the slave.
1st word 2nd word 3rd word 4th word (m+2). word
PKE IND PWE1 PWE2 . . . . . With:
1 word ≤m ≤118 words (maximum) when 8 PZD words (maximum) are contained in the net data block.
1 word ≤ m ≤ 126 words (maximum) when there is no PZD.
The length of elements PEW1 to PWEm in the reply telegram and what is contained in them depends on the task issued by the master. Variable length means that only the number of words necessary to pass on the appropriate information is transferred. The minimum length, however. is always 3 words. If a slave, for example, transfers a parameter value which is a 16-bit quantity (e.g. the status word in parameter r0052; data format: U16), then only 3 words of the PKW area are sent in the telegram from the slave to the master. If, for example, for MICROMASTER the actual frequency is to be read (parameter r0021), then the PKW area in the telegram from the slave to the master is 4 words large; the reason for this is that the speed is represented as 32-bit quantity (data format: Float). It is mandatory to parameterize for a variable word length, if e.g. all values are to be
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 157
read at once from an “indexed” parameter (refer to "Index", special setting, index = 255). This setting to variable word-length is made during start-up. (refer to parameter P2013).
Parameter ID (PKE) 1st word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit No.:
AK SPM PNU1
Parameter index (IND) 2nd word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit No.:
PNU2 RES TXT Index
Parameter value (PWE)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit No.:
Parameter value, high (PWE1) 3rd word
Parameter value, low (PWE2) 4th word The following applies:
AK Task or reply ID SPM Toggle bit for processing of parameter-change reports
(MICROMASTER does not support this, SPM = 0) PNU Parameter number RES Reserved TXT Read / write from parameter text
(MICROMASTER does not support this, TXT = 0)
CAUTION Do not use a variable word length if SIMATIC S5 or SIMATIC S7 is the master. This setting must be made both at the master as well as at the slave – and
cannot be changed while the bus is operational. NOTE
The PKW area is transferred in increasing order, always starting with the 1st word.
Reserved fields or functions that are not supported should be specifically pre-assigned zero in the master implementation.
The bit 11 (SPM) is the toggle bit for parameter change reports. Parameter change reports when reading/writing parameter texts are not supported by MICROMASTER.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 158 6SE6400-5AW00-0BP0
Task or reply ID (AK): Bits 12 to 15 (AK) contain the task or reply ID. The task IDs are sent in the telegram from the master to the slave. The meaning of the IDs is listed in the following table.
Table 3-19 Task IDs (master -> drive converter)
Reply ID Task ID Meaning
positive negative0 No task 0 -
1 Request parameter value 1 or 2 7
2 Change parameter value (word) and save only in RAM 1 7 or 8
3 Change parameter value (double word) and save only in RAM 2 7 or 8
4 Request descriptive element 1 3 7
5 Changing the descriptive element 1 MICROMASTER does not support this 3 7 or 8
6 Request parameter value (array)1 4 or 5 7
7 Change parameter value (array, word)2 and save only in RAM 4 7 or 8
8 Change parameter value (array, double word)2 and save only in RAM 5 7 or 8
9 Request the number of array elements 6 7
10 Reserved - -
11 Change parameter value (array, double word) and save in RAM and EEPROM2 5 7 or 8
12 Change parameter value (array, word) and save in RAM and EEPROM2 4 7 or 8
13 Change parameter value (double word) and save in RAM and EEPROM 2 7 or 8
14 Change parameter value (word) and save in RAM and EEPROM 1 7 or 8
15 Read or change text MICROMASTER does not support this 15 7 or 8
1 The required element of the parameter description is specified in IND (2nd word) 2 The required element of the indexed parameter is specified in IND (2nd word)
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 159
Correspondingly, the Response IDs are transferred in the telegram from the slave to the master at this position. Depending on the request ID, only specific response IDs are possible.
Table 3-20 Response ID (converter -> master)
Response ID Significance Request
ID 0 No response 0
1 Transfer parameter value (word) 1, 2 or 14
2 Transfer parameter value (double word) 1, 3 or 13
3 Transfer descriptive element 1 4 or 5
4 Transfer parameter value (array, word) 2 6, 7 or 12
5 Transfer parameter value (array, double word) 2 6, 8 or 11
6 Transfer the number of array elements 9
7 Request cannot be executed (with fault number) 1 or 15
8 The PKW interface does not have master authority 2, 3, 5, 7, 8, 11-14 or 15
9 Parameter change report (word) MICROMASTER does not support this -
10 Parameter change report (double word) MICROMASTER does not support this -
11 Parameter change report (array, word) 2 MICROMASTER does not support this -
12 Parameter change report (array, double word) 2 MICROMASTER does not support this -
13 Reserved -
14 Reserved -
15 Transfer text MICROMASTER does not support this 15
1 The required element of the parameter description is specified in IND (2nd word) 2 The required element of the indexed parameter is specified in IND (2nd word)
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 160 6SE6400-5AW00-0BP0
If the response ID has the value 7 (request cannot be executed), then a fault number is saved in parameter value 2 (PWE2). The fault numbers are documented in the following table.
Table 3-21 Fault numbers for the response ID "Request cannot be executed"
Fault No. Significance 0 Inadmissible legal parameter number (PNU); if PNU is not available
1 Parameter value cannot be changed; if the parameter is a visualization parameter
2 Lower or upper limit exceeded
3 Erroneous sub-index
4 No array
5 Incorrect type of data
6 Setting not permitted (can only be reset)
7 Descriptive element cannot be changed; not possible
11 No operator control rights
12 Key word missing, device parameter: ‘access keyl’ and/or ‘special parameter access’ notappropriately set
15 No text array available
17 Request cannot be executed due to operating states; The frequency inverter state presently does not allow the request that was issued
101 Parameter number presently de-activated; In the present frequency inverter state, the parameter has no function (e.g. closed-loop control type)
102
Channel width too small: Only for short channels; the parameterized length of the PKW area has been selected too large due to the restrictions in the device. This fault message can only occur for the USS protocol on the technology module T 100 if basic device parameters are accessed from this interface
103
Incorrect PKW number; only for G-SST 1/2 and SCB interface (USS). The fault number is transferred in the following two cases:
If the request involves all indices of an indexed parameter (request index equal to 255) or the complete parameter description is requested and a variable telegram length was not parameterized.
If, for the request issue, the parameterized number of PKW data in the telegram is too low (e.g.: Changing from a double word and PKW number equal to 3 (words).
104
Parameter value not permissible; This fault number is transferred if the parameter value – that is to be transferred – is not assigned any function in the device or at the time of the change it is not able to be transferred for internal reasons (although it lies within the limits).
105 The parameter is indexed e.g. request: ‘PWE, change word’ for indexed parameters
106 Request not implemented
200 New minimum value
201 New maximum value
203 No BOP/AOP display, Parameter cannot be displayed on the BOP or AOP.
204 The ‘BOP/AOP key word’ does not match the parameter access stage.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 161
Parameter number (PNU) The complete parameter number (refer to the parameter list) is formed from the "basis parameter number” PNU1 and the "page parameter number” PNU2. The following applies: PNU = PNU1 + 2000 • PNU2
With PNU2 definition:
PNU2 2nd word
15 14 13 12 Bit No.:
20 23 22 21 Weighting The parameter areas are mapped using PNU1 and PNU2 as follows:
Basis parameter number PNU1 bits 0 – 10 (PKE)
Page parameter number PNU2 bits 12 – 15 (IND)
Parameter number (area)
0 ... 1999 0 0 ... 1999
0 ... 1999 1 2000 ... 3999
0 ... 1999 2 4000 ... 5999
0 ... 1999 3 6000 ... 7999
0 ... 1999 4 8000 ... 9999
... ... ...
0 ... 1999 15 30000 ... 31999
Index The index (bit 0 to 7), depending on the task, describes a definite element:
desired array element in the case of indexed parameters, desired element of the parameter description,
Special significance of index value 255 For the following requests, the index value 255 has a special significance:
"request parameter descriptive element", or. for the requests to read/write indexed parameters (= arrays)
Here, the following applies:
Task ID Meaning 4 The complete parameter description is requested
6 All values of the indexed parameters are requested This request can generate fault message 102.
7, 8, 11 or 12
All values of the indexed parameters should be changed. These requests can generate fault message 102.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 162 6SE6400-5AW00-0BP0
Parameter value (PWE) The parameter value (PWE) is transferred, depending on the parameterization of the word length (refer to parameter "USS-PKW length" P2013) of the PKW area as word or double word (32 bit). Only one parameter value can be transferred in a telegram. If the word length of the PKW area is parameterized with 3 words (P2013 = 3), then only 16-bit parameters can be transferred. Parameter descriptive elements, that are greater than 16 bit cannot be transferred. If the word length of the PKW area is parameterized to be 4 words (P2013 = 4), then 16 and 32-bit parameters can be transferred. Parameter descriptive elements that exceed 32 bits cannot be transferred. If the word length of the PKW area is parameterized with "variable length" (P2013 = 127), then 16, 32-bit parameter and parameter descriptive elements can be transferred. Further, all elements of an indexed parameter can be read or changed with a single request, as well as the complete parameter description requested if the index corresponds to the value 255 (index = 255). Transferring one 16-bit parameter value: 1. Fixed PKW area, 3 words:
The value is in PWE1 2. Fixed PKW area, 4 words:
The value is in PWE2 (least significant word, 4th word); PWE1 is set to 0. 3. Variable PKW area:
The value is in PWE1. PWE2 and higher not available!
Transferring one 32-bit parameter value: 1. Fixed PKW area, 3 words:
Request is rejected with fault message 103. 2. Fixed PKW area, 4 words:
PWE1 (most significant word; 3rd word) contains the high word of the double word, PWE2 (least significant word; 4th word) contains the low word of the double word.
3. Variable PKW area: As for 2.; PWE3 and higher not available!
Process data area (PZD) Process data is continually exchanged between the master and slaves in this area. At the start of communications it is configured as to which process data is to be exchanged with a slave. For instance, for slave x, the current setpoint is to be transferred in the second PZD (= PZD2). This setting remains for the complete data transfer.
1 word 1 word 1 word 1 word 1 word
PZD1 PZD2 PZD3 PZD4 . . . . . PZD8 PZD1 – PZD8 = process data = control / status word(s) and setpoint / actual value(s)); The control / status word(s), setpoints and actual values required for the automation are transferred in this area. The length of the PZD area is defined by the number of PZD elements (P2012). Contrary to the PKW area, that can be variable, the length of this area between the communication partners (master and slave) must always be permanently declared.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 163
The maximum number of PZD words per telegram is, for MICROMASTER, limited to 8 words (USS-PZD length in MICROMASTER is set using parameter P2012). If only PKW data are to be transferred in the net data block, then the number of the PZD can also be 0! Depending on the data transfer direction, always control word 1 or status word 1 are to be transferred in the PZD1. Depending on the data transfer direction, the main setpoint or the main actual value is always transferred in PZD 2. Additional setpoints or actual values are set in the following process data PZD3 to PZDn. For MICROMASTER, if required, control word 2 or status word 2 should be transferred in PZD4. Request telegram, master ⇒ slave
PZD1 PZD2 PZD3 PZD4 . . . . . PZD8
Control word 1 Setpoint 1 Control word
2 Setpoint 2 . . . . . Setpoint 6
Response telegram, slave ⇒ master
PZD1 PZD2 PZD3 PZD4 . . . . . PZD8
Status word 1 Main actual value 1
Actual value 2status word
2
Actual value 3 . . . . . Actual value
7
NOTE
A maximum of 8 PZD words A minimum of 0 PZD words - i.e. no PZD area in the net data area On the USS bus, PZD n is always transferred before PZD n+1. For MICROMASTER, double words cannot be transferred in the PZD section. Data received from MICROMASTER is always interpreted as 16-bit words. The
appropriate de-normalization is implemented by assigning the appropriate parameters.
If MICROMASTER sends data to the master via the PZD area, then for physical quantities, a normalization is made to a 16-bit value (4000 hex notation).
The setpoint can be freely assigned to the actual value; This means for example that the frequency setpoint is transferred in the request telegram in PZD2 so the actual frequency value can be signaled back in PZD2 in the response telegram (this also makes sense from a technological/process perspective); or however, also another actual value – such as the actual torque value, actual voltage actual value or actual current value. The setpoint can be freely assigned to the actual value; for example the frequency setpoint is transferred in the request telegram in PZD2, which means that the actual frequency value can be signaled back in the response telegram in PZD2 (this also makes sense from a technological/process perspective) – or also another actual value – such as actual torque value, actual voltage value or actual current value.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 164 6SE6400-5AW00-0BP0
3.7.1.3 USS bus configuration via COM link (RS485) In order to ensure disturbance-free USS operation, the bus cable must be terminated at both ends using bus terminating resistors. In this case, the bus cable from the first USS device [node] up to the last USS device [node] should be considered as one bus cable – so that the USS bus should be terminated twice. For the first bus node [device] (e.g. master) and last bus node [device] (e.g. drive converter), th bus terminating resistor must be switched-in.
NOTE
♦ When supplied, the bus terminating resistors are not switched-in!
♦ Please note that you only switch-in the bus terminating at the first bus node [device] and last bus note [device]! The bus terminating resistors should be always set with the system in a no-voltage state (e.g. powered-down)!
♦ Data transfer errors on the bus are possible! In active bus operation, devices where the terminating resistor is switched-in, may not be in a no-voltage state. The terminating resistor draws the voltage from the connected device. This is the reason that the terminating resistor is no longer effective when the device is in a no-voltage state (e.g. when powered down) .
The following diagram shows the structure of a bus connection through terminals 29, 30:
Screening
Screening Screening
Potential equilization cable
RS
485
term
inat
or
RS
485
term
inat
or
Master
0 V(M)
− a terminating resistor must be connected at the first and last devices [nodes] on the bus cable − no bus termination for other devices [nodes]
Fig. 3-47 Connecting the USS bus cable
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 165
When the MICROMASTER is used in an RS485 bus communications network the following is required: 1. A power supply 2. A terminating resistor between P+ and N- at both bus ends
(refer to Fig. 3-48)
Control terminals
RS485 terminator
29
P+
30
N-
1+10 V
20 V
to terminal 2 of the next slave
Fig. 3-48 Connecting the RS485 terminator
If the frequency inverter is the last slave on the bus (refer to Fig. 3-47), then the P+ and N- of the RS485 terminator provided must be connected there to the RS485 terminals (refer to Fig. 3-48). P10 and 0 V can be connected to terminals 1 and 2 for the power supply. If the frequency inverter is the first slave, then the bus should only be terminated there with P+ and N- (120 Ω). If the first or last bus node is not a MICROMASTER 4, then the bus between P+ and N– must be terminated with a resistor (between 120 Ω and 220 Ω).
The bus must be operated with a bias on one or on both ends (pull-up resistance from P+ to P5 or P10, pull-down resistance from N– to 0 V). If the first or last bus node is not a MICROMASTER 4 (e.g. a controller of the S7-200 series), the bus can then be biased by connecting 390 Ω resistors from P+ to P5 and from N– to 0 V.
If the first or last bus node is a controller of the S7-200 series, SIMATIC PROFIBUS connectors, e.g. 6ES7972-0BA41-0XA0, can be used for the bias and the termination.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 166 6SE6400-5AW00-0BP0
NOTE When making the installation it must be ensured that EMC disturbances/noise
cannot result in communication failures/errors or damage to the RS485 drivers. As a minimum, the following measures must be taken: 1) Shield the motor cable and correctly ground the shield at both ends. If at all
possible, avoid interruptions in the cables. If this cannot be avoided, then it must be ensured that the shield continues in an EMC-correct fashion at the connecting locations.
2) All node points must be well grounded (EMC ground). 3) All relay coils must be provided with noise suppression elements. 4) The cables should be routed - as far as possible - separately from other
cables. For RS485 cables it is especially important that they are kept well away from motor cables.
5) The shields of RS485 cables must be correctly grounded. If the AOP communicates via the USS protocol, then contrary to the BOP, the
appropriate USS parameters (Table 3-13 and Table 3-14) should be set. For error-free communications, the appropriate communication parameters must
be harmonized with one another and correctly set - in the frequency inverter, the connected device and/or in the connected option board. Please refer to the corresponding Operating Instructions for the AOP and for the communications modules.
While RS485 communications is operational the power supply must always be available using pull-up/pull-down resistors.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 167
3.8 Fixed frequencies (FF) Number: 15 Parameter range: P1001 – P1028 Warnings - Faults - Function chart number: FP3200, FP3210
A setpoint can be entered via the analog inputs, the serial communication interfaces, the JOG function, the motorized potentiometer as well as also using fixed frequencies. The fixed frequencies are defined using parameters P1001 – P1015 and selected via binector inputs P1020 – P1023, P1025, P1026. The effective fixed frequency setpoint is available via connector output r1024 which means that it can be connected further. If this is to be used as setpoint source, then either parameter P1000 or P0719 should be modified or BICO parameter r1024 should be connected to the main setpoint P1070 or supplementary setpoint P1075. Contrary to parameter P0719, when parameter P1000 is modified, this implicitly changes BICO parameters P1070, P1075.
Example: Fixed frequencies as setpoint source a) Standard method → P1000 = 3 b) BICO method → P1070 = 1024, P1075 = 0
3 methods are available when selecting the fixed frequencies.
Direct selection In this particular mode, the control signal directly selects the fixed frequency. This control signal is entered via the binector inputs. If several fixed frequencies are simultaneously active, then the selected frequencies are added.
Table 3-22 Example for direct coding via digital inputs
FF1 P1001 0 0 0 0 0 1
FF2 P1002 0 0 0 0 1 0
FF3 P1003 0 0 0 1 0 0
FF4 P1004 0 0 1 0 0 0
FF5 P1005 0 1 0 0 0 0
FF6 P1006 1 0 0 0 0 0
FF1+FF2 0 0 0 0 1 1
… …
FF1+FF2+FF3+FF4+FF5+FF6 1 1 1 1 1 1
DIN6 DIN5 DIN4 DIN3 DIN2 DIN1FF0 0 Hz 0 0 0 0 0 0
The fixed frequencies can be selected via the digital inputs as well as also via serial communication interfaces. The fixed frequency is selected, when using digital inputs, using 2 techniques. This will be shown in the following example using the fixed frequency P1001 and digital input 1 (refer to Fig. 3-49). a) Standard methods → P0701 = 15 b) BICO methods → P0701 = 99, P1020 = 722.0, P1016 = 1
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 168 6SE6400-5AW00-0BP0
P1016
P0701 = 15 or P0701 = 99, P1020 = 722.0, P1016 = 1
DIN1
r1024
r0722.0P1020
1
2,3
P1001
0
0
P0702 = 15 or P0702 = 99, P1021 = 722.1, P1017 = 1
P1017
DIN2 r0722.1P1021
1
2,3
P1002
0
0
. . .
. +
. . .
+
Fig. 3-49 Example for directly selecting FF1 via DIN1 and FF2 via DIN2
Direct selection + ON command When this fixed frequency is selected, the fixed frequencies are also directly selected whereby the selection is combined with the ON command. When this technique is used, a separate ON command is not required. The following is obtained essentially analog to the example shown above: a) Standard method → P0701 = 16 b) BICO method → P0701 = 99, P1020 = 722.0, P1016 = 2
Binary-coded selection + ON command Using this technique up to 16 fixed frequencies can be selected using 4 control signals. These 4 control signals are either entered via digital inputs or a serial communications interface. The fixed frequencies are indirectly selected using the binary coding (refer to Table 3-23, → e.g. selected using the digital DIN inputs), whereby the selection is combined with the ON command.
Table 3-23 Example for binary coding via digital inputs
DIN4 DIN3 DIN2 DIN1
0 Hz FF0 0 0 0 0
P1001 FF1 0 0 0 1
P1002 FF2 0 0 1 0
… … … … … …
… … … … … …
P1014 FF14 1 1 1 0
P1015 FF15 1 1 1 1
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 169
Contrary to "Direct selection + ON command", the ON command is only active if the setting for the first 4 binary inputs is set to "Binary-coded selection + ON command" or P0701 = P0702 = P0703 = P0704 = 17. The following is obtained analog to the above example: a) Standard method → P0701 = 17 b) BICO method → P0701 = 99, P1020 = 722.0, P1016 = 3
P1016
P0701 = 17 or P0701 = 99, P1020 = 722.0, P1016 = 3
DIN1 r0722.0P1020
1
2,30
P0702 = 17 or P0702 = 99, P1021 = 722.1, P1017 = 3
P1017
DIN2 r0722.1P1021
1
2,30
. . .
.
0 0 01
1 1 11
Festf requenz 15-650.00 ... 650.00
[Hz]P1015.D (65.00)
r1024
CO: Ist-Festf req.
.
.
....
...Festf requenz 1
-650.00 ... 650.00 [Hz]P1001.D (0.00)
Fig. 3-50 Example for selecting FF1 via DIN1 and FF2 via DIN2 using the binary-coded method
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 170 6SE6400-5AW00-0BP0
3.9 Motorized potentiometer (MOP) Parameter range: P1031 – r1050 Warnings - Faults - Function chart number: FP3100
This function emulates an electromechanical potentiometer to enter setpoints. The motorized potentiometer value is adjusted using the "Raise" and "Lower control signal" which is selected using BICO parameters P1035 and P1036 (refer to Fig. 3-51). The value which has been set is available through connector output r1050 so that it can be further connected and used.
Fig. 3-51 Motorized potentiometer
Selecting via serial interfaces The MOP functionality can be selected via the operator panels (refer to Section 3.2), digital inputs as well as via serial interfaces (refer to the example). Parameterization is also possible directly using BICO parameters P1035 and P1036 as well as also parameters P0700 and P0719. In this case, for a value assigned to P0700, the BICO parameter is appropriately modified.
Example: Command source via "USS on BOP link" interface a) Standard method → P0700 = 4
b) BICO method → P1035 = 2032.13 P1036 = 2032.14 :::: (refer to P0700 for a complete list)
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 171
If the motorized potentiometer is to be used as setpoint source, then either parameter P1000 or P0719 should be modified or the BICO parameter r1050 should be connected to the main setpoint P1070 or supplementary setpoint P1075. Contrary to parameter P0719, when parameter P1000 is modified, this implicitly changes BICO parameters P1070, P1075.
Example: Setpoint via the motorized potentiometer (MOP) a) Standard method → P1000 = 1 b) BICO method → P1070 = 1050 P1075 = 0 The MOP is configured using the following parameters and has the mode of operation as shown in Table 3-24:
Limits using the minimum frequency P1080 or maximum frequency P1082 Ramp-up/ramp-down time P1120 or P1121 Inhibits MOP reversing function P1032 Saves the MOP setpoint P1031 MOP setpoint P1040
Table 3-24 Mode of operation of the MOP
Motorized potentiometer Lower Raise
Function
0 0 Setpoint is frozen
0 1 Raise setpoint
1 0 Lower setpoint
1 1 Setpoint is frozen
Selecting via BOP or AOP The following settings / operator actions should be made when selecting the motorized potentiometer using the BOP or AOP:
Table 3-25 Selecting the motorized potentiometer
Parameters / keys BOP AOP (at the BOP link) Command source
P0700 1 4
P1000 1
P1035 - 2032.13 (2032.D)
P1036 - 2032.14 (2032.E)
Raise MOP output frequency
Setpoint source
Lower MOP output frequency
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 172 6SE6400-5AW00-0BP0
3.10 JOG Parameter range: P1055 – P1061 Warnings A0923 Faults - Function chart number: FP5000
The JOG function is used as follows: To check the functionality of the motor and drive inverter after commissioning
has been completed (the first traversing motion, checking the direction of rotation, etc.)
Positioning a drive / a driven load into a specific position Traversing a drive, e.g. after a program has been interrupted
The drive is traversed using this function by entering fixed frequencies P1058, P1059. The JOG mode can be selected either using the operator panel (refer to Section 3.2), digital inputs or also via the serial interfaces (refer to the example). An ON/OFF command is not used to move the drive, but when the "JOG keys" are pressed. These "JOG keys" are selected using the BICO parameters P1055 and P1056.
JOG right
f
P1058
P1059
A0923 A0923
P10
60
P10
60
(0)P1055
(0)P1056
"1"
"0"
"1"
"0"
t
t
t
P10
61
DIN
BOP
USSBOP link
USSCOM link
CBCOM link
JOG left
P1082
-P1082
P10
61
Fig. 3-52 JOG counter-clockwise and JOG clockwise
If both JOG keys are simultaneously pressed, then the instantaneous frequency is kept (constant velocity phase) and alarm A0923 is output. When a key is pressed, the drive inverter accelerates the motor to the fixed frequency in the time entered in P1060. This frequency is only exited after the key has been cancelled and the drive then brakes down to 0 Hz in the time entered in P1061.
In addition to the explicit parameterization (P1055 and P1056), the JOG functionality is also enabled via parameter P0700 or P0719 (implicit parameterization). In this case, if a value is assigned to P0700, the BICO parameter is appropriately modified.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 173
Example: Command source via "USS on BOP link" interface a) Standard method → P0700 = 4 b) BICO method → P1055 = 2032.8 P1056 = 2032.9 :::: (refer to P0700 for a complete list)
3.11 PID controller (technological controller) Parameter range: P2200 P2201 – P2355 Warnings - Faults - Function chart number: FP3300, FP3400, FP5100 Features: - cycle time: 8 ms
In addition to the open-loop/closed-loop control of a three-phase motor (standard application for a frequency inverter), MICROMASTER has a technology controller. This can be used to control process quantities – such as pressure or level. Depending on the application, different control structures are required to control process quantities. For MICROMASTER, the following structures have been integrated; these can be selected or de-selected using parameters P2200, P2251 (also refer to Fig. 3-53): a) Variable-speed drive (VSD) b) Closed-loop PID control c) Closed-loop dancer roll control The PID controller – integrated in MICROMASTER – is required for control structures b) and c). The frequency inverter can address many new applications using the higher-level control (closed-loop PID/dancer roll control). The following typical applications can be implemented:
Closed-loop pressure control for extruders Closed-loop water level control for pump drives Closed-loop temperature control for fan drives Closed-loop dancer roll position control for winder applications And similar control tasks
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 174 6SE6400-5AW00-0BP0
Application Control structure
SUMsetpoint
PIDRFG PID
AFM RFG
x2
v2 v1
4
2PID
setpoint
PIDfeedback
PIDRFG PID PID
limit AFM RFG
v2*
x2*
x2
p2*
p2
P2200 = 0:0 2)
P2251 = 01
P2200 = 1:0 2)
P2251 = 02
P2200 = 0:0 1)
P2251 = 13
P2200 = 1:0 1)
P2251 = 14
−
−
−
ON: activeOFF1/3: active
ON: -OFF1/3: -
ON: -OFF1/3: -
SUM PID controller RFG PID-RFG
1) will take change with drive running2) change only taken when drive stopped
−
−
VSD
Dancer control
ON: activeOFF1/3: active
ON: activeOFF1/3: active
ON: activeOFF1/3: active
ON: activeOFF1/3: -
ON: -OFF1/3: active
PIDsetpoint
PIDfeedback
PIDlimit
Motorcontrol
Motorcontrol
Setpoint via
PID control
VSD
PID control
Dancer control
Variable speed drive (VSD)
1
3
p2
SUMsetpoint AFM RFG
Motorcontrol
v
Fig. 3-53 Structure of the technology controller
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 175
3.11.1 Closed-loop PID control MICROMASTER has a technology controller (PID controller, enabled using P2200); this can be used to execute basic, higher-level control functions. The technological setpoints and actual values can be entered via the PID motorized potentiometer (PID-MOP), PID fixed setpoint (PID-FF), analog inputs (ADC, ADC2) or via serial interfaces (USS on BOP link, USS on COM link, CB on COM link) (refer to the example). The appropriate parameterization of the BICO parameter defines which setpoints or actual values are to be used (refer to Fig. 3-54).
PIDMOP
ADC
PIDSUM PID
PIDFF
USSBOP link
USSCOM link
CBCOM link
ADC2
P2254
P2253PIDRFG
PIDPT1
− ∆PID
P2200
P2264 PIDPT1
PIDSCL
&
P2251
OutputPID
0
1
Motorcontrol
Fig. 3-54 Structure of the technological controller (PID controller)
Important parameter settings for the setpoint and actual value sources of the closed-loop PID control:
Parameter
BI: Enable PID controllerP2200
Parameter text Setting Meaning
1.0 PID controller always activeDigital input x722.x
CI: PID setpointP2253
Analog input 1755.0USS on BOP link2015.1USS on COM link2019.1CB on COM link2050.1
CI: PID feedbackP2264 755.0 Analog input 1Analog input 2755.1
PID modeP2251 0 PID as setpoint2224 Fixed PID setpoint (PID-FF)
PID-MOP2250
NOTICE Changes in parameter P2200 take effect only after a fresh ON command.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 176 6SE6400-5AW00-0BP0
Example: Permanent PID controller should fulfill the following secondary conditions: PID controller enable and PID setpoint input via PID fixed frequencies and PID actual value via the analog input
Parameterization: a) Permanent PID controller enable: P2200 = 1.0 b) Setpoint input via PID-FF: P2253 = 2224 c) Actual value input via analog input ADC: P2264 = 755 d) Setpoint input via PID: P2251 = 0
The supplementary (additional) setpoint is added to the main setpoint (PID-SUM) and the sum is fed to the setpoint filter (PID-PT1) at the setpoint-actual value summation point via the PID ramp-function generator (PID-RFG). The source of the supplementary setpoint (BICO parameter P2254), the ramp-up / ramp-down times of the PID ramp-function generator (P2257, P2258) as well as also the filter time (P2261) can be adapted to the particular application by appropriately parameterizing the corresponding parameters.
Similar to the PID setpoint branch, the actual value branch of the technological controller has a filter (PID-PT1) which can be set using parameter P2265. In addition to the smoothing, the actual value can be modified using a scaling unit (PID-SCL).
The technological controller can be parameterized as either P, I, PI or PID controller using parameters P2280, P2285 or P2274.
+
-ddt
+
+
0
1
PIDsetpoint
P2274
P2263
PIDfeedback
r2262
r2272
Kp Tn
P2285P2280
r2273
Motorcontrol
x
y
P2291
P2293
P2293
P2292
r2294
Fig. 3-55 PID controller
For specific applications, the PID output quantity can be limited to defined values. This can be achieved using the fixed limits - P2291 and P2292. In order to prevent the PID controller output exercising large steps at power-on, these PID output limits are ramped-up with ramp time P2293 from 0 to the corresponding value P2291 (upper limit for the PID output) and P2292 (lower limit for the PID output). As soon as these limits have been reached, the dynamic response of the PID controller is no longer limited by this ramp-up/ramp-down time (P2293).
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 177
3.11.1.1 PID motorized potentiometer (PID-MOP) Parameter range: P2231 – r2250 Warnings - Faults - Function chart number: FP3400
The PID controller has a PID motorized potentiometer which can be separately adjusted. The functionality is identical with the motorized potentiometer (refer to Section 3.9), whereby the PID parameters are emulated in the range from P2231 – r2250 (refer to the comparison → Table 3-26).
Table 3-26 Correspondence between the parameters
PID motorized potentiometer Motorized potentiometer P2231[3] Setpoint memory of PID-MOP P1031[3] Setpoint memory of the MOP
P2232 Inhibit rev. direct. of PID-MOP P1032 Inhibit reverse direction of MOP
P2235[3] BI: Enable PID-MOP (UP-CMD) P1035[3] BI: Enable MOP (UP command)
P2236[3] BI: Enable PID-MOP (DOWN- CMD)
P1036[3] BI: Enable MOP (DOWN command)
P2240[3] Setpoint of PID-MOP P1040[3] Setpoint of the MOP
r2250 CO: Output setpoint of PID-MOP r1050 CO: Act. output freq. of the MOP
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 178 6SE6400-5AW00-0BP0
3.11.1.2 PID fixed setpoint (PID-FF) Number: 15 Parameter range: P2201 – P2228 Warnings - Faults - Function chart number: FP3300, FP3310
Analog to the fixed frequencies (refer to Section 3.7), the PID controller has separate programmable PID fixed setpoints. The values are defined using parameters P2201 – P2215 and are selected using binector inputs P2220 – P2223, P2225, P2226. The selected PID fixed setpoint is available via connector output r2224 where it can be further processed (e.g. as PID main setpoint → P2253 = 2224). 3 methods are available to select the PID fixed setpoints, analog to the fixed frequencies (Section 3.7):
Direct selection Direct selection + ON command Binary-coded selection + ON command
The methods are selected using parameters P2216 – P2219, P2225, P2227.
P2216
P0701 = 15orP0701 = 99, P2220 = 722.0, P2216 = 1
DIN1
r2224
r0722.0P2220
1
2,3
P2201
0
. . . .0
. . .
.
. . . .
Fig. 3-56 Example to directly select the PID fixed frequency of fixed frequency 1 via DIN1
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 179
3.11.1.3 PID dancer roll control For various continuous production processes, e.g. in the paper and pulp industry, or in the manufacture of cables, it is necessary to control (closed-loop) the velocity of stations along the production process so that the continuous material web is not subject to any inadmissible tension levels. It is also important that no folds or creases are formed. For applications such as these, it is practical to provide a type of material buffer in the form of a loop with a defined tension. This provides a de-coupling between the individual drive locations. This loop represents the difference between the material fed-in and that fed-out and therefore indicates the process quality. Using the PID dancer roll control, with MICROMASTER 440 it is possible to ensure that continuous material webs have a constant tension.
SUMsetpoint
PIDRFG PID
AFM RFG
x2
v2 v1
v2*
x2*
x2
−
PIDsetpoint
PIDfeedback
PIDlimit
Motorcontrol
Stru
ctur
eA
pplic
atio
n
Fig. 3-57 PID dancer roll control
The velocity v1 is assumed to be an independent disturbance; the input velocity v2 should be controlled using drive rolls A2 so that the length x2 of the loop corresponds, as far as possible, to the setpoint. The structure and important parameters for the PID dancer roll control are listed in Fig. 3-58 and Table 3-27.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 180 6SE6400-5AW00-0BP0
NOTE When selecting the closed-loop dancer roll control it should be noted that neither PID-MOP nor PID-FF should be used - but instead the MOP (motorized potentiometer, refer to Section 3.9) or the FF (fixed frequencies, refer to Section 3.7).
MOP
ADC
PIDSUM PID
FF
USSBOP link
USSCOM link
CBCOM link
ADC2
P2254
P2253PIDRFG
PIDPT1
−∆PID
P2200
P2264 PIDPT1
PIDSCL
&
P2251= 1
OutputPID
0
1
Motorcontrol
P22
57
P22
58
P22
61
P2271
P22
69
P22
70
P2265
P22
80
P22
85
0
SUM
P1070
P1075 AFM
P11
20
P11
21
RFG
Fig. 3-58 Structure of the closed-loop PID-dancer roll control
Table 3-27 Important parameters for the PID dancer roll control
Parameter
BI: Enable PID controllerP2200
Parameter text Setting Meaning
1.0 PID controller always activeDigital input x722.x
CI: PID setpointP2253 1024 Fixed setpoint (FF)MOP1050Analog input 1755.0USS on BOP link2015.1USS on COM link2019.1CB on COM link2050.1
CI: PID feedbackP2264 755.0 Analog input 1Analog input 2755.1
CI: Main setpointP1070
PID mode
1024 Fixed setpoint (FF)MOP1050Analog input 1755.0USS on BOP link2015.1USS on COM link2019.1CB on COM link2050.1
P2251 1 PID as trim
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 181
3.12 Setpoint channel The setpoint channel (refer to Fig. 3-59) forms the coupling element between the setpoint source and the closed-loop motor control. MICROMASTER has a special characteristic which allows the setpoint to be entered simultaneously from two setpoint sources. The generation and subsequent modification (influencing the direction, suppression frequency, up/down ramp) of the complete setpoint is carried-out in the setpoint channel.
MOP
ADC
FF
USSBOP link
USSCOM link
CBCOM link
ADC2
Setpoint source
Mainsetpoint
Additonalsetpoint
SUM AFM Limit RFG
Setpoint channel Motorcontrol
Motorcontrol
Fig. 3-59 Setpoint channel
3.12.1 Summation and modification of the frequency setpoint (AFM)
Parameter range: P1070 – r1114 Warnings - Fault - Function chart number: FP5000, FP5200
For applications where the control quantities are generated from central control systems, fine tuning is often required locally on-site (correction quantity). For MICROMASTER, this can be very elegantly realized using the summation point where the main and supplementary (additional) setpoint are added in the setpoint channel. In this case, both quantities are simultaneously read-in via two separate or one setpoint source and summed in the setpoint channel. Depending on external circumstances, the supplementary setpoint can be dynamically disconnected or switched-in to the summation point (refer to Fig. 3-60). This functionality can be used to advantage, especially for discontinuous processes.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 182 6SE6400-5AW00-0BP0
AFM Limit RFG
r1078
0 1
CI: Add. setp.scal
(1:0)P1076.C
CI: Add. setpoint
(0:0)P1075.C
(0:0)
BI: Disab.add.setpP1074.C
CI: Main setp scal
(1:0)P1071.C
CI: Main setpoint
(755:0)P1070.C
+
+ Motorcontrol
Fig. 3-60 Summation
MICROMASTER has the following possibilities to select the setpoint source: 1. P1000 – selecting the frequency setpoint source 2. P0719 – selecting the command / setpoint source 3. BICO parameterization
- P1070 CI: Main setpoint - P1075 CI: Additional setpoint
Further, the main setpoint as well as the supplementary (additional) setpoint can be scaled independently of one another. In this case, for example, a user can simply implement an override function using the appropriate parameterization.
A scan sequence is generally associated with a forwards and a backwards motion. When selecting the reversing functionality, after reaching the end position, a direction of rotation reversal can be initiated in the setpoint channel (refer to Fig. 3-61).
On the other hand, if it is to be prevented that a direction of rotation reversal or a negative frequency setpoint is to be entered via the setpoint channel, then this can be inhibited using BICO parameter P1110.
SUM -1
0
1
0
1
P1113r1078 P1110 P1091 P1094
P1101
...
Skip Limit
P1080 P1082
RFG
Fig. 3-61 Modifying the frequency setpoint
Driven machines can have one or several resonance points in the range from 0 Hz up to the reference frequency. These resonance points result in oscillations which, under worst case conditions, can damage the driven load. Using suppression frequencies, MICROMASTER allows these resonant frequencies to be passed through as quickly as possible. This means that the suppression frequencies increase the availability of the driven load over the long term.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 183
3.12.2 Ramp-function generator (RFG) Parameter range: P1120, P1121 r1119, r1170 P1130 – P1142 Warnings - Faults - Function chart number: FP5000, FP5300
The ramp-function generator is used to limit the acceleration when the setpoint changes according to a step function. This therefore helps to reduce the stressing on the mechanical system of the machine. An acceleration ramp and a braking ramp can be set independently of one another using the ramp-up time P1120 and the ramp-down time P1121. This allows a controlled transition when the setpoint is changed (refer to Fig. 3-62).
With
out r
ound
ing
t
ffmax
P1120 P1121
f2
f1
ffmax
P1133P1132P1131P1130 t
f2
f1tup tdown
With
roun
ding
for P1131) P1130(21 P1120
P1082 f - f 12 +≥⋅
P1120 P1082
f - fP1131) P1130(21
t 12up ⋅++=
for P1133) P1132(21 P1121
P1082 f - f 12 +≥⋅
P1121 P1082
f - fP1133) P1132(21
t 12down ⋅++=
Where the rounding times are increased to be greater than the ramp period then the ramp period is determined by the following equations:
( ) ( )( ) ⎟⎟
⎠
⎞⎜⎜⎝
⎛ +⋅⎟⎟⎠
⎞⎜⎜⎝
⎛
+⋅⋅⋅−⋅=
1130P1131P1
1131P1130Pf1130P1120Pff2
tmax
212
up
( ) ( )( ) ⎟⎟
⎠
⎞⎜⎜⎝
⎛ +⋅⎟⎟⎠
⎞⎜⎜⎝
⎛
+⋅⋅⋅−⋅=
1132P1133P1
1133P1132Pf1132P1120Pff2
tmax
212
down
Fig. 3-62 Ramp-function generator
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 184 6SE6400-5AW00-0BP0
In order to avoid torque surges at the transitions (constant velocity phase ←→ accelerating / braking phase), additional rounding-off times P1130 – P1133 can be programmed. This is especially important for applications (e.g. transporting/pumping liquids or for cranes) which require an especially "soft", jerk-free acceleration and braking.
If the OFF1 command is initiated while the drive is accelerating, then rounding-off can be activated or de-activated using parameter P1134 (refer to Fig. 3-63). These rounding-off times are defined using parameters P1132 and P1133.
f
OFF1
ON
t
Setpoint reachedfSet
t
f
P1132 > 0P1133 > 0
P1132
Setpoint reached
Setpoint not reached
fSet
t
Setpoint not reached
P1134 = 0
P1134 = 1
P1133 P1133P1132
P1132 P1133 P1133
Fig. 3-63 Rounding off after an OFF1 command
In addition to the rounding-off times, the ramp-function generator can be influenced using external signals. The ramp-function generator provides the following functionality using BICO parameters P1140, P1141 and P1142 (refer to Table 3-28).
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 185
Table 3-28 BICO parameters for ramp-function generator
Parameter Description P1140 BI: RFG enable The ramp-function generator output is set to 0 if the
binary signal = 0.
P1141 BI: RFG start The ramp-function generator output keeps its actual value if the binary signal = 0.
P1142 BI: RFG enable setpoint If the binary signal = 0, then the ramp-function generator input is set to 0 and the output is reduced to 0 via the ramp-function generator ramp.
The ramp-function generator itself is enabled after the pulses have been enabled (inverter enable) and after the excitation time has expired (P0346). After limiting to the maximum speeds for the positive and negative directions of rotation (P1082, - P1082 or 0 Hz for the direction of rotation inhibit) the setpoint speed for the control is obtained (r1170). NOTE The maximum frequency of the setpoint channel is set using parameter P1080. In V/f mode the maximum frequency is 650 Hz. In vector mode the maximum frequency it is limited to 200 Hz (r1084).
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 186 6SE6400-5AW00-0BP0
3.12.3 OFF/braking functions Parameter range: P1121, P1135, P2167, P2168 P0840 – P0849 r0052 bit 02 Warnings - Faults - Function chart number: -
The drive inverter and the user must respond to an extremely wide range of situations and stop the drive. In this case, both requirements relating to operations as well as drive inverter protective functions (e.g. electrical and thermal overload) and man-machine protective functions have to be taken into account. As a result of the different OFF/braking functions (OFF1, OFF2, OFF3) MICROMASTER can flexibly respond to the requirements mentioned above.
OFF1 The OFF1 command is closely coupled to the ON command. When the ON command is withdrawn, then OFF1 is directly activated. The drive is braked by OFF1 with the ramp-down time P1121. If the output frequency falls below the parameter value P2167 and if the time in P2168 has expired, then the inverter pulses are cancelled.
tP2168
t
P2167
Operation
actf
OFF1
P1082fmax
r0052 Bit02P1121
P1082 f P1121 t
21AUS,down ⋅=
tdown,AUS1
Pulsencellation
f 2
Fig. 3-64 OFF1
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 187
NOTE OFF1 can be entered using a wide range of command sources via BICO
parameter P0840 (BI: ON/OFF1) and P0842 (BI: ON/OFF1 with reversing). BICO parameter P0840 is pre-assigned by defining the command source using
P0700. The ON and the following OFF1 command must have the same source. If the ON/OFF1 command is set for more than one digital input, then only the
digital input that was last set, is valid, e.g. DIN3 is active. OFF1 is low active When simultaneously selecting the various OFF commands, the following
priority applies: OFF2 (highest priority) – OFF3 – OFF1 OFF1 can be combined with DC current braking or compound braking. When the motor holding brake MHB (P1215) is activated, for an OFF1, P2167
and P2168 are not taken into account.
OFF2 The inverter pulses are immediately cancelled by the OFF2 command. This means that the motor coasts-down and it is not possible to brake in a controlled fashion.
t
t
actfP1082
fmax
r0052 Bit02
Operation
OFF2
Pulseancellation
Fig. 3-65 OFF2
NOTE The OFF2 command can have one or several sources. The command sources
are defined using BICO parameters P0844 (BI: 1. OFF2) and P0845 (BI: 2. OFF2).
As a result of the pre-assignment (default setting), the OFF2 command is set to the BOP. This source is still available even if another command source is defined (e.g. terminal as command source → P0700 = 2 and OFF2 is selected using DIN2 → P0702 = 3).
OFF2 is low-active When simultaneously selecting the various OFF commands, the following
priority applies: OFF2 (highest priority) – OFF3 – OFF1
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 188 6SE6400-5AW00-0BP0
OFF3 The braking characteristics of OFF3 are identical with those of OFF1 with the exception of the autonomous OFF3 ramp-down time P1135. If the output frequency falls below parameter value P2167 and if the time in P2168 has expired, then the inverter pulses are cancelled as for the OFF1 command.
tP2168
t
P2167
Operation
actf
OFF3
P1082fmax
r0052 Bit02P1135
P1082 f P1135 t
23AUS,down ⋅=
tdown,AUS3
Pulsencellation
f 2
Fig. 3-66 OFF3
NOTE OFF3 can be entered using a wide range of command sources via BICO parameters P0848 (BI: 1. OFF3) and P0849 (BI: 2. OFF3).
OFF3 is low active When simultaneously selecting the various OFF commands, the following
priority applies: OFF2 (highest priority) – OFF3 – OFF1
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 189
3.12.4 Manual / automatic operation Parameter range: P0700, P1000, P0810, P0811 Warnings - Faults - Function chart number: -
It is necessary to change-over from the automatic mode into the manual mode to load and unload production machines and to feed new materials (e.g. batch processing). The machine operator carries-out the preparatory activities for subsequent automatic operation in the manual mode. In the manual mode, the machine operator locally controls the machine (enters the ON/OFF command as well as also the setpoint). A changeover is only made into the automatic mode after the set-up has been completed. In the automatic mode, the control (open-loop) of the machines and production processes are handled by a higher-level control system (e.g. PLC). This operation is maintained until it is necessary to again load and unload the machine or feed new material into the machine or production process. For MICROMASTER 440, indexed parameters P0700 or P1000 and BICO parameters P0810 and P0811 are used to changeover (toggle between) the manual/automatic modes. The command source is defined using P0700 and the setpoint source is defined using P1000 (refer to Table 3-30), whereby index 0 (P0700[0] and P1000[0]) defines the automatic mode and index 1 (P0700[1] and P1000[1]) the manual mode. BICO parameters P0810 and P0811 are used to changeover (toggle between) the automatic and manual modes. These BICO parameters can be controlled from any control source (refer to Table 3-29). In so doing, in addition to P0700 and P1000, also all of the other CDS parameters are changed over (manual/automatic changeover is generalized as a CDS changeover).
BOP
Setpointchannel
Motorcontrol
Sequence control
MOP
ADC
FF
Terminals
USSCB
Com
man
d so
urce
Set
poin
t sou
rce
P0700[0] = 2
P0700[1] = 1
CmdRemote
CmdLocal
P1000[0] = 2
P1000[1] = 3
SetpointRemote
SetpointLocal
P0810
0
1
2
0
1
2
P07
00P
1000
P0811
Cmd3. CDS
Setpoint3. CDS
Fig. 3-67 Changing-over using the BICO parameters P0810 and P0811
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 190 6SE6400-5AW00-0BP0
Table 3-29 Examples for settings of parameter P0810
Parameter setting Command source
P0810 = 722.2 requires P0703 = 99 Digital input 3 P0810 = 2032.15 USS at the BOP link P0810 = 2036.15 USS at the COM link P0810 = 2090.15 CB at the COM link
Table 3-30 Possible settings for parameters P0700 and P1000
Value
Command source (P0700) Value
Setpoint source (P1000)
1 BOP (keyboard) 1 MOP setpoint 2 Terminal strip 2 Analog setpoint 4 USS at the BOP link 3 Fixed frequency 5 USS at the COM link 4 USS at the BOP link 6 CB at the COM link 5 USS at the COM link
6 CB at the COM link 7 Analog setpoint 2 10 No main setpoint + MOP setpoint ...
77 Analog setpoint 2 + analog setpoint 2
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 191
3.13 Free function blocks (FFB) Parameter range: P2800 – P2890 Warnings - Faults - Function chart number: FP4800 – FP4830 Cycle time: 128 ms
For many applications, interlocking logic is required in order to control (open-loop) the drive inverter. This interlocking logic couples several states (e.g. access control, plant/system state) to form a control signal (e.g. ON command). Previously this was implemented using either a PLC or relays. This represented additional costs for the plant or system. In addition to logic operations, increasingly, arithmetic operations and storage elements are required in drive inverters which generate a new unit from several physical quantities. This simplified PLC functionality is integrated in MICROMASTER 440 using the freely programmable function blocks (FFB).
The following function blocks are integrated in MICROMASTER 440:
Table 3-31 Free function blocks
No. Type Example 3 AND AND 1
P2800 P2801[0]
AB
C&P2810
r2811
A B C0 0 00 1 01 0 01 1 1
Index0
Index1
3 OR OR 1
AB
CP2816
r2817
A B C0 0 00 1 11 0 11 1 1
1
P2800 P2801[3]
Index0
Index1
3 XOR XOR 1
AB
CP2822
r2823
A B C0 0 00 1 11 0 11 1 0
1=
P2800 P2801[6]
Index0
Index1
3 NOT NOT 1
P2828r28291 CA A C
0 11 0
P2800 P2801[9]
Index0
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 192 6SE6400-5AW00-0BP0
No. Type Example 2 D-FlipFlops D-FlipFlop 1
1
P2834 SET (Q=1)
RESET (Q=0)
D
STORE
POWER ON
r2835
r2836
Q
Q
P2800 P2801[12]
Index0
Index1
Index2
Index3
SET RESET D STORE Q Q1 0 x x 1 00 1 x x 0 11 1 x x Qn-1 Qn-1
0 0 1 1 00 0 0 0 1
POWER-ON 0 1 3 RS-FlipFlops RS-FlipFlop 1
P2800 P2801[14]
SET(Q=1)
RESET(Q=0)
Q
Q
P2840
POWER ON 1
r2841
r2842
Index0
Index1
SET RESET Q Q0 0 Qn-1 Qn-1
0 1 0 11 0 1 01 1 Qn-1 Qn-1
POWER-ON 0 1 4 Timer Timer 1
T 0
0 T
T T
r2852
1 r2853
P2849
0
1
2
3
In Out
NOut
P2851(0)P2850 (0.000)P2800 P2802.0 Delay Time Mode
ON Delay
OFF Delay
ON/OFF Delay
PulseGernerator
Index0
T
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 193
No. Type Example 2 ADD ADD 1
r2870x1
x2
200%
-200%
P2800 P2802[4]
Result = x1 + x2If: x1 + x2 > 200% →
x1 + x2 < -200% → Result = 200% Result = -200%
Result
P2869
x1 + x2
Index0
Index1
2 SUB SUB 1
r2874x1
x2
200%
-200%
P2800 P2802[6]
Result = x1 - x2If: x1 - x2 > 200% →
x1 - x2 < -200% → Result = 200% Result = -200%
Result
P2873
x1 + x2
Index0
Index1
2 MUL MUL 1
r2878x1
x2
200%
-200%
100%x2x1∗
> 200% →
< -200%→
%1002x1x
%1002x1x
∗
∗ Result = 200%
Result = -200%
If:
P2877
Index0
Index1
%100
2x1x ∗
P2800 P2802[8]
Result =
Result
2 DIV DIV 1
r2882x1
x2
200%
-200%
2X
%1001x ∗
x2100%x1∗
P2800 P2802[10]
> 200% →
< -200% → x2100%x1
x2100%x1
∗
∗ Result = 200%
Result = -200%
If:
P2881
Index1
Index0
Result =
Result
2 CMP CMP 1
P2885
r2886x1
x2Out
x1 ≥ x2 → Out = 1x1 < x2 → Out = 0
P2800 P2802[12]
Out = x1 ≥ x2
CMPIndex0
Index1
2 FFB setpoints
(connector settings)
P2889
P2890
Connector Setting in %
Range : -200% ... 200%
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 194 6SE6400-5AW00-0BP0
The free function blocks (FFB) are enabled in two steps: 1. General enable P2800:
The function "Free function blocks (FFB)" is enabled using parameter P2800 (P2800 =1).
2. Specific enable P2801, P2802: Using parameter P2801 or P2802, the particular function block is enabled (P2801[x] > 0 or P2802[x] > 0) and the sequence in which they are executed is also defined.
All free function blocks are called within the 128 ms time slice (cycle time). Further, to adapt to the application, the chronological sequence in which the FFB are executed, can also be controlled. This is especially important so that the FFB are executed in the sequence which is technologically correct. Parameter P2801 and P2802 are used for the individual enable function as well as to define the priority in which the blocks are executed. The following priority levels can be assigned: 0 Inactive 1 Level 1 2 Level 2 3 Level 3 The following Table indicates that the priority decreases from the top towards the bottom (priority 1 → level) or from the right to left (priority 2 → line) (refer to Table 3-32).
Table 3-32 FFB priority table
3210
P28
02 [1
3] C
MP
2P
2802
[12]
CM
P 1
P28
02 [1
1] D
IV 2
P28
02 [1
0] D
IV 1
P280
2 [9
] M
UL
2P2
802
[8]
MU
L 1
P28
02 [7
] S
UB
2P
2802
[6]
SU
B 1
P280
2 [5
] A
DD
2P2
802
[4]
AD
D 1
P28
02 [3
] T
imer
4P
2802
[2]
Tim
er 3
P28
02 [1
] T
imer
2P
2802
[0]
Tim
er 1
P28
01 [1
6] R
S-F
F 3
P28
01 [1
5] R
S-F
F 2
P28
01 [1
4] R
S-F
F 1
P280
1 [1
3] D
-FF
2P2
801
[12]
D-F
F 1
P280
1 [1
1] N
OT
3P2
801
[10]
NO
T 2
P280
1 [9
] N
OT
1P2
801
[8]
XO
R 3
P280
1 [7
] X
OR
2P2
801
[6]
XO
R 1
P280
1 [5
] O
R 3
P280
1 [4
] O
R 2
P280
1 [3
] O
R 1
P280
1 [2
] A
ND
3P2
801
[1]
AN
D 2
P280
1 [0
] A
ND
1
LevelLevelLevelInactive
low high
Prio
rity
1
Priority 2
low
Example 1:
Enabling the FFB: P2800 = 1 Enabling individual FFB including assigning a priority: P2801[0] = 1 AND 1 P2801[1] = 2 AND 2 P2801[2] = 3 AND 3 P2802[12] = 2 CMP 1 P2802[13] = 3 CMP 2 The FFB are calculated in the following sequence: AND 3, CMP2, AND 2, CMP 1, AND 1
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 195
Example 2: Enabling the FFB: P2800 = 1 Enabling individual FFB including assigning a priority: P2801[3] = 2 OR 1 P2801[4] = 2 OR 2 P2802[3] = 3 Timer 4 P2801[0] = 1 AND 1
The FFB are calculated in the following sequence: Timer 4, OR 1, OR 2, AND 1 The function blocks are interconnected using BICO technology (refer to Section 3.1.2.3). In so doing, the function blocks can be connected with one another as well as to other signals and quantities as long as these signals / quantities have the appropriate attribute (BO, BI, CO and CI).
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 196 6SE6400-5AW00-0BP0
3.14 Motor holding brake (MHB) Parameter range: P1215 P0346, P1216, P1217, P1080 r0052 bit 12 Warnings - Faults - Function chart number: -
For drives which must be secured when powered-down to prevent them undesirably moving, the MICROMASTER brake sequence control (enabled via P1215) can be used to control the motor holding brake.
Before opening the brake, the pulse inhibit must be removed and a current impressed which keeps the drive in that particular position. In this case, the impressed current is defined by the min. frequency P1080. A typical value in this case is the rated motor slip r0330. In order to protect the motor holding brake from continuous damage, the motor may only continue to move after the brake has been released (brake release times lie between 35 ms and 500 ms). This delay must be taken into account in parameter P1216 "Holding brake release delay" (refer to Fig. 3-68).
Fig. 3-68 Motor holding brake after ON / OFF1
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 197
The motor holding brake is either closed using OFF1 / OFF3 or OFF2. For OFF1 / OFF3, when the minimum frequency P1080 is reached, the motor is operated at this frequency until the brake has been applied (closing times of brakes lie between 15 ms and 300 ms). The actual time is specified using parameter P1217 "Holding time after ramp down" (refer to Fig. 3-68). If, on the other hand, an OFF2 command has been output, then independent of the drive state, the status signal r0052 bit 12 "Motor holding brake active" is reset. This means that the brake immediately closes after OFF2 (refer to Fig. 3-69).
0
fmin(p1080)
p1216
OFF1/OFF3
ON
ON / OFF2:
1r0052.C Bit 12
f p0346
Motor excitationfinished
r0056 Bit04
t
t
t
t
t
tOFF2
BrakeStatus
Brake Release Time Brake Closing Time
open
closed
Active
Inactive
Fig. 3-69 Motor holding brake after OFF2
The mechanical brake is controlled using the status signal r0052 bit 12 "Motor holding brake active" of the brake control. This signal can be output as follows:
Via digital outputs The status signal is output via the digital output. In this case, the internal MICROMASTER relay (if the specification is sufficient) or also an external contactor or relay can be used to control the brake.
Via status signal using the serial interface (USS or PROFIBUS) The master must process the status signal. The signal must be connected to the digital output of the master to which the contactor / relay for the motor holding brake is connected.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 198 6SE6400-5AW00-0BP0
NOTE Motors have optional holding brakes which are not designed to be used as
brakes for normal operation. The holding brakes are only designed for a limited number of emergency braking operations / motor revolutions with the brake closed (refer to the Catalog data).
When commissioning a drive with integrated holding brake it is therefore absolutely imperative that it is ensured that the holding brake functions perfectly. A "clicking noise" in the motor indicates that the brake has been correctly released.
Parameter settings: ♦ To open/close, the digital output controls the motor holding brake at point 1/2
(refer to Fig. 3-68). In this case the prerequisite is that the motor holding brake P1215 has been activated as well as the selection of the motor holding brake at the digital output.
♦ Brake opening time P1216 is greater than/equal to the time to open the holding brake.
♦ Brake delay time P1217 is greater than/equal to the time to close the holding brake.
♦ Select the min. frequency P1080 so that it acts just like a weight equalization function.
♦ A typical value for the min. frequency P1080 for the motor holding brake is the slip frequency of the motor r0330. The rated slip frequency can be calculated using the following formula:
nnsy
nnsySlip f
nn n P0310
100 r0330 [Hz]f ⋅−=⋅=
♦ The following control parameters should be noted in conjunction with the
motor holding brake: − for V/f control (open-loop) P1310, P1311, P1333, P1335 − for closed-loop vector control (SLVC) P1610, P1611, P1750, P1755
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 199
WARNING It is not sufficient to select the status signal r0052 bit 12 "Motor holding brake
active" in P0731 – P0733. In order to activate the motor holding brake, in addition, parameter P1215 must also be set to 1.
If the frequency inverter controls the motor holding brake, then a commissioning may not be carried-out for potentially hazardous loads (e.g. suspended loads for crane applications) unless the load has been secured. Potentially hazardous loads can be secured as follows before commissioning is started: ♦ Lower the load to the floor ♦ During the commissioning phase or after the frequency inverter has been
replaced, the frequency inverter must be inhibited from controlling the motor holding brake (it is not permissible that the frequency inverter controls the holding brake). Quick commissioning or a parameter download using STARTER etc. may only be carried-out after this has been absolutely ensured. The motor holding brake terminals can then be re-assigned (in this case, it is not permissible that digital output P0748 is inverted for the motor holding brake).
♦ In order to hold the motor against the mechanical brake at a specific frequency, it is important that the min. frequency P1080 approximately corresponds to the slip frequency. If the value is selected to be too high, then the current drawn can be too high so that the frequency inverter shuts-down (trips) due to an overcurrent. If the value selected is too low, then it is possible that not enough torque is produced to hold the load.
It is not permissible to use the motor holding brake as operating brake. The reason for this is that generally it is only dimensioned/designed for a limited number of emergency braking operations.
Motor with motor holding brake (example) A motor with motor holding brake for a hanging (suspended) axis is connected to the frequency inverter. This holding brake is to be controlled using the 1st digital output.
Which settings have to be made?
Select the "motor holding brake active" function (52.12) at digital output P0731. Activate the brake sequence control in the frequency inverter (P1215 = 1). Set parameter P1216 to open the holding brake after an ON command.
The brake opening time P1216 must be set so that it is equal to or longer than the time required to open the holding brake. The opening time of the brake (refer to the Motor Catalog, e.g. M11) plus the relay opening time can be used as nominal value for P1216.
Set parameter P1217 to close the holding brake after an OFF1/3 command. The brake delay time P1217 must be set so that it is equal to or longer than the time required to close the holding brake. The closing time of the brake (refer to Motor Catalog, e.g. M11) plus the relay closing time can be used as nominal value for P1217.
Set the load holding The opening / closing times of mechanical brakes are subject to certain fluctuations; this is the reason that a weight equalization function must be parameterized in the frequency inverter for the time P1216 and P1217. The following parameters must be defined so that the axis cannot sag (i.e. the axis cannot drop/fall).
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 200 6SE6400-5AW00-0BP0
♦ In order that the motor can immediately establish a torque after an ON command, the magnetizing time P0346, determined with the quick commissioning, may not be reset. This is the reason that parameter P0346 should be checked for the weight equalization. Typical magnetizing times for 4-pole 1LA7 motors are: 0.12 kW 50 ms 7.50 kW 300 ms 1.50 kW 100 ms 55.0 kW 700 ms 5.50 kW 250 ms
♦ The min. frequency P1080 should approximately correspond to the rated motor slip (P1080 ≈ r0330[Hz])
♦ In addition, the voltage boost should be adapted: − V/f mode (P1300 = 0 ... 3)
- constant voltage boost P1310 ≈ 90 % (empirical value) - voltage boost when accelerating
P1311 ≈ 50 % (empirical value) − SLVC mode (P1300 = 20)
- constant torque boost P1610 ≈ 90 % (empirical value) - torque boost when accelerating
P1611 ≈ 50 % (empirical value) Connecting-up the motor holding brake control
♦ Directly connected to the 1st relay output
Motor withmotorholding brake
COM
NC
NO
COM
NC
NO
COM
NO
20
18
19
25
23
24
22
21
CPU
MICROMASTER 440
M3~
=
Fig. 3-70 Direct motor holding brake connection
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 201
If the frequency inverter directly controls the motor holding brake using the relay integrated in the frequency inverter, then the max. load capability of this relay should be carefully taken into consideration in conjunction with the voltage/current data of the holding brake. The following applies for the relay integrated in the frequency inverter: − 30 V DC / 5 A − 250 V AC / 2 A
If this value is exceeded, an additional relay should, for example, be used. ♦ Indirectly connecting 1st relay output via an additional relay
Motor withmotorholding brake
COM
NC
NO
COM
NC
NO
COM
NO
20
18
19
25
23
24
22
21
9
28Output 0 V, max. 100 mA(isolated)
Output +24 V, max. 100 mA(isolated)
CPU
Surgeabsorberdiode
24 V
0 V
Relay
MICROMASTER 440
M3~
=
Caution The relay may not overload the internal 24 V power supply!
Fig. 3-71 Indirect motor holding brake connection
Hoisting gear applications For high loads and low mechanical friction, especially when lowering a load, energy is regenerated that can cause the DC link voltage to increase. This increase can be prevented using dynamic braking (refer to Section 3.15.3; P1237). In order that there is no negative effect when using dynamic braking, the following functions should be disabled for hoisting gear applications: ♦ Vdc_max controller P1240 ♦ Compound brake P1236
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 202 6SE6400-5AW00-0BP0
3.15 Electronic brakes MICROMASTER 440 has 3 electronic brakes: DC braking (refer to Section 3.15.1) Compound braking (refer to Section 3.15.2) Dynamic braking (refer to Section 3.15.3)
These brakes can actively brake the drive and avoid a possible DC link overvoltage condition. An inter-dependency as shown in Fig. 3-72 is present.
DC brakingP1233 > 0
?
yes
no
DC brakingenabled
Compoundbraking
P1236 > 0?
Compound brakingenabled
Dynamicbraking
P1237 > 0?
Dynamic brakingenabled disabled
no no
yes yes
Fig. 3-72 Inter-dependency of the electronic brakes
3.15.1 DC braking
Parameter range: P1230, P1233 P1232, P1234 r0053 Bit00 Warnings - Faults - Function chart number: -
The drive decelerates along a parameterized braking ramp if an OFF1 / OFF3 command is output. A "flat" ramp must be selected so that the drive inverter is not tripped (shutdown) due to the high regenerative energy which would cause a DC link overvoltage condition. The DC brake should be activated while the OFF1 / OFF3 command is present if the drive is to be braked faster. For DC braking, instead of continually reducing the output frequency / voltage during the OFF1 / OFF3 phase, from a selectable frequency, a DC voltage / current is input (refer to sequence a).
The drive can be brought to a standstill in the shortest time using DC current braking (DC brake). DC braking is selected as follows:
After OFF1 or OFF3 (the DC brake is released via P1233) Sequence ℵ Directly selected using BICO parameter P1230 Sequence ℑ
For DC braking, a DC current is impressed in the stator winding which results in a significant braking torque for an induction motor. The magnitude, duration and frequency at which braking starts can be set for the braking current and therefore braking torque by setting the appropriate parameters.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 203
The DC brake can therefore support a braking operation from approx. < 10 Hz or prevents / minimizes the increase in the DC link voltage for regenerative braking. This is realized because energy is directly absorbed in the motor. The essential advantage and the main application of the DC brake is the fact that a holding torque can be generated at standstill (0 Hz). For instance, this is important for applications where after positioning, any motion in the mechanical system / product itself can result in waste. DC braking is especially used for:
Centrifuges Saws Grinding machines Conveyor belts
Sequence ℵ 1. Enabled using P1233 2. DC braking is activated with the OFF1 or OFF3 command (refer to Fig. 3-73) 3. The drive inverter frequency is ramped-down along the parameterized OFF1 /
OFF3 ramp down to the frequency at which DC braking is to start - P1234. This means that the kinetic energy of the motor can be reduced without endangering the drive. However, if the ramp-down time is too short, there is a danger that a fault will be output as a result of an overvoltage condition in DC link - F0002.
4. The inverter pulses are inhibited for the duration of the de-magnetizing time P0347.
5. The required braking current P1233 is then impressed for the selected braking time P1232. The status is displayed using signal r0053 bit 00.
The inverter pulses are inhibited after the braking time has expired.
t
P1234
OFF1/OFF3
ON
t
t
?f?
P1233
1
tt
P0347
OFF2DC braking
OFF2
0
1
DC braking active
r0053Bit 00
Fig. 3-73 DC braking after OFF1 / OFF3
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 204 6SE6400-5AW00-0BP0
Sequence ℑ 1. Enabled and selected using BICO parameter P1230 (refer to Fig. 3-74) 2. The inverter pulses are inhibited for the duration of the de-magnetizing time
P0347. 3. The requested braking current P1232 is impressed for the time selected and the
motor is braked. This state is displayed using signal r0053 bit 00. 4. After DC braking has been cancelled, the drive accelerates back to the setpoint
frequency until the motor speed matches the drive inverter output frequency. If there is no match, then there is danger that a fault will be output as a result of overcurrent - F0001. This can be avoided by activating the flying restart function.
ON/OFF1
f
P0347
f*
i
t
t
t
t
1
0
f_act
DC braking
0
1
DC braking active
r0053Bit 00
t
f_set
(0:0)P1230.CBI: Enable DC brk.
Fig. 3-74 DC braking after external selection
NOTE 1. The "DC braking" function is only practical for induction motors ! 2. DC braking is not suitable to hold suspended loads ! 3. For DC current braking, the motor kinetic energy is converted into thermal
energy in the motor. If braking lasts too long, then the drive can overheat ! 4. While DC braking, there is no other way of influencing the drive speed using an
external control. When parameterizing and setting the drive system, then as far as possible, it should be tested using real loads !
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 205
3.15.2 Compound braking Parameter range: P1236 Warnings - Faults - Function chart number: -
For compound braking (this is enabled using P1236) DC braking is superimposed with regenerative braking (where the drive regenerates into the line supply as it brakes along a ramp). If the DC link voltage exceeds the compound switch-in threshold VDC-Comp (refer to Fig. 3-75), then a DC current is impressed as a function of P1236. In this case, braking is possible with a controlled (closed-loop) motor frequency and minimum regenerative feedback. Effective braking is obtained without having to use additional components by optimizing the ramp-down time (P1121 for OFF1 or when braking from f1 to f2, P1135 for OFF3) and using compound braking P1236.
Compound braking is suitable for:
Horizontal motion (e.g. traversing drives, conveyor belts) Vertical motion (e.g. hoisting gear)
f
it
t
f_act
f_set
P1236 = 0Without Compound braking
u
t
f
it
t
f_act
f_set
P1236 >0With Compound braking
t
DC-link
uDC-link
UDC-Comp
P0210213.1U : 0 = P1254 Comp-DC ⋅⋅=
1242r0.98 U : 0 P1254 Comp-DC ⋅=≠
Fig. 3-75 Compound braking
The compound braking switch-in threshold VDC-Comp is calculated as a function of parameter P1254 (Auto detect VDC switch-on levels) either directly using the line supply voltage P0210 or indirectly using the DC link voltage and r1242 (refer to the formula in Fig. 3-75).
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 206 6SE6400-5AW00-0BP0
WARNING For compound braking, regenerative braking is superimposed on the DC
braking (braking along a ramp). This means that components of the kinetic energy of the motor and driven load are converted into thermal energy in the motor. If this power loss is too high or if the braking operation takes too long, then this can cause the drive to overheat !
When using compound braking it must be expected that there is a higher level of noise above the compound braking switch-in threshold.
NOTE Only active in conjunction with V/f control. Compound braking is de-activated, if
- flying restart is active, - DC braking is active, and - Vector control (SLVC, VC) is selected.
The compound switch-in threshold VDC-Comp is dependent on P1254 VDC-Comp(P1254 = 0) ≠ VDC-Comp(P1254 ≠ 0) a) Auto-detect circuit enabled (P1254 = 1):
- VDC-Comp (P1254 = 1) is automatically calculated when the drive inverter runs-up - i.e. after the line supply voltage has been connected
- Using the auto-detect function, the VDC-Comp threshold automatically adapts itself to the line supply voltage at the particular installation location.
b) Auto-detect function disabled (P1254 = 0): - 0210P213.1U Comp,DC ⋅⋅= - The VDC-Comp threshold is immediately re-calculated after entering P0210 - P0210 must be adapted to the particular installation location
3.15.3 Dynamic braking
Parameter range: P1237 Warnings A0535 Faults F0022 Function chart number: -
For several drive applications, in certain operating states, the motor can regenerate. Examples of these applications include:
Cranes Traction drives Conveyor belts which transport loads downwards
When the motor is in the regenerative mode, the energy from the motor is fed back into the DC link of the drive converter via the inverter. This means that the DC link voltage increases and when the maximum threshold is reached, the drive inverter is shutdown (tripped) with fault F0002. This shutdown (trip) can be avoided by using dynamic braking. Contrary to DC and compound braking, this technique requires that an external braking resistor is installed.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 207
The advantages of dynamic resistor braking include: The regenerative energy is not converted into heat in the motor It is significantly more dynamic and can be used in all operating states (not only
when an OFF command is output)
Chopper resistor
Choppercontrol
B-
=~
~
B+
=
~
MM4
Fig. 3-76 Connecting the chopper (braking) resistor
The braking energy in the DC link is converted into heat when dynamic braking is activated (enabled using P1237). The energy is converted into heat using the voltage-controlled chopper resistor (ballast resistor). Chopper resistors are used if regenerative energy is dissipated in the DC link for a short time, e.g. when a drive brakes and the drive should be prevented from being shutdown (tripped) with fault message F0002 ("DC link overvoltage"). In this case, when the DC link threshold VDC chopper is exceeded, then the chopper resistor is switched-in using an electronic switch (semiconductor switch). Switch-in threshold of the chopper resistor:
If P1254 = 0 : 0210P213.1V213.1V plysuplineChopper,DC ⋅⋅=⋅⋅=
Otherwise : 1242r98.0V Chopper,DC ⋅=
The chopper switch-in threshold VDC chopper is calculated as a function of parameter P1254 (Auto detect VDC switch-on levels), either directly using the line supply voltage P0210 or indirectly using the DC link voltage and r1242.
tChopper, ON t 100
x ⋅= Chopper
VDC, act
–
VDC, Chopper
100 %
V∆V
0
1
1
0x
AlarmA0535
Duty cyclemonitoring
0
1
P1237
Mains200 - 240 V
9.8 V∆ V380 - 480 V
17.0 V500 - 600 V
21.3 V
Fig. 3-77 Mode of operation of the dynamic braking
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 208 6SE6400-5AW00-0BP0
The regenerative (braking) energy is converted into thermal energy using the chopper resistor. A braking module (chopper control) is integrated in the DC link for this purpose. The chopper of the braking module switches the resistor with a mark-space ratio corresponding to the regenerative power to be dissipated. The braking module is only active if, as a result of the regenerative operation, the DC link voltage lies above the chopper switch-in threshold VDC chopper. This means that the braking module is not active in normal operation when motoring. The chopper resistor is only designed for a specific power and a certain load duty cycle and can only absorb a limited amount of braking energy within a specific time period. The chopper resistors, specified in MICROMASTER Catalog DA51.2, have the following load duty cycle.
Power
0.05t [s]
12240
PDB
1P100
PDB
P100
= continuous power= permissable power for 12 s every 240 sDBP 20 = ⋅
Fig. 3-78 Load duty cycle – chopper resistors (MICROMASTER Catalog DA51.2)
This load duty cycle (P1237 = 1 → 5 %) is saved in MICROMASTER. If the values are exceeded due to the load required, then when the maximum acceptable braking energy is reached, the load duty cycle monitoring controls the chopper so that the value is reduced to the value entered in parameter P1237. This means that the energy to be dissipated in the chopper resistor is reduced which means that the DC link voltage quickly increases due to the regenerative energy available and the drive inverter is shutdown (tripped) due to a DC link overvoltage condition. If the continuous power or the load duty cycle for a resistor is too high, then the continuous rating can be quadrupled using 4 resistors in a bridge circuit configuration. In this case, in addition, the load duty cycle must be increased using parameter P1237 from P1237 = 1 (→ 5 %) to P1237 = 3 (→ 20 %). When using the bridge circuit, the overtemperature switch of the resistors should be connected in series and incorporated in the fault circuit. This guarantees, that when a resistor overheats, the complete system / drive inverter is shut down.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 209
Choppercontrol
B-B+
R
P1237 = 1(5 %)
Choppercontrol
B-B+
R
P1237 = 3(20 %)
R
R R
Fig. 3-79 Increasing the level of braking energy which can be absorbed
The continuous power and the load duty cycle are modified using parameter P1237 (setting values, refer to Fig. 3-80a). If the load duty cycle monitoring switches from the peak power (100%) to the continuous power, then this is dissipated for an unlimited length of time in the braking resistor (refer to Fig. 3-80b). Contrary to the braking resistor, as listed in Catalog DA51.2, the chopper control can be permanently operated with 100% power.
t
tcycle
PDB
P100
tON tOFF
P1237 tON tOFF tcycle PDB
5 % 12.0 228.0 240.0 0.05
10 % 12.6 114.0 126.6 0.10
20 % 14.2 57.0 71.2 0.20
50 % 22.8 22.8 45.6 0.50
100 % Infinite 0 Infinite 1.00
t
tcycle
PDB
P100
t100
tP1237 tOFF
a
b
Fig. 3-80 Chopper load duty cycle
For MICROMASTER 440, up to and including Size FS F, the braking module is integrated in the drive inverter and the braking resistor can be connected via external terminals B+, B-.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 210 6SE6400-5AW00-0BP0
NOTE The switch-on threshold VDC chopper of the dynamic resistor braking is dependent
on P1254 VDC chopper(P1254 = 0) ≠ VDC chopper(P1254 ≠ 0).
a) Auto-detect circuit enabled (P1254 = 1): - UDC-Chopper (P1254 = 1) is automatically calculated when the drive
inverter runs-up - i.e. after the line supply voltage has been connected.
- Using the auto-detect function, the UDC-Chopper threshold automatically adapts itself to the line supply voltage at the particular installation location.
b) Auto-detect function disabled (P1254 = 0): - 0210P213.1U Chopper,DC ⋅⋅= - The UDC-Chopper threshold is immediately re-calculated after entering
P0210 - P0210 must be adapted to the particular installation location
External braking modules (chopper units) including braking resistor can be used with all of the sizes, FS FX and FS GX. When engineering the system, the particular braking module / resistor must be taken into consideration.
WARNING Braking resistors, which are to be mounted on MICROMASTER 440, must be
designed so that they can tolerate the power dissipated. If an unsuitable braking resistor is used there is a danger of fire and that the
associated drive inverter will be significantly damaged. The chopper control, integrated in the drive converter is designed for the
braking resistor value assigned in Catalog DA51.2, e.g.: MICROMASTER 440 6SE6440-2UD23-0BA1 brake resistor 6SE6400-4BD12-0BA0 brake resistor value 160 Ω
A brake resistor with a lower resistance value will destroy the drive converter. In this case, an external braking unit must be used.
When operational, the temperature of braking resistors increases – do not touch ! Ensure that there is sufficient clearance around the unit and there is adequate ventilation.
A temperature protection switch must be used to protect the units against overheating.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 211
3.16 Automatic restart Parameter range: P1210 P1211 Warnings A0571 Faults F0035 Function chart number: -
After a power failure (F0003 "Undervoltage"), the "Automatic restart" function (enabled using P1210) automatically powers-up the drive inverter again. Any faults are automatically acknowledged by the drive inverter. When it comes to power failures (line supply failure), then a differentiation is made between the following conditions:
Line undervoltage (brownout) "Line undervoltage" is a situation where the line supply is interrupted and returns before (if installed) the BOP display has gone dark (this is an extremely short line supply interruption where the DC link hasn't completely collapsed).
Line failure (blackout) "Line failure" is a situation where the display has gone dark (this represents a longer line supply interruption where the DC link has completely collapsed) before the line supply returns. The automatic restart function P1210 is shown in the following diagram (refer to Fig. 3-81) as a function of external states / events.
0 − − − − −
1 − −
2 + − − −
3 + + + +
4 + + − − −
5 + − + +
6 + + + + +
Fault acknowl.
Fault acknowl.
Fault acknowl.
Fault acknowl.
Fault acknowl.
Fault acknowl.
restart
restart
restart
restart
restart
Fault acknowl.
Fault acknowl.
Fault acknowl.
restart
restart
Fault acknowl.
Fault acknowl.
Fault acknowl.
restart
restart
restart
Fault acknowl.
Fault acknowl.
restart
restart
Fault acknowl.
Fault acknowl.
Fault acknowl.
restart
restart
restart
ON always active (permanent)P1210 ON in no-voltage condition
Fault F0003 on All other faults onBrownoutBlackout BrownoutBlackout
All faults on Blackout
−
−
−
Restart
No faults on Blackout
−
+Fault acknowl.
restart
−
−
Fault acknowl.
Restart
Restart
Fig. 3-81 Automatic restarts
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 212 6SE6400-5AW00-0BP0
The number of start attempts is specified using parameter P1211. The number is internally decremented after each unsuccessful attempt. After all attempts have been made (as specified in parameter P1211), automatic restart is cancelled with message F0035. After a successful start attempt, the counter is again reset to the initial value.
NOTE The "Flying restart" function (refer to Section 3.17) must be additionally
activated if, for an automatic restart, the drive inverter is to be connected to a motor which may already be spinning.
DANGER For longer line supply failures (blackouts)and when the automatic restart
function is activated, over a longer period of time it may be assumed that MICROMASTER is powered-down. However, when the line supply returns, motors can automatically start to run again without any operator intervention.
If the operating range of the motors is entered in this status, this can result in death, severe injury or material damage.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 213
3.17 Flying restart Parameter range: P1200 P1202, P1203 r1204, r1205 Warnings - Faults - Function chart number: -
The "Flying restart" function (this is enabled using P1200, refer to Table 3-33) allows the drive inverter to be switched to a motor which is still spinning. If the drive inverter was to be powered-up without using the flying restart function, there would be a high possibility that a fault with overcurrent F0001 would occur. The reason for this is that the flux must first be established in the motor and the V/f control or closed-loop Vector control must be set corresponding to the actual motor speed. The drive inverter frequency is synchronized with the motor frequency using the flying restart function. When the drive inverter is normally powered-up it is assumed that the motor is stationary and the drive inverter accelerates the motor from standstill and the speed is ramped-up to the setpoint which has been entered. However, in many cases this condition is not fulfilled. A fan drive is a typical example. When the drive inverter is powered-down the air flowing through the fan can cause it to rotate in any direction.
Parameter P1200 Flying restart active Search direction 0 Disabled -
1 Always Start in the direction of the setpoint
2 For line supply on and fault Start in the direction of the setpoint
3 For fault and OFF2 Start in the direction of the setpoint
4 Always Only in the direction of the setpoint
5 For line supply on, fault and OFF2 Only in the direction of the setpoint
6 For fault and OFF2 Only in the direction of the setpoint
Table 3-33 Settings for parameter P1200
Flying restart without speed encoder a) Depending on parameter P1200, after the de-magnetizing time has expired
P0347, flying restart is started with the maximum search frequency fsearch,max (refer to Fig. 3-82).
P0310 100r0330 2 P1802f2f f
standardslip,
maxmaxsearch,⋅⋅+=⋅= +
This is realized either after the line supply returns when the automatic restart function has been activated or after the last shutdown with the OFF2 command (pulse inhibit).
V/f characteristic (P1300 < 20): The search frequency is reduced, as a function of the DC link current with the search rate which is calculated from parameter P1203. In so doing, the parameterizable search current P1202 is impressed. If the search frequency is close to the rotor frequency, the DC link current suddenly changes because the flux in the motor establishes itself. Once this state has been reached, the search frequency is kept constant and the output voltage is changed to the voltage value of the V/f characteristic with the magnetizing time P0346 (refer to Fig. 3-82).
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 214 6SE6400-5AW00-0BP0
Closed-loop Vector control without encoder (SLVC): Starting from the initial value, the search frequency approaches the motor frequency with the impressed current P1202. The motor frequency has been found if both frequencies coincide. The search frequency is then kept constant and the flux setpoint is changed to the rated flux with the magnetizing time constant (dependent on P0346).
After the magnetizing time P0346 has expired, the ramp-function generator is set to the speed actual value and the motor is operated with the actual reference frequency.
Setpoint frequency
t
ff
Ramp upMagnetizingtime
P0346
Demagnetizingtime
P0347
Flying restartP1202P1203
search,max
Fig. 3-82 Flying restart
Flying restart with speed encoder Depending on parameter P1200, after the de-magnetizing time P0347 expires a) After the line supply returns with the automatic restart active, or b) After the last shutdown using the OFF2 command (pulse inhibit) flying restart is started with the maximum search frequency fsearch,max.
V/f characteristic (P1300 < 20): For V/f control, the output voltage of the drive inverter is linearly increased from 0 to the V/f characteristic value within the magnetizing time P0347.
Closed-loop Vector control with speed encoder (VC): For the closed-loop Vector control, the necessary magnetizing current is established within the magnetizing time P0347.
After the magnetizing time P0346 has expired, the ramp-function generator is set to the speed actual value and the motor is operated at the actual setpoint frequency.
NOTE If a higher value is entered for the search velocity P1203 this results in a flatter
search curve and therefore to an extended search time. A lower value has the opposite effect.
For "Flying restart", a braking torque is generated which can cause drives, with low moments of inertia, to brake.
For group drives, "Flying restart" should not be activated due to the different characteristics of the individual motors when coasting down.
WARNING When "Flying restart" is activated (P1200 > 0), although the drive is at a stand-
still and the setpoint is 0, it is possible that the drive is accelerated as a result of the search current !
If the operating range of the motors is entered when the drive is in this state, this can result in death, severe injury or material damage.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 215
3.18 Closed-loop Vdc control In addition to DC, compound and dynamic braking, for MICROMASTER it is possible to prevent a DC link overvoltage condition using the closed-loop Vdc controller. With this technique, the output frequency is automatically modified during operation using the closed-loop Vdc controller so that the motor doesn't go too far into the regenerative mode.
DC link overvoltage Cause:
The drive regenerates and feeds too much energy back into the DC link. Remedy:
The DC link voltage is further reduced using the Vdc_max controller (refer to Section 3.18.1) by reducing the regenerative torque down to zero.
Using the Vdc controller, it is also possible to prevent the drive converter being shut down (tripped) during brief line supply dips – which cause a DC link undervoltage condition. Also in this case, the output frequency is automatically modified by the Vdc controller during operation. Contrary to an overvoltage condition, in this case the motor is operated with increased regenerative operation in order to support and buffer the DC link voltage.
DC link undervoltage Cause:
Line supply voltage failure or dip (blackout or brownout) Remedy:
A regenerative torque is entered for the operational drive which compensates the existing losses and therefore stabilizes the voltage in the DC link. This technique is carried-out using the Vdc_min controller (refer to Section ) and is known as kinetic buffering.
3.18.1 Vdc_max controller
Parameter range: P1240, r0056 bit 14 r1242, P1243 P1250 – P1254 Warnings A0502, A0910 Faults F0002 Function chart number: FP4600
A brief regenerative load can be handled using this function (enabled using P1240) without the drive inverter being shut down (tripped) with fault message F0002 ("DC link overvoltage"). In this case, the frequency is controlled (closed-loop) so that the motor doesn't go too far into regenerative operation. If the drive inverter regenerates too much when braking the machine due to a fast ramp-down time P1121, then the braking ramp / ramp time are automatically extended and the drive inverter is operated at the DC link voltage limit r1242 (refer to Fig. 3-83). If the DC link threshold r1242 is again fallen below, then the Vdc_max controller withdraws the extension of the braking ramp.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 216 6SE6400-5AW00-0BP0
t
t
f
1
-controller activeVDC_max
t
VDC
r1242
0r0056 Bit 14
f
fact
set
A0911
Fig. 3-83 Vdc_max controller
On the other hand, if the Vdc_max controller increases the output frequency (e.g. for a steady-state regenerative load), then the Vdc_max controller is disabled by an internal drive inverter monitoring function and warning A0910 is output. If the regenerative load continues, the drive inverter is protected using fault F0002.
In addition to controlling the DC link (closed-loop), the Vdc_max controller supports the stabilizing processes of the speed at the end of an acceleration phase. This is especially the case if there is an overshoot and the motor therefore briefly goes into regenerative operation (damping effect).
The automatic increase of the braking ramp (refer to Fig. 3-83) can be contradictory to the objective of the application. This behavior is not required, especially for positioning drives and hoisting gear (e.g. cranes). A DC link overvoltage condition can still be avoided by disabling the Vdc-max controller (P1240 = 0) and by activating the following functions:
Extending the braking ramp (P1121) Activating the compound brake (P1236) or dynamic brake (P1230)
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 217
NOTE If the DC link voltage exceeds the power-on threshold r1242 (switch-on level of
Vdc_max.) of the Vdc_max controller in the "Ready" state, then the Vdc_max controller is de-activated and warning A0910 is output. Cause: The line supply voltage does not match the application situation. Remedy: Refer to parameters P1254 and P0210.
If, in the "Run" state, the DC link voltage exceeds the power-on threshold r1242 and if the Vdc_max controller output is limited by parameter P1253 for approx. 200 ms, then the Vdc_max controller is de-activated and warning A0910 and, where relevant, fault F0002 are output. Cause: Line supply voltage P0210 or ramp-down time P1121 too low The moment of inertia of the driven load is too high Remedy: Refer to parameters P1254, P0210, P1121 Use a braking resistor
The Vdc_max switch-in threshold VDC_max depends on P1254 VDC_max(P1254 = 0) ≠ VDC_max(P1254 ≠ 0)
a) Auto-detect function enabled (P1254 = 1): - VDC_max (P1254 = 1) is automatically calculated when the drive inverter
runs-up, i.e. after the line supply voltage has been connected - Using the auto-detect function, the VDC-Comp threshold automatically
adapts itself to the line supply voltage at the particular installation location.
b) Auto-detect function disabled (P1254 = 0): - 0210P215.1U max_DC ⋅⋅= - The VDC-Comp threshold is immediately re-calculated after entering P0210 - P0210 must be adapted to the particular installation location.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 218 6SE6400-5AW00-0BP0
3.18.2 Kinetic buffering (Vdc_min controller) Parameter range: P1240 r0056 bit 15 P1245, r1246, P1247 P1250 – P1253 P1256, P1257 Warnings A0503 Faults F0003 Function chart number: FP4600
Brief line supply failures can be buffered using the kinetic buffering function (enabled using P1240). Line supply failures are buffered using the kinetic energy (i.e. moments of inertia) of the driven load. In this case the prerequisite is that the driven load has a sufficiently high flywheel mass or is rotating at an appropriately high speed – i.e. has adequate kinetic or rotating energy.
2kin mv
21 W:Energie Kinetische = 2
rot J21 W:nergieRotationse ω=
Using this technique, the frequency is controlled (closed-loop), so that energy is fed to the drive inverter from the regenerating motor thus covering the system losses. The losses during the line supply failure still remain which means that the motor speed decreases. When using kinetic buffering it has to be taken into consideration that the motor speed reduces.
t
1
KIB activet
VDC
100 %
0r0056Bit 15
P1245 5 %
Power restoration
Power failure
Vdc_min
0210P2100
P1245 ⋅⋅
0210P2 ⋅
IfI
f1
f2
P1120 P1082
f - f t 21b ⋅=
ttb
Fig. 3-84 Kinetic buffering (Vdc_min controller)
When the line supply returns, the energy feed is again from the line side and the output frequency of the drive inverter returns to the selected setpoint along the ramp defined by the ramp-function generator.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 219
NOTE When the minimum DC link voltage VDC_min is fallen below, fault F0003
"Undervoltage" is output and the drive inverter is shut down. The shutdown threshold VDC_min depends on the drive inverter type / line supply voltage.
Table 3-34 DC link undervoltage – shutdown threshold
Drive inverter type / line supply voltage Shutdown threshold VDC_min
1-ph. 200 V – 240 V AC ± 10 % 215 V
3-ph. 200 V – 240 V AC± 10 % 215 V
3-ph. 380 V – 480 V AC ± 10 % 430 V
3-ph. 500 V – 600 V AC ± 10 % 530 V
3.19 Positioning down ramp Parameter range: P0500 P2480 – r2489 Warnings - Faults - Function chart number: -
The positioning down ramp (enabled using P0500) can be used for applications where it is necessary that a residual distance is moved-through up to the stop dependent on an external event (e.g. BERO switch). In this case, MICROMASTER 440 generates a continuous braking ramp by selecting OFF1 depending on the actual load speed / velocity. The drive is then stopped/positioned along this braking ramp (refer to Fig. 3-85).
Motor Gear
f ⋅==21 P2488 s
t
OFF1f OFF1 . t P2488
.
tP2488
fOFF1
Fig. 3-85 Positioning down ramp
In this case, the remaining distance P2488 moved through must be entered, referred to the load. In order to carry-out the residual distance calculation on the load side, the mechanical arrangement of the axis (gearbox ratio, linear or rotary axis) must be appropriately parameterized (refer to Fig. 3-86).
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 220 6SE6400-5AW00-0BP0
n nMotor Load
Ü
Ü =P2482P2481 =Motor revolutions
Load revolutionsMotor
lin
rot Gear
ParameterDisposition
Load s rot
No. of revolutions1 [unit]
Ü =P2482P2481 =
Motor revolutionsLoad revolutions
n nMotor Load
Ü
Motor Gear
slin
Load
zz = screw spindle = = P2484
Fig. 3-86 Rotary or linear axis
Using this data, MICROMASTER 440 calculates the ratio between the distance and the motor revolutions and can therefore consider the movement on the load side.
NOTE When the positioning down ramp is enabled using parameter P0500 = 3, then
implicitly the control mode P1300 is reset as follows as a function of parameter P0205: a) P0205 = 0 → P1300 = 0 b) P0205 = 1 → P1300 = 2 This change can be undone again after the positioning down ramp has been enabled by modifying parameter P1300.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 221
3.20 Monitoring functions / messages
3.20.1 General monitoring functions / messages
Parameter range: P2150 – P2180 r0052, r0053, r2197, r2198 Warnings - Faults - Function chart number: FP4100, FP4110
MICROMASTER has an extensive range of monitoring functions / messages which can be used for open-loop process control. The control can either be implemented in the drive inverter or also using an external control (e.g. PLC). The interlocking functions in the drive inverter (refer to Section 3.1.2.3) as well as the output of signals (refer to Section 3.6.2 or 3.7) for external control are implemented using BICO technology.
The status of the individual monitoring functions / messages are emulated in the following CO/BO parameters:
r0019 CO/BO: BOP control word r0050 CO/BO: Active command data set r0052 CO/BO: Status word 1 r0053 CO/BO: Status word 2 r0054 CO/BO: Control word 1 r0055 CO/BO: Supplementary (additional) control word r0056 CO/BO: Status word – closed-loop motor control r0403 CO/BO: Encoder status word r0722 CO/BO: Status, digital inputs r0747 CO/BO: Status, digital outputs r1407 CO/BO: Status 2 – closed-loop motor control r2197 CO/BO: Messages 1 r2198 CO/BO: Messages 2
Frequently used monitoring functions / messages including parameter number and bit are shown in the following Table.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 222 6SE6400-5AW00-0BP0
Table 3-35 Partial excerpt of monitoring functions / messages
Functions / states Parameter / bit number Function chart Drive ready 52.0 - Drive ready to run 52.1 - Drive running 52.2 - Drive fault active 52.3 - OFF2 active 52.4 - OFF3 active 52.5 - On inhibit active 52.6 - Drive warning active 52.7 - Deviation setpoint – actual value 52.8 - PZD control 52.9 - Maximum frequency reached 52.A - Warning: Motor current limit 52.B - Motor holding brake active 52.C - Motor overload 52.D - Motor runs right 52.E - Drive inverter overload 52.F - DC brake active 53.0 - Ramping finished 53.9 - PID output R2294 == P2292 (PID_min) 53.A FP5100 PID output R2294 == P2291 (PID_max) 53.B FP5100 Download data set 0 from AOP 53.E - Download data set 0 from AOP 53.F - |f_act| > P1080 (f_min) 53.2 2197.0 FP4100 |f_act| <= P2155 (f_1) 53.5 2197.1 FP4110 |f_act| > P2155 (f_1) 53.4 2197.2 FP4110 f_act > zero 2197.3 FP4110 f_act >= setpoint (f_set) 53.6 2197.4 - |f_act| >= P2167 (f_off) 53.1 2197.5 FP4100 |f_act| > P1082 (f_max) 2197.6 - f_act == setpoint (f_set) 2197.7 FP4110 i_act r0068 >= P2170 53.3 2197.8 FP4100 Approx. Vdc_act < P2172 53.7 2197.9 FP4110 Approx. Vdc_act > P2172 53.8 2197.A FP4110 No-load operation 2197.B - |f_act| <= P2157 (f_2) 2198.0 - |f_act| > P2157 (f_2) 2198.1 - |f_act| <= P2159 (f_3) 2198.2 - |f_act| > P2159 (f_3) 2198.3 - |f_set| < P2161 (f_min_set) 2198.4 - f_set > 0 2198.5 - Motor blocked 2198.6 - Motor stalled 2198.7 - |i_act r0068| < P2170 2198.8 FP4100 |m_act| > P2174 & setpoint reached 2198.9 - |m_act| > P2174 2198.A - Load torque monitoring: Warning 2198.B - Load torque monitoring: Fault 2198.C -
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 223
3.20.2 Load torque monitoring Parameter range: P2181 P2182 – P2192 r2198 Warnings A0952 Faults F0452 Function chart number: -
This function allows the mechanical force transmission between the motor and driven load to be monitored. Typical applications include, for example, pulley belts, flat belts or chains, or pulleys for toothed wheels of drive-in and drive-out shafts which then transmit circumferential velocities and circumferential forces (refer to Fig. 3-87). The load torque monitoring function can then detect whether the driven load is locked or the force transmission has been interrupted.
For the load torque monitoring function, the actual frequency/torque characteristic is compared with the programmed frequency/torque characteristic (refer to P2182 – P2190). If the actual value lies outside the programmed tolerance bandwidth, then, depending on parameter P2181, either warning A0952 or fault F0452 is generated. Parameter P2192 can be used to delay the output of the warning or fault message. This avoids erroneous alarms which could be caused by brief transient states (refer to Fig. 3-88).
P2186
P2185
P2188
P2187
P2190
P2189
P2183 P2184
Torque [Nm]
Frequency[Hz]
P1082
0
1r2198Bit 11 t
P2192 P2192
A0952
Actualtorque
P2182
Fig. 3-88 Load torque monitoring (P2181 = 1)
Driveshaft
Deflectionroll
Fig. 3-87 Shaft drive with flat belts
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 224 6SE6400-5AW00-0BP0
The frequency/torque tolerance bandwidth is defined by the gray shaded area in Fig. 3-89. The bandwidth is determined by the frequency values P2182 – P2184 and the torque limits P2186 – P2189. When defining the tolerance bandwidth it should be ensured that a specific tolerance is taken into account in which the torque values are allows to vary corresponding to the application.
P2189Upper torque threshold 3P2190Lower torque threshold 3
P2187Upper torque threshold 2P2188Lower torque threshold 2
P2185Upper torque threshold 1P2186Lower torque threshold 1
Boundary zonesDe-activated monitoring
Envelope curveActive monitoring
P2182Threshold frequency 1
P2183Threshold frequency 2 P2184
Threshold frequency 3
|Torque| [Nm]
|Frequency|[Hz]
P1082Max. frequency
P1080Min. frequency
Fig. 3-89 Frequency/torque tolerance bandwidth
Commissioning steps 1. In order to define the position of the tolerance bandwidth, different
characteristics must be determined as a function of the required load torque monitoring (P2181). A differentiation can be made between the following cases:
a) P181 = 1 / 4 Load torque monitoring to detect a broken belt, i.e. under fault conditions, the actual load torque is below the permissible tolerance bandwidth. In this case, the load torque characteristic with minimum permissible load should be determined.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 225
Permissible min.load characteristic
P2186
P2182
|Torque| [Nm]
|Frequency|[Hz]
P2188
P2183
P2190
P2184
P2185+P2187+P2189
Rated loadcharacteristic
Fig. 3-90 Load torque characteristic with minimum permissible load
b) P2181 = 2 / 5 Load torque monitoring as anti-stall protection. This means that when a fault occurs, the actual load torque is above the permissible tolerance bandwidth. In this case, the load torque characteristic with maximum permissible load should be determined.
Permissible max.load characteristic
P2189
P2182
|Torque| [Nm]
|Frequency|[Hz]
P2187
P2183
P2185
P2184
P2186+P2188+P2190
Rated loadcharacteristic
Fig. 3-91 Load torque characteristic with maximum permissible load
c) P2181 = 3 / 6 Load torque monitoring to detect whether the drive is blocked (stalled) or a transmission belt has broken. This means that when a fault occurs, the load torque is either above or below the permissible tolerance bandwidth. In this case, the load torque characteristic with the minimum and maximum permissible load should be determined.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 226 6SE6400-5AW00-0BP0
Permissible max.load characteristic
P2182
|Torque| [Nm]
|Frequency|[Hz]P2183
P2185+P2187+P2189
P2184
P2186+P2188+P2190Permissible min.load characteristic
Rated loadcharacteristic
Fig. 3-92 Load torque characteristic with minimum and maximum permissible load
2. The permissible load torque characteristic must be determined in the operating
range of the plant or system. This characteristic can be determined as follows:
a) Theoretical determination In this case, the prerequisite is that the load torque characteristic in the operating range must first be known. Frequently, this is not the case in practice. Especially changing mechanical effects involve investigations that require considerable time and costs if they are to be forecast in advance.
b) Practical determination The load torque characteristic is directly determined at the plant/system using a "teach-in technique". In this case, the operating range is passed-through step-by-step and the value pair comprising the actual output frequency r0021 and actual torque r0031 are read-out in the steady-state condition. If necessary, this should be carried-out for both directions of rotation.
3. The position of the tolerance bandwidth (P2182 - P2190) is determined by defining the 3 points along the characteristic.
4. In order to prevent the torque monitoring responding unnecessarily, dynamic states should be suppressed using delay time P2192. As a rule of thumb, P2192 should be > P1120.
Note The load torque monitoring is active in all 4 quadrants If it is not possible to determine the min. or max. load torque characteristic at
the drive in operation, then the load torque characteristic should be determined for operation at rated load. By taking into account the tolerances, the max. or min. permissible load characteristic can be calculated (e.g. the max. load characteristic is obtained from the 120% rated load characteristic).
If only a specific frequency range is to be monitored, then it is sufficient to plot the load characteristic between the frequency thresholds of the envelope curve (P2182, P2184).
If the drive is only permitted to have one direction of rotation, then the load characteristic should only be determined for the permissible direction of rotation.
The load characteristic and/or envelope curve determined should be represented in a frequency-torque diagram, e.g. using Microsoft Excel.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 227
3.21 Thermal motor protection and overload responses Parameter range: P0601 – P0640 P0344 P0350 – P0360 r0035 Warnings A0511 Faults F0011, F0015 Function chart number: -
MICROMASTER 440 has a completely new integrated concept for thermal motor protection. There are numerous possibilities of effectively protecting the motor but at the same time ensuring high motor utilization. The basic philosophy of this innovative concept is to detect critical thermal states, output warnings and initiate the appropriate responses. By responding to critical states it is possible to operate the drive at the thermal power limit and to avoid, under all circumstances, an immediate shutdown (where the drive inverter is tripped).
Features The protective concept (refer to Fig. 3-93) distinguishes itself as a result of the following individual features:
Protection is effective without using any temperature sensor (P0601 = 0). The temperatures of various locations in the motor are indirectly determined using a temperature model.
It is possible to evaluate temperature sensors. This has the advantage that after a line supply failure, precise initial temperatures are immediately available. Both PTC sensors (P0601 = 1) as well as KTY84 sensors (P0601 = 2) can be connected and evaluated (refer to Section 3.21.2).
When using a KTY84 sensor, the drive inverter can be parameterized so that a sensor wire breakage or short-circuit F0015 is detected and the system automatically changes-over to the temperature model. This means that the drive inverter is not shut down (tripped) and operation can continue.
Selectable temperature warning thresholds P0604 (default: 130 °C) for operation with the temperature model or KTY84 sensor. The drive inverter is shut down or the current reduced depending on P0610 for a value of P0604 +10%.
Selectable responses P0610 which are to be initiated when the warning threshold is exceeded in order to prevent an overload condition.
The motor protection has been designed to be completely independent of the drive inverter protection. Warning thresholds and responses for drive inverter protection must be separately parameterized.
Various data sets are taken into account in the model. The model is separately calculated for each data set so that when changing-over between various motors the cooling of the presently non-active (fed) motors are taken into account.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 228 6SE6400-5AW00-0BP0
r0631
ADC
5 V
Signalloss
detection
T1 = 4 s
2
1
No sensorPTCKTY
0
P0604
FaultF0015
&P0601 = 2
Thermalmotormodel
r0633
r0632
r0035
1≥Motor
i2ttemp.
reaction
P0610P0601
Equivalentcircuit data
PV,mot
Power dissipation
V
?
0
1
0
1
r0052Bit13
PTCKTY
Fig. 3-93 Thermal motor protection
Temperature rise classes In drive technology, temperature rise issues play a decisive role when dimensioning electrical machinery. Different temperature limits apply for the various materials used in electric motors. Depending on the insulating material being used, a differentiation is made according to thermal classes (refer to the motor rating plate) with defined limit temperatures. An excerpt from IEC85 is provided in Table 3-36.
Max.perm.temperatureThermal ClassYAEBF
90 °C105 °C120 °C130 °C155 °C
H 180 °C
Excerpt from IEC 85
Table 3-36 Thermal classes
For the temperature model or the KTY84 sensor, the appropriate value ϑwarn must be calculated and entered into parameter P0604 (temperature warning threshold, default: 130°C). The following applies:
1.1
trip warn P0604ϑ
=ϑ=
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 229
3.21.1 Thermal motor model The data, required for the thermal motor model, is estimated from the rating plate data entered during the quick commissioning (refer to Section 3.5.3). This data permits reliable, stable operation for standard Siemens motors. If required, parameter changes must be made for motors from third-party manufacturers. We always recommend that an automatic motor data identification run is made after quick commissioning so that the electrical equivalent circuit diagram data can be determined. This allows a more precise calculation of the losses which occur in the motor which has a positive impact on the accuracy of the thermal motor model.
Example: A stator resistance, which is parameterized to be too high, would result, in the model, to higher losses than in a real motor and an excessively high calculated motor temperature would be displayed. If changes are required in order to optimize the thermal model, then as a first step, the motor weight (P0344) should be checked for plausibility. Generally, the motor weight is taken from the Catalog data of the motor manufacturer. The thermal model can be further optimized by adapting the standard overtemperatures for the stator iron P0626, the stator winding P0627 and the rotor P0628. The standard overtemperatures represent the steady-state temperatures to be expected in rated operation with respect to the environment and are used to estimate the thermal resistances. Generally, these overtemperatures are not listed in the Catalog. The ambient temperature P0625 is another important parameter which influences the precision of the thermal model.
NOTE In addition to the thermal motor protection, the motor temperature is also
included in the adaptation of the motor equivalent circuit diagram data. This adaptation has a significant influence on the degree of stability of the closed-loop vector control – especially for a high thermal motor load.
When switching-in the line supply voltage (i.e. powering-up), depending on whether a KTY sensor is being used or not, the motor temperature model is either initialized with the ambient temperature P0625 – saved in the frequency inverter – or with the actual motor temperature.
If the frequency inverter is continually supplied with an external 24 V voltage, then the motor temperature is tracked/corrected using the motor temperature time constant – even when the line supply voltage is shutdown (powered-down).
For closed-loop vector control, a high thermal motor load and if the line supply voltage is frequently switched-out/switched-in, then the following is required ♦ a KTY84 sensor should be used, or ♦ an external 24 V power supply should be connected
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 230 6SE6400-5AW00-0BP0
3.21.2 Temperature sensor When the motor is operated below the rated speed the cooling effect of the shaft-mounted fan is reduced. As a result, for most motors when continually operated at lower frequencies, the power has to be reduced. Under these conditions, motor protection against overheating can only be guaranteed if either a temperature sensor (PTC or KTY84 sensor) is integrated in the motor and is connected to the control terminals 14 and 15 of the MICROMASTER 440 (refer to Fig. 3-94) or the motor temperature model was determined (refer to Section 3.21.1).
NOTE In order to avoid EMC noise from being coupled-in to the drive converter electronics – and the associated disturbances – it is not permissible to use free conductors in the motor cable to connect the temperature sensor to the drive converter. The temperature sensor must be connected to the drive converter using a separate cable (if at all possible, this cable should be shielded).
PTC/KTY
5 V
Kl. 14
Kl. 15
A
D
574 Ω
Fig. 3-94 Connecting a temperature sensor to MICROMASTER
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 231
With PTC temperature sensor (P0601 = 1) The PTC is connected to the control terminals 14 and 15 of the MICROMASTER 440. PTC monitoring is activated with the parameter setting P0601 = 1. If the resistance value, connected at the terminals, is less than 1500 Ω, then neither alarm nor fault is generated. If this value is exceeded, the drive inverter outputs alarm A0511 and fault F0011. The resistance value where the alarm and fault are output does not lie below 1000 Ω and not above 2000 Ω. Response thresholds: 4.0 V 0 → 1 3.8 V 1 → 0
With KTY84 temperature sensor (P0601 = 2) The KTY84 must be connected so that the diode is in the conductive direction. This means that the anode is connected to terminal 14 and the cathode to terminal 15. If the temperature monitoring function is activated with the setting P0601 = 2, the temperature of the sensor (i.e. of the motor windings) is written into parameter r0035 (refer toFig. 3-93). The threshold temperature ϑtrip (refer to Table 3-36) of the motor can now be set using the warning threshold, motor overtemperature ϑwarn (parameter P0604) (the factory setting is 130 °C). The following applies:
1.1 P0604 trip warn
ϑ=ϑ=
Wire breakage or short-circuit If the circuit between the drive inverter and PTC or KTY84 sensor is interrupted or there is a short-circuit, the drive inverter is shut down (tripped) and fault F0015 is displayed.
Fig. 3-95 PTC characteristic for 1LG / 1LA motors
Fig. 3-96 KTY84 characteristic for
1LG / 1LA motors
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 232 6SE6400-5AW00-0BP0
3.22 Power module protection
3.22.1 General overload monitoring
Parameter range: P0640, r0067, r1242, P0210 Warnings A0501, A0502, A0503 Faults F0001, F0002, F0003, F0020 Function chart number: -
Just the same as for motor protection, MICROMASTER provides extensive protection for the power components. This protection concept is also sub-divided into 2 levels:
Warning and response Fault and shutdown
Using this concept, a high utilization of the power module components can be achieved without the drive inverter being immediately shut down. The power module components are monitored as follows:
Table 3-37 General protection of the power components
Warning and response Fault and shutdown Overcurrent / short circuit Imax controller for V/f
A0501 r0056 bit 09 r0056 bit 13
(refer to Section 3.23.1.2) Current controller for SLVC /
VC ---
r0056 bit 09 r1407 bit 08 r1407 bit 09
F0001
DC link overvoltage Vdc_max controller A0502
(refer to Section 3.18.1)
F0002
DC link undervoltage Vdc_min controller A0503
(refer to Section )
F0003
Line phase failure detection (refer to P0291)
--- F0020
The monitoring thresholds for the righthand column in the table above are permanently saved in the drive inverter and cannot be changed by the user. On the other hand, the threshold levels for the "Warning and response" column can be modified by the user to optimize the system. These values have default settings so that the "Fault and shutdown" thresholds do not respond.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 233
3.22.2 Thermal monitoring functions and overload responses Parameter range: P0290 – P0294 r0036 – r0037 Warnings A0504, A0505 Faults F0004, F0005, F0012, F0020, F0022 Function chart number: -
Similar to motor protection, the main function of the thermal power module monitoring is to detect critical states. Parameterizable responses are provided to the user which allows the drive system to be still operated at the power limit thus avoiding immediate shutdown. However, the possibilities of assigning parameters only involves interventions below the shutdown threshold which cannot be changed by users. MICROMASTER 440 has the following thermal monitoring functions:
i2t monitoring The i2t monitoring is used to protect components which have a long thermal time constant in comparison to the semiconductors. An overload with reference to i2t is present if the drive inverter utilization r0036 indicates a value greater than 100 % (utilization as a % referred to rated operation).
Heatsink temperature The monitoring of the heatsink temperature r0037[0] of the power semiconductor (IGBT).
Chip temperature Significant temperature differences can occur between the barrier junction of the IGBT and the heatsink. These differences are taken into account by the chip temperature r0037[1] and monitored.
When an overload occurs regarding one of these three monitoring functions, initially, a warning is output. The warning threshold P0294 (i2t monitoring) and P0292 (heatsink temperature and chip temperature monitoring) can be parameterized relative to the shutdown values.
Example The warning threshold P0292 for the temperature monitoring (chip / heatsink temperature) is set to 15 °C in the factory. This means that warning A0504 is output 15 °C below the shutdown threshold.
At the same time that the warning is output, the parameterized responses are initiated via P0290. Possible responses include:
Reducing the pulse frequency (P0290 = 2, 3) This is an extremely effective method to reduce losses in the power module, as the switching losses represent a very high proportion of the overall losses. In many applications, a temporary reduction of the pulse frequency can be tolerated in favor of maintaining the process.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 234 6SE6400-5AW00-0BP0
Disadvantage The current ripple is increased when the pulse frequency is reduced. This can result in an increase of the torque ripple at the motor shaft (for low moments of inertia) and an increase in the noise level. When the pulse frequency is reduced this has no influence on the dynamic response of the current control loop as the current control sampling time remains constant !
Reducing the output frequency (P0290 = 0,2) This is advantageous if it is not desirable to reduce the pulse frequency or if the pulse frequency is already set to the lowest level. Further, the load should have a characteristic similar to that of a fan, i.e. a square-law torque characteristic for decreasing speed. When the output frequency is reduced, this significantly reduces the drive inverter output current and in turn reduces the losses in the power module.
No reduction (P0290 = 1) This option should be selected if neither a reduction in the pulse frequency nor a reduction in the output current is being considered. In this case, the drive inverter does not change its operating point after the warning threshold has been exceeded so that the drive can be further operated until the shutdown values are reached. After the shutdown threshold has been reached, the drive inverter shuts down (trips) with fault F0004. The time which expires up to shutdown is however not defined and depends on the magnitude of the overload. Only the warning threshold can be changed in order to obtain an earlier warning and, if required, externally intervene in the drive process (e.g. by reducing the load, lowering the ambient temperature).
NOTE If the drive inverter fan fails, this would be indirectly detected by the
measurement of the heatsink temperature. A wire breakage or short circuit of the temperature sensor(s) is also monitored.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 235
3.23 Open-loop/closed-loop control technique There are several open-loop/closed-loop techniques for closed-loop speed and torque control for drive inverters with induction and synchronous motors. These techniques can be roughly classified as follows:
V/f characteristic control (briefly: V/f control) Field-orientated closed-loop control technique (briefly: Vector control)
The field-orientated control technique – also known as Vector control – can be further sub-divided into two groups:
Vector control without speed feedback (sensorless Vector control (SLVC)) Vector control with speed feedback (Vector control (VC))
These techniques differ from one another both regarding the control quantity as also in the complexity of the technique, which in turn are obtained as a result of the requirements associated with the particular application. For basic applications (e.g. pumps and fans), to a large extent, V/f control is used. Vector control is mainly used for sophisticated applications (e.g. winders), where a good control and behavior in noisy conditions are required regarding the speed and torque. If these requirements are also present in the range from 0 to approx. 1 Hz, then the speed/torque accuracy without encoder is not sufficient. In this case, Vector control with speed feedback must be used.
3.23.1 V/f control
Parameter range: P1300 P1310 – P1350 Warnings - Faults - Function chart number: FP6100
The V/f characteristic represents the simplest control technique. In this case the stator voltage of the induction motor or synchronous motor is controlled proportionally to the stator frequency. This technique has proven itself for a wide range of "basic" applications, such as
Pumps, fans Belt drives
and similar processes. The goal of V/f control is to keep the flux Φ constant in the motor. In this case, this is proportional to the magnetizing current Iµ and the ratio between voltage V and frequency f.
Φ ~ Iµ ~ V/f The torque M, developed by induction motors, is proportional to the product (precisely the Vectorial product Φ x I) of flux and current.
M ~ Φ ∗ I In order to generate the highest possible torque from a given current, the motor must operate with a constant flux which is as high as possible. In order to keep the flux Φ constant, when frequency f changes, the voltage V must be changed in proportion so that a constant magnetizing current Iµ flows. The V/f characteristic control is derived from these basic principles.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 236 6SE6400-5AW00-0BP0
f
U, M, P, Φ
Voltage control range Field control range
Rated motoroperating pointMn, Φn
fn fmax
M, ΦU, P
U, P
Fig. 3-97 Operating ranges and characteristics of an induction motor when fed from a
drive inverter
There are several versions of the V/f characteristic as shown in Table 3-38.
Table 3-38 V/f characteristic (parameter P1300)
Parameter value Significance Use / property
0 Linear character-
istic
Standard case
Vn
0 fn
V
f
P1300 = 0
1 FCC Characteristic which compensates the voltage losses of the stator
resistance for static (steady-state) or dynamic loads (flux current control FCC). This is especially used for small motors which have a relatively high stator resistance.
2 Square-law character-
istic
This is a characteristic which takes into consideration the torque characteristic of the driven load (e.g. fan / pump) a) Square-law characteristic
(f 2 characteristic) b) Energy saving as the lower
voltage also results in lower currents and losses.
Vn
0 fn
V
f
P1300 = 2
3 Programm-
able character-
istic
Characteristic which takes into consideration the torque characteristic of the motor / driven load (e.g. synchronous motor).
V
P1325
f1P1320
fmaxP1082
Vmaxr0071
VnP0304
P1323
P1321
f00 Hz
f2P1322
f3P1324
fnP0310
f
P1300 = 3
P1310
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 237
5 Application adaptation
This is a characteristic which takes into consideration the special technological issues of an application (e.g. textile applications), a) Where the current limiting (Imax controller) only influences the output voltage and not the output frequency, and b) By inhibiting the slip compensation
6 Application adaptation
with FCC
This is a characteristic which takes into consideration the special technological issues of an application (e.g. textile applications), a) Where the current limiting (Imax controller) only influences the output voltage and not the output frequency, and b) By inhibiting the slip compensation
19 Independent voltage input
The user can enter the output voltage of the drive inverter, independently of the frequency, using a BICO parameter P1330 via the interfaces (e.g. analog input → P1330 = 755).
3.23.1.1 Voltage boost
Parameter range: P1310, P1311, P1312 r0056 bit 05 Warnings - Faults - Function chart number: FP6100
For low output frequencies, the V/f characteristics only output a low output voltage. Even at low frequencies, the ohmic resistances of the stator winding play a role, which are neglected when determining the motor flux in Section 3.23.1. This means that the output voltage can be too low in order to
implement the magnetization of an induction motor, to hold the load to compensate voltage drops (ohmic losses in the winding resistances) in the
system or to provide a breakaway / accelerating / braking torque.
The output voltage can be increased (boosted) in MICROMASTER using the following parameters (refer to Table 3-39):
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 238 6SE6400-5AW00-0BP0
Table 3-39 Voltage boost
Parameter Voltage boost Explanation P1310 Constant
voltage boost The voltage boost is effective over the complete frequency range whereby the value continually decreases at high frequencies.
Vmax
Vn(P0304)
VContBoost,100
0 fn(P0310)
f max(P1082)
f
V
fBoost,end(P1316)
Boost
Linear V/f
Output voltage
actual V
Normal
V/f
(P13
00 =
0)
VContBoost,50
P1311 Voltage boost when
accelerating- / braking The voltage boost is only effective when accelerating or braking.
Vmax
Vn(P0304)
VAccBoost,100
0 fn(P0310)
fmax(P1082)
f
V
fBoost,end(P1316)
VAccBoost,50
Boost
Linear V/f
Output voltage
Normal V
/f
(P1300 = 0)
actual V
P1312 Voltage boost when starting The voltage boost is only effective when accelerating
for the first time (standstill)
Vmax
Vn(P0304)
VStartBoost,10
0
0 fn(P0310)
fmax(P1082)
f
V
fBoost,end(P1316)
VStartBoost,50
Boost
Linear V/f
Output volta
ge
Normal V
/f
(P1300 = 0)
actual V
NOTE
Especially at low frequencies, the motor temperature is additionally increased as a result of the voltage boost (the motor overheats) !
The voltage value at 0 Hz is determined from the product of rated motor current P0305, stator resistance P0350 and the appropriate parameters P1310 – P 1312.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 239
3.23.1.2 Slip compensation Parameter range: P1335 Warnings - Faults - Function chart number: FP6100
In the V/f characteristic operating mode the motor frequency is always lower than the drive inverter output frequency by the slip frequency fs. If the load (the load is increased from M1 to M2) is increased with a constant output frequency, then the slip s when motoring increases and the motor frequency decreases (from f1 to f2). This behavior, typical for an induction motor, can be compensated using slip compensation P1335. This therefore eliminates the speed reduction, caused by the load, by boosting (increasing) the drive inverter output frequency (refer to Fig. 3-98).
Without Slip compensation
M
f∆ff2 f1
M2
M1
With Slip compensation
M
f∆ff2 f1
M2
M1
fout M1
fout M2
Fig. 3-98 Slip compensation
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 240 6SE6400-5AW00-0BP0
3.23.1.3 V/f resonance damping Parameter range: P1338 Warnings - Faults - Function chart number: -
For variable-speed drives, resonance effects can occur in the upper frequency range (> 20 Hz). These resonance effects result in an increased noise level and also can damage / destroy the mechanical system. These resonance effects can occur for:
Geared motors Reluctance motors Large motors
(low stator resistance → poor electrical damping) Contrary to the "skip frequency" function (refer to Section 3.12.1 and parameters P1091 to P1094), where the resonance frequency is passed through as quickly as possible, for the V/f resonance damping (parameter P1338), the resonance effects are dampened from a control-related perspective. The advantage of this function is that by using this active damping, operation is possible in the resonance range. The V/f resonance damping is activated and adjusted using parameter P1338. This parameter represents a gain factor that is a measure for the damping of the resonance frequency. The following oscillogram indicates the effect of the resonance damping function using as an example a reluctance motor with gearbox. The phase output currents are displayed for an output frequency of 45 Hz.
Without V/f resonance damping (P1338 = 0) V/f resonance damping active (P1338 = 1)
Fig. 3-99 Effect of V/f resonance damping
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 241
3.23.1.4 V/f open-loop control with flux current control (FCC) Parameter range: P1300, P1333 Warnings - Faults - Function chart number: -
An improved current measurement function has been developed for our MICROMASTER drive inverters. This permits the output current to be precisely determined referred to the motor voltage. This measurement guarantees that the output current is sub-divided into a load component and a flux component. Using this sub-division, the motor flux can be controlled and can be appropriately adapted and optimized in-line with the prevailing conditions. FCC operation is only activated after the FCC starting frequency P1333 has been exceeded. The FCC starting frequency P1333 is entered as a percentage to the rated motor frequency P0310. For a rated motor frequency of 50 Hz and a factory setting of P1333 = 10 %, this results in an FCC starting frequency of 5 Hz. The FCC starting frequency may not be selected too low as this has a negative impact on the control characteristics and can result in oscillation and system instability. The "V/f with FCC" control type (P1300 = 1) has proven itself in many applications. It has the following advantages with respect to the standard V/f control:
Higher motor efficiency Improved stabilizing characteristics
♦ → higher dynamic response ♦ → improved behavior to disturbances / control
NOTE Contrary to closed-loop vector control with / without speed encoder (VC / SLVC), for the V/f open-loop control mode with FCC, it is not possible to specifically influence the motor torque. This is the reason that it isn’t always possible to avoid the motor stalling – even when using "V/f with FCC". An improvement in the stabilizing behavior and in the motor efficiency can be expected when using the closed-loop vector control with / without speed encoder when compared to V/f control with FCC.
totali
fluxi
loadi
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 242 6SE6400-5AW00-0BP0
3.23.1.5 Current limiting (Imax controller) Parameter range: P1340 – P1346 r0056 bit 13 Warnings A0501 Faults F0001 Function chart number: FP6100
In the V/f characteristic mode, the drive inverter has a current limiting controller in order to avoid overload conditions (Imax controller, refer to Fig. 3-100). This controller protects the drive inverter and the motor against continuous overload by automatically reducing the drive inverter output frequency by fImax (r1343) or the drive converter output voltage by VImax (r1344). By either reducing the frequency or voltage, the stressing on the drive inverter is reduced and it is protected against continuous overload and damage.
Imax controller setpoint
+?
r1343CO:Imax ctrl Foutp
r1344CO:Imax ctrl Voutp
Current feedback
r0067CO: Outp cur limit [A]
r0068CO: Output current [A]
Motor ovl fact [%]10.0 ... 400.0 [%]P0640.D (150.0)
Motor temperaturInverter temperaturi2t inverter
Motor ovl fact [%]10.0 ... 400.0 [%]P0640.D (150.0)
Imax ctrl prp gain0.000 ... 5.499
P1345.D (0.250)
Kp Tn
Kp Tn
Imax ctrl int time0.000 ... 50.000 [s]
P1346.D (0.300)
Imax ctrl prp gain0.000 ... 0.499
P1340.D (0.000)
Imax ctrl int time0.000 ... 50.000 [s]
P1346.D (0.300)
UI_max
fI_max
Fig. 3-100 Imax controller
NOTE The drive inverter load is only reduced when the frequency is reduced if the load decreases at lower speeds (e.g. square-law torque – speed characteristic of the driven load).
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 243
3.23.2 Vector control Field-orientated Vector control (briefly: Vector control) significantly improves torque control when compared to V/f control. The Vector control principle is based on the fact that for a specific load situation or required torque, the required motor current is impressed with respect to the motor flux so that the appropriate torque is obtained. If the stator current is emulated in a circulating coordinate system, linked with the rotor flux Φ, then it can be broken-down into flux-generating current component id in-line with the rotor flux and in a torque-generating current component iq, vertical to the rotor flux. These components are corrected to track their setpoints in the current controller using their own dedicated PI controllers and are equal quantities in steady-state operation.
Stator axis
Flux axis
Rotor axis
ω
Measured steady state trajectories
ω1
ωmRimR
iS(t)
ib
ia
id
iq
Fig. 3-101 Current Vector diagram in a steady-state condition
In the steady-state condition, the field-generating current component id is proportional to the flux Φ and the torque is proportional to the product of id and iq.
M ~ Φ ∗ iq Φ ~ id,stat M ~ id ∗ iq
When compared to V/f control, Vector control has the following advantages: Stable during load and setpoint changes Short rise times for setpoint changes (→ better control performance) Short rise times for load changes (→ better noise/disturbance characteristics) Accelerating and braking are possible with a max. adjustable torque The motor and driven machine are protected using the adjustable torque limit,
both when motoring and regenerating (refer to Section 3.23.2.4) The drive and braking torque are controlled independently of the speed Full holding torque is possible at 0 speed
These advantages are, under certain circumstances, already achieved without using speed feedback.
The Vector control can be used both with and without speed encoder.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 244 6SE6400-5AW00-0BP0
The following criteria provide a basis as to when a speed actual value encoder is required:
High speed accuracy is required High requirements are placed on the dynamic response
♦ Improved control performance ♦ Improved immunity to disturbances
The torque is to be controlled over a control range greater than 1:10 A defined and/or a changing torque has to be maintained for speeds below
approx. 10 % of the rated motor frequency P0310
When it comes to entering a setpoint, the Vector control (refer to Table 3-40) is sub-divided into
Closed-loop speed control, and Closed-loop torque/current control (briefly: Closed-loop torque control).
Table 3-40 Vector control versions
Vector control (closed-loop) Without encoder With encoder Closed-loop speed control P1300 = 20, P1501 = 0 P1300 = 21, P1501 = 0
Closed-loop torque control P1300 = 20, P1501 = 1 P1300 = 22
P1300 = 21, P1501 = 1 P1300 = 23
When closed-loop speed control is used, the closed-loop torque control is secondary. This type of cascaded closed-loop control has proven itself in practice regarding commissioning and increased transparency.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 245
3.23.2.1 Vector control without speed encoder (SLVC) Parameter range: P1400 – P1780
P1610, P1611 P1755, P1756, P1758 P1750 Warnings - Faults - Function chart number: FP7000
When Vector control is used without speed encoder (refer to Table 3-40) then the position of the flux and the actual speed must be determined using the motor model. In this case, the model is supported by the accessible currents and voltages. At low frequencies (≈ 0 Hz), the model is not able to determine the speed. This is the reason and also due to uncertainty in the model parameters and measuring inaccuracy, that a changeover is made from closed-loop to open-loop controlled operation in this range.
The changeover between closed-loop controlled / open-loop controlled operation is controlled using the time and frequency conditions (P1755, P1756, P1758) (refer to Fig. 3-102). The system does not wait for the time condition if the setpoint frequency at the ramp-function generator input and the actual frequency simultaneously lie below P1756.
SLVC open loop
f_act
t
P1755P1756 [Hz]
SLVC closed loopP1758
t
[%] 100[%] P1756 [Hz] P1755 [Hz] P1756 ⋅=
Fig. 3-102 Changeover condition for SLVC
In the open-loop controlled mode, the speed actual value is the same as the setpoint. For suspended loads or when accelerating, parameter P1610 (constant torque boost) and P1611 (torque boost when accelerating) must be modified in order to allow the drive to provide the steady-state and/or dynamic load torque. If P1610 is set to 0 %, then only the magnetizing current r0331 is impressed for a value of 100 % of the rated motor current P0305. In order that the drive does not stall when accelerating, P1611 can be increased or the acceleration pre-control can be used for the speed controller (refer to Section 3.23.2.3). This is also practical in order that the motor is not thermally overloaded at low speeds. For Vector control without speed actual value encoder MICROMASTER 440 has, in the low frequency range, the following outstanding features with respect to other AC drive inverters:
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 246 6SE6400-5AW00-0BP0
Closed-loop controlled operation down to ≈ 1 Hz Can start in the closed-loop controlled mode (immediately after the drive has
been energized) The low frequency range (0 Hz) is passed-through in closed-loop controlled
operation
f
t
P1755
Closed loop
Open loop
Start f
t
Closed loop
Open loop
Zero crossing
P1755
P1755
Fig. 3-103 Starting and passing-through 0 Hz in closed-loop controlled operation
The following advantages are obtained as a result of closed-loop controlled operation down to approx. 1 Hz (this can be selected using parameter P1755) as well as also the possibility to immediately start closed-loop controlled at 0 Hz or to reverse closed-loop controlled (this can be set using parameter P1750):
No changeover operation is required within the closed-loop control (smooth behavior – no frequency dips)
Continuous closed-loop speed-torque control is possible down to approx. 1 Hz.
NOTE For closed-loop controlled reversing or closed-loop controlled starting from 0 Hz it must be taken into account that when staying too long (> 2 s or > P1758) in the range around 0 Hz, that the closed-loop control automatically changes-over from closed-loop into the open-loop controlled mode.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 247
3.23.2.2 Vector control with speed encoder (VC) Parameter range: P1400 – P1740 P0400 – P0494 Warnings - Faults - Function chart number: FP7000
For Vector control with speed encoder (refer to Table 3-40), a pulse encoder evaluation (option module) as well as a pulse encoder, e.g. encoder with 1024 pulses/revolution are required. In addition to the correct wiring, the pulse encoder module must be activated, corresponding to the encoder type, using the parameter range P0400 – P0494 or using the DIP switch on the module (refer to Fig. 3-104).
Parameter Terminal Track Encoder output
single endedP0400 = 1 A
differentialA
AN
A
B
A
AN
B
BN
differential
P0400 = 2 single ended
OutputTypedifferential
TTL(e.g. 1XP8001-2)
HTL
111111 010101
(e.g. 1XP8001-1) 101010 000000
single ended
Fig. 3-104 P0400 and DIP switch on the pulse encoder module
Advantages of Vector control with encoder:
The speed can be closed-loop controlled down to 0 Hz (i.e. at standstill) Stable control behavior over the complete speed range Constant torque in the rated speed range When compared to closed-loop speed control without encoder, the dynamic
response for drives with encoder is significantly higher as the speed is directly measured and is incorporated in generating the model of current components id, iq.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 248 6SE6400-5AW00-0BP0
3.23.2.3 Speed controller Parameter range: P1300, P1400 – P1780 SLVC: P1470, P1472, P1452 VC: P1460, P1462, P1442 Warnings - Faults - Function chart number: FP7500, FP7510
Both of the control techniques (SLVC, VC) have the same speed controller structure which includes the following components as kernel:
PI controller Speed controller pre-control Droop
The sum of the output quantities forms the speed setpoint, which is reduced to the permissible level using the torque setpoint limiting function (refer to Section 3.23.2.4).
Speed controller (SLVC: P1470, P1472, P1452 VC: P1460, P1462, P1442) The speed controller (refer to Fig. 3-105) receives its setpoint r0062 from the setpoint channel (refer to Section 3.12), the actual value r0063 either directly from the speed actual value encoder or, for VC, also directly through the motor model for SLVC. The system error is amplified by the PI controller and, together with the pre-control, forms the torque setpoint. For increasing load torques, when the droop function is active, the speed setpoint is proportionally reduced so that the load on an individual drive within a group (where two or several motors are mechanically coupled) is reduced when excessively high torques occur.
–Torquesetpoint
Droop
Act. frequency
– r1538 r1538
r1539 r1539
Pre-control
Freq. setpoint
PISpeed
controller
SLVC:VC:
P1452P1442
P1470P1460
P1472P1462
Ti
Kp Tn
Ti Kp Tn
r1084
r0063
r0062
Speed control
*)
*) only active if pre-control is activated (P1496 > 0)
Fig. 3-105 Speed controller
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 249
If the moment of inertia was entered, the speed controller (Kp,Tn) can be calculated using the automatic parameterization (P0340 = 4) (refer to Section 3.5.4). The controller parameters are defined according to the symmetrical optimum as follows:
Tn = 4 * Tσ
Kp = ½ * r0345 / Tσ = 2 * r0345 / Tn
Tσ = sum of the low delay times
If oscillations occur with these particular settings, then the speed controller gain Kp should be manually reduced. It is also possible to increase the speed actual value smoothing (this is the usual procedure for gearbox play or high-frequency torsional oscillations) and then re-call the controller calculation as the value is incorporated in the computation of Kp and Tn. The following interrelationships apply for the optimization routine:
If Kp is increased then the controller becomes faster and the overshoot is reduced. However, the signal ripple and oscillations in the speed controller loop are increased.
If Tn is reduced, then the controller also becomes faster. However, the overshoot increases.
When manually adjusting the speed control, the simplest procedure is to initially define the possible dynamic response using Kp (and the speed actual value smoothing) in order to then reduce the integral action time as far as possible. In this case it is important to ensure that the closed-loop control must also remain stable in the field-weakening range. When oscillations occur in the closed-loop speed control, it is generally sufficient to increase the smoothing time in P1452 for SLVC or P1442 for VC (or to reduce the controller gain) in order to dampen oscillations. The integral output of the speed controller can be monitored using r1482 and the unlimited controller output can be monitored using r1508 (torque setpoint).
NOTE When compared to closed-loop control with encoder (refer to Section 3.23.2.2), the dynamic response for sensorless drives is significantly reduced. This is because the speed can only be derived from the drive inverter output quantities for current and voltage which have the appropriate noise level.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 250 6SE6400-5AW00-0BP0
Speed controller pre-control (P1496, P0341, P0342) The control behavior of the speed control loop can be improved if the speed controller of the drive inverter also generates values for the current setpoints (corresponds to the torque setpoint) from the speed setpoint. This torque setpoint mv, which is calculated as follows
dtdn0342P0341P1496Pdt
dn1496Pmv ⋅⋅⋅=⋅Θ⋅=
is entered into the current controller through an adaptation element directly as additive control quantity (this is enabled using P1496).
The motor moment of inertia P0341 is directly calculated during the quick commissioning (refer to Section 3.5.8) or the complete parameterization (P0340 = 1, refer to Section 3.5.4). The factor P0342 between the total moment of inertia and motor moment of inertia must be manually determined.
–Torquesetpoint
Droop
–r1538 r1538
r1539 r1539
PISpeed
controller
r1518
=0
>0
P0341 P0342
P1496
Pre-control
SLVC:VC:
P1452P1442
P1470P1460
P1472P1462
Ti
Kp Tn
Ti Kp Tn
Freq. setpoint
Act. frequency
r1084
Fig. 3-106 Speed controller with pre-control
When correctly adapted, then the speed controller only has to correct noise quantities/disturbances in its control loop and this is achieved with a relatively low manipulated quantity change. On the other hand, speed setpoint changes bypass the speed controller and are therefore executed faster. The effect of the pre-control quantity can be adapted, depending on the particular application, using the pre-control factor P1496. Using P1496 = 100 %, the pre-control is calculated according to the motor and load moment of inertia (P0341, P0342). In order that the speed controller does not work against the torque setpoint which is entered, a balancing filter is automatically used. The time constant of the balancing filter corresponds to the equivalent delay time of the speed control loop. The speed controller pre-control is correctly set (P1496 = 100 %, calibration via P0342), if the I component of the speed controller (r1482) does not change during a ramp-up or ramp-down in the range n > 20% * P0310. This means, using the pre-control, it is possible to approach a new speed setpoint without overshoot (prerequisite: The torque limiting does not intervene and the moment of inertia remains constant).
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 251
If the speed controller is pre-controlled, then the speed setpoint (r0062) is delayed with the same smoothing (P1442 or P1452) as the actual value (r1445). This ensures that when accelerating, there is no setpoint – actual value difference (r0064) at the controller input which would have been exclusively caused by the signal propagation time. When the speed pre-control is activated, it must be ensured that the speed setpoint is continuously entered and without any significant noise level (avoid torque surges). An appropriate signal can be generated by smoothing the analog signal P0753 (refer to Section 3.6.3) or by activating the rounding-off function of the ramp-function generator P1130 – P1133 (refer to Section 3.12.2).
NOTE The ramp-up and ramp-down times (P1120; P1121) of the ramp-function
generator (refer to Section 3.12.2) in the setpoint channel should only be set so fast that when accelerating and braking, the motor speed can follow the setpoint. This then guarantees the optimum functioning of the speed controller pre-control.
The starting time r0345 is a measure for the overall moment of inertia of the machine and describes that time in which the unloaded drive can accelerate from standstill to the rated motor speed P0311 with the rated motor torque r0333.
0333r600311P20342P0341PM60
n2T r0345
rated,Mot
rated,Motstarting⋅⋅π⋅⋅⋅=⋅
⋅π⋅⋅Θ==
If these secondary conditions match the particular application, then the starting time can be used as the shortest value for the ramp-up and ramp-down times.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 252 6SE6400-5AW00-0BP0
Droop (P1488 – P1492) The droop (enabled using P1488) means that with increasing load torque, the speed setpoint is proportionally reduced.
–
–
Pre-control
PISpeed
controller
r1538
r1539
0
2
1
3
0
0 1
0
r1538
r1539r1538
r1539Torquesetpoint
P1492
P1489
P1488
r1482
r1490
Droop
150 ms
SLVC:VC:
P1452P1442
P1470P1460
P1472P1462
Ti
Kp Tn
Ti Kp TnAct. frequency
Freq. setpoint
*)
*) only active if the pre-control is activated (P1496 > 0)
Fig. 3-107 Speed controller with droop
Droop is the simplest method to implement load sharing control. However, this load sharing control can only be used if the drives only motor and are operated more or less under steady-state conditions (i.e. at constant speed). For drives, which are frequently accelerated and braked with high speed changes, this technique is only conditionally suitable. The most simple load sharing control is, e.g., used for applications where two or several motors are mechanically coupled or operate on a common shaft and which have to fulfill the requirements above. In this case, the droop controls torsional stressing associated with the mechanical coupling by changing the speeds of the individual motors (excessive torques are reduced for an individual drive).
Prerequisite All of the drives must be operated with closed-loop Vector speed control (with or
without speed actual value encoder) The ramp-up and ramp-down times of the ramp-function generator must be
identical for all of the drives.
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 253
3.23.2.4 Closed-loop torque control Parameter range: P1300, P1500 – P1511 P1400 – P1780 Warnings - Faults - Function chart number: FP7200, FP7210, FP7700, FP7710
For sensorless closed-loop speed control SLVC (P1300 = 20) or for closed-loop speed control with sensor VC (P1300 = 21), it is possible to changeover to closed-loop torque control (slave drive) using BICO parameter P1501. It is not possible to changeover between closed-loop speed and torque control if the closed-loop torque control is directly selected using P1300 = 22 or 23. The torque setpoint and supplementary torque setpoint can be selected using parameter P1500 and also using BICO parameter P1503 (CI: Torque setpoint) or P1511 (CI: Supplementary torque setpoint). The supplementary torque acts both for the closed-loop torque control as well as for the closed-loop speed control (refer to Fig. 3-108). As a result of this feature, a pre-control torque for the speed control can be implemented using the supplementary torque setpoint.
NOTE For safety reasons, it is presently not possible to assign fixed torque setpoints.
–
Torquesetpoint
Droop
Act. frequency
–r1538 r1538
r1539 r1539
0
CI: Torque setp.
(0:0)P1503.C
(0:0)
BI:-> torque ctrl.P1501.C
CI: Add. trq. setp
(0:0)P1511.C
Pre-control
Freq. setpoint
PISpeed
controller
SLVC:VC:
P1452P1442
P1470P1460
P1472P1462
Ti
Kp Tn
Ti Kp Tn
*)
*) only active if pre-control is activated (P1496 > 0)
Fig. 3-108 Closed-loop speed/torque control
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 254 6SE6400-5AW00-0BP0
The sum of both torque setpoints is limited in the same way as the torque setpoint of the speed control (refer to Section 3.23.2.5). Above the maximum speed (plus 3 %), a speed limiting controller reduces the torque limits in order to prevent the drive accelerating any further. A "real" closed-loop torque control (with automatically set speed) is only possible in the closed-loop controlled range but not in the open-loop controlled range. In the open-loop controlled range, the torque setpoint changes the setpoint speed through a ramp-up integrator (integration time ~ P1499 * P0341 * P0342). This is the reason that sensorless closed-loop torque control in the area around standstill (0 speed) is only suitable for applications which require an accelerating torque there and not a load torque (e.g. traversing drives). For closed-loop torque control with sensors, this restriction does not apply. If the closed-loop torque control is active, and a fast stop command (OFF3) is output, then the system automatically changes-over to closed-loop speed control and the drive is braked. If a normal stop command (OFF1) is output, there is no changeover. Instead, the system waits until a higher-level control has brought the drive to a standstill, in order to inhibit the pulses there. This is necessary in order to allow the master and slave drives to be shut down together. For P1300 = 22 or 23, for OFF1, the drive is directly powered-down (as for OFF2).
3.23.2.5 Limiting the torque setpoint
Parameter range: P1520 – P1531 P0640, r0067 r1407 bit 08, r1407 bit 09 Warnings - Faults - Function chart number: FP7700, FP7710
All of the following limits act on the torque setpoint which is either entered at the speed controller output for closed-loop speed control or as torque input for closed-loop torque control. The minimum is used from the various limits. This minimum is cyclically computed in the drive inverter and displayed in parameters r1538, r1539.
r1538 Upper torque limit r1539 Lower torque limit
This means that these cyclic values limit the torque setpoint at the speed controller output / torque input and indicate the instantaneously maximum possible torque. If the torque setpoint is limited in the drive inverter, then this is displayed using the following diagnostic parameters
r1407 bit 08 Upper torque limit active r1407 bit 09 Lower torque limit active
Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 255
Torque limiting The value specifies the maximum permissible torque whereby different limits are parameterizable for motoring and regenerative operation.
P1520 CO: Upper torque limit value P1521 CO: Lower torque limit value P1522 CI: Upper torque limit value P1523 CI: Lower torque limit value P1525 Scaling, lower torque limit value
The currently active torque limit values are displayed in the following parameters: r1526 CO: Upper torque limit value r1527 CO: Lower torque limit value
f 1 ~
Torque limitation
Resultanttorque limit
Powerlimitation
|fact
r1526r1527
Stalllimitation
P1530P1531
f 1 ~ 2
Constanttorque
fstallConstant
power
|
|M|
Stallpower
Fig. 3-109 Torque limits
Power limits This value specifies the maximum permissible power, whereby different limits can be parameterized for motoring and regenerative operation.
P1530 Motor power limit P1531 Regenerative power limit
Stall limiting (locked rotor limiting) The stall limiting is internally calculated in the drive from the motor data.
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions 256 6SE6400-5AW00-0BP0
Current limiting The current limiting additionally limits the maximum torque which the motor can provide. If the torque limit is increased, more torque is only available if a higher current can flow. It may be necessary to also adapt the current limit. The current limiting is influenced by:
P0640 motor overload factor Thermal motor protection (refer to Section 3.21) Thermal drive inverter protection (refer to Section 3.22)
After limiting, the instantaneous maximum possible drive inverter current is displayed in parameter r0067 (limited output current).
Issue 10/06 4 Troubleshooting
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 257
4 Troubleshooting
This Chapter contains: An overview of the operating statuses of the inverter with the SDP Notes on troubleshooting with the BOP Information and instructions on alarms and fault messages
4.1 Troubleshooting with the SDP .............................................................................. 258
4.2 Troubleshooting with the BOP.............................................................................. 259
4.3 Fault messages..................................................................................................... 260
4.4 Alarm messages ................................................................................................... 260
4 Troubleshooting Issue 10/06
MICROMASTER 440 Operating Instructions 258 6SE6400-5AW00-0BP0
WARNING Repairs on equipment may only be carried out by Siemens Service, by repair
centers authorized by Siemens or by qualified personnel who are thoroughly acquainted with all the warnings and operating procedures contained in this manual.
Any defective parts or components must be replaced using parts contained in the relevant spare parts list.
Disconnect the power supply before opening the equipment for access
4.1 Troubleshooting with the SDP Table 4-1 explains the meaning of the various states of the LEDs on the SDP.
Table 4-1 Inverter conditions indicated by the LEDs on the SDP
Mains not present
Fault inverter temperature
Ready to run Warning current limit - both
LEDs twinkling same time
Inverter fault - other than the ones listed below
Other warnings - both LEDs twinkling alternatively
Inverter running
Undervoltage trip / undervoltage warning
Fault overcurrent
Drive is not in ready state
Fault overvoltage
ROM failure - Both LEDs flashing same time
Fault motor overtemperature
RAM failure - Both LEDs flashing alternatively
LEDs for indicating the drive state
Off On approx. 0,3 s, flashing approx. 1 s, twinkling
Issue 10/06 4 Troubleshooting
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 259
4.2 Troubleshooting with the BOP Warnings and faults are displayed on the BOP with Axxx and Fxxx respectively. The individual messages are shown in the Parameter list.
If the motor fails to start when the ON command has been given:
Check that P0010 = 0. Check that a valid ON signal is present. Check that P0700 = 2 (for digital input control) or
P0700 = 1 (for BOP control). Check that the setpoint is present (0 to 10V on Terminal 3) or the setpoint has
been entered into the correct parameter, depending upon the setpoint source (P1000). See the Parameter List for further details.
If the motor fails to run after changing the parameters, set P0010 = 30 then P0970 = 1 and press P to reset the inverter to the factory default parameter values.
Now use a switch between terminals 5 and 9 (Figure 3-14). The drive should now run to the defined setpoint by analogue input.
NOTICE Motor data must relate to the inverter data power range and voltage.
4 Troubleshooting Issue 10/06
MICROMASTER 440 Operating Instructions 260 6SE6400-5AW00-0BP0
4.3 Fault messages In the event of a failure, the inverter switches off and a fault code appears on the display.
NOTE To reset the fault code, one of three methods listed below can be used: 1. Cycle the power to the drive. 2. Press the button on the BOP or AOP. 3. Via Digital Input 3 (default setting)
Fault messages are stored in parameter r0947 under their code number (e.g. F0003 = 3). The associated error value is found in parameter r0949. The value 0 is entered if a fault has no error value. It is furthermore possible to read out the point in time that a fault occurred (r0948) and the number of fault messages (P0952) stored in Parameter r0947. A detailed description of the fault messages is provided in the parameter list.
4.4 Alarm Messages Alarm messages are stored in parameter r2110 under their code number (e.g. A0503 = 503) and can be read out from there. A detailed description of the alarm messages is provided in the parameter list.
Issue 10/06 5 MICROMASTER 440 specifications
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 261
5 MICROMASTER 440 specifications
This Chapter contains: Table 5.1 contains the general technical specifications for the
MICROMASTER 440 inverter Table 5-2 contains dimensions, the required cooling air flow and tightening
torque for power connections Table 5-3 contains current values, depending on the pulse frequency Table 5-4 contains data for the braking resistors Table 5-5 includes various tables of specific technical data for individual
MICROMASTER 440 inverters
5 MICROMASTER 440 specifications Issue 10/06
MICROMASTER 440 Operating Instructions 262 6SE6400-5AW00-0BP0
Table 5-1 MICROMASTER 440 Performance Ratings
Feature Specification Mains Operating Voltage & Power Ranges
1 AC 200 to 240 V ± 10 % CT: 0,12 kW – 3,0 kW (0,16 hp – 4,0 hp) 3 AC 200 to 240 V ± 10 % CT: 0,12 kW – 45,0 kW (0,16 hp – 60,0 hp) VT: 5,50 kW – 45,0 kW (7,50 hp – 60,0 hp) 3 AC 380 to 480 V ± 10 % CT: 0,37 kW – 200 kW (0,50 hp – 268 hp) VT: 7,50 kW – 250 kW (10,0 hp – 335 hp) 3 AC 500 to 600 V ± 10 % CT: 0,75 kW – 75,0 kW (1,00 hp – 100 hp) VT: 1,50 kW – 90,0 kW (2,00 hp – 120 hp)
Input Frequency 47 to 63 Hz
Output frequency 0 Hz to 650 Hz
Power Factor 0.95
Inverter Efficiency Frame Sizes A to F: 96 % to 97 % Frame Sizes FX and GX: 97 % to 98 %
Constant Torque (CT)
Frame Sizes A to F: 1.5 x Nominal output current (i.e. 150 % overload) for 60 s every 300 s and 2 x Nominal output current (i.e 200 % overload) for 3 s every 300 s
Frame Sizes FX and GX: 1.36 x Nominal output current (i.e 136 % overload) for 57 s every 300 s and 1.6 x Nominal output current (i.e 160 % overload) for 3 s every 300 s Overload
Capability Variable Torque (VT)
Frame Sizes A to F: 1.1 x Nominal output current (i.e. 110 % overload) for 60 s every 300 s and 1.4 x Nominal output current (i.e 140 % overload) for 3 s every 300 s
Frame Sizes FX and GX: 1.1 x Nominal output current (i.e. 110% overload) for 59 s every 300 s and 1.5 x Nominal output current (i.e 150% overload) for 1 s every 300s
Inrush Current Less than rated input current
Power-ON-OFF cycle time Frame Sizes A to E: every 30 s Frame Size F: every 150 s Frame Sizes FX and GX: every 300 s
Control Method V/f control, output frequency between 0 Hz and 650 Hz: Linear V/f control, Linear V/f control with FCC, Parabolic V/f control, Multi-point V/f control, V/f control for textile applications, V/f control with FCC for textile applications, V/f control with independent voltage setpoint, Vector control, output frequency between 0 Hz and 200 Hz: Sensorless Vector Control, Sensorless Vector Torque Control, Speed control with Encoder Feedback, Torque control with Encoder Feedback
Pulse Frequency Frame Sizes A to C: 1/3AC 200 V to 5,5 kW (Standard 16 kHz) Frame Sizes A to F: other powers and voltages
2 kHz to 16 kHz (2 kHz steps) (Standard 4 kHz) power reduction see Table 5-3
Frame Sizes FX and GX: 2 kHz to 4 kHz (2 kHz steps) (Standard 2 kHz (VT), 4 kHz (CT)) power reduction see Table 5-3
Fixed Frequencies 15, programmable
Skip Frequencies 4, programmable
Setpoint Resolution 0.01 Hz Digital, 0.01 Hz Serial, 10 bit Analogue (motor potentiometer 0.1 Hz [0.1% (in PID mode)
Digital Inputs 6, programmable (isolated), switchable active high / active low (PNP/NPN)
Analog Inputs 2, programmable, both are parameterizable as 7th and 8th digital inputs 0 V to 10 V, 0 mA to 20 mA and –10 V to +10 V (ADC1) 0 V to 10 V and 0 mA to 20 mA (ADC2)
Relay Outputs 3, programmable 30 V DC / 5 A (resistive), 250 V AC 2 A (inductive)
Analogue Output 2, programmable (0 to 20 mA)
Issue 10/06 5 MICROMASTER 440 specifications
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 263
Feature Specification Serial Interface RS485, optional RS232
Electromagnetic Compatibility Frame Sizes A to C: optional class A or B filters available according to EN55011
Frame Sizes A to F: inverter with integrated class A filter available Frame Sizes FX and GX: With EMI filter (available as an option) the limiting
values of the EN 55011, Class A are fulfilled for conducted emission. (line commutating choke required)
Braking DC braking, compound braking Dynamic braking Frame Sizes A to F with integrated chopper
Frame Sizes FX and GX with external chopper
Protection Level IP20
Temperature range Frame Sizes A to F: -10 °C to +50 °C (14 °F to 122 °F) (CT) -10 °C to +40 °C (14 °F to 104 °F) (VT)
Frame Sizes FX and GX: 0 °C to +40 °C (32 °F to 104 °F), up to 55 °C (131 °F) Power reduction see Figure 2.2
Storage Temperature -40 °C to +70 °C (-40 °F to 158 °F)
Humidity < 95 % RH – non-condensing
Operational Altitudes Frame Sizes A to F: Up to 1000 m above sea level without derating Frame Sizes FX and GX: Up to 2000 m above sea level without derating
Protection Features Undervoltage , Overvoltage, Overload, Ground Faults, Short circuit, Stall Prevention, Motor Blocking Protection, Motor Overtemperature, Inverter Overtemperature, Parameter Interlock
Standards Frame Sizes A to F: UL, cUL, CE, C-tick Frame Sizes FX and GX: UL, cUL, CE
CE Marked Conformity with EC Low Voltage Directive 73/23/EEC and filtered versions also Electromagnetic Compatibility Directive 89/336/EEC
5 MICROMASTER 440 specifications Issue 10/06
MICROMASTER 440 Operating Instructions 264 6SE6400-5AW00-0BP0
Table 5-2 Dimensions, required cooling air flow and tightening torques for power terminals
Frame Size Dimensions Required cooling air flow Tightening torque for
power connections mm 73 × 173 × 149 l/s 4.8 Nm 1.1
A WxHxD inch 2.87 × 6.81 × 5.87 CFM 10.2
mm 149 × 202 × 172 l/s 24 Nm 1.5 B WxHxD
inch 5.87 × 7.95 × 6.77 CFM 51
mm 185 × 245 × 195 l/s 54.9 Nm 2.25 C WxHxD
inch 7.28 × 9.65 × 7.68 CFM 116.3
mm 275 × 520 × 245 l/s 2 × 54.9 Nm 10 (max.) D WxHxD
inch 10.82 × 20.47 × 9.65 CFM 2 × 116.3
mm 275 × 650 × 245 l/s 2 × 54.9 Nm 10 (max.) E WxHxD
inch 10.82 × 25.59 × 9.65 CFM 2 × 116.3
mm 350 × 850 Height with filter 1150 l/s 150 Nm 50
F WxHxD inch 13.78 × 33.46 × 12.60
Height with filter 45.28 CFM 317.79
mm 326 × 1400 × 356 l/s 225 Nm 25 FX WxHxD
inch 12.80 × 55.12 × 12.83 CFM 478.13
mm 326 × 1533 × 545 l/s 440 Nm 25 GX WxHxD
inch 12.80 × 60.35 × 21.46 CFM 935
Issue 10/06 5 MICROMASTER 440 specifications
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 265
Table 5-3 Current reduction depending on pulse frequency
Output current in A with a switching frequency of; Mains voltage Power (CT) [kW] 4 kHz 6 kHz 8 kHz 10 kHz 12 kHz 14 kHz 16 kHz
0.12 to 5.5 Factory setting 16 kHz – no derating necessary 7.5 28.0 26.6 25.2 22.4 19.6 16.8 14.0 11 42.0 37.8 33.6 29.4 25.2 21.0 16.8 15 54.0 48.6 43.2 37.8 32.4 27.0 21.6
18.5 68.0 64.6 61.2 54.4 47.6 40.8 34.0 22 80.0 72.0 64.0 56.0 48.0 40.0 32.0 30 104.0 91.0 78.0 70.2 62.4 57.2 52.0 37 130.0 113.8 97.5 87.8 78.0 71.5 65.0
1/3 AC 200 V
45 154.0 134.8 115.5 104.0 92.4 84.7 77.0 0.37 1.3 1.3 1.3 1.3 1.3 1.2 1.0 0.55 1.7 1.7 1.7 1.6 1.5 1.4 1.2 0.75 2.2 2.2 2.2 2.0 1.8 1.5 1.3
1.1 3.1 2.9 2.8 2.5 2.2 1.9 1.6 1.5 4.1 3.7 3.3 2.9 2.5 2.1 1.6 2.2 5.9 5.6 5.3 4.7 4.1 3.5 3.0 3.0 7.7 6.9 6.2 5.4 4.6 3.9 3.1 4.0 10.2 9.2 8.2 7.1 6.1 5.1 4.1 5.5 13.2 11.9 10.6 9.2 7.9 6.6 5.3 7.5 19.0 18.1 17.1 15.2 13.3 11.4 9.5
11.0 26.0 23.4 20.8 18.2 15.6 13.0 10.4 15.0 32.0 30.4 28.8 25.6 22.4 19.2 16.0 18.5 38.0 34.2 30.4 26.6 22.8 19.0 15.2
22 45.0 40.5 36.0 31.5 27.0 22.5 18.0 30 62.0 58.9 55.8 49.6 43.4 37.2 31.0 37 75.0 67.5 60.0 52.5 45.0 37.5 30.0 45 90.0 76.5 63.0 51.8 40.5 33.8 27.0 55 110.0 93.5 77.0 63.3 49.5 41.3 33.0 75 145.0 112.4 79.8 68.9 58.0 50.8 43.5 90 178.0 – – – – – –
110 205.0 – – – – – – 132 250.0 – – – – – – 160 302.0 – – – – – –
3 AC 400 V
200 370.0 – – – – – – 0.75 1.4 1.2 1.0 0.8 0.7 0.6 0.6
1.5 2.7 2.2 1.6 1.4 1.1 0.9 0.8 2.2 3.9 2.9 2.0 1.6 1.2 1.0 0.8 4.0 6.1 4.6 3.1 2.4 1.8 1.5 1.2 5.5 9.0 6.8 4.5 3.6 2.7 2.3 1.8 7.5 11.0 8.8 6.6 5.5 4.4 3.9 3.3
11.0 17.0 12.8 8.5 6.8 5.1 4.3 3.4 15.0 22.0 17.6 13.2 11.0 8.8 7.7 6.6 18.5 27.0 20.3 13.5 10.8 8.1 6.8 5.4
22 32.0 24.0 16.0 12.8 9.6 8.0 6.4 30 41.0 32.8 24.6 20.5 16.4 14.4 12.3 37 52.0 39.0 26.0 20.8 15.6 13.0 10.4 45 62.0 52.7 43.4 40.3 37.2 32.6 27.9 55 77.0 67.4 57.8 52.0 46.2 42.4 38.5
3 AC 500 V
75 99.0 84.2 69.3 64.4 59.4 52.0 44.6
5 MICROMASTER 440 specifications Issue 10/06
MICROMASTER 440 Operating Instructions 266 6SE6400-5AW00-0BP0
Table 5-4 Data for braking resistors
IDC_max for Frame Size Rated voltage VDC_max
A B C D E F
230 V 410 - 420 V 2,33 A(180 Ω)
6,18 A(68 Ω)
10,77 A (39 Ω)15,56 A (27 Ω)
41,0 A (10 Ω)
60,3 A (6,8 Ω)
124,2 A(3,3 Ω)
400 V 820 - 840 V 2,15 A(390 Ω)
5,25 A(160 Ω)
15 A (56 Ω)
30,4 A (27 Ω)
54,7 A (15 Ω)
100,0 A(8,2 Ω)
575 V 1020 V - - 8,5 A (120 Ω)12,4 A (82 Ω)
26,2 A (39 Ω)
37,8 A (27 Ω)
85,0 A(12 Ω)
Table 5-5 MICROMASTER 440 Specifications
In order that the system is in compliance with UL, UL-certified fuses must be used with the appropriate rated current.
Input voltage range 1 AC 200 V – 240 V, ± 10 % (with built in Class A Filter)
Order No. 6SE6440- 2AB11-2AA1
2AB12-5AA1
2AB13-7AA1
2AB15-5AA1
2AB17-5AA1
2AB21-1BA1
2AB21-5BA1
2AB22-2BA1
2AB23-0CA1
[kW] 0.12 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3.0 Output Rating (CT) [hp] 0.16 0.33 0.5 0.75 1.0 1.5 2.0 3.0 4.0
Output Power [kVA] 0.4 0.7 1.0 1.3 1.7 2.4 3.2 4.6 6.0
CT Input Current 1) [A] 1.8 3.2 4.6 6.2 8.2 11.0 14.4 20.2 35.5
CT Output Current [A] 0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4 13.6
Fuse [A] 10 10 10 16 16 20 20 32 40 Recommended 3NA 3803 3803 3803 3805 3805 3807 3807 3812 3817 for UL specified * * * * * * * * *
[mm2] 1.0 1.0 1.0 1.5 1.5 2.5 2.5 4.0 6.0 Input Cable Min. [awg] 18 18 18 16 16 14 14 12 10
[mm2] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0 Input Cable Max. [awg] 14 14 14 14 14 10 10 10 8
[mm2] 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5 Output Cable Min. [awg] 18 18 18 18 18 18 18 18 16
[mm2] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0 Output Cable Max. [awg] 14 14 14 14 14 10 10 10 8
[kg] 1.3 1.3 1.3 1.3 1.3 3.4 3.4 3.4 5.7 Weight [lbs] 2.9 2.9 2.9 2.9 2.9 7.5 7.5 7.5 12.5
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 240 V without line commutating reactor.
* UL listed fuses such as Class NON from Bussmann are required for use in America
Issue 10/06 5 MICROMASTER 440 specifications
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 267
Input voltage range 1 AC 200 V – 240 V. ± 10 % (Unfiltered)
Order No. 6SE6440- 2UC11-2AA1
2UC12-5AA1
2UC13-7AA1
2UC15-5AA1
2UC17-5AA1
2UC21-1BA1
2UC21-5BA1
2UC22-2BA1
2UC23-0CA1
[kW] 0.12 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3.0 Output Rating (CT) [hp] 0.16 0.33 0.5 0.75 1.0 1.5 2.0 3.0 4.0
Output Power [kVA] 0.4 0.7 1.0 1.3 1.7 2.4 3.2 4.6 6.0
CT Input Current 1) [A] 1.8 3.2 4.6 6.2 8.2 11.0 14.4 20.2 35.5
CT Output Current [A] 0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4 13.6
Fuse [A] 10 10 10 16 16 20 20 32 40 Recommended 3NA 3803 3803 3803 3805 3805 3807 3807 3812 3817 for UL specified * * * * * * * * *
[mm2] 1.0 1.0 1.0 1.5 1.5 2.5 2.5 4.0 6.0 Input Cable Min. [awg] 18 18 18 16 16 14 14 12 10
[mm2] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0 Input Cable Max. [awg] 14 14 14 14 14 10 10 10 8
[mm2] 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5 Output Cable Min. [awg] 18 18 18 18 18 18 18 18 16
[mm2] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0 Output Cable Max. [awg] 14 14 14 14 14 10 10 10 8
[kg] 1.3 1.3 1.3 1.3 1.3 3.3 3.3 3.3 5.5 Weight [lbs] 2.9 2.9 2.9 2.9 2.9 7.3 7.3 7.3 12.1
Input voltage range 3 AC 200 V – 240 V. ± 10 % (with built in Class A Filter)
Order No. 6SE6440- 2AC23-0CA1
2AC24-0CA1
2AC25-5CA1
[kW] 3.0 4.0 5.5 Output Rating (CT) [hp] 4.0 5.0 7.5
Output Power [kVA] 6.0 7.7 9.6
CT Input Current 1) [A] 15.6 19.7 26.5
CT-Output Current [A] 13.6 17.5 22.0
VT Input Current 1) [A] - 28.3 34.2
VT-Output Current [A] - 22.0 28.0
Fuse [A] 25 32 35 Recommended 3NA 3810 3812 3814 for UL specified * * *
[mm2] 2.5 4.0 4.0 Input Cable Min. [awg] 14 12 12
[mm2] 10.0 10.0 10.0 Input Cable Max. [awg] 8 8 8
[mm2] 1.5 4.0 4.0 Output Cable Min. [awg] 16 12 12
[mm2] 10.0 10.0 10.0 Output Cable Max. [awg] 8 8 8
[kg] 5.7 5.7 5.7 Weight [lbs] 12.5 12.5 12.5
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 240 V without line commutating reactor.
* UL listed fuses such as Class NON from Bussmann are required for use in America
5 MICROMASTER 440 specifications Issue 10/06
MICROMASTER 440 Operating Instructions 268 6SE6400-5AW00-0BP0
Input voltage range 3 AC 200 V – 240 V. ± 10 % (Unfiltered)
Order No. 6SE6440- 2UC11-2AA1
2UC12-5AA1
2UC13-7AA1
2UC15-5AA1
2UC17-5AA1
2UC21-1BA1
2UC21-5BA1
2UC22-2BA1
2UC23-0CA1
[kW] 0.12 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3.0 Output Rating (CT) [hp] 0.16 0.33 0.5 0.75 1.0 1.5 2.0 3.0 4.0
Output Power [kVA] 0.4 0.7 1.0 1.3 1.7 2.4 3.2 4.6 6.0
CT Input Current 1) [A] 1.1 1.9 2.7 3.6 4.7 6.4 8.3 11.7 15.6
CT Output Current [A] 0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4 13.6
Fuse [A] 10 10 10 16 16 20 20 25 25 Recommended 3NA 3803 3803 3803 3805 3805 3807 3807 3810 3810 for UL specified * * * * * * * * *
[mm2] 1.0 1.0 1.0 1.5 1.5 2.5 2.5 2.5 4.0 Input Cable Min. [awg] 18 18 18 16 16 14 14 14 12
[mm2] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0 Input Cable Max. [awg] 14 14 14 14 14 10 10 10 8
[mm2] 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5 Output Cable Min. [awg] 18 18 18 18 18 18 18 18 16
[mm2] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0 Output Cable Max. [awg] 14 14 14 14 14 10 10 10 8
[kg] 1.3 1.3 1.3 1.3 1.3 3.3 3.3 3.3 5.5 Weight [lbs] 2.9 2.9 2.9 2.9 2.9 7.3 7.3 7.3 12.1
Order No. 6SE6440- 2UC24-
0CA1 2UC25-5CA1
2UC27-5DA1
2UC31-1DA1
2UC31-5DA1
2UC31-8EA1
2UC32-2EA1
2UC33-0FA1
2UC33-7FA1
2UC34-5FA1
[kW] 4.0 5.5 7.5 11.0 15.0 18.5 22.0 30.0 37.0 45.0 Output Rating (CT) [hp] 5.0 7.5 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0
Output Power [kVA] 7.7 9.6 12.3 18.4 23.7 29.8 35.1 45.6 57.0 67.5
CT Input Current 1) [A] 19.7 26.5 34.2 38.0 50.0 62.0 71.0 96.0 114.0 135.0
CT-Output Current [A] 17.5 22.0 28.0 42.0 54.0 68.0 80.0 104.0 130.0 154.0
VT Input Current 1) [A] 28.3 34.2 38.0 50.0 62.0 71.0 96.0 114.0 135.0 164.0
VT-Output Current [A] 22.0 28.0 42.0 54.0 68.0 80.0 104.0 130.0 154.0 178.0
Fuse [A] 32 35 50 80 80 100 125 200 200 250 Recommended 3NA 3812 3814 3820 3824 3824 3830 3832 3140 3142 3144 for UL specified 3NE * * 1817-0 1820-0 1820-0 1021-0 1022-0 1225-0 1225-0 1227-0
[mm2] 4.0 4.0 10.0 16.0 16.0 25.0 25.0 70.0 70.0 95.0 Input Cable Min. [awg] 12 12 8 6 6 3 3 2/0 2/0 3/0
[mm2] 10.0 10.0 35.0 35.0 35.0 35.0 35.0 150.0 150.0 150.0 Input Cable Max. [awg] 8 8 2 2 2 2 2 300 300 300
[mm2] 4.0 4.0 10.0 16.0 16.0 25.0 25.0 50.0 70.0 95.0 Output Cable Min. [awg] 12 12 8 6 6 3 3 1/0 2/0 3/0
[mm2] 10.0 10.0 35.0 35.0 35.0 35.0 35.0 150.0 150.0 150.0 Output Cable Max. [awg] 8 8 2 2 2 2 2 300 300 300
[kg] 5.5 5.5 17.0 16.0 16.0 20.0 20.0 55.0 55.0 55.0 Weight [lbs] 12.1 12.1 37.0 35.0 35.0 44.0 44.0 121.0 121.0 121.0
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 240 V without line commutating reactor.
* UL listed fuses such as Class NON from Bussmann are required for use in America
Issue 10/06 5 MICROMASTER 440 specifications
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 269
Input voltage range 3 AC 380 V – 480 V. ± 10 % (with built in Class A Filter)
Order No. 6SE6440- 2AD22-2BA1
2AD23-0BA1
2AD24-0BA1
2AD25-5CA1
2AD27-5CA1
2AD31-1CA1
2AD31-5DA1
[kW] 2.2 3.0 4.0 5.5 7.5 11.0 15.0 Output Rating (CT) [hp] 3.0 4.0 5.0 7.5 10.0 15.0 20.0
Output Power [kVA] 4.5 5.9 7.8 10.1 14.0 19.8 24.4
CT-Input Current 1) [A] 7.5 10.0 12.8 15.6 22.0 23.1 33.8
CT Output Current [A] 5.9 7.7 10.2 13.2 18.4 26.0 32.0
VT Input Current 1) [A] – – – 17.3 23.1 33.8 37.0
VT-Output Current [A] – – – 20.2 29.0 39.0 45.2
Fuse [A] 16 16 20 20 32 35 50 Recommended 3NA 3805 3805 3807 3807 3812 3814 3820 for UL specified 3NE * * * * * * 1817-0
[mm2] 1.5 1.5 2.5 2.5 4.0 6.0 10.0 Input Cable Min. [awg] 16 16 14 14 12 10 8
[mm2] 6.0 6.0 6.0 10.0 10.0 10.0 35.0 Input Cable Max. [awg] 10 10 10 8 8 8 2
[mm2] 1.0 1.0 1.0 2.5 4.0 6.0 10.0 Output Cable Min. [awg] 18 18 18 14 12 10 8
[mm2] 6.0 6.0 6.0 10.0 10.0 10.0 35.0 Output Cable Max. [awg] 10 10 10 8 8 8 2
[kg] 3.4 3.4 3.4 5.7 5.7 5.7 17.0 Weight [lbs] 7.5 7.5 7.5 12.5 12.5 12.5 37.0
Order No. 6SE6440- 2AD31-
8DA1 2AD32-2DA1
2AD33-0EA1
2AD33-7EA1
2AD34-5FA1
2AD35-5FA1
2AD37-5FA1
[kW] 18.5 22.0 30.0 37.0 45.0 55.0 75.0 Output Rating (CT) [hp] 25.0 30.0 40.0 50.0 60.0 75.0 100.0
Output Power [kVA] 29.0 34.3 47.3 57.2 68.6 83.8 110.5
CT-Input Current 1) [A] 37.0 43.0 59.0 72.0 87.0 104.0 139.0
CT Output Current [A] 38.0 45.0 62.0 75.0 90.0 110.0 145.0
VT Input Current 1) [A] 43.0 59.0 72.0 87.0 104.0 139.0 169.0
VT-Output Current [A] 45.0 62.0 75.0 90.0 110.0 145.0 178.0
Fuse [A] 63 80 100 125 160 200 250 Recommended 3NA 3822 3824 3830 3832 3836 3140 3144 for UL specified 3NE 1818-0 1820-0 1021-0 1022-0 1224-0 1225-0 1227-0
[mm2] 10.0 16.0 25.0 25.0 35.0 70.0 95.0 Input Cable Min. [awg] 8 6 3 3 2 2/0 3/0
[mm2] 35.0 35.0 35.0 35.0 150.0 150.0 150.0 Input Cable Max. [awg] 2 2 2 2 300 300 300
[mm2] 10.0 16.0 25.0 25.0 50.0 70.0 95.0 Output Cable Min. [awg] 8 6 3 3 1/0 2/0 3/0
[mm2] 35.0 35.0 35.0 35.0 150.0 150.0 150.0 Output Cable Max. [awg] 2 2 2 2 300 300 300
[kg] 17.0 17.0 22.0 22.0 75.0 75.0 75.0 Weight [lbs] 37.0 37.0 48.0 48.0 165.0 165.0 165.0
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 400 V without line commutating reactor.
* UL listed fuses such as Class NON from Bussmann are required for use in America
5 MICROMASTER 440 specifications Issue 10/06
MICROMASTER 440 Operating Instructions 270 6SE6400-5AW00-0BP0
Input voltage range 3 AC 380 V – 480 V. ± 10 % (Unfiltered) Order No. 6SE6440- 2UD13
-7AA1 2UD15-5AA1
2UD17-5AA1
2UD21-1AA1
2UD21-5AA1
2UD22-2BA1
2UD23-0BA1
2UD24-0BA1
2UD25-5CA1
2UD27-5CA1
[kW] 0.37 0.55 0.75 1.1 1.5 2.2 3.0 4.0 5.5 7.5 Output Rating (CT) [hp] 0.5 0.75 1.0 1.5 2.0 3.0 4.0 5.0 7.5 10.0
Output Power [kVA] 0.9 1.2 1.6 2.3 3.0 4.5 5.9 7.8 10.1 14.0
CT Input Current 1) [A] 2.2 2.8 3.7 4.9 5.9 7.5 10.0 12.8 15.6 22.0
CT Output Current [A] 1.3 1.7 2.2 3.1 4.1 5.9 7.7 10.2 13.2 19.0
VT Input Current 1) [A] − − − − − − − − 17.3 23.1
VT-Output Current [A] − − − − − − − − 19.0 26.0
Fuse [A] 10 10 10 10 10 16 16 20 20 32 Recommended 3NA 3803 3803 3803 3803 3803 3805 3805 3807 3807 3812 for UL specified * * * * * * * * * *
[mm2] 1.0 1.0 1.0 1.0 1.0 1.5 1.5 2.5 2.5 4.0 Input Cable Min. [awg] 18 18 18 18 18 16 16 14 14 12
[mm2] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0 10.0 Input Cable Max. [awg] 14 14 14 14 14 10 10 10 8 8
[mm2] 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 2.5 4.0 Output Cable Min. [awg] 18 18 18 18 18 18 18 18 14 12
[mm2] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0 10.0 Output Cable Max. [awg] 14 14 14 14 14 10 10 10 8 8
[kg] 1.3 1.3 1.3 1.3 1.3 3.3 3.3 3.3 5.5 5.5 Weight [lbs] 2.9 2.9 2.9 2.9 2.9 7.3 7.3 7.3 12.1 12.1
Order No. 6SE6440- 2UD31
-1CA1 2UD31-5DA1
2UD31-8DA1
2UD32-2DA1
2UD33-0EA1
2UD33-7EA1
2UD34-5FA1
2UD35-5FA1
2UD37-5FA1
[kW] 11.0 15.0 18.5 22.0 30.0 37.0 45.0 55.0 75.0 Output Rating (CT) [hp] 15.0 20.0 25.0 30.0 40.0 50.0 60.0 75.0 100.0
Output Power [kVA] 19.8 24.4 29.0 34.3 47.3 57.2 68.6 83.8 110.5
CT Input Current 1) [A] 23.1 33.8 37.0 43.0 59.0 72.0 87.0 104.0 139.0
CT Output Current [A] 26.0 32.0 38.0 45.0 62.0 75.0 90.0 110.0 145.0
VT Input Current 1) [A] 33.8 37.0 43.0 59.0 72.0 87.0 104.0 139.0 169.0
VT-Output Current [A] 32.0 38.0 45.0 62.0 75.0 90.0 110.0 145.0 178.0
Fuse [A] 35 50 63 80 100 125 160 200 250 Recommended 3NA 3814 3820 3822 3824 3830 3832 3836 3140 3144 for UL specified 3NE * 1817-0 1818-0 1820-0 1021-0 1022-0 1224-0 1225-0 1227-0
[mm2] 6.0 10.0 10.0 16.0 25.0 25.0 35.0 70.0 95.0 Input Cable Min. [awg] 10 8 8 6 3 3 2 2/0 3/0
[mm2] 10.0 35.0 35.0 35.0 35.0 35.0 150.0 150.0 150.0 Input Cable Max. [awg] 8 2 2 2 2 2 300 300 300
[mm2] 6.0 10.0 10.0 16.0 25.0 25.0 35.0 70.0 95.0 Output Cable Min. [awg] 10 8 8 6 3 3 2 2/0 3/0
[mm2] 10.0 35.0 35.0 35.0 35.0 35.0 150.0 150.0 150.0 Output Cable Max. [awg] 8 2 2 2 2 2 300 300 300
[kg] 5.5 16.0 16.0 16.0 20.0 20.0 56.0 56.0 56.0 Weight [lbs] 12.1 35.0 35.0 35.0 44.0 44.0 123.0 123.0 123.0
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 400 V without line commutating reactor.
* UL listed fuses such as Class NON from Bussmann are required for use in America
Issue 10/06 5 MICROMASTER 440 specifications
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 271
Input voltage range 3 AC 380 V – 480 V ± 10 % (Unfiltered)
Order No. 6SE6440- 2UD38-8FA1 2UD41-1FA1 2UD41-3GA1 2UD41-6GA1 2UD42-0GA1[kW] 90 110 132 160 200 Output Rating (CT) [hp] 125 150 200 250 300
Output Power [kVA] 145.4 180 214.8 263.2 339.4
CT Input Current 1) [A] 169 205 245 297 354
CT Output Current [A] 178 205 250 302 370
VT Input Current 1) [A] 205 245 297 354 442
VT Output Current [A] 205 250 302 370 477
[A] 250 315 400 450 560 Recommended Fuse
3NE 1227-0 1230-0 1332-0 1333-0 1435-0
Pipe cable shoe to DIN 46235 [mm] 10 10 10 10 10
[mm2] 1 x 95 or 2 x 35
1 x 150 or 2 x 50
1 x 185 or 2 x 70
1 x 240 or 2 x 70 2 x 95
Input Cable Min. [awg] or
[kcmil] 1 x 4/0 or
2 x 2 1 x 300 or
2 x 1/0 1 x 400 or
2 x 2/0 1 x 500 or
2 x 2/0 2 x 4/0
[mm2] 1 x 185 or 2 x 120
1 x 185 or 2 x 120 2 x 240 2 x 240 2 x 240
Input Cable Max. [awg] or
[kcmil] 1 x 350 or
2 x 4/0 1 x 350 or
2 x 4/0 2 x 400 2 x 400 2 x 400
[mm2] 1 x 95 or 2 x 35
1 x 150 or 2 x 50
1 x 185 or 2 x 70
1 x 240 or 2 x 70 2 x 95
Output Cable Min. [awg] or
[kcmil] 1 x 4/0 or
2 x 2 1 x 300 or
2 x 1/0 1 x 400 or
2 x 2/0 1 x 500 or
2 x 2/0 2 x 4/0
[mm2] 1 x 185 or 2 x 120
1 x 185 or 2 x 120 2 x 240 2 x 240 2 x 240
Output Cable Max. [awg] or
[kcmil] 1 x 350 or
2 x 4/0 1 x 350 or
2 x 4/0 2 x 400 2 x 400 2 x 400
[kg] 110 110 170 170 170 Weight [lbs] 242 242 418 418 418
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk ≥ 2.33 % referred to the rated drive converter power and a rated line supply voltage of 400 V without line commutating reactor.
5 MICROMASTER 440 specifications Issue 10/06
MICROMASTER 440 Operating Instructions 272 6SE6400-5AW00-0BP0
Input voltage range 3 AC 500 V – 600 V ± 10 % (Unfiltered) Order No. 6SE6440
- 2UE17-5CA1
2UE21-5CA1
2UE22-2CA1
2UE24-0CA1
2UE25-5CA1
2UE27-5CA1
2UE31-1CA1
2UE31-5DA1
[kW] 0.75 1.5 2.2 4.0 5.5 7.5 11.0 15.0 Output Rating (CT) [hp] 1.0 2.0 3.0 5.0 7.5 10.0 15.0 20.0
Output Power [kVA] 1.3 2.6 3.7 5.8 8.6 10.5 16.2 21.0
CT Input Current 1) [A] 2.0 3.7 5.3 8.1 11.1 14.4 21.5 24.9
CT Output Current [A] 1.4 2.7 3.9 6.1 9.0 11.0 17.0 22.0
VT Input Current 1) [A] 3.2 4.4 6.9 9.4 12.6 18.1 24.9 30.0
VT-Output Current [A] 2.7 3.9 6.1 9.0 11.0 17.0 22.0 27.0
Fuse [A] 10 10 10 16 16 25 32 35 Recommended 3NA 3803-6 3803-6 3803-6 3805-6 3805-6 3810-6 3812-6 3814-6 for UL specified 3NE * * * * * * * 1803-0
[mm2] 1.0 1.0 1.0 1.5 1.5 2.5 4.0 6.0 Input Cable Min. [awg] 18 18 18 16 16 14 12 10
[mm2] 10.0 10.0 10.0 10.0 10.0 10.0 10.0 35.0 Input Cable Max. [awg] 8 8 8 8 8 8 8 2
[mm2] 1.0 1.0 1.0 1.0 1.0 2.5 4.0 4.0 Output Cable Min. [awg] 18 18 18 18 18 14 12 12
[mm2] 10.0 10.0 10.0 10.0 10.0 10.0 10.0 35.0 Output Cable Max. [awg] 8 8 8 8 8 8 8 2
[kg] 5.5 5.5 5.5 5.5 5.5 5.5 5.5 16.0 Weight [lbs] 12.1 12.1 12.1 12.1 12.1 12.1 12.1 35.0
Order No. 6SE6440- 2UE31-
8DA1 2UE32-2DA1
2UE33-0EA1
2UE33-7EA1
2UE34-5FA1
2UE35-5FA1
2UE37-5FA1
[kW] 18.5 22.0 30.0 37.0 45.0 55.0 75.0 Output Rating (CT) [hp] 25.0 30.0 40.0 50.0 60.0 75.0 100.0
Output Power [kVA] 25.7 30.5 39.1 49.5 59.1 73.4 94.3
CT Input Current 1) [A] 30.0 35.0 48.0 58.0 69.0 83.0 113.0
CT Output Current [A] 27.0 32.0 41.0 52.0 62.0 77.0 99.0
VT Input Current 1) [A] 35.0 48.0 58.0 69.0 83.0 113.0 138.0
VT-Output Current [A] 32.0 41.0 52.0 62.0 77.0 99.0 125.0
Fuse [A] 50 63 80 80 125 160 160 Recommended 3NA 3820-6 3822-6 3824-6 3824-6 3132-6 3136-6 3136-6 for UL specified 3NE 1817-0 1818-0 1820-0 1820-0 1022-0 1224-0 1224-0
[mm2] 10.0 10.0 16.0 25.0 25.0 50.0 50.0 Input Cable Min. [awg] 8 8 6 3 3 1/0 1/0
[mm2] 35.0 35.0 35.0 35.0 150.0 150.0 150.0 Input Cable Max. [awg] 2 2 2 2 300 300 300
[mm2] 6.0 10.0 16.0 16.0 25.0 35.0 50.0 Output Cable Min. [awg] 10 8 6 6 3 2 1/0
[mm2] 35.0 35.0 35.0 35.0 150.0 150.0 150.0 Output Cable Max. [awg] 2 2 2 2 300 300 300
[kg] 16.0 16.0 20.0 20.0 56.0 56.0 56.0 Weight [lbs] 35.0 35.0 44.0 44.0 123.0 123.0 123.0
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 2 % referred to the rated drive converter power and a rated line supply voltage of 500 V without line commutating reactor.
* UL listed fuses such as Class NON from Bussmann are required for use in America
Issue 10/06 6 Options
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 273
6 Options An overview of the options available for the MICROMASTER 440 is given in this section. For further information about options. please refer to the catalog or the documentation CD.
6.1 Inverter-independent options Basic Operator Panel (BOP) Advanced Operator Panel (AOP) DeviceNet module CANopen option module Pulse encoder evaluation module PROFIBUS module PC to inverter connection kit PC to AOP connection kit Operator panel door mounting kit for single inverter control AOP door mounting kit for multiple inverter control “DriveMonitor” and "Starter" commissioning tool
6 Options Issue 10/06
MICROMASTER 440 Operating Instructions 274 6SE6400-5AW00-0BP0
6.2 Inverter-dependent options
Frame Sizes A to F EMC filter. Class A EMC filter. Class B Additional EMC filter. Class B Low leakage Class B filter Line commutating choke Output choke Gland plate LC filter
CAUTION When using output reactors and LC filters, operation up to a pulse frequency of 4 kHz only is permitted. Please ensure that the automatic pulse frequency reductions are also deactivated. Mandatory parameter settings when using an output reactor: P1800 = 4 kHz , P0290 = 0 or 1.
Frame Sizes FX and GX Line commutating choke EMC filter. Class A (power commutating choke required) LC filter
CAUTION When using output reactors and LC filters, operation up to a pulse frequency of 4 kHz only is permitted. Please ensure that the automatic pulse frequency reductions are also deactivated. Mandatory parameter settings when using an output reactor: P1800 = 4 kHz , P0290 = 0 or 1.
Issue 10/06 7 Electro-magnetic compatibility
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 275
7 Electro-magnetic compatibility (EMC)
This Chapter contains: EMC information.
7.1 Electro-magnetic compatibility .............................................................................. 276
7 Electro-magnetic compatibility Issue 10/06
MICROMASTER 440 Operating Instructions 276 6SE6400-5AW00-0BP0
7.1 Electro-magnetic compatibility (EMC) All manufacturers / assemblers of electrical apparatus which “performs a complete intrinsic function and is placed on the market as a single unit intended for the end user” must comply with the EMC directive 89/336/EEC.
There are three routes for the manufacturer/assembler to demonstrate compliance:
7.1.1 Self-certification
This is a manufacturer's declaration that the European standards applicable to the electrical environment for which the apparatus is intended have been met. Only standards that have been officially published in the Official Journal of the European Community can be cited in the manufacturer's declaration.
7.1.2 Technical construction file
A technical construction file can be prepared for the apparatus describing its EMC characteristics. This file must be approved by a ‘Competent Body’ appointed by the appropriate European government organization. This approach allows the use of standards that are still in preparation.
7.1.3 EC type examination certificate
This approach is only applicable to radio communication transmitting apparatus. All MICROMASTER 440 units are certified for compliance with the EMC directive. when installed in accordance with the recommendations in Section 2.
Issue 10/06 7 Electro-magnetic compatibility
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 277
7.1.4 EMC Directive Compliance with Imminent Harmonics Regulations
From 1st January 2001 all electrical apparatus covered by the EMC Directive will have to comply with EN 61000-3-2 "Limits for harmonic current emissions (equipment input ≤ 16 A per phase)".
All Siemens variable speed drives of the MICROMASTER. MIDIMASTER. MICROMASTER Eco and COMBIMASTER ranges. which are classified as "Professional Equipment" within the terms of the standard. fulfill the requirements of the standard.
The allowed harmonic currents for “professional equipment” with an input power > 1 kW are not yet defined. Therefore. any electrical apparatus containing the above drives which has an input power > 1 kW will not require connection approval.
Only Frame Sizes A to C Special considerations for 250 W to 550 W drives with 230 V 1ac mains supplies when used in non-industrial applications:
Units in this voltage and power range will be supplied with the following warning:
”This equipment requires supply authority acceptance for connection to the public supply network”. Please refer to EN 61000-3-12 sections 5.3 and 6.4 for further information. Units connected to Industrial Networks1 do not require connection approval (see EN 61800-3. section 6.1.2.2).
The harmonic current emissions from these products are described in the table below:
Table 7-1 Permissible harmonic current emissions
Rating Typical Harmonic Current (A)
Typical Harmonic Current (%)
Typical Voltage Distortion
Distribution Transformer Rating 10 kVA 100 kVA 1 MVA
3rd 5th 7th 9th 11th 3rd 5th 7th 9th 11th THD (%) THD (%) THD (%)
250 W 1AC 230 V 2.15 1.44 0.72 0.26 0.19 83 56 28 10 7 0.77 0.077 0.008
370 W 1AC 230 V 2.96 2.02 1.05 0.38 0.24 83 56 28 10 7 1.1 0.11 0.011
550 W 1AC 230 V 4.04 2.70 1.36 0.48 0.36 83 56 28 10 7 1.5 0.15 0.015
NOTE The allowed harmonic currents for “professional equipment” with an input power > 1 kW are not yet defined. Therefore. any electrical apparatus containing the above drives which has an input power > 1 kW will not require connection approval. Alternatively. the necessity to apply for connection approval can be avoided by fitting the input chokes recommended in the technical catalogues (except 550 W 230 V 1ac units).
1 Industrial Networks are defined as those which do not supply buildings used for domestic purposes.
7 Electro-magnetic compatibility Issue 10/06
MICROMASTER 440 Operating Instructions 278 6SE6400-5AW00-0BP0
7.1.5 Classification of EMC performance
General classes of EMC performance are available as detailed below:
Class 1: General Industrial Compliance with European Standard EN 61800-3 (EMC Product Standard for Power Drive Systems) for use in Second Environment (Industrial).
Table 7-2 General industrial application
EMC Phenomenon Standard Level Radiated emissions EN 55011 Level A1 Emissions:
Conducted emissions EN 61800-3 Limits complying with EN 55011, Class A, Group 2
Electrostatic discharge EN 61000-4-2 8 kV air discharge
Burst interference EN 61000-4-4 2 kV power cables, 1 kV control cables
Immunity:
Radio-frequency electromagnetic field
EN 61000-4-3 26–1000 MHz, 10 V/m
Class 2: Industrial application with filter This level of EMC performance will allow the manufacturer/installer to certify their equipment themselves for compliance with the EMC directive for the industrial environment, as far as the EMC performance characteristics of the power drive system are concerned. Performance limits are as specified in the Generic Industrial Emissions and Immunity Standards EN 61000-6-4 und EN 61000-6-2.
Table 7-3 With filter, for industrial applications
EMC Phenomenon Standard Level Radiated emissions EN 55011 Level A1 Emissions: Conducted emissions
EN 61800-3 Limits complying with EN 55011, Class A, Group 2
Supply voltage distortion
EN 61000-2-4
Voltage fluctuations, dips, unbalance, frequency variations
EN 61000-2-1
Magnetic fields EN 61000-4-8 50 Hz, 30 A/m Electrostatic discharge EN 61000-4-2 8 kV air discharge Burst interference
EN 61000-4-4 2 kV power cables, 2 kV control cables
Radio-frequency electro-magnetic field, amplitude- modulated
EN 61000-4-3 80–1000 MHz, 10 V/m, 80% AM, power and signal lines
Immunity:
Radio-frequency electro-magnetic field, pulse- modulated
EN 61000-4-3 900 MHz, 10 V/m 50 % duty cycle, repetition rate 200 Hz
Issue 10/06 7 Electro-magnetic compatibility
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 279
Only Frame Sizes A to F
Class 3: With filter, for residential, commercial and trade applications This level of EMC performance will allow the manufacturer/installer to certify compliance of their equipment themselves with the EMC directive for the residential, commercial and light industrial environment, as far as the EMC performance characteristics of the power drive system are concerned. Performance limits are as specified in the Generic Emission and Immunity Standards EN 61000-6-3 and EN 61000-6-1 in residential applications.
Table 7-4 With filter, for residential, commercial and trade applications
EMC Phenomenon Standard Level Radiated emissions* EN 55011 Level B Emissions: Conducted emissions
EN 61800-3 Category C1: Limit complying with EN 55011, Class B Category C2: Limit complying with EN 55011, Class A
Supply voltage distortion EN 61000-2-4 Voltage fluctuations, dips, unbalance, frequency variations
EN 61000-2-1
Magnetic fields EN 61000-4-8 50 Hz, 30 A/m Electrostatic discharge EN 61000-4-2 8 kV air discharge Burst interference
EN 61000-4-4 2 kV power cables, 2 kV control cables
Radio-frequency electro-magnetic field, amplitude-modulated
EN 61000-4-3 80–1000 MHz, 10 V/m, 80 % AM, power and signal lines
Immunity:
Radio-frequency electro-magnetic field, pulse-modulated
EN 61000-4-3 900 MHz, 10 V/m 50 % duty cycle, repetition rate 200 Hz
* These limits are dependent on the inverter being correctly installed inside a
metallic switchgear enclosure. The limits will not be met if the inverter is not enclosed.
NOTES To achieve these performance levels. you must not exceed the default Pulse
frequency nor use cables longer than 25 m. The MICROMASTER inverters are intended exclusively for professional
applications. Therefore. they do not fall within the scope of the harmonics emissions specification EN 61000-3-2.
Maximum mains supply voltage when filters are fitted is 460 V.
7 Electro-magnetic compatibility Issue 10/06
MICROMASTER 440 Operating Instructions 280 6SE6400-5AW00-0BP0
Table 7-5 Compliance Table
Frame Sizes A to F Model Remarks Class 1 – General industrial application 6SE6440-2U***-**A1 Units without filters, all voltages and performances. The product norm EN 61800-3
+A11 for "Variable-speed electrical drives, Part 3: EMC product standard including specific test methods” specifies limits for conducted emissions which cannot be complied with by unfiltered inverters in the second environment. Filtered inverters (as described under Class 2) must be installed for drive systems in C3 installations. The use of unfiltered inverters in industrial environments is allowed only if they are part of a system which is equipped with line filters on the higher-level supply side.
Class 2 – With filter, for industrial application 6SE6440-2A***-**A1 All units with integral Class A filters
6SE6440-2A***-**A1 with 6SE6440-2FA00-6AD1
Frame size A units 400 - 480 V with external Class A footprint filters
Class 3 – With filter, for residential, commercial and trade applications 6SE6440-2U***-**A1 with 6SE6400-2FB0*-***0
Units without filter fitted with external Class B footprint filters.
6SE6440-2A***-**A1 with 6SE6400-2FS0*-***0 or 6SE6400-2FL0*-***0
Units with fitted Class A filters and additional external Class B filters.
6SE6440-2U***-**A0 with EMC filter Class B (e.g. Fa. Schaffner) 6SE6440-2A***-**A0
Units without filter fitted with external Class A footprint filters. All units with fitted Class A filters. For drive systems in category C2 installations, the following warning notice is necessary: In residential environments, this product may cause radio-frequency disturbances which may necessitate interference suppression measures.
* denotes any value is allowed.
Frame Sizes FX to GX Model Remarks Class 1 – General industrial application 6SE6440-2U***-**A1 Units without filters, all voltages and performances. The product norm EN 61800-3
+A11 for "Variable-speed electrical drives, Part 3: EMC product standard including specific test methods” specifies limits for conducted emissions which cannot be complied with by unfiltered inverters in the second environment. Filtered inverters (as described under Class 2) must be installed for drive systems in C3 installations. The use of unfiltered inverters in industrial environments is allowed only if they are part of a system which is equipped with line filters on the higher-level supply side.
Class 2 – With filter, for industrial application 6SE6440-2U***-**A1 With external EMI filter (available as an option) the limiting values of the EN 55011.
Class A are fulfilled for conducted emission. (line commutating choke required)
Category C3: Drive system (PDS) with rated voltage < 1000 V. For use in second environment. Category C2: Drive system (PDS) with rated voltage < 1000 V.
For use in first environment. Installation and commissioning by EMC expert only. Category C1: Drive system (PDS) with rated voltage < 1000 V. For use in first environment.
Issue 10/06 Changing the Operator Panel
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 281
Appendices
A Changing the Operator Panel
Removing Front Covers Issue 10/06
MICROMASTER 440 Operating Instructions 282 6SE6400-5AW00-0BP0
B Removing Front Covers
B.1 Removing Front Covers. Frame Sizes A
Issue 10/06 Removing Front Covers
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 283
B.2 Removing Front Covers. Frame Sizes B and C
Removing Front Covers Issue 10/06
MICROMASTER 440 Operating Instructions 284 6SE6400-5AW00-0BP0
B.3 Removing Front Covers. Frame Sizes D and E
Issue 10/06 Removing Front Covers
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 285
B.4 Removing Front Covers. Frame Size F
1
3
2
19 mm
Removing Front Covers Issue 10/06
MICROMASTER 440 Operating Instructions 286 6SE6400-5AW00-0BP0
B.5 Removing Front Covers. Frame Sizes FX and GX
Issue 10/06 Removing the I/O Board
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 287
C Removing the I/O Board
NOTICE 1. Only a small amount of pressure is required to release the I/O Board catch. 2. Currently. the I/O Board is removed using the same technique regardless of
frame size.
Removing ‘Y’ Cap Issue 10/06
MICROMASTER 440 Operating Instructions 288 6SE6400-5AW00-0BP0
D Removing ‘Y’ Cap
D.1 Removing ‘Y’ Cap. Frame Size A
Issue 10/06 Removing ‘Y’ Cap
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 289
D.2 Removing ‘Y’ Cap. Frame Sizes B and C
Removing ‘Y’ Cap Issue 10/06
MICROMASTER 440 Operating Instructions 290 6SE6400-5AW00-0BP0
D.3 Removing ‘Y’ Cap. Frame Sizes D and E
Issue 10/06 Removing ‘Y’ Cap
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 291
D.4 Removing ‘Y’ Cap. Frame Size F
Removing ‘Y’ Cap Issue 10/06
MICROMASTER 440 Operating Instructions 292 6SE6400-5AW00-0BP0
D.5 Removing ‘Y’ Cap. Frame Size FX
Issue 10/06 Removing ‘Y’ Cap
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 293
D.6 Removing ‘Y’ Cap. Frame Size GX
Removing fan Issue 10/06
MICROMASTER 440 Operating Instructions 294 6SE6400-5AW00-0BP0
E Removing fan
E.1 Removing fan. Frame Size A
Issue 10/06 Removing fan
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 295
E.2 Removing fan. Frame Sizes B and C
Removing fan Issue 10/06
MICROMASTER 440 Operating Instructions 296 6SE6400-5AW00-0BP0
E.3 Removing fan. Frame Size D and E
Issue 10/06 Removing fan
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 297
E.4 Removing fan. Frame Size F
Removing fan Issue 10/06
MICROMASTER 440 Operating Instructions 298 6SE6400-5AW00-0BP0
E.5 Removing fan. Frame Size F with filter
Issue 10/06 Removing fan
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 299
E.6 Removing fan. Frame Sizes FX and GX When replacing the fans for sizes FX and GX. refer to the documentation CD ROM. directory - "Spares".
Short circuit current rating (SCCR) Issue 10/06
MICROMASTER 440 Operating Instructions 300 6SE6400-5AW00-0BP0
F Short circuit current rating (SCCR)
Frame Sizes A to C The equipment has a "standard SCCR" value of 10 kA, which complies with the requirements of UL508C. In addition to the "standard SCCR" a "high SCCR" is available which can be used for industrial control panel installations in line with the National Electrical Code (NEC) article 409 (edition 2005) and Underwriters Laboratories UL508A (effective April 2006). The uL certification of MICROMASTER 440 allows the drives to adopt a high SCCR equal to the interupt current rating of the branch-circuit protection (BCP) device protecting the drive. Hence by selection of the correct uL listed BCP device with appropriate interrupt rating for the application, any high SCCR rating can be achieved for MICROMASTER 440, including SCCR values above 10 kA. The above statements are valid for the respective maximum voltage of the drive when protected by a UL recognised/listed H, J or K type fuse, a circuit breaker or self-protected combination motor controller.
Frame Sizes D to GX The equipment has a "standard SCCR" value of 42 kA, which complies with the requirements of UL508C. A "high SCCR", which can be used for industrial control panel installations in line with the National Electrical Code (NEC) article 409 (edition 2005) and Underwriters Laboratories UL508A (effective April 2006), can be achieved with the use of current limiting fuses or circuit breakers with an appropriate interrupt rating and derived let through current. For compliance with NEC article 409 and UL508A the calculation, selection and marking of the current limiting device must be carried out by an qualified engineer. The above statements are valid for the respective maximum voltage of the drive when protected by a UL recognised/listed H, J or K type fuse, a circuit breaker or self-protected combination motor controller
Issue 10/06 Standards
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 301
G Standards
European Low Voltage Directive The MICROMASTER product range complies with the requirements of the Low Voltage Directive 73/23/EEC as amended by Directive 98/68/EEC. The units are certified for compliance with the following standards: EN 61800-5-1 Adjustable speed electrical power drive systems,
Part 5-1: Safety requirements – Electrical, thermal and energy
EN 60204-1 Safety of machinery - Electrical equipment of machines
European Machinery Directive The MICROMASTER inverter series does not fall under the scope of the Machinery Directive. However. the products have been fully evaluated for compliance with the essential Health & Safety requirements of the directive when used in a typical machine application. A Declaration of Incorporation is available on request.
European EMC Directive When installed according to the recommendations described in this manual. the MICROMASTER fulfils all requirements of the EMC Directive as defined by the EMC Product Standard for Power Drive Systems EN61800-3.
Underwriters Laboratories UL and CUL LISTED POWER CONVERSION EQUIPMENT
ISO 9001 Siemens plc operates a quality management system. which complies with the requirements of ISO 9001.
List of Abbreviations Issue 10/06
MICROMASTER 440 Operating Instructions 302 6SE6400-5AW00-0BP0
H List of Abbreviations AC Alternating current AD Analog digital converter ADC Analog digital converter ADR Address AFM Additional frequency modification AG Automation unit AIN Analog input AOP Advanced operator panel AOUT Analog output ASP Analog setpoint ASVM Asymmetric space vector modulation BCC Block check character BCD Binary-coded decimal code BI Binector input BICO Binector / connector BO Binector output BOP Basic operator panel C Commissioning CB Communication board CCW Counter-clockwise CDS Command data set CI Connector input CFM Cubicfeet per minute (1 l/s ≅ 2,1 CFM) CM Configuration management CMD Commando CMM Combimaster CO Connector output CO/BO Connector output / Binector output COM Common (terminal that is connected to NO or NC) COM-Link Communication link CT Commissioning. ready to run CT Constant torque CUT Commissioning. run. ready to run CW Clockwise DA Digital analog converter DAC Digital analog converter DC Direct current DDS Drive data set DIN Digital input DIP DIP switch DOUT Digital output
Issue 10/06 List of Abbreviations
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 303
DS Drive state EEC European Economic Community EEPROM Electrical erasable programmable read-only memory ELCB Earth leakage circuit breaker EMC Electro-magnetic compatibility EMF Electromotive force EMI Electro-magnetic interference ESB Equivalent circuit FAQ Frequently asked questions FB Function block FCC Flux current control FCL Fast current limit FF Fixed frequency FFB Free function block FOC Field orientated control FSA Frame size A GSG Getting started guide GUI ID Global unique identifier HIW Main actual value HSW Main setpoint HTL High-threshold logic I/O Input and output IBN Commissioning IGBT Insulated gate bipolar transistor IND Sub-index JOG Jog KIB Kinetic buffering LCD Liquid crystal display LED Light emitting diode LGE Length MHB Motor holding brake MM4 MICROMASTER 4th. Generation MOP Motor potentiometer NC Normally closed NO Normally open OPI Operating instructions PDS Power drive system PID PID controller (proportional. integral. derivative) PKE Parameter ID PKW Parameter ID value PLC Programmable logic controller PLI Parameter list PPO Parameter process data object PTC Positive temperature coefficient
List of Abbreviations Issue 10/06
MICROMASTER 440 Operating Instructions 304 6SE6400-5AW00-0BP0
PWE Parameter value PWM Pulse-width modulation PX Power extension PZD Process data QC Quick commissioning RAM Random-access memory RCCB Residual current circuit breaker RCD Residual current device RFG Ramp function generator RFI Radio-frequency interference RPM Revolutions per minute SCL Scaling SDP Status display panel SLVC Sensorless vector control STW Control word STX Start of text SVM Space vector modulation TTL Transistor-transistor logic USS Universal serial interface VC Vector control VT Variable torque ZSW Status word ZUSW Additional setpoint
Issue 10/06 Index
MICROMASTER 440, Operating Instructions 6SE6400-5AW00-0BP0 305
Index
A
Adaptation of fan voltage.........................41 Alarm Messages....................................260 Altitude.....................................................24 Ambient operating conditions
Altitude .................................................24 Atmospheric Pollution ..........................25 Electromagnetic Radiation...................24 Humidity Range ...................................24 Installation and cooling ........................25 Shock ...................................................24 Temperature ........................................24 Vibration...............................................24 Water hazard .......................................25
Ambient operating conditions ..................24 Atmospheric pollution ..............................25 Automatic restart ...................................211
B
BICO technology .....................................57 Block diagram..........................................74 Brake unit ................................................36
C
Changing the Operator Panel................281 Changing the Operator Panel................281 Closed-loop motor control .....................235
Closed-loop speed control .................248 Closed-loop torque control.................253 V/f control...........................................235 Vector control.....................................243
Closed-loop speed control.....................248 Closed-loop torque control ....................253 Closed-loop Vdc control ........................215
Kinetic buffering .................................218 Vdc_max controller ............................215
Commissioning........................................77 50 / 60 Hz setting.................................79 Commissioning the application ............97 Fast commissioning .............................83 Motor / control data..............................88 Motor data identification.......................91 Reset to the factory setting ................133 Series commissioning........................132 With BOP or AOP ................................83
Communications ................................... 144 Compound braking................................ 205 Connection drawing
FX........................................................ 38 GX ....................................................... 39
Connection of brake unit ......................... 36 Connection Terminals............................. 37 Contact address........................................ 5 Current reduction depending on pulse
frequency........................................... 265
D
Data sets................................................. 63 DC braking ............................................ 202 Dimensions and Torques........................ 30 Drill pattern for MICROMASTER 440 ..... 27 Dynamic braking ................................... 206
E
Electrical Installation ............................... 33 Electro-Magnetic Compatibility
EC type-examination certificate ........ 276 general ...................................... 275, 276 self-certification ................................. 276 technical construction file .................. 276
Electro-Magnetic Interference................. 43 avoiding EMI........................................ 43
Electromagnetic radiation ....................... 24 Electronic brakes .................................. 202
Compound braking............................ 205 DC braking ........................................ 202 Dynamic braking................................ 206
EMC ...................................................... 276 EMC Directive Compliance................... 277 EMC performance
filtered for residential. commercial and light industry ...................................... 279 filtered industrial class....................... 278 general industrial class...................... 278
EMI.......................................................... 43
Index Issue 10/06
MICROMASTER 440, Operating Instructions 306 6SE6400-5AW00-0BP0
F
Fan fuses.................................................41 Fault messages .....................................260
with the BOP fitted .............................259 with the SDP fitted .............................258
Features ..................................................19 Fixed frequencies ..................................167 Flying restart..........................................213 Foreword ...................................................5 Free function blocks ..............................191 Functions .................................................47
H
Humidity Range.......................................24
I
Inputs / outputs ......................................135 Analog inputs .....................................140 Analog outputs ...................................142 Digital inputs ......................................135 Digital outputs ....................................138
Installation ...............................................21 after a period of storage.................21, 23
Installation and cooling............................25 Installation dimensions for MICROMASTER
440 Version FX ....................................28 Installation dimensions for MICROMASTER
440 Version GX....................................29 Installation of options...............................32
J
Jog.........................................................172 JOG .......................................................172
L
Load torque monitoring .........................223 Long cables
operation with.......................................35
M
Main characteristics.................................19 Mechanical Installation ............................26 MICROMASTER 440
general .................................................18 main characteristics .............................19 performance characteristics.................20 protection characteristics .....................20 specifications .....................................261
Monitoring functions / messages...........221 Motor connections ...................................35
Motor holding brake .............................. 196 Motorized potentiometer ....................... 170 Mounting on standard rail ....................... 31 Mounting onto standard rail .................... 31
O
Online Service & Support ......................... 5 Operation with
long cables .......................................... 35 Residual Current Device ..................... 34 ungrounded IT supplies....................... 34
Operator panels for MM4........................ 70 AOP..................................................... 71 BOP..................................................... 70 SDP ..................................................... 75
Options Inverter-dependent options ............... 274 Inverter-independent options ............ 273
Options.................................................. 273 Options for electronic box ....................... 32 Overload responses.............................. 227 Overview ................................................. 17
P
Parameters ............................................. 51 Attributes ............................................. 52 Changing with BOP............................. 73 Grouping and access .......................... 56 Monitoring parameters ........................ 52 Setting parameters .............................. 51
Performance characteristics ................... 20 Performance Ratings ............................ 262 PID controller ........................................ 173
PID dancer roll control....................... 179 PID fixed setpoint .............................. 178 PID motorized potentiometer ............ 177
Positioning down ramp ......................... 219 Power and motor connections ................ 35
Access................................................. 36 single phase ........................................ 40
Power connections.................................. 35 Power module protection ...................... 232 Protection characteristics........................ 20
Q
Qualified personnel ................................... 6
Issue 10/06 Index
MICROMASTER 440, Operating Instructions 6SE6400-5AW00-0BP0 307
R
Removing ‘Y’ Cap..................................288 Removing fan
Frame Size A .....................................294 Frame Size D and E ..........................296 Frame Size F .....................................297 Frame Size F with filter ......................298 Frame Sizes B and C.........................295 Frame Sizes FX and GX....................299
Removing Front Covers ........................282 Removing the I/O Board........................287 Residual Current Device
operation with.......................................34
S
Safety instructions .....................................7 Screening Methods .................................44 Setpoint channel....................................181
AFM ...................................................181 Ramp-function generator ...................183
Shock.......................................................24 Specifications ........................................266 Standards
European EMC Directive ...................301 European Low Voltage Directive .......301 European Machinery Directive...........301 ISO 9001............................................301 Underwriters Laboratories .................301
T
Technical Support ..................................... 5 Technological controller ........................ 173 Terminal Torques.................................. 264 Thermal motor protection...................... 227 Troubleshooting .................................... 257
U
Ungrounded (IT) supplies operation with ...................................... 34
V
V/f control.............................................. 235 Vector control........................................ 243
W
Warnings, cautions & notes commissioning....................................... 8 definitions .............................................. 6 dismantling & disposal........................... 9 general .................................................. 7 operation ............................................... 9 repair ..................................................... 9 transport & storage................................ 8
Water hazard .......................................... 25 Wiring Guidelines EMI ............................ 44
Index Issue 10/06
MICROMASTER 440, Operating Instructions 308 6SE6400-5AW00-0BP0
MICROMASTER 440, Operating Instructions 6SE6400-5AW00-0BP0 309
Suggestions and/or Corrections
Suggestions
Corrections
To: Siemens AG Automation & Drives Group SD SM P.O. Box 3269 D-91050 Erlangen Federal Republic of Germany
For Publication/Manual: MICROMASTER 440
Email: [email protected]
User Documentation
From
Name:
Operating Instructions Order Number: 6SE6400-5AW00-0BP0 Date of Issue: 10/06
Company/Service Department
Address:
Telephone: __________ /
Telefax: ________ /
Should you come across any printing errors when reading this publication. please notify us on this sheet.
Suggestions for improvement are also welcome.
MICROMASTER 440, Operating Instructions 310 6SE6400-5AW00-0BP0
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 311
Siemens AG Bereich Automation and Drives (A&D) Geschäftsgebiet Standard Drives (SD) Postfach 3269, D-91050 Erlangen Federal Republic of Germany
© Siemens AG 2001, 2002, 2003, 2005, 2006 Subject to change without prior notice
Siemens Aktiengesellschaft Order No.: 6SE6400-5AW00-0BP0 Date: 10/06