16/5/2014 Siemens Industry Online Support - Automation Service, Automation Support, Simatic Service, Simatic Support, Technical Support, Technical Consulting
https://support.automation.siemens.com/WW/llisapi.dll/41737436?func=ll&objId=41737437&objAction=csView&nodeid0=41886031&lang=en&siteid=cseus&… 1/7
show the entry list
S7-1200 CPU 12xx -- Setting up and parameterizing hardware -- Initializing and parameterizing
modules
Which settings do you have to make in the TIA Portal to read out messages and status information over the CPU's
web server and display them in the web browser?
What is the meaning of the system constants in STEP 7 (TIA Portal) with S7-1200/1500?
How can the CPU analog inputs of the SIMATIC S7-1200 also measure currents of 0-20mA?
How can you access user-defined web pages of the S7-1200 directly?
How do you have the web pages updated automatically in STEP 7 (TIA Portal) and how do you incorporate the user-
defined web pages with relative path names?
How do you program the "GET" and "PUT" instructions in the user program of the SIMATIC S7-1200 CPU in order to
transfer more than 160 bytes of data?
Why must you never remove a memory card when the S7-300/S7-400/S7-1200 CPU is in operation (RUN)?
How in STEP 7 (TIA Portal) can you access the unstructured data types bit-by-bit, byte-by-byte or word-by-word
and symbolically?
How does startup work in an S7-1200?
What is the connection between subnet masks and IP addresses with regard to subnetting and supernetting
(Classless Inter Domain Routing CIDR)?
How can you prevent data loss of runtime-generated parameters when updating your S7-1200 PLC program?
How can you share runtime-generated parameters between several S7-1200 PLCs with a KTP Basic Panel?
How can you change the IP address of an S7-1200 without us ing STEP 7 Bas ic?
How can you delete the IP address and reset your S7-1200 to factory settings using the SIMATIC MC memory card
(2MB or 24MB)?
How can you download to a network of several S7-1200 PLCs with the same IP address?
How can you reset the IP address of your S7-1200 PLC using STEP 7 Basic software?
How can you change the IP address of an S7-1200 without using STEP 7 Basic?
Display part number
Descript ion
The S7-1200 tool enables you to specify the IP address of one or several S7-1200 CPUs without using
the STEP 7 Basic software.
This tool is particularly useful for mass filling; if, for example, you download a project by means of a
memory card to multiple CPUs in a network and then have to change the IP address for each CPU.
Sett ing the PG/PC interface
No.
1. Click the "PG/PC Interface" button.
Fig. 01
2. 1. Select the access point below for the application: "S7IPTool".
2. For "Interface Parameter Assignment Used:" you select "TCP/IP" and the network card
you are using. You achieve the best results with the "TCP/IP(Auto)" for automatic
configuration of the network card you are using.
3. Apply the settings with "OK".
16/5/2014 Siemens Industry Online Support - Automation Service, Automation Support, Simatic Service, Simatic Support, Technical Support, Technical Consulting
https://support.automation.siemens.com/WW/llisapi.dll/41737436?func=ll&objId=41737437&objAction=csView&nodeid0=41886031&lang=en&siteid=cseus&… 2/7
Fig. 02
Table 01
Manual ass ignment of an IP address for your S7-1200
No.
1. Double-click the "Update accessible devices" button to update the list of accessible nodes.
Fig. 03
2. The S7-1200 tool displays the MAC address of CPUs without an assigned IP address.
Fig. 04
3. 1. Select the CPU to be configured from the list of accessible devices.
16/5/2014 Siemens Industry Online Support - Automation Service, Automation Support, Simatic Service, Simatic Support, Technical Support, Technical Consulting
https://support.automation.siemens.com/WW/llisapi.dll/41737436?func=ll&objId=41737437&objAction=csView&nodeid0=41886031&lang=en&siteid=cseus&… 3/7
2. Click the "Flash LED lights" button to flash the status LEDs of the CPU selected.
Fig. 05
4. Click the "Stop CPU" button to put the CPU into STOP mode.
Fig. 06
5. 1. Specify the IP address, subnet mask and gateway address for the CPU selected.
2. Then click the "Set" button.
If you enable the "Set as Default" option, the current settings are saved as "Default"
settings when you click the "Set" button.
3. Click the "Use Defaults" button to load the saved "Default" settings.
Fig. 07
6. Click the "Start CPU" button to put the CPU into RUN mode.
16/5/2014 Siemens Industry Online Support - Automation Service, Automation Support, Simatic Service, Simatic Support, Technical Support, Technical Consulting
https://support.automation.siemens.com/WW/llisapi.dll/41737436?func=ll&objId=41737437&objAction=csView&nodeid0=41886031&lang=en&siteid=cseus&… 4/7
Fig. 08
Table 02
Network Mapping
No.
1. Mark the network card folder in the tree view.
A table is displayed listing all the connected S7-1200 CPUs.
Fig. 09
2. Click the "Export..." button to generate a CSV file with the current network settings of all the
connected S7-1200 CPUs.
Save this file on your computer.
16/5/2014 Siemens Industry Online Support - Automation Service, Automation Support, Simatic Service, Simatic Support, Technical Support, Technical Consulting
https://support.automation.siemens.com/WW/llisapi.dll/41737436?func=ll&objId=41737437&objAction=csView&nodeid0=41886031&lang=en&siteid=cseus&… 5/7
Fig. 10
3. Open the exported CSV file with Notepad.
Each line in the CSV file contains a MAC address, IP address, subnet mask and gateway
address for each separate S7-1200 CPU.
You can change the network settings of each CPU as required. You must not change the MAC
address.
You can use the "#" character to insert comments in the CSV file.
Fig. 11
4. Click the "Import..." button and select the modified CSV file from Step 3.
Fig. 12
5. Your changes are shown in the Network Mapping table .
Click the "Update" button to apply the new network settings of all the CPUs.
16/5/2014 Siemens Industry Online Support - Automation Service, Automation Support, Simatic Service, Simatic Support, Technical Support, Technical Consulting
https://support.automation.siemens.com/WW/llisapi.dll/41737436?func=ll&objId=41737437&objAction=csView&nodeid0=41886031&lang=en&siteid=cseus&… 6/7
Fig. 13
6. A green circle next to the S7-1200 CPU indicates that the update has been successful.
A red circle indicates that the update has failed.
A yellow circle indicates that the S7-1200 CPU is in the process of being updated.
Fig. 14
Table 03
Addit ional Funct ions
No.
1. Click the "Fault Capture" button to read out system information from the selected S7-1200 CPU.
This information can be forwarded to Siemens for analysis.
16/5/2014 Siemens Industry Online Support - Automation Service, Automation Support, Simatic Service, Simatic Support, Technical Support, Technical Consulting
https://support.automation.siemens.com/WW/llisapi.dll/41737436?func=ll&objId=41737437&objAction=csView&nodeid0=41886031&lang=en&siteid=cseus&… 7/7
My tags : Create new bookmark/tag
Fig. 15
2. Click the "Reset To Factory Defaults" button to reset the selected S7-1200 CPU back to its
original factory settings. All the data including the IP address will be deleted.
Fig. 16
Table 04
Requirements
Operating system: Windows XP, Windows Vista or Windows 7 (32-bit versions are supported)
S7-1200
Ethernet cable
PC/PG with Ethernet interface
S7-1200 Tool V2.0.0.5
S7-1200Tool.zip ( 55566 KB )
Keywords
IPTool, IP TOOL, IP-Tool
Entry ID:41737436 Date:2011-11-21
This entry is available in the following languages:
german french italian spanish chinese
I regard this art ic le. . . . as helpful as not helpful
Copy link Suggestion for the entry Send to a friend
© Siemens AG 2014 - Corporate Information - Privacy Policy - Terms of Use