FIRE • SOUND • SPACE
800.233.8366www.cornelliron.comSAFE AND SECURE
TRANZFORM® Fire TRANZFORM® Sound TRANZFORM® Space
Side Folding Accordion ProductsSide Folding Accordion Products
Rev. 1
i.1 © Cornell Iron Works
Index – Cornell Side Folding Accordion Products Registration Card
i. 1. Index 2. TranZform® Side Folding Accordion Products Brochure Tab 1 Accordion Folding Fire Doors
1. TranZform® Fire 1 / 1 Data Sheet
1 / 2 Assembly Drawing 1 / 3 Design Applications 1 / 4 Frequently Asked Questions 1 / 5.1, 2 Ratings Information, Building Code Compliance Overview 1 / 5.3 UL Listing Info 1 / 5.4 ICC-ES Listing ESR-2300 1 / 5.5 CA State Fire Marshal Doc.
Sub Tab - TranZform Fire - Drawings 1 / 6.1 Elevation, Single Slide with Pocket 1 / 6.2 Elevation, Single Slide, Vision Window Option
1 / 6.3 Elevation, bi part 1 / 6.4 Elevation, Front View 1 / 6.5 Header Detail 1 / 6.6 Plan of Opening with Striker, Single Slide 1 / 6.7 Plan of Opening Pocket Detail 1 / 6.8 Pocket Door Guidelines 1 / 6.9 Detail Electrical Components, Single Slide 1 / 6.10 Electrical Coordination, Operator Sequence of Operation 1 / 6.11 Pocket Perspective
Sub Tab - TranZform Fire - Specification
1 / 7 Specification - TranZform Fire
1 / 8 Budget Pricing and Weight
Tab 2 According Folding Partitions ii TranZform® Sound &Space Wall Panel Finish Options
2. TranZform® Sound 2 / 1 Assembly Drawing Sub Tab - TranZform Sound- Drawings
2 / 2.1 Elevation – single slide with pocket, bi part with pocket 2 / 2.2 Plan Views, Manual Operation w/ Pockets, All Heights 2 / 2.3 Section – Recessed Track, Surface Track with Soffit 2 / 2.4 Header Detail – Doors Under 14’ 2 / 2.5 Header Detail – Doors Over 14’
Sub Tab - TranZform Sound - Specification
2 / 3 Specification - TranZform Sound
2 / 4 Budget Pricing and Weight
Rev. 1
i.2 © Cornell Iron Works
3. TranZform® Space 3 / 1 Assembly Drawing Sub Tab - TranZform Space- Drawings
3 / 2.1 Elevation – single slide with pocket, bi part with pocket 3 / 2.2 Plan Views, single slide with pocket, bi parting with pocket 3 / 2.3 Section – Recessed Track, Surface Track with Soffit 3 / 2.4 Header Details
Sub Tab - TranZform Space - Specification 3 / 3 Specification - TranZform Space
3 / 4 Budget Pricing and Weight
SID
E F
OLD
ING
A
CC
OR
DIO
N P
RO
DU
CT
S
Designed to provide automatic closing in the event of fire
detection, TranZform Fire units are rated physical fire
barriers that protect openings from the spread of fire and
smoke. TranZform Fire units can be used in openings that
are part of a required means of egress. Its minimal
headroom track and double wall panel design features fire
retardant, flexible header and floor seals attached to the
top and bottom of the panels to protect against the
passage of fire, air and smoke. No floor track required. Up
to 3 hour UL Classified fire rating, UL “S” label smoke rating
and FM ratings are available. With Emergency Egress
Hardware provided as standard, TranZform Fire units are
compliant with the Americans with Disabilities Act accessibility
standards. STC 41. IBC® compliant per ICC-ES ESR 2300.
In addition to providing privacy and security separation,
Cornell’s TranZform Sound units offer unparalleled sound
control. Its double wall panel design allows both interior
walls to be completely covered with continuous blankets of
sound absorbing material. TranZform Sound achieved an
STC 45 when tested to today’s ASTM E90 standards by an
independent laboratory. When Noise Isolation Class (NIC)
field tested in the same opening as a competitor’s product
that claims the best sound control in the industry with a higher
listed STC rating, Cornell’s TranZform Sound product
emerged as the acoustic control champion.
Though similar in finished appearance, TranZform Space
units feature single wall panel construction with a bonded
vinyl finish on public side standard, vinyl both sides optional
in a finish as selected by the end user. Use in areas where
convenient separation of space is desired, but fire control or
higher level acoustic control is not a concern, such as off
hour pedestrian control, closets and storage areas. STC 30.
TRANZFORM SOUNDMODEL ESP20
STC 45: Unparalleled Sound ControlTRANZFORM FIREMODEL ERP10
UL Classified Fire and Smoke Protection with Emergency Egress Capabilities
TRANZFORM SPACEMODEL ESP10
Convenient Space Separation, Security
Motor Operation - Provided as standard
for controlled automatic closing with
emergency exit capability and ease of
testing. DC 1/4 or 1/2 HP gear-motor, limit
switch control system, drive sprocket and
clutch. Operated by DC power supplied
from two 12-volt maintenance free batteries
located in the electronic control box.
Batteries are continuously charged by
the building’s electrical service and are
automatically maintained at capacity.
Header and Floor Sweeps -
Continuous, fire retardant flexible seals
in flat black are attached to the top and
bottom of the panels to eliminate gaps
at the floor and head area for fire and
smoke protection.
Panels - Continuous length, 4 1/2” wide
panels formed of 24 gauge commercial
grade corrugated coated steel. Coating
process includes a flexible urethane
primer followed by a high performance,
medium gloss, baked-on polyester coating
in standard platinum gray color.
Key Product Components/Construction
Size - Openings from 3’ 6" to 22’ H to a
max. of 1440 sq. ft, standard construction.
Practical Applications -
+ Openings requiring building code
compliant emergency egress
+ elevator lobbies
+ horizontal exits
+ opening protectives in
fire rated corridors
+ An alternative to banks of
fire rated swing doors where
maintaining the use of the full
opening width for functionality
and aesthetics is desired.
+ atriums + casinos
+ hotels and conference centers
+ Openings with minimal headroom
requiring rated fire, smoke or ADA
compliant fire protection
+ Stage Proscenium Openings
Lead Post - 24 gauge commercial
grade coated steel member with material
and finish to match panels. Lead sensing
edge and full length interior tubing
support provided standard. An internally
mounted stabilizer bar support shall
keep the lead posts vertical and in
proper alignment during operation and
ensure tight fitting closure of the door.
Wall Mounted Strike Post -
Recessed 18 gauge coated cold rolled
steel member that receives the lead
post and is secured to the wall opposite
the stacked door. Finish to match panels.
Product Options+ Single Slide or Bi-Parting construction
+ Curved track + Non-sway construction
+ Vision Panel + Pocket Doors
+ Powder coat finish colors: consult factory
HEAD DETAIL (Straight Track Design Shown) PLAN VIEW
FIRERatings / Listings+ UL Classified 3, 1 1/2, 1, 3/4, 1/2, 1/3 hour and “S” labels available.
+ Factory Mutual Approvals Listing. + STC 41
+ Compliance with the American with Disabilities Act
accessibility standards. + CSFM Listing
+ Acceptable for use in openings that are part of a required
means of egress. + ICC-ES ESR-2300
OperationFail-safe emergency response capability. When an alarm is
activated, TranZform Fire closes automatically to prevent the
spread of fire and smoke. In emergency mode, pressure on the
vertical exit bar causes door to open at least 54”, pause for
3 seconds, then automatically close. Closing fire doors can also be
opened manually by pushing against the leading sensing edge.
Track - Interconnected double rail heavy duty extruded aluminum or
14 gauge cold rolled steel track sections on 8” centers to support
and retain the roller assemblies. Track is supplied with a white
baked-on powder coated finish standard, with mill finish aluminum a
readily available option. Header support construction is not by Cornell.
Rollers - Each lead post / stabilizer bar assembly shall be suspended
by a 12 wheel ball bearing trolley system. Each individual panel is
suspended using a steel hanger pin and ball
bearing roller.
Track by
Cornell
3 1/4"
53/4"
1' 6"
Motor
Drive Assembly
by Cornell
3 layers 1/2" x 3 5/8"
x cont. type x fire rated
gypsum board by others
2 layers 5/8" x 18" x
cont. type x fire rated
gypsum board by others
1/2" dia. threaded rod w/ nuts
& washers by others, 18" o.c.
along opening width,
12" o.c. max. along
stack depth area
3 layers3/4" x 18"x cont. plywoodwith staggeredjoints by
others
53/4"
Floating Jamb - 18 gauge aluminized steel floating
jamb assembly that travels within the storage pocket.
PUSH
PUSH
PUSH
TO
EXIT
Hinges - Continuous length, full height 24 gauge commercial grade
coated metal hinges interconnect door panels. Material and finish to
match panels. Allow for simple panel installation and replacement.
Emergency Exit Hardware - ADA compliant, clearly marked vertical exit bar provided
as standard. Additional exit bars available on wide doors. Located on both sides.
1' 6"
4 1/4"
ClearOpening
Floating Jamb Exit HardwarePocket Door by others shown, byCIW available
Floating JambStop
Recessed Striker
4 1/8"
OperatorControlBox
TranZform Fire Hang Weight - approximately
5.5 lbs. per square foot, extended.
Pocket Depth: 1/4 HP operator (up to 100 sq. ft.) = 2.1” per ft. of opening width + 22”.1/2 HP = 2.1” per foot + 30”. Contact Cornell when clearance dimensions are critical.For units over 16’ High or if clearances are critical, consult factory.
(TranZform Sound unit shown,
TranZform Space units similar, but
are single wall construction)
Track - Heavy duty extruded aluminum
or steel shape to support and retain
the roller assemblies. Multiple types are
available for varying field ceiling
construction. Header support
construction is not by Cornell.
Header and Floor Sweeps - Flexible
extruded vinyl seals are attached to the
top and bottom of the panels to eliminate
gaps at the floor and head area.
End Member Post - Used to attach
the stack side(s) of the unit to the wall
jamb to provide a full height, secured
and sealed fit. (Not shown in illustration)
TranZform Sound Stabilizer Bar
Support - Provided with all motorized
units and for units greater 12’ tall or
when greater than 30’ wide. Is a
concealed, internally mounted diagonal
support positioned from an independent
trolley to the lead post to provide reinforced
vertical alignment during operation and
latching. (Not shown in illustration)
Sound Blocker Lining (TranZform Sound units only) - Both interior panel
surfaces are fitted with continuous blankets of sound absorbing material
attached with tear resistant fasteners that ensure lasting, effective
retention of the sound liner.
Rollers - Every panel is fitted with a nylon wheel, ball bearing
roller for added wall panel support and smooth operation.
Lead posts are fitted with heavy duty trolleys that have
multiple sets of dual rollers.
Lead Post - Heavy duty extruded aluminum
shapes fitted with grip-type handles
provide operational support and
hook bolt connection to strike
posts. Keyed locking is optional,
powder coated finish to
compliment wall panels.
+ Pocket Door - A heavy duty 12 gauge
steel pocket door and frame assembly can
be provided to neatly close off the pocket
area of a stored partition. A powder coat finish
i is standard in gray or in an optional color
as selected by the customer. Consult
factory for pocket doors over 12’ tall.
+ Single Slide or Bi-Parting Construction
+ Header Trim and Track Types including
Curved Track + Finish Colors
+ Motor Operated Sound Units
+ Locking at Lead Post: key cylinder, thumb turn
+ Fixed or Floating Jamb Construction
Strike Post (shown) /
Bi-Parting Post (not shown) -
Heavy duty extruded
aluminum shapes with hook
bolt strike to seal tight with
the lead post. Bi-part posts
are fitted with grip-type handles
and provide operational
support. Powder coated finish
to compliment wall panels.
Panels - Continuous roll
formed corrugated steel for
strength. Customer selected
permanently bonded vinyl
finishes allow personalization.
Space units feature bonded
vinyl finish on public side, platinum
gray painted finish opposite side.
Hinges - Full height extruded
vinyl hinges are rugged for
lasting performance and allow
for simple panel replacement
with units mounted in place.
Color matched to compliment
wall panels.
TRANZFORM SOUND TRANZFORM SOUND PLAN VIEW TRANZFORM SOUND PLAN VIEWDOOR PROFILE WIDTHS SINGLE SLIDE, FIXED JAMB BI-PART, FIXED JAMB
Cornell side folding accordion partitions can
accommodate virtually any width opening. With the track capable
of being recessed into the ceiling construction and with use of a
recessed pocket, they store virtually out of sight and mind allowing
full use of building space. Then, as needed, all TranZform units can
be easily moved into place allowing for convenient and private
space separation. Cornell accordion partitions are solely supported
by a low headroom overhead track and are built to opening height
requirements from 3’6” to 22’ Sound units and 3’6” to 18’+ for Space Units.
Product Options
SPACE & SOUND
Almond Driftwood Vanilla Cream Embossed Weave Embossed Weave Embossed Leather
Stock Finishes: Printed representation only. Contact Cornell for color accurate swatch.
Other finishes available with extended lead times at no added cost. Custom
finishes are available with extended lead time and additional cost. Contact
Cornell when color is critical and for additional details.
Blocking
By Others
3"
Stacked
WidthExtended
Width
Opening Width
3"
Stack Depth = 2" per foot plus
7" for lead post
1.875"
Blocking By
Others
3"
3"
Opening Width
Jamb Striker
Blocking
By Others Stack Depth = 2" per foot plus
7" for lead post per side
Blocking
By
Others
1.934"DOOR PROFILE WIDTHS:
Manual Operated Doors Below 12' H:
Stacked Width: 11.56" Extended Width: 10.25" to 10.875"
Motorized Doors & Manual Operated Doors Above 12' H or 30' W:
Stacked Width: 13.56" Extended Width: 12.25" to 12.875"
Key Product Components/Construction
DurabilityCornell accordion partitions are designedand constructed to last. Panels are roll-formed from 24 gauge vinyl coated steelinto a corrugated pattern with rolled endbeads for added strength and durability.Panels offer a high level of impact resistance,warding off dents and scratches. Nylonwheel, ball bearing rollers are utilized forquiet, smooth operation and are positionedon every panel for optimum and lastingperformance. Lead and end posts areconstructed of heavy duty extruded aluminum shaped sections.
Field Friendly RepairsAlthough built for lasting performance,Cornell considered ease of service toproducts installed in the field. With theunit in place, one or multiple panels canbe easily replace by removing andreplacing flexible vinyl hinges. Servicesection of track is provided and installedto allow panel section repair or replacementwithout removing the entire unit.
Cornell Quality WarrantyMaterials are warranted against productdefects and workmanship for a period of24 months from date of shipment.
Smooth Glide OperationNylon wheel, ball bearing rollers attachto every panel and ride in a supportingshaped extruded aluminum track providingoptimum operation of the unit. LargerTranZform Sound units incorporate a stabilizer bar to distribute even forcesacross the entire height of the lead member. Manual push/pull operation is accomplished with minimal effort.
InstallationCornell is very mindful of installationlabor costs and is industry leading inlimiting field installation steps by assembling all that is possible in theirfactory controlled environment. In mostcases, Cornell accordion partitions areeasily installed by a two person crewwithout special equipment.
Cornell ValueWith more than 180 years of experiencewith supplying building products to theconstruction industry, Cornell understandssatisfying customers. From the onset of aproject through the life cycle of the product,Cornell provides an unprecedented valueexperience to their customers.
Design ReviewStacking Requirements - Cornell accordion partitions are
designed to stack at a fraction of their extended width.
Approximate stack space can be calculated as follows:
TranZform Space stack area = 1 3/4” per foot of width+5 1/2”
TranZform Sound stack area = 2” per foot of width+7”
(Note: for Sound units above 12’ high or 30’ wide,
minimum stack area is 43” per stacking area)
Hang Weight - Cornell accordion partitions are designed
with the perfect balance of materials for minimal hang
weight, ease of operation and optimal durability.
TranZform Space units have an approximate hang weight
of 1.9 pounds per square foot and TranZform Sound units
are approximately 4.5 pounds per square foot, extended
positions.
Performance Ratings & Code Compliance -
TranZform partitions Surface Burning Characteristics per
ASTM E 84 have a Flame Spread Index of less than 20
and a Smoke Developed Index of less than 60. TranZform
Space units are STC 30 rated per ASTM E 90, Sound units
are STC 45.
The Cornell
SAFE AND SECURE
Crestwood Industrial Park, Mountaintop, PA 18707800.233.8366 • 570.474.6773 • Fax: 800.526.0841 • Email: [email protected]
www.cornel l i ron.com
Competitive Points of Difference+ Do not utilize a pantograph style frame system - no
internal parts to break or get damaged by impact.
+ Every panel is track supported by a smooth glide
nylon wheel, ball bearing roller assembly.
+ Modular construction allows for simple, in-place cost
effective installation and service.
+ Quality Components: Heavy duty roller with steel
hanger pin assembly, mechanically secured hinges
and drive chain configuration all ensure long life.
+ Corrugated steel panels add strength and durability.
Sound and Space units are coated with a scratch
resistant, permanently bonded decorative vinyl finish.
+ TranZform partitions are installed by Cornell’s
national network of over 250 distributors.
Practical Product
Advantage
SOUND & SPACE continued
ApplicationsUse TranZform Sound and Space units
whenever there is a need for flexibility of
building space. Quickly “transform” a large
room into two or more independent spaces
as desired or use for off hour pedestrian
control.
+ Religious facilities
+ Educational & Government facilities
+ Community centers
+ Healthcare facilities
+ Hotel multi-function rooms
+ Conference centers
+ Airports
+ Museums
+ Public and private office buildings
+ Theaters
An ISO 9001:2000 Registered Company
© Cornell Iron Works, Inc. Rev. 8.009
Tab 1 – Section 1
TranZform® Fire
+ Fail-safe emergency response capability. When an alarm is activated, TranZform Fire closes automatically
to prevent the spread of fire and smoke, even in the event of a power failure.
+ Emergency Exit Hardware, provided as standard, allows units to be used in openings that are part of a
required means of egress. High temperature sensors prevent the unit from opening when a dangerous
condition exists on the other side.
+ ADA Compliance: TranZform Fire units comply with the American with Disabilities Act accessibility standards.
+ UL Classified 3, 1 1/2, 1, 3/4, 1/2, 1/3 hour labels and UL "S" label for smoke and draft control available.
cUL Listing. Factory Mutual Approval Listing. IBC® compliant as per ICC-ES ESR-2300.CSFM Listing. STC 41.
+ Less Headroom Clearance Required than Rolling Fire Doors. TranZform Fire also requires no floor track.
+ For use in openings that are part of a required means of egress.
+ Design Flexibility: Single Slide or Bi-Parting Construction. Curved Track Construction available.
+ Quality Components: Heavy duty roller with steel hanger pin assembly, mechanically secured hinges and
drive chain configuration all ensure long life and allow for simple, cost effective service.
Designed to provide automatic closing in the event of fire detection, TranZform Fire units are rated physical fire barriers
that protect openings from the spread of fire and smoke. TranZform Fire units can be used in openings that are part of a
required means of egress. Its double wall panel design requires minimal headroom and features fire retardant, flexible
header and floor seals attached to the top and bottom of the panels to protect against the passage of air and smoke. Up
to 3 hour UL fire rating, UL “S” label smoke rating and FM ratings are available. IBC® compliant as per ICC-ES ESR-2300.
Clearly marked Emergency Egress Hardware standard; compliant with the American with Disabilities Act accessibility standards.
Applications+ Egress path openings requiring building
code compliant emergency egress
+ elevator lobbies
+ horizontal exits
+ opening protectives in fire rated
corridors
+ An alternative to banks of fire rated
swing doors where maintaining the
use of the full opening width for
functionality and aesthetics is desired.
+ atriums + casinos
+ hotels and conference centers
+ Openings with minimal headroom
requiring rated fire, smoke or ADA
compliant fire protection
+ Stage Proscenium Openings
SAFE AND SECURE
Practical Design
Model ERP10
Features and BenefitsOther Available
TranZform Fire Ratings+ UL Classified 3, 1 1/2, 1, 3/4, 1/2,
1/3 HR & “S” labels. cUL Listing.
+ Factory Mutual Approval Listing.
+ IBC® compliant as per ICC-ES ESR-2300.
+ Compliance with the American with
Disabilities Act accessibility standards.
+ Acceptable for use in openings that
are part of a required means of egress.
+ CA State Fire Marshal (CSFM) Listing.
+ STC 41.
OperationFail-safe emergency response
capability. When an alarm is activated,
TranZform Fire closes automatically to
prevent the spread of fire and smoke. In
emergency mode, pressure on the vertical
exit bar causes door to open 54”, pause
for 3 seconds, then automatically close.
Closing fire doors can also be opened
manually by pushing against the leading
sensing edge.
TranZform Fire Hang WeightApprox. 5.5 lbs. per ft2., extended.
TranZform Fire Stack Depth1/4 HP operator (up to 100 sq.ft.): 2.1” per
foot of opening width plus 22”. 1/2 HP
operator: 2.1” per foot of opening width
plus 30”. For units over 16’ high and
when clearance is critical consult factory.
Standard Features+ Intelligent automatic operation
+ Cornell electric motor operator
+ Leading Sensing Edge
+ Openings 3’ 6” to 22’ H to a max. of
1440 square feet.
Product Options+ Single Slide or Bi-Parting
Construction
+ Curved track construction
+ Non-sway construction
+ Vision Window
+ Pocket Door(s) by Cornell
+ Finish colors: consult factory for
powder coat color options
Full Line Product FamilyAlso available: STC 45 TranZform®
Sound provides unparalleled sound
control, TranZform® Space provides
convenient space separation and security.
Crestwood Industrial Park
Mountaintop, PA 18707
TEL 800.233.8366
FAX 800.526.0841
Architect & Design Support: Ext. 551
Website: www.cornelliron.com
Email: [email protected]
TranZform® Fire Components
Head Detail Plan View
An ISO 9001:2000 Registered Company
Mounting & Clearances(Straight Track Design Shown)
TranZform Fire Doors are built to order to fit openings from 3’ 6” to 22’ high to a maximum of 1440
square feet, standard construction.
Patent review pending.
1'6"
4 1/4"Pocket Depth Clear
Opening
Floating Jamb Exit Hardware Pocket Door
by others
Floating JambStop
Track by
Cornell
3 1/4"
53/4"
1' 6"
Motor
Drive Assembly
by Cornell
3 layers 1/2" x 3 5/8"
x cont. type x fire rated
gypsum board by others
2 layers 5/8" x 18" x
cont. type x fire rated
gypsum board by others
1/2" dia. threaded rod w/ nuts
& washers by others, 18" o.c.
along opening width,
12" o.c. max. along
stack depth area
3 layers3/4" x 18"x cont. plywoodwith staggeredjoints byothers
53/4"
Lead Post - 24
gauge commercial
grade coated steel
member with material
and finish to match
panels. Lead sensing
edge and full length
interior tubing support
provided standard.
An internally mounted
stabilizer bar support
shall keep the lead
posts vertical and in
proper alignment during
operation and ensure
tight fitting closure of
the door.
Wall Mounted Strike
Post - Recessed 18
gauge coated cold
rolled steel member
that receives the lead
post and is secured to
the wall opposite the
stacked door. Finish
to match wall panels.
Emergency Exit
Hardware - Vertical
exit bar with ADA /
Emergency Egress
instructions provided
as standard, both
sides. Additional exit
bars available on wide
doors.
Motor Operation - Provided as
standard for controlled automatic
closing with emergency exit
capability and ease of testing.
DC 1/4 or 1/2 HP gear-motor,
limit switch control system, drive
sprocket and clutch. Operated
by DC power supplied from two
12-volt maintenance free batteries
located in the electronic control
box. Batteries are continuously
charged by the building’s electrical
service and are automatically
maintained to capacity.
Header and Floor Sweeps -
Continuous, fire retardant
flexible seals in flat black are
attached to the top and bottom
of the panels to eliminate gaps
at the floor and head area for
fire and smoke protection.
Floating Jamb - 18 gauge aluminized steel
floating jamb assembly that travels within
the storage pocket.
Track - Interconnected double rail heavy duty
extruded aluminum or 14 gauge cold rolled
steel track sections on 8” centers to support
and retain the roller assemblies. Track is
supplied with a white baked-on powder
coated finish standard, with mill finish
aluminum a readily available option. Header
support construction is not by Cornell.
Rollers - Each lead post / stabilizer
bar assembly shall be suspended by
a 12 wheel ball bearing trolley system.
Each individual panel is suspended
using a steel hanger pin and
ball bearing roller.
Panels - Continuous length, 4 1/2” wide panels
formed of 24 gauge commercial grade corrugated
coated steel. Coating process includes a flexible
urethane primer followed by a high performance,
medium gloss, baked-on polyester coating in
standard platinum gray color.
Hinges - Continuous length, full
height 24 gauge commercial
grade coated metal hinges
interconnect door panels.
Material and finish to match
panels. Allow for simple panel
installation and replacement.
PUSH
PUSH
PUSH
TO
EXIT
Recessed Striker
4 1/8"
OperatorControlBox
© Rev. 9.009 Cornell Iron WorksPrinted with Pride in the USA
50% Recycled Paper
Rev. 1
1 / 2.1 Cornell Iron Works
TRANZFORM® Fire - Assembly Drawing
Panels
Lead Post
Wall MountedStrike Post
Rollers
Floor Sweep
HeaderSweep
Hinges
SAFE AND SECURE
Track
PUSH
PUSH
PUSHTOEXIT
MotorOperation
Floating JambEmergencyExit Hardware
Rev. 1
1 / 3.1 © Cornell Iron Works
TranZform® Fire Design Applications: Product Applications Overview TranZform Fire is ideal at openings where a fire and/or smoke rating is required and:
• Egress is required but fire rated swinging man doors are not practical or aesthetically appealing. • A curved opening is required and the opening construction does not permit installation of fire
rated coiling doors or the use of coiling doors is not aesthetically appealing.
TranZform Fire System Advantages: • All units provide UL / FM labeled fire and smoke protection • Minimal headroom and no floor track required • Can accommodate curved openings • Use in lieu of banks of rated swing doors to:
a. Increase emergency exit opening widths b. Eliminate visual barriers c. Maintain the spaciousness of the facility
• Allows maximization of elevator lobby openings allowing guest a clear view of the elevators as compared to swing doors with frames
• Eliminates minimum encroachment requirements of swing doors into floor level corridors • TranZform’s ability to span wide openings in areas such as convention centers, transportation
facilities and casinos allows for free flow of the general public with the capability of providing emergency separation protection as needed.
• Use in atriums as an alternative to a complying sprinkler and smoke removal system. • Emergency egress hardware allows units to comply with the Americans with Disabilities Act.
Common Applications: (Relevant 2006 IBC® sections shown in parenthesis)
• Elevator Lobbies (IBC 707.14.1) • Elevator and Vertical Shaft Opening Enclosures (IBC 707) • Cross Corridor, Emergency Egress Exits (IBC 715.4.3, 1017) • Fire & Smoke Rated Corridor Wall Openings (IBC 715) • Required Smoke Barrier Openings (IBC 709) • Atriums (IBC 404.5) • Stage Proscenium Openings (IBC 410.3.5) • Large Opening Area Separation – such as airport terminals, casinos & convention centers (IBC 1022)
Additional Applications for TranZform Fire: • Underground buildings where openings are required to be smoke barriers. Generally low
headroom conditions in which TranZform Fire units work well. • Facilities with Mixed Use and Occupancy • Incidental Use Areas within Buildings (for example, boiler rooms) • When Smoke Barriers are required to sub-divide each building story into at least two
compartments • Buildings requiring an Area of Refuge – require an accessible means of egress and smoke
barrier protection.
Rev. 1
1 / 4.1 © Cornell Iron Works
TranZform® Fire Frequently Asked Questions: What is the standard labeling size of TranZform Fire? TranZform Fire’s test size is 11’0” wide x 9’-0” high, and will include both UL and FM labels. This dimension was determined by test oven size and the maximum unit size able to be tested on it. By testing the maximum size possible, Cornell is also able to provide larger TranZform Fire units with UL and FM Oversize Construction classification labels. What is TranZform Fire’s maximum approved opening size? UL procedure allows UL Oversize Construction classification for units to product limits: from 3’ 6" to 22’ Hign to a maximum of 1600 square feet, standard construction. Does TranZform Fire provide high temperature override of the egress hardware, as defined in the building codes and NFPA 80? Yes. TranZform Fire has sensors that will lock out operation of the egress hardware if the temperature exceeds 500° F on either side of the opening. Is TranZform’s battery system monitored and does it provide a low battery warning signal? Yes. TranZform Fire continuously monitors the voltage level of its batteries and displays it on the front of the control box panel. An audible low battery warning signal is transmitted whenever the battery voltage drops below a desirable level. There is also a terminal connection at the operator if the owner desires to include an external monitoring device. In addition, a load test is performed every 30 hours to simulate running the door on battery power. Does TranZform Fire offer an optical eye path obstruction detector? No. Such a device could not be used on units that incorporate a curved track and would not be fool-proof. The sensing beam projects across a straight path and may not detect a chair, table edge or any object obstructing the path that is not directly in the beam. Mounting such a device with pocket doors that are normally closed is also problematic. Instead, Cornell recommends routine operation of the door, which will detect obstructions in the opening as well as confirm the proper operation of the life safety devices. To facilitate this, TranZform’s controller has an available option to automatically cycle the door once a day at a selected time. The door would then stop at any obstruction left in the opening to alert the building’s occupants or owner. Can TranZform Fire be powder coated? Yes. Why can’t the door have a vinyl cover? Not tested per UL procedure. Panels and hinges may bind up. During what part of travel is the sensing edge active? Inactive for the first 12” to 18” out of the pocket (preset at 12”, but adjustable to 18”) and the last 1”-2” of travel as the door closes into striker channel. Will it push a pocket door open before it activates and stops? Yes. What is the expected battery life before they require replacement? 1 1/2 - 2 years with normal operation. What is the battery cost? Approximate cost is $35 each. Two standard 12vDC batteries are required, but should be rated to 18v. Can be purchased off the shelf trough Grainger, Friedman Electric, etc.
Rev. 1
1 / 4.2 © Cornell Iron Works
CanTranZform Fire units be used daily for security? Yes. Operators include a “Security Mode” that locks out the egress hardware functionality until the unit is activated by alarm. What is the closing rate of the door? Approximately 9” per second for single pocket units, 6” per second per side for bi-parting units.
Rev. 1
1 / 5.1 © Cornell Iron Works
TranZform® Fire Ratings Information: Cornell TranZform Fire doors have been through rigorous internal and third party testing and are compliant with all current life safety and building codes. In addition, Cornell products are backed by a 180+ year old company that has been providing UL Classified fire and life safety building products for over eighty years. Per UL file number R25122, TranZform Fire Doors were tested and provide UL labels documenting their classification for fire resistance per UL 10B and for smoke and draft control per UL 1784. Other Potential Documentation Requests UL Operator Listing The TranZform Fire operator is listed per UL 325 and the door is UL tested per UL 10B, UL file number R25122. UL Operator Listing Per UL 864 UL 864 only applies to “Control Units and Accessories for Fire Alarm Systems” and is not appropriate for systems that do not send signals to the fire alarm system. As directed by Underwriter Laboratories, TranZform Fire’s operator has been listed under UL 325 - “Door, Drapery, Gate, Louver, and Window Operators and Systems.” Any products claiming to be equal should also provide the UL 325 listing. I.C.B.O. Research Report The I.C.B.O. evaluation service no longer exists and it is not possible to obtain a report from them. With the consolidation of several building codes into the International Building Code, the International Code Council Evaluation Services (ICC-ES) has taken over its function. When utilizing old I.C.B.O. reports, it is important to ensure that the version of the product being provided today is consistent with the product tested at that time. ICC-ES Evaluation Report ICC-ES exists to evaluate and provide guidance for products that are not specifically addressed by building codes. Since the criteria for horizontal sliding fire doors for use in a means of egress is clearly identified in the current building codes listed below, a “code exception” is not required for TranZform Fire. TranZform Fire has been evaluated by ICC-ES to be compliant for use in means of egress openings per the International Building Code®, Report ICC-ES ESR 2300. Cornell’s TranZform Fire complies with: • 2006 International Building Code section 1008.1.3.3 – Horizontal sliding doors • 2009 NFPA 101-Life Safety Code section 7.2.1.14 – Horizontal-Sliding Door Assemblies • 2007 NFPA 80 chapter 9 – Special Purpose Horizontal Sliding Accordion or Folding Doors • 1997 Uniform Building Code Standard 7-8 – Horizontal Sliding Fire Doors Used In An Exit Performance Testing As stated above, TranZform Fire complies with the established building code requirements for horizontal sliding doors. To ensure compliance with NFPA 80, Cornell encourages that the Authority Having Jurisdiction (AHJ) witness a field test of the actual installed doors. Cornell believes that validating the performance of each unit in this manner is superior to testing one particular configuration in a laboratory environment.
Rev. 1
1 / 5.2 © Cornell Iron Works
TranZform® Fire Code Overview International Building Code® (IBC) Means of Egress – Section 1008.1.3.3 of the IBC lists the requirements for Horizontal Sliding Doors for use in place of side-hinged swinging doors in a means of egress. Please note that Cornell’s TranZform Fire doors comply with these code requirements. The code section is written as follows: 1008.1.3.3 Horizontal sliding doors. In other than group H occupancies, horizontal sliding doors permitted to be a component of a means of egress in accordance with Exception 6 to Section 1008.1.2 shall comply with all of the following criteria:
1. The doors shall be power operated and shall be capable of being operated manually in the event of a power failure.
2. The doors shall be openable by a simple method from both sides without special knowledge or effort.
3. The force required to operate the door shall not exceed 30 lbs. (133 N) to set the door in motion and 15 lbs. (67 N) to close the door or open it to the minimum required width.
4. The door shall be openable with a force not to exceed 15 lbs. (67 N) when a force of 250 pounds (1100 N) is applied perpendicular to the door adjacent to the operating device.
5. The door assembly shall comply with the applicable fire protection rating and, where rated, shall be self-closing or automatic closing by smoke detection in accordance with Section 715.4.7.3 (Smoke Activated Doors), shall be installed in accordance with NFPA 80 and shall comply with Section 715 (Opening Protectives).
6. The door assembly shall have an integrated standby power supply. 7. The door assembly power supply shall be electrically supervised. 8. The door shall open to the minimum required width within 10 seconds after activation of the
operating device. NFPA 80 – Standard for Fire Doors and Other Opening Protectives TranZform Fire Doors are required to comply with the General Provisions of NFPA 80 and as specifically outlined in NFPA 80 Chapter 9 – Special Purpose Horizontal Sliding Accordion or Folding Doors. Highlights include:
• Doors shall be automatic closing and shall not have a delay in the initiation of closing or reclosing of more than 10 seconds.
• Average closing speed shall be between 6” and 24” per second. • Standby or emergency power shall be provided • Power operated opening shall not occur if the temperature on either side of the door
reaches 500° F (260° C) • Fire door assemblies shall be inspected and tested not less than annually and a written
record shall be signed and kept for inspection by the AHJ • Where a fire door is damaged to the extent that it could impair the door’s proper emergency
function, the door shall be repaired with parts obtained from the door’s original manufacturer and then the door shall be tested to ensure proper emergency operation.
Rev. 1
1 / 5.3 © Cornell Iron Works
UL Listing Information – TranZform® Fire Accordion Folding Fire Doors Underwriters Laboratories, Inc. (UL) is the leading third-party product safety certification organization in North America. UL evaluates product samples to requirements in areas such as performance, environmental and public health, and electromagnetic compatibility. The UL Listing Mark is used in connection with products that have been evaluated by UL and found to be in compliance with UL’s requirements. Cornell’s TranZform Fire Accordion Folding Fire Doors products have been UL classified and are listed under the following UL Product Category and Control Number: Special Purpose Type Fire Doors – GSXZ UL File Number: R25122 Ratings: 3 HR, 1-1/2 HR, 1 HR, 3/4 HR, 1/2 HR, 20 minute Sizes: Classified for openings up to 11’0”W x 9’0”H. Doors 23’H x virtually unlimited width are eligible for Oversize Construction labeling. Cornell TranZform Fire Accordion Folding Fire Doors with UL “S” Label TranZform Fire Accordion Folding Fire Doors have been UL classified and are listed under the UL Product Category and Control Number: Leakage Rated Door Assemblies –OPBW UL File Number: R25122. See product listing above for details. Ratings: UL “S” label for smoke and draft control. Sizes: Classified for openings to product size limits. See product listing above for details For more detailed UL information, visit the Underwriter’s Laboratory website at www.ul.com
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 3261-0550:0107 Page 1 of 1
CATEGORY: 3261 -- FOLDING DOOR (FIRE-RATED)
LISTEE: CORNELL IRON WORKS INC, 24 Elmwood Ave, Crestwood Industrial Park, Mountaintop, PA 18707
Contact: Jim Dever (570) 474-6773 Fax (570) 715-0492
Email: [email protected]
DESIGN: TranZform Fire Model ERP10 folding accordion door. Refer to listee's data sheet for
detailed product description and operational considerations.
RATING:
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, fire rating and UL label.
APPROVAL: Listed as 1/3 hour, ½ hour, ¾ hour, 1 hour, 1 ½ hour, and 3 hour fire-rated interior
automatic-closing horizontal folding doors. Authority having jurisdiction should be consulted
prior to installation. Opening size not to exceed 9 feet high and 11 feet wide.
Doors exceeding the above limits are considered oversize construction and are based
upon , and is similar to, the approval product design, but they have not been subject to
approval testing due to test facility limitations. Acceptance of these doors is the prerogative
of the authority having jurisdiction.
NOTE:
*Rev 5-7-09 MA
July 01, 2010
FRANCIS MATEO, Program Coordinator
Date Issued: Listing Expires June 30, 2011
Authorized By:
Fire Engineering Division
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria. Refer to listee’s data sheet, installation instructions and/or other suitable
information sources.
SAFE AND SECURE
Rev. 1© Cornell Iron Works 1 / 6.8
TranZform® Fire Pocket Cover Door Guidelines
Although pocket cover doors are not required, they are commonly used to conceal stacked Cornell TranZform Fire units. Cornell offers powder coated 12 gauge steel pocket cover doors for openings up to 12' in height, or pocket cover doors can be provided by others. Unless specifically required bythe "Authority Having Jurisdiction", pocket cover doors do not have to be fire-rated. The door thickness and covering material is at the discretion of thedesigner. Many different cover materials have been successfully used for pocket cover doors by others including the following: plastic laminates, woodveneers, vinyl, paint, bronze, and stainless steel. However, if the aggregate thickness of the pocket door exceeds 2", the additional thickness must beadded to the calculation of the pocket depth.
Some basic criteria for the successful design of the pocket cover doors are listed below:1. Doors must be side hinge swinging and must swing at least ninety (90) degrees. When in the open position, pocket doors may not encroach on the
18" clear minimum opening width required for the pocket. Designing "notches" on either side of the pocket to accommodate the cover door thicknesswill prevent this (see Pocket Cover Door Details).
2. Pocket cover doors must be operable with less than 50 lbs. of lateral force. As the Cornell TranZform Fire Door is activated, the leading edge willmake contact with cover door and push it open. Fifty (50) lbs. is the normal operating force required for egress-style swinging doors and only if thecover door is unusually heavy would special considerations need to be taken.
3. When activated, pocket doors should remain in the open position so as not to obstruct the path of the TranZform Fire door when it is closing.
Cornell recommends specifying either (1) a spring-action hinge such as the Stanley # 422100 (with reversed spring-action) to hold the cover door openwhen activated, or (2) a continuous hinge such as a Stanley #314 or a full mortise hinge like the Stanley # 050490.
(1) The reversed spring-action of the Stanley # 422100 butt hinge makes the cover door self-opening rather than self-closing. (2) For aesthetic considerations, a continuous hinge is recommended because it does not protrude beyond the face of the pocket cover door and
therefore presents a "hingeless" appearance. A full mortise hinge can also be used. Both the continuous hinge and the full mortise hingesrequire the use of a bumper, which prevents the pocket door from swinging back into the operating path of the TranZform Fire door. Cornellpocket cover doors include bumpers as shown on drawing 1 / 6.7.1. The recommended bumper design for Pocket Covers by Others is shownon drawing 1 / 6.7. Note that his bumper adds 1" to the pocket depth requirement.
4. A magnetic catch not to exceed thirty (30) lbs. can be used to keep the pocket cover doors in the closed position when the Cornell TranZform Firedoor is not in use. Positive latches such as hooks or throw bolts are not permitted because they prevent the Cornell TranZform Fire door from pushing the cover door open during operation.
5. A door frame is not required although one may be used. However, for aesthetic considerations, a "frame-less" design may be preferable because itleaves only two (2) slight reveals at the door edges and provides a less noticeable pocket cover door installation.
SAFE AND SECURE
Rev. 1© Cornell Iron Works 1 / 6.10
TranZform® Fire Electrical Coordination
Installer Requirements:• Mount operator and Control Box• Mount Control Station• Run wires and make connections at control box for Leading Sensing
Edge, Emergency Exit Hartware & High Temperature Limit Sensor
Electrical Contractor Requirements:• Mount two 4" x 4" J-boxes, back of pocket, 12" up from floor• Conduit / 120 VAC wiring to J-box & control box• Conduit / wiring from other J-box to control box, wall mounted control
station, and alarm signaling device.
TranZform Fire Sequence of Operation
Normal Operation and AC power is available. Security mode not selected.
1. Capable of daily operation2. Normal open / close operation via surface mounted three function con-
trol station provided as standard. Open and Close require constantpressure to maintain door motion. Stop button will stop door move-ment.
3. The Leading Sensing Edge stops door motion. Sensing edge also dis-engages clutch so door can be manually pushed in the opening direc-tion when sensing edge is compressed.
4. Emergency Exit Hardware on both sides will open a closed door. Dooropens the preset distance and remains open.
Normal Operation and AC power is available. Security mode is selected.
1. All functions of "Normal Operation" except: Emergency Exit Hardwarewill not open a closed door when not in alarm mode.
Normal Operation and AC power is NOT available. Both in Security modeand not in Security mode.
1. Door operation is the same as when AC power is available.2. Green AC power light on control box cover goes off. ( cannot be seen
outside of pocket)3. Monitoring signal (24vdc signal) activates. Monitoring device must be
provided by end user.
Monitoring contacts.
1. Monitoring connection points are provided at terminal strip so that enduser can monitor door position.
Alarm Condition. AC power available or No AC power.
1. Door is signaled to close automatically upon alarm signal. 2. Leading Sensing edge will stop on any object in opening. When object
is removed door will continue closing until it reaches full closed posi-tion.
3. Emergency Exit Hardware on both sides of the door will open the doorto the preset distance. Minimum opening is 54 inches.
4. Repeated activation of the Emergency Exit Hardware bar will open thedoor a second preset distance. (cumulative operation ). Also note thatpushing on sensing edge disengages clutch. Door can be pushed openif you push on sensing edge.
5. Emergency Exit Hardware bar functions as above even if securitymode was selected for normal operation.
6. After door has opened the preset distance it will pause for 2 secondsand then re-close. (Pause time is adjustable to 10 seconds.)
7. A high limit sensor will prevent Emergency Exit Hardware activation ifthe temperature at the door reaches 450° F.
8. 24 VDC signal is available.
Doc 11.009 08 11 73-1
SECTION 08352 or MasterFormat 2004™ SECTION 08 11 73
CORNELL TRANZFORM® FIRE
HORIZONTAL SLIDING, ACCORDION FOLDING FIRE & SMOKE RATED DOORS
GENERAL NOTES TO SPECIFIER: THIS SPECIFICATION SECTION HAS BEEN PREPARED TO ASSIST DESIGN PROFESSIONALS IN THE PREPARATION OF PROJECT OR OFFICE MASTER SPECIFICATIONS. IT FOLLOWS GUIDELINES ESTABLISHED BY THE CONSTRUCTION SPECIFICATIONS INSTITUTE, AND THEREFORE MAY BE USED WITH MOST MASTER SPECIFICATION SYSTEMS WITH MINOR EDITING. EDIT CAREFULLY TO SUIT PROJECT REQUIREMENTS. MODIFY AS NECESSARY AND DELETE ITEMS THAT ARE NOT APPLICABLE. VERIFY THAT REFERENCED SECTION NUMBERS AND TITLES ARE CORRECT. (NUMBERS AND TITLES REFERENCED ARE BASED ON MASTERFORMAT™, 2004 EDITION). THIS SECTION ASSUMES THE PROJECT MANUAL WILL CONTAIN COMPLETE DIVISION 01 DOCUMENTS INCLUDING SECTIONS 01 33 00 SUBMITTAL PROCEDURES, 01 62 00 PRODUCT OPTIONS, 01 25 13 PRODUCT SUBSTITUTION PROCEDURES, 01 66 00 PRODUCT STORAGE AND HANDLING REQUIREMENTS, 01 77 00 CLOSEOUT PROCEDURES, AND 01 78 00 CLOSEOUT SUBMITTALS. IF THE PROJECT MANUAL DOES NOT CONTAIN THESE SECTIONS, ADDITIONAL INFORMATION SHOULD BE INCLUDED UNDER THE APPROPRIATE ARTICLES. THIS IS AN OPEN PROPRIETARY SPECIFICATION ALLOWING USERS THE OPTION OF APPROVING OTHER MANUFACTURERS THAT COMPLY WITH THE CRITERIA SPECIFIED HEREIN. NOTES TO THE SPECIFIER ARE CONTAINED IN BOXES AND SHOULD BE DELETED FROM FINAL COPY. OPTIONAL ITEMS REQUIRING SELECTION BY THE SPECIFIER ARE ENCLOSED WITHIN BRACKETS, E.G.: [35] [40] [45]. IN CASES WHERE ONE OF THE OPTIONAL ITEMS IS A STANDARD FEATURE OF THE CLOSURE MODEL, IT IS LISTED IN THE FIRST POSITION. MAKE APPROPRIATE SELECTION AND DELETE OTHERS. ITEMS REQUIRING ADDITIONAL INFORMATION ARE UNDERLINED, E.G.: ___________ . OPTIONAL PARAGRAPHS ARE SEPARATED BY A REDLINED "OR" E.G.:
OR
PART 1 GENERAL 1.1 SUMMARY A. Section Includes: Metal, electrically operated, horizontal sliding, accordion folding fire
doors with UL and FM Fire and SmokeShield® leakage rated assembly labels. B. Related Sections: 1. 05 50 00 Metal Fabrications. Structural support for track. 2. 06 10 00 Rough Carpentry: All headers, support structures, jambs, field painting,
blocking, trim and pockets shall be furnished and installed by others. 3. 08 31 00 Access Doors and Panels. 4. 08 70 00 Hardware. 5. 09 91 00 Painting - Field painting of all door panels, lead posts, track, soffit, chain
guide and wall mounted striker posts.
Doc 11.009 08 11 73-2
6. Division 26. Electrical wiring and conduit, fuses, disconnect switches, connection of operator to power supply, installation of control station and wiring, and connection to alarm systems.
1.2 SYSTEM DESCRIPTION A. Performance Requirements: 1. Provide doors with Underwriters' Laboratories, Inc. and Factory Mutual labels for the
fire rating classification, [3 hr] [1 1/2 hr] [1 hr] [3/4 hr] [1/2 hr] [20 minutes]. 2. Provide doors with Underwriters' Laboratories, Inc. and Factory Mutual labels for
“Leakage Rated Assembly” or “S” label. a. Comply with NFPA 105 air leakage requirements.
b. Fire doors shall have air leakage of less than 3 cubic feet per square foot at 0.1 inch of water column pressure when tested in accordance with UL 1784 with an artificial bottom seal.
OR b. Fire doors at the point of access to an elevator shall have air leakage of less than
3 cubic feet per square foot at 0.1 inch of water column pressure when tested in accordance with UL 1784 without an artificial bottom seal.
3. Provide horizontal sliding fire doors that are recognized by the International Code Council- Evaluation Services (ICC-ES) as a permitted component in a means of egress.
4. Horizontal sliding fire door operating systems are to be listed as a complete assembly per UL325.
5. IAS Testing Laboratory to provide proof of testing to the performance requirements of the IBC, NFPA 80 and to the requirements for electrical installations per the NEC.
6. IAS Testing Laboratory to provide proof of successful product endurance testing of not less than 10,000 complete close/open cycles of a unit installed in accordance with required field conditions that covers an opening of not less than 25’ wide and 8’ high.
1.3 SUBMITTALS A. Reference Section 01 33 00 Submittal Procedures; submit the following items: 1. Product Data. 2. Shop Drawings: Show interface with adjacent work. Indicate required stacking depth,
pocket width, and height from finished floor to bottom side of header. Show installation details and layout.
3. Quality Assurance/Control Submittals: a. Product to be labeled with ICC-ES evaluation report number as a permitted
component in a means of egress. b. Provide proof of manufacturer ISO 9001:2000 registration. c. Provide manufacturer's installation instructions. 4. Closeout Submittals: a. Operation and Maintenance Manual. b. Certificate stating that installed materials comply with this specification. 1.4 QUALITY ASSURANCE A. Manufacturer Qualifications: ISO 9001:2000 registered and a minimum of five years
experience in producing fire and smoke control products.
Doc 11.009 08 11 73-3
B. Installation shall be performed by manufacturer trained or authorized personnel according to manufacturer’s installation instructions.
C. Fire doors shall be listed by Underwriters Laboratories and Factory Mutual for ratings as
indicated, when tested in accordance with the requirements of UL 10B & ASTM E-2074. D. Fire door operating systems are to be listed as a complete assembly per UL325. 1.5 DELIVERY, STORAGE AND HANDLING A. Deliver to the job site in manufacturer’s original, unopened package. B. Reference Section 01 66 00 Product Storage and Handling Requirements. C. Follow manufacturer's instructions. 1.6 COORDINATION BY GENERAL CONTRACTOR A. Coordinate the efforts of the various trades affected by the work of this section. Assure
accurate installation of header, jamb, and trim. Provide field dimensions for fabrication. Supervise unloading and handling of materials.
B. Permanent power shall be in-place and ready for final connection when fire doors are
erected. Assure access to and proper clearance for motor operators. C. After testing the fire alarm system, automatic-closing fire doors shall be re-set to their
original positions. D. Store boxes flat (not more than three high) in a dry area and protect from elements that
may damage materials. General Contractor to replace damaged materials at no cost to the owner.
1.7 WARRANTY A. Standard Warranty: Two years from date of shipment against defects in material and
workmanship. B. Maintenance: Submit for owner’s consideration and acceptance of an annual testing and
maintenance service agreement for installed products to comply with building code and NFPA 80 requirements.
PART 2 PRODUCTS 2.1 MANUFACTURER A. Manufacturer: Cornell Iron Works, Inc., 24 Elmwood Avenue, Crestwood Industrial
Park, Mountaintop, PA 18707. Telephone: (800) 233-8366, Fax: (800) 526-0841. INSERT NAME, ADDRESS, AND PHONE NUMBERS OF LOCAL DISTRIBUTOR BELOW.
Doc 11.009 08 11 73-4
1. Distributor: B. Model: ERP10 C. Substitutions: Reference Section 01 25 13 Product Substitution Procedures. 2.2 MATERIALS
A. Accordion Folding Fire Door Construction 1. Construction: Shall consist of two parallel, accordion-type walls of panels
independently suspended from an interconnected double rail overhead track with no pantographs or internal connections except at the upright lead post.
2. Door Panels: Each assembly to consist of continuous length, 4 ½” wide panels formed of 24 gauge commercial grade coated steel, corrugated for strength and resilience.
3. Hinges: Continuous length, full height 24 gauge commercial grade coated steel hinges interconnect door panels.
4. Upright Lead Post: Formed of 24 gauge commercial grade coated steel with finish to match door panels. Connect to door panels with specially formed sections. An internally mounted stabilizer bar support shall keep the lead posts vertical and in proper alignment during operation and insure tight fitting closure of the door.
5. Wall Mounted Striker Post: Recessed 18 gauge coated cold rolled steel member that receives the lead post and is secured to the wall opposite the stacked door.
6. Floating Jamb: 18 gauge aluminized steel floating jamb assembly that travels within the storage pocket and forms a seal at the pocket end of the door.
7. Fully assembled and extended unit hanging weight shall be approximately 5.5 pounds per square foot.
B. Suspension System
ALUMINUM TRACK IS AVAILABLE FOR STRAIGHT SLIDING UNITS TO 1 1/2 HOUR MAXIMUM RATING. SELECT FORMED STEEL TRACK WHEN DESIRED, WHEN REQUIRED BY LOCAL CODES AND WHEN CURVED TRACK OR A 3 HOUR RATING IS REQUIRED. A MINIMUM 5’ RADIUS IS REQUIRED FOR ALL CURVED SECTIONS.
1. Track: Interconnected double rail [heavy duty extruded aluminum] [formed steel] track sections on 8” centers for attachment to overhead structural support system. Shape is designed for smooth running operation of the roller assemblies while prohibiting any opportunity for the rollers to derail.
2. Rollers: Each lead post/stabilizer bar assembly shall be suspended by a 12 wheel ball bearing trolley system. Each individual panel shall be suspended using a steel hanger pin and ball bearing roller.
C. Perimeter Seals: Continuous extruded fire-rated sweeps and a fire liner attached to the top
and bottom of the fire door form a smoke and draft seal.
D. Finishes 1. Door panels, hinges and upright posts: Coating process to include a flexible urethane
primer followed by a high performance, medium gloss, baked-on polyester coating [in manufacturer’s standard Platinum Gray color.] [. Color shall be selected from
Doc 11.009 08 11 73-5
manufacturer available optional colors at additional cost and additional production lead-time.]
2. Track: to be supplied [with a white baked-on powder coat finish.] [mill finish aluminum.] [with a color as selected from manufacturer available color options at an additional cost and additional production lead-time.]
3. Perimeter Seals: Flat black. 2.3 OPTIONS FACTORY SUPPLIED POCKET DOORS ARE AN AVAILABLE OPTION WITH ALL SLIDING FIRE DOOR UNITS UP TO 12’ HEIGHT TO TOP OF TRACK. DELETE IF UNIT HEIGHT IS OVER 12’ OR IF FACTORY SUPPLIED POCKET DOORS ARE NOT DESIRED. POCKET DOORS STOP AT UNDERSIDE OF HEADER SOFFIT REVEAL. A. Pocket Door(s): 1. Door a. Material: A36 HR steel b. Thickness: USS 12-gauge c. Finish: Phosphate treatment followed by a light gray baked-on polyester powder
coat; minimum 2.5 mils cured film thickness. OR
c. Finish: Phosphate treatment followed by a baked-on polyester powder coat, [color as selected from manufacturer’s standard color range] [custom color as selected by Architect]; minimum 2.5 mils cured film thickness; ASTM-D-3363 pencil hardness: H or better.
d. Size: Designed to fit 18” pocket width: height to underside of soffit reveal. 2. Frame a. Material: A36 HR steel b. Thickness: USS 12-gauge steel c. Finish: Phosphate treatment followed by a light gray baked-on polyester powder
coat; minimum 2.5 mils cured film thickness. OR
c. Finish: Phosphate treatment followed by a baked-on polyester powder coat, [color as selected from manufacturer’s standard color range] [custom color as selected by Architect]; minimum 2.5 mils cured film thickness; ASTM-D-3363 pencil hardness: H or better.
3. Hinges: 4” reversed spring action type 4. Magnetic catch provided to hold door in closed position. THE FOLLOWING CONSTRUCTION FEATURE IS REQUIRED TO SATISFY UL 1784 TESTING WITHOUT AN ARTIFICIAL BOTTOM SEAL. NOT AVAILABLE FOR UNITS WITH CURVED TRACK. COORDINATE WITH SECTION 1.2-A2b. DELETE SECTION 2.3 OPTION “B” FOR CURVED TRACK UNITS OR IF NOT REQUIRED OR DESIRED.
B. Non-Sway Construction Feature: Provide Fire Door with non-sway construction to limit the amount of curtain deflection due to notable air pressure differential on either side of the Fire Door opening.
2.4 OPERATION
Doc 11.009 08 11 73-6
A. Motor Operator Assembly: Operating systems is to be listed as a complete assembly per UL325 and shall consist of DC gear-motor, limit switch control system, drive sprocket and clutch. The motor shall drive the fire door by means of a chain attached to the stabilizer bar trolley system. Motor operator assembly shall be located within a fire rated enclosure equal to the wall assembly rating. Motors shall be operated by DC power supplied from two (2) 12-volt maintenance-free batteries located in an electronic control box. Batteries shall be continuously charged by the building’s electrical service and be automatically maintained at capacity. Fire doors may be operated manually in either the conventional or emergency mode. Electronic control box shall house the control panel, two (2) 12-volt maintenance-free batteries, power supply charger, and motor control relays. Control system is capable of remote status monitoring and remote operation. The control panel shall initiate a warning signal should any of the following conditions occur: • Loss of AC power. • Low DC battery power. • Overload condition. • High limit temperature switch activation or malfunction. 1. Control Station: Flush mounted, "Open/Close" key switch with "Stop" push button;
NEMA 1B. OR
1. Control Station: Surface mounted, "Open/Close/Stop" push buttons; NEMA 1. OR
1. Control Station: Surface mounted, "Open/Close" key switch with "Stop" push button; NEMA 3R.
B. Leading Sensing Edge: Fire doors shall be equipped with a pressure sensitive, vertical
leading edge such that each contact with an obstruction shall cause the door to stop and pause before attempting to re-close. Fire doors can be manually opened by pushing against the leading edge.
C. Exit Hardware: Shall be located on both sides of the fire door near the leading member.
Slight pressure on the hardware will cause the door to open approximately 54”, pause for three seconds, then automatically close. The system shall be field programmable to allow automatic opening distances up to the entire opening width. The hardware can be used to open the door and move it back into the storage area during non alarm operation of door.
D. Security Control: When activated, the Exit Hardware shall not respond when pressed
unless there is an active emergency signal from the smoke or fire alarm system. The motor operator assembly will provide greater than 250 pounds of resistance to manual forced opening. (Note: At least one key switch will be required to utilize this feature.)
E. Automatic Closing System: Shall consist of an electronic control box, motor operator
assembly and leading sensing edge. Closing system shall be activated by the building’s fire/smoke detection equipment and automatically close the fire doors. For additional protection, if the door is in the closed position and the temperature reaches 470° F on either side of the opening, door mounted high limit sensors will prevent Exit Hardware opening activation.
PART 3 EXECUTION 3.1 EXAMINATION
Doc 11.009 08 11 73-7
A. Examine header substrates upon which the accordion folding metal fire doors will be installed and verify that conditions are in accordance with approved shop drawings. Openings shall be prepared to the dimensions specified and be plumb and level. Header shall be leveled with the finished floor to within +/- 1/4” (.25”) tolerance over the entire length of the opening.
B. Upon inspection of prepared opening, coordinate immediately with responsible entity to
perform corrective work on unsatisfactory substrates and header, floor or sill levels. C. Commencement of work by installer is considered acceptance of substrate. 3.2 INSTALLATION A. Install accordion folding metal fire doors in accordance with manufacturer’s printed
instructions for clearances and attachment. B. Upon completion of the installation, the General Contractor shall protect the fire door
units from damage and replace or repair subsequent damage so that the units are acceptable to the architect, at no additional cost to the owner.
3.3 ADJUSTING A. Following completion of installation, including related work by others, test and adjust
accordion fire doors for ease of operation. 3.4 FIELD QUALITY CONTROL A. Site Test: Test fire doors for normal operation and automatic closing. Coordinate with
building owner representative to witness and sign Automatic Closing Test Form. 3.5 CLEANING A. Clean surfaces soiled by work as recommended by manufacturer. B. Remove surplus materials and debris from the site. 3.6 DEMONSTRATION A. Demonstrate proper operation to Owner's Representative. B. Instruct Owner's Representative in maintenance procedures.
END OF SECTION
Rev. 1
1 / 8.1 © Cornell Iron Works
Accordion Folding Fire Doors - *Budget Installed Prices
TRANZFORM® Fire Based on 1 1/2 hour rated units, straight sliding with stacking at one jamb
and with standard material & finishes. Includes motor and controller.
HEIGHT
8’ – 0” 10’ – 0” 12’ – 0” 14’ – 0”
6' - 0" 14,347 15,006 15,372 16,089
8' - 0" 15,226 16,104 16,631 17,353
10' - 0" 16,104 16,958 17,568 18,105
12' - 0" 16,631 17,568 18,446 19,881
14' - 0" 17,353 18,276 19,061 20,803
16' - 0" 18,271 19,325 20,613 22,136
18' - 0" 20,555 21,521 22,663 24,288
20' - 0" 21,082 22,204 23,717 25,278
22' - 0" 21,901 23,351 24,800 25,927
24’ - 0” 22,487 24,302 25,649 26,645
26’ - 0” 23,092 25,059 26,645 28,865
28’ - 0” 24,595 26,303 27,875 29,173
30’ - 0” 25,181 27,084 28,548 30,232
32' - 0" 25,923 28,109 29,514 31,154
34' - 0" 26,547 28,621 30,363 31,940
36' - 0" 27,055 28,987 31,095 33,204
38' - 0" 28,187 30,134 31,710 34,399
40' - 0" 28,890 31,232 32,794 35,526
*NOTE: Figures shown are national average INSTALLED prices and will vary depending on locality, union labor, door quantity and other factors. Please contact your local Cornell distributor for accurate pricing.
WID
TH
Rev. 1
1 / 8.2 © Cornell Iron Works
Accordion Folding Fire Doors – WEIGHT Chart
TRANZFORM® Fire with standard material & finish components
HEIGHT
8’ – 0” 10’ – 0” 12’ – 0” 14’ – 0”
6' - 0"
316
370
424
478
8' - 0"
388
460
532
604
10' - 0"
460
550
640
730
12' - 0"
532
640
748
856
14' - 0"
604
730
856
982
16' - 0"
676
820
964
1108
18' - 0"
748
910
1072
1234
20' - 0"
820
1000
1180
1360
22' - 0"
892
1090
1288
1486
24’ - 0”
964
1180
1396
1612
26’ - 0”
1036
1270
1504
1738
28’ - 0”
1108
1360
1612
1864
30’ - 0”
1180
1450
1720
1990
32' - 0"
1252
1540
1828
2116
34' - 0"
1324
1630
1936
2242
36' - 0"
1396
1720
2044
2368
38' - 0"
1468
1810
2152
2494
40' - 0"
1540
1900
2260
2620 Includes Motor Operator and Controller.
WID
TH
Section 2
Accordion Folding Partitions
®
Cornell goes to extremes to provide finished products that will satisfy their customers for the long run.
In addition to delivering products that are durable, easy to operate and maintain, overall aesthetics is
equally important. Along with an array of available wall panel finish options, Cornell is diligent on having
the colored vinyl connecting hinges and powder coated upright members compliment the customer selected
panel finish. Top and bottom sweep seals are provided in neutral flat black to compliment all panel finishes.
Wall Panel OptionsTranZform Space Model ESP10, TranZform Sound Model ESP20
Custom Finished Wall Panels to match a custom provided finish are available, but will extend the project lead time and add cost to the project. Consult factory for details.
Steel Gray - Embossed Leather Dark Oak - Wood Grain
Vanilla Cream - Embossed Leather Antique Blue - Embossed Weave
Blush - Embossed Weave Almond - Embossed Weave
Driftwood - Embossed Weave Colonial Green - Embossed Weave
Rouge - Embossed Weave Granite Gray - Embossed Weave
Light Oak - Wood Grain Matte Black - Granular
Sto
ck F
inis
hes
Read
ily A
vailab
le F
inis
hes
(Exte
nde
d lead t
ime -
no a
dded c
ost)
SPACE & SOUND
SAFE AND SECURE
Crestwood Industrial Park • Mountain Top, PA 18707
Tel. 800.233.8366 • Fax 800.526.0841
www.cornelliron.com
An ISO 9001:2000 Registered Company
© Rev. 11.007 Cornell Iron Works, Inc.
Track - Heavy duty extruded
aluminum shape or formed steel.
Supplied with a white baked-on
powder coat finish as standard. Mill
finish aluminum and brown powder
coat are readily available options.
Consult factory for optional colors.
Header and Floor Sweeps -
Flexible extruded vinyl seals in
flat black.
Sound Blocker Lining (TranZform Sound units only) - Interior
panel surfaces.
Rollers - Panels fitted with nylon wheel, ball bearing roller.
Lead posts are fitted with heavy duty trolleys that have
multiple sets of dual rollers.
Lead Post - Heavy duty extruded aluminum
shapes with powder coated finish to
compliment wall panels.
Wall Mounted Strike Post (shown) /
+ Panel Finish
+ Single Slide or Bi-Parting
Construction
+ Header Trim and Track Types
including Steel and Curved Track
+ Cylinder Locking at Lead Post
+ Fixed or Floating Jamb Construction
Bi-Parting Post available -
Heavy duty extruded aluminum
shapes with hook bolt strike.
Baked-on powder coated finish
to compliment wall panels.
Panels - Continuous roll
formed corrugated steel for
strength. Customer selected
permanently bonded vinyl
finish allows personalization.
Vinyl is laminated to steel prior
to forming the panels. Space
units feature vinyl finish public
side standard, vinyl both sides
optional.
Hinges - Full height extruded
vinyl hinges are color matched
to compliment wall panels.
Product Options
Key Product Components/Features
Cornell side folding accordion partitions quickly, easily and cost effectively transform
a large room into two or more independent spaces in religious, hospitality, health care and other multi-use facilities,
maximizing the use of building space. Available for openings of virtually any width, from 3’ 6” high to 22’ high for
Sound units and to 14’ high for Space units.
Fire ResistanceTranZform Space: The accordion
folding door material and finish
shall achieve a Flame Spread
Index less of not more than 15
and a Smoke Developed Index of
not more than 50 when tested in
accordance with ASTM E84.
TranZform Sound: The accordion
folding door material and finish
shall achieve a Flame Spread
Index of not more than 20 and a
Smoke Developed Index of not
more than 60 when tested in
accordance with ASTM E84.
TranZform Sound unit shown, TranZform Space units similar, but are single wall construction. UL Classified TranZform Fire available: consult factory.
® SPACE & SOUND
Section 2
TranZform® Sound
Rev. 1
2 / 1.1 Cornell Iron Works
TRANZFORM® Sound - Assembly Drawing
SAFE AND SECURE
Sound Blocker Lining
Panels
Lead Post
Strike Post / Bi-Parting Post
Rollers
Floor Sweep
HeaderSweep
Hinges
Track
Doc 100710 22 26.13-1
SECTION 10650 orMasterFormat 2004 SECTION 10 22 26.13
TRANZFORM® SOUNDACCORDION FOLDING PARTITIONS, WALLS OR DOORS
GENERAL NOTES TO SPECIFIER:
THIS SPECIFICATION SECTION HAS BEEN PREPARED TO ASSIST DESIGN PROFESSIONALS IN THE PREPARATION OFPROJECT OR OFFICE MASTER SPECIFICATIONS. IT FOLLOWS GUIDELINES ESTABLISHED BY THE CONSTRUCTIONSPECIFICATIONS INSTITUTE, AND THEREFORE MAY BE USED WITH MOST MASTER SPECIFICATION SYSTEMS WITH MINOREDITING.
EDIT CAREFULLY TO SUIT PROJECT REQUIREMENTS. MODIFY AS NECESSARY AND DELETE ITEMS THAT ARE NOTAPPLICABLE. VERIFY THAT REFERENCED SECTION NUMBERS AND TITLES ARE CORRECT. (NUMBERS AND TITLESREFERENCED ARE BASED ON MASTERFORMAT, 2004 EDITION).
THIS SECTION ASSUMES THE PROJECT MANUAL WILL CONTAIN COMPLETE DIVISION 01 DOCUMENTS INCLUDINGSECTIONS 01 33 00 SUBMITTAL PROCEDURES, 01 62 00 PRODUCT OPTIONS, 01 25 13 PRODUCT SUBSTITUTION PROCEDURES,01 66 00 PRODUCT STORAGE AND HANDLING REQUIREMENTS, 01 77 00 CLOSEOUT PROCEDURES AND 01 78 00 CLOSEOUTSUBMITTALS. IF THE PROJECT MANUAL DOES NOT CONTAIN THESE SECTIONS, ADDITIONAL INFORMATION SHOULD BEINCLUDED UNDER THE APPROPRIATE ARTICLES.
THIS IS AN OPEN PROPRIETARY SPECIFICATION ALLOWING USERS THE OPTION OF APPROVING OTHER MANUFACTURERSWHICH COMPLY WITH THE CRITERIA SPECIFIED HEREIN.
NOTES TO THE SPECIFIER ARE CONTAINED IN BOXES AND SHOULD BE DELETED FROM FINAL COPY.
OPTIONAL ITEMS REQUIRING SELECTION BY THE SPECIFIER ARE ENCLOSED WITHIN BRACKETS, E.G.: [35] [40] [45]. INCASES WHERE ONE OF THE OPTIONAL ITEMS IS A STANDARD FEATURE OF THE ACCORDION FOLDING PRODUCT MODEL,IT IS LISTED IN THE FIRST POSITION. MAKE APPROPRIATE SELECTION AND DELETE OTHERS.
ITEMS REQUIRING ADDITIONAL INFORMATION ARE UNDERLINED, E.G.: ___________ .
OPTIONAL PARAGRAPHS ARE SEPARATED BY A REDLINED "OR" E.G.:
OR
PART 1 GENERAL
1.1 SUMMARY
A. Section Includes: manually operated, side folding accordion-type products for partition, wall ordoor applications.
B. Related Sections:1. 06 10 00 Rough Carpentry: All headers, support structures, surrounding insulation, jambs,
field painting, blocking, wood trim and pocket doors when not provided by Cornell shall befurnished and installed by others.
2. 08 70 00 Hardware: Masterkeyed cylinders by others.
1.2 SYSTEM DESCRIPTION
A. Operation: All units shall be top supported without the use of any floor tracks or single point locksockets. Smooth glide manual push/pull operation is accomplished with ease and minimal force.
B. Design: Accordion folding product assembly shall be repairable at installation site withoutremoval requirement for repair at factory.
Doc 100710 22 26.13-2
C. Acoustic Performance: Provide accordion-type folding products that have been tested by aqualified independent agency for the following acoustic properties as per the following testmethod:1. Sound Transmission Requirements: Accordion-type side folding products tested for
laboratory sound transmission loss performance according to ASTM E90, determined byASTM E413 and rated for an STC as follows:a. Sound Transmission Class (STC): 45
D. Fire Resistance: The accordion folding door material and finish shall achieve a Flame SpreadIndex of not more than 20 and a Smoke Developed Index of not more than 60 when tested inaccordance with ASTM E84.
1.3 SUBMITTALS
A. Reference Section 01 33 00 Submittal Procedures; submit the following items:1. Product Data.2. Shop Drawings: Show interface with adjacent work. Indicate required stacking depth, pocket
width (if applicable), and height from finished floor to bottom side of header. Showinstallation details and layout.
3. Closeout Submittals:a. Operation and Maintenance Manual.b. Certificate stating that installed materials comply with this specification.
1.4 QUALITY ASSURANCE
A. Installation shall be performed by manufacturer trained or authorized personnel according tomanufacturer’s installation instructions.
B. Surface Burning Characteristics: Provide operable wall with the following surface burningcharacteristics as determined by testing identical products per ASTM E84 by an authorizedindependent testing agency that is acceptable to the authority having jurisdiction:1. Flame Spread: 202. Smoke Developed: 60
1.5 DELIVERY STORAGE AND HANDLING
A. Reference Section 01 66 00 Product Storage and Handling Requirements.
B. Deliver to the job site in manufacturer’s original, unopened package(s).
1.6 COORDINATION BY GENERAL CONTRACTOR
A. Coordinate the efforts of the various trades affected by the work of this section. Assure accurateinstallation of header, jamb and trim. Provide field dimensions for fabrication
B. Supervise unloading and handling. Store boxes flat, and no more than four high, in a dry area andprotect from elements that may damage materials. Replace damaged materials at no additionalcost to the owner.
1.7 WARRANTY
A. Standard Warranty: Two years from date of shipment against defects in material andworkmanship.
Doc 100710 22 26.13-3
B. Maintenance: Submit for owner’s consideration and acceptance of a maintenance serviceagreement for installed products.
PART 2 PRODUCTS
2.1 MANUFACTURER
A. Manufacturer: Cornell Iron Works, Inc., 100 Elmwood Avenue, Crestwood Industrial Park,Mountaintop, PA 18707. Telephone: (800) 233-8366, Fax: (800) 526-0841.
B. Model: ESP20
C. Substitutions: Reference Section 01 25 13 Product Substitution Procedures.
2.2 MATERIALS
A. Accordion Folding Wall Construction1. Construction shall consist of a two parallel accordion-type side folding walls of panels
independently suspended from an interconnected double rail overhead track with nopantographs or internal connections except at the upright posts.
2. Wall Panels: Each assembly to consist of continuous length, 4 1/2” wide panels formed ofvinyl clad 24 gauge steel, corrugated and reinforced with double rolled end beads for strengthand resilience. Vinyl shall be permanently bonded to the outside face of the steel panels usinga heat and pressure process prior to the panels being roll formed.
3. Sound Blocker Lining: Interior surfaces of both panel walls shall be completely covered withcontinuous blankets of sound absorbing material attached with tear resistant fasteners thatensure lasting, effective retention of the sound liner.
4. Hinges: Continuous length, formed extruded vinyl members that interconnect full height withthe panel sections and upright posts to form the desired width wall panels. Hinges allow wallpanels to expand and collapse to create an operable product.
5. Upright Lead & Striker Posts: Heavy duty, formed extruded aluminum members located atleading and end sections of the wall panels. Lead post shall be equipped with grip-typeoperating handles and a slide latch mechanism to secure the unit when closed. [Single slideunits to utilize a striker post to seal fit with the lead post and secure the hook bolt latch.] [Bi-parting units to utilize a combination lead/striker post that mates to, and secures, the leadpost.] Latch design, operation and location shall be ADA compliant. [For units greater than14’ tall, manufacturer to supply a concealed, internally mounted diagonal Plumb Bar Supportbrace that is track supported and connected to the lead post for reinforced vertical alignmentduring latching and operation (requires a 14” wide header).]
6. Fully assembled and extended panel wall hang weight shall be approximately 4.5 pounds persquare foot.
B. Suspension System1. Track: Interconnected double rail heavy duty extruded aluminum track section designed to
attach to overhead structural support system. Shape is designed for smooth running support ofthe roller assemblies while prohibiting any opportunity for the rollers to derail.
2. Rollers: Every panel shall be supported and suspended by a nylon wheel ball bearing roller.Each lead post shall be connected to, and suspended by, a heavy duty trolley system that isfitted with three sets of double nylon wheel ball bearing rollers per rail.
C. Perimeter Seals: Continuous extruded vinyl sweep strips shall be attached to the top and bottomof both wall panels to close off gaps at the header and floor. Leading edges of the lead and striker
Doc 100710 22 26.13-4
posts shall be provided with interlocking extruded vinyl seals that also cushion the contact pointduring closing operation.
D. Finishes1. Wall Panels: Customer selected, tear resistant decorative vinyl. Color and pattern [as selected
from manufacturer’s stock finishes, minimum of 12 finish choices.] [to match custom finishas provided by the customer.] All surface treatments as applied to the metal panel substratesshall meet the Surface Burning Characteristics per ASTM E84 as described in Section 1.4 B.
2. Hinges: Manufacturer selected color to compliment the customer selected wall panel finish.3. Upright Posts: Supplied with a baked-on powder coat finish in a manufacturer selected color
to compliment the customer selected wall panel finish.4. Track: Supplied with a white baked-on powder coat finish as standard. Mill finish aluminum
and brown powder coat are readily available options. Consult factory for optional colors.5. Perimeter Seals: Flat black.
2.3 Accessories
THE ACCESSORIES LISTED BELOW ARE AVAILABLE OPTIONS. FACTORY SUPPLIEDPOCKET DOORS ARE AN AVAILABLE OPTION TO A MAXIMUM OF 12’ HIGH. POCKETDOORS STOP AT UNDERSIDE OF TRACK AND LOOK BETTER AESTHETICALLY WHEN THETRACK IS RECESSED IN A CEILING OR SOFFIT. DELETE ITEMS THAT ARE NOT DESIRED.
A. Cylinder Locks: Cylinder locking at lead posts operable from public side with key, secured sidewith [key] [thumbturn]. 1” mortise cylinder, non-removable core.
B. Pocket Door(s):1. Door and Frame
a. Material: A36 HR steelb. Thickness: USS 12-gaugec. Finish: Phosphate treatment followed by a baked-on powder coat finish in [standard
white] [color as selected from manufacturer’s standard color range] [custom color asselected by Architect].
2. Hinges: 3” non-mortise type3. Lock: 1” security mortise cylinder
C. Header Trim: For use with exposed track. Provide rigid extruded vinyl aesthetic trim members ina white finish on [one] [both] sides of the track assembly.
PART 3 EXECUTION
3.1 EXAMINATION
A. Examine header substrates upon which accordion folding product will be installed and verifyconditions are in accordance with approved shop drawings. Openings shall be prepared to thedimensions specified and be plumb and level. Header shall be leveled with the finished floor towithin +/- ¼” tolerance over the entire length of the opening.
B. Upon inspection of prepared opening, coordinate immediately with responsible entity to performcorrective work on unsatisfactory substrates and header, floor or sill levels.
C. Commencement of work by installer is considered acceptance of substrate.
3.2 INSTALLATION
Doc 100710 22 26.13-5
A. Install accordion folding products in accordance with manufacturer’s printed instructions.
B. Upon completion of the installation, the General Contractor shall protect the accordion foldingunits from damage and replace or repair subsequent damage so that the units are acceptable to thearchitect, at no additional cost to the owner.
3.3 ADJUSTING
A. Following completion of installation, including related work by others, test and adjust accordionfolding products for ease of operation.
3.4 CLEANING
A. Clean surfaces soiled by work as recommended by manufacturer.
B. Remove surplus materials and debris from the site.
3.5 DEMONSTRATION
A. Demonstrate proper operation to Owner's Representative.
B. Instruct Owner's Representative in maintenance procedures.
END OF SECTION
Rev. 1
2 / 4.1 © Cornell Iron Works
TRANZFORM® Sound - *Budget Installed Prices
with standard material & finish components
HEIGHT
8’ – 0” 10’ – 0” 12’ – 0” 14’ – 0”
6' - 0" 2684 3171 3605 5053
8' - 0" 3340 3961 4505 6117
10' - 0" 3883 4596 5230 6985
12' - 0" 4875 5751 6537 8885
14' - 0" 5419 6385 7260 9753
16' - 0" 6185 7333 8336 11013
18' - 0" 6730 7968 9061 11880
20' - 0" 7274 8602 9786 12747
22' - 0" 7818 9235 10509 13614
24’ - 0” 8362 9870 11234 14481
26’ - 0” 8906 10504 11958 15349
28’ - 0” 9450 11139 12683 16216
30’ - 0” 10218 12087 13770 17477
32' - 0" 10760 12721 14483 18343
34' - 0" 11306 13354 15207 19210
36' - 0" 11850 13989 15932 20078
38' - 0" 12394 14623 16657 20945
40' - 0" 12938 15257 17380 21811
*NOTE: Figures shown are national average INSTALLED prices and will vary depending on locality, union labor, door quantity and other factors. Please contact your local Cornell distributor for accurate pricing.
WID
TH
Rev. 1
2 / 4.2 © Cornell Iron Works
TRANZFORM® Sound – WEIGHT Chart
With standard material & finish components
HEIGHT
8’ – 0” 10’ – 0” 12’ – 0” 14’ – 0”
6' - 0"
216
270
324
378
8' - 0"
288
360
432
504
10' - 0"
360
450
540
630
12' - 0"
432
540
648
756
14' - 0"
504
630
756
882
16' - 0"
576
720
864
1008
18' - 0"
648
810
972
1134
20' - 0"
720
900
1080
1260
22' - 0"
792
990
1188
1386
24’ - 0”
864
1080
1296
1512
26’ - 0”
936
1170
1404
1638
28’ - 0”
1008
1260
1512
1764
30’ - 0”
1080
1350
1620
1890
32' - 0"
1152
1440
1728
2016
34' - 0"
1224
1530
1836
2142
36' - 0"
1296
1620
1944
2268
38' - 0"
1368
1710
2052
2394
40' - 0"
1440
1800
2160
2520
WID
TH
Section 3
TranZform® Space
Rev. 1
3 / 1.1 Cornell Iron Works
TRANZFORM® Space - Assembly Drawing
PanelsLead Post
Rollers
Floor Sweep
HeaderSweep
Hinges
SAFE AND SECURE
Track
Floating EndMemberShown, fixedend memberavailable.
Doc 11.009
10 22 26.13-1
SECTION 10650 or MasterFormat™ 2004 SECTION 10 22 26.13
TRANZFORM® SPACE
ACCORDION FOLDING PARTITIONS, WALLS OR DOORS GENERAL NOTES TO SPECIFIER: THIS SPECIFICATION SECTION HAS BEEN PREPARED TO ASSIST DESIGN PROFESSIONALS IN THE PREPARATION OF PROJECT OR OFFICE MASTER SPECIFICATIONS. IT FOLLOWS GUIDELINES ESTABLISHED BY THE CONSTRUCTION SPECIFICATIONS INSTITUTE, AND THEREFORE MAY BE USED WITH MOST MASTER SPECIFICATION SYSTEMS WITH MINOR EDITING. EDIT CAREFULLY TO SUIT PROJECT REQUIREMENTS. MODIFY AS NECESSARY AND DELETE ITEMS THAT ARE NOT APPLICABLE. VERIFY THAT REFERENCED SECTION NUMBERS AND TITLES ARE CORRECT. (NUMBERS AND TITLES REFERENCED ARE BASED ON MASTERFORMAT™, 2004 EDITION). THIS SECTION ASSUMES THE PROJECT MANUAL WILL CONTAIN COMPLETE DIVISION 01 DOCUMENTS INCLUDING SECTIONS 01 33 00 SUBMITTAL PROCEDURES, 01 62 00 PRODUCT OPTIONS, 01 25 13 PRODUCT SUBSTITUTION PROCEDURES, 01 66 00 PRODUCT STORAGE AND HANDLING REQUIREMENTS, 01 77 00 CLOSEOUT PROCEDURES AND 01 78 00 CLOSEOUT SUBMITTALS. IF THE PROJECT MANUAL DOES NOT CONTAIN THESE SECTIONS, ADDITIONAL INFORMATION SHOULD BE INCLUDED UNDER THE APPROPRIATE ARTICLES. THIS IS AN OPEN PROPRIETARY SPECIFICATION ALLOWING USERS THE OPTION OF APPROVING OTHER MANUFACTURERS WHICH COMPLY WITH THE CRITERIA SPECIFIED HEREIN. NOTES TO THE SPECIFIER ARE CONTAINED IN BOXES AND SHOULD BE DELETED FROM FINAL COPY. OPTIONAL ITEMS REQUIRING SELECTION BY THE SPECIFIER ARE ENCLOSED WITHIN BRACKETS, E.G.: [35] [40] [45]. IN CASES WHERE ONE OF THE OPTIONAL ITEMS IS A STANDARD FEATURE OF THE ACCORDION FOLDING PRODUCT MODEL, IT IS LISTED IN THE FIRST POSITION. MAKE APPROPRIATE SELECTION AND DELETE OTHERS. ITEMS REQUIRING ADDITIONAL INFORMATION ARE UNDERLINED, E.G.: ___________ . OPTIONAL PARAGRAPHS ARE SEPARATED BY A REDLINED "OR" E.G.:
OR
PART 1 GENERAL 1.1 SUMMARY A. Section Includes: manually operated, side folding accordion-type products for partition, wall or
door applications. B. Related Sections: 1. 06 10 00 Rough Carpentry: All headers, support structures, surrounding insulation, jambs,
field painting, blocking, wood trim and pocket doors when not provided by Cornell shall be furnished and installed by others.
2. 08 70 00 Hardware: Masterkeyed cylinders by others. 1.2 SYSTEM DESCRIPTION
A. Operation: All units shall be top supported without the use of any floor tracks or single point lock sockets. Smooth glide manual push/pull operation is accomplished with ease and minimal force.
B. Design: Accordion folding product assembly shall be repairable at installation site without
removal requirement for repair at factory.
Doc 11.009
10 22 26.13-2
C. Acoustic Performance: Provide accordion-type folding products that have been tested by a qualified independent agency for the following acoustic properties as per the following test method: 1. Sound Transmission Requirements: Accordion-type side folding products tested for
laboratory sound transmission loss performance according to ASTM E90, determined by ASTM E413 and rated for an STC as follows: a. Sound Transmission Class (STC): 30
D. Fire Resistance: The accordion folding door material and finish shall achieve a Flame Spread
Index less of not more than 15 and a Smoke Developed Index of not more than 50 when tested in accordance with ASTM E84.
1.3 SUBMITTALS A. Reference Section 01 33 00 Submittal Procedures; submit the following items: 1. Product Data. 2. Shop Drawings: Show interface with adjacent work. Indicate required stacking depth, pocket
width (if applicable), and height from finished floor to bottom side of header. Show installation details and layout.
3. Closeout Submittals: a. Operation and Maintenance Manual. b. Certificate stating that installed materials comply with this specification. 1.4 QUALITY ASSURANCE A. Installation shall be performed by manufacturer trained or authorized personnel according to
manufacturer’s installation instructions. B. Surface Burning Characteristics: Provide operable wall with the following surface burning
characteristics as determined by testing identical products per ASTM E84 by an authorized independent testing agency that is acceptable to the authority having jurisdiction:
1. Flame Spread: 15 2. Smoke Developed: 50 1.5 DELIVERY STORAGE AND HANDLING A. Reference Section 01 66 00 Product Storage and Handling Requirements. B. Deliver to the job site in manufacturer’s original, unopened package(s). 1.6 COORDINATION BY GENERAL CONTRACTOR A. Coordinate the efforts of the various trades affected by the work of this section. Assure accurate
installation of header, jamb and trim. Provide field dimensions for fabrication B. Supervise unloading and handling. Store boxes flat, and no more than four high, in a dry area and
protect from elements that may damage materials. Replace damaged materials at no additional cost to the owner.
1.7 WARRANTY
A. Standard Warranty: Two years from date of shipment against defects in material and workmanship.
Doc 11.009
10 22 26.13-3
B. Maintenance: Submit for owner’s consideration and acceptance of a maintenance service
agreement for installed products. PART 2 PRODUCTS 2.1 MANUFACTURER A. Manufacturer: Cornell Iron Works, Inc., 24 Elmwood Avenue, Crestwood Industrial Park,
Mountaintop, PA 18707. Telephone: (800) 233-8366, Fax: (800) 526-0841. B. Model: ESP10 C. Substitutions: Reference Section 01 25 13 Product Substitution Procedures. 2.2 MATERIALS A. Accordion Folding Wall Construction
1. Construction shall consist of a single accordion-type side folding wall of panels suspended from a single overhead track.
2. Wall Panels: Continuous length, 4 1/2” wide formed of vinyl clad 24 gauge steel, corrugated and reinforced with double rolled end beads for strength and resilience. Vinyl shall be permanently bonded to the outside face of the steel panels using a heat and pressure process prior to the panels being roll formed. Interior face of the panel is a flexible urethane primer followed by a medium gloss, Platinum Gray color baked-on polyester coating.
3. Hinges: Continuous length, formed extruded vinyl members that interconnect full height with the panel sections and upright posts to form the desired width wall panels. Hinges allow wall panels to expand and collapse to create an operable product.
4. Upright Lead & Striker Posts: Heavy duty, formed extruded aluminum members located at leading and end sections of the wall panels. Lead post shall be equipped with grip-type operating handles and a slide latch mechanism to secure the unit when closed. [Single slide units to utilize a striker post to seal fit with the lead post and secure the hook bolt latch.] [Bi-parting units to utilize a combination lead/striker post that mates to, and secures, the lead post.] Latch design, operation and location shall be ADA compliant.
5. Fully assembled and extended panel wall hang weight shall be approximately 1.9 pounds per square foot.
B. Suspension System 1. Track: Single rail heavy duty extruded aluminum track section designed to attach to overhead
structural support system. Shape is designed for smooth running support of the roller assemblies while prohibiting any opportunity for the rollers to derail.
2. Rollers: Every panel shall be supported and suspended by a nylon wheel ball bearing roller. Each lead post shall be connected to, and suspended by, a heavy duty trolley system that is fitted with four sets of double nylon wheel ball bearing rollers.
C. Perimeter Seals: Continuous extruded vinyl sweep strips shall be attached to the top and bottom
of the wall panels to close off gaps at the header and floor. Leading edges of the lead and striker posts shall be provided with interlocking extruded vinyl seals that also cushion the contact point during closing operation.
D. Finishes
1. Wall Panels: Customer selected, tear resistant decorative vinyl applied to the outside face of the curtain. Color and pattern [as selected from manufacturer’s stock finishes, minimum of 12
Doc 11.009
10 22 26.13-4
finish choices.] [to match custom finish as provided by the customer.] All surface treatments as applied to the metal panel substrates shall meet Surface Burning Characteristics per ASTM E84 as described in Section 1.4 B.
2. Hinges: Manufacturer selected color to compliment the customer selected wall panel finish. 3. Upright Posts: Supplied with a baked-on powder coat finish in a manufacturer selected color
to compliment the customer selected wall panel finish. 4. Track: Supplied with a white baked-on powder coat finish as standard. Mill aluminum and
brown powder coat are readily available options. Consult factory for optional colors. 5. Perimeter Seals: Flat black. 2.3 Accessories THE ACCESSORIES LISTED BELOW ARE AVAILABLE OPTIONS. FACTORY SUPPLIED POCKET DOORS ARE AN AVAILABLE OPTION TO A MAXIMUM OF 12’ HIGH. POCKET DOORS STOP AT UNDERSIDE OF TRACK AND LOOK BETTER AESTHETICALLY WHEN THE TRACK IS RECESSED IN A CEILING OR SOFFIT. DELETE ITEMS THAT ARE NOT DESIRED. A. Cylinder Locks: Cylinder locking at lead posts operable from public side with key, secured side with [key] [thumbturn]. 1” mortise cylinder, non-removable core. B. Pocket Door(s): 1. Door and Frame a. Material: A36 HR steel b. Thickness: USS 12-gauge c. Finish: Phosphate treatment followed by a baked-on powder coat finish in [standard
white] [color as selected from manufacturer’s standard color range] [custom color as selected by Architect].
2. Hinges: 3” non-mortise type 3. Lock: 1” security mortise cylinder C. Header Trim: For use with exposed track. Provide rigid extruded vinyl aesthetic trim members in
a white finish on [one] [both] sides of the track assembly. PART 3 EXECUTION 3.1 EXAMINATION A. Examine header substrates upon which accordion folding product will be installed and verify
conditions are in accordance with approved shop drawings. Openings shall be prepared to the dimensions specified and be plumb and level. Header shall be leveled with the finished floor to within +/- ¼” tolerance over the entire length of the opening.
B. Upon inspection of prepared opening, coordinate immediately with responsible entity to perform
corrective work on unsatisfactory substrates and header, floor or sill levels. C. Commencement of work by installer is considered acceptance of substrate. 3.2 INSTALLATION A. Install accordion folding products in accordance with manufacturer’s printed instructions.
Doc 11.009
10 22 26.13-5
B. Upon completion of the installation, the General Contractor shall protect the accordion folding units from damage and replace or repair subsequent damage so that the units are acceptable to the architect, at no additional cost to the owner.
3.3 ADJUSTING A. Following completion of installation, including related work by others, test and adjust accordion
folding products for ease of operation. 3.4 CLEANING A. Clean surfaces soiled by work as recommended by manufacturer. B. Remove surplus materials and debris from the site. 3.5 DEMONSTRATION A. Demonstrate proper operation to Owner's Representative. B. Instruct Owner's Representative in maintenance procedures.
END OF SECTION
Rev. 1
3 / 4.1 © Cornell Iron Works
TRANZFORM® Space - *Budget Installed Prices
With standard material & finish components
HEIGHT
8’ – 0” 10’ – 0” 12’ – 0” 14’ – 0”
6' - 0" 1878 2256 2551 2797
8' - 0" 2241 2706 3060 3350
10' - 0" 2490 2993 3387 3714
12' - 0" 2827 3329 3765 4152
14' - 0" 3074 3617 4091 4514
16' - 0" 3439 4067 4599 5067
18' - 0" 3687 4354 4926 5430
20' - 0" 3936 4641 5252 5793
22' - 0" 4183 4929 5578 6156
24’ - 0” 4432 5216 5904 6518
26’ - 0” 4680 5502 6229 6882
28’ - 0” 4952 5789 6555 7244
30’ - 0” 5292 6239 7064 7798
32' - 0" 5541 6527 7390 8161
34' - 0" 5789 6814 7715 8524
36' - 0" 6038 7100 8041 8886
38' - 0" 6285 7388 8367 9250
40' - 0" 6534 7675 8693 9612
*NOTE: Figures shown are national average INSTALLED prices and will vary depending on locality, union labor, door quantity and other factors. Please contact your local Cornell distributor for accurate pricing.
WID
TH
Rev. 1
3 / 4.2 © Cornell Iron Works
TRANZFORM® Space – WEIGHT Chart
With standard material & finish components
HEIGHT
8’ – 0” 10’ – 0” 12’ – 0” 14’ – 0”
6' - 0"
91
114
137
160
8' - 0"
121
152
182
213
10' - 0"
152
190
228
266
12' - 0"
182
228
274
319
14' - 0"
213
266
319
373
16' - 0"
243
304
365
426
18' - 0"
273
342
410
479
20' - 0"
304
380
456
532
22' - 0"
335
418
502
585
24’ - 0”
365
456
547
638
26’ - 0”
395
494
593
692
28’ - 0”
426
532
638
745
30’ - 0”
456
570
684
798
32' - 0"
486
608
730
851
34' - 0"
517
646
775
904
36' - 0"
547
684
821
958
38' - 0"
578
722
866
1012
40' - 0"
608
760
912
1064
WID
TH
Crestwood Industiral ParkMountain Top, PA 18707