SHOP DRAWING REVIEW
PROJECT NAME: Shelby High School JOB NO: 08-ED1-052
SUBMITTAL ITEM: Surge Protection Devices SPEC. REFERENCE: 26 43 13
MANUFACTURER: Varies
REVIEWED REVIEWED AS NOTED
REVISE AND RESUBMIT NOT ACCEPTED Checking is only for conformance with the design concept of the project and compliance with the information given in the contract documents. The Contractor is responsible for dimensions to be confirmed and correlated at the job site. For information that pertains solely to the fabrication processes or to techniques of construction and for coordination of the work of all trades.
DATE: 8-16-12 BY: TMM
COMMENTS:THE FOLLOWING COMMENTS HAVE NOT BEEN MARKED ON THE ATTACHED SHOP DRAWINGS: GENERAL ITEMS: 1. The SPD device for the designated “T” panelboards shall be provided with spare modules per 264313 1.9. 3. Nameplate quantity and nomenclature is the responsibility of the contractor and as per Spec Section 25 05 53. 4. Provide arc flash labeling per Spec Section 25 05 53. Shop drawing #264313-1 and #264313-2.
Shelby New 9-12 High School ResubSpec Section 26 43 13 Surge Protect ion DevicesApproval Drawing Package
Factory Order #: 31134940
07-09-2012
Distributor:
N/A
Contractor / Installer:
N/A
Consult ing Engineer:
N/A
Steve Brubaker
Sales Representat ive
Simeone Dominijanni
Project Manager
North American Operat ing Division
440-746-3148
Make the most of your energySM
2 of 17
3 of 17
4 of 17
5 of 17
6 of 17
7 of 17
8 of 17
9 of 17
10 of 17
11 of 17
TM
Square DTM brand SurgelogicTM internal modular Surge Protective
Devices (SPDs) deliver specification grade performance for
service entrance or critical branch panel applications. This multi-
phase system provides suppression for all critical modes inside
electrical equipment and shorter lead lengths with superior SPD
performance.
Internal Modular SPDs Square D Internally Mounted
Surge Protective Devices
12 of 17
02
Document Number 9990-0116C March 2011 bw
Schneider Electric USA, Inc. 1751 S. 4800 W., Salt Lake City, UT 84104, USA Telephone: (801)-977-9009 Fax: (801)-977-0200 www.surgelogic.com © 2
011
Sc
hn
eid
er
Ele
ctr
ic.
All
rig
hts
re
se
rve
d.
FEATURES ADVANTAGES BENEFITS
Integral to electrical gear and panels SPDs are professionally installed inside electrical gear and panels
Delivers high levels of SPD performance and saves on enclosure and installation expenses
120,000 to 480,000 Amp Capacity (depending on model)
Longer service life and suppressionagainst high-energy lightning strikes
High performance surge suppression even in severe electrical conditions
EMI/RFI Noise Rejection Increased transient suppression Improves surge suppression to the equipment
Advanced Diagnostics Allows for online testing of the suppressor’s functionality
Provides immediate response if suppressor is damaged
Suppression Status Alarms Allows multiple methods of alarm notification
Provides immediate notification through audible, visual and remote signaling if reduced suppression occurs
Coordinated Fuse Technology Coordinated fusing allows disconnection methods for thermal and high-current events
Provides premium surge suppression while managing both thermal and high-current end-of-life events
Internal Modular SPDs
Features
Internal panel modular Surge Protective
Devices (SPDs) provide superior design
and service life for a wide variety of
commercial, industrial, or institutional
applications. Square D brand SurgeLogic
SPDs offer first-rate performance and
surge suppression for demanding service
entrance applications or as part of a
suppression network. The robust modular
construction reduces possible down time
and maintenance costs.
Superior Performance
Surgelogic SPDs utilize a high-energy suppression circuit that provides 10 modes of suppression from
120,000 to 480,000 peak Amps of surge current rating per phase. Modular SPDs feature circuity that
provides not only transient surge suppression, but also noise filtration.
InstallationIntegral solutions come professionally pre-wired into electrical gear and panels from the factory insuring short lead lengths and high performance. All units are tested at the factory before delivery to their final destination, maintaining Square D brand’s high standard of quality. There is also no need for additional enclosures or installation labor costs.
Warranty
Surgelogic internal modular SPDs have a 10-year warranty.
13 of 17
03
Document Number 9990-0116C March 2011 bw
Schneider Electric USA, Inc. 1751 S. 4800 W., Salt Lake City, UT 84104, USA Telephone: (801)-977-9009 Fax: (801)-977-0200 www.surgelogic.com © 2
011
Sc
hn
eid
er
Ele
ctr
ic.
All
rig
hts
re
se
rve
d.
Internal Modular SPDs
Features (continued)
Performance Surge Current Rating per Phase Up to 480kAShort Circuit Current Rating 200kAModes of Protection 10Fusing Individually fused MOVs Thermal Fusing YesOcercurrent Fusing YesFiltering YesOperating Frequency 50/60 Hz
Mechanical DescriptionConnection Method #10-#2 AWG TerminalsMounting Method/Circuit Type ParallelOperating Altitude Sea Level-12,000’ (3,658 m)Storage Temperature -40 ̊F (-40 ̊C) to 149 ̊F (65 ̊C)Operating Temp. -4 ̊F (-20 ̊C) to 149 ̊F (65 ̊C)LCD Operating Temp. 32 ̊F (0 ̊C) to 149 ̊F (65 ̊C)Operating Humidity 0 to 95% non-condensing
DiagnosticsPush to test diagnostic switches, red and green status LEDs per phase (internal redundant status LEDs are green), module status LEDs per mode, dry contacts, audible alarm with disable switch, surge counter.
Options• Remote monitor
Safety and PerformancecULus Listed per UL1449 3rd Edition Type 2 SPD, UL 1283 5th Ed., and CAN/CSA C22.2 No. 8-M1986.
Complies with UL 96A 12th Ed. Master Label
requirements for Lighting Protection Systems
Internal SPDsNQ/NF Panelboard
QED Switchboard
NQ and NF panelboards are primarily used for
lighting and power distribution up to 600 Amps.
These panelboards, following the 2008 National
Electric Code changes, provide electrical capac-
ity up to 84 circuit breakers. Both types of panels
are designed with 200% rated copper neutrals for
non-linear loads. (NQ max volts 240 Vac, NF max
volts 600/347 Vac)
SPD available surge current ratings: 120, 160,
240 kA
QED Switchboards are made for use as service
entrance equipment or as distribution centers in
commercial, institutional, and industrial applica-
tions. QEDs are extremely versatile providing front
accessible load connections with multiple breaker
and fusible switch options. QEDs enable easy
access to power monitoring equipment such as
products from our PowerLogicTM brand. (Max volts
600 Vac, max current 4,000 Amps)
SPD available surge current ratings: 120, 160, 240, 320, 480 kA
14 of 17
04
Document Number 9990-0116C March 2011 bw
Schneider Electric USA, Inc. 1751 S. 4800 W., Salt Lake City, UT 84104, USA Telephone: (801)-977-9009 Fax: (801)-977-0200 www.surgelogic.com © 2
011
Sc
hn
eid
er
Ele
ctr
ic.
All
rig
hts
re
se
rve
d.
Power-ZoneTM Switchgear
Motor Control Center
The Square D brand Power-Zone 4 low voltage
metal-enclosed drawout switchgear is designed to
provide superior electrical distribution and power
quality management. Power-Zone 4 switchgear
is designed to deliver maximum uptime, system
selectivity, and ease of maintenance. All of these
features are packed into one of the smallest foot-
prints available for low voltage drawout switchgear.
(Max volts 600 Vac, max current 5,000 Amps)
SPD available surge current ratings: 120, 160, 240, 320, and 480 kA
The feature-rich modular design minimizes space
and maximizes ease-of-use and accessibility of
motor control devices. The Model 6 MCC has
integrated industry-leading components into the
smallest and one of the most flexible footprints
possible to meet industry’s power, control, and au-
tomation needs. (Max volts 480 Vac, max current
2,500 Amps)
SPD available surge current ratings: 120, 160, 240 kA
Internal Modular SPDs
Features (continued)
QMB Panelboard
When specifications or electrical codes call for a
fusible panelboard, the QMB family offers superior
performance and time-saving installation features.
The reliability of the QMB panelboard makes it the
product of choice for large commercial and indus-
trial applications. (Max volts 600 Vac, max current
400 Amps)
SPD available surge current ratings: 120, 160, 240 kA
Busway
Square D brand I-LineTM Busway is engineered to
replace old cable and conduit systems. This next-
generation power distribution system is loaded
with exceptional features, including a 200% neu-
tral and a 100% isolated ground path. (Max volts
600 Vac, max current 5,000 Amps)
SPD available surge current ratings: 120, 160, 240 kA
15 of 17
05
Document Number 9990-0116C March 2011 bw
Schneider Electric USA, Inc. 1751 S. 4800 W., Salt Lake City, UT 84104, USA Telephone: (801)-977-9009 Fax: (801)-977-0200 www.surgelogic.com © 2
011
Sc
hn
eid
er
Ele
ctr
ic.
All
rig
hts
re
se
rve
d.
Internal Modular SPDs
Specifications
SPD OPTIONS
Remote Monitor TVS12RMUMODEL NUMBER SUFFIX CODES
P NQ/NF panelboard (Not available in 320 and 480 kA)
B QED switchboard
Z PZ3/PZ4 switchgear (Not available in TVS1 or TVS3)
Q QMB switchboard (Not available in 320 and 480 kA)
M Motor Control Center (Not available in 320 and 480 kA)
O OEM kit (Not available in 320 and 480 kA)
208Y/120 series also applies to the following voltage 220Y/127 480Y/277 series also applies to the following voltages 380Y/220, 400Y/230, and 415Y/240
Voltage
Surge Current per
Phase
Modes of
Protection Configuration Model Number MCOV In
VPR
L-N L-G L-L N-G
120/240V 120kA 6 1 Ø, 3-wire+G TVS1IMA12_ 150V 20kA 700V 800V 1200V 700V
208Y/120V 120kA 10 3 Ø, Wye, 4-wire+G TVS2IMA12_ 150V 20kA 700V 800V 1200V 700V
480Y/277V 120kA 10 3 Ø, Wye, 4-wire+G TVS4IMA12_ 320V 20kA 1200V 1200V 2000V 1200V
600Y/347V 120kA 10 3 Ø, Wye, 4-wire+G TVS8IMA12_ 420V 20kA 1500V 1500V 2500V 1500V
120/240V 160kA 6 1 Ø, 3-wire+G TVS1IMA16_ 150V 20kA 700V 800V 1200V 700V
208Y/120V 160kA 10 3 Ø, Wye, 4-wire+G TVS2IMA16_ 150V 20kA 700V 800V 1200V 700V
480Y/277V 160kA 10 3 Ø, Wye, 4-wire+G TVS4IMA16_ 320V 20kA 1200V 1200V 2000V 1200V
600Y/347V 160kA 10 3 Ø, Wye, 4-wire+G TVS8IMA16_ 420V 20kA 1500V 1500V 2500V 1500V
120/240V 240kA 6 1 Ø, 3-wire+G TVS1IMA24_ 150V 20kA 700V 800V 1200V 700V
208Y/120V 240kA 10 3 Ø, Wye, 4-wire+G TVS2IMA24_ 150V 20kA 700V 800V 1200V 700V
480Y/277V 240kA 10 3 Ø, Wye, 4-wire+G TVS4IMA24_ 320V 20kA 1200V 1200V 2000V 1200V
600Y/347V 240kA 10 3 Ø, Wye, 4-wire+G TVS8IMA24_ 420V 20kA 1500V 1500V 2500V 1500V
120/240V 320kA 6 1 Ø, 3-wire+G TVS1IMA32_ 150V 20kA 700V 800V 1200V 700V
208Y/120V 320kA 10 3 Ø, Wye, 4-wire+G TVS2IMA32_ 150V 20kA 700V 800V 1200V 700V
480Y/277V 320kA 10 3 Ø, Wye, 4-wire+G TVS4IMA32_ 320V 20kA 1200V 1200V 2000V 1200V
600Y/347V 320kA 10 3 Ø, Wye, 4-wire+G TVS8IMA32_ 420V 20kA 1500V 1500V 2500V 1500V
120/240V 480kA 6 1 Ø, 3-wire+G TVS1IMA48_ 150V 20kA 700V 800V 1200V 700V
208Y/120V 480kA 10 3 Ø, Wye, 4-wire+G TVS2IMA48_ 150V 20kA 700V 800V 1200V 700V
480Y/277V 480kA 10 3 Ø, Wye, 4-wire+G TVS4IMA48_ 320V 20kA 1200V 1200V 2000V 1200V
600Y/347V 480kA 10 3 Ø, Wye, 4-wire+G TVS8IMA48_ 420V 20kA 1500V 1500V 2500V 1500V
Voltage
Surge
Current
per
Phase
Modes of
Protection Configuration
Model
Number MCOV In
VPR
L-N H-N L-G H-G L-L H-L N-G
240/120HLD 120kA 10 3 Ø, HLD*, 4-wire+G TVS3IMA12_ 150V 20kA 700V 1200V 800V 1200V 1200V 1500V 700V
240/120HLD 160kA 10 3 Ø, HLD*, 4-wire+G TVS3IMA16_ 150V 20kA 700V 1200V 800V 1200V 1200V 1500V 700V
240/120HLD 240kA 10 3 Ø, HLD*, 4-wire+G TVS3IMA24_ 150V 20kA 700V 1200V 800V 1200V 1200V 1500V 700V
240/120HLD 320kA 10 3 Ø, HLD*, 4-wire+G TVS3IMA32_ 150V 20kA 700V 1200V 800V 1200V 1200V 1500V 700V
240/120HLD 480kA 10 3 Ø, HLD*, 4-wire+G TVS3IMA48_ 150V 20kA 700V 1200V 800V 1200V 1200V 1500V 700V
Model numbers not recognized as line items in Schneider Electric ordering system until a suffix code is applied
*HLD = High-leg delta
16 of 17
Shelby High School
PROJECT
PRODUCT
Surge Protective Devices
APPROVAL DRAWING SUBMITTAL PACKAGE
School District
Shelby City Schools
Shelby, OH
Electrical Consulting Firm
MKC Associates Inc
Mansfield, OH
Construction Management
Barton Malow Company
Columbus, OH
Electrical Contractor
Carter Electric
Galion, OH
Distributor
Graybar
Mansfield, OH
Advanced Protection Technologies, Inc.
14550 58th Street N., Clearwater, FL 33760 (727) 535-6339 * Fax (727) 539-8955
Toll Free (800) 237-4567 * [email protected]
"Professionals Serving Professionals"
*SUBMITTED AS EXTERNAL SPD UNIT FOR MSB. TO BE INSTALLED ON TOP OF SWITCH GEAR ON A 100A/3P SWITCH LOCATED IN THE TOP POSITION OF THE SWITCH GEAR SECTION NEAREST THE MAIN SWITCH.
ROD MATNEY - CARTER ELECTRIC, INC.
APPROVAL DRAWING SUBMITTAL PACKAGE
Shelby High School
Table of Contents
Products
Item Qty Model Voltage Location
1 1 TE04XAS40E1X 480Y/277V 3ph, 4w +grd External to MSB
Documents Included:
Product Information Sheet
TEXAS Cut Sheet
TEXA Electrical Drawing
TEXA 400-500K Mechanical Drawing
TEXAS UL Letters Series ND Page 1
Warranty, 10 year
Advanced Protection Technologies, Inc.
14550 58th Street N., Clearwater, FL 33760 (727) 535-6339 * Fax (727) 539-8955
Toll Free (800) 237-4567 * [email protected]
"Professionals Serving Professionals"
APPROVAL DRAWING SUBMITTAL PACKAGE
Shelby High School
Product Information for Item: 1
TE04XAS40E1X
Product Features and Specifications:
UL 1449 3rd Edition Listed*
UL 1283 Complimentary Listing*
UL 3rd Edition Inominal Rating: 20 kA*
UL 3rd Edition Type Rating: Type 1*
Mode of Protection - L-N*
Mode of Protection - L-G*
Mode of Protection - N-G*
Surge Current Rating Per Phase: 400 kA*
Surge Current Rating - L-N: 200 kA*
Surge Current Rating - L-G: 200 kA*
Surge Current Rating - N-G: 200 kA*
Short Circuit Current Rating: 200kA per UL 1449 3rd Edition (SCCR)*
UL 1449 3rd Edition VPR (6kV, 3kA) - L-N: 1200 Volts*
UL 1449 3rd Edition VPR (6kV, 3kA) - L-G: 1000 Volts*
UL 1449 3rd Edition VPR (6kV, 3kA) - N-G: 1000 Volts*
UL 1449 3rd Edition VPR (6kV, 3kA) - L-L: 1800 Volts*
EMI/RFI Filtering: Up to -50dB from 100kHz to 100MHz dB*
MCOV: 320 Volts*
Suppression Technology: Large Block 50kA MOV*
Connection Method: Parallel*
Disconnect Method: Circuit breaker in panel*
Mounting Method: Surface*
Installation Method: External*
Overcurrent Protection Method: Individually Fused per MOV*
Thermal Cutout Circuit: For each MOV*
Module Connection Method: Bolted to backplane*
Enclosure Rating: NEMA 1/12/3R/4*
Dimensions: 12X12X7 HxWxD"*
Typical Weight: 24 lbs.*
Audible Alarm*
Silence Switch for Audible Alarm*
Warranty Period: 10 Years*
Dry Contacts*
Surge Counter*
cUL Listed*
Options:
Advanced Protection Technologies, Inc.
14550 58th Street N., Clearwater, FL 33760 (727) 535-6339 * Fax (727) 539-8955
Toll Free (800) 237-4567 * [email protected]
"Professionals Serving Professionals"
APPROVAL DRAWING SUBMITTAL PACKAGE
Shelby High School
Product Information for Item: 1
TE04XAS40E1X
40: Increase Surge Current to 400kA/phase*
E1: NEMA 1/12/3R/04 Steel Enclosure*
X: Surge Counter*
Advanced Protection Technologies, Inc.
14550 58th Street N., Clearwater, FL 33760 (727) 535-6339 * Fax (727) 539-8955
Toll Free (800) 237-4567 * [email protected]
"Professionals Serving Professionals"
Advanced Protection Technologies14550 58th Street North · Clearwater, Florida 33760(800) 237-4567 · (727) 535-6339 · Fax (727) 539-8955www.apttvss.com · [email protected] · www.aptsurge.com · [email protected]
Design Features !Designed, Manufactured & Tested consistent with:
– ANSI/IEEE C62.41.1-2002, C62.41.2-2002, and
C62.45-2002
– NEMA LS-1
– NEC Article 285
– IEC 61643
!High Energy Parallel Design for Category C3 & C-High applications
!For External Mounting next to Switchgear, Motor Controls
Centers or Panelboards
! Individually Fused & Thermally Protected MOVs
!Large-Block, 34mm square, 50kA MOVs
!Replaceable Module Construction
!Solid State Bidirectional Operation
Physical Specifications !Relative Humidity Range: 0 -95% non-condensing
!Operating Frequency: 47-63Hz
!Operating Temperature: -25°C (-15°F) to +60°C (140°F)
!Weight: 24 lbs (11 kg)
!Standard NEMA 1/12/3R/4 enclosure
!Standard size: 12” x 12” x 6.5” (305mm x 305mm x 165mm)
!Lug size: #2 - #14 AWG (w/opt. disconnect: #6 - #1/0)
!Typical connection: #6 AWG and 60A breaker
Quality, Standards & Validation !UL 1449 Third Edition, cUL, UL 1283 R/C
!UL file: VZCA.E321351 at www.UL.com
!RoHS-compliant
! IEC 61643, CE
!10 year warranty (longer optional)
!Burn-In tested Prior to Shipment
! ISO 9001:2008 Quality Management System
! ISO 17025:2005 Laboratory Qualification
!Made in USA
TEXAS SeriesType 1 Surge Protective Device/SPD/TVSS
Features: !"#!$%%&!'()*+!,+)-)./!#)0-1+!2314-!566&7 !$6689!:!;6689!41*!4(<01!*<-)/=0 !'>41!$!3?@!:!
– All UL required OCP & Safety Coordination included inside – Can be installed line-side or load-side of main disconnect
!5689!A/.B)/<C!2B.0-!B.+1C07 !56689!3DDE0!2B.0-!B.+1C07 !"#!&F9!#)=(-/)/=!?*.-1G-)./!H<0-1*!#<I1C!G.B4C)</-!2J5689!A/7 !K.C-<=1!341G)L)G!@10)=/!:!M)=(C>!G./L)=N*<IC1 !9CC!HOK!0N44*100)./!1C1B1/-0!B./)-.*1+ !O4-)./<C!E.-<*>!@)0G.//1G-!3P)-G(
Performance Specifications !Surge Capacities L-N L-G N-G
100kA/phase 50kA 50kA 50kA
150kA/phase 100kA 50kA 50kA
200kA/phase 100kA 100kA 100kA
250kA/phase 150kA 100kA 100kA
300kA/phase 150kA 150kA 150kA
400kA/phase 200kA 200kA 200kA
500kA/phase 250kA 250kA 250kA
!UL 1449 Third Edition Listed, cUL, UL 1283 R/C
!UL 1449-3 Type 1 SPD (cUL Type 2 optional)
!UL 1449-3 tested Inominal: 20kA & 10kA
!UL 1449-3 tested SCCR: 200kA & 100kA
!UL 1449-3 Voltage Protection Ratings (VPRs):
– 208Y/120V: as low as 600V
– 480Y/277V: as low as 1000V
!Less than 1 nanosecond response time
!Repetitive Impulse: 5,000 hits
!AC Sinewave Tracking Filter with EMI/RFI Filtering up to
-50dB from 10kHz to 100MHz
Diagnostic Monitoring !100% monitoring – Every MOV is monitored, incl. N-G
!Green LED Status indicator per phase
!Red LED service indicator
!Audible Alarm with Silence Switch
!Test Function: toggles red service LED, audible alarm & dry
contact (if equipped)
!N-G overvoltage detection
!Phase Loss monitoring (toggles LED & dry contacts)
!Electrically isolated circuitry ensures surges do not damage
diagnostics
!Form C Dry Contacts, 240V, 5A (two sets)
!Optional Surge Counter, six-digit LCD, with test function,
reset & no-maintenance Eprom memory
Advanced Protection Technologies14550 58th Street North · Clearwater, Florida 33760
(800) 237-4567 · (727) 535-6339 · Fax (727) 539-8955www.apttvss.com · [email protected]
TEXAS MODEL NUMBER CONFIGURATOR & OPTIONS
Voltage Code for Electrical System Surge Current Rating Options
TE XAS ! ...
Common North American Systems
UL 1449 THIRD Edition (Sept 2009) Test Data
Voltage Protection Ratings (VPR - 3kA)
L-N L-G N-G L-L "#$% &' ())* +),-
01 = 240/120V Split Phase (<300kA) 700 700 700 1200 Type 1 20kA 100kA 150
01 = 240/120V Split Phase (=>300kA) 700 600 600 1000 Type 1 20kA 100kA 150
02 = 208Y/120V 3Ø Wye (<300kA) 700 700 700 1200 Type 1 20kA 200kA 150
02 = 208Y/120V 3Ø Wye (=>300kA) 700 600 600 1000 Type 1 20kA 200kA 15003 = 240Y/120V B High Leg Delta 700/1200 700/1200 700 1800 Type 1 20kA 200kA 150 / 32004 = 480Y/277V 3Ø Wye (<300kA) 1200 1200 1200 2000 Type 1 20kA 200kA 32004 = 480Y/277V 3Ø Wye (=>300kA) 1200 1000 1000 1800 Type 1 20kA 200kA 32005 = 480V 3Ø Delta (<300kA) - 1800 - 1800 Type 1 10kA 200kA 550
05 = 480V 3Ø Delta (=>450kA) - 1800 - 1800 Type 1 20kA 200kA 550
07 = 380Y/220V 3Ø Wye (<300kA) 1200 1200 1200 2000 Type 1 20kA 200kA 320
08 = 600Y/347V 3Ø Wye (<300kA) 1500 1500 1500 2500 Type 1 10kA 200kA 42008 = 600Y/347V 3Ø Wye (=>300kA) 1500 1500 1500 2500 Type 1 20kA 200kA 420
Other Available Systems:Please see supplementary data sheet, contact us at [email protected], or confirm at www.UL.com using CCN of VZCAOptional disconnect switch may increase VPRs
Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6
SPLIT2 Hots, 1 Neu, 1 Grnd
HI-LEG DELTA (B High)3 Hots, (B HIGH), 1 Neu, 1 Grnd
SINGLE POLE1 Hot, 1 Neu, 1 Grnd
WYE3 Hots, 1 Neu, 1 Grnd
DELTA & HRG WYE3 Hots, 1 Grnd
CORNER GROUNDDELTA (B grounded)2 Hots, 1 Grnd
Hot (BLK)
Hot (BLK)
Neutral (WHT)V
V
}}
Ground (GRN)
}
Phase A (BLK)
Phase B (BLK)
Neutral (WHT)
Phase C (BLK)
Ground (GRN)
A
C
N
V
B
Phase A (BLK)
Phase B (ORNG)
Neutral (WHT)
Phase C (BLK)
Ground (GRN)
}V V}Neutral (WHT)
Hot (BLK)
Ground (GRN)
Phase A (BLK)
Phase C (BLK)
Phase B (BLK)
Ground (GRN)
}V Phase A (BLK)
Phase C (BLK)
Ground (GRN)
V}
Enclosure Rating
X = Surge Counter, six-digit LCD counter includes maintenance-free Eprom memory backup
E = Remote Locatable Display on 4 ft Cable custom cable lengths available
F = Noise Filtering - Extended Range & Attenuation (available on 400kA & 500kA models)
D = Rotary Disconnect Switch, Bussmann, UL98
T = Thru-Door Rotary Disconnect Switch, Bussmann, UL98, E1 enclosure only(Consult factory for other disconnect switch options)
2 = Type 2 SPD Bearing cUL Mark
Delete Options - Consult Factory for Order CodeDelete L-N Protection (reduces kA rating)Delete L-G Protection (reduces kA rating)Delete N-G Protection (reduces kA rating)Delete Noise Filtering
Available Accessory (order separately)RM = Remote Monitor
,./%0 12345365% (#7.%87 9 ):';4083.4:' %'<:=03>%?@
15 = 254/127V Split Phase - 1Ø 3W+Grnd (Fig 1)18 = 480/277V 2-Pole, (480/240V Split Phase) (Fig 1) 21 = 220Y/127V Wye - 3Ø 4W+Grnd (Fig 2)41 = 520Y/300V Wye - 3Ø 4W+Grnd (Fig 2)42 = 415Y/240V Wye - 3Ø 4W+Grnd (Fig 2)43 = 400Y/230V Wye - 3Ø 4W+Grnd (Fig 2)44 = 440Y/250V Wye - 3Ø 4W+Grnd (Fig 2)51 = 480V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6)
(450kA replaces 400kA or 500kA)06 = 240V Delta - 3Ø 3W+Grnd (Fig 4)
(450kA replaces 400kA or 500kA)61 = 240V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6)
(450kA replaces 400kA or 500kA)07 = 380Y/220V Wye - 3Ø 4W+Grnd (Fig 2)09 = 600V Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye
(Available: 100kA, 150kA, 200kA, 250kA)91 = 600V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6)
(Available: 100kA, 150kA, 200kA, 250kA)11 = 120V Single Phase (Fig 5)12 = 240V Single Phase (Fig 5) - Not split phase13 = 127V Single Phase (Fig 5)14 = 300V Single Phase (Fig 5)16 = 277V Single Phase (Fig 5)17 = 480V Single Phase (1 Hot, 1 Neu, 1 Grnd) (Fig 5)
AB = ABBC1DE/37%
AF = AFBC1DE/37%
GB = GBBC1DE/37%
GF = GFBC1DE/37%
HB = HBBC1DE/37%
IB = IBBC1DE/37%
IF = IFBC1DE/37%(Voltage Codes 05, 51, 06 & 61)
FB = FBBC1DE/37%
):88:' J:0./ 18%04<3' (#7.%87@
BA = GIBDAGB- ($54. E/37% 9 AK HLMN0'? OP4> AQBG = GBRSDAGB- L#% 9 HK ILMN0'? OP4> GQ
BH = GIBDAGB- T4>/ U%> V%5.3 OW T4>/Q OP4> HQBI = IRBSDGXX- L#% 9 HK ILMN0'? OP4> GQBF = IRB- V%5.3 9 HK HLMN0'? OP4> IQ Y T*N L#%
OIFBC1 0%$53<%7 IBBC1 :0 FBBC1Q
BR = ZBBSDHIX- L#% 9 HK ILMN0'? OP4> GQ
[A = J[+1 ADAGDH*DI O74\%@ AG] ^ AG] ^ X_F]QI` = J[+1 I` J:'9+%.3554< O74\%@ AI] ^ AG]^ Z]Q
(polycarbonate, display inside clear front door)
I( = J[+1 I` (.34'5%77 (.%%5 O74\%@ AGa ^ AGa^ ZaQ
(display inside door)
P+ = J[+1 A P5=7/ +:='. Ob355 <324.# 74\%@ AG] ^ AG]^ Z] ?%%$Q EA = J[+1 A $=556:^ c4'?::0d O74\%@ AG] ^ AG] ^ Z]Q 4'<5=?%7 c[d :$.4:'
(Optional rotary disconnect increases enclosure sizes to 16” x 14” x 6” on models > 300kA)
Performance Data
5.14.12 #8386
File E321351
Project 09CA32494
September 17, 2009
REPORT
On
SURGE PROTECTION DEVICES
(VZCA, VZCA7)
ADVANCED PROTECTION TECHNOLOGIES
Clearwater, FL
Copyright © 2009 Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above-named company to
reproduce this report provided it is reproduced in its entirety.
The information contained in this document is an
excerpt taken from the APT’s UL File referenced
above. The complete UL file is extremely lengthy
but can be provided upon request. If you would
like a copy of the complete UL File, please contact Customer Service at (800) 237-4567
File E321351 Vol. 1 Sec. 1 Page 1 Issued: 2009-09-17
and Report
DESCRIPTION
PRODUCT COVERED:
USL - Surge Protection Devices, Type 1 SPD, Models “TE” or “ST”, followed by
“01”, “11”, “12”, “13”, “14”, “15”, “16” “17”, “18”, “02”, “21”, “03”, “04”,
“41”, “42”, “43”, “44”, “05”, “51”, “06”, “61”, “07”, “08”, “09”, or “91”,
followed by “XA” followed by “S” or “L”, followed by “05”, “10”, “15”, “20”,
“25”, “30”, “31”, “40”, “45” or “50”, followed by blank or options “X”, “Y”,
“Z”, “E”, “D”, “T”, “K”, “S”, “L”, “G”, “N”, “F”, “J”, or “P”.
USL, CNL – Surge Protection Devices, Type 2 SPD, Models “TE” or “ST” followed
by “01”, “11”, “12”, “13”, “14”, “15”, “16” “17”, “18”, “02”, “21”, “03”,
“04”, “41”, “42”, “43”, “44”, “05”, “51”, “06”, “61”, “07”, “08”, “09”, or
“91”, followed by “XA” followed by “S” or “L”, followed by “05”, “10”, “15”,
“20”, “25”, “30”, “31”, “40”, “45” or “50”, followed by blank or options “X”,
“Y”, “Z”, “E”, “D”, “T”, “K”, “S”, “L”, “G”, “N”, “F”, “J”, or “P”, followed
by required option “2”.
NOMENCLATURE:
TE 02 XA S 31 E1 X 2
I II III IV V VI VII VIII
I. Prefix
TE – APT model number prefix
ST – SurgTec™ model number prefix (APT trademark)
File E321351 Vol. 1 Sec. 1 Page 2 Issued: 2009-09-17
and Report
II. System Voltage
01 240/120V 1Ø, 3W Plus Ground, ( 2 Lines, 1 Neutral, 1 Ground)
15 254/127V 1Ø, 3W Plus Ground, ( 2 Lines, 1 Neutral, 1 Ground)
18 480/277V 1Ø, 3W Plus Ground, ( 2 Lines, 1 Neutral, 1 Ground)
02 208Y/120V 3Ø, 4W Plus Ground ( 3 Lines, 1 Neutral, 1 Ground)
21 220Y/127V 3Ø, 4W Plus Ground ( 3 Lines, 1 Neutral, 1 Ground)
03 240/120V 3Ø, 4W Plus Ground High Leg Delta ( 3 Lines, 1
Neutral, 1 Ground)
04 480Y/277V 3Ø, 4W Plus Ground ( 3 Lines, 1 Neutral, 1 Ground)
41 520/300V 3Ø, 4W Plus Ground ( 3 Lines, 1 Neutral, 1 Ground)
42 415Y/240V 3Ø, 4W Plus Ground ( 3 Lines, 1 Neutral, 1 Ground
43 400Y/230V 3Ø, 4W Plus Ground ( 3 Lines, 1 Neutral, 1 Ground)
44 440Y/250V 3Ø, 4W Plus Ground ( 3 Lines, 1 Neutral, 1 Ground)
05 480V 3Ø, 3W Plus Ground ( 3 Lines, 1 Ground)
51 480V 3Ø, 3W Plus Ground Corner Grounded, Delta ( 2 Lines, 1
Ground)
06 240V 3Ø, 3W Plus Ground ( 3 Lines, 1 Ground)
61 240V 3Ø, 3W Plus Ground Corner Grounded, Delta ( 2 Lines, 1
Ground)
07 380Y/220V 3Ø, 4W Plus Ground ( 3 Lines, 1 Neutral, 1 Ground)
08 600Y/347V 3Ø, 4W Plus Ground ( 3 Lines, 1 Neutral, 1 Ground)
09 600V 3Ø, 3W Plus Ground ( 3 Lines, 1 Ground)
91 600V 3Ø, 3W Plus Ground Corner Grounded, Delta ( 2 Lines, 1
Ground)
11 120V Single Phase ( 1 Line, 1 Neutral, 1 Ground)
12 240V Single Phase ( 1 Line, 1 Neutral, 1 Ground)
13 127V Single Phase ( 1 Line, 1 Neutral, 1 Ground)
14 300V Single Phase ( 1 Line, 1 Neutral, 1 Ground)
16 277V Single Phase ( 1 Line, 1 Neutral, 1 Ground)
17 480V Single Phase ( 1 Line, 1 Neutral, 1 Ground)
III. Model Number Series
XA
File E321351 Vol. 1 Sec. 1 Page 3 Issued: 2009-09-17
and Report
IV. Configuration
S – Standard Configuration (L-N, L-G, N-G)
L – 10 mode Configuration (L-L, L-N, L-G, N-G)
V. Manufacturer Declared Surge Current Rating (Not verified by UL)
10 – 10 per phase (XR modules; not available with “L” configuration)
15 – 150kA per phase (XR modules; available with “L” configuration)
20 – 200kA per phase (XR modules; not available with “L” configuration)
25 – 250kA per phase (XR modules; not available with “L” configuration)
30 – 300kA per phase (XR modules; available with “L” configuration)
31 – 300kA per phase (XW modules; available with “L” configuration)
40 – 400kA per phase (XW modules; not available with “L” configuration)
45 – 450kA per phase (XW modules; available with “L” configuration)
50 – 500kA per phase (XW modules; not available with “L” configuration)
VI. Enclosure Ratings
E1 – Type 1/12/3R/04
4X – Type 4X Non Metallic
4S – Type 4X Stainless Steel
UE – Type 1 U10/E10 Size 16.9 by 10.0 by 5.7 in. with Display on Module
P1 – Type 1 – Screw Cover Pull Box with Extended Display
FM – Type 1 – Flush Mount
VII. Options
Blank – Dry Contacts (Two sets – Normally Open, Common, Normally
Closed)
X – Surge Counter
Y – External Surge Counter Signal
Z – Combines options X & Y
E – Extended Display (remotely mounted)
D – Internal Rotary Disconnect - Bussmmann (UL98)
T - Internal Rotary Disconnect - Bussmmann (UL98) with thru door handle;
this option only available with Type 1, 12, and 3R Enclosures
K – Internal Rotary Disconnect - Katko (UL508)
S - Internal Rotary Disconnect - Katko (UL508) with thru door handle
L – Deletes L-N protection (not available with G option)
G – Deletes L-G protection (not available with L option)
N – Deletes N-G protection
F – Extended range capacitor(only available with 31, 40, 45, 50kA)
J – Deletes capacitor
P* – Any alphanumeric character not used above which indicate marketing text changes to any non-UL marking labels.
VIII. Type
Blank – Type 1 SPD (USL covered only)
2 – Type 2 SPD (USL and CNL covered)
File E321351 Vol. 1 Sec. 1 Page 4 Issued: 2009-09-17
and Report ELECTRICAL AND VOLTAGE PROTECTION RATINGS: [7 mode, no disconnect, XR modules]
Cat. No.
Rated
Voltage
(V ac)
Freq
(Hz) Phase Mode
VPR
(Vpk)
In
(kA)
MCOV
(V
ac)
SCCR
(kA)
Intended
End-Use
SPD
Type
L-N * 700 150
L-G ** 700 150
N-G *** 700 150
TE01XAS##
ST01XAS## 240/120 60 S
L-L 1200
20
276
100
1 or 2
L-N * 800 180
L-G ** 700 180
N-G *** 700 180
TE15XAS##
ST15XAS##
254/127 60 S
L-L 1200
20
300
100
1 or 2
L-N * 1200 320
L-G ** 1200 320
N-G *** 1200 320
TE18XAS##
ST18XAS## 480/277 60 S
L-L 2000
20
552
200
1 or 2
L-N * 700 150
L-G ** 700 150
N-G *** 700 150
TE02XAS##
ST02XAS## 208/120 60 Y
L-L 1200
20
276
200
1 or 2
L-N * 800 180
L-G ** 700 180
N-G *** 700 180
TE21XAS##
ST21XAS## 220/127 60 Y
L-L 1200
20
300
100
1 or 2
L-N * 700 150
HL-N 1200 320
L-G ** 700 150
HL-G 1200 320
N-G *** 700 150
L-L 1800 320
TE03XAS##
ST03XAS## 240/120 60 H
HL-L 1800
20
320
200
1 or 2
L-N * 1200 320
L-G ** 1200 320
N-G *** 1200 320
TE04XAS##
ST04XAS## 480/277 60 Y
L-L 2000
20
552
200
1 or 2
L-N * 1500 420
L-G ** 1500 420
N-G *** 1500 420
TE41XAS##
ST41XAS## 520/300 60 Y
L-L 2500
10
690
200
1 or 2
L-N * 1200 320
L-G ** 1200 320
N-G *** 1200 320
TE42XAS##
ST42XAS## 415/240 60 Y
L-L 2000
20
552
200
1 or 2
L-N * 1200 320
L-G ** 1200 320
N-G *** 1200 320
TE43XAS##
ST43XAS## 400/230 60 Y
L-L 2000
20
552
200
1 or 2
## - May be replaced by 10, 15, 20, 25 or 30.
* - Not available with option “L”.
** - Not available with option “G”.
*** - Not available with option “N”.
File E321351 Vol. 1 Sec. 1 Page 19 Issued: 2009-09-17
and Report
ELECTRICAL AND VOLTAGE PROTECTION RATINGS: (CONT’D) [7 mode, no disconnect, XW modules]
Cat. No.
Rated
Voltage
(V ac)
Freq
(Hz) Phase Mode
VPR
(Vpk)
In
(kA)
MCOV
(V
ac)
SCCR
(kA)
Intended
End-Use
SPD
Type
L-N * 700 150
L-G ** 600 150
N-G *** 600 150
TE01XAS##
ST01XAS## 240/120 60 S
L-L 1000
20
276
100
1 or 2
L-N * 800 180
L-G ** 700 180
N-G *** 700 180
TE15XAS##
ST15XAS##
254/127 60 S
L-L 1200
20
300
100
1 or 2
L-N * 1200 320
L-G ** 1000 320
N-G *** 1200 320
TE18XAS##
ST18XAS## 480/277 60 S
L-L 1800
20
552
200
1 or 2
L-N * 700 150
L-G ** 600 150
N-G *** 600 150
TE02XAS##
ST02XAS## 208/120 60 Y
L-L 1000
20
276
200
1 or 2
L-N * 800 180
L-G ** 700 180
N-G *** 700 180
TE21XAS##
ST21XAS## 220/127 60 Y
L-L 1200
20
300
100
1 or 2
L-N * 700 150
HL-N 1200 320
L-G ** 600 150
HL-G 1000 320
N-G *** 600 150
L-L 1500 320
TE03XAS##
ST03XAS## 240/120 60 H
HL-L 1500
20
320
200
1 or 2
L-N * 1200 320
L-G ** 1000 320
N-G *** 1200 320
TE04XAS##
ST04XAS## 480/277 60 Y
L-L 1800
20
552
200
1 or 2
L-N * 1500 420
L-G ** 1500 420
N-G *** 1500 420
TE41XAS##
ST41XAS## 520/300 60 Y
L-L 2500
20
690
200
1 or 2
L-N * 1200 320
L-G ** 1000 320
N-G *** 1200 320
TE42XAS##
ST42XAS## 415/240 60 Y
L-L 1800
20
552
200
1 or 2
L-N * 1200 320
L-G ** 1000 320
N-G *** 1200 320
TE43XAS##
ST43XAS## 400/230 60 Y
L-L 1800
20
552
200
1 or 2
## - May be replaced by 31, 40, 45 or 50.
* - Not available with option “L”.
** - Not available with option “G”.
*** - Not available with option “N”.
File E321351 Vol. 1 Sec. 1 Page 34 Issued: 2009-09-17
and Report
Additional Details Regarding Electrical Ratings:
PHASE: Y – Wye, H – Hi-Leg Delta, D – Delta, S – Split
AMPERAGE: NA – Not Applicable for One Port SPDs not intended to carry load
current.
Mode(s) — Refers to the pair of electrical connections where the VPR applies.
The term "ALL" indicates that the VPR applies to all combinations of pairs of
electrical connections.
In: Nominal Discharge Current Rating in amps or kA - for Type 1 and 2 SPDs.
NA – Not Applicable, Optional for Type 3 SPDs.
Voltage Protection Rating (VPR) — A rating (VPR) has been assigned to each
mode of protection. The value of the VPR is determined as the nearest
highest value taken from Table 63.1 in UL 1449 to the measured limiting
voltage determined during the transient-voltage surge suppression test using
the combination wave generator at a setting of 6 kV, 3 kA.
MCOV: Maximum Continuous Operating Voltage Rating in volts - for Type 1 and 2
SPDs.
SCCR: Short-Circuit Current Rating in amps or kA - for Type 1 and 2 SPDs.
TECHNICAL CONSIDERATIONS (NOT FOR FIELD REPRESENTATIVE’S USE):
These surge protective devices have been investigated with respect to
electrical, fire and shock hazards only.
These surge protective devices been tested to verify that transient voltage
surges are limited to maximum amplitudes specified by the manufacturer when
subjected to a 1.2 by 50 s, 6 kV peak and an 8.0 by 20 s, 3 kA surge, and
that they can withstand 15 impulses at 20 kA surge current and continue
normal operation. These devices have been tested to withstand 200 kA or 100
kA (per Ratings Tables) of available RMS fault current.
Type 1 SPD — Permanently connected SPDs intended for installation between the
secondary of the service transformer and the line side of the service
equipment overcurrent device, as well as the load side, including watt-hour
meter socket enclosures and intended to be installed without an external
overcurrent protective device.
Type 2 SPD — Permanently connected SPDs intended for installation on the load
side of the service equipment overcurrent device, including SPDs located at
the branch panel.
Nov 10. RevB
10 YEAR LIMITED WARRANTY
Advanced Protection Technologies, Inc. warrants panel protection products against defective workmanship and materials for 10 years. Liability is limited to the replacement of the defective product. A Return Authorization (RA#) must be given by the company prior to the return of any product. Returned products must be sent to the factory with transportation charges prepaid. In addition, the company also warrants unlimited replacements of modular and component parts within the warranty period previously described. The company specifically disclaims all other warranties, expressed or implied. Additionally, the company will not be responsible for incidental or consequential damages resulting from any defect in any product or component thereof.
Advanced Protection Technologies, Inc. Clearwater, Florida