25
Shelter at Railway Stations and Interchanges T MU SS 90002 ST Standard Version 1.0 Issued date: 28 July 2015 Important Warning This document is one of a set of standards developed solely and specifically for use on public transport assets which are vested in or owned, managed, controlled, commissioned or funded by the NSW Government, a NSW Government agency or a Transport Agency (as defined in the Asset Standards Authority Charter). It is not suitable for any other purpose. You must not use or adapt it or rely upon it in any way unless you are authorised in writing to do so by a relevant NSW Government agency. If this document forms part of a contract with, or is a condition of approval by a NSW Government agency, use of the document is subject to the terms of the contract or approval. This document may not be current. Current standards are available for download from the Asset Standards Authority website at www.asa.transport.nsw.gov.au. © State of NSW through Transport for NSW

Shelter at Railway Stations and Interchanges · Shelter at Railway Stations and Interchanges ... • define the specific ... is a vehicle that operates on or uses a railway, and includes

  • Upload
    lediep

  • View
    223

  • Download
    3

Embed Size (px)

Citation preview

Shelter at Railway Stations and Interchanges

T MU SS 90002 ST

Standard

Version 1.0

Issued date: 28 July 2015

Important Warning This document is one of a set of standards developed solely and specifically for use on public transport assets which are vested in or owned, managed, controlled, commissioned or funded by the NSW Government, a NSW Government agency or a Transport Agency (as defined in the Asset Standards Authority Charter). It is not suitable for any other purpose. You must not use or adapt it or rely upon it in any way unless you are authorised in writing to do so by a relevant NSW Government agency. If this document forms part of a contract with, or is a condition of approval by a NSW Government agency, use of the document is subject to the terms of the contract or approval. This document may not be current. Current standards are available for download from the Asset Standards Authority website at www.asa.transport.nsw.gov.au. © State of NSW through Transport for NSW

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

Standard governance

Owner: Lead Stations and Buildings Engineer, Asset Standards Authority

Authoriser: Chief Engineer Rail, Asset Standards Authority

Approver: Director, Asset Standards Authority on behalf of the ASA Configuration Control Board

Document history

Version Summary of Changes

1.0 First issue

For queries regarding this document, please email the ASA at [email protected] or visit www.asa.transport.nsw.gov.au

© State of NSW through Transport for NSW

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

Preface The Asset Standards Authority (ASA) is an independent unit within Transport for NSW (TfNSW)

and is the network design and standards authority for defined NSW transport assets.

The ASA is responsible for developing engineering governance frameworks to support industry

delivery in the assurance of design, safety, integrity, construction, and commissioning of

transport assets for the whole asset life cycle. In order to achieve this, the ASA effectively

discharges obligations as the authority for various technical, process, and planning matters

across the asset life cycle.

The ASA collaborates with industry using stakeholder engagement activities to assist in

achieving its mission. These activities help align the ASA to broader government expectations

of making it clearer, simpler, and more attractive to do business within the NSW transport

industry, allowing the supply chain to deliver safe, efficient, and competent transport services.

The ASA develops, maintains, controls, and publishes a suite of standards and other

documentation for transport assets of TfNSW. Further, the ASA ensures that these standards

are performance-based to create opportunities for innovation and improve access to a broader

competitive supply chain.

This standard describes the requirements for shelter at railway stations and interchanges.

This document should be read in conjunction with the remainder of the five-volume RailCorp

standards relating to station design standard requirements as follows:

• ESB 000 Introduction

• ESB 001 Design Context and Process

• ESB 002 Design Principles

• ESB 003 Station Functional Spaces

• ESB 004 Station Services and Systems

This standard has been prepared by the ASA in consultation with other TfNSW divisions and

agencies, and is a first issue.

© State of NSW through Transport for NSW Page 3 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

Table of contents 1. Introduction .............................................................................................................................................. 5

2. Purpose .................................................................................................................................................... 5 2.1. Scope ..................................................................................................................................................... 5 2.2. Application ............................................................................................................................................. 5 3. Reference documents ............................................................................................................................. 6

4. Terms and definitions ............................................................................................................................. 7

5. Shelter functional design considerations ............................................................................................. 8 5.1. Customer comfort and safety................................................................................................................. 8 5.2. Whole-of-life costs ................................................................................................................................. 9 5.3. Operational reasons for shelter ............................................................................................................. 9 5.4. Reduction of safety risk factors ........................................................................................................... 10 5.5. Design life ............................................................................................................................................ 11 5.6. Structural design requirements ............................................................................................................ 11 6. Shelter locations .................................................................................................................................... 12

7. Lateral extent of shelter ........................................................................................................................ 13 8. Station shelter design requirements ................................................................................................... 13 8.1. Shelter function .................................................................................................................................... 14 8.2. Shelter and structure clearances ......................................................................................................... 14 8.3. Station shelter clearance from platform edge ...................................................................................... 14 8.4. Shelter design aesthetics ..................................................................................................................... 19 8.5. Other design requirements .................................................................................................................. 19 8.6. Shelter design aesthetics ..................................................................................................................... 22 9. Related factors in shelter design ......................................................................................................... 22

10. Wind breaks ........................................................................................................................................... 24

11. Earthing and bonding ........................................................................................................................... 25

© State of NSW through Transport for NSW Page 4 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

1. Introduction This standard identifies the design considerations to achieve public comfort and safety

performance requirements for effective shelter at railway stations and interchanges.

2. Purpose The purpose of this standard is to achieve the following:

• identify the risks to the public caused by various aspects of the weather at railway stations

and interchanges

• identify benefits and limitations in mitigation of these risks

• define an overall approach to shelter for customers at railway stations and interchanges

• define the specific design parameters which shall be considered in the design of shelter

• define related work which shall be done when providing shelter

2.1. Scope This standard covers shelter in the following areas:

• shelter at railway stations on electrified and non-electrified lines

• shelters for taxi ranks, bus stops, and 'kiss and ride' areas associated with a transport

interchange

• shelters at or adjacent to train station buildings

Dedicated shelters for taxi ranks, bus stops, ferry wharves and other transport modes not

associated with train stations are not included within the scope of this document.

2.2. Application This standard is intended for use by suitably qualified professional engineers, architects and

designers of train stations and associated facilities.

This standard applies to shelters in the Metropolitan Rail Area.

This standard does not apply to the following:

• Sydney light rail passenger stations

• passenger train stations not in public use

• railway access points, used only by staff including maintenance facilities, sidings and yards

• shelters associated with freight facilities

© State of NSW through Transport for NSW Page 5 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

• enclosed rooms

3. Reference documents The following documents are cited in the text. For dated references, only the cited edition

applies. For undated references, the latest edition of the referenced document applies.

International standards

ASTM E903-12 Standard Test Method for Solar Absorption, Reflectance, and Transmittance of

Materials Using Integrating Spheres

Australian standards

AS 1170 Structural design actions (all parts)

AS 1657 Fixed platforms, walkways, stairways and ladders - Design, construction and

installation

AS 3600 Concrete structures

AS 4100 Steel structures

Transport for NSW standards

EP 12 10 00 21 SP Low Voltage Installations Earthing

ESB 000 Introduction

ESB 001 Design Context and Process

ESB 002 Design Principles

ESB 003 Station Functional Spaces

ESB 004 Station Services and Systems

T HR EL 12002 GU Electrolysis from Stray DC Current

SPC 301 Structures Construction

Legislation

Heritage Act 1977

Other reference documents

Office of Environment and Heritage, State Agency Heritage Guide – Management of Heritage

Assets by NSW Government Agencies, publication number HO05/01

National Construction Code Series

© State of NSW through Transport for NSW Page 6 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

4. Terms and definitions The following terms and definitions apply in this document:

AEO Authorised Engineering Organisation

CPTED crime prevention through environmental design

ASTM American Society for Testing and Materials

intermodal transfer a point of transfer from one mode of transport to another, such as bus to

train or taxi to train

Metropolitan Rail Area is the area bounded by Newcastle (in the north), Richmond (in the

northwest), Bowenfels (in the west), Macarthur (in the southwest) and Bomaderry (in the south),

and all connection lines and sidings within these areas, but excluding private sidings.

possession closure of one or more lines to allow work to be carried out in the Danger Zone

using a Local Possession Authority (LPA) or a Track Occupancy Authority (TOA)

rain shadow the dry area in the lee side of a roof, canopy or screen in the path of rain-bearing

winds

rolling stock is a vehicle that operates on or uses a railway, and includes a locomotive,

carriage, rail car, rail motor, light rail vehicle, train, tram, light inspection vehicle, self-propelled

infrastructure maintenance vehicle, trolley, wagon or monorail vehicle, but does not include a

vehicle designed to operate both on and off a railway when the vehicle is not operating on a

railway

SFAIRP so far as is reasonably practicable

structure gauge a defined envelope around the track, within which no structure is permitted

superelevation the difference in level between the two rails of a track on a curve

swept path the maximum three dimensional volume taken up by a specified rolling stock outline

(including rolling stock tolerances) as it moves along a track at specified track tolerances,

through design curves, transitions etc. Similarly, this term can also apply to the path of road

vehicles (such as buses) on roads.

transit space a clearance envelope that provides for the safe passage of defined rolling stock

and for infrastructure service requirements; the envelope is defined by a transit space outline

referred to as 'structure gauge'

TfNSW Transport for New South Wales

© State of NSW through Transport for NSW Page 7 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

5. Shelter functional design considerations The primary function of shelter is to provide protection from the weather.

The following factors shall be considered when providing shelter:

• customer comfort and safety

• whole-of-life costs

• transport network operations

• accessibility and circulation

• safety and risk including crime prevention through environmental design (CPTED)

requirements and security

• design life

• structural design requirements

• aesthetic appearance of shelter in relation to environmental surroundings

• compliance with the National Construction Code and relevant legislation

5.1. Customer comfort and safety A full demographic cross-section shall be considered in shelter design including age and

mobility.

At any given location and for the particular scope of work, designers shall exercise a

professional duty of care to passengers to ensure that shelters are safe and secure.

Designers shall pursue the aim of ensuring a high level of customer comfort consistent across

the transport network. Determining the degree of discomfort will depend on whether customers

and the public are stationary or moving, and the length of time spent waiting for transport.

Where appropriate, canopy designs shall provide adequate space to accommodate shelter for

luggage, prams and mobility aids.

Shelter structures above and adjacent to equipment for customer and public use, such as at

integrated ticket scanners, vending machines, help points, escalators and stairs can encourage

use of these facilities as well as provide comfort and protection while they are being used.

Adequate shelter shall be provided for static activities such as queuing, waiting for lifts, or using

vending machines.

© State of NSW through Transport for NSW Page 8 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

5.2. Whole-of-life costs The designer shall optimise the provision of shelter to provide value for money for the whole of

the asset life cycle.

All aspects of maintainability shall be considered including access for periodic maintenance,

cleaning, component inspection, replacement, painting, and on-going maintenance. Shelter

design should aim to optimise capital and maintenance costs by ensuring all performance

requirements at the minimum comparative life cycle cost. In general, this will mean providing

relatively simple shelter in form and detail, without skylights or glazing.

Refer to Section 8.5.3 for further information on maintenance requirements.

An acceptable design will ensure satisfaction of all the performance criteria over the design life

of the asset.

5.3. Operational reasons for shelter The following are possible operational reasons for providing shelter:

• protection of equipment and servicing

• encouraging particular behaviours

5.3.1. Protection of equipment, its use and servicing

Equipment such as vending machines, escalators, air conditioning components and passenger

information systems can be vulnerable to malfunction, lack reliability, and require greater

maintenance if exposed to the weather.

Equipment shall be adequately protected to ensure high reliability and minimum life cycle costs.

Any power, data, water supply, drainage or related plant serving such equipment will similarly

make the operation of equipment vulnerable and shall also be adequately protected.

Shelters can provide protection to persons who service such equipment. The location of access

points and vulnerability of the equipment during servicing or replenishment shall be included in

shelter design.

5.3.2. Encouraging particular behaviours Shelter can encourage people to congregate or spread out. For example, extensive canopy

coverage can encourage customers to spread along the platform to more doors of the train,

which can in turn affect train dwell times. Similarly, in other crowd situations, congestion can be

alleviated by providing alternative sheltered locations for customers to use.

© State of NSW through Transport for NSW Page 9 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

Canopies and wind breaks can encourage people to gravitate to areas where seating or

protection from direct sunlight, glare and inclement weather is provided. Potential discomfort is

thereby minimised.

5.4. Reduction of safety risk factors Shelter can help reduce safety risks related to weather and crowd movement. For reasons of

safety, designs for shelters shall take into account the requirements for maintaining good visual

surveillance and the need to avoid creating places of concealment and climbable structures.

5.4.1. Risk from weather Shelter structures that give protection from the sun, glare, wind, rain and snow will eliminate or

reduce some safety risk factors in addition to providing a level of human comfort. For example,

adequate shelter can help mitigate the risk of slips, trips and falls, given that wet surfaces can

contribute to this risk particularly where other risk factors are present.

Elements of weather vary in different geographic locations or exposures, and shall be

adequately considered by the designer for the particular location.

Expected climatic conditions at a station shall be considered. Climatic conditions include

annual, seasonal, monthly as well as diurnal climatic averages, statistical distribution

(maximums and minimums), the frequency, intensity and direction of potential extremes of

weather and local microclimate. Obtain information available from the Bureau of Meteorology to

ensure designs allow adequate protection.

Section 10 contains specific information relating to wind breaks.

5.4.2. Risk from crowd movement Crowding reduces the pace and freedom of movement of individuals, restricts visibility,

contributes to a feeling of disorientation, and heightens dependency on the directional

movement of others. These effects are amplified with increasing crowd density, and can reach

high levels during an emergency or in extraordinary situations. Factors which can affect crowd

safety in these situations should be avoided or at least mitigated. Providing shelter can help to

reduce risk, and may be appropriate where potential crowding can be predicted, subject to an

overall risk assessment.

Where potential for crowding exists along a path of travel, the consistency of mitigating

particular aspects of risk can also be an important factor in mitigating overall risk. Continuity of

shelter, where crowding risk exists, should be considered by risk assessment.

© State of NSW through Transport for NSW Page 10 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

5.5. Design life All structural elements, including the following, shall be designed to have a minimum life of

50 years:

• footings and slabs

• columns, posts and beams

• rafters and trusses

• structural fixings

All cladding and attachments, including the following, shall be designed to have a minimum life

of 25 years:

• purlins and connections

• roof sheeting, walling and associated screens

• gutters and downpipes

• above ground services, services elements, distribution and support systems

Subject to meeting their functional requirements, shelter elements with greater durability and

maintainability associated with longer life, offer better value for money and a perception of

permanence. They tend to minimise potential disruption to transport services and the travelling

public due to required repairs, replacement and maintenance.

Life cycle costing of the shelter elements related to overall options shall be undertaken and

considered on a cost benefit basis to justify selections at appropriate points in the design

process.

5.6. Structural design requirements Structural design shall comply with relevant Australian standards including the following:

• AS 1170 Structural Design Actions

• AS 3600 Concrete Structures

• AS 4100 Steel Structures

Design loads are specified in Section 9 of this document.

Structural elements shall be made from steel or concrete.

Timber shall not be used for structural elements.

The design, construction and documentation of shelter structures shall comply with SPC 301

Structures Construction.

© State of NSW through Transport for NSW Page 11 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

6. Shelter locations The minimum extent of shelter shall be determined by the station classification and particular

station constraints.

Provide shelter by means of a roof and secondly, if required, by means of vertical screening.

Where appropriate, provide shelter at the following locations:

• At points where wet weather can increase the risk of slips, trips and falls.

• At points of congestion in pedestrian flow where passengers' sightlines to see a hazard on

the walking surface may be restricted. For example, the provision of shelter over stairs and

ramps or other vertical transportation elements where ascending or descending, at

landings and crowd accumulation points at the tops and bottoms of stairs and ramps, or at

changes of direction, or where funnelling congestion slows pedestrian flow.

• At points where weather can affect the operation, life or reliability of mechanical plant

associated with pedestrian movement. For example, over escalators or travelators, or

where water might overflow or leak into moving machinery, lift shafts, or machinery pits

containing associated equipment.

• At customer queuing or waiting areas where passengers may have to pause or wait for

various reasons. For example, areas such as ticket windows, ticket and commercial

vending machines, lift entries, decision points where information is provided and needs to

be read and understood or where staff hubs provide information.

• At ticket verification and validation points where there are ticket barriers (for the protection

of customers queuing and protection of the equipment) or at smartcard ticketing tap on and

tap off locations and top up machines.

• At entry points to sheltered areas to provide a transition and prevent the 'walking in' of

external hazards such as water on feet or other contaminants, thereby reducing the risk of

those contaminants causing slips, trips and falls.

• At boarding zone locations adjacent to train doors. Safe and comfortable boarding and

alighting from the train occurs to the extent required by the station classification or specific

station configuration.

• To provide continuous pedestrian flow to facilitate a safe and continuous pedestrian route

from one area to another. This may be to join the abovementioned areas, or provide a

discreet path in its own right. The numbers and frequency of use of a route may determine

the need for the provision of shelter.

• At intermodal and inter-service transfer precincts to provide effective and safe connection

between adjacent transport services and modes.

Refer to Section 7 for information on the lateral extent of shelter. © State of NSW through Transport for NSW Page 12 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

7. Lateral extent of shelter Wind-blown rain can contribute to safety risk, as well as provide discomfort. Where not

constrained by the design requirements and clearance dimensions, wind-blown rain shall dictate

the lateral extent of canopies.

A combination of shelter elements shall protect customers from wind-blown rain to form a rain

shadow appropriate to a particular location, exposure and orientation. Where this is not known

and cannot be discovered, use a minimum angle of incidence to the horizontal of 65 ° projected

upwards from the extent of the path to be covered at pedestrian foot level. Figure 1 illustrates

the 65 ° rain shadow protection.

Dry area65°

Stair widthor

pedestrian route

Canopy

65°

Wet area

Wind driven rain

Wet area

Figure 1 – Canopy rain shadow

Shelter for stairs, station entrances and pedestrian routes through stations may require an

extended canopy overhang, fully enclosed sides or partially enclosed sides.

Refer to Section 8.3 for information relating to shelter structures and clearances.

8. Station shelter design requirements Station shelter includes all canopies of the railway transport interchange. Canopies and wind

breaks are the primary building elements of shelter.

Considerations for canopy design include the following:

• shelter function

• nature of prevailing weather conditions

• shelter and structure clearances

• pedestrian flows

• shelter design aesthetics

© State of NSW through Transport for NSW Page 13 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

• any other functional or statutory requirement appropriate to the particular location

Refer to Section 9 for information regarding shelter design.

8.1. Shelter function The primary goal for canopy design is to provide shelter from weather and in doing so, satisfy all

the stated functional requirements, including providing value for money over the whole of the

asset life cycle.

8.2. Shelter and structure clearances Shelter structures and their support elements require specific clearances to the following station

elements and nearby related features:

• platform edge (edge of coping)

• vertical to platform or footpath including required clearances to attached elements such as

suspended indicator panels and wayfinding signage

• stairs

• intermodal transfer facilities including car parks

• bus stops, taxi stands, and kiss and ride facilities

• accessible path

• overhead wiring structures

Additionally, adequate clearances shall be maintained between shelters and existing trees to

prevent access onto the roof of shelter via overhanging branches, and avoid potential damage

to assets from branch contact or gutters filling with twigs and leaves.

8.3. Station shelter clearance from platform edge Structural columns and supports for roofs, canopies and wind screens shall have the minimum

clearance of 3300 mm from the platform edge to maintain the statutorily required unobstructed

accessible path on the platform. A dimension of 3500 mm is preferred.

The leading edge of a canopy structure on a straight platform shall not be less than 400 mm

from the vertically projected line of the edge of the platform, with the required vertical clearance.

Figure 2 shows the setback for the leading edge of a canopy in relation to the platform edge and

the canopy clearance envelope.

Figure 3 illustrates the setback for a straight platform where there is no track superelevation.

© State of NSW through Transport for NSW Page 14 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

CANOPY SET BACK FOR HEIGHTS ABOVE 3000 mm SHALL BE UNDERTAKEN IN CONSULTATION WITH COMPETENT TRACK AND OVERHEAD WIRING ENGINEERS

3000

max

.

SET BACK

2400

2400 MINIMUM CLEARANCE HEIGHT FOR PLATFORM INFORMATION, FIXTURES AND ATTACHMENTS

INDICATORS

Figure 2 - Canopy structure envelope and clearance set back from platform edge

CANOPY STRUCTURE ENVELOPE

CL

SET BACK400

© State of NSW through Transport for NSW Page 15 of 25

Figure 3 - Straight platform – no superelevation

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

The platform edge clearance shall be varied in the following circumstances:

• where the platform is curved and the superelevation causes the train lean into (convex), or

away (concave) from the platform

• where the leading edge of the canopy to the platform obstructs vision to train signals

No antennae or any other attached fixtures shall project beyond the leading edge of a canopy

structure into the setback zone from the platform edge.

Figure 4 illustrates the setback for the leading edge of a canopy on a convex platform with

positive superelevation.

Figure 5 illustrates the setback for the leading edge of a canopy on a concave platform with

negative superelevation.

CANOPY STRUCTURE ENVELOPE

SUPE

R E

LEVA

TIO

N

(+)V

E

CL

SET BACK

© State of NSW through Transport for NSW Page 16 of 25

Figure 4 - Convex platform – positive superelevation

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

CANOPY STRUCTURE ENVELOPE

SUPE

R E

LEVA

TIO

N

(-)VE

CL

SET BACK

© State of NSW through Transport for NSW Page 17 of 25

Figure 5 - Concave platform – negative superelevation

8.3.1. Calculating setback for the leading edge of a platform canopy

The setback for a canopy is the horizontal offset dimension from the platform edge to the

leading edge of the canopy structure. Figure 2 illustrates the setback.

Setback = 400 mm + superelevation factor

Superelevation factor = ± 1.6 × superelevation at the location along the platform

A positive superelevation causes rolling stock to lean towards the platform. This will increase

the setback dimension to greater than 400 mm; positive superelevation occurs adjacent to

convex platforms.

A negative superelevation causes rolling stock to lean away from platform. This will decrease

the setback dimension to less than 400 mm; negative superelevation occurs adjacent to

concave platforms.

Superelevation varies along the track and can be obtained from the regional track surveyor of

the AEO responsible for the track configuration.

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

An example calculation for the setback required for a canopy structure on a convex platform is

provided as follows:

Setback = 400 mm + 1.6 × 75 mm superelevation

= 520 mm

Similarly an example calculation for the setback required for a canopy structure on a concave

platform is as follows:

Setback = 400 mm - 1.6 × 50 mm superelevation

= 320 mm

Refer to Section 13 of ESC 215 Transit Space for safe clearances for track.

8.3.2. Station canopy or attachments vertical clearance Above platforms and on concourses and ramps, the lowest point of any component on the

underside of any canopy structure or finished soffit, shall be 2700 mm above platform or floor

level. This includes permanent components such as gutters and downpipes.

Above stairs, the underside of a finished canopy soffit or exposed structure shall have a

minimum height, measured vertically above the finished stair nosings of 2700 mm.

Any passenger information system or other fittings, elements and equipment that are likely to be

attached to the underside of a canopy shall have a minimum clear height above the finished

platform or floor level of 2400 mm. Equipment can include indicators, station passenger

information (SPI) panels, clocks, light fittings, public address (PA) system speakers, closed

circuit television (CCTV) cameras or cable trays.

When setting the height of the canopy structure and finishes, the vertical clearances shall

include provision for all likely or possible future attached elements.

The minimum heights are to ensure that all fixed items are beyond the normal reach of vandals.

In large spaces, it may be necessary to increase these minimum heights to prevent spaces

becoming visually oppressive.

8.3.3. Canopy horizontal clearance at bus, taxi, kiss and ride facilities Where a canopy at a bus stop, taxi rank or kiss and ride facility does not pass over the top of

the vehicles, the leading edge of the canopy shall be set back by a minimum of 600 mm from

the edge of the road kerb. A dimension of 800 mm is however preferred.

The clearance dimension may need to be increased at curved kerbs to allow for the sweep

paths of the front and rear overhangs of buses manoeuvring out of parking locations in order to

prevent the vehicles coming into contact with shelter fascias, eaves or downpipes.

© State of NSW through Transport for NSW Page 18 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

8.3.4. Accessible path support structure clearances

Structural columns and supports should be located clear of desired paths and away from natural

pedestrian paths.

The roof and canopy design shall minimise structural obstructions to pedestrians on platforms.

Refer to Section 8.4 for information relating to station shelter clearance.

8.3.5. Line of sight Structural columns and supports shall not restrict vision to SPI panels or vision for CCTV

cameras, guard indicator lights or signals.

8.3.6. Clearance from overhead wiring structures Canopy structures shall have a minimum 2000 mm vertical or horizontal clearance to overhead

wiring (OHW) structures unless alternative touch potential protection is provided. Clearances

from high voltage overhead cables shall comply with AS 7000.

T HR EL 00004 ST Buildings and Structures under Overhead Lines outlines TfNSW

requirements for buildings and structures under overhead lines within and outside the rail

corridor.

T HR EL 08001 ST Safety Screens and Barriers for 1500 V OHW Equipment provides details of

clearance envelopes associated with 1500 V traction power equipment.

8.4. Shelter design aesthetics Shelter design shall be integrated into the overall design concept of the public areas, their

function and the station classification. The design shall consider scale, spatial volume and form,

aesthetic character, materials, colour, as well as performance constraints. Achievement of a

particular aesthetic shall not be to the detriment of the achievement of the shelter’s functional

purposes.

8.5. Other design requirements Other specific shelter design requirements include the following:

• thermal performance, including impact of solar heat loads during summer

• canopy drainage

• maintenance considerations including bird proofing of shelter structures

• heritage considerations

• optimisation of shade

© State of NSW through Transport for NSW Page 19 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

8.5.1. Thermal performance

Canopy roofs shall not radiate heat to provide an environment more uncomfortable than if a

canopy were not provided. Specifically, metal roof canopies shall have a light coloured roof with

a solar absorbance factor not greater than 0.43 measured in accordance with ASTM E903-12

Standard Test Method for Solar Absorption, Reflectance, and Transmittance of Materials Using

Integrating Spheres.

Canopy roofs shall be designed to prevent condensation. Condensation can cause nuisance

dripping and compromise the life of materials and finishes.

8.5.2. Canopy drainage considerations Canopy drainage design shall integrate downpipes with canopy structure and footings to avoid

protrusions and trip hazards. Box gutters should (preferably) be avoided.

Maintenance access shall be provided at platform level where downpipes discharge to drains.

Water discharge from the canopy stormwater drainage system shall be captured and kept

separate from track drainage, given the safety critical nature of the latter.

Drainage design should provide the following:

• adequate gutters, downpipes, sumps, connected discharge pipes and junction for 100 year

weather events

• protection of downpipes from impact load and damage by vandals, or select materials to

withstand impact loads and vandalism

• overflow or alternative drainage points at gutters

• eaves gutters, but only where they can be cleaned out, in the event of an emergency,

without a possession

• sump and gutter guards to prevent the accumulation of leaves and other rubbish in gutters

valleys or high level sumps

• access for regular gutter maintenance from platform level without the need for roof access

or possessions

• provision of ladder brackets where other forms of maintenance access are not available

• canopies over stairs shall not extend more than one flight without the provision of

intermediate gutters

Collection of rainwater for storage and reuse in grey water applications shall be considered

where practicable. Using gravity-fed systems will assist to make this more viable. Mechanical

pump systems that require maintenance should be avoided.

© State of NSW through Transport for NSW Page 20 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

Sufficient drainage shall be provided to move water away from customer areas and to ensure

no ponding occurs at shelter locations. Surface gradients shall be altered where practicable to

prevent water flowing under canopies.

Canopy structures, fascias and supports shall be provided with flashings, drip moulds or

grooves where necessary to prevent water running down the structure to the platform.

8.5.3. Maintenance considerations Shelter structures shall be designed to minimise the need for maintenance.

There are established safety clearances from the overhead wiring and transit space clearances

that cannot be infringed without a track possession. Wherever possible, platform canopies shall

be designed with sufficient safety clearances (for example, from overhead wires and

pantographs) such that periodic maintenance of canopy elements can occur without the need

for a possession. Required safety clearances from aerial power cables are specified in AS 7000

(clause 3.11).

Where access to radio masts is needed, access hatches, attached ladders and platforms that

comply with AS 1657 Fixed platforms, walkways, stairways and ladders - Design, construction

and installation shall be used.

8.5.4. Heritage Transport agencies are responsible for maintaining and appropriately managing heritage items

under their stewardship and control.

The Heritage Act 1977 is designed to protect, maintain and manage environmental heritage in

NSW, including items of archaeological significance.

When changes are proposed to items that have heritage significance, the following applies:

• for items listed on the State Heritage Register, the provisions of the Heritage Act shall be

met

• for items listed on a state agency Section 170 Heritage and Conservation Register, the

principles and relevant guidelines contained within the State Agency Heritage Guide shall

be followed

The identified significance of a particular item or precinct, as well as its contributory elements

and values shall not be unduly compromised by any new works. Identifying the significant

features, values and characteristics of a heritage item or precinct is an essential step in

developing appropriate designs for new elements including shelters and canopies at heritage

listed stations.

© State of NSW through Transport for NSW Page 21 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

Advice from a professional heritage practitioner shall be obtained early in a project's scoping

and design stage to assess any potential heritage impacts, and to guide the nature and extent

of all proposed works including new shelter structures.

The likely heritage impacts of shelters and canopies proposed to be erected within the vicinity of

existing heritage items shall be identified.

Designs for new shelters and canopies at heritage listed stations shall be developed in

consultation with the relevant approval authorities, including the nominated operator and

maintainer or the regulatory authority. Consultation with local community groups may also be

warranted for new shelters in particular locations.

Shelter and canopy design should demonstrate how identified heritage elements have been

considered in the design before the approved for construction stage.

The scale, form, bulk and character of new shelter structures should relate well to existing site

features and characteristics. Any new construction materials, finishes and colours should

complement those of existing buildings and structures.

Design considerations such as locating new canopies in less sensitive areas, maintaining a

physical separation between new works and significant building fabric and using materials that

clearly distinguish new built elements from existing fabric may be used to mitigate potential

adverse impacts on heritage items in order to maintain their significance.

8.6. Shelter design aesthetics Shelter design shall be integrated into the overall design concept of the public areas, their

function and the station classification. The design shall consider scale, spatial volume and form,

aesthetic character, materials, colour, as well as performance constraints. Achievement of a

particular aesthetic shall not be to the detriment of the achievement of the shelter’s functional

purposes.

9. Related factors in shelter design The following factors shall be demonstrated to have been adequately addressed as an integral

part of all canopy design:

• a comprehensive review of earthing, bonding and isolation requirements. Refer to

Section 12 for earthing and bonding requirements.

• roof access and fall protection systems shall be provided to roofs and canopies for periodic

and emergency maintenance from level areas for safe ladder access

• under-canopy lighting shall be designed and installed to provide required levels of

illumination in accordance with the law. Required lighting levels under a canopy are greater

© State of NSW through Transport for NSW Page 22 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

than for an open area (refer to ESB E001). Where practicable, light fittings should be

recessed in ceilings and soffits to minimise vandalism.

• bird and rodent-proofing shall be incorporated to prevent perching or nesting over or

around all public or customer spaces. The potential for birds to roost or nest should be

considered at the design stage so that the need to install spikes or wires at a later stage is

largely avoided.

• support of station systems, including SPI panels plus the weight of two maintenance

personnel, maintenance-related tools and replacement parts

• clearances and proximity to services distribution

• static signage support, clearances and visibility

• services distribution system

• location of structural supports with footing design to minimise (or avoid) obstructions and

trip hazards

• choice of simple and stable structural system with integrity and independence from

platform and station building structure

• visibility of all structural joints and column base plates to facilitate easy inspection

• choice of materials; materials shall be robust, vandal resistant and low maintenance

• choice of finishes; finishes should be tough and durable and conform to colour palette

guidelines

• shelter structures shall be designed to prevent them from being readily climbable or used

to climb onto other structures

• the following engineering design loads shall be considered in addition to the general live

and imposed loads:

o wind and potential snow loads

o seismic loads

o collision and crowd loads

o earthing and bonding

© State of NSW through Transport for NSW Page 23 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

10. Wind breaks A wind break is typically a vertical element that provides protection to passenger seating areas

from wind and wind-driven rain. Wind breaks may also provide protection to designated

wheelchair and pram parking positions as well as 'refuge' spaces for customers with disability.

Wind breaks shall be integrated with other required structures (canopies, seating, waste bins)

wherever possible, and may be introduced at designated safety zones on platforms.

Wind breaks shall be provided on platforms where any of the following conditions apply:

• average wind speed equal to or more than 30 km/h for 60% of the time during the morning

peak period

• for the months of June or July, the mean lowest temperature is less than 10 °C for a 24 h

period

Measured meteorological data shall be used to ascertain the prevailing weather conditions at

specific locations. Orientation of windbreaks should respond to local conditions.

Wind breaks shall have the following requirements:

• not impede passenger circulation paths or queuing areas

• allow for natural surveillance through the wind break. The use of plastic should be avoided,

and glass minimised where possible in order to reduce maintenance and replacement

costs. Glass shall comply with the rules for the use of glass in stations set out in ESB 003

• have a minimum height of 2000 mm

• be resistant to acts of vandalism

• comply with relevant codes and standards addressing glazing (when glazed vertical panels

are used in the design)

Refer to Section 5.4.1 for information relating to risk from weather.

© State of NSW through Transport for NSW Page 24 of 25

T MU SS 90002 ST Shelter at Railway Stations and Interchanges

Version 1.0 Issued date: 28 July 2015

11. Earthing and bonding An analysis of a proposed shelter structure, including roof canopy, shall be conducted to identify

earthing, bonding and isolation requirements and any pertinent safety issues.

It is imperative that an earthing and bonding design engineer is consulted at various stages of

the design process to ensure that safety hazards associated with earthing and bonding are

completely mitigated or minimised so far as is reasonably practicable (SFAIRP). Some of the

matters (the list is not exhaustive) that shall be considered in any analysis of the shelter

structure and associated canopy includes the following:

• proximity to overhead wiring structures

• areas where the shelter interfaces with other conductive structures and elements (such as

handrails and street lighting poles)

• transfer of hazard from one location to another due to continuity of the structure;

particularly where structures extend beyond the edge of a station platform

• construction under high voltage aerial lines

• low voltage systems and installations attached to the shelter (for example a lighting

system), or installed under it (for example, vending machines), or integrated in it (for

example, lifts)

Various methods can be used to achieve a safe design from an earthing and bonding

perspective. Refer to EP 12 10 00 21 SP Low Voltage Installations Earthing and

T HR EL 12002 GU Electrolysis from Stray DC Current for further information.

© State of NSW through Transport for NSW Page 25 of 25