CG Switchgear and ControlA Business Unit of Crompton Greaves Ltd.
TECHNOLOGY TO THE FORE
SWITCHGEARC O M P L E X
SF6-GAS CIRCUIT BREAKERSFOR OUT-DOOR USE UPTO 36kV
INTRODUCTIONMore than 9000 Crompton Greaves SF6 GasCircuit Breakers with puffer type interruptors upto420 kV have been put into service in variousenvironments in many countries since 1983 wherethey are operating satisfactorily.Type SFGP SF6 Circuit Breakers are of live tank typewith rated voltage of 24 & 36 kV. Each breakerconsists of three puffer type interruptors,providing a high insulation as well as an excellentbreaking capability, a spring operating mechanismensuring high operational reliability.All our SF6 Gas Breakers (24 to 420 kV) adhere tothe requirements of the quality standards and scopeof supply of ISO 9001, 1994.
FEATURESThese SF6 Gas Circuit Breakers are extremely simpleand compact in their design owing to the fact thatno gas blast valves or exhaust valves are requiredand the force of contact separation simultaneouslydrives the puffer piston, which builds up the gaspressure according to the contact stroke. The struc-tural simplicity results in high performancereliability and, therefore, minimal inspection andre-assembly. Also this ensures that themaintenance time is low. Inspection is simple andeasy since the interrupting medium, which is alsothe insulating medium, is monitored with easethrough clearly readable pressure gauges andmechanical as well as electrical interlocks.The breaker opens from front as well as backpanels to provide easy access to all parts of themechanism. The checking or replacing of fixed,moving or arc contacts and nozzle can be done byremoving only the upper terminal of the interruptorunit as and when required. This operation does notrequire the breaker to be dismantled and it takesonly a few hours to put the breaker back intoservice.The low operating noise level of the spring chargedoperating mechanism used in this breaker enablesits use in residential areas. All exposed ferrous partsare treated to give high corrosion resistance andare finally painted with polyurethane based paintensuring excellent finish and protection. The breakerhas been made extraordinarily simple and light toincrease safety in the event of earthquakes.
INTERRUPTER UNIT - FIG1
OPERATING MECHANISM - FIG2
TECHNOLOGY TO THE FORE
SWITCHGEARC O M P L E X
Exploded schematic view ofthe operating mechanism
Motor
Spur gear
Closing trigger
Roller
Closing latch
Plunger core (closing coil)
HookInterlock spring
Link
Closing cam
Cam rollerPlunger core (tripping coil)
Hook
Tripping trigger
Roller lever
Cam shaftCrank lever
Crank pin
Connectingrod
Push rod
Tripping latch
Latch arm
Closingspring
Eccentric crankshaft
Ratchet wheelPawls
Main shaft
Main-shaft lever
Roller
Tripping spring
Absorbent
Stationary contact holder
Stationary contact
Gas flowArc
Nozzel
Moving arc contact
Moving main contact
PistonPuffer cylinder
Main contact
Contact spring
TESTS AND PERFORMANCEThe performance and reliability of these breakers and their excellent interrupting capability has been verified at renownedinternational testing laboratories like CESI, Italy and CPRI, India. The breakers are type tested for short circuit duties and capacitivecurrent switching test as per IEC 56-1987
EASE OF INSTALLATIONSince these units are shipped in two parts - namely the pole unit and the mechanism - minimal site preparation is required and setuptime is very low.
DESIGNThe interrupting unit (FIG.1) is puffer type and is contained in a porcelain insulator and the terminals. During interruption the puffercylinder is quickly driven downwards with its attached parts by the operating mechanism (from the breaker "closed" position to thebreaker "open" position). The gas within the puffer cylinder is compressed by the piston and blown to the arc through the nozzleachieving arc extinction.The operating mechanism (FIG.2) is an easy to handle motor charged spring type. It also permits manual operation of the breaker. Highreliability has been ensured by keeping the number of components to a minimum and, therefore, maintenance required is easy andminimal.
GUARANTEED TECHNICAL PARTICULARS24 / 36 kV SF6 GAS CIRCUIT BREAKER
UNITS 24 kV 36 kV
1. TYPE REFERENCE : - 20-SFGP-25A 30-SFGP-25A 30-SFGP-40A2. RATED VOLTAGE : kV 24 363. RATED LIGHTNING IMPULSE WITHSTAND VOLTAGE : kVp 150 2004. RATED POWER FREQUENCY WITHSTAND : kV 60 805. CREEPAGE DISTANCE (TOTAL) : mm 600 9166. APPLICABLE STANDARDS : - IEC 56, BS 5311 & JEC 1817. TYPE OF MECHANISM : - SPRING CLOSING / TRIPPING8. RATED NORMAL CURRENT : A 1250, 1600, 20009. RATED SHORT CIRCUIT BREAKING CURRENT : kAp 25
10. RATED SHORT CIRCUIT MAKING CURRENT : kA 62.511. RATED OPERATING SEQUENCE : - O-0.3 sec-CO-15 sec-CO12. RATED FREQUENCY : Hz 50 / 6013. RATED BREAK TIME : ms 8014. RATED CLOSING TIME : ms 10015. RATED CLOSING / TRIPPING VOLTAGE : V 110 / 220 VDC16. CURRENT OF CLOSING / TRIPPING COIL : A 5 at 110 VDC17. FIRST POLE TO CLEAR FACTOR : - 1.518. RATED DURATION OF SHORT CIRCUIT : sec 319. RATED CABLE CHARGING BREAKING : A / pu 50, <2.5
CURRENT AND OVER VOLTAGE.20. RATED SINGLE CAPACITOR BANK BREAKING : A / pu 440, <2.5
CURRENT AND OVER VOLTAGE.21. RATED OUT OF PHASE BREAKING CURRENT : kA 6.25 1022. AUXILLIARY CONTACTS : - 5 NO + 5 NC23. SF6 GAS PRESSURE (AT 20 ºC)
-NORMAL : Kg / cm2 5-GAS FEED ALARM : Kg / cm2 4.5-LOCKOUT : Kg / cm2 4
OPTIONALS
1. CREEPAGE DISTANCE 25, 31, 35 mm / kV2. CLOSING / TRIPPING COIL VOLTAGE 24 / 30 / 60 / 110 / 125 / 220 VDC3. CLEARANCE OF LIVE PARTS TO GROUND AS PER CUSTOMER SPECIFICATION4. ALTITUDE ABOVE SEA LEVEL UPTO 2500 M5. AUXILLIARY CONTACTS 10 NO & 10 NC6. LIGHTNING IMPULSE WITHSTAND VOLTAGE 250 kVp7. EARTHQUAKE WITHSTAND (SEISMIC ACCELERATION) 0.3 g / 0.5 g
25 & 4062.5 & 100
6.25 & 10
The Thapar GroupCG-S&C/EXP/Cat.No.SF6-102/3/01/2000
Data subject to change
CG Switchgear and ControlA Business Unit of Crompton Greaves Ltd.
Switchgear ComplexA-3, MIDC, Ambad, Nashik - 422 010 IndiaTel: (+91) 253 382271 to 75 Ext 107/108/110Fax: (+91) 253 382219/381247E-mail: [email protected] (Exports)
[email protected] (General)URL: www.cgswgear.com
FOUNDATION PLAN DETAILS
DETAILS OF TERMINAL PAD(MATERIAL - AL, 22 THK)
GAS SYSTEM
GENERAL OUTLAY
1. INTERRUPTER2. SUPPORT PORCELAIN3. BASE FRAME4. MECHANISM HOUSING5. SUPPORT STRUCTURE
F
G
C
E
H
A A
B
D
1
2
3
4
5
FOUNDATION BOLT(M24×400) LOCATION250 50
80
4801100
450
900
Ø14, 4 HOLES
Ø15, 4 HOLES
1644.5 60
140
4040
40
150
44.5
15CO
ND
UC
TO
RS
IDE
BR
EA
KE
RS
IDE
DIMENSIONS (mm)
A B C D E F G H TOTAL WEIGHT (Kg)
20-SFGP-25A 600 1560 3349 680 1025 522 2783 502 675(24 kV)
30-SFGP-25A 750 1860 3819 680 1225 672 3103 502 750(36 kV)
30-SFGP-40A 750 1860 4079 680 1290 976 3103 502 750(36 kV)
A-Phase B-Phase C-Phase
Arcing column
Stop valve
Pressure gauge
Stop valveBlind cap
Temperaturecompensatedpressure switch
Gas pipe