SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL Model name <Indoor unit> Model name <Indoor unit> SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Series SEZ 2012 INDOOR UNIT WIRED REMOTE CONTROLLER ON/OFF TEMP. WIRELESS REMOTE CONTROLLER ON/OFF TEMP

SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

  • Upload
    lamlien

  • View
    254

  • Download
    3

Embed Size (px)

Citation preview

Page 1: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

TECHNICAL & SERVICE MANUAL

Model name<Indoor unit>Model name<Indoor unit>

SEZ-KD25VA(L)SEZ-KD35VA(L)SEZ-KD50VA(L)SEZ-KD60VA(L)SEZ-KD71VA(L)

Series SEZ

2012

INDOOR UNIT

WIRED REMOTE CONTROLLER

ON/OFF TEMP.

WIRELESS REMOTECONTROLLER

ON/OFF TEMP

Page 2: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

HWE0711C.qx 12.10.10 14:09 Page 1

Page 3: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

1. PART NAMES AND FUNCTIONS···········································································22. SPECIFICATIONS ···································································································53. OUTLINES AND DIMENSIONS·············································································184. WIRING DIAGRAM································································································205. REFRIGERANT SYSTEM DIAGRAM····································································216. TROUBLESHOOTING···························································································227. DISASSEMBLY PROCEDURE··············································································34

CONTENTS

Page 4: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

2

1 PART NAMES AND FUNCTIONS

Indoor UnitSEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L)

Air outlet duct flangeAir outlet

Air inlet

Operation buttons

Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.Wired remote controller

PAR-21MAA

ON/OFF

FILTER

CHECK

OPERATION CLEAR

TEST

TEMP.

MENU

BACK DAYMONITOR/SET

CLOCK

ON/OFF

Set Temperature buttons

Down

Up

Timer Menu button(Monitor/Set button)

Mode button (Return button)

Set Time buttons

Back

Ahead

Timer On/Off button(Set Day button)

Opening thedoor

Start/Stop button

Fan Speed button

Filter button(<return sign> button)

Test Run button

Service button (Clear button)

Airflow Up/Down button

Louver button( Operation button)

To preceding operationnumber

Ventilation button( Operation button)

To next operation number

HWE0711C.qx 12.10.10 14:09 Page 2

Page 5: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

3

Display

For purposes of this explanation,all parts of the display are shownas lit. During actual operation, onlythe relevant items will be lit.

˚F˚C

˚F˚C

ERROR CODEAFTER

TIMERTIME SUN MON TUE WED THU FRI SAT

ON

OFF

Hr

AFTER

FILTERFUNCTION

ONLY1Hr.

WEEKLYSIMPLE

AUTO OFF

Identifies the current operationShows the operating mode, etc.* Multilanguage display is sup-

ported.

“Centrally Controlled” indicatorIndicates that operation of the re-mote controller has been prohib-ited by a master controller.

“Timer Is Off” indicatorIndicates that the timer is off.

Temperature SettingShows the target temperature.

Day-of-WeekShows the current day of the week.

Time/Timer DisplayShows the current time, unless the simple or Auto Offtimer is set.If the simple or Auto Off timer is set, shows the timeremaining.

“Sensor” indicationDisplayed when the remote controller sensor is used.

“Locked” indicatorIndicates that remote controller but-tons have been locked.

“Clean The Filter” indicatorComes on when it is time to clean thefilter.

Timer indicatorsThe indicator comes on if the corre-sponding timer is set.

Up/Down Air Direction indica-torThe indicator shows the direc-tion of the outcoming airflow.

“One Hour Only” indicatorDisplayed if the airflow is set toLow and downward during COOLor DRY mode. (Operation variesaccording to model.)The indicator goes off after onehour, at which time the airflow di-rection also changes.

Room Temperature displayShows the room temperature.

Louver displayIndicates the action of the swinglouver. Does not appear if thelouver is stationary.

(Power On indicator)Indicates that the power is on.

Fan Speed indicatorShows the selected fan speed.

Ventilation indicatorAppears when the unit is running inVentilation mode.

Caution Only the Power on indicator lights when the unit is stopped and power supplied to the unit. If you press a button for a feature that is not installed in the indoor unit, the remote controller will display the “Not Available”

message.If you are using the remote controller to operate multiple indoor units, this message will appear only if the feature is not present at the parent unit.

When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indication(For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappears then start the operation.

HWE0711C.qx 12.10.10 14:09 Page 3

Page 6: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

4

Wireless remote controller

When using the wireless remote controller, point it towards the receiver onthe indoor unit.

If the remote controller is operated within approximately two minutes afterpower is supplied to the indoor unit, the indoor unit may beep twice as theunit is performing the initial automatic check.

The indoor unit beeps to confirm that the signal transmitted from theremote controller has been received. Signals can be received up toapproximately 7 meters in a direct line from the indoor unit in an area 45°to the left and right of the unit. However, illumination such as fluorescentlights and strong light can affect the ability of the indoor unit to receive sig-nals.

If the operation lamp near the receiver on the indoor unit is flashing, theunit needs to be inspected. Consult your dealer for service.

Handle the remote controller carefully. Do not drop the remote controller orsubject it to strong shocks. In addition, do not get the remote controllerwet or leave it in a location with high humidity.

To avoid misplacing the remote controller, install the holder included withthe remote controller on a wall and be sure to always place the remotecontroller in the holder after use.

CLOCK

CHECK

RESETSET

TEST RUN

MODE

FAN

VANE

LOUVER

min

h

AUTO START

AUTO STOP

ON/OFF TEMP

NOT AVAILABLE

MODEL SELECTTEST RUNCHECK SET TEMPERATURE button

SET TEMPERATURE button sets and any desired room temperature.

AUTO STOP/AUTO START buttonUsed for selecting timed starting or st-opping.

VANE CONTROL buttonUsed to change the airflow direction.

LOUVER buttonUsed for adjusting the airflow direction.

min buttonUsed for setting the current time.

h buttonUsed for setting the current time.

FAN SPEED buttonThis button is used to set fan speed to low, medium or high.

MODE SELECT buttonThis button is used to change between auto, cooling, heating and drying oper-ation modes.

TEST RUN button

CHECK button

ON/OFF buttonPushing button starts operation.Pushing again stops operation.

Battery installation/replacement

1. Remove the top cover, insert two AAAbatteries, and then install the top cover.

Top cover

2. Press the Reset button.

1

23

Press the Reset buttonwith an object that hasa narrow end.

Two AAA batteriesInsert the negative (–)end of each batteryfirst. Install the batter-ies in the correct direc-tions (+, –).

Operation buttons

HWE0711C.qx 12.10.10 14:09 Page 4

Page 7: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

5

2 SPECIFICATIONS

kW A˚C(˚F)

FanPa

kW

m3/min

mm In.kg mm(in.) A

Liquid mm(in.) Gas mm(in.)

mm(in.)

dB<A>

Net weight

R410A

Motor output

Airflow rate(Low-Mid-High)

Motor type

External finish

Wiring

Model Name

Power source

Optional parts Remark

Document Standard attachment

Power input Current

Type x Quantity Airflow direction Temperature set range Remote controller

Operation Mode

Varistor

External static press

Driving mechanism

External dimension

Drain piping diameter

H x W x D

<Cooling> Indoor: 27˚CD.B./19˚CW.B. (81˚FD.B. / 66˚FW.B. Outdoor:35˚CD.B. (95˚FD.B. )

Insulation material Air filter Refrigerant control device Protection devices

Note

Pipe length: 7.5m (24-9/16ft) Height difference: 0m (0ft)2.The external static pressure is set to 15 Pa at factory shipment.

<Heating> Indoor:20˚CD.B. (68˚FD.B.) Outdoor:7˚CD.B. / 6˚CW.B. (45˚FD.B. / 43˚FW.B.)

1.Cooling/Heating capacity indicates the maximum value at operation under the following condition.

3.Wired Remote Controller for VA model , Wireless Remote Controller for VAL model

Refrigerant piping diameter R410A

Noise level (Low-Mid-High)(measured in anechoic room)

Heat exchanger

Terminal block Power outlet A

Accessory *3

Min.size of wire Amperage of wire breaker

19 to 30 (67 to 86) 17 to 28 (63 to 83)

220 - 240V (50/60Hz)0.040.39

-Sirocco fan x 2

5-15-35-50DC blushless motor

0.096Direct-driven5.5-7.0-9.0Galvanized

200 x 700 x 7007-7/8 x 27-9/16 x 27-9/16

181.6 (1/8)

15ø6.35 (ø1/4) Flareø9.52 (ø3/8) Flare

O.D. 32 (1-9/32)

23-26-30

Polystyrene foam, Polyethylene foam, Urethane foamPP Honeycomb fabric (washable)

-Fuse (250V 6.3A)

Cross fin (Aluminum fin and copper tube)ERZV10D471

To outdoor unit : 3P To wired remote controller : 2P10

Installation Manual, Instruction BookDrain hose (flexible joint), Remote ControllerDrain Iift-up mechanism (PAC-KE07DM-E)

SEZ-KD25VA(L)

19 to 30 (67 to 86) 17 to 28 (63 to 83)

Cooling Heating Cooling Heating220 - 240V (50/60Hz)

0.050.46

-Sirocco fan x 2

5-15-35-50DC blushless motor

0.096Direct-driven7.0-9.0-11.0Galvanized

200 x 900 x 7007-7/8 x 35-7/16 x 27-9/16

211.6 (1/8)

15ø6.35 (ø1/4) Flareø9.52 (ø3/8) Flare

O.D. 32 (1-9/32)

23-28-33

Polystyrene foam, Polyethylene foam, Urethane foamPP Honeycomb fabric (washable)

-Fuse (250V 6.3A)

Cross fin (Aluminum fin and copper tube)ERZV10D471

To outdoor unit : 3P To wired remote controller : 2P10

Installation Manual, Instruction BookDrain hose (flexible joint), Remote ControllerDrain Iift-up mechanism (PAC-KE07DM-E)

SEZ-KD35VA(L)

HWE0711C.qx 12.10.10 14:09 Page 5

Page 8: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

6

kW A˚C(˚F)

FanPa

kW

m3/min

mm In.kg mm(in.) A

Liquid mm(in.) Gas mm(in.)

mm(in.)

dB<A>

Net weight

R410A

Motor output

Airflow rate(Low-Mid-High)

Motor type

External finish

Wiring

Model Name

Power source

Optional parts Remark

Document Standard attachment

Power input Current

Type x Quantity Airflow direction Temperature set range Remote controller

Operation Mode

Varistor

External static press

Driving mechanism

External dimension

Drain piping diameter

H x W x D

<Cooling> Indoor: 27˚CD.B./19˚CW.B. (81˚FD.B. / 66˚FW.B. Outdoor:35˚CD.B. (95˚FD.B. )

Insulation material Air filter Refrigerant control device Protection devices

Note

Pipe length: 7.5m (24-9/16ft) Height difference: 0m (0ft)2.The external static pressure is set to 15 Pa at factory shipment.

<Heating> Indoor:20˚CD.B. (68˚FD.B.) Outdoor:7˚CD.B. / 6˚CW.B. (45˚FD.B. / 43˚FW.B.)

1.Cooling/Heating capacity indicates the maximum value at operation under the following condition.

3.Wired Remote Controller for VA model , Wireless Remote Controller for VAL model

Refrigerant piping diameter R410A

Noise level (Low-Mid-High)(measured in anechoic room)

Heat exchanger

Terminal block Power outlet A

Accessory *3

Min.size of wire Amperage of wire breaker

19 to 30 (67 to 86) 17 to 28 (63 to 83)

220 - 240V (50/60Hz)0.070.63

-Sirocco fan x 3

5-15-35-50DC blushless motor

0.096Direct-driven

10.0-12.5-15.0Galvanized

200 x 900 x 7007-7/8 x 35-7/16 x 27-9/16

231.6 (1/8)

15ø6.35 (ø1/4) Flareø12.7 (ø1/2) Flare

O.D. 32 (1-9/32)

30-34-37

Polystyrene foam, Polyethylene foam, Urethane foamPP Honeycomb fabric (washable)

-Fuse (250V 6.3A)

Cross fin (Aluminum fin and copper tube)ERZV10D471

To outdoor unit : 3P To wired remote controller : 2P20

Installation Manual, Instruction Book

Drain hose (flexible joint), Remote Controller

Drain Iift-up mechanism (PAC-KE07DM-E)

SEZ-KD50VA(L)

19 to 30 (67 to 86) 17 to 28 (63 to 83)

Cooling Heating Cooling Heating220 - 240V (50/60Hz)

0.070.63

-Sirocco fan x 4

5-15-35-50DC blushless motor

0.096Direct-driven

12.0-15.0-18.0Galvanized

200 x 1100 x 7007-7/8 x 43-5/16 x 27-9/16

271.6 (1/8)

15ø6.35 (ø1/4) Flareø15.88 (ø5/8) Flare

O.D. 32 (1-9/32)

30-34-38

Polystyrene foam, Polyethylene foam, Urethane foamPP Honeycomb fabric (washable)

-Fuse (250V 6.3A)

Cross fin (Aluminum fin and copper tube)ERZV10D471

To outdoor unit : 3P To wired remote controller : 2P20

Installation Manual, Instruction Book

Drain hose (flexible joint), Remote Controller

Drain Iift-up mechanism (PAC-KE07DM-E)

SEZ-KD60VA(L)

HWE0711C.qx 12.10.10 14:09 Page 6

Page 9: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

7

kW A˚C(˚F)

FanPa

kW

m3/min

mm In.kg mm(in.) A

Liquid mm(in.) Gas mm(in.)

mm(in.)

dB<A>

Net weight

R410A

Motor output

Airflow rate(Low-Mid-High)

Motor type

External finish

Wiring

Model Name

Power source

Optional parts Remark

Document Standard attachment

Power input Current

Type x Quantity Airflow direction Temperature set range Remote controller

Operation Mode

Varistor

External static press

Driving mechanism

External dimension

Drain piping diameter

H x W x D

<Cooling> Indoor: 27˚CD.B./19˚CW.B. (81˚FD.B. / 66˚FW.B. Outdoor:35˚CD.B. (95˚FD.B. )

Insulation material Air filter Refrigerant control device Protection devices

Note

Pipe length: 7.5m (24-9/16ft) Height difference: 0m (0ft)2.The external static pressure is set to 15 Pa at factory shipment.

<Heating> Indoor:20˚CD.B. (68˚FD.B.) Outdoor:7˚CD.B. / 6˚CW.B. (45˚FD.B. / 43˚FW.B.)

1.Cooling/Heating capacity indicates the maximum value at operation under the following condition.

3.Wired Remote Controller for VA model , Wireless Remote Controller for VAL model

Refrigerant piping diameter R410A

Noise level (Low-Mid-High)(measured in anechoic room)

Heat exchanger

Terminal block Power outlet A

Accessory *3

Min.size of wire Amperage of wire breaker

19 to 30 (67 to 86) 17 to 28 (63 to 83)

Cooling Heating220 - 240V (50/60Hz)

0.100.84

-Sirocco fan x 4

5-15-35-50DC blushless motor

0.096Direct-driven

12.0-16.0-20.0Galvanized

200 x 1100 x 7007-7/8 x 43-5/16 x 27-9/16

271.6 (1/8)

15ø9.52 (ø3/8) Flareø15.88 (ø5/8) Flare

O.D. 32 (1-9/32)

30-35-40

Polystyrene foam, Polyethylene foam, Urethane foamPP Honeycomb fabric (washable)

-Fuse (250V 6.3A)

Cross fin (Aluminum fin and copper tube)ERZV10D471

To outdoor unit : 3P To wired remote controller : 2P20

Installation Manual, Instruction Book

Drain hose (flexible joint), Remote Controller

Drain Iift-up mechanism (PAC-KE07DM-E)

SEZ-KD71VA(L)

HWE0711C.qx 12.10.10 14:09 Page 7

Page 10: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

8

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD25VA(L)External static pressure: 15Pa High

Middle30

SPL(dB)

26Low 23

LINE<50/60Hz>

NOTCH

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD25VA(L)External static pressure: 5Pa High

Middle29

SPL(dB)

25Low 22

LINE<50/60Hz>

NOTCH

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD25VA(L)External static pressure: 50Pa High

Middle33

SPL(dB)

29Low 25

LINE<50/60Hz>

NOTCH

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD25VA(L)External static pressure: 35Pa High

Middle31

SPL(dB)

28Low 24

LINE<50/60Hz>

NOTCH

NOISE CRITERION CURVES

NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The soundmay be bigger than displayed level under actual installation condition by surrounding echoes. The sound levelcan be higher by about 2 dB than the displayed level during cooling and heating operation.

HWE0711C.qx 12.10.10 14:09 Page 8

Page 11: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

9

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD35VA(L)External static pressure: 15Pa High

Middle33

SPL(dB)

28Low 23

LINE<50/60Hz>

NOTCH

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD35VA(L)External static pressure: 5Pa High

Middle33

SPL(dB)

28Low 23

LINE<50/60Hz>

NOTCH

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD35VA(L)External static pressure: 50Pa High

Middle35

SPL(dB)

31Low 25

LINE<50/60Hz>

NOTCH

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD35VA(L)External static pressure: 35Pa High

Middle34

SPL(dB)

29Low 24

LINE<50/60Hz>

NOTCH

NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The soundmay be bigger than displayed level under actual installation condition by surrounding echoes. The sound levelcan be higher by about 2 dB than the displayed level during cooling and heating operation.

HWE0711C.qx 12.10.10 14:09 Page 9

Page 12: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

10

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD50VA(L)External static pressure: 15Pa High

Middle37

SPL(dB)

34Low 30

LINE<50/60Hz>

NOTCH

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD50VA(L)External static pressure: 5Pa High

Middle36

SPL(dB)

33Low 29

LINE<50/60Hz>

NOTCH

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD50VA(L)External static pressure: 50Pa High

Middle39

SPL(dB)

36Low 32

LINE<50/60Hz>

NOTCH

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD50VA(L)External static pressure: 35Pa High

Middle38

SPL(dB)

35Low 31

LINE<50/60Hz>

NOTCH

NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The soundmay be bigger than displayed level under actual installation condition by surrounding echoes. The sound levelcan be higher by about 2 dB than the displayed level during cooling and heating operation.

HWE0711C.qx 12.10.10 14:09 Page 10

Page 13: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

11

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD60VA(L)External static pressure: 15Pa High

Middle38

SPL(dB)

34Low 30

LINE<50/60Hz>

NOTCH

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD60VA(L)External static pressure: 5Pa High

Middle37

SPL(dB)

33Low 29

LINE<50/60Hz>

NOTCH

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD60VA(L)External static pressure: 50Pa High

Middle39

SPL(dB)

36Low 32

LINE<50/60Hz>

NOTCH

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD60VA(L)External static pressure: 35Pa High

Middle39

SPL(dB)

35Low 31

LINE<50/60Hz>

NOTCH

NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The soundmay be bigger than displayed level under actual installation condition by surrounding echoes. The sound levelcan be higher by about 2 dB than the displayed level during cooling and heating operation.

HWE0711C.qx 12.10.10 14:09 Page 11

Page 14: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

12

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD71VA(L)External static pressure: 15Pa High

Middle40

SPL(dB)

35Low 30

LINE<50/60Hz>

NOTCH

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD71VA(L)External static pressure: 5Pa High

Middle39

SPL(dB)

34Low 29

LINE<50/60Hz>

NOTCH

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD71VA(L)External static pressure: 50Pa High

Middle42

SPL(dB)

37Low 32

LINE<50/60Hz>

NOTCH

90

80

70

60

50

40

30

20

1063 125 250 500 1000 2000 4000 8000

APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISE

NC-60

NC-50

NC-40

NC-30

NC-20

NC-70

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

L, d

B (

0 d

B =

0.0

002

µb

ar)

BAND CENTER FREQUENCIES, Hz

SEZ-KD71VA(L)External static pressure: 35Pa High

Middle41

SPL(dB)

36Low 31

LINE<50/60Hz>

NOTCH

NOTE: The sound level is measured in an anechoic room whereechoes are few, when compressor stops. The sound may bebigger than displayed level under actual installation condi-tion by surrounding echoes. The sound level can be higherby about 2 dB than the displayed level during cooling andheating operation. Measurement location

2m 1m

Aux. duct

1.5m

test unit

HWE0711C.qx 12.10.10 14:09 Page 12

Page 15: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

13

INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW

SEZ-KD25VA(L)(External static pressure 15Pa) 220-240V 50/60Hz

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

10

20

30

40

50

Airflow rate(m3/min)4 5 6 7 8 9 10

Middle

Low

High

Limit

Rated point

0

40

30

20

10

4 5 6 7 8 9 10Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD25VA(L)(External static pressure 5Pa) 220-240V 50/60Hz

Middle

Low

High

Rated point

Limit

0

10

20

30

40

50

60

70

80

4 5 6 7 8 9 10Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD25VA(L)(External static pressure 50Pa) 220-240V 50/60Hz

Middle

Low

High

Limit

Rated point

0

10

20

30

40

50

60

70

80

4 5 6 7 8 9 10Airflow rate(m3/min)

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD25VA(L)(External static pressure 35Pa) 220-240V 50/60Hz

Middle

Low

High

Limit

Rated point

HWE0711C.qx 12.10.10 14:10 Page 13

Page 16: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

14

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD35VA(L)(External static pressure 15Pa) 220-240V 50/60Hz

Airflow rate(m3/min)

0

10

20

30

40

50

6 7 8 9 10 11 12

Middle

Low

High

Limit

Rated point

0

40

30

20

10

Ext

erna

l sta

tic p

ress

ure

(Pa)

6 7 8 9 10 11 12Airflow rate(m3/min)

SEZ-KD35VA(L)(External static pressure 5Pa) 220-240V 50/60Hz

Middle

Low

High

Limit

Rated point

0

20

10

30

40

50

60

70

80

Ext

erna

l sta

tic p

ress

ure

(Pa)

Airflow rate(m3/min)

SEZ-KD35VA(L)(External static pressure 50Pa) 220-240V 50/60Hz

6 7 8 9 10 11 12

Middle

Low

High

Limit

Rated point

0

20

10

30

40

50

60

70

80

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD35VA(L)(External static pressure 35Pa) 220-240V 50/60Hz

6 7 8 9 10 11 12Airflow rate(m3/min)

Middle

Low

High

Limit

Rated point

HWE0711C.qx 12.10.10 14:10 Page 14

Page 17: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

15

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD50VA(L)(External static pressure 15Pa) 220-240V 50/60Hz

Airflow rate(m3/min)8 9 10 11 12 13 14 15 16

0

50

40

30

20

10

High

Limit

Rated point

Middle

Low

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD50VA(L)(External static pressure 5Pa) 220-240V 50/60Hz

Airflow rate(m3/min)

0

40

30

20

10

8 9 10 11 12 13 14 15 16

Middle

Low

High

Limit

Rated point

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD50VA(L)(External static pressure 50Pa) 220-240V 50/60Hz

Airflow rate(m3/min)8 9 10 11 12 13 14 15 16

0

10

20

30

40

50

60

70

80

Middle

Low

High

Limit

Rated point

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD50VA(L)(External static pressure 35Pa) 220-240V 50/60Hz

Airflow rate(m3/min)8 9 10 11 12 13 14 15 16

0

10

20

30

40

50

60

70

80

Middle

Low

High

Limit

Rated point

HWE0711C.qx 12.10.10 14:10 Page 15

Page 18: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

16

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD60VA(L)(External static pressure 15Pa) 220-240V 50/60Hz

Airflow rate(m3/min)9 10 11 12 13 14 15 16 17 18 19

0

50

40

30

20

10

Middle

Low

High

Limit

Rated point

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD60VA(L)(External static pressure 5Pa) 220-240V 50/60Hz

Airflow rate(m3/min)9 10 11 12 13 14 15 16 17 18 19

0

40

30

20

10 Middle

Low

High

Limit

Rated point

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD60VA(L)(External static pressure 50Pa) 220-240V 50/60Hz

Airflow rate(m3/min)9 10 11 12 13 14 15 16 17 18 19

0

10

20

30

40

60

70

50

80

Middle

Limit

Rated point

Low

High

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD60VA(L)(External static pressure 35Pa) 220-240V 50/60Hz

Airflow rate(m3/min)9 10 11 12 13 14 15 16 17 18 19

0

10

20

30

40

60

70

50

80

Middle

Limit

Rated point

Low

High

HWE0711C.qx 12.10.10 14:10 Page 16

Page 19: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

17

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD71VA(L)(External static pressure 15Pa) 220-240V 50/60Hz

Airflow rate(m3/min)

0

50

40

30

20

10

11 12 13 14 15 16 17 18 19 20 21

Middle

High

Low

Limit

Rated point

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD71VA(L)(External static pressure 5Pa) 220-240V 50/60Hz

Airflow rate(m3/min)

0

40

30

20

10

11 12 13 14 15 16 17 18 19 20 21

Middle

Low

High

Limit

Rated point

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD71VA(L)(External static pressure 50Pa) 220-240V 50/60Hz

Airflow rate(m3/min)2120191817161514131211

0

10

20

30

40

50

80

70

60

Middle

Low

High

Limit

Rated point

Ext

erna

l sta

tic p

ress

ure

(Pa)

SEZ-KD71VA(L)(External static pressure 35Pa) 220-240V 50/60Hz

Airflow rate(m3/min)

0

10

20

30

40

50

80

70

60

2120191817161514131211

Middle

Low

High

Limit

Rated point

HWE0711C.qx 12.10.10 14:10 Page 17

Page 20: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

18

OUTLINES AND DIMENSIONS3

Unit : mmSEZ-KD25VA(L)SEZ-KD35VA(L)SEZ-KD50VA(L)SEZ-KD60VA(L)SEZ-KD71VA(L)

24

20

16

900

700

500

9

7

5

1060

860

660LJH K

12.7

SEZ-KD71VA(L)SEZ-KD60VA(L)SEZ-KD50VA(L)SEZ-KD35VA(L)

700 752 798 660 7 600 800

15.889.52

6.359.52

1198

998

AModelSEZ-KD25VA(L)

1152

952

B

1100

900

C

1060

860

D

11

9

E

1000

800

F

1200

1000

G

Airoutlet

Airinlet

Terminal block(Remote controller transmission line)

Drain pipe(O.D.32)(Spontaneous draining)

1

Gas pipe1 Liquid pipe2

Refrigerant pipingflare connection (gas)

2 Refrigerant piping

flare connection (liquid)

Terminal block(Indoor/outdoor connecting line)

Suspension bolt hole4-14X30 Slot

Air filter

Control box

2XE-2.9

2X2-2.9

L-2.9

Knockout hole 27(Indoor/outdoor connecting line)

Knockout hole 27(Remote controller transmission line)

10

170

57

15

20

100

100X

(E-1

)=F

30

D (

Duc

t)

625 (Suspension bolt pitch) 90A

23B

(S

uspe

nsio

n bo

lt pi

tch)

C

23 677700

2510

0

2315

0(D

uct)

116 70

270

102

25

49

10

8810

010

0XJ=

K88

12

12 37 100

20 157.5

20H

200

37

Note1.Use M10 screw for the suspension bolt (field supply). 2.Keep the service space for the maintenance at the bottom. 3.This chart indicates for SEZ-KD50VA(L) model,which has 3 fans. SEZ-KD25,35VA(L) models have 2 fans. SEZ-KD60,71VA(L) models have 4 fans. 4.In case an inlet duct is used,remove the air filter(supply with the unit), then install the filter(field supply) at suction side.

HWE0711C.qx 12.10.10 14:10 Page 18

Page 21: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

19

Unit : mm

SEZ-KD25VA(L)SEZ-KD35VA(L)SEZ-KD50VA(L)SEZ-KD60VA(L)SEZ-KD71VA(L)

SEZ-KD60, 71SEZ-KD35, 50

700 50~150 800 13001000

PModelSEZ-KD25

150~250

Q

900

R

15001200250~3501100 1700

S

(mm)

Electric box

Ceiling

Min.

300

mm

Min.

10 m

m

AAccess door 2 (450 x 450)

Ceiling beam

Intake airSupply air

Electric box

Ceiling Min.

20

mm

Min.

10 m

m

B

Ceiling beam

Access door 3

Intake airSupply air

700

450

475 450

Q

50~150 450

450

100~200

Bottom of indoor unit

Maintenance access space

Min. 300 mm

(Viewed from the direction of the arrow A)

Access door 2 (450 x 450)

Access door 1 (450 x 450)

P

Electric box

Access door 3

P50

R

777

450

100~200

Maintenance access space

Bottom of indoor unit

Electric box

(Viewed from the direction of the arrow B)

Access door 1 (450 x 450)

45047570050 Min. 300 mm

Fig. 1

Fig. 3

Fig. 2

Fig. 4

Secure enough access space to allow for the maintenance, inspection, and replacement of the motor, fan, drain pump, heat exchanger, and electric box in one of the following ways.Select an installation site for the indoor unit so that its maintenance access space will not be obstructed by beams or other objects.(1) When a space of 300 mm or more is available below the unit between the unit and the ceiling (Fig. 1)

• Create access door 1 and 2 (450 x 450 mm each) as shown in Fig. 2.(Access door 2 is not required if enough space is available below the unit for a maintenance worker to work in).

(2) When a space of less than 300 mm is available below the unit between the unit and the ceiling (At least 20 mm of space should be left below the unit as shown in Fig. 3.)• Create access door 1 diagonally below the electric box and access door 3 below the unit as shown in Fig. 4.

or• Create access door 4 below the electric box and the unit as shown in Fig. 5.

777

S

50

50P

700

Maintenance access space

Bottom of indoor unit

Electric box

Min. 300 mm

(Viewed from the direction of the arrow B)

Access door 4

Fig. 5

HWE0711C.qx 12.10.10 14:10 Page 19

Page 22: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

20

4 WIRING DIAGRAM

SEZ-KD25VA(L)SEZ-KD35VA(L)SEZ-KD50VA(L)SEZ-KD60VA(L)SEZ-KD71VA(L)

1~M

1 3 5

3 1145673 4

1 2

42 31

41 2 3 6 7 8 95

54321 6 7 8

1 32 4

9 1 2

3

LED1

Optional Parts

L1:only SEZ-KD71VA(L)

INSIDE SECTION OF CONTROL BOX

CN22

(Red)

CN3C

CNMF

SW2SW1

CN90

CN32

CN20CN44CN4F

CN41

SWE

ON OFF

CN51

(Blue)

TO MA REMOTE CONTROLLER

FS TH2 TH5 TH1Fan motor

TB15

CN4F

Optional Parts

CN2L (Blue)

LED3LED2

I.B.

S1TB4

S3

S2 TO OUTDOOR UNIT

Drainpump

FS FLOAT SWITCH

L1 AC REACTOR (POWER FACTOR IMPROVEMENT)

SW2 SWITCH (COOLING ON/OFF)

SWITCH (HEATING ON/OFF)SW1

LED (RUN INDICATOR)LED1

BZ1 BUZZER

RU RECEIVING UNIT

W.B. WIRELESS REMOTE CONTROLLER BOARD

TB4

TB15TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE)

TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)

LED2

LED3 TRANSMISSION (INDOOR-OUTDOOR)

POWER SUPPLY (I.B.)

LED1 POWER SUPPLY (I.B.)

CN90 CONNECTOR (WIRELESS)

ZNR01,02 VARISTOR

AUX. RELAYX1

FUSE FUSE AC250V 6.3A

DSA

CONNECTOR (CENTRALLY CONTROL)

CN41

CN51

CONNECTOR (HA TERMINAL-A)

CN2L

NAME

SYMBOL EXPLANATION

SW1

SW2

INDOOR CONTROLLER BOARD

CN32

I.B.

SYMBOL SYMBOL NAME

CONNECTOR (LOSSNAY)

CONNECTOR (REMOTE SWITCH)

SWE

ARRESTER

SWITCH (FOR MODEL SELECTION)

SWITCH (FOR CAPACITY CODE)

CONNECTOR (EMERGENCY OPERATION)

TH1 INTAKE AIR TEMP. THERMISTOR

TH2 PIPE TEMP. THERMISTOR/LIQUID

TH5 COND. /EVA. TEMP. THERMISTOR

X1

DC310~340VRectify circuit

U

U

FUSEZNR01

(Black)CN01

CNP

ZNR02

(Blue)

DSA

1

t° Mt°t°

1

2

L1

RECEIVERRU

CN1

LED1

SW1 SW2

W.B.

BZ1

For SEZ-KD • VAL

For SEZ-KD • VA

NOTE)1. Since the outdoor side electric wiring may change be sure tocheck the outdoor unit electric wiring for servicing.

2. Indoor and outdoor connecting wires are made with polarities, makewiring matching terminal numbers(S1,S2,S3).

3. Symbols used in wiring diagram above are, :Connector, :Terminal Block.

HWE0711C.qx 12.10.10 14:10 Page 20

Page 23: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

21

REFRIGERANT SYSTEM DIAGRAM5

Pipe temperature thermistor/liquid (TH2)

Distributor

Condenser/evaporator temperature thermistor(TH5)

Room temperature thermistor (TH1)

Refrigerant flow in coolingRefrigerant flow in heating

Strainer#50

Strainer #50

Heat exchangerRefrigerant GAS pipe connection(Flare)

Refrigerant LIQUID pipe connection(Flare)

SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L)

HWE0711C.qx 12.10.10 14:10 Page 21

Page 24: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

22

6 TROUBLESHOOTING

6-1. CAUTIONS ON TROUBLESHOOTING(1) Before troubleshooting, check the followings:

1 Check the power supply voltage.2 Check the indoor/outdoor connecting wire for mis-wiring.

(2) Take care the followings during servicing.1 Before servicing the air conditioner, be sure to turn off the remote controller first to stop the main unit, and then turn

off the breaker.2 When removing the indoor controller board, hold the edge of the board with care NOT to apply stress on the

components.3 When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.

Lead wires

˚C

˚CSIMPLE

PAR-21MAA

ON/OFF

FILTER

CHECK

OPERATION CLEAR

TEST

TEMP.

MENU

BACK DAYMONITOR/SET

CLOCK

ON/OFF

B

C

A

E D

6-2. SELF-CHECK FUNCTIONWired remote controller(1) Turn on the power.(2) Press the [CHECK] button twice.(3) Set refrigerant address with [TEMP] button

if system control is used.(4) Press the [ON/OFF] button to stop the

self-check.AA CHECK buttonBB Refrigerant addressCC TEMP buttonDD IC : Indoor unit

OC : Outdoor unitEE Check code

1 Check code Symptom RemarkP1 Intake sensor errorP2 Pipe (TH2) sensor errorP9 Pipe (TH5) sensor errorE6,E7 Indoor/outdoor unit communication errorP4 Drain sensor errorP5 Drain pump errorP6 Freezing/Overheating protection operationEE Communication error between indoor and outdoor unitsP8 Pipe temperature errorE0, E3~E5 Remote controller transmission errorE1, E2 Remote controller control board errorFb Indoor unit control system error (memory error, etc.)E9 Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)UP Compressor overcurrent interruptionU3,U4 Open/short of outdoor unit thermistorsUF Compressor overcurrent interruption (When compressor locked)U2 Abnormal high discharging temperature/49C worked/insufficient refrigerantU1,Ud Abnormal high pressure (63H worked)/Overheating protection operationU5 Abnormal temperature of heat sinkU8 Outdoor unit fan safeguard stopU6 Compressor overcurrent interruption/Abnormal of power moduleU7 Abnormality of super heat due to low discharge temperatureU9,UH Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit

/Current sensor errorOthers Other errors (Refer to the technical manual for the outdoor unit.)

For details, check the LED displayof the outdoor controller board.As for outdoor unit, refer toservice manual OC322.

• On wired remote controller.

1 Check code displayed in the LCD.

• For description of each check code, refer to the following table.

HWE0711C.qx 12.10.10 14:10 Page 22

Page 25: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

23

• If the unit cannot be operated properly after the test run has been performed, refer to the following table to remove the cause.

SymptomCause

Wired remote controller LED 1, 2 (PCB in outdoor unit)

On the wireless remote controller with condition above, following phenomena take place.• No signals from the remote controller are accepted.• Operation lamp is blinking.• The buzzer makes a short piping sound.

PLEASE WAIT

PLEASE WAIT → Error code

Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).

For about 2minutes afterpower-on

After about 2minutes hasexpired afterpower-on

After LED 1, 2 are lighted, LED 2 is turned off, then only LED 1 is

Only LED 1 is lighted. → LED 1, 2 blink.

Only LED 1 is lighted. →

LED 1 blinks twice,LED 2 blinks once.

•For about 2 minutes after power-on,op-eration of the remote controller is not possible due to system start-up. (Correct operation)

•Connector for the outdoor unit’s protection device is not connected.

•Reverse or open phase wiring for the outdoor unit’s power terminal block (L1, L2, L3)

• Incorrect wiring between indoor and outdoorunits (incorrect polarity of S1, S2, S3)

•Remote controller wire short

Note:Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)

For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.

LED1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED isalways lit.

LED2 (power for remote controller) Indicates whether power is supplied to the remote controller. This LED lights only in the case of the indoor unit which is connected to the outdoor unit refrigerant address “0”.

LED3 (communication between indoor and outdoor units)

Indicates state of communication between the indoor and outdoor units. Make sure that this LED is always blinking.

lighted. (Correct operation)

Wireless remote controller(1) Turn on the power to the unit at least 12 hours before the test run.(2) Press the TEST RUN button AA twice continuously.

(Start this operation from the status of remote controller display turned off.)and current operation mode are displayed.

(3) Press the MODE button BB to activate COOL mode, then check whethercool air is blown out from the unit.

(4) Press the MODE button BB to activate HEAT mode, then check whetherwarm air is blown out from the unit.

(5) Press the FAN button CC and check whether fan speed changes.(6) Press the VANE button DD and check whether the auto vane operates prop-

erly.(7) Press the ON/OFF button to stop the test run.

Note:• Point the remote controller towards the indoor unit receiver while fol-

lowing steps (2) to (7).• It is not possible to run the in FAN, DRY or AUTO mode.

TEST RUN

HWE0711C.qx 12.10.10 14:10 Page 23

Page 26: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

24

• If the unit cannot be operated properly after the test run has been performed, refer to the following table to remove the cause.

On the wireless remote controller with conditions above, following phenomena takes place.• No signals from the remote controller are accepted.• OPE lamp is blinking.• The buzzer makes a short ping sound.

Note:Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)

PLEASE WAIT

PLEASE WAIT → Error code

Display messages do not appeareven when operation switch isturned ON (operation lamp doesnot light up).

Symptom

After LED 1, 2 are lighted, LED 2 is turnedoff, then only LED 1 is lighted. (Correctoperation)

Only LED 1 is lighted. → LED 1, 2 blink.

Only LED 1 is lighted. → LED 1, 2 blinkstwice, LED 2 blinks once.

• For about 2 minutes after power-on, operation of theremote controller is not possible due to system start-up.(Correct operation)

• Connector for the outdoor unit’s protection device is notconnected.

• Reverse or open phase wiring for the outdoor unit’s powerterminal block (L1, L2, L3)

• Incorrect wiring between indoor and outdoor units(incorrect polarity of S1, S2, S3)

• Remote controller wire short

For about 2 minutes

following power-on

After about 2 min-utes has expired

following power-on

LED 1, 2 (PCB in outdoor unit)Wired remote controllerCause

[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)

Wireless remote controllerBeeper sounds/OPERATION INDICATOR

lamp flashes (Number of times)12345678910

11

121314

Symptom

Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)Compressor overcurrent interruptionOpen/short of outdoor unit thermistorsCompressor overcurrent interruption (When compressor locked)Abnormal high discharging temperature/49C worked/ insufficient refrigerantAbnormal high pressure (63H worked)/ Overheating safeguard operationAbnormal temperature of heat sinkOutdoor unit fan protection stopCompressor overcurrent interruption/Abnormal of power moduleAbnormality of super heat due to low discharge temperatureAbnormality such as overvoltage or voltage shortage and abnormalsynchronous signal to main circuit/Current sensor error––Other errors (Refer to the technical manual for the outdoor unit.)

Remark

For details, check the LEDdisplay of the outdoor controllerboard.

[Output pattern A] Errors detected by indoor unit

Wireless remote controller

Beeper sounds/OPERATIONINDICATOR lamp flashes

(Number of times)123456789101112

No sound

Wired remotecontroller

Check code

P1P2, P9E6, E7P4P5P6EEP8E4––Fb

– –

Symptom

Intake sensor errorPipe (Liquid or 2-phase pipe) sensor errorIndoor/outdoor unit communication errorDrain sensor errorDrain pump errorFreezing/Overheating safeguard operationCommunication error between indoor and outdoor unitsPipe temperature errorRemote controller signal receiving error––Indoor unit control system error (memory error, etc.)

14 PL Refrigerant circuit abnormalNo corresponding

Remark

*1 If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does notcome on, there are no error records.

*2 If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm the self-check start signal wasreceived, the specified refrigerant address is incorrect.

• On wireless remote controllerThe continuous buzzer sounds from receiving section of indoor unit.Blink of operation lamp

• On wired remote controllerCheck code displayed on the LCD.

HWE0711C.qx 12.10.10 14:10 Page 24

Page 27: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

25

Indicates whether control power is supplied. Make sure that this LED is always lit.

Indicates whether power is supplied to the remote controller. This LED lights only in the case of

the indoor unit which is connected to the outdoor unit refrigerant address “0”.

Indicates state of communication between the indoor and outdoor units. Make sure that this LED is

always blinking.

LED 1 (power for microcomputer)

LED 2 (power for remote controller)

LED 3 (communication between indoor and outdoor units)

AUTO RESTART FUNCTIONIndoor controller boardThis model is equipped with the AUTO RESTART FUNCTION.When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are memorized by the indoor controller board. The auto restart function sets to work the moment the power has restored after power failure, then, the unit will restart automatically.Set the AUTO RESTART FUNCTION using the wireless remote controller. (Mode no.1).

For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.

HWE0711C.qx 12.10.10 14:10 Page 25

Page 28: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

26

6-3. SELF-DIAGNOSIS ACTION TABLENote: Refer to the manual of outdoor unit for the details of display

such as F, U, and other E.

Error Code Abnormal point and detection method Cause Countermeasure

P1

Room temperature thermistor (TH1)1 The unit is in three-minute resume

prevention mode if short/open of thermistor is detected. Abnormal if theunit does not reset normally after threeminutes. (The unit returns to normaloperation, if it has normally reset.)

2 Constantly detected during cooling, drying and heating operationShort: 90: or moreOpen: -40: or less

1 Defective thermistor characteristics

2 Contact failure of connector(CN20) on the indoor controllerboard (Insert failure)

3 Breaking of wire or contact failure of thermistor wiring

4 Defective indoor controllerboard

1–3 Check resistance value of thermistor.0: ······15.0k"10: ····9.6k"20: ····6.3k"30: ····4.3k"40: ····3.0k"If you put force on (draw or bend) the lead wirewith measuring resistance value of thermistorbreaking of wire or contact failure can bedetected.2 Check contact failure of connector (CN20) on

the indoor controller board. Refer to 6-5.Turn the power on again and check restartafter inserting connector again.

4 Check room temperature display on remotecontroller.Replace indoor controller board if there isabnormal difference with actual room temperature.

Turn the power off, and on again to operate after check.

P2

Pipe temperature thermistor/Liquid (TH2)1 The unit is in three-minute resume

prevention mode if short/open of thermistor is detected. Abnormal if theunit does not reset normally after threeminutes. (The unit returns to normaloperation, if it has normally reset.)

2 Constantly detected during cooling, drying, and heating (except defrosting)operation.Short: 90: or moreOpen: -40: or less

1 Defective thermistor characteristics

2 Contact failure of connector(CN44) on the indoor controllerboard (Insert failure)

3 Breaking of wire or contact failure of thermistor wiring

4 Defective refrigerant circuit iscausing thermistor temperatureof 90: or more or -40: orless.

5 Defective indoor controller board

1–3 Check resistance value of thermistor.For characteristics, refer to (P1) above.2 Check contact failure of connector (CN44) on

the indoor controller board. Refer to 6-5. Turnthe power on again and check restart afterinserting connector again.

4 Check pipe <liquid> temperature with remotecontroller in test run mode. If pipe <liquid>temperature is extremely low (in coolingmode) or high (in heating mode), refrigerantcircuit may have defective.

5 Check pipe <liquid> temperature with remotecontroller in test run mode. If there is extremedifference with actual pipe <liquid> temperature,replace indoor controller board.

Turn the power off, and on again to operate after check.

P4(5701)

Contact failure of drain float switch (CN4F)1 Extract when the connector of drain float

switch is disconnected.(3 and 4 of connector CN4F is notshort-circuited.)

2 Constantly detected during operation.

1 Contact failure of connector(Insert failure)

2 Defective indoor controllerboard

1 Check contact failure of float switch connec-tor.Turn the power on again and check afterinserting connector again.

2 Operate with connector (CN4F) short-circuited.Replace indoor controller board if abnormali-ty reappears.

P5

Drain overflow protection operation1 Suspensive abnormality, if drain float

switch is detected to be underwater for 1minute and 30 seconds continuouslywith drain pump on.Turn off compressor and indoor fan.

2 Drain pump is abnormal if the conditionabove is detected during suspensiveabnormality.

3 Constantly detected during drain pumpoperation.

1 Malfunction of drain pump2 Defective drain

Clogged drain pumpClogged drain pipe

3 Defective drain float switchCatch of drain float switch ormalfunction of moving partscause drain float switch to bedetected under water (SwitchOn)

4 Defective indoor-controllerboard

1 Check if drain-up machine works.2 Check drain function.

3 Remove drain float switch connector CN4Fand check if it is short (Switch On) with themoving part of float switch UP, or OPEN withthe moving part of float switch down.Replace float switch if it is short with themoving part of float switch down.

4 Replace indoor controller board if it is short-circuited between 3-4 of the drain floatswitch connector CN4F and abnormalityreappears.

It is not abnormal if there is no problem about the above-mentioned 1~4Turn the power off, and on again to operate after check.

HWE0711C.qx 12.10.10 14:10 Page 26

Page 29: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

27

Error Code Abnormal point and detection method Cause Countermeasure

P6

Freezing/overheating protection isworking1 Freezing protection (Cooling mode)

The unit is in six-minute resume preventionmode if pipe <liquid or condenser/evap-orator> temperature stays under -15: for three minutes after the com-pressor started. Abnormal if it staysunder -15: for three minutes againwithin 16 minutes after six-minuteresume prevention mode.

2 Overheating protection (Heating mode)The units is in six-minute resume prevention mode if pipe <Liquid or con-denser / evaporator> temperature isdetected as over 70: after the com-pressor started. Abnormal if the temper-ature of over 70: is detected againwithin 10 minutes after six-minuteresume prevention mode.

P8

1 Slight temperature differencebetween indoor room temperature and pipe <liquid or condenser / evaporator> temperature thermistor• Shortage of refrigerant• Disconnected holder of pipe

<liquid or condenser / evaporator> thermistor

• Defective refrigerant circuit2 Converse connection of

extension pipe (on plural unitsconnection)

3 Converse wiring of indoor/outdoor unit connecting wire(on plural units connection)

4 Defective detection of indoorroom temperature and pipe<condenser / evaporator> temperature thermistor

5 Stop valve is not opened completely.

(Cooling or drying mode)1 Clogged filter (reduced airflow)2 Short cycle of air path3 Low-load (low temperature)

operation beyond the tolerancerange

4 Defective indoor fan motor• Fan motor is defective.• Indoor controller board is

defective.

5 Defective outdoor fan control6 Overcharge of refrigerant7 Defective refrigerant circuit

(clogs)

(Heating mode)1 Clogged filter (reduced airflow)2 Short cycle of air path3 Over-load (high temperature)

operation beyond the tolerancerange

4 Defective indoor fan motor• Fan motor is defective.• Indoor controller board is

defective.

5 Defective outdoor fan control6 Overcharge of refrigerant7 Defective refrigerant circuit

(clogs)8 Bypass circuit of outdoor unit

is defective.

(Cooling or drying mode)1 Check clogging of the filter.2 Remove shields.

4 Refer to 6-7. DC Fan motor (FAN MOTOR/INDOOR CONTROLLER BOARD)

5 Check outdoor fan motor.67 Check operating condition of refrigerant

circuit.

(Heating mode)1 Check clogs of the filter.2 Remove shields.

4 Refer to 6-7. DC Fan motor (FAN MOTOR/INDOOR CONTROLLER BOARD)

5 Check outdoor fan motor.6~8Check operating condition of refrigerant

circuit.

Pipe temperature<Cooling mode>Detected as abnormal when the pipe tem-perature is not in the cooling range 3 min-utes after compressor start and 6 minutesafter the liquid or condenser/evaporator pipeis out of cooling range.Note 1) It takes at least 9 minutes. to

detect.Note 2) Abnormality P8 is not detected in

drying mode.Cooling range : -3 deg ] (TH-TH1) TH: Lower temperature between: liquid

pipe temperature (TH2) and con-denser/evaporator temperature (TH5)

TH1: Intake temperature

<Heating mode>When 10 seconds have passed after thecompressor starts operation and the hotadjustment mode has finished, the unit isdetected as abnormal whencondenser/evaporator pipe temperature isnot in heating range within 20 minutes.

Note 3) It takes at least 27 minutes todetect abnormality.

Note 4) It excludes the period of defrosting(Detection restarts when defrost-ing mode is over)

Heating range : 3 deg [ (TH5-TH1)

1~4 Check pipe <liquid or condenser /evaporator> temperature with room temperature display on remote controller and outdoor controller circuitboard.Pipe <liquid or condenser / evaporator> temperature display is indicated by setting SW2 of outdoor controller circuit board as follows.

23Check converse connection of extension pipe or converse wiring of indoor/outdoor unit connecting wire.

Conduct temperature check with outdoorcontroller circuit board after connecting ‘A-Control Service Tool(PAC-SK52ST)’.( )

HWE0711C.qx 12.10.10 14:10 Page 27

Page 30: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

28

Error Code Abnormal point and detection method Cause Countermeasure

P9

Abnormality of pipe temperature ther-mistor / Condenser-Evaporator (TH5)1 The unit is in three-minute resume pro-

tection mode if short/open of thermistoris detected. Abnormal if the unit doesnot get back to normal within three min-utes. (The unit returns to normal opera-tion, if it has normally reset.)

2 Constantly detected during cooling, dry-ing, and heating operation (exceptdefrosting)Short: 90: or moreOpen: -40: or less

1 Defective thermistor characteristics

2 Contact failure of connector(CN44) on the indoor controllerboard (Insert failure)

3 Breaking of wire or contact failure of thermistor wiring

4 Temperature of thermistor is90: or more or -40: or lesscaused by defective refrigerantcircuit.

5 Defective indoor controllerboard

1–3 Check resistance value of thermistor.For characteristics, refer to (P1) above.

2 Check contact failure of connector (CN44)on the indoor controller board.Refer to 6-5.Turn the power on and check restart afterinserting connector again.

4 Operate in test run mode and check pipe<condenser / evaporator> temperature.If pipe <condenser / evaporator> tempera-ture is extremely low (in cooling mode) orhigh (in heating mode), refrigerant circuitmay have defect.

5 When no problems are found in 1-4 above,replace the indoor unit control board.

E0orE4

Remote controller transmissionerror(E0)/signal receiving error(E4)1 Abnormal if main or sub remote con-

troller can not receive normally anytransmission from indoor unit of refriger-ant address “0” for three minutes.(Error code : E0)

2 Abnormal if sub remote controller couldnot receive for any signal for two min-utes. (Error code: E0)

1 Abnormal if indoor controller board cannot receive normally any data fromremote controller board or from otherindoor controller board for three minutes.(Error code: E4)

2 Indoor controller board cannot receiveany signal from remote controller for twominutes. (Error code: E4)

1 Check disconnection or looseness of indoorunit or transmission wire of remote controller.

2 Set one of the remote controllers “main” ifthere is no problem with the action above.

3 Check wiring of remote controller.• Total wiring length: max.500m

(Do not use cable 3 or more)• The number of connecting indoor units:

max.16units• The number of connecting remote con-

troller: max.2units

When it is not the above-mentioned problem of1~34 Diagnose remote controllers.

a) When “RC OK” is displayed,Remote controllers have no problem.Turn the power off, and on again to check.If abnormality generates again, replaceindoor controller board.

b) When “RC NG” is displayed,Replace remote controller.

c) When “RC E3” is displayed,d) When “ERC 00-06” is displayed,[ c),d)→Noise may be causing abnormality. ]

∗ If the unit is not normal after replacingindoor controller board in group control,indoor controller board of address “0”may be abnormal.

E3orE5

Remote controller transmissionerror(E3)/signal receiving error(E5)1 Abnormal if remote controller could not

find blank of transmission path for sixseconds and could not transmit.(Error code: E3)

2 Remote controller receives transmitteddata at the same time, compares thedata, and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E3)

1 Abnormal if indoor controller board couldnot find blank of transmission path.(Error code: E5)

2 Indoor controller board receives trans-mitted data at the same time, comparesthe data,and when detecting it, judgesdifferent data to be abnormal 30 continuous times. (Error code: E5)

1 Set a remote controller to main, and theother to sub.

2 Remote controller is connected with only oneindoor unit.

3 The address changes to a separate setting.

4~6 Diagnose remote controller.a) When “RC OK”is displayed, remote con-

trollers have no problem.Turn the power off,and on again to check.When becoming abnormal again, replaceindoor controller board.

b)When “RC NG”is displayed, replaceremote controller.

c)When “RC E3”or “ERC 00-66”is displayed,noise may be causing abnormality.

1 Contact failure at transmissionwire of remote controller

2 All remote controllers are setas “sub” remote controller. Inthis case, E0 is displayed onremote controller, and E4 isdisplayed at LED (LED1, LED2)on the outdoor controller circuitboard.

3 Mis-wiring of remote controller4 Defective transmitting receiving

circuit of remote controller5 Defective transmitting receiving

circuit of indoor controller boardof refrigerant address “0”

6 Noise has entered into thetransmission wire of remotecontroller.

1 Two remote controller are setas “main.”(In case of 2 remote con-trollers)

2 Remote controller is connectedwith two indoor units or more.

3 Repetition of refrigerantaddress

4 Defective transmitting receivingcircuit of remote controller

5 Defective transmitting receivingcircuit of indoor controllerboard

6 Noise has entered into trans-mission wire of remote con-troller.

HWE0711C.qx 12.10.10 14:10 Page 28

Page 31: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

29

E6

1 Contact failure, short circuit or,mis-wiring (converse wiring) ofindoor/outdoor unit connectingwire

2 Defective transmitting receivingcircuit of indoor controller board

3 Defective transmitting receivingcircuit of indoor controller board

4 Noise has entered into indoor/outdoor unit connecting wire.

∗ Check LED display on the outdoor control cir-cuit board. (Connect A-control service tool,PAC-SK52ST.)Refer to Outdoor manual.

1 Check disconnection or looseness of indoor/outdoor unit connecting wire of indoor unit oroutdoor unit.Check all the units in case of twin triple indoor unit system.

2-4 Turn the power off, and on again to check.If abnormality generates again, replaceindoor controller board or outdoor controller circuit board.

∗ Other indoor controller board may have defect in case of twin triple indoor unit system.

E7

Indoor/outdoor unit communicationerror (Transmitting error)Abnormal if “1” receiving is detected 30times continuously though indoor controllerboard has transmitted “0”.

1 Defective transmitting receivingcircuit of indoor controller board

2 Noise has entered into powersupply.

3 Noise has entered into outdoorcontrol wire.

1-3 Turn the power off, and on again to check.If abnormality generates again, replaceindoor controller board.

Indoor/outdoor unit communicationerror (Signal receiving error)1 Abnormal if indoor controller board

cannot receive any signal normally forsix minutes after turning the power on.

2 Abnormal if indoor controller board cannot receive any signal normally forthree minutes.

3 Consider the unit as abnormal under thefollowing condition: When two or moreindoor units are connected to an outdoor unit, indoor controller board cannot receive a signal for three minutesfrom outdoor controller circuit board, asignal which allows outdoor controllercircuit board to transmit signals.

Error Code Abnormal point and detection method Cause Countermeasure

Fb

Indoor controller boardAbnormal if data cannot be read normallyfrom the nonvolatile memory of the indoorcontroller board.

1 Defective indoor controllerboard

1 Replace indoor controller board.

E1orE2

Remote controller control board1 Abnormal if data cannot be read normal-

ly from the nonvolatile memory of theremote controller control board.(Error code: E1)

2 Abnormal if the clock function of remotecontroller cannot be operated normally.(Error code: E2)

1 Defective remote controller 1 Replace remote controller.

PA(2500)

Water leakageThis detection is performed during theoperation (stop, heating, fan, or error stopmode etc.) other than cooling and dry.1 When a) and b) are found, water leakage

occurs.a) Pipe <liquid> temperature - inlet tem-

perature < -10˚C for 30 minutesb) When drain float switch is detected to

be soaked in the water for 15 minutes or more.

* When drain float switch is detected tobe NOT soaked in the water, eachcounting of a) and b) is cleared.

*When this error is detected, the errorwill not be reset until the main power isreset.

1 Mis-piping of extension pipes(When connected with multipleunits)

2 Mis-wiring of indoor/outdoor unit connecting wire (When connected with multiple units)

3 Detection failure of the indoorunit inlet/ pipe <liquid> ther-mistor

4 Drain pump failure

5 Drainage failure· Clogged drain pump· Clogged drain pipe

6 Drain float switch failure· Drain float switch is detected

to be soaked in the water (ON status) due to the operation failure of the moving parts.

· Contact failure of drain float switch connector(Loose connector)

1Check the extension pipes for mis-piping.

2Check the Indoor/outdoor unit connecting wire for mis-wiring.

3Check room temperature display on remotecontroller and indoor pipe <liquid> tempera-ture. (Refer to the countermeasure on P2.)

4Check if drain-up machine works.

5 Check drain function.

6Check drain float switch. (Refer to the coun-termeasure on P4 and P5.)

HWE0711C.qx 12.10.10 14:10 Page 29

Page 32: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

30

6-4. TROUBLESHOOTING BY INFERIOR PHENOMENA Note: Refer to the manual of outdoor unit for the detail of remote

controller.

Phenomena Cause Countermeasure(1)LED2 on indoor controller board

is off.• When LED1 on indoor controller board is also off.1 Power supply of rated voltage is not supplied to out-

door unit.

2 Defective outdoor controller circuit board

3 Power supply of 220~240V is not supplied to indoorunit.

4 Defective indoor controller board

1 Check the voltage of outdoor power supply terminal block (L, N) or (L3, N).• When AC 220~240V is not detected.

Check the power wiring to outdoor unit and the breaker.

• When AC 220~240V is detected.—Check 2 (below).

2 Check the voltage between outdoor terminal block S1 and S2.• When AC 220~240V is not detected.

Check the fuse on outdoor controllercircuit board.Check the wiring connection.

• When AC 220~240V is detected.—Check 3 (below).

3 Check the voltage between indoor terminalblock S1 and S2.• When AC 220~240V is not detected.

Check indoor/outdoor unit connecting wire for mis-wiring.

• When AC 220~240V is detected.—Check 4 (below).

4 Check the fuse on indoor controller board.Check the wiring connection.If no problem are found, indoor controllerboard is defective.

(2)LED2 on indoor controller board is blinking.

• When LED1 on indoor controller board is also blinking.Connection failure of indoor/outdoor unit connecting wire

• When LED1 is lit.1 Mis-wiring of remote controller wires

Under twin triple indoor unit system, 2 or more indoor units are wired together.

2 Refrigerant address for outdoor unit is wrong or notset.Under grouping control system, there are some units whose refrigerant address is 0.

3 Short-cut of remote controller wires4 Defective remote controller

Check indoor/outdoor unit connecting wirefor connection failure.

1 Check the connection of remote con-troller wires in case of twin triple indoor unit system. When 2 or more indoor unitsare wired in one refrigerant system, connect remote controller wires to one ofthose units.

2 Check the setting of refrigerant addressin case of grouping control system.If there are some units whose refrigerant addresses are 0 in one group, set one of the units to 0 using SW1 (3-6) on outdoor controller circuit board.

34 Remove remote controller wires and check LED2 on indoor controller board.

• When LED2 is blinking, check theshort-cut of remote controller wires.

• When LED2 is lit, connect remote controller wires again and:if LED2 is blinking, remote controller is defective; if LED2 is lit, connection failure of remote controller terminal block etc. has returned to normal.

HWE0711C.qx 12.10.10 14:10 Page 30

Page 33: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

31

6-5. TEST POINT DIAGRAM6-5-1. Indoor controller boardSEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L)

CN01 Power supply voltage (220 - 240VAC)

SWE Emergency operation

SW1 Model selection

SW2 Capacity setting

CN32 Remote start/stop adapter

CN22 For MA remote controller cable con-nection (10 - 13 VDC (Between 1 and 3.))

CN51 Centralized control

CN41 JAMA standard HA terminal A

CN44 Thermistor (liquid/condenser/evaporator temperature)

CN4F Float thermistor

CN20 Thermistor (Inlet temperature)

CN3C Indoor-outdoor transmission(0 - 24VDC)

CNMF Fan motor output1 - 4: 310 - 340 VDC5 - 4: 15 VDC6 - 4: 0 - 6.5 VDC7 - 4: Stop 0 or 15 VDC Run 7.5 VDC

(0 - 15 pulse)

CNP Drain-up mechanism output (200VAC)

CN2L LOSSNAY

CN90 Wireless remote controller

(*1)

VFG Voltage on the (-) side of PC672 and C955(Same with the voltage between 7 (+) and 4 (-) of CNMF)

VCC Voltage between the C955 pins 15 VDC(Same with the voltage between 5 (+) and 4 (-) of CNMF)

Vsp Voltage between the C626 pins0VDC (with the fan stopped)1 - 6.5VDC (with the fan in operation)(Same with the voltage between 6 (+) and 4 (-) of CNMF)

CN3C

CNP

Fuse(6.3A 250V)

CNMF

CN20

CN44

CN90

CN4F

LED1

LED2

LED3

SWE

CN2L

C626

PC672

SW2

CN41

CN22

SW1

CN32

CN51

CN01

C955

HWE0711C.qx 12.10.10 14:10 Page 31

Page 34: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

32

6-6. TROUBLE CRITERION OF MAIN PARTSSEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L)

Room temperaturethermistor(TH1)

Condenser/evaporator temperature thermistor(TH5)

Measure the resistance with a tester.(Part temperature 10°C ~ 30°C)

Pipe temperature thermistor/liquid(TH2)

Wiring diagram

Check method and criterionPart name

Normal

8kΩ~20kΩ

Abnormal

Opened or short-circuited

Motor

Board with build-in motor

Current detecting resistor

Regulator Hall IC

Motor winding

Powerdevice

Predriver

Vm (Power supply for motor)

Vcc (Power supply for control)

Vsp (Speed command voltage)

PG (Pulse output for rotation)

GND

HWE0711C.qx 12.10.10 14:10 Page 32

Page 35: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

33

6-7. DC FAN MOTOR (FAN MOTOR/ INDOOR CONTROLLER BOARD)

Notes · High voltage is applied to the connecter (CNMF) for the fan motor. Give attention to the service. · Do not pull out the connector (CNMF) for the motor with the power supply on. (It causes trouble of the indoor controller circuit board and fan motor.)Self checkSymptom : The indoor fan cannot turn around.

No

NG

NG

Wiring contact checkContact of fan motor connector (CNMF)

Check the fuse (FUSE) on indoorcontroller board.

Power supply check (Remove the connector (CNMF))Measure the voltage in the indoor controller circuit board.TEST POINT 1 : VDC (between 1 (+) and 4 (-) of the fan connector): VDC DC310~340VTEST POINT 2 : VCC (between 5 (+) and 4 (-) of the fan connector): VCC DC15V

Wiring recovery

Replace drain pump (DP).

Replace indoor controller board.

Replace the fan motor.

Replace indoor controller board (I.B).Replace fan motor (MF).

Replace indoor controller board.

Replace the fan motor.

Is the voltage normal?

Is there no contact failure?

Yes

1

2

Yes

No

Did the fuse blow?Check the drain pump (DP)Is the resistance betweenterminals normal?

No

Yes Yes

No

Check the operation of fan. END

Yes OK

Check the operation. END

OK

Check method of DC fan motor (fan motor / indoor controller circuit board)

HWE0711C.qx 12.10.10 14:10 Page 33

Page 36: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

34

SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L)

1. Control box1. Removing the control box cover(1) Remove the two fixing screws on the cover (A)

to remove it.

2. Thermistor (Intake air)1. Remove the control box cover according to the

procedure in section [1].(1) Pull out the thermistor holder (B) and thermis-

tor (C) on the control box.

(A)Fig. 1

Fig. 2

SEZ-KD·VA model onlyKD71VA(L) model only

(B),(C)

Fig. 3

DISASSEMBLY PROCEDURE7Exercise caution when removing heavy parts.

HWE0711C.qx 12.10.10 14:10 Page 34

Page 37: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

35

3. DrainpanExercise caution when removing heavy parts.

1. Removing the filter and the bottom plate(1) Push up the tab on the filter, and pull out the

filter in the direction of the arrow 1.(2) Remove the fixing screws on the bottom plate

(D), (E) to remove it.

2. Removing the drainpan(1) Pull out the drain pan in the direction of the

arrow 1.

Note• Drain the water out of the drain pan before

removing it.• To avoid dew condensation, use insulated

screws in the places marked with circles inFig. 6.

(D) (E)

(a)(a) (a)

(a)

(a) Tab

Fig. 4

Fig. 5

Insulation material

(E)

Fig. 6

HWE0711C.qx 12.10.10 14:10 Page 35

Page 38: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

36

4. Thermistor (Condenser / evaporator)(Liquid pipe)1. Remove the drain pan according to the proce-

dure in section [3].2. Removing the Heat exchanger cover(1) Remove the four fixing screws on the heat

exchanger cover (F) to remove it.

3. Removing the thermistor(1) Remove the thermistor (G) from the thermistor

holder (H) on the copper tube.

Thermistor sizeLiquid pipe: ø8mmCondenser / evaporator: ø6mm

(F)

Fig. 7

(G),(H)

Fig. 8

Exercise caution when removing heavy parts.

HWE0711C.qx 12.10.10 14:10 Page 36

Page 39: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

37

3. Removing the motor cable(1) Remove the motor cable threw the rubber

bush.

4. Removing the fan motor and the Sirocco fan(1) Remove the two motor fixing screws to

remove the motor and the Sirocco fan in thedirection of arrow 3.

Fig. 11

(2) Remove the four fan case fixing screws totake the top half of the fan casing off.

Fig. 12

Exercise caution when removing heavy parts.

2. Removing the fan casing (bottom half)(1) Squeeze the tabs on the fan casing to remove

it in the direction of arrow 2.(a)

(a) Tab

Fig. 10

5. Fan and fan motor1. Removing the filter and the bottom plate(1) Push down the tab on the filter, and pull out

the filter in the direction of the arrow 1.(2) Remove the fixing screws on the bottom plate

(J) to remove it.

(J)

(a)

(a) Tab

(a)(a)(a)

Fig. 9

HWE0711C.qx 12.10.10 14:10 Page 37

Page 40: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

38

(K)

Fig. 13

(2) Remove the two bearing retainer screws toremove the bearing.

Fig. 14

6. Bearing [KD50·60·71VA(L) model only]1. Removing the bearing(1) Remove the two fixing screws on the bearing

cover (K) to remove it.

7. Heat exchanger1. Remove the drain pan according to the proce-

dure in section [3].2. Remove the heat exchanger cover according to

the procedure in section [4] 2.3. Removing the cover(1) Remove the two fixing screws on the cover (L)

to remove it.

4. Removing the Heat exchanger(1) Remove the fixing screws on the heat

exchanger (M) to remove it.

(L)

Fig. 15

(M)

Fig. 16

Exercise caution when removing heavy parts.

HWE0711C.qx 12.10.10 14:10 Page 38

Page 41: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

HWE0711C.qx 12.10.10 14:10 Page 39

Page 42: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

HWE0711C.qx 12.10.10 14:10 Page 40

Page 43: SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ · PDF file2 1 PART NAMES AND FUNCTIONS Indoor Unit SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Air outlet Air

HWE0711C.qx 12.10.10 14:10 Page 41