    SEWER DESIGN CALCULATION

    Waste Water Flow Rate

    1.

    Average Flow = 225 liters per person

    = 225 x 1 x 10-3

    m3/s

    2. Peak Flow Factor = 4.7 / P 0.11 (P is estimated population equivalent

    in thousand)

    Hydraulic Design

    1. Minimum Velocity = 0.8 m/s

    2. Maximum Velocity = 4.0 m/s

    3. Minimum Depth of Invert = 1.5 m

    4. Minimum Size of Sewer = 225mm VCP5. Minimum Size of Laterals = 150mm VCP

    Manholes

    1. Distance between Manholes

    Maximum 100m for sewer up to 225 mm diameter

    2. Location of Manholes

    Upstream end of all sewer

    Every change in direction

    Every change in gradient Every change in size of sewer

    All intersection and junction

    Materials

    Vitrified Clay Pipe (VCP)Sewers up to 225 mm diameter

    METHOD OF CALCULATION

    1. Design for Sewerage Flow Rate

    Peak Flow, Q peak = Average flow, Q averagex Peak Flow Factor

    = Q averagex 4.7 / P0.11

    (NOTE: P is population Equivalent in Thousand)

  • 7/23/2019 Sewer Design Calculation

    2/2

    2. Flow Data in Verified Clay Pipe

    From Mannings Formula,

    V = 1/n R 2/3S 1/2 ------------------------ (1)

    From Continuity Equation.

    Q = V A ------------------------ (2)

    Applying (1) into (2)

    Q = (1/n R2/3

    S) A

    Where

    V = velocity (m/s)

    R = hydraulic radius (m)

    S = gradient

    Q = capacity (m3/s)

    A = cross-sectional area of pipe (m2)

    n = Mannings coefficient (0.013 for VCP)