SEWER DESIGN CALCULATION
Waste Water Flow Rate
1.
Average Flow = 225 liters per person
= 225 x 1 x 10-3
m3/s
2. Peak Flow Factor = 4.7 / P 0.11 (P is estimated population equivalent
in thousand)
Hydraulic Design
1. Minimum Velocity = 0.8 m/s
2. Maximum Velocity = 4.0 m/s
3. Minimum Depth of Invert = 1.5 m
4. Minimum Size of Sewer = 225mm VCP5. Minimum Size of Laterals = 150mm VCP
Manholes
1. Distance between Manholes
Maximum 100m for sewer up to 225 mm diameter
2. Location of Manholes
Upstream end of all sewer
Every change in direction
Every change in gradient Every change in size of sewer
All intersection and junction
Materials
Vitrified Clay Pipe (VCP)Sewers up to 225 mm diameter
METHOD OF CALCULATION
1. Design for Sewerage Flow Rate
Peak Flow, Q peak = Average flow, Q averagex Peak Flow Factor
= Q averagex 4.7 / P0.11
(NOTE: P is population Equivalent in Thousand)
7/23/2019 Sewer Design Calculation
2/2
2. Flow Data in Verified Clay Pipe
From Mannings Formula,
V = 1/n R 2/3S 1/2 ------------------------ (1)
From Continuity Equation.
Q = V A ------------------------ (2)
Applying (1) into (2)
Q = (1/n R2/3
S) A
Where
V = velocity (m/s)
R = hydraulic radius (m)
S = gradient
Q = capacity (m3/s)
A = cross-sectional area of pipe (m2)
n = Mannings coefficient (0.013 for VCP)