IS-F-PRV-2 INSTALLATION INSTRUCTIONS Installation Instructions 1. The valve should be installed by a licensed contractor in accordance with local codes and ordi- nances. This valve should be installed where it is accessible with sufficient clearance for cleaning, service, or adjustment. 2. Before installing the valve, be sure that the pipe ends are reamed and threads are cut to size. 3. Flush the lines to remove all loose scale, dirt and other foreign matter that can damage or clog the valve. 4. Install the regulator with the arrow on the body pointing in the direction of the flow. 5. Regulator may be installed vertically or horizontally (upright or inverted). 6. Start Up — Open cold water supply then hot water supply. Inspect for leaks. Note: The valve should be inspected annually to assure maximum life and performance. Note: PRV-2 — These valves are suitable for outdoors or pit installations. Series PRV-2 Water Pressure Reducing Valves Sizes: 1  ⁄ 2" - 2" (15 – 50mm)  Parallel installations are recommended where high flow or low flow demand is intermittent/occasional. They are also used for installations where service cannot be interrupted. Typical Installation Series Installation Parallel Installation Series installations are recommended where very high supply pressure must be reduced to a very low downstream pressure. Reducing the pressure in stages eliminates whistling and noise. TO FIXTURES BACKFLOW PREVENTER PRESSURE REGULATOR    T    O     S    I    L    L    C    O    C    K WATER METER SUPPLY PRESSURE GAUGE ( 2 PLACES ) SHUTOFF VALVE ( 2 PLACES ) TO FIXTURES BACKFLOW PREVENTER PRESSURE REGULATOR ( 2 PLACES )    T    O     S    I    L    L    C    O    C    K WATER METER SUPPLY SHUTOFF VALVE ( 2 PLACES ) PRESSURE GAUGE ( 2 PLACES) TO FIXTURES WATER METER BACKFLOW PREVENTER PRESSURE REGULATOR ( 2 PLACES )    T    O     S    I    L    L    C    O    C    K SUPPLY SHUTOFF VALVE ( 6 PLACES ) PRESSURE GAUGE ( 2 PLACES ) PRV-2-U 1  ⁄ 2" - 1" (15 - 25mm) PRV-2-DU 1 1  ⁄ 4" - 2" (32 - 50mm)

Series PRV-2 Installation Instructions

  • Upload
    febco

  • View
    222

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Series PRV-2 Installation Instructions

8/8/2019 Series PRV-2 Installation Instructions

http://slidepdf.com/reader/full/series-prv-2-installation-instructions 1/2

IS-F-PRV

I N S T A L L A T I O N I N S T R U C T I O N S

Installation Instructions1. The valve should be installed by a licensed contractor in accordance with local codes and ordi-

nances. This valve should be installed where it is accessible with sufficient clearance for cleaning,service, or adjustment.

2. Before installing the valve, be sure that the pipe ends are reamed and threads are cut to size.

3. Flush the lines to remove all loose scale, dirt and other foreign matter that can damage or clog thevalve.

4. Install the regulator with the arrow on the body pointing in the direction of the flow.

5. Regulator may be installed vertically or horizontally (upright or inverted).

6. Start Up — Open cold water supply then hot water supply. Inspect for leaks.

Note: The valve should be inspected annually to assure maximum life and performance.

Note: PRV-2 — These valves are suitable for outdoors or pit installations.

Series PRV-2

Water Pressure Reducing Valves

Sizes: 1 ⁄ 2" - 2" (15 – 50mm)

 Parallel installations are recommendedwhere high flow or low flow demand isintermittent/occasional. They are also usedfor installations where service cannotbe interrupted.

Typical Installation

Series Installation

Parallel Installation

Series installations are recommended wherevery high supply pressure must be reduced toa very low downstream pressure. Reducingthe pressure in stages eliminates whistlingand noise.

TO FIXTURES

BACKFLOWPREVENTER

PRESSUREREGULATOR

   T   O    S

   I   L   L   C   O   C   K

WATER

METERSUPPLY

PRESSURE GAUGE

( 2 PLACES )

SHUTOFF VALVE( 2 PLACES )

TO FIXTURES

BACKFLOW

PREVENTER

PRESSURE

REGULATOR

( 2 PLACES )

   T   O    S

   I   L   L   C   O   C   K

WATER

METERSUPPLY

SHUTOFF VALVE

( 2 PLACES )

PRESSURE GAUGE

( 2 PLACES)

TO FIXTURES

WATER

METER

BACKFLOW

PREVENTERPRESSURE

REGULATOR

( 2 PLACES )

   T   O    S

   I   L   L   C   O   C   K

SUPPLY

SHUTOFF VALVE

( 6 PLACES )

PRESSURE GAUGE

( 2 PLACES )

PRV-2-U1 ⁄ 2" - 1" (15 - 25mm)

PRV-2-DU11 ⁄ 4" - 2" (32 - 50mm)

Page 2: Series PRV-2 Installation Instructions

8/8/2019 Series PRV-2 Installation Instructions

http://slidepdf.com/reader/full/series-prv-2-installation-instructions 2/2

• To clean strainer or replace seat/stem module, shut off supply, loosenLocknut and Lock Seal and back off Adjusting Screw.

• Remove Spring Cage, Spring, Washer and Slip Ring. Grasp Stem Nutwith fingers or pliers and lift module from body.

• Replace module and reassemble valve.

• Readjust pressure setting.

 AdjustmentRegulator is factory preset to 50psi (345 kPa). To adjust pressure setting,loosen the lock nut and turn the adjusting bolt clockwise to increase pres-sure, counter clockwise to decrease pressure.

Note: Use a pressure gauge downstream to adjust and verify the pressuresetting.

Bypass Feature*This regulator has a built-in thermal expansion bypass feature. This featureprevents downstream pressure from rising to more than 10psi above thesupply pressure.

* Bypass will not work if inlet pressure is above 150psi (10.3 bar).

TroubleshootingHigh System PressureIf the downstream system pressure is higher than the set pressure underno flow conditions, the cause could be thermal expansion, pressure creepor dirt/debris on the seat.

Thermal expansion occurs whenever water is heated in a closed system.The system is closed when supply pressure exceeds 150psi, or a checkvalve or backflow preventer is installed in the supply piping.

You must make provisions for pressure relief protection of your plumbingsystem and components. The use of a relief valve or potable water expan-sion tank may be required.

To determine if this is the result of thermal expansion, try briefly openingthe cold water tap. If the increased pressure is caused by thermal expan-sion, the pressure will immediately be relieved and the system will returnto the set pressure.

Stem Nut

Strainer

Stem Nut

Strainer

SEAT/STEM MODULE

SEAT/STEM MODULE

AdjustingScrew

Lock Nut

Lock Seal

Spring Washer

Spring

Spring Cage

Stem Nut

Slip Ring

Seat/StemModule

Strainer

Maintenance Instructions

Repair Kits 1 ⁄ 2" – 2" (15 – 50mm)When ordering, specify Ordering Code, Kit number and Valve Size.

Ordering Code Kit No. Sizein. mm 

0710606 PRV-1, PRV-2 EZ-RK 1 ⁄ 2", 3 ⁄ 4", 1" 15, 20, 25

0710607 PRV-1, PRV-2 EZ-L-RK 11 ⁄ 4", 11 ⁄ 2", 2" 32, 40, 50

Kit consists of: Seat / Stem module.

AdjustingScrew

Lock NutLock Seal

Spring Washer

Spring

Spring Cage

Slip Ring

Seat/StemModule

PRV-2-U1 ⁄ 2" - 1" (15 - 25mm)

PRV-2-DU

11 ⁄ 4" - 2" (32 - 50mm)

 A Di vision of Watts Water Techno logies, I nc. USA: 4381 N. Brawley • Ste. 102 • Fresno, CA • 93722 • Tel. (559) 441-5300 • Fax: (559) 441-5301 • www.FEBCOonline.com

Canada: 5435 North Service Rd. • Burlington, ONT. • L7L 5H7 • Tel. (905) 332-4090 • Fax: (905) 332-7068 • www.FEBCOonline.ca

IS-F-PRV-2 0845 EDP# 1915945 © FEBCO, 2008

Limited Warranty: FEBCO warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of original shipment. In the event

of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHERWARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIEDWARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be respons ible for any incidental, specialor consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resultingfrom labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has nocontrol. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the abovelimitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws todetermine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OFMERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.