Series “L”Air conditioners for

Laboratories

Page 13: Series L Air conditioners for Laboratories

Modular air conditioners with upflow air supply.

With direct expansion circuit: OLA series

With chilled water coil: OLU series

Page 14: Series L Air conditioners for Laboratories

     

Possible Applications:

Surgical roomsPharmaceutical industries   Aseptic surgical rooms    Electronic industries

Food industries

Air-space industries Metrological rooms

Research laboratories     Hospital laboratories

Fresh air treatment

Page 15: Series L Air conditioners for Laboratories

•For the treatment of total fresh air or with partial or total re-circulation.

•Possibility of exaust section.

•Available static pressure up to 400 Pa downstream the F9 filter

•Possibility of automatic control of the overpressure of

the controlled room in regards to a reference one.

Page 16: Series L Air conditioners for Laboratories
Page 17: Series L Air conditioners for Laboratories

“L” (Low air flow):

low air flow in regards to the cooling capacity and therefore good for all or quite all fresh air treatment for every type of installation.It must be notice that in these units the installation of a preheating coil is impossible and therefore the risk of freezing the cold water one cannot be avoided, so either an antifreeze coil is installed inside the fresh air ducts, or a glycole charge must be added to the water content of the hydraulic circuit. “H” (High air flow):

hence high air flow in regards to the cooling capacity, therefore good for the treatment of higher air recirculation.

Page 18: Series L Air conditioners for Laboratories

Fundamental Characteristics: in conformity to the G.M.P (good manufacturing practice). 

The air conditioners of the “L” series can satisfy the following requests:

Page 19: Series L Air conditioners for Laboratories

The units of the “L” Series come with a G4 class filter as standard equipment installed upstream the cooling coil and a post filter of class F9 on air supply.

The F9 filter, complete with its gaskets locking system to assure the elimination of any air bypass through the gasket, is entered in a supply plenum to be installed as standard on top of the unit.

In alternative, when the total height is a problem, the discharge plenum can be installed on the back of the unit (accessory: fans backward rotated).

Page 20: Series L Air conditioners for Laboratories

In case of necessity of higher available static pressure (above 400 Pa up to 800), the units of the Series “H”: air conditioners for surgical rooms, or of the Series “W: “air conditioners for clean rooms” must be forecast.

The unit provides, downstream of the supply filter, up to 400 Pa of prevalence (controlled by the inverter) for the air ducts both in intake and supply to the room, for the sound dampers and for the eventual absolute terminal filtering system which, if installed, must anyway have a very low pressure drop: maximum of 200 Pa.

Page 21: Series L Air conditioners for Laboratories

These units are compatible with absolute filters working in low air speed: unidirectional (laminar) ceilings.

The two filter sections of the units are equipped with a differential pressostat for the indication through the microprocessor of the status of dirty filter.

Page 22: Series L Air conditioners for Laboratories

Control microprocessor

All the operating and safety functions of “L” Series air conditioners are managed by the standard pCO2

microprocessor, which allows controlling temperature in two ways: proportional or proportional-integral and relative humidity in proportional.

Also, the pCO2 controls the room overpressure and can be easily connected, through a standard MODBUS/JBUS protocol incorporated in the software, with the BMS systems of all major Manufacturers.

Page 23: Series L Air conditioners for Laboratories

Inverter on the supply air fans

A measurer, standard installed in the supply section, controls the actual air flow so that the microprocessor can compare it with the set point and adjust through an inverter the fan revolution number to compensate the increased pressure drop due to the filters becoming dirty. An absolutely constant air flow is therefore assured. In alternative, when a constant air pressure inside the supply duct is required, a pressure transmitter is installed downstream the F9 air filter and the unit is handled to keep it constant.

Page 24: Series L Air conditioners for Laboratories

Framework: “sandwich” panels

The framework of the unit is made of galvanised steel with anodised aluminium profiles. The compressors, electric panel and regulation are installed in a lateral section completely separated from the air flow.

The panels are two-wall “sandwich” type, made of light grey prepainted galvanised steel plates, and are thermally and acoustically insulated inside with 25mm-thick foamed polyurethane.

The condensate bac is in stainless steel.

Page 25: Series L Air conditioners for Laboratories

Post-heating/heating hot water coil with modulating proportional valveStep or modulating electric post-heater/heaterHot gas bypass modulating reheating coilAutonomous modulating humidifier with immersed electrodes.Modulating dehumidification modulating system.

Rigorous control of the temperature and humidity

Page 26: Series L Air conditioners for Laboratories

These units are compatible with absolute filters working in low air speed: unidirectional (laminar) ceilings.

The two filter sections of the units are equipped with a differential pressostat for the indication through the microprocessor of the status of dirty filter.

Page 27: Series L Air conditioners for Laboratories
Page 28: Series L Air conditioners for Laboratories

\

Page 29: Series L Air conditioners for Laboratories

\

Page 30: Series L Air conditioners for Laboratories
Page 31: Series L Air conditioners for Laboratories
Page 32: Series L Air conditioners for Laboratories
Page 33: Series L Air conditioners for Laboratories
Page 34: Series L Air conditioners for Laboratories

Thank you