30
Series description: Wilo-Stratos-D Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 1 / 30 90 80 60 40 20 70 50 30 10 0 Q/m³/h 0 2 6 8 10 12 14 16 4 H/m 80/1-12 65/1-16 50/1-16 65/1-12 40/1-16 32/1-8 32/1-12 40(50)1-8 Wilo-Stratos-D + 40/1-12 50/1-9 50/1-12 Design Glandless double circulation pump with flange connection, EC motor with automatic power adjustment Application Hot-water heating systems of all kinds, air-conditioning systems, closed cooling circuits, industrial circulation systems Type key Example: Stratos‐D 40/1-8 Stratos High-efficiency pump (flange-end pump), electronically controlled D Double pump 40/ Nominal connection diameter 1-8 Nominal delivery head range [m] Special features/product advantages Position-independent LC display Infrared interface System expansion by means of interface modules for communication: Modbus, BACnet, CAN, LON, PLR Volume flow limitation by Q limit function (via IR stick) Pump housing with cataphoretic (KTL) coating protects against corrosion due to condensation formation Technical data Energy efficiency index (EEI) ≤ 0.27 Permissible temperature range ‐-10°C to +110°C Mains connection 1~230 V, 50/60 Hz Protection class IP X4D Flange connection DN 32 to DN 80 Max. operating pressure, standard version: 6/10 bar or 6 bar (special version: 10 bar or 16 bar) Equipment/function Operating modes Manual control mode (n=constant) Δp-c for constant differential pressure Δp-v for variable differential pressure Δp-T for temperature-controlled differential pressure (programmable via IR-Stick, IR-Monitor, Modbus, BACnet, LON or CAN) Q-Limit to restrict the maximum volume flow (setting only via IR-Stick) Manual functions Setting the operating mode Setting the differential pressure setpoint Setting automatic setback operation Setting the pump ON/OFF Setting the speed (manual control mode) Automatic functions Infinitely variable power adjustment according to the operating mode Automatic setback operation Deblocking function Soft start Full motor protection with integrated trip electronics External control functions "Overriding Off" control input (possible with Stratos IF-Modules) "Overriding Min" control input (possible with Stratos IF-Modules) "Analogue In 0 ‐ 10 V" control input (remote speed adjustment) (possible with Stratos IF-Modules) "Analogue In 0 ‐ 10 V" control input (remote setpoint adjustment) (possible with Stratos IF-Modules) Signal and display functions Individual/collective fault signal (potential-free NC contact) (programmable with the IR-Stick/IR-Monitor) Collective fault signal (potential-free NC contact) Individual run signal (potential-free NO contact) (possible with Stratos IF-Modules) Fault signal light LC display for indication of pump data and fault codes Data exchange Infrared interface for wireless data exchange with IR-Stick/IR-Monitor Modbus RTU serial digital interface for connection to building automation BA via RS485 BUS system (possible with Stratos IF- Modules) BACnet serial digital interface MS/TP slave for connection to building automation BA via RS485 BUS system (possible with Stratos IF- Modules) CAN serial digital interface for connection to building automation BA via IF-Modules BUS system (possible with Stratos IF-Modules) LON serial digital interface for connection to a LONWorks network (possible with Stratos IF-Modules) PLR serial digital interface for connection to BA via Wilo interface converter or company-specific coupling modules (possible with Stratos IF-Modules) Dual pump management (double pump or 2 x single pumps) Main/standby operation (automatic fault-actuated switchover/time- dependent pump cycling): various combinations with Stratos IF- Modules (accessories) possible Parallel operation (efficiency-optimised peak load activation and deactivation): various combinations with Stratos IF-Modules (accessories) possible Features

Series description: Wilo-Stratos-D - Home | ATAC Solutionsatacsolutions.com/eshop_uploads/wilo/wilo-stratos-d/wilo_stratos_d.pdf · Series description: Wilo-Stratos-D Subject to change

Embed Size (px)

Citation preview

Series description: Wilo-Stratos-D

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 1 / 30

9080604020 705030100 Q/m³/h0

2

6

8

10

12

14

16

4

H/m

80/1-12

65/1-16

50/1-16

65/1-12

40/1-16

32/1-8

32/1-12

40(50)1-8

Wilo-Stratos-D+

40/1-12

50/1-9

50/1-12

DesignGlandless double circulation pump with flange connection, EC motor withautomatic power adjustment

ApplicationHot-water heating systems of all kinds, air-conditioning systems, closedcooling circuits, industrial circulation systems

Type keyExample: Stratos‐D 40/1-8

StratosHigh-efficiency pump (flange-end pump),electronically controlled

D Double pump

40/ Nominal connection diameter

1-8 Nominal delivery head range [m]

Special features/product advantagesPosition-independent LC display•Infrared interface•System expansion by means of interface modules for communication:Modbus, BACnet, CAN, LON, PLR

Volume flow limitation by Q limit function (via IR stick)•Pump housing with cataphoretic (KTL) coating protects againstcorrosion due to condensation formation

Technical dataEnergy efficiency index (EEI) ≤ 0.27•Permissible temperature range ‐-10°C to +110°C•Mains connection 1~230 V, 50/60 Hz•Protection class IP X4D•Flange connection DN 32 to DN 80•Max. operating pressure, standard version: 6/10 bar or 6 bar (specialversion: 10 bar or 16 bar)

Equipment/functionOperating modes

Manual control mode (n=constant)•Δp-c for constant differential pressure•Δp-v for variable differential pressure•Δp-T for temperature-controlled differential pressure (programmablevia IR-Stick, IR-Monitor, Modbus, BACnet, LON or CAN)

Q-Limit to restrict the maximum volume flow (setting only via IR-Stick)•Manual functions

Setting the operating mode•Setting the differential pressure setpoint•Setting automatic setback operation•Setting the pump ON/OFF•Setting the speed (manual control mode)•

Automatic functionsInfinitely variable power adjustment according to the operating mode•Automatic setback operation•Deblocking function•Soft start•Full motor protection with integrated trip electronics•

External control functions"Overriding Off" control input (possible with Stratos IF-Modules)•"Overriding Min" control input (possible with Stratos IF-Modules)•"Analogue In 0 ‐ 10 V" control input (remote speed adjustment)(possible with Stratos IF-Modules)

"Analogue In 0 ‐ 10 V" control input (remote setpoint adjustment)(possible with Stratos IF-Modules)

Signal and display functionsIndividual/collective fault signal (potential-free NC contact)(programmable with the IR-Stick/IR-Monitor)

Collective fault signal (potential-free NC contact)•Individual run signal (potential-free NO contact) (possible with StratosIF-Modules)

Fault signal light•LC display for indication of pump data and fault codes•

Data exchangeInfrared interface for wireless data exchange with IR-Stick/IR-Monitor•Modbus RTU serial digital interface for connection to buildingautomation BA via RS485 BUS system (possible with Stratos IF-Modules)

BACnet serial digital interface MS/TP slave for connection to buildingautomation BA via RS485 BUS system (possible with Stratos IF-Modules)

CAN serial digital interface for connection to building automation BAvia IF-Modules BUS system (possible with Stratos IF-Modules)

LON serial digital interface for connection to a LONWorks network(possible with Stratos IF-Modules)

PLR serial digital interface for connection to BA via Wilo interfaceconverter or company-specific coupling modules (possible with StratosIF-Modules)

Dual pump management (double pump or 2 x single pumps)Main/standby operation (automatic fault-actuated switchover/time-dependent pump cycling): various combinations with Stratos IF-Modules (accessories) possible

Parallel operation (efficiency-optimised peak load activation anddeactivation): various combinations with Stratos IF-Modules(accessories) possible

Features

Series description: Wilo-Stratos-D

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 2 / 30

Flange versions:•Standard version for DN 32 to DN 65 pumps: PN 6/10 combinationflange (PN 16 flange according to EN 1092-2) for PN 6 and PN 16counter flanges,

Standard version for pumps DN 80: PN 6 flange (designed for PN 16according to EN 1092-2) for PN 6 counter flange

Special version for DN 32 to DN 80 pumps: PN 16 flange (accordingto EN 1092-2) for PN 16 counter flange,

Double switchover valve in pump housing•Plug-in position for optional extension with Wilo-IF‐Modules•

MaterialsPump housing: Grey cast iron•Shaft: stainless steel•Bearing: Carbon, metal impregnated•Impeller: Plastic•

Scope of deliveryPump•Incl. washers for flange screws (for nominal connection diameters DN32 ‐ DN 65)

Including installation and operating instructions•

OptionsSpecial versions for operating pressure PN 16•

AccessoriesCounter flanges for flange connection•Blind flanges•IR-Stick•IR Monitor•Stratos IF-Module: Modbus, BACnet, CAN, PLR, LON, DP, Ext. Off, Ext.Min., SBM, Ext. Off/SBM

Duty chart: Wilo-Stratos-D

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 3 / 30

Duty chart

Q/m³/h0 10 20 30 40 50 60 70 80 90 100

H/m

0

2

4

6

8

10

12

14

16

Wilo-Stratos-D+

50/1-12 65/1-12

80/1-12

40/1-12

40/1-16

65/1-16

50/1-16

40(50)/1-8

32/1-1232/1-8

50/1-9

Product list: Wilo-Stratos-D

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 4 / 30

Type Max. volumeflow

Max.delivery

head

Energyefficiencyindex (EEI)

Nominalflange

diameter

Ratedpressure

Overalllength

Mainsconnection

Grossweight

Art no.

Qmax / m3/h Hmax / m PN / bar l0 / mm m / kg

Stratos-D 32/1-8 13 7 ≤ 0.27 DN 32 6/10 2201~230 V,50/60 Hz

14.0 2090461

Stratos-D 32/1-12 21 10 ≤ 0.27 DN 32 6/10 2201~230 V,50/60 Hz

19.0 2090462

Stratos-D 40/1-8 26 8 ≤ 0.27 DN 40 6/10 2201~230 V,50/60 Hz

19.0 2090463

Stratos-D 40/1-12 35 12 ≤ 0.27 DN 40 6/10 2501~230 V,50/60 Hz

28.0 2090464

Stratos-D 40/1-16 36 17 ≤ 0.27 DN 40 6/10 2501~230 V,50/60 Hz

47.0 2150597

Stratos-D 50/1-8 26 8 ≤ 0.27 DN 50 6/10 2401~230 V,50/60 Hz

21.0 2090465

Stratos-D 50/1-9 38 9 ≤ 0.27 DN 50 6/10 2801~230 V,50/60 Hz

30.0 2090466

Stratos-D 50/1-12 41 12 ≤ 0.27 DN 50 6/10 2801~230 V,50/60 Hz

30.0 2090467

Stratos-D 50/1-16 57 18 ≤ 0.27 DN 50 6/10 3401~230 V,50/60 Hz

51.0 2150598

Stratos-D 65/1-12 69 11 ≤ 0.27 DN 65 6/10 3401~230 V,50/60 Hz

53.5 2150596

Stratos-D 65/1-16 79 17 ≤ 0.27 DN 65 6/10 3401~230 V,50/60 Hz

54.0 2150599

Stratos-D 80/1-12 109 13 ≤ 0.27 DN 80 6 3601~230 V,50/60 Hz

64.5 2150600

Stratos-D 80/1-12 109 13 ≤ 0.27 DN 80 10 3601~230 V,50/60 Hz

64.5 2150601

Data sheet: Wilo-Stratos-D 32/1-8

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 5 / 30

Pump curves Δp-c (constant)

0 2 4 6 8 10 12

0 1 2 3 4

14

14

0 1 2 3 4 5

0

1

2

3

4

5

6

7

0

10

20

30

40

50

60

70

0 2 4 6 8 10 120

100

200

300

min.

P1/W

max.

Wilo-Stratos-D 32/1-81~230 V - DN 32

p/kPa

m/sv

max.

∆p-c

+

P1 Wilo-Stratos 32/1-8

min.

1m

2m

3m4m5m6m7m

H/m

Q/m³/h

Q/l/s

Q/m³/h

Pump curves Δp-v (variable)

0 2 4 6 8 10 12

0 1 2 3 4

0 1 2 3 4 5

0

1

2

3

4

5

6

7

0

10

20

14

14

30

40

50

60

70

0 2 4 6 8 10 120

100

200

300

P1/W

Q/m³/h

Q/l/s

Q/m³/h

max.

Wilo-Stratos-D 32/1-81~230 V - DN 32

p/kPa

m/sv

+

P1 Wilo-Stratos 32/1-8min.

2m3m4m5m6m7m

min.

H/m

max.

∆p-v

Approved fluids (other fluids on request)

Heating water (in accordance with VDI2035)

Water-glycol mixtures (max. 1:1; above20% admixture, the pumping datamust be checked)

Permitted field of application

Temperature range at max. ambienttemperature +40 °C

-10...+110 °C

Maximum permissibleoperating pressure

Pmax 6/10 bar

Pipe connections

Flange Combination flange PN6/10 (PN16 flange according to EN1092-2)

Nominal flange diameter DN 32

Overall length l0 220 mm

Motor/electronics

Energy efficiency index (EEI) ≤ 0.27

Electromagnetic compatibility EN 61800-3

Emitted interference EN 61000-6-3

Interference resistance EN 61000-6-2

Speed control Frequency converter

Protection class IP X4D

Insulation class F

Mains connection 1~230 V, 50/60 Hz

Nominal motor power P2 100.00 W

Speed n 1400 - 3700 rpm

Power consumption P1 9 - 130 W

Current consumption I 0.13 - 1.20 A

Motor protection integrated

Threaded cable connection PG 1x7/1x9/1x13.5

Materials

Pump housing Grey cast iron (EN-GJL-250)

Impeller Plastic (PPE - 30% GF)

Pump shaft Stainless steel (X30CR13)

Bearing Carbon, metal impregnated

Minimum suction head at suction port for avoidingcavitation at water pumping temperature

Data sheet: Wilo-Stratos-D 32/1-8

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 6 / 30

Dimension drawing

Pg 7

Pg 9Pg 13,5

182

10

61

12

107107

22

0

11

48

9

44

11

0

DN 32

Dimension drawing, flangeØ 140

Ø 100

Ø 90

Ø 76

DN 32

4 x Ø14

4 x Ø19

Terminal diagram

L1 L3

L2 L3

L1 L2

PE SSM

3~230 V, 50/60 Hz

L N PE SSM

1~ 230 V, 50/60 Hz

SSM:

Collective fault signal(NC contact according to VDI 3814, load capacity 1 A,250 V ~)For function, see Wilo catalogue, chapter "Pumpmanagement Wilo-Control, consulting guide"

Minimum suction head at 50 / 95 / 110°C

3 / 10 / 16 m

Information for order placements

Make Wilo

Type Stratos-D 32/1-8

Art no. 2090461

Weight approx. m 12 kg

Data sheet: Wilo-Stratos-D 32/1-12

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 7 / 30

Pump curves Δp-c (constant)

0 4 8 12 16 20

0 1 2 3 4 5 6

0 2 4 6

0

2

4

6

8

10

0

20

40

60

80

100

0 4 8 12 16 200

200

400

600

min.

H/m

P1/W

max.

Wilo-Stratos-D 32/1-121~230 V - DN 32

p/kPa

m/sv

max.

∆p-c

+

P1 Wilo-Stratos 32/1-12

min.

1m2m

3m

4m5m6m8m9m

7m

Q/m³/h

Q/l/s

Q/m³/h

Pump curves Δp-v (variable)

0 4 8 12 16 20

0 1 2 3 4 5 6

0 2 4 6

0

2

4

6

8

10

0

20

40

60

80

100

0 4 8 12 16 200

200

400

600

H/m

P1/W

Q/m³/h

Q/l/s

Q/m³/h

max.

Wilo-Stratos-D 32/1-121~230 V - DN 32

p/kPa

m/sv

+

min.

4m5m6m7m8m

min.

P1 Wilo-Stratos 32/1-12

max.

∆p-v

Approved fluids (other fluids on request)

Heating water (in accordance with VDI2035)

Water-glycol mixtures (max. 1:1; above20% admixture, the pumping datamust be checked)

Permitted field of application

Temperature range at max. ambienttemperature +40 °C

-10...+110 °C

Maximum permissibleoperating pressure

Pmax 6/10 bar

Pipe connections

Flange Combination flange PN6/10 (PN16 flange according to EN1092-2)

Nominal flange diameter DN 32

Overall length l0 220 mm

Motor/electronics

Energy efficiency index (EEI) ≤ 0.27

Electromagnetic compatibility EN 61800-3

Emitted interference EN 61000-6-3

Interference resistance EN 61000-6-2

Speed control Frequency converter

Protection class IP X4D

Insulation class F

Mains connection 1~230 V, 50/60 Hz

Nominal motor power P2 200.00 W

Speed n 1400 - 4800 rpm

Power consumption P1 12 - 310 W

Current consumption I 0.22 - 1.37 A

Motor protection integrated

Threaded cable connection PG 1x7/1x9/1x13.5

Materials

Pump housing Grey cast iron (EN-GJL-250)

Impeller Plastic (PPS - 40% GF)

Pump shaft Stainless steel (X30CR13)

Bearing Carbon, metal impregnated

Minimum suction head at suction port for avoidingcavitation at water pumping temperature

Data sheet: Wilo-Stratos-D 32/1-12

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 8 / 30

Dimension drawing

Pg 7

Pg 9Pg 13,5

204

13

01

17

130110

22

0

12

01

06

57

11

0

DN 32

Dimension drawing, flangeØ 140

Ø 100

Ø 90

Ø 76

DN 32

4 x Ø14

4 x Ø19

Terminal diagram

L1 L3

L2 L3

L1 L2

PE SSM

3~230 V, 50/60 Hz

L N PE SSM

1~ 230 V, 50/60 Hz

SSM:

Collective fault signal(NC contact according to VDI 3814, load capacity 1 A,250 V ~)For function, see Wilo catalogue, chapter "Pumpmanagement Wilo-Control, consulting guide"

Minimum suction head at 50 / 95 / 110°C

3 / 10 / 16 m

Information for order placements

Make Wilo

Type Stratos-D 32/1-12

Art no. 2090462

Weight approx. m 16 kg

Data sheet: Wilo-Stratos-D 40/1-8

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 9 / 30

Pump curves Δp-c (constant)

0 5 10 15 20 25

0 2 4 6

0 1 2 3 4 5 6

0

2

4

6

8

0

20

40

60

80

0 5 10 15 20 250

200

400

600

H/m

P1/W

Wilo-Stratos-D 40/1-81~230 V - DN 40

p/kPa

m/sv

max.

∆p-c

+

P1 Wilo-Stratos 40/1-8

min.

Q/m³/h

Q/l/s

Q/m³/h

min.

max.

1m

2m

3m4m5m6m8m 7m

Pump curves Δp-v (variable)

0 5 10 15 20 25

0 2 4 6

0 1 2 3 4 5 6

0

2

4

6

8

0

20

40

60

80

0 5 10 15 20 250

200

400

600

H/m

P1/W

Q/m³/h

Q/l/s

Q/m³/h

Wilo-Stratos-D 40/1-81~230 V - DN 40

p/kPa

m/sv

+

min.P1 Wilo-Stratos 40/1-8

max.

∆p-v

max.

3m4m5m6m7m

min.

Approved fluids (other fluids on request)

Heating water (in accordance with VDI2035)

Water-glycol mixtures (max. 1:1; above20% admixture, the pumping datamust be checked)

Permitted field of application

Temperature range at max. ambienttemperature +40 °C

-10...+110 °C

Maximum permissibleoperating pressure

Pmax 6/10 bar

Pipe connections

Flange Combination flange PN6/10 (PN16 flange according to EN1092-2)

Nominal flange diameter DN 40

Overall length l0 220 mm

Motor/electronics

Energy efficiency index (EEI) ≤ 0.27

Electromagnetic compatibility EN 61800-3

Emitted interference EN 61000-6-3

Interference resistance EN 61000-6-2

Speed control Frequency converter

Protection class IP X4D

Insulation class F

Mains connection 1~230 V, 50/60 Hz

Nominal motor power P2 200.00 W

Speed n 1400 - 4800 rpm

Power consumption P1 12 - 310 W

Current consumption I 0.22 - 1.37 A

Motor protection integrated

Threaded cable connection PG 1x7/1x9/1x13.5

Materials

Pump housing Grey cast iron (EN-GJL-250)

Impeller Plastic (PPS - 40% GF)

Pump shaft Stainless steel (X30CR13)

Bearing Carbon, metal impregnated

Minimum suction head at suction port for avoidingcavitation at water pumping temperature

Data sheet: Wilo-Stratos-D 40/1-8

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 10 / 30

Dimension drawing

Pg 7

Pg 9Pg 13,5

200

13

81

25

135115

22

0

12

01

06

64

11

0

DN 40

Dimension drawing, flangeØ 150Ø 110

Ø 100

Ø 84

DN 40

4 x Ø14

4 x Ø19

Terminal diagram

L1 L3

L2 L3

L1 L2

PE SSM

3~230 V, 50/60 Hz

L N PE SSM

1~ 230 V, 50/60 Hz

SSM:

Collective fault signal(NC contact according to VDI 3814, load capacity 1 A,250 V ~)For function, see Wilo catalogue, chapter "Pumpmanagement Wilo-Control, consulting guide"

Minimum suction head at 50 / 95 / 110°C

3 / 10 / 16 m

Information for order placements

Make Wilo

Type Stratos-D 40/1-8

Art no. 2090463

Weight approx. m 17 kg

Data sheet: Wilo-Stratos-D 40/1-12

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 11 / 30

Pump curves Δp-c (constant)

0 5 10 15 20 25

0 2 4 6 8

0 1 2 3 4 5 6

0

2

4

6

8

10

12

0

20

40

60

80

100

120

0 5 10 15 20 25

30

300

400

800

7

min.

H/m

P1/W

Q/m³/h

Q/l/s

Q/m³/h

max.

p/kPa

m/sv

Wilo-Stratos-D 40/1-121~230 V - DN 40

+

P1 Wilo-Stratos 40/1-12

max.

∆p-c

min.

1m2m

3m

4m

5m6m8m9m

11m12m

7m10m

Pump curves Δp-v (variable)

max.

0 5 10 15 20 25

0 2 4 6 8

0 1 2 3 4 5 6

0

4

8

12

0

40

80

120

0 5 10 15 20 250

400

800

30

7

30

H/m

P1/W

Q/m³/h

Q/l/s

Q/m³/h

p/kPa

m/sv

Wilo-Stratos-D 40/1-121~230 V - DN 40

+

max.

∆p-v

min.

P1 Wilo-Stratos 40/1-12min.

4m

5m6m8m

9m10m11m

7m

12m

Approved fluids (other fluids on request)

Heating water (in accordance with VDI2035)

Water-glycol mixtures (max. 1:1; above20% admixture, the pumping datamust be checked)

Permitted field of application

Temperature range at max. ambienttemperature +40 °C

-10...+110 °C

Maximum permissibleoperating pressure

Pmax 6/10 bar

Pipe connections

Flange Combination flange PN6/10 (PN16 flange according to EN1092-2)

Nominal flange diameter DN 40

Overall length l0 250 mm

Motor/electronics

Energy efficiency index (EEI) ≤ 0.27

Electromagnetic compatibility EN 61800-3

Emitted interference EN 61000-6-3

Interference resistance EN 61000-6-2

Speed control Frequency converter

Protection class IP X4D

Insulation class F

Mains connection 1~230 V, 50/60 Hz

Nominal motor power P2 450.00 W

Speed n 1400 - 4600 rpm

Power consumption P1 25 - 550 W

Current consumption I 0.20 - 2.40 A

Motor protection integrated

Threaded cable connection PG 1x7/1x9/1x13.5

Materials

Pump housing Grey cast iron (EN-GJL-250)

Impeller Plastic (PPS - 40% GF)

Pump shaft Stainless steel(X30Cr13/X46Cr13)

Bearing Carbon, metal impregnated

Minimum suction head at suction port for avoidingcavitation at water pumping temperature

Data sheet: Wilo-Stratos-D 40/1-12

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 12 / 30

Dimension drawing

Pg 7

Pg 9Pg 13,5

252

14

41

51

145145

25

0

13

61

20

62

12

5

DN 40

Dimension drawing, flangeØ 150Ø 110

Ø 100

Ø 84

DN 40

4 x Ø14

4 x Ø19

Terminal diagram

L1 L3

L2 L3

L1 L2

PE SSM

3~230 V, 50/60 Hz

L N PE SSM

1~ 230 V, 50/60 Hz

SSM:

Collective fault signal(NC contact according to VDI 3814, load capacity 1 A,250 V ~)For function, see Wilo catalogue, chapter "Pumpmanagement Wilo-Control, consulting guide"

Minimum suction head at 50 / 95 / 110°C

5 / 12 / 18 m

Information for order placements

Make Wilo

Type Stratos-D 40/1-12

Art no. 2090464

Weight approx. m 25 kg

Data sheet: Wilo-Stratos-D 50/1-8

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 13 / 30

Pump curves Δp-c (constant)

0 5 10 15 20 25

0 2 4 6

0 1 2 3 4

0

2

4

6

8

0

20

40

60

80

0 5 10 15 20 25

200

400

600

0 min.

H/m

P1/W

max.

Wilo-Stratos-D 50/1-81~230 V - DN 50

p/kPa

m/sv

max.

∆p-c

+

P1 Wilo-Stratos 50/1-8

min.

Q/m³/h

Q/l/s

Q/m³/h

1m

2m

4m 3m5m6m8m 7m

Pump curves Δp-v (variable)

0 5 10 15 20 25

0 2 4 6

0 1 2 3 4

0

2

4

6

8

0

20

40

60

80

0 5 10 15 20 25

200

400

600

0

H/m

P1/W

Q/m³/h

Q/l/s

Q/m³/h

max.

Wilo-Stratos-D 50/1-81~230 V - DN 50

p/kPa

m/sv

+

min.

min.

P1 Wilo-Stratos 50/1-8

max.

∆p-v

3m4m5m6m7m

Approved fluids (other fluids on request)

Heating water (in accordance with VDI2035)

Water-glycol mixtures (max. 1:1; above20% admixture, the pumping datamust be checked)

Permitted field of application

Temperature range at max. ambienttemperature +40 °C

-10...+110 °C

Maximum permissibleoperating pressure

Pmax 6/10 bar

Pipe connections

Flange Combination flange PN6/10 (PN16 flange according to EN1092-2)

Nominal flange diameter DN 50

Overall length l0 240 mm

Motor/electronics

Energy efficiency index (EEI) ≤ 0.27

Electromagnetic compatibility EN 61800-3

Emitted interference EN 61000-6-3

Interference resistance EN 61000-6-2

Speed control Frequency converter

Protection class IP X4D

Insulation class F

Mains connection 1~230 V, 50/60 Hz

Nominal motor power P2 200.00 W

Speed n 1400 - 4800 rpm

Power consumption P1 12 - 310 W

Current consumption I 0.22 - 1.37 A

Motor protection integrated

Threaded cable connection PG 1x7/1x9/1x13.5

Materials

Pump housing Grey cast iron (EN-GJL-250)

Impeller Plastic (PPS - 40% GF)

Pump shaft Stainless steel (X30CR13)

Bearing Carbon, metal impregnated

Minimum suction head at suction port for avoidingcavitation at water pumping temperature

Data sheet: Wilo-Stratos-D 50/1-8

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 14 / 30

Dimension drawing

Pg 7

Pg 9Pg 13,5

204

13

51

23

132113

24

0

12

01

06

61

12

0

DN 50

Dimension drawing, flangeØ 165Ø 125

Ø 110

Ø 99

DN 50

4 x Ø14

4 x Ø19

Terminal diagram

L1 L3

L2 L3

L1 L2

PE SSM

3~230 V, 50/60 Hz

L N PE SSM

1~ 230 V, 50/60 Hz

SSM:

Collective fault signal(NC contact according to VDI 3814, load capacity 1 A,250 V ~)For function, see Wilo catalogue, chapter "Pumpmanagement Wilo-Control, consulting guide"

Minimum suction head at 50 / 95 / 110°C

3 / 10 / 16 m

Information for order placements

Make Wilo

Type Stratos-D 50/1-8

Art no. 2090465

Weight approx. m 19 kg

Data sheet: Wilo-Stratos-D 50/1-9

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 15 / 30

Pump curves Δp-c (constant)

0 5 10 15 20 25 30

0 2 4 6 8

0 1 2 3 4

0

2

4

6

8

10

0

20

40

60

80

100

0 5 10 15 20 25 300

400

800

10

35

35

max.

P1 Wilo-Stratos 50/1-9

H/m

P1/W

Wilo-Stratos-D 50/1-91~230 V - DN 50

p/kPa

m/sv

max.

∆p-c

+

min.

Q/m³/h

Q/l/s

Q/m³/h

min.1m

2m

4m

3m

5m6m8m9m 7m

Pump curves Δp-v (variable)

0 5 10 15 20 25 30

0 2 4 6 8

0 1 2 3 4

0

2

4

6

8

0

20

40

60

80

5

0 5 10 15 20 25 30 35

35

10

0

400

800

v

Wilo-Stratos-D 50/1-91~230 V - DN 50

+

P1 Wilo-Stratos 50/1-9

H/m

P1/W

Q/m³/h

Q/l/s

Q/m³/h

max.

p/kPa

m/s

max.

∆p-v

min.

min.

3m

4m5m6m7m8m9m

Approved fluids (other fluids on request)

Heating water (in accordance with VDI2035)

Water-glycol mixtures (max. 1:1; above20% admixture, the pumping datamust be checked)

Permitted field of application

Temperature range at max. ambienttemperature +40 °C

-10...+110 °C

Maximum permissibleoperating pressure

Pmax 6/10 bar

Pipe connections

Flange Combination flange PN6/10 (PN16 flange according to EN1092-2)

Nominal flange diameter DN 50

Overall length l0 280 mm

Motor/electronics

Energy efficiency index (EEI) ≤ 0.27

Electromagnetic compatibility EN 61800-3

Emitted interference EN 61000-6-3

Interference resistance EN 61000-6-2

Speed control Frequency converter

Protection class IP X4D

Insulation class F

Mains connection 1~230 V, 50/60 Hz

Nominal motor power P2 400.00 W

Speed n 1400 - 4100 rpm

Power consumption P1 25 - 490 W

Current consumption I 0.20 - 2.15 A

Motor protection integrated

Threaded cable connection PG 1x7/1x9/1x13.5

Materials

Pump housing Grey cast iron (EN-GJL-250)

Impeller Plastic (PPS - 40% GF)

Pump shaft Stainless steel(X30Cr13/X46Cr13)

Bearing Carbon, metal impregnated

Minimum suction head at suction port for avoidingcavitation at water pumping temperature

Data sheet: Wilo-Stratos-D 50/1-9

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 16 / 30

Dimension drawing

Pg 7

Pg 9Pg 13,5

256

14

81

59

145145

28

0

13

61

20

62

14

0

DN 50

Dimension drawing, flangeØ 165Ø 125

Ø 110

Ø 99

DN 50

4 x Ø14

4 x Ø19

Terminal diagram

L1 L3

L2 L3

L1 L2

PE SSM

3~230 V, 50/60 Hz

L N PE SSM

1~ 230 V, 50/60 Hz

SSM:

Collective fault signal(NC contact according to VDI 3814, load capacity 1 A,250 V ~)For function, see Wilo catalogue, chapter "Pumpmanagement Wilo-Control, consulting guide"

Minimum suction head at 50 / 95 / 110°C

5 / 12 / 18 m

Information for order placements

Make Wilo

Type Stratos-D 50/1-9

Art no. 2090466

Weight approx. m 27 kg

Data sheet: Wilo-Stratos-D 50/1-12

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 17 / 30

Pump curves Δp-c (constant)

0 10 20 30 40

0 2 4 6 8 10 12

0 1 2 3 4 5 6

0

2

4

6

8

10

12

0

20

40

60

80

100

120

0 10 20 30 400

400

1200

800

min.

H/m

P1/W

Wilo-Stratos-D 50/1-121~230 V - DN 50

p/kPa

m/sv

max.

∆p-c

+

P1 Wilo-Stratos 50/1-12

Q/m³/h

Q/l/s

Q/m³/h

max.

1m2m

3m

4m5m6m8m9m10m11m 7m

min.

Pump curves Δp-v (variable)

0 10 20 30 40

0 1 2 3 4 5 6

0

2

4

6

8

10

12

0

20

40

60

80

100

120

0 10 20 30 400

400

1200

800

0 2 4 6 8 10 12

H/m

P1/W

Q/m³/h

Q/m³/h

p/kPa

m/sv

min.

min.

Wilo-Stratos-D 50/1-121~230 V - DN 50

p/kPa

+

P1 Wilo-Stratos 50/1-12

max.

∆p-v

Q/l/s

max.

4m5m6m8m9m10m11m7m

Approved fluids (other fluids on request)

Heating water (in accordance with VDI2035)

Water-glycol mixtures (max. 1:1; above20% admixture, the pumping datamust be checked)

Permitted field of application

Temperature range at max. ambienttemperature +40 °C

-10...+110 °C

Maximum permissibleoperating pressure

Pmax 6/10 bar

Pipe connections

Flange Combination flange PN6/10 (PN16 flange according to EN1092-2)

Nominal flange diameter DN 50

Overall length l0 280 mm

Motor/electronics

Energy efficiency index (EEI) ≤ 0.27

Electromagnetic compatibility EN 61800-3

Emitted interference EN 61000-6-3

Interference resistance EN 61000-6-2

Speed control Frequency converter

Protection class IP X4D

Insulation class F

Mains connection 1~230 V, 50/60 Hz

Nominal motor power P2 500.00 W

Speed n 1400 - 4600 rpm

Power consumption P1 25 - 590 W

Current consumption I 0.20 - 2.60 A

Motor protection integrated

Threaded cable connection PG 1x7/1x9/1x13.5

Materials

Pump housing Grey cast iron (EN-GJL-250)

Impeller Plastic (PPS - 40% GF)

Pump shaft Stainless steel(X30Cr13/X46Cr13)

Bearing Carbon, metal impregnated

Minimum suction head at suction port for avoidingcavitation at water pumping temperature

Data sheet: Wilo-Stratos-D 50/1-12

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 18 / 30

Dimension drawing

Pg 7

Pg 9Pg 13,5

256

14

81

59

145145

28

0

13

61

20

62

14

0

DN 50

Dimension drawing, flangeØ 165Ø 125

Ø 110

Ø 99

DN 50

4 x Ø14

4 x Ø19

Terminal diagram

L1 L3

L2 L3

L1 L2

PE SSM

3~230 V, 50/60 Hz

L N PE SSM

1~ 230 V, 50/60 Hz

SSM:

Collective fault signal(NC contact according to VDI 3814, load capacity 1 A,250 V ~)For function, see Wilo catalogue, chapter "Pumpmanagement Wilo-Control, consulting guide"

Minimum suction head at 50 / 95 / 110°C

5 / 12 / 18 m

Information for order placements

Make Wilo

Type Stratos-D 50/1-12

Art no. 2090467

Weight approx. m 27 kg

Data sheet: Wilo-Stratos-D 50/1-16

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 19 / 30

Dimension drawing

Pg 7

Pg 9Pg 13,5

305

19

22

01

188188

34

0

16

31

56

70

17

0

DN 50

Dimension drawing, flangeØ 165

Ø 125

Ø 110

Ø 99

70

70

DN 50

4 x Ø14

4 x Ø19

Terminal diagram

L1 L3

L2 L3

L1 L2

PE SSM

3~230 V, 50/60 Hz

L N PE SSM

1~ 230 V, 50/60 Hz

SSM:

Collective fault signal(NC contact according to VDI 3814, load capacity 1 A,250 V ~)For function, see Wilo catalogue, chapter "Pumpmanagement Wilo-Control, consulting guide"

Approved fluids (other fluids on request)

Heating water (in accordance with VDI2035)

Water-glycol mixtures (max. 1:1; above20% admixture, the pumping datamust be checked)

Permitted field of application

Temperature range at max. ambienttemperature +40 °C

-10...+110 °C

Maximum permissibleoperating pressure

Pmax 6/10 bar

Pipe connections

Flange Combination flange PN6/10 (PN16 flange according to EN1092-2)

Nominal flange diameter DN 50

Overall length l0 340 mm

Motor/electronics

Energy efficiency index (EEI) ≤ 0.27

Electromagnetic compatibility EN 61800-3

Emitted interference EN 61000-6-3

Interference resistance EN 61000-6-2

Speed control Frequency converter

Protection class IP X4D

Insulation class F

Mains connection 1~230 V, 50/60 Hz

Nominal motor power P2 1050.00 W

Speed n 950 - 3400 rpm

Power consumption P1 40 - 1250 W

Current consumption I 0.30 - 5.50 A

Motor protection integrated

Threaded cable connection PG 1x7/1x9/1x13.5

Materials

Pump housing Grey cast iron (EN-GJL-250)

Impeller Plastic (PPE - 30% GF)

Pump shaft Stainless steel(X30Cr13/X46Cr13)

Bearing Carbon, metal impregnated

Minimum suction head at suction port for avoidingcavitation at water pumping temperature

Data sheet: Wilo-Stratos-D 50/1-16

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 20 / 30

Minimum suction head at 50 / 95 / 110°C

7 / 15 / 23 m

Information for order placements

Make Wilo

Type Stratos-D 50/1-16

Art no. 2150598

Weight approx. m 48 kg

Data sheet: Wilo-Stratos-D 40/1-16

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 21 / 30

Dimension drawing

Pg 7

Pg 9Pg 13,5

310

19

21

92

188188

25

0

16

31

56

65

12

5

DN 40

Dimension drawing, flangeØ 150

Ø 110

Ø 100

Ø 84

65

65

DN 40

4 x Ø14

4 x Ø19

Terminal diagram

L1 L3

L2 L3

L1 L2

PE SSM

3~230 V, 50/60 Hz

L N PE SSM

1~ 230 V, 50/60 Hz

SSM:

Collective fault signal(NC contact according to VDI 3814, load capacity 1 A,250 V ~)For function, see Wilo catalogue, chapter "Pumpmanagement Wilo-Control, consulting guide"

Approved fluids (other fluids on request)

Heating water (in accordance with VDI2035)

Water-glycol mixtures (max. 1:1; above20% admixture, the pumping datamust be checked)

Permitted field of application

Temperature range at max. ambienttemperature +40 °C

-10...+110 °C

Maximum permissibleoperating pressure

Pmax 6/10 bar

Pipe connections

Flange Combination flange PN6/10 (PN16 flange according to EN1092-2)

Nominal flange diameter DN 40

Overall length l0 250 mm

Motor/electronics

Energy efficiency index (EEI) ≤ 0.27

Electromagnetic compatibility EN 61800-3

Emitted interference EN 61000-6-3

Interference resistance EN 61000-6-2

Speed control Frequency converter

Protection class IP X4D

Insulation class F

Mains connection 1~230 V, 50/60 Hz

Nominal motor power P2 650.00 W

Speed n 950 - 3500 rpm

Power consumption P1 35 - 800 W

Current consumption I 0.30 - 3.50 A

Motor protection integrated

Threaded cable connection PG 1x7/1x9/1x13.5

Materials

Pump housing Grey cast iron (EN-GJL-250)

Impeller Plastic (PPE - 30% GF)

Pump shaft Stainless steel(X30Cr13/X46Cr13)

Bearing Carbon, metal impregnated

Minimum suction head at suction port for avoidingcavitation at water pumping temperature

Data sheet: Wilo-Stratos-D 40/1-16

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 22 / 30

Minimum suction head at 50 / 95 / 110°C

7 / 15 / 23 m

Information for order placements

Make Wilo

Type Stratos-D 40/1-16

Art no. 2150597

Weight approx. m 44 kg

Data sheet: Wilo-Stratos-D 80/1-12

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 23 / 30

Dimension drawing

Pg 7

Pg 9Pg 13,5

329

22

12

35

203203

36

0

16

41

56

100

18

0

DN 80

Dimension drawing, flangeØ 200

Ø 150

Ø 132

4 x Ø 19

DN 80

Terminal diagram

L1 L3

L2 L3

L1 L2

PE SSM

3~230 V, 50/60 Hz

L N PE SSM

1~ 230 V, 50/60 Hz

SSM:

Collective fault signal(NC contact according to VDI 3814, load capacity 1 A,250 V ~)For function, see Wilo catalogue, chapter "Pumpmanagement Wilo-Control, consulting guide"

Approved fluids (other fluids on request)

Heating water (in accordance with VDI2035)

Water-glycol mixtures (max. 1:1; above20% admixture, the pumping datamust be checked)

Permitted field of application

Temperature range at max. ambienttemperature +40 °C

-10...+110 °C

Maximum permissibleoperating pressure

Pmax 6 bar

Pipe connections

Flange Flange PN 6 (PN 16 design,according to EN 1092-2)

Nominal flange diameter DN 80

Overall length l0 360 mm

Motor/electronics

Energy efficiency index (EEI) ≤ 0.27

Electromagnetic compatibility EN 61800-3

Emitted interference EN 61000-6-3

Interference resistance EN 61000-6-2

Speed control Frequency converter

Protection class IP X4D

Insulation class F

Mains connection 1~230 V, 50/60 Hz

Nominal motor power P2 1300.00 W

Speed n 900 - 3300 rpm

Power consumption P1 40 - 1550 W

Current consumption I 0.30 - 6.80 A

Motor protection integrated

Threaded cable connection PG 1x7/1x9/1x13.5

Materials

Pump housing Grey cast iron (EN-GJL-250)

Impeller Plastic (PP - 50% GF)

Pump shaft Stainless steel(X30Cr13/X46Cr13)

Bearing Carbon, metal impregnated

Minimum suction head at suction port for avoidingcavitation at water pumping temperature

Data sheet: Wilo-Stratos-D 80/1-12

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 24 / 30

Minimum suction head at 50 / 95 / 110°C

7 / 15 / 23 m

Information for order placements

Make Wilo

Type Stratos-D 80/1-12

Art no. 2150600

Weight approx. m 61 kg

Data sheet: Wilo-Stratos-D 80/1-12

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 25 / 30

Dimension drawing

Pg 7

Pg 9Pg 13,5

329

22

12

35

203203

36

0

16

41

56

100

18

0

DN 80

Dimension drawing, flangeØ 200

Ø 160

Ø 132

8 x Ø 19

DN 80

Terminal diagram

L1 L3

L2 L3

L1 L2

PE SSM

3~230 V, 50/60 Hz

L N PE SSM

1~ 230 V, 50/60 Hz

SSM:

Collective fault signal(NC contact according to VDI 3814, load capacity 1 A,250 V ~)For function, see Wilo catalogue, chapter "Pumpmanagement Wilo-Control, consulting guide"

Approved fluids (other fluids on request)

Heating water (in accordance with VDI2035)

Water-glycol mixtures (max. 1:1; above20% admixture, the pumping datamust be checked)

Permitted field of application

Temperature range at max. ambienttemperature +40 °C

-10...+110 °C

Maximum permissibleoperating pressure

Pmax 10 bar

Pipe connections

Flange Flange PN16 (according to EN1092-2)

Nominal flange diameter DN 80

Overall length l0 360 mm

Motor/electronics

Energy efficiency index (EEI) ≤ 0.27

Electromagnetic compatibility EN 61800-3

Emitted interference EN 61000-6-3

Interference resistance EN 61000-6-2

Speed control Frequency converter

Protection class IP X4D

Insulation class F

Mains connection 1~230 V, 50/60 Hz

Nominal motor power P2 1300.00 W

Speed n 900 - 3300 rpm

Power consumption P1 40 - 1550 W

Current consumption I 0.30 - 6.80 A

Motor protection integrated

Threaded cable connection PG 1x7/1x9/1x13.5

Materials

Pump housing Grey cast iron (EN-GJL-250)

Impeller Plastic (PP - 50% GF)

Pump shaft Stainless steel(X30Cr13/X46Cr13)

Bearing Carbon, metal impregnated

Minimum suction head at suction port for avoidingcavitation at water pumping temperature

Data sheet: Wilo-Stratos-D 80/1-12

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 26 / 30

Minimum suction head at 50 / 95 / 110°C

7 / 15 / 23 m

Information for order placements

Make Wilo

Type Stratos-D 80/1-12

Art no. 2150601

Weight approx. m 61 kg

Data sheet: Wilo-Stratos-D 65/1-16

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 27 / 30

Dimension drawing

Pg 7

Pg 9Pg 13,5

309

20

22

21

198198

34

0

16

31

56

80

17

0

DN 65

Dimension drawing, flangeØ 185

Ø 145

Ø 130

Ø 118

80

80

DN 65

4 x Ø14

4 x Ø19

Terminal diagram

L1 L3

L2 L3

L1 L2

PE SSM

3~230 V, 50/60 Hz

L N PE SSM

1~ 230 V, 50/60 Hz

SSM:

Collective fault signal(NC contact according to VDI 3814, load capacity 1 A,250 V ~)For function, see Wilo catalogue, chapter "Pumpmanagement Wilo-Control, consulting guide"

Approved fluids (other fluids on request)

Heating water (in accordance with VDI2035)

Water-glycol mixtures (max. 1:1; above20% admixture, the pumping datamust be checked)

Permitted field of application

Temperature range at max. ambienttemperature +40 °C

-10...+110 °C

Maximum permissibleoperating pressure

Pmax 6/10 bar

Pipe connections

Flange Combination flange PN6/10 (PN16 flange according to EN1092-2)

Nominal flange diameter DN 65

Overall length l0 340 mm

Motor/electronics

Energy efficiency index (EEI) ≤ 0.27

Electromagnetic compatibility EN 61800-3

Emitted interference EN 61000-6-3

Interference resistance EN 61000-6-2

Speed control Frequency converter

Protection class IP X4D

Insulation class F

Mains connection 1~230 V, 50/60 Hz

Nominal motor power P2 1200.00 W

Speed n 950 - 3400 rpm

Power consumption P1 40 - 1450 W

Current consumption I 0.30 - 6.40 A

Motor protection integrated

Threaded cable connection PG 1x7/1x9/1x13.5

Materials

Pump housing Grey cast iron (EN-GJL-250)

Impeller Plastic (PPE - 30% GF)

Pump shaft Stainless steel(X30Cr13/X46Cr13)

Bearing Carbon, metal impregnated

Minimum suction head at suction port for avoidingcavitation at water pumping temperature

Data sheet: Wilo-Stratos-D 65/1-16

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 28 / 30

Minimum suction head at 50 / 95 / 110°C

7 / 15 / 23 m

Information for order placements

Make Wilo

Type Stratos-D 65/1-16

Art no. 2150599

Weight approx. m 51 kg

Data sheet: Wilo-Stratos-D 65/1-12

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 29 / 30

Dimension drawing

Pg 7

Pg 9Pg 13,5

325

19

62

09

188188

34

0

16

41

56

88

17

0

DN 65

Dimension drawing, flangeØ 185Ø 145

Ø 130

Ø 118

DN 65

4 x Ø14

4 x Ø19

Terminal diagram

L1 L3

L2 L3

L1 L2

PE SSM

3~230 V, 50/60 Hz

L N PE SSM

1~ 230 V, 50/60 Hz

SSM:

Collective fault signal(NC contact according to VDI 3814, load capacity 1 A,250 V ~)For function, see Wilo catalogue, chapter "Pumpmanagement Wilo-Control, consulting guide"

Approved fluids (other fluids on request)

Heating water (in accordance with VDI2035)

Water-glycol mixtures (max. 1:1; above20% admixture, the pumping datamust be checked)

Permitted field of application

Temperature range at max. ambienttemperature +40 °C

-10...+110 °C

Maximum permissibleoperating pressure

Pmax 6/10 bar

Pipe connections

Flange Combination flange PN6/10 (PN16 flange according to EN1092-2)

Nominal flange diameter DN 65

Overall length l0 340 mm

Motor/electronics

Energy efficiency index (EEI) ≤ 0.27

Electromagnetic compatibility EN 61800-3

Emitted interference EN 61000-6-3

Interference resistance EN 61000-6-2

Speed control Frequency converter

Protection class IP X4D

Insulation class F

Mains connection 1~230 V, 50/60 Hz

Nominal motor power P2 650.00 W

Speed n 950 - 3300 rpm

Power consumption P1 38 - 800 W

Current consumption I 0.30 - 3.50 A

Motor protection integrated

Threaded cable connection PG 1x7/1x9/1x13.5

Materials

Pump housing Grey cast iron (EN-GJL-250)

Impeller Plastic (PP - 50% GF)

Pump shaft Stainless steel(X30Cr13/X46Cr13)

Bearing Carbon, metal impregnated

Minimum suction head at suction port for avoidingcavitation at water pumping temperature

Data sheet: Wilo-Stratos-D 65/1-12

Subject to change without prior notice. www.wilo.com 50 Hz 2015-03 30 / 30

Minimum suction head at 50 / 95 / 110°C

7 / 15 / 23 m

Information for order placements

Make Wilo

Type Stratos-D 65/1-12

Art no. 2150596

Weight approx. m 52 kg