20

Series 7000 Analog Electronic Controls, Selection … CONTROLS • SERIES 7000 5 The heart of the Series 7000 Con-trol System is the master controller. It incorporates a differential

Embed Size (px)

Citation preview

Analog Electronic vs. DDC Controls Comparison ...................................................................................3

Series 7000 Pressure Independent System.............................................................................................5

ComponentsPressure Independent Master Controller..........................................................................................7Heat / Fan Modules ..........................................................................................................................8Setback / Warm-Up Modules ...........................................................................................................9Flow Control Modules.....................................................................................................................10Field Devices

Analog Electronic Thermostat ...................................................................................................11Air Pressure Switch....................................................................................................................12Transformer ...............................................................................................................................12Duct Temperature Sensor ..........................................................................................................13Floating Point Control Direct Coupled Actuator ........................................................................13

Airflow Ranges .....................................................................................................................................13

Series 7000 Calibration Chart ...............................................................................................................14

Control SequencesSingle and Dual Duct Constant Volume and Static Pressure

Control Sequence Table .............................................................................................................15Series Flow Fan Powered (Continuous Fan)

Control Sequence Table .............................................................................................................16Parallel Flow Fan Powered (Intermittent Fan)

Control Sequence Table .............................................................................................................17

Special Applications............................................................................................................................18

Guide Specifications ...........................................................................................................................19

GENERAL NOTES• All data herein is subject to change without notice. Refer to www.enviro-tec.com for current catalog and

control sequence drawings.• Refer to IOM manual at www.enviro-tec.com.• Refer to Series 7000 Application Guide and sequence drawings at www.enviro-tec.com.• See Analog Electronic Controls drawings at www.enviro-tec.com for connections.

ENVIRO-TEC® • TABLE OF CONTENTS

2 ENVIRO-TEC

ELECTRONIC CONTROLS • SERIES 7000

3

Fierce competition motivates commercial office building ownersand real estate managers to provide comfortable office spacewhile minimizing air conditioningpower consumption and initialconstruction costs. Direct DigitalControls (DDC) are frequentlymounted on each variable air volume (VAV) terminal, permittingcommunication between theautomat ion system centra l monitor and each VAV unit. State-of-the-art Analog Electronic Controls(AEC) for VAV terminals provide aviable lower cost alternative toDDC control.

Both sophisticated, solid state Analog Electronic and DDC VAV controllers provide superior zonecomfort by minimizing room temperature deviation from setpoint. Both systems permit nightsetback and morning warm-upoperation. Both allow the user tofactory and/or field set minimumand maximum airflow settings.Both provide pressure indepen-dent control. Neither requiresannual calibration as do the proportional pneumatic controllers.

In view of the cost difference between Analog E lectronic controllers and DDC controllers(see tables at right), when shouldthe owner and HVAC system designer use DDC VAV control?

DDC control systems provide twoway communications between theVAV terminal controllers and the automation system front end. Abuilding manager, from his office,can view zone temperatures, VAV unit operating status, zone airflow rates, and zone heating andcooling setpoints. He can resetzone temperature setpoints and

ANALOG VARIABLE AIR VOLUME TERMINAL CONTROLSARE A COST EFFECTIVE ALTERNATIVE TO DDC CONTROLS

The VAV controller type significantly impacts the building cost. TheVAV controller contributes between $.21 and $1.44 per square footto the initial cost of a building. The first cost of a DDC VAV con-troller is more than the cost of the VAV single zone terminal. Theanalog VAV control is less than half the cost of the DDC control.

What is the First Cost Premium for DDC Communications Between VAV Terminals and the Building Automation Front End?

Analog Controls DDC Controls

Controller & Thermostat $152 $257

Wiring & Setup $40 $175

Total $192 $432

DDC VS. ANALOG CONTROL COSTS

Analog Controls DDC Controls

Average Zone Area 300 Sq. Ft. 900 Sq. Ft.300 Sq. Ft.900 Sq. Ft.

Cost per Square Foot $.64 $.48$1.44$.21

VAV CONTROLS COST PER SQUARE FOOT

ENVIRO-TEC® elec-tronic analog andDDC controllers arequality tested for 24hours prior to finalassembly within aNEMA 1 enclosurewith transformerand unit safeties.All terminal unitsand control assem-

blies are ETL listed with the electronic controllers factory mounted.ENVIRO-TEC® onboard transducers and FlowStarTM airflow sensors are capa-ble of accurately controlling at lower airflow rates than typically availablein the industry.

ENVIRO-TEC

SERIES 7000 • ELECTRONIC CONTROLS

4

minimum and maximum airflowlimits. Zone controllers can sendan alarm to the central monitorwhen abnormal conditions arise.These are powerful tools whichmeet requirements for some own-ers and tenants.

However, for the typical officespace, the owner may find it morecost effective to limit DDC build-ing automation to large chillers,boilers, major air handling units,fire and life safety systems, andother critical applications.

For non-critical zones, VAV zone terminals may only require AnalogElectronic Controllers with systeminterlock controls. The VAV Analog Electronic Controls have thesame dependability and accuracyas DDC Controls. They also allowthe minimum and maximum CFMsetpoints to be adjusted from thelocal space thermostat for ease ofbalancing the airside of the HVACsystem. In addition, the Series7000 Analog Electronic Controlsincorporate a plug-in modulardesign for ease of adding featuressuch as morning warm-up, nightset back and additional stages of heat, without replacing the original master controller.

Communications wiring for DDCcontrollers may become prohibi-tive when great distances or remotebuildings are involved. In thosecases, stand-alone Analog ElectronicControls may be the only practi-cal choice.

Commissioning DDC VAV systemsrequires factory trained staff famil-iar with DDC hardware andsoftware, increasing the installedcosts of DDC systems. The operatingcost also increases because theowner has to employ highly trainedtechnicians to maintain the systemor pay for expensive yearly

ENVIRO-TEC® electronic control retrofitkits facilitate field renovations of exist-ing VAV terminals. All electronic analogcontrol sequences include NEMA 1enclosures and transformers. Model RFT-MS airflow sensors and flow sensingstations are available when renovatingpressure dependent systems and con-verting to pressure independent control.ENVIRO-TEC® retrofit control kits can beinstalled on the existing VAV terminalsof most manufacturers.

maintenance contracts from thelocal controls manufacture representative.

When renovating buildings thathave pneumatic controls or expand-ing campuses that have long usedpneumatic VAV controls, the ownershould consider replacing thepneumatic controls with AnalogElectronic VAV Controls. AnalogElectronic VAV Controls enjoy several advantages over their pneumatic counterparts withapproximately the same initialinstalled first cost. • Analog controls eliminate the first

cost of air compressors, filters anddriers.

• Analog controls, unlike pneu-matic, do not require annualcalibration of thermostat and controllers.

• Air compressor, pneumatic pip-ing and filter/drier maintenanceand operating costs are elimi-nated.

• Analog controllers maintain spacetemperatures within plus orminus 1° F which provides better comfort and greater energy efficiency than pneu-matic controllers.

Many VAV system renovations areaccomplished without replacing thesheet metal VAV terminals. Control system problems, such asmalfunctioning VAV controllersand oil and water in pneumatic tubing, often have rendered aVAV system inoperable. Failure toannually calibrate pneumatic controls can also render the VAVsystem inoperable. In theseinstances, the system can berepaired by changing only thecontrols. Pressure dependent systems can be upgraded to a pressure independent systems byadding duct airflow sensor kits.

Savings to the owner can be substantial. VAV terminals andductwork are reused. Disturbanceof the ceiling is minimal. The controls retrofit is done in a fraction of the time that a completerenovation might take.

Conclusion:Stand-alone, Analog ElectronicVAV Controllers offer the same reliability and low maintenance asDDC controls at a much lower operating and first cost. In addition,analog electronic controls requireonly a standard volt/ohms multi-meter for setup and calibration,whereas DDC controls require a lap-top or PC computer with expensivesoftware and in many cases, cost-ly specialized product training.One of the only advantages ofthe DDC alternative, is the com-munication with the PC workstationfront end. As building owners anddesigners develop new projectsand renovate existing properties, careful economic analysis will berequired when selecting betweenAnalog Electronic and communi-cating DDC control systems.

ENVIRO-TEC

ELECTRONIC CONTROLS • SERIES 7000

5

The heart of the Series 7000 Con-trol System is the master controller.It incorporates a differential pres-sure transducer, airflow controland air valve modulation circuitry,and a DC power supply. With athermostat and actuator, it servesas a stand-alone cooling only, pres-sure independent VAV controlsystem. The master controller alsoincludes connectors to allow mod-ules to be added in the factory orfield to configure the system for various types of terminals: singleor dual duct, series flow or variablevolume fan. Other standard optionsare discussed below.

FLOW SENSING METHODA center averaging differentialpressure sensor (FlowStarTM) locat-ed in the inlet collar of the VAVterminal is piped to a hot wire differential pressure transducerlocated within the electronic controller. A small orifice in thetransducer creates a minute airflowwhich is proportional to the differential pressure. This flowpasses over a hot thermistor, causing an increase in dissipationand increasing its resistance. Sincecooler air would also have theeffect of increasing resistance, a second thermistor is incorporatedfor temperature compensation.The electronic circuitry causes a constant difference in resistance(temperature) between the twothermistors by increasing power tothe hot thermistor as flow increas-es, and decreasing power to the hotthermistor as flow decreases. Thepower required to maintain this constant difference is the parameterused for flow control.

AIR VALVE CONTROLThe electronic signal developedby the differential pressure trans-ducer is compared to a signaldeveloped from a rapid responsethermistor within the electronic thermostat. Setpoint correspondsto the minimum flow limit set atthe thermostat. The electroniccontroller modulates the air valveactuator from minimum flow tomaximum flow (also set at the thermostat) to provide cooling asnecessary to maintain space temperature. As the actual airflowapproaches airflow setpoint, theactuator control circuitry uses pulsewidth modulation (PWM) to slowthe rate of change of the airflow,thus preventing overshoot andhunting. A calibration curve of DCvoltage vs. CFM is provided sothat flow limits may be set with-out actual airflow being present.

HEAT / FAN CONTROLFour types of heat and two typesof fan control are available with theSeries 7000. Heat options includestaged electric or hot water, floating modulating hot water,proportional modulating hot wateror proportional modulating SSR electric heat. Either terminal and/orbaseboard heat may be controlled.

Both variable volume and series flow fan control strategies are available. For variable volumeapplications, the unit fan is ener-gized one degree below setpoint.A half degree of hysteresis preventsrapid cycling. For series flow appli-cations, the fan runs constantlyduring day mode.

Two methods of reverse fan rota-tion are provided on series flow fanterminals. If system air is failed, theprimary air valve is closed and thefan is de-energized to prevent re-application of air from spinning thefan wheel in reverse before the fanrestarts. On application of powerto the terminal, the primary air valveis closed for three to five minutesbefore the fan is started, in case primary air had spun the fan wheelin reverse before the fan terminalwas powered.

For staged heat applications, astage of electric or hot water heatis energized two degrees below setpoint. Up to two additionalstages may also be energized atthree and four degrees below setpoint. All stages are providedwith a half degree of hysteresis toprevent rapid cycling.

In floating modulating applica-tions, the valve actuator is pulsedin the open direction when thespace temperature reaches twodegrees below setpoint. If the temperature continues to fall, thevalve actuator is pulsed again in theopen direction. If the temperaturedoes not decrease, the valve actuator is not energized, thusremaining in position. On anincrease in space temperature, thevalve actuator is pulsed in theclosed direction. The length of thepulses is proportional to the temperature difference from twodegrees below setpoint.

SERIES 7000 MODULAR, PRESSURE INDEPENDENT VAV CONTROL SYSTEM

ENVIRO-TEC

6

SERIES 7000 • ELECTRONIC CONTROLS

6

An analog signal is used to posit ion a hot water valve actuator in proportional hot waterheat applications. When space temperature drops to two degreesbelow setpoint, the valve is positioned open slightly. If temperature continues to drop,the valve actuator is positioned further open. If temperature rises,the valve actuator is positioned inthe closed direction. The degreeof position change is dependent onthe temperature difference fromtwo degrees below setpoint.

Proportional electric heat applica-tions use an analog signal tocontrol a voltage to a pulse widthmodulation (PWM) circuit which inturn, time proportions the on andoff times of an SSR (solid state relay).When space temperature falls twodegrees below setpoint, very shortpulses of current provide a smallamount of heat. As space tem-perature continues to fall, thepulses become longer to providemore heat.

All types of heat applications forsingle duct VAV terminals featurean auxiliary (heating) minimum.When heat is energized in theseapplications, minimum airflow setpoint is increased to a fieldadjustable volume for optimal airflow with heat.

NIGHT SETBACKAn airflow switch senses whenthe main air handlers have beenshut down, initiating night setback.The controller causes the air valveactuator to close the valve. Whenspace temperature falls to an offset value set on a setback/

warm-up module, the fan is energized and heat is modulatedto maintain temperature. The setpoint temperature in this modeis the day setpoint minus the offset value.

MORNING WARMUP/AUTOMATIC CHANGEOVERAn electronic duct sensor signalsthe presence of warm supply air tothe terminal, which inhibits heat andfan operation and drives the air valveopen to the maximum airflow setpoint. When the thermostat issatisfied, the controller drives theair valve as necessary to maintainsetpoint. For applications such asgas-fired central heat requiringconstant airflow across the heater,a constant volume version of morning warm-up is available. Onsensing warm supply air, the airvalve is driven to maximum airflowsetpoint. This setpoint is maintaineduntil cool primary supply air issensed, when the air valve beginsmodulating in the day (cooling)mode.

PRESSURE CONTROLTwo control sequences provide ameans of controlling static pressurein applications utilizing a constantvolume air handler. The controlleris mounted in a sheet metal enclo-sure which incorporates an integralstatic pressure probe. This assem-bly is mounted on the main ductwith the probe inserted into theduct. As static pressure increases,the electronic controller sends a signal to open a pressure regulat-ing air valve which will bypass airto the return plenum. As static pressure decreases, the air valve isdriven closed, thus bypassing less

air and maintaining constant static pressure in the duct.

WARRANTYThe Series 7000 analog electroniccontrols are warranted for 18months from shipment or 12months from start-up, whichevercomes first.

ENVIRO-TEC

7

CONTROL COMPONENTS • SERIES 7000

7

SPECIFICATIONSSupply Voltage

• 24VAC - 10%, + 15%, 50/60Hz

Power Consumption• 10 VA max. (including actuator)

Flow Sensing Method• Center Averaging FlowStarTM Differential Pressure

Sensor and Hot Wire Differential Pressure Transducer

Range• 0.015" - 1.5" w.g.

Thermostat Outputs• +18 VDC (short circuit protected)

• DC Common

Thermostat Inputs• Flow Setpoint Voltage

Actuator Control Outputs• Pulse Width Modulated• Operates with a 3 wire floating point actuator

Sensor Inputs

• Differential Pressure Transducer (tubing)

Connections• Screw Type, Terminal Block (thermostat)• 1/4" Quick Connect (24VAC input and actuator

outputs)

• 0.025" 50 pin headers (modules)

Ambient Storage Temperature• -35°F to 150°F, 0 to 95% rH, non-condensing

Ambient Operating Temperature• 35°F to 120°F, 10 to 95% rH, non-condensing

Size• 2.25"W x 6.125"L

Enclosure (Bracket) Material Size• 4.375"W x 7.5"L x 2.625"D

This device is an electronic printed circuit board assem-bly housed in a sheet metal enclosure. A hot-wiredifferential pressure transducer is mounted on theprinted circuit board. A computer generated labelindicates controller type, inventory number, and factory order number. High and low ports, alongwith terminal number designations are screened onthe printed circuit board.

CONNECTIONSThermostat connections are fixed screw terminal typefor rapid installation and servicing. Field connectionsare made by stripping wire approximately 1/4",inserting wire in connector, and tightening screw firmly. 24VAC input connections are 1/4" quick disconnect type. All wiring except input power andthermostat are provided by the factory.

The ports of the pressure transducer are located onthe printed circuit board. Flexible tubing providesairtight, kink-free connection to transitions throughthe wall of the sheet metal enclosure. 1/4" I.D. flameretardant tubing is used for piping external to thesheet metal enclosure. Piping is provided at the factory, except in retrofit applications.

Modular design allows for ease of adding optionalfeatures to the master controller. Connectors are pro-vided on the electronic printed circuit board to acceptthe heat/fan, setback/warm-up and/or flow controlmodules. Modules are color-coded for visual aid inselecting the desired temperature control sequence.

CALIBRATIONThe pressure transducer is pre-calibrated at the factory. It should never need recalibration and cannot be calibrated in the field.

MOUNTINGAttaches to mounting plate with plastic standoffs.May be mounted in any position. Controllers are factory mounted, except on some retrofit applications.

MAINTENANCEInput power must be maintained within specified limits. No other maintenance is necessary.

SERIES 7000 PRESSURE INDEPENDENT MASTER CONTROLLER

ENVIRO-TEC

SERIES 7000 • CONTROL COMPONENTS

8

SPECIFICATIONSSupply Voltage

• 18 VDC ± 3% (from Master Controller)

Thermostat Inputs• Heat Demand Voltage

Thermostat Outputs• Auxiliary (Heating) Minimum Select

Sensor Inputs• Pressure Switch

Control Outputs• 0-10 / 2-10 VDC (proportional heat)• 24 VAC, 15 VA max. each (staged or floating heat)

Connections• Screw Type, Terminal Block (thermostat & sensors) • 1/4" Quick Connect (24 VAC control outputs)• Through-mount Receptacle (master controller)

Ambient Storage Temperature• -35°F to 150°F, 0 to 95% rH, non-condensing

Ambient Operating Temperature• 35°F to 120°F, 5 to 95% rH, non-condensing

Size• 3.10"W x 3.45"L

PCB Color Code• Red

NOTE: Specific input and output configurationswill vary depending on model.

HEAT / FAN MODULESMODELSETPH3: 3 staged heat outputs w/auxiliary (heating) minimum.Staged outputs are energized at 2°F, 3°F and 4°F below temperaturesetpoint.

ETPFH2: Constant fan output with two staged heat outputs.Stages are energized at 2°F and 3°F below temperature setpoint.On application of power, damper closes and fan stays off forthree minutes to prevent reverse fan rotation. A pressure switchinput allows damper to be closed and fan de-energized for nightoperation.

ETPHM1: Proportional 10-2 VDC (N.O.) modulating heat output w/auxiliary (heating) minimum. Output is off at 2°F below temperature setpoint, full on at 5°F below setpoint.

ETPFVHM1: Variable fan output and proportional 10-2 VDC (N.O.)modulating heat output. Fan energizes 1°F below temperaturesetpoint. Heat output is off at 2°F below setpoint, full on at5°F below setpoint.

ETPFHMI: Constant fan output and proportional 10-2 VDC (N.O.)modulating heat output. Heat output is off at 2°F below setpoint, full on at 5°F below setpoint. On application ofpower, damper closes and fan stays off for three minutes to prevent reverse fan rotation. A pressure switch input allows damperto be closed and fan de-energized for night operation.

ETPHM2: Floating, modulating (tri-state) heat output without auxiliary (heating) minimum. Modulates at 2°F belowtemperature setpoint.

ETPFVHM2: Variable fan output and floating, modulating (tri-state) heat output. Fan energizes 1°F below temperature setpoint. Heat modulates at 2°F below temperature setpoint.

ETPFHM2: Constant fan output and floating, modulating (tri-state) heat output. Heat modulates at 2°F below temperaturesetpoint. On application of power, damper closes and fan staysoff for three minutes to prevent reverse fan rotation. A pressure switch input allows damper to be closed and fan de-energized for night operation.

ETPHM3: Proportional 2-10 VDC modulating heat output forSSR applications w/auxiliary (heating) minimum. Output is offat 2°F below temperature setpoint, full on at 5°F below setpoint.

ETPFVHM3: Variable fan output and proportional 2-10 VDC modulating heat output. Fan energizes 1°F below temperaturesetpoint. Heat output is off at 2°F below setpoint, full on at5°F below setpoint.

ETPFHM3: Constant fan output and proportional 2-10 VDC modulating heat output for SSR applications. Heat output isoff at 2°F below setpoint, full on at 5°F below setpoint. On application of power, damper closes and fan stays off for threeminutes to prevent reverse fan rotation. A pressure switch inputallows damper to be closed and fan de-energized for night operation.

ETPFH3: Constant fan output with 3 staged heat outputs. Stagesare energized at 2°F, 3°F and 4°F below temperature setpoint.On application of power, damper closes and fan stays off forthree minutes to prevent reverse fan rotation. A pressure switchinput allows damper to be closed and fan de-energized for nightoperation.

ENVIRO-TEC

CONTROL COMPONENTS • SERIES 7000

9

SPECIFICATIONSSupply Voltage

• 18 VDC ± 3% (from Master Controller)

Thermostat Inputs• Heat Demand Voltage

Thermostat Outputs• Cooling/Heating Select

Sensor Inputs• Duct Temperature Sensor• Pressure Switch

Connections• Screw Type, Terminal Block (thermostat & sensors) • Through-mount Receptacle (master controller)

Ambient Storage Temperature• -35°F to 150°F, 0 to 95% rH, non-condensing

Ambient Operating Temperature• 35°F to 120°F, 5 to 95% rH, non-condensing

Size• 3.45"W x 2.40"L

PCB Color Code• Green

NOTE: Specific input and output configurationswill vary depending on model.

SETBACK / WARM-UP MODULES

MODELSETPCO: Changeover or modulating warmup. Damperreverses modulation when an inlet duct sensor senses warm air. Contact closure may be used in lieuof duct sensor, if desired.

ETPSB: Night setback. Pressure switch input causesdamper to close and fan and heat to cycle aroundan adjustable offset from day temperature setpoint.

ETPW: Fixed warmup. Damper goes to maximumairflow setpoint when an inlet duct sensor senses warmair. Contact closure may be used in lieu of duct sensor, if desired.

ETPCOSB: Night setback and changeover/modulat-ing warmup. Pressure switch input causes damperto close and fan and heat to cycle around anadjustable offset from day temperature setpoint.Damper reverses modulation when an inlet duct sensor senses warm air. Contact closure may be usedin lieu of duct sensor, if desired.

ETPWSB: Night setback and fixed warmup. Pressureswitch input causes damper to close and fan and heatto cycle around an adjustable offset from day temperature setpoint. Damper goes to maximum airflow setpoint when an inlet duct sensor senses warmair. Contact closure may be used in lieu of duct sensor, if desired.

ETPSR: Return or discharge air temperature control.

ENVIRO-TEC

SERIES 7000 • CONTROL COMPONENTS

10

SPECIFICATIONSSupply Voltage

• 18 VDC ± 3% (from Master Controller)

Thermostat Inputs• Heat Demand Voltage• Tracking Offset

Module Inputs• Auxiliary Minimum Select• Cooling / Heating Select

Control Inputs• 2-10 VDC or 4-20 mADC (BMS control)

Control Outputs• 2-10 VDC or 4-20 mADC (flow indication)

Connections• Screw Type, Terminal Block (thermostat & sensors) • Through-mount Receptacle (master controller)

Ambient Storage Temperature• -35°F to 150°F, 0 to 95% rH, non-condensing

Ambient Operating Temperature• 35°F to 120°F, 5 to 95% rH, non-condensing

Size• 3.00"W x 3.25"L

PCB Color Code• Blue

NOTE: Specific input and output configurationswill vary depending on model.

FLOW CONTROL MODULES

MODELSETPCV2: Two constant primary air volumes. Particularvolume selected through contact closure. Separateinput allows damper to be closed on contact closure.

ETPUC: Cold deck control for dual duct applications.Includes airflow adjustments.

ETPUH: Hot deck control for dual duct applications.Includes airflow adjustments and temperature offset adjustment.

ETPEIO: Analog slave for BMS control on SDR andVFR applications. 2-10 VDC control input from BMSand 2-10 VDC flow indication output to BMS.Includes airflow adjustments and dual minimums.

ETPFEIO: Analog slave for BMS control on CFR applications. 2-10 VDC control input from BMS and2-10 VDC flow indication output to BMS. Includesairflow adjustments.

ETPECO: Airflow adjustments with changeover inputand dual minimums.

ENVIRO-TEC

CONTROL COMPONENTS • SERIES 7000

11

ANALOG ELECTRONIC THERMOSTAT

SPECIFICATIONSTemperature Sensor:Rapid response, glass encapsulated, hermetically sealed thermistor.

Temperature Setpoint Range: • 50°F to 90°F (hidden or exposed)• 10°C to 32°C (exposed only)• 1° Increments

Supply Voltage: • 18 VDC ± 3% (supplied by controller; short circuit

protected)

Analog Outputs:• Flow Setpoint Voltage• Heat Demand Voltage

Analog Inputs:• Cool/Heat Select• Heat Min Select

Adjustments:• Minimum Flow• Maximum Flow• Heating Minimum Flow• Temperature Setpoint• Temperature Calibration

Connectors:• Protected Screw Terminal Block

Ambient Storage Temperature:• -35°F to 140°F (-37°C to 60°C),

0 TO 95% rH, non-condensing

Ambient Operating Temperature:• 40°F to 122°F (5°C to 50°C),

5 TO 95% rH, non-condensing

Size:• 2.0"W x 2.0"H x 0.6"D

(51 x 51 x 15 mm)

The Johnson Controls model ETST5AW analog elec-tronic thermostat is used with Series 7000 pressureindependent contro l lers and opt ional modules to control both fan powered and single ductvariable air volume terminals in HVAC systems. Thethermostat provides accurate control of space temperature in an attractive, low profile unit. Itincludes minimum and maximum air volume limitadjustments for ease of balancing. Options includehidden or exposed temperature setpoint, English ormetric setpoint scale, and locking cover. Several mounting methods are available.

FEATURES• Low profile contemporary design• External screw terminal block for easier field

termination• Minimum and maximum air volume limits are

located at the thermostat for convenience of balancing

• A separate heating minimum air volume setpointis provided for use with single duct VAV reheatterminals

• Concealed setpoint or exposed temperature setpoint adjustment with English or metric scale

TEST AND BALANCEAir volume limits are set using airflow calibration curvesand a digital voltmeter or flow hood. Instructionsare provided in the Installation, Operation andMaintenance Manual for ENVIRO-TEC® Series 7000Analog Electronic Controls.

CALIBRATIONThermostats are factory calibrated and rarely requirefield temperature calibration.

MOUNTINGAll necessary screws, wall anchors, and a junctionbox plate are provided to mount the 2" thermostatto dry wall or a vertical or horizontal single gang junction box.

MAINTENANCEThe 2" thermostat requires no routine maintenanceor calibration.

ENVIRO-TEC

SERIES 7000 • CONTROL COMPONENTS

12

AIR PRESSURE SWITCH

SPECIFICATIONSVoltage:

• 278 VA pilot duty @ 24 VAC• 300 VA pilot duty @ 120 to 277 VAC

Electrical Switch:• Single pole, normally closed, snap acting contacts

Electrical Connection:• 1/4" male quick-connect terminals

Operating Pressure:• Fixed - 0.05" w.g. (±0.02" w.g.)• Adjustable - 0.05" w.g. (±0.02" w.g.) to 12.0" w.g.

Maximum Pressure:• 1/2 PSIG

Environmental (Storage and Operating):• -40 to 180°F• 5 - 95% rH, non-condensing

This device is used in conjunction with a total pressure sensor located in the primary air inlet of fanterminals. When primary air is shut down, the airpressure switch makes a contact closure, thus closing a circuit to the electronic controller. This indicates the desire for night time operation and thecontroller goes into the night setback mode.

CONNECTIONSTwo barbed fittings are provided for standard 3/8"O.D. flexible tubing to sample total and/or static pressure signals.

MOUNTINGThis device is secured to terminal by two sheet metalscrews through mounting holes located on a bracket. It should be mounted in the vertical planeso the internal diaphragm is not working against gravity.

MAINTENANCENo routine maintenance is required

SPECIFICATIONSSecondary Voltage:

• 24 VAC, ± 15%, 50/60 Hz• 50 VA standard, 75 VA available• Higher VA’s available on special order

Primary Voltages Available:• 120, 208, 240, 277, 480 VAC• All Single Phase

This device provides the control voltage (24 VAC) tothe controller, actuator, and contactors from a highvoltage source in the building. This device is a ULrated component. Where applicable, it is incorpo-rated in the electric heater or fan power circuitry.

CONNECTIONSAll primary and secondary voltages are connectedvia spade type terminals.

MOUNTINGThis device is factory mounted using sheet metalscrews.

MAINTENANCENo routine maintenance is required.

TRANSFORMER

ENVIRO-TEC

CONTROL COMPONENTS • SERIES 7000

13ENVIRO-TEC

SPECIFICATIONSResistance:

• 22.1 Kohm, ± 10% at 77°F, NCT

Ambient Storage Temperature:• -35 to 150°F, 0 to 95% rH, non-condensing

Ambient Operating Temperature:• 0 to 120°F, 10 to 95% rH, non-condensing

This device incorporates a rapid response, glass encapsulated, hermetically sealed thermistor and linearization network encapsulated in flame retar-dant tubing. An aluminum tube and flange supportthe device‘s cable and allow mounting to ductwork.

CALIBRATIONThis device is pre-calibrated at the factory to a specific controller bearing a matching serial number. For field replacement, calibration instruc-tions are provided in the Installation, Operationand Maintenance manual for ENVIRO-TEC® Series7000 Analog Electronic Controls.

MOUNTINGThis device is factory mounted to the air valve inletusing two sheet metal screws, except in retrofitapplications.

MAINTENANCENo routine maintenance is required.

ENVIRO-TEC®

TERMINAL INLET SIZE

SERIES 7000 ANALOG ELECTRONIC

MINIMUM* MAXIMUM

4 35 225

5 55 350

6 65 550

8 120 1000

10 195 1600

12 280 2300

14 400 3100

16 550 4100

19 1025 6500

22 1450 8000

The ENVIRO-TEC® Windows® based computer selection program is available through your ENVIRO-TEC® representative forcomplete terminal selection with Series 7000 controls.

* Factory CFM settings (except zero) will not be made below this range,due to reduction in control accuracy.

DUCT TEMPERATURE SENSOR

AIRFLOW RANGES (CFM)

FLOATING POINT CONTROL DIRECT COUPLED ACTUATORRefer to the M9104 Series Product Bulletin at www.enviro-tec.com

SERIES 7000 • CONTROL COMPONENTS

14

SERIES 7000 CALIBRATION CHART

• For air terminals with a desired minimum setpoint of 0 CFM, set minimum voltage at 17 VDC.• Sizes 6 through 22 utilize FlowStarTM multi-axis center averaging sensor. • Sizes 4 and 5 utilize single axis, linear averaging multi-point sensor.

ENVIRO-TEC

CONTROL SEQUENCES • SERIES 7000

15ENVIRO-TEC

SIN

GL

EA

ND

DU

AL

DU

CT

CO

NT

RO

LSE

QU

EN

CE

S

CO

NTR

OL

S EQ

UEN

CE

NU

MB

ER

S UM

MER

/W

INTE

RC

HA

NG

EOV

ERO

RW

AR

M-U

P(R

EVER

SED

AM

PER

MO

DU

LATI

ON)

WA

RM

-UP

(DA

MP

ERTO

MA

X.

CFM

)

DU

AL

MIN

IMU

MC

FMS E

TPO

INTS

CO

NST

AN

TV

OLU

ME2

S TA

TIC

PR

ESSU

RE

CO

NTR

OL

(0.1

-

1.0

" W

.C.)

S TA

TIC

PR

ESSU

RE

CO

NTR

OL

(0.5

-

2.5

" W

.C.)

NO

HEA

TO

PTI

ON

S(C

OO

LIN

GO

NLY

)

UP

TO3

S TA

GES

E LEC

TRIC

(ON/O

FF)

OR

HO

TW

ATE

RR

EHEA

T1

(2 P

OS.

)

PR

OP

OR

TIO

NA

LM

OD

ULA

TIN

GH

OT

WA

TER

REH

EAT1

F LO

ATI

NG

MO

DU

LATI

NG

HO

TW

ATE

RR

EHEA

T1

PR

OP

OR-

TIO

NA

L(S

SR)

E LEC

TRIC

REH

EAT1

SD70

00�

SD70

01�

�SD

7003

��

SD70

04�

�SD

7005

��

SD71

00�

SD71

01�

��

SD71

03�

��

SD71

04�

��

SD71

05�

��

SD73

00�

�SD

7301

��

�SD

7303

��

�SD

7304

��

�SD

7305

��

�SD

7600

�2

SD76

06�

SD76

07�

CO

NST

AN

TO

RV

AR

IALB

EV

OLU

ME

DIS

CH

AR

GE

CO

NTR

OL

VA

RIA

BLE

VO

LUM

EW

ITH

Z ER

OH

EATI

NG

MIN

IMU

M3

DT7

100

�D

D72

00�

SIN

GLE

DU

CT

DU

AL

DU

CT

Not

es:

1.A

ll H

eat

Opt

ions

fea

ture

a s

epar

ate

heat

ing

min

imum

set

poin

t w

hich

may

be

disa

bled

if n

ot d

esir

ed.

2.Fo

r co

nsta

nt v

olum

e ap

plic

atio

ns w

ith

rehe

at, s

elec

t SD

7001

, SD

7003

, SD

7004

, or

SD70

05 d

epen

ding

on

type

of

heat

as

desc

ribe

d.3.

Refe

r to

Ser

ies

7000

App

licat

ion

Gui

de a

t w

ww

.env

iro-

tec.

com

for

ful

l seq

uenc

e de

scri

ptio

n.

SERIES 7000 • CONTROL SEQUENCES

16

SER

IES

FLO

WFA

NP

OW

ER

ED

CO

NT

RO

LSE

QU

EN

CE

S

CO

NTR

OL

SEQ

UEN

CE

NU

MB

ER

SUM

MER

/ W

INTE

RC

HA

NG

EOV

ERO

RW

AR

M-U

P(R

EVER

SED

AM

PER

MO

DU

LATI

ON)

WA

RM

-UP

(DA

MP

ERTO

MA

X.

CFM

)

NIG

HT2

SETB

AC

KN

IGH

T1

LOC

KO

UT

FAN

AN

DU

PTO

2 S

TAG

ESEL

ECTR

IC(O

N/O

FF)

OR

HO

TW

ATE

RR

EHEA

T(2

PO

S.)

FAN

AN

DU

PTO

3 S

TAG

ESEL

ECTR

IC(O

N/O

FF)

OR

HO

TW

ATE

RR

EHEA

T(2

PO

S.)

PR

OP

OR

TIO

NA

LM

OD

ULA

TIN

GH

OT

WA

TER

REH

EAT

F LO

ATI

NG

MO

DU

LATI

NG

HO

TW

ATE

RR

EHEA

T

PR

OP

OR

TIO

NA

L(S

SR)

E LEC

TRIC

REH

EAT

FC70

01�

FC70

02�

FC70

03�

FC70

04�

FC70

05�

FC71

01�

��

FC71

02�

��

FC71

03�

��

FC71

04�

��

FC71

05�

��

FC72

01�

FC72

02�

FC72

03�

FC72

04�

FC72

05�

FC73

01�

��

FC73

02�

��

FC75

05FC

7504

FC75

03FC

7502

FC75

01FC

7405

FC74

04FC

7403

FC74

02FC

7401

FC73

05FC

7304

FC73

03

�����

��������

����������

���

��

��

���

���

���

Not

es:

1.N

ight

Loc

kout

: w

hen

the

air

term

inal

tem

pera

ture

con

trol

ler

dete

cts

that

the

mai

n sy

stem

air

is o

ff,

the

prim

ary

air

valv

e cl

oses

and

the

uni

t fa

n an

d he

at a

rede

-ene

rgiz

ed f

or n

ight

ope

rati

on.

Prov

ided

for

all

sequ

ence

s ex

cept

for

tho

se w

ith

Nig

ht S

etba

ck.

2.N

ight

Set

back

: w

hen

the

air

term

inal

tem

pera

ture

con

trol

ler

dete

cts

that

the

mai

n sy

stem

air

is o

ff,

the

term

inal

aut

omat

ical

ly c

lose

s th

e pr

imar

y ai

r va

lve

and

cycl

es t

he f

an a

nd h

eat

to m

aint

ain

the

offs

et t

empe

ratu

re v

alue

as

set

on t

he t

erm

inal

con

trol

ler.

ENVIRO-TEC

CONTROL SEQUENCES • SERIES 7000

17ENVIRO-TEC

PA

RA

LL

EL

FLO

WFA

NP

OW

ER

ED

CO

NT

RO

LSE

QU

EN

CE

S

CO

NTR

OL

SEQ

UEN

CE

NU

MB

ER

SUM

MER

/ W

INTE

RC

HA

NG

EOV

ERO

RW

AR

M-U

P(R

EVER

SED

AM

PER

MO

DU

LATI

ON)

WA

RM

-UP

(DA

MP

ERTO

MA

X.

CFM

)

NIG

HT

S ETB

AC

K

FAN

AN

DU

PTO

2 S

TAG

ESEL

ECTR

IC(O

N/O

FF)

OR

HO

TW

ATE

RR

EHEA

T(2

PO

S.)

FAN

AN

DU

PTO

3 S

TAG

ESEL

ECTR

IC(O

N/O

FF)

OR

HO

TW

ATE

RR

EHEA

T(2

PO

S.)

PR

OP

OR

TIO

NA

LM

OD

ULA

TIN

GH

OT

WA

TER

REH

EAT

FLO

ATI

NG

MO

DU

LATI

NG

HO

TW

ATE

RR

EHEA

T

PR

OP

OR

TIO

NA

L(S

SR)

E LEC

TRIC

REH

EAT

FV70

01�

FV70

02�

FV70

03�

FV70

04�

FV70

05�

FV71

01�

FV71

02�

FV71

03�

FV71

04�

FV71

05�

FV72

01�

FV72

02�

FV72

03�

FV72

04�

FV72

05�

FV73

01�

FV73

02�

FV75

05FV

7504

FV75

03FV

7502

FV75

01FV

7405

FV74

04FV

7403

FV74

02FV

7401

FV73

05FV

7304

FV73

03

�����

��������

����������

��

��

���

���

���

GENERAL NOTESSince the actions below involve control signals, theymust be done with a dry contact closure (contact clo-sure cannot be paralleled from terminal to terminal):

CLOSE DAMPERTo close the air valve, open ETPM7 terminal 6 to ther-mostat terminal 5.

Sample Application: Could be used during smokesequences to isolate different areas.

OPEN DAMPERTo open the air valve fully, short ETPM7 terminal 6to ETPM7 terminal 7.

Sample Application: Could be used by airside testand balance to set CFM of the air handler.

OPEN AIR VALVE TO MAXIMUM CFM SETPOINTTo open the air valve to maximum CFM setpoint, dis-able heat and disable VFR fan (if applicable), shortETPH terminal 5 to ETPH terminal 7 (if present) or ETPM7terminal 7.

Sample Application: Could be used during airsidetest and balance.

DISABLE HEATTo disable heat and heating minimum (SD only), shortETPM7 terminal 4 to ETPM7 terminal 7.

Sample Application: Could be used if boiler is offand you don‘t want the VAV terminals to go into heat-ing mode.

CONNECTING MORE THAN ONE BOX TO A THERMOSTATTo operate up to four air terminals from one ther-mostat, wire first terminal to thermostat per sequencediagram. Parallel connector terminals 5 (if present),6 and 7 to other air terminals. Do not connect con-nector terminal 8‘s together as serious damage willresult. Since balancing is performed at the thermo-stat, all air terminals should be balanced with samevoltages. In addition, for best results, all air termi-nals connected for this application should be the samesize.

Sample Application: Could be used in open area whereone thermostat could sense general temperature andcontrol several air terminals in unison.

SERIES 7000 • SPECIAL APPLICATIONS

18 ENVIRO-TEC

SPECIAL APPLICATIONS • SERIES 7000

19

GUIDE SPECIFICATIONS • SERIES 7000

ENVIRO-TEC

GENERALFurnish and install an ENVIRO-TEC®

Series 7000 Pressure Independent Ana-log Electronic Control System whereindicated on the plans and in the spec-ifications. The complete system shall befully operational and include the fol-lowing:• Single duct, dual duct, and/or fan

powered terminal units• Pressure independent Series 7000 ana-

log electronic zone controllers withintegral differential pressure trans-ducer

• Analog electronic wall thermostat• Electronic air valve actuator• 24 VAC control transformers• Air pressure switches as required• Electronic duct temperature sensors as

required

TERMINAL UNITSProvide terminal units with multi-axis cen-ter averaging differential pressure sensoras specified in Section___, “Air TerminalUnits.”

ANALOG ELECTRONIC ZONE CONTROLLERThe fully standalone controller shallconsist of an electronic circuit board withintegral flow-compensated differentialpressure transducer. The circuit boardshall incorporate different type terminalsfor AC and DC connection to preventdamage caused by inadvertent fieldwiring errors. Thermostat, sensor andcontact closure terminations shall bethrough screw terminal connectors foreasy field termination. 24 VAC termi-nations shall be of the quick-connect type.The circuit board shall also incorporatean automotive-style, glass tube fusecircuit protector for ease of local replace-ment.

Modular design shall allow for ease ofadding optional features such as fan,stages of heat, morning warm-up, sum-mer/winter changeover, night setback andsmoke purge and shall be accomplishedby selecting the appropriate modular cardand plugging it into the existing mas-ter controller. Controllers that requirereplacement to change or update optionsare not acceptable. The use of sepa-rately wired modules to implementoptional features is not acceptable dueto the increased risk of control problemsfrom inadvertent field wiring errors andintermittent connections.

Series flow fan terminal controllers shallincorporate logic to prevent reverserotation of the unit fan on power inter-ruption or introduction of primary air.

REHEAT CONTROLThe plug-in Heat Modules, used with sin-gle duct or fan powered air terminalcontrollers, shall be capable of control-ling the following types of ductedreheat: 1) Control up to three stages ofElectric Duct Heat, 2) Provide 3-wire float-ing point control for Hot Water Reheat,3) Provide proportional modulating con-trol for Hot Water Reheat, 4) Provideproportional SSR control for ElectricDuct Heat.

ELECTRONIC DUCT TEMPERATURESENSORWhere required by the control sequence,each control package shall include a sup-ply air duct temperature sensor furnished,mounted and wired by the terminalunit manufacturer.

Summer/Winter Changeover: Whenthe supply air temperature increases toa field adjustable setpoint, between 50°and 90°F, the controller shall automati-cally reverse the control action of the airvalve and modulate the air valve to con-dition the space with warm air from theRTU or Air Handler.

Morning Warmup: When the supply airtemperature increases to a field adjustablesetpoint, between 50° and 90°F, thecontroller shall automatically drive the airvalve to the Maximum CFM position andallow for conditioning of the space withwarm air from the RTU or Air Handler.

DIFFERENTIAL PRESSURE TRANSDUCERThe flow-compensated differential pres-sure transducer shall be permanentlymounted on the analog electronic con-trol circuit board. The analog electroniccontrol shall drive the transducer insuch a way as to produce a voltage out-put proportional to flow. Transducerswith outputs proportional to differen-tial pressure are not acceptable. Thecontroller shall use the flow proportionalvoltage output to maintain desired air-flow within five percent of setpointregardless of changes in system staticpressure. Inlet mounted, single point hot-wire velocity transducers are notacceptable.

ANALOG ELECTRONIC WALL THERMOSTATThe analog electronic thermostat circuitboard shall incorporate a glass encap-sulated, hermetically sealed rapid responsethermistor, a hidden temperature setpointwith scale marked in one degree Fahren-heit increments, and maximum, coolingminimum and heating minimum airflow

limit adjustments. All thermostat sig-nals shall be low voltage, low current forshort circuit protected DC.

The thermostat shall be capable ofbeing installed directly to drywall, or toa horizontally or vertically mounted sin-gle-gang junction box with an adapterplate provided. The thermostat shall notprotrude further than 5/8" from thewall or adapter plate when installed.

Where required by the control sequence,each thermostat shall include both heat-ing and cooling minimum airflowadjustments. The control system shallallow both the heat and heating mini-mum to be disabled via a dry contactclosure provided by the Temperature Con-trols Contractor.

ELECTRONIC ACTUATORThe electronic actuator shall be a separate component from the control sys-tem. Due to the high cost of replacementparts after the warranty period, systemswith the actuator integral to the elec-tronic controller are not acceptable.

The electronic actuator shall be capableof stalling indefinitely at the terminal unit‘smechanical stops without damage eitherto the actuator or the terminal, and main-tain positive mechanical pressure againstthe unit‘s closed foam seal to preventexcessive airflow leakage. The use of endswitches to limit the damper‘s mechan-ical travel is not acceptable. DC currentto the actuator motor in the stall posi-tion shall be electronically limited toprevent damage to the motor due toexcessive power dissipation.

CONTROL TRANSFORMERProvide a 24 VAC control transformersized to match the power requirementsof the terminal and voltage available inthe building.

AIR PRESSURE SWITCHWhere required by the control sequence,each control package shall include an airpressure switch furnished, mountedand wired by the terminal unit manu-facturer. When the switch senses thatthe system static pressure has failed, thecontroller and unit shall automaticallyswitch to the night setback mode. Fanand heat shall be used to maintain theseparate night temperature offset.

Printed on recycled paper

Catalog: ET130.13-TD1 (1108) Supersedes: Nothing© 2008 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53201 Printed in USAwww.johnsoncontrols.com