SENTOX IDI

TECHNICAL MANUAL

GAS CONTROL PANEL

FOR ADDRESSABLE GAS DETECTORS

SENSITRON S.r.l. Viale della Repubblica, 48

20010 CORNAREDO MI - Italy

Ph: + 39 02 93548155 Fax: + 39 02 93548089

E-MAIL: [email protected]

Page 2: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 2 di 32

Warning

THIS MANAUL MUST BE CAREFULLY READ BY ALL PERSONS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like any equipment, this product will perform as designed only if installed, used and serviced in accordance with the manufacturer’s instructions. OTHERWISE, IT COULD FAIL TO PERFORM AS DESIGNED AND PERSONS WHO RELY ON THIS PRODUCT FOR THEIR SAFETY COULD SUFFER SEVERE PERSONAL INJURY OR DEATH. The warranties made by Sensitron s.r.l. with respect to this product are voided if the product is not installed, used and serviced in accordance with the instructions in this user guide. Please protect yourself and others by following them. We recommend our customers to write or call regarding this equipment prior to use or for any additional information relative to use or repair.

Page 3: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 3 di 32

INDEX

1) INTRODUCTION................................................................................................................................... 4

1.1) DETECTION CONTROL PANEL CHARACTERISTICS................................................................................. 4

1.2) SYSTEM CONFIGURATION.................................................................................................................. 4

1.3) TECHNICAL SPECIFICATIONS ............................................................................................................. 5

2) INSTALLATION.................................................................................................................................... 5

2.1) CONTROL UNIT................................................................................................................................. 5

2.2) GAS DETECTORS ............................................................................................................................. 6

2.2.1) SMART 3 GAS DETECTOR ......................................................................................................... 6

2.2.2) SMART3 DETECTORS ADDRESS PROGRAMMING......................................................................... 7

2.2.3) LCR 3 PK IDI DETECTORS ........................................................................................................ 8

2.3) OUTPUT CARDS G/OUT16................................................................................................................ 9

2.4) CONNECTION LAYOUT OF THE CONTROL UNIT MAIN BOARD................................................................ 10

2.5) SYSTEM WIRING ............................................................................................................................. 10

2.6) GAS DETECTORS CONNECTION........................................................................................................ 10

2.7) OUTPUT MODULE CONNECTION ....................................................................................................... 12

2.8) SERIAL CONNECTION TO A PERSONAL COMPUTER............................................................................ 12

3) SYSTEM POWER UP AND OPERATION.......................................................................................... 13

3.1) OPERATION OF THE SENTOX IDI CONTROL PANEL .......................................................................... 13

3.1.1) START-UP OPERATION OF THE CONTROL PANEL ........................................................................ 14

3.1.2) SYSTEM SET ....................................................................................................................... 15

3.1.3) SYSTEM UNSET .................................................................................................................. 15

3.1.4) ALARM STATUS................................................................................................................... 15

3.1.5) EVENT LOG............................................................................................................................. 16

4) PROGRAMMING MENU..................................................................................................................... 16

4.1) PROGRAMMING BY THE CONTROL PANEL KEYPAD AND DISPLAY ......................................................... 16

4.2) PROGRAMMING BY PC.................................................................................................................... 18

5) PCM 602 CONFIGURATION SOFTWARE (OPTIONAL) .................................................................. 19

5.1) INSTALLATION OF THE SOFTWARE .................................................................................................... 19

5.2) WIRING AND CONNECTIONS............................................................................................................. 19

5.3) STARTING THE PROGRAM ................................................................................................................ 20

5.4) PARAMETERS PRE-SETTING ............................................................................................................ 20

5.5) CREATING A NEW CONFIGURATION FILE ........................................................................................... 21

5.5.1) GENERAL................................................................................................................................ 21

5.5.2) PROFILES ............................................................................................................................... 22

5.5.3) CHANNELS.............................................................................................................................. 24

5.5.4) OUTPUTS................................................................................................................................ 25

4-RELAY OUTPUT SETUP......................................................................................................................... 26

5.6) SEND CONFIGURATION (DOWNLOAD) .............................................................................................. 28

5.7) RECEIVE CONFIGURATION (UPLOAD) ............................................................................................... 28

5.8) TEST MENU................................................................................................................................... 29

5.8.1) STATE .................................................................................................................................... 29

5.8.2) EVENT LOG ............................................................................................................................. 30

Page 4: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 4 di 32

1) INTRODUCTION

1.1) Detection control panel characteristics

The gas control panel SENTOX IDI has been designed for light industrial applications and can be connected to 32 SMART 3 IDI or LCR3 PK IDI detectors daisy chained to the RS 485 bus.

On the SENTOX IDI front plate, an OLED Pictiva 96x64 high brightness display provides an ongoing reading of the concentration being measured and, in case of an alarm, the alarm threshold attained and the respective channel.

Each threshold or function is visualised by a double LED raw. Acknowledge, Reset, and Set functions can be activated by 3 push buttons placed nearby the LED's.

The display also shows the highest gas concentration reached by each detector being connected. SENTOX IDI is provided with 5 output relays, of which three are associated to the alarm thresholds, 1 to Fault and 1 to WD (Watch Dog).

The panel also features the implementation of further 32 optional outputs via remote ST.G/OUT16 cards.

The unit comes into a metal cabinet complete with 24Vdc, 3A power supply and offers the possibility to allocate 2 back-up batteries max. 12V 7 Ah.

To offer higher safety, an interactive RS485 output has been implemented for the connection to a supervising system.

1.2) System configuration

16 USCITE OPENCOLLECTOR

16 OPEN COLLECTOROUTPUTS

2 MODULI USCITA2 X OUTPUT MODULES

FINO A 30 RIVELATORI GAS SMART3 IDI O LCR 3 PK IDI

UP TO 30 SMART3 IDI OR LCR 3 PK IDI GAS DETECTORS

4 USCITE RELE’

4 RELAY OUTPUTS

I/F Rs485 /USB or Rs232(OPTIONAL)

PC PER PROGRAMMAZIONE

PC FOR CONTROL PANEL SET-UP

Page 5: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 5 di 32

1.3) Technical specifications

Housing: Metal box 360x225x150 mm.

Inputs: Max. 32 detectors type SMART3 IDI or LCR3 PK IDI on 1 bus RS485.

Outputs: 5 relay board mounted in the control panel + 32 remote open collector outputs (optional) by the 2 remote card (16 Open Collector for each remote card), on the RS485.

Relay contact rating 1A 24 Vdc 60VA

Serial Ports: N° 2 x RS485

Power Supply: 230V AC +/- 10% 50Hz

Power consumption: Max 6 VA

Backup battery 2 x 12V 7 Ah max.

Display: OLED Pictiva 96 x 64

Visual indications LED: 3 LED's for Alarm thresholds, 1 for Fault, 1 for powered unit.

Temperature: Operational 0-50°C Storage -20 / +70 C°

Relative humidity: Operational 15-85% Storage 5-85% (non condensing)

EMC compliance: EN 50270 (1999): Electromagnetic compatibility-Electrical apparatus for the detection and measurement of combustible gases, toxic gases or oxygen.

EN 61000-6-3 (2001)+A11 (2004):Electromagnetic compatibility – Part 6-3 Generic standard. Emission standard for residential, commercial and light industry.

2) INSTALLATION

2.1) Control Unit

Have the control unit mounted by using the three mounting holes as shown in the figure below

153 153

358

179 179

26 26

220

168

26

26

5 mm

5 mm 5 mm

Page 6: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 6 di 32

Connect the three core mains supply cable to the power supply terminals (1.5 mm2 per core minimum) and have it secured with the appropriate cable grip.

Connect the Power supply and the RS485 line for the detectors and the output modules (optional) to the CN3 terminal block before powering up the control panel.

After powering up the control panel, connect the red and black power supply cables fitted with Faston connectors to the 2 x sealed lead acid batteries (12 Vdc / 7 Ah max.). The battery should be carefully fitted inside the space at the left side of the cabinet.

Battery12 V / 7 Ah

Battery12 V / 7 Ah

27,4 Vdc/ 5A power supply

230 Vac

2.2) Gas Detectors

SENTOX IDI gas control panel can be connected to Sensitron's SMART3 and LCR3 PK IDI.

Detectors are to be duly installed according to the gas to be detected and in fulfilment of all EU or national rules in force.

Before installing the gas detectors, we recommend to strictly follow what stated in the detectors' handbook and to consider the few rules given here below just as a generic prescription.

As a general statement, detectors should be mounted close to any possible source of release or where any eventual gas stagnation could be foreseen.

To measure a gas with specific weight higher than air, like Propane or Butane, the detectors should be installed at 30 cm. from floor. Whereas to detect a gas with specific weight lighter than air, like Methane or Hydrogen, the detectors should be placed 30 cm. from ceiling.

To detect Carbon Monoxide or Oxygen, we recommend to mount the detector at a breathing level or “nose height” about 150 cm. from floor, while for CO2 (Carbon Dioxide) detectors should be mounted at 30 cm from the floor.

For the remaining gases not mentioned as an example here above, we invite our customers to contact Sensitron or its local agent or to consult our Tutorial Guide to Gas detection.

We remind that the correct positioning of a gas detector is vital to assure a prompt and accurate detection.

2.2.1) SMART 3 gas detector

The following instructions explain how to insert the ST.S/IDI serial interface to make the SMART3 CC and SMART3 CD communicate on RS485 bus.

Page 7: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 7 di 32

Before inserting the ST.S/IDI interface, be sure the detector has been powered off. Insert the vertical plug-in card into the 10-pole connector, paying attention to leave the two left side poles free. Make sure the card has been fully plugged in.

Turn the side comprising the red LED towards the main terminal board, as shown in the drawing here below.

1

ON

23

45

6

1

ON

23

45

6

Rs485 board

SMART3 GAS DETECTOR BOARD

2.2.2) SMART3 detectors address programming

On the RS485 serial line the detectors are daisy chained on one bus only. In order for the system to work properly, it is very important the right identification through the defined code on the detector’s electronic card.

The addressing is made by some dip-switches on the main PCB of the SMART3 detectors.

The serial loop accepts 32 detectors and 2 remote 16-output modules.

The addresses accepted for the detectors are from 02 till 33 included, while the addresses 0 and 1 are reserved to the output modules.

The table below shows how the dip-switches are to be set for the address definition.

The detector addressed as 2 on the loop is the identified as No. 1 to the control panel; the one addressed as 3 is identified as No.2 to the panel and so on, till the address 33 that will be the number 32 to the control panel.

Page 8: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 8 di 32

Detector 1

Detector 5 Detector 6 Detector 7

Detector 8 Detector 9 Detector 10

Detector 11 Detector 12 Detector 13

Detector 14 Detector 15 Detector 16

Detector 17 Detector 18 Detector 19

Detector 20 Detector 21 Detector 22

Detector 23 Detector 24 Detector 25

Detector 26 Detector 27 Detector 28

Detector 29 Detector 30 Detector 31

Detector 32

Detector 5 Detector 6 Detector 7

Detector 4

Detector 5 Detector 6 Detector 7Detector 5

Detector 2 Detector 3

2.2.3) LCR 3 PK IDI detectors

LCR3 PK IDI gas detectors have a RS485 serial output and are to be connected to Sensitron's “IDI” control panels.

For the LCR3 PK IDI, the handheld calibration keypad ST.S/CKD must be used to set the address of each detector being connected on the RS485 line.

The serial loop accepts 32 detectors and 2 remote 16-output modules.

The addresses accepted for the detectors are from 02 till 33 included, while the addresses 0 and 1 are reserved to the output modules.

The detector addressed as 2 on the loop is the identified as No. 1 to the control panel; the one addressed as 3 is identified as No.2 to the panel and so on, till the address 33 that will be the number 32 to the control panel

Page 9: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 9 di 32

LCR3 PK gas detectors ST.CKD calibration keypad

For LCR3 and SMART3 detectors

2.3) Output cards G/OUT16

The remote output cards ST.G/OUT16 should be fixed by using the 4 holes (3 mm) at the corner of the card. The card can be housed in a plastic box (P/N ST.G/BOX) or in a power supply cabinet P/N VM.B/138V15.

The cards are connected in RS485 serial mode (daisy chained) to the control unit, and they need an identification addressing.

The figure here below shows the mechanical dimensions and the jumpers JP3 to addressing the card.

+V A B -V

+v

O1

O2

O3

O4

O5

O6

O7

O8

-v +v

O9

O10

O11

O13

O14

O15

O16

-v

O12

01231

0

CN2

CN1

JP3

120 mm

105 mm

75 m

m

90 m

m

The serial loop can accept up to 2 output boards with the following addressing:

Page 10: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 10 di 32

2.4) Connection layout of the control unit main board

All connections of the SENTOX IDI are to be performed on the main board and are shown below.

Cn3

Cn2

1

8

+

-

B

A

NO

NC

C

NO

NC

C

NO

NC

C

Layout circuito e connessioni elettriche / Circuit layout and electrical connections

Uscite relè di allarme

Relay alarm outputs

24 Vdc dall’alimentatore

24 Vdc from the Power Supply unit

500 mAFUSE+

-

A

B

Uscita relè di FaultFault relay output

Uscita relè di WD relay output(watch dog)

WD (watch dog)NO

NO

Collegamento rilevatori.(Bus Rs485 + alimentazione)

Detector connections(bus Rs485 + power supply)

SENTOX “IDI” CONTROL PANEL

Rs485 serial line for the PC

PC Rs485 serial line

Scheda Rs485 comm. rilevatoriDetectors Rs485 comm. board

Scheda Rs485 comm. con PCPC Rs485 comm. board

Al1

Al2

Al3

(Rl1)

(Rl2)

(Rl3)

(Rl5)

(Rl4)

2.5) System wiring

Communication between the SENTOX IDI and the detectors is by RS485 bus. The control panel constantly monitors the detectors and the remote modules connected. A break in the communication from any one of the detectors or modules generates a Fault status in the control panel.

2.6) Gas detectors connection

Wirings between the control panel and the remote devices (detectors and the output modules) should be made by using 4 wires: 2 wires for the RS485 communication and 2 wires for the power supply. The cable for the RS485 communication must an EIA RS485: 2 core wires with section 0.22 / 0.35 mm2 and shield (twisted pair). Nominal capacity between the wires < 50pF/m, nominal impedance 120 ohm. These features can be found in BELDEN cable 9842 or similar (data transmission cable in EIA RS485). By this wiring, the line total length should not exceed 1000 m. Detectors and output modules are to be daisy chained. Absolutely avoid any star or tree mode connection to prevent interference or wrong communication.

Page 11: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 11 di 32

Make sure that each multi-polar wire includes just one RS485. Make sure that a 120 Ohm end line resistor is placed at the beginning and at the end (on the last detector or output module) of the bus line. For the detectors' power supply connection use a 2-wire cable with suitable section as a function of the distance and the number of detectors.

Once the installation has been completed and the system is powered-on, make sure that each detector gets at least 12 Vdc.

Collegamento rilevatori Smart3 IDI / Smart3 IDI detector connection

Powersupply12/24 Vdc

Make sure that a 120 ohm end of line resistance is placed at the beginning and at the end (on the last detectoror output module) of the bus line

120 o

hm

* *120 o

hm

*

Schermo a terra da un solo lato(earth at only one end)

Make sure that a 120 ohm end of line resistance is placed at the beginning and at the end (on the last detectoror output module) of the bus line

ALIMENTATORE(POWER SUPPLY)12 / 24 Vdc

+ A B -

+ A B - + A B - + A B -

Schermo a terra da un solo lato(earth at only one end)

Centrale

(controlpanel)

Collegamento rilevatori LCR 3 PK / LCR 3 PK gas detectors connection

Serial “A”

Serial “B”

120 ohm

-

+

120 oh

m * *

*

Page 12: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 12 di 32

2.7) Output module connection

The connection of the remote output modules to the serial line of the RS485 bus is shown below.

If the 16-output module is the last element of the chain, a 120 Ohm end of line resistance must connected across the A and B terminals.

Collegamento rivelatori e moduli di uscita(Detectors and output modules connection )

ALIMENTATORE(POWER SUPPLY)12 / 24 Vdc

Smart3 IDIgas detector

ST/G OUT16Output module

2.8) Serial connection to a Personal Computer

The control panel can be connected to a Personal Computer using the RS485 serial port, to permit initial programming or system management with the appropriate management software. Below the connection to the Personal Computer.

Cn

3

Cn

2

1

8

+

-

B

A

NO

NC

C

NO

NC

C

NO

NC

C

500 mAFUSE+

-

A

B

NO

NO

SENTOX “IDI” circuitlayout

Rs485 serial line for the PC

PC Rs485 serial line

Scheda Rs485 comm. con PCPC Rs485 comm. board

PCRs485 USB or

Rs232 interface

Page 13: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 13 di 32

3) SYSTEM POWER UP AND OPERATION

3.1) Operation of the SENTOX IDI control panel

On the SENTOX IDI front plate, a display provides an ongoing reading of the gas concentration measured by each detector being connected and, in case of an alarm, the alarm threshold attained and the respective channel.

Each threshold or function is visualised by a double LED raw. Acknowledge, Reset, and Set functions can be activated by 3 push buttons placed nearby the LED's.

After a two-minute inactivity, the display intensity progressively fades. In case of alarm or by simply pressing any of the keys, the display will turn on again.

M. 0 SET

OK

Page 14: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 14 di 32

3.1.1) Start-up operation of the control panel

At the start-up, SENTOX IDI control panel will enter a warm-up phase during which the indication PCM616 is shown on the display and all LED's turn off exception made for FAULT and POWER indications. Once the warm-up phase is over and the start-up procedure is correct, the first detector status will be displayed.

Should the buzzer sound after the start up, mute it by pressing ACK and check the cause by controlling which LED on the front panel is ON among Fault, Alarm1, Alarm2 or Alarm3. On the display it will appear either the wording FLT (Fault) or L1, L2 or L3 according to the alarm levels. At this point, after verifying that the system is either on Fault or Alarm condition, operate as follows:

In case of system in Fault

It will be sufficient to enter the Unset (UNS) status by keeping SET pushed for 3 seconds then push ACK. A Fault status may either be caused by one or more gas detectors in Fault or any anomaly in the RS485 communication between the control panel and the detectors.

In case of system in Alarm:

Press ACK key to mute the audible Alarm. To Reset and then Unset the system, it is absolutely necessary to eliminate the Alarm status first. Once the Alarm condition has been restored press the RST key to reset the system.

Page 15: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 15 di 32

3.1.2) SYSTEM SET

System Set is the normal operation mode of the control panel. The gas concentration being detected is shown on the display and the following messages are reported:

status (OK or FT fault), L1 (Caution or alarm 1), L2 (Warning or alarm 2), L3 (Alarm or alarm 3) along with the SET or UNSET system condition. Keep the ACK key pressed for two seconds to allow the display scroll to the other channels and display their status. When the unit receives an alarm condition the corresponding output relay activates.

SENTOX IDI is provided with 5 output relays with the functions below listed

RL1 (threshold 1) RL2 (threshold 2) RL3 (threshold 3) RL4 (fault) RL5 (watch–dog). RL1 activates when the first programmed alarm threshold is attained, RL2 when the second one is reached, RL3 when the third one is reached.

RL4 activates when a Fault is present (one or more detectors on fault or the RS485 communication bus failure) and RL5 deactivates in case the microprocessor controlling the board should lockout during normal operation (during normal operation RL5 is always active). All the relays provide free changeover contacts.

3.1.3) SYSTEM UNSET

To Unset the system (UNS) keep the SET key pushed for 3 seconds and then press ACK. In this condition the control panel is monitoring the detectors but when the unit reports an Alarm or a Fault condition the relay output are not activated.

To move back to the SET status, press the SET key for 3 second and then ACK.

3.1.4) ALARM STATUS

Outputs

When a programmed alarm threshold is attained, the control unit provides a visual/acoustic signalling by activating the buzzer along with the LED and the relay corresponding to that alarm status.

The ACK key allows muting the audible alarm, thus deactivating the buzzer.

Any time an alarm threshold is exceeded, the buzzer activates and needs muting.

Soon after muting, the ACK key recovers its function of channel scrolling, by keeping it pressed for about two seconds.

When the alarm condition has been recovered and no further gas presence is being detected, both alarms and the visual indications of the maximum alarm threshold reached can be reset. In order to activate this procedure press the RST key.

During the alarm condition, the display shows the concentration attained in real time. At the same time, the wording status OK changes progressively into L1 or L2 or L3 to show the detector status, contrary to the visual indications that record the maximum level reached.

Page 16: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 16 di 32

3.1.5) Event Log

The unit event log records date, time and type of alarm or fault. To enter the menu proceed as detailed in the flowchart:

4) PROGRAMMING MENU

It is necessary to program the system after the first power up and each time a system component is added or removed. It is possible to locally program the system using the keypad on the front panel or better using a Personal Computer and the dedicated configuration software.

4.1) Programming by the control panel keypad and display

It is possible to enter the programming mode from the Unset (UNS) mode only, following the flowchart detailed in the next page.:

Page 17: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 17 di 32

FI CH01.02 FLT

- - - 0 %LEL M. O UNS

Lan Engl Pass1 1 Pass2 0 Adr 1 Dt gg.mm.yy Tm 24

Lan: Select language Italian or English Pass1 (password 1): 0-9999 Pass2 (password 2): 0-9999 Adr. (Address): 0-255 Dt. (Date): dd.mm.yy Tm (time): 12 / 24h

SET (3 SEC.) SET Press SET to scroll from one parameter to the other and ACK or RST to modify

SET ?

Hour 18 Min 10 Day 07 Mon 01 Year 08 W. ON 02

Hour Min (Minutes) Day Mon (month) Year W. ON (warm-up time) From 0 to 3 minutes

RST SET Press SET to scroll from one parameter to the other and ACK or RST to modify

SETUP ?

PRF 01 % LEL FS 100 UP Th1 10 BOFF Th2 20 Th3 30 Hys 3

PRF01 is the first out of the 32 profiles that can be set for each channel (CH1 to CH32). For each one of the Profiles, it is possible to select the measuring range (%LEL, ppm, % Vol, O2), the three alarm thresholds and the hysteresis (Hys). Signal can be of increasing (UP) or decreasing (DOWN) type. The audible alarm associated to the first threshold can be activated (BON) or deactivated (BOFF).

ACK RST Press SET to scroll from one parameter to the other and ACK or RST to modify

PASS 0

CH01 PRF 01 SET Wt1 100 Wt2 100 Wt3 100

CH01: Input channel No. 1 PRFxx: profile to associate to the respective channel (from 01 to 32 or SPARE) SET: channel status SET or UNSET Wt1, Wt2 e Wt3: (not to be used) always to be at 100.

ACK ACK

PASS 1

CH02 PRF 01 SET Wt1 100 Wt2 100 Wt3 100

Repeat for the other Channels (from 2 to 32 the same routine carried for Channel 1

SET RST

WAIT REMOTE

OTh1 MEMO DL ON 6s HIGH

OTh1: threshold 1 programming MEMO: relay latched until reset, REFLEX; relay unlatched, PULSE (relay pulsed). DL ON: activation delay (0-720 sec.) T OFF: deactivation delay (0-720 sec.) HIGH: relay energized, LOW: relay de-energized..

SET ACK

RST and ACK to exit the programming mode.

Repeat the same routine to program the OTh2, OTh3 and OFLT outputs

Page 18: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 18 di 32

Notes on programming menu:

1. The wording BON/BOFF indicates the buzzer setting/un-setting for the first alarm threshold

2. Output HIGH/LOW mode states for the relay being in latched or unlatched mode (coil always energised / coil always de-energised)

3. Wt, Wt2; Wt3 are not used parameters. Setting are always to be left at 100

4. In measurement units menu it is possible to configure %LEL, %vol, ppm, %O2

5. For PRF configuration (profile) for Oxygen depletion, Th1 has to be higher than Th2 and this latter has to be higher than Th3. E.g.:

-Th1 19

-Th2 18

-Th3 17

6. While setting OTh1, OTh2, OTh3 OFLT output options, it is possible to select three different operating modes for the relays:

Reflex (Stable) follows the course of the alarm; alarm activated, output activated after a possible activation delay; alarm disabled, output low after a possible activation delay.

Pulse (Pulsed) produces a pulsed output with a time dependent on the moment the alarm arrives and after a possible activation delay.

Memo (Latched) as per the Reflex output, but becomes disabled only after the system has been reset.

The above three operating modes allow configure activation and deactivation timers RI ON and RI OFF.

4.2) Programming by PC

The SENTOX IDI control panel is fully programmable by a personal computer with a dedicated configuration software (optional). The “PCM 602 configuration” software has been designed to make the control panel programming simpler and faster. The programming of the control panel by the keypad is laborious in that the control panel has various functions.

Page 19: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 19 di 32

5) PCM 602 CONFIGURATION SOFTWARE (OPTIONAL)

The “PCM 602 configuration” software has been designed to make the control panel programming simpler and faster. The programming the control panel from the keypad is laborious in that the control panel has various functions and numerous zones. The programming necessary to make the system operative is described in the following pages. The “PCM 602 configuration” software has been designed to work in both Windows 95/98/2000/XP environments, and as such the user interface is similar to other Windows software

5.1) Installation of the software

Switch on the Personal Computer and wait for the Windows to be running. Insert the “PCM 602 configuration” CD-Rom into the computer’s drive, start “File Manager” and run the executable file UP.EXE from the CD-Rom. Follow the instructions which appear in the monitor screen until the software installation is finished.

5.2) Wiring and connections

In order to connect the SENTOX IDI control panel with a Personal Computer, it is essential to use an RS232/RS485 (or USB) interface. The next figure shows the electrical connections.

Cn

3

Cn

2

1

8

+

-

B

A

N O

NC

C

N O

NC

C

N O

NC

C

5 00 mAFU SE+

-

A

B

NO

NO

SENTOX “IDI” circuitlayout

Rs485 serial l ine for the PC

PC Rs485 seria l line

Scheda Rs485 comm. con PCPC Rs485 comm. board

PCRs485 USB or

Rs232 interface

Page 20: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 20 di 32

5.3) Starting the program

From the Programs menu select the “Pcm602EV V. 2.01” group and then select “Pcm602EV V. 2.01”

The following window will appear:

The programming software window offers the following menus:

• File

• Action

• Test

5.4) Parameters pre-setting

By choosing “File” and clicking on the submenu “Parameters” the window below appears where it is possible to select the language used by the program, the password for the connection to the control panel (for the Up-load and the Down-load), the serial communication port for the PC, and the path for saving the configuration files.

Page 21: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 21 di 32

5.5) Creating a new configuration file

Select New from the File menu and, between the three options Analogic, ISA and IDI, chose IDI that is the right one for the SENTOX IDI control unit. The window below appears

About the menu:

General: is for setting the general options of the SENTOX IDI control panel. See the par. 5.5.1.

Profiles: this option specifies up to 32 operation channel functions to be customized to the user’s requirements. e.g. the % LEL monitoring, the alarm levels and so on. See the par. 5.5.2

Channels: indicates the operational status that one wishes to give to the channel in question. See the par. 5.5.3.

Outputs: programming the output parameters implies defining how the outputs, that have been programmed in the various input channels, will operate. See the Par. 5.5.4.

5.5.1) General

Page 22: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 22 di 32

Model: SENTOX IDI that it is the name of the control panel

Start up Delay: it is the Warm Up time of the control panel, after the power up (0-999 minutes). Suggested 2 minutes.

Serial number: is the serial number of the control panel. It will appear after the first data Up-load or Down-load from the control panel.

Test date: factory test date of the control panel. It will appear after the first data Up-load or Down-load from the control panel.

Language: is the language of the texts on the control panel display

Date format: the date format: dd/mm/yy or mm/dd/yy or yy/mm/dd.

Time format: 24 h or Am/Pm

Control panel address: is the address of the control panel (fixed to 1 for SENTOX IDI)

Firmware version: firmware version of the control panel. It will appear after the first data Up-load or Down-load from the control panel.

5.5.2) Profiles

up to 32 Profiles are available for programming. The “Profile” specifies all settable parameters for each gas that has to be detected and the detection tasks required, e.g. measure unit, full scale range, the alarm levels etc. Measure Unit: can be % LEL (Lower Explosive Limit) for flammable gas detectors, ppm (Part Per Million) for Toxic gas detectors, % Vol. for CO2 and % O2 for Oxygen detectors. Signal direction: Down for Oxygen detectors or Up for every other kind of gas detector. Full Scale: is the measuring range of each gas detector. Usually this corresponds to 100 for flammable gas detectors but can be different from type to type for Toxic gas detectors. (it is related to the gas detector to be connected to the SENTOX IDI). Threshold 1: the first Alarm level of this Profile Threshold 2: the second Alarm level of this Profile Threshold 3: the third Alarm level of this Profile

Page 23: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 23 di 32

Hysteresis: This value indicates how variations in the signal will be ignored when in close proximity to the alarm threshold. The value is expressed as for the measure unit (% or ppm). Copy Profile: This command allows copying the settings for one Profile to other Profiles. In the Channel menu (see paragraph 5.5.3.) one out of the programmed Profiles will have to be associated to each detector being connected.

Below some Profiles, as examples.

Flammable gas detector

(Methane, LPG, Hydrogen etc.)

Carbon Monoxide (CO) gas detector

(range 300 ppm)

Carbon Dioxide (CO2) gas detector

(range 0-5% Vol.)

Oxygen depletion gas detector

(range 0-25% O2)

Page 24: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 24 di 32

5.5.3) Channels

Setting the Channel parameters implies programming the appropriate Profile for each detector and define the Channel status (Set or Unset).

Select the channel (detector) from 1 to 32 Associated type: choose the right Profile between those previously programmed in the Profiles menu. If the Channel is not used (detector not connected) the option Spare must be chosen. Channel status: Choose SET for a normal channel (detector) operation. If SET, the input channel is monitored and, in the event of an alarm, all the associated outputs are activated. Choose UNSET for a channel (detector) in test mode. If UNSET, the input channel is monitored but in the event of an alarm the associated outputs will not activate. Weight Threshold 1: not used (forced to 100) Weight Threshold 2: not used (forced to 100) Weight Threshold 3: not used (forced to 100) Copy Channel: This command allows the settings of a particular channel to be copied to other channels.

Page 25: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 25 di 32

5.5.4) Outputs

Programming the output parameters implies defining how the outputs that are part of the system will operate.

select the output to be programmed. All the outputs of the system are listed below:

Threshold 1: relay of the control panel for the Alarm level 1. See par. 2.4

Threshold 2: relay of the control panel for the Alarm level 2. See par. 2.4

Threshold 3: relay of the control panel for the Alarm level 3. See par. 2.4

Fault: relay of the control panel for the Fault condition. See par. 2.4

External Output 1 to 16 (optional): Open collector outputs of the remote 16-output module address 0 (if connected). See par. 2.3

External Output 17 to 32 (optional): Open collector Outputs of the remote 16-output module address 1 (if connected). See par. 2.3

Page 26: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 26 di 32

4-relay output setup.

Output type: the Output can have three different operation modes:

Reflex Stable follows the course of the alarm; alarm activated: output activated after a pre-set activation delay; alarm restored: output low after a pre-set de-activation delay.

Pulse Pulsed produces a pulsed output with a time dependent on the moment the alarm arrives and after a possible activation delay.

Memo Latched as per the stable output, but becomes disabled only after the system has been reset.

Activation delay: Can delay from 1 to 720 seconds the activation of the output

Deactivation delay (just for the Reflex mode): Can delay from 1 to 999 seconds the deactivation for the output after the alarm event is restored.

Pulse duration: (just for the Pulse mode) Can set the duration time of an energized output.

Output level: It defines if the relay output it is normally activated (high) or normally deactivated (low).

Page 27: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 27 di 32

Setup the Open Collector outputs on the ST.G/OUT16 modules.

When the remote output modules ST.G/OUT16 are connected on the RS485 loop, it is possible to program the external outputs from 1 to 16 (if the module is addressed as 0) and from 17 to 32 (if the module is addressed as 1). See paragraph 2.3

choose the external outputs from 1 to 16 (first output module addressed 0) or from 17 to 32 (second output module addressed 1).

Output type: the Output can have three different operation modes:

Reflex Stable follows the course of the alarm; alarm activated: output activated after a pre-set activation delay; alarm restored: output low after a pre-set de-activation delay.

Memo Latched as per the stable output, but becomes disabled only after the system has been reset.

Not used The output is not used. If the output is not existing (because the output module is non connected on the control panel loop) the option must be Not used.

Output level: It defines if the relay output it is normally energized (high) or normally not energized (low).

Type (Profile) and Threshold: the Type (Profile) is to be selected to create the association between the output and the Profile (from Prf. 1 to Prf. 32). The relationship between the output and the channel (detector) is done by setting the same Profile.

Page 28: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 28 di 32

First example:

-) should channel (detector) 4 be set to Profile 1

-) External output 3 set to Profile n. 1

-) and the Threshold set to Threshold 3

means that whenever Channel 4 (detector 4) reaches the 3rd

alarm Threshold, the External output No. 3 will activate.

The rule to bear in mind is the detector (channel) and the output to be activated must be configured with the same Profile.

Second example:

-) Should 32 detectors be connected, each one with an individual output associated to the 2nd

alarm threshold

To create 32 External outputs associated to the 2nd

alarm Threshold of each of the 32 gas detectors (channels), it is necessary to create 32 Profiles (menu Profiles) and associate each one of the 32 channels (detectors) to one of the 32 Profiles (menu Channels).

The last operation is to set each one of the 32 External outputs (menu Outputs) to each one of the 32 Profiles. In this case, Threshold 2 will be set.

Note: the above configuration requires that two remote output modules ST.G/OUT16 are loop connected.

5.6) Send Configuration (Download)

Once the parameter programming has been completed, it is possible to download (Send) the set-up to the control panel. It is advisable to save the programming file before downloading data to the SENTOX IDI control panel using the Save option from the File menu. By using the Parameters option in the File menu, check that the configuration of the port to which the control panel has been connected is correct. Select ”Send” from the “Action” menu, enter the password (default 000001) and enter the Control panel address “1” but do not give the OK command at this point.

In the control panel, enter the Programming mode (please refer to the control panel programming part of this manual)

Click Ok to start downloading. The downloading bar will be immediately displayed. On the control panel display the message “Remote prog.” will appear and during this phase it is neither possible to carry out any other operation nor monitor the inputs.

Once the data download is over, disconnect the cable between the control panel and the PC. The control panel is still in Programming mode and it is necessary to exit (see par. 4.1)

5.7) Receive configuration (Upload)

Whenever the data stored in the panel need updating or revising, connect the panel to the PC and upload the old parameters.

Page 29: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 29 di 32

In the control panel, enter the Programming mode (please refer to the control panel programming part of this manual). Select the Receive option in the Action menu of the configuration software.

Enter the control panel address “1” then click OK. The downloading bar will be immediately displayed. During this time it is neither possible to carry out any other operation on the control panel nor monitor the inputs.

Once the data up-load has ended, disconnect the cable between the control panel and the PC. The control panel is still in Programming mode and it is necessary to exit (see par. 4.1)

Data can now be modified on the PC and once ready for downloading, please refer to paragraph 5.6).

5.8) TEST menu

The “TEST” menu offers the following options:

• State

• Event log

5.8.1) State

This option gives users the ability to view graphically the state of the control panel and of all the 32 channels. To launch this option click on State in the TEST drop down menu. To Log On to the panel, the user must enter the control panel address “1” as prompted by the window displayed below:

Then press OK. The uploading bar will be immediately displayed. Once the State function has been accessed, the user is presented with a graphical representation of the SENTOX IDI control panel currently on-line. The window gives a general overview of the SENTOX IDI system. All the 32 channels are displayed with details. See below.

Page 30: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 30 di 32

Indication of the system statusSET or UN-SET

Alarm level 1

Alarm level 2

Alarm level 3 Fault status

Communication Fault output module “0”

Communication Fault output module “1”

ChannelstatusSET or UNSETor SPARE

ChannelProfile

Gas concentrationmeasured.In real time

Channelnumber

5.8.2) Event log

This option displays the system event log. The log records all events that occurred in the system. To launch this option click on Event log in the TEST drop down menu. To Log On to the panel, the user must enter the control panel address “1” as prompted by the window displayed below:

Then click OK. The uploading bar will be immediately displayed. On entering this option, the most recent events displayed in the following format:

Page 31: Sentox

Technical Manual SENTOX IDI

MT1714E.doc rev. 0 08/07/2008 Pagina 31 di 32

• By the Export command You can save the event list in the computer as a .csv file. A .csv file can be opened by other programs as Microsoft Excel for further elaboration.

• By the Print command all the events can be printed.

• By the Update command the event list is up-dated with the last events.