Range
� SEMP - Safegard ElectroMechanical Panel for the controland monitoring of up to 30 offsmoke/fire dampers.
Standard off the shelf panel.
� SCMP - Safegard Control andMonitoring Panel.
Bespoke panel to suit specificproject requirements.
June 2008
SEMP - Standard SCMP - BespokeElectro Mechanical Control and
Monitoring Panels
AUTOMATIC DAMPER OPERATION UTILISING RELAY LOGICAND LED INDICATION OF DAMPER STATUS
Example SCMP
Example SEMP
SEMP – Safegard Electro Monitoring Panel
Introduction
The range of Safegard Electro MechanicalStandard Control Panels are designed forthe control and monitoring of either 24Vor 230V damper actuators in groups of10, 20 or 30.
Damper control actuators to be connectedto the site wiring, which when installed bythe contractors, shall provide the relevantstandard functions.
Specification
Each group of 10 dampers are controlledand monitored via separate controllerswhich can be numbered/referencedaccording to site requirements.
The damper control controllers areterminated to provide for all externalconnections to the dampers, Fire Alarmsand BMS Contacts.
Dampers are controlled by Zones andmonitored individually.
Damper locations can also be recordedon a printed label fitted beside each LED.
Input terminals are provided to accept 1Volt free contact interface with the FireAlarm System per group of 10 dampers.
These contacts are Normally Closed (NC)going open in an alarm.
SEMP 20 & SEMP 30 are dispatched asstandard with links for additional zoneoperation.
In addition each Control Panel providesan output terminal to provide a Volt freecontact interface with a BMS. This is achangeover contact, which goes closedcircuit to indicate either a not normal orfault condition.
Features
Dampers control panels are standardmanufacture
Wall mount enclosures to IP20
Vinyl overlay facia
Damper Controlled in zones andindividually monitored
Top cable gland entry
Fire Interface(s) per zone
BMS common fault relay output perpanel
Test/Normal/Override keyswitch
Optional battery back up
Keyswitch mains isolator
Lamp test
Hinged on left.
2
SEMP
SEMP Sizes
Damper quantity Enclosure size (mm) Zones BMS outputsType No. off H x W x D
SEMP10 1 – 10 500 x 400 x 200 Max 1 Max 1
SEMP20 11 – 20 500 x 500 x 200 Max 2 Max 1
SEMP30 21 – 30 600 x 600 x 200 Max 3 Max 1
SEMP10
SCMP – Safegard Control and Monitoring Panel
3
SCMP
SCMP sizes
No.of dampers Estimated enclosure
Introduction
The SCMP consists of a number ofsmoke/fire dampers hard wiredindividually or in groups to a centralcontrol panel. The dampers may beindividually or collectively controlled andcontinuously monitored.
Dampers and control actuators may havediffering control and monitoringrequirements and therefore will beconnected to the site wiring, which wheninstalled by the contractor, will providethe relevant specified functions.
Specification
The SCMP typically consists of theappropriate number of switches toprovide individual or group control, LEDindication for status monitoring and allnecessary relays and timers to complywith the customer needs for fully or semi-automatic damper operation.
Interface with the Fire Alarm panel is viavolt-free contacts which are normallyclosed and open upon alarm, the SCMPwill then activate relevant dampers to theiralarm status.
Safegard Damper Control Panels arepurposely manufactured for any particularproject to suit specific customerrequirements.
Features
SCMP’s are purposely manufactured forany particular project to suit specificcustomer requirements
Dampers can be individually or collectivelycontrolled and continually monitored
Wall mounted enclosures to IP20
Custom engraved traffolyte fascia
LED indication of damper status
Zonal inputs
Door interlocking isolator
Miniature circuit breaker protection
Options
Lockable glazed door
Special paint finish to RAL Standard
Number
Flush mounting flanges
Latching push buttons
Fireman’s override key switches
Test switch
Lamp test
Audible alarm with mute facility
B.M.S common fault relay interface
B.M.S output
Delay timers
Battery backup
size (mm)
1 - 4 400 x 400 x 200
5 - 8 400 x 400 x 200
9 - 12 500 x 500 x 200
13 - 16 500 x 500 x 200
17 - 20 600 x 600 x 200
21 - 30 600 x 600 x 200
SEMP and SCMP
Systems House, Unit 34,Southern Cross Business Park,Bray, Co.WicklowT: +353 1 2761600 F: +353 1 2761611
Penthouse Floor, No 5 Lapps Quay, Co. CorkT: +353 21 4943989F: +353 21 4943988
E: [email protected] W: www.safegard.ie
Typical SEMP and SCMPElectro Mechanical Schematic
Commissioning.Safegard Systems offers a comprehensiveafter sales service to include for pre-commissioning checks, completecommissioning serviceof all our products in line with and toencompass CIBSE guidelines andplanned preventive maintenance visits.
The information contained herein is subject to changewithout notice due to continuing research anddevelopment.