Upload
audrey-patrick-kalla
View
239
Download
0
Embed Size (px)
Citation preview
7/30/2019 Selecting Centrifugal Pumps Data
1/92
Technical inormation
Selecting Centriugal Pumps
7/30/2019 Selecting Centrifugal Pumps Data
2/92
7/30/2019 Selecting Centrifugal Pumps Data
3/92
Copyright by
KSB Aktiengesellschat
Published by:
KSB Aktiengesellschat,
Communications (V5),
67225 Frankenthal / Germany
All rights reserved. No part o
this publication may be used,
reproduced, stored in or intro-
duced in any kind o retrieval
system or transmitted, in any
orm or by any means (electro-
nic, mechanical, photocopying,
recording or otherwise) without
the prior written permission o
the publisher.
4th completely revised and ex-
panded edition 005
Layout, drawings and
composition:
KSB Aktiengesellschat,
Media Production V5
ISBN -00-0784-4
7/30/2019 Selecting Centrifugal Pumps Data
4/92
4
Contents
1 Nomenclature ..................................................................6
2 Pump Types ................................................................89
3 Selection or Pumping Water..........................................0
3.1 Pump Data...............................................................................0
.. Pump Flow Rate ......................................................................0
.. Developed Head and Developed Pressure o the Pump .............0.. Eciency and Input Power ......................................................0
..4 Speed o Rotation ....................................................................
..5 Specic Speed and Impeller Type ..............................................
..6 Pump Characteristic Curves .....................................................
3.2 System Data .............................................................................6
.. System Head ...........................................................................6
... Bernoullis Equation .................................................................6
... Pressure Loss Due to Flow Resistances .....................................8
.... Head Loss in Straight Pipes ......................................................8
.... Head Loss in Valves and Fittings ..............................................
.. System Characteristic Curve .....................................................6
3.3 Pump Selection.........................................................................8
.. Hydraulic Aspects ....................................................................8
.. Mechanical Aspects ..................................................................9
.. Motor Selection .......................................................................9
... Determining Motor Power .......................................................9
... Motors or Seal-less Pumps ......................................................
... Starting Characteristics ............................................................
3.4 Pump Perormance and Control...............................................4
.4. Operating Point .......................................................................4
.4. Flow Control by Throttling ......................................................4
.4. Variable Speed Flow Contol .....................................................5
.4.4 Parallel Operation o Centriugal Pumps ..................................6.4.5 Series Operation .......................................................................8
.4.6 Turning Down Impellers ..........................................................8
.4.7 Under-ling o Impeller Vanes ..................................................9
.4.8 Pre-swirl Control o the Flow ...................................................9
.4.9 Flow Rate Control or Change by Blade Pitch Adjustment ........9
.4.0 Flow Control Using a Bypass ...................................................40
3.5 Suction and Inlet Conditions....................................................4
.5. The NPSH Value o the System: NPSHa ..................................4
.5.. NPSHa or Suction Lit Operation ...........................................4
.5.. NPSHa or Suction Head Operation .........................................44
.5. The NPSH Value o the Pump: NPSHr .....................................44
.5. Corrective Measures ................................................................45
3.6 Eect o Entrained Solids .........................................................47
4 Special Issues when Pumping Viscous Fluids ..................48
4.1 The Shear Curve ......................................................................48
4.2 Newtonian Fluids .....................................................................50
4.. Infuence on the Pump Characteristics ......................................50
4.. Infuence on the System Characteristics ....................................54
4.3 Non-Newtonian Fluids ............................................................54
4.. Infuence on the Pump Characteristics ......................................54
4.. Infuence on the System Characteristics ....................................55
Table o contents
7/30/2019 Selecting Centrifugal Pumps Data
5/92
5
5 Special Issues when Pumping Gas-laden Fluids ..............56
6 Special Issues When Pumping Solids-laden Fluids ..........57
6. Settling Speed ...........................................................................57
6. Infuence on the Pump Characteristics ......................................58
6. Infuence on the System Characteristics ....................................596.4 Operating Perormance ............................................................59
6.5 Stringy, Fibrous Solids ..............................................................59
7 The Periphery ................................................................6
7. Pump Installation Arrangements ..............................................6
7. Pump Intake Structures ............................................................6
7.. Pump Sump ..............................................................................6
7.. Suction Piping ..........................................................................6
7.. Intake Structures or Tubular Casing Pumps ............................64
7..4 Priming Devices .......................................................................65
7. Arrangement o Measurement Points .......................................67
7.4 Shat Couplings ........................................................................68
7.5 Pump Nozzle Loading ..............................................................69
7.6 National and International Standards and Codes .....................69
8 Calculation Examples
(or all equations numbered in bold typeace) ................7
9 Additional Literature .....................................................79
10 Technical Annex (Tables, Diagrams, Charts) .................80
Tab. : Centrigal pump classication ...................................................8
Tab. : Reerence speeds o rotation ....................................................
Tab. : Approximate average roughness height k or pipes ..................0
Tab. 4: Inside diameter d and wall thickness s in mm and weight otypical commercial steel pipes and their water content ...........0
Tab. 5: Loss coecients or various types o valves and ttings ........Tab. 6: Loss coecients in elbows and bends ....................................4
Tab. 7: Loss coecients or ttings ..............................................4/5Tab. 8: Loss coecients or adapters .................................................5
Tab. 9: Types o enclosure or electric motors to EN 60 59 and
DIN/VDE 050, Part 5 ............................................................0
Tab. 0: Permissible requency o starts Z per hour or electric motors ..0
Tab. : Starting methods or asynchronous motors ..............................
Tab. : Vapour pressure, density and kinematic viscosity o water at
saturation conditions as a unction o the temperature .............4
Tab. : Infuence o the altitude above mean sea level on the annual
average atmospheric pressure and on the corresponding
boiling point .........................................................................4
Tab. 4: Minimum values or undisturbed straight lengths o piping
at measurement points in multiples o the pipe diameter D ......67
Contents
Tables
7/30/2019 Selecting Centrifugal Pumps Data
6/92
6
A m Area
A m Distance between measuring point and pump
fange
a m, mm Width o a rectangular elbow
B m, mm Vertical distance rom suction pipe to foor
Cv gpm Flow coecient or valves, dened as the fowo water at 60 F in US gallons/minute at a
pressure drop o lb/in across the valve
cD Resistance coecient o a sphere in water fow
cT (%) Solids content in the fow
D m (mm) Outside diameter; maximum diameter
DN (mm) Nominal diameter
d m (mm) Inside diameter; minimum diameter
ds m (mm) Grain size o solids
d50 m (mm) Mean grain size o solids
F N Force
Throttling coecient o an orice
H Conversion actor or head (KSB system)
Q Conversion actor or fow rate (KSB system)
Conversion actor or eciency (KSB system)
g m/s Gravitational constant = 9.8 m/s
H m Head; discharge head
Hgeo m Geodetic head
Hs m Suction lit
Hs geo m Vertical distance between water level and pump
reerence plane or suction lit operation
Hz geo m Vertical distance between pump reerence planeand water level or positive inlet pressure
operation
HL m Head loss
H0 m Shut-o head (at Q = 0)
I A Electric current (amperage)
K Dimensionless specic speed, type number
k mm, m Mean absolute roughness
k Conversion actors kQ, kH, k (HI method)
kv m/h Metric fow actor or valves, dened as the
fow o water at 0 C in cubic metres per hour
at a pressure drop o bar
L m Length o pipe
Ls m Straight length o air-lled pipe
M Nm Moment
NPSHr m NPSH required by the pump
NPSHa m NPSH available
Ns Specic speed in US units
n min (rpm) Speed o rotation
s (rev/s)
nq min Specic speed in metric units
P kW (W) Power; input power
1
1Nomenclature
Nomenclature
7/30/2019 Selecting Centrifugal Pumps Data
7/92
7
pe Pressure in suction or inlet tank
PN (bar) Nominal pressure
p bar (Pa) Pressure rise in the pump; pressure dierential(Pa N/m)
p bar (Pa) Pressure (Pa N/m = 05 bar)
pb mbar (Pa) Atmospheric pressure (barometric)pL bar (Pa) Pressure loss
pv bar (Pa) Vapour pressure o fuid pumped
Q m/s, m/h Flow rate / capacity (also in litre/s)
qair % Air or gas content in the fuid pumped
Qo m/h Flow rate at switch-o pressure
Qon m/h Flow rate at start-up pressure
R m (mm) Radius
Re Reynolds number
S m Submergence (fuid level above pump);
immersion depth
s mm Wall thickness
s m Dierence o height between centre o pump im-
peller inlet and centre o pump suction nozzle
T Nm Torque
t C Temperature
U m Length o undisturbed fow
U m Wetted perimeter o a fow section
VB m Suction tank volume
VN m Useul volume o pump sump
v m/s Flow velocity
w m/s Settling velocity o solidsy mm Travel o gate valve; distance to wall
Z /h Switching cycle (requency o starts)
z Number o stages
zs,d m Height dierence between pump discharge and
suction nozzles
Angle o change in fow direction; opening angle Angle o inclination Loss coecient (%) Eciency
Pa s Dynamic viscosity Pipe riction actor m/s Kinematic viscosity
kg/m Density
N/m Shear stress N/m Shear stress at yield point Temperature actor; opening angle o a butter-
fy valve; cos : power actor o asynchronousmotors
Head coecient (dimensionless head generatedby impeller)
1
Indices, Subscripts
a At outlet cross-section o
the system; branching o
Bl Reerring to orice bore
d On discharge side; at dis-
charge nozzle; fowing
through
dyn Denoting dynamic com-
ponent
E At the narrowest cross-
section o valves (Table 5)
E At suction pipe or bell-
mouth inlet
e At inlet cross-section o
system, e. g. in suction
or inlet tank Reerring to carrier fuid
H Horizontal
in Reerring to inlet fow
K Reerring to curvature
L Reerring to losses
m Mean value
max Maximum value
min Minimum value
N Nominal value
opt Optimum value; at best
eciency point (BEP)P Reerring to pump
p Reerring to pressure
r Reduced, or cutdown im-
peller or impeller vanes
s On suction side; at suc-
tion nozzle
s Reerring to solids
stat Static component
sys Reerring to system /
installation
t Reerring to impeller
prior to trimming
V Vertical
w Reerring to water
z Reerring to viscous fuid
0 Basic position, reerred
to individual sphere
, , Consecutive numbers;
items
I, II Number o pumps oper-
ated
Nomenclature
7/30/2019 Selecting Centrifugal Pumps Data
8/92
8
Table 1: Centriugal pump classication
Number o stages Single stage Multistage
Shat position Horizontal Vertical Horiz. Vertic.
Casing design Radial Axial Radial Axial Stage casing
Impeller entries
Motor type, Fig. ..Dry (standardized)
motor a b c d e g h
Magnetic drive i
Submerged dry rotor
motor (See ..) j k l m
Wet rotor motor
(See ..) n o p
2Pump Types
Typical selection criteria or
centriugal pumps are their
design data (fow rate or capac-
ity Q, discharge head H, speed
o rotation n and NPSH), the
properties o the fuid pumped,
the application, the place o
installation and the applicable
regulations, specications, laws
and codes. KSB oers a broad
range o pump types to meet the
most varied requirements.
Main design eatures or classi-
cation are:
the number o stages (single-
stage / multistage),
2
the position o the shat (hori-
zontal / vertical),
the pump casing (radial, e. g.
volute casing / axial, e. g.
tubular casing),
the number o impeller entries
(single entry / double entry),
the type o motor (dry mo-
tor / dry rotor motor, e. g.
submerged motor / wet rotor
motor, e. g. canned motor,
submersible motor).
These eatures usually determine
what a pump type or series
looks like. An overview o typi-cal designs according to classi-
cation eatures is given below
(Table and Figs. a to p).
Other pump classication
eatures include:
the mode o installation, which
is dealt with in section 7.,
the nominal diameter (or thepump size, as a unction o
the fow rate),
the rated pressure (or the
wall thickness o casings and
fanges),
the temperature (or example
or the selection o cooling
equipment or shat seals),
the fuid pumped (abrasive,
aggressive, toxic fuids),
the type o impeller (radial
fow / axial fow depending on
the specic speed),
the sel-priming ability,
the casing partition, the posi-
tion o the pump nozzles, an
outer casing, etc.
a
b
Pump Types (Examples)
7/30/2019 Selecting Centrifugal Pumps Data
9/92
9
2
Fig 1 (a to p):
Centriugal pump classication
acc. to Table 1
hg
kji
ml
po
edc
n
Pump Types (Examples)
7/30/2019 Selecting Centrifugal Pumps Data
10/92
0
3 Flow Rate Head Eciency Input Power
3Selection or Pumping Water
This section applies mainly to
pumping water; the particulari-
ties o pump selection or other
media are treated in sections 4,
5 and 6.
3.1Pump Data
3.1.1Pump Flow Rate
The pump fow rate or capacity
Q is the useul volume o fuid
delivered to the pump discharge
nozzle in a unit time in m/s
(l/s and m/h are also used in
practice, as are GPM in the US).
The fow rate changes propor-
tionally to the pump speed o
rotation. Leakage fow as well
as the internal clearance fows
are not considered part o the
pump fow rate.
3.1.2Developed Head andDeveloped Pressure othe Pump
The total developed head H o
a pump is the useul mechani-
cal energy in Nm transerred
by the pump to the fow, per
weight o fuid in N, expressed
in Nm/N = m (also used to be
called metres o fuid)). The
head develops proportionally
to the square o the impellers
speed o rotation and is inde-
pendent o the density o the
fuid being pumped. A given
centriugal pump will impart the
same head H to various fuids
(with the same kinematic viscos-
ity ) regardless o their density
. This statement applies to all
centriugal pumps.
The total developed head H
maniests itsel according to
Bernoullis equation (see section
...) as
the pressure head Hp propor-
tional to the pressure dier-
ence between discharge and
suction nozzles o the pump,
the geodetic head zs,d (Figs. 8
and 9), i.e., the dierence in
height between discharge and
suction nozzles o the pump
and
the dierence o the kinetic
energy head (vd-vs
)/g be-
tween the discharge and suc-
tion nozzles o the pump.
The pressure rise p in thepump (considering the location
o the pressure measurement
taps according to section 7.!)
is determined solely by the pres-
sure head Hp along with the
fuid density according to the
equation
p = g[H-zs,d-(vd-vs)/g] (1)
where
Density o the fuid beingpumped in kg/m
g Gravitational constant
9.8 m/s
H Total developed head o the
pump in m
zs,d Height dierence between
pump discharge and suction
nozzles in m (see Figs. 8
and 9)
vd Flow velocity in the discharge
nozzle = 4 Q/pdd in m/s
vs Flow velocity in the suction
nozzle = 4 Q/pds in m/s
Q Flow rate o the pump atthe respective nozzle in m/s
d Inside diameter o the re-
spective pump nozzle in m
p Pressure rise in N/m (orconversion to bar: bar =
00 000 N/m)
High-density fuids thereore
increase the pressure rise and
the pump discharge pressure.
The discharge pressure is thesum o the pressure rise and the
inlet pressure and is limited by
the strength o the pump casing.
The eect o temperature on the
pumps strength limits must also
be considered.
3.1.3Eciency and Input Power
The input power P o a pump(also called brake horsepower)
is the mechanical power in
kW or W taken by the shat or
coupling. It is proportional to
the third power o the speed o
rotation and is given by one o
the ollowing equations:
) In the US, the corresponding units are
t-lb/lbm, i. e. oot head = oot-
pound-orce per pound mass; the
numerical value o head and specic
work are identical.
7/30/2019 Selecting Centrifugal Pumps Data
11/92
P =gQH
in W =gQH
in kW =QH
in kW 000 67
(2)
3
where
Density in kg/m
in kg/m
in kg/dm
Q Flow rate in m/s in m/s in m/h
g Gravitational constant = 9.8 m/s
H Total developed head in m
Eciency between 0 and
7/30/2019 Selecting Centrifugal Pumps Data
12/92
(IGHHEAD
IMPELLER
UPTO
-EDIUMHEAD
IMPELLER
UPTO
,OWHEAD
IMPELLER
UPTO
-IXEDFLOW
IMPELLER
UPTO
!XIALFLOW
PROPELLER
TONQ RPM
3
nq = n = n (3)
where Qopt in m/s Qopt in m
/s = Flow rate at optHopt in m Hopt in m = Developed head at optn in rpm n in rev/s = Pump speed
nq in metric units nq Dimensionless parameter
g Gravitational constant 9.8m/s
Approximate reerence values:
nq up to approx. 5 Radial high head impellerup to approx. 40 Radial medium head impeller
up to approx. 70 Radial low head impeller
up to approx. 60 Mixed fow impeller
approx. rom 40 to 400 Axial fow impeller (propeller)
Fig. 2: Eect o the specic speed nq on the design o centriugal
pump impellers. The diuser elements (casings) o single stage
pumps are outlined.
Qopt/
(Hopt/)/4
Qopt(g Hopt)/4
Specic Speed
dimensionless characteristic
parameter while retaining the
same numerical value by using
the denition in the right-hand
version o the ollowing equa-
tion []:
For multistage pumps the devel-
oped head Hopt at best eciency
or a single stage and or double-
entry impellers, the optimum
fow rate Qopt or only one im-
peller hal are to be used.
As the specic speed nq in-
creases, there is a continuous
change rom the originally
radial exits o the impellers to
mixed fow (diagonal) and
eventually axial exits (see Fig. ).
The diuser elements o radial
pump casings (e.g. volutes) be-
come more voluminous as long
as the fow can be carried o
radially. Finally only an
axial exit o the fow is possible
(e.g. as in a tubular casing).
Using Fig. it is possible to de-
termine nq graphically. Further
types o impellers are shown in
Fig. 4: Star impellers are used in
sel-priming pumps. Periph-
eral impellers extend the speci-c speed range to lower values
down to approximately nq = 5
(peripheral pumps can be de-
signed with up to three stages).
For even lower specic speeds,
rotary (or example progressive
cavity pumps with nq = 0. to )
or reciprocating positive dis-
placement pumps (piston
pumps) are to be preerred.
The value o the specic speed
is one o the infuencing para-
meters required when convert-
ing the pump characteristic
curves or pumping viscous or
solids-laden media (see sections
4 and 6).
In English-language pump lit-
erature the true dimensionless
specic speed is sometimes des-
ignated as the type number K.
In the US, the term Ns is used,
which is calculated using gal-
lons/min (GPM), eet and rpm.
The conversion actors are:
K = nq / 5.9
Ns = nq / 5.6(4)
7/30/2019 Selecting Centrifugal Pumps Data
13/92
Radial double-entry impeller*)
Star impeller or side channel pump(sel-priming)
Peripheral pump impeller or very lowspeciic speed (nq 5 to 0)
*) Plan view shown without ront shroud
Closed (shrouded) mixed low impeller *)
Open (unshrouded) mixed low impeller
Axial low propeller
Radial impeller *)
3
Fig. 3: Nomograph to determine specic speed nq (enlarged view on p. 80)Example: Qopt= 66 m
3/h = 18.3 l/s; n = 1450 rpm, Hopt= 17.5 m. Found: nq = 23 (metric units).
Fig. 4:
Impeller types or clear liquids
Specic Speed Impeller Types Characteristic Curves
3.1.6Pump Characteristic Curves
Unlike positive displacement
pumps (such as piston pumps),
centriugal pumps deliver a var-
iable fow rate Q (increasing
with decreasing head H) when
operating at constant speed.
They are thereore able to ac-
commodate changes in the
system curve (see section ..).
The input power P and hence
the eciency as well as theNPSHr (see section .5.4) are
dependent on the fow rate.
7/30/2019 Selecting Centrifugal Pumps Data
14/92
4
90
80
70
60
50
40
20
30
80
70
60
50
40
0
5
10
20
30
100 20 40 60 80 100 120
Flow rate Q [m3/h] Flow rate Q [m3/h] Flow rate Q [m3/h]
140 160 0 100 200 300 400 500 0 500 15001000 2000 2500 3000550
HeadH[m]
NPSHr[m]
PowerP[kW]
EfficiencyH[
%]
2422
18
14
10
20
16
12
86
90
30
80
70
60
50
40
0
5
1510
15
14
16
17
13
HeadH[m]
NPSHr[m]
PowerP[kW]
EfficiencyH[
%]
2
4
18
14
10
20
16
12
8
6
90
30
80
70
60
50
40
5
15
10
60
40
20
80
100
0
HeadH[m]
NPSHr[m]
PowerP[kW]
EfficiencyH[
%]
n = 2900 min1 n = 1450 min1 n = 980 min1
Operating limit
> L V
11OPT
H
HOPT
11OP
0
0OPT
300
25
11OPT
(
(OPT
Operating limit forlow input power
for highinput power
25
25
300
300
150
150
70
70
40
40
11OP
NPSHrNPSHr opt
25
25
300
300
150
70
40
150
300
7040
25
3
Fig. 5: Eect o specic speed nq on centriugal pump characteristic
curves (Not drawn to scale! For NPSHr, see section 3.5.4).
Fig. 6: Three examples o characteristic curves or pumps o diering specic speeds.
a: radial impeller, nq 20; b: mixed fow impeller, nq 80; c: axial fow impeller, nq 200.(For NPSH
rsee section 3.5.4)
Characteristic Curves
The relationship o these val-
ues is shown graphically in the
pump characteristic curves,
whose shape is infuenced by
the specic speed nq and which
document the perormance o acentriugal pump (see Fig. 5 or
a comparison o characteristics
and Fig. 6 or examples). The
head curve o the pump is also
reerred to as the H/Q curve.
The H/Q curve can be steep or
fat. For a steep curve, the fow
rate Q changes less or a given
change o developed head H
than or a fat curve (Fig. 7).This can be advantageous when
controlling the fow rate.
7/30/2019 Selecting Centrifugal Pumps Data
15/92
5
(EAD
(
1STEEP
1FLAT
&LOWRATE1
5NSTABLE
REGION
3TEEPCHARACTERISTICCURVE
&LATCHARACTERISTICCURVE
-AXIMUM
(
Fig. 7: Steep, fat or unstable characteristic curve
3Characteristic Curves
H/Q characteristics normally
have a stable curve, which
means that the developed head
alls as the fow rate Q in-
creases. For low specic speeds,
the head H may in the low
fow range drop as the fow
rate Q decreases, i. e., the curve
is unstable (shown by the dash
line in Fig. 7). This type o
pump characteristic curve need
only be avoided when two
intersections with the system
curve could result, in particularwhen the pump is to be used or
parallel operation at low fow
rates (see section .4.4) or when
it is pumping into a vessel which
can store energy (accumulator
lled with gas or steam). In all
other cases the unstable curve is
just as good as the stable charac-
teristic.
Unless noted otherwise, thecharacteristic curves apply or
the density and the kinematic
viscosity o cold, deaerated
water.
7/30/2019 Selecting Centrifugal Pumps Data
16/92
6
A VA
EVE
EVE
VD
VS
AVA
(GEO
(SGEO
ZSD
A VA
PA PA
! " #
PE
$ %
3
Fig. 8: Centriugal pump system with variously designed vessels in suction lit operation
A = Open tank with pipe ending below the water level
B = Closed pressure vessel with ree fow rom the pipe ending above the water level
C = Closed pressure vessel with pipe ending below the water level
D = Open suction/inlet tank
E = Closed suction/inlet tank
va and ve are the (usually negligible) fow velocities at position a in tanks A and C and at position e
in tanks D and E. In case B, va is the non-negligible exit velocity rom the pipe end at a .
System Head Bernoulli
3.2System Data
3.2.1System Head
3.2.1.1Bernoullis Equation
Bernoullis equation expresses
the equivalence o energy in
geodetic (potential) energy,
static pressure and kinetic
energy orm. The system head
Hsys or an assumed rictionless,
inviscid fow is composed o the
ollowing three parts (see Figs.
8 and 9):
Hgeo (geodetic head) is the
dierence in height between
the liquid level on the inlet
and discharge sides. I the dis-
charge pipe ends above the
liquid level, the centre o the
exit plane is used as reerence
or the height (see Figs 8B and
9B).
(pa - pe)/( g) is the pressure
head dierence between the
inlet and outlet tank, applic-
7/30/2019 Selecting Centrifugal Pumps Data
17/92
7
AVA
E VEE VE
VD
VS
A VA
(GEO
(ZGEO
ZSD
A VA
PA PA
! " #
PE
$ %
3
Fig. 9: Centriugal pump system with variously designed vessels in suction head (positive inlet pressure)
operation. Legend as in Fig. 8.
System Head Bernoulli
able when at least one o the
tanks is closed as or B, C or
E (see Figs. 8B, C, E, 9B, C,
E).
(va-ve
)/g is the dierence in
the velocity heads between the
tanks.
For a physically real fow, the
riction losses (pressure head
losses) must be added to these
components:
HL is the sum o the head
losses (fow resistance in the
piping, valves, ttings, etc in
the suction and discharge lines
as well as the entrance and exit
losses, see section ...), and
is reerred to as the system pres-
sure loss.
The sum o all our componentsyields the system head Hsys:
Hsys = Hgeo + (pape)/( g) + (va-ve)/g + HL (5)
where
all the heads H are in m,
all the pressures p are in Pa ( bar = 00 000 Pa),
all velocities v are in m/s,
the density is in kg/m,
the gravitational constant is g = 9.8 m/s
.
7/30/2019 Selecting Centrifugal Pumps Data
18/92
8
Fig. 10: Pipe riction actor as a unction o the Reynolds number Re and the relative roughness d/k(enlarged view on p. 81)
3 System Head Pressure Loss Head Loss
DK
&ULLYROUGHK
LAMINAR TURBULENT
2ECRIT
,IMITINGCURVE
(YDRAULICALLYSMOOTHK
L
2E
2EYNOLDSNUMBER2E
0IPE
FRIC
TION
FACTORL
The dierence o the velocity
heads can oten be neglected in
practice. When at least one tank
is closed as or B, C or E (see
Figs. 8B, C, E, 9B, C, E), Eq. 5
can be simplied as
HsysHgeo+(pape)/(g)+HL (6)
and urther simplied when
both tanks are open as or A
and D (see Figs. 8A, D and 9A,
D) as
HsysHgeo+HL (7)
3.2.1.2Pressure Loss Due to FlowResistances
The pressure loss pL is caused
by wall riction in the pipes and
fow resistances in valves, t-tings, etc. It can be calculated
rom the head loss HL, which is
independent o the density ,
using the ollowing equation:
pL = g HL (8)
where
Density in kg/m
g Gravitational constant
9.8 m/s
HL Head loss in m
pL Pressure loss in Pa
( bar = 00 000 Pa)
3.2.1.2.1Head Loss in Straight Pipes
The head loss or fow in
straight pipes with circular
cross-sections is given in general
by
HL = L
v (9) d g
where
Pipe riction actor accordingto Eqs. () to (4)
L Length o pipe in m
d Pipe inside diameter in m
v Flow velocity in m/s(= 4Q/pd or Q in m/s)
g Gravitational constant
9.8 m/s
7/30/2019 Selecting Centrifugal Pumps Data
19/92
9
3Head Loss in Straight Pipes
For pipes with non-circular
cross-sections the ollowing
applies:
d = 4A/U (10)
where
A Cross-sectional fow area
in m
U Wetted perimeter o the
cross-section A in m; or
open channels the ree fuid
surace is not counted as part
o the perimeter.
Recommended fow velocities
or cold waterInlet piping 0.7.5 m/sDischarge piping .0.0 m/sor hot water
Inlet piping 0.5.0 m/sDischarge piping .5.5 m/sThe pipe riction actor hasbeen determined experimentally
and is shown in Fig. 0. It varies
with the fow conditions o the
liquid and the relative rough-ness d/k o the pipe surace. The
fow conditions are expressed
according to the anity laws
(dimensional analysis) using the
Reynolds number Re. For cir-
cular pipes, this is:
Re = v d/ (11)
where
v Flow velocity in m/s
(= 4Q/pd or Q in m/s)d Pipe inside diameter in m
Kinematic viscosity in m/s
(or water at 0 C exactly
.00 (0)6 m/s).
For non-circular pipes, Eq. 0 is
to be applied or determining d.
For hydraulically smooth pipes
(or example drawn steel tubing
or plastic pipes made o poly-
ethylene (PE) or polyvinyl chlor-
ide (PVC)) or or laminar fow,
can be calculated:
In the laminar fow region
(Re 0)
the test results can be repre-
sented by the ollowing empiri-
cal relationship dened by Eck
(up to Re < 08 the errors are
smaller than %):
=0.09
(lgRe
)(13)
7
In Fig. 0 it can be seen that
the pipe riction actor depends
on another dimensionless para-
meter, the relative roughness o
the pipe inner surace d/k; k is
the average absolute roughnesso the pipe inner surace, or
which approximate values are
given in Table . Note: both d
and k must be expressed in the
same units, or example mm!
As shown in Fig. 0, above a
limiting curve, is dependentonly on the relative roughness
d/k. The ollowing empirical
equation by Moody can be used
in this region:
=0.0055+0.5/ (d/k) (14)
For practical use, the head
losses HL per 00 m o straight
steel pipe are shown in Fig.
as a unction o the fow rate Q
and pipe inside diameter d. The
values are valid only or cold,
clean water or or fuids with
the same kinematic viscosity, or
completely lled pipes and or an
absolute roughness o the pipe
inner surace o k = 0.05 mm,
i.e., or new seamless or longi-tudinally welded pipes. (For
the pipe inside diameters, see
Table 4).
The eect o an increased
surace roughness k will be de-
monstrated in the ollowing
or a requently used region in
Fig. (nominal diameter 50
to 00 mm, fow velocity 0.8
to .0 m/s). The dark-shadedregion in Fig. 11 corresponds
to the similarly marked region
in Fig. 10 or an absolute rough-
ness k = 0.05 mm. For a rough-
ness increased by a actor 6
(slightly incrusted old steel pipe
with k = 0.0 mm), the pipe
riction actor(proportionalto the head loss HL) in the
lightly shaded region in Fig. 0
is only 25% to 60% higher thanbeore.
For sewage pipes the increased
roughness caused by soiling
must be taken into considera-
tion (see section .6). For pipes
with a large degree o incrusta-
tion, the actual head loss can
only be determined experimen-
tally. Deviations rom the no-
minal diameter change the headloss considerably, since the pipe
inside diameter enters Eq. (9) to
the 5th power! (For example, a
5% reduction in the inside dia-
meter changes the head loss by
0%). Thereore the nominal
diameter may not be used as
the pipe inside diameter or the
calculations!
7/30/2019 Selecting Centrifugal Pumps Data
20/92
0
*i>i> `vii
-ii i] i>i >V`Vi>i` }>>i`
}` >i`i`] Li` }>>i` Viii`
ii`
i`] `i>i }V> i>V> >viVi>}
LiVii ii>V> >>}i i
Vii i] vi` v-VVii i] vi` v,ivVi VVii i] vVVii i`] v
i>i `>>]>V,LLiL} i] iLi`7` i >vi}ii>i>
x x x x {
x x x x
3
Table 4: Inside diameter d and wall thickness s in mm and weight o typical commercial steel pipes and their
water content in kg/m to ENV 10 220 (ormerly DIN ISO 4200). D = outside diameter, s = wall thickness
All dimensions in mm Seamless pipe Welded pipeSeamless Welded weight in kg/m weight in kg/m
DN D s * d s ** d Pipe Water Pipe Water
5 . .0 7. .8 7.7 0.95 0.5 0.866 0.460 6.9 .0 .9 .8 . . 0.4 . 0.465 .7 . 9. .0 9.7 .78 0.665 .56 0.69 4.4 .6 7. . 7.8 .55 .09 .7 .40 48. .6 4. . 4.7 .9 .46 .6 .5050 60. .9 54.5 . 55.7 4. . .9 .4465 76. .9 70. .6 70.9 4.7 .88 5.4 .9580 88.9 . 8.5 .9 8. 6.76 5.4 6.5 5.4
00 4. .6 07. . 07.9 9.8 9.00 8.77 9.45 9.7 4.0 .7 .6 .5 .4 .6 . .850 68. 4.5 59. 4.0 60. 8. 9.9 6. 0.00 9. 6. 06.5 4.5 0. . .5 .8 4.750 7.0 6. 60.4 5.0 6.0 4.4 5. .0 54.00 .9 7. 09.7 5.6 .7 55.5 75. 44.0 76.850 55.6 8.0 9.6 5.6 44.4 68.6 90.5 48. 9.400 406.4 8.8 88.8 6. 9.8 86. 8.7 6. .7500 508.0 .0 486.0 6. 495.4 5 85.4 77.9 9.7600 60.0 .5 585.0 6. 597.4 84 68.6 9.8 80.
* above nominal diameter DN identical to DIN 448 ** above nominal diameter DN 5 identical to DIN 458
Table 3: Approximate average roughness height k (absolute rough-
ness) or pipes
Head Loss in Straight Pipes Dimensions and Weights o Steel Pipes
7/30/2019 Selecting Centrifugal Pumps Data
21/92
7/30/2019 Selecting Centrifugal Pumps Data
22/92
3
Fig. 13: Schematic representation o the valve designs listed in
Table 5
4 5
6 7 8 9 0
4 5
6 7 8 9
Head Loss in Straight Pipes Valves and Fittings
The head losses HL in plastic
(or example PE or PVC) pipes
or smooth drawn metal pip-
ing are very low thanks to the
smooth pipe surace. They are
shown in Fig. and valid orwater at 0 C. At other tem-
peratures, the loss or plastic
pipes must be multiplied with
a temperature correction actor
indicated in Fig. to account
or their large thermal expan-
sion. For sewage or other un-
treated water, an additional
00% head loss should betaken into consideration or po-tential deposits (see section .6).
3.2.1.2.2Head Loss in Valves andFittings
The head loss in valves and t-
tings is given by
HL = v/g (15)
where
Loss coecientv Flow velocity in a charac-
teristic cross-section A (or
example the fange) in m/s
g Gravitational constant
9.8 m/s
Tables 5 to 8 and Figures to5 contain inormation about
the various loss coecients orvalves and ttings or operation
with cold water.
The minimum and maximum
in Table 5 bracket the values
given in the most important
technical literature and apply to
valves which have a steady ap-
proach fow and which are ully
open. The losses attributable to
straightening o the fow dis-
turbances over a length o pipe
equivalent to x DN down-
stream o the valve are included
in the value in accordancewith VDI/VDE 7 guidelines.
Depending on the inlet and
exit fow conditions, the valve
models used and the develop-
ment objectives (i.e. inexpensivevs. energy-saving valves), the
loss values can vary dramatically.
7/30/2019 Selecting Centrifugal Pumps Data
23/92
7/30/2019 Selecting Centrifugal Pumps Data
24/92
4
/iZ>ivi}iciL`Li`Li`]LLii`Liv>V`V>i`L>iiiV>i`LiVL>viL>i`
/>Li\VivvViZvv}
L>viLi`-iL\
>\iii>}`ii Zzi>LiLi` Zzni>i`Vi>LiLi` ZziiVi>LiLi`Zz{
iiv}\
ii`}i-> Zz x vDrxc c {xc
>vii` Zz x xx x Zz n
n{
D
V>}iiv}\
Zz`i>v>>`i>ii}v>}i>> >iviV LiiViVZz v>ii}>iV`L]vi>ii`>i `i>v>iv}>>i]iV
i`i>}i
A xc c {xc c c
-v>Vi -v>Vi -v>Vi -v>Vi -v>Vi
} } } } }
Zv ,r { x x x x Zv ,r` q q { { { x
Zv ,r` q q {
Zv ,x` q q n
LivVVvii>i` q q q q q q q
Z q q q q x q q x q
,`iL
7i`i`Li`
,A
A
`
Table 6: Loss coecients in elbows and bends
3 Head Loss in Valves and Fittings Loss Coecients or Fittings
Note: For the branch ttings
in Table 7 and the adapters o
Table 8, one must dierentiate
between the irreversible pressure
loss (reduction in pressure)
pL = v/ (16)
where
pL Pressure loss in Pa
Loss coecient Density in kg/m
v Flow velocity in m/s
and the reversible pressure
change o the rictionless fow
according to Bernoullis equa-
tion (see ...):
pp = (vv)/ (17)
For accelerated fows (or ex-
ample a reduction in the pipe
diameter), pp is alwaysnegative, or decelerated fows
(e.g. pipe expansion) it is always
positive. When calculating the
net pressure change as the arith-
metic sum o pL and pp, thepressure losses rom Eq. 6 are
always to be subtracted.
Oten the so-called kv value is
used instead o the loss coe-
7/30/2019 Selecting Centrifugal Pumps Data
25/92
5
A
A
2+
2+
,OSSC
OEFFICIENTZ
%LBOWRADIUS2+$UCTWIDTHA
2ADIUSONINNERCORNER7ITHTURNING
VANECASCADE
2ADIUSONOUTERCORNER
3
Flow meters:
Short Venturi tube = 0
is reerred to the velocity v at diameter D.
Diameter ratio d/D = 0.0 0.40 0.50 0.60 0.70 0.80
Area ratio m = (d/D) = 0.09 0.6 0.5 0.6 0.49 0.64
Short Venturi tube 6 0.7 0. 0.Standard orice 00 85 0 4.5
Water meters (volume meters) 0For domestic water meters, a max. pressure drop o bar is specied or the
rated load. In practice, the actual pressure loss is seldom higher.
Branch ttings (o equal diameter)
Note:
The loss coecients a or the branched-o fow Qa or d or the main fowQd = Q Qa reer to the velocity o the total fow Q in the branch. On the
basis o this denition, a or d may have negative values; in this case, theyare indicative o a pressure gain instead o a pressure loss. This is not to be
conused with the reversible pressure changes according to Bernoullis equa-
tion (see notes to Tables 7 and 8).Qa/Q = 0. 0.4 0.6 0.8
a 0.4 0.08 0.47 0.7 0.9 d 0.7 0.0 0.4 0.5
a 0.88 0.89 0.95 .0 .8 d 0.08 0.05 0.07 0.
a 0.8 0 0. 0.7 0.7 d 0.7 0.9 0.09 0.7
a 0.68 0.50 0.8 0.5 0.48 d 0.06 0.04 0.07 0.0
Table 8: Loss coecients or adapters
Expansion Contraction
Type I II III IV
Type d/D 0.5 0.6 0.7 0.8 0.9
I 0.56 0.4 0.6 0. 0.04 = 8 0.07 0.05 0.0 0.0 0.0II or = 5 0.5 0. 0.07 0.0 0.0 = 0 0. 0.7 0. 0.05 0.0III 4.80 .0 0.88 0.4 0.IV or 0 < < 40 0. 0.0 0.05 0.0 0.0
Ddv Dd
v D dv D d
v
Fig. 14: Eect o rounding o
the inner and outer side o el-
bows in square ducts on the loss
coecient
Head Loss in Valves and Fittings Loss Coecients or Fittings and Flow Meters
D d D D
Standard oriice
Dv
dv
Qd
Qd
Qd
Qa
Q
Qa
Q
Qd
Qa
Q45
45
Qa
Q
cient when calculating thepressure loss or water in valves:
pL = (Q / kv) . /000 (18)
where
Q Volume rate o fow in m/h (!)
Density o water in kg/m
pL Pressure loss in bar (!)
The kv value is the fow rate in
m/h which would result rom a
pressure drop o bar through
the valve or cold water. It cor-
relates with the pressure loss pL
in bar with the fow rate Q in
m/h. The notation kvs is usedor a ully open valve.
Conversion or cold water:
6 d4/kv (19)
where
d Reerence (nominal) diameter
o the valve in cm (!)
Table 7 (continued)
7/30/2019 Selecting Centrifugal Pumps Data
26/92
6
3YSTEMH
EAD(SYS
3YSTEMHEADCHARACTERISTIC( SYS$YNAMICCOMPONENT(,
VAnVE
G
3TATICCOMPONENT(GEOPAnPEqG
Fig. 16: System characteristic curve Hsys with static and dynamic
components
3
3.2.2System Characteristic Curve
The system characteristic curve
plots the head Hsys required by
the system as a unction o the
fow rate Q. It is composed o
the so-called static and
dynamic components (see
Fig. 6).
The static component consists
o the geodetic head Hgeo andthe pressure head dierence
(pa-pe)/(g) between the inlet
J
J
J
V V
Y
V
10
A
,OSS
COEFFICIENTZ
2ELATIVEOPENINGANGLEJnJJ Degree of opening y/a or relative lift y/DN
Fig. 15:
Loss coecients
o butterfyvalves, globe
valves and gate
valves as aunction o the
opening angle
or degree o
opening (The
numbers desig-
nate the types
illustrated in
Fig. 13)
Head Loss in Valves System Characteristic Curve
One must be careul to distinguishbetween this use o static anddynamic components and the pre-cisely dened static head and dy-namic head used in fuid dynamics,since the dynamic component othe system head curve consists o bothstatic head (i.e. pressure losses)and dynamic head (i.e. velocity or
kinetic energy head).
7/30/2019 Selecting Centrifugal Pumps Data
27/92
7
1M
H
1LS
(
M
n
n
n
n
n n n n n
n
n n
n
n
n n n
n n
n
n n n
nn
n
n
3
and outlet tanks, which are in-
dependent o the fow rate. The
pressure head dierence is zero
when both tanks are open to the
atmosphere.
The dynamic component con-
sists o the head loss HL, which
increases as the square o the
fow rate Q (see section ...),
and o the change in velocity
head (va-ve)/g between theinlet and outlet cross-sections o
the system. Two points are su-
cient to calculate this parabola,
one at Q = 0 and one at any
point Q > 0.
For pipe systems connected
one ater the other (series con-
nection) the individual system
curves Hsys, Hsys etc. are
plotted as unctions o Q, and
Fig. 17: Selection chart or a volute casing pump series or n = 2900 rpm
(First number = nominal diameter o the discharge nozzle, second number = nominal impeller diameter)
the heads or each fow rate are
added to obtain the total system
curve Hsys = (Q).
For branched piping systems the
system curves Hsys, Hsys, etc.
o the individual branches be-
tween the fow dividers are each
calculated as unctions o Q.
The fow rates Q, Q, etc. o
all branches in parallel or each
given head Hsys are then addedto determine the total system
curve Hsys = (Q) or all the
branches together. The sections
beore and ater the fow
dividers must be added as or a
series connection.
System Characteristic Curve Selection Chart
7/30/2019 Selecting Centrifugal Pumps Data
28/92
8
100
50
40
30
20
10
61 2
0.3 0.4 0.5 1 2
3 4 5 10 20Q m3/h
Q l/s
3
10987
65
4
3
2
987
6
5
4
3
2
76
5
3
10
4
2
3
4
2
Pump size 1 Pump size 2 Pump size 3 Pump size 4
H
m
3 4 5
,S
MH
&LOWRATE
MH
K7
(EAD
M
M
.03(
0OWER
MM)MPELLER
H
3
3.3Pump Selection
3.3.1Hydraulic Aspects
The data required or selecting
a pump size, i.e. the fow rate Q
and the head H o the desired
operating point are assumed
to be known rom the system
characteristic curve; the electric
mains requency is also given.
With these values it is possible
to choose the pump size, the
speed o rotation and, i neces-
sary, the number o stages, rom
the selection chart in the salesliterature (see Figs. 7 and 9).
Further details o the chosen
pump such as the eciency ,the input power P, the required
NPSHr (see section .5.4) and
the reduced impeller diameter
Dr can then be determined rom
Fig. 19: Selection chart or a multistage pump series or n = 2900 rpm
Fig. 18: Complete characteristics
o a centriugal pump
Hydraulic Aspects o Pump Selection
7/30/2019 Selecting Centrifugal Pumps Data
29/92
9
3
the individual characteristic
curve (or example see Fig. 8).
I there are no specic reasons
or doing otherwise, a pump
should be selected so that the
operating point lies near its
best eciency point Qopt (=
fow rate at which eciency is
highest, BEP). The limits Qmin
and Qmax (or example due to
vibration behaviour, noise emis-
sion as well as radial and axial
orces) are given in the product
literature or can be determined
by inquiry [].
To conclude the selection, theNPSH conditions must be
checked as described in section
.5.
A multistage pump is chosen us-
ing the same general procedure;
its selection chart shows the
number o stages in addition to
the pump size (Fig. 9).
For pumps operating in series
(one ater the other) the devel-oped heads H, H, etc. o the
individual characteristic curves
must be added (ater subtracting
any head losses which occur be-
tween them) to obtain the total
characteristic H = (Q).
For pumps operating in parallel,
the individual characteristics H,
H, etc. = (Q) are rst reduced
by the head losses occurring up
to the common node (head loss
HL calculation according to sec-
tion ...) and plotted versus
Q. Then the fow rates Q o
the reduced characteristics are
added to produce the eective
characteristic curve o a vir-
tual pump. This characteristic
interacts with the system curve
Hsys or the rest o the system
through the common node.
3.3.2Mechanical Aspects
When selecting a pump the me-
chanical aspects require atten-
tion in addition to the hydrau-
lics. Several examples are:
the eects o the maximum
discharge pressure and tem-
perature o the fuid pumpedon the operating limits,
the choice o the best shat
sealing method and cooling
requirements,
the vibration and noise emis-
sions,
the choice o the materials o
construction to avoid corro-
sion and wear while keeping
in mind their strength andtemperature limits.
These and other similar re-
quirements are oten specic to
certain industries and even to
individual customers and must
be addressed using the product
literature [] or by consulting
the design department.
3.3.3Motor Selection
3.3.3.1Determining Motor Power
Operation o a centriugal pump
is subject to deviations rom
rated speed and fuctuations
in the fow volume handled,
and, consequently, changes in
the operating point (see section
.4.). In particular i steep
power curves are involved (see
Figs. 5 and 6), this may result
in a higher required pump input
power P than originally speci-
ed. For practical purposes, a
saety allowance is thereore
added when the appropriate
motor size is selected. Saety
allowances may be speciedby the purchaser, or laid down
in technical codes, see Fig. 0.
The saety allowances stipulated
by individual associations are
shown in the relevant type series
literature [] or the customers
specication.
When energy-saving control
methods are used (e. g., speed
control systems), the maximum
Fig. 20: Drive power as a unction o rated pump input power at the
operationg point
Example as per ISO 9905, 5199 and 9908 (Class I, II and III)
K7
Drivepowerrelativetopumpinpu
tpowerunderrated
conditionsin%
0UMPINPUTPOWERUNDERRATEDCONDITIONS
Hydraulic Aspects o Pump Selection Motor Selection
7/30/2019 Selecting Centrifugal Pumps Data
30/92
0
3
power peaks which may pos-
sibly occur must be taken into
account.
I a pump is selected or a
product with a density lower
than that o water, the motor
power required may have to be
determined on the basis o the
density o water (or example,
during the perormance test or
acceptance test in the test bay).
Typical eciencies and poweractors cos o standardized IP54 motors at 50 Hz are shown
in Fig. , and the curves o e-
ciency and power actorcos as a unction o relativemotor load P/PN in Fig. .
Table 9 lists types o enclosure
that provide protection o elec-
tric motors against ingress o
oreign objects or water, and
o persons against accidental
contact.
The specic heat build-up in
both electric motors and fexi-
ble couplings during start-up
as well as the risk o premature
contactor wear limit the requen-
cy o starts. Reerence values
or the maximum permissible
number o starts Z are given in
table 0, unless otherwise speci-
ed.
Submersible motor pumps (Figs.
j to m) are ready-assembled
pump units whose motors need
not be selected individually [7].
Their electrical characteristics
are given in the type series
literature. The motor is lled
with air and can be operated
submerged in the product han-
dled thanks to a in most cases
double-acting shat seal with a
paran oil barrier.
Table 9: Types o enclosure or electric motors to EN 60 59 andDIN/VDE 050, Part 5
The type o protective enclosure is indicated by the IP code as ollows:Code letters (International Protection) IPFirst digit (0 to 6 or X i not applicable) XSecond digit (0 to 8 or X i not applicable) X
Alternatively letters A, B, C, D and H, M, S, W or special purposes only.Key to Protection o electrical Protection o persons againstdigits: equipment against ingress o accidental contact by
solid objects
First 0 (not protected) (not protected)digit > 50 mm in dia. back o the hand
> .5 mm in dia. nger > .5 mm in dia. tool4 > .0 mm in dia. wire5 protected against dust (limited wire
ingress permitted, no harmuldeposits)
6 totally protected against dust wire
Protection against ingress o water with harmul consequences
Second 0 (not protected)digit vertical dripwater
dripwater up to 5 rom the vertical sprays (60 rom the vertical)4 sprays (all directions)5 low-pressure jets o water6 strong jets o water (heavy sea)7 temporary fooding8 permanent fooding
K7
H
COSJ
2ATEDPOWER0.
%FFICIENCYH
0OWERFACTORCOSJ
POLES
POLES
Fig. 21: Typical eciencies and power actors cos o standard-ized motors, IP 54 enclosure, at 50 Hz as a unction o motor
power PN
Table 0: Permissible requency o starts Z per hour or electric motors
Motor installation Dry Wet (submersible motors)
Motors up to 4 kW 5 0Motors up to 7.5 kW 5 5Motors up to kW 5Motors up to 0 kW 0Motors above 0 kW 0 0
Motor Selection
7/30/2019 Selecting Centrifugal Pumps Data
31/92
3
K7
H
K7
K7
K7]
COSJ
%FFICIENCYH
0OWERFACTORCOSJ
2ATEDPOWER00.
POLESPOLES
Fig. 22: Curve o eciency and power actor cos o standardizedIP 54 motors plotted over relative motor power P/PN
Submersible borehole pumps,
which are mostly used or ex-
tracting water rom wells, are
another type o ready-assembled
units whose motors need not be
selected individually (Fig. p).
On these pumps, the rotor and
the windings are immersed in
water [7]. Their electrical char-acteristics and permissible re-
quency o starts are indicated in
the type series literature [].
3.3.3.2Motors or Seal-less Pumps
Seal-less pumps are requently
used or handling aggressive,
toxic, highly volatile or valu-
able fuids in the chemical and
petrochemical industries. They
include magnetic-drive pumps
(Fig. ) and canned motor
pumps (Figs. n and o). A
mag-drive pump is driven by a
primary magnetic eld rotating
outside its fameproo enclosure
and running in synchronization
with the secondary magnets in-
side the enclosure [].
The primary component in
turn is coupled to a commercial
dry driver. The impeller o a
canned motor pump is mounted
directly on the motor shat, so
that the rotor is surrounded by
the fuid pumped. It is separated
rom the stator windings by the
can [7].
Seal-less pump sets are generally
selected with the help o compu-
terized selection programs, tak-
ing into account the ollowing
considerations:
The rotor is surrounded by
the fuid pumped, whose kine-
matic viscosity (see section4.) must be known, as it
infuences riction losses andthereore the motor power
required.
Metal cans or containment
shrouds (or example made
o .460) cause eddy current
losses, resulting in an increase
in the motor power required.
Non-metal shrouds in mag-
drive pumps do not have this
eect.
The vapour pressure o the
fuid pumped must be known,
so as to avoid bearing damage
caused by dry running when
the fuid has evaporated. It is
advisable to install monitoringequipment signalling dry run-
ning conditions, i any.
Data on specic fuid proper-
ties such as its solids content
and any tendency to solidiy
or polymerize or orm incrus-
tations and deposits, need to
be available at the time o se-
lection.
3.3.3.3Starting Characteristics
The pump torque Tp transmit-
ted by the shat coupling is
directly related to the power P
and speed o rotation n. Dur-
ing pump start-up, this torque
ollows an almost parabolical
curve as a unction o the speed
o rotation [0], as shown inFig. . The torque provided
by the asynchronous motor
must, however, be higher so as
to enable the rotor to run up to
duty speed. Together with the
voltage, this motor torque has a
direct eect on the motors cur-
rent input, and the latter in turn
on heat build-up in the motor
windings. The aim, thereore, is
to prevent unwanted heat build-up in the motor by limiting the
run-up period and/or current
inrush [] (see also Table ).
Motors or Seal-less Pumps Starting Characteristics
7/30/2019 Selecting Centrifugal Pumps Data
32/92
Table : Starting methods or asynchronous motors
Starting Type o Current Run-up Heat build- Mechani- Hydraulic Cost Recommended Commentsmethod equipment input time up in motor cal loading loading relation motor designs
(mains load) duringstart-up
D. o. l. Contactor 48 IN Approx. High Very high Very high All Mostly limited to(mecha- 0.55 s 4 kW by energynical) supply companies
Star- Contactor / o d. o. l. Approx. High Very high Very high .5 All; canned mo- Usually stipu-delta combi- values 0 s tors and sub- lated or motors
nation mersible motors >4 kW by(mecha- subject to a energy supplynical) major drop in companies
speed duringswitchover
Reduced Autotrans- 0.49 times Approx. High High High 55 All No currentlessvoltage ormer, the d. o. l. 0 s phase during
mostly values switchover70% tap- (gradually re-ping placed by sot
starters)Sot Sot starter Continuous- Approx. High Low Low 55 All Run-up and run-start (power ly variable; 00 s down continu-
electro- typically ously variablenics) IN via ramps or
each individualload appllication;no hydraulicsurges
Fre- Frequency IN 060 s Low Low Low Approx. All Too expensive toquency inverter 0 use solely or run-inverter (power up and run-down
electro- purposes; betternics) suited or open-
or closed-loopcontrol
3
In the case o d.o.l. starting
(where the ull mains voltage
is instantly applied to the mo-
tor once it is switched on), the
ull starting torque is instantly
available and the unit runs up
to its duty speed in a very short
period o time. For the motor
itsel, this is the most avour-
able starting method. But at up
to 4 8 times the rated current,
the starting current o the d.o.l.
method places a high load on
the electricity supply mains,
particularly i large motors are
involved, and may cause prob-
lematic voltage drops in electri-
cal equipment in their vicinity.
For motor operation on public
low-voltage grids (80 V), the
regulations laid down by the en-
ergy supply companies or d.o.l.
starting o motors o 5.5 kW
and above must be complied
with. I the grid is not suitable
or d.o.l starting, the motor can
be started up with reduced volt-
ages, using one o the ollowing
methods:
Star-delta starting is the most
requent, since most inexpen-
sive, way o reducing the start-
ing current. During normal
operation, the motor runs in
delta, so that the ull mains
voltage (or example 400 V) is
applied to the motor windings.
For start-up, however, the wind-
ings are star-connected, so that
the voltage at the windings is
reduced by a actor o 0.58 rela-
tive to the mains voltage. This
reduces the starting current and
torque to one third o the values
o d.o.l. starting, resulting in a
longer start-up process.
The motor runs up in star con-
nection beyond pull-out torque
up to the maximum speed o
rotation at point B in Fig. .
Then, switchover to delta is e-
ected and the motor continues
to accelerate up to rated speed.
During the switchover period o
approx. 0. s, the current sup-
ply to the motor is interrupted
Starting Methods
7/30/2019 Selecting Centrifugal Pumps Data
33/92
Fig. 23: Starting curve or current I and torque T o squirrel-cage
motors in star-delta connection
( = star connection; = delta connection; P = pump)
3
"gg
$g
$gg
$
)
)
4
4
40
"g
"
OFNSYNCHR
#URRENT)
4ORQUE4
-OTORSPEEDN
and the speed drops. On pump
sets with a low moment o in-
ertia (canned motors and sub-
mersible motors), this speed re-
duction may be so pronounced
that switchover to delta mayresult in almost the ull starting
current being applied ater all,
same as with d.o.l. starting.
An autotransormer also serves
to reduce voltage at the motor
windings and unlike star-delta
starting allows selection o
the actual voltage reduction. A
70% tapping o the transormer,or instance, will bring down
the start-up torque and current
supplied by the mains to 49%
o the values or d.o.l. starting.
The act that current supply is
never interrupted is another ad-
vantage o autotransormers.
Sot starters are used or elec-
tronic continuous variation o
the voltage at the motor wind-
ings in accordance with the
dimmer principle. This means
that the start-up time and start-
ing current can be reely selected
within the motors permissible
operating limits (heat losses due
to slip!). Special constraints re-
garding the requency o starts
(contrary to Table 0) have tobe heeded [].
Frequency inverters (usually or
open- or closed-loop control)
provide a sot starting option
without the need or any addi-
tional equipment. For this pur-
pose, the output requency and
voltage o the requency inverter
(see section .4.) are increased
continuously rom a minimum
value to the required value,
without exceeding the motors
rated current.
Starting Methods
7/30/2019 Selecting Centrifugal Pumps Data
34/92
4
3
3.4Pump Perormance andControl [4], [6], [8]
3.4.1Operating Point
The operating point o a centri-ugal pump, also called its duty
point, is given by the intersec-
tion o the pump characteristic
curve (see section ..6) with
the system characteristic curve
(see section ..). The fow
rate Q and the developed head
H are both determined by the
intersection. To change the op-
erating point either the system
curve or the pump curve must
be changed.
A system characteristic curve
or pumping water can only be
changed
by changing the fow resist-
ance (or example, by chang-
ing the setting o a throttling
device, by installing an orice
or a bypass line, by rebuildingthe piping or by its becoming
incrusted) and/or
by changing the static head
component (or example, with
a dierent water level or tank
pressure).
A pump characteristic curve can
be changed
by changing the speed o rota-
tion (see section .4.),
by starting or stopping pumps
operated in series or parallel
(see sections .4.4 or .4.5),
or pumps with radial impel-
lers, by changing the impel-
lers outside diameter (see sec-
tion .4.6),
or pumps with mixed fow
impellers, by installing or
changing the setting o in-
stalled pre-swirl control
equipment (see section .4.8),
or axial fow (propeller)
pumps, by changing the blade
pitch setting (see section
.4.9).
Please note: the eect o these
measures or changing the char-
acteristic curve can only be pre-
dicted or non-cavitating opera-
tion (see section .5).
3.4.2Flow Control by Throttling
Changing the fow rate Q by
operating a throttle valve is the
simplest fow control method
not only or a single adjustment
o the fow rate but also or
its continuous control, since it
requires the least investment.
But it is also the most energy
wasting method, since the fow
energy is converted irreversibly
to heat.
Fig. 4 illustrates this process:
by intentionally increasing the
system resistance (or exampleby throttling a valve on the
1;=
1;=
(;=
"
"
0
0
0;=
0UMPCHARAC
TERISTICCURVE
4HROTTLING
3URPLUSHEAD
3YSTEMHEAD
REQUIREMENT
3YSTEMCURVE( SYS
3YSTEMCURVE(SYS
0OWERSAVED
Fig. 24: Change o the operating point and power saved by
throttling a pump whose power curve has a positive slope
Pump Perormance Operating Point Throttling
7/30/2019 Selecting Centrifugal Pumps Data
35/92
5
3
pump discharge side) the origi-nal system curve Hsys becomes
steeper and transorms into
Hsys. For a constant pump
speed, the operating point B on
the pump characteristic moves
to B at a lower fow rate. The
pump develops a larger head
than would be necessary or
the system; this surplus head is
eliminated in the throttle valve.
The hydraulic energy is irrevers-
ibly converted into heat which
is transported away by the fow.
This loss is acceptable when
the control range is small or
when such control is only sel-
dom needed. The power saved
is shown in the lower part o
the gure; it is only moderate
compared with the large surplus
head produced.
D"L
D
!REARATIOD"LD
4HROTTLINGC
OEFFICIENTF
Fig. 25: Orice plate and its throttling coecient
The same is principally trueo the installation o a xed,
sharp-edged orifce plate in the
discharge piping, which can be
justied or low power or short
operating periods. The neces-
sary hole diameter dBl o the
orice is calculated rom the
head dierence to be throttled
H, using the ollowing equa-tion:
dBl = Q/ g H (20)
where
dBl Hole diameter o the orice
in mm
Throttling or pressure drop
coecient acc. to Fig. 5
Q Flow rate in m/h
g Gravitational constant
9.8 m/s
H Head dierence to bethrottled in m
Since the area ratio (dBl/d)
must be estimated in advance,
an iterative calculation is neces-
sary (plotting the calculated vs.
the estimated diameter dBl is
recommended so that ater two
iterations the correct value can
be directly interpolated, see
example calculation 8.0).
3.4.3
Variable Speed Flow Control
At various speeds o rotation n,
a centriugal pump has dier-
ent characteristic curves, which
are related to each other by the
anity laws. I the characteris-
tics H and P as unctions o Q
are known or a speed n, then
all points on the characteristic
curve or n can be calculated
by the ollowing equations:
Q = Q . n/n (21)
H = H (n/n) (22)
P = P (n/n) (23)
Eq. () is valid only as long
as the eciency does not de-crease as the speed n is reduced.
With a change o speed, the op-
erating point is also shited (see
section .4.). Fig. 6 shows the
H/Q curves or several speeds o
rotation; each curve has an in-
tersection with the system char-
acteristic Hsys. The operating
point B moves along this system
curve to smaller fow rates when
the speed o rotation is reduced.
Orice Plate Variable Speed
7/30/2019 Selecting Centrifugal Pumps Data
36/92
6
I the system curve is a parabola
through the origin as or Hsys
in the example, the developed
head H according to Eq. () is
reduced to one ourth its value
and the required driving power
in Eq. () to one eighth itsvalue when the speed is halved.
The lower part o Fig. 6 shows
the extent o the savings Pcompared with simple
throttling.
I the system curve is a parabola
with a large static head compo-
nent as or Hsys, it is possible
that the pump characteristic at
reduced speed has no intersec-
Fig. 26: Operation o a variable speed pump or dierent system
characteristic curves Hsys1 and Hsys2(Power savings P1 andP2 at hal load each compared with simplethrottling)
1;=
1;=
(;=
(!
(!
(!
0
0
(!
"
0;=
]
N
N
N
0
0
0
(EADREQUIRED
(!STAT
Powersaved
3
tion with it and hence, that no
operating point results; the low-
er speed range is then o no use
and could be eliminated. The
potential power savings Pat a given fow rate Q are less
than or the system curve Hsysas shown in the lower part o
the diagram [4]. The improve-
ment compared with throttling
decreases as the static head
component Hsys,stat increases
(i.e., or a lower dynamic head
component Hsys,dyn).
Variation o the speed usually
means varying the electrical
driving requency, which must
be considered when choosing
the motor. The expenditure or
variable speed drives is not low,
but it is amortized quickly or
pumps which are used oten and
which are requently requiredto run at reduced fows with
small static head component
Hsys,stat [8]. This is particularly
the case or pumps in heating
systems.
3.4.4Parallel Operation o Centri-ugal Pumps
Where one pump is unable todeliver the required fow Q at
the operating point, it is possi-
ble to have two or more pumps
working in parallel in the same
piping system, each with its
own non-return valve (Fig. 7).
Parallel operation o pumps is
easier when their shuto heads
H0 are all equal, which is the
case or identical pumps. I the
shuto heads H0 dier, the low-
est shuto head marks the point
on the common H/Q curve or
the minimum fow rate Qmin,
below which no parallel opera-
tion is possible, since the non-
return valve o the pump with
smaller shuto head will be held
shut by the other pump(s).
During parallel pumping it
must be kept in mind that aterstopping one o two identical
centriugal pumps (Fig. 7),
the fow rate Qsingle o the re-
maining pump does not all
to hal o Qparallel, but rather
increases to more than hal. The
remaining pump might then
immediately run at an operat-
ing point Bsingle above its design
point, which must be considered
Variable Speed Parallel Operation
7/30/2019 Selecting Centrifugal Pumps Data
37/92
7
3
when checking the NPSH values
(see section .5) and the drive
power (see section ..). The
reason or this behaviour is the
parabolic shape o the system
characteristic Hsys. For the samereason, the reverse procedure o
taking a second identical pump
on line does not double the fow
rate Qsingle o the pump that
was already running, but rather
increases the fow rate less than
that:
Qparallel
7/30/2019 Selecting Centrifugal Pumps Data
38/92
8
3
3.4.5
Series Operation
In series operation, the pumps
are connected one ater the
other so that the developed
heads can be added or a given
fow rate. This means that the
discharge pressure o the rst
pump is the inlet pressure or
the second pump, which must
be considered or the choice o
shat seal and or the strength
o the casing. For this reason
multistage pumps are usually
used or such applications (ex-
cept or the hydraulic transporto solids, see section 6). They
do not pose these shat sealing
problems.
3.4.6
Turning Down Impellers
I the fow rate or developed
head o a radial or mixed fow
centriugal pump are to be
reduced permanently, the out-
side diameter D o the impeller
should be reduced. The reduc-
tion should be limited to the
value or which the impeller
vanes still overlap when viewed
radially. The documentation o
the pump characteristics (Fig.
8) usually shows curves or
several diameters D (in mm).
Impellers made rom hard ma-terials, such as those used or
solids-handling pumps, or rom
stainless steel sheet metal, as
well as single vane impellers
(Fig. 4) and star or periph-
eral pump impellers cannot be
turned down. (The same is true
or under-ling as described in
section .4.7). For multistage
pumps, usually only the vanes
Dt
Dr
D1
but not the shrouds o the im-
pellers are cut back. It is some-
times possible to simply remove
the impeller and diuser o one
stage o a multistage pump and
replace them with a blind stage(two concentric cylindrical cas-
ings to guide the fow) instead
o cutting back the impeller
vanes. Impellers with a non-
cylindrical exit section are either
turned down or have only their
blades cut back as specied in
the characteristic curve litera-
ture (or example, as shown in
Fig. 9).
I the impeller diameter only
needs to be reduced slightly, a
rule o thumb can be applied.
An exact calculation cannot be
made, since the geometrical sim-
ilarity o the vane angle and exit
width are not preserved when
turning down the impeller. The
ollowing approximate relation-
ship exists between Q, H and
the impeller diameter D to beound (averaged, i required):
(Dt/Dr) Qt/Qr Ht/Hr (26)
where subscript t designates the
condition beore the reduction
Fig. 29: Contour or cutting
back the vanes o an impeller
with a mixed fow exit
o the impeller outer diameter
and index r the condition ater
the reduction. The required
(average) reduced diameter re-
sults as:
DrDt (Qr/Qt)Dt (Hr/Ht) (27)
The parameters needed to deter-
mine the reduced diameter can
be ound as shown in Fig. 0:
in the H/Q curve (linear scales
required!) a line is drawn con-
necting the origin (careul: some
scales do not start at zero!) and
the new operating point Br . The
extension o the line intersects
the characteristic curve or ull
diameter Dt at the point Bt. In
this way the values o Q and H
with the subscripts t and r can
be ound, which are used with
Eq. (7) to nd the desired re-
duced diameter Dr.
The ISO 9906 method is more
accurate, but also more involvedthrough the consideration o
the average diameter D o the
impeller leading edge (sub-
script ), valid or nq < 79 and
or a change o diameter < 5%,
as long as the vane angle and
the impeller width remain con-
stant. Thus using the nomen-
clature o Figs. 9 and 0:
Series Operation Impeller Diameter Reduction
7/30/2019 Selecting Centrifugal Pumps Data
39/92
9
3
"T
1T
"R
1R
(T
$T
(R
$R
usin
gEq
.28
using
Eq.26
Totaldevelopedhe
adH
Flow rate Q
Fig. 30:
Determination
o the reduced
impeller dia-
meter Dr
A solution is only possible when
D is known and when a para-
bola H ~ Q is drawn through
the reduced operating point Br
(with Hr and Qr), not a line as
n
(DrD)/(DtD) = Hr/Ht = (Qr/Qt) (28)
in Fig. 0, which intersects the
base H/Q curve or diameter Dt
at a dierent point Bt (with di-
erent Ht and Qt).
Fig. 31: Under-led vanes o a
radial impeller
Fig. 32: Characteristic curve set o a centriugal pump with pre-swirl
control equipment, nq 160
HHOPT
/PERATINGLIMIT
0RESWIRLCONTROLSETTING
2ELATIVEFLOWRATE11OPT
2ELATIVEDE
VELOPED
HEAD
((OPT
3.4.8Pre-Swirl Control o the Flow
For tubular casing pumps with
mixed fow impellers, the pump
characteristic can be infuenced
by changing the pre-rotation
in the impeller inlet fow. Such
pre-swirl control equipment is
oten tted to control the fow
rate. The various characteristic
curves are then shown in the
product literature labelled with
the control setting (Fig. ).
3.4.9
Flow Rate Control or Changeby Blade Pitch Adjustment
The characteristic curves o ax-
ial fow (propeller) pumps can be
altered by changing the setting
o the propeller blade pitch. The
setting can be xed and rmly
bolted or a device to change the
blade pitch during operation
can be used to control the fow
rate. The blade pitch angles are
3.4.7Under-ling o ImpellerVanes
A small, permanent increase o
the developed head at the best
eciency point (up to 4 6%)
can be achieved or radial im-
pellers by ling the back sides o
the backward-curved vanes, i.e.,
by sharpening the vanes on the
concave side, as shown in Fig.
. The shuto head does not
change. This method is suitable
or minor nal corrections.
Impeller Diameter Reduction Under-ling Pre-swirl Blade Pitch Adjustment
7/30/2019 Selecting Centrifugal Pumps Data
40/92
40
3
shown in the product literature
with their respective characteris-
tic curves (see Fig. ).
3.4.10Flow Control Using a Bypass
The system characteristic curve
can be made steeper by closing
a throttle valve, but it can also
be made fatter by opening a
bypass in the discharge piping
as shown in Fig. 4. The pump
operating point moves rom B
to a larger fow rate B. The
bypass fow rate is controlled
and can be ed back into theinlet tank without being used
directly. From the point o view
o saving energy, this type o
control only makes sense when
the power curve alls or in-
creasing pump fow rates (P >
P), which is the case or high
specic speeds (mixed and axial
fow propeller pumps).
For these types o pumps, con-trolling the fow by pre-swirl
control or by changing the blade
pitch is even more economical,
however. The expenditure or a
bypass and control valve is not
small [4]. This method is also
suitable or preventing pumps
rom operating at unacceptably
low fow rates (see operating
limits in Figs. 5 and 6c as well
as in Figs. and ).
HHOPT
/PERATINGLIMIT
"LADEPITCHSETTING
2ELATIVEFLOWRATE11OPT
2ELATIVEDEVELOPED
HEA
D
((OPT
1;=
1;=
(;=
"
"
0
0
0;=
-
"YPASSFLOWRATE5SEFULFLOWRATE
3URPLUSHEAD
(EADREQUIRED
BYTHESYSTEM
3YSTEMCURVE
WITHOUTBYPASS0UMP
CHARACTERISTIC
3YSTEMCURVE
WITHBYPASS
0OWERSAVED
Fig. 33: Characteristic curve set o an axial fow pump with blade
pitch adjustment, nq 200
Fig. 34: Characteristic curves and operating points o a pump with
a alling power curve and fow control using a bypass. (For a radial
fow pump the power curve would increase towards the right and
this type o control would cause an increase in power input, see
Fig. 5).
Blade Pitch Adjustment Bypass
7/30/2019 Selecting Centrifugal Pumps Data
41/92
4
3
3.5Suction and Inlet Conditions[3]
NPSH = Net Positive Suction
Head
3.5.1
The NPSH Value o theSystem: NPSHa
The NPSHa value is the dier-
ence between the total pressure
in the centre o the pump inlet
and the vapour pressure pv,
expressed as a head dierence
in m. It is in certain respects a
measure o the probability o
vaporization at that location
and it is determined only by
the operating data o the sys-
tem and the type o fuid. The
vapour pressure o water and
other liquids are shown in Table
and in Fig. 5 as a unction
o the temperature.
Carbon
disulph
ide
!CETON
E"E
NZOL
N"UT
ANE
%TH
ANE
%TH
ANOL
$IETH
YLETH
ER
0ROPANE
I"
UTA
NE
"ENZOL
0HE
NOL
4OLU
OL
!NILIN
E
-ETH
ANOL
!CETO
NE
!CETICACID&
ORMIC
ACID
'LY
CERIN
#ARB
ON
DIS
ULPHID
E
!MM
ONI
A
3ULP
HURDIOXI
DE
#ARBO
NTETRACHL
ORID
E
"ENZOL
n #
BAR
4EMPERATURET
6APOURPRESSURE
P6
Fig. 35: Vapour pressure pv o various fuids as a unction o the
temperature t (or an enlarged view see page 84)
Suction and Inlet Conditions NPSH Available
7/30/2019 Selecting Centrifugal Pumps Data
42/92
4
Table 12: Vapour pressure pv, density and kinematic viscosity o water at saturation conditions as a
unction o the temperature t
3 NPSH Available Data or Water
t pv C bar kg/m mm/s
0 0.006 999.8 .79 0.00656 999.9 0.00705 999.9 0.00757 000.04 0.008 000.05 0.0087 000.06 0.0095 999.97 0.000 999.98 0.007 999.89 0.046 999.7
0 0.07 999.6 .07
0.0 999.5 0.040 999.4 0.0496 999.4 0.0597 999.5 0.070 999.06 0.086 998.8
7 0.096 998.78 0.006 998.59 0.096 998.40 0.07 998. .004
0.0485 997.9 0.064 997.7 0.0808 997.54 0.098 997.5 0.067 997.06 0.060 996.77 0.0564 996.48 0.0779 996.
9 0.04004 995.80 0.044 995.6 0.80
0.0449 995.
0.0475 994.9 0.0509 994.64 0.058 994.5 0.056 99.96 0.05940 99.57 0.0674 99.8 0.0664 99.99 0.0699 99.640 0.0775 99. 0.658
4 0.07777 99.84 0.0898 99.44 0.0869 99.044 0.0900 990.645 0.0958 990.46 0.0085 989.8
47 0.06 989.48 0.6 988.949 0.76 988.550 0.5 988.0 0.55
5 0.960 987.75 0.6 987.5 0.49 986.754 0.500 986.55 0.574 985.756 0.6509 985.57 0.7 984.758 0.846 984.59 0.905 98.760 0.990 98. 0.474
t pv C bar kg/m mm/s
6 0.086 98.66 0.84 98.6 0.85 98.664 0.9 98.65 0.50 980.566 0.64 980.067 0.7 979.468 0.856 978.869 0.98 978.70 0.6 977.7 0.4
7 0.5 977.7 0.96 976.67 0.54 976.074 0.696 975.475 0.855 974.876 0.409 974.77 0.489 97.7
78 0.465 97.079 0.4547 97.580 0.476 97.8 0.65
8 0.49 97.8 0.5 970.68 0.54 969.984 0.5557 969.485 0.5780 968.786 0.600 968.87 0.649 967.488 0.6495 966.789 0.6749 966.090 0.70 965. 0.6
9 0.78 964.79 0.756 964.09 0.7849 96.94 0.846 96.695 0.845 96.996 0.8769 96.97 0.9095 960.498 0.940 959.899 0.9776 959.0
00 .0 958. 0.95
0 .0878 956.804 .668 955.506 .504 954.008 .90 95.60 .47 95.0
.56 949.6
4 .66 948.06 .7465 946.48 .868 944.80 .9854 94. 0.460
.44 94.54 .50 99.86 .9 98.8 .544 96.50 .70 94.8
.8668 9.4 .040 9.46 .4 99.68 .47 97.940 .64 96. 0.60
t pv C bar kg/m mm/s
45 4.55 9.750 4.760 96.9
55 5.4 9.60 6.80 907.4 0.890
65 7.008 90.470 7.90 897.
75 8.95 89.80 0.07 886.9 0.697
85 .4 88.490 .55 876.0
95 .989 870.00 5.550 864.7 0.579
05 7.45 858.70 9.080 85.8
5 .06 846.60 .0 840. 0.488
5 5.504 84.00 7.979 87.
5 0.65 80.640 .480 8.6 0.40