Selecting Centrifugal Pumps Data

Embed Size (px)

Citation preview

  • 7/30/2019 Selecting Centrifugal Pumps Data

    1/92

    Technical inormation

    Selecting Centriugal Pumps

  • 7/30/2019 Selecting Centrifugal Pumps Data

    2/92

  • 7/30/2019 Selecting Centrifugal Pumps Data

    3/92

    Copyright by

    KSB Aktiengesellschat

    Published by:

    KSB Aktiengesellschat,

    Communications (V5),

    67225 Frankenthal / Germany

    All rights reserved. No part o

    this publication may be used,

    reproduced, stored in or intro-

    duced in any kind o retrieval

    system or transmitted, in any

    orm or by any means (electro-

    nic, mechanical, photocopying,

    recording or otherwise) without

    the prior written permission o

    the publisher.

    4th completely revised and ex-

    panded edition 005

    Layout, drawings and

    composition:

    KSB Aktiengesellschat,

    Media Production V5

    ISBN -00-0784-4

  • 7/30/2019 Selecting Centrifugal Pumps Data

    4/92

    4

    Contents

    1 Nomenclature ..................................................................6

    2 Pump Types ................................................................89

    3 Selection or Pumping Water..........................................0

    3.1 Pump Data...............................................................................0

    .. Pump Flow Rate ......................................................................0

    .. Developed Head and Developed Pressure o the Pump .............0.. Eciency and Input Power ......................................................0

    ..4 Speed o Rotation ....................................................................

    ..5 Specic Speed and Impeller Type ..............................................

    ..6 Pump Characteristic Curves .....................................................

    3.2 System Data .............................................................................6

    .. System Head ...........................................................................6

    ... Bernoullis Equation .................................................................6

    ... Pressure Loss Due to Flow Resistances .....................................8

    .... Head Loss in Straight Pipes ......................................................8

    .... Head Loss in Valves and Fittings ..............................................

    .. System Characteristic Curve .....................................................6

    3.3 Pump Selection.........................................................................8

    .. Hydraulic Aspects ....................................................................8

    .. Mechanical Aspects ..................................................................9

    .. Motor Selection .......................................................................9

    ... Determining Motor Power .......................................................9

    ... Motors or Seal-less Pumps ......................................................

    ... Starting Characteristics ............................................................

    3.4 Pump Perormance and Control...............................................4

    .4. Operating Point .......................................................................4

    .4. Flow Control by Throttling ......................................................4

    .4. Variable Speed Flow Contol .....................................................5

    .4.4 Parallel Operation o Centriugal Pumps ..................................6.4.5 Series Operation .......................................................................8

    .4.6 Turning Down Impellers ..........................................................8

    .4.7 Under-ling o Impeller Vanes ..................................................9

    .4.8 Pre-swirl Control o the Flow ...................................................9

    .4.9 Flow Rate Control or Change by Blade Pitch Adjustment ........9

    .4.0 Flow Control Using a Bypass ...................................................40

    3.5 Suction and Inlet Conditions....................................................4

    .5. The NPSH Value o the System: NPSHa ..................................4

    .5.. NPSHa or Suction Lit Operation ...........................................4

    .5.. NPSHa or Suction Head Operation .........................................44

    .5. The NPSH Value o the Pump: NPSHr .....................................44

    .5. Corrective Measures ................................................................45

    3.6 Eect o Entrained Solids .........................................................47

    4 Special Issues when Pumping Viscous Fluids ..................48

    4.1 The Shear Curve ......................................................................48

    4.2 Newtonian Fluids .....................................................................50

    4.. Infuence on the Pump Characteristics ......................................50

    4.. Infuence on the System Characteristics ....................................54

    4.3 Non-Newtonian Fluids ............................................................54

    4.. Infuence on the Pump Characteristics ......................................54

    4.. Infuence on the System Characteristics ....................................55

    Table o contents

  • 7/30/2019 Selecting Centrifugal Pumps Data

    5/92

    5

    5 Special Issues when Pumping Gas-laden Fluids ..............56

    6 Special Issues When Pumping Solids-laden Fluids ..........57

    6. Settling Speed ...........................................................................57

    6. Infuence on the Pump Characteristics ......................................58

    6. Infuence on the System Characteristics ....................................596.4 Operating Perormance ............................................................59

    6.5 Stringy, Fibrous Solids ..............................................................59

    7 The Periphery ................................................................6

    7. Pump Installation Arrangements ..............................................6

    7. Pump Intake Structures ............................................................6

    7.. Pump Sump ..............................................................................6

    7.. Suction Piping ..........................................................................6

    7.. Intake Structures or Tubular Casing Pumps ............................64

    7..4 Priming Devices .......................................................................65

    7. Arrangement o Measurement Points .......................................67

    7.4 Shat Couplings ........................................................................68

    7.5 Pump Nozzle Loading ..............................................................69

    7.6 National and International Standards and Codes .....................69

    8 Calculation Examples

    (or all equations numbered in bold typeace) ................7

    9 Additional Literature .....................................................79

    10 Technical Annex (Tables, Diagrams, Charts) .................80

    Tab. : Centrigal pump classication ...................................................8

    Tab. : Reerence speeds o rotation ....................................................

    Tab. : Approximate average roughness height k or pipes ..................0

    Tab. 4: Inside diameter d and wall thickness s in mm and weight otypical commercial steel pipes and their water content ...........0

    Tab. 5: Loss coecients or various types o valves and ttings ........Tab. 6: Loss coecients in elbows and bends ....................................4

    Tab. 7: Loss coecients or ttings ..............................................4/5Tab. 8: Loss coecients or adapters .................................................5

    Tab. 9: Types o enclosure or electric motors to EN 60 59 and

    DIN/VDE 050, Part 5 ............................................................0

    Tab. 0: Permissible requency o starts Z per hour or electric motors ..0

    Tab. : Starting methods or asynchronous motors ..............................

    Tab. : Vapour pressure, density and kinematic viscosity o water at

    saturation conditions as a unction o the temperature .............4

    Tab. : Infuence o the altitude above mean sea level on the annual

    average atmospheric pressure and on the corresponding

    boiling point .........................................................................4

    Tab. 4: Minimum values or undisturbed straight lengths o piping

    at measurement points in multiples o the pipe diameter D ......67

    Contents

    Tables

  • 7/30/2019 Selecting Centrifugal Pumps Data

    6/92

    6

    A m Area

    A m Distance between measuring point and pump

    fange

    a m, mm Width o a rectangular elbow

    B m, mm Vertical distance rom suction pipe to foor

    Cv gpm Flow coecient or valves, dened as the fowo water at 60 F in US gallons/minute at a

    pressure drop o lb/in across the valve

    cD Resistance coecient o a sphere in water fow

    cT (%) Solids content in the fow

    D m (mm) Outside diameter; maximum diameter

    DN (mm) Nominal diameter

    d m (mm) Inside diameter; minimum diameter

    ds m (mm) Grain size o solids

    d50 m (mm) Mean grain size o solids

    F N Force

    Throttling coecient o an orice

    H Conversion actor or head (KSB system)

    Q Conversion actor or fow rate (KSB system)

    Conversion actor or eciency (KSB system)

    g m/s Gravitational constant = 9.8 m/s

    H m Head; discharge head

    Hgeo m Geodetic head

    Hs m Suction lit

    Hs geo m Vertical distance between water level and pump

    reerence plane or suction lit operation

    Hz geo m Vertical distance between pump reerence planeand water level or positive inlet pressure

    operation

    HL m Head loss

    H0 m Shut-o head (at Q = 0)

    I A Electric current (amperage)

    K Dimensionless specic speed, type number

    k mm, m Mean absolute roughness

    k Conversion actors kQ, kH, k (HI method)

    kv m/h Metric fow actor or valves, dened as the

    fow o water at 0 C in cubic metres per hour

    at a pressure drop o bar

    L m Length o pipe

    Ls m Straight length o air-lled pipe

    M Nm Moment

    NPSHr m NPSH required by the pump

    NPSHa m NPSH available

    Ns Specic speed in US units

    n min (rpm) Speed o rotation

    s (rev/s)

    nq min Specic speed in metric units

    P kW (W) Power; input power

    1

    1Nomenclature

    Nomenclature

  • 7/30/2019 Selecting Centrifugal Pumps Data

    7/92

    7

    pe Pressure in suction or inlet tank

    PN (bar) Nominal pressure

    p bar (Pa) Pressure rise in the pump; pressure dierential(Pa N/m)

    p bar (Pa) Pressure (Pa N/m = 05 bar)

    pb mbar (Pa) Atmospheric pressure (barometric)pL bar (Pa) Pressure loss

    pv bar (Pa) Vapour pressure o fuid pumped

    Q m/s, m/h Flow rate / capacity (also in litre/s)

    qair % Air or gas content in the fuid pumped

    Qo m/h Flow rate at switch-o pressure

    Qon m/h Flow rate at start-up pressure

    R m (mm) Radius

    Re Reynolds number

    S m Submergence (fuid level above pump);

    immersion depth

    s mm Wall thickness

    s m Dierence o height between centre o pump im-

    peller inlet and centre o pump suction nozzle

    T Nm Torque

    t C Temperature

    U m Length o undisturbed fow

    U m Wetted perimeter o a fow section

    VB m Suction tank volume

    VN m Useul volume o pump sump

    v m/s Flow velocity

    w m/s Settling velocity o solidsy mm Travel o gate valve; distance to wall

    Z /h Switching cycle (requency o starts)

    z Number o stages

    zs,d m Height dierence between pump discharge and

    suction nozzles

    Angle o change in fow direction; opening angle Angle o inclination Loss coecient (%) Eciency

    Pa s Dynamic viscosity Pipe riction actor m/s Kinematic viscosity

    kg/m Density

    N/m Shear stress N/m Shear stress at yield point Temperature actor; opening angle o a butter-

    fy valve; cos : power actor o asynchronousmotors

    Head coecient (dimensionless head generatedby impeller)

    1

    Indices, Subscripts

    a At outlet cross-section o

    the system; branching o

    Bl Reerring to orice bore

    d On discharge side; at dis-

    charge nozzle; fowing

    through

    dyn Denoting dynamic com-

    ponent

    E At the narrowest cross-

    section o valves (Table 5)

    E At suction pipe or bell-

    mouth inlet

    e At inlet cross-section o

    system, e. g. in suction

    or inlet tank Reerring to carrier fuid

    H Horizontal

    in Reerring to inlet fow

    K Reerring to curvature

    L Reerring to losses

    m Mean value

    max Maximum value

    min Minimum value

    N Nominal value

    opt Optimum value; at best

    eciency point (BEP)P Reerring to pump

    p Reerring to pressure

    r Reduced, or cutdown im-

    peller or impeller vanes

    s On suction side; at suc-

    tion nozzle

    s Reerring to solids

    stat Static component

    sys Reerring to system /

    installation

    t Reerring to impeller

    prior to trimming

    V Vertical

    w Reerring to water

    z Reerring to viscous fuid

    0 Basic position, reerred

    to individual sphere

    , , Consecutive numbers;

    items

    I, II Number o pumps oper-

    ated

    Nomenclature

  • 7/30/2019 Selecting Centrifugal Pumps Data

    8/92

    8

    Table 1: Centriugal pump classication

    Number o stages Single stage Multistage

    Shat position Horizontal Vertical Horiz. Vertic.

    Casing design Radial Axial Radial Axial Stage casing

    Impeller entries

    Motor type, Fig. ..Dry (standardized)

    motor a b c d e g h

    Magnetic drive i

    Submerged dry rotor

    motor (See ..) j k l m

    Wet rotor motor

    (See ..) n o p

    2Pump Types

    Typical selection criteria or

    centriugal pumps are their

    design data (fow rate or capac-

    ity Q, discharge head H, speed

    o rotation n and NPSH), the

    properties o the fuid pumped,

    the application, the place o

    installation and the applicable

    regulations, specications, laws

    and codes. KSB oers a broad

    range o pump types to meet the

    most varied requirements.

    Main design eatures or classi-

    cation are:

    the number o stages (single-

    stage / multistage),

    2

    the position o the shat (hori-

    zontal / vertical),

    the pump casing (radial, e. g.

    volute casing / axial, e. g.

    tubular casing),

    the number o impeller entries

    (single entry / double entry),

    the type o motor (dry mo-

    tor / dry rotor motor, e. g.

    submerged motor / wet rotor

    motor, e. g. canned motor,

    submersible motor).

    These eatures usually determine

    what a pump type or series

    looks like. An overview o typi-cal designs according to classi-

    cation eatures is given below

    (Table and Figs. a to p).

    Other pump classication

    eatures include:

    the mode o installation, which

    is dealt with in section 7.,

    the nominal diameter (or thepump size, as a unction o

    the fow rate),

    the rated pressure (or the

    wall thickness o casings and

    fanges),

    the temperature (or example

    or the selection o cooling

    equipment or shat seals),

    the fuid pumped (abrasive,

    aggressive, toxic fuids),

    the type o impeller (radial

    fow / axial fow depending on

    the specic speed),

    the sel-priming ability,

    the casing partition, the posi-

    tion o the pump nozzles, an

    outer casing, etc.

    a

    b

    Pump Types (Examples)

  • 7/30/2019 Selecting Centrifugal Pumps Data

    9/92

    9

    2

    Fig 1 (a to p):

    Centriugal pump classication

    acc. to Table 1

    hg

    kji

    ml

    po

    edc

    n

    Pump Types (Examples)

  • 7/30/2019 Selecting Centrifugal Pumps Data

    10/92

    0

    3 Flow Rate Head Eciency Input Power

    3Selection or Pumping Water

    This section applies mainly to

    pumping water; the particulari-

    ties o pump selection or other

    media are treated in sections 4,

    5 and 6.

    3.1Pump Data

    3.1.1Pump Flow Rate

    The pump fow rate or capacity

    Q is the useul volume o fuid

    delivered to the pump discharge

    nozzle in a unit time in m/s

    (l/s and m/h are also used in

    practice, as are GPM in the US).

    The fow rate changes propor-

    tionally to the pump speed o

    rotation. Leakage fow as well

    as the internal clearance fows

    are not considered part o the

    pump fow rate.

    3.1.2Developed Head andDeveloped Pressure othe Pump

    The total developed head H o

    a pump is the useul mechani-

    cal energy in Nm transerred

    by the pump to the fow, per

    weight o fuid in N, expressed

    in Nm/N = m (also used to be

    called metres o fuid)). The

    head develops proportionally

    to the square o the impellers

    speed o rotation and is inde-

    pendent o the density o the

    fuid being pumped. A given

    centriugal pump will impart the

    same head H to various fuids

    (with the same kinematic viscos-

    ity ) regardless o their density

    . This statement applies to all

    centriugal pumps.

    The total developed head H

    maniests itsel according to

    Bernoullis equation (see section

    ...) as

    the pressure head Hp propor-

    tional to the pressure dier-

    ence between discharge and

    suction nozzles o the pump,

    the geodetic head zs,d (Figs. 8

    and 9), i.e., the dierence in

    height between discharge and

    suction nozzles o the pump

    and

    the dierence o the kinetic

    energy head (vd-vs

    )/g be-

    tween the discharge and suc-

    tion nozzles o the pump.

    The pressure rise p in thepump (considering the location

    o the pressure measurement

    taps according to section 7.!)

    is determined solely by the pres-

    sure head Hp along with the

    fuid density according to the

    equation

    p = g[H-zs,d-(vd-vs)/g] (1)

    where

    Density o the fuid beingpumped in kg/m

    g Gravitational constant

    9.8 m/s

    H Total developed head o the

    pump in m

    zs,d Height dierence between

    pump discharge and suction

    nozzles in m (see Figs. 8

    and 9)

    vd Flow velocity in the discharge

    nozzle = 4 Q/pdd in m/s

    vs Flow velocity in the suction

    nozzle = 4 Q/pds in m/s

    Q Flow rate o the pump atthe respective nozzle in m/s

    d Inside diameter o the re-

    spective pump nozzle in m

    p Pressure rise in N/m (orconversion to bar: bar =

    00 000 N/m)

    High-density fuids thereore

    increase the pressure rise and

    the pump discharge pressure.

    The discharge pressure is thesum o the pressure rise and the

    inlet pressure and is limited by

    the strength o the pump casing.

    The eect o temperature on the

    pumps strength limits must also

    be considered.

    3.1.3Eciency and Input Power

    The input power P o a pump(also called brake horsepower)

    is the mechanical power in

    kW or W taken by the shat or

    coupling. It is proportional to

    the third power o the speed o

    rotation and is given by one o

    the ollowing equations:

    ) In the US, the corresponding units are

    t-lb/lbm, i. e. oot head = oot-

    pound-orce per pound mass; the

    numerical value o head and specic

    work are identical.

  • 7/30/2019 Selecting Centrifugal Pumps Data

    11/92

    P =gQH

    in W =gQH

    in kW =QH

    in kW 000 67

    (2)

    3

    where

    Density in kg/m

    in kg/m

    in kg/dm

    Q Flow rate in m/s in m/s in m/h

    g Gravitational constant = 9.8 m/s

    H Total developed head in m

    Eciency between 0 and

  • 7/30/2019 Selecting Centrifugal Pumps Data

    12/92

    (IGHHEAD

    IMPELLER

    UPTO

    -EDIUMHEAD

    IMPELLER

    UPTO

    ,OWHEAD

    IMPELLER

    UPTO

    -IXEDFLOW

    IMPELLER

    UPTO

    !XIALFLOW

    PROPELLER

    TONQ RPM

    3

    nq = n = n (3)

    where Qopt in m/s Qopt in m

    /s = Flow rate at optHopt in m Hopt in m = Developed head at optn in rpm n in rev/s = Pump speed

    nq in metric units nq Dimensionless parameter

    g Gravitational constant 9.8m/s

    Approximate reerence values:

    nq up to approx. 5 Radial high head impellerup to approx. 40 Radial medium head impeller

    up to approx. 70 Radial low head impeller

    up to approx. 60 Mixed fow impeller

    approx. rom 40 to 400 Axial fow impeller (propeller)

    Fig. 2: Eect o the specic speed nq on the design o centriugal

    pump impellers. The diuser elements (casings) o single stage

    pumps are outlined.

    Qopt/

    (Hopt/)/4

    Qopt(g Hopt)/4

    Specic Speed

    dimensionless characteristic

    parameter while retaining the

    same numerical value by using

    the denition in the right-hand

    version o the ollowing equa-

    tion []:

    For multistage pumps the devel-

    oped head Hopt at best eciency

    or a single stage and or double-

    entry impellers, the optimum

    fow rate Qopt or only one im-

    peller hal are to be used.

    As the specic speed nq in-

    creases, there is a continuous

    change rom the originally

    radial exits o the impellers to

    mixed fow (diagonal) and

    eventually axial exits (see Fig. ).

    The diuser elements o radial

    pump casings (e.g. volutes) be-

    come more voluminous as long

    as the fow can be carried o

    radially. Finally only an

    axial exit o the fow is possible

    (e.g. as in a tubular casing).

    Using Fig. it is possible to de-

    termine nq graphically. Further

    types o impellers are shown in

    Fig. 4: Star impellers are used in

    sel-priming pumps. Periph-

    eral impellers extend the speci-c speed range to lower values

    down to approximately nq = 5

    (peripheral pumps can be de-

    signed with up to three stages).

    For even lower specic speeds,

    rotary (or example progressive

    cavity pumps with nq = 0. to )

    or reciprocating positive dis-

    placement pumps (piston

    pumps) are to be preerred.

    The value o the specic speed

    is one o the infuencing para-

    meters required when convert-

    ing the pump characteristic

    curves or pumping viscous or

    solids-laden media (see sections

    4 and 6).

    In English-language pump lit-

    erature the true dimensionless

    specic speed is sometimes des-

    ignated as the type number K.

    In the US, the term Ns is used,

    which is calculated using gal-

    lons/min (GPM), eet and rpm.

    The conversion actors are:

    K = nq / 5.9

    Ns = nq / 5.6(4)

  • 7/30/2019 Selecting Centrifugal Pumps Data

    13/92

    Radial double-entry impeller*)

    Star impeller or side channel pump(sel-priming)

    Peripheral pump impeller or very lowspeciic speed (nq 5 to 0)

    *) Plan view shown without ront shroud

    Closed (shrouded) mixed low impeller *)

    Open (unshrouded) mixed low impeller

    Axial low propeller

    Radial impeller *)

    3

    Fig. 3: Nomograph to determine specic speed nq (enlarged view on p. 80)Example: Qopt= 66 m

    3/h = 18.3 l/s; n = 1450 rpm, Hopt= 17.5 m. Found: nq = 23 (metric units).

    Fig. 4:

    Impeller types or clear liquids

    Specic Speed Impeller Types Characteristic Curves

    3.1.6Pump Characteristic Curves

    Unlike positive displacement

    pumps (such as piston pumps),

    centriugal pumps deliver a var-

    iable fow rate Q (increasing

    with decreasing head H) when

    operating at constant speed.

    They are thereore able to ac-

    commodate changes in the

    system curve (see section ..).

    The input power P and hence

    the eciency as well as theNPSHr (see section .5.4) are

    dependent on the fow rate.

  • 7/30/2019 Selecting Centrifugal Pumps Data

    14/92

    4

    90

    80

    70

    60

    50

    40

    20

    30

    80

    70

    60

    50

    40

    0

    5

    10

    20

    30

    100 20 40 60 80 100 120

    Flow rate Q [m3/h] Flow rate Q [m3/h] Flow rate Q [m3/h]

    140 160 0 100 200 300 400 500 0 500 15001000 2000 2500 3000550

    HeadH[m]

    NPSHr[m]

    PowerP[kW]

    EfficiencyH[

    %]

    2422

    18

    14

    10

    20

    16

    12

    86

    90

    30

    80

    70

    60

    50

    40

    0

    5

    1510

    15

    14

    16

    17

    13

    HeadH[m]

    NPSHr[m]

    PowerP[kW]

    EfficiencyH[

    %]

    2

    4

    18

    14

    10

    20

    16

    12

    8

    6

    90

    30

    80

    70

    60

    50

    40

    5

    15

    10

    60

    40

    20

    80

    100

    0

    HeadH[m]

    NPSHr[m]

    PowerP[kW]

    EfficiencyH[

    %]

    n = 2900 min1 n = 1450 min1 n = 980 min1

    Operating limit

    > L V

    11OPT

    H

    HOPT

    11OP

    0

    0OPT

    300

    25

    11OPT

    (

    (OPT

    Operating limit forlow input power

    for highinput power

    25

    25

    300

    300

    150

    150

    70

    70

    40

    40

    11OP

    NPSHrNPSHr opt

    25

    25

    300

    300

    150

    70

    40

    150

    300

    7040

    25

    3

    Fig. 5: Eect o specic speed nq on centriugal pump characteristic

    curves (Not drawn to scale! For NPSHr, see section 3.5.4).

    Fig. 6: Three examples o characteristic curves or pumps o diering specic speeds.

    a: radial impeller, nq 20; b: mixed fow impeller, nq 80; c: axial fow impeller, nq 200.(For NPSH

    rsee section 3.5.4)

    Characteristic Curves

    The relationship o these val-

    ues is shown graphically in the

    pump characteristic curves,

    whose shape is infuenced by

    the specic speed nq and which

    document the perormance o acentriugal pump (see Fig. 5 or

    a comparison o characteristics

    and Fig. 6 or examples). The

    head curve o the pump is also

    reerred to as the H/Q curve.

    The H/Q curve can be steep or

    fat. For a steep curve, the fow

    rate Q changes less or a given

    change o developed head H

    than or a fat curve (Fig. 7).This can be advantageous when

    controlling the fow rate.

  • 7/30/2019 Selecting Centrifugal Pumps Data

    15/92

    5

    (EAD

    (

    1STEEP

    1FLAT

    &LOWRATE1

    5NSTABLE

    REGION

    3TEEPCHARACTERISTICCURVE

    &LATCHARACTERISTICCURVE

    -AXIMUM

    (

    Fig. 7: Steep, fat or unstable characteristic curve

    3Characteristic Curves

    H/Q characteristics normally

    have a stable curve, which

    means that the developed head

    alls as the fow rate Q in-

    creases. For low specic speeds,

    the head H may in the low

    fow range drop as the fow

    rate Q decreases, i. e., the curve

    is unstable (shown by the dash

    line in Fig. 7). This type o

    pump characteristic curve need

    only be avoided when two

    intersections with the system

    curve could result, in particularwhen the pump is to be used or

    parallel operation at low fow

    rates (see section .4.4) or when

    it is pumping into a vessel which

    can store energy (accumulator

    lled with gas or steam). In all

    other cases the unstable curve is

    just as good as the stable charac-

    teristic.

    Unless noted otherwise, thecharacteristic curves apply or

    the density and the kinematic

    viscosity o cold, deaerated

    water.

  • 7/30/2019 Selecting Centrifugal Pumps Data

    16/92

    6

    A VA

    EVE

    EVE

    VD

    VS

    AVA

    (GEO

    (SGEO

    ZSD

    A VA

    PA PA

    ! " #

    PE

    $ %

    3

    Fig. 8: Centriugal pump system with variously designed vessels in suction lit operation

    A = Open tank with pipe ending below the water level

    B = Closed pressure vessel with ree fow rom the pipe ending above the water level

    C = Closed pressure vessel with pipe ending below the water level

    D = Open suction/inlet tank

    E = Closed suction/inlet tank

    va and ve are the (usually negligible) fow velocities at position a in tanks A and C and at position e

    in tanks D and E. In case B, va is the non-negligible exit velocity rom the pipe end at a .

    System Head Bernoulli

    3.2System Data

    3.2.1System Head

    3.2.1.1Bernoullis Equation

    Bernoullis equation expresses

    the equivalence o energy in

    geodetic (potential) energy,

    static pressure and kinetic

    energy orm. The system head

    Hsys or an assumed rictionless,

    inviscid fow is composed o the

    ollowing three parts (see Figs.

    8 and 9):

    Hgeo (geodetic head) is the

    dierence in height between

    the liquid level on the inlet

    and discharge sides. I the dis-

    charge pipe ends above the

    liquid level, the centre o the

    exit plane is used as reerence

    or the height (see Figs 8B and

    9B).

    (pa - pe)/( g) is the pressure

    head dierence between the

    inlet and outlet tank, applic-

  • 7/30/2019 Selecting Centrifugal Pumps Data

    17/92

    7

    AVA

    E VEE VE

    VD

    VS

    A VA

    (GEO

    (ZGEO

    ZSD

    A VA

    PA PA

    ! " #

    PE

    $ %

    3

    Fig. 9: Centriugal pump system with variously designed vessels in suction head (positive inlet pressure)

    operation. Legend as in Fig. 8.

    System Head Bernoulli

    able when at least one o the

    tanks is closed as or B, C or

    E (see Figs. 8B, C, E, 9B, C,

    E).

    (va-ve

    )/g is the dierence in

    the velocity heads between the

    tanks.

    For a physically real fow, the

    riction losses (pressure head

    losses) must be added to these

    components:

    HL is the sum o the head

    losses (fow resistance in the

    piping, valves, ttings, etc in

    the suction and discharge lines

    as well as the entrance and exit

    losses, see section ...), and

    is reerred to as the system pres-

    sure loss.

    The sum o all our componentsyields the system head Hsys:

    Hsys = Hgeo + (pape)/( g) + (va-ve)/g + HL (5)

    where

    all the heads H are in m,

    all the pressures p are in Pa ( bar = 00 000 Pa),

    all velocities v are in m/s,

    the density is in kg/m,

    the gravitational constant is g = 9.8 m/s

    .

  • 7/30/2019 Selecting Centrifugal Pumps Data

    18/92

    8

    Fig. 10: Pipe riction actor as a unction o the Reynolds number Re and the relative roughness d/k(enlarged view on p. 81)

    3 System Head Pressure Loss Head Loss

    DK

    &ULLYROUGHK

    LAMINAR TURBULENT

    2ECRIT

    ,IMITINGCURVE

    (YDRAULICALLYSMOOTHK

    L

    2E

    2EYNOLDSNUMBER2E

    0IPE

    FRIC

    TION

    FACTORL

    The dierence o the velocity

    heads can oten be neglected in

    practice. When at least one tank

    is closed as or B, C or E (see

    Figs. 8B, C, E, 9B, C, E), Eq. 5

    can be simplied as

    HsysHgeo+(pape)/(g)+HL (6)

    and urther simplied when

    both tanks are open as or A

    and D (see Figs. 8A, D and 9A,

    D) as

    HsysHgeo+HL (7)

    3.2.1.2Pressure Loss Due to FlowResistances

    The pressure loss pL is caused

    by wall riction in the pipes and

    fow resistances in valves, t-tings, etc. It can be calculated

    rom the head loss HL, which is

    independent o the density ,

    using the ollowing equation:

    pL = g HL (8)

    where

    Density in kg/m

    g Gravitational constant

    9.8 m/s

    HL Head loss in m

    pL Pressure loss in Pa

    ( bar = 00 000 Pa)

    3.2.1.2.1Head Loss in Straight Pipes

    The head loss or fow in

    straight pipes with circular

    cross-sections is given in general

    by

    HL = L

    v (9) d g

    where

    Pipe riction actor accordingto Eqs. () to (4)

    L Length o pipe in m

    d Pipe inside diameter in m

    v Flow velocity in m/s(= 4Q/pd or Q in m/s)

    g Gravitational constant

    9.8 m/s

  • 7/30/2019 Selecting Centrifugal Pumps Data

    19/92

    9

    3Head Loss in Straight Pipes

    For pipes with non-circular

    cross-sections the ollowing

    applies:

    d = 4A/U (10)

    where

    A Cross-sectional fow area

    in m

    U Wetted perimeter o the

    cross-section A in m; or

    open channels the ree fuid

    surace is not counted as part

    o the perimeter.

    Recommended fow velocities

    or cold waterInlet piping 0.7.5 m/sDischarge piping .0.0 m/sor hot water

    Inlet piping 0.5.0 m/sDischarge piping .5.5 m/sThe pipe riction actor hasbeen determined experimentally

    and is shown in Fig. 0. It varies

    with the fow conditions o the

    liquid and the relative rough-ness d/k o the pipe surace. The

    fow conditions are expressed

    according to the anity laws

    (dimensional analysis) using the

    Reynolds number Re. For cir-

    cular pipes, this is:

    Re = v d/ (11)

    where

    v Flow velocity in m/s

    (= 4Q/pd or Q in m/s)d Pipe inside diameter in m

    Kinematic viscosity in m/s

    (or water at 0 C exactly

    .00 (0)6 m/s).

    For non-circular pipes, Eq. 0 is

    to be applied or determining d.

    For hydraulically smooth pipes

    (or example drawn steel tubing

    or plastic pipes made o poly-

    ethylene (PE) or polyvinyl chlor-

    ide (PVC)) or or laminar fow,

    can be calculated:

    In the laminar fow region

    (Re 0)

    the test results can be repre-

    sented by the ollowing empiri-

    cal relationship dened by Eck

    (up to Re < 08 the errors are

    smaller than %):

    =0.09

    (lgRe

    )(13)

    7

    In Fig. 0 it can be seen that

    the pipe riction actor depends

    on another dimensionless para-

    meter, the relative roughness o

    the pipe inner surace d/k; k is

    the average absolute roughnesso the pipe inner surace, or

    which approximate values are

    given in Table . Note: both d

    and k must be expressed in the

    same units, or example mm!

    As shown in Fig. 0, above a

    limiting curve, is dependentonly on the relative roughness

    d/k. The ollowing empirical

    equation by Moody can be used

    in this region:

    =0.0055+0.5/ (d/k) (14)

    For practical use, the head

    losses HL per 00 m o straight

    steel pipe are shown in Fig.

    as a unction o the fow rate Q

    and pipe inside diameter d. The

    values are valid only or cold,

    clean water or or fuids with

    the same kinematic viscosity, or

    completely lled pipes and or an

    absolute roughness o the pipe

    inner surace o k = 0.05 mm,

    i.e., or new seamless or longi-tudinally welded pipes. (For

    the pipe inside diameters, see

    Table 4).

    The eect o an increased

    surace roughness k will be de-

    monstrated in the ollowing

    or a requently used region in

    Fig. (nominal diameter 50

    to 00 mm, fow velocity 0.8

    to .0 m/s). The dark-shadedregion in Fig. 11 corresponds

    to the similarly marked region

    in Fig. 10 or an absolute rough-

    ness k = 0.05 mm. For a rough-

    ness increased by a actor 6

    (slightly incrusted old steel pipe

    with k = 0.0 mm), the pipe

    riction actor(proportionalto the head loss HL) in the

    lightly shaded region in Fig. 0

    is only 25% to 60% higher thanbeore.

    For sewage pipes the increased

    roughness caused by soiling

    must be taken into considera-

    tion (see section .6). For pipes

    with a large degree o incrusta-

    tion, the actual head loss can

    only be determined experimen-

    tally. Deviations rom the no-

    minal diameter change the headloss considerably, since the pipe

    inside diameter enters Eq. (9) to

    the 5th power! (For example, a

    5% reduction in the inside dia-

    meter changes the head loss by

    0%). Thereore the nominal

    diameter may not be used as

    the pipe inside diameter or the

    calculations!

  • 7/30/2019 Selecting Centrifugal Pumps Data

    20/92

    0

    *i>i> `vii

    -ii i] i>i >V`Vi>i` }>>i`

    }` >i`i`] Li` }>>i` Viii`

    ii`

    i`] `i>i }V> i>V> >viVi>}

    LiVii ii>V> >>}i i

    Vii i] vi` v-VVii i] vi` v,ivVi VVii i] vVVii i`] v

    i>i `>>]>V,LLiL} i] iLi`7` i >vi}ii>i>

    x x x x {

    x x x x

    3

    Table 4: Inside diameter d and wall thickness s in mm and weight o typical commercial steel pipes and their

    water content in kg/m to ENV 10 220 (ormerly DIN ISO 4200). D = outside diameter, s = wall thickness

    All dimensions in mm Seamless pipe Welded pipeSeamless Welded weight in kg/m weight in kg/m

    DN D s * d s ** d Pipe Water Pipe Water

    5 . .0 7. .8 7.7 0.95 0.5 0.866 0.460 6.9 .0 .9 .8 . . 0.4 . 0.465 .7 . 9. .0 9.7 .78 0.665 .56 0.69 4.4 .6 7. . 7.8 .55 .09 .7 .40 48. .6 4. . 4.7 .9 .46 .6 .5050 60. .9 54.5 . 55.7 4. . .9 .4465 76. .9 70. .6 70.9 4.7 .88 5.4 .9580 88.9 . 8.5 .9 8. 6.76 5.4 6.5 5.4

    00 4. .6 07. . 07.9 9.8 9.00 8.77 9.45 9.7 4.0 .7 .6 .5 .4 .6 . .850 68. 4.5 59. 4.0 60. 8. 9.9 6. 0.00 9. 6. 06.5 4.5 0. . .5 .8 4.750 7.0 6. 60.4 5.0 6.0 4.4 5. .0 54.00 .9 7. 09.7 5.6 .7 55.5 75. 44.0 76.850 55.6 8.0 9.6 5.6 44.4 68.6 90.5 48. 9.400 406.4 8.8 88.8 6. 9.8 86. 8.7 6. .7500 508.0 .0 486.0 6. 495.4 5 85.4 77.9 9.7600 60.0 .5 585.0 6. 597.4 84 68.6 9.8 80.

    * above nominal diameter DN identical to DIN 448 ** above nominal diameter DN 5 identical to DIN 458

    Table 3: Approximate average roughness height k (absolute rough-

    ness) or pipes

    Head Loss in Straight Pipes Dimensions and Weights o Steel Pipes

  • 7/30/2019 Selecting Centrifugal Pumps Data

    21/92

  • 7/30/2019 Selecting Centrifugal Pumps Data

    22/92

    3

    Fig. 13: Schematic representation o the valve designs listed in

    Table 5

    4 5

    6 7 8 9 0

    4 5

    6 7 8 9

    Head Loss in Straight Pipes Valves and Fittings

    The head losses HL in plastic

    (or example PE or PVC) pipes

    or smooth drawn metal pip-

    ing are very low thanks to the

    smooth pipe surace. They are

    shown in Fig. and valid orwater at 0 C. At other tem-

    peratures, the loss or plastic

    pipes must be multiplied with

    a temperature correction actor

    indicated in Fig. to account

    or their large thermal expan-

    sion. For sewage or other un-

    treated water, an additional

    00% head loss should betaken into consideration or po-tential deposits (see section .6).

    3.2.1.2.2Head Loss in Valves andFittings

    The head loss in valves and t-

    tings is given by

    HL = v/g (15)

    where

    Loss coecientv Flow velocity in a charac-

    teristic cross-section A (or

    example the fange) in m/s

    g Gravitational constant

    9.8 m/s

    Tables 5 to 8 and Figures to5 contain inormation about

    the various loss coecients orvalves and ttings or operation

    with cold water.

    The minimum and maximum

    in Table 5 bracket the values

    given in the most important

    technical literature and apply to

    valves which have a steady ap-

    proach fow and which are ully

    open. The losses attributable to

    straightening o the fow dis-

    turbances over a length o pipe

    equivalent to x DN down-

    stream o the valve are included

    in the value in accordancewith VDI/VDE 7 guidelines.

    Depending on the inlet and

    exit fow conditions, the valve

    models used and the develop-

    ment objectives (i.e. inexpensivevs. energy-saving valves), the

    loss values can vary dramatically.

  • 7/30/2019 Selecting Centrifugal Pumps Data

    23/92

  • 7/30/2019 Selecting Centrifugal Pumps Data

    24/92

    4

    /iZ>ivi}iciL`Li`Li`]LLii`Liv>V`V>i`L>iiiV>i`LiVL>viL>i`

    />Li\VivvViZvv}

    L>viLi`-iL\

    >\iii>}`ii Zzi>LiLi` Zzni>i`Vi>LiLi` ZziiVi>LiLi`Zz{

    iiv}\

    ii`}i-> Zz x vDrxc c {xc

    >vii` Zz x xx x Zz n

    n{

    D

    V>}iiv}\

    Zz`i>v>>`i>ii}v>}i>> >iviV LiiViVZz v>ii}>iV`L]vi>ii`>i `i>v>iv}>>i]iV

    i`i>}i

    A xc c {xc c c

    -v>Vi -v>Vi -v>Vi -v>Vi -v>Vi

    } } } } }

    Zv ,r { x x x x Zv ,r` q q { { { x

    Zv ,r` q q {

    Zv ,x` q q n

    LivVVvii>i` q q q q q q q

    Z q q q q x q q x q

    ,`iL

    7i`i`Li`

    ,A

    A

    `

    Table 6: Loss coecients in elbows and bends

    3 Head Loss in Valves and Fittings Loss Coecients or Fittings

    Note: For the branch ttings

    in Table 7 and the adapters o

    Table 8, one must dierentiate

    between the irreversible pressure

    loss (reduction in pressure)

    pL = v/ (16)

    where

    pL Pressure loss in Pa

    Loss coecient Density in kg/m

    v Flow velocity in m/s

    and the reversible pressure

    change o the rictionless fow

    according to Bernoullis equa-

    tion (see ...):

    pp = (vv)/ (17)

    For accelerated fows (or ex-

    ample a reduction in the pipe

    diameter), pp is alwaysnegative, or decelerated fows

    (e.g. pipe expansion) it is always

    positive. When calculating the

    net pressure change as the arith-

    metic sum o pL and pp, thepressure losses rom Eq. 6 are

    always to be subtracted.

    Oten the so-called kv value is

    used instead o the loss coe-

  • 7/30/2019 Selecting Centrifugal Pumps Data

    25/92

    5

    A

    A

    2+

    2+

    ,OSSC

    OEFFICIENTZ

    %LBOWRADIUS2+$UCTWIDTHA

    2ADIUSONINNERCORNER7ITHTURNING

    VANECASCADE

    2ADIUSONOUTERCORNER

    3

    Flow meters:

    Short Venturi tube = 0

    is reerred to the velocity v at diameter D.

    Diameter ratio d/D = 0.0 0.40 0.50 0.60 0.70 0.80

    Area ratio m = (d/D) = 0.09 0.6 0.5 0.6 0.49 0.64

    Short Venturi tube 6 0.7 0. 0.Standard orice 00 85 0 4.5

    Water meters (volume meters) 0For domestic water meters, a max. pressure drop o bar is specied or the

    rated load. In practice, the actual pressure loss is seldom higher.

    Branch ttings (o equal diameter)

    Note:

    The loss coecients a or the branched-o fow Qa or d or the main fowQd = Q Qa reer to the velocity o the total fow Q in the branch. On the

    basis o this denition, a or d may have negative values; in this case, theyare indicative o a pressure gain instead o a pressure loss. This is not to be

    conused with the reversible pressure changes according to Bernoullis equa-

    tion (see notes to Tables 7 and 8).Qa/Q = 0. 0.4 0.6 0.8

    a 0.4 0.08 0.47 0.7 0.9 d 0.7 0.0 0.4 0.5

    a 0.88 0.89 0.95 .0 .8 d 0.08 0.05 0.07 0.

    a 0.8 0 0. 0.7 0.7 d 0.7 0.9 0.09 0.7

    a 0.68 0.50 0.8 0.5 0.48 d 0.06 0.04 0.07 0.0

    Table 8: Loss coecients or adapters

    Expansion Contraction

    Type I II III IV

    Type d/D 0.5 0.6 0.7 0.8 0.9

    I 0.56 0.4 0.6 0. 0.04 = 8 0.07 0.05 0.0 0.0 0.0II or = 5 0.5 0. 0.07 0.0 0.0 = 0 0. 0.7 0. 0.05 0.0III 4.80 .0 0.88 0.4 0.IV or 0 < < 40 0. 0.0 0.05 0.0 0.0

    Ddv Dd

    v D dv D d

    v

    Fig. 14: Eect o rounding o

    the inner and outer side o el-

    bows in square ducts on the loss

    coecient

    Head Loss in Valves and Fittings Loss Coecients or Fittings and Flow Meters

    D d D D

    Standard oriice

    Dv

    dv

    Qd

    Qd

    Qd

    Qa

    Q

    Qa

    Q

    Qd

    Qa

    Q45

    45

    Qa

    Q

    cient when calculating thepressure loss or water in valves:

    pL = (Q / kv) . /000 (18)

    where

    Q Volume rate o fow in m/h (!)

    Density o water in kg/m

    pL Pressure loss in bar (!)

    The kv value is the fow rate in

    m/h which would result rom a

    pressure drop o bar through

    the valve or cold water. It cor-

    relates with the pressure loss pL

    in bar with the fow rate Q in

    m/h. The notation kvs is usedor a ully open valve.

    Conversion or cold water:

    6 d4/kv (19)

    where

    d Reerence (nominal) diameter

    o the valve in cm (!)

    Table 7 (continued)

  • 7/30/2019 Selecting Centrifugal Pumps Data

    26/92

    6

    3YSTEMH

    EAD(SYS

    3YSTEMHEADCHARACTERISTIC( SYS$YNAMICCOMPONENT(,

    VAnVE

    G

    3TATICCOMPONENT(GEOPAnPEqG

    Fig. 16: System characteristic curve Hsys with static and dynamic

    components

    3

    3.2.2System Characteristic Curve

    The system characteristic curve

    plots the head Hsys required by

    the system as a unction o the

    fow rate Q. It is composed o

    the so-called static and

    dynamic components (see

    Fig. 6).

    The static component consists

    o the geodetic head Hgeo andthe pressure head dierence

    (pa-pe)/(g) between the inlet

    J

    J

    J

    V V

    Y

    V

    10

    A

    ,OSS

    COEFFICIENTZ

    2ELATIVEOPENINGANGLEJnJJ Degree of opening y/a or relative lift y/DN

    Fig. 15:

    Loss coecients

    o butterfyvalves, globe

    valves and gate

    valves as aunction o the

    opening angle

    or degree o

    opening (The

    numbers desig-

    nate the types

    illustrated in

    Fig. 13)

    Head Loss in Valves System Characteristic Curve

    One must be careul to distinguishbetween this use o static anddynamic components and the pre-cisely dened static head and dy-namic head used in fuid dynamics,since the dynamic component othe system head curve consists o bothstatic head (i.e. pressure losses)and dynamic head (i.e. velocity or

    kinetic energy head).

  • 7/30/2019 Selecting Centrifugal Pumps Data

    27/92

    7

    1M

    H

    1LS

    (

    M

    n

    n

    n

    n

    n n n n n

    n

    n n

    n

    n

    n n n

    n n

    n

    n n n

    nn

    n

    n

    3

    and outlet tanks, which are in-

    dependent o the fow rate. The

    pressure head dierence is zero

    when both tanks are open to the

    atmosphere.

    The dynamic component con-

    sists o the head loss HL, which

    increases as the square o the

    fow rate Q (see section ...),

    and o the change in velocity

    head (va-ve)/g between theinlet and outlet cross-sections o

    the system. Two points are su-

    cient to calculate this parabola,

    one at Q = 0 and one at any

    point Q > 0.

    For pipe systems connected

    one ater the other (series con-

    nection) the individual system

    curves Hsys, Hsys etc. are

    plotted as unctions o Q, and

    Fig. 17: Selection chart or a volute casing pump series or n = 2900 rpm

    (First number = nominal diameter o the discharge nozzle, second number = nominal impeller diameter)

    the heads or each fow rate are

    added to obtain the total system

    curve Hsys = (Q).

    For branched piping systems the

    system curves Hsys, Hsys, etc.

    o the individual branches be-

    tween the fow dividers are each

    calculated as unctions o Q.

    The fow rates Q, Q, etc. o

    all branches in parallel or each

    given head Hsys are then addedto determine the total system

    curve Hsys = (Q) or all the

    branches together. The sections

    beore and ater the fow

    dividers must be added as or a

    series connection.

    System Characteristic Curve Selection Chart

  • 7/30/2019 Selecting Centrifugal Pumps Data

    28/92

    8

    100

    50

    40

    30

    20

    10

    61 2

    0.3 0.4 0.5 1 2

    3 4 5 10 20Q m3/h

    Q l/s

    3

    10987

    65

    4

    3

    2

    987

    6

    5

    4

    3

    2

    76

    5

    3

    10

    4

    2

    3

    4

    2

    Pump size 1 Pump size 2 Pump size 3 Pump size 4

    H

    m

    3 4 5

    ,S

    MH

    &LOWRATE

    MH

    K7

    (EAD

    M

    M

    .03(

    0OWER

    MM)MPELLER

    H

    3

    3.3Pump Selection

    3.3.1Hydraulic Aspects

    The data required or selecting

    a pump size, i.e. the fow rate Q

    and the head H o the desired

    operating point are assumed

    to be known rom the system

    characteristic curve; the electric

    mains requency is also given.

    With these values it is possible

    to choose the pump size, the

    speed o rotation and, i neces-

    sary, the number o stages, rom

    the selection chart in the salesliterature (see Figs. 7 and 9).

    Further details o the chosen

    pump such as the eciency ,the input power P, the required

    NPSHr (see section .5.4) and

    the reduced impeller diameter

    Dr can then be determined rom

    Fig. 19: Selection chart or a multistage pump series or n = 2900 rpm

    Fig. 18: Complete characteristics

    o a centriugal pump

    Hydraulic Aspects o Pump Selection

  • 7/30/2019 Selecting Centrifugal Pumps Data

    29/92

    9

    3

    the individual characteristic

    curve (or example see Fig. 8).

    I there are no specic reasons

    or doing otherwise, a pump

    should be selected so that the

    operating point lies near its

    best eciency point Qopt (=

    fow rate at which eciency is

    highest, BEP). The limits Qmin

    and Qmax (or example due to

    vibration behaviour, noise emis-

    sion as well as radial and axial

    orces) are given in the product

    literature or can be determined

    by inquiry [].

    To conclude the selection, theNPSH conditions must be

    checked as described in section

    .5.

    A multistage pump is chosen us-

    ing the same general procedure;

    its selection chart shows the

    number o stages in addition to

    the pump size (Fig. 9).

    For pumps operating in series

    (one ater the other) the devel-oped heads H, H, etc. o the

    individual characteristic curves

    must be added (ater subtracting

    any head losses which occur be-

    tween them) to obtain the total

    characteristic H = (Q).

    For pumps operating in parallel,

    the individual characteristics H,

    H, etc. = (Q) are rst reduced

    by the head losses occurring up

    to the common node (head loss

    HL calculation according to sec-

    tion ...) and plotted versus

    Q. Then the fow rates Q o

    the reduced characteristics are

    added to produce the eective

    characteristic curve o a vir-

    tual pump. This characteristic

    interacts with the system curve

    Hsys or the rest o the system

    through the common node.

    3.3.2Mechanical Aspects

    When selecting a pump the me-

    chanical aspects require atten-

    tion in addition to the hydrau-

    lics. Several examples are:

    the eects o the maximum

    discharge pressure and tem-

    perature o the fuid pumpedon the operating limits,

    the choice o the best shat

    sealing method and cooling

    requirements,

    the vibration and noise emis-

    sions,

    the choice o the materials o

    construction to avoid corro-

    sion and wear while keeping

    in mind their strength andtemperature limits.

    These and other similar re-

    quirements are oten specic to

    certain industries and even to

    individual customers and must

    be addressed using the product

    literature [] or by consulting

    the design department.

    3.3.3Motor Selection

    3.3.3.1Determining Motor Power

    Operation o a centriugal pump

    is subject to deviations rom

    rated speed and fuctuations

    in the fow volume handled,

    and, consequently, changes in

    the operating point (see section

    .4.). In particular i steep

    power curves are involved (see

    Figs. 5 and 6), this may result

    in a higher required pump input

    power P than originally speci-

    ed. For practical purposes, a

    saety allowance is thereore

    added when the appropriate

    motor size is selected. Saety

    allowances may be speciedby the purchaser, or laid down

    in technical codes, see Fig. 0.

    The saety allowances stipulated

    by individual associations are

    shown in the relevant type series

    literature [] or the customers

    specication.

    When energy-saving control

    methods are used (e. g., speed

    control systems), the maximum

    Fig. 20: Drive power as a unction o rated pump input power at the

    operationg point

    Example as per ISO 9905, 5199 and 9908 (Class I, II and III)

    K7

    Drivepowerrelativetopumpinpu

    tpowerunderrated

    conditionsin%

    0UMPINPUTPOWERUNDERRATEDCONDITIONS

    Hydraulic Aspects o Pump Selection Motor Selection

  • 7/30/2019 Selecting Centrifugal Pumps Data

    30/92

    0

    3

    power peaks which may pos-

    sibly occur must be taken into

    account.

    I a pump is selected or a

    product with a density lower

    than that o water, the motor

    power required may have to be

    determined on the basis o the

    density o water (or example,

    during the perormance test or

    acceptance test in the test bay).

    Typical eciencies and poweractors cos o standardized IP54 motors at 50 Hz are shown

    in Fig. , and the curves o e-

    ciency and power actorcos as a unction o relativemotor load P/PN in Fig. .

    Table 9 lists types o enclosure

    that provide protection o elec-

    tric motors against ingress o

    oreign objects or water, and

    o persons against accidental

    contact.

    The specic heat build-up in

    both electric motors and fexi-

    ble couplings during start-up

    as well as the risk o premature

    contactor wear limit the requen-

    cy o starts. Reerence values

    or the maximum permissible

    number o starts Z are given in

    table 0, unless otherwise speci-

    ed.

    Submersible motor pumps (Figs.

    j to m) are ready-assembled

    pump units whose motors need

    not be selected individually [7].

    Their electrical characteristics

    are given in the type series

    literature. The motor is lled

    with air and can be operated

    submerged in the product han-

    dled thanks to a in most cases

    double-acting shat seal with a

    paran oil barrier.

    Table 9: Types o enclosure or electric motors to EN 60 59 andDIN/VDE 050, Part 5

    The type o protective enclosure is indicated by the IP code as ollows:Code letters (International Protection) IPFirst digit (0 to 6 or X i not applicable) XSecond digit (0 to 8 or X i not applicable) X

    Alternatively letters A, B, C, D and H, M, S, W or special purposes only.Key to Protection o electrical Protection o persons againstdigits: equipment against ingress o accidental contact by

    solid objects

    First 0 (not protected) (not protected)digit > 50 mm in dia. back o the hand

    > .5 mm in dia. nger > .5 mm in dia. tool4 > .0 mm in dia. wire5 protected against dust (limited wire

    ingress permitted, no harmuldeposits)

    6 totally protected against dust wire

    Protection against ingress o water with harmul consequences

    Second 0 (not protected)digit vertical dripwater

    dripwater up to 5 rom the vertical sprays (60 rom the vertical)4 sprays (all directions)5 low-pressure jets o water6 strong jets o water (heavy sea)7 temporary fooding8 permanent fooding

    K7

    H

    COSJ

    2ATEDPOWER0.

    %FFICIENCYH

    0OWERFACTORCOSJ

    POLES

    POLES

    Fig. 21: Typical eciencies and power actors cos o standard-ized motors, IP 54 enclosure, at 50 Hz as a unction o motor

    power PN

    Table 0: Permissible requency o starts Z per hour or electric motors

    Motor installation Dry Wet (submersible motors)

    Motors up to 4 kW 5 0Motors up to 7.5 kW 5 5Motors up to kW 5Motors up to 0 kW 0Motors above 0 kW 0 0

    Motor Selection

  • 7/30/2019 Selecting Centrifugal Pumps Data

    31/92

    3

    K7

    H

    K7

    K7

    K7]

    COSJ

    %FFICIENCYH

    0OWERFACTORCOSJ

    2ATEDPOWER00.

    POLESPOLES

    Fig. 22: Curve o eciency and power actor cos o standardizedIP 54 motors plotted over relative motor power P/PN

    Submersible borehole pumps,

    which are mostly used or ex-

    tracting water rom wells, are

    another type o ready-assembled

    units whose motors need not be

    selected individually (Fig. p).

    On these pumps, the rotor and

    the windings are immersed in

    water [7]. Their electrical char-acteristics and permissible re-

    quency o starts are indicated in

    the type series literature [].

    3.3.3.2Motors or Seal-less Pumps

    Seal-less pumps are requently

    used or handling aggressive,

    toxic, highly volatile or valu-

    able fuids in the chemical and

    petrochemical industries. They

    include magnetic-drive pumps

    (Fig. ) and canned motor

    pumps (Figs. n and o). A

    mag-drive pump is driven by a

    primary magnetic eld rotating

    outside its fameproo enclosure

    and running in synchronization

    with the secondary magnets in-

    side the enclosure [].

    The primary component in

    turn is coupled to a commercial

    dry driver. The impeller o a

    canned motor pump is mounted

    directly on the motor shat, so

    that the rotor is surrounded by

    the fuid pumped. It is separated

    rom the stator windings by the

    can [7].

    Seal-less pump sets are generally

    selected with the help o compu-

    terized selection programs, tak-

    ing into account the ollowing

    considerations:

    The rotor is surrounded by

    the fuid pumped, whose kine-

    matic viscosity (see section4.) must be known, as it

    infuences riction losses andthereore the motor power

    required.

    Metal cans or containment

    shrouds (or example made

    o .460) cause eddy current

    losses, resulting in an increase

    in the motor power required.

    Non-metal shrouds in mag-

    drive pumps do not have this

    eect.

    The vapour pressure o the

    fuid pumped must be known,

    so as to avoid bearing damage

    caused by dry running when

    the fuid has evaporated. It is

    advisable to install monitoringequipment signalling dry run-

    ning conditions, i any.

    Data on specic fuid proper-

    ties such as its solids content

    and any tendency to solidiy

    or polymerize or orm incrus-

    tations and deposits, need to

    be available at the time o se-

    lection.

    3.3.3.3Starting Characteristics

    The pump torque Tp transmit-

    ted by the shat coupling is

    directly related to the power P

    and speed o rotation n. Dur-

    ing pump start-up, this torque

    ollows an almost parabolical

    curve as a unction o the speed

    o rotation [0], as shown inFig. . The torque provided

    by the asynchronous motor

    must, however, be higher so as

    to enable the rotor to run up to

    duty speed. Together with the

    voltage, this motor torque has a

    direct eect on the motors cur-

    rent input, and the latter in turn

    on heat build-up in the motor

    windings. The aim, thereore, is

    to prevent unwanted heat build-up in the motor by limiting the

    run-up period and/or current

    inrush [] (see also Table ).

    Motors or Seal-less Pumps Starting Characteristics

  • 7/30/2019 Selecting Centrifugal Pumps Data

    32/92

    Table : Starting methods or asynchronous motors

    Starting Type o Current Run-up Heat build- Mechani- Hydraulic Cost Recommended Commentsmethod equipment input time up in motor cal loading loading relation motor designs

    (mains load) duringstart-up

    D. o. l. Contactor 48 IN Approx. High Very high Very high All Mostly limited to(mecha- 0.55 s 4 kW by energynical) supply companies

    Star- Contactor / o d. o. l. Approx. High Very high Very high .5 All; canned mo- Usually stipu-delta combi- values 0 s tors and sub- lated or motors

    nation mersible motors >4 kW by(mecha- subject to a energy supplynical) major drop in companies

    speed duringswitchover

    Reduced Autotrans- 0.49 times Approx. High High High 55 All No currentlessvoltage ormer, the d. o. l. 0 s phase during

    mostly values switchover70% tap- (gradually re-ping placed by sot

    starters)Sot Sot starter Continuous- Approx. High Low Low 55 All Run-up and run-start (power ly variable; 00 s down continu-

    electro- typically ously variablenics) IN via ramps or

    each individualload appllication;no hydraulicsurges

    Fre- Frequency IN 060 s Low Low Low Approx. All Too expensive toquency inverter 0 use solely or run-inverter (power up and run-down

    electro- purposes; betternics) suited or open-

    or closed-loopcontrol

    3

    In the case o d.o.l. starting

    (where the ull mains voltage

    is instantly applied to the mo-

    tor once it is switched on), the

    ull starting torque is instantly

    available and the unit runs up

    to its duty speed in a very short

    period o time. For the motor

    itsel, this is the most avour-

    able starting method. But at up

    to 4 8 times the rated current,

    the starting current o the d.o.l.

    method places a high load on

    the electricity supply mains,

    particularly i large motors are

    involved, and may cause prob-

    lematic voltage drops in electri-

    cal equipment in their vicinity.

    For motor operation on public

    low-voltage grids (80 V), the

    regulations laid down by the en-

    ergy supply companies or d.o.l.

    starting o motors o 5.5 kW

    and above must be complied

    with. I the grid is not suitable

    or d.o.l starting, the motor can

    be started up with reduced volt-

    ages, using one o the ollowing

    methods:

    Star-delta starting is the most

    requent, since most inexpen-

    sive, way o reducing the start-

    ing current. During normal

    operation, the motor runs in

    delta, so that the ull mains

    voltage (or example 400 V) is

    applied to the motor windings.

    For start-up, however, the wind-

    ings are star-connected, so that

    the voltage at the windings is

    reduced by a actor o 0.58 rela-

    tive to the mains voltage. This

    reduces the starting current and

    torque to one third o the values

    o d.o.l. starting, resulting in a

    longer start-up process.

    The motor runs up in star con-

    nection beyond pull-out torque

    up to the maximum speed o

    rotation at point B in Fig. .

    Then, switchover to delta is e-

    ected and the motor continues

    to accelerate up to rated speed.

    During the switchover period o

    approx. 0. s, the current sup-

    ply to the motor is interrupted

    Starting Methods

  • 7/30/2019 Selecting Centrifugal Pumps Data

    33/92

    Fig. 23: Starting curve or current I and torque T o squirrel-cage

    motors in star-delta connection

    ( = star connection; = delta connection; P = pump)

    3

    "gg

    $g

    $gg

    $

    )

    )

    4

    4

    40

    "g

    "

    OFNSYNCHR

    #URRENT)

    4ORQUE4

    -OTORSPEEDN

    and the speed drops. On pump

    sets with a low moment o in-

    ertia (canned motors and sub-

    mersible motors), this speed re-

    duction may be so pronounced

    that switchover to delta mayresult in almost the ull starting

    current being applied ater all,

    same as with d.o.l. starting.

    An autotransormer also serves

    to reduce voltage at the motor

    windings and unlike star-delta

    starting allows selection o

    the actual voltage reduction. A

    70% tapping o the transormer,or instance, will bring down

    the start-up torque and current

    supplied by the mains to 49%

    o the values or d.o.l. starting.

    The act that current supply is

    never interrupted is another ad-

    vantage o autotransormers.

    Sot starters are used or elec-

    tronic continuous variation o

    the voltage at the motor wind-

    ings in accordance with the

    dimmer principle. This means

    that the start-up time and start-

    ing current can be reely selected

    within the motors permissible

    operating limits (heat losses due

    to slip!). Special constraints re-

    garding the requency o starts

    (contrary to Table 0) have tobe heeded [].

    Frequency inverters (usually or

    open- or closed-loop control)

    provide a sot starting option

    without the need or any addi-

    tional equipment. For this pur-

    pose, the output requency and

    voltage o the requency inverter

    (see section .4.) are increased

    continuously rom a minimum

    value to the required value,

    without exceeding the motors

    rated current.

    Starting Methods

  • 7/30/2019 Selecting Centrifugal Pumps Data

    34/92

    4

    3

    3.4Pump Perormance andControl [4], [6], [8]

    3.4.1Operating Point

    The operating point o a centri-ugal pump, also called its duty

    point, is given by the intersec-

    tion o the pump characteristic

    curve (see section ..6) with

    the system characteristic curve

    (see section ..). The fow

    rate Q and the developed head

    H are both determined by the

    intersection. To change the op-

    erating point either the system

    curve or the pump curve must

    be changed.

    A system characteristic curve

    or pumping water can only be

    changed

    by changing the fow resist-

    ance (or example, by chang-

    ing the setting o a throttling

    device, by installing an orice

    or a bypass line, by rebuildingthe piping or by its becoming

    incrusted) and/or

    by changing the static head

    component (or example, with

    a dierent water level or tank

    pressure).

    A pump characteristic curve can

    be changed

    by changing the speed o rota-

    tion (see section .4.),

    by starting or stopping pumps

    operated in series or parallel

    (see sections .4.4 or .4.5),

    or pumps with radial impel-

    lers, by changing the impel-

    lers outside diameter (see sec-

    tion .4.6),

    or pumps with mixed fow

    impellers, by installing or

    changing the setting o in-

    stalled pre-swirl control

    equipment (see section .4.8),

    or axial fow (propeller)

    pumps, by changing the blade

    pitch setting (see section

    .4.9).

    Please note: the eect o these

    measures or changing the char-

    acteristic curve can only be pre-

    dicted or non-cavitating opera-

    tion (see section .5).

    3.4.2Flow Control by Throttling

    Changing the fow rate Q by

    operating a throttle valve is the

    simplest fow control method

    not only or a single adjustment

    o the fow rate but also or

    its continuous control, since it

    requires the least investment.

    But it is also the most energy

    wasting method, since the fow

    energy is converted irreversibly

    to heat.

    Fig. 4 illustrates this process:

    by intentionally increasing the

    system resistance (or exampleby throttling a valve on the

    1;=

    1;=

    (;=

    "

    "

    0

    0

    0;=

    0UMPCHARAC

    TERISTICCURVE

    4HROTTLING

    3URPLUSHEAD

    3YSTEMHEAD

    REQUIREMENT

    3YSTEMCURVE( SYS

    3YSTEMCURVE(SYS

    0OWERSAVED

    Fig. 24: Change o the operating point and power saved by

    throttling a pump whose power curve has a positive slope

    Pump Perormance Operating Point Throttling

  • 7/30/2019 Selecting Centrifugal Pumps Data

    35/92

    5

    3

    pump discharge side) the origi-nal system curve Hsys becomes

    steeper and transorms into

    Hsys. For a constant pump

    speed, the operating point B on

    the pump characteristic moves

    to B at a lower fow rate. The

    pump develops a larger head

    than would be necessary or

    the system; this surplus head is

    eliminated in the throttle valve.

    The hydraulic energy is irrevers-

    ibly converted into heat which

    is transported away by the fow.

    This loss is acceptable when

    the control range is small or

    when such control is only sel-

    dom needed. The power saved

    is shown in the lower part o

    the gure; it is only moderate

    compared with the large surplus

    head produced.

    D"L

    D

    !REARATIOD"LD

    4HROTTLINGC

    OEFFICIENTF

    Fig. 25: Orice plate and its throttling coecient

    The same is principally trueo the installation o a xed,

    sharp-edged orifce plate in the

    discharge piping, which can be

    justied or low power or short

    operating periods. The neces-

    sary hole diameter dBl o the

    orice is calculated rom the

    head dierence to be throttled

    H, using the ollowing equa-tion:

    dBl = Q/ g H (20)

    where

    dBl Hole diameter o the orice

    in mm

    Throttling or pressure drop

    coecient acc. to Fig. 5

    Q Flow rate in m/h

    g Gravitational constant

    9.8 m/s

    H Head dierence to bethrottled in m

    Since the area ratio (dBl/d)

    must be estimated in advance,

    an iterative calculation is neces-

    sary (plotting the calculated vs.

    the estimated diameter dBl is

    recommended so that ater two

    iterations the correct value can

    be directly interpolated, see

    example calculation 8.0).

    3.4.3

    Variable Speed Flow Control

    At various speeds o rotation n,

    a centriugal pump has dier-

    ent characteristic curves, which

    are related to each other by the

    anity laws. I the characteris-

    tics H and P as unctions o Q

    are known or a speed n, then

    all points on the characteristic

    curve or n can be calculated

    by the ollowing equations:

    Q = Q . n/n (21)

    H = H (n/n) (22)

    P = P (n/n) (23)

    Eq. () is valid only as long

    as the eciency does not de-crease as the speed n is reduced.

    With a change o speed, the op-

    erating point is also shited (see

    section .4.). Fig. 6 shows the

    H/Q curves or several speeds o

    rotation; each curve has an in-

    tersection with the system char-

    acteristic Hsys. The operating

    point B moves along this system

    curve to smaller fow rates when

    the speed o rotation is reduced.

    Orice Plate Variable Speed

  • 7/30/2019 Selecting Centrifugal Pumps Data

    36/92

    6

    I the system curve is a parabola

    through the origin as or Hsys

    in the example, the developed

    head H according to Eq. () is

    reduced to one ourth its value

    and the required driving power

    in Eq. () to one eighth itsvalue when the speed is halved.

    The lower part o Fig. 6 shows

    the extent o the savings Pcompared with simple

    throttling.

    I the system curve is a parabola

    with a large static head compo-

    nent as or Hsys, it is possible

    that the pump characteristic at

    reduced speed has no intersec-

    Fig. 26: Operation o a variable speed pump or dierent system

    characteristic curves Hsys1 and Hsys2(Power savings P1 andP2 at hal load each compared with simplethrottling)

    1;=

    1;=

    (;=

    (!

    (!

    (!

    0

    0

    (!

    "

    0;=

    ]

    N

    N

    N

    0

    0

    0

    (EADREQUIRED

    (!STAT

    Powersaved

    3

    tion with it and hence, that no

    operating point results; the low-

    er speed range is then o no use

    and could be eliminated. The

    potential power savings Pat a given fow rate Q are less

    than or the system curve Hsysas shown in the lower part o

    the diagram [4]. The improve-

    ment compared with throttling

    decreases as the static head

    component Hsys,stat increases

    (i.e., or a lower dynamic head

    component Hsys,dyn).

    Variation o the speed usually

    means varying the electrical

    driving requency, which must

    be considered when choosing

    the motor. The expenditure or

    variable speed drives is not low,

    but it is amortized quickly or

    pumps which are used oten and

    which are requently requiredto run at reduced fows with

    small static head component

    Hsys,stat [8]. This is particularly

    the case or pumps in heating

    systems.

    3.4.4Parallel Operation o Centri-ugal Pumps

    Where one pump is unable todeliver the required fow Q at

    the operating point, it is possi-

    ble to have two or more pumps

    working in parallel in the same

    piping system, each with its

    own non-return valve (Fig. 7).

    Parallel operation o pumps is

    easier when their shuto heads

    H0 are all equal, which is the

    case or identical pumps. I the

    shuto heads H0 dier, the low-

    est shuto head marks the point

    on the common H/Q curve or

    the minimum fow rate Qmin,

    below which no parallel opera-

    tion is possible, since the non-

    return valve o the pump with

    smaller shuto head will be held

    shut by the other pump(s).

    During parallel pumping it

    must be kept in mind that aterstopping one o two identical

    centriugal pumps (Fig. 7),

    the fow rate Qsingle o the re-

    maining pump does not all

    to hal o Qparallel, but rather

    increases to more than hal. The

    remaining pump might then

    immediately run at an operat-

    ing point Bsingle above its design

    point, which must be considered

    Variable Speed Parallel Operation

  • 7/30/2019 Selecting Centrifugal Pumps Data

    37/92

    7

    3

    when checking the NPSH values

    (see section .5) and the drive

    power (see section ..). The

    reason or this behaviour is the

    parabolic shape o the system

    characteristic Hsys. For the samereason, the reverse procedure o

    taking a second identical pump

    on line does not double the fow

    rate Qsingle o the pump that

    was already running, but rather

    increases the fow rate less than

    that:

    Qparallel

  • 7/30/2019 Selecting Centrifugal Pumps Data

    38/92

    8

    3

    3.4.5

    Series Operation

    In series operation, the pumps

    are connected one ater the

    other so that the developed

    heads can be added or a given

    fow rate. This means that the

    discharge pressure o the rst

    pump is the inlet pressure or

    the second pump, which must

    be considered or the choice o

    shat seal and or the strength

    o the casing. For this reason

    multistage pumps are usually

    used or such applications (ex-

    cept or the hydraulic transporto solids, see section 6). They

    do not pose these shat sealing

    problems.

    3.4.6

    Turning Down Impellers

    I the fow rate or developed

    head o a radial or mixed fow

    centriugal pump are to be

    reduced permanently, the out-

    side diameter D o the impeller

    should be reduced. The reduc-

    tion should be limited to the

    value or which the impeller

    vanes still overlap when viewed

    radially. The documentation o

    the pump characteristics (Fig.

    8) usually shows curves or

    several diameters D (in mm).

    Impellers made rom hard ma-terials, such as those used or

    solids-handling pumps, or rom

    stainless steel sheet metal, as

    well as single vane impellers

    (Fig. 4) and star or periph-

    eral pump impellers cannot be

    turned down. (The same is true

    or under-ling as described in

    section .4.7). For multistage

    pumps, usually only the vanes

    Dt

    Dr

    D1

    but not the shrouds o the im-

    pellers are cut back. It is some-

    times possible to simply remove

    the impeller and diuser o one

    stage o a multistage pump and

    replace them with a blind stage(two concentric cylindrical cas-

    ings to guide the fow) instead

    o cutting back the impeller

    vanes. Impellers with a non-

    cylindrical exit section are either

    turned down or have only their

    blades cut back as specied in

    the characteristic curve litera-

    ture (or example, as shown in

    Fig. 9).

    I the impeller diameter only

    needs to be reduced slightly, a

    rule o thumb can be applied.

    An exact calculation cannot be

    made, since the geometrical sim-

    ilarity o the vane angle and exit

    width are not preserved when

    turning down the impeller. The

    ollowing approximate relation-

    ship exists between Q, H and

    the impeller diameter D to beound (averaged, i required):

    (Dt/Dr) Qt/Qr Ht/Hr (26)

    where subscript t designates the

    condition beore the reduction

    Fig. 29: Contour or cutting

    back the vanes o an impeller

    with a mixed fow exit

    o the impeller outer diameter

    and index r the condition ater

    the reduction. The required

    (average) reduced diameter re-

    sults as:

    DrDt (Qr/Qt)Dt (Hr/Ht) (27)

    The parameters needed to deter-

    mine the reduced diameter can

    be ound as shown in Fig. 0:

    in the H/Q curve (linear scales

    required!) a line is drawn con-

    necting the origin (careul: some

    scales do not start at zero!) and

    the new operating point Br . The

    extension o the line intersects

    the characteristic curve or ull

    diameter Dt at the point Bt. In

    this way the values o Q and H

    with the subscripts t and r can

    be ound, which are used with

    Eq. (7) to nd the desired re-

    duced diameter Dr.

    The ISO 9906 method is more

    accurate, but also more involvedthrough the consideration o

    the average diameter D o the

    impeller leading edge (sub-

    script ), valid or nq < 79 and

    or a change o diameter < 5%,

    as long as the vane angle and

    the impeller width remain con-

    stant. Thus using the nomen-

    clature o Figs. 9 and 0:

    Series Operation Impeller Diameter Reduction

  • 7/30/2019 Selecting Centrifugal Pumps Data

    39/92

    9

    3

    "T

    1T

    "R

    1R

    (T

    $T

    (R

    $R

    usin

    gEq

    .28

    using

    Eq.26

    Totaldevelopedhe

    adH

    Flow rate Q

    Fig. 30:

    Determination

    o the reduced

    impeller dia-

    meter Dr

    A solution is only possible when

    D is known and when a para-

    bola H ~ Q is drawn through

    the reduced operating point Br

    (with Hr and Qr), not a line as

    n

    (DrD)/(DtD) = Hr/Ht = (Qr/Qt) (28)

    in Fig. 0, which intersects the

    base H/Q curve or diameter Dt

    at a dierent point Bt (with di-

    erent Ht and Qt).

    Fig. 31: Under-led vanes o a

    radial impeller

    Fig. 32: Characteristic curve set o a centriugal pump with pre-swirl

    control equipment, nq 160

    HHOPT

    /PERATINGLIMIT

    0RESWIRLCONTROLSETTING

    2ELATIVEFLOWRATE11OPT

    2ELATIVEDE

    VELOPED

    HEAD

    ((OPT

    3.4.8Pre-Swirl Control o the Flow

    For tubular casing pumps with

    mixed fow impellers, the pump

    characteristic can be infuenced

    by changing the pre-rotation

    in the impeller inlet fow. Such

    pre-swirl control equipment is

    oten tted to control the fow

    rate. The various characteristic

    curves are then shown in the

    product literature labelled with

    the control setting (Fig. ).

    3.4.9

    Flow Rate Control or Changeby Blade Pitch Adjustment

    The characteristic curves o ax-

    ial fow (propeller) pumps can be

    altered by changing the setting

    o the propeller blade pitch. The

    setting can be xed and rmly

    bolted or a device to change the

    blade pitch during operation

    can be used to control the fow

    rate. The blade pitch angles are

    3.4.7Under-ling o ImpellerVanes

    A small, permanent increase o

    the developed head at the best

    eciency point (up to 4 6%)

    can be achieved or radial im-

    pellers by ling the back sides o

    the backward-curved vanes, i.e.,

    by sharpening the vanes on the

    concave side, as shown in Fig.

    . The shuto head does not

    change. This method is suitable

    or minor nal corrections.

    Impeller Diameter Reduction Under-ling Pre-swirl Blade Pitch Adjustment

  • 7/30/2019 Selecting Centrifugal Pumps Data

    40/92

    40

    3

    shown in the product literature

    with their respective characteris-

    tic curves (see Fig. ).

    3.4.10Flow Control Using a Bypass

    The system characteristic curve

    can be made steeper by closing

    a throttle valve, but it can also

    be made fatter by opening a

    bypass in the discharge piping

    as shown in Fig. 4. The pump

    operating point moves rom B

    to a larger fow rate B. The

    bypass fow rate is controlled

    and can be ed back into theinlet tank without being used

    directly. From the point o view

    o saving energy, this type o

    control only makes sense when

    the power curve alls or in-

    creasing pump fow rates (P >

    P), which is the case or high

    specic speeds (mixed and axial

    fow propeller pumps).

    For these types o pumps, con-trolling the fow by pre-swirl

    control or by changing the blade

    pitch is even more economical,

    however. The expenditure or a

    bypass and control valve is not

    small [4]. This method is also

    suitable or preventing pumps

    rom operating at unacceptably

    low fow rates (see operating

    limits in Figs. 5 and 6c as well

    as in Figs. and ).

    HHOPT

    /PERATINGLIMIT

    "LADEPITCHSETTING

    2ELATIVEFLOWRATE11OPT

    2ELATIVEDEVELOPED

    HEA

    D

    ((OPT

    1;=

    1;=

    (;=

    "

    "

    0

    0

    0;=

    -

    "YPASSFLOWRATE5SEFULFLOWRATE

    3URPLUSHEAD

    (EADREQUIRED

    BYTHESYSTEM

    3YSTEMCURVE

    WITHOUTBYPASS0UMP

    CHARACTERISTIC

    3YSTEMCURVE

    WITHBYPASS

    0OWERSAVED

    Fig. 33: Characteristic curve set o an axial fow pump with blade

    pitch adjustment, nq 200

    Fig. 34: Characteristic curves and operating points o a pump with

    a alling power curve and fow control using a bypass. (For a radial

    fow pump the power curve would increase towards the right and

    this type o control would cause an increase in power input, see

    Fig. 5).

    Blade Pitch Adjustment Bypass

  • 7/30/2019 Selecting Centrifugal Pumps Data

    41/92

    4

    3

    3.5Suction and Inlet Conditions[3]

    NPSH = Net Positive Suction

    Head

    3.5.1

    The NPSH Value o theSystem: NPSHa

    The NPSHa value is the dier-

    ence between the total pressure

    in the centre o the pump inlet

    and the vapour pressure pv,

    expressed as a head dierence

    in m. It is in certain respects a

    measure o the probability o

    vaporization at that location

    and it is determined only by

    the operating data o the sys-

    tem and the type o fuid. The

    vapour pressure o water and

    other liquids are shown in Table

    and in Fig. 5 as a unction

    o the temperature.

    Carbon

    disulph

    ide

    !CETON

    E"E

    NZOL

    N"UT

    ANE

    %TH

    ANE

    %TH

    ANOL

    $IETH

    YLETH

    ER

    0ROPANE

    I"

    UTA

    NE

    "ENZOL

    0HE

    NOL

    4OLU

    OL

    !NILIN

    E

    -ETH

    ANOL

    !CETO

    NE

    !CETICACID&

    ORMIC

    ACID

    'LY

    CERIN

    #ARB

    ON

    DIS

    ULPHID

    E

    !MM

    ONI

    A

    3ULP

    HURDIOXI

    DE

    #ARBO

    NTETRACHL

    ORID

    E

    "ENZOL

    n #

    BAR

    4EMPERATURET

    6APOURPRESSURE

    P6

    Fig. 35: Vapour pressure pv o various fuids as a unction o the

    temperature t (or an enlarged view see page 84)

    Suction and Inlet Conditions NPSH Available

  • 7/30/2019 Selecting Centrifugal Pumps Data

    42/92

    4

    Table 12: Vapour pressure pv, density and kinematic viscosity o water at saturation conditions as a

    unction o the temperature t

    3 NPSH Available Data or Water

    t pv C bar kg/m mm/s

    0 0.006 999.8 .79 0.00656 999.9 0.00705 999.9 0.00757 000.04 0.008 000.05 0.0087 000.06 0.0095 999.97 0.000 999.98 0.007 999.89 0.046 999.7

    0 0.07 999.6 .07

    0.0 999.5 0.040 999.4 0.0496 999.4 0.0597 999.5 0.070 999.06 0.086 998.8

    7 0.096 998.78 0.006 998.59 0.096 998.40 0.07 998. .004

    0.0485 997.9 0.064 997.7 0.0808 997.54 0.098 997.5 0.067 997.06 0.060 996.77 0.0564 996.48 0.0779 996.

    9 0.04004 995.80 0.044 995.6 0.80

    0.0449 995.

    0.0475 994.9 0.0509 994.64 0.058 994.5 0.056 99.96 0.05940 99.57 0.0674 99.8 0.0664 99.99 0.0699 99.640 0.0775 99. 0.658

    4 0.07777 99.84 0.0898 99.44 0.0869 99.044 0.0900 990.645 0.0958 990.46 0.0085 989.8

    47 0.06 989.48 0.6 988.949 0.76 988.550 0.5 988.0 0.55

    5 0.960 987.75 0.6 987.5 0.49 986.754 0.500 986.55 0.574 985.756 0.6509 985.57 0.7 984.758 0.846 984.59 0.905 98.760 0.990 98. 0.474

    t pv C bar kg/m mm/s

    6 0.086 98.66 0.84 98.6 0.85 98.664 0.9 98.65 0.50 980.566 0.64 980.067 0.7 979.468 0.856 978.869 0.98 978.70 0.6 977.7 0.4

    7 0.5 977.7 0.96 976.67 0.54 976.074 0.696 975.475 0.855 974.876 0.409 974.77 0.489 97.7

    78 0.465 97.079 0.4547 97.580 0.476 97.8 0.65

    8 0.49 97.8 0.5 970.68 0.54 969.984 0.5557 969.485 0.5780 968.786 0.600 968.87 0.649 967.488 0.6495 966.789 0.6749 966.090 0.70 965. 0.6

    9 0.78 964.79 0.756 964.09 0.7849 96.94 0.846 96.695 0.845 96.996 0.8769 96.97 0.9095 960.498 0.940 959.899 0.9776 959.0

    00 .0 958. 0.95

    0 .0878 956.804 .668 955.506 .504 954.008 .90 95.60 .47 95.0

    .56 949.6

    4 .66 948.06 .7465 946.48 .868 944.80 .9854 94. 0.460

    .44 94.54 .50 99.86 .9 98.8 .544 96.50 .70 94.8

    .8668 9.4 .040 9.46 .4 99.68 .47 97.940 .64 96. 0.60

    t pv C bar kg/m mm/s

    45 4.55 9.750 4.760 96.9

    55 5.4 9.60 6.80 907.4 0.890

    65 7.008 90.470 7.90 897.

    75 8.95 89.80 0.07 886.9 0.697

    85 .4 88.490 .55 876.0

    95 .989 870.00 5.550 864.7 0.579

    05 7.45 858.70 9.080 85.8

    5 .06 846.60 .0 840. 0.488

    5 5.504 84.00 7.979 87.

    5 0.65 80.640 .480 8.6 0.40