End Suction Fire PumpsetFDXBSD Series

www.dynamixpumps.com

E N G I N E E R E D T O B E T H E B E S T

Diesel Engine Driven

LHCD SERIES

Selected Models

Page 2: Selected Models FDXBSD Series End Suction Fire Pumpsetdynamixpumps.com/wp-content/uploads/2017/01/FDXBSD_Firepump… · 9. Jockey Pump Controller Details The jockey pump shall be

Dynamix Hydro Systems

Dynamix offers the FDXBSD series state-of-the-art fire pumpset with a diesel engine driven, horizontal end suction pump.

These pumpsets are typically used in fire-fighting applications for supplying water to fire hose reels, fire hydrants or sprinkler systems.

FDXBSD Pumps have a discharge range from 500 to 3000 USgpm (1892.7 to 11,352 l/m) and a head range from 40 to 230 psi.

The fire pumpsets meet or exceed the requirements of NFPA 20.

Installation of these pumpsets ensures the safety of human life, buildings, expensive plants and equipments.

FDXSD fire pumpset shall be used only where a positive suction is provided as specified in NFPA 20.

The fire pumpset typically consists of the following components:• Pump• Diesel engine assembled with

- cooling system- fuel system- battery system- exhaust system

• Fire pump controller• Suction and discharge gauges• Air relief valve• Common base plate

Note: For your jockey pump requirements kindly refer our literature for DXBS pumps.* All above equipment, except fuel supply tank and fire pump controller, are mounted on a common base frame.* Dynamix can also supply Packaged fire pumping system with all

required accessories ready for site installation.

FDXBSD Series Horizontal End Suction Fire PumpsetIntroduction Applications

• Commercial complexes and high rise buildings• Petrochemical industries and gas plants• Oil and Gas on-shore & off-shore platforms• Oil terminals• Airports and ports• Marine applications• Power stations and transformer stations• Chemical industries• Manufacturing plants• Fire-work industries• Warehouses

Features and Benefits• State-of-the-art design fire pumping system.• NFPA-20 design• Compact diesel engine driven pump package• Rugged construction• More economical than Horizontal Split Case diesel packages• Back pull-out design which simplifies inspection and maintenance

without disturbing pipe work• Impellers are dynamically balanced to grade6.3 of ISO 1940• Low NPSH requirements• Automatic air relief valve• Efficient operation• Lower initial cost• Reduced installation time and cost• Simplified piping design• Suitable for space saving installation and retrofit applications• Easy access to all working parts• Ease of maintenance• Single source unit responsibility.

Model Reference Key

FDXBS D 100400 B 040Type Range: Single-Stage

End Suction Pump

Fire Pumpset: D = Diesel Engine

Driven Pump

Model: Engine Speed: B = 1500 rpmC = 1800 rpmD = 2000 rpm

Diesel Engine Rating:

040 = 40 HP600 = 600 HP

End Suction Fire Pumpset

Page 3: Selected Models FDXBSD Series End Suction Fire Pumpsetdynamixpumps.com/wp-content/uploads/2017/01/FDXBSD_Firepump… · 9. Jockey Pump Controller Details The jockey pump shall be

Performance Range

18931514

17035678

37852839

2271

Q (USgpm)

4001500

1000750

600500

45030 50 70 90

110

130

150

170

190

p (psi)

100

150

200

250

300

350

400

H ft.

Q (l/min)

400 USgpm79 - 123 psi

1500 USgpm50 - 78 psi

1000 USgpm56 - 96 psi

750 USgpm49 - 160 psi

600 USgpm55 - 165 psi

500 USgpm47 - 148 psi

450 USgpm76 - 120 psi

NOMINAL FLOW[USgpm]

Diesel Engine Speed (rpm)1500 1800 2000

400 ü ü ü450 ü500 ü ü600 ü ü ü750 ü ü

1000 ü1500 ü ü

üAvailable

FDXBSD Diesel 400 - 15000 USgpm 50 Hz

End Suction Fire Pumpset

Dynamix Hydro Systems

Page 4: Selected Models FDXBSD Series End Suction Fire Pumpsetdynamixpumps.com/wp-content/uploads/2017/01/FDXBSD_Firepump… · 9. Jockey Pump Controller Details The jockey pump shall be

End Suction Fire Pumpset

Design Features

1. Pump Controller• State-of-the-art designed to specifically to meet the

NFPA 20• Controller uses PLC technology to control automatic

engine and alternation between batteries during cranking

• Monitors and records system alarms and pressure, battery voltage and engine functions

• Standard NEMA 2 enclosure, corresponding to IP 31• Available with 12V DC operation as standard, 24V

DC operation on request• Simple start-up and maintenance procedures• Human Interface Device (HMI), manual start

pushbuttons, stop push button and AUTO-OFF-MANUAL selector switch are located on the exterior door for easy access.

6. Fuel Supply Tank• Designed and sized according to NFPA 20.

2. Diesel Engine• Engine with silencer and flexible

exhaust• Power safety factor as per NFPA 20• Each diesel fire pump set is factory

tested• Radiator cooled standard, heat

exchanger cooled on request• Drive shaft

3. Coupling• Flexible pin-bush type coupling• Highly flexible, resilient • Maintenance free

4. Base Frame• Robust designed fabricated steel

base frame for stable mounting• Lifting points provided on the base

frame for loading and unloading

5. Battery Set• 12V/24V battery set provide redundant

power supply and ensure full reliability• Sized according to NFPA 20.

1

2

6

54

3

Dynamix Hydro Systems

Page 5: Selected Models FDXBSD Series End Suction Fire Pumpsetdynamixpumps.com/wp-content/uploads/2017/01/FDXBSD_Firepump… · 9. Jockey Pump Controller Details The jockey pump shall be

The fire pumpset supplied by Dynamix shall include the pump, diesel engine, controller and fittings as detailed in the following technical specifications. All the materials supplied shall be installed as recommended in NFPA 20.

Technical Specifications

1. Pump Technical DetailsThe fire pump shall be horizontal, centrifugal single/two stage end suction, construction specifically labeled for fire service and shall be a Dynamix pump type . The fire pump shall be designed to deliver USgpm of clear water at a total differential pressure of psig. The pump shall be connected to the (fire standpipe) (fire sprinkler) (underground fire main) system. The suction supply for the fire pump shall be from a (public service water main) (elevated storage tank) (ground storage tank) (underground reservoir) at a maximum pressure of psig and a minimum pressure of psig. The pump shall be axially split into two half, upper half and lower half. Lower half shall comprise a radial suction port and radial discharge port. Suction and discharge connections shall be on the same plane. Upper half and rotating parts shall be removable and can be dismantled without disturbing the pipe work. Pump casing shall be of cast iron and fitted with replaceable bronze wear ring. Impeller shall be bronze, enclosed type dynamically balanced and keyed to an alloy steel shaft. Shaft shall to be fitted with replaceable S.S AISI 410 sleeves. Shaft shall be mounted in two deep grooves and regreasable ball bearings. Each stuffing box shall be fitted with lantern rings and graphite gland packing rings. Packing rings shall be removable without disturbing wetted parts or the pump bearings.

2. Diesel Engine DetailsThe fire pump driver shall be a horizontal shaft type internal combustion diesel engine manufactured by: Model no. with maximum power rated kW at rpm. The fire pump shall be directly coupled through flexible coupling to a diesel engine.

3. Standard Accessories DetailsThe pump shall be supplied with the following accessories:•Combinationsuctiongauge,3½”dialtypewith¼”cockandleverhandle-1no.•Airreleasevalve-1no.•Dischargegauge,3½”dialtypewith¼”cockandleverhandle-1no.

4. Fire Pump Controller DetailsThe fire pump controller shall be factory assembled, wired and tested as a unit prior to shipment. The controller shall be available for either 12VDC or 24VDC systems. The controller shall include the following standard features:•NEMAtype2(IP31)dripproofmetalwallmountorfreestandingenclosure•Dualsolidstatebatterychargers•Twoouterdoormountedcrankpushbuttonsandtwoinnerpanelmountedbatteryon/offswitches•OuterdoormountedkeyoperatedAUTO,OFF,MANUAL,modeselectorswitch•Thecontrollershallbesuppliedwithasolidstatepressuretransducerwitharangeofpsiformonitoringsystempressureandprovidingthefeedbackto the controller•TouchscreencolorHumanInterfaceDevice(HMI)displayshallbeprovidedofminimum5inchsizecapableofbeingreadinbothdirectsunlightordarklightingconditions•TouchscreenpushbuttonsshallbeprovidedonHMIforeasyscreennavigation,alarmreset,andalarmsilencing•ControllersettingsshallbeprogrammablethroughtheHMIandshallbeprotectedbypasswords•AllfeaturesshallbeenabledordisabledthroughtheHMI,nojumpersorexternalwiresshallbeneededorallowedtoactivateordeactivateafeature•ThesystemstatusdatashallbedisplayedontheHMI•Audiblealarmshallbeprovidedwithalarmsilencefeatureforsilenceablealarms•Dataloggingshallbepossiblewithrealtime/dateclocktostorethecontinuouspressurelog,eventlog,alarmlogandalluserchangeablesetpointsandsystemdata. Battery backup of any kind shall not be allowed•ThecontrollershallbeprovidedwithaUSBportcapableofacceptingUSBflashmemorydisktodownloadhistoricaldataofevents,alarmsandpressurelogs•ThecontrollershallfeatureaRS485serialcommunicationportforusewith2or4wireModBusRTUcommunication•Anticondensationspaceheaterscanbeprovidedwhencontrollerisinstalledinabasementhavinghighhumidity(optional).

5. Battery Set Details•Eachengineshallbeprovidedwithtwostoragebatteryunits.•Electrolyteshallbeaddedaminimumof24hourspriortothetimetheenginehastobestarted•Batteriesshallbekeptchargedatalltimesandtestedfrequently(weeklytest)todeterminecondition•Onlydistilledwatershallbeused•Batteryplatesshallbekeptsubmergedatalltimes.

Dynamix Hydro Systems

End Suction Fire Pumpset

Page 6: Selected Models FDXBSD Series End Suction Fire Pumpsetdynamixpumps.com/wp-content/uploads/2017/01/FDXBSD_Firepump… · 9. Jockey Pump Controller Details The jockey pump shall be

Technical Specifications6. Fuel Supply Tank Details•Thefuelsupplytankshallbesingle/doublewalledconstructionconformingtoUL142•Thefuelsupplytankandfuelshallbereservedexclusivelyforthefirepumpdieselengine•Thereshallbeseparatefuelsupplytankforeachengine•Thereshallbeaseparatefuelsupplyandreturnline(ifrequired)foreachengine•Thefuelsupplytankoutletshallbelocatedsothatitsopeningisnolowerthantheleveloftheengine’sfueltransferpump•Insiteswheretemperaturesbelow0°C(32°F)couldbeencountered,thefuelsupplytankshallbelocatedinthepumproom•Amechanicalfuellevelgaugeshallbeprovidedtoshowapproximatefuellevelinthefuelsupplytank•Thefuelsupplytankshallhaveafillconnectionwitha2inchlockablefuelcap•Thefuelsupplytankshallhaveadrainconnectionofatleast1inchconnection•ThefuelsupplytankshallhaveregularandemergencyscreenedventconnectionasperUL142•Fuelsupplypipeconnectionwithvalveshallbeprovidedabove5%capacityoftank•Thefuelsupplytankshallbeprovidedwitha2inchNPTthreadedportonthetopofthefuelsupplytanktoaccomodatethelowfuellevelswitch•Fordoublewalledtanka2inchthreadedportshallbeprovidedintheoutertanktoaccomodateafueldetectorwhichwillhelpindetectionofinnertankleakage.

7. Base Frame Details•Apumpandaengineshallbemountedonacommonbaseframe•Thebaseframeshallhavemachinedmountingsurfacesforpumpsaswellasdieselengine•Liftingpointsshallbeprovideonthebaseframeforloadingandunloading•ThebaseplatewillbeprovidedwithholestoaccommodateheavydutyanchorboltsformountingitontheRCCfoundation.

8. Jockey Pump DetailsThe jockey pump shall be manufactured by Dymanix Model no. for a capacity of USgpm at a pressure boosting of psig. The jockey pump shall be driven by a TEFC electric motor of HP, rpm, Volt, Phase, Hz.

9. Jockey Pump Controller DetailsThe jockey pump shall be controlled by an automatic jockey pump controller model .The jockey pump controller shall be factory assembled, wired and tested as a unit prior to shipment. The controller shall include the following standard features:•NEMAtype2(IP31)dripproofmetalfreestanding/wallmountingenclosure•Thecontrollershallhaveafusedhorsepowerrateddoorinterlockedrotaryswitch•Thecontrollershallbeofcombinedmanualandautomatictypedesignedforoneofthefollowingstartingmethods(a)DOL(b)Star/Delta(c)Softstarter•Thecontrollershallprovideprotectionagainstoverloadandsinglephasing•Thecontrollershallbesuppliedwithasolidstatepressuretransducerwitharangeofpsiformonitoringsystempressureandprovidingthefeedbackto the controller•TouchscreencolorHumanInterfaceDevice(HMI)displayshallbeprovidedofminimum3inchsizecapableofbeingreadinbothdirectsunlightordarklightingconditions•TouchscreenpushbuttonsshallbeprovidedonHMIforeasyscreennavigation,alarmreset,andalarmsilencing•ControllersettingsshallbeprogrammablethroughtheHMIandshallbeprotectedbypasswords•AllfeaturesshallbeenabledordisabledthroughtheHMI,nojumpersorexternalwiresshallbeneededorallowedtoactivateordeactivateafeature•ThesystemstatusdatashallbedisplayedontheHMI•Audiblealarmshallbeprovidedwithalarmsilencefeatureforsilenceablealarms•Dataloggingshallbepossiblewithrealtime/dateclocktostorethecontinuouspressurelog,eventlog,alarmlogandalluserchangeablesetpointsandsystemdata. Battery backup of any kind shall not allowed•ThecontrollershallbeprovidedwithaUSBportcapableofacceptingUSBflashmemorydisktodownloadhistoricaldataofevents,alarmsandpressurelogs.

10. Mounting and Testing DetailsThe pump shall be suitable for a maximum working pressure of . Each pump shall be hydrostatically tested at a pressure of not less than 1.5 times thenoflow(shutoff)headofthepump’smaximumdiameterimpellerplusthemaximumallowablesuctionheadbutinnocaselessthan250psig.Thepumpshallbeperformancetestedatratedspeed.Thepumpshallfurnishnotlessthan150%ofratedcapacityatapressurenotlessthan65%ofratedhead.Theshut-offtotalheadofthepumpshouldnotexceed140%oftotalratedhead.Acertifiedtestcurve,indicatingtheflow,head,powerandefficiencyshallbesupplied.Thefirepumpanddieselengineshallbebasemountedandalignedatthepumpmanufacture’sfactory.Finalalignmentshallbemadeafterinstallationonsite.

11. PaintingFire pump, Diesel engine & its controller, base plate and fuel tank are to be painted RAL 3002 as per NFPA 20.

DYNAMIX HYDRO SYSTEMS1321 Upland Dr., Suite 6926, Houston, TX, 77043 USATel/Fax:+1-713-474-9010•www.dynamixpumps.com