DISTRIBUTION SYSTEM SELECT YOUR GLOBAL SPECIALIST FOR ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

Embed Size (px)

Citation preview

Page 1: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

rand

dISTrIBuTIOn SySTEmSELECT yOUR

GLOBAL SPECIALIST FOR ELECTRICALAND DIGITAL BUILDING INFRASTRUCTURES

EXB1

3064

-Ju

ly20

13

artment- France8755

EXB13064-Couv-EN.indd 1 02/07/13 08:56

Page 2: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

Indistr

www.legrand

Distribution is an essential functionfor the electrical panels, as wellas for control and circuit protection.As well as purely technical factors(intensity, number of outputs, etc.),the choice of a distribution systemis critical regarding implementation,maintenance, operatingrequirements and possibilityof evolving the panels.To meet all specifications (practices,speed of implementation, ease ofmaintenance, continuity of service,etc.), Legrand offers three typesof solutions: “Standard” distribution,“Optimised” distribution and“Increased Saftey” distribution.All these solutions integrateperfectly with the Legrandpower and protection range.

EXB13064_01-17_EN.indd 2 02/07/13 09:40

Page 3: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

Universal solutions for traditional cabling...................................................... 4

The distribution systems at the heart of power offer...................................... 2

4-5Standard

distribution

Contents

Innovation for panel builders...........................................................................6Optimised distribution in XL3 400 and 800 enclosures ...................................8Optimised distribution in XL3 4000 enclosures .............................................10

6-11Optimised

distribution

12-17Increased Safety

distribution system

18-49Catalogue

pages

Increased Safety distribution system for high criticality sites......................12The VX³ IS and HX³ IS distribution systems ...................................................14VX³ IS and HX³ IS bases and distribution blocks............................................16

1www.legrand.com

sential functional panels, as well

ol and circuit protection.echnical factors

, number of outputs, etc.),tribution system

ding implementation,ating

s and possibilityving the panels.

ations (practices,ation, ease of

ontinuity of service,s three types

andard” distribution,tribution andy” distribution.

All these solutions integratey with the Legrand

ection range.

EXB13064_01-17_EN.indd 1 02/07/13 09:40

Page 4: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

Supply busbars Distributionblocks

Supports andbusbars

VX³ 63and 125 A HX³ 125 A

HX³80/125 Aplug-in

HX³ 400 A VX³System VX³ / HX³-ISXL³ enclosures

XL³ 160

XL³ 400

XL³ 800

XL³ 4 000

With its XL³ enclosures,the DX³ , DPX³, DPX, DMX³ranges of circuit breakersand three types of distribution,Legrand offers powerfulsolutions adapted to every site.

Distribution blocks and busbarsspecially designed to save timeand space in XL³ cabinetsand enclosures.See p. 6 to 11

Supply busbars, distributionblocks, busbar supports:universal solutions for all typesof panel up to 4000 A.See p.4

The univerSal SoluTionfor TradiTional cabling.

TimeSaving andincreaSed SafeTy

conTinuiTyof Service

For installations whavailability of enerIncreased Safety doffers three levelsSee p. 12 to 17

DISTrIbUTIOnAT THe HeArT OF

POWer

Standard diStribution HX³/VX³ optimiSed diStribution HX³/VX³ iS increaSed Safety

SIMPLIFIeD nAMIngSySTeM TO FACILITATeyOUr CHOICe:

HX³ xxxHorizontal

distributionMax. rating

Verticaldistribution

Max. rating

VX³ xxx

CHOOSe One OF LegrAnD'STHree DISTrIbUTIOn SOLUTIOnS

2www.legrand

EXB13064_01-17_EN.indd 2 02/07/13 09:40

Page 5: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

Ain

HX³ 400 A VX³System VX³ / HX³-IS

XL³ enCLOSUreSA range of robust, easy-to-cable cabinetsand enclosures, with a full choice ofequipment and accessories for any sizeinstallation up to 6 300 A.

XL PrO³Study software for designingOptimised and IncreasedSafety panels and selectingthe right products.

busbarsve times

conTinuiTyof Service

For installations which require a largeavailability of energy, the LegrandIncreased Safety distribution systemoffers three levels of service.See p. 12 to 17

ibution HX³/VX³ iS increaSed Safety diStribution SyStem

A COMPLeTe rAngeFOr ALL eLeCTrICAL PAneLS

CIrCUIT breAkIng AnD PrOTeCTIOnSeveral ranges of circuit breakers and switches,with a wide choice of breaking capacities andcharacteristics:- DX³: modular circuit breakers up to 125 A,- DPX³ and DPX: moulded case circuit breakers

up to 1600A,- DMX³: air circuit breakers up to 6300 A.

3www.legrand.com

tHe cHoice of diStribution

EXB13064_01-17_EN.indd 3 02/07/13 09:40

Page 6: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

The Legrand standarddistribution can be installedin any kind of enclosure andrespects working practices.

UnIVerSAL SOLUTIOnSFOr TrADITIOnAL

CAbLIngSUPPLy bUSbArSThey enable distribution to occurvery rapidly on the level of eachrow, in total safety, in every panel.They perfectly complement theVX³ automatic connection verticaldistribution blocks (see p. 7)

Supply busbars are available in one,two, three and four-pole versionsand in several lengths.

MODULArDISTrIbUTIOn bLOCkSThese are mounted on the DIn rail,next to the devices, in all distributionpanels. They allow complete freedomof distribution, using traditional cabling,up to 250 A. Their electrical andmechanical characteristics area guarantee of safety.

SUPPOrTSAnD bUSbusbars facilitatThe various Legrto be used within- vertical busbar on the si- vertical busbar- horizontal busbar

4www.legrand

EXB13064_01-17_EN.indd 4 02/07/13 09:40

Page 7: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

ngTrIbUTIOn bLOCkS

on the DIn rail,all distribution

omplete freedomtraditional cabling,ctrical andristics are

SUPPOrTSAnD bUSbArSbusbars facilitate power distribution in enclosures from 400 to 6300 A.The various Legrand isolating supports enable numerous configurationsto be used within an XL³ enclosure:- vertical busbar on the side or at the back of the enclosure,- vertical busbar in cable sleeve,- horizontal busbar at top or bottom of the enclosure.

InPUTAnD OUTPUTTerMInALS

COPPer/ALUMInIUMCOnneCTIOn bOXeSfacilitate thepreparation of powercable connections.They accept powercables up to 200 mm².

POWer TerMInALbLOCkSfacilitate the creationof output terminal blocksfor high power outputs.Various versions areavailable: copper oraluminium cables, with orwithout lugs, copper bars.

5www.legrand.com

Standard diStribution

EXB13064_01-17_EN.indd 5 02/07/13 09:40

Page 8: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

Legrand optimiseddistribution is designedto facilitate the workof the panel builder.It reduces fiddlycabling tasks and theneed to make copperbars, which requiresspecialist tools.The extent of theoptimised solutionson offer allows allrequirements to be met.

HX³ 80/125 A WITH PLUg-In COnneCTIOnHorizontal 4-pole distribution blocks forXL³ 160, 400, 800 and 4000 cabinets and enclosures.

VX³ 63 AnDAUTOMATICTerMInALSFour-pole verticalto power modular160 and 400 cabin

InnOVATIOnFOr PAneL

bUILDerS

THe ADVAnTAgeSOF OPTIMISeDDISTrIbUTIOnTIMeSAVIng- Automatic connections- Prefabricated connection kits

SPACe SAVIng- COmpact system, fully integrated

into XL³ enclosures- Increased safety- Less cabling, secure and lasting

connections, IP XXb protection

→ Installation on aluminium DIn rails.

→ Automatic, tool-free connection of upstream terminals to the distributionblock, with no cabling or tightening, even when the distribution block is livebut off-load. The power module itself cannot be handled when live.

→ Freedom to mix 1P, 1P+n, 2P, 3P and 4P devices on the same row

→ It is possible to supply the block via the four-pole power supply moduleor via the head of row MCb

→ Installation nextmaintaining fuldevices

→ Direct connectionaccessories toterminals for fl

Connection modules (L1, L2, L3, n).The phases are balanced freely by choosing the right connection module.

6www.legrand

EXB13064_01-17_EN.indd 6 02/07/13 09:40

Page 9: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

TIOn VX³ 63 AnD 125 AAUTOMATICTerMInALSFour-pole vertical distribution blockto power modular rows in XL³ 125,160 and 400 cabinets with 3-6 rows.

HX³ 125 AWITH AUTOMATICTerMInALSHorizontal 4-pole distribution blockfor XL³ 160, 400, 800 and 4000cabinets and enclosures.

AUTOMATICTerMInALS:gUArAnTeeOF SAFeTy

TIOn

distributionn block is livelive.

row

y module

Use of automatic connections savestime but it is also a guaranteeof safety: no risk of loosening norof forgetting to tighten a terminal.

→ Installation next to rows whilemaintaining full access to protectiondevices

→ Direct connection with no additionalaccessories to IP XXb automaticterminals for flexible or rigid wires

→ Installation between rows of devices

→ It is possible to mix 1P, 2P, 3P, 4Pcircuit breakers

→ Automatic terminals IP XXb for flexibleor rigid wiresmodule.

7www.legrand.com

optimiSed diStribution

EXB13064_01-17_EN.indd 7 02/07/13 09:40

Page 10: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

1

2

3

3

1

2

3

VX³ 400 OrIn CAbLe SLeeVe

A system designed to make lifesimple for panel builders withjust three types of product:vertical busbars, plug-indistribution blocks andconnection kits.

VX³ 400 Or VX³ 800 bUSbArAT bACk OF enCLOSUre

2 VX³ bUSbArinstalled at back of enclosure:optimised dimensions. C-sectiontinned copper aluminium busbarsusing a special process which ensureselectrochemical compatibility withthe copper busbars.

3 HX³ 250 A Or 400 A3-POLe DISTrIbUTIOn bLOCktakes DPX³ and DX³ devices viaplug-in support bases.

IP xxb distribution block with directfeed via busbar at rear of enclosureor via prefabricated kit and busbar incable sleeveConnection and disconnectionof devices possible even when livebut off-load.Support base for device, made upof two parts:- one fixed part which connects to

the distribution block with crimps- one mobile part which takes

the device

1 PreFAbrICATeD COnneCTIOn kITconnects the busbar to the main devicemounted in a vertical position on theplate (up to 1600 A).

OPTIMISeD DISTrIbUTIOn InXL3 400 AnD 800

enCLOSUreS

1

2

3

3

1

2

3

8www.legrand

EXB13064_01-17_EN.indd 8 02/07/13 09:41

Page 11: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

1

1

2

3

3

45

54

6

2

VX³ 400 Or VX³ 800 bUSbArIn CAbLe SLeeVe

closure:C-section

nium busbarss which ensures

ompatibility with

n bLOCkvices via

ock with directear of enclosurekit and busbar in

onnectionven when live

ice, made up

which connects tock with crimpsich takes

OnneCTIOn kITthe main device

osition on the

PrOTeCTIOn DeVICeS In VerTICAL POSITIOn1 Main devices in cable sleeve2 Prefabricated power supply kit (up to 630A)3 VX³ 400 or 800 busbars4 Connection kits for HX³ distribution blocks5 DPX³ and DX³ devices on HX³ 250/400

row distribution blocks6 Modular row with HX³ 80/125 A plug-in connection

distribution block

PrOTeCTIOn DeVICeS In HOrIzOnTAL POSITIOn1 Main device in enclosure2 Prefabricated power supply kit (up to 800A)3 VX³ 400 or 800 busbars4 Prefabricated connection kit5 Plate-mounted device

n In 800

reS

1

1

2

3

3

45

54

6

2

9www.legrand.com

optimiSed diStribution

EXB13064_01-17_EN.indd 9 02/07/13 09:41

Page 12: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

3

1

2

7

9

6

5

8

4

eXAMPLeOF A MAInFOr A SHOPPIngDeSIgnIng THe P

Main protection de2 DMX³ as supplyOutput protectio3 DPX 630 4P, 5 D

OPTIMISeD DISTrIbUTIOn In XL3 4000

enCLOSUreS

630 TO 3200 A VX³ bUSbAr

STAnDArD DISTrIbUenclosures depth

OPTIMISeD DISTrIbUenclosures depth 725 mm, 1 e

1 SCP busbar2 Linking interface between XL³ 4000 enclosure and SCP busbars3 DMX³ connection kit on SCP linking interface4 Connection kits for transfer5 VX³ 800/1600 busbar behind functional uprights or in cable sleeve6 Connection kits for power supply for VX³ busbars7 VX³ 800 busbar at back of enclosure8 HX³ 400 A row distribution blocks9 Prefabricated connection kits

3

1

2

7

9

6

5

8

4

10www.legrand

EXB13064_01-17_EN.indd 10 02/07/13 09:41

Page 13: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

eXAMPLe OF A COMPArATIVe STUDyOF A MAIn LV DISTrIbUTIOn bOArDFOr A SHOPPIng CenTreDeSIgnIng THe PAneL

Main protection device:2 DMX³ as supply invertersOutput protection:3 DPX 630 4P, 5 DPX³ 250 4P, 5 DPX³ 160 4P, 3 DX³ 4P, 10 DX³ 2P

n In

STAnDArD DISTrIbUTIOn SOLUTIOnenclosures depth 975 mm and 2 external cable sleeves

OPTIMISeD DISTrIbUTIOn SOLUTIOnenclosures depth 725 mm, 1 external cable sleeve, 1 internal cable sleeve.

In COMPArISOnWITH THeSTAnDArDSOLUTIOn:7 % LeSS WIDe

25 % LeSS DeeP

33 % FeWerWOrkIng HOUrSnot including the downstreamconnection of the DMX³ supplyinverter and the connectionof the modular devices and smallDPX³ MCCbs

STUDy COnDUCTeDWITH XL PrO³Study software for designingOptimised and Increased Safetyelectrical panels and selectingthe right products.

s

eeve

11www.legrand.com

optimiSed diStribution

EXB13064_01-17_EN.indd 11 02/07/13 09:41

Page 14: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

TEST

DISTrIbUTIOn

OPerATIOn iS X-- MAInTenAnCe iS -X-

THe IS SerVICerATIngFor the safety of persons,standard IeC 61439-1 & 2defines two concepts: theforms of separation and thewithdrawability index.Legrand goes further withthe IS service rating.The three numbers of the ISservice rating represent thelevel of response to servicecontinuity requirements inthree types of intervention:operation, maintenance andevolution.

1: low | 2: medium | 3: high

In light of increasingservice continuityrequirements, theability to work onpanels while they arelive is crucial.The Legrand IncreasedSafety distributionsolutions offer aninnovative responseto service continuityrequirements byproviding a viablealternative to draweredenclosures.

iS 1-- Complete shutdownof the panel.

iS 2-- Complete stop of thefunctional unit concerned.

iS 3-- Cutoff power contactsof the functional unit concerned.Allows automation test, in orderto check installation.

eVOLUTIOn

iS -1- Complete shutdownof the panel.

iS -2- Interruption limited to the functionalunit concerned. The replacement requiresan intervention on downstream connections.

iS -3- Interruption limited tothe functional unit concerned.The replacement will be completedwithout intervention on connections.

iS --3 Addition offunctional unit in alocation, without pthe panel.

iS --2 Interruptionto the functional ureserves of functiare planned.

iS --1 Completeof the panel.

This figure shows the panelaccessibility conditions for carryingout work on the installation.

This figure shows the panelaccessibility conditions formaintaining the installation.

This figure showsaccessibility conditthe installation.

IS FOr HIgHCrITICALITySITeS

12www.legrand

EXB13064_01-17_EN.indd 12 02/07/13 09:41

Page 15: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

nTenAnCe iS -X- FOrMS OF SePArATIOnThe forms of separation defined by IeC 61439-2 standardare the barriers to be put in place in distribution assembliesto ensure different levels of protection against contact withhazardous parts.

eVOLUTIOn iS --X

WITHDrAWAbILITy InDeXThe withdrawability index, according to standard IeC 61439-2,defines the type of electric connection for the functional units (FU).

Main criterion Sub-criterion ForMno internal separation Form 1

Separation of busbars and functional units.

terminals for external conductorsnot separated from busbars Form 2a

terminals for external conductorsseparated from busbars Form 2b

Separation of busbars and functional units andseparation of all functional units from each other.Separation of terminals for external conductorsfrom functional units but not the terminals for otherfunctional units.

terminals for external conductorsnot separated from busbars Form 3a

terminals for external conductorsseparated from busbars Form 3b

Separation of busbars and functional units andseparation of all functional units from each other.Separation of terminals for external conductorsassociated with one functional unit from those of allthe other functional units and the busbars.

terminals for external conductors in the samecompartment as the associated functional unit Form 4a

terminals for external conductors which are notin the same compartment as the functional unitwith which they are associated but in separateand enclosed protected spaces or individualcompartments

Form 4b

shutdown

imited to the functionalreplacement requireswnstream connections.

imited toncerned.be completed

on connections.

iS --3 Addition of any type offunctional unit in an unequippedlocation, without powering offthe panel.

iS --2 Interruption limitedto the functional unit concerned.reserves of functional unitsare planned.

iS --1 Complete shutdownof the panel.

e paneltions for

llation.

This figure shows the panelaccessibility conditions for evolvingthe installation.

1St letter 2nd letter 3rd letter

type of electricalconnection for themain incoming circuit

type of electricalconnection for themain outgoing circuit

type of electricalconnection for theauxiliary circuits

F = for fixed connectionsD = for disconnectable connectionsW= for withdrawable connections

corresponds to the following types ofcircuit breakers: fixed, plug-in, draw-out

13www.legrand.com

increaSed Safety diStribution SyStem

EXB13064_01-17_EN.indd 13 02/07/13 09:41

Page 16: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

1

2

3

6

4

7

7

7

5

CHOOSe yOUrFrOM AMOInCreASeDThe three Legrandof adding new devipower to the panel,traditional solution

VX3 IS AnD HX3 ISDISTrIbUTIOnSySTeMS

VX3 IS COLUMnCHASSISThe tinned cooper aluminium barsof the IS column chassis, thanksto their exclusive design, facilitateautomatic connection of the IS basesensuring the quality and longevityof the contacts.

1 XL³ 4000 enclosure, height2200 mm, depth 725 or 975 mm

2 VX³ IS column chassis deliveredwith isolating profiles to ensurethe IPXXb takes the VX³ IS bars(1250 A or 2000 A)

3 VX³ IS bases. The base is fixedon the VX³ IS column chassis.The withdrawable plate takesthe protection device.

4 Universal bases (IS 223, 233 and333), take any kind of functional unit

5 The HX³ IS 400 A row distributionblock takes moulded case andmodular devices

6 The HX³ IS 125 A row distributionblock takes modular devices

7 Partitioning - facilitating forms 3band 4b

ADVAnTAgeSOF THe LegrAnDInCreASeD SAFeTy(IS) DISTrIbUTIOnSySTeM:TIMeSAVIng- ease of fitting- ease of cabling (automatic

feed crimping)

SIMPLICITy AnD eCOnOMy- responds to all levels

of the IS service rating(ease of maintenanceand evolution while live)

- It is possible to powermotor controls

- IS 223 possible withmodular devices

- Safety of interventionfor users.

With its new IncreasedSafety distribution system,Legrand offers three levelsof service for so-calledhigh criticality sites whereit is impossible to shutdown the network formaintenance (hospitals,computer rooms, etc.)

iS 223 (DDF, FOrMHigh criticality siterequiring work on→ evolution of the

it is possible toto the panel.

iS 233 (DDD, FOrMHighly critical site,→ evolution + maint

no interventionno intervention

iS 333 (WWW, FOrMextremely critical→ evolution + maint

position test toare functioning

1

2

3

6

4

7

7

7

5

Products may be handled when livebut protection and switching devicesmust be off-load when being insertedor withdrawn.

14www.legrand

EXB13064_01-17_EN.indd 14 02/07/13 09:41

Page 17: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

CHOOSe yOUr SerVICe LeVeLFrOM AMOng THe THree LegrAnDInCreASeD SAFeTy (IS) SOLUTIOnSThe three Legrand solutions offer everybody the possibilityof adding new devices in unequipped locations, without cuttingpower to the panel, something that was unthinkable withtraditional solutions (withdrawable forms and devices).

ISn

Mn

ooper aluminium barsassis, thankssign, facilitate

ion of the IS basesand longevity

e, height25 or 975 mmssis deliverediles to ensure

he VX³ IS bars

VX³ IS bases. The base is fixedmn chassis.plate takesice.

sal bases (IS 223, 233 ande any kind of functional unit

ow distributionded case and

ow distributionlar devicesitating forms 3b

iS 223 (DDF, FOrM 3b):High criticality site, shutdown of functional unit permitted,requiring work on connections.→ evolution of the installation while live:

it is possible to add a device without cutting powerto the panel.

iS 233 (DDD, FOrM 3b):Highly critical site, power shutdown permitted for testing.→ evolution + maintenance while live:

no intervention on the upstream connection,no intervention on the downstream connection.

iS 333 (WWW, FOrM 3b):extremely critical site, continuity of service essential→ evolution + maintenance + operation while live:

position test to enable verification that the auxiliariesare functioning correctly.

SUMMAryOF THe LegrAnDreSPOnSeaccording to service indexstringency levels

Minim

umex

pecte

diS

legra

ndiS

solut

ioin

Maxim

umfor

min

legra

ndso

lution

Withd

rawab

ility

index

inle

grand

solut

ion

111 Fixedversions1 4b FFF

211 223 4b2 dFF/dFd221 223 4b2 dFF/dFd222 223 4b2 dFF/dFd223 223 4b2 dFF/dFd231 233 4b ddd232 233 4b ddd233 233 4b ddd311 333 4b WWW321 333 4b WWW322 333 4b WWW323 333 4b WWW331 333 4b WWW332 333 4b WWW333 333 4b WWW

1: with rotary handle on door for main device2: using external terminals

ndled when liveection and switching devices

en being inserted

15www.legrand.com

increaSed Safety diStribution SyStem

EXB13064_01-17_EN.indd 15 02/07/13 09:41

Page 18: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

11

1 12

2

23

3

3

4 4

4

5

The IS bases for DPXand DPX3 and the universalbases satisfy levels IS 223,IS 233 and IS 333 serviceratings. The IS distributionblocks satisfy level IS 223.

VX3 IS AnD HX3 ISbASeS AnDDISTrIbUTIOnbLOCkS

125 A HX³ IDISTrIbUT- For DX³ circuit br- Upstream connecti

distribution block- Downstream con

to the circuit bre

1 base: direct conto the column cha

2 Withdrawable dtakes the devices equipped withsupport bases, slbase and ensureconnection of the

3 Connectors for4 Downstream con

1 base: direct connection to thecolumn chassis

2 Withdrawable plate: takes the deviceand slots into the base

3 Downstream connection4 Terminal shield

1 base: direct connection to thecolumn chassis

2 Withdrawable plate: takes the deviceand slots into the base

3 Downstream connection4 Terminal shield

→ It is possible towhile live.

→ It is possible towhile live.

→ replacement ofin less than one hour

→ It is possible to add a functionalunit while live.

→ replacement of a functional unitin less than one hour.

→ It is possible to add a functionalunit while live.

→ replacement of a functional unitin less than quarter of an hour.

VX³ IS 223 bASeFOr DPX³ AnD DPXCIrCUIT breAkerS- Upstream connection via the base- Downstream connection directly

to the circuit breaker terminals

VX³ IS 233 bASeFOr DPX³ AnD DPXCIrCUIT breAkerS- Upstream connection via the base- Downstream connection via the base

1 base: direct connection to thecolumn chassis

2 Withdrawable plate: takes the deviceand slots into the base

3 Downstream connection4 Terminal shield5 Withdrawable cpnnector for auxiliary

circuits

→ It is possible to add a functionalunit while live.

→ replacement of a functional unitin less than quarter of an hour.

→ Lockout of the functional unitto allow testing of off-loadauxiliary circuits.

VX³ IS 333 bASeFOr DPX³ AnD DPXCIrCUIT breAkerS- Upstream connection via the base- Downstream connection via the base- Connection of auxiliaries on

withdrawable connector

16www.legrand

EXB13064_01-17_EN.indd 16 02/07/13 09:42

Page 19: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

1

1

2

2

3

34

4

5

4

5

3 ISTIOn

125 A HX³ IS 223DISTrIbUTIOn bLOCk- For DX³ circuit breakers- Upstream connection via the

distribution block- Downstream connection directly

to the circuit breaker terminals

400 A HX³ IS 223DISTrIbUTIOn bLOCk- For DX³ and DPX³ circuit breakers- Upstream connection via the

distribution block- Downstream connection directly

to the circuit breaker terminals

1 base: direct connectionto the column chassis

2 Withdrawable distribution block:takes the devices equipped withsupport bases, slots into thebase and ensures the upstreamconnection of the devices

3 Connectors for modular devices4 Downstream connection

1 base: direct connection to thecolumn chassis

2 Withdrawable distribution block:takes the devices equipped withsupport bases, slots into thebase and ensures the upstreamconnection of the devices

3 DPX³ support base4 Modular support base5 Downstream connection

→ It is possible to add a devicewhile live.

→ It is possible to add a rowwhile live.

→ replacement of a functional unitin less than one hour.

→ It is possible to add a devicewhile live.

→ Possible addition of a rowwhile live.

→ replacement of a functionalunit in less than one hour.

onnection to the

e: takes the devicease

nection

nnector for auxiliary

add a functional

functional uniter of an hour.

functional unitoff-load

ASenD DPX

breAkerSon via the base

nection via the baseauxiliaries ononnector

UnIVerSALbASeS IS 223,IS 233 AnDIS 333:Allowing devices which do not havea dedicated base to be mounted(for example, motor contactors).

17www.legrand.com

increaSed Safety diStribution SyStem

EXB13064_01-17_EN.indd 17 02/07/13 09:42

Page 20: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

18

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

Supply busba"standard" distribution

Supply busbars and distribution blocks

Supply buSbarS from 63 to 90 a

• Isc peak 17 k Lenght Universal1-pole + neutral

or 1-pole

2-pole 2-pole balancedon 3-phase

3-pole 4-pole

Prong-type

1 row 4 049 26 4 049 38 4 049 40 4 049 42 4 049 44

meter 4 049 37 4 049 39 4 049 41 4 049 43 4 049 45

Fork-type

1 row 4 049 11 - 4 049 17 -

meter 4 049 12 4 049 14 4 049 18 4 049 20

DIstrIbUtIon termInaL bLocks From 63 to 100 a

• Isc peak 10 k numberof outputs

bar terminal blocks Insulated terminal blocks IP 2X (XXb)

with screws on support black blue green

4 0 048 01 0 048 20 0 048 50 0 048 40 0 048 30

6 0 048 16 0 048 15

8 0 048 03 0 048 22 0 048 52 0 048 42 0 048 32

12 0 048 24 0 048 54 0 048 44 0 048 34

14 0 048 05

16 0 048 25 0 048 45 0 048 35

19 0 048 06

21 0 048 26 0 048 46 0 048 36

24 0 048 07

33 0 048 28 0 048 48 0 048 38

moDULar DIstrIbUtIon bLocks From 40 to 250 a

• Isc peak 14.5 to 42 k admissiblemaximum

rating(a)

2-pole 4-pole terminal blocks IP 2X

number and section offlexible conductors (mm2)

number and section offlexible conductors (mm2)

additionaloutputs

cat.nos Inputs outputs cat.nos Inputs outputs earth neutral (mm2)

40 0 048 81 2 x 10 11 x 4 0 048 85 2 x 10 11 x 4 0 048 34 0 048 44 12 x 6

100 0 048 80 2 x 16 5 x 10 0 048 84 2 x 16 5 x 10 0 048 32 0 048 42 8 x 6

125

0 048 82 2 x 25 2 x 16 + 11 x 10 0 048 86 2 x 25 2 x 16 + 7 x 10 0 048 44 12 x 6

0 048 88 2 x 25 2 x 25 + 11 x 10 0 048 35 0 048 45 16 x 6

0 048 76 1 x 35 1 x 25 + 1 x 16+ 14 x 10 0 048 46 21 x 6

160 0 048 79 1 x 70 2 x 25 + 4 x 16+ 8 x 10 0 048 45 16 x 6

250 0 048 77 1 x 120 1 x 35 + 2 x 25+ 2 x 16 + 6 x 10

sInGLe PoLe moDULar DIstrIbUtIon bLocks anD DIstrIbUtIon termInaLs From 125 to 250 a

• Isc peak 27 to 60 k admissiblemaximum rating (a) cat.nos

number and section of conductors per pole (mm2)

Inputs outputs

125 0 048 71 4 x 35 12 x 10

1600 048 83 1 x 50 (flexible bar 13 mm max.) 3 x 25 + 2 x 16 + 7 x 10

0 048 67 (distribution terminal) Direct into the downstream terminal 6 x 25

2500 048 73 1 x 120 (flexible bar 16 mm max.) 6 x 25 + 4 x 10

0 048 68 (distribution terminal) Direct into the downstream terminal 4 x 35 + 2 x 25

PoWer DIstrIbUtIon bLocks From 125 to 400 a

• Isc peak 20 to 75 k admissiblemaximum

rating(a)

extra-flat stepped

number and section ofconductors per pole (mm2)

number and section ofconductors per pole (mm2)

cat.nos Inputs outputs cat.nos Inputs outputs

1250 374 47 1 x 35 10 x 16 (Ph)

17 x 16 (N) 0 373 95 4 bars 12 x 4 mm receiving5 connectors 2 x 10 each

0 374 30 1 x 35 5 x 25

160 0 374 31 1 x 70 5 x 35

250 0 374 00 1 x 150 1 x 70 or 1 x 50+ 1 x 35 or 2 x 35 0 374 35 1 x 120 5 x 50

4000 373 08 2 x Ø8.5 mm

21 holes M670 mm2 max.connectors

0 374 42 2 x 185 15 holes M615 holes M8

4 049 44

4 049 26

4 049 14

1: Filled

Pack Cat.Nos Prong

UnRev

Le

20 4 049 26 110 4 049 37 Me

Do50 4 049 381 110 4 049 39 Me

Do3 4 049 401 110 4 049 41 Me

triple40 4 049 421 110 4 049 43 Me

Four30 4 049 44 110 4 049 45 Me

For

sinLe

20 4 049 11 110 4 049 12 Me

Do10 4 049 14 Me

triple5 4 049 17 110 4 049 18 Me

Four10 4 049 20 Me

Prot

Prot20 4 049 88 12

Can

Pro40 4 049 89 For20 4 049 90 For d20 4 049 91 For

en20 4 049 05 For

or sCro

20 4 049 06 ForCro

pages répartition_18-33.indd 18 19/06/13 14:51

Page 21: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

19

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

Supply busbars, entry terminals"standard" distribution

Supply busbars, entry terminals"standard" distribution

4-pole

4 049 44

4 049 45

-

4 049 20

minal blocks IP 2X (XXb)

green

0 048 30

0 048 32

0 048 34

0 048 35

0 048 36

0 048 38

minal blocks IP 2X

additionaloutputs

neutral (mm2)

0 048 44 12 x 6

0 048 42 8 x 6

0 048 44 12 x 6

0 048 45 16 x 6

0 048 46 21 x 6

0 048 45 16 x 6

o 250 a

s per pole (mm2)

outputs

12 x 10

x 25 + 2 x 16 + 7 x 10

6 x 25

6 x 25 + 4 x 10

4 x 35 + 2 x 25

ed

number and section ofconductors per pole (mm2)

outputs

12 x 4 mm receivingnectors 2 x 10 each

5 x 25

5 x 35

5 x 50

m21 holes M670 mm2 max.connectors15 holes M615 holes M8

entry terminal

n Use of supply busbars

Universal single phase + neutral- blue for neutral- black for live

Four pole busbar

n technical characteristics

4 049 44

4 049 26

4 049 05

4 049 14

1: Filled with end protection

Pack Cat.Nos Prong-type supply busbars

Universal single pole + neutralReversible: blue for neutral, black for live

Length Max. number ofdevices connected

20 4 049 26 1 row 1310 4 049 37 Meter 57

Double pole50 4 049 381 1 row 610 4 049 39 Meter 28

Double pole balanced on 3 phases3 4 049 401 1 row 610 4 049 41 Meter 28

triple pole40 4 049 421 1 row 410 4 049 43 Meter 19

Four pole30 4 049 44 1 row 310 4 049 45 Meter 14

Fork-type supply busbars

single poleLength Max. number of

devices connected20 4 049 11 1 row 1210 4 049 12 Meter 57

Double pole10 4 049 14 Meter 28

triple pole5 4 049 17 1 row 410 4 049 18 Meter 19

Four pole10 4 049 20 Meter 14

Protection

Protection of prongs20 4 049 88 12 modules

Can be cut to length

Protection of supply busbar ends40 4 049 89 For single pole/single pole + neutral20 4 049 90 For double pole length 1 m and triple pole20 4 049 91 For four-pole

entry terminals20 4 049 05 For universal single pole + neutral

or single pole supply busbarsCross section: 4 to 25 mm2 - IP 2X

20 4 049 06 For all supply busbarsCross section: 6 to 35 mm2

busbarstypes

max.number

of devicesconnected

Length innumber of17.5 mmmodules

crosssection(mm2)

Permissible current:

1 centralpower

supply point

2 powersupplypoint

single pole orsingle pole + neutral

1 row 13 13162 80 100

Meter 57 57

Double pole1 row 6 12 102 63 90

Meter 28 56 162 80 100

Double pole balancedon 3-phases

1 row 6 12 102 63 90

Meter 28 56 162 80 100

triple pole1 row 4 12 102 63 90

Meter 19 57 162 80 100

Four pole1 row 3 12 102 63 90

Meter 14 56 162 80 100

Power supply at the rear of thebusbarFor all devices with moving cageterminals

Power supply at the front of thebusbarFor all devices with fixed cageterminals

pages répartition_18-33.indd 19 19/06/13 14:51

Page 22: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

20

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

Modular distr40 to 250 A

Distribution terminal blocksDistribution terminal blocks

0 048 22

n mounting of terminal blocks on support

on 12 x 2 flat bar

0 048 03

0 048 32

0 048 22

0 048 19/016 40

0 048 17

0 048 10

on support for terminal blocks cat.no 0 048 17Enables you to make exactly the right number of connections• Example:

0 048 22

0 048 11

0 048 34

0 048 50

0 048 40

Universal support cat.no 0 048 11Mounted on 4 or 1 rail, takes all terminal blocks

on distribution block support cat.no 0 048 10Possibility of forming a 2P, 3P or 4P distribution block by associatingIP 2X terminal blocks

0 048 15

Pack Cat.Nos Distribution terminal blocks

Conform to standard IEC 60998-2-1Supplied ready for use (screws nottightened)100 A max. - 400 V± with 25 mm2 input80 A max. - 400 V± with 16 mm2 input

screw terminal blocksFit with Ø M4 screws

Number of connections (mm2) Length (mm)10 0 048 01 1 x 6 to 25 + 4 x 1.5 to 16 4510 0 048 03 1 x 6 to 25 + 8 x 1.5 to 16 7310 0 048 05 1 x 6 to 25 + 14 x 1.5 to 16 12210 0 048 06 1 x 6 to 25 + 19 x 1.5 to 16 15710 0 048 07 1 x 6 to 25 + 25 x 1.5 to 16 192

terminal blocks on supportMounting on 4 or 1 rail with universalsupport Cat.No 0 048 11, or on 12 x 2 flat barSupplied with Duplix markers

10 0 048 201 4 x 1.5 to 16 4710 0 048 221 8 x 1.5 to 16 7510 0 048 241 1 x 6 to 25 + 12 x 1.5 to 16 11310 0 048 251 1 x 6 to 25 + 16 x 1.5 to 16 14110 0 048 261 1 x 6 to 25 + 21 x 1.5 to 16 17610 0 048 281 1 x 6 to 25 + 33 x 1.5 to 16 276

IP 2X terminal blocks

Phase(black)

Neutral(blue)

Mounting on 4 or 1 rail with universalsupport Cat.No 0 048 11, or on 12 x 2 flatbar

10 0 048 16 0 048 15 1 x 10 to 35 + 5 x 6 to 25 6210 0 048 50 0 048 40 4 x 1.5 to 16 4710 0 048 52 0 048 42 8 x 1.5 to 16 7510 0 048 54 0 048 44 1 x 6 to 25 + 12 x 1.5 to 16 11310 0 048 45 1 x 6 to 25 + 16 x 1.5 to 16 14110 0 048 46 1 x 6 to 25 + 21 x 1.5 to 16 17610 0 048 48 2 x 6 to 25 + 33 x 1.5 to 16 276

Earth (green)10 0 048 30 4 x 1.5 to 16 4710 0 048 32 8 x 1.5 to 16 7510 0 048 34 1 x 6 to 25 + 12 x 1.5 to 16 11310 0 048 35 1 x 6 to 25 + 16 x 1.5 to 16 14110 0 048 36 1 x 6 to 25 + 21 x 1.5 to 16 17610 0 048 38 2 x 6 to 25 + 33 x 1.5 to 16 276

supports for terminal blocks1 0 048 10 Distribution block support for connecting

up to 4 IP 2X terminal block of the samesize to create a distribution block

5 0 048 11 Universal support for mounting an terminalblocks on 3 or 1 rail

5 0 048 17 35-holes empty support, for screw terminalblocksLength: 276 mm

Flat bar 12 x 210 0 048 19 Length: 1 meter

1: Each terminal block is supplied with:- 2 green Duplix marked T - 2 blue Duplix marked N- 2 red Duplix marked L

Pack Cat.Nos monobloc modular distribution blocks

MouSupplproEacPosCat

DoEqu

Ratin(A

5 0 048 81 40

10 0 048 80 10

5 0 048 82 12

FourEqu

Ratin(A

5 0 048 85 40

10 0 048 84 10

5 0 048 86 12

5 0 048 881 12

1 0 048 762 12

1 0 048 791 16

1 0 048 77 25

Standard distributionConnection with or withSelf-extinguishing, acco

0 048 76 + 0 048 46

1: W2: Inc

C

Technical characte

pages répartition_18-33.indd 20 19/06/13 14:51

Page 23: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

21

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

Modular distribution blocks40 to 250 A

upport

0 048 17

no 0 048 17connections

0 048 34

ks

block by associating

Pack Cat.Nos monobloc modular distribution blocks

Mounting on rail 4 or on plate with 2 screwsSupplied with insulated back plate and transparentprotective front coverEach bar can be labelled using CAB 3Possible to add IP 2X terminal block (exceptCat.No 0 048 77)

Double poleEquipped with 2 bars

Rating(A)

Connections per bar Iscpeak(kÂ)

Icw(kA)

Numberof

modulesrigid

(mm²)flexible(mm²)

5 0 048 81 40 11 x 1.5 to 42 x 6 to 16

11 x 0.75 to 42 x 4 to 10

20 3 6

10 0 048 80 100 5 x 2.5 to 102 x 10 to 25

5 x 1.5 to 102 x 6 to 16

20 4.5 4

5 0 048 82 125 11 x 2.5 to 102 x 10 to 252 x 10 to 35

11 x .5 to 102 x 6 to 162 x 10 to 25

18 4.5 8

Four poleEquipped with 4 bars

Rating(A)

Connections per bar Iscpeak(kÂ)

Icw(kA)

Numberof

modulesrigid

(mm²)flexible(mm²)

5 0 048 85 40 11 x 1.5 to 42 x 6 to 16

11 x 0.75 to 42 x 4 to 10

20 3 6

10 0 048 84 100 5 x 2.5 to 102 x 10 to 25

5 x 1.5 to 102 x 6 to 16

20 4.5 4

5 0 048 86 125 7 x 2.5 to 102 x 10 to 252 x 10 to 35

7 x 1.5 to 102 x 6 to 162 x 10 to 25

20 4.5 6

5 0 048 881 125 11 x 2.5 to 104 x 10 to 35

11 x 1.5 to 104 x 6 to 25

14.5 4.2 8

1 0 048 762 125 14 x 2.5 to 101 x 10 to 251 x 10 to 35

-

14 x 1.5 to 101 x 6 to 161 x 6 to 251 x 16 to 35

20 4.5 10

1 0 048 791 160 8 x 2.5 to 104 x 10 to 252 x 10 to 351 x 35 to 70

8 x 1.5 to 104 x 6 to 162 x 10 to 251 x 35 to 70

27 8.4 10

1 0 048 77 250 6 x 2.5 to 162 x 10 to 252 x 10 to 351 x 16 to 501 x 50 to 120

6 x 2.5 to 102 x 6 to 162 x 10 to 251 x 16 to 351 x 50 to 120

42 14.4 9

Pack Cat.Nos modular distribution blocks

Mounting on rail 4Fitted with Lexic label holderCan be joined togetherPossibility of forming a four pole distribution block byadding modules

single pole

Rating(A)

Connections per barIsc

peak (kÂ)

Numberof

modulesrigid

(mm²)flexible(mm²)

4 0 048 71 125 4 x 16 to 5012 x 1.5 to 10

4 x 16 to 3512 x 1.5 to 10

35 2

4 0 048 83 160 1 x 35 to 707 x 2.5 to 102 x 6 to 253 x 10 to 35

1 x 25 to 507 x 1.5 to 62 x 6 to 163 x 10 to 25

27 2

4 0 048 73 250 1 x 70 to 150 4 x 2.5 to 166 x 10 to 35

1 x 70 to 120 4 x 2.5 to 106 x 10 to 25

60 2

Distribution terminalsIsc peak (kÂ)

1 0 048 67 160 A - 6 outputs 25 mm2 flexibleCan be fitted directly ontodownstream terminal of DPX3 160,Vistop 100/160 A and DX H 125 A

30

1 0 048 68 250 A - 4 outputs 35 mm2 flexibleand 2 outputs 25 mm2 flexibleCan be fitted directly ontodownstream terminal of DPX3 250ER and DPX-IS 250

36

Standard distributionConnection with or without Starfix ferrulesSelf-extinguishing, according to EN 60695-2-11: 960 °C on active part supports

0 048 830 048 770 048 76 + 0 048 46 0 048 79

1: With short ferrule supplied for flexible connection 25 mm2

2: Incoming conductors must be equiped with ferrulesConnection: 25 mm2 witth ferrules without insulating flange

Technical characteristics p. 22-24

pages répartition_18-33.indd 21 19/06/13 14:51

Page 24: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

22

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

Modular distribution blocks40 to 250 A

Power distribution blocks

0 373 08

"Standard" distributionSupplied with screen protection

0 374 00

Conform to EN 60947-1Insulating voltage according to EN 60947-1 / IEC 60664-1: 500 VImpulse voltage (Uimp): 8 kV - Degree of pollution: 3Use in DC: without deratingSelf-extinguishing 960 °C on active parts supports

n monobloc modular distribution blocks

Double pole 40 - 100 - 125 a, cat.nos 0 048 81/80/82

Four pole 40 - 100 - 125 a, cat.nos 0 048 85/84/86/88

4450w

493923

4450w

88.5

8623

Four pole 160 a, cat.no 0 048 79

4450

96.8

91.5

23

w

Four pole 250 a, cat.no 0 048 77Self-extinguishing 960 °C according to EN 60695-2-11

W

134.5 7570.5

85

75

150

2510

5.5

45

4450

9791.5

W

Four pole 125 a cat.no 0 048 76

cat.nos Width(mm)

0 048 80 700 048 81 1050 048 82 1400 048 84 700 048 85 1050 048 86 1050 048 88 1400 048 76 1790 048 77 1600 048 79 179Pack Cat.Nos extra-flat for lugs

125 a1 0 374 47 Fixing on rail EN 60715 4 or on plate

with M6 screws. Equipped with:- 1 incoming 35 mm2 (possible tapp-off)- 10 phase outgoing 16 mm2 - M5 screws- 17 neutral outgoing 16 mm2 - M5 screwsConnection possible using connectorCat.No 0 373 65250 a

1 0 374 00 Fixing on plain plate or on plate with M6 screwsDistribution block 1 incoming 150 mm2 per pole:- 1 pole is composed of 3 parts- Each part can receive:1 x 70 mm2 or 1 x 50 mm2 and 1 x 35 mm2,or 2 x 35 mm2 or 1 connector with 3 outgoingterminals Cat.No 0 374 03 (p. 25)

stepped for lugs125 a

1 0 373 95 Fixing on rail EN 60715 4 depth 15 mm or on platewith screws Ø4 mm (by removing claws)4 bars 12 x 4 mm with five connectors 2 x 10 mm2/bar (not mounted)

1 0 374 30 Fixing on rail EN 60715 4, with clawsCat.No 0 374 39 or on plate with M6 screws4 bars 15 x 4 mm supplied with:- 1 incoming 35 mm2 - M8 screws- 5 outgoing 25 mm2 - M6 screws

160 a1 0 374 31 Fixing on rail EN 60715 4, with claws

Cat.No 0 374 39 or on plate with M6 screws4 bars 18 x 4 mm supplied with:- 1 incoming 70 mm2 max. - M8 screws- 5 outgoing 35 mm2 - M6 screws

250 a1 0 374 35 Fixing on rail EN 60715 4, with claws

Cat.No 0 374 39 or on plate with M6 screws4 bars 25 x 4 mm supplied with:- 1 incoming 120 mm2 - M10 screws- 5 outgoing 50 mm2 - M8 screws

400 a1 0 373 08 Horizontal mounting in XL3 400 cabinets, vertical

in XL3 400 cable sleeve, vertical in XL3 800 internalcable sleeve or on solid plate using the M6 screwssuppliedDistribution block consisting of 4 tin-coated bars32 x 5 mm with insulated protectionComposition of each bar:- 2 x Ø8.5 mm untapped holes for power supply(flexible bars, …)- 21 outgoing M6 holes (70 mm2 lugs max.)

1 0 374 42 Fixing on rail EN 60715 4, with clawsCat.No 0 374 39Distribution block consisting of 4 bars 32 x 5 mmComposition of each bar:- 2 x Ø10.5 mm untapped holes for power supply(185 mm2 max.)- 15 outgoing M6 holes, 4 outgoing M8 holes

1: Supplementary insulation proUTE C 15712 double insula

2: Impulse voltage tested at 12 kV in the conteinsulation

n characteristics ofphotovoltaic installa

no of18 mm

modulescat.no max.

for "

2 0 048 71 4 x12 x 1.5 to

4 0 048 80 5 x2 x

8 0 048 8211 x2 x

2 x

47

5616

26.510.56.5 12.5

n Distribution termi

160 a

n modular distribut

single pole 125 - 160 -

connection

44 760

104.

5

4510

1.5

125 a

Cat.No 048 71

36

Torque3.5 Nm

10 Nm

pages répartition_18-33.indd 22 19/06/13 14:51

Page 25: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

23

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

C 60664-1: 500 Von: 3

rts

0/82

86/88

5-2-11

150

cat.nos Width(mm)

0 048 80 700 048 81 1050 048 82 1400 048 84 700 048 85 1050 048 86 1050 048 88 1400 048 76 1790 048 77 1600 048 79 179

n section for connecting rigid or flexible conductors (withstarfix ferrules)

Distributionblocks

cat.nos

connectionsper bar

rigidconductors

Flexible conductorswith ferrules

number Ø(mm)

section(mm2)

section(mm2)

starfix ferrulescat.nos

0 048 67 6 8.5 6 to 25 0 376 68 to 71

0 048 684 10 6 to 35 0 376 68 to 772 8.9 6 to 25 0 376 68 to 71

0 048 7112 5.3 16 to 50 1.5 to 10 0 376 64 to 694 10 1.5 to 10 16 to 35 0 376 70 to 72

0 376 70 to 77

0 048 734 6 70 to 150 2.5 to 10 0 376 66 to 696 8.5 2.5 to 16 10 to 25 0 376 69 to 721 - 10 to 35 70 to 120 -

0 048 805 5.3 2.5 to 10 1.5 to 10 0 376 64 to 692 7.5 10 to 25 6 to 16 0 376 68 to 70/72

0 048 8111 4.3 1.5 to 4 0.75 to 4 0 376 62 to 672 6 6 to 16 4 to 10 0 376 67/68/69

0 048 8211 5.3 2.5 to 10 1.5 to 10 0 376 64 to 692 7.5 10 to 25 6 to 16 0 376 68 to 70/722 9 10 to 35 10 to 25 0 376 69/72/71

0 048 83

7 5.3 35 to 70 1.5 to 10 0 376 64 to 692 7.5 2.5 to 10 6 to 16 0 376 68/69/723 8.9 6 to 25 10 to 25 0 376 69/721 - 10 to 35 25 to 50 0 376 71 to 77/78

0 048 845 5.3 2.5 to 10 1.5 to 10 0 376 64 to 692 7.5 10 to 25 6 to 16 0 376 68 to 70/72

0 048 8511 4.3 1.5 to 4 0.75 to 4 0 376 62 to 672 6 6 to 16 4 to 10 0 376 67/68/69

0 048 867 5.3 2.5 to 10 1.5 to 10 0 376 64 to 692 7.5 10 to 25 6 to 16 0 376 68 to 70/722 9 10 to 35 10 to 25 0 376 69/72

0 048 8811 5.3 2.5 to 10 1.5 to 10 0 376 64 to 694 8.5 10 to 35 6 to 25 0 376 68 to 71

0 048 79

1 35 to 70 35 to 70 0 376 77/788 5.3 2.5 to 10 1.5 to 10 0 376 64 to 694 7.5 10 to 25 6 to 16 0 376 68 to 70/722 8.5 10 to 35 10 to 25 0 376 69/72

0 048 76

14 5.3 2.5 to 10 1.5 to 10 0 376 64 to 691 7.5 10 to 25 6 to 16 0 376 68 to 70/721 8.5 10 to 35 6 to 25 0 376 68 to 70/721 - - 16 to 35 0 376 70 to 77

0 048 77

6 6 2.5 to 16 2.5 to 10 0 376 66 to 692 7.5 10 to 25 6 to 16 0 376 68 to 70/722 8.5 10 to 35 10 to 25 0 376 69 to 721 10 16 to 50 16 to 35 0 376 70 to 72/771 - 50 to 120 50 to 120 0 376 78

1: Supplementary insulation provided for the support rail in the context of application ofUTE C 15712 double insulation

2: Impulse voltage tested at 12 kV in the context of application of UTE C 15712 doubleinsulation

n characteristics of distribution blocks for use inphotovoltaic installations

no of18 mm

modulescat.no max. cross-section

for "solar cable"

max. le (a) currentt = (+40°c/+60°c)

Iec 60364-1

Ui (V)Degree ofpollution 2

Iec 60664-1

ImpulsevoltageUimpIec

60664-1

single pole distribution block

2 0 048 71 4 x 16 to 25 mm2

12 x 1.5 to 6 mm2 or 6 x 10 mm2 125/100 1000 V(1) 8 kV(2)

Double pole distribution blocks

4 0 048 80 5 x 1.5 to 6 mm2

2 x 6 to 16 mm2 100/80 800 V(1) 8 kV(2)

8 0 048 8211 x 1.5 to 6 mm2

2 x 6 to 16 mm2

2 x 10 to 25 mm2125/100 800 V(1) 8 kV(2)

47

5616

26.510.56.5 12.5

60

8025

30176.5 10 Ø 10

n Distribution terminals, cat.nos 0 048 67/68

160 a 250 a

n Use of IP 2X terminal blocks

n modular distribution blocks

single pole 125 - 160 - 250 a, cat.nos 0 048 71/83/73

connection

14444 760

104.

5

4510

1.5

125 a 160 a 250 a

Cat.No 048 71

36

Torque3.5 Nm

10 Nm

Cat.No 048 83

36

Torque3.5 Nm

Cat.No 048 73

36

Torque24 Nm

1: T2: Neutral

0 048 80 + 0 048 32

modular IP 2XDerating

distribution terminalblocks blocks Voltage rating

0 048 80 0 048 32(1) 400 V 80 A

0 048 81 0 048 34(1) 400 V 40 A

0 048 82 0 048 35(1) 400 V 100 A

0 048 84 0 048 42(2) 400 V 80 A

0 048 85 0 048 44(2) 400 V 40 A

0 048 86 0 048 44(2) 400 V 100 A

0 048 88 0 048 45(2) 400 V 100 A

0 048 76 0 048 46(2) 400 V 100 A

0 048 79 0 048 45(2) 400 V 100 A

pages répartition_18-33.indd 23 19/06/13 14:51

Page 26: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

24

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

ConnectionPower distribution blocks

n extra-flat for lugs

125 a cat.no 0 374 47 - Isc peak 25 kÂInsulating voltage according to EN 60947-1 / IEC 60664-1: 500 VSelf extinguishing: 960 °C according to EN 60695-2-11

250 a cat.no 0 374 00 - Isc peak 60 kÂInsulating voltage according to EN 60947-1 / IEC 60664-1: 1000 VSelf extinguishing: 960 °C according to EN 60695-2-11

n stepped for lugs

125 a cat.no 0 373 95 - Isc peak 20 kÂInsulating voltage according to EN 60947-1 / IEC 60664-1: 600 VSelf extinguishing: 850 °C according to EN 60695-2-11

125/160/250 a cat.nos 0 374 30/31/35 - Isc peak 35 kÂInsulating voltage according to EN 60947-1 / IEC 60664-1: 1000 VSelf extinguishing: 850 °C according to EN 60695-2-11Uimp: 12 kV, degree of pollution: 3

400 a(1) cat.no 0 373 08 - Isc peak 42 kÂInsulating voltage according to EN 60947-1 / IEC 60664-1: 1000 VUimp: 12 kV, degree of pollution: 3Self extinguishing: 960 °C according to EN 60695-2-11

1: Horizontal mounting with minimum faceplates height 300 mm

44

58

61.5

135 59

60 289

265

NN

125

150

165

228

200

140

220

5

M8connection width 35 mm

M6connection width 35 mm

75.5

260

460

300

395

440250

101

107

270

A JI

B H

CG

DEF

Dimensions (mm)

Distributionblocks a b c D e f G H I J

125 a 225 125 110 125 165 189 6.5 117.5 165 108

160 a 240 125 110 125 165 189 6.5 117.5 180 120

250 a 260 155 110 125 185 209 6.5 147.5 195 120

98

108

6.5

14.5

44

122.5

83.5

7771

cat.no 374 42 - Isc peak 50/75 kÂInsulating voltage according to EN 60947-1 / IEC 60664-1: 1000 Vfixing centres 50 mm,1500 V fixing centres 75 mmUimp: 8 kV fixing centres 50 mm, 12 kV fixing centres 75 mmDegree of pollution: 3

"Standard" distribution

0 374 05on copper bar

0 374 80

Pack Cat.Nos conn

Wit10 0 374 03 Fits

CatCap- 1for- 2for

Wit4 0 373 99 Fits

heaCap- 4- 2

Wit5 0 374 05 Fits

Cap- 4for- 3for

aluupAdacablIP 2UniRevOpacc• ACon• CConSup

5 0 374 80 AlumInccoppOut

4 0 374 81 AlumInccoppOut

JuFor4 cRevFittean iKnoSeaRA

1 0 330 441 0 330 541 0 330 741 0 330 84

pages répartition_18-33.indd 24 19/06/13 14:51

Page 27: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

25

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

Connection Connection

60664-1: 600 V5-2-11

peak 35 kÂ60664-1: 1000 V

5-2-11

60664-1: 1000 V

5-2-11460

300

395

440

G H I J

.5 117.5 165 108

.5 117.5 180 120

.5 147.5 195 120

60664-1: 1000 Vmntres 75 mm

"Standard" distribution

0 374 05on copper bar

0 374 80 0 330 74

n connectors

Cat.No 0 374 03 Cat.No 0 374 05

n Junction boxesA

Ø G

45

F E

A

C

D

connectionJunction Distribution

AI/Cu

AI/Cu AI/Cu

Cu Cu

AI/Cu

Cu

connecting in seriesThis bridging is made with 2 copper bars (suppliedwith each product) and accept max. rating ofincoming cable for tap-off between 2 distributionsboards

n aluminium/copper distribution boxes

technical characteristics

12

5

66

6574

15

7.5

52.5

4454

15

2

12

5

DimensionsCat.No 0 374 80 Cat.No 0 374 81

4

11.5

12

4

11.5

12

16

29

21.5 29

Ø 8.5 15 1520

21.5 29

Ø 8.5

62.5

Cat.No 0 373 9926,590

31

31

13,5

13,5 6

8,5

Ø 10 x 4

Ø 8,9 x 2

cat.nos a(mm)

c(mm)

D(mm)

e(mm)

f(mm)

G(mm)

0 330 44 236 75 89 264 40 60 330 54 176 84 99 314 40 70 330 74 319 103 118 361 50 70 330 84 510 129 144 613 65 9

Pack Cat.Nos connectors

With 3 outgoing terminals 200 a10 0 374 03 Fits onto flat copper bars and distribution block

Cat.No 0 374 00 (p. 22)Capacity:- 1 x Ø5.3 mm outgoing terminalfor 1.5 to 6 mm2 connection- 2 x Ø7.5 mm outgoing terminalsfor 6 to 16 mm2 connection

With 6 outgoing terminals 250 a4 0 373 99 Fits onto C section aluminium bars with M10 hammer

head bolt Cat.No 0 373 59 or onto flat copper barsCapacity:- 4 x 6 to 35 mm2

- 2 x 6 to 25 mm2

With 7 outgoing terminals 400 a5 0 374 05 Fits onto flat copper bars

Capacity:- 4 x Ø5.3 mm outgoing terminalsfor 1.5 to 6 mm2 connection- 3 x Ø7.5 mm outgoing terminalsfor 6 to 16 mm2 connection

aluminium/copper distribution boxesup to 300 mm2

Adapt the cross-section of the incoming or outgoingcable in order to connect a deviceIP 2X box, self-extinguishing transparent coverUniversal fixing on 4 rail or on plateReversible sealable cover with area for labelOperational voltage: Ue = 690 V±according to EN 60947-1/IEC 60664-1• Aluminium connectionConform to standard NFC 63-061 class B• Copper connectionConform to standard EN 60947-7-1Supplied with copper coupling strip

5 0 374 80 Aluminium/copper 120 mm2 distribution box 300 A max.Incoming: 16 to 120 mm2 Aluminium or 16 to 120 mm2

copperOutgoing: 16 to 70 mm2 copper

4 0 374 81 Aluminium/copper 300 mm2 distribution box 540 A max.Incoming: 70 to 300 mm2 Aluminium or 70 to 185 mm2

copperOutgoing: 70 to 150 mm2 copper

Junction boxes IP 30 - Ik 07For copper cables4 connections per poleReversible stirrup for zero clampingFitted with 4 or 5 junction blocks mounted onan insulated strip with a sheet steel coverKnock-out entries for conduits Ø9 and 21 mmSealable cover screwsRAL 7032

Poles Cable section (mm2) Rated current (A)1 0 330 44 4 35 1251 0 330 54 4 70 1921 0 330 74 4 150 3091 0 330 84 4 240 415

cat.no 0 374 80 cat.no 0 374 81Impulse voltage (Uimp)short-circuit current 10 kV 12 kV

Icw for 1 second 14.5 kA 22.2 kAtightening torque 14 Nm 30 Nm

pages répartition_18-33.indd 25 19/06/13 14:51

Page 28: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

26

"Standard" distribution

max. In (a)

Flat copper bars c-section aluminium bars

400 800 1000 1600 4000 1600 1600 1600 1600

supports

mounting 0 373 10 0 373 15 0 373 20 0 373 21 0 373 22/23 0 373 24/250 373 66/

86/500 373 68/

51 0 373 67 0 373 69

XL3 400

Vertical at backof cabinet orenclosure

l

Vertical at back ofcable sleeve

l

XL3 800

Vertical at backof cabinet orenclosure

l+ 0 373 14

Vertical at backof internal cablesleeve

l

Vertical at backof external cablesleeve

l

XL3 4000

Mainhorizontalat top orat bottomof cabinet

D: 475 l+ 0 205 51(5) l(5)

D: 725 l+ 0 205 52 l(5) l(6) l(5)

D: 975 l+ 0 205 53 l(1) l(1)(7) l(7)

Horizontaltransfer

D: 725 l+ 0 205 51 l(4+5) l l(5)

D: 975 l+ 0 205 52 l l(1) l

Verticallateralinsidecablesleeve

D: 475 l+ 0 205 51

l+ 0 205 51

l+ 0 205 51 l l

D: 725 l+ 0 205 52

l+ 0 205 52

l+ 0 205 52 l l(1) l l(1) l

D: 975 l+ 0 205 53

l+ 0 205 53

l+ 0 205 53 l(1) l(1) l(1) l(1) l(1)

Verticallateralinsidecabinetbehindupright

D: 725 l+ 0 205 51

l+ 0 205 51 l

D: 975 l+ 0 205 52

l+ 0 205 52 l l(1) l

Verticalat backof cabinet

W: 475 l+ 0 205 51

l+ 0 205 51(2) l

W: 725l

+ 0 373 14l

+ 0 205 52l

+ 0 205 52 l l

W: 975 l+ 0 205 53

l+ 0 205 53 l l(1)

Horizontalat backof cabinet

W: 475 l(3)

+ 0 205 51l(3)

+ 0 205 51l(3)

+ 0 205 51

W: 725 l(3)

+ 0 205 52l(3)

+ 0 205 52l(3)

+ 0 205 52

W: 975 l(3)

+ 0 205 53l(3)

+ 0 205 53l(3)

+ 0 205 53

1: With upright Cat.No 0 205 20 in cable sleeve - 2: Depth min. 725 mm - 3: Fixed supports only - 4: Inside complementary cable sleeve - 5: Partial chassis -6: With crosspieces Cat.No 0 205 52 - 7: With crosspieces Cat.No 0 205 53

D(mm)

D(mm)

D(mm)

D(mm)

W(mm)

W(mm)

Dimensions p. 31Distances between

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

Isolating suppXL3 cabinets and encl

Busbars supports selectionstandard distribution

0 373 10

Pack Cat.Nos 1 bar

≤ 210 0 373 98 Sin

12 x10 0 374 37 Sin

15 x5 0 373 96 Set

for12 x

1 0 374 32 Setfor15 x

1 0 374 36 Setfor

1 b

≤ 41 0 373 15 Sup

18 xFor

1 0 373 10 Sup25 xin sverFor

≤ 81 0 373 20 Sup

18 x 463

≤ 101 0 373 21 Sup

50 xin s

pages répartition_18-33.indd 26 19/06/13 14:51

Page 29: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

27

"Standard" distribution

ion aluminium bars

1600 1600 1600

0 373 68/51 0 373 67 0 373 69

l(5)

l(7)

l(5)

l

l

l l(1) l

l(1) l(1) l(1)

l

l

l(1)

Dimensions p. 31Distances between the supports p. 28

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

Isolating supports for busbarsXL3 cabinets and enclosures

0 373 10 0 373 24

Pack Cat.Nos 1 bar per pole universal supports

≤ 280 a10 0 373 98 Single pole support for flat copper bars

12 x 2 or 14 x 4 mm10 0 374 37 Single pole support for flat copper bars

15 x 4, 18 x 4 or 25 x 4 mm5 0 373 96 Set of 2 four pole supports

for flat copper bars12 x 2 or 12 x 4 mm

1 0 374 32 Set of 2 four pole supportsfor flat copper bars15 x 4 or 18 x 4 mm

1 0 374 36 Set of 2 four pole supportsfor flat copper bars 25 x 4 mm

1 bar per pole

≤ 400 a1 0 373 15 Support for flat copper bars

18 x 4, 25 x 5 and 32 x 5 mmFor XL3 400 cabinets and enclosures

1 0 373 10 Support for flat copper bars 18 x 4,25 x 4, 25 x 5 and 32 x 5 mm,in sloping position to create avertical busbars at backFor direct mounting on solid or perforated plate

≤ 800 a1 0 373 20 Support for flat copper bars

18 x 4, 25 x 5, 32 x 5, 50 x 5 and63 x 5 mm in sloping position

≤ 1000 a1 0 373 21 Support for flat copper bars

50 x 5, 63 x 5, 75 x 5 and 80 x 5 mmin staggered position

Pack Cat.Nos 1 or 2 bars per pole

Supports for flat copper bars50 x 5, 63 x 5, 75 x 5, 80 x 5 and100 x 5 mm, in aligned position

≤ 1600 a1 0 373 22 Fixed support1 0 373 23 Additional support

Mounted in addition to fixed support Cat.No 0 373 22to comply with the distances (Isc withstand)

1 to 4 bars per poleSupports for 4 flat bars from50 x 5 to 125 x 5 mm or 3 bars from50 x 10 to 120 x 10 mm, in alignedposition

≤ 4000 a1 0 373 24 Fixed support1 0 373 25 Additional support

Mounted in addition to fixed support Cat.No 0 373 24to comply with the distances (Isc withstand)

Fixing supportsadjustable crosspieces

1 0 205 51 Set of 2 crosspieces length 350 mm1 0 205 52 Set of 2 crosspieces length 600 mm1 0 205 53 Set of 2 crosspieces length 850 mm

Crosspieces for partial chassis1 0 205 31 Set of 2 fixed crosspieces length 350 mm1 0 205 32 Set of 2 fixed crosspieces length 600 mm

extension piece1 0 373 14 For mounting busbars supports Cat.No 0 373 15 in

XL3 800 and 4000 cabinets and enclosures

pages répartition_18-33.indd 27 19/06/13 14:51

Page 30: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

28

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

Isolating supports for busbars

n Peak current IpkThe distance between the busbar supports depends on the electrodynamic forces generated when there is a short-circuit, these being directlyproportional to the peak value of the short-circuit current (Ipk)Two methods can be used to determine the peak current value according to data that is generally available:

Using the limiting capacity of the protective devicesThe limitation curves of the protective devices (DX and DPX) givethe limited peak current according to the prospective short-circuit currentThe "Non-limited peak Isc" curve corresponds to no protectionThe table opposite gives the limited peak value (Ipk) for a maximumprospective short-circuit value equal to the breaking capacity (Icu) ofthe deviceFor lower prospective short-circuit values, reading the curves willprovide an optimised value

the peak value is much higher ifThere are no limiting protective devicesThis value is calculated by applying a coefficient of asymmetry (n)to the prospective rms value shown in the table opposite

n Determining the distances between the supports

D

E

maximum distances "D" (mm) e adjustable

maximum distances "D" (mm) e fixed

Iscpeak

Iscnon-lim

ited peak

prospective Isc

Isclimited

peak

Isc RMS.

rating Isc peak max.(a) (kÂ)

DPX 125 16-25 11.9

DPX 125 40-63 15

DPX 125 100-125 17

DPX 160 25 14.3

DPX 160 40 to 160 20

DPX 250 er 100 to 250 22

DPX 250 All 27

DPX-H 250 All 34

DPX 630 All 34

DPX-H 630 All 42

DPX 1600 All 85

DPX-H 1600 All 110

Isc prospective rms (ka) n≤ 5 1.5

5 < I ≤ 10 1.7

10 < I ≤ 20 2

20 < I ≤ 50 2.1

50 < I 2.2

supports 0 373 98 0 374 37

bars 0 373 88 (12 x 2) or 0 373 89 (12 x 4) 0 374 33 (15 x 4) or 0 374 34 (18 x 4)or 0 374 38 (25 x 4)

e (mm) 50 75 100 125 50 75 100 125

Isc peak(Ipk in kÂ)

10 400 600 800 350 600 750

15 300 450 600 800 250 400 500 700

20 250 350 450 600 150 225 300 375

25 200 250 300 400 125 150 200 250

30 100 125 150 175

35 100 125 150

supports 0 373 96 0 374 32 0 374 36 0 373 10 0 373 15

bars 0 373 88 0 373 89 0 374 33/34 0 374 38 0 374 34 0 374 38 0 374 18 0 374 19 0 374 34 0 374 18 0 374 19(12 x 2) (12 x 4) (15 x 4) (25 x 4) (18 x 4) (25 x 4) (25 x 5) (32 x 5) (18 x 4) (25 x 5) (32 x 5)

(18 x 4)

Isc peak(Ipk in kÂ)

10 200 400 550 650 550 650 800 900 1000 1200 1500

15 150 300 400 500 400 600 700 800 700 1000 1200

20 125 200 300 400 300 450 550 700 550 750 950

25 100 150 200 350 250 350 400 500 400 600 750

30 150 200 200 300 350 400 350 500 650

35 100 150 150 250 300 350 300 400 550

40 100 150 200 300 300 250 350 450

45 150 200 200 200 300 400

50 150 175 100 200 300 400

55 100 150 100 200 250 300

60 150 200 250 300

70 150 200 250

80 150 200 250

n Determining the

maximum distances "D

maximum distances "D

maximum distances "D" (

supports

bars 0 374 34(18 x

Isc peak(Ipk in kÂ)

10 80

15 40

20 30

25 25

30 22

35 20

40 17

45 15

50 15

60 12

70 10

8090

100110120

supports

bars 0 374 40(50 x

Isc peak(Ipk in kÂ)

10 1000

15 80

20 65

25 50

30 40

35 35

40 30

45 30

50 25

60 20

70 15

80 10

90 10

100 10

110 10

120 10

supports

bars0 373 54

Isc peak(Ipk in kÂ)

30 1600

40 1000

52 80

63 70

73 60

80 60

94 50

105 50

132 -

154 -

pages répartition_18-33.indd 28 19/06/13 14:51

Page 31: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

29

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

these being directly

Iscnon-lim

ited peak

prospective IscIsc RMS.

0 374 195)

1500

0

0

0

0

0

0

0

0

0

0

0

0

n Determining the distances between the supports (continued)

maximum distances "D" (mm) - e fixed: 75 mm

maximum distances "D" (mm) - e fixed: 75 mm

additional support:• Horizontal busbars(1)

Mounted in addition:- to 2 fixed supports in

enclosurewidth 725 et 975

- to fixed support in cablesleeves width 475

• Vertical busbarsMounted in addition to 3 fixedsupports if necessary1: In case of flat bar mounting, use fixedsupport only

maximum distances "D" (mm)

supports 0 373 20 0 373 21

bars1 flat bar per pole 1 flat bar per pole

0 374 34 0 374 18 0 374 19 0 374 40 0 374 41 0 374 40 0 374 41 0 374 59 0 374 43(18 x 4) (25 x 5) (32 x 5) (50 x 5) (63 x 5) (50 x 5) (63 x 5) (75 x 5) (80 x 5)

Isc peak(Ipk in kÂ)

10 800 800 900 1000 1200 1200 1200

15 400 600 600 700 800 800 900 1000 1000

20 300 450 500 600 700 650 700 750 750

25 250 350 400 500 550 500 600 600 600

30 225 300 350 400 450 400 500 550 550

35 200 250 300 350 400 350 450 450 450

40 175 200 250 275 300 300 350 400 400

45 150 200 200 225 250 300 300 350 350

50 150 150 150 200 200 250 250 300 300

60 125 125 125 150 150 200 250 250 250

70 100 100 100 150 150 150 200 200 200

80 100 100 100 150 200 200

90 100 150 200 200

100 100 150 150 150

110 100 100 150 150

120 100 100 100 100

supports 0 373 22, 0 373 23

bars1 flat bar per pole 2 bars per pole

0 374 40 0 374 41 0 374 59 0 374 43 0 374 46 0 374 40 0 374 41 0 374 59 0 374 43 0 374 46(50 x 5) (63 x 5) (75 x 5) (80 x 5) (100 x 5) (50 x 5) (63 x 5) (75 x 5) (80 x 5) (100 x 5)

Isc peak(Ipk in kÂ)

10 1000 1200 1200 1200 1200

15 800 900 1000 1000 1200

20 650 700 750 750 900

25 500 600 600 600 700

30 400 500 550 550 600 700 600

35 350 450 450 450 550

40 300 350 400 400 450 550 600 650 650 700

45 300 300 350 350 400

50 250 250 300 300 350 450 500 500 500 550

60 200 250 250 250 300 350 400 400 400 450

70 150 200 250 250 250 250 350 350 350 400

80 100 150 200 200 200 250 300 300 300 300

90 100 150 200 200 200 200 250 300 300 300

100 100 150 150 150 150 200 200 250 250 250

110 100 100 150 150 150 200 150 200 200 200

120 100 100 100 100 100 150 150 200 200 200

supports 0 373 50/66/67/86 0 373 51/68/69

bars1 c-section aluminium bar per pole 1 c-section aluminium bar per pole

0 373 54 0 373 55 0 373 56 0 373 57 0 373 58 0 373 54 0 373 55 0 373 56 0 373 57 0 373 58

Isc peak(Ipk in kÂ)

30 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600

40 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

52 800 800 800 800 800 800 800 800 800 800

63 700 700 700 700 700 600 600 600 600 600

73 600 600 600 600 600 500 500 500 500 500

80 600 600 600 600 600 500 500 500 500 500

94 500 500 500 500 500 400 400 400 400 400

105 500 500 500 500 500 400 400 400 400 400

132 - - 500 500 500 - - 400 400 400

154 - - 400 400 400 - - 300 300 300

pages répartition_18-33.indd 29 19/06/13 14:51

Page 32: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

30

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

Isolating supports for busbars

maximum distances "D" (mm) with bars thick 5 mm - e fixed: 125 mm

additional support:• Horizontal busbars(1)

Mounted in addition:- to 2 fixed supports in enclosure

width 725 et 975- to fixed support in cable

sleeves width 475• Vertical busbarsMounted in addition to 3 fixedsupports if necessary1: In case of flat bar mounting, use fixedsupport only

n Insulating characteristicsEN 60947-1/IEC 60664-1 (degree of pollution: 3)

supports 0 373 24, 0 373 25

bars1 bar per pole 2 bars per pole 3 bars per pole 4 bars per pole

50 x 5 63 x 575 x 5

100 x 5 125 x 5 50 x 5 63 x 575 x 5

100 x 5 125 x 5 50 x 5 63 x 575 x 5

100 x 5 125 x 5 50 x 5 63 x 575 x 5

100 x 5 125 x 580 x 5 80 x 5 80 x 5 80 x 5

Isc peak(Ipk in kÂ)

10 1550 1700 1700 1700 1700 1700 1700 1700 1700 1700 - - - - - - - - - -15 1050 1200 1350 1550 1700 1550 1700 1700 1700 1700 1700 - - - - - - - - -20 800 900 1000 1150 1350 1200 1350 1500 1700 1700 1550 1700 1700 1700 1700 1700 1700 1700 1700 170025 650 750 800 950 1100 950 1100 1200 1400 1550 1250 1450 1600 1700 1700 1550 1700 1700 1700 170030 550 600 700 800 900 800 900 1000 1150 1300 1050 1200 1350 1550 1700 1300 1500 1700 1700 170035 450 550 600 650 800 700 800 900 1000 1150 900 1050 1150 1300 1500 1150 1250 1450 1650 170040 400 450 550 600 700 600 700 800 900 1000 800 900 1050 1150 1300 1000 1100 1300 1450 165045 350 400 450 550 600 550 600 700 800 900 700 800 900 1050 1200 900 1000 1150 1300 145050 350 350 450 500 550 500 550 650 700 800 650 750 850 950 1050 800 900 1050 1150 135060 300 300 350 400 450 400 450 550 600 700 550 600 700 800 900 650 750 850 1000 110070 250 250 300 350 400 350 400 450 500 650 450 550 600 700 750 600 650 750 850 95080 - 250 250 300 350 300 350 400 450 550 400 450 550 600 700 500 600 650 750 85090 - - 250 250 300 300 300 350 400 500 350 400 500 550 600 450 500 600 650 750

100 - - - 250 300 250 300 300 350 500 350 400 450 500 550 400 450 550 600 700110 - - - 250 250 250 250 300 350 450 300 350 400 450 500 350 450 500 550 600120 - - - - 250 - 250 250 300 450 300 300 350 400 450 350 400 450 550 550130 - - - - 250 - - 250 300 400 250 300 350 350 450 300 350 400 500 550140 - - - - - - - 250 250 400 250 250 300 350 400 300 350 400 450 500150 - - - - - - - - 250 350 250 250 300 350 350 300 300 350 400 450160 - - - - - - - - 250 350 - 250 250 300 350 250 300 350 400 350170 - - - - - - - - - 350 - 250 250 300 350 250 300 300 350 300180 - - - - - - - - - 300 - - 250 300 300 250 250 300 350 300190 - - - - - - - - - - - - 250 250 300 250 250 300 300 250200 - - - - - - - - - - - - - 250 300 - 250 250 300 250210 - - - - - - - - - - - - - 250 250 - 250 250 250 200220 - - - - - - - - - - - - - 250 250 - - 250 250 200

supports 0 373 24, 0 373 25

bars1 bar per pole 2 bars per pole 3 bars per pole

80 x 10 100 x 10 120 x 10 80 x 10 100 x 10 120 x 10 80 x 10 100 x 10 120 x 10

Isc peak(Ipk in kÂ)

20 1700 1700 1700 1700 1700 1700 1700 1700 170025 1600 1700 1700 1700 1700 1700 1700 1700 170030 1350 1550 1700 1700 1700 1700 1700 1700 1700

35 1150 1300 1450 1700 1700 1700 1700 1700 170040 1050 1150 1300 1500 1700 1700 1700 1700 170045 900 1050 1150 1350 1550 1700 1700 1700 1700

50 850 950 1050 1200 1400 1550 1600 1700 1700

60 700 800 850 1000 1150 1300 1350 1550 1700

70 600 700 750 900 1000 1100 1150 1300 1500

80 550 600 650 750 900 1000 1000 1150 1300

90 500 550 600 700 800 900 900 1050 1100

100 450 500 550 600 700 800 850 900 950

110 400 450 500 550 650 750 750 800 800

120 350 400 450 550 600 650 700 750 750

130 350 350 400 500 550 600 650 700 700

140 300 350 400 450 500 600 600 650 650

150 300 350 350 450 500 550 550 650 600

160 250 300 350 400 450 500 550 600 500

170 250 300 300 350 450 500 500 500 500

180 250 300 300 350 400 450 500 450 450

190 250 250 300 350 400 450 450 400 400

200 200 250 300 300 350 400 450 400 400

210 200 250 250 300 350 350 400 350 350

220 - 250 250 300 350 300 350 300 300

230 - 200 250 300 300 300 300 300 300

240 - - 200 250 300 250 300 250 250

250 - - 200 250 300 250 250 250 250

cat.nos 0 373 98 0 374 37 0 373 96 0 374 32 0 374 36 0 373 10/20 0 373 21 0 373 22/23 0 373 24/25 0 373 50/51/66/67/68/69/86

Ui (V) 500 500 690 1000 1000 1000 1000 1000 1000 1000

Uimp (kV) 8 8 8 12 12 12 12 12 12 8

maximum distances "D" (mm) with bars thick 10 mm - e fixed: 125 mm

125

110

148

40

208

cat.no 0 374 36

345

A

300

fixing centre 325

cat.no 0 373 22 (fixed suppor

Side for 12 x 4 mm ba

12.4 25.5

4

cat.no 0 373 98Side for 12 x 2 mm ba

12.4

25.52

cat.no 0 373 24 (fixed suppor

min. 567 / max. 630

567

A

B

D

C

A

E F F E

35

A A

cat.nos 0 373 50/51/66/69

cat.no 0 373 20

328344

fixing centre325

25

n Dimensions

pages répartition_18-33.indd 30 19/06/13 14:51

Page 33: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

31

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

support:busbars(1)

addition: supports in enclosure et 975pport in cabledth 475usbars addition to 3 fixednecessary

bar mounting, use fixed

4 bars per pole

575 x 5

100 x 5 125 x 580 x 5

- - -- - -

1700 1700 1700 17001700 1700 1700 17001500 1700 1700 17001250 1450 1650 17001100 1300 1450 1650

0 1150 1300 14501050 1150 1350850 1000 1100750 850 950650 750 850600 650 750550 600 700500 550 600450 550 550400 500 550400 450 500350 400 450350 400 350300 350 300300 350 300300 300 250250 300 250250 250 200250 250 200

50/51/66/67/68/69/86

1000

8

125

110

148

40

208

cat.no 0 374 36

65 50 50 50 6540

9

433

400

cat.no 0 373 15

8620

270

250

100

cat.no 0 373 10

345

40

A

300

fixing centre 325

B

cat.no 0 373 22 (fixed support)40

A

300

B

cat.no 0 373 23 (additional support)

Side for 12 x 4 mm bar

12.4 25.5

4

cat.no 0 373 96

7014 83

125

110

118

40

188

cat.no 0 374 32cat.no 0 374 376.2

256.2

17.5

35

75

42= =

==

53

cat.no 0 373 98Side for 12 x 2 mm bar View from above

12.4

25.52 Ø 4.5

Ø 9

25.5

8.7

8.7

cat.no 0 373 24 (fixed support)

min. 567 / max. 630

567

A B

9425

2512

.5 567

A

94

cat.no 0 373 25 (additional support)

B

D

C

A

E F F E

70

99

35

A A

Ø 6.5

D

C

B

E F F E

3570

70

99

199

Ø 6.5

A A A

cat.nos 0 373 50/51/66/69 cat.nos 0 373 67/69

cat.nos a b c D e f0 373 66 75 350 330 300 75 75

0 373 68 125 600 580 550 150 125

0 373 67 75 350 330 300 75 75

0 373 69 125 600 580 550 150 125

0 373 50 75 - 330 300 75 75

0 373 51 125 - 580 550 150 125

bars thick 5 or 10 mm

cat.nos Dim. (mm) h75 h80 h100 h120 h125

0 373 24a 151 156 176 196 201

b 187.5 192.5 215.5 232.5 237.5

0 373 25 a 151 156 176 196 201

copper barDim.(mm) 50 x 5 63 x 5 75 x 5 80 x 5 100 x 5

a 112 125 137 142 162

b 126 126 171 171 171

cat.no 0 373 20 cat.no 0 373 21

328344

fixing centre325

36.5

99.5

25

36440

A

295

fixing centre 325

copper barDim.(mm) 50 x 5 63 x 5 75 x 5 80 x 5

a 217 230 242 247

n Dimensions

pages répartition_18-33.indd 31 19/06/13 14:51

Page 34: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

32

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

Flat copper bars selectionstandard distribution

≤ 400 a ≤ 800 a ≤ 1000 a ≤ 1600 a

Flat busbars supports Cat.Nos 0 373 22/23

Cat.No 0 373 10 Cat.No 0 373 15 Cat.No 0 373 20 Cat.No 0 373 21 bar mounting:edgewise

bar

Flat copper bars

cat.noscross

section(mm)

number of barper pole

I (a) I (a) I (a) I (a) I (a)

IP ≤ 30 IP > 30 IP ≤ 30 IP > 30 IP ≤ 30 IP > 30 IP ≤ 30 IP > 30 IP ≤ 30 IP > 30 IP ≤ 3

0 374 34 18 x 4 1 245 200 245 200 245 200 - - - - -

0 374 38 25 x 4 1 280 250 - - - - - - - - -

0 374 18 25 x 5 1 330 270 330 270 330 270 - - - - -

0 374 19 32 x 5 1 450 400 450 400 450 400 - - - - -

0 374 40 50 x 5

1 - - - - 700 630 700 630 700 630 430

2 - - - - - - - - 1150 1000 650

3 - - - - - - - - - - -

4 - - - - - - - - - - -

0 374 41 63 x 5

1 - - - - 800 700 800 700 800 700 500

2 - - - - - - - - 1350 1150 770

3 - - - - - - - - - - -

4 - - - - - - - - - - -

0 374 59 75 x 5

1 - - - - - - 950 850 950 850 600

2 - - - - - - - - 1500 1300 890

3 - - - - - - - - - - -

4 - - - - - - - - - - -

0 374 43 80 x 5

1 - - - - - - 1050 900 1000 900 630

2 - - - - - - - - 1650 1450 940

3 - - - - - - - - - - -

4 - - - - - - - - - - -

0 374 46

100 x 5

1 - - - - - - - - 1250 1050 750

2 - - - - - - - - 1900 1600 1120

3 - - - - - - - - - - -

4 - - - - - - - - - - -

125 x 5

1 - - - - - - - - - - -

2 - - - - - - - - - - -

3 - - - - - - - - - - -

4 - - - - - - - - - - -

80 x 10

1 - - - - - - - - - - -

2 - - - - - - - - - - -

3 - - - - - - - - - - -

100 x 10

1 - - - - - - - - - - -

2 - - - - - - - - - - -

3 - - - - - - - - - - -

120 x 10

1 - - - - - - - - - - -

2 - - - - - - - - - - -

3 - - - - - - - - - - -

pages répartition_18-33.indd 32 19/06/13 14:51

Page 35: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

33

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

Copper bars and accessories

≤ 1000 a ≤ 1600 a ≤ 4000 a

Cat.Nos 0 373 22/23 Cat.Nos 0 373 24/25

Cat.No 0 373 21 bar mounting:edgewise

bar mounting:flat

bar mounting:edgewise

bar mounting:flat

I (a) I (a) I (a) I (a) I (a)

IP ≤ 30 IP > 30 IP ≤ 30 IP > 30 IP ≤ 30 IP > 30 IP ≤ 30 IP > 30 IP ≤ 30 IP > 30

- - - - - - - - - -

- - - - - - - - - -

- - - - - - - - - -

- - - - - - - - - -

700 630 700 630 430 350 700 630 500 420

- - 1150 1000 650 510 1180 1020 750 630

- - - - - - 1600 1380 1000 900

- - - - - - 2020 1720 1120 1000

800 700 800 700 500 400 800 700 600 500

- - 1350 1150 770 590 1380 1180 750 630

- - - - - - 1900 1600 1100 1000

- - - - - - 2350 1950 1350 1200

950 850 950 850 600 475 950 850 700 600

- - 1500 1300 890 700 1600 1400 1000 850

- - - - - - 2200 1900 1250 1100

- - - - - - 2700 2300 1600 1400

1050 900 1000 900 630 500 1000 900 750 630

- - 1650 1450 940 740 1700 1480 1050 900

- - - - - - 2350 2000 1300 1150

- - - - - - 2850 2400 1650 1450

- - 1250 1050 750 580 1250 1050 850 700

- - 1900 1600 1120 900 2050 1800 1200 1050

- - - - - - 2900 2450 1600 1400

- - - - - - 3500 2900 1900 1650

- - - - - - 1450 1270 1000 800

- - - - - - 2500 2150 1450 1250

- - - - - - 3450 2900 1800 1600

- - - - - - 4150 3450 2150 1950

- - - - - - 1460 1270 1150 950

- - - - - - 2500 2150 1700 1500

- - - - - - 3450 2900 2500 2000

- - - - - - 1750 1500 1350 1150

- - - - - - 3050 2550 2000 1650

- - - - - - 4150 3500 2900 2400

- - - - - - 2000 1750 1650 1450

- - - - - - 3600 2950 2500 2000

- - - - - - 4800 4000 3500 3000

"Standard" distribution

0 374 19 + 0 373 11

0 374 40 0 374 10

Pack Cat.Nos copper bars

rigid, flat, threaded holesCross

section(mm)

I permissible(A) HolesØ mm

Length(mm)IP ≤ 30 IP >30

10 0 373 88 12 x 2 110 80 M5 99010 0 373 89 12 x 4 160 125 M5 99010 0 374 33 15 x 4 200 160 M5 990

10 0 374 34 18 x 4 245 200 M6 99010 0 374 38 25 x 4 280 250 M6 990

4 0 374 18 25 x 5 330 270 M6 17504 0 374 19 32 x 5 450 400 M6 1750

rigid flat clear holesCross

section(mm)

I permissible(A)HolesØ mm

Length(mm)IP ≤ 30 IP >30

1 0 374 40 50 x 5 700 630 10.5 - 6.5 17501 0 374 41 63 x 5 800 700 10.5 - 8.5 17501 0 374 59 75 x 5 950 850 10.5 - 6.5 17501 0 374 43 80 x 5 1000 900 10.5 - 6.5 17501 0 374 46 100 x 5 1250 1050 10.5 - 6.5 1750

FlexibleSupplied flat, length 2 m

Crosssection(mm)

I (A)

IP ≤ 30 IP >301 0 374 10 13 x 3 200 1601 0 374 67 20 x 5 400 2501 0 374 11 24 x 4 400 2501 0 374 12 32 x 5 630 4001 0 374 57 50 x 5 850 6301 0 374 58 50 x 10 1250 1000

accessoriesIsolating profile

1/10 0 373 11 Isolating profile for flat copper bars 18 x 4,25 x 4, 25 x 5 and 32 x 5 mm, length 1 mSupplied with fixing clips

Insulating screws50 0 367 74 M6 x 10

HF screws with contact washe50 0 367 75 M6 x 10

255 Ø 8,5

184

184

2525

5

12.5

pages répartition_18-33.indd 33 19/06/13 14:51

Page 36: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

34

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

HX³ optimised

HX³/VX³ IS inc

VX³ optimised distribution system selection

VX³distribution

system

Imax(A) Mounting Cat.Nos

Plexo³XL³ 125XL³ 160

XL³ 400 XL³ 800 XL³ 4000

VX³ 4-poleautomaticterminalsvertical

distributionblock(p. 36)

63 A side-mounted

For cabinetswith 3 rows:

4 rows:5 rows:6 rows:

4 050 234 050 244 050 254 050 26

l

125 A side-mounted

For cabinetswith 4 rows:

5 rows:6 rows:

4 050 344 050 354 050 36

l(1) l

VX³busbars

400 A

(p. 40)

Verticalat back ofenclosure

Insulatedbackplate:

Support:Supp. for lug:

250 A bar:400 A bar:

4 044 364 044 374 044 384 044 304 044 31

l

Vertical incable sleeve

Support:Supp. for lug:

250 A bar:400 A bar:

4 044 504 044 514 044 304 044 31

l

800 A

(p. 41)

Verticalat back ofenclosure

Support:Supp. for lug:

800 A bar:

4 044 604 044 614 044 33

l l

Vertical inexternal cable

sleeve

Support:Supp. for lug:

800 A bar:

4 044 704 044 714 044 33

l

1600 A

(p. 42)

XL³ 4000

630 A bar: 0 373 54800 A bar: 0 373 55

1000 A bar: 0 373 561250 A bar: 0 373 571600 A bar: 0 373 58

Positions of bars Aligned Stepped:

Fixing centres ofbars 75 mm 125 mm 75 mm 125 mm

Fixed support 0 373 66/86 0 373 68 0 373 67 0 373 69

Additional support 0 373 50 0 373 51 - -

L(mm)

vertical en fondd'armoire

L: 475 mm l

L: 725 mm l l

L: 975 mm l l

P(mm)

Side-mountedvertical in

enclosure behinduprights

D: 475 mm

D: 725 mm l(2) l

D: 975 mm l(2) l

P(mm)

Vertical in cablesleeve*

D: 475 mm l(2) l

D: 725 mm l(2) l l l

D: 975 mm l(2)(3) l(3) l(3) l(3)

P(mm)

Horizontal top orbottom

D: 475 mm l(2)

D: 725 mm l(2) l

D: 975 mm l(2) l

P(mm)

Horizontal transfer

D: 475 mm

D: 725 mm l(2) l

D: 975 mm l(2) l

1: XL3 160 only2: Only these configurations take the VX3 optimised prefabricated connection kits3: With upright Cat.Nos 0 205 20/51

HX³ distribut

HX³ universal singlepole prong-type

busbar (p. 19)

HX³ 4-pole prong-typbusbar (p. 19)

HX³ 4-pole automatiterminals

distribution block(p. 37)

HX3 4-pole plug-indistribution blocks

(p. 38)

HX³ 4-pole rowdistribution blocks

(p. 39)

1: With 125 A power supply m3: Without connection, power

VX³ IS columnchassis

(p. 48)

VX³ IS basesfor devices

(p. 48)

4-pole rowdistribution

blocks(p. 46-47)

pages répartition_34-49.indd 34 02/07/13 08:54

Page 37: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

35

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

HX³ optimised distribution system selection

HX³/VX³ IS increased safety distribution system selection

³ 800 XL³ 4000

l l

l

Stepped:

mm 125 mm

3 67 0 373 69

-

l

l l l

3) l(3)

HX³ distribution system Imax Cat.NosEnclosures

EkinoxeXL³ 125Plexo³

XL³ 160 XL³ 400 XL³ 800 XL³ 4000

HX³ universal singlepole prong-type

busbar (p. 19)63 A

4 049 26 (13 modules)4 049 37 (57 modules)

l l l l l l

HX³ 4-pole prong-typebusbar (p. 19)

63 A4 052 00 (6 modules)4 052 01 (12 modules)4 052 02 (18 modules)

l l l l l l

HX³ 4-pole automaticterminals

distribution block(p. 37)

125 A 4 052 30 (1 row)4 052 31(1/2 row)

l(1/2 row)

l l l l

HX3 4-pole plug-indistribution blocks

(p. 38)

80 A4 052 40 (24 modules)4 052 41 (36 modules)

l l l l

125 A 4 052 40(1) (24 modules)4 052 41(1) (36 modules) l l l l

HX³ 4-pole rowdistribution blocks

(p. 39)

250 A4 044 80(2) (24 modules)4 044 81(2) (24 modules)

l

400 A4 044 83(2) (24 modules)4 044 84(2) (24 modules)

l l

1: With 125 A power supply module Cat.No 4 052 42 - 2: With direct connection, power supply via busbar at back of enclosure3: Without connection, power supply via head of row device or side-mounted power supply module Cat.No 4 044 82

Mounting in XL³ 4000 enclosures IS 223 IS 233 IS 333

VX³ IS columnchassis

(p. 48)

Uprights,isolating supports,form 4b partitioning

For depth 725 mm 4 046 00 4 046 00 4 046 00

For depth 975 mm 4 046 02 4 046 02 4 046 02

Tinned copperaluminium busbars

1250 A 4 046 04 4 046 04 4 046 04

2000 A 4 046 06 4 046 06 4 046 06

VX³ IS basesfor devices

(p. 48)

DPX³ 160

3P 4 046 10 4 046 20 4 046 40

4P 4 046 11 4 046 21 4 046 41

DPX³ 160 withe.l.c.bs 4P 4 046 11 4 046 31 4 046 51

DPX³ 250

3P 4 046 12 4 046 22 4 046 42

4P 4 046 13 4 046 23 4 046 43

DPX³ 250 withe.l.c.bs 4P 4 046 13 4 046 33 4 046 53

DPX 630

3P 4 046 16 4 046 26 4 046 46

4P 4 046 17 4 046 27 4 046 47

DPX 630 with withe.l.c.bs

3P 4 046 16 4 046 36 4 046 56

4P 4 046 17 4 046 37 4 046 57

4-pole rowdistribution

blocks(p. 46-47)

HX³ 125 A IS(connection modules: see p. 46) 4 046 68 - -

HX³ 400 A IS(support bases: see p. 47) 4 046 60 - -

pages répartition_34-49.indd 35 02/07/13 08:54

Page 38: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

36

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

HX3 125 A autodistribution bl

VX3 63 and 125 A automatic terminalsvertical distribution blocks - 4-pole

VX3 63 and 125 A automatic terminalsvertical distribution blocks - 4-pole

IP XXB 4-pole distribution block with automatic output terminalsFor distribution using flexible wires with or without ferrulesPower supply via the top or bottom, via screw terminalsSupplied with blanking plates for unused supply terminals and fixing lugsfor side-mounting in different enclosuresConnection/disconnection operations only with power off

n Technical characteristicsRated voltage (Ue): 230/400 V±Rated frequency: 50/60 HzPermissible short-circuit current (Ipk):- VX3 63 A automatic terminals: 20 kÂ- VX3 125 A automatic terminals: 30 kÂInsulation voltage (Ui): 500 V±Protection index: IP XXB

4 050 23 4 050 24 4 050 25 4 050 26 4 050 34 4 050 35 4 050 36A 336 461 586 711 506 631 756

B 324 449 574 699 478 603 728

Pack Cat.Nos VX3 63 A automatic terminals verticaldistribution blocksFor side-mounting in Plexo3, XL3 125 and XL3 160cabinets- Fixing lugs on rack for adjusting the vertical positionTerminals capacity:- Incoming lines (power supply): 6 to 16 mm2

(flexible)/25 mm2 (rigid)- Outgoing lines: 4 to 10 mm2 (flexible)

2 4 050 23 For cabinets with 3 rowsPhase: 3 x 4 outgoing linesNeutral: 6 outgoing lines

2 4 050 24 For cabinets with 4 rowsPhase: 3 x 6 outgoing linesNeutral: 9 outgoing lines

2 4 050 25 For cabinets with 5 rowsPhase: 3 x 8 outgoing linesNeutral: 12 outgoing lines

2 4 050 26 For cabinets with 6 rowsPhase: 3 x 10 outgoing linesNeutral: 15 outgoing lines

VX3 125 A automatic terminals verticaldistribution blocksFor side-mounting in XL3 125 and XL3 160 cabinetsTerminals capacity:- Incoming lines (power supply): 16 to 35 mm2

(flexible)/50 mm2 (rigid)- Outgoing lines: 6 to 16 mm2 (flexible)

1 4 050 34 For cabinets with 4 rowsPhase: 3 x 6 outgoing linesNeutral: 9 outgoing lines

1 4 050 35 For cabinets with 5 rowsPhase: 3 x 8 outgoing linesNeutral: 12 outgoing lines

1 4 050 36 For cabinets with 6 rowsPhase: 3 x 10 outgoing linesNeutral: 15 outgoing lines

4 050 344 050 24

n Dimensions

VX3 63 A VX3 125 A

65

99

55

B

A

83

70

79

39

B A

4 052 30

Pack Cat.Nos HXdisTer- Inor flsuppl- O

1 4 052 30 ForForPhaNeut

1 4 052 31 ForForXL3

PhaNeu

IP XXB 4-pole distributiFor distribution in rows uwiresPower supply via the topSupplied with fixing lugXL3 125, XL3 160 and XLmanagementCan be fitted on a solid p

Technical characteristics see opposite

Technical characte

pages répartition_34-49.indd 36 02/07/13 08:54

Page 39: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

37

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

HX3 125 A automatic terminals horizontaldistribution blocks - 4-pole

HX3 125 A automatic terminals horizontaldistribution blocks - 4-pole

erminals4-pole

35 4 050 36756

728

25 A99

55

B

A

4 052 30

Pack Cat.Nos HX3 125 A automatic terminals horizontaldistribution blocksTerminals capacity:- Incoming lines (power supply): 10 to 35 mm2 (rigidor flexible) limited to 25 mm2 with feedthrough powersupply- Outgoing lines: 0.5 to 6 mm2

1 4 052 30 For complete rowFor mounting in XL3 160/400/800/4000 enclosuresPhase: 3 x 9 outgoing linesNeutral: 18 outgoing lines

1 4 052 31 For 1/2 rowFor mounting in Plexo3 cabinets andXL3 125/160/400/800/4000 enclosuresPhase: 3 x 4 outgoing linesNeutral: 8 outgoing lines

IP XXB 4-pole distribution blocks equipped with automatic terminalsFor distribution in rows using flexible wires with or without ferrules or rigidwiresPower supply via the top, bottom or feedthrough via screw terminalsSupplied with fixing lugs for mounting on 3 rails in Plexo3 cabinets,XL3 125, XL3 160 and XL3 400 enclosures and brackets for wiremanagementCan be fitted on a solid plate

n Technical characteristicsRated voltage (Ue): 230/400 V±Rated frequency: 50/60 HzPermissible short-circuit current (Ipk): 20 kÂInsulation voltage (Ui): 500 V±Impulse voltage Uimp: 6 kV - degree of pollution 3Rated current: 125 AProtection index: IP XXB

n Dimensions

Cat.No 4 052 30

Cat.No 4 052 31

52 4645

130

54

254 50

52 4645

130

54

454 50

Technical characteristics see opposite

pages répartition_34-49.indd 37 02/07/13 08:54

Page 40: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

38

4 052 46

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

HX³ 400 A opthorizontal mounting

HX3 80/125 A plug-in systemhorizontal distribution blocks - 4-pole

HX3 80/125 A plug-in systemhorizontal distribution blocks - 4-pole

Pack Cat.Nos HXForTakCap

1 4 044 80 Witbac

1 4 044 81 Wit1 4 044 82 Sid

blodist

HXForTakdevCap

1 4 044 83 Witbac

1 4 044 84 Wit1 4 044 82 Sid

blodist

HXFor250Sup

Fo1 4 045 00 3P1 4 045 01 4P w

Fo1 4 045 02 3P1 4 045 03 4P w

HX

ForHXThebloPlu

1 4 045 08 For1 4 045 09 For1 4 045 10 For1 4 045 11 For1 4 045 12 For1 4 045 13 For

Wir1 4 045 15 For1 4 045 16 For1 4 045 17 For1 4 045 18 For1 4 045 19 For1 4 045 20 For

Wir1 4 045 21 For1 4 045 22 For1 4 045 23 For1 4 045 24 For1 4 045 25 For1 4 045 26 For

Un1 4 045 27 Em

4 044 84

4 052 40 + 4 052 42

4 052 454 052 43 4 052 44

Pack Cat.Nos HX3 80/125 A plug-in system horizontaldistribution blocksDistribution blocksFixed directly onto rails Cat.Nos 0 202 06, 0 206 01and 0 206 51Maximum rated current:- 80 A when supplied via head of row device- 125 A when equipped with power supply moduleCat.No 4 052 42

1 4 052 40 24 modules1 4 052 41 36 modules

125 A power supply module1 4 052 42 Power supply module and protection cover

Connection modulesUsed for automatic connection and disconnectionof modular devices on the HX3 80/125 A plug-indistribution blockFor 1 module per pole devices

1 4 052 43 Pack of 10 connection modules L11 4 052 44 Pack of 10 connection modules L21 4 052 45 Pack of 10 connection modules L31 4 052 46 Pack of 10 connection modules N

Accessory for mounting in XL3 160 enclosure1 4 052 24 Used for mounting the 24 modules HX3 125 A

plug-in distribution block Cat.No 4 052 20 in XL3 160enclosures

Used for 3-phase distribution without wiring of DX/DX3 modular devicesup to 125 A on a single rowAutomatic connection and disconnection of equipment totally safely,thanks to the distribution block's IP XXB insulationProtection devices can be added or removed even whenHX3 80/125 distribution block is powered-up, thanks to the integralconnection modulesPower supply module and head of row device canbe removed only after cutting off the power of HX³ distribution blockTotal freedom to install and combine devices: 1P+N, 2P, 3P, 4P, add-onmodules modules, auxiliaries, control devices, etcSelection of the phase to be connected by selecting the connectionmoduleFor mounting in XL3 400/800/4000 enclosures with 2-position aluminiumrail Cat.Nos 0 202 01 and 0 206 01/51 and in XL3 160 enclosures with themounting accessory Cat.No 4 052 24

n Technical characteristicsRated voltage (Ue): 230/400 V±Rated frequency: 50/60 HzPermissible short-circuit current (Ipk): 25 kÂInsulation voltage (Ui): 690 V±Maximum rated current:- 125 A when equipped with power supply module Cat.No 4 052 42- 80 A when supplied via head of row deviceProtection index: IP 20Maximum connection cross-section for the power supply module: 50 mm2

Compatible DX3 modular devices Connection modules1P+N RCBOs for protecting the outgoing lines

4 052 43/44/45/46(L1, L2, L3, N)

2P RCCBs for protecting the outgoing lines4P RCCBs for protecting the outgoing lines4P RCBOs for protecting the outgoing lines2P RCBOs for protecting the outgoing lines1P, 2P, 3P, 4P circuit breakers, 1 module/pole(1)

1: Except for products dedicated to the HX3 4-pole supply busbar

n Installation

Direct power supply via the power supply module (for protectingthe outgoing lines) - maximum rated current 125 A

D1DX3 C4P20A

D2DX3 C2P32A

D3DX3 C4P20A

D1DX3 C4P20A

D2DX3 C1P16A

D3DX3 C1P16A

Indirect power supply via head of row device - maximum ratedcurrent 80 AThe distribution block is protected by the head of group device and itsrated current is limited by the latter's rating

D2DX3 C1P16A

D3DX3 C1P16A

D4DX3 C1P16A

D1DX3 C4P40A

Technical characteristics see opposite

pages répartition_34-49.indd 38 02/07/13 08:54

Page 41: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

39

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

HX³ 400 A optimised distribution systemhorizontal mounting in XL3 400, XL3 800 and XL3 4000 enclosures

HX³ 400 A optimised distribution systemhorizontal mounting in XL3 400, XL3 800 and XL3 4000 enclosuress - 4-pole

75.5

69.5

27

140.

25

Pack Cat.Nos HX³ 250 A row distribution blockFor mounting in XL3 400 enclosuresTake bases for DPX3 and bases for DX3 devicesCapacity 24 modules

1 4 044 80 With direct connection on VX3 250/400 A busbars atback of enclosure

1 4 044 81 Without connections1 4 044 82 Side-mounting power supply module for distribution

block without connections for 250 and 400 Adistribution block

HX³ 400 A row distribution blockFor mounting in XL3 800 and XL3 4000 enclosuresTake the support bases for DPX3 and for modulardevicesCapacity 24 modules

1 4 044 83 With direct connection on VX3 800 A busbars atback of enclosure

1 4 044 84 Without connections1 4 044 82 Side-mounting power supply module for distribution

block without connections for 250 and 400 Adistribution block

HX³ support bases for DPX³ MCCBsFor automatic connection of DPX³ MCCBs on HX³250 A and 400 A row distribution blocksSupplied with terminal shields

For DPX3 1601 4 045 00 3P1 4 045 01 4P with or without e.l.c.bs

For DPX³ 2501 4 045 02 3P1 4 045 03 4P with or without e.l.c.bs

HX³ support bases for DX³ modular devices

For automatic connection of DX3 devices onHX³ 250 and 400 A row distribution blocksThe bases are supplied via the distributionblockPlug-in bases for 1 module per pole DX³

1 4 045 08 For 4-pole DX3

1 4 045 09 For 3-pole DX3

1 4 045 10 For single pole DX3 - Phase L11 4 045 11 For single pole DX3 - Phase L21 4 045 12 For single pole DX3 - Phase L31 4 045 13 For single pole DX3 - Neutral N

Wired bases for 1.5 module per pole DX³1 4 045 15 For 4-pole DX3

1 4 045 16 For 3-pole DX3

1 4 045 17 For single pole DX3 - Neutral N1 4 045 18 For single pole DX3 - Phase L11 4 045 19 For single pole DX3 - Phase L21 4 045 20 For single pole DX3 - Phase L3

Wired bases for 1 module per pole DX³ - In ≤ 63 A1 4 045 21 For 4-pole DX3

1 4 045 22 For 3-pole DX3

1 4 045 23 For single pole DX3 - Neutral N1 4 045 24 For single pole DX3 - Phase L11 4 045 25 For single pole DX3 - Phase L21 4 045 26 For single pole DX3 - Phase L3

Universal base1 4 045 27 Empty base, 1 module without power supply

4 044 824 044 84 4 045 01

n Technical characteristicsRated voltage (Ue): 230/400 V±Rated frequency: 50/60 HzPermissible short circuit current (Ipk): xx kAInsulation voltage (Ui): 1000 VRated current: 250/400 A maximum (central power supply)Protection index: IP 20Maximum connection cross-section for the power supply module:flexible bars 32 x 4 mm

n Installation

n Dimensions

Direct power supplyVia busbars at back of enclosure

Cat.Nos 4 045 00/01/02/03

Bases for DX³

Indirect power supplyVia head of row device

600

432

208.

5

184.

08

Cat.Nos A B C4 045 00 150 108 2454 045 01 150 108 2454 045 02 150 139,5 266,54 045 03 150 139,5 266,5

Cat.Nos A B4 044 80/81 515 208.54 044 83/84 600 202

"Plug-in" "Wired"

Cat.Nos 4 044 82/85Cat.Nos 4 044 80/81/83/84

245

99.5

B

C

69B

A

37.5

Via busbars in cable sleeve

Cat.Nos 4 044 80/83 Cat.Nos 4 044 81/84

Cat.Nos 4 044 81/84 Cat.No 4 044 82 Cat.No 4 044 87

110.7

69.518

140.

25

le Cat.No 4 052 42

upply module: 50 mm2

Connection modules

4 052 43/44/45/46(L1, L2, L3, N)

odule (for protecting125 A

D2DX3 C1P16A

D3DX3 C1P16A

maximum rated

group device and its

pages répartition_34-49.indd 39 02/07/13 08:54

Page 42: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

40

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

VX3 800 A optivertical mounting in X

HX3/VX3 optimised distribution systemvertical mounting in XL3 400 enclosures

VX3 400 A optimised distribution systemvertical mounting in XL3 400 enclosures

n Mounting options

Set of busbars at back of enclosure

Set of busbars in external cable sleeve and main devicein enclosure

Set of busbars and main device in external cable sleeve

C-section bars Cat.No 4 044 30 + supports Cat.No 4 044 50+ connection kit Cat.No 4 044 54

Pack Cat.Nos VX3 250/400 A optimised distribution systemof aluminium busbarsComplete kit

1 4 044 35 Complete kit containing: 1 XL3 400 enclosure height1900 mm + 1 insulated backplate + 3 isolatingsupports + 1 lug support + 4 x 400 A busbars+ 1 set of IP 2x isolating profiles

Tinned copper aluminium C-section busbarsElectrolytic compatibility with copper guaranteed

1 4 044 30 250 A - height 1600 mm1 4 044 31 400 A - height 1600 mm

Mounting accessories for busbars at back ofenclosureFor mounting in XL3 400 enclosuresThe tinned copper aluminium C-section busbarsmust be inserted in an insulated backplate and heldin place by isolating supportsBusbar fixing centres 43 mm

5 4 044 36 Insulated backplate for enclosure height 1900 mm1 4 044 37 Isolating support for aluminium C-section busbar1 4 044 38 Isolating lug support for aluminium C-section busbar6 4 044 39 Set of isolating profiles for IP 2x busbar protection

Mounting accessories for aluminium busbarsin cable sleeveFor mounting in XL3 400 external cable sleeve or inXL3 800 internal cable sleeve

1 4 044 50 Isolating support for aluminium C-section busbar1 4 044 51 Isolating lug support for aluminium C-section busbar

Accessories for 250 and 400 A aluminiumbusbars

1 4 044 90 IP 2X 250 A tap-off terminal80 4 044 91 M8 hammer screws

Prefabricated connection kitsRigid copper busbars for connecting devices on VX3

250/400 A set of aluminium busbarsSupplied with screws

For supplying a set of busbars at the backof the enclosure

1 4 044 40 Via a DPX3 160 with or without e.l.c.bs1 4 044 41 Via a DPX3 250 with or without e.l.c.bs1 4 044 42 Via a DPX 630 with or without e.l.c.bs1 4 044 43 Via a DPX-IS 2501 4 044 44 Via a DPX-IS 630

For supplying a set of busbars in a cable sleevevia a device in a cable sleeve

1 4 044 52 Via a DPX3 160 with or without e.l.c.bs1 4 044 53 Via a DPX3 250 with or without e.l.c.bs1 4 044 54 Via a DPX 630 with or without e.l.c.bs

For connecting a horizontal device in anenclosure on a set of busbars in a cable sleeve

1 4 044 57 Via a DPX3 160 with or without e.l.c.bs1 4 044 55 Via a DPX3 250 with or without e.l.c.bs1 4 044 58 For a DPX 630 with or without e.l.c.bs

For connecting a HX3 250 row distribution blockon a set of busbars in a cable sleeve

1 4 044 87 For one row distribution block Cat.No 4 044 81equipped with side mounting power supply moduleCat.No 4 044 82

C-section bars Cat.No 4 044 33+ connection kit Cat.No 4 044 6

Pack Cat.Nos VXof aConsbusord

TinEle

1 4 044 33 800

MoencFor

1 4 044 60 Iso1 4 044 61 Iso1 4 044 62 Set

MosleFor

1 4 044 70 Iso1 4 044 71 Iso

Acc1 4 044 89 IP 2

80 4 044 92 M8 h

PrefPredevSuppl

Forenc

1 4 044 63 Via1 4 044 64 Via1 4 044 65 Via1 4 045 30 Via

bus1 4 045 31 Via

bus

Forvia

1 4 044 72 Via

Forenc

1 4 044 73 Via1 4 044 74 Via1 4 044 75 For1 4 044 76 For

Foron a

1 4 044 86 ForequCat

For1 4 044 77 For

with

DPX3 160/250DPX 630

Power supply kitCat.Nos 4 044 40/41

Power supply kitCat.No 4 044 42

Plug-in HX³ 125 Arow distributionblock Cat.No 4 052 20

HX³ 250 A rowdistribution blockCat.No 4 044 80

Row distribution blocks supplied by side-mounted busbars must beequipped with power supply module Cat.Nos 4 044 82/85

DPX3 160/250

DPX3

160/250Connectionkit Cat.No4 044 87

DPX 630Power supply kitCat.Nos 4 044 52/53

Connectionkit Cat.No4 044 55/57

Connectionkit Cat.No4 044 87

Power supply kitCat.No 4 044 54

HX³ 250 A row distribution blockCat.No 4 044 81with power supply moduleCat.No 4 044 82

HX³ row distribution blockCat.No 4 044 81with power supply moduleCat.No 4 044 82

Connection kitCat.No 4 044 87

Connection kitCat.No 4 044 58

Connection kitCat.Nos 4 044 55/57

DPX 630

DPX³ 160/250

Technical characteristics see opposite Technical characte

pages répartition_34-49.indd 40 02/07/13 08:54

Page 43: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

41

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

HX3/VX3 optimised distribution systemvertical mounting in XL3 800 enclosures

VX3 800 A optimised distribution systemvertical mounting in XL3 800 and XL3 4000 enclosures

on system

n Mounting options

Set of busbars at back of enclosure

Set of busbars in external cable sleeve and main devicein enclosure

main device

ble sleeve

Set of busbars and main device in external cable sleeve

C-section bars Cat.No 4 044 33 + Supports Cat.No 4 044 60+ connection kit Cat.No 4 044 63

Pack Cat.Nos VX3 800 A optimised distribution systemof aluminium busbarsConsisting of tinned copper aluminium C-sectionbusbars, held in place by isolating supports (to beordered separately)

Tinned copper aluminium C-section busbarsElectrolytic compatibility with copper guaranteed

1 4 044 33 800 A - height 1600 mm

Mounting accessories for busbars at back ofenclosureFor mounting in XL3 800 and XL3 4000 enclosures

1 4 044 60 Isolating support for 800 A C-section busbars1 4 044 61 Isolating lug support for 800 A C-section busbars1 4 044 62 Set of isolating profiles for IP 2X busbar protection

Mounting accessories for busbars in cablesleeveFor mounting in XL3 800 external cable sleeve

1 4 044 70 Isolating support for 800 A C-section busbars1 4 044 71 Isolating lug support for 800 A C-section busbars

Accessories for 800 A aluminium busbars1 4 044 89 IP 2X 250 A tap-off terminal

80 4 044 92 M8 hammer screw

Prefabricated connection kitsPre-prepared rigid copper busbars for connectingdevices on VX3 800 A set of aluminium busbarsSupplied with screws

For supplying a set of busbars at the back of theenclosure

1 4 044 63 Via a DPX 630 with or without e.l.c.bs1 4 044 64 Via a DPX 16001 4 044 65 Via a DPX-IS 6301 4 045 30 Via a top or bottom horizontal set of aluminium

busbars in XL3 4000 enclosure depth 725 mm1 4 045 31 Via a top or bottom horizontal set of 1600 A copper

busbars in XL3 4000 enclosure depth 725 mm

For supplying a set of busbars in a cable sleevevia a device in a cable sleeve

1 4 044 72 Via a DPX 630 with or without e.l.c.bs

For connecting a horizontal device in anenclosure on a set of busbars in a cable sleeve

1 4 044 73 Via a DPX3 160 with or without e.l.c.bs1 4 044 74 Via a DPX3 250 with or without e.l.c.bs1 4 044 75 For a DPX 630 with or without e.l.c.bs1 4 044 76 For a DPX 1600

For connecting a HX3 400 row distribution blockon a set of busbars in a cable sleeve

1 4 044 86 For one row distribution block Cat.No 4 044 84equipped with side mounting power supply moduleCat.No 4 044 82

For supplying the main circuit breaker upstream1 4 044 77 For a DPX 1600 mounted horizontally in an enclosure

with internal cable sleeve for cable entry

ted busbars must be044 82/85

DPX3

160/250Connectionkit Cat.No4 044 87

DPX 630Power supply kitCat.No 4 044 54

block

module

57

DPX 630

DPX 1600

Power supply kitCat.No 4 044 63

Power supply kitCat.No 4 044 64

Plug-in HX³ 125 Arow distribution blockCat.No 4 052 20

HX³ 400 A rowdistribution blockCat.No 4 044 83

DPX³ 160/250

Power supply kitCat.No 4 044 72

DPX 630

Connection kitCat.No 4 044 86

Connection kitCat.Nos 4 044 73/74

HX³ 400 A row distribution blockCat.No 4 044 84 with power supplymodule 4 044 82

DPX³160/250

DPX 630

DPX 630

DPX 1600Connection kitCat.No 4 044 75

Upstream connectionkit Cat.No 4 044 77

Connection kitCat.No 4 044 76

Connectionkit Cat.No4 044 86

Connection kitCat.Nos 4 044 73/74

Connection kitCat.No 4 044 75

HX³ 400 A row distributionblock Cat.No 4 044 84with power supply moduleCat.No 4 044 82

Technical characteristics see opposite

pages répartition_34-49.indd 41 02/07/13 08:54

Page 44: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

42

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

VX3/HX3 optimVX3/HX3 3200 A optimised distribution systemin XL3 4000 enclosures

0 373 66 0 373 69

Pack Cat.Nos VX3 630 to 1600 A isolating supportsFor tinned copper aluminium C-section busbars

Aligned busbars in enclosure or internal cablesleeveAll configurations possible in XL3 4000 enclosures:- Vertical at the back of the enclosure- Side-mounted vertical behind upright- Side-mounted vertical in internal cable sleeve- Horizontal top or bottom- Horizontal transferInsulation voltage Ui: 1000 VImpulse voltage Uimp: 8 kV

1 0 373 66 75 mm fixing centres for enclosures depth 725 mmor 475 mm in partial chassis

1 0 373 86 75 mm fixing centres for enclosures depth 975 mm1 0 373 50 Additional support with 75 mm fixing centres for

enclosure depth 725 mm1 0 373 68 125 mm fixing centres for enclosures depth 975 mm

The support can be doubled for a current of 3200 A1 0 373 51 Additional support with 125 mm fixing centres for

enclosure depth 975 mm

Staggered busbars in cable sleeveSide-mounted vertically in cable sleeve

1 0 373 67 75 mm fixing centres for cable sleeves depth725 mm and 475 mm

1 0 373 69 125 mm fixing centres for cable sleeves depth975 mmThe support can be doubled (in external cablesleeves only) for a current of 3200 A

Tinned copper aluminium C-sectionbusbarsElectrolytic compatibility with copper guaranteedLength 1780 mm

Cross-section (mm2)

I(A)

IP ≤ 30 IP ≥ 301 0 373 54 524 800 6301 0 373 55 549 1000 8001 0 373 56 586 1250 10001 0 373 57 686 1450 12501 0 373 58 824 1750 1600

Connectors with 6 x 250 A outputs4 0 373 99 Fixed onto aluminium C-section bars with M10

hammer screw Cat.No 0 373 59 or flat copper barsOutput capacity:- 4 x 6 to 35 mm2

- 2 x 6 to 25 mm2

Accessories80 4 044 92 M8 hammer screw4 0 373 59 M10 hammer screw1 0 373 77 Joining kit for support Cat.Nos 0 373 66 and

0 373 68 to create sets of busbars up to 3200 A1 4 044 89 IP 2X 250 A tap-off terminal

n Mounting options

VX3 800 A set of busb

VX3 630 to 1600 A set

VX3 630 to 1600 A set

XL3 4000 depth 475 mPower sumain devup to 800

XL3 4000Power sucopper bto 1600 A

Powerof coppper pofixing c

XL3 4000 depth 475 m

4 045 41

Pack Cat.Nos HX³ row distribution block for 4 DPX³ 160For direct supply of a row of 4 DPX³ from VX³ 630 to1600 A aligned busbars

1 4 045 44 For busbars behind upright in enclosures depth 725or 975 mm

1 4 045 54 For busbars in internal cable sleeve depth 475 mm1 4 045 64 For busbars in internal cable sleeve depth 725 or

975 mm

Connection kits for VX3 busbarsFor connecting vertical aluminium C-section busbarson horizontal busbars

For sets of busbars with the same fixing centresCan be used to extend a set of busbars

1 0 373 82 1 busbar per phase1 0 373 83 2 busbars per phase

For sets of busbars with different fixing centresFor connecting a vertical set of aluminium busbarswith 75 mm fixing centres on a horizontal set ofcopper busbars up to 4000 A with 125 mm fixingcentres

1 4 045 45 For vertical set of aligned busbars fixed behindfunctional upright in enclosure depth 725 mm

1 4 045 46 For vertical set of aligned busbars fixed behindfunctional upright in enclosure depth 975 mm

VX3 prefabricated connection kitsPre-prepared flexible copper busbars for connectingdevices on VX3 630 to 1600 A set of alignedaluminium busbars, 75 mm fixing centresSupplied with screwsKits for fixed circuit breakers without accessories -mounted on fixed plates

For side-mounted set of busbars behind uprightFor mounting in enclosure depth 725 or 975 mm

1 4 045 40 For horizontal DPX3 1601 4 045 41 For horizontal DPX3 2501 4 045 42 For horizontal DPX 6301 4 045 43 For row distribution block Cat.No 4 044 84

For side-mounted set of busbars in internal cablesleeve depth 475 mm

1 4 045 50 For horizontal DPX3 1601 4 045 51 For horizontal DPX3 2501 4 045 52 For horizontal DPX 6301 4 045 53 For row distribution block Cat.No 4 044 84 equipped

with side mounting power supply moduleCat.No 4 044 82

For side-mounted set of busbars in internal cablesleeve depth 725 and 975 mm

1 4 045 60 For horizontal DPX3 1601 4 045 61 For horizontal DPX3 2501 4 045 62 For horizontal DPX 6301 4 045 63 For row distribution block Cat.No 4 044 84 equipped

with side mounting power supply moduleCat.No 4 044 82

Dimensions p. 45For distances between the supports p. 45

pages répartition_34-49.indd 42 02/07/13 08:54

Page 45: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

43

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

VX3/HX3 optimised distribution in XL3 4000 enclosures

n Mounting options

VX3 800 A set of busbars at back of enclosure

VX3 630 to 1600 A set of aligned busbars, 75 mm fixing centres, mounted side by side in enclosure behind functional upright

VX3 630 to 1600 A set of aligned busbars, 75 mm fixing centres, mounted side by side in internal cable sleeve

XL3 4000 depth 725 mm XL3 4000 depth 725 mmXL3 4000 depth 475 mm

Power supply viamain deviceup to 800 A

Power supply via horizontalset of aluminium busbars,1 bar up to 1600 A(75 mm fixing centres)

Power supply via horizontal setof copper busbars, 1 or 2 barsper pole up to 1600 A(75 mm fixing centres)

XL3 4000 depth 725 or 975 mmPower supply via horizontal set ofcopper busbars, 1 or 2 bars per pole upto 1600 A (75 mm fixing centres)

Power supply via horizontal setof copper busbars, 1 or 2 barsper pole up to 1600 A (75 mmfixing centres)

Power supply via horizontal setof copper busbars, 1 or 2 barsper pole up to 1600 A (75 mmfixing centres)

Power supply via horizontal setof copper busbars, 1 to 3 bars

per pole upto 4000 A(125 mm fixingcentres)Partial chassis,depth 725

XL3 4000 depth 725 or 975 mmXL3 4000 depth 475 mm with partial chassis

Power supply kitCat.No 4 045 31

Power supply kitCat.No 4 045 30

HX³ 400 A rowdistribution blockCat.No 4 044 83

HX³ 400 A rowdistribution blockCat.No 4 044 83

DPX 630/1600

Power supply kitCat.Nos 4 044 63/64

HX³ 400 A rowdistribution blockCat.No 4 044 83

HX³ 125 A rowdistribution blockCat.No 4 052 20

HX³ 125 A rowdistribution blockCat.No 4 052 20

HX³ 125 A rowdistribution blockCat.No 4 052 20

DPX 630

DPX³ 250

DPX³ 160

Connection kit Cat.No 4 045 42

Connection kit Cat.Nos 0 373 82/83

Connection kit Cat.No 4 045 41

Connection kit Cat.No 4 045 40

Distribution block for 4 DPX³ 160Cat.No 4 045 44

HX³ 400 A row distribution blockCat.No 4 044 84 with connectionkit Cat.No 4 045 43

Connection kit- Cat.No 4 045 45 (depth 725 mm)- Cat.No 4 045 46 (depth 975 mm)

DPX³ 160

Connection kit Cat.No 4 045 42

Connection kit Cat.No 4 045 41

Connection kit Cat.No 4 045 40

Distribution block for 4 DPX³ 160Cat.No 4 045 44

HX³ 400 A row distribution blockCat.No 4 044 84 with connection kitCat.No 4 045 43

DPX 630

DPX³ 250

DPX 630

DPX³ 250

DPX³ 160

Connection kit Cat.No 4 045 52

Connection kit Cat.No 4 045 51

Connection kit Cat.No 4 045 50

Connection kit Cat.No 4 045 43

Distribution block for 4 DPX³ 160Cat.No 4 045 54

HX³ 400 A row distribution blockCat.No 4 044 84 with powersupply module Cat.No 4 044 82

Connection kitCat.Nos 0 373 82/83

Connection kitCat.No 4 045 45 (depth 725 mm)Cat.No 4 045 46 (depth 975 mm)

Distribution block for 4 DPX³160 Cat.No 4 045 64

HX³ 400 A row distributionblock Cat.No 4 044 84with power supply moduleCat.No 4 044 82

DPX³ 160

Connection kit Cat.No 4 045 62

Connection kitCat.Nos 0 373 82/83

Connection kit Cat.No 4 045 61

Connection kit Cat.No 4 045 60

Connection kit Cat.No 4 045 63

DPX 630

DPX³ 250

ck for 4 DPX³ 160DPX³ from VX³ 630 to

enclosures depth 725

sleeve depth 475 mm sleeve depth 725 or

busbarsnium C-section busbars

e same fixing centresof busbars

ferent fixing centresof aluminium busbars a horizontal set of with 125 mm fixing

bars fixed behinde depth 725 mmbars fixed behinde depth 975 mm

ction kitsbusbars for connectingset of aligned

xing centres

without accessories -

sbars behind uprightpth 725 or 975 mm

.No 4 044 84

sbars in internal cable

.No 4 044 84 equippedpply module

sbars in internal cablem

.No 4 044 84 equippedpply module

XL3 4000 depth 725 or 975 mmPower supply via horizontal set ofcopper busbars, 1 to 3 bars per pole upto 4000 A (125 mm fixing centres)

pages répartition_34-49.indd 43 02/07/13 08:54

Page 46: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

44

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

VX3 optimisedVX³ kits for optimised connectionin XL³ 4000 enclosures

Kits de raccordements VX³ optimiséesjusqu'à 4000 A - en armoires XL³ 4000

Pack Cat.Nos Connection kits for transfer

Angled, drilled copper bars for downstreamconnection of devices on horizontal aluminiumtransfer busbars, fixing centres 75 mmThe busbars can be installed at the top or the bottom

For size 2 DMX³ - 2500 or 3200 AFor mounting in XL³ 4000 enclosures depth725 mm and 975 mm

1 4 043 60 For fixed version1 4 043 61 For inverter fixed version1 4 043 62 For draw-out version1 4 043 63 For DMX³ inverter, draw-out version

For size 1 DMX³ - 1000 to 2000 AFor mounting in XL³ 4000 enclosures depth725 mm and 975 mm

1 4 043 64 For fixed version - 2 bars per pole 1600 to 2000 A1 4 043 65 For inverter fixed version - 2 bars per pole 1600 to

2000 A1 4 043 66 For draw-out version - 2 bars per pole 1600 to

2000 A1 4 043 67 For DMX³ inverter draw-out version

2 bars per pole 1600 to 2000 A1 4 043 68 For fixed version - 1 bar per pole up to 1600 A1 4 043 69 For inverter fixed version - 1 bar per pole up to

1600 A1 4 043 70 For draw-out version - 1 bar per pole up to 1600 A1 4 043 71 For DMX³ inverter draw-out version

1 bar per pole up to 1600 A

For vertical DPX 16001 4 043 80 For fixed version with front terminals in XL³ 4000

depth 475 mm1 4 043 81 For fixed version with front terminals in XL³ 4000

depth 725 mm1 4 043 82 For draw-out version with front terminals in XL³ 4000

depth 725 mm1 4 043 83 For fixed version with rear terminals in XL³ 4000

depth 725 mm1 4 043 84 For draw-out version with rear terminals in XL³ 4000

depth 725 mm

DMX³ connection kits for SCP connectioninterfacesAngled, drilled bars for upstream connection ofDMX³ on prefabricated busbar system entriesFor mounting in XL³ 4000 enclosures depth 725 mmand 975 mm

1 4 043 00 For 1600 A SCP entry, fixed version1 4 043 01 For 2000 A SCP entry, fixed version1 4 043 02 For 2500 A SCP entry, fixed version1 4 043 03 For 1600 A SCP entry, draw-out version1 4 043 04 For 2000 A SCP entry, draw-out version1 4 043 05 For 2500 A SCP entry, draw-out version

SCP connection interfaces for XL³ enclosuresElements used for connecting SCP Zucchini busbarsto XL³ 4000 enclosuresTo be used with the set of 2 roof reinforcementbrackets Cat.No 0 205 29

1 4 050 90 630 A1 4 050 92 1000 A1 4 050 93 1250 A1 4 050 94 1600 A1 4 050 95 2000 A1 4 050 96 2500 A1 4 050 97 3200 A1 4 050 98 4000 A

n Downstream connection of DMX³ on transfer busbar

n Connection of DMX³ supply inverters on transfer busbar

n Vertical DPX 1600 connection on transfer busbarFront terminals Rear terminals

4 043 60 4 043 80 4 050 95

Determining the maximum

Determining the maximum

Dimensions (mm)

Determining the maximum

Cat.Nos 0 373 50/51/6

B

D

C

A

E F F E

35

A A

n VX³ 400 A aluminInsulation voltage in aImpulse voltage (Uimp

n VX³ 800 A aluminInsulation voltage in acImpulse voltage (Uimp

n VX³ 630 to 1600 A aluminium bInsulation voltage in aImpulse voltage (Uimp

Bars

Ipk (kÂ) 30405263738094

105132154

Bars 4 0Ipk (kÂ) 10 1600

21 1600304052

BarsIpk 30

405263738094

105

pages répartition_34-49.indd 44 02/07/13 08:54

Page 47: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

45

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

VX3 optimised vertical distribution systemction

transfer busbar

on transfer busbar

fer busbarnals

Determining the maximum distances between the supports (mm)

Determining the maximum distances between the supports (mm) Dimensions (mm)

Dimensions (mm)

Dimensions (mm)

Determining the maximum distances between the supports (mm)

Cat.Nos 0 373 50/51/66/68

Cat.Nos 4 044 50/51

Cat.Nos 4 044 60/61

Cat.Nos 4 044 70/71

Cat.Nos 0 373 67/69Cat.Nos A B C D E F0 373 66 75 350 330 300 75 75

0 373 68 125 600 580 550 150 125

0 373 67 75 350 330 300 75 75

0 373 69 125 600 580 550 150 125

0 373 50 75 - 330 300 75 75

0 373 51 125 - 580 550 150 125

B

D

C

A

E F F E

70

99

35

A A

Ø 6.5

D

C

B

E F F E

3570

70

99

199

Ø 6.5

A A A

n VX³ 400 A aluminium busbarsInsulation voltage in accordance with EN 60947-1/IEC 60664-1: 1000 VAImpulse voltage (Uimp): 8 kV

n VX³ 800 A aluminium busbarsInsulation voltage in accordance with EN 60947-1/IEC 60664-1: 1000 VAImpulse voltage (Uimp): 8 kV

n VX³ 630 to 1600 A aluminium busbarsInsulation voltage in accordance with EN 60947-1/IEC 60664-1: 1000 VAImpulse voltage (Uimp): 8 kV

0 373 50/66/67 0 373 51/68/69

Bars1 C-section aluminium bar per pole 1 C-section aluminium bar per pole

0 373 54 0 373 55 0 373 56 0 373 57 0 373 58 0 373 54 0 373 55 0 373 56 0 373 57 0 373 58

Ipk (kÂ) 30 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600

40 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

52 800 800 800 800 800 800 800 800 800 800

63 700 700 700 700 700 600 600 600 600 600

73 600 600 600 600 600 500 500 500 500 500

80 600 600 600 600 600 500 500 500 500 500

94 500 500 500 500 500 400 400 400 400 400

105 500 500 500 500 500 400 400 400 400 400

132 - - 500 500 500 - - 400 400 400

154 - - 400 400 400 - - 300 300 300

4 044 37/38 4 044 50/51Insulated backplate Staggered in cable sleeve

Bars 4 044 30 4 044 31 4 044 30 4 044 31Ipk (kÂ) 10 1600 1800 1600 1600

21 1600 1800 800 80030 800 1000 400 50040 800 800 350 40052 400 600 250 300

4 044 60/61 4 044 70/71Back of enclosure Staggered in cable sleeve

Bars 4 044 33 4 044 33Ipk 30 1600 1600

40 1000 100052 800 80063 700 70073 600 60080 500 60094 400 500

105 400 500

195

175

110

43.5 43.5 43.5

325

525

543.95

54.5

3843 66

41.5

70 70 70

70

325

400

425

159

127.

5

70 70

pages répartition_34-49.indd 45 02/07/13 08:55

Page 48: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

46

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

HX3 - IS increaup to 400 A - ho

HX3 125-ISincreased safetydistribution systemup to 125 A - horizontal mounting in XL³ 4000 enclosures

Pack Cat.Nos HX³ 125 A IS 223 row distribution blockPlug-in distribution blockFor mounting on functional uprights in XL³ 4000Automatic connection and disconnection on the VX³IS column chassis in accordance with IS 223

1 4 046 68 Base with power supply via clamps, equipped withHX³ 125 A row distribution block and pre-wiredpower supply module (can not be removed)Width: 24 modulesCapacity: 20 modules

Connection modulesUsed for automatic connection and disconnection ofmodular devices on the 125 A row distribution blockFor 1 module per pole devices

1 4 052 43 Pack of 10 connection modules L11 4 052 44 Pack of 10 connection modules L21 4 052 45 Pack of 10 connection modules L31 4 052 46 Pack of 10 connection modules N

4 046 68

4 052 45

4 046 60

Pack Cat.Nos HX

ForAutIS cTakmo

1 4 046 60 24-clamp

HXForwithbloSup

Fo1 4 045 00 3P1 4 045 01 4P w

Fo1 4 045 02 3P1 4 045 03 4P w

HX

For400ThePlu

1 4 045 08 For1 4 045 09 For1 4 045 10 For1 4 045 11 For1 4 045 12 For1 4 045 13 For

Wir1 4 045 15 For1 4 045 16 For1 4 045 17 For1 4 045 18 For1 4 045 19 For1 4 045 20 For

Wir1 4 045 21 For1 4 045 22 For1 4 045 23 For1 4 045 24 For1 4 045 25 For1 4 045 26 For

Uni1 4 045 27 Em

Technical characteristics p. 47

Technical characte

IS 223:- Optimum upgradingThe automatic connectionbases enable a device ora row distribution block tobe added without having toswitch off the panel

IS 233:- Optimum upgrading- Optimum maintenanceA device is replacedwithout doing anything tothe connections

IS 333:- Optimum upgrading- Optimum maintenance- Optimum operationA "test" positionenables a device to bedisconnected whilekeeping the auxiliariesconnected

IS223, IS233IS333

The service index (IS) guaranteesthe level of service of the panelfor operation, maintenance andupgrade operations. With theVX³ IS IPxxB increased safetyaluminium busbar, Legrand isproviding innovative solutions forlevels 223, 233 and 333

HX³/VX³ IS INCREASEDSAFETY DISTRIBUTIONSYSTEM

4 052 43 4 052 44 4 052 46

pages répartition_34-49.indd 46 02/07/13 08:55

Page 49: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

47

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

HX3 - IS increased safety distributionsystem horizontal mounting

HX3 - IS increased safety distribution systemup to 400 A - horizontal mounting in XL³ 4000 enclosures

ributionsystemL³ 4000 enclosures

tribution block

prights in XL³ 4000sconnection on the VX³nce with IS 223amps, equipped with

ock and pre-wiredot be removed)

on and disconnection of A row distribution block

ses L1es L2es L3es N

4 046 60

Pack Cat.Nos HX3 400 A IS 223 row distribution block

For mounting on functional uprights in XL3 4000Automatic connection and disconnection on the VX³IS column chassis in accordance with IS 223Takes the 4-pole bases for DPX3 and the bases formodular devices

1 4 046 60 24-module distribution block with power supply viaclamps

HX³ support bases for DPX³ MCCBsFor automatic connection of DPX³ MCCBs with orwithout e.l.c.bs on HX³ 400 A IS 223 row distributionblocksSupplied with terminal shields

For DPX3 1601 4 045 00 3P1 4 045 01 4P with or without e.l.c.bs

For DPX³ 2501 4 045 02 3P1 4 045 03 4P with or without e.l.c.bs

HX³ support bases for DX³ modular devices

For automatic connection of DX3 devices on HX³400 A IS 223 row distribution blocksThe bases are supplied via the distribution blockPlug-in base for 1 module per pole DX³

1 4 045 08 For 4-pole DX3

1 4 045 09 For 3-pole DX3

1 4 045 10 For single pole DX3 - Phase L11 4 045 11 For single pole DX3 - Phase L21 4 045 12 For single pole DX3 - Phase L31 4 045 13 For single pole DX3 - Neutral N

Wired bases for 1.5 module per pole DX³1 4 045 15 For 4-pole DX3

1 4 045 16 For 3-pole DX3

1 4 045 17 For single pole DX3 - Neutral N1 4 045 18 For single pole DX3 - Phase L11 4 045 19 For single pole DX3 - Phase L21 4 045 20 For single pole DX3 - Phase L3

Wired bases for 1 module per pole DX³ - In ≤ 63 A1 4 045 21 For 4-pole DX3

1 4 045 22 For 3-pole DX3

1 4 045 23 For single pole DX3 - Neutral N1 4 045 24 For single pole DX3 - Phase L11 4 045 25 For single pole DX3 - Phase L21 4 045 26 For single pole DX3 - Phase L3

Universal base1 4 045 27 Empty base, 1 module without power supply

n HX³ 125 A IS row distribution block

n HX³ 400 A IS row distribution block

4 045 01

HX³ 125 A IS 223row distribution blockCat.No 4 046 68

HX³ 400 A IS 233row distribution blockCat.No 4 046 60

HX³ support basefor DPX3

Cat.Nos 4 045 01/03

Technical characteristics see opposite

pages répartition_34-49.indd 47 02/07/13 08:55

Page 50: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

48

CF-EP0

BATDate :Nom RMF :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom chef de Pub :

Signature :

VX3 - IS increaVX3 2000 - IS increased safety distribution system up to 2000 Avertical mounting in XL³ 4000 enclosures

Pack Cat.Nos VX3 IS xx3 column chassis

Tinned copper aluminium busbar Specialprofile for automatic connection via clampsTakes VX³ IS bases for devices and HX³ ISrow distribution blocksFor distribution conforming to IS 223,233 and 333 according to the bases anddistribution blocks installedSupplied with partitions for form 4bFor mounting in XL³ 4000 enclosures

VX³ IS chassisDepth of enclosure

(mm)Chassis consisting of an upright andisolating supports for aluminium bars725 975

1 4 046 00 4 046 02 For XL3 4000 enclosure height 2200 mm

Faceplate support frames1 0 208 55 Fixed for 725 mm width enclosure or

975 mm width enclosure without internalwiring sleeve

1 0 208 56 Fixed for 975 mm width enclosure withinternal wiring sleeve

VX³ IS xx3 tinned copper aluminium barsFront profile for automatic connectionRear C-section profile for power supplyEquipped with IP 2X isolating profilesHeight 1800 mm

1 4 046 04 1250 A1 4 046 06 2000 A

VX³ IS bases for devicesFor fixing on the functional uprightsPower supply via clampsAutomatic connection and disconnectionon the VX³ IS column chassis

VX³ IS 223 bases

3P 4P

Automatic upstream connectionDownstream connection via front terminals

1 4 046 10 4 046 11 For DPX3 160 with or without e.l.c.bs1 4 046 12 4 046 13 For DPX3 250 with or without e.l.c.bs1 4 046 16 4 046 17 For DPX 630 with or without e.l.c.bs

VX³ IS 233 basesAutomatic upstream connectionAutomatic downstream connection

1 4 046 20 4 046 21 For DPX3 160 without e.l.c.bs1 4 046 22 4 046 23 For DPX3 250 without e.l.c.bs1 4 046 26 4 046 27 For DPX 630 without e.l.c.bs1 4 046 31 For DPX3 160 with e.l.c.bs1 4 046 33 For DPX3 250 with e.l.c.bs1 4 046 36 4 046 37 For DPX 630 with e.l.c.bs

VX³ IS 333 basesAutomatic upstream connectionAutomatic downstream connectionBase for automatic connection module forauxiliaries

1 4 046 40 4 046 41 For DPX3 - 160 without e.l.c.bs1 4 046 42 4 046 43 For DPX3 - 250 without e.l.c.bs1 4 046 46 4 046 47 For DPX 630 without e.l.c.bs1 4 046 51 For DPX3 - 160 with e.l.c.bs1 4 046 53 For DPX3 - 250 with e.l.c.bs1 4 046 56 4 046 57 For DPX 630 with e.l.c.bs

Pack Cat.Nos Equipment for IS increased safetydistribution systemSpecial IS 223/233 faceplatesFaceplates with hinges and lock

1 4 046 70 For 3P/4P DPX3 160/250 with no accessoryHeight 200 mm

1 4 046 71 For 3P/4P DPX 630 with no accessoryHeight 300 mm

10 4 046 72 For 3P/4P DPX3 160/250 with rotary or motor-drivenhandle - Height 200 mm

1 4 046 73 For 3P/4P DPX 630 with rotary or motor-drivenhandle - Height 300 mm

1 4 046 74 Faceplate for HX³ 400 A IS row distribution blockHeight 300 mm

10 4 046 75 Faceplate for HX³ 125 A IS row distribution blockHeight 200 mm

Special IS 333 faceplatesx 4 046 76 Faceplate for HX³ 400 A IS row distribution block

Height 300 mmx 4 046 77 Faceplate for HX³ 125 A IS row distribution block

Height 200 mm1 4 046 80 For 3P/4P DPX3 160/250 with no accessory

Height 200 mm1 4 046 81 For 3P/4P DPX 630 with no accessory

Height 300 mm5 4 046 82 For 3P/4P DPX3 160/250 with rotary or motor-driven

handle - Height 200 mm1 4 046 83 For 3P/4P DPX 630 with rotary or motor-driven

handle - Height 300 mm

Mounting lugs for standard screw-mountingfaceplates

20 4 046 79 (4 lugs) for IS 333 only

Universal bases (height 300 mm)1 4 046 65 IS 2231 4 046 66 IS 2331 4 046 67 IS 333

Connection kits on horizontal busbarsLinking bars prepared for supplying the VX³ IScolumn chassis via the main top or bottom horizontalbusbarSupplied with partitioning housing for the horizontalbusbar

1 4 046 90 For 4000 A copper busbars, In 1250 A(fixing centres 125 mm)

1 4 046 91 For 4000 A copper busbars, In 2000 A(fixing centres 125 mm)

1 4 046 92 For 1600 A aluminium busbars, In 1250 A(fixing centres 75 mm)

1 4 046 93 For 3200 A aluminium busbars, In 2000 A(fixing centres 75 mm)

Connection module for auxiliaries1 4 046 59 for IS 223 and IS 233 bases (supplied with

IS 333 bases)

Partitioning for form1 4 046 85 Partitioning kit for horizontal busbars in internal

wiring sleeve1 4 046 86 Partitioning kit for horizontal busbars in external

wiring sleeve1 4 046 87 IS 233/333 rear partitioning kit, height 200 mm1 4 046 88 IS 233/333 rear partitioning kit, height 300 mm1 4 046 89 Partition, height 300 mm, for reserve

4 046 594 046 00 4 046 23

n Mounting

n Dimensions (mm)Bases for DPX³ 160

614525.7

6001

06

,7

pages répartition_34-49.indd 48 02/07/13 08:55

Page 51: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and

BATDate :Nom chef de Pub :

Signature :

CF-EP0

BAT

:

e :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RM :

Signature :

BATDate :Nom RMF :

Signature :

BATDate :Nom RMF :

Signature :

VX3 - IS increased safety distribution system, vertical mounting

ed safety

tesock no accessory

ccessory

rotary or motor-driven

y or motor-driven

w distribution block

w distribution block

w distribution block

w distribution block

no accessory

ccessory

rotary or motor-driven

y or motor-driven

screw-mounting

mm)

tal busbarspplying the VX³ ISop or bottom horizontal

using for the horizontal

n 1250 A

n 2000 A

s, In 1250 A

s, In 2000 A

liariessupplied with

busbars in internal

busbars in external

t, height 200 mmt, height 300 mmeserve

4 046 59

n Mounting

n Dimensions (mm)Bases for DPX³ 160 Bases for DPX³ 250 Bases for DPX 630

614525.7

600

194

190

37.61

115.

4

51.5

70

10

6,7

125.

2

80.39

35

35

353

5

614525.7

600

194

190

37.61

115.

4

51.5

70

106,

7

125.

2

80.39

35

35

35

35

600.2524.5

194 34.5

44.5

100

290

91.4

18.5

29.5 12

2.7

58 43.5

43.5

43.5

pages répartition_34-49.indd 49 02/07/13 08:55

Page 52: SELECT yOUR dISTrIBuTIOnSySTEm - Legrand · The distribution systems at the heart of power offer ... 2 Linking interface between XL³ 4000 enclosure and SCP busbars ... inverter and