SECTION 1: HV SWITCHBOARDSSECTION 1: HV SWITCHBOARDS
1.1 GENERAL
1.1.01 Functional description
The Medium Voltage Switchboards Scope of Works includes the detailed design, engineering, workshop drawings preparation and approval, manufacturing, factory testing, supply, delivery, installation, testing and commissioning and finally handover to the Employer of the Medium Voltage Switchboards rated as shown on the relevant drawing in the framework of entire project completion as indicated on the relevant drawings.
1.1.02 Cross references
Workstation General Requirements
Workstation Electrical & Control Systems General Requirements
Medium Voltage Switchboards
Distribution Transformers
Power Cables
1.1.03 Standard
General
The Medium Voltage Switchboards shall comply with the lastest issues of the following IEC recommendations:
IEC 60056 High Voltage Alternating Current Circuit Breakers
IEC 60129 High Voltage A.C. Switchgear and controlgear disconnectors (isolators) and earthing
IEC 60185 Current transformers for measurement and protection.
IEC 60186 Voltage transformers for measurement and protection.
IEC 60265-1 High voltage Switch for rated voltages above 1 KV and less than 52 KV
IEC 60298 AC Metal Enclosed Switchgear and ControlGear for Rated Voltages above 1 kV and up to and including 54 kV.
IEC 60282-1 HV fuses
IEC 60420 High voltage a.c. Switchgear and control gear – switch - fuse combinations.
IEC 60529 Degrees of protection provided for enclosures (IP Code).
IEC 60605 Approval and test specification – general requirements for electrical equipment.
IEC 60694 High voltage a.c. Switchgear and control-gear-circuit breakers for rated voltages above 1000V.
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/2
1.1.04 Design
General
The Medium Voltage Switchboards shall be designed in accordance with the above-mentioned standards, and applicable drawings.
The Medium Voltage Switchboards shall be capable of continuous duty at rated voltage/frequency stated in this Specification.
Technical Parameters
Rated voltage – 24 kV
Operating voltage – 15 kV (existing)
Operating voltage – 22 kV (future)
Frequency – 50 Hz
Rated power frequency withstand voltage - 50 kV - 50 Hz, 1 min
Rated lightning impulse withstand voltage - 125 kV - 1,2/50 µs
Rated short-circuit breaking current - 25 kA - 3 s
Rated short-circuit making current - 60 kA
Busbars rated current – 1250 A
The auxiliary supply voltage shall be 110 V DC with a permissible variation range of -15% to +10%.
Incoming/Outgoing CB’s shall be rated – 1250 A – two units
Distribution Transformers CB’s shall be rated – 630 A – two units
Service conditions
The Medium Voltage Switchboards shall be suitable for installation and operation in Vietnam and the environmental conditions described in the data sheets and project specifications.
The manufacturer shall be responsible for ensuring that all equipment and components supplied are suitable for the operation and conditions stated. Where the manufacturer standard or preferred design option does not meet the operation or environmental conditions, the manufacturer shall give details of the technical changes and commercial impact of complying with the stated conditions.
The Medium Voltage Switchboards shall be designed for ambient temperature of 40ºC.
Safety and Reliability
The Medium Voltage Switchboards shall be designed to minimise any risk of an internal short circuit and shall be of metal clad design. In the event of any internal arcing fault on a functional unit, the damage shall be confined to that unit so that the busbars and all other functional units are undamaged and operational.
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/3
The Medium Voltage Switchboards design shall incorporate arc fault containment features. The level of arc containment test to which the switchboard complies shall be stated and any required features (e.g. vent flaps) shall be identified.
The Medium Voltage Switchboards shall be designed in such a manner that all components shall be operated and maintained safely and shall not present a hazard to personnel or cause damage to other equipment.
The metal enclosure shall be hermetically sealed and “safe to touch”.
All MV and internal drive parts shall be maintenance-free for at least 10 years or 10 000 mechanical operations.
Switchgear shall be arc-fault tested
Submission
The Contractor shall submit for the Engineer’s approval the following workshop drawings and calculations:
Single Line Diagram
Protection Diagram
Calculation of prospective relay settings
Types, model numbers and ratings of assemblies.
Detailed dimensions.
Shipping sections, general arrangement, plan view, front elevations and cross-section of each compartment.
Projections from the assembly that may affect clearances or inadvertent operation, such as handles, knobs
Fixing details for floor or wall mounting.
External and internal paint colours and paint systems.
Construction and plinth details, ventilation requirements
Engraving Mimic Diagram
Manufacturer’s name
Type designation
Purchaser order number
1.2 QUALITY
1.2.01 Switchboards type
The Medium Voltage Switchboards shall be indoor type unit designed with the minimum acceptable degree of ingress protection (IP) for electrical equipment and devices shall be as IP2x.
The Medium Voltage Switchboards shall be free-standing, floor mounted, and all switching operation shall be carried out from the dead-front operating panel.
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/4
Live line test facilities shall be available on the panel front.
Drive mechanism and current transformers secondary circuits shall be freely and safely accessible.
1.2.02 Functional units
Medium Voltage Switches
The Medium Voltage Switches shall use low pressure SF6 gas or vacuum for current interruption and shall require no maintenance. The Medium Voltage Switches enclosure shall be mounted horizontally within the cubicle and the position of the main and earthing contacts shall be clearly visible from the front of the cubicle. The position indicator shall be placed directly on the contact operating shaft.
The Medium Voltage Switches shall be of the high operating frequency type in accordance with paragraph 3.104 of IEC 60265-1 recommendations. They shall have three positions (closed, open and earthed) and shall be fully assembled and tested before leaving the factory.
The Medium Voltage Switches shall have a service life of at least 30 years. No refilling of the gas or vacuum creation shall be required over this period.
The mechanical endurance of the switch operating mechanisms shall ensure at least 1000 operations.
Circuit Breakers
The Medium Voltage Circuit Breakers shall be of the three-pole, fixed mounted or draw-out type. They must be maintenance free as regards the switching element and the operating mechanism. Switching devices have to be fitted in the switchgear vessel to be independent from climate and environment. The Medium Voltage Circuit Breakers shall be designed to withstand 10,000 mechanical operating cycles respectively and 50 breaking operations at rated short circuit breaking current.
The control power for breaker closing, tripping and spring charging shall be DC 110 V. All control circuits of each Circuit Breaker shall be separately protected by means of MCB’s. The close and trip circuits shall be separately protected.
The Medium Voltage Circuit Breakers shall be provided with a minimum of two (2) Normally Open (NO) and two (2) Normally Closed (NC) spare auxiliary contacts, and wired up-to an accessible terminal block for external connections. If spare auxiliary contacts are not available, an auxiliary relay shall be used to multiply the available spare auxiliary contacts.
The tripping supply shall be monitored at the tripping coil of each breaker and a common alarm relay shall be operated if the tripping supply is unavailable.
Motor wound operating mechanisms shall be automatically recharged immediately following a closing duty. In addition to motorised spring charging, the circuit breakers shall be provided with manual spring charging facilities.
All The Medium Voltage Circuit Breakers shall have electrical / mechanical tripping facilities and the mechanical tripping button shall be accessible without opening the switchboard cover.
The Switchgear Interrupting Medium shall be SF6 or vacuum.
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/5
1.2.03 Protection and control system
General
The term "protection and control system" designates all the elements included: current and voltage sensors, relays, automation devices, trip units, associated auxiliaries, etc.
The functional units shall be equipped with integrated digital protection and control units, which include the protection, automation, measurement, counting and communication functions.
Since the Protection and Control unit is integrated as close as possible to the switchgear, it must meet the severest environmental withstand requirements, in particular IEC standards:
255-4 Impulse withstand 5 kV
255-22-1 1 MHz wave Class III
255-22-4 Fast transients Class IV
255-22-3 Electromagnetic radiation 20 V/m minimum
The operating temperature shall be up to + 45° C.
The Protection and Control units shall be operational by auxiliary power supply voltage: 110 V DC, and current sensors: 1 A - CT, and voltage sensors: 110 V - VT.
The manufacturer’s plant of the Protection Units shall be ISO 9001 certified.
The logic input shall have the same voltage rating as the auxiliary power supply and shall comply with the standards (IEC 11-32) relative to PLC’s and the current shall be at least 6 mA
Each Protection and Control Unit shall contain all the necessary specified protections.
Each protection device shall have wide setting ranges, in particular for current protections, providing a choice of curve types (direct time) DT, (IDMT) SIT, VIT, EIT, UIT and time delays from instantaneous (50 ms) to 500 s as a minimum.
Setting shall be performed by the direct input of primary current values.
Detection fault pick-up may reach 100 mA primary current.
The unit shall allow for the use of upstream and downstream logical discrimination, this applying to protection plans using IDMT times as well.
Protection tripping shall be indicated on the front of the device by a signal lamp and a message indicating the cause of the fault..
Incoming/Outgoing Feeder Protection
All functional units, which are protecting Incoming/Outgoing feeders shall be equipped with protection relays be able to perform the following protection functions:
Overcurrent
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/6
Earth fault
Remnant Under Voltage
Over/Under VoltageOver /Under Frequency
Distribution Transformer Protection
All functional units, which are protecting power transformers shall be equipped with protection relays be able to perform the following protection functions:
Thermal Overload
Overcurrent
Earth fault
Neutral Voltage Displacement
Transformer Differential
Measurement
Each Protection and Control unit shall include the measurements needed for operation and commissioning, i.e.:
Phase current measurement
Maximum phase current demand
Measurement of fault current interrupted in each phase
Additional measurements such as residual current
Measurement accuracy shall be 1 % (according to IEC 255-4).
The unit shall include voltage, frequency and energy measurements.
For power and energy data, the unit shall measure real and reactive values and take into consideration the direction of energy flow (incoming, outgoing)
Operation
The Protection and Control unit shall include display unit that indicates:
Measurement values
Operating messages in English
Maintenance messages
Circuit breaker open or closed position, displayed on the front of the device by two signal lamps
It shall be possible to make the settings and perform parameter setting via a portable terminal downloaded from Supervisory Control and Data Acquisition System Master Terminal Station.
Control and Monitoring
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/7
The Protection and Control unit shall include the input resources and logic outputs required for control of the circuit breaker
Open and close control, whatever the type of shunt trip or undervoltage release coil control
Earthing switch closed position
Lockout of making in the presence of a fault
Monitoring of the circuit-breaker operating mechanism and trip circuit (power supply, wiring and coil)
Detection of unit connected and plugged in connectors
Operation counter, fault trip counter
SF6 pressure
Cumulative total of kA interrupted
Storage of information (even during auxiliary power supply outages)
Communication
The Protection and Control unit shall be fitted with a communication interface of the MODBUS type, RS-232/RS-422/RS-485 type, 1200 – 38400-baud speed.
The unit shall provide time tagging of events within ms, with an adapted input available for an external clock synchronisation contact
Operating Dependability
The Protection and Control Unit shall include:
An internal function self-monitoring mechanism, which activates two fail-safe watchdog changeover contacts.
An automatic device for switching to the fail-safe position, with disabling of output controls when an internal failure is detected.
The indications shall be on the front of the device by signal lamps and messages indicating self-test status.
Commissioning
The Protection and Control unit shall be delivered ready to use. Only settings and parameter setting specific to the installation will need to be performed on site.
However, the unit shall include capacity for customisation and adaptation:
Extension of the number of logic inputs and outputs: to 20 inputs and 10 outputs
Modification of the control logic program shall be available on the Engineer request
Maintenance
After a spare hardware base has been set up, the proposed system shall enable restarting without any setting or the use of special equipment.
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/8
The parameter and setting values shall be saved on a movable storage medium, which is part of the unit
References
The proposed Protection and Control unit supplier shall have a large number of international references with well-known industrialists and utilities.
The list of references shall be enclosed with the proposal.
Service
The Contractor shall carry out network co-ordination studies on the Engineer request (including settings’ sheets) according to the best terms possible.
After installation, the manufacturer’s personnel shall provide all necessary services. The manufacturer shall have a competent organisation and the equipment necessary for making quick diagnoses locally.
The list of maintenance service outlets shall be enclosed with the technical proposal.
1.2.04 Power monitoring and analysis system
The term "Power monitoring and analysis system" designates all the elements included in:
The monitoring and analysis system - sensors, measuring and counting devices, monitoring and diagnosis devices
The communication interface for integration in a remote monitoring and control system
Monitoring and Analysis
The functional units shall be equipped with integrated measurement, counting, monitoring and diagnosis digital Power Analysers according to the following technical requirements:
Hardware Features
CPU - microcontroller with 20 MHz oscilator
BUS width - 8 bit data bus
ROM - EPROM 64 Kb
MAIN RAM with battery backup
REAL TIME CLOCK - embedded into RAM
EXTENDED NON-VOLATILE RAM with battery backup
Minimum 8 multiplexed ANALOGUE INPUTS with maximum 10ms sample / conversion time
Minimum 8 programmable opto-isolated DIGITAL INPUTS
Software Requirements
HIGH-SPEED SETPOINT CONTROL SYSTEM
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/9
SIGNAL PROCESSING SOFTWARE
Measured Parameters
Voltage per phase (L-N/L-L)
Current per phase
Auxiliary current (earth leakage)
Digital inputs
Frequency
Calculated Parameters
True RMS phase-to-neutral voltage (per phase)
True RMS line-to-line voltage (per phase)
Unbalanced current
Earth leakage
Active power (per phase and total)
Reactive power (per phase and total)
Apparent power (per phase and total)
Power maximum demand
Accumulated demand (per phase)
Ampere demand (per phase)
Active energy (imp, exp, net, tot)
Reactive energy (imp, exp, net, tot)
Apparent energy (imp, exp, net, tot)
Power factor (per phase and average)
Voltage and current harmonics per phase (up to 31 harmonic)
Total harmonics distortion (THD) per phase (voltage and current)
Displayed Parameters
All measured and calculated parameters and status inputs.
Alarm/Events Set Points
Over/under current
Over/under voltage
Over/under power factor
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/10
Over/under active power
Over/under reactive power
Over/under apparent power
Over accumulated power demand
Over unbalanced current
Over/under frequency
Over THD
Over/under date
Over/under time
Over/under pulse counter (1-8)
Status inputs (1-8)
Relay status (1-8)
User/manual control (1-8)
Relay Operation
Alarm/event set-point controlled
kWh, kVArh, kVAh and maximum demand interval pulse out
Manual controlled via communication channel
Status / Input
Alarm/event conditions
External demand interval synchronisation
Programming multiplexed analogue output
Analogue Output Operation
Current output range 4-20 mA per order
Any measured quantity may be assigned to analogue output
User-configurable zero offset and full scale factors
Set Up
Downloaded from PC or done manually from keyboard
Full software support
Parameter Access Designation
K - Keypad access
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/11
C - Communication access
Set Up Access (K)
Password option (ON/OFF)
Password check
Redefine password
Time Clock Setting (K/C)
Year, month, day, hour, minute
Resetting seconds
Digital Inputs Allocation (K/C)
For analogue output selector when multiplexed analogue output is used (1-4)
For monitoring external dry contacts (1-8)
For external synchronisation source to reset power demand interval (1)
For triggering alarm/event conditions (1-8)
Analogue Output (K/C)
Non-multiplexed/ multiplexed
For multiplexed output: the number of digital inputs used as selector for programming multiplexed analogue output and the measured parameters associated with the analogue output selector’s keys
For non-multiplexed output: he measured parameters assigned to the analogue output
For any selected analogue parameter: low scale corresponding to a zero-scale analogue current - 4 mA and high scale corresponding to the full-scale analogue current - 20 mA.
Relay Control (K/C)
Alarm/event set-point controlled
kWh, kVArh, or kVAh pulse output
Maximum demand interval pulse output
Pulse duration for pulse mode allocation (100-1000 ms)
Alarm/Events Set-points (K/C)
Set Point Definition
Condition input group (real-time/average analogue value, pulse counter, status input, relay status, user event)
Condition reference
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/12
Time delay to operate (0.1-999.0 s)
Time delay to release (0.01-999.0 s)
Action 1st reference
Action 2nd reference
Condition Definition
Analogue value:
Analogue parameter
Compare
Operate limit
Release limit
Pulse counter:
Counter number
Compare
Operate limit
Release limit
Status input:
Status input number (1-8)
Operate status (ON/OFF)
Relay status:
Relay number (1-8)
Operate status (ON/OFF)
User events / manual control:
User event flag (1-8)
Operate status (ON/OFF)
Action Definition
Relay control
Set/reset user event
Increment/decrement/clear counter
Reset/clear: energy registers, maximum demand registers
Reset Control (K/C)
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/13
Reset functions enabled/disabled (ON/OFF)
Reset energy registers
Reset maximum demand registers
Communications Parameters (K)
Communications protocol (ASCII/MODBUS)
Interface (232/422/485)
Baud rate and data format (38400 baud minimum, 8 bit, no/even parity)-
Handshakes (OFF/RTS-CTS)
Instrument address (1 - 247)
Data Scale Factors
Voltage high scale (+)
Current high scale(+)
Power low scale(+/-)
Power high scale (+)
Sampling
Instrument shall be able to sample 128 samples per cycle. No degrading in accuracy shall happen up to 65 Hz.
Sampling rate shall be synchronised exactly to the fundamental frequency so that the harmonics measurements will not be falsified by adjacent frequencies.
Averaging
Number of buffer entries used for average shall be 8/16/32 entries.
Wiring Configurations
Four wiring configurations shall apply:
Three-wire system configuration direct connection
Four-wire system configuration direct connection
Four-wire system configuration, wiring via PT Y-Y connection
Three-wire system configuration, wiring via PT with open delta connection
Waveform Capture
Waveform capture shall let the user trigger via communications and upload to the PC 4 cycles x 2 inputs of voltage and current waveforms on any phase, sampled synchronously at a rate of 128 samples per cycle, allowing detailed spectrum and waveform analysis.
Alarm / Event Set Points
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/14
Alarm/event set points shall be defined for all parameters to trigger up to 4 relay or activate any logging function. Set points shall be set by keyboard or via communications.
For any set point, it shall be possible to define:
Event condition
Up to 2 set-point actions
Time delays to operate/release set-point (histeresis)
Time resolution (0.1 s/1 s)
For any set-point, it shall be possible to define two delay values: one to activate a set-point when conditions are true, and the second - to deactivate (in the range from 0.1 to 999.0 s at 100 ms resolution, or from 1 to 9999 s at 1 s resolution).
Conditions
Over/under the limit of a measured analogue value
Over/under date or time
Over/under pulse counter
Status input ON/OFF
Relay status ON/OFF
User event/manual control ON/OFF
Eight user controlled global events shall be possible to set/reset by a set point or manually via communications to trigger any set-point.
For over/under the limit condition, it shall be possible to specify the ON and OFF thresholds (limits) to activate the condition, and the value evaluation base (real-time one-cycle calculation average value).
Alarm/Event Actions
For any set point violation, it shall be possible to assign the following actions:
Relay control
Pulse counter control
User event control
Reset cumulative registers (selectively or all)
Communication Interface and Features
Digital Power System Analysers shall be capable to interface with the RTU’s by acceptable protocols:
RS-232/RS-422/RS-485 communication
Baud rate from 1200 up to 38400
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/15
RTS/CTS, MODBUS protocols
Configuration Information
Set-point system
Data logging
Status input
Instrument status
Interposing Relays
Ratings
4 relays rated at 5A 250 VAC, 30 VDC, 3 contacts SPDT. All relays shall be de-energised.
Operations
Any relay shall be configured to indicate:
Set-point violation
Energy pulsing
Maximum demand interval pulsing
Tariff time interval pulsing
Alarms/Events Relays Set Points
Each of the programmable set points shall be allocated to any of the 4 relays.
Energy Pulsing
kWh, kVArh, and kVAh pulsing shall be available for interface with PLC’s or other electronic devices. It is available on any one of the relays.
Pulsing options shall be as follows: 1 pulse per 1 unit to 200 units
Contacts shall be closed for approx. 100 ms each pulse by default. Pulse width shall be changeable by programming.
Maximum Demand Interval Pulsing
Any relay shall be able to be configured to output a time pulse indicating the beginning of a maximum demand time interval. The timing pulse should be synchronised with the beginning of an hour.
Analogue Output
1 Channel 4 - 20 mA programmable non-multiplexed/multiplexed.
High CMV isolation: 1500 V RMS
Low offset temperature: ± 300 nA/°C
Non-linearity: ± 0.02%
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/16
It shall be possible to define the scaling of the analogue output through communications or through keyboard. Output range shall have default value set in factory. It shall be possible to determine the zero offsets and the conversion coefficients.
Start -up
Upon power up, the instrument shall start with self-test. Start-up procedure shall include:
Memory read/write test
Configuration test
1.2.05 Current transformers
The Current Transformers for protection and measurements shall be based of the conventional type toroidal Current Transformers of the single or multi-ratio type, mounted inside the medium-voltage enclosure with grounded cores.
The rated secondary current of toroidal Current Transformers shall be 1 A.
The toroidal Current Transformers shall have secondary terminals outside the medium-voltage enclosure, mounted in suitable, accessible terminal boxes. All secondary leads of all Current Transformers must be wired to shorting-type terminals on the terminal strip in the local control cubicle of each bay.
The Current Transformers shall be 0.5 Class or better.
1.2.06 Voltage transformers
The Voltage Transformers for protection and measurements shall be of RC-divider type. They shall be mounted directly on the medium-voltage enclosure with plug-in contacts to allow easy removal.
The secondary terminals of the Voltage Transformers shall be located in easy accessible, grounded terminal boxes on the voltage transformer itself. The secondary connections must be wired to a terminal strip in the local control cabinet.
The Voltage Transformers shall be 0.5 Class or better
1.2.07 Lightning arresters
The Contractor shall perform simulation with the actual plant data to give accurate determination of the over-voltages and to design number and location of lightning arresters.
1.2.08 Auxiliary contacts
The switchgear shall be equipped with auxiliary indication contacts connected to terminals in the factory.
The terminal blocks, which received the available auxiliary contacts, shall be located in the low voltage compartment.
1.2.09 Low voltage auxiliaries
The protection and control system shall also be equipped with:
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/17
Test units for the injection of current or voltage into the transformer secondary circuits, installed on the front of the low voltage compartment:
1 unit for voltage
1 unit for measurement current circuits
1 unit for protection current circuits
1 unit for the zero current circuit
Low voltage protection circuit breakers, located in the low voltage compartment. Fuse protections are not acceptable.
A "local-remote" selector switch shall be installed for integration in a remote monitoring and control system.
The low voltage auxiliaries shall comply with the standards IEC 298 section 5-4 and IEC 694, article 5, section 5.4.
The low voltage cables shall be of the self-extinguishing, 1000 V insulation class. Both ends shall be identified to facilitate checking during maintenance operations.
For the current circuits, the cable cross-section shall 2.5 mm², and 1.5 mm² for the other circuits.
1.2.10 Enclosure
Steel enclosures: minimum 2 mm thick electro-galvanized sheet steel. It shall be painted to provide protection against corrosion. The epoxy based paint shall have a thickness at least 50 microns and shall be applied at both side of all sheet metal. The colour shall correspond to the RAL colour range proposed.eel enclosures: minimum 2 mm thick electro-galvanized sheet steel. It shall be painted to provide protection against corrosion. The epoxy based paint shall have a thickness at least 50 microns and shall be applied at both side of all sheet metal. The colour shall correspond to the RAL colour range proposed.
1.2.11 Assembly
The Medium Voltage Switchboards shall be of the modular design for free combination and extension.
They shall be rigid, ventilated, insect-screened enclosures consisting of panels, doors, or both, giving the designated enclosure, separation and degree of protection.
The Medium Voltage Switchboards shall be single tier, floor mounted, free standing suitable for tropical indoor application in accordance to the requisition specification. The Switchboard shall be designed for ease of maintenance and operation with the height of equipment requiring regular operation and testing being kept to a minimum.
The construction of the Medium Voltage Switchboards shall allow for future extensions at either end. Certified lifting lugs shall be provided in each shipping sections of the switchboard.
All cubicles shall be manufactured from electro-galvanised steel sheets with a minimum thickness of 2.0 mm. on a framework of folded sheet steel or structural sections. The
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/18
Switchboard construction shall be such that no distortion occurs when it is being lifted by hoist or moved into position on rollers.
The components used shall be of proven design with high service reliability and maintenance free long life features. Where relevant, components shall have flame retardant properties.
Gland plates and enclosure panels shall be provided with captive nuts or screws.
1.2.12 Earthing
An earthing bar of hard drawn, high conductivity copper shall be installed the full length of the switchboard in the bottom compartment. All metallic, non-current carrying parts of the switchboards shall be effectively and securely connected to this earthing bar. All gland plates shall be earthed to the earth bar.
Earthing bolts, lugs, nuts and spring washers shall be provided at each end of the bar suitable for the connection of 1x240 mm2 earthing cables to the external main earthing grid.
All doors and covers of the switchboards shall be effectively earthed using flexible connections.
An integrally mounted three phase earthing switch, capable of making and carrying the full perspective short circuit current and suitable for local manual operation shall be provided on the cable side of all Medium Voltage switching devices. Earthing facilities for the earthing of the busbar system of each section shall also be provided.
Earth Continuity
The earthing bars of each of the cubicles making up the switchboard shall be interconnected by a set of busbars which shall be connectable outside the switchboard and extend over its full width.
The cross-section of the busbars shall be determined so as to withstand the rated short-circuit current of the switchgear in accordance with IEC 60298 recommendations.
The earthing bar shall be designed for connection to the main earthing bar of the substation without dismantling any of the bars.
Effectively bond equipment and assembly cabinet metal frame to the protective earth conductor. Strip painted surfaces and coat with corrosion resistant material immediately before bolting to the earth bar. Provide serrated washers under bolt heads and nuts at painted, structural metal-to-metal joints.
Earthing of the Power Circuit
Cable earthing shall be carried out by an earthing switch with short-circuit making capacity, in accordance with IEC 60129 recommendations. It shall be possible to operate the earthing switch when the switch or disconnector is open.
A padlocking system shall be provided to lock the earthing switch in either open or closed position. The position of the earthing switch shall be clearly visible from the front of the cubicle.
Mechanical interlocking systems shall be provided to prevent incorrect operations such as the closing of the earthing switch with the switch or disconnector in closed position.
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/19
The use of keyed or electric locks to actuate the above mentioned interlocking system shall not be accepted.
1.2.13 Cable entries
Provide cable entry facilities within incoming and outgoing sections. Provide sufficient clear space for cables not to be stressed or impose on there bending radius. Please specify the cable entry trench depth.
The gland plates shall be fitted with gaskets to maintain the degree of protection, materials: pre-drilled 1.6 mm thick electro-galvanised steel.
1.2.14 Cable ducting
The Contractor shall design and construct cable ducting facilities within the premises of Medium Voltage Switchboard Chamber for incoming and outgoing cables. Provide sufficient clear space for cables not to be stressed or impose on there bending radius.
1.2.15 Cover and gland plates
Gland plates: Provide removable gland plates fitted with gaskets to maintain the degree of protection made from 1.6 mm thick electrically galvanised steel.
1.2.16 Doors and covers
Space adjacent doors to allow both to open to 90o at the same time. The single right angle return shall be implemented on all sides and fit suitable resilient sealing rubber to provide the degree of protection and prevent damage to paintwork.
The all doors shall be fitted with corrosion-resistant lever-type handles, operating a latching system with latching bar and guides strong enough to withstand explosive force resulting from fault conditions within the assembly.
Earth continuity shall be maintain to door in all positions.
The covers shall be fixed to frames with at least 4 fixings. Provide corrosion-resistant acorn nuts if the cover exceeds 600 mm in width. Rest cover edges on the cubicle body.
1.2.17 Busbars
The main circuit supply busbars within assemblies, extending from incoming supply terminals to the line side of protective equipment for outgoing functional units and for future functional units.
The busbars shall be installed in segregated enclosed compartments. No wiring equipment or devices shall be installed in the busbars compartments. The busbars shall be of hard drawn high conductivity bars made of tough pitched tinned copper alloy using electrolytic copper and have the same current rating throughout the length of the entire Switchboard.
A fully fault rated earth bus shall be provided in the switchboard and the size shall be indicated in the offer.
Sufficient supports made from non-hygroscopic insulation material capable of holding busbars at 105oC.to shall withstand thermal and magnetic stresses under maximum prospective fault currents.
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/20
For active conductors calculation it shall be taken into account Take into account thermal stresses due to short circuit current, assuming magnetic material enclosures located indoors in well-ventilated rooms and 90oC final temperature.
The size of protective earth conductors shall be at least 50% of the rated short-circuit withstand current for 100% of the clearance time.
1.2.18 Interlocking and padlocking
In general the following minimum padlocking facilities shall be provided:
Panel door
Local trip/close switches (electrical / mechanical)
Earthing switch in closed position
The Switchboard manufacturer shall recommend and provide the details of the interlocking required for busbar earthing.
1.2.19 Fastenings
ISO metric nuts and bolts in accordance with the requirements of ISO1111 and ISO1112 shall be used in the construction of the Switchboard. All fastening shall be corrosion resistant.
Cover bolts shall be retained in place when undone.
1.2.20 DC power supply
All DC power supply units necessary for the complete, satisfactory and independent operation of all the Medium Voltage Switchgears are to be included in this Contract. DC supply voltage for the Medium Voltage Switchgear shall be 110 volt. Capacities of the DC supply system shall be determined by the Contractor to satisfy the Functional Units correct performance.
Batteries
Batteries to be nickel/cadmium type. Dual rate (trickle/booster) charger, ammeter, voltmeter, indicating lamps, fuses must also be provided. All components of the DC supply units shall be housed in a metalclad enclosure with hinged door floor or wall mounted.
A battery test switch and all necessary test components shall be provided to test the discharging capacity of the DC supply units.
Battery Charger
The tripping battery shall be of sufficient capacity to supply the tripping current of three units simultaneously and housed in a self contained free standing ventilated steel sheet cubicle. Together with the batteries, there shall be installed with the automatic charging equipment, fuses for outgoing circuits, ammeter, mains or indication lamp, non locking load test switch, voltmeter with terminal voltage clearly marked in red on scale inclusive of engraved instruction label for manner and duration of test.
1.2.21 Operation
In order to make the Medium Voltage Switchboard simple and safe to use, the following construction requirements must be met:
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/21
Operating Mechanisms
All operating mechanisms and access points shall be on the front of the functional units, in particular, cable and busbar connections must be accessible via the front.
Instruction Guide
The operating procedures for the most current operations must be described on the front of each functional unit.
This shall be described exclusively in the form of explicit symbols and colour codes.
1.2.22 Main offer
The Main Offer shall comprise a quotation including:
The technical proposal to meet the Specification
Proposed variances with respect to the Specification
This document shall be accompanied by at least the following:
Technical documents presenting the equipment
Single-line diagrams of all the switchboards
Low voltage functional diagrams
Dimensional and layout drawings, with mounting and cable running
An accurate representation of the front view of the equipment
The list of test certificates related to the requested performances
The services associated with equipment supply
Any options, with prices and impact on equipment availability time
Operating and servicing documents
The list of spare parts with prices, indicating the average delivery lead times
Warranty terms
Before an order is placed, the supplier will be requested to supply the complete wiring diagrams, as well as the engineering and installation documents.
1.2.23 Labels
Label with essential markings shall include:
Manufacturer’s name
Switchboard type designation
Purchaser order number
Switchboard title and tag number
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/22
Year of manufacture
Service voltage, rated frequency
Rated current of the busbar system
Rated voltage of the auxiliary circuits
Rated peak and short time withstand current and withstand time
Degree of protection
Designation labels: For other than main assemblies, provide designation label stating source of electrical supply. Identify separate sections of enclosures
1.3 MANUFACTURING
1.3.01 Manufacturer
The Medium Voltage Switchboards and their components shall be manufactured in the factory(ies) certified with ISO 9001 certificate with at least 10 years experience in the specified equipment production
1.3.02 Inspections
The equipment may be inspected during manufacturing in any of the plants, which are involved in the related manufacturing. The Contractor shall make provision in his rates to cover the Engineer expenses for such inspection.
The equipment shall be delivered with all the documents required for installation, testing, commissioning, operation and servicing-maintenance.
The Contractor shall notify the Engineer so that inspections may be conducted at the following stages:
Fabrication and painting completed.
Factory assembly completed, with busbars exposed and functional units assembled.
Assembly ready for routine testing and dispatch.
Assembly installed and connected.
Acceptance and handover.
1.4 TEST
1.4.01 Type test
The Contractor shall submit for the Engineer’s approval with the proposed manufacturer Medium Voltage Switchboards Type Test certificates from independence laboratory (KEMA or equivalent).
The Contractor shall present the following type testing certificates:
Impulse dielectric withstand test
Dielectric withstand at power frequency test
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/23
Overheating test
Admissible short time current withstand test
Mechanical operation test
Degree of protection check
Electromagnetic compatibility check (EMC test)
Switchgear device breaking capacity checks
Switchgear device making capacity check
1.4.02 Routine testing
All equipment covered by this specification shall be subject to the Engineer’s inspection at the manufacturer’s works. The manufacturer shall notify the Engineer fourteen (14) days in advance when the tests are to be performed. Carry out the following tests:
Assemblies: Electrical and mechanical routine function tests at the factory using externally connected simulated circuits and equipment.
Dielectric testing:
Functional testing: Operate mechanical devices, relays, protection, interlocking and alarm equipment.
Primary and secondary current injection test
Insulation resistance test
AC voltage/Power frequency one minute test
Impulse voltage test
Wiring continuity test
Functional test of all components
All test reports/certificates shall be submitted to Engineer within fourteen (14) days of the completion of such tests.
Test reports and certificates shall be approved by the Engineer prior to the equipment leaving the factory.
If the test results show that any equipment of the purchase order is not met, Supplier shall make necessary correction to the satisfaction of the Engineer before acceptance is made.
1.5 INSTALLATION
Installation of the Medium Voltage Switchboards shall be carried out according to the manufacturer’s recommendations and relevant drawings and in conformity with IEE regulations and applicable IEC standards.
The Switchgear manufacturer shall be capable of providing all the services necessary, from training of personnel to installation and full commissioning on site if required by the Engineer.
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/24
1.5.01 Transportation
Each functional unit shall be set on and screwed onto a wooden floor.
The units shall be individually protected against rain and dust by polyethylene wrapping, in which desiccant bags are placed.
Wooden straps shall be used to protect against impact.
1.5.02 Handling and storage
The wooden floor onto which each functional unit is screwed should allow for handling by a forklift.
The switchgear should be capable of being stored for as long as necessary in the following conditions:
Splashing water, wind, sand and all direct chemical pollution
Humidity in compliance with that defined for normal operating conditions
1.6 TESTING AND COMMISSIONING
Field testing and commissioning of the Medium Voltage Switchboards shall be carried out by the code of InterNational Electrical Testing Association (NETA).
Only qualified personnel shall test and commission the Medium Voltage Switchboards.
1.6.01 Site testing
In order to reduce commissioning time, the equipment proposed shall be designed so that the commissioning of each functional unit does not require an additional individual testing of each protection and measurement function.
Testing shall be limited to:
Checking of the parameter settings by direct reading
Checking of the connections to the current and voltage sensors by secondary injection
Measurement of residual current and voltage for configurations which use those values
Checking of logical input/output wiring
Switchgear device operation by push-button
Pilot wire connection test
No configurations, which require other test procedures, will be accepted.
1.6.02 Commissioning
The only settings required during the commissioning of the Medium Voltage Switchboards shall be parameter settings of the protections and the alarms on the protection and control unit.
Atelier Management and Design Consultancy (Vietnam) Co.,Ltd SEL1-HV SWITCHBOSRDS/25