Page 1: SEL-700G Protection, Control and Automation Leo Gaghan

S E L - 7 0 0 G P r o t e c t i o n , C o n t r o l a n d A u t o m a t i o n

L e o G a g h a n , C a s c o S y s t e m s

J a n u a r y 2 4 , 2 0 1 9

Page 2: SEL-700G Protection, Control and Automation Leo Gaghan

Table of Contents

Device Overview………………………………………………………….… 3Sample System………………………………………………………………. 4Logic Diagram………………………………………………………………… 5Example Protection Elements………………………………………… 9

Loss-of-Field (40)………………………………………………….…… 9Voltage-Controlled Overcurrent (51C)……………….…….. 12Ground Over Voltage (59G)…………………………….……..… 14100% Stator Protection (64G)………………………….….…… 16

Event Reporting………………………………………………….….……. 19References…………………………………………………………….….…. 24

Page 3: SEL-700G Protection, Control and Automation Leo Gaghan

Device Overview

Page 4: SEL-700G Protection, Control and Automation Leo Gaghan

Sam

ple

Sys

tem

Page 5: SEL-700G Protection, Control and Automation Leo Gaghan

Logi

c D

iagr

am

Page 6: SEL-700G Protection, Control and Automation Leo Gaghan
Page 7: SEL-700G Protection, Control and Automation Leo Gaghan
Page 8: SEL-700G Protection, Control and Automation Leo Gaghan
Page 9: SEL-700G Protection, Control and Automation Leo Gaghan

Example Protection Elements

Loss of Field (40)

The source of excitation for a generator may be completely or partially

removed through such incidents as accidental tripping of a field breaker, field

open circuit, field short circuit (flash over of the slip rings), voltage regulation

system failure, or the loss of supply to the excitation system. Partial or total

loss-of-field on a synchronous generator is detrimental to both the generator

and the power system which it is connected.

Sample System

Page 10: SEL-700G Protection, Control and Automation Leo Gaghan

Loss of Field (40)

The SEL-700G uses a pair of offset mho circles to detect loss-of-field.

Page 11: SEL-700G Protection, Control and Automation Leo Gaghan

Loss of Field (40)

Mho circles plotted against generator capability curve.

Page 12: SEL-700G Protection, Control and Automation Leo Gaghan

Voltage-Controlled Overcurrent (51C)

The differential relay generally provides primary fault protection for the

generator. Backup fault protection is also recommended to protect the

generator from the effects of faults that are not cleared because of failures

within the normal protection scheme. The backup relaying can be applied to

provide protection in the event of a failure at the generation station, on the

transmission system, or both.

Sample System

Page 13: SEL-700G Protection, Control and Automation Leo Gaghan

Voltage-Controlled Overcurrent (51C)

Page 14: SEL-700G Protection, Control and Automation Leo Gaghan

Ground Overvoltage (59G)

When a SLG fault occurs on an ungrounded system the effected phase

potential to ground goes to zero but the potential from that phase to the other

two phases does not change. The result is the un effected phases potential to

ground being increased by a square root of three and having a phase angle

difference of 60 degrees between each other. This phase arrangement creates

a zero-sequence voltage.

Sample System

Page 15: SEL-700G Protection, Control and Automation Leo Gaghan

Ground Overvoltage (59G)

Page 16: SEL-700G Protection, Control and Automation Leo Gaghan

100% Stator Protection (64G)

The SEL-700G provides a two-zone function designed to detect stator winding

ground faults on high-impedance grounded generators. The Zone 1 element

uses a fundamental-frequency neutral overvoltage element that is sensitive to

faults in the middle and upper portions of the winding. The Zone 2 element

uses a third-harmonic neutral undervoltage scheme to detect ground faults on

the lower portions of the winding

Sample System

Page 17: SEL-700G Protection, Control and Automation Leo Gaghan

100% Stator Protection (64G)

Page 18: SEL-700G Protection, Control and Automation Leo Gaghan

100% Stator Protection (64G)

No Load Full Load

Page 19: SEL-700G Protection, Control and Automation Leo Gaghan

Event Reporting

Event reporting can be triggered from any predefined logic or protection

element. Reports can be as long as 180 cycles (3 seconds) and can record

defined pre and post event lengths

Event reporting give's three phase oscillography as well as word bit status

during the duration of the event.

Can be remotely accessed with proper network configuration

Very helpful tool for troubleshooting

Page 20: SEL-700G Protection, Control and Automation Leo Gaghan

Event Reporting (Differential Trip)

Page 21: SEL-700G Protection, Control and Automation Leo Gaghan

Event Reporting (Lightning Arrestor Fail)

Page 22: SEL-700G Protection, Control and Automation Leo Gaghan

Event Reporting (Sync Capture)

Page 23: SEL-700G Protection, Control and Automation Leo Gaghan

Sync Report

Page 24: SEL-700G Protection, Control and Automation Leo Gaghan

References- Protective Relaying: Principles and Applications, 4th Edition by

Blackburn and Domin

- Protective Relaying for Power Generation Systems by Donald

Reimert

- IEEE Tutorial on Synchronous Generators: Cat. Number 95 TP 102

- IEEE Guide for AC Generator Protection, Standard C37.102-2006

- IEEE 1547 Standard for Interconnecting Distributed Resources with

Electric Power Systems

- SEL-700G Instruction Manual, Date Code 20180629

- Paul Shea and Todd Ward

Page 25: SEL-700G Protection, Control and Automation Leo Gaghan

THANK YOU !