Upload
jakkyjery
View
216
Download
0
Embed Size (px)
Citation preview
8/11/2019 Section08_A4.pdf
1/806
P-1 of 2
M a i n C o n t e n t s - a
Main Table of ContentsOperation and Maintenance Instruction ManualVolume 2 Maintenance and System Description Manual
Book No Section No Item Drawing No
Volume 2 Section 8 GeneratorManual
8.1 740MVA T/G INSTRUCTION LIST EKC003097 8.2 740MVA TURBINE GENERATOR DESIGN DATA EKC003098
8.3 740MVA GENERATOR STRUCTURE EKC0030998.4 FILLING AND RELEASING OF H2 GAS EKC003087
8.5 GAS CONTROL SYSTEM AND SHAFT SEAL OIL SYSTEM EKC003100
8.6 OPERATION OF GENERATOR EKC0027008.7 ACTION TO BE TAKEN ON ALARMS FROM GAS CONTROL
SYSTEM AND SHAFT SEAL OIL SYSTEM EKC003101 8.8 STATOR COOLING WATER SYSTEM EKC003102 8.9 PERIODIC OPERATIONAL INSPECTION AND TESTS EKC002435
8.10 PERIODIC INSPECTION CHECK SHEET EKC002382
8.11 REGULAR INSPECTION OF HYDROGEN COOLEDTURBINE GENERATOR E1O00069
8.12 DRYING THE TURBINE GENERATOR WINDINGS E1O000J7
8.13 DIELECTRIC STRENGTH TEST OF TURBINE GENERATORARMATURE WINDINGS EKC002852
8.14 MAINTENANCE OF GAS TIGHTNESS AT ROTOR WINDINGLEADS EKC002433
8.15 PREPARATIONS FOR DISASSEMBLY AND REASSEMBLY
OF GENERATOR E1O000H6 8 16 INSTALLATION AND ASSEMBLY OF GENERATOR EKC003063
8/11/2019 Section08_A4.pdf
2/806
P-2 of 2
M a i n C o n t e n t s - a
Main Table of ContentsOperation and Maintenance Instruction ManualVolume 2 Maintenance and System Description Manual
Book No Section No Item Drawing No
Volume 2 Section 8 GeneratorDrawing
8.30 GENERATOR CHARACTERISTIC DATA VA1-TSB-00MKA-E-M1B-DAS-31108.31 740MVA Generator Rating Plate VA1-TSB-00MKA-E-M1B-DLB-3111
8.32 740MVA GENERATOR OUTLINE VA1-TSB-00MKA-E-M1B-DRD-31008.33 740MVA GENERATOR TERMINAL
BUSHING ASSEMBLY VA1-TSB-00MKA-E-M1B-DRD-31018.34 DETAIL OF AUX. TERMINAL BOX VA1-TSB-00MKA-E-M1B-DGA-3109
8.35 GENERATOR SOLE PLATES & ANCHOR
BOLTS VA1-TSB-00MKA-E-M1B-DFN-31248.36 ARRANGEMENT OF SOLE PLATE FOR
740MVA GENERATOR VA1-TSB-00MKA-E-M1B-DRD-3107 8.37 LOCATION OF R.T.D FOR 740MVA
GENERATOR VA1-TSB-00MKA-E-M1B-DGA-3108 8.38 DIAGRAM OF GAS CONTROL SYSTEM VA1-TSB-00MKG-E-M1B-PFD-3113
8.39 DIAGRAM OF SHAFT SEAL OIL SYSTEM VA1-TSB-00MKW-E-M1B-PFD-31148.40 DIAGRAM OF STATOR COOLING WATER
SYSTEM VA1-TSB-00MKF-E-M1B-PFD-31128.41 DESIGN OUTLINE OF GENERATOR VENT
TO ATMOSPHERE VA1-TSB-00MKA-E-M1B-DRD-31058.42 SPECIFICATION OF TEMPERATURE GAUGE VA1-TSB-00MAY-I-M1B-SPC-55308.43 INSTRUMENT LIST ***VA1-TSB-00MAY-I-M1B-SPC-55758 44 OUTLINE OF 740MVA GENERATOR NEUTRAL
8/11/2019 Section08_A4.pdf
3/806
8/11/2019 Section08_A4.pdf
4/806
8/11/2019 Section08_A4.pdf
5/806
8/11/2019 Section08_A4.pdf
6/806
8/11/2019 Section08_A4.pdf
7/806
8/11/2019 Section08_A4.pdf
8/806
1 11
E KC0 0 3 0 9 8 - a
Vi e t n a m Li l a ma Co r p or a t i o n
740MVA Tur bi ne Gen er at or
De s i gn Da t a
740MVA Tur bi ne Gene r a t or Des i gn Dat a
8/11/2019 Section08_A4.pdf
9/806
E KC0 0 3 0 9 8 - a
2 11 à –¾ • ‘ xpl anat i on
–¼ Ì TITLE
740MVA Tur bi ne Gene r at or Des i gn Dat a
‹q æ¼ CUSTOMER • F Vi e t na m / Li l a ma Cor p or a t i o n
Œn ‹ Ší EQ/ SYS. • F 740MVA Tur bi ne Gene r at or
»”Ô JOB • F M231001 , M231002 RT 2201
ƒvƒ‰“ƒg PROJECT • F VVA1 , VVA2
8/11/2019 Section08_A4.pdf
10/806
E KC0 0 3 0 9 8 - a
3 11à –¾ • ‘ Expl anat i on
1. General···························································································································· 4
2 Rating
······························································································································
4
2.1.
Generator ··············································································································4
3 Characteristic Curves ··································································································· 5
3.1. Estimated Saturation and Synchronous Impedance Curves ································5
3.2. Estimated “V” Curves ·························································································6
3.3.
Estimated Reactive Capability Curves ·································································7
4 Auxiliary System ··············································································································· 8
4.1.
Gas Control System······························································································8
4.2.
Gas Cooling System ·····························································································8
4.3.
Shaft Sealing System····························································································9
4.4. Stator Cooling Water System ···············································································9
4.5. Generator Unbalanced Load Capability ·······························································9
8/11/2019 Section08_A4.pdf
11/806
E KC0 0 3 0 9 8 - a
4 11à –¾ • ‘ Expl anat i on
1 General
This instruction manual gives overall data and descriptions of 740,000kVA generator and its auxiliary
units.
The rated electrical power output of generator is 629,000kW at a power factor of 0.85 lagging. The
generator is mechanically driven by its associated steam turbine, electrically excited by the static thyristor
rectifier excitation system and internally cooled by hydrogen gas.
2 Rating
2 1 Generator
Rating: TAKS-2P-740,000kVA-3000rpm-LCH-26,000V-16,433A-50Hz-0.85PF-0.52MPag
(a) Cold gas temperature (Outlet of H2 coolers): 46 • Ž
(b) Alarm temperature of cold gas temp. high: 48 • Ž
8/11/2019 Section08_A4.pdf
12/806
E KC0 0 3 0 9 8 - a
5 11à –¾ • ‘ Expl anat i on
3 Characteristic Curves
3 1 Estimated Saturation and Synchronous Impedance Curves
0.52MPag
8/11/2019 Section08_A4.pdf
13/806
E KC0 0 3 0 9 8 - a
6 11à –¾ • ‘ Expl anat i on
3 2 Estimated V
Curves
0. 52MPag
8/11/2019 Section08_A4.pdf
14/806
E KC0 0 3 0 9 8 - a
7 11à –¾ • ‘ Expl anat i on
3 3 Estimated Reactive Capability Curves
0. 52MPag
8/11/2019 Section08_A4.pdf
15/806
E KC0 0 3 0 9 8 - a
8 11à –¾ • ‘ Expl anat i on
4 Auxiliary System
4 1 Gas Control System
(a) Amount of gas space in generator casing: 115 m3
(b) Amount of carbon dioxide required for removing air from casing
(Generator at standstill or low speed): 175 m3
(c) Amount of carbon dioxide required for removing hydrogen from casing
(Generator at standstill or low speed): 230 m3
(d) Amount of hydrogen required for filling casing to 90 percent purity
at the atmospheric pressure (Generator at standstill): 230 m3
(e) Amount of hydrogen required for increasing pressure in casing
from 0 to 0.52MPag: 600 m3
(f) Mi i i f li d h d 99 %
8/11/2019 Section08_A4.pdf
16/806
E KC0 0 3 0 9 8 - a
9 11à –¾ • ‘ Expl anat i on
4 3 Shaft Sealing System
(a) Maximum oil flow to shaft seals in normal operation at 0.52MPag: 195 L/min
(b) Gas side oil flow in the above: 20 L/min
(c) Differential between seal oil and hydrogen pressure: 50 kPa
(d) Alarm of the above differential pressure low: 30 kPa
(e) Alarm of filter differential pressure high: 20 kPa
4 4 Stator Cooling Water System
(a) Water flow through stator winding: 980 L/min
(b) Cooling water inlet temperature: 46 • Ž
(c) Alarm temperature of stator winding temp. high: 10 • Žabove temperature
at full load
8/11/2019 Section08_A4.pdf
17/806
E KC0 0 3 0 9 8 - a
10 11à –¾ • ‘ Expl anat i on
This page is intentionally blanked.
8/11/2019 Section08_A4.pdf
18/806
E KC0 0 3 0 9 8 - a
11 11à –¾ • ‘ Expl anat i on
Œo —ð • ‘
Re vi s i on Hi s t or y( f or i nt e r n a l u s e )
Ï X
REV. PAGE
Ï X‰Ó Š‹y ‚Ñ “à —e
CHANGED PLACE AND CONTENT
³”F
APPROVED
’² ¸
REVIEWED
’S “–
PREPARED
‚• Initial Issue.Written in
page 2.
Written in
page 2.
Written in
page 2.
8/11/2019 Section08_A4.pdf
19/806
1 33
E KC0 0 3 0 9 9 - a
Vi e t n a m Li l a ma Co r p or a t i o n
740MVA GENERATOR STRUCTURE
8/11/2019 Section08_A4.pdf
20/806
E KC0 0 3 0 9 9 - a
2 33 à –¾ • ‘ xpl anat i on
–¼ Ì TITLE
740MVA GENERATOR STRUCTURE
‹q æ¼ CUSTOMER • F Vi e t na m / Li l a ma Cor p or a t i o n
Œn ‹ Ší EQ/ SYS. • F 740MVA Tur bi ne Gene r at or
»”Ô JOB • F M231001 , M231002 RT 2201
ƒvƒ‰“ƒg PROJECT • F VVA1 , VVA2
8/11/2019 Section08_A4.pdf
21/806
E KC0 0 3 0 9 9 - a
3 33à –¾ • ‘ Expl anat i on
Table of Contents
1. Introduction 5
2. Precaut ions for Safety
5
3. Generator Structure
11
3.1 General ···············································································································11
3.2 Stator Frame and Stator Core ·············································································12
3.2.1 Stator Frame ····························································································12
3.2.2 Spring Mounting······················································································12
3.2.3 Stator Core·······························································································13
3.3 Stator Winding (Armature Winding) ·································································15
3.3.1 Stator Bar and Insulation ·········································································15
3.3.2 Insulating connection Tube ·····································································16
3.4 Generator Terminal Plate ···················································································18
8/11/2019 Section08_A4.pdf
22/806
E KC0 0 3 0 9 9 - a
4 33à –¾ • ‘ Expl anat i on
This Page Intentionally Left Blank
8/11/2019 Section08_A4.pdf
23/806
E KC0 0 3 0 9 9 - a
5 33à –¾ • ‘ Expl anat i on
1. Introduction
This manual is written to ensure safe handling of the 740MVA Generator Structure. Before
operation, maintenance and inspection, be certain to read this manual for proper use of the
equipment. This manual should be kept near the equipment so it can be readily referenced.
2. Precautions for Safety
Signs and messages in this manual and on the equipment body are important for management,
operation, maintenance and inspection. They are given to avoid possible injuries and damages
as well as to ensure correct handling of the equipment. The following signs and short messages
should thoroughly be understood before reading this manual. It is advised that you also read
the instruction manuals of related equipment and components.
IMPORTANT MESSAGES
Read this manual and follow its instructions. Signal words such as DANGER, WARNING, two kinds of CAUTION,and NOTE, will be followed by important safety information that must be carefully reviewed.
Indicates an imminently hazardous situation, which will result in death or serious injury if you
DANGER!
8/11/2019 Section08_A4.pdf
24/806
E KC0 0 3 0 9 9 - a
6 33à –¾ • ‘ Expl anat i on
WARRANTY AND LIMITATION OF LIABILITY
TOSHIBA CORPORATION AND THE USER’S DIRECT SELLER ACCEPT NO
LIABILITY FOR ANY INJURY, LOSS OR DAMAGE THAT RESULTS OR MAY
APPLICATION
This Toshiba Steam Turbine and Generator Manual does not include all information necessary for every possible
contingency concerning the installation, operation and maintenance of the Toshiba Steam Turbine and Generator
Unit.
Should you require further information about the Toshiba Steam Turbine and Generator Unit or should a particular
situation arise which is not covered by this Toshiba Steam Turbine and Generator Manual, the matter should be
referred to Toshiba (contact details are specified at page 2 of this Manual).
8/11/2019 Section08_A4.pdf
25/806
E KC0 0 3 0 9 9 - a
7 33à –¾ • ‘ Expl anat i on
QUALIFIED PERSONS ONLY
AS A MINIMUM SAFETY REQUIREMENT, ONLY A “QUALIFIED PERSON”
SHOULD INSTALL, OPERATE OR MAINTAIN A TOSHIBA STEAM TURBINE
AND GENERATOR UNIT. THIS TOSHIBA STEAM TURBINE AND GENERATOR
MANUAL IS WRITTEN SOLELY FOR USE BY A “QUALIFIED PERSON”.
ONLY A “QUALIFIED PERSON” SHOULD INSTALL, OPERATE AND MAINTAIN
THE TOSHIBA STEAM TURBINE AND GENERATOR UNIT IN ACCORDANCE
WITH ALL APPLICABLE LAWS, REGULATIONS AND SAFETY PROCEDURES.
TO BE A “QUALIFIED PERSON”, YOU SHOULD HAVE SATISFIED ALL OF THE
FOLLOWING CRITERIA:
(1) YOU MUST HAVE CAREFULLY READ AND UNDERSTOOD THETOSHIBA STEAM TURBINE AND GENERATOR UNIT MANUAL AND ANY
OTHER MANUALS OF THE ASSOCIATED DEVICES AND COMPONENTS
OF THE TOSHIBA STEAM TURBINE AND GENERATOR UNIT MANUAL.
(2) YOU MUST HAVE RECEIVED TRAINING OFFERED BY TOSHIBA.
BEFORE YOU INSTALL, OPERATE OR MAINTAIN THE TOSHIBA STEAM
8/11/2019 Section08_A4.pdf
26/806
E KC0 0 3 0 9 9 - a
8 33à –¾ • ‘ Expl anat i on
SAFETY SIGN
(1) To ensure safety, all the SAFETY SIGNS (including DANGER LABELS, WARNING LABELS, CAUTION
LABELS and NOTE LABELS) must be read and understood
(2) All the SAFETY SIGNS (including DANGER LABELS, WARNING LABELS, CAUTION LABELS and NOTE
LABELS) must be kept in such condition that they can be easily seen. They must be clear enough to be
clearly visible and never be removed or blocked from view.
8/11/2019 Section08_A4.pdf
27/806
E KC0 0 3 0 9 9 - a
9 33à –¾ • ‘ Expl anat i on
■ When the rotor extracted from, or inserted into the stator, be sure to
protect the inner walls of the stator core from damage.
If the punchings are burred or shorted together at the tooth tips, this would permit circulating currents,induced by the magnetic flux in the core, resulting in a hot spot and possible damage to the core.
CAUTION
8/11/2019 Section08_A4.pdf
28/806
E KC0 0 3 0 9 9 - a
10 33à –¾ • ‘ Expl anat i on
This Page Intentionally Left Blank
8/11/2019 Section08_A4.pdf
29/806
E KC0 0 3 0 9 9 - a
11 33à –¾ • ‘ Expl anat i on
3. Generator Structure
3.1 General
The generator is completely enclosed and, in operation uses hydrogen gas as the cooling
medium. The ventilation system including the fans and gas coolers is self-contained andcompletely enclosed to prevent entrance of dirt and moisture. Stator winding is directly cooled
by demineralized water and rotor winding are directly cooled with the hydrogen gas.
The generator casing is substantially cylindrical in shape and of welded gastight construction.
The outer end shields at either end of the casing are also of welded gastight construction and
support the generator bearings and shaft sealing devices. The generator casing and outer end
shields are of the explosion-proof type.
The stator core is supported by spring plates in the stator frame to isolate core vibration. The
rotor is of the gap pickup direct cooling type. Both ends of the rotor pass through the end
shields, and shaft seals are used to prevent hydrogen gas leakage. The generator is designed
for continuous operation and is constructed to withstand a sudden change in load and
three-phase shortcircuit. Various kinds of supervising and controlling instruments are provided
for keeping the generator in satisfactory operation.
Accessories include a gas control device, a cooling water control device for controlling the gas
temperature inside the generator as well as supervising and controlling device, and various
8/11/2019 Section08_A4.pdf
30/806
8/11/2019 Section08_A4.pdf
31/806
8/11/2019 Section08_A4.pdf
32/806
E KC0 0 3 0 9 9 - a
14 33à –¾ • ‘ Expl anat i on
8/11/2019 Section08_A4.pdf
33/806
E KC0 0 3 0 9 9 - a
15 33à –¾ • ‘ Expl anat i on
3.3 Stator Winding Armature Winding)
3.3.1 Stator Bar and Insulation
The stator winding is formed by insulated bars assembled in the slots of the stator core, jointed
at the ends to form coils, and connected to the proper phase belts by bus rings.
The stator bars shown in Fig.4 are composed of insulated copper strands arranged in the formof rectangular bars. As shown in Fig.3, each strand is so assembled that it occupies, for an
equal length of the bar, every radial position in the bar, which is accomplished by a spiral
progression of each strand around the bar, called “Reobel” transposition. This arrangementavoids eddy current losses under load conditions which would otherwise be caused by the
self-inductive magnetic flux distribution in the coil slot.
Required numbers of mica tapes are applied half lapped on the molded strands by using
automatic taping machine with constant tension device. After taping, stator bars are treated byvacuum to remove bubbles included in the bar insulation. Finally, the bars are molded into
required form. The peripheral parts of the insulator in the slot are coated with a semi-conductivecorona-inhibitive material, and the portion of the bar just outside the slot is protected with a
corona-inhibitive tape.
The end portions of stator windings are securely laced with glass cord to the binding bands,which are molded polyester-glass rings supported with end flanges through the binding band
supports. These supports are made from non magnetic steel and insulated.
8/11/2019 Section08_A4.pdf
34/806
E KC0 0 3 0 9 9 - a
16 33à –¾ • ‘ Expl anat i on
8/11/2019 Section08_A4.pdf
35/806
E KC0 0 3 0 9 9 - a
17 33à –¾ • ‘ Expl anat i on
8/11/2019 Section08_A4.pdf
36/806
E KC0 0 3 0 9 9 - a
18 33à –¾ • ‘ Expl anat i on
3.4 Generator Terminal Plate
The main armature leads extend through the bottom of the generator casing and the generator
terminal plate.
On this machine, connections are provided at the collector end portion. The terminal plate is
made from nonmagnetic material to prevent inducted currents from the current flow in the
armature leads. Drain is located in the terminal plate to prevent accumulation of oil or wateraround the connections. Gaskets are provided between the terminal plate and high-voltage
bushing flange to prevent hydrogen leakage. (See Fig.6)
8/11/2019 Section08_A4.pdf
37/806
E KC0 0 3 0 9 9 - a
19 33à –¾ • ‘ Expl anat i on
3.5 High-voltage Bushing and Current Transformer
The armature connections extend through the terminal plate by means of gas-tight, porcelain
insulated high-voltage bushings.
Site assembly of the bushings, armature leads in the terminal box, and covering of the
associated joints are accomplished after stator frame on base.
Mounting arrangement of the bushings is shown in Fig.7. Shows the assembly of a
bushing-type current transformer. The bushing type current transformer is mounted as enclosing
the terminal bushing and is used to measure generator output current and to protect and control
the generator. The bushing type current transformer is fastened to the terminal plate with studs.
8/11/2019 Section08_A4.pdf
38/806
E KC0 0 3 0 9 9 - a
20 33à –¾ • ‘ Expl anat i on
3.6 Rotor
3.6.1 Rotor Assembly
The rotor shaft is machined from a solid forging of Ni-Cr-Mo-V alloy steel. It’s quality has
been corroborated by mechanical, chemical, and metallurgical inspection and non-destructive
testing. The rotor core is slotted to accommodate rotor coils, and the rotor coils are secured in position with wedges that stand the centrifugal force of the coils.
As shown in Fig.8, the rotor pole portions are provided with semi-circular-shaped grooves
(cross slot) in the right angle direction to the rotor shaft axis for the purpose of equalizing therigidity in the magnetic pole direction and the right angle direction to it. The rotor pole, fan
bosses and collector fan can be fitted with balance weights to reduce rotor vibration. The
coupling and fan boss on turbine end are machined from the rotor shaft. The collector end fan boss is made of a shrink-fit forging of alloy steel. The axial flow fan, with wing-shaped blades,
is made of high-strength aluminum alloy and is engaged and bolted to the fan boss.
8/11/2019 Section08_A4.pdf
39/806
E KC0 0 3 0 9 9 - a
21 33à –¾ • ‘ Expl anat i on
3.6.2 Rotor Winding Field Winding) and Retaining Ring
The rotor conductors are machined to provide gas ducts, formed into shape, and put into the
slots in the rotor core. Fiber reinforced insulator is used for layer insulation and for the slot
insulation. A creepage block of fiber-glass-reinforced insulator, capable of withstanding the
centrifugal force of the conductor, is seated between the top of the conductor and the rotor
wedge to ensure a high insulation resistance to ground. Glass-base insulating blocks are set between coils to check the displacement of rotor end windings due to thermal stress and
centrifugal force. In addition, the end windings are supported with retaining rings shrink-fitted
on the core end. The retaining ring is secured to the rotor with an retaining ring key. A
glass-base annular insulator is set between retaining ring and the top of the coils for isolation
from the ground. The retaining ring is made of nonmagnetic Mn-Cr alloy steel with high
mechanical strength.
The rotor core and retaining ring are brought in direct contact with each other, and to flow
current in between in case of an unbalanced load or a sudden short-circuit fault. To reduce theeffect of this current, the engagement between the retaining ring and rotor shaft is metallized for
a reduced contact resistance. An amortisseur is provided under the retaining ring and the rotor
end wedge. Fig.9 shows arrangement of the retaining ring.
Fig.10 shows the arrangement of rotor winding.
8/11/2019 Section08_A4.pdf
40/806
P r o pr i e t ar y I n
f or m a t i on
© T o s h i b a C or p or a t i on2 0 1 1 ,A l l Ri gh t s
R e s er v e d
Wedge
Rotation
Suction hole
Layer insulation
Wedge
Suction hol
Rotor wed e
Creepage block
Sucton hole
Rotation
F
g
1
A
A
M
N
O
T
H
R
O
O
W
N
N
8/11/2019 Section08_A4.pdf
41/806
E KC0 0 3 0 9 9 - a
23 33à –¾ • ‘ Expl anat i on
3.7 Outer End Shield and Bearing
Fig.11 shows the outer end shield and bearing.
8/11/2019 Section08_A4.pdf
42/806
8/11/2019 Section08_A4.pdf
43/806
E KC0 0 3 0 9 9 - a
25 33à –¾ • ‘ Expl anat i on
8/11/2019 Section08_A4.pdf
44/806
E KC0 0 3 0 9 9 - a
26 33à –¾ • ‘ Expl anat i on
3.8 Shaft Sealing Device
A shaft sealing device is installed inside the machine to come inside of the bearing, and is used
to prevent hydrogen gas leaking from the machine through the shaft penetrant part.
Fig.13 shows the general assembly of the shaft sealing device. The seal casing has two seal
rings, and is mounted on the outer end shield. The collector end seal casing is split into inner and
outer halves; an insulating plate is provided between the inner and outer halves, and anotherinsulating plate is provided between the outer half casing and the outer end shield. These
insulating plates serve to prevent shaft current.
Fig.14 shows the seal ring and the flow of sealing oil. There are two seal rings of inner
(hydrogen side) and outer (air side) ring. The seal ring which is divided into two half-circles is
supported with upper and lower springs to follow the movement of the rotor shaft, and is
designed to ensure the continuity of oil film.
The seal ring is always supplied with sealing oil which is 50kPa higher than the insidehydrogen gas pressure. The sealing oil passes through the gap between the seal ring and shaft,
and is drained dividing into the hydrogen side and air side.
8/11/2019 Section08_A4.pdf
45/806
E KC0 0 3 0 9 9 - a
27 33à –¾ • ‘ Expl anat i on
8/11/2019 Section08_A4.pdf
46/806
E KC0 0 3 0 9 9 - a
28 33à –¾ • ‘ Expl anat i on
3.9 Collector and Brush
The brushes and collector rings are ventilated by an open circuit system in which the cooling
air is circulated through the air filter mounted on the air inlet.
The cooling air is sucked in from the air feed port of the operation floor and is discharged out
of the vent port of the collector cover
3.9.1 Collector Ring
The collector rings consist of negative and positive poles, which are made of high quality alloy
steel and shrunk onto insulated shaft.
As illustrated in Fig.15, the outer surface of the collector ring has spiral grooves for cooling
and removal of dust. The collector ring has axial holes for cooling ventilation and is fitted with a
shaft mounted fan between both rings for reducing temperature rise caused by excitation current.
E KC0 0 3 0 9 9
8/11/2019 Section08_A4.pdf
47/806
E KC0 0 3 0 9 9 - a
29 33à –¾ • ‘ Expl anat i on
3.9.2 Brush and Brush Holder
The rotor winding of the generator is directly cooled. Its exciting current is large and
necessitates large-capacity collector rings and a number of brushes.
As illustrated in Fig.16, the brush holder is of the magazine type, capable of attaching and
detaching four brushes en bloc. All brush holders are circumferentially arranged. By turning the
handle 90 • ‹, brush holders can be attached or detached to the brush holder receiver.Accordingly, in-service brush inspection and replacement can be carried out safely.
The brush for the generator is made of natural graphite, and has low friction and high
self-lubricating characteristic. The brush is fitted with a pigtail wire having a crimp-style
terminal on its end.
The constant-pressure spring in the brush holder forces the brush in the racial direction, and
the brush needs no pressure adjustment as it wears.
E KC0 0 3 0 9 9
8/11/2019 Section08_A4.pdf
48/806
E KC0 0 3 0 9 9 - a
30 33à –¾ • ‘ Expl anat i on
3.10 Hydrogen Gas Cooler
Four gas coolers are installed upright in the four corners of the stator frame. They use cooling
water to remove heat from hydrogen gas that is heated while being circulated within the
generator. Fig.17 shows installation of a typical, vertical-type, hydrogen gas cooler. The
hydrogen gas cooler is composed of a heat exchange section having a bundle of copper alloy
finned tubes, upper and lower tube sheets holding the upper and lower ends of the tube bundle,
and upper and lower water boxes.
Heat exchange between the cooling water and hydrogen gas is carried out by the counter-flow
system. Hot hydrogen gas enters the cooler from the cooling water drain side, and the cooled
hydrogen gas leaves the cooler from the cooling water supply side.
That part of the hydrogen gas cooler which passes through the stator frame is totally sealed to
prevent hydrogen gas leaking from the machine. At the lower part, a gland packing type seal is
used which is slidable to absorb the expansion and contraction of the cooler due to temperature
change.
8/11/2019 Section08_A4.pdf
49/806
P r o pr i e t ar y I n
f or m a t i on
© T o s h i b a C o
r p or a t i on2 0 1 1 ,A l l Ri gh t s
R e s er v e d
F
G
1
1
G
N
R
A
O
S
C
O
D
A
W
N
8/11/2019 Section08_A4.pdf
50/806
P r o pr i e t ar y I n
f or m a t i on
© T o s h i b a C o
r p or a t i on2 0 1 1 ,A l l Ri gh t s
R e s er v e d
F
G
1
2G
N
R
A
O
S
C
O
D
A
W
N
E KC0 0 3 0 9 9 - aŒo —ð • ‘
8/11/2019 Section08_A4.pdf
51/806
E KC0 0 3 0 9 9 - a
33 33à –¾ • ‘ Expl anat i onRevision History (for internal use)
Ï X
REV. PAGE
Ï X‰Ó Š‹y ‚Ñ “à —e
CHANGED PLACE AND CONTENT
³”F
APPROVED
’² ¸
REVIEWED
’S “–
PREPARED
‚• ‰ ”Å INITIAL ISSUEDWritten in
page 2.
Written in
page 2.
Written in
page 2.
8/11/2019 Section08_A4.pdf
52/806
8/11/2019 Section08_A4.pdf
53/806
8/11/2019 Section08_A4.pdf
54/806
8/11/2019 Section08_A4.pdf
55/806
8/11/2019 Section08_A4.pdf
56/806
8/11/2019 Section08_A4.pdf
57/806
8/11/2019 Section08_A4.pdf
58/806
8/11/2019 Section08_A4.pdf
59/806
8/11/2019 Section08_A4.pdf
60/806
8/11/2019 Section08_A4.pdf
61/806
8/11/2019 Section08_A4.pdf
62/806
8/11/2019 Section08_A4.pdf
63/806
8/11/2019 Section08_A4.pdf
64/806
8/11/2019 Section08_A4.pdf
65/806
8/11/2019 Section08_A4.pdf
66/806
8/11/2019 Section08_A4.pdf
67/806
8/11/2019 Section08_A4.pdf
68/806
8/11/2019 Section08_A4.pdf
69/806
8/11/2019 Section08_A4.pdf
70/806
8/11/2019 Section08_A4.pdf
71/806
8/11/2019 Section08_A4.pdf
72/806
8/11/2019 Section08_A4.pdf
73/806
8/11/2019 Section08_A4.pdf
74/806
8/11/2019 Section08_A4.pdf
75/806
1 of 22
E K C 0 0 3 1 0 0 - a
8/11/2019 Section08_A4.pdf
76/806
Vi etnam Li l ama Corporat i on
740MVA Turbi ne Generat or
Gas Cont rol Syst emAnd Shaf t Seal O l Syst em
I nst ruct i on Manual
2 of 22
E K C 0 0 3 1 0 0 - a
8/11/2019 Section08_A4.pdf
77/806
–¼• Ì TITLE
Ga s Cont r o l Sys t e m And Sha f t Se a l Oi l Sys t e m
‹q æ¼ CUSTOMER • F Li l ama Cor por a t i on
Œn ‹ Ší EQ/ SYS. • F 740MVA Tur bi ne Gene r at or
»”Ô J OB • F M231001, M231002, RT 2201
ƒvƒ‰ƒ“ ƒg PROJ ECT • F VVA1, VVA2,
3 of 22
E K C 0 0 3 1 0 0 - a
8/11/2019 Section08_A4.pdf
78/806
Table of Contents
Table of Contents·················································································································· 3
1. Introduction··················································································································· 5
2. Precautions for Safety··································································································· 5
3. Scope ····························································································································· 11
4.
Related Documents······································································································ 11
5. Explanation of Shaft Seal Oil System ······································································· 11
5.1 Shaft Seal Oil Circuit ·························································································11
5.2 Measuring Shaft Seal Oil Amount ·····································································16
5.3
Units Disconnection from System ·····································································17
6. Explanation of Gas Control System·········································································· 19
6.1
Continuous Scavenging······················································································19
6.2 Hydrogen-Gas Purity ·························································································19
6.3
Hydrogen-Gas Pressure······················································································20
7. Alarm Lists··················································································································· 21
E K C 0 0 3 1 0 0 – a
4 of 22
8/11/2019 Section08_A4.pdf
79/806
8/11/2019 Section08_A4.pdf
80/806
E K C 0 0 3 1 0 0 – a
6 of 22
8/11/2019 Section08_A4.pdf
81/806
WARRANTY AND LIMITATION OF LIABILITY
TOSHIBA CORPORATION AND THE USER’S DIRECT SELLER ACCEPT NO
LIABILITY FOR ANY INJURY, LOSS OR DAMAGE THAT RESULTS OR MAY
RESULT FROM ANY FAILURE TO OBSERVE THE PROCEDURES,
INSTRUCTIONS, WARNINGS, DESCRIPTIONS, DATA AND INFORMATION
APPLICATION
This Toshiba Steam Turbine and Generator Manual does not include all information necessary for every possible
contingency concerning the installation, operation and maintenance of the Toshiba Steam Turbine and Generator
Unit.
Should you require further information about the Toshiba Steam Turbine and Generator Unit or should a particular
situation arise which is not covered by this Toshiba Steam Turbine and Generator Manual, the matter should bereferred to Toshiba (contact details are specified at page 4 of this Manual).
E K C 0 0 3 1 0 0 – a
7 of 22
8/11/2019 Section08_A4.pdf
82/806
QUALIFIED PERSONS ONLY
AS A MINIMUM SAFETY REQUIREMENT, ONLY A “QUALIFIED PERSON”
SHOULD INSTALL, OPERATE OR MAINTAIN A TOSHIBA STEAM TURBINE
AND GENERATOR UNIT. THIS TOSHIBA STEAM TURBINE AND GENERATOR
MANUAL IS WRITTEN SOLELY FOR USE BY A “QUALIFIED PERSON”.
ONLY A “QUALIFIED PERSON” SHOULD INSTALL, OPERATE AND
MAINTAIN THE TOSHIBA STEAM TURBINE AND GENERATOR UNIT IN
ACCORDANCE WITH ALL APPLICABLE LAWS, REGULATIONS AND SAFETYPROCEDURES.
TO BE A “QUALIFIED PERSON”, YOU SHOULD HAVE SATISFIED ALL OF
THE FOLLOWING CRITERIA:
(1) YOU MUST HAVE CAREFULLY READ AND UNDERSTOOD THE
TOSHIBA STEAM TURBINE AND GENERATOR UNIT MANUAL AND ANY
OTHER MANUALS OF THE ASSOCIATED DEVICES AND COMPONENTS
OF THE TOSHIBA STEAM TURBINE AND GENERATOR UNIT MANUAL.
(2) YOU MUST HAVE RECEIVED TRAINING OFFERED BY TOSHIBA.
BEFORE YOU INSTALL, OPERATE OR MAINTAIN THE TOSHIBA STEAM
TURBINE AND GENERATOR UNIT, YOU MUST HAVE BEEN SO
AUTHORIZED BY THE PURCHASER
E K C 0 0 3 1 0 0 – a
8 of 22
8/11/2019 Section08_A4.pdf
83/806
SAFETY SIGN
(1) To ensure safety, all the SAFETY SIGNS (including DANGER LABELS, WARNING LABELS, CAUTION
LABELS and NOTE LABELS) must be read and understood
(2) All the SAFETY SIGNS (including DANGER LABELS, WARNING LABELS, CAUTION LABELS and NOTE
LABELS) must be kept in such condition that they can be easily seen. They must be clear enough to be
clearly visible and never be removed or blocked from view.
E K C 0 0 3 1 0 0 – a
9 of 22
8/11/2019 Section08_A4.pdf
84/806
■ In case the main seal oil pump and emergency seal oil pump cannot
be operated, lower the hydrogen-gas pressure in the generator
casing below 50kPag.
Hydrogen gas may leak and an explosion may potentially result.
■ In case supply pressure of shaft seal oil cannot be maintained,
dissociate and shut down the generator, release hydrogen gas in the
generator casing through the release pipe and lower the hydrogen-
gas pressure to atmospheric pressure. And fill carbon dioxide in the
generator casing.
Hydrogen-gas pressure is lowered, or hydrogen gas may leak and an explosion may potentially result.
■Always assume the by-pass valve of the float-trap to be closed.
Confirm hydrogen gas pressure in the generator is less than 10kPag
when you open the by-pass valve, and observe continuously so that
the oil level should not fall more than the center of level gauge.
Hydrogen gas may leak through the by-pass valve, air detraining section, oil drain pipe and outer oil
DANGER!
E K C 0 0 3 1 0 0 – a
10 of 22
8/11/2019 Section08_A4.pdf
85/806
■ In case the DC power to the pump motor cannot be supplied, makepreparation to lower gas pressure in the generator casing by
isolating the generator load and releasing hydrogen gas.
An accident involving generator damage may result.
■ Keep pressure in the generator is more than 10kPag while shaft seal
oil system is operating.
Oil drain flow may be bad and the oil leakage to inside of generator may result.
■ Do not allow unauthorized persons to enter your working area.
Clarify your off limits area by loping and displaying such as [Keep out].
Moving parts cause deaths or serious injuries.
■ Confirm grounding of your equipment before conducting a test.
Electric leakage or failure of your equipment causes a fire or an electric shock.
■ Prepare a stable scaffold and fall prevention & personal protective
equipment when working at an elevated place.
ARNING!
E K C 0 0 3 1 0 0 – a
11 of 22
8/11/2019 Section08_A4.pdf
86/806
3. Scope
This manual describes the method to operate the gas and shaft seal oil systems of the hydrogen-
cooled turbine generator.
4. Related DocumentsRefer to the system diagrams of the shaft seal oil system and gas system for use as system
diagrams in operating the generator under this manual.
Refer to the instructions EKC003087 “Instruction Manual for Filling and Releasing of H2 Gas” for filling and releasing hydrogen gas in the generator casing.
Refer to the instructions EKC003101 “Instruction Manual for Action to be Taken on Alarms
from Gas Control System and Shaft Seal Oil System” on actions to be taken on alarms.
5. Explanation of Shaft Seal Oil System
5.1 Shaft Seal Oil CircuitDepending on operational condition of the pumps in the bearing lubricating oil system and shaft
seal oil system of the turbine generator, the circuits for shaft seal oil are divided as follows.
a. Normal Operation
In normal operation, receiving oil cooled to a predetermined temperature from the bearing
lubricating oil system of the turbine generator as illustrated below, the shaft seal oil system
E K C 0 0 3 1 0 0 – a
12 of 22
8/11/2019 Section08_A4.pdf
87/806
The supply pressure of shaft seal oil is monitored by the pressure gauge and by differential-
pressure gauge. During generator operation, supply pressure for shaft seal oil is always adjusted
50kPag higher than the generator casing pressure. Therefore, the supply pressure for shaft seal
oil also will be automatically adjusted in accordance with variations in generator casing
pressure.
b. Emergency Shaft Seal Oil Circuit
(a) When Emergency Seal Oil Pump is Running
In case the main seal oil pump cannot be operated, the emergency seal oil pump will actuate
automatically and the oil will be fed to the shaft seals.
■ In case the DC power to the pump motor cannot be supplied, make
preparation to lower gas pressure in the generator casing byisolating the generator load and releasing hydrogen gas.
An accident involving generator damage may result.
Turbine-Lube Oil Tank Oil CoolerTurbine- Lube Oil Pump Emergency Seal Oil Pump
DANGER!
E K C 0 0 3 1 0 0 – a
13 of 22
8/11/2019 Section08_A4.pdf
88/806
■ In case the main seal oil pump and emergency seal oil pump cannot
be operated, lower the hydrogen-gas pressure in the generator
casing below 50kPag.
Hydrogen gas may leak and an explosion may potentially result.
In case the main seal oil pump and emergency seal oil pump cannot be operated, the generator
will be operated at supply oil pressure from the bearing lubricating oil system. During this
operation, hydrogen gas will be sealed by supply oil pressure of the bearing lubricating oil
system and the hydrogen-gas pressure inside the generator casing has to be lowered below
50kPag. The oil will be fed to the shaft seals through the differential-pressure regulating valve,
bypassing the pump.
Turbine-
Lube Oil
Turbine-
Lube OilOil Differential-Pressure
Regulating Valve
Shaft
S l
Float-Trap
Hydrogen
detraining section
Air
detraining
DANGER!
E K C 0 0 3 1 0 0 – a
14 of 22
8/11/2019 Section08_A4.pdf
89/806
‡ When the closed loop circulate operation is carried out at the rated hydrogen gas pressure,
the operation should not be over 1 hour.
‡A When it is necessary to carry out the closed loop circulate operation over 1hour, the
hydrogen pressure must be lowered under 50kpag beforehand.
‡B Monitor continuously the seal oil temperature on the shaft seal that should be 60ºC or under
to ensure the hydrogen seal function. In closed loop circuit operation, the temperature of
the seal oil that does not go through the main oil tank and the oil cooler, have the tendency
of becoming higher. The temperature should be measured on the return pipe just before the
float trap with a liquid-in-glass thermometer.
‡C When the main seal oil pump is started at the normal operation, hunting phenomena in the
Differential-Pressure
Regulating Valve
Float
Trap
Main
Seal
Pump
Shaft
Seals
Air
detraining
section
Hydrogen
detraining
section
Relief
Valve
E K C 0 0 3 1 0 0 – a
15 of 22
8/11/2019 Section08_A4.pdf
90/806
■ Do not operate the main seal oil pump and emergency seal oil pump
simultaneously on the closed loop circuit (without turbine lube oilsystem).
If the two pumps are operated simultaneously, temperature of the main seal oil pump may rise due to
stirring heat caused by a difference in discharge, potentially damaging the pumps.
■ In case supply pressure of shaft seal oil cannot be maintained,
dissociate and shut down the generator, release hydrogen gas in the
generator casing through the vent pipe and lower the hydrogen-gas
pressure to atmospheric pressure. And fill carbon dioxide in the
generator casing.
Hydrogen-gas pressure is lowered, or hydrogen gas may leak and an explosion may potentially result.
■ In case of closed loop circulate operation (without turbine lube oil
NOTE
DANGER!
E K C 0 0 3 1 0 0 – a
16 of 22
8/11/2019 Section08_A4.pdf
91/806
5.2 Measuring Shaft Seal Oil Amount
■ Operate in the correct sequence.
Otherwise oil leakage or other accident may potentially result.
This section describes the method to measure the amount of shaft seal oil to measure the
consumption of hydrogen gas.
a. Total Amount of Seal Oil Supply
1) Open Valves x0MKW40AA913 and x0MKW40AA015 installed front/rear of the flow
meter in the downstream of the differential-pressure regulating valve. Then slowly
close Valve x0MKW40AA014 by paying attention to the seal differential pressure.
2) Measure the amount of supply seal oil on the flow meter and record the supplied
amount.3) After finishing measurement, open Valve x0MKW40AA014 and close Valves
x0MKW40AA913 and x0MKW40AA015 installed front/rear of the flow meter
b. Hydrogen Side Amount of Seal Oil Supply
Let us assume that the bypass valve of the float-trap is closed, and that the level of oil in the
float-trap can be read on the liquid level gauge.
NOTE
E K C 0 0 3 1 0 0 – a
17 of 22
8/11/2019 Section08_A4.pdf
92/806
5.3 Units Disconnection from System
■ Operate in the correct sequence.
Otherwise oil leakage or other accident may potentially result.
a. Disconnecting Main Seal Oil Pump and Relief Valve x0MKW40AA602
1) Start up the emergency seal oil pump.
2) Shut down the main seal oil pump and close its Inlet Valve x0MKW40AA007
and Outlet Valve x0MKW40AA032 of relief valve. Then close Outlet Valve
x0MKW40AA704 of the main seal oil pump.
The generator units can be serviced for checks and repairs after operating as described
above.
b. Disconnecting Float-Trap1) Change the oil level gauge of the float-trap from the float-trap to the bypass tank.
Close Valves x0MKW30AA003 and x0MKW30AA006. Open Valves
x0MKW30AA904 and x0MKW30AA905.
2) Adjust the opening of Outlet Valve 0MKW30AA002 of the bypass tank and
stabilize the oil the bypass tank.
NOTE
E K C 0 0 3 1 0 0 – a
18 of 22
8/11/2019 Section08_A4.pdf
93/806
c. Disconnecting Differential-Pressure Regulating Valve x0MKW40AA101
1) Adjust the opening Bypass Valve x0MKW40AA012 of the differential-pressureregulating valve in accordance with indication on the differential-pressure gauge.
Adjust to 50kPag in case the differential pressure currently indicated is below
50kPag. Otherwise adjust between 5k • ` 20kPag higher than the current
indication.
2) Close Outlet Valve x0MKW40AA014 of the differential-pressure regulating
valve with watching indication on the differential-pressure gauge. Check that
the differential pressure does not vary.3) Close Inlet Valve x0MKW40AA011 of the differential-pressure regulating
valve.
4) Close Differential-Pressure Detection Valves x0MKW40AA016 and
x0MKW40AA017 of the differential-pressure regulating valve.
The differential-pressure regulating valve can be serviced for checks and repairs after
operating as described above.
E K C 0 0 3 1 0 0 – a
19 of 22
8/11/2019 Section08_A4.pdf
94/806
6. Explanation of Gas Control System
6.1 Continuous Scavenging
A continuous scavenging system is used for this generator as a method to seal a hydrogen
gas in the generator casing.
Since the air-contained oil is supplied for the shaft seals from the shaft seal oil system.
This air is discharged from the oil and mixed to hydrogen gas in the section between inner
oil deflector and oil seal casing. Therefore the gas in this section must be continuouslyscavenged to prevent lowering hydrogen gas purity. The scavenging flow rate is 6000• `
10000 cc/min (total of turbine and collector end), from the hydrogen detraining sections at
turbine and collector end.
Refer to 5.4.1 Checking Continuous Scavenging Operation in the Instruction Manual for
Filling and Releasing of H2 Gas (Document No. EKC003087 ).
6.2 Hydrogen-Gas Purity
An alarm will be issued in case the purity of hydrogen gas scavenged from the hydrogen
detraining section lowers to 85% and 80%. During generator operation, gas in the
hydrogen detraining section is continuously flowed to the transmitter of the purity
indicator to measure the hydrogen-gas purity.
The flow rate to the gas purity transmitter is adjusted to about 500 to 1000cc/min by
needle valves (x0MKG50AA015 and x0MKG50AA016)
E K C 0 0 3 1 0 0 – a
20 of 22
8/11/2019 Section08_A4.pdf
95/806
6.3 Hydrogen-Gas Pressure
Hydrogen-gas pressure is monitored by the hydrogen-gas pressure gauge. An alarm is issued when
pressure varies to normal operating pressure 20kPag. Generally, hydrogen-gas consumption of a
generator can be expressed by the following formula:
This means that hydrogen gas inside the generator casing is consumed by the amount of hydrogen
dissolved in hydrogen side seal oil and of scavenging gas in it even if no hydrogen gas is leaked
through the gas system of the generator. Normally, hydrogen gas is automatically supplied through
the hydrogen-gas pressure regulating valve during steady generator operation, and hydrogen-gas
pressure in the generator casing can be maintained at desired pressure almost constantly. In case quick
boosting of hydrogen-gas pressure inside the generator casing is needed, hydrogen gas is suppliedthrough the bypass valve of the hydrogen-gas pressure regulating valve as in initial filling.
A hazard potentially exists if hydrogen-gas pressure inside the generator casing gradually lowers or
lowers in a short time. Troubleshoot the cause as soon as possible and examine the leakage location.
The hydrogen-gas pressure inside the generator casing slightly rises or lowers depending on the
generator hydrogen-gas temperature.
Consumption = Leakage amount
Amount of hydrogen
dissolved in hydrogen
side seal oil
+ +
Amount of
scavenging
gas
E K C 0 0 3 1 0 0 – a
21 of 22
8/11/2019 Section08_A4.pdf
96/806
7. Alarm Lists
Periodically test the level switches and pressure switches whether or not alarms function
properly, for each of the following items:
Shaft Seal Oil System:
Item Actuation Value Remarks
1 Discharge pressure of main
seal oil pump
Service pressure -100kPa
or lower.
See NOTE 1.
Emergency seal oil
pump actuated.
2 Differential pressure of duplex
seal oil strainer
20kPa or higher
3 Differential pressure of shaft
seal oil (Supply pressure of
shaft seal oil : Hydrogen-gas
pressure inside generator
casing)
30kPa or lower
4 Hydrogen detraining section
oil level
±10mm of sight-gauge
centerline
5 Air detraining section oil level -50mm or lower from
normal level
E K C 0 0 3 1 0 0 – a
22 of 22
8/11/2019 Section08_A4.pdf
97/806
This Page Intentionally Left Blank
8/11/2019 Section08_A4.pdf
98/806
8/11/2019 Section08_A4.pdf
99/806
8/11/2019 Section08_A4.pdf
100/806
8/11/2019 Section08_A4.pdf
101/806
8/11/2019 Section08_A4.pdf
102/806
8/11/2019 Section08_A4.pdf
103/806
8/11/2019 Section08_A4.pdf
104/806
8/11/2019 Section08_A4.pdf
105/806
8/11/2019 Section08_A4.pdf
106/806
8/11/2019 Section08_A4.pdf
107/806
8/11/2019 Section08_A4.pdf
108/806
8/11/2019 Section08_A4.pdf
109/806
8/11/2019 Section08_A4.pdf
110/806
8/11/2019 Section08_A4.pdf
111/806
8/11/2019 Section08_A4.pdf
112/806
8/11/2019 Section08_A4.pdf
113/806
8/11/2019 Section08_A4.pdf
114/806
8/11/2019 Section08_A4.pdf
115/806
8/11/2019 Section08_A4.pdf
116/806
8/11/2019 Section08_A4.pdf
117/806
8/11/2019 Section08_A4.pdf
118/806
8/11/2019 Section08_A4.pdf
119/806
8/11/2019 Section08_A4.pdf
120/806
8/11/2019 Section08_A4.pdf
121/806
8/11/2019 Section08_A4.pdf
122/806
8/11/2019 Section08_A4.pdf
123/806
8/11/2019 Section08_A4.pdf
124/806
8/11/2019 Section08_A4.pdf
125/806
8/11/2019 Section08_A4.pdf
126/806
8/11/2019 Section08_A4.pdf
127/806
8/11/2019 Section08_A4.pdf
128/806
8/11/2019 Section08_A4.pdf
129/806
8/11/2019 Section08_A4.pdf
130/806
8/11/2019 Section08_A4.pdf
131/806
8/11/2019 Section08_A4.pdf
132/806
8/11/2019 Section08_A4.pdf
133/806
1 of 38
E K C 0 0 3 1 0 2 - a
8/11/2019 Section08_A4.pdf
134/806
Vi etnam Li l ama Corporat i on
740MVA Turbi ne Generat or
St at or Cool i ng Wat er Syst em
I nst ruct i on Manual
2 of 38
E C K 0 0 3 1 0 2 - a
–¼• Ì TITLE
St a t o r Cool i ng Wa t e r Sys t e m
8/11/2019 Section08_A4.pdf
135/806
‹q æ¼ CUSTOMER • F Li l a ma Cor p r a t i on
Œn ‹ Ší EQ/ SYS. • F 740MVA Tur bi ne Gene r at or
»”Ô J OB • F M231001, M231002, RT 2201
ƒvƒ‰ƒ“ ƒg PROJ ECT • F VVA1, VVA2
E K C 0 0 3 0 2 - a
3 of 38
Table of Contents
8/11/2019 Section08_A4.pdf
136/806
1. Introduction 5
2. Precautions for Safety 5
3. Scope 13
4. Related Documents 13
5. Description 13
5.1 Design Data ········································································································13
5.2 General Description ··························································································· 14
6. Operation 21
6.1 Introduction ········································································································21
6.2 Operating Procedure ·························································································· 23
6.3 Operating Values and Limits ············································································· 24
6.4 Alarm Action······································································································25
6.5 Prestart Valve Status ··························································································28
7. Maintenance 35
7 1 Periodic Operation Inspection and Tests····························································35
E K C 0 0 3 1 0 2 - a
4 of 38
This page Intentionally Left Blank
8/11/2019 Section08_A4.pdf
137/806
This page Intentionally Left Blank
E K C 0 0 3 0 2 - a
5 of 38
1. Introduction
This manual is written to ensure safe handling of Stator Cooling Water System Before
8/11/2019 Section08_A4.pdf
138/806
This manual is written to ensure safe handling of Stator Cooling Water System. Before
operation, maintenance and inspection, be certain to read this manual for proper use of the
equipment. This manual should be kept near the equipment so it can be readily referenced.
2. Precautions for Safety
Signs and messages in this manual and on the equipment body are important for management,operation, maintenance and inspection. They are given to avoid possible injuries and damages as
well as to ensure correct handling of the equipment. The following signs and short messages
should thoroughly be understood before reading this manual. It is advised that you also read theinstruction manuals of related equipment and components.
IMPORTANT MESSAGES
Read this manual and follow its instructions. Signal words such as DANGER, WARNING, two kinds of CAUTION,and NOTE, will be followed by important safety information that must be carefully reviewed.
Indicates an imminently hazardous situation, which will result in death or serious injury if
you do not follow instructionsDANGER!
E K C 0 0 3 1 0 2 - a
6 of 38
APPLICATION
8/11/2019 Section08_A4.pdf
139/806
This Toshiba Steam Turbine and Generator Manual does not include all information necessary for every possible
contingency concerning the installation, operation and maintenance of the Toshiba Steam Turbine and Generator
Unit.
Should you require further information about the Toshiba Steam Turbine and Generator Unit or should a particular
situation arise which is not covered by this Toshiba Steam Turbine and Generator Manual, the matter should be
referred to Toshiba (contact details are specified at page 2 of this Manual)
WARRANTY AND LIMITATION OF LIABILITY
TOSHIBA CORPORATION AND THE USER’S DIRECT SELLER ACCEPT NO
LIABILITY FOR ANY INJURY, LOSS OR DAMAGE THAT RESULTS OR MAY
RESULT FROM ANY FAILURE TO OBSERVE THE PROCEDURES,
INSTRUCTIONS, WARNINGS, DESCRIPTIONS, DATA AND INFORMATION
8/11/2019 Section08_A4.pdf
140/806
E K C 0 0 3 1 0 2 - a
8 of 38
SAFETY SIGN
8/11/2019 Section08_A4.pdf
141/806
(1) To ensure safety, all the SAFETY SIGNS (including DANGER LABELS, WARNING LABELS, CAUTION
LABELS and NOTE LABELS) must be read and understood
(2) All the SAFETY SIGNS (including DANGER LABELS, WARNING LABELS, CAUTION LABELS and NOTE
LABELS) must be kept in such condition that they can be easily seen. They must be clear enough to be
clearly visible and never be removed or blocked from view.
E K C 0 0 3 0 2 - a
9 of 38
P i t t d i th t t h i l d It i i d t
ARNING!
8/11/2019 Section08_A4.pdf
142/806
■ Pump is not operated in the state where is no load. It is required to
pour in water before operating.
Pump is damaged.
■ Second alarm point (9.9ƒÊ
S/cm) is very dangerous.
This value indicates the maximum permissible conductivity.
If the conductivity has been reached this point, the generator shouldbe tripped.
■ The Generator can be run without the Stator Water system in
operation but output is then limited to 185,000kVA at 0.85pf.
■ If Stator Water conductivity reaches the second alarm point of 9.9ƒÊ
S/cm, the generator should be tripped immediately.
■ The second alarm contact is set at 9.9ƒÊS/cm, which indicates the
maximum permissible conductivity.
If the conductivity has been reached this point, the generator should
E K C 0 0 3 1 0 2 - a
10 of 38
O t ft ki ll th d f i d l i
CAUTION!
8/11/2019 Section08_A4.pdf
143/806
■ Operate a pump after making small the degree of opening and closing
of a pressure regulating valve.
It becomes the cause which an excessive pressure joins a stator coil and damage produces.
■ Make into 60• Ž
or less temperature of the cooling water which flows
to deionizer.
If temperature exceeds 60•Ž the performance will fall.
■ Do not freeze resin.
Effect will be lost once resin is frozen.
■ When not using deionizer, pure water is kept in the state of full of
water in a tub.
Dryness of resin reduces the performance.
■ When a stator water pump is started, don’t stand by it. Check the
water level of the storage tank after pump operating. If the water
level goes on decreasing the pump must be stopped at once The
E K C 0 0 3 0 2 - a
11 of 38
CAUTION
8/11/2019 Section08_A4.pdf
144/806
■ Set up the no fire zone near the hydrogen vent discharge pipe above
the roof. Check the existence of water at a “U” seal pipe of the vent
pipe near the storage tank.
If water does not exist in “U” seal pipe, hydrogen gas may be spread in a building and a fire and explosion
may occur. Moreover air flows into the tank and degrades the electrical conductivity of cooling water.
■ When the differential pressure increases to 0.09MPa, must be replace
the filter elements.
Only use manufacturer recommended filter elements.
■ Keep the following matters, when you exchange filters.
‡ Filter element exchanges total.‡AWash a filter
‡B
Air vent valve is opened, and water is poured into the tub,
extracting the air contained in the filter. Then drain valve is
opened and water is discharged.
E K C 0 0 3 1 0 2 - a
12 of 38
■ Since make up water could initially contain metal oxides etc it
NOTE
8/11/2019 Section08_A4.pdf
145/806
■ Since make-up water could initially contain metal oxides, etc., it
should be drained until clear before being fed through the filter to the
storage tank.
■ The amberlite IRN-150 is based on the resin being of the gel type and
having a matrix structure of styrene-divinyl benzene, and contains
copper.When you abolish it, please follow your regulations.
E K C 0 0 3 0 2 - a
13 of 38
3. Scope
This manual describes the method of operate the stator cooling water systems of the watercooled turbine generator
8/11/2019 Section08_A4.pdf
146/806
cooled turbine generator.
4. Related Documents
Refer to the Diagram of Stator Cooling Water System : 1KC003727.
5. Description
5.1 Design Data
Stator cooling water pump : 2920rpm, 1200 /min
Stator cooling water pump motor : 2920rpm, 30kW
Stator cooling water
Rated inlet pressure : Higher than 0.16MPa
Low inlet pressure alarm : set at site at equivalent flow rate 880 /min
x0MKF40CP104 (at x0MKF30AA851 Valve)
E K C 0 0 3 1 0 2 - a
14 of 38
5.2 General Description
8/11/2019 Section08_A4.pdf
147/806
5.2.1 Outline of Stator Winding Cooling Water System
Stator winding cooling system is designed to maintain temperature rise of the stator winding
suitably, and conductivity of the cooling water low. The cooling water to be supplied to stator
winding is held at rated flow under the conditions that the inlet temperature is 46• Žand the
conductivity at 25• Žis below 0.5ƒÊS/cm.
The flow rate and conductivity of the cooling water for stator winding is inspected and adjusted
by the control system consisting of stator water storage tank, two stator cooling water circulating
pumps, two stator water coolers, temperature and pressure control valves, stator water filter,
demineralizing equipment and instruments. There is a branch, bypassing the generator, with a
deionizer for keeping continuous purification of the water.
5.2.2 Stator Water Storage TankThe storage tank has a capacity of approximately 2.69m
3, and the water level is continuously
monitored by float switch which provides alarm when water level fluctuates above or below the
normal level. It also has a water level gauge so its water level can be observed with the naked eye.
Make-up water will be replenished to the deionizer through a filter so as not to increase
E K C 0 0 3 0 2 - a
15 of 38
5.2.3 Stator Cooling Water Circulating Pump
The cooling water circulation in normally performed by an A.C. motor-driven centrifugal pump.
In addition, an A.C. motor-driven centrifugal pump of equal capacity is installed as standby. The
8/11/2019 Section08_A4.pdf
148/806
pump can be started manually, and it can also be started automatically by a pressure switch
(x0MKF40CP105, x0MKF40CP106) located on the outlet pipe common to both pumps.
The rate of flow circulating through the deionizer is approximately 10% of that flowing through
the generator winding.
In order to remove either pump for inspection during one pump operation, valves are provided at
both inlet and outlet of each pump.
■ Pump is not operated in the state where is no load. It is required to
pour in water before operating.
Pump is damaged.
ARNING!
CAUTION!
E K C 0 0 3 1 0 2 - a
16 of 38
5.2.5 Stator Water Filter and Strainer
In the cooling water system, depth type disposable wound cartridge filters are provided at the
stator cooling water pump discharge to filter all the water to the generator winding.
8/11/2019 Section08_A4.pdf
149/806
These filters are designed to prevent metallic corrosive particles generated in winding and
piping from entering into winding hollow conductor. The minimum size of grains to be filtered by
the filters is about 3ƒÊm. A differential pressure gauge (x0MKF20CP101) is provided across
filter for observation of any solid substance which is accumulated.
■ When the differential pressure increases to 0.09MPa, must be replace
the filter elements.
Only use manufacturer recommended filter elements.
■ Keep the following matters, when you exchange filters.
‡ Exchange all Filter elements.
‡A
Wash a filter
‡BAir vent valve is opened, and water is poured into the tub,
extracting the air contained in the filter. Then drain valve is
opened and water is discharged.
CAUTION
E K C 0 0 3 0 2 - a
17 of 38
5.2.6 Deionizer
The deionizer is an ion exchange resin tower of floor type where the amberlite IRN-150 resin
(cathion exchange resin IRN-77 and anion exchange resin IRN-78 are mixed) are filled in
8/11/2019 Section08_A4.pdf
150/806
stainless steel wire-netting supporting the resin layers in a stainless steel tower. A pipe is provided
for replacing and removing resin from the deionizer.
■ Make into 60• Žor less temperature of the cooling water which flowsto deionizer.
If temperature exceeds 60•Ž the performance will fall.
■ Do not freeze resin.
Effect will be lost once resin is frozen.
■ When not using deionizer, pure water is kept in the state of full of
water in a tub.
Dryness of resin reduces the performance.
CAUTION!
E K C 0 0 3 1 0 2 - a
18 of 38
The quantity of water flowing into the deionizer can be inspected by a flow meter, but it should
not exceed 15% of the flow running to the generator winding. When the amount of water flowing
into the deionizer reaches this flow rate, and the conductivity of the generator inlet cooling water
can not be held under 0.5ƒÊS/cm, it is necessary to replace the ion exchange resin.
8/11/2019 Section08_A4.pdf
151/806
5.2.7 Cooling Water Conductivity
Each of the three conductivity measurements are temperature compensated to 25• Ž, and the
conductivity is measured by a conductivity indicator at the three points (the generator cooling
water inlet, the generator outlet and the deionizer outlet) in the cooling water system.
The conductivity indicator will successively indicate and has two alarm contacts in case of high
conductivity. Conductivity measuring elements are attached to above three points, and are so
arranged that they can be removed without taking the plant out of service.
5.2.7.1 Make-up Water to System
ALL make-up water for cooling water system is sent through filters and deionizer.
Fl shing sho ld caref ll be applied to the filter piping if feed ater
CAUTION
E K C 0 0 3 0 2 - a
19 of 38
5.2.7.2 Operation without Stator Cooling Water Flow
During normal operation, it is expected that the conductivity will be less than 0.5ƒÊS/cm. One
alarm contact is set at this value to anticipate any subsequent increase in conductivity and to
i ki i
8/11/2019 Section08_A4.pdf
152/806
permit making necessary corrections.
■ The second alarm contact is set at 9.9ƒÊ
S/cm, which indicates the
maximum permissible conductivity.
If the conductivity has been reached this point, the generator should
be tripped.
5.2.8 Alarm and Reduction of Generator Output with Turbine Interlock
5.2.8.1 Alarm
Item Alarm setting value
Generator inlet cooling water
press.( x0MKF40CP104
at x0MKF30AA851 VALVE)
LowSet pressure valve at equivalent flow rate
880 /min at site.
ARNING!
E K C 0 0 3 1 0 2 - a
20 of 38
5.2.8.1 Trip
Item Alarm setting value
Generator outlet cooling water temperature
(x0MKF20CT001 CT002 CT003)High 95• Ž
8/11/2019 Section08_A4.pdf
153/806
(x0MKF20CT001, CT002, CT003)g
Generator inlet cooling water pressure.
(x0MKF40CP101, CP102, CP103)Reduced
Set pressure valve at equivalent flow rate
720 /min at site.
5.2.9 Stator Winding Cooling Water Controlling Equipment
This equipment consists of stator water tank, stator water pumps, stator water coolers, statorwater filter, regulating valves, deionizer, and related piping and valves which are perfectly
installed on the base.
Refer to outline stator cooling water unit : Drawing No.1KC003760.
E K C 0 0 3 0 2 - a
21 of 38
6. Operation
6.1 Introduction
8/11/2019 Section08_A4.pdf
154/806
In the procedures below, the terms Stator Water and Cooling Water are used to distinguish
between the treated and untreated water, respectively.
■ The Generator can be run without the Stator Water system in
operation but output is then limited to 185,000kVA at 0.85pf.
During normal (weekend) shutdown, the Stator Water system is kept running to maintain water
conductivity.
The Stator Water interlock should not be canceled before tripping the unit since shutdown offers
the opportunity to check that Stator Water pumps trip with the generator. Immediately aftertripping, however, the interlock should be canceled and the Stator Water pump restarted.
6.1.1 Charging the Stator Water System
ARNING!
E K C 0 0 3 1 0 2 - a
22 of 38
6.1.2 Coolers
Each Stator Water cooler is rated at 100%.
As being filled, the coolers are filled first with Cooling Water and then Stator Water. As being
8/11/2019 Section08_A4.pdf
155/806
shut down for an extended period, they are drained of cooling water.
Prior to a cold start, the Cooling Water flow is shut off to allow the Stator Water temperature to
increase (due to friction losses).
6.1.3 Deionizer
■ If Stator Water conductivity reaches the second alarm point of 9.9ƒÊ
S/cm, the generator should be tripped immediately.
Deionizer resin has a life of about one year. It is replaced if:
a. The pressure drop across the deionizer exceed 1bar.
b. Stator water conductivity at its outlet exceeds
0.5ƒÊS/cm (with the normal proportion of Stator Water by-passing the coolers).
ARNING!
E K C 0 0 3 0 2 - a
23 of 38
6.1.4 Pump Testing on Load
Auto starting of the Stator Water standby pump is tested without stopping the duty pump.
8/11/2019 Section08_A4.pdf
156/806
6.2 Operating Procedure
6.2.1 Preparation for Starting
a. Set up the system as in the prestart valve status.
b. Check electrical supplies to motors.
c. Check alarm and protection supplies.
d. Check that air supply is available to proportioning valve.
e. Check that conductivity meters are in service.
f. Check that Stator Water pump bearing lubricating oil levels at the bearing oil gauge.
6.2.2 Charging and Starting the System
g. Start the duty pump, and set the standby pump to AUTO.
h. Trip the duty pump, confirm starting of standby pump automatically.
E K C 0 0 3 1 0 2 - a
24 of 38
q. Check that the pump discharge pressure returns to normal value(0.74MPa).
r. Set the standby pump to AUTO.
6 3 Operating Values and Limits
8/11/2019 Section08_A4.pdf
157/806
6.3 Operating Values and Limits
Item Unit Normal Alarm Trip
Stator water temperature
Generator inlet
Generator outlet
• Ž
• Ž
40 to 46
*76
48
10 above measured
outlet temp. at full
load
95
Storage tank level mm
Gauge glass
indication Normal• }
100
Stator water conductivity
Generator outlet
Generator inletƒÊS/cm less than 0.3
(1st) (2nd)
0.5 9.9 •
E K C 0 0 3 0 2 - a
25 of 38
6.4 Alarm Action
Alarm conditions Possible causes Action required
Stator
cooling water
LOW Failure of stator water
pump and motor
Check the stator water
pump and motor
8/11/2019 Section08_A4.pdf
158/806
cooling water
inlet pressure
pump and motor
Failure of press. switch
pump and motor.
Check the discharge
pressure gauge, standby
stator water pump will be
started.
Statorcooling water
inlet flow
LOW Failure of stator water pump and motor
Failure of press. Regulating
valve (x0MKF20AA103)
Leakage of water inlet line
Above action is required.
Check the pressure
regulating valve and
control sequence.
Check the leakage point.
Stator
cooling water
pump discharge
pressure
LOW Failure of stator water
pump and motor
Failure of press. switch
Check the failed pump and
motor.
Check the pressure gauge
and switches.
E K C 0 0 3 1 0 2 - a
26 of 38
Alarm conditions Possible causes Action required
Statorcooling water outlet
t t
HIGH Failure of regulating valve(x0MKF20AA101)
Check the generatorloading, stator water inlet
fl d
8/11/2019 Section08_A4.pdf
159/806
temperature flow and pressure.
Check the stator coil
temperatures with R.T.D
If necessary, detail check is
required with outlet water
temperature of each stator
coil.
Water level
in water storage
tank
HIGH
LOW
(Normal level• }100mm)
Failure of water level
switch
Leakage of storage tank
and piping
Check the water level
gauge with storage tank.
Normally, the water level is
decreased, because theevaporating steam of the
discharge water is vented
out through the vent
piping.
E K C 0 0 3 0 2 - a
27 of 38
Alarm conditions Possible causes Action required
Turbine interlock Without circulation
through the stator cooling
water system
The quality of the cooling
water will deteriorate and
conductivity will increase
8/11/2019 Section08_A4.pdf
160/806
Failure of both stator water
pump
Failure of regulating valves
Failure of stator water
coolers.
The rate of deterioration
may be influenced by
several factors and
following parameters have
been established by test.
Following reduction in
output to rated capability
without stator cooling
water circulation.
1) If the conductivity prior to
cessation of flow is more
than 0.5ƒÊS/cm within 3
minutes, reduce
voltage to zero and trip.
2) If the conductivity prior to
cessation of flow is less than
0.5ƒÊS/cm within 60
E K C 0 0 3 1 0 2 - a
28 of 38
6.5 Prestart Valve Status
NOTE
1. O: Open C: Close T: Throttle A: Automatic S: Select
8/11/2019 Section08_A4.pdf
161/806
VALVE
NUM-
BER
VALVE NAMEPLATE INSCRIPTION
VALVE
POSI-
TION
CHECK
REM-
ARKS
x0MKF20AA001 SCWP(A) SUCTION ISOL VALVE O
x0MKF20AA003 SCWP(B) SUCTION ISOL VALVE O
x0MKF20AA851 SCWP(A) DRAIN VALVE C
x0MKF20AA852 SCWP(B) DRAIN VALVE C
x0MKF20AA801 SCWP(A) AIR VENT VALVE C
x0MKF20AA802 SCWP(B) AIR VENT VALVE C
x0MKF20AA701 SCWP(A) DISHC. NON RETURN VALVE O
x0MKF20AA702 SCWP(B) DISHC. NON RETURN VALVE O
0MKF20AA002 SCWP(A) DISHC GATE VALVE O
E K C 0 0 3 0 2 - a
29 of 38
VALVE
NUM-
BER
VALVE NAMEPLATE INSCRIPTION
VALVE
POSI-
TION
CHECK
REM-
ARKS
0MKF20AA856
8/11/2019 Section08_A4.pdf
162/806
x0MKF20AA856
(For cooler B)COOLER (B) DRAIN VALVE C
x0MKF20AA101 TCV TEMP. CONTROL VALVE A
x0MKF20AA009 FILTER INLET ISOL VALVE O
x0MKF20AA013 FILTER OUTLET ISOL VALVE O
x0MKF20AA807 FILTER AIR VENT VALVE C
x0MKF20AA910 FILTER ISOL VALVE FOR PDI O
x0MKF20AA912 FILTER ISOL VALVE FOR PDI O
x0MKF20AA911 FILTER EQUALIZE VALVE FOR PDI C
x0MKF20AA867 FILTER DRAIN VAVLE C
E K C 0 0 3 1 0 2 - a
30 of 38
VALVE
NUM-
BER
VALVE NAMEPLATE INSCRIPTION
VALVE
POSI-
TION
CHECK
REM-
ARKSx0MKF30AA851 GEN/STAT CLG WTR GAUGE VALVE C
8/11/2019 Section08_A4.pdf
163/806
x0MKF30AA903 GEN/STAT CLG WTR GAUGE VALVE O
x0MKF50AA001 GEN/SCW INL HDR BLOW VALVE C
x0MKF50AA002 GEN/SCW OTL HDR BLOW VALVE C
x0MKF20AA868 GEN OUT SAMPLING VALVE C
x0MKF20AA929 GEN OUT CDTY CELL ISOL VALVE O
x0MKF20AA926 STORAGE TANK LS ISOL VALVE O
x0MKF20AA927 STORAGE TANK LS ISOL VALVE O
x0MKF20AA866 STORAGE TANK LS DRAIN VALVE C
E K C 0 0 3 0 2 - a
31 of 38
VALVE
NUM-
BER
VALVE NAMEPLATE INSCRIPTION
VALVE
POSI-
TION
CHECK
REM-
ARKSx0MKF20AA015 DEIONIZER INLET ISOL VALVE T
8/11/2019 Section08_A4.pdf
164/806
x0MKF20AA703 DEIONIZER INLET NON RETURN VALVE O
x0MKF20AA916 DEIONIZER INL PRESS ISOL VALVE O
x0MKF20AA018 DEIONIZER OTL ISOL VALVE O
x0MKF20AA808 DEIONIZER AIR VENT VALVE C
x0MKF20AA860 DEIONIZER INLET PRESS DRAIN VALVE C
x0MKF20AA861 DEIONIZER RESIN DRAIN VALVE C
x0MKF20AA917 DEIONIZER OTL PRESS ISOL VALVE O
x0MKF20AA862 DEIONIZER RESIN WASH VALVE C
x0MKF20AA919 DEIONIZER CDTY CELL ISOL VALVE O
x0MKF20AA867 STRAGE TANK DRAIN ISOL VALVE C
E K C 0 0 3 1 0 2 - a
32 of 38
VALVE
NUM-
BER
VALVE NAMEPLATE INSCRIPTION
VALVE
POSI-
TION
CHECK
REM-
ARKSGEN. INLET STATOR COOLING WATER PRESS
x0MKF40CP104 ISOL VALVEO
8/11/2019 Section08_A4.pdf
165/806
x0MKF40CP104 ISOL VALVEx0MKF40AA004
GEN. INLET STATOR COOLING WATER PRESS
x0MKF40CP104 TEST VALVEC
GEN. INLET STATOR COOLING WATER PRESS.
x0MKF40CP101 PS ISOL VALVEO
x0MKF40AA001 GEN. INLET STATOR COOLING WATER PRESS.x0MKF40CP101 TEST VALVE
C
GEN. INLET STATOR COOLING WATER PRESS.
x0MKF40CP102 ISOL VALVEO
x0MKF40AA002 GEN. INLET STATOR COOLING WATER PRESS.
x0MKF40CP102 TEST VALVEC
GEN. INLET STATOR COOLING WATER PRESS.
x0MKF40CP103 ISOL VALVE O
x0MKF40AA003 GEN. INLET STATOR COOLING WATER PRESS.
x0MKF40CP103 TEST VALVEC
GEN. INLET STATOR COOLING WATER PRESS.O
E K C 0 0 3 0 2 - a
33 of 38
VALVE
NUM-
BER
VALVE NAMEPLATE INSCRIPTION
VALVE
POSI-
TION
CHECK
REM-
ARKSGEN. INLET STATOR COOLING WATER FLOW
x0MKF40CF001 ISOL(L) VALVEO
8/11/2019 Section08_A4.pdf
166/806
( )
GEN. INLET STATOR COOLING WATER FLOW
x0MKF40CF001TEST VALVEC
x0MKF40AA009 GEN. INLET STATOR COOLING WATER