Section08_A4.pdf

Embed Size (px)

Citation preview

  • 8/11/2019 Section08_A4.pdf

    1/806

     

    P-1 of 2

    M a i n C o n t e n t s - a

    Main Table of ContentsOperation and Maintenance Instruction ManualVolume 2 Maintenance and System Description Manual

    Book No Section No Item Drawing No

    Volume 2 Section 8  GeneratorManual

    8.1 740MVA T/G INSTRUCTION LIST EKC003097 8.2 740MVA TURBINE GENERATOR DESIGN DATA EKC003098 

    8.3 740MVA GENERATOR STRUCTURE EKC0030998.4  FILLING AND RELEASING OF H2 GAS EKC003087 

    8.5 GAS CONTROL SYSTEM AND SHAFT SEAL OIL SYSTEM EKC003100 

    8.6 OPERATION OF GENERATOR EKC0027008.7  ACTION TO BE TAKEN ON ALARMS FROM GAS CONTROL

    SYSTEM AND SHAFT SEAL OIL SYSTEM EKC003101 8.8 STATOR COOLING WATER SYSTEM EKC003102 8.9 PERIODIC OPERATIONAL INSPECTION AND TESTS EKC002435 

    8.10 PERIODIC INSPECTION CHECK SHEET EKC002382 

    8.11 REGULAR INSPECTION OF HYDROGEN COOLEDTURBINE GENERATOR E1O00069 

    8.12 DRYING THE TURBINE GENERATOR WINDINGS E1O000J7 

    8.13 DIELECTRIC STRENGTH TEST OF TURBINE GENERATORARMATURE WINDINGS EKC002852 

    8.14 MAINTENANCE OF GAS TIGHTNESS AT ROTOR WINDINGLEADS  EKC002433 

    8.15 PREPARATIONS FOR DISASSEMBLY AND REASSEMBLY

    OF GENERATOR E1O000H6 8 16 INSTALLATION AND ASSEMBLY OF GENERATOR EKC003063

  • 8/11/2019 Section08_A4.pdf

    2/806

     P-2 of   2

    M a i n C o n t e n t s - a

    Main Table of ContentsOperation and Maintenance Instruction ManualVolume 2 Maintenance and System Description Manual

    Book No Section No Item Drawing No

    Volume 2 Section 8  GeneratorDrawing 

    8.30 GENERATOR CHARACTERISTIC DATA VA1-TSB-00MKA-E-M1B-DAS-31108.31 740MVA Generator Rating Plate VA1-TSB-00MKA-E-M1B-DLB-3111

    8.32 740MVA GENERATOR OUTLINE VA1-TSB-00MKA-E-M1B-DRD-31008.33 740MVA GENERATOR TERMINAL

    BUSHING ASSEMBLY VA1-TSB-00MKA-E-M1B-DRD-31018.34 DETAIL OF AUX. TERMINAL BOX  VA1-TSB-00MKA-E-M1B-DGA-3109

      8.35 GENERATOR SOLE PLATES & ANCHOR

    BOLTS VA1-TSB-00MKA-E-M1B-DFN-31248.36 ARRANGEMENT OF SOLE PLATE FOR

    740MVA GENERATOR VA1-TSB-00MKA-E-M1B-DRD-3107  8.37 LOCATION OF R.T.D FOR 740MVA

    GENERATOR VA1-TSB-00MKA-E-M1B-DGA-3108  8.38 DIAGRAM OF GAS CONTROL SYSTEM VA1-TSB-00MKG-E-M1B-PFD-3113

    8.39 DIAGRAM OF SHAFT SEAL OIL SYSTEM VA1-TSB-00MKW-E-M1B-PFD-31148.40 DIAGRAM OF STATOR COOLING WATER

    SYSTEM VA1-TSB-00MKF-E-M1B-PFD-31128.41 DESIGN OUTLINE OF GENERATOR VENT

    TO ATMOSPHERE VA1-TSB-00MKA-E-M1B-DRD-31058.42 SPECIFICATION OF TEMPERATURE GAUGE VA1-TSB-00MAY-I-M1B-SPC-55308.43 INSTRUMENT LIST ***VA1-TSB-00MAY-I-M1B-SPC-55758 44 OUTLINE OF 740MVA GENERATOR NEUTRAL

  • 8/11/2019 Section08_A4.pdf

    3/806

  • 8/11/2019 Section08_A4.pdf

    4/806

  • 8/11/2019 Section08_A4.pdf

    5/806

  • 8/11/2019 Section08_A4.pdf

    6/806

  • 8/11/2019 Section08_A4.pdf

    7/806

  • 8/11/2019 Section08_A4.pdf

    8/806

     

    1 11

    E KC0 0 3 0 9 8 - a

    Vi e t n a m Li l a ma Co r p or a t i o n

    740MVA Tur bi ne Gen er at or

     

    De s i gn Da t a

    740MVA Tur bi ne Gene r a t or Des i gn Dat a

  • 8/11/2019 Section08_A4.pdf

    9/806

     

    E KC0 0 3 0 9 8 - a

    2 11 à –¾ • ‘ xpl anat i on

    –¼ Ì TITLE

    740MVA Tur bi ne Gene r at or Des i gn Dat a

    ‹q æ¼ CUSTOMER • F Vi e t na m / Li l a ma Cor p or a t i o n

    Œn ‹ Ší EQ/ SYS. • F 740MVA Tur bi ne Gene r at or

    »”Ô JOB • F M231001 , M231002 RT 2201

    ƒvƒ‰“ƒg PROJECT • F   VVA1 , VVA2

  • 8/11/2019 Section08_A4.pdf

    10/806

     

    E KC0 0 3 0 9 8 - a

    3 11à –¾ • ‘ Expl anat i on

    1.  General···························································································································· 4 

    2 Rating

    ······························································································································

    2.1. 

    Generator ··············································································································4 

    3 Characteristic Curves ··································································································· 5 

    3.1. Estimated Saturation and Synchronous Impedance Curves ································5 

    3.2. Estimated “V” Curves ·························································································6 

    3.3. 

    Estimated Reactive Capability Curves ·································································7 

    4 Auxiliary System ··············································································································· 8

     

    4.1. 

    Gas Control System······························································································8 

    4.2. 

    Gas Cooling System ·····························································································8 

    4.3. 

    Shaft Sealing System····························································································9 

    4.4.  Stator Cooling Water System ···············································································9 

    4.5.  Generator Unbalanced Load Capability ·······························································9 

  • 8/11/2019 Section08_A4.pdf

    11/806

     

    E KC0 0 3 0 9 8 - a

    4 11à –¾ • ‘ Expl anat i on

    1 General

    This instruction manual gives overall data and descriptions of 740,000kVA generator and its auxiliary

    units.

    The rated electrical power output of generator is 629,000kW at a power factor of 0.85 lagging. The

    generator is mechanically driven by its associated steam turbine, electrically excited by the static thyristor

    rectifier excitation system and internally cooled by hydrogen gas.

    2 Rating

    2 1 Generator

    Rating: TAKS-2P-740,000kVA-3000rpm-LCH-26,000V-16,433A-50Hz-0.85PF-0.52MPag

    (a) Cold gas temperature (Outlet of H2 coolers): 46 • Ž

    (b) Alarm temperature of cold gas temp. high: 48 • Ž

  • 8/11/2019 Section08_A4.pdf

    12/806

     

    E KC0 0 3 0 9 8 - a

    5 11à –¾ • ‘ Expl anat i on

    3 Characteristic Curves

    3 1 Estimated Saturation and Synchronous Impedance Curves

    0.52MPag

  • 8/11/2019 Section08_A4.pdf

    13/806

     

    E KC0 0 3 0 9 8 - a

    6 11à –¾ • ‘ Expl anat i on

    3 2 Estimated V

     

    Curves

    0. 52MPag

  • 8/11/2019 Section08_A4.pdf

    14/806

     

    E KC0 0 3 0 9 8 - a

    7 11à –¾ • ‘ Expl anat i on

    3 3 Estimated Reactive Capability Curves

    0. 52MPag

  • 8/11/2019 Section08_A4.pdf

    15/806

     

    E KC0 0 3 0 9 8 - a

    8 11à –¾ • ‘ Expl anat i on

    4 Auxiliary System

    4 1 Gas Control System

    (a)  Amount of gas space in generator casing: 115 m3 

    (b)  Amount of carbon dioxide required for removing air from casing

    (Generator at standstill or low speed): 175 m3 

    (c)  Amount of carbon dioxide required for removing hydrogen from casing

    (Generator at standstill or low speed): 230 m3 

    (d)  Amount of hydrogen required for filling casing to 90 percent purity

    at the atmospheric pressure (Generator at standstill): 230 m3 

    (e)  Amount of hydrogen required for increasing pressure in casing

    from 0 to 0.52MPag: 600 m3 

    (f) Mi i i f li d h d 99 %

  • 8/11/2019 Section08_A4.pdf

    16/806

     

    E KC0 0 3 0 9 8 - a

    9 11à –¾ • ‘ Expl anat i on

    4 3 Shaft Sealing System

    (a) Maximum oil flow to shaft seals in normal operation at 0.52MPag: 195 L/min

    (b) Gas side oil flow in the above: 20 L/min

    (c) Differential between seal oil and hydrogen pressure: 50 kPa

    (d) Alarm of the above differential pressure low: 30 kPa

    (e) Alarm of filter differential pressure high: 20 kPa

    4 4 Stator Cooling Water System

    (a) Water flow through stator winding: 980 L/min

    (b) Cooling water inlet temperature: 46 • Ž

    (c) Alarm temperature of stator winding temp. high: 10 • Žabove temperature

    at full load

  • 8/11/2019 Section08_A4.pdf

    17/806

     

    E KC0 0 3 0 9 8 - a

    10 11à –¾ • ‘ Expl anat i on

    This page is intentionally blanked.

  • 8/11/2019 Section08_A4.pdf

    18/806

     

    E KC0 0 3 0 9 8 - a

    11 11à –¾ • ‘ Expl anat i on

    Œo —ð • ‘

    Re vi s i on Hi s t or y( f or i nt e r n a l u s e )

    Ï X

    REV.  PAGE 

    Ï X‰Ó Š‹y ‚Ñ “à —e

    CHANGED PLACE AND CONTENT 

    ³”F

     APPROVED

    ’² ¸

    REVIEWED

    ’S “–

    PREPARED

    ‚•   Initial Issue.Written in

    page 2. 

    Written in

    page 2. 

    Written in

    page 2. 

  • 8/11/2019 Section08_A4.pdf

    19/806

     

    1 33

    E KC0 0 3 0 9 9 - a

    Vi e t n a m Li l a ma Co r p or a t i o n

    740MVA GENERATOR STRUCTURE

  • 8/11/2019 Section08_A4.pdf

    20/806

     

    E KC0 0 3 0 9 9 - a

    2 33 à –¾ • ‘ xpl anat i on

    –¼ Ì TITLE

    740MVA GENERATOR STRUCTURE

    ‹q æ¼ CUSTOMER • F Vi e t na m / Li l a ma Cor p or a t i o n

    Œn ‹ Ší EQ/ SYS. • F 740MVA Tur bi ne Gene r at or

    »”Ô JOB • F M231001 , M231002 RT 2201

    ƒvƒ‰“ƒg PROJECT • F   VVA1 , VVA2

  • 8/11/2019 Section08_A4.pdf

    21/806

     

    E KC0 0 3 0 9 9 - a

    3 33à –¾ • ‘ Expl anat i on

    Table of Contents

    1. Introduction 5

    2. Precaut ions for Safety

     

    5

    3. Generator Structure

     

    11

    3.1 General ···············································································································11

    3.2 Stator Frame and Stator Core ·············································································12

    3.2.1 Stator Frame ····························································································12

    3.2.2 Spring Mounting······················································································12

    3.2.3 Stator Core·······························································································13

    3.3 Stator Winding (Armature Winding) ·································································15

    3.3.1 Stator Bar and Insulation ·········································································15

    3.3.2 Insulating connection Tube ·····································································16

    3.4 Generator Terminal Plate ···················································································18

  • 8/11/2019 Section08_A4.pdf

    22/806

     

    E KC0 0 3 0 9 9 - a

    4 33à –¾ • ‘ Expl anat i on

    This Page Intentionally Left Blank

  • 8/11/2019 Section08_A4.pdf

    23/806

     

    E KC0 0 3 0 9 9 - a

    5 33à –¾ • ‘ Expl anat i on

    1. Introduction

    This manual is written to ensure safe handling of the 740MVA Generator Structure. Before

    operation, maintenance and inspection, be certain to read this manual for proper use of the

    equipment. This manual should be kept near the equipment so it can be readily referenced.

    2. Precautions for Safety

    Signs and messages in this manual and on the equipment body are important for management,

    operation, maintenance and inspection. They are given to avoid possible injuries and damages

    as well as to ensure correct handling of the equipment. The following signs and short messages

    should thoroughly be understood before reading this manual. It is advised that you also read

    the instruction manuals of related equipment and components.

    IMPORTANT MESSAGES

    Read this manual and follow its instructions. Signal words such as DANGER, WARNING, two kinds of CAUTION,and NOTE, will be followed by important safety information that must be carefully reviewed.

    Indicates an imminently hazardous situation, which will result in death or serious injury if you

    DANGER!

  • 8/11/2019 Section08_A4.pdf

    24/806

     

    E KC0 0 3 0 9 9 - a

    6 33à –¾ • ‘ Expl anat i on

    WARRANTY AND LIMITATION OF LIABILITY

    TOSHIBA CORPORATION AND THE USER’S DIRECT SELLER ACCEPT NO

    LIABILITY FOR ANY INJURY, LOSS OR DAMAGE THAT RESULTS OR MAY

    APPLICATION

    This Toshiba Steam Turbine and Generator Manual does not include all information necessary for every possible

    contingency concerning the installation, operation and maintenance of the Toshiba Steam Turbine and Generator

    Unit.

    Should you require further information about the Toshiba Steam Turbine and Generator Unit or should a particular

    situation arise which is not covered by this Toshiba Steam Turbine and Generator Manual, the matter should be

    referred to Toshiba (contact details are specified at page 2 of this Manual). 

  • 8/11/2019 Section08_A4.pdf

    25/806

     

    E KC0 0 3 0 9 9 - a

    7 33à –¾ • ‘ Expl anat i on

    QUALIFIED PERSONS ONLY

    AS A MINIMUM SAFETY REQUIREMENT, ONLY A “QUALIFIED PERSON” 

    SHOULD INSTALL, OPERATE OR MAINTAIN A TOSHIBA STEAM TURBINE

    AND GENERATOR UNIT. THIS TOSHIBA STEAM TURBINE AND GENERATOR

    MANUAL IS WRITTEN SOLELY FOR USE BY A “QUALIFIED PERSON”.

    ONLY A “QUALIFIED PERSON” SHOULD INSTALL, OPERATE AND MAINTAIN

    THE TOSHIBA STEAM TURBINE AND GENERATOR UNIT IN ACCORDANCE

    WITH ALL APPLICABLE LAWS, REGULATIONS AND SAFETY PROCEDURES.

    TO BE A “QUALIFIED PERSON”, YOU SHOULD HAVE SATISFIED ALL OF THE

    FOLLOWING CRITERIA:

    (1)  YOU MUST HAVE CAREFULLY READ AND UNDERSTOOD THETOSHIBA STEAM TURBINE AND GENERATOR UNIT MANUAL AND ANY

    OTHER MANUALS OF THE ASSOCIATED DEVICES AND COMPONENTS

    OF THE TOSHIBA STEAM TURBINE AND GENERATOR UNIT MANUAL.

    (2)  YOU MUST HAVE RECEIVED TRAINING OFFERED BY TOSHIBA.

    BEFORE YOU INSTALL, OPERATE OR MAINTAIN THE TOSHIBA STEAM

  • 8/11/2019 Section08_A4.pdf

    26/806

     

    E KC0 0 3 0 9 9 - a

    8 33à –¾ • ‘ Expl anat i on

    SAFETY SIGN

    (1) To ensure safety, all the SAFETY SIGNS (including DANGER LABELS, WARNING LABELS, CAUTION

    LABELS and NOTE LABELS) must be read and understood

    (2) All the SAFETY SIGNS (including DANGER LABELS, WARNING LABELS, CAUTION LABELS and NOTE

    LABELS) must be kept in such condition that they can be easily seen. They must be clear enough to be

    clearly visible and never be removed or blocked from view. 

  • 8/11/2019 Section08_A4.pdf

    27/806

     

    E KC0 0 3 0 9 9 - a

    9 33à –¾ • ‘ Expl anat i on

    ■  When the rotor extracted from, or inserted into the stator, be sure to

    protect the inner walls of the stator core from damage.

    If the punchings are burred or shorted together at the tooth tips, this would permit circulating currents,induced by the magnetic flux in the core, resulting in a hot spot and possible damage to the core.

    CAUTION

  • 8/11/2019 Section08_A4.pdf

    28/806

     

    E KC0 0 3 0 9 9 - a

    10 33à –¾ • ‘ Expl anat i on

    This Page Intentionally Left Blank

  • 8/11/2019 Section08_A4.pdf

    29/806

     

    E KC0 0 3 0 9 9 - a

    11 33à –¾ • ‘ Expl anat i on

    3. Generator Structure

    3.1 General

    The generator is completely enclosed and, in operation uses hydrogen gas as the cooling

    medium. The ventilation system including the fans and gas coolers is self-contained andcompletely enclosed to prevent entrance of dirt and moisture. Stator winding is directly cooled

     by demineralized water and rotor winding are directly cooled with the hydrogen gas.

    The generator casing is substantially cylindrical in shape and of welded gastight construction.

    The outer end shields at either end of the casing are also of welded gastight construction and

    support the generator bearings and shaft sealing devices. The generator casing and outer end

    shields are of the explosion-proof type.

    The stator core is supported by spring plates in the stator frame to isolate core vibration. The

    rotor is of the gap pickup direct cooling type. Both ends of the rotor pass through the end

    shields, and shaft seals are used to prevent hydrogen gas leakage. The generator is designed

    for continuous operation and is constructed to withstand a sudden change in load and

    three-phase shortcircuit. Various kinds of supervising and controlling instruments are provided

    for keeping the generator in satisfactory operation.

    Accessories include a gas control device, a cooling water control device for controlling the gas

    temperature inside the generator as well as supervising and controlling device, and various

  • 8/11/2019 Section08_A4.pdf

    30/806

  • 8/11/2019 Section08_A4.pdf

    31/806

  • 8/11/2019 Section08_A4.pdf

    32/806

     

    E KC0 0 3 0 9 9 - a

    14 33à –¾ • ‘ Expl anat i on

  • 8/11/2019 Section08_A4.pdf

    33/806

     

    E KC0 0 3 0 9 9 - a

    15 33à –¾ • ‘ Expl anat i on

    3.3 Stator Winding Armature Winding)

    3.3.1 Stator Bar and Insulation

    The stator winding is formed by insulated bars assembled in the slots of the stator core, jointed

    at the ends to form coils, and connected to the proper phase belts by bus rings.

    The stator bars shown in Fig.4 are composed of insulated copper strands arranged in the formof rectangular bars. As shown in Fig.3, each strand is so assembled that it occupies, for an

    equal length of the bar, every radial position in the bar, which is accomplished by a spiral

     progression of each strand around the bar, called “Reobel”  transposition. This arrangementavoids eddy current losses under load conditions which would otherwise be caused by the

    self-inductive magnetic flux distribution in the coil slot.

    Required numbers of mica tapes are applied half lapped on the molded strands by using

    automatic taping machine with constant tension device. After taping, stator bars are treated byvacuum to remove bubbles included in the bar insulation. Finally, the bars are molded into

    required form. The peripheral parts of the insulator in the slot are coated with a semi-conductivecorona-inhibitive material, and the portion of the bar just outside the slot is protected with a

    corona-inhibitive tape.

    The end portions of stator windings are securely laced with glass cord to the binding bands,which are molded polyester-glass rings supported with end flanges through the binding band

    supports. These supports are made from non magnetic steel and insulated.

  • 8/11/2019 Section08_A4.pdf

    34/806

     

    E KC0 0 3 0 9 9 - a

    16 33à –¾ • ‘ Expl anat i on

  • 8/11/2019 Section08_A4.pdf

    35/806

     

    E KC0 0 3 0 9 9 - a

    17 33à –¾ • ‘ Expl anat i on

  • 8/11/2019 Section08_A4.pdf

    36/806

     

    E KC0 0 3 0 9 9 - a

    18 33à –¾ • ‘ Expl anat i on

    3.4 Generator Terminal Plate

    The main armature leads extend through the bottom of the generator casing and the generator

    terminal plate.

    On this machine, connections are provided at the collector end portion. The terminal plate is

    made from nonmagnetic material to prevent inducted currents from the current flow in the

    armature leads. Drain is located in the terminal plate to prevent accumulation of oil or wateraround the connections. Gaskets are provided between the terminal plate and high-voltage

     bushing flange to prevent hydrogen leakage. (See Fig.6)

  • 8/11/2019 Section08_A4.pdf

    37/806

     

    E KC0 0 3 0 9 9 - a

    19 33à –¾ • ‘ Expl anat i on

    3.5 High-voltage Bushing and Current Transformer

    The armature connections extend through the terminal plate by means of gas-tight, porcelain

    insulated high-voltage bushings.

    Site assembly of the bushings, armature leads in the terminal box, and covering of the

    associated joints are accomplished after stator frame on base.

    Mounting arrangement of the bushings is shown in Fig.7. Shows the assembly of a

     bushing-type current transformer. The bushing type current transformer is mounted as enclosing

    the terminal bushing and is used to measure generator output current and to protect and control

    the generator. The bushing type current transformer is fastened to the terminal plate with studs.

     

  • 8/11/2019 Section08_A4.pdf

    38/806

    E KC0 0 3 0 9 9 - a

    20 33à –¾ • ‘ Expl anat i on

    3.6 Rotor

    3.6.1 Rotor Assembly

    The rotor shaft is machined from a solid forging of Ni-Cr-Mo-V alloy steel. It’s quality has

     been corroborated by mechanical, chemical, and metallurgical inspection and non-destructive

    testing. The rotor core is slotted to accommodate rotor coils, and the rotor coils are secured in position with wedges that stand the centrifugal force of the coils.

    As shown in Fig.8, the rotor pole portions are provided with semi-circular-shaped grooves

    (cross slot) in the right angle direction to the rotor shaft axis for the purpose of equalizing therigidity in the magnetic pole direction and the right angle direction to it. The rotor pole, fan

     bosses and collector fan can be fitted with balance weights to reduce rotor vibration. The

    coupling and fan boss on turbine end are machined from the rotor shaft. The collector end fan boss is made of a shrink-fit forging of alloy steel. The axial flow fan, with wing-shaped blades,

    is made of high-strength aluminum alloy and is engaged and bolted to the fan boss.

     

  • 8/11/2019 Section08_A4.pdf

    39/806

    E KC0 0 3 0 9 9 - a

    21 33à –¾ • ‘ Expl anat i on

    3.6.2 Rotor Winding Field Winding) and Retaining Ring

    The rotor conductors are machined to provide gas ducts, formed into shape, and put into the

    slots in the rotor core. Fiber reinforced insulator is used for layer insulation and for the slot

    insulation. A creepage block of fiber-glass-reinforced insulator, capable of withstanding the

    centrifugal force of the conductor, is seated between the top of the conductor and the rotor

    wedge to ensure a high insulation resistance to ground. Glass-base insulating blocks are set between coils to check the displacement of rotor end windings due to thermal stress and

    centrifugal force. In addition, the end windings are supported with retaining rings shrink-fitted

    on the core end. The retaining ring is secured to the rotor with an retaining ring key. A

    glass-base annular insulator is set between retaining ring and the top of the coils for isolation

    from the ground. The retaining ring is made of nonmagnetic Mn-Cr alloy steel with high

    mechanical strength.

    The rotor core and retaining ring are brought in direct contact with each other, and to flow

    current in between in case of an unbalanced load or a sudden short-circuit fault. To reduce theeffect of this current, the engagement between the retaining ring and rotor shaft is metallized for

    a reduced contact resistance. An amortisseur is provided under the retaining ring and the rotor

    end wedge. Fig.9 shows arrangement of the retaining ring.

    Fig.10 shows the arrangement of rotor winding.

  • 8/11/2019 Section08_A4.pdf

    40/806

    P r  o pr i   e t   ar  y I  n

    f   or m a t  i   on

     © T  o s h i   b  a C  or  p or  a t  i   on2  0 1 1  ,A l  l  Ri   gh  t   s 

    R e s  er v  e d 

    Wedge

    Rotation

    Suction hole

    Layer insulation

    Wedge

    Suction hol

    Rotor wed e

    Creepage block

    Sucton hole

    Rotation

    F

    g

    1

    A

    A

    M

    N

    O

    T

    H

    R

    O

    O

    W

    N

    N

     

  • 8/11/2019 Section08_A4.pdf

    41/806

    E KC0 0 3 0 9 9 - a

    23 33à –¾ • ‘ Expl anat i on

    3.7 Outer End Shield and Bearing

    Fig.11 shows the outer end shield and bearing.

  • 8/11/2019 Section08_A4.pdf

    42/806

     

  • 8/11/2019 Section08_A4.pdf

    43/806

    E KC0 0 3 0 9 9 - a

    25 33à –¾ • ‘ Expl anat i on

     

  • 8/11/2019 Section08_A4.pdf

    44/806

    E KC0 0 3 0 9 9 - a

    26 33à –¾ • ‘ Expl anat i on

    3.8 Shaft Sealing Device

    A shaft sealing device is installed inside the machine to come inside of the bearing, and is used

    to prevent hydrogen gas leaking from the machine through the shaft penetrant part.

    Fig.13 shows the general assembly of the shaft sealing device. The seal casing has two seal

    rings, and is mounted on the outer end shield. The collector end seal casing is split into inner and

    outer halves; an insulating plate is provided between the inner and outer halves, and anotherinsulating plate is provided between the outer half casing and the outer end shield. These

    insulating plates serve to prevent shaft current.

    Fig.14 shows the seal ring and the flow of sealing oil. There are two seal rings of inner

    (hydrogen side) and outer (air side) ring. The seal ring which is divided into two half-circles is

    supported with upper and lower springs to follow the movement of the rotor shaft, and is

    designed to ensure the continuity of oil film.

    The seal ring is always supplied with sealing oil which is 50kPa  higher than the insidehydrogen gas pressure. The sealing oil passes through the gap between the seal ring and shaft,

    and is drained dividing into the hydrogen side and air side.

     

  • 8/11/2019 Section08_A4.pdf

    45/806

    E KC0 0 3 0 9 9 - a

    27 33à –¾ • ‘ Expl anat i on

     

  • 8/11/2019 Section08_A4.pdf

    46/806

    E KC0 0 3 0 9 9 - a

    28 33à –¾ • ‘ Expl anat i on

    3.9 Collector and Brush

    The brushes and collector rings are ventilated by an open circuit system in which the cooling

    air is circulated through the air filter mounted on the air inlet.

    The cooling air is sucked in from the air feed port of the operation floor and is discharged out

    of the vent port of the collector cover

    3.9.1 Collector Ring

    The collector rings consist of negative and positive poles, which are made of high quality alloy

    steel and shrunk onto insulated shaft.

    As illustrated in Fig.15, the outer surface of the collector ring has spiral grooves for cooling

    and removal of dust. The collector ring has axial holes for cooling ventilation and is fitted with a

    shaft mounted fan between both rings for reducing temperature rise caused by excitation current.

     

    E KC0 0 3 0 9 9

  • 8/11/2019 Section08_A4.pdf

    47/806

    E KC0 0 3 0 9 9 - a

    29 33à –¾ • ‘ Expl anat i on

    3.9.2 Brush and Brush Holder

    The rotor winding of the generator is directly cooled. Its exciting current is large and

    necessitates large-capacity collector rings and a number of brushes.

    As illustrated in Fig.16, the brush holder is of the magazine type, capable of attaching and

    detaching four brushes en bloc. All brush holders are circumferentially arranged. By turning the

    handle 90 • ‹, brush holders can be attached or detached to the brush holder receiver.Accordingly, in-service brush inspection and replacement can be carried out safely.

    The brush for the generator is made of natural graphite, and has low friction and high

    self-lubricating characteristic. The brush is fitted with a pigtail wire having a crimp-style

    terminal on its end.

    The constant-pressure spring in the brush holder forces the brush in the racial direction, and

    the brush needs no pressure adjustment as it wears.

     

    E KC0 0 3 0 9 9

  • 8/11/2019 Section08_A4.pdf

    48/806

    E KC0 0 3 0 9 9 - a

    30 33à –¾ • ‘ Expl anat i on

    3.10 Hydrogen Gas Cooler

    Four gas coolers are installed upright in the four corners of the stator frame. They use cooling

    water to remove heat from hydrogen gas that is heated while being circulated within the

    generator. Fig.17 shows installation of a typical, vertical-type, hydrogen gas cooler. The

    hydrogen gas cooler is composed of a heat exchange section having a bundle of copper alloy

    finned tubes, upper and lower tube sheets holding the upper and lower ends of the tube bundle,

    and upper and lower water boxes.

    Heat exchange between the cooling water and hydrogen gas is carried out by the counter-flow

    system. Hot hydrogen gas enters the cooler from the cooling water drain side, and the cooled

    hydrogen gas leaves the cooler from the cooling water supply side.

    That part of the hydrogen gas cooler which passes through the stator frame is totally sealed to

     prevent hydrogen gas leaking from the machine. At the lower part, a gland packing type seal is

    used which is slidable to absorb the expansion and contraction of the cooler due to temperature

    change.

  • 8/11/2019 Section08_A4.pdf

    49/806

    P r  o pr i   e t   ar  y I  n

    f   or m a t  i   on

     © T  o s h i   b  a C  o

    r  p or  a t  i   on2  0 1 1  ,A l  l  Ri   gh  t   s 

    R e s  er v  e d 

    F

    G

    1

    1

    G

    N

    R

    A

    O

    S

    C

    O

    D

    A

    W

    N

  • 8/11/2019 Section08_A4.pdf

    50/806

    P r  o pr i   e t   ar  y I  n

    f   or m a t  i   on

     © T  o s h i   b  a C  o

    r  p or  a t  i   on2  0 1 1  ,A l  l  Ri   gh  t   s 

    R e s  er v  e d 

    F

    G

    1

    2G

    N

    R

    A

    O

    S

    C

    O

    D

    A

    W

    N

     

     

    E KC0 0 3 0 9 9 - aŒo —ð • ‘

  • 8/11/2019 Section08_A4.pdf

    51/806

    E KC0 0 3 0 9 9 - a

    33 33à –¾ • ‘ Expl anat i onRevision History (for internal use) 

    Ï X

    REV.  PAGE 

    Ï X‰Ó Š‹y ‚Ñ “à —e

    CHANGED PLACE AND CONTENT 

    ³”F

     APPROVED

    ’² ¸

    REVIEWED

    ’S “–

    PREPARED

    ‚•   ‰ ”Å INITIAL ISSUEDWritten in

    page 2. 

    Written in

    page 2. 

    Written in

    page 2. 

  • 8/11/2019 Section08_A4.pdf

    52/806

  • 8/11/2019 Section08_A4.pdf

    53/806

  • 8/11/2019 Section08_A4.pdf

    54/806

  • 8/11/2019 Section08_A4.pdf

    55/806

  • 8/11/2019 Section08_A4.pdf

    56/806

  • 8/11/2019 Section08_A4.pdf

    57/806

  • 8/11/2019 Section08_A4.pdf

    58/806

  • 8/11/2019 Section08_A4.pdf

    59/806

  • 8/11/2019 Section08_A4.pdf

    60/806

  • 8/11/2019 Section08_A4.pdf

    61/806

  • 8/11/2019 Section08_A4.pdf

    62/806

  • 8/11/2019 Section08_A4.pdf

    63/806

  • 8/11/2019 Section08_A4.pdf

    64/806

  • 8/11/2019 Section08_A4.pdf

    65/806

  • 8/11/2019 Section08_A4.pdf

    66/806

  • 8/11/2019 Section08_A4.pdf

    67/806

  • 8/11/2019 Section08_A4.pdf

    68/806

  • 8/11/2019 Section08_A4.pdf

    69/806

  • 8/11/2019 Section08_A4.pdf

    70/806

  • 8/11/2019 Section08_A4.pdf

    71/806

  • 8/11/2019 Section08_A4.pdf

    72/806

  • 8/11/2019 Section08_A4.pdf

    73/806

  • 8/11/2019 Section08_A4.pdf

    74/806

  • 8/11/2019 Section08_A4.pdf

    75/806

     1 of 22

    E K C 0 0 3 1 0 0 - a

  • 8/11/2019 Section08_A4.pdf

    76/806

    Vi etnam Li l ama Corporat i on

    740MVA Turbi ne Generat or

     

    Gas Cont rol Syst emAnd Shaf t Seal O l Syst em

    I nst ruct i on Manual

      2 of 22

    E K C 0 0 3 1 0 0 - a

  • 8/11/2019 Section08_A4.pdf

    77/806

     –¼• Ì TITLE

    Ga s Cont r o l Sys t e m And Sha f t Se a l Oi l Sys t e m 

    ‹q æ¼ CUSTOMER • F Li l ama Cor por a t i on

    Œn ‹ Ší EQ/ SYS. • F 740MVA Tur bi ne Gene r at or

    »”Ô J OB • F M231001, M231002, RT 2201

    ƒvƒ‰ƒ“ ƒg PROJ ECT • F VVA1, VVA2,

     

    3  of   22

    E K C 0 0 3 1 0 0 - a

  • 8/11/2019 Section08_A4.pdf

    78/806

    Table of Contents

    Table of Contents·················································································································· 3 

    1.  Introduction··················································································································· 5 

    2.  Precautions for Safety··································································································· 5 

    3.  Scope ····························································································································· 11 

    4. 

    Related Documents······································································································ 11 

    5.  Explanation of Shaft Seal Oil System ······································································· 11 

    5.1  Shaft Seal Oil Circuit ·························································································11 

    5.2  Measuring Shaft Seal Oil Amount ·····································································16 

    5.3 

    Units Disconnection from System ·····································································17 

    6.  Explanation of Gas Control System·········································································· 19 

    6.1 

    Continuous Scavenging······················································································19 

    6.2  Hydrogen-Gas Purity ·························································································19 

    6.3 

    Hydrogen-Gas Pressure······················································································20 

    7.  Alarm Lists··················································································································· 21 

     E  K  C  0  0  3  1 0 0  –  a

    4 of 22

  • 8/11/2019 Section08_A4.pdf

    79/806

  • 8/11/2019 Section08_A4.pdf

    80/806

     E  K  C  0  0  3  1 0 0  –  a

    6 of 22

  • 8/11/2019 Section08_A4.pdf

    81/806

    WARRANTY AND LIMITATION OF LIABILITY

    TOSHIBA CORPORATION AND THE USER’S DIRECT SELLER ACCEPT NO

    LIABILITY FOR ANY INJURY, LOSS OR DAMAGE THAT RESULTS OR MAY

    RESULT FROM ANY FAILURE TO OBSERVE THE PROCEDURES,

    INSTRUCTIONS, WARNINGS, DESCRIPTIONS, DATA AND INFORMATION

    APPLICATION

    This Toshiba Steam Turbine and Generator Manual does not include all information necessary for every possible

    contingency concerning the installation, operation and maintenance of the Toshiba Steam Turbine and Generator

    Unit.

    Should you require further information about the Toshiba Steam Turbine and Generator Unit or should a particular

    situation arise which is not covered by this Toshiba Steam Turbine and Generator Manual, the matter should bereferred to Toshiba (contact details are specified at page 4 of this Manual). 

     E K C 0 0 3 1 0 0  –  a 

    7  of   22

  • 8/11/2019 Section08_A4.pdf

    82/806

     QUALIFIED PERSONS ONLY

    AS A MINIMUM SAFETY REQUIREMENT, ONLY A “QUALIFIED PERSON” 

    SHOULD INSTALL, OPERATE OR MAINTAIN A TOSHIBA STEAM TURBINE

    AND GENERATOR UNIT. THIS TOSHIBA STEAM TURBINE AND GENERATOR

    MANUAL IS WRITTEN SOLELY FOR USE BY A “QUALIFIED PERSON”.

    ONLY A “QUALIFIED PERSON”  SHOULD INSTALL, OPERATE AND

    MAINTAIN THE TOSHIBA STEAM TURBINE AND GENERATOR UNIT IN

    ACCORDANCE WITH ALL APPLICABLE LAWS, REGULATIONS AND SAFETYPROCEDURES.

    TO BE A “QUALIFIED PERSON”, YOU SHOULD HAVE SATISFIED ALL OF

    THE FOLLOWING CRITERIA:

    (1)  YOU MUST HAVE CAREFULLY READ AND UNDERSTOOD THE

    TOSHIBA STEAM TURBINE AND GENERATOR UNIT MANUAL AND ANY

    OTHER MANUALS OF THE ASSOCIATED DEVICES AND COMPONENTS

    OF THE TOSHIBA STEAM TURBINE AND GENERATOR UNIT MANUAL.

    (2)  YOU MUST HAVE RECEIVED TRAINING OFFERED BY TOSHIBA.

    BEFORE YOU INSTALL, OPERATE OR MAINTAIN THE TOSHIBA STEAM

    TURBINE AND GENERATOR UNIT, YOU MUST HAVE BEEN SO

    AUTHORIZED BY THE PURCHASER

     E  K  C  0  0  3  1 0 0  –  a

    8 of 22

  • 8/11/2019 Section08_A4.pdf

    83/806

    SAFETY SIGN

    (1) To ensure safety, all the SAFETY SIGNS (including DANGER LABELS, WARNING LABELS, CAUTION

    LABELS and NOTE LABELS) must be read and understood

    (2) All the SAFETY SIGNS (including DANGER LABELS, WARNING LABELS, CAUTION LABELS and NOTE

    LABELS) must be kept in such condition that they can be easily seen. They must be clear enough to be

    clearly visible and never be removed or blocked from view. 

     E K C 0 0 3 1 0 0  –  a 

    9  of   22

  • 8/11/2019 Section08_A4.pdf

    84/806

     

    ■  In case the main seal oil pump and emergency seal oil pump cannot

    be operated, lower the hydrogen-gas pressure in the generator

    casing below 50kPag.

    Hydrogen gas may leak and an explosion may potentially result.

    ■  In case supply pressure of shaft seal oil cannot be maintained,

    dissociate and shut down the generator, release hydrogen gas in the

    generator casing through the release pipe and lower the hydrogen-

    gas pressure to atmospheric pressure. And fill carbon dioxide in the

    generator casing.

    Hydrogen-gas pressure is lowered, or hydrogen gas may leak and an explosion may potentially result.

    ■Always assume the by-pass valve of the float-trap to be closed.

    Confirm hydrogen gas pressure in the generator is less than 10kPag

    when you open the by-pass valve, and observe continuously so that

    the oil level should not fall more than the center of level gauge.

    Hydrogen gas may leak through the by-pass valve, air detraining section, oil drain pipe and outer oil

    DANGER!

     E  K  C  0  0  3  1 0 0  –  a

    10 of 22

  • 8/11/2019 Section08_A4.pdf

    85/806

    ■  In case the DC power to the pump motor cannot be supplied, makepreparation to lower gas pressure in the generator casing by

    isolating the generator load and releasing hydrogen gas.

     An accident involving generator damage may result.

    ■  Keep pressure in the generator is more than 10kPag while shaft seal

    oil system is operating.

    Oil drain flow may be bad and the oil leakage to inside of generator may result.

    ■  Do not allow unauthorized persons to enter your working area.

    Clarify your off limits area by loping and displaying such as [Keep out].

    Moving parts cause deaths or serious injuries.

    ■  Confirm grounding of your equipment before conducting a test.

    Electric leakage or failure of your equipment causes a fire or an electric shock.

    ■  Prepare a stable scaffold and fall prevention & personal protective

    equipment when working at an elevated place.

    ARNING!

     E K C 0 0 3 1 0 0  –  a 

    11  of   22

  • 8/11/2019 Section08_A4.pdf

    86/806

    3.  Scope

    This manual describes the method to operate the gas and shaft seal oil systems of the hydrogen-

    cooled turbine generator.

    4.  Related DocumentsRefer to the system diagrams of the shaft seal oil system and gas system for use as system

    diagrams in operating the generator under this manual.

    Refer to the instructions EKC003087 “Instruction Manual for Filling and Releasing of H2 Gas” for filling and releasing hydrogen gas in the generator casing.

    Refer to the instructions EKC003101 “Instruction Manual for Action to be Taken on Alarms

    from Gas Control System and Shaft Seal Oil System” on actions to be taken on alarms.

    5. Explanation of Shaft Seal Oil System

    5.1 Shaft Seal Oil CircuitDepending on operational condition of the pumps in the bearing lubricating oil system and shaft

    seal oil system of the turbine generator, the circuits for shaft seal oil are divided as follows.

    a. Normal Operation

    In normal operation, receiving oil cooled to a predetermined temperature from the bearing

    lubricating oil system of the turbine generator as illustrated below, the shaft seal oil system

     E  K  C  0  0  3  1 0 0  –  a

    12 of 22

  • 8/11/2019 Section08_A4.pdf

    87/806

    The supply pressure of shaft seal oil is monitored by the pressure gauge and by differential-

     pressure gauge. During generator operation, supply pressure for shaft seal oil is always adjusted

    50kPag higher than the generator casing pressure. Therefore, the supply pressure for shaft seal

    oil also will be automatically adjusted in accordance with variations in generator casing

     pressure.

     b.  Emergency Shaft Seal Oil Circuit

    (a) When Emergency Seal Oil Pump is Running

    In case the main seal oil pump cannot be operated, the emergency seal oil pump will actuate

    automatically and the oil will be fed to the shaft seals.

    ■  In case the DC power to the pump motor cannot be supplied, make

    preparation to lower gas pressure in the generator casing byisolating the generator load and releasing hydrogen gas.

     An accident involving generator damage may result.

    Turbine-Lube Oil Tank Oil CoolerTurbine- Lube Oil Pump Emergency Seal Oil Pump

    DANGER!

     E K C 0 0 3 1 0 0  –  a 

    13  of   22

  • 8/11/2019 Section08_A4.pdf

    88/806

     

    ■  In case the main seal oil pump and emergency seal oil pump cannot

    be operated, lower the hydrogen-gas pressure in the generator

    casing below 50kPag.

    Hydrogen gas may leak and an explosion may potentially result.

    In case the main seal oil pump and emergency seal oil pump cannot be operated, the generator

    will be operated at supply oil pressure from the bearing lubricating oil system. During this

    operation, hydrogen gas will be sealed by supply oil pressure of the bearing lubricating oil

    system and the hydrogen-gas pressure inside the generator casing has to be lowered below

    50kPag. The oil will be fed to the shaft seals through the differential-pressure regulating valve,

     bypassing the pump.

    Turbine-

    Lube Oil

    Turbine-

    Lube OilOil Differential-Pressure

    Regulating Valve

    Shaft

    S l

    Float-Trap

    Hydrogen

    detraining section

    Air

    detraining

    DANGER!

     E  K  C  0  0  3  1 0 0  –  a

    14 of 22

  • 8/11/2019 Section08_A4.pdf

    89/806

    ‡ When the closed loop circulate operation is carried out at the rated hydrogen gas pressure,

    the operation should not be over 1 hour.

    ‡A When it is necessary to carry out the closed loop circulate operation over 1hour, the

    hydrogen pressure must be lowered under 50kpag beforehand.

    ‡B  Monitor continuously the seal oil temperature on the shaft seal that should be 60ºC or under

    to ensure the hydrogen seal function. In closed loop circuit operation, the temperature of

    the seal oil that does not go through the main oil tank and the oil cooler, have the tendency

    of becoming higher. The temperature should be measured on the return pipe just before the

    float trap with a liquid-in-glass thermometer.

    ‡C  When the main seal oil pump is started at the normal operation, hunting phenomena in the

    Differential-Pressure

    Regulating Valve

    Float

    Trap

    Main

    Seal

    Pump 

    Shaft

    Seals 

    Air

    detraining

    section

    Hydrogen

    detraining

    section

    Relief

    Valve

     E K C 0 0 3 1 0 0  –  a 

    15  of   22

  • 8/11/2019 Section08_A4.pdf

    90/806

     

    ■  Do not operate the main seal oil pump and emergency seal oil pump

    simultaneously on the closed loop circuit (without turbine lube oilsystem).

    If the two pumps are operated simultaneously, temperature of the main seal oil pump may rise due to

    stirring heat caused by a difference in discharge, potentially damaging the pumps.

    ■  In case supply pressure of shaft seal oil cannot be maintained,

    dissociate and shut down the generator, release hydrogen gas in the

    generator casing through the vent pipe and lower the hydrogen-gas

    pressure to atmospheric pressure. And fill carbon dioxide in the

    generator casing.

    Hydrogen-gas pressure is lowered, or hydrogen gas may leak and an explosion may potentially result.

    ■ In case of closed loop circulate operation (without turbine lube oil

    NOTE

    DANGER!

     E  K  C  0  0  3  1 0 0  –  a

    16 of 22

  • 8/11/2019 Section08_A4.pdf

    91/806

    5.2  Measuring Shaft Seal Oil Amount

    ■  Operate in the correct sequence.

    Otherwise oil leakage or other accident may potentially result.

    This section describes the method to measure the amount of shaft seal oil to measure the

    consumption of hydrogen gas.

    a. Total Amount of Seal Oil Supply

    1)  Open Valves x0MKW40AA913 and x0MKW40AA015 installed front/rear of the flow

    meter in the downstream of the differential-pressure regulating valve. Then slowly

    close Valve x0MKW40AA014 by paying attention to the seal differential pressure.

    2)  Measure the amount of supply seal oil on the flow meter and record the supplied

    amount.3)  After finishing measurement, open Valve x0MKW40AA014 and close Valves

    x0MKW40AA913 and x0MKW40AA015 installed front/rear of the flow meter

     b. Hydrogen Side Amount of Seal Oil Supply

    Let us assume that the bypass valve of the float-trap is closed, and that the level of oil in the

    float-trap can be read on the liquid level gauge.

    NOTE

     E K C 0 0 3 1 0 0  –  a 

    17  of   22

  • 8/11/2019 Section08_A4.pdf

    92/806

    5.3  Units Disconnection from System

    ■  Operate in the correct sequence.

    Otherwise oil leakage or other accident may potentially result.

    a. Disconnecting Main Seal Oil Pump and Relief Valve x0MKW40AA602

    1)  Start up the emergency seal oil pump.

    2)  Shut down the main seal oil pump and close its Inlet Valve x0MKW40AA007

    and Outlet Valve x0MKW40AA032 of relief valve. Then close Outlet Valve

    x0MKW40AA704 of the main seal oil pump.

    The generator units can be serviced for checks and repairs after operating as described

    above.

     b. Disconnecting Float-Trap1)  Change the oil level gauge of the float-trap from the float-trap to the bypass tank.

    Close Valves x0MKW30AA003 and x0MKW30AA006. Open Valves

    x0MKW30AA904 and x0MKW30AA905.

    2)  Adjust the opening of Outlet Valve 0MKW30AA002 of the bypass tank and

    stabilize the oil the bypass tank.

    NOTE

     E  K  C  0  0  3  1 0 0  –  a

    18 of 22

  • 8/11/2019 Section08_A4.pdf

    93/806

    c. Disconnecting Differential-Pressure Regulating Valve x0MKW40AA101

    1)  Adjust the opening Bypass Valve x0MKW40AA012 of the differential-pressureregulating valve in accordance with indication on the differential-pressure gauge.

    Adjust to 50kPag in case the differential pressure currently indicated is below

    50kPag. Otherwise adjust between 5k • ` 20kPag higher than the current

    indication.

    2)  Close Outlet Valve x0MKW40AA014 of the differential-pressure regulating

    valve with watching indication on the differential-pressure gauge. Check that

    the differential pressure does not vary.3)  Close Inlet Valve x0MKW40AA011 of the differential-pressure regulating

    valve.

    4)  Close Differential-Pressure Detection Valves x0MKW40AA016 and

    x0MKW40AA017 of the differential-pressure regulating valve.

    The differential-pressure regulating valve can be serviced for checks and repairs after

    operating as described above.

     E K C 0 0 3 1 0 0  –  a 

    19  of   22

  • 8/11/2019 Section08_A4.pdf

    94/806

    6. Explanation of Gas Control System

    6.1 Continuous Scavenging

    A continuous scavenging system is used for this generator as a method to seal a hydrogen

    gas in the generator casing.

    Since the air-contained oil is supplied for the shaft seals from the shaft seal oil system.

    This air is discharged from the oil and mixed to hydrogen gas in the section between inner

    oil deflector and oil seal casing. Therefore the gas in this section must be continuouslyscavenged to prevent lowering hydrogen gas purity. The scavenging flow rate is 6000• `

    10000 cc/min (total of turbine and collector end), from the hydrogen detraining sections at

    turbine and collector end.

    Refer to 5.4.1 Checking Continuous Scavenging Operation in the Instruction Manual for

    Filling and Releasing of H2 Gas (Document No. EKC003087 ).

    6.2 Hydrogen-Gas Purity

    An alarm will be issued in case the purity of hydrogen gas scavenged from the hydrogen

    detraining section lowers to 85% and 80%. During generator operation, gas in the

    hydrogen detraining section is continuously flowed to the transmitter of the purity

    indicator to measure the hydrogen-gas purity.

    The flow rate to the gas purity transmitter is adjusted to about 500 to 1000cc/min by

    needle valves (x0MKG50AA015 and x0MKG50AA016)

     E  K  C  0  0  3  1 0 0  –  a

    20 of 22

  • 8/11/2019 Section08_A4.pdf

    95/806

    6.3 Hydrogen-Gas Pressure

    Hydrogen-gas pressure is monitored by the hydrogen-gas pressure gauge. An alarm is issued when

     pressure varies to normal operating pressure 20kPag. Generally, hydrogen-gas consumption of a

    generator can be expressed by the following formula:

    This means that hydrogen gas inside the generator casing is consumed by the amount of hydrogen

    dissolved in hydrogen side seal oil and of scavenging gas in it even if no hydrogen gas is leaked

    through the gas system of the generator. Normally, hydrogen gas is automatically supplied through

    the hydrogen-gas pressure regulating valve during steady generator operation, and hydrogen-gas

     pressure in the generator casing can be maintained at desired pressure almost constantly. In case quick

     boosting of hydrogen-gas pressure inside the generator casing is needed, hydrogen gas is suppliedthrough the bypass valve of the hydrogen-gas pressure regulating valve as in initial filling.

    A hazard potentially exists if hydrogen-gas pressure inside the generator casing gradually lowers or

    lowers in a short time. Troubleshoot the cause as soon as possible and examine the leakage location.

    The hydrogen-gas pressure inside the generator casing slightly rises or lowers depending on the

    generator hydrogen-gas temperature.

    Consumption = Leakage amount

    Amount of hydrogen

    dissolved in hydrogen

    side seal oil

    + +

    Amount of

    scavenging

    gas

     E K C 0 0 3 1 0 0  –  a 

    21  of   22

  • 8/11/2019 Section08_A4.pdf

    96/806

    7. Alarm Lists

    Periodically test the level switches and pressure switches whether or not alarms function

     properly, for each of the following items:

    Shaft Seal Oil System:

    Item Actuation Value Remarks

    1 Discharge pressure of main

    seal oil pump

    Service pressure -100kPa

    or lower.

    See NOTE 1.

    Emergency seal oil

     pump actuated.

    2 Differential pressure of duplex

    seal oil strainer

    20kPa or higher

    3 Differential pressure of shaft

    seal oil (Supply pressure of

    shaft seal oil : Hydrogen-gas

     pressure inside generator

    casing)

    30kPa or lower

    4 Hydrogen detraining section

    oil level

    ±10mm of sight-gauge

    centerline

    5 Air detraining section oil level -50mm or lower from

    normal level

     E  K  C  0  0  3  1 0 0  –  a

    22 of 22

  • 8/11/2019 Section08_A4.pdf

    97/806

    This Page Intentionally Left Blank

  • 8/11/2019 Section08_A4.pdf

    98/806

  • 8/11/2019 Section08_A4.pdf

    99/806

  • 8/11/2019 Section08_A4.pdf

    100/806

  • 8/11/2019 Section08_A4.pdf

    101/806

  • 8/11/2019 Section08_A4.pdf

    102/806

  • 8/11/2019 Section08_A4.pdf

    103/806

  • 8/11/2019 Section08_A4.pdf

    104/806

  • 8/11/2019 Section08_A4.pdf

    105/806

  • 8/11/2019 Section08_A4.pdf

    106/806

  • 8/11/2019 Section08_A4.pdf

    107/806

  • 8/11/2019 Section08_A4.pdf

    108/806

  • 8/11/2019 Section08_A4.pdf

    109/806

  • 8/11/2019 Section08_A4.pdf

    110/806

  • 8/11/2019 Section08_A4.pdf

    111/806

  • 8/11/2019 Section08_A4.pdf

    112/806

  • 8/11/2019 Section08_A4.pdf

    113/806

  • 8/11/2019 Section08_A4.pdf

    114/806

  • 8/11/2019 Section08_A4.pdf

    115/806

  • 8/11/2019 Section08_A4.pdf

    116/806

  • 8/11/2019 Section08_A4.pdf

    117/806

  • 8/11/2019 Section08_A4.pdf

    118/806

  • 8/11/2019 Section08_A4.pdf

    119/806

  • 8/11/2019 Section08_A4.pdf

    120/806

  • 8/11/2019 Section08_A4.pdf

    121/806

  • 8/11/2019 Section08_A4.pdf

    122/806

  • 8/11/2019 Section08_A4.pdf

    123/806

  • 8/11/2019 Section08_A4.pdf

    124/806

  • 8/11/2019 Section08_A4.pdf

    125/806

  • 8/11/2019 Section08_A4.pdf

    126/806

  • 8/11/2019 Section08_A4.pdf

    127/806

  • 8/11/2019 Section08_A4.pdf

    128/806

  • 8/11/2019 Section08_A4.pdf

    129/806

  • 8/11/2019 Section08_A4.pdf

    130/806

  • 8/11/2019 Section08_A4.pdf

    131/806

  • 8/11/2019 Section08_A4.pdf

    132/806

  • 8/11/2019 Section08_A4.pdf

    133/806

     1 of 38

    E K C 0 0 3 1 0 2 - a

  • 8/11/2019 Section08_A4.pdf

    134/806

    Vi etnam Li l ama Corporat i on

    740MVA Turbi ne Generat or

     

    St at or Cool i ng Wat er Syst em

    I nst ruct i on Manual

      2 of 38

    E C K 0 0 3 1 0 2 - a

     –¼• Ì TITLE

    St a t o r Cool i ng Wa t e r Sys t e m

     

  • 8/11/2019 Section08_A4.pdf

    135/806

    ‹q æ¼ CUSTOMER • F Li l a ma Cor p r a t i on

    Œn ‹ Ší EQ/ SYS. • F 740MVA Tur bi ne Gene r at or

    »”Ô J OB • F M231001, M231002, RT 2201

    ƒvƒ‰ƒ“ ƒg PROJ ECT • F VVA1, VVA2

     

    E K C 0 0 3 0 2 - a

    3  of   38

    Table of Contents

  • 8/11/2019 Section08_A4.pdf

    136/806

    1. Introduction   5

    2. Precautions for Safety  5

    3. Scope   13

    4. Related Documents  13

    5. Description   13

    5.1 Design Data ········································································································13

    5.2 General Description  ··························································································· 14

    6. Operation  21

    6.1 Introduction ········································································································21

    6.2 Operating Procedure  ·························································································· 23

    6.3 Operating Values and Limits  ············································································· 24

    6.4 Alarm Action······································································································25

    6.5 Prestart Valve Status ··························································································28

    7. Maintenance  35

    7 1 Periodic Operation Inspection and Tests····························································35

     E K C 0 0 3 1 0 2 - a

    4 of 38

    This page Intentionally Left Blank

  • 8/11/2019 Section08_A4.pdf

    137/806

    This page Intentionally Left Blank

     

    E K C 0 0 3 0 2 - a

    5  of   38

    1. Introduction

    This manual is written to ensure safe handling of Stator Cooling Water System Before

  • 8/11/2019 Section08_A4.pdf

    138/806

    This manual is written to ensure safe handling of Stator Cooling Water System. Before

    operation, maintenance and inspection, be certain to read this manual for proper use of the

    equipment. This manual should be kept near the equipment so it can be readily referenced.

    2. Precautions for Safety

    Signs and messages in this manual and on the equipment body are important for management,operation, maintenance and inspection. They are given to avoid possible injuries and damages as

    well as to ensure correct handling of the equipment. The following signs and short messages

    should thoroughly be understood before reading this manual. It is advised that you also read theinstruction manuals of related equipment and components.

    IMPORTANT MESSAGES

    Read this manual and follow its instructions. Signal words such as DANGER, WARNING, two kinds of CAUTION,and NOTE, will be followed by important safety information that must be carefully reviewed.

    Indicates an imminently hazardous situation, which will result in death or serious injury if

    you do not follow instructionsDANGER!

     E K C 0 0 3 1 0 2 - a

    6 of 38

    APPLICATION

  • 8/11/2019 Section08_A4.pdf

    139/806

    This Toshiba Steam Turbine and Generator Manual does not include all information necessary for every possible

    contingency concerning the installation, operation and maintenance of the Toshiba Steam Turbine and Generator

    Unit.

    Should you require further information about the Toshiba Steam Turbine and Generator Unit or should a particular

    situation arise which is not covered by this Toshiba Steam Turbine and Generator Manual, the matter should be

    referred to Toshiba (contact details are specified at page 2 of this Manual) 

    WARRANTY AND LIMITATION OF LIABILITY

    TOSHIBA CORPORATION AND THE USER’S DIRECT SELLER ACCEPT NO

    LIABILITY FOR ANY INJURY, LOSS OR DAMAGE THAT RESULTS OR MAY

    RESULT FROM ANY FAILURE TO OBSERVE THE PROCEDURES,

    INSTRUCTIONS, WARNINGS, DESCRIPTIONS, DATA AND INFORMATION

  • 8/11/2019 Section08_A4.pdf

    140/806

     E K C 0 0 3 1 0 2 - a

    8 of 38

    SAFETY SIGN

  • 8/11/2019 Section08_A4.pdf

    141/806

    (1) To ensure safety, all the SAFETY SIGNS (including DANGER LABELS, WARNING LABELS, CAUTION

    LABELS and NOTE LABELS) must be read and understood

    (2) All the SAFETY SIGNS (including DANGER LABELS, WARNING LABELS, CAUTION LABELS and NOTE

    LABELS) must be kept in such condition that they can be easily seen. They must be clear enough to be

    clearly visible and never be removed or blocked from view. 

     

    E K C 0 0 3 0 2 - a

    9  of   38

     

    P i t t d i th t t h i l d It i i d t

    ARNING!

  • 8/11/2019 Section08_A4.pdf

    142/806

    ■  Pump is not operated in the state where is no load. It is required to

    pour in water before operating.

    Pump is damaged.

    ■  Second alarm point (9.9ƒÊ

    S/cm) is very dangerous.

    This value indicates the maximum permissible conductivity.

    If the conductivity has been reached this point, the generator shouldbe tripped.

    ■  The Generator can be run without the Stator Water system in

    operation but output is then limited to 185,000kVA at 0.85pf.

    ■  If Stator Water conductivity reaches the second alarm point of 9.9ƒÊ

    S/cm, the generator should be tripped immediately.

    ■  The second alarm contact is set at 9.9ƒÊS/cm, which indicates the

    maximum permissible conductivity.

    If the conductivity has been reached this point, the generator should

     E K C 0 0 3 1 0 2 - a

    10 of 38

    O t ft ki ll th d f i d l i

    CAUTION!

  • 8/11/2019 Section08_A4.pdf

    143/806

    ■  Operate a pump after making small the degree of opening and closing

    of a pressure regulating valve.

    It becomes the cause which an excessive pressure joins a stator coil and damage produces.

    ■  Make into 60• Ž

    or less temperature of the cooling water which flows

    to deionizer.

    If temperature exceeds 60•Ž  the performance will fall.

    ■  Do not freeze resin.

    Effect will be lost once resin is frozen.

    ■  When not using deionizer, pure water is kept in the state of full of

    water in a tub.

    Dryness of resin reduces the performance.

    ■  When a stator water pump is started, don’t stand by it. Check the

    water level of the storage tank after pump operating. If the water

    level goes on decreasing the pump must be stopped at once The

     

    E K C 0 0 3 0 2 - a

    11  of   38

     

    CAUTION

  • 8/11/2019 Section08_A4.pdf

    144/806

    ■  Set up the no fire zone near the hydrogen vent discharge pipe above

    the roof. Check the existence of water at a “U” seal pipe of the vent

    pipe near the storage tank.

    If water does not exist in “U” seal pipe, hydrogen gas may be spread in a building and a fire and explosion

    may occur. Moreover air flows into the tank and degrades the electrical conductivity of cooling water.

    ■  When the differential pressure increases to 0.09MPa, must be replace

    the filter elements.

    Only use manufacturer recommended filter elements. 

    ■  Keep the following matters, when you exchange filters.

    ‡ Filter element exchanges total.‡AWash a filter

    ‡B

    Air vent valve is opened, and water is poured into the tub,

    extracting the air contained in the filter. Then drain valve is

    opened and water is discharged.

     E K C 0 0 3 1 0 2 - a

    12 of 38

    ■ Since make up water could initially contain metal oxides etc it

    NOTE

  • 8/11/2019 Section08_A4.pdf

    145/806

    ■  Since make-up water could initially contain metal oxides, etc., it

    should be drained until clear before being fed through the filter to the

    storage tank. 

    ■  The amberlite IRN-150 is based on the resin being of the gel type and

    having a matrix structure of styrene-divinyl benzene, and contains

    copper.When you abolish it, please follow your regulations. 

     

    E K C 0 0 3 0 2 - a

    13  of   38

    3. Scope

    This manual describes the method of operate the stator cooling water systems of the watercooled turbine generator

  • 8/11/2019 Section08_A4.pdf

    146/806

    cooled turbine generator.

    4.  Related Documents

    Refer to the Diagram of Stator Cooling Water System : 1KC003727.

    5. Description

    5.1 Design Data

    Stator cooling water pump : 2920rpm, 1200 /min

    Stator cooling water pump motor : 2920rpm, 30kW

    Stator cooling water

    Rated inlet pressure : Higher than 0.16MPa

    Low inlet pressure alarm : set at site at equivalent flow rate 880 /min

    x0MKF40CP104 (at x0MKF30AA851 Valve)

     E K C 0 0 3 1 0 2 - a

    14 of 38

    5.2 General Description

  • 8/11/2019 Section08_A4.pdf

    147/806

    5.2.1 Outline of Stator Winding Cooling Water System

    Stator winding cooling system is designed to maintain temperature rise of the stator winding

    suitably, and conductivity of the cooling water low. The cooling water to be supplied to stator

    winding is held at rated flow under the conditions that the inlet temperature is 46• Žand the

    conductivity at 25• Žis below 0.5ƒÊS/cm.

    The flow rate and conductivity of the cooling water for stator winding is inspected and adjusted

     by the control system consisting of stator water storage tank, two stator cooling water circulating

     pumps, two stator water coolers, temperature and pressure control valves, stator water filter,

    demineralizing equipment and instruments. There is a branch, bypassing the generator, with a

    deionizer for keeping continuous purification of the water.

    5.2.2 Stator Water Storage TankThe storage tank has a capacity of approximately 2.69m

    3, and the water level is continuously

    monitored by float switch which provides alarm when water level fluctuates above or below the

    normal level. It also has a water level gauge so its water level can be observed with the naked eye.

    Make-up water will be replenished to the deionizer through a filter so as not to increase

     

    E K C 0 0 3 0 2 - a

    15  of   38

    5.2.3 Stator Cooling Water Circulating Pump

    The cooling water circulation in normally performed by an A.C. motor-driven centrifugal pump.

    In addition, an A.C. motor-driven centrifugal pump of equal capacity is installed as standby. The

  • 8/11/2019 Section08_A4.pdf

    148/806

     pump can be started manually, and it can also be started automatically by a pressure switch

    (x0MKF40CP105, x0MKF40CP106) located on the outlet pipe common to both pumps.

    The rate of flow circulating through the deionizer is approximately 10% of that flowing through

    the generator winding.

    In order to remove either pump for inspection during one pump operation, valves are provided at

     both inlet and outlet of each pump.

    ■  Pump is not operated in the state where is no load. It is required to

    pour in water before operating.

    Pump is damaged.

    ARNING!

    CAUTION!

     E K C 0 0 3 1 0 2 - a

    16 of 38

    5.2.5 Stator Water Filter and Strainer

    In the cooling water system, depth type disposable wound cartridge filters are provided at the

    stator cooling water pump discharge to filter all the water to the generator winding.

  • 8/11/2019 Section08_A4.pdf

    149/806

    These filters are designed to prevent metallic corrosive particles generated in winding and

     piping from entering into winding hollow conductor. The minimum size of grains to be filtered by

    the filters is about 3ƒÊm. A differential pressure gauge (x0MKF20CP101) is provided across

    filter for observation of any solid substance which is accumulated.

    ■  When the differential pressure increases to 0.09MPa, must be replace

    the filter elements.

    Only use manufacturer recommended filter elements. 

    ■  Keep the following matters, when you exchange filters.

    ‡ Exchange all Filter elements.

    ‡A

    Wash a filter

    ‡BAir vent valve is opened, and water is poured into the tub,

    extracting the air contained in the filter. Then drain valve is

    opened and water is discharged.

    CAUTION

     

    E K C 0 0 3 0 2 - a

    17  of   38

    5.2.6 Deionizer

    The deionizer is an ion exchange resin tower of floor type where the amberlite IRN-150 resin

    (cathion exchange resin IRN-77 and anion exchange resin IRN-78 are mixed) are filled in

  • 8/11/2019 Section08_A4.pdf

    150/806

    stainless steel wire-netting supporting the resin layers in a stainless steel tower. A pipe is provided

    for replacing and removing resin from the deionizer.

    ■  Make into 60• Žor less temperature of the cooling water which flowsto deionizer.

    If temperature exceeds 60•Ž  the performance will fall.

    ■  Do not freeze resin.

    Effect will be lost once resin is frozen.

    ■  When not using deionizer, pure water is kept in the state of full of

    water in a tub.

    Dryness of resin reduces the performance.

    CAUTION!

     E K C 0 0 3 1 0 2 - a

    18 of 38

    The quantity of water flowing into the deionizer can be inspected by a flow meter, but it should

    not exceed 15% of the flow running to the generator winding. When the amount of water flowing

    into the deionizer reaches this flow rate, and the conductivity of the generator inlet cooling water

    can not be held under 0.5ƒÊS/cm, it is necessary to replace the ion exchange resin.

  • 8/11/2019 Section08_A4.pdf

    151/806

    5.2.7 Cooling Water Conductivity

    Each of the three conductivity measurements are temperature compensated to 25• Ž, and the

    conductivity is measured by a conductivity indicator at the three points (the generator cooling

    water inlet, the generator outlet and the deionizer outlet) in the cooling water system.

    The conductivity indicator will successively indicate and has two alarm contacts in case of high

    conductivity. Conductivity measuring elements are attached to above three points, and are so

    arranged that they can be removed without taking the plant out of service.

    5.2.7.1 Make-up Water to System

    ALL make-up water for cooling water system is sent through filters and deionizer.

    Fl shing sho ld caref ll be applied to the filter piping if feed ater

    CAUTION

     

    E K C 0 0 3 0 2 - a

    19  of   38

    5.2.7.2 Operation without Stator Cooling Water Flow

    During normal operation, it is expected that the conductivity will be less than 0.5ƒÊS/cm. One

    alarm contact is set at this value to anticipate any subsequent increase in conductivity and to

    i ki i

  • 8/11/2019 Section08_A4.pdf

    152/806

     permit making necessary corrections.

    ■  The second alarm contact is set at 9.9ƒÊ

    S/cm, which indicates the

    maximum permissible conductivity.

    If the conductivity has been reached this point, the generator should

    be tripped.

    5.2.8 Alarm and Reduction of Generator Output with Turbine Interlock

    5.2.8.1 Alarm

    Item Alarm setting value

    Generator inlet cooling water

     press.( x0MKF40CP104

    at x0MKF30AA851 VALVE)

    LowSet pressure valve at equivalent flow rate

    880 /min at site.

    ARNING!

     E K C 0 0 3 1 0 2 - a

    20 of 38

    5.2.8.1 Trip

    Item Alarm setting value

    Generator outlet cooling water temperature

    (x0MKF20CT001 CT002 CT003)High 95• Ž

  • 8/11/2019 Section08_A4.pdf

    153/806

    (x0MKF20CT001, CT002, CT003)g

    Generator inlet cooling water pressure.

    (x0MKF40CP101, CP102, CP103)Reduced

    Set pressure valve at equivalent flow rate

    720 /min at site.

    5.2.9 Stator Winding Cooling Water Controlling Equipment

    This equipment consists of stator water tank, stator water pumps, stator water coolers, statorwater filter, regulating valves, deionizer, and related piping and valves which are perfectly

    installed on the base.

    Refer to outline stator cooling water unit : Drawing No.1KC003760.

     

    E K C 0 0 3 0 2 - a

    21  of   38

    6. Operation

    6.1 Introduction

  • 8/11/2019 Section08_A4.pdf

    154/806

    In the procedures below, the terms Stator Water and Cooling Water are used to distinguish

     between the treated and untreated water, respectively.

    ■  The Generator can be run without the Stator Water system in

    operation but output is then limited to 185,000kVA at 0.85pf.

    During normal (weekend) shutdown, the Stator Water system is kept running to maintain water

    conductivity.

    The Stator Water interlock should not be canceled before tripping the unit since shutdown offers

    the opportunity to check that Stator Water pumps trip with the generator. Immediately aftertripping, however, the interlock should be canceled and the Stator Water pump restarted.

    6.1.1 Charging the Stator Water System

    ARNING!

     E K C 0 0 3 1 0 2 - a

    22 of 38

    6.1.2 Coolers

    Each Stator Water cooler is rated at 100%.

    As being filled, the coolers are filled first with Cooling Water and then Stator Water. As being

  • 8/11/2019 Section08_A4.pdf

    155/806

    shut down for an extended period, they are drained of cooling water.

    Prior to a cold start, the Cooling Water flow is shut off to allow the Stator Water temperature to

    increase (due to friction losses).

    6.1.3 Deionizer

    ■  If Stator Water conductivity reaches the second alarm point of 9.9ƒÊ

    S/cm, the generator should be tripped immediately.

    Deionizer resin has a life of about one year. It is replaced if:

    a.  The pressure drop across the deionizer exceed 1bar.

     b.  Stator water conductivity at its outlet exceeds

    0.5ƒÊS/cm (with the normal proportion of Stator Water by-passing the coolers).

    ARNING!

     

    E K C 0 0 3 0 2 - a

    23  of   38

    6.1.4 Pump Testing on Load

    Auto starting of the Stator Water standby pump is tested without stopping the duty pump.

  • 8/11/2019 Section08_A4.pdf

    156/806

    6.2 Operating Procedure

    6.2.1 Preparation for Starting

    a. Set up the system as in the prestart valve status.

     b. Check electrical supplies to motors.

    c. Check alarm and protection supplies.

    d. Check that air supply is available to proportioning valve.

    e. Check that conductivity meters are in service.

    f. Check that Stator Water pump bearing lubricating oil levels at the bearing oil gauge.

    6.2.2 Charging and Starting the System

    g. Start the duty pump, and set the standby pump to AUTO.

    h. Trip the duty pump, confirm starting of standby pump automatically.

     E K C 0 0 3 1 0 2 - a

    24 of 38

    q. Check that the pump discharge pressure returns to normal value(0.74MPa).

    r. Set the standby pump to AUTO.

    6 3 Operating Values and Limits

  • 8/11/2019 Section08_A4.pdf

    157/806

    6.3 Operating Values and Limits

    Item Unit Normal Alarm Trip

    Stator water temperature

    Generator inlet

    Generator outlet

    • Ž

      • Ž

     

    40 to 46

    *76

    48

    10 above measured

    outlet temp. at full

    load

    95

    Storage tank level mm

    Gauge glass

    indication  Normal• }

    100

    Stator water conductivity

    Generator outlet

    Generator inletƒÊS/cm less than 0.3

    (1st) (2nd)

    0.5 9.9 •

     

    E K C 0 0 3 0 2 - a

    25  of   38

    6.4 Alarm Action

    Alarm conditions Possible causes Action required

    Stator

    cooling water

    LOW Failure of stator water

    pump and motor

    Check the stator water

    pump and motor

  • 8/11/2019 Section08_A4.pdf

    158/806

    cooling water

    inlet pressure

     pump and motor

    Failure of press. switch

     pump and motor.

    Check the discharge

     pressure gauge, standby

    stator water pump will be

    started.

    Statorcooling water

    inlet flow

    LOW Failure of stator water pump and motor

    Failure of press. Regulating

    valve (x0MKF20AA103)

    Leakage of water inlet line

    Above action is required.

    Check the pressure

    regulating valve and

    control sequence.

    Check the leakage point.

    Stator

    cooling water

     pump discharge

     pressure

    LOW Failure of stator water

     pump and motor

    Failure of press. switch

    Check the failed pump and

    motor.

    Check the pressure gauge

    and switches.

     E K C 0 0 3 1 0 2 - a

    26 of 38

    Alarm conditions Possible causes Action required

    Statorcooling water outlet

    t t

    HIGH Failure of regulating valve(x0MKF20AA101)

    Check the generatorloading, stator water inlet

    fl d

  • 8/11/2019 Section08_A4.pdf

    159/806

    temperature flow and pressure.

    Check the stator coil

    temperatures with R.T.D

    If necessary, detail check is

    required with outlet water

    temperature of each stator

    coil.

    Water level

    in water storage

    tank

    HIGH

    LOW

    (Normal level• }100mm)

    Failure of water level

    switch

    Leakage of storage tank

    and piping

    Check the water level

    gauge with storage tank.

     Normally, the water level is

    decreased, because theevaporating steam of the

    discharge water is vented

    out through the vent

     piping.

     

    E K C 0 0 3 0 2 - a

    27  of   38

    Alarm conditions Possible causes Action required

    Turbine interlock Without circulation

    through the stator cooling

    water system

    The quality of the cooling

    water will deteriorate and

    conductivity will increase

  • 8/11/2019 Section08_A4.pdf

    160/806

    Failure of both stator water

     pump

    Failure of regulating valves

    Failure of stator water

    coolers.

    The rate of deterioration

    may be influenced by

    several factors and

    following parameters have

     been established by test.

    Following reduction in

    output to rated capability

    without stator cooling

    water circulation.

    1)  If the conductivity prior to

    cessation of flow is more

    than 0.5ƒÊS/cm within 3

    minutes, reduce

    voltage to zero and trip.

    2)  If the conductivity prior to

    cessation of flow is less than

    0.5ƒÊS/cm within 60

     E K C 0 0 3 1 0 2 - a

    28 of 38

    6.5 Prestart Valve Status

     NOTE

    1. O: Open C: Close T: Throttle A: Automatic S: Select

  • 8/11/2019 Section08_A4.pdf

    161/806

    VALVE

     NUM-

    BER

    VALVE NAMEPLATE INSCRIPTION

    VALVE

    POSI-

    TION

    CHECK

    REM-

    ARKS

    x0MKF20AA001 SCWP(A) SUCTION ISOL VALVE O

    x0MKF20AA003 SCWP(B) SUCTION ISOL VALVE O

    x0MKF20AA851 SCWP(A) DRAIN VALVE C

    x0MKF20AA852 SCWP(B) DRAIN VALVE C

    x0MKF20AA801 SCWP(A) AIR VENT VALVE C

    x0MKF20AA802 SCWP(B) AIR VENT VALVE C

    x0MKF20AA701 SCWP(A) DISHC. NON RETURN VALVE O

    x0MKF20AA702 SCWP(B) DISHC. NON RETURN VALVE O

    0MKF20AA002 SCWP(A) DISHC GATE VALVE O

     

    E K C 0 0 3 0 2 - a

    29  of   38

    VALVE

     NUM-

    BER

    VALVE NAMEPLATE INSCRIPTION

    VALVE

    POSI-

    TION

    CHECK

    REM-

    ARKS

    0MKF20AA856

  • 8/11/2019 Section08_A4.pdf

    162/806

    x0MKF20AA856

    (For cooler B)COOLER (B) DRAIN VALVE C

    x0MKF20AA101 TCV TEMP. CONTROL VALVE A

    x0MKF20AA009 FILTER INLET ISOL VALVE O

    x0MKF20AA013 FILTER OUTLET ISOL VALVE O

    x0MKF20AA807 FILTER AIR VENT VALVE C

    x0MKF20AA910 FILTER ISOL VALVE FOR PDI O

    x0MKF20AA912 FILTER ISOL VALVE FOR PDI O

    x0MKF20AA911 FILTER EQUALIZE VALVE FOR PDI C

    x0MKF20AA867 FILTER DRAIN VAVLE C

     E K C 0 0 3 1 0 2 - a

    30 of 38

    VALVE

     NUM-

    BER

    VALVE NAMEPLATE INSCRIPTION

    VALVE

    POSI-

    TION

    CHECK

    REM-

    ARKSx0MKF30AA851 GEN/STAT CLG WTR GAUGE VALVE C

  • 8/11/2019 Section08_A4.pdf

    163/806

    x0MKF30AA903 GEN/STAT CLG WTR GAUGE VALVE O

    x0MKF50AA001 GEN/SCW INL HDR BLOW VALVE C

    x0MKF50AA002 GEN/SCW OTL HDR BLOW VALVE C

    x0MKF20AA868 GEN OUT SAMPLING VALVE C

    x0MKF20AA929 GEN OUT CDTY CELL ISOL VALVE O

    x0MKF20AA926 STORAGE TANK LS ISOL VALVE O

    x0MKF20AA927 STORAGE TANK LS ISOL VALVE O

    x0MKF20AA866 STORAGE TANK LS DRAIN VALVE C

     

    E K C 0 0 3 0 2 - a

    31  of   38

    VALVE

     NUM-

    BER

    VALVE NAMEPLATE INSCRIPTION

    VALVE

    POSI-

    TION

    CHECK

    REM-

    ARKSx0MKF20AA015 DEIONIZER INLET ISOL VALVE T

  • 8/11/2019 Section08_A4.pdf

    164/806

    x0MKF20AA703  DEIONIZER INLET NON RETURN VALVE O

    x0MKF20AA916  DEIONIZER INL PRESS ISOL VALVE O

    x0MKF20AA018  DEIONIZER OTL ISOL VALVE O

    x0MKF20AA808  DEIONIZER AIR VENT VALVE C

    x0MKF20AA860  DEIONIZER INLET PRESS DRAIN VALVE C

    x0MKF20AA861  DEIONIZER RESIN DRAIN VALVE C

    x0MKF20AA917  DEIONIZER OTL PRESS ISOL VALVE O

    x0MKF20AA862  DEIONIZER RESIN WASH VALVE C

    x0MKF20AA919  DEIONIZER CDTY CELL ISOL VALVE O

    x0MKF20AA867  STRAGE TANK DRAIN ISOL VALVE C

     E K C 0 0 3 1 0 2 - a

    32 of 38

    VALVE

     NUM-

    BER

    VALVE NAMEPLATE INSCRIPTION

    VALVE

    POSI-

    TION

    CHECK

    REM-

    ARKSGEN. INLET STATOR COOLING WATER PRESS

    x0MKF40CP104 ISOL VALVEO

  • 8/11/2019 Section08_A4.pdf

    165/806

    x0MKF40CP104 ISOL VALVEx0MKF40AA004 

    GEN. INLET STATOR COOLING WATER PRESS

    x0MKF40CP104 TEST VALVEC

    GEN. INLET STATOR COOLING WATER PRESS.

    x0MKF40CP101 PS ISOL VALVEO

    x0MKF40AA001 GEN. INLET STATOR COOLING WATER PRESS.x0MKF40CP101 TEST VALVE

    C

    GEN. INLET STATOR COOLING WATER PRESS.

    x0MKF40CP102 ISOL VALVEO

    x0MKF40AA002 GEN. INLET STATOR COOLING WATER PRESS.

    x0MKF40CP102 TEST VALVEC

    GEN. INLET STATOR COOLING WATER PRESS.

    x0MKF40CP103 ISOL VALVE O

    x0MKF40AA003 GEN. INLET STATOR COOLING WATER PRESS.

    x0MKF40CP103 TEST VALVEC

    GEN. INLET STATOR COOLING WATER PRESS.O

     

    E K C 0 0 3 0 2 - a

    33  of   38

    VALVE

     NUM-

    BER

    VALVE NAMEPLATE INSCRIPTION

    VALVE

    POSI-

    TION

    CHECK

    REM-

    ARKSGEN. INLET STATOR COOLING WATER FLOW

    x0MKF40CF001 ISOL(L) VALVEO

  • 8/11/2019 Section08_A4.pdf

    166/806

    ( )

    GEN. INLET STATOR COOLING WATER FLOW 

    x0MKF40CF001TEST VALVEC

    x0MKF40AA009 GEN. INLET STATOR COOLING WATER