82
Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications are complementary to each other. Drawings are graphic means of showing work to be done. They are particularly suited to showing materials are located. Thus, drawings exist essentially to show dimension, location and placement. Not all works, however, can be presented in the drawings. Generalized works are usually statement form and hence, the contractor is required to read the specifications carefully. Specifications, on the other hand, are used to describe the materials, construction techniques, samples, shop drawings, guarantees and other contract requirements. Together, the drawings and the specifications are used to inform the contractor. In cases where the specified brand carries with it the manufacturer’s specifications, the manufacturer’s specifications shall hold precedence over these specifications. The Specifications are of the abbreviated type and include incomplete sentences. The selection of the sentence depends on the underlying principles of Specifications: A. That the Technical Specifications are only one part of the contract Documents. B. That the contract is between the Owner and the General Contractor and C. That the General Contractor is the only party responsible for completing the work in accordance with the Contract Documents. Therefore: A. Only the General Contractor is referred to in the Specifications so as not to violate the intent of the contract and so as not to undermine the proper chain of command. B. Any reference to Specialty Trade Contractors in the technical Specifications is made only in so far as selection of Specialty Trade Contractors is made through bidding. Once the Specialty Trade Contractors are selected and assigned to the General Contractor, the General Contractor assumes all the responsibilities for the execution of the whole project in accordance with the Contract Documents. Therefore, in the contract between the Owner and the General Contractor, the Specialty Trade Contractor is not referred to. In all contract Documents, the word “Contractor” means the General Contractor. C. The brand names specified are intended to assure the level of quality needed for the project. This does not mean however that the brands specified are exclusive. The

Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

  • Upload
    others

  • View
    16

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

Section X. Technical Specifications

SECTION 01000

EXPLANATION FOR THE SPECIFICATIONS

1.0 INTRODUCTION

The Drawings and Specifications are complementary to each other. Drawings are graphic

means of showing work to be done. They are particularly suited to showing materials are

located. Thus, drawings exist essentially to show dimension, location and placement. Not

all works, however, can be presented in the drawings. Generalized works are usually

statement form and hence, the contractor is required to read the specifications carefully.

Specifications, on the other hand, are used to describe the materials, construction

techniques, samples, shop drawings, guarantees and other contract requirements. Together,

the drawings and the specifications are used to inform the contractor. In cases where the

specified brand carries with it the manufacturer’s specifications, the manufacturer’s

specifications shall hold precedence over these specifications.

The Specifications are of the abbreviated type and include incomplete sentences. The

selection of the sentence depends on the underlying principles of Specifications:

A. That the Technical Specifications are only one part of the contract Documents.

B. That the contract is between the Owner and the General Contractor and C. That the General Contractor is the only party responsible for completing the work in

accordance with the Contract Documents.

Therefore:

A. Only the General Contractor is referred to in the Specifications so as not to violate the

intent of the contract and so as not to undermine the proper chain of command.

B. Any reference to Specialty Trade Contractors in the technical Specifications is made

only in so far as selection of Specialty Trade Contractors is made through bidding. Once

the Specialty Trade Contractors are selected and assigned to the General Contractor,

the General Contractor assumes all the responsibilities for the execution of the whole

project in accordance with the Contract Documents. Therefore, in the contract between

the Owner and the General Contractor, the Specialty Trade Contractor is not referred

to. In all contract Documents, the word “Contractor” means the General Contractor.

C. The brand names specified are intended to assure the level of quality needed for the

project. This does not mean however that the brands specified are exclusive. The

Page 2: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

Contractor shall prove by laboratory tests and certificates that substitute materials are

of the equivalent quality and the Contractor shall secure the Architect’s approval prior

to use of such substitutes.

D. The omission of the phrase “The Contractor shall “is intentional because the whole

Specifications is directed to the Contractor. Omitted words or phrases shall be supplied

by inference in the same manner as they are when a “note” occurs on the drawings.

E. Where “as shown”, “as indicated”, “as detailed” or words of similar import are used, it

shall be understood that reference to the drawings accompanying the Specifications is

made unless otherwise stated.

F. Where “as directed “, “as required”, “as permitted”, “as authorized”, “as approved,

accepted” or words of similar import as used, it shall be understood that the direction,

requirements, permission, authorization, approval or acceptance of the Architect is

intended unless otherwise stated.

G. As used herein, “provided” shall be understood to mean “provided complete in place,”

that is, “furnished and installed”.

H. Most sentences are in the imperative mood. This style is especially suited for

instructions covering installation of products and equipment.

Example:

“Spread planting soil mixture to depth required to meet thickness, grades, elevations shown”

“Reuse surface soil stockpiled on site”

“Maintain ground cover by watering”

The verb is the first word of the sentence clearly defining the action to be performed.

This style is readily understandable and concise.

2.0 CLARIFICATIONS

All reference to any particular brand, material, equipment, or systems in the specifications,

drawings, and bid documents is indicative of the type and quality of what is required.

However, any equal material or equipment or system can be used if approved by the

University.

END OF SECTION 01000

Page 3: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

SECTION 01010

SUMMARY OF WORK

1.1 GENERAL REQUIREMENTS

1.2 DESCRIPTION OF THE PROJECT

Furnish all materials, equipment, plant tools, and other facilities and perform labor to

complete all works in the design and construction of the

IMPROVEMENT/EXTENSION OF PSHS SYSTEM TRAINING AND

ADIMINISTRATION CENTER, in accordance with the plans, specifications, the

Philippine Bidding Documents, the Terms of Reference and other related contract

documents.

1.3 PERMITS, LICENSES AND TAXES

A. Secure and pay all permits, fees, licenses, taxes, etc. Necessary for the execution

of the general construction works

B. Prepare a monthly progress report which shall include, among others. An overall

progress chart and progress value of construction work.

1.4 TEMPORARY FACILITIES

A. Construct temporary facilities like field office, bodega, housing, toilet facilities for

workers.

B. Secure all existing equipment, materials and facilities which shall eventually be re-

used.

C. Take all necessary measures to protect all existing facilities, site development, and

equipment from damage, loss and dirt.

1.5 DEMOBILIZATION AND CLEANING

A. Demobilize, dismantle and remove all temporary facilities, including all

workmen’s houses, construction equipment, tools, personnel and debris out of the

project site and/or University premises.

Page 4: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

B. Clean building and site; spic and span, ready for use.

1.6 DIVISION SECTIONS

1.0 GENERAL REQUIREMENTS

01000 Explanation to the Specifications

01010 Summary of Work

01020 Summary of Materials and Finishes

01200 Shop Drawings

01310 Project Management and Coordination

01320 Construction Progress Documentation

01330 Submittal Procedures

01524 Construction Waste Management

01600 Product Requirements

01750 Warranties and Bonds

01770 Closeout Procedures

01781 Project Record Documents

2.0 SITEWORK

02100 Site Preparation

02200 Earthwork

02230 Site Clearing and Demolition

02280 Termite Proofing

02350 Sanitary Sewarage

02510 Water Systems

02630 Storm Drainage

Page 5: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

02700 Site Drainage

02900 Landscaping

02920 Lawns and Grasses

02930 Exterior Plants

3.0 CONCRETE

03100 Concrete Formwork

03200 Concrete Reinforcement

03300 Cast-in-Place Concrete

03400 Architectural Pre-Cast Concrete

4.0 MASONRY

04100 Mortar

04200 Unit Masonry

04720 Cast Stone

5.0 METALS

05100 Structural Steel Framing

05200 Miscellaneous Metals

05310 Steel Decking

05400 Cold Formed Metal Framing

05500 Metal Fabrications

05511 Metal Stairs and Railings

6.0 WOOD AND PLASTICS

Page 6: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

06100 Rough Carpentry

06200 Finish Carpentry

06402 Interior Architectural Woodwork

06416 Plastic Laminate Wood Cabinets

7.0 THERMAL AND MOISTURE PROTECTION

07100 Waterproofing and Dampproofing

07210 Building and Roofing Insulation

07400 Sheet Metal Roofing

07413 Composite Metal Wall Panels

07842 ire-Resistive Joint Systems

07900 Joint Sealants

07951 Expansion Joint Covers

8.0 DOORS AND WINDOWS

08125 Interior Aluminum Frames

08211 Flush Wood Doors

08411 Aluminum-Framed Entrances and Storefronts

08520 Aluminum Windows

08700 Hardware

08710 Door Hardware

08712 Finish Hardware

08716 Automatic Door Operators

08800 Glazing

Page 7: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

9.0 FINISHES

09200 Plaster

09250 Gypsum Board

09265 Gypsum Board Assemblies

09300 Tile

09511 Acoustical Panel Ceilings

09612 Concrete Densifier and Sealer

09622 Resilient Sports Floor Covering

09680 Carpet Tile

09900 Painting

10.0 SPECIALTIES

10155 Toilet Compartments

10265 Impact Resistant Wall and Door Protection

10400 Identifying Devices

10425 Interior Signage

10520 Fire-Protection Specialties

10522 Fire Extinguisher, Cabinets, Accessories

10800 Toilet and Bath Accessories

12.0 FURNISHINGS

12356 Countertops

12500 urniture Systems (for coordination, not in contract)

15.0 MECHANICAL

Page 8: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

15050 Basic Mechanical Materials and Methods

15052 Common Work Results for Plumbing

15092 Sleeves and Sleeve Seals for Plumbing

15145 Domestic Water Piping

15155 Sanitary Waste and Vent Piping

15165 Storm Drainage Piping

15451 Plumbing Fixtures and Trims

16.0 ELECTRICAL

16050 Basic Electrical Materials and Methods

16055 Overcurrent Protective Device Coordination

16060 Grounding and Bonding

16073 Hangers and Supports for Electrical Systems

16075 Electrical Identification

16100 Wiring methods

16120 Conductors and Cables

16140 Wiring Devices

16145 Lighting Control Devices

16511 Interior Lighting

16521 Exterior Lighting

16720 Security Systems

16721 Fire Alarm System

END OF SECTION 01010

Page 9: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

SECTION 01020

SUMMARY OF MATERIALS AND FINISHES

1.1 GENERAL REQUIREMENTS

1.2 RELATED SECTIONS

All applicable provisions of the different divisions of the Specifications for each work

trade shall apply for all items cited in this Summary.

1.3 INFERRED ITEMS AND WORK

Materials and workmanship deemed necessary to complete the works but NOT

specifically mentioned in the Specifications, Working Drawings, or in the other

Contract Documents, shall be supplied and installed by the Contractor without extra

cost to the Owner. Such materials shall be of the highest quality available, and installed

or applied in a workmanlike manner at prescribed or appropriate locations.

1.4 SPECIFICS

Materials specifically mentioned in this Summary shall be installed following efficient

and sound engineering and construction practice, and especially as per manufacturer's

application for installation specifications which shall govern all works alluded to in

these Specifications.

1.5 ON-SITE ITEMS

Materials and finishes for on-site improvements and facilities as listed below are part

of the scope of work and shall be supplied and installed by the Contractor without

extra cost to the Owner.

A. Installation of engineered and drainage fills for building and landscaped

areas where specified.

B. Construction of:

Page 10: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

1. Concrete driveways, walks, ramps, steps, posts, and miscellaneous

slabs;

2. Concrete splash slabs, steel or hard plastic gratings;

3. Below grade utility structures such as septic vaults, cisterns, handholes,

and manholes;

4. Above-grade utility structures such as electrical poles, concrete

pedestals, and the like;

C. Exterior utility lines, raceway system, fixtures, breakers, switches, buzzers,

controls including fittings and accessories as required by the specialty trades

under plumbing, electrical and communication works.

D. Pumps, tanks and other necessary equipment and facilities.

1.6 OFF-SITE ITEMS

Off-site improvements shall generally be under the responsibility of the Owner and

not included in the Contract, with the exception of the following which shall be part

of the Contractor's Work:

A. Concreting of entry slabs. This work shall neatly make connections to the

existing roads or curbs, if any, and shall incorporate necessary utility ways

under such as required. Access road drainage system and other existing utility

lines must be kept in working condition.

B. Installation of concrete drainage pipes to neatly receive connections from the

storm drainage system of the site to access road and/or to existing drainage

system.

C. Permanent connections to the local utility lines for electrical, water, drainage,

sewer and telephone lines including equipment, facilities, materials, fees,

and/or work which utility companies or authorities may require of the

applicant Owner, such as electrical transformers, electric poles, service

laterals and drops, etc. by their respective Specialty Contractors.

2.1 SITEWORK

2.2 02100: SITE PREPARATION

A. DISPOSAL OF MATERIALS

1. All salvageable materials shall remain the property of the Owner. Hauling and

stacking of salvaged material within a 300-meter radius to Owner's specified

Page 11: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

storage shall be for the account of the Contractor. However, upon Owner's

written instructions, salvageable materials may be disposed of by the

Contractor at the Contractor's expense.

2. All debris and other materials resulting from clearing and grubbing work shall

be immediately removed from the premises and dumped at sites provided by

the Contractor in manner approved by the Architect.

2.3 02200: EARTHWORK

A. FILL MATERIALS

1. General Fill for structures and under spread footings, pavers, or concrete slabs

on grade shall conform to the general requirement for soil materials above and

shall be classified as GW, GM, GP, SW, SM by the ASTM 2487 and conform

to the following.

a) Liquid Limit – shall not exceed 25% when tested in accordance with

ASTM 423.

b) Plasticity Index – shall not exceed 12 % when tested in accordance

with ASTM 424.

c) Under Buildings, no more than 25% by weight shall be finer than No.

200 sieve when tested in accordance with ASTM D 1140.

2. Granular Fill shall conform to the general requirements for soil material above

and shall be clean, crushed stone or gravel conforming to ASTM C 33, size 67

and with a sand equivalent of not less than 50% when tested in accordance

with ASTM D 2419.

3. Backfill material behind walls shall consist of free-draining granular fills,

sized in particular to provide a filter media around subsoil drainage system.

4. Drainage Fill: Fill material shall clean, well graded, free draining sand

conforming to ASTM C 33 for Fine Aggregate.

5. Borrow: If additional material is required for fill in excess of that obtained by

excavation at the site, obtain same from sources acceptable to the Owner’s

Engineer. All arrangement for obtaining borrow from off-site shall be the

responsibility of the Contractor and all cost thereof shall be borne by the

Contractor. Acceptable borrow will consist of suitable material for fills as

herein before specified. Representative of each type of borrow materials

considered suitable shall be delivered to the Testing Laboratory and tested

prior to placement. Any borrow material not meeting the standard herein

specified, or considered unsuitable by the Owner’s Engineer will be rejected

at the site.

B. BATTERBOARDS

Page 12: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

1. Second class, pest free lumber assembled and rendered secure for proper

delineation of building lines and grades

2.4 02230: SITE CLEARING AND DEMOLITION

A. FILL MATERIALS

1. Satisfactory Soil Material: Requirements for satisfactory soil material are

specified in Division 2 Section "Earthwork."

a) Obtain approved borrow soil material off-site when satisfactory soil

material is not available on-site.

2.5 02282: TERMITE PROOFING

Product and application by Owner-accredited termite and pest control contractor.

A. TERMITE PROOFING

1. Use Termiticide Concentrate or approved equal. Dilution rating: 1 part

Termiticide Concentrate to 50 parts water. There shall be no disturbance of

treated soil between application of poison and pouring concrete.

2.6 02630: STORM DRAINAGE

A. CONCRETE PIPE

1. Reinforced-Concrete Pipe (RCP): Shall conform to AASHTO Specification

M-170-81-1 and ASTM C 76, Class III, as indicated on the drawings. Joints

shall be standard tongue and groove with mastic and butyl sealants in

accordance with ASTM C990-96.

B. POLYETHYLENE PIPE

1. Corrugated HDPE Pipe and Fittings: ADS N-12 WT IB HDPE pipe with

smooth interior and annular exterior corrugations. Pipe shall meet AASHTO

M294, Type S, or ASTM F2306.

C. . PVC PIPE AND FITTINGS

1. PVC Pipe: AWWA C900, Class 200, for gasketed joints and using ASTM F

477, elastomeric seals.

a) Fittings NPS 4 to NPS 8: PVC pressure fittings complying with AWWA

C907, for gasketed joints and using ASTM F 477, elastomeric seals.

Page 13: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

b) Perforated pipe for foundation drains.

c) Solid pipe between foundation drains and daylight or drainage structures.

D. EARTH FILL

1. Backfill shall be as specified in Division 2 Section “Earthwork” and be

substantially free from organic materials, loam, wood, trash and other

objectionable materials which may be compressible, or which cannot be

properly compacted. Additionally, the fill material shall not contain stones or

rocks larger than 2 inches in diameter, blocks, broken concrete, masonry

rubble, snow, ice, frozen earth or other similar materials. Compact in layers as

specified in Division 2 Section “Earthwork”.

2.7 02700: SITE DRAINAGE

A. DRAINAGE PIPE:

1. Plain concrete drain pipes and fittings: 250 mm (10") and below in diameter:

T & G conforming to ASTM C-14-59.

2. Reinforced concrete pipes fittings: 300 mm (12”) and bigger: Centrifugally

cast or vibrated T & G conforming to ASTM C-76-59 T.

B. JOINING MATERIAL

1. One-part cement to two parts sand.

C. BUILDING STORM DRAIN CONNECTION TO MAIN

1. Concrete wye branch and clean out, T & G or use junction boxes.

D. AREA DRAIN CATCH BASIN

1. Load-bearing 4.8 Mpa (700 PSI) concrete hollow blocks (CHB) or reinforced

concrete with cover as shown on the drawings.

E. CATCH BASINS OF JUNCTION BOXES

1. Load-bearing 4.8 Mpa (700 PSI) concrete hollow blocks (CHB) or reinforced

concrete as indicated in the drawings, with solid reinforced concrete cover.

2.8 02900: LANDSCAPINGS

A. TREE AND SHRUB MATERIALS

Page 14: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

1. General: Furnish nursery-grown trees and shrubs conforming to ANSI Z60.1,

with healthy root systems developed by transplanting or root pruning. Provide

well-shaped, fullybranched, healthy, vigorous, and stock free of disease,

insects, eggs, larvae, and defects such as knots, sun scald, injuries, abrasions,

and disfigurement.

2. Grade: Provide trees and shrubs of sizes and grades conforming to ANSI Z60.1

for types of trees and shrubs required. Trees and shrubs of a larger size may

be used if acceptable to the Landscape Architect, with a proportionate increase

in size or roots or balls.

3. Shade Trees: Single-stern trees with straight trunk, well-balanced crown, and

intact leader, of height and caliper indicated, conforming to ANSI Z60.1 for

type of trees required. Branching height shall still be 1/3 to ½ of tree height.

4. Small Trees: Small upright or spreading type, branched or pruned naturally

according to species and type, and with relationship of caliper, height and

branching recommended by ANSI Z60.1, and multi-stem form of clump, with

2 or more main stems

B. GROUND COVER MATERIALS

1. Provide ground covers established and well rooted in removable containers or

integral peat pots and with not less than the minimum number and length of

runners required by ANSI Z60.1 for the pot size indicated.

C. GRASS MATERIALS

1. Paspalum conjugatum (Carabao Grass) Sod Sprigs: Healthy living stems,

rhizoms or stolons with a minimum of 2 nodes and any attached roots free of

soil.

D. TOPSOIL

1. ASTM D 5258. pH range of 5.5 to 7, 4 percent organic material minimum,

free of stones 1 inch (25 mm) or larger in any dimension, and other extraneous

materials harmful to plant growth.

E. FERTILIZER

1. Commercial Fertilizer. Commercial-grade complete fertilizer of neutral

character, consisting of fast- and slow-release nitrogen, 50 percent derived

from natural organic source of urea-form, phosphorus, and potassium in the

Page 15: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

following composition: 0.5 kg per 100 sqm (1 lb per 1000 sq. ft.) lawn area of

actual nitrogen, 4 percent phosphorus, and 2 percent potassium, by weight.

F. MULCHES

1. Organic Mulch: Free from deleterious materials and suitable as a top dressing

of trees and shrubs, consisting of wood and bark chips.

G. EXISTING TREES

1. Contractor shall secure the necessary environmental permits required to ball-

out, or cut down affected existing trees with 100mm or more in trunk diameter.

Cut down trees shall be the property of the Owner. All costs and logistics of

the transportation and transfer of balled-out trees to the new site shall be the

responsibility of the contractor.

H. PLANT LIST

(To be specified by the winning bidder in their Detailed Design Drawings)

2.9 02930: EXTERIOR PLANTS

A. TOP SOIL AND VEGETATION

1. Owner shall approve the Landscape Plans prior to start of construction.

2. Coordinate plant selection and required top soil quantity with the Architect of

Record and the Construction Manager.

3. All debris and other materials resulting from clearing and grubbing work shall

be immediately removed from the premises and dumped at sites provided by

the Contractor in manner approved by the Construction Manager.

3.1 CONCRETE

3.2 03100: CONCRETE FORM WORKS

A. FORMS

1. TYPE OF FORMS: Use phenolic boards for exposed and unexposed concrete

works, Armourply brand or approved equal, for all cast in place and pre-cast

works.

Page 16: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

2. SCAFFOLDS: Use metal scaffolding whenever necessary. Wood nor coco

lumber are not allowed. Form work, shoring, temporary bracing, staging,

construction of temporary facilities, and any other measures needed to support

the structural elements or provide shelter from debris during construction shall

be the responsibility of the builder.

3.3 03200: CONCRETE STEEL REINFORCEMENT

A. STEEL BARS

1. Use locally manufactured deformed billet-steel bars conforming to Philippine

standard, Intermediate Grade of 275.8 Mpa (Fy = 40,000 psi) for bars 10mm

diameter or smaller, and High Strength Grade of 415 Mpa (Fy = 60,000 psi)

for bars 12mm diameter and larger

2. Use standard-sized deformed steel conforming with ASTM A615/PNS 49

standards, for concrete and masonry reinforcements. Upgrade to next bigger

size if specified standard sizes are unavailable.

B. TIE WIRES

1. Use Ga.16 Galvanized Iron (G.I.) tie wires at joints or laps of placed

reinforcements.

3.4 03300: CAST IN PLACE CONCRETE

A. GENERAL

1. Concrete shall be composed of Portland cement, fine and coarse aggregates,

water and admixture as specified, all thoroughly mixed and brought to the

proper consistency, uniformity and temperature for final placement. Strength

requirements shall be (see Sheet S-01):

a) 28 MPa (4000 psi) for footings, retaining walls, footing tie beams, cistern

and suspended slabs.

b) 28 MPa (4000 psi) for columns, girders, beams and RC gutters;

c) 17.2 MPa (2500 psi) for slabs-on-grade, partitions, walks, & other non-

structural members;

d) 10.5 MPa (1500 psi) for lean concrete, or as required by the Engineer.

B. CEMENT

1. Cement shall be Portland cement, conforming to the Standard Specifications

for Portland Cement (ASTM Designation C-150 latest revision) for type 1

Portland Cement. Use only one brand of cement throughout.

Page 17: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

C. FINE AGGREGATES

1. Fine aggregates shall consist of natural sand, manufactured sand, or a

combination thereof. If the fine aggregate shall be a combination of separately

processed sizes, or if hatching shall result in a combination of natural and

manufactured sand, the different components shall be batched separately.

2. Fine aggregates shall consist of hard, tough, durable, uncoated particles. The

specified percentages of fines in the sand may be obtained either by the

processing of natural sand or by the production of a suitably graded

manufactured sand. The shape of the particles shall be generally rounded or

cubical and reasonably free from flat or elongated pieces. The use of beach

sand shall be prohibited. The fine aggregate shall conform to the following

specific requirements:

Sieve Sizes

Standard (mm) U.S. Standard, Square

Mesh

Cumulated Percentage by

Weight Passing

9.5 3/8 100

4.75 No. 4 95-100

2.36 No. 8 -

1.18 No. 16 45-80

0.60 No. 30 -

0.30 No. 50 10-30

No. 100 2-10

In addition to the grading limits shown above, the fine aggregates, as delivered

to the mixer shall have a fineness modulus of not less than 2.3 nor more than

Page 18: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

3.0 and during normal operations, the grading of the fine aggregate shall be

controlled so that the fineness modulus of at least nine (9) of ten (10) test

samples of the fine aggregate as delivered to the mixer shall not vary more

than 0.20 from the average fineness modulus of all samples tested during the

preceding 30-day period. The fineness modulus can be determined by dividing

by 100 the sum of the cumulated percentages retained on U.S. Standard Sieves

Nos. 4, 8, 16, 30, 50 and 100. At the option of the Contractor, fine aggregates

may be separated into two or more sizes or classification, but the resulting

combined sand shall be of uniformed grading within the limits specified

above. It can be generally assumed that fine blending sand maybe required to

meet the above grading.

D. COARSE AGGREGATES

1. Coarse agreement shall consist of gravel, crushed gravel or rock, or a

combination thereof. The coarse aggregate as delivered to the batching plant

shall have a uniform and stablemoisture content. The approval of deposits

shall not be construed as constituting the approval of all the materials taken

from the deposits and the Contractor shall be held responsible for the specified

quality of all such materials used in the work.

2. Coarse aggregate shall consist of hard, tough, durable, clean and uncoated

particles. All foreign materials and dust shall be removed by adequate

processing.

3. The particle shape of one of the smallest size of crushed coarse aggregate shall

be generally rounded or cubical, and the coarse aggregate shall be reasonably

free from flat and elongated particles. A thin, flat and elongated particle can

be defined as a particle having a maximum dimension greater than five times

the minimum dimension.

4. The coarse aggregate shall be well graded from fine to coarse. It shall be

separated into size groups. The grading of the aggregate within the separated

size groups as delivered to the mixer shall be as follows:

Sieve Sizes

Standard(MM) U.S. Standard,

Square Mesh

Percent by

Weight Sizes 1-

1/2”

Passing Individual

3/4”size

0.00 2” - 100

37.50 1-1/2” - 90-100

Page 19: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

25.00 1” 100 20-55

19.00 3/4" 90-100 0-15

9.50 3/8” 20-55 0-5

4.75 No. 4 0-10 -

- Use 19 mm (3/4) coarse aggregate for slabs-on-grade, columns, beams,

suspended slabs, tie beams.

- Use 38 mm (1 ½”) coarse aggregate for footings or as specified by the

structural engineer.

E. WATER

1. Water shall be clean and free from injurious amounts of oils, acids, alkalis,

salts and organic materials, or other substances that may be deleterious to

concrete or steel.

F. ADMIXTURES

1. MIXTURES 1. Admixtures shall be subject to prior approval by the Engineer.

The admixtures shall be capable of maintaining essentially the same

composition and performance throughout the work.

a) Plasticizing admixtures shall be free from chlorides and shall conform to

ASTM C494. The admixtures shall be used in concrete mixtures in

accordance with the manufacturer's instructions.

b) Use POSSOLITH 3R or DARATARD 17 or approved equal in the

amounts as recommended by the manufacturer, with the approval of the

Architect.

c) Air-entraining admixtures - DAREX AEA or approved equal to improve

workability or durability of concrete mixes.

d) Accelerators - DAREX SET ACCELERATOR or approved equal.

e) Water Reducing Retarders - DARATARD 17 or approved equal.

f) Integral Waterproofing Compound - SIKA or approved equal. For canopy

slab. Use one kilo pack per forty kilo bag of Portland cement.

g) Calcium chloride is not allowed. Secure approval of the Engineer prior to

using of any other additive.

Page 20: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

G. EPOXY BONDING COMPOUND

1. ASTM C881, 2-component materials suitable for use on dry or damp surfaces;

material type, grade and class to suit project requirements. For bonding new

to old concrete, repair of cracks, bonding grout.

NOTE: Placement Drawings: Shop drawings of each reinforcing steel detail and

placement drawings shall be submitted for approval in accordance with the

requirements of the General Conditions. Any material fabricated before final

approval of the shop drawings will be done at Contractor's risk, but no material

shall be placed until shop drawings have final approval. Shop drawings shall be

in accordance with the "Manual of Standard Practice for Detailing Reinforced

Concrete Structures" (ACI 315).

4.1 MASONRY

4.2 04100: MORTAR

A. MATERIALS

1. PORTLAND CEMENT: Use only one brand of cement throughout. Portland

cement shall conform to the Standard Specifications for Portland Cement

(ASTM Designation C- 150 latest revision) for type 1 Portland Cement.

2. SAND: ASTM C 35 – 67, clean, washed river sand, strong, free from organic

and other deleterious materials. Sand from salt water or lahar is not allowed.

3. WATER: Fit for drinking, free from injurious amount of oil, acids, alkali,

organic materials and other deleterious substances.

4. CONCRETE MORTAR COMPRESSIVE STRENGTH: ( f'c ) = 13.8 Mpa

(2000 psi).

5. ADHESIVE MORTAR: Use adhesive mortar for laying vitrified ceramic tiles,

with dispersion compound as an additive to adhesive mortar.

Page 21: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

6. GROUT: Use grout pre-mixed dry wall filler for floor and wall tile joints either

glazed or semi-glazed tiles. Masonry concrete grout compressive strength ( fc’

) = 13.8 Mpa (2000 psi). For tile works.

7. PLASTER BOND: Apply on all wall areas prior to plastering.

8. MORTAR TOPPING & PLASTER REINFORCING FIBER: For plaster

works thicker than 25mm (1”) and for mortar topping over membrane

waterproofing for roof decks and balconies

B. MIXES

1. Cement Mortar:1 part Portland Cement, 2 parts sand, but not more than 1 part

Portland Cement, 3 parts sand.

2. For plaster works thicker than 25 mm (1”), use plaster mix with FIBRIN – 23

as per manufacturer’s specifications.

4.3 04200: UNIT MASONRY

A. CONCRETE HOLLOW BLOCKS (CHB)

1. Use 150 mm x 200 mm x 400 mm (6" x 8" x 16") and 100 mm x 200 mm x

400 mm (4” x 8” x 16”) Non-Load Bearing Concrete Hollow Block Units of

standard manufacture, machine vibrated with even texture and well defined

edges, steam-cured, conforming to PNS16 Type 1, Class A, with a minimum

compressive strength of 2.5 MPa (350 psi) for building exterior and interior

walls and septic tank retaining wall around open court and wherever else

specified.

Note: For interior walls, use 4” CHB from floor to bottom of slab or bottom of

beam, with 10mm dia. reinforcing bars at 600 mm o.c. bothways. Anchor to floor

by embedding vertical bars 75mm deep into the floor slab. Anchor to slab or beam

by providing 10mm dia. dowels. Provide stiffener columns and beams as required

in the general notes.

5.1 METALS

5.2 05100: STRUCTURAL STEEL

A. MATERIALS

Page 22: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

Owner/Architect–approved manufacturer/sub–contractor should conform all

materials and workmanship to the requirements of the American Institute of Steel

Construction "Specifications for Design, Fabrication and Erection of Structural

Steel for Buildings" as amended to date or as may be specifically modified by the

drawings or by these Specifications.

1. PLATES, SHEETS AND CONNECTORS: Conform to ASTM Designation

A36 with specified yield point of 248 MPa (36,000 psi). From mild steel sheets

or plates with standard thickness, size, shape and design as indicated in the

plans. For miscellaneous stiffener, bearing anchorage and connector plates or

straps. Upgrade to next higher / bigger size and thickness if specified sizes &

thicknesses are unavailable.

2. STANDARD SOLID SECTION: Conform to ASTM A36 with specified yield

point of 248 MPA (36000 psi). Mild steel angles, flat bars, square bars,

channels, U and other sections. For structural steel trusses, purlins, building

eaves framing, overhead anchorage of roll-up doors, grillworks, miscellaneous

fabricated mounting brackets, straps, dowels, frames and connectors. Upgrade

to next higher/bigger size and thickness if specified sizes and thickness are

unavailable.

3. HIGH STRENGTH BOLTS, NUTS AND WASHERS: Conform bolts to the

Specification for High Strength Bolts ASTM A 325, Type 1. See structural

connection details for location of bearing-type and friction-type bolts.

4. ANCHOR BOLTS: A36.

5. WELDING ELECTRODES: Conform welding electrodes to AWS D1.1:2000

Structural Welding Code – Steel, E-60XX for structural welding.

6. GROUT: Conform non-shrink grout to ASTM C827. Grout shall be

nonmetallic. Use Non-shrink non-viscous cementitious grout. Apply using

manufacturer’s standards strictly,

7. STRUCTURAL STEEL PRIMER PAINT: Epoxy zinc chromate primer

except as otherwise recommended by the manufacturer of the coating for all

structural steel surfaces.

8. FIRE COVER: Cementitious Fireproofing System. Refer to Section 07251

Sprayed-On Fireproofing, whenever necessary.

B. FABRICATION

1. Fabricate structural steel within tolerances specified under Codes and

Standards referenced in paragraph 1.03.

2. Fabricate and assemble structural steel in the shop to the greatest extent

possible. Do shearing carefully and accurately using machine equipment

where possible.

Page 23: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

3. Connections shall be welded or bolted as indicated. Shop connections not

otherwise shown shall be welded. Eccentric connections are not permitted

unless shown in detail on shop drawings.

4. Surfaces required to be milled or planned are indicated on the drawings.

5. Provide bearing plates for members bearing on footings, piers and walls.

6. Drift pins may be used for assembling parts provided metal is not distorted or

holes enlarged. Holes requiring enlargement to admit bolts shall be reamed.

Misaligned holes will subject members to rejection.

7. Shop Cleaning:

a) Cleaning: Thoroughly clean loose mill scale, rust, dirt, grease and other

foreign matter from structural steel shapes.

8. Shop Painting: Shop paint structural steel work which will be exposed in the

finish work and other fabrications exposed to weather. Coordinate the use of

primer paint on the steel with architectural drawings and fire ratings.

a) Surface Preparation: After inspection and before shipping, clean steel

work to be painted. Remove loose rust, loose mill scale, and spatter slag

or flux deposits. Clean steel in accordance with Steel Structures Painting

Council (SSPC) SP-2, SP-3, or SP-7. Remove oil and grease deposits by

solvent.

b) Painting: Immediately after surface preparation, apply structural steel

primer paint in accordance with manufacturer’s instructions and at a rate

to provide uniform dry film thickness on 1.5 mils. Use painting methods

which will result in full coverage of joints, corners, edges, and exposed

surfaces.

5.3 05200: MISCELLANEOUS METALS

A. MATERIALS

1. STANDARD SOLID SECTION: Conform to ASTM 611 with specified yield

point of 228 Mpa (33,000 psi). Mild steel flat bars, square bars, overhead

anchorage of roll-up doors, grill work, miscellaneous fabricated mounting

brackets, straps, dowels, frames and connectors. Upgrade to next higher /

bigger size and thickness if specified sizes & thickness are unavailable.

2. BRACING RODS: Standard structural grade steel rods with turnbuckles

whenever required ex. for roof framing.

3. PAINTING: Use only approved brand of epoxy zinc chromate paint and

linseed oil for all architectural steel components only. For field painting, use

only approved brand of enamel paint.

4. ALUMINUM COMPOSITE PANEL (ACP) CLADDING:

Page 24: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

a) Lightweight, rigid, bendable, composite aluminum; 3.0 mm thick.; front

side – aluminum with advance fluorocarbon paint (PVDF); core – nontoxic

low density polyethelene (LDPE);

b) back side – aluminum coated with polyester; passing test for hardness

(ASTM D-3363- 74), flexibility (ASTM D-4145-83), adhesion (ASTM D-

3359-87), abrasion (ASTM D-968- 81), mortar resistance (AAMA 605, 2-

91), detergent resistance ASTM D-2248-73), acid pollutants (ASTM D-

1308-87; AAMA 605, 2-90), alkali resistance (ASTM D-1308-87), salt fog

(ASTM B-117-85), humidity ASTM D-2247-87 D-714-87), color

retention (ASTM D- 2244-85, D-2244-89) and chalk resistance (ASTM

D-659-86, D-4214-89). Install by manufacturer-approved installer with

guarantee. Provide the necessary sealants to ensure water-tightness.

Provide shop drawings for approval by the Architect before fabrication and

installation. For exterior cover of solid walls, fascias, sun-shading devices,

exterior parapets and other areas as shown in the plans.

5. STAINLESS STEEL: Pipes, tubes, square bars, and other sections.

Manufactured and installed with guarantee. Provide shop drawings for

approval by the Architect before fabrication/installation

a) Roof Gutter: 1.2 mm (gauge 18) thick, Stainless Steel Sheets, Type 304

bent to design shape. For all other gutters aside from RC gutters. To be

approved by Architect before installation

b) RC Precast Anchors: 10mm Stainless Steel Plain Bars

c) Stair, ramp and corridor railings.

d) Grab bars for toilets (where applicable).

Note: Upgrade to next bigger size if specified standard sizes are

unavailable.

6. GALVANIZED IRON:

a) Yard Hose Bibbs: G.I. Pipes: schedule 40, painted with Epoxy Enamel

Paint.

b) Hangers: Gauge 10 G.I. wire hanger

7. BRASS NOSING: 3 mm thk. x 38 mm wide brass nosing for every stair tread

and for every change in floor elevation, unless otherwise indicated or any

approved equivalent by architect.

8. FASTENINGS: Commercial types, except where special types are shown or

required.Fastenings for all exterior work shall be non-ferrous, unless

otherwise shown. Fastening for stainless steel and aluminum and other interior

work, where exposed shall match the fastened metal.

5.4 05310: STEEL DECK

Page 25: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

A. MATERIALS

1. CONCRETE FLOOR STEEL DECKING: Use 275.8 Mpa (Fy=40,000 psi)

steel strength; 21 Mpa (Fc= 3,000 psi) concrete strength; effective coverage =

0.25 M; using manufacturer’s specifications for thickness, reinforcements and

method of construction. Use temporary proppings at 1.0 M on centers during

pouring until fully cured. Installation by manufacturer and Architect approved

installer with guarantee.

2. ROOF DECK: 1-1/2-INCH-DEEP, WIDE RIB (38 MM): Cold rolled, 20

gauge, ASTM A653/653M SS Grade 33 (minimum) steel sheet. Galvanize to

Class G60; Minimum Moment of Inertia: 0.21 inches4 per foot; Minimum

Section Modulus: 0.23 inches3 per foot; Interlocking sides.

3. FLOOR DECK: 3-INCH-DEEP COMPOSITE DESIGN (76 MM): Cold

rolled, 20 gauge, ASTM A653/653M SS Grade 33 steel sheet. Galvanize to

Class G90; Minimum Moment of Inertia: 0.96 inches4 per foot; Minimum

Section Modulus: 0.57 inches3 per foot positive and 0.60 inches3 per foot

negative.

4. ACCESSORIES: Welding Materials: AWS D1.3; Cell Closures: Flexible

rubber 1-inch-thick, profiled to decking; Metal Closure Strips, Cover Plates

and Related Accessories: Of required profiles and size; Concrete Pour Stops:

16-gauge minimum, size as required; Expansion Bolts: Hilti Inc.; Kwik Bolt

II, or substitution subject to Section 01 63 00. For exterior locations, use

galvanized bolts; Powder Actuated Fasteners: Hilti Inc.; Hilti DX System;

Galvanizing Repair: SSPC Paint 20, with dry film containing at least 94

percent zinc dust by weight.

B. DESIGN STANDARDS

Structural properties specified are the design standards for the Project. Slight

variation will be considered, provided that engineering data, illustrating that deck

is capable of supporting both gravity and lateral loads specified, is submitted for

review and approval.

5.5 05400: COLD FORMED METAL FRAMING

A. MATERIALS

1. Framing Materials

a) Studs: Sheet steel, ASTM A1003/A1003M Structural Grade 50, Type H

(ST50H) formed to channel shape with pre-punched slotted holes.

Minimum thickness 16 gauge.

b) Coating: ASTM A653/A653M, Grade 50, galvanized to G90.

Page 26: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

c) Track: Sheet steel formed to channel shape, same gauge and width as

studs, tight fit, same steel grade and finish as studs. Top track shall have

2-1/2 inch extended legs to allow for deflection of overhead construction.

Pre-punched slots in deflection head tracks

2. Accessories

a) Bracing, Furring, Bridging and Other Components: Formed sheet steel,

thickness as required for conditions encountered, manufacturer's standard

shapes, same finish as framing members.

b) Galvanizing Repair Paint: Paint containing zinc dust in concentrations of

not less than 92%, conforming to ASTM A780.

3. Fasteners

a) Screws: Self-drilling, Self-tapping; corrosion resistant coating

zinc/chromate/organic, equal to Hilti “Kwikote”.

b) Bolts, Nuts and Washers: ASTM A90, hot-dip galvanized.

c) Anchorage Devices: Power-driven or powder-actuated.

d) Welding: Follow AWS D1.1.

B. FABRICATION

1. Fabricate assembly of sections with framing members fitted, reinforced and

braced to suit design requirements.

2. Assemble in largest practical sections for delivery to site.

5.6 05500: METAL FABRICATIONS

A. MANUFACTURERS

Products listed are approved. Substitutions are permitted subject to approval.

B. .MATERIALS

1. Metal Surface Quality

a) For metal fabrications exposed to view in the finished work, provide

materials selected for their surface flatness, smoothness and freedom from

surface blemishes.

b) Do not use materials with exposed pitting, seam marks, roller marks, rolled

trade names, or roughness.

2. Ferrous Metal

a) Steel Plates, Shapes, and Bars: ASTM A36.

b) Steel Tubing: ASTM A500 Grade B, seamless.

c) Steel Pipe: ASTM A53, Schedule 40 unless otherwise specified.

Page 27: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

d) Steel Sheet:

- Cold rolled, commercial quality, ASTM A1008.

- Hot rolled sheet and strip, structural and commercial quality, ASTM

A1011.

- Zinc coated sheet, structural quality, ASTM A653/A653M and

commercial quality, ASTM A653/A653M.

e) Cast Iron: ASTM A48 in Class (tensile strength) recommended by

manufacturer for proposed use.

f) Stainless Steel: Type 302 or 304, ASTM A276, A240, A269 or A480 as

applicable to purpose required. Finish: Electro-polish free of grinding

marks, pits or other minor surface imperfections.

3. Aluminum

a) Sheet and Plate: ASTM B209.

b) Tubular Shapes: ASTM B210, B221, B483 as best suited for proposed use.

c) Bars, Rods, Wire, Profiles and Tubes: ASTM B211 or B221 as best suited

for proposed use.

d) Structural Shapes: ASTM B308 and B429 respectively, as applicable

4. Fasteners

a) Steel-to-Steel Connections: Follow AISC Specifications.

b) Stainless Steel and Aluminum: Stainless steel.

c) Include bolts, nuts, washers, shims, and special type fastening devices.

5. Accessories

a) Grout: Master Builders; Embeco Masterflow 713 Non-Ferrous Non-

Shrink Grout.

b) Welding Materials: AWS D1.1; type required for materials being welded.

c) Ungalvanized Steel Primer For Items Receiving Standard Alkyd or Latex

Topcoats:

d) Ungalvanized Steel Primer For Items Receiving Epoxy or Urethane

Topcoats:

e) Galvanized Steel Primer:

f) Aluminum Primer for items receiving Alkyd finish:

g) Alkyd Enamel Undercoater and Primer Sealers: Equal to or better than

Benjamin Moore & Co.: Moorcraft Super Spec Alkyd Enamel

Undercoater & Primer Sealer C245. Field Repair of Unprimed Galvanized

Steel: Sherwin-Williams; Zincplate 49 Organic Primer or ZincClad IV

Organic Zinc Rich Primer.

h) ) Epoxy Adhesive System for Edge Angles at Slab Openings: 2

components, 100 percent solids, 100 percent reactive compound suitable

for use on dry or damp surfaces; moisture insensitive.

Page 28: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

C. FABRICATION

1. Verify dimensions on site prior to shop fabrication.

2. Make exposed joints flush and hairline tight.

3. Grind exposed welds flush and smooth with adjacent finished surface. Ease

exposed edges to small uniform radius.

4. For exposed fastenings, use flush countersunk screws or bolts; unobtrusively

located; consistent with design of structure, except where specifically noted

otherwise.

5. Supply components required for anchorage of metal fabrications. Fabricate

anchorage and related components of same material and finish as metal

fabrication, except where specifically noted otherwise.

6. Shop assemble in largest practical sections.

D. SHOP PAINTING

1. Surface Preparation: SSPC-SP1 Solvent Cleaning and SSPC-SP3 Power Tool

Cleaning. Use SSPC-SP6 Commercial Blast when required for special

primers. Remove loose mill scale, rust, oil, grease, weld slag, and other foreign

matter.

2. Do not paint ferrous metal in contact with concrete or where field welding is

required.

3. Paint ferrous metal, except stainless steel, on all surfaces. Shop paint

galvanized items unless shown otherwise.

4. Paint aluminum surfaces in contact with dissimilar metals.

5. Paint aluminum surfaces in contact with concrete or masonry, whether or not

primed, with heavy- bodied bituminous paint.

6. Do not paint aluminum surfaces in contact with joint sealants.

E. GALVANIZING

1. Galvanize the following items, including anchorages, fasteners and

accessories:

a) Shelf angles and lintels located in exterior walls.

b) Other ferrous metal exposed to exterior atmosphere.

c) Ferrous metal at building interior only where shown or specified.

2. Products made from Rolled, Pressed and Forged Shapes, Castings, Plates,

Bars, and Strips: Grade 65, ASTM A123/A123M.

3. . Fasteners: ASTM A153/A153M, Class A.

4. Steel Sheet: G90 zinc coating, ASTM A653/A653M [A924/A924M].

Page 29: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

5.7 05511: METAL STAIRS AND RAILINGS

A. BASIS OF DESIGN

Design and Shop drawings upon approval of procuring agency.

B. MATERIALS

1. Steel Sections: ASTM A36.

2. Sheet Steel: 12 gauge minimum, hot rolled, ASTM A569.

3. Steel Tubing: Cold Formed, ASTM A500B and A513.

4. Steel Pipe: ASTM A53, type and grade selected by manufacturer as required

for design loading.

5. Wall Mounted Handrail Assemblies: Match stair mounted assemblies.

6. Threaded End Hanger Rods: 16 mm (5/8 inch) diameter minimum, ASTM

A36.

7. Pipe Columns (If Required): 50 mm (2 inch) nominal minimum.

8. Plates, Angles, and Other Accessories: ASTM A36.

9. Reinforcing for Concrete Fill: No. 5 bars, grade 40, 356 mm (14 inches) OC

maximum.

10. Welding Material: AWS D1.1; type required for materials being welded.

11. Bolts, Nuts, Washers, and Other Fasteners: ASTM A307.

12. Paint Primer for Steel: Manufacturer's standard.

13. Stair Nosing: 76 mm wide x minimum 6 mm thick x 3 mm less than tread

width (3 inches wide x minimum 1/4 inch thick x 1/8 inch less than tread

width). Provide with abrasive finish, American Stair: Style 331-3". Acceptable

substitutions include:

a) American Safety Tread Co. Inc.: Type 8511.

b) Balco Inc.: R-305LP

c) Wooster: Type 231BF.

d) Other pre-engineered steel stair company with manufacturing operations

in the Philippines.

C. FABRICATION

1. General:Fabricate stairs to conform to sizes and arrangements indicated. Join

stairs and components together by welding unless otherwise indicated.

2. Stairs are to be complete assemblies including metal framing, hangers,

railings, struts, clips, brackets, bearing plates and other components necessary

for support of stairs, platforms required to anchor and contain stairs on the

supporting structure members.

Page 30: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

3. Fabricate components required for anchorage to each other and to building

structure. Form Sections to required shapes and sizes, with true angles.

Provide necessary rebates and brackets for assembly.

4. Reinforce undersides to meet design load criteria.

5. Where ends of railings are exposed, close ends with welded on caps. Provide

close radius 90 degree bend. Terminate railings 50 mm (1/2 inch) from wall.

6. Field Poured Concrete Stair Treads: Fourteen (12) gauge or greater (depending

on span) steel formed into sub-treads for 50 mm (2 inch) field poured-in-place

concrete treads.

7. Risers: Manufactured from 12 gauge or greater (depending on span) hot rolled

mild steel.

8. Concrete Platforms and Landings: Formed of manufacturer's standard

fourteen (12) gauge or greater (depending on span) steel sub-deck reinforced

with No. 5 rebars at 14 inch centers and field poured-in place with concrete.

9. Fabricate stair guards and handrails of 38 mm (1½ inch) eleven (11) gauge

square tubing or 41 mm (1 5/8 inch) fourteen (14) gauge round structural steel

tubing with 19 mm (¾ inch) square steel vertical pickets at 100 mm (4 inches)

on center. Weld connections and grid joints smooth. Close posts and rail ends

(as applicable), weld and grind smooth.

10. Handrails are to be mounted to walls and/or guardrails with brackets spaced

no more than 1220 mm (4 feet) OC. Form railings with end extensions as

indicated with closed ends.

11. Supply all components for proper anchorage of handrail

12. Joints and Welds:

a) Grind contact surfaces of connected members true. Assemble parts for

flush and hairline tight joints.

b) Exposed mechanical fasteners, if required, shall be flush countersunk type,

unobtrusively located.

c) Except as otherwise shown or specified, welds exposed to view shall be

continuous for full length of connection.

d) Use welding method which develops strength required to comply with

structural performance criteria.

e) Grind exposed welds flush and smooth with adjacent finished surface.

Ease exposed edges to small uniform radius.

D. FINISH

1. Clean surfaces of rust, scale, grease and foreign matter prior to priming.

2. Shop prime paint; one coat.

3. Do not prime surfaces in direct contact bond with concrete where field welding

is required.

Page 31: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

6.1 WOOD AND PLASTICS

6.2 06100: ROUGH CARPENTRY

A. GENERAL

1. Dimension Lumber:

a) If no species is specified, provide any species graded by the agency

specified; if no grading agency is specified, provide lumber graded by any

grading agency meeting the specified requirements

b) Grading Agency: Any grading agency whose rules are approved by the

Board of Review, American Lumber Standard Committee (www.alsc.org)

and who provides grading service for the species and grade specified;

provide lumber stamped with grade mark unless otherwise indicated.

2. Lumber:

a) Yakal: generally, for all plates, corbels, struts and other components of

woodbased structures requiring wood which is strong, not resistant and/or

capable of holding on firmly to driven nails or other connectors. For

cabinet base wood blocks or as specifically called for in the drawings.

Note: For K.D. Tanguile, plywood inner sides and for cut ends of Apitong

joints, nailers, and framings, supplementary termite and rot treatment to be

applied by Owner-approved termite and pest control company, with

guarantee. Effect: butt joint appearance for all T and cross intersections of

exposed frames. When stronger joints are required, introduce half-laps,

dowelling or mortise and tenon but still effect a simple butt joint at the

exposed surface.

3. Hardware and Fasteners:

Use metals nails, screws, bolts, plates, straps, miscellaneous fasteners or

anchorage concealed or countersunk whenever called for, with size, shape and

type to ensure a rigid connection for laminated items and at cabinet framing

joints.

B. DIMENSION LUMBER FOR CONCEALED APPLICATIONS

1. Grading Agency: Southern Pine Inspection Bureau, Inc. (SPIB).

2. Sizes: Nominal sizes as indicated on drawings, S4S.

Page 32: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

3. Moisture Content: MC15 (15 percent moisture content).

4. Miscellaneous Framing, Blocking, Nailers, Grounds, and Furring:

a) Lumber: Philippine hardwood, Sta. Clara or approved equal, S4S (finished

4 sides), No. 2 or Standard Grade.

b) Boards: Standard or No. 3.

C. PLYWOOD

1. . Exposed to View: APA Grade A-C, exterior, sanded, 19 mm (3/4 inch) thick

unless shown otherwise in manufacturer’s site requirements.

2. Concealed from View: APA Grade C-C, plugged, exterior, unsanded, 19 mm

(3/4 inch) thick unless shown otherwise manufacturer’s site requirements.

D. FASTENERS AND ANCHORS

1. Fasteners, General Use: Size and type to suit condition.

2. Anchors:Toggle bolt type for hollow masonry; expansion shield and lag bolt

type for solid masonry or concrete; threaded nuts and bolts for anchorage to

steel.

3. Metal and Finishes:

a) Hot dip galvanized steel per ASTM A153 where exposed to exterior

atmosphere or high humidity environments.

b) Where used with treated wood: Hot-dipped galvanized steel fasteners

meeting ASTM A153 and connectors complying with ASTM 653, Class

G185.

c) Other Areas: Unfinished steel.

E. WOOD PRESERVATIVE PRESSURE TREATMENT

1. Preservative Treatment by Pressure Process: Plywood (AWPA C9). Lumber

that is not in contact with the ground and is continuously protected from liquid

water shall be treated according to AWPA C31 with inorganic boron (SBX).

Lumber in contact with the ground and not continuously protected from water

(AWPA C2).

2. Preservative Chemicals: Ammoniacal copper quat (ACQ).

a) Do not use chemical formulations that require incising.

b) For exposed items indicated to receive transparent finish, do not use

chemical formulations that contain colorants or that bleed through or

otherwise adversely affect finishes.

Page 33: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

c) Kiln-dry material after treatment to levels required for untreated material.

Do not use material that is warped or does not comply with requirements

for untreated material.

d) Mark each treated item with the Quality Mark Requirements of an

inspection agency approved by the American Lumber Standards'

Committee Board of Review.

F. WOOD PRESERVATIVE - FIELD APPLIED

1. AWPA Standard M4.

G. FACTORY WOOD TREATMENT

1. Treated Lumber and Plywood: Comply with requirements of AWPA U1 - Use

Category System for wood treatments determined by use categories, expected

service conditions, and specific applications.

a) Fire-Retardant Treated Wood: Mark each piece of wood with producer's

stamp indicating compliance with specified requirements. b) Preservative-

Treated Wood: Provide lumber and plywood marked or stamped by an

ALSC- accredited testing agency, certifying level and type of treatment in

accordance with AWPA standards.

2. Fire Retardant Pressure Treatment:

a) Interior Type A: AWPA Use Category UCFA, Commodity Specification

H (Treatment C20 for lumber and C27 for plywood), low temperature (low

hygroscopic) type, chemically treated and pressure impregnated; capable

of providing a maximum flame spread rating of 25 when tested in

accordance with ASTM E 84, with no evidence of significant combustion

when test is extended for an additional 20 minutes.

- Kiln dry wood after treatment to a maximum moisture content of 19

percent for lumber and 15 percent for plywood.

- Do not use treated wood in applications exposed to weather or where

the wood may become wet.

- Treat rough carpentry items as indicated.

6.3 06200: FINISH CARPENTRY (See 9.02 and 9.03 for all DRY WALL and

CEILING Finishes)

A. LUMBER: Moisture content; between 5 and 10 percent.

1. Softwood: Any commercial softwood species.

2. Hardwood Lumber: Birch or Poplar.

Page 34: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

3. GUIJO: quarter-sawn, sound and free from imperfections impairing its

strength and finish; Kiln-dried (max. moisture content: 12%), with the same

shade and color for assemblies or sets of assemblies, warp-free, treated, S4S

and fine sanded lumber. For louver slats of doors and edgings, when required.

Note: Each separate lumber piece or assembly is required to bear an official

mark of the millworks supplier.

Note: Each separate lumber piece or assembly is required to bear an official

mark of the millworks supplier.

B. SHEET MATERIAL

1. Softwood Plywood: The purpose for which plywood is used shall determine

types, grades, waterproof or water-resistive construction, and thickness

according to "Guide to Plywood Grades under Product Standard PS 1, except

as shown otherwise. Exposed Faces: Veneer Grade Pine for interior plywood

and Medium Density Overlay for exterior plywood.

2. Hardwood Plywood: Philippine hardwood, varying ply thickness as detailed.

PS 51; particleboard core; type of glue recommended for application.

3. Particleboard: Medium density, ANSI A208.1 Grade 1-M-2, density: 45 pcf;

moisture resistant and fire retardant treated.

4. Hardboard: ANSI A135.4; pressed wood fiber with resin binder; tempered

grade.

5. Medium Density Fiberboard (MDF): 19mm (3/4”). For free span shelves, and

for miscellaneous components of cabinets, overhead cabinets and closet

housing; for all doors and exposed and unexposed sides of closets and kitchen

cabinets/overhead cabinets.

6. Fiber Cement Board: Use 4.5mm thick for ceiling boards and backing of

mirrors; 6mm thick for wall boards; and 9mm thick for fascia boards; 1200

mm x 2400 mm. Install as per manufacturer’s instructions.

7. Fiber Cement Soffit: Wood-grain, 300mm wide x indicated length. Install and

paint per manufacturer’s instructions. Fixings shall be rust-proof screws or

nails. For all roof eaves or any approved soffit material by architect.

C. PLASTIC LAMINATE MATERIAL

1. Plastic Laminate: NEMA LD 3, in colors and textures as shown. Types as

follows:

Page 35: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

a) GP 50: Horizontal grade. Use this grade for all exposed horizontal and

vertical applications. The following may also be used for specific

applications where GP 50 is not suitable.

b) GP 28: Vertical Grade

c) PF 42: Post-forming Grade

d) CL 20: Cabinet Liner

e) BK 20: Backing Sheet

2. Adhesives: Mill option

D. PVC MOULDINGS AND TRIMS

1. For baseboards, use 86.3mm (3-3/4”) height, with Baseboard Molding.

Provide baseboards for all walls (even if not designated in the plans), except

for walls finished with tiles, stone and aluminum cladding.

E. ACCESSORIES

1. Hardware and Fasteners: Use metal nails, screws, plates, straps, miscellaneous

fasteners or anchorage; concealed or countersunk whenever called for, with

size, shape and type to ensure a rigid connection for laminated items.

2. Assembly Materials: Approved water-resistant glue, and nails, screws and

bolts of appropriate type, shape and size for all types of joints.

3. Closet Hardware: Chrome plated steel with matching end and intermediate

supports.

6.4 06402: INTERIOR ARCHITECTURAL WOODWORK

A. LUMBER: Moisture content between 5 and 10 percent

1. AWI Custom grade suitable for transparent finish.

2. Softwood: Spieces: Redwood plain swan.

3. Hardwood: Species, color and grain to match hardwood face veneer

B. SHEET MATERIAL

1. Hardwood Faced Panels:

a) ) Hardwood Face Veneer: Plain sliced Philippines hardwood selected for

uniform color and grain quality capable of transparent finish. Grain match

adjacent sheets to book matching.

2. Particleboard: Medium density, ANSI A208.1 Grade 1-M-2, density: 45 pcf;

moisture resistant and fire retardant treated.

Page 36: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

3. Hardboard: ANSI A135.4; pressed wood fiber with resin binder; tempered

grade.

4. Pegboard: Pressed wood fiber with resin binder; tempered grade; 3.2 mm (1/8

inch) thick with holes 25 mm (1 inch) OC.

5. Low-emitting Materials: Provide materials made with adhesives and

composite wood products that do not contain urea-formaldehyde resins.

6. Panel Products: Any of the following:

a) Particleboard made from wood particles [, with binder containing no

ureaformaldehyde resin], complying with ANSI A208.1, Grade M-2.

b) Particleboard made from straw, complying with ANSI A208.1, Grade M-

2.

c) Medium-density fiberboard made from wood fiber [, with binder

containing no urea- formaldehyde resin], complying with ANSI A208.2,

Grade MD.

d) Medium-density fiberboard made from agricultural waste fiber, complying

with ANSI A208.2, Grade MD.

e) Hardboard, complying with AHA A135.4.

f) Veneer core plywood [, made with adhesive containing no urea-

formaldehyde resin].

C. ACCESSORIES

1. Fasteners, Bolts, Nuts, Washers, Lags, Pins and Screws: Size and type to suit

application, except where specific types are shown.

D. FIRE RETARDANT TREATMENT

1. AWPA Interior Type A, Standard C-20 for lumber and C-27 for plywood.

Material shall provide a maximum flame spread and smoke development

classification of 25 or less, ASTM E84.

2. Use treated lumber and plywood in Server Rooms, LAN/IT closets,

mechanical equipment rooms, storage rooms.

E. CASEWORK HARDWARE AND ACCESSORIES

1. Manufacturers: The manufacturers and products named are acceptable;

substitutions of other unnamed manufacturers are permitted subject to

approval by the Owner.

a) Shelf Standards and Rests: KV No. 255 BRN-Brown steel recessed

standards and No. 256 zinc plated clips; four supports per shelf.

Page 37: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

b) Shelf Brackets: See Division 12 Laboratory Casework. Shelf bracket wall

system products shall be capable of providing shelves that can support 50

kg / 300 mm foot width of sheving.

c) Support Brackets: Hafele "Hebgo" Series, table bracket primed for field

painting.

d) Drawer and Door Pulls: Stanley No. 4484, 4-inch wire pulls, satin

aluminum US28.

e) Sliding Door Pulls: Ives No. 226, circular recessed pull, US26D.

f) Cabinet Locks: Schlage CL Series; provide with bar or mortise strike as

applicable.

g) Catches: Stanley No. SP46, aluminum.

h) Drawer Slides: Full extension telescoping action on precision steel ball

bearings; BHMA 100-pound class load rating; Knape & Vogt

Manufacturing Company, Medium duty, Model No. 8400.

i) Hinges: Grass America No. 3606 Snap-On, 95 degree opening, nickel

plated.

j) Sliding Door Hardware: frameless, barn-door type, top mounted, heavy

duty PVC casters.

6.5 06416: PLASTIC LAMINATE WOOD CABINETS

A. SCHEDULE OF MATERIALS AND FINISHES

1. Casework Shell, Counters, Shelves, Drawers and Doors: Particleboard.

2. Stiles and Rails: Lumber.

3. Exterioir Finish: Chemically resistant, plastic laminate.

4. Interior Finish: Phenolic resin shelving, melamine or plastic laminate on solid

panels

B. LUMBER: Moisture content between 5 and 10 percent

1. Moisture content between 5 and 10 percent.

2. Any commercial softwood species.

C. SHEET MATERIAL

1. Particleboard: Medium density, ANSI A208.1 Grade 1-M-2, density: 45 pcf;

moisture resistant and fire retardant treated.

2. Low-emitting Materials: Provide materials made with adhesives and

composite wood products that do not contain urea-formaldehyde resins.

3. Panel Products: Any of the following:

a) Particleboard made from wood particles [, with binder containing no urea

formaldehyde resin], complying with ANSI A208.1, Grade M-2.

Page 38: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

b) Particleboard made from straw, complying with ANSI A208.1, Grade M-

2.

c) Medium-density fiberboard made from wood fiber [, with binder

containing no urea- formaldehyde resin], complying with ANSI A208.2,

Grade MD.

d) Medium-density fiberboard made from agricultural waste fiber, complying

with ANSI A208.2, Grade MD.

e) Hardboard, complying with AHA A135.4. f) Veneer core plywood[, made

with adhesive containing no urea-formaldehyde resin].

D. PLASTIC LAMINATE MATERIAL

1. Plastic Laminate: NEMA LD 3, in colors and textures as shown. Types as

follows:

a) GP 50: Horizontal grade. Use this grade for all exposed horizontal and

vertical applications. The following may also be used for specific

applications where GP 50 is not suitable.

b) GP 28: Vertical Grade

c) PF 42: Post-forming Grade

d) CL 20: Cabinet Liner

e) BK 20: Backing Sheet

2. Adhesives: Mill option

E. FIRE RETARDANT TREATMENT

1. AWPA Interior Type A, Standard C-20 for lumber and C-27 for plywood.

Material shall provide a maximum flame spread and smoke development

classification of 25 or less, ASTM E84.

2. Use treated lumber and plywood in Server Rooms, LAN/IT closets,

mechanical equipment rooms, storage rooms.

F. CASEWORK HARDWARE AND ACCESSORIES

1. Manufacturers: The manufacturers and products named are acceptable;

substitutions of other unnamed manufacturers are permitted subject to

approval by the Owner.

a) Fasteners: Bolts, Nuts, Washers, Lags, Pins and Screws: Size and type to

suit application, except where specific types are shown.

b) Plastic Edge Trim: Extruded convex shaped; smooth finish; self-locking

serrated tongue; of width to match component thickness; color to be

chosen by A/E.

c) Shelf Standards and Rests: Stanley No. 1805 aluminum mortise. Four

supports per shelf.

Page 39: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

d) Drawer and Door Pulls: Stanley No. 4484, 4-inch wire pulls, satin

aluminum US28.

e) Catches: Stanley No. SP46, with impregnated rubber magnet, satin

aluminum US28.

f) Drawer Slides: Full extension telescoping action on precision steel ball

bearings; BHMA 100-pound class load rating; Knape & Vogt

Manufacturing Company, Medium duty, Model No. 8400.

g) Hinges: Grass American No. 3613VS or Blum No. 75M3580, concealed

adjustable type for a 95 degree opening, nickel plated.

h) Wire Access Grommets: Doug Mockett & Company, Inc., Style TG, 2 3/8

inches wide, with 2-inch hole, round black plastic liner and cap.

7.1 THERMAL AND MOISTURE PROTECTION

7.2 07100: WATERPROOFING AND DAMP PROOFING

Apply with surface preparation, methods application and density as per

manufacturer’s specifications. To be installed only by authorized Applicator with

guarantee.

A. WATERPROOFING COMPOUND: Applied as per manufacturer’s

specifications for all concrete sub-roofs, concrete gutters and suspended floor

toilets.

B. FLUID APPLIED WATERPROOFING. Synthetic rubber, cold-vulcanized,

liquid applied waterproofing membrane. Applied 1mm thick following

manufacturer’s specifications; for positive application on concrete gutter and plant

boxes, with 3m8mm conc. topping, to be installed only by authorized Applicator

or by the Architect’s approved applicator.

C. SINGLE PLY WATERPROOFING MEMBRANE: Pre-formed, self-adhesive

rubberized bitumen with cross-laminated PVC plastic facing, for suspended

toilets.

D. EXPOSED TYPE LIQUID MEMBRANE WATERPROOFING: Single pack

liquid rubber compound for concrete ledges.

E. ICE & WATER SHIELD or approved equal: Underlay Waterproofing Membrane

– self- sealing and self-adhering rubberized membrane for all concrete deck roofs

and canopies.

F. DAMP-PROOFING: Vapor barrier, one layer at six mils (0.006) thick. For slabs

on fill at the building interior. Provide 300 mm overlapping.

Page 40: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

G. WATERSTOP: PVC, for all concrete joints wall and floor construction below

grade

7.3 07210: BUILDING AND ROOFING INSULATION

A. For inaccessible concrete roof deck of machine room and main stairways: Use

extruded polystyrene board covered with 60mm concrete topping. Installation by

Architect-approved manufacturer, with guarantee.

B. METAL ROOFING INSULATION: Thermal Barrier INSULATION. For all

metal roofing, installed directly under C-purlins.

C. DRAINAGE SHEET AND FILTER: When necessary, use Drainage Sheets and

Geotextile Filter to cover all underground exterior walls and slabs fastened Hilti

DX 36M with 6.8/11 yellow cartridge case with DN 37 P 8 nail and washer or

equivalent. Use stop pins, or Butyl on sheeting overlaps and DELTA-MS Profile

or equivalent on top edge of sheeting; Installation by Architect-approved

manufacturer with guarantee.

D. PROTECTION BOARD: 4.5mm (3/16”) thick Fiber cement board for basement

walls on positive applied membrane waterproofing to be applied by an Architect-

approved installer and or supplier.

E. GLASS FIBER BATT INSULATION

1. Description: ASTM C665, formaldehyde free preformed glass fiber batt or

blanket form; Type III, Class A, Category 1, foil faced, 25 percent minimum

recycled content.

2. Vapor Transmission (Perm) Rating: 0.05 or less, ASTM E96.

3. Thermal Resistance "R": 13 for 3 1/2 inch thickness, 19 for 6 1/2 inch

thickness.

4. Flame Spread: 25, ASTM E84. 5. Smoke Developed: 50, ASTM E84.

F. ACCESSORIES

Page 41: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

1. Nails, Staples, and Other Fasteners: Rust resistant type where exposed to

exterior atmosphere. Other Areas: Unfinished.

2. Tape: Polyethylene self-adhering type; 50 mm (2 inches) wide.

3. Spindle Fasteners: Galvanized wire spindle on flat metal base; self-adhering

backing.

4. Wire Mesh: Galvanized steel, hexagonal wire mesh.

5. Metal Furring: Galvanized steel; of type to receive specified wall finish.

6. Adhesive: Type recommended by insulation manufacturer for application.

7.4 07400: SHEET METAL ROOFING

A. MATERIALS

1. Sheet Steel: ASTM A653/A653M Grade A; galvanize to ASTM

A653/A653M G90.

2. Panels: 22 gauge minimum thickness, 406 mm (16 inches) wide, with double

standing seam at least 64 mm (2-1/2 inches) high. and intermediate

longitudinal ribs to minimize oil-canning. Provide full lengths from ridge-to-

eave with no horizontal laps

3. Soffit, Facia, Trim, Battens, Closures, Flashing, Snowguards, Gutters and

Downspouts: Same material type, thickness, and finish as roofing. Provide

mitered and welded corners and transitions.

4. Temper of flashing may be reduced to facilitate forming.

5. Soffit: Flush style.

6. Finish: Fluoropolymer coating. Standard heavy 2 coat system

7. Apply protective coating to concealed surfaces to be in contact with

cementitious materials or dissimilar metals.

8. Provide thermal spacers to compress insulation at girt locations, as required.

B. ACCESSORIES

1. Caulking and Gasketing: As required for a complete weather-tight installation.

2. All seams and joints shall be sealed.

3. Stainless steel fasteners and galvanized clips, concealed where possible. Do

not use exposed fasteners in roof panels. At other locations, keep exposed

fasteners to a minimum; locations must be approved by A/E.

4. Profile Closures: Precut closed cell foam.

5. Steel Subgirts: Zee-shaped, ASTM A653/A653M Grade A; gauge as required

to meet requirements for UL rating; galvanize to ASTM A653/A653M G90.

Page 42: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

6. Wall Counter flashing Assemblies: Custom profile as shown; roll formed

0.050-inch-thick powder coated galvanized iron reglets and counterflashing.

Finish: Fluorocarbon coating, color to match roofing.

7. Counter flashing of Mechanical Penetrations:

8. Splash Blocks: Precast concrete, 762 mm (30 inch) size.

9. Provide base sheets, premoulded pipe seals, prefabricated expansion joint

covers, and other materials required for a complete warrantable roof

installation.

10. Provide Vycor ultra ice and water shield on continuous underlayment to

prevent secondary water encroachment.

7.5 07410: EXTERIOR METAL WALL SYSTEM

A. METAL SOFFIT PANELS: Provide factory-formed metal soffit panels designed

to be field assembled by lapping and interconnecting side edges of adjacent panels

and mechanically attaching through panel to supports using concealed fasteners

and factory-applied sealant in side laps. Include accessories required for weather

tight installation.

7.6 07413: COMPOSITE METAL WALL PANELS

A. PANEL MATERIALS:

Aluminum Sheet: Coil-coated sheet, ASTM B 209, alloy as standard with

manufacturer, with temper as required to suit forming operations and structural

performance required. Surface: Smooth, flat finish

B. MISCELLANEOUS METAL FRAMING

1. Miscellaneous Metal Framing, General: Refer to Division 5 Section “Cold

Formed Metal Framing” for additional requirements.

2. Subgirts: Manufacturer's standard C- or Z-shaped sections 0.064-inch nominal

thickness.

3. Zee Clip, Angles, Channels: 0.079-inch nominal thickness.

4. Cold-Rolled Furring Channels: Minimum 1/2-inch- wide flange.

5. Fasteners for Miscellaneous Metal Framing: Of type, material, size, corrosion

resistance, holding power, and other properties required to fasten

miscellaneous metal framing members to substrates

C. MISCELLANEOUS MATERIALS

Page 43: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

1. Aluminum Extrusions: ASTM B 221 (ASTM B 221M), alloy and temper

recommended by manufacturer for type of use and finish indicated.

2. Fasteners: Self-tapping screws, bolts, nuts, self-locking rivets and bolts, end-

welded studs, and other suitable fasteners designed to withstand design loads.

Provide exposed fasteners with heads matching color of metal-faced

composite wall panels by means of plastic caps or factory applied coating.

Provide EPDM, PVC, or neoprene sealing washers

D. METAL-FACED COMPOSITE WALL PANELS

Provide factory-formed and -assembled metal-faced composite wall panels

fabricated from two metal facings bonded, using no glues or adhesives, to solid

extruded thermoplastic core; formed into profile for installation method indicated.

Include attachment system components and accessories required for weathertight

system.

7.7 07900: JOINT SEALANTS

A. MATERIALS:

1. Silicon Sealant: Use as a general purpose, neutral cure sealant. Contractor

must guarantee watertightness of all joints even during strong winds. Use also

as sealant for acoustic-treated walls in between classrooms.

2. Co-Polymer Clear Sealant: For roofs, awnings, roof flashings, skylights,

gutters and downspouts.

3. Solvent-Based Synthetic Rubber Contact Type Adhesive: For bonding wood,

plastic laminate, concrete, steel aluminum and hardwood, rubber and glass.

4. Acrylic Latex Gap Sealant: For use between windows or door frames and

walls, along skirting boards, around cornices, between countertops and

splashboard. In corner or between the wall and ceiling or where shrinkage or

movement causes rigid fillers to crack.

5. Acid Cure Silicon: For use on non-porous surfaces such as glass, ceramics and

porcelain.

B. SEALANTS:

Products listed in Section 07900 are approved. Substitutions are permitted.

Color(s) will be selected from manufacturer's standard and premium line.

1. JS-1: Urethane Architectural Sealant; 2 part, non-sag, movement capability

plus or minus 50 percent. ASTM C920, Type M, Grade NS, Class 50.

Page 44: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

2. JS-2: Urethane Self Leveling Paving Sealant; Traffic Bearing, 2 part,

movement capability plus/minus 25 percent. ASTM C920, Type M, Grade P,

Class 25. USDA approved.

3. JS-3: Urethane Non-Sag Paving Sealant, Slope Grade; Traffic Bearing,

movement capability plus or minus 25 percent. ASTM C920, Type M, Grade

NS, Class 25.

4. JS-4: Silicone Architectural Sealant; one part, movement capability plus 100

percent minus 50 percent. ASTM C920, Type S, Grade NS, Class 100/50.

5. JS-5: Paintable silicone Sealant; one part, movement capability plus or minus

25 percent; ASTM C920, Type S, Grade NS, Class 25.

6. JS-6: Silicone Sanitary Sealant; one part, movement capability plus or minus

25 percent, fungus resistant; ASTM C920, Type S, Grade NS, Class 25.

7. JS-7: Acrylic Latex Sealant; one part, fungus resistant, paintable; ASTM

C834, Type P, Grade NF. USDA approved.

8. JS-8: Silicone Sanitary Sealant; one part, no bacterial growth; ASTM C920,

Type S, Grade NS, Class 50. USDA approved.

9. JS-9: Pre-compressed Expanding Foam Sealant; movement capability of plus

or minus 25 percent. Color: Black.

10. JS-10: Pre-compressed Expanding Foam Sealant; high density polyurethane,

impregnated with polymer modified acrylic and faced with factory applied

silicone. Movement capability plus or minus 25 percent; Emseal; ColorSeal.

11. JS-11: High Containment Shrink Wrap: Heat shrink tubing, medium duty

tubing, NP-700md, medium duty polyolefin tubing. Coordinate locations and

lengths with High Containment penetration details.

12. JS-12: High Containment Structural Silicone Sealant: one component high

strength, neutral cure silicone sealant GE SilPruf SCS2000.

C. ACCESSORIES

1. Joint Primers and Cleaner: Non-corrosive and non-staining.

2. Joint Backing: Pre-formed compressible type, ASTM C 1330, Type C, closed-

cell material with a surface skin. Open-cell material is not acceptable. Size

joint backing so that when installed, backing will compress approximately 30

percent. Backing shall not out-gas when punctured or ruptured.

3. Bond Breaker: Pressure sensitive tape. 4. Joint Insulation: Glass fiber for

friction fit in voids.

Page 45: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

8.1 DOORS AND WINDOWS

8.2 08114: CUSTOM STEEL DOORS AND FRAMES

A. MATERIALS

1. Cold-Rolled Steel Sheet: ASTM A 1008/A 1008M, Commercial Steel (CS),

Type B; suitable for exposed applications.

2. Hot-Rolled Steel Sheet: ASTM A 1011/A 1011M, Commercial Steel (CS),

Type B; free of scale, pitting, or surface defects; pickled and oiled.

3. Frame Anchors: ASTM A 591/A 591M, Commercial Steel (CS), 4 0Z coating

designation; mill phosphatised

i. For anchors built into exterior walls, steel sheet complying with ASTM A

1008/A 1008M or ASTM A 1011/A 1011M, hot-dip galvanized according

to ASTM A 153/A 153M, Class B

4. Inserts, Bolts, and Fasteners: Hot-dip galvanized according to ASTM A 153/A

153M.

5. Powder-Actuated Fasteners in Concrete: Fastener system of type suitable for

application indicated, fabricated from corrosion-resistant materials, with clips

or other accessory devices for attaching hollow metal frames of type indicated.

6. Grout: ASTM C 476, except with a maximum slump of 100 mm (4 inches), as

measured according to ASTM C 143/C 143M.

B. DOORS AND FRAMES

1. Exterior Doors: ANSI A250.8 Level 3 (extra heavy duty) 16 gauge, Model 2

(seamless hollow steel); with manufacturer’s standard insulating core. Loose-

fill and urethane are not acceptable

2. Interior Non-Rated Doors [and Panels]: ANSI A250.8 Level 2 (heavy duty),

18-gauge Model 2 (seamless hollow steel); core of vertical steel stiffeners and

manufacturer's standard sound deadener, except that loose-fill and urethane are

not acceptable.

3. Interior Fire Rated Doors: ANSI A250.8 Level 2 (heavy duty), 18 gauge, Model

2 (seamless hollow steel); mineral fiberboard core.

4. Interior Acoustical Doors: ANSI A250.8 Level 3 (extra heavy duty), Model 2

(seamless hollow steel); STC rating [45], ASTM E90.

5. Exterior Frames: Level 4, 14 gauge.

6. Interior Frames: Level 3, 16 gauge

C. ACCESSORIES

1. Glazing Stops: Minimum 21-gauge steel channel shape, butted or mitered

corners; prepared for countersunk screws, minimum of two screws per side.

2. Anchors: Minimum 3 wall anchors per jamb, appropriate for wall construction;

floor anchors or additional wall anchors as required.

Page 46: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

D. FINISH

8.3 08125: INTERIOR ALUMINUM FRAMES

A. COMPONENTS

1. Aluminum Framing, General: ASTM B 221, Alloy 6063-T5 or alloy and

temper required to suit structural and finish requirements, not less than 0.062

inch thick.

2. Door Frames: Reinforced for hinges and strikes.

a) Fabricate frame members for 90-minute fire-protection rating with

interior cold- formed, primed, steel liner

3. Glazing Frames: For glazing thickness indicated.

4. Ceiling Tracks: Extruded aluminum.

5. Trim: Extruded aluminum, not less than 0.062-inch-thick, with removable

snap-in casing trim, glazing stops and door stops without exposed fasteners.

B. ACCESSORIES

1. Fasteners: Aluminum, nonmagnetic stainless-steel or other non-corrosive

metal fasteners compatible with frames, stops, panels, reinforcement plates,

hardware, anchors, and other items being fastened.

2. Sound Seals: Manufacturer's standard continuous mohair, wool pile, or vinyl

seals.

3. Smoke Seals: Intumescent strip or fire-rated gaskets.

4. Glazing Gaskets: Manufacturer's standard extruded or molded plastic, to

accommodate glazing thickness indicated.

5. Glazing: Comply with requirements in Division 8 Section "Glazing."

6. Hardware: Comply with requirements in Division 8 Section “Door Hardware”.

C. ALUMINUM FINISHES

1. General: Comply with NAAMM's "Metal Finishes Manual for Architectural

and Metal Products" for recommendations for applying and designating

finishes.

2. Finish designations prefixed by AA comply with the system established by the

Aluminum Association for designating aluminum finishes.

3. Class II, Clear Anodic Finish: AA-M12C22A31 (Mechanical Finish:

nonspecular as fabricated; Chemical Finish: etched, medium matte; Anodic

Coating: Architectural Class II, clear coating 0.010 mm or thicker) complying

with AAMA 611.

8.4 08211: FLUSH WOOD DOORS

A. DOOR AND TRANSOM PANEL CONSTRUCTION

Page 47: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

1. Unless otherwise shown, scheduled or specified, doors and panels shall be 1

3/4-inch-thick, solid core.

2. Non-Rated: AWI Section 1300, Type PC-5 (Hot Press, 5 ply); particleboard

core.

3. Fire Rated: AWI Section 1300, Type FD as required for rating shown or

scheduled;

4. Special Function: AWI Section 1300, Type SR - Sound Retardant (Acoustical)

5. Facing Adhesive: AWI Type II or better for assembling core parts; Type I for

bonding faces and crossbands to core.

6. Low-emitting Materials: Provide doors made with adhesives and composite

wood products that do not contain urea-formaldehyde resins.

B. FACE VENEER

1. Wood Veneer Facing for Transparent Finish: AWI Custom quality species

Birch wood, [plain sliced with matched grain, end matched transoms, selected

for uniform color and grain in coordination with Section 06 40 16.

2. Facing for Opaque Finish: ANSI A 135.4, medium density overlay.

3. Cross Banding Behind Laminate Finish: Manufacturer's option.

C. ACCESSORIES

1. Glazing Stops: Wood, of same species as door facing. Fire rated light kit with

wood veneer to match door, for rated doors. Mitered corners; prepared for

countersunk style tamper resistant fasteners.

D. FINISH

1. Finish in accordance with AWI System Catalyzed Polyurethane Custom

grade. Apply wood filler if required. Sand surfaces smooth and set exposed

nails and screws. Apply wood filler in exposed nail and screw indentations.

On items to receive transparent finishes, use wood filler to match surrounding

surfaces and of types recommended for applied finishes. Finish to color and

sheen selected, or to match A/E's sample.

2. Wood Doors for Opaque Finish: Primer paint for field applied finish.

8.5 08311: ACCESS DOORS

A. ACCESS DOORS

Page 48: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

1. At Gypsum Board Ceilings: Steel door lined with 9mm (3/8 inch) mineral

fiberboard; steel frame; concealed pivot hinge or piano hinge.

a) In high moisture, containment areas, animal holding areas, cagewash

areas; use stainless steel with gasketing all sides

2. At Concealed Grid Acoustical Tile Ceilings: Steel door designed to receive

acoustical tile without use of adhesive; steel frame; concealed pivot hinge or

piano hinge.

8.6 08411: ALUMINUM-FRAMED ENTRANCES

A. MATERIALS

1. Extruded Aluminum: ASTM B221, 6063 alloy, T5 temper

2. Sheet Aluminum: ASTM B209: Minimum thickness; 0.050 inch.

3. Stainless Steel: AISI Type 302 or 304.

4. Carbon Steel: ASTM A36.

5. Fastenings:

a) Aluminum to Aluminum: Aluminum or stainless steel.

b) Aluminum to Stainless or Carbon Steel: Stainless steel or zinc plated

steel.

c) Stainless Steel to Stainless Steel: Stainless steel.

d) Carbon Steel to Carbon Steel: Stainless steel or zinc plated stee

6. Sealants: For sealants integral with assembly, use polyurethane, or silicone

type, as appropriate for condition.

7. Internal Reinforcing: Galvanized sheet steel, ASTM A653/A653M or

galvanized rolled steel shapes, in gauge and profile to provide required

strength and stiffness.

8. Touch-Up Primer for Galvanized Surfaces: FS TT-P-641G.

9. Glazing Gaskets: Pre-formed closed cell elastomer.

10. Weatherstripping: Continuous wool pile.

11. Shim Space Insulation: Glass fiber

B. MANUFACTURED UNITS

1. Frames: Dimensions and profiles indicated; flush glazing stops to provide

proper bite on glass and infill panels; drilled drainage holes, deflector plates

and internal flashings to accommodate internal weep drainage system.

2. Doors: 45 mm (1 3/4-inch-thick), wide stiles, [1 15/16] [3 1/2] [5] inch vertical

stiles, [2 1/2] [3 1/2] [6 1/2] inch top rail, 12-inch bottom rail; square snap-in

style glazing stops, sized to fit specified glass.

Page 49: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

3. Panels: Outer face of 0.050 gauge aluminum with glass fiber insulation core

with R value of [ ] [7.5]; Inner face of 0.050 gauge aluminum. Form corners

with sharp arris.

C. FINISH HARDWARE SCHEDULE

See Section 08710 – Door Hardware

D. FINISHES

1. Comply with NAAMM "Metal Finishes Manual" for recommendations

relative to applying and designating finishes.

2. Finish designations prefixed by AA conform to the system established by the

Aluminum Association for designating aluminum finishes.

3. Color: As selected by Architect from the full range of industry colors and color

densities

8.7 08520: ALUMINUM WINDOWS

A. MATERIALS

1. Aluminum Extrusions: Provide alloy and temper recommended by

manufacturer for strength, corrosion resistance, and application of required

finish, but not less than 22,000- psi (150-MPa) ultimate tensile strength and

not less than 0.062 inch (1.6 mm) thick at any location for main frame and

sash members.

a) Reinforcement: Where fasteners screw anchor into aluminum less than

0.125 inch (3.2 mm) thick, reinforce interior with aluminum or

nonmagnetic stainless steel to receive screw threads or provide standard,

noncorrosive, pressed-in, splined grommet nuts.

b) Exposed Fasteners: Except where unavoidable for application of

hardware, do not use exposed fasteners. For application of hardware, use

fasteners that match finish of member or hardware being fastened, as

appropriate.

2. Fasteners: Provide aluminum, nonmagnetic stainless steel, epoxy adhesive, or

other materials warranted by manufacturer to be noncorrosive and compatible

Page 50: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

with aluminum window members, trim, hardware, anchors, and other

components of window units.

3. Anchors, Clips, and Window Accessories: Fabricate anchors, clips, and

window accessories of aluminum, nonmagnetic stainless steel, or hot-dip zinc-

coated steel or iron complying with requirements of ASTM B 633; provide

sufficient strength to withstand design pressure indicated.

4. Compression-Type Glazing Strips and Weatherstripping: Unless otherwise

indicated, and at manufacturer's option, provide compressible stripping for

glazing and weatherstripping such as molded EPDM or neoprene gaskets

complying with ASTM D 2000 Designation 2BC415 to 3BC620, or molded

PVC gaskets complying with ASTM D 2287, or molded expanded EPDM or

neoprene gaskets complying with ASTM C 509, Grade 4.

5. Sliding-Type Weatherstripping: Provide woven-pile weatherstripping of

wool, polypropylene, or nylon pile and resin-impregnated backing fabric.

Comply with AAMA 701.2.

a) Provide stripping with integral centerline barrier fin of semirigid plastic

sheet of polypropylene.

6. Sealant: For sealants required within fabricated window units, provide type

recommended by manufacturer for joint size and movement. Sealant shall

remain permanently elastic, nonshrinking, and nonmigrating. Comply with

Division 7 Section "Joint Sealants" of these Specifications for selection and

installation of sealants.

B. HARDWARE

1. General: Provide manufacturer's standard hardware fabricated from

aluminum, stainless steel, or other corrosion-resistant material compatible

with aluminum and of sufficient strength to perform the function for which it

is intended.

2. Four-Bar Friction Hinges: Comply with AAMA 904.1.

a) Friction Shoes: Provide friction shoes of nylon or other nonabrasive,

nonstaining, noncorrosive, durable material.

C. ACCESSORIES

1. Exterior Louver Units: Where indicated, provide exterior, fixed, extruded-

aluminum, solarshade louver units, of type recommended by manufacturer for

Page 51: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

application on roof dormers. Provide main extrusion members of 0.062-inch-

(1.6-mm-) minimum wall thickness.

2. Weatherstripping: Provide sliding-type weatherstripping where sash rails slide

horizontally or vertically along unit frame. Provide compression-type

weatherstripping at perimeter of each operating sash where sliding type is

inappropriate.

a) Provide weatherstripping locked into extruded grooves in sash.

D. AWNING WINDOWS

1. Window Grade and Class: Comply with requirements of AAMA Grade and

Performance Class A-C20.

2. Hardware: Provide the following equipment and operating hardware:

a) Operating Device: Push-bar-type operator located on jamb at sill.

b) Hinges: Concealed 4-bar friction hinges (2 per ventilator) located on each

jamb near top rail. Ventilator operation shall permit inside cleaning of

outside glass face.

c) Lock: Combination lever handle and cam-action lock with concealed pawl.

E. HORIZONTAL-SLIDING WINDOWS

1. Window Grade and Class: Comply with requirements of AAMA Grade and

Performance Class HS-AW40. Window units shall successfully pass operating

force test performance requirements specified in AAMA 101 and life-cycle

test requirements specified in AAMA 910.

a) Provide window units with sash that can be removed from inside for

cleaning.

2. Hardware: Provide the following operating hardware:

a) Sash Rollers: Steel, lubricated ball-bearing rollers with nylon tires.

b) Sash Rollers: Nylon rollers.

c) Lock: Cam-action sweep sash lock and keeper at meeting rails.

d) Lock: Spring-loaded snap-type lock at jambs (2 per sash)

e) Lock: Spring-loaded plunger lock on meeting rail (2 per sash).

F. FIXED WINDOWS

1. Window Grade and Class: Comply with requirements of AAMA Grade and

Performance Class F-AW40.

G. FINISHES

Page 52: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

1. Comply with NAAMM "Metal Finishes Manual" for recommendations

relative to applying and designating finishes.

2. Finish designations prefixed by AA conform to the system established by the

Aluminum Association for designating aluminum finishes.

3. Finish aluminum windows to match other aluminum components of curtain

wall system.

4. Refer to Division 8 Section "Glazed Aluminum Curtain Walls" for finish

requirements.

5. Class I, Color Anodic Finish: AA-M12C22A42/A44 (Mechanical Finish:

nonspecular as fabricated; Chemical Finish: etched, medium matte; Anodic

Coating: Architectural Class I, integrally colored or electrolytically deposited

color coating 0.018 mm or thicker) complying with AAMA 606.1 or AAMA

608.1.

a) Color: As selected by Architect from the full range of industry colors

and color densities.

8.8 08710: DOOR HARDWARE

A. HINGES, GENERAL

1. Quantity: Provide the following:

a) Three Hinges: For doors with heights 61 to 90 inches, add one hinge for

each additional 30 inches in height, or any fraction thereof..

b) Nonremovable Pins: Provide set screw in hinge barrel that, when

tightened into a groove in hinge pin, prevents removal of pin while door

is closed; for the following applications:

i. Out-swinging doors with lockets.

2. Template Requirements: Provide only template-produced units.

3. Hinge Weight: Provide the following:

a) Doors with Closers: Heavy-weight ball bearing hinges.

b) Interior Doors: Standard-weight ball bearing hinges

4. Hinge Base Metal: Provide the following:

a) Exterior Hinges: Stainless steel, with stainless-steel pin.

b) Interior Hinges: Stainless steel, with stainless-steel pin.

c) Hinges for Fire-Rated Assemblies: Stainless steel, with stainless-steel

pin.

5. Fasteners: Comply with the following:

a) Machine Screws: For metal doors and frames. Install into drilled and

tapped holes.

b) Wood Screws: For wood doors.

Page 53: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

c) Threaded-to-the-Head Wood Screws: For fire-rated wood doors

B. HINGES

1. Butts and Hinges: BHMA A156.1

2. Template Hinge Dimensions: BHMA A156.7.

3. Provide shims and shimming instructions for proper door adjustment

C. LOCKS AND LATCHES, GENERAL

1. Accessibility Requirements: Where indicated to comply with accessibility

requirements, comply with BP 344 Accessibility Law

2. Latches and Locks for Means of Egress Doors: Comply with NFPA 101.

Latches shall not require more than 15 lbf to release the latch. Locks shall not

require use of a key, tool, or special knowledge for operation.

3. Lock Trim

a) Levers: Cast to match Schlage 17 lever

b) Escutcheons (Roses): Wrought to match Schlage A rose.

4. Strikes: Manufacturer's standard strike with strike box for each latchbolt or

lock bolt, with curved lip extended to protect frame, finished to match door

hardware set.

D. KEYING

1. Keying System: Factory registered, complying with guidelines in BHMA

A156.28, Appendix A. Incorporate decisions made in keying conference, and

as follows:

a) Master key or grand master key locks as directed by Owner.

2. Keys: Nickel silver

a) Stamping: Permanently inscribe each key with a visual key control

number.

b) Quantity: Provide the following:

i. Master Keys: Three (3)

ii. Duplicate Keys: Five (5)

E. CLOSERS, GENERAL

1. Accessibility Requirements: Where handles, pulls, latches, locks, and other

operating devices are indicated to comply with accessibility requirements,

comply with BP 344 Accessibility Law

Page 54: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

a) Comply with the following maximum opening-force requirements:

i. Interior, Non-Fire-Rated Hinged Doors: 5 lbf applied

perpendicular to door.

ii. Fire Doors: Minimum opening force allowable by authorities

having jurisdiction.

b) Door Closers for Means of Egress Doors: Comply with NFPA 101. Door

closers shall not require more than 30 lbf to set door in motion and not

more than 15 lbf to open door to minimum required width.

F. CLOSERS

1. Closers: BHMA A156.4, Grade 1.

a) All closers shall have solid forged steel main arms (and forged forearms

for parallel arm closers).

b) All surface mounted mechanical closers shall be certified to exceed ten

million (10,000,000) full load cycles by a recognized independent testing

laboratory.

c) Closers will have Powder coating finish certified to exceed 100 hours

salt spray testing by ETL, an independent testing laboratory used by

BHMA for ANSI certification.

d) Door closers shall have fully hydraulic, full rack and pinion action with

a high strength cast iron cylinder. Cylinder body shall be 1 ½” in

diameter, and double heat treated pinion shall be 11/16” in diameter with

double D slab drive arm connection.

e) Hydraulic fluid shall be of a type requiring no seasonal closer adjustment

for temperatures ranging from 120 degrees F to –30 degrees F.

2. Surface Closers: BHMA A156.4, Grade 1. Provide type of arm required for

closer to be located on non-public side of door, unless otherwise indicated.

G. STOPS AND HOLDERS

1. Stops and Bumpers: BHMA A156.16, Grade 1.

2. Provide wall stops for doors unless other type stops are scheduled or indicated.

At openings where wall stops are inappropriate a “stop arm closer” at outswing

doors or an overhead stop at in swing doors shall be used.

H. DOOR GASKETING

1. Standard: BHMA A156.22. Listed under Category J in BHMA's "Certified

Product Directory."

Page 55: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

2. General: Provide continuous weather-strip gasketing on exterior doors.

Provide noncorrosive fasteners for exterior applications and elsewhere as

indicated.

3. Fire-rated Doors, Resilient Seals: UL10C/UBC-7-2 compliant. Coordinate

with selected door manufacturers and selected frame manufacturer’s

requirements.

I. SCHEDULED HARDWARE

1. Requirements for design, grade, function, finish, size, and other distinctive

qualities of each type of finish hardware are indicated in the "Hardware

Schedule" at the end of this Section. Products are identified by using hardware

designation numbers of the following:

a) Manufacturer's Product Designations: The product designation and

name of one manufacturer are listed for each hardware type required for

the purpose of establishing minimum requirements. Provide a product

from the list specified. The Article "Manufacturers" in Part 2 for each

hardware type.

2. ANSI/BHMA designations used elsewhere in this Section or in schedules to

describe hardware items or to define quality or function are derived from the

following standards. Provide products complying with these standards and

requirements specified elsewhere in this Section.

a) Butts and Hinges: ANSI/BHMA A156.1.

b) Bored and Preassembled Locks and Latches: ANSI/BHMA A156.2.

c) Exit Devices: ANSI/BHMA A156.3.

d) Door Controls - Closers: ANSI/BHMA A156.4.

e) Auxiliary Locks and Associated Products: ANSI/BHMA A156.5.

f) Architectural Door Trim: ANSI/BHMA A156.6.

g) Template Hinge Dimensions: ANSI/BHMA A156.7.

h) Door Controls - Overhead Holders: ANSI/BHMA A156.8.

i) Interconnected Locks and Latches: ANSI/BHMA A156.12.

j) Mortise Locks and Latches: ANSI/BHMA A156.13.

k) Sliding and Folding Door Hardware: ANSI/BHMA A156.14.

l) Closer Holder Release Devices: ANSI/BHMA A156.15.

m) Auxiliary Hardware: ANSI/BHMA A156.16.

n) Self-Closing Hinges and Pivots: ANSI/BHMA A156.17.

o) Materials and Finishes: ANSI/BHMA A156.18.

J. HINGES, BUTTS, AND PIVOTS

Page 56: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

1. Templates: Except for hinges and pivots to be installed entirely (both leaves)

into wood doors and frames, provide only template-produced units.

2. Screws: Provide Phillips flat-head screws complying with the following

requirements:

a) For metal doors and frames install machine screws into drilled and

tapped holes.

b) For wood doors and frames install wood screws.

c) For fire-rated wood doors install #12 x 1-1/4-inch, threaded-to-the-

head steel wood screws.

d) Finish screw heads to match surface of hinges or pivots.

3. Hinge Pins: Except as otherwise indicated, provide hinge pins as follows:

a) Out-Swing Exterior Doors: Nonremovable pins.

b) Out-Swing Corridor Doors with Locks: Nonremovable pins.

c) Interior Doors: Nonrising pins.

4. Number of Hinges: Provide number of hinges indicated but not less than 3

hinges per door leaf for doors 90 inches or less in height and one additional

hinge for each 30 inches of additional height

K. LOCK CYLINDERS

1. Lock Cylinders: Tumbler type, constructed from brass or bronze, stainless

steel, or nickel silver. Same manufacturer as for locking devices.

2. Standard Lock Cylinders: BHMA A156.5; Grade 1; permanent cores that are

interchangeable; face finished to match lockset.

3. High-Security Lock Cylinders: BHMA A156.30; Grade 1; Type M,

mechanical; permanent cores that are removable; face finished to match

lockset.

4. Construction Master Keys: Provide cylinders with feature that permits

voiding of construction keys without cylinder removal.

L. WEATHERSTRIPPING AND SEALS

1. General: Provide continuous weatherstripping on exterior doors and smoke,

light, or sound seals on interior doors where indicated or scheduled. Provide

noncorrosive fasteners for exterior applications and elsewhere as indicated.

2. Replaceable Seal Strips: Provide only those units where resilient or flexible

seal strip is easily replaceable and readily available from stocks maintained by

manufacturer.

3. Weatherstripping at Jambs and Heads: Provide bumper-type resilient insert

and metal retainer strips, surface applied unless shown as mortised or

semimortised, and of following metal, finish, and resilient bumper material:

Page 57: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

a) Extruded aluminum with natural anodized finish, 0.062-inch minimum

thickness of main walls and flanges.

b) Extruded aluminum with color anodized finish as selected from

manufacturer's standard color range, 0.062-inch minimum thickness of

main walls and flanges.

c) Extruded bronze (brass), finish to match frame, 0.050-inch minimum

thickness of main walls and flanges.

d) Sponge neoprene conforming to MIL R 6130, Class II (Closed Cell).

e) Expanded neoprene: Cellular rubber conforming to ASTM D 1056

Type 2 (closed-cell); Class B (low-swell, oil-resistant); Grade 2

(compressiondeflection of 5 - 9 psi); and self-extinguishing in

following size:

i. 5 mm x 16 mm (3/16 x 5/8 inch).

ii. 6.35 mm x 19 mm (1/4 x 3/4 inch). I

iii. 9.5 mm x 32 mm (3/8 x 1-1/4 inches)

f) Solid neoprene conforming to MIL R 6855, Class II, Grade 40.

g) Flexible vinyl hollow bulb or loop insert.

h) Brush pile insert of polypropylene or nylon woven pile and aluminum

strip backing complying with AAMA 701.2.

4. Weatherstripping at Door Bottoms: Provide threshold consisting of contact-

type resilient insert and metal housing of design and size shown and of

following metal, finish, and resilient seal strip:

a) Extruded aluminum with natural anodized finish, 0.062-inch minimum

thickness of main walls and flanges.

b) Extruded aluminum with color anodized finish as selected from

manufacturer's standard color range, 0.062-inch minimum thickness of

main walls and flanges.

c) Extruded bronze (brass) finished to match doors, 0.050-inch minimum

thickness of main walls and flanges.

d) Solid neoprene wiper or sweep seal complying with MIL R 6855, Class

II, Grade 40.

e) Flexible vinyl wiper or sweep seal strip.

f) Brush pile insert of polypropylene or nylon woven pile and aluminum

strip backing complying with AAMA 701.2.

8.9 08800: GLAZING

A. MANUFACTURERS

1. PRIMARY FLOAT GLASS MANUFACTURERS

2. INSULATING UNIT FABRICATORS

Page 58: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

3. FIRE RATED LAMINATED GLASS MANUFACTURERS- Comply with

CPSC 16 CFR 1201 Category II, Impact safety.

4. Or other approved equal

B. GLASS MATERIALS, GENERAL REQUIREMENTS

1. Comply with ASTM C1036 (for untreated glass) and C1048 (for heat treated

tempered glass), respectively, for types, classes, styles, kinds, forms, qualities,

dimensional tolerances and other applicable requirements.

2. Except as otherwise shown or specified, glass shall be clear; flat, glazing select

quality q3, vertical vision float glass, polished; 6.35 mm (1/4 inch) thick.

3. Factory label each factory cut light of glass. Do not remove labels until

approved. Labels on glass surfaces which will be inaccessible after installation

may be removed prior to installation, providing glass is certified to be as

specified.

4. Limit localized roll distortion to 0.127 mm (0.005 inch).

5. All tinted glass of each color shall be by the same manufacturer.

C. SEALED INSULATING GLASS UNITS

1. Standard: ASTM E774 for CBA units and IGMA TM-3000.Fabrication:

Factory assembled double glass units with space filled with argon and dual-

sealed finished edges with primary seal of polyisobutylene and secondary seal

of silicone. Insulated glass with dehydrated air is not preferred due to lower

CRF (insulation values).

2. Metal Spacers: Thermally broken warm edge spacer, aluminum, mill finish,

with polyurethane thermal barrier to eliminate thermal bridge.

D. HEAT MIRROR INSULATING GLASS

1. Substitutions are permitted subject to review of substitute insulating values

and approval by Owner.

2. Fabrication - Standard Units: Where indicated; sealed insulating glass units

with suspended substrate inner layer with wavelength-selective coating.

Provide dual dehydrated air spaces. Provide edge barrier to protect exposed

perimeter sealant from ultraviolet radiation.

3. Metal Spacers: Thermally broken warm edge spacer, aluminium

E. GLAZING COMPOUNDS

Page 59: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

1. Glazing Compound: Modified oil type, non-hardening, knife grade

consistency. Color unselected if painted, or tinted to match adjoining wood if

not painted.

2. Butyl Sealant: Single component; black color; non-skinning.

3. Acrylic Sealant: Single component, solvent curing, cured Shore A hardness of

35; non-bleeding; color as selected from manufacturer's standards.

4. Silicone Sealant: Single component, capable of water immersion without loss

of properties; non-bleeding; non-staining; cured Shore A hardness of 15-25;

color as selected from manufacturer's standards.

5. Structural Sealant: ASTM C 1184, neutral-curing silicone formulation

compatible with system components with which it comes in contact,

specifically formulated and tested for use as structural sealant, and approved

by structural-sealant manufacturer for use in curtain-wall systems indicated

for exterior butt glazed mullions.

a) Color: As selected by Architect from manufacturer's full range of

colors.

b) Type: Single component.

c) Minimum Tensile Strength and Modulus of Elasticity: As required by

structural-sealantglazed curtain-wall system design to meet

performance requirements. Sealant shall withstand tensile and shear

stresses imposed by system without failing adhesively or cohesively

and shall remain permanently elastic, nonshrinking, and nonmigrating.

Field Applied Dow Corning Structural Silicone 995 or other as

recommended by manufacturer. [For all blast resistant window units,

provide minimum 1/4 inch wide bead.]

F. GLAZING ACCESSORIES

1. Setting Blocks: Neoprene; 70-90 Shore A durometer hardness; size as

required.

a) For Fire Rated Glass: Use calcium silicate setting blocks of size

recommended by glass manufacturer

2. Spacer Shims: Neoprene; 50 Shore A durometer hardness; size as required. 3.

Glazing Tape: Pre-formed butyl compound with integral resilient tube spacing

device; 15-18 Shore A durometer hardness; coiled on release paper; size as

required; black color.

a) For Fire Rated Glass: Use EPDM tape or other listed flame resistant

gasket material recommended by glass manufacturer

3. Extruded Glazing Strips: As furnished by other Sections. 5. Glazing Clips:

Manufacturer's standard type.

Page 60: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

G. MIRROR ASSEMBLIES

1. Mirror Glass: Clear float tempered safety type, q2 mirror quality, with copper

and silver coating, organic overcoating, 1/4 inch thick. Make unframed edges

square cut and beveled.

2. Mirror Adhesive: As recommended by mirror manufacturer

3. Mounting accessories:

a) Stainless steel glass clamps with concealed fasteners.

b) Stainless steel angle backing trim.

8.10 08911: GLAZED ALUMINUM CURTAIN WALLS

A. MATERIALS

1. Aluminum: Alloy and temper recommended by manufacturer for type of use

and finish indicated.

a) Sheet and Plate: ASTM B 209

b) Extruded Bars, Rods, Shapes, and Tubes: ASTM B 221.

c) Extruded Structural Pipe and Tubes: ASTM B 429.

2. Steel Reinforcement: With manufacturer's standard corrosion-resistant primer

complying with SSPC-PS Guide No. 12.00 applied immediately after surface

preparation and pretreatment. Select surface preparation methods according to

recommendations in SSPC-SP COM and prepare surfaces according to

applicable SSPC standard.

a) Structural Shapes, Plates, and Bars: ASTM A 36/A 36M.

b) Cold-Rolled Sheet and Strip: ASTM A 611.

c) Hot-Rolled Sheet and Strip: ASTM A 570/A 570M.

B. FRAMING

1. Framing Members: Manufacturer’s standard extruded-or formed-aluminum

framing members of thickness required and reinforced as required to support

imposed loads.

a) Construction: Thermally broken.

b) Glazing System: Retained mechanically with gaskets on four sides.

c) Glazing Plane: Front

Page 61: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

2. Brackets and Reinforcements: Manufacturer's standard high-strength

aluminum with nonstaining, nonferrous shims for aligning system

components.

3. Fasteners and Accessories: Manufacturer's standard corrosion-resistant, non-

staining, nonbleeding fasteners and accessories compatible with adjacent

materials.

a) Where fasteners are subject to loosening or turn out from thermal and

structural movements, wind loads, or vibration, use self-locking

devices.

b) Reinforce members as required to receive fastener threads.

c) Where exposed fasteners are used provide countersunk, stainless steel

Phillips screw heads.

d) Finish exposed portions to match framing system.

4. Anchors: Three-way adjustable anchors that accommodate fabrication and

installation tolerances in material and finish compatible with adjoining

materials and recommended by manufacturer.

a) Concrete and Masonry Inserts: Hot-dip galvanized cast-iron,

malleable-iron, or steel inserts complying with ASTM A 123/A 123M

or ASTM A 153/A 153M requirements

5. Concealed Flashing: Dead-soft, 0.018-inch- thick stainless steel, ASTM A

240/A 240M of type recommended by manufacturer.

6. Framing Gaskets: As recommended by manufacturer for joint type, color:

black.

7. Framing Sealants: As recommended by manufacturer for joint type.

C. GLAZING SYSTEMS

1. Glazing: As specified in Division 8 Section "Glazing."

2. Glazing Gaskets: Manufacturer's standard sealed-corner pressure-glazing

system of black, resilient elastomeric glazing gaskets, setting blocks, and

shims or spacers.

3. Glazing Sealants: As recommended by manufacturer.

D. ACCESSORY MATERIALS

1. Perimeter Fire-Containment Systems (Safing Insulation): Specified in

Division 7 Sections.

2. Insulating Materials: Specified in Division 7 Section "Building Insulation."

3. Bituminous Paint: Cold-applied asphalt-mastic paint complying with SSPC-

Paint 12 requirements except containing no asbestos, formulated for 30-mil

thickness per coat.

Page 62: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

E. ALUMINUM FINISHES

1. for recommendations for applying and designating finishes.

2. Finish designations prefixed by AA comply with the system established by the

Aluminum Association for designating aluminum finishes.

3. Class II, Clear Anodic Finish: AA-M12C22A31 (Mechanical Finish:

nonspecular as fabricated; Chemical Finish: etched, medium matte; Anodic

Coating: Architectural Class II, clear coating 0.010 mm or thicker) complying

with AAMA 611.

9.1 FINISHES

9.2 09111: NON-LOAD BEARING STEEL FRAMING

A. NON-LOAD-BEARING STEEL FRAMING, GENERAL

1. Framing Members, General: Comply with ASTM C 754 for conditions

indicated.

2. Steel Sheet Components: Comply with ASTM C 645 requirements for metal,

unless otherwise indicated.

B. SUSPENSION SYSTEM COMPONENTS

1. Tie Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper, 0.0625-

inch diameter wire, or double strand of 0.0475-inch diameter wire.

2. Wire Hangers: ASTM A 641/A 641M, Class 1 zinc coating, soft temper,

0.162-inch diameter.

3. Carrying Channels: Cold-rolled, commercial-steel sheet with a base-metal

thickness of 0.0538 inch and minimum 1/2-inch wide flanges.

a) Depth: As indicated on drawing partition schedule

4. Hat-Shaped, Rigid Furring Channels: ASTM C 645, 7/8 inch deep.

a) Minimum Base Metal Thickness: 0.0179 inch.

5. Resilient Furring Channels: 1/2-inch deep members designed to reduce sound

transmission.

a) Configuration: Hat shaped.

Page 63: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

6. Grid Suspension System for Ceilings: ASTM C 645, direct-hung system

composed of main beams and cross-furring members that interlock.

C. STEEL FRAMING FOR FRAMED ASSEMBLIES

1. Steel Studs and Runners: ASTM C 645.

2. Slip-Type Head Joints: Where indicated, provide the following:

a) Single Long-Leg Runner System: ASTM C 645 top runner with 2-inch

deep flanges in thickness not less than indicated for studs, installed

with studs friction fit into top runner and with continuous bridging

located within 12 inches of the top of studs to provide lateral bracing.

3. Firestop Tracks: Top runner manufactured to allow partition heads to expand

and contract with movement of the structure while maintaining continuity of

fire-resistance- rated assembly indicated; in thickness not less than indicated

for studs and in width to accommodate depth of studs.

4. Cold-Rolled Channel Bridging: 0.0538-inch bare-steel thickness, with

minimum 1/2- inch wide flanges.

a) Depth: 1-1/2 inches.

b) Clip Angle: Not less than 1-1/2 by 1-1/2 inches, 0.068-inch thick,

galvanized steel.

5. Hat-Shaped, Rigid Furring Channels: ASTM C 645.

a) Minimum Base Metal Thickness: 0.0179 inch.

b) Depth: 7/8 inch

6. Resilient Furring Channels: 1/2-inch deep, steel sheet members designed to

reduce sound transmission.

a) Configuration: Asymmetrical or hat shaped.

7. Cold-Rolled Furring Channels: 0.0538-inch bare-steel thickness, with

minimum 1/2- inch wide flanges.

a) Depth: 3/4 inch.

b) Furring Brackets: Adjustable, corrugated-edge type of steel sheet with

minimum bare steel thickness of 0.0312 inch.

c) Tie Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper,

0.0625-inch diameter wire, or double strand of 0.0475-inch diameter

wire

8. Z-Shaped Furring: With slotted or nonslotted web, face flange of 1-1/4 inches,

wall attachment flange of 7/8 inch, minimum bare-metal thickness of 0.0179

inch, and depth required to fit insulation thickness indicated.

D. AUXILIARY MATERIALS

Page 64: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

1. General: Provide auxiliary materials that comply with referenced installation

standards.

2. Fasteners for Metal Framing: Of type, material, size, corrosion resistance,

holding power, and other properties required to fasten steel members to

substrates.

9.3 09200: PLASTER

A. PLAIN CEMENT PLASTER FINISH: Consisting of the scratch and finish coats,

both consisting of one (1) part Portland cement and two (2) parts of clean, washed

sand, measured by volume. For all interior and exterior wall surfaces where

plastering is essential to complete the work.

B. WOOD TROWEL FINISH: Provide score joints whenever required. For exterior

and interior surfaces to be painted.

C. STEEL TROWEL FINISH: Provide score joints whenever required. For curbs,

catch basins, septic tank.

D. SMOOTH RUBBED FINISH: For all exposed undersides of suspended floor RC

slabs and beams and when required by the Architect. Use phenolic forms to attain

smooth surface at exposed areas.

E. TOOLED JOINT FINISH: Surface preparation shall be plain cement plaster finish

with tooled mortar joints. Joints shall be concave, clean, plumb and true to line.

All joints shall be spaced as directed by the Architect.

F. BURLAP FINISH: Achieve consistent texture pattern through proper selection of

burlap material and application of consistent pressure on surface. Provide 50mm

plain concrete borders at all edges and at approximately every 1.00 m on center,

for all exterior corridors, ramps, steps, and sidewalks.

G. PLASTERING GUIDE SYSTEM: Use for interior and exterior grooves, drip

moulds, construction joints and surface wall plastering.

9.4 09250: GYPSUM BOARD

A. PANELS, GENERAL: Size: Provide in maximum lengths and widths available

that will minimize joints in each area and that correspond with support system

indicated.

B. GYPSUM BOARD

1. General: Complying with ASTM C 36/C 36M or ASTM C 1396/C 1396M, as

applicable to type of gypsum board indicated and whichever is more stringent.

2. Type X:

a) Thickness: 5/8 inch.

b) Long Edges: Tapered.

Page 65: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

3. Ceiling Type: Manufactured to have more sag resistance than regular-type

gypsum board.

a) Thickness: 5/8 inch.

b) Long Edges: Tapered.

C. TRIM ACCESSORIES

1. Interior Trim: ASTM C 1047.

a) Material: Galvanized or aluminum-coated steel sheet, rolled zinc,

plastic, or paperfaced Galvanized steel sheet.

b) Shapes:

Cornerbead.

Bullnose bead.

V-shaped reveal; exposed long flange receives joint compound.

LC-Bead: J-shaped; exposed long flange receives joint

compound.

L-Bead: L-shaped; exposed long flange receives joint

compound.

U-Bead: J-shaped; exposed short flange does not receive joint

compound. •

Expansion (control) joint

D. JOINT TREATMENT MATERIALS

1. General: Comply with ASTM C 475/C 475M.

2. Joint Tape:

a) Interior Gypsum Wallboard: Paper.

b) Glass-Mat Gypsum Sheathing Board: 10-by-10 glass mesh.

c) Tile Backing Panels: As recommended by panel manufacturer.

3. Joint Compound for Interior Gypsum Wallboard: For each coat use

formulation that is compatible with other compounds applied on previous or

for successive coats.

E. AUXILIARY MATERIALS

1. General: Provide auxiliary materials that comply with referenced installation

standards and manufacturer's written recommendations.

2. Steel Drill Screws: ASTM C 1002, unless otherwise indicated.

3. Sound Attenuation Blankets: ASTM C 665, Type I (blankets without

membrane facing) produced by combining thermosetting resins with mineral

fibers manufactured from glass, slag wool, or rock wool.

4. Acoustical Sealant: As specified in Division 7 Section "Joint Sealants."

Page 66: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

5. Thermal Insulation: As specified in Division 7 Section "Building Insulation."

6. Vapor Retarder: As specified in Division 7 Section "Building Insulation."

7. Felts: 15 pound roofing felt.

9.5 09265: GYPSUM BOARD ASSEMBLIES

Shall comply with all quality assurance and performance standards in this Section.

A. FRAMING MATERIALS

1. Studs and Track: ASTM C645; galvanized steel: Use minimum 0.0179 inch

base metal thickness (25 ga.), except where heavier gauge is required by

ASTM C754 for fire rating or height limitations; minimum 0.0296 inch base

metal thickness (20 ga.) at partitions receiving abuseresistant board, and

minimum 0.0329 inch base metal thickness (20 ga.) at wall hung shelves and

wall hung casework. Top track shall have [2-1/2 inch extended legs to allow

for deflection of overhead construction.

2. Shaft Wall System: USG C-H studs, with J runners.

3. Furring and Accessories: ASTM C645, except use 12 gauge hanger wire.

4. Fasteners: ASTM C1002.

5. Cold-Rolled Channel Bridging: 2 mm bare-steel thickness, with minimum 13

mm wide flanges.

a) Depth: As indicated on Drawings 38.1 mm.

b) Clip Angle: Not less than 38 mm x 38 mm x 2mm thick, galvanized

steel.

B. GYPSUM BOARD MATERIALS

1. Standard Gypsum Board: ASTM C1396; 13 mm (1/2 inch) or 16 mm (5/8-

inch) thick as may be specified on drawings.

2. Fire Rated Gypsum Board: ASTM C1396; fire resistive and water resistant

type, UL rated; 13 mm (1/2 inch) or 16 mm (5/8-inch), thickness as required

for rating shown.

3. Gypsum Ceiling Board: ASTM C1396, 13 mm (1/2 inch) thick.

4. Abuse Resistant Gypsum Board: U.S. Gypsum “Fiberock Aqua-Tough

Interior Panels”, foilbacked ASTM C1278, 16 mm (5/8 inch) thick, mold

resistant, water resistant, fire resistive type, UL rated.

5. Tile Backer Board: Georgia-Pacific DensShield tile backer board, 13 mm (1/2

inch) or 16 mm (5/8-inch) Fireguard Type X tested in accordance with ASTM

D3273, with a test score of 10.

Page 67: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

C. OTHER MATERIALS

1. Fasteners: Gypsum board screws, self-drilling, self-tapping steel screws. For

steel framing less than 0.033 inch thick (generally, drywall studs), and ASTM

C954 for fastening panels to steel members from 0.033 to 0.112 inch thick

(generally, cold-formed metal framing specified in Division 5.

2. Acoustical Insulation: Sound Attenuation Blankets: ASTM C 665, Type I

(blankets without membrane facing), produced by combining thermosetting

resins with mineral fibers manufactured from glass, slag wool, or rock wool.

Fire-Resistance-Rated Assemblies: Comply with mineral-fiber requirements

of assembly.

3. Acoustical Sealant: ASTM C919, approved for fire rated designs shown.

4. Joint Materials: ASTM C475;

a) Joint Compound for Interior Gypsum Wallboard: For each coat use

formulation that is compatible with other compounds applied on

previous or for successive coats.

b) Prefilling: At open joints, rounded or beveled panel edges, and

damaged surface areas, use setting-type taping compound: USG

Durabond G90.

c) Embedding and First Coat: For embedding tape and first coat on joints,

fasteners, and trim flanges, use setting-type taping compound: USG

Durabond G90.

d) Fill Coat: For second coat, use setting-type, sandable topping

compound: USG Sheetrock Brand Topping Joint Compound Ready-

Mixed.

e) Third Coat: Same as Fill Coat.

9.6 09300: TILE

A. GROUT AND TILE COLORS AND FINISHES: Manufacturer's standards as

selected.

B. CERAMIC WALL AND FLOOR TILE: Substitutions are permitted. Refer to

Finish Schedule for locations

C. PORCELAIN TILE: Substitutions are permitted subject to Section 01 63 00. Refer

to Finish Legend on Drawings for selections. Trim Tile: Bullnose, cove base, and

other special shapes as shown or required, composition and finish to match

adjacent tile.

D. QUARRY (STONE) TILE: Manufacturers: Substitutions are permitted. Refer to

Finish Schedule for locations. Trim Tile: Bullnose, cove base and other special

shapes shown or required.

Page 68: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

E. FILL AND LEVELING COATS:

1. Cementitious Fill Under Floor Tile: 3 parts sand to one part Portland cement.

2. Portland Cement: ASTM C150, Type I.

3. Sand: ASTM C144, clean and washed, 100 percent passing 16 mesh screen.

4. Self-Leveling Underlayment Under Floor Tile Where Indicated:

Cementitious, rapid hardening compound; compressive strength at 28 days, at

least 4300 psi.

5. Lime: ASTM C207, Type S.

6. Water: Clean and potable

F. SETTING MATERIALS

1. Dry-Set Mortar: ANSI A118.1.

2. Latex-Portland Cement Mortar: ANSI A118.4.

3. Flexible Latex Modified Portland Cement: ANSI A118.4; 25 percent

minimum modulus of elongation.

G. GROUTS

1. Standard Grout: Latex Portland cement, ANSI A118.6, integrated with

silicone sealant.

2. Epoxy Grout for exterior locations.

H. WATERPROOFING MEMBRANE

1. Manufacturers: Substitutions are permitted.

2. ANSI/ASTM A118.10, Fabric-Reinforced, Fluid-Applied system consisting

of liquid-latex rubber with a VOC content of 65g/L or less when calculated

according to 400CFR059, Subpart D (EPA Method 24), and fabric

reinforcement.

I. ACCESSORIES

1. Divider and Edge Strips: Schluter Systems, stainless steel, size to

accommodate tile thickness.

2. Expansion and Control Joints: Schluter Systems, PVC, standard color(s) as

selected, size to accommodate tile thickness.

3. Welded Wire Mesh: ASTM A185, 2 x 2 inch x 16/16 gauge , galvanized.

Page 69: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

4. Thresholds: Domestic marble, white or gray color, honed finish, full width of

wall or frame opening, beveled exposed edges, complying with ASTM C 503,

with little or no veining, "Group A" as classified by the Marble Institute of

America, having an abrasive hardness of 11 per ASTM C 241, and a maximum

48-hour absorption of .145% by weight, with sand rubbed finish unless finish

otherwise selected by the Architect. Color, texture and pattern of marble as

selected by the Architect and conforming to profiles and sizes noted on the

drawings.

5. Cleaning Solution: Type which will not damage or discolor tile, joint

materials, or accessories.

6. Grout Release: As recommended by manufacturers to prevent staining of

unglazed tile by grout.

7. Primer for Gypsum Wallboard: As recommended by manufacturer of setting

materials.

9.7 09511: ACOUSTIC PANEL CEILINGS

A. DESIGN STANDARD MANUFACTURER: The basis of design is the

manufacturer listed for each type of ceiling system specified. Substitutions are

permitted subject to review and approval by the Owner.

B. ACOUSTICAL CEILING TYPE ACT-1

1. Acoustical Panels: OFFICES, CORRIDORS, Acceptable Product: Cortega

Tile & Lay-In, 824 as manufactured by Armstrong World Industries or

approved equal.

a) Surface Texture: Medium.

b) Composition: Mineral Fiber.

c) Color: White.

d) Size: 610 mm x 610 mm x 16 mm (24in x 24in x 5/8in).

e) Edge Profile: Square Lay-In for interface with Prelude XL 15/16

inch Exposed Tee.

f) Noise Reduction Coefficient (NRC): ASTM C 423; Classified with

UL label on product carton, 0.55.

g) Ceiling Attenuation Class (CAC): ASTM C 1414; Classified with

UL label on product carton, 35.

h) Articulation Class (AC): ASTM E 1111; Classified with UL label on

product carton N/A.

i) Flame Spread: ASTM E 1264; Class A (UL)

j) Light Reflectance (LR): ASTM E 1477; White Panel: Light

Reflectance: 0.82.

k) Dimensional Stability: Standard.

Page 70: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

2. Suspension System: Acceptable Product: Prelude XL 24 mm (15/16) inch

Exposed Tee as manufactured by Armstrong World Industries, Inc. or

approved equal.

a) Components: All main beams and cross tees shall be commercial

quality hot-dipped galvanized as per ASTM A 653. Main beams and

cross tees are double-web steel construction with type exposed flange

design. Exposed surfaces chemically cleansed, capping pre-finished

aluminum in baked polyester paint. Main beams and cross tees shall

have rotary stitching.

i. Structural Classification: ASTM C 635 Intermediate

Duty.

ii. Color: White and match the actual color of the selected

ceiling tile, unless noted otherwise.

b) Attachment Devices: Size for five times design load indicated in

ASTM C 635, Table 1, Direct Hung unless otherwise indicated.

c) Wire for Hangers and Ties: ASTM A 641, Class 1 zinc coating, soft

temper, prestretched, with a yield stress load of at least time three

design load, but not less than 12 gauge.

d) Edge Moldings and Trim: Metal or extruded aluminum of types and

profiles indicated or, if not indicated, manufacturer's standard

moldings for edges and penetrations, including light fixtures, that fit

type of edge detail and suspension system indicated. Provide moldings

with exposed flange of the same width as exposed runner.

C. ACCESSORIES

1. Acoustic Insulation: ASTM C665, Type I, friction fit type, unfaced; 2 inch

thick, 0.75 pcf size cut to fit acoustic system. Provide batt insulation for all

24in x 24in panel ceilings, and roll or blanket insulation for larger size panel

ceilings.

2. Hold-Down Clips: Where indicated, provide manufacturer's standard hold-

down clips spaced 24 inches OC on all cross tees.

9.8 09622: RESILIENT SPOORTS FLOOR COVERING

A. RUBBER ATHLETIC FLOORING TILE:

1. Subject to compliance with Division 1 requirements, provide: Recycled rubber

compound with Rubber wear layer and rubber shock- absorbent layer,

vulcanized together.

Page 71: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

2. Installation Method: Adhered.

3. Traffic-Surface Texture: Nondirectional, stipple texture

4. Size: Manufacturer’s standard-size square tile

5. Thickness: 10mm

6. Manufacturers: Subject to compliance with requirements, the following

manufacturers and products named are acceptable; substitutions of other

unnamed manufacturers are [permitted subject to Section 01 63 00]

Armstrong Flooring

Johnsonite Floor Products.

Manila Rubber Corporation

9.9 09680: CARPET TILE

A. CARPET TILE: Subject to approval by Owner and to requirements in Section

09680

B. ACCESSORIES

1. Concrete-Slab Primer: Nonstaining type as recommended by carpet tile

manufacturer.

2. Trowelable Leveling and Patching Compounds: Latex-modified, hydraulic-

cement-based formulation provided by or recommended by carpet tile

manufacturer.

3. Adhesives: Water-resistant, mildew-resistant, nonstaining type to suit

products and subfloor conditions indicated, that complies with flammability

requirements for installed carpet tile and that is recommended by carpet tile

manufacturer.

9.10 09900: PAINTING

A. MATERIALS

1. Use materials in accordance with the manufacturer's directions printed on the

labels unless otherwise approved by the Owner’s Representative.

2. Coatings shall have good flow and application properties; capable of drying

or curing free of streaks or sags.

3. Materials for each application shall be compatible with one another and with

other materials with which they may come in contact.

4. Provide accessory materials as recommended by coating manufacturer,

whether or not specified, as required to achieve specified finishes

5. Substitutions proposed shall include manufacturer's recommendations

regarding surface preparation, primers and rate of coverage, which may differ

from systems specified.

6. Gloss Ranges; ASTM D523:

Page 72: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

B. SURFACE PREPARATION

1. Masonry (new surface)

a) All areas to be painted must be dry and free of dirt, grease, oil, dust,

loose grit or mortar and other contaminants.

b) Treat with Concrete Neutralizer at least a week prior to painting. Apply

sufficient coats, let dry, then brush off white crystals that form on the

surface.

c) Apply one coat Concrete Primer & Sealer.

d) Fill up all hairline cracks and crevices with Concrete Putty. Allow to

dry, sand smooth, dust off, then spot prime before applying finish

coats.

2. Wood (new surface)

a) All areas to be painted must be dry and free of dirt, dust, grease, oil

and other foreign matter.

b) Sand surface until wood is smooth to touch and no slivers or rough

edges remain.

c) Dust off completely, then wipe with clean rag.

d) Apply one coat of Interior Primer & Sealer or Exterior Wood Primer.

e) Fill nail holes, cracks, dents and damaged areas with Plastic Wood

Dough or Glazing Putty

3. Metal (new surface)

a) Remove dust, dirt, grease, oil, wax, loose scales and other

contaminants by wiping with rag soaked in lacquer thinner or naphtha.

b) Sand, wire brush or scrape all rusty metal exposed to the weather for

some time.

c) Treat surface with Rust Converter. Let stand overnight, then wipe off

white residue with clean rag soaked in lacquer thinner of naphtha.

d) Apply one coat Red oxide or Red Lead or Zinc Chromate Primer. Let

dry overnight before finishing with one or two coats of recommended

topcoat.

C. COLORS

1. The following information is given to convey a general intent as to color

scheme required. Owner to accept finish colors and schemes based on mock-

up approval.

a) For most wall surfaces, one light color will be designated.

b) Deep accent colors will be designated for approximately [10] percent

of wall surfaces. Not more than [3] deep accent colors will be required.

Small scope surfaces will be painted in one or more accent colors.

c) Painted doors will generally be painted in one accent color. Where

painted doors occur in accent color walls, doors and frames will be

same accent color unless otherwise designated. Door frames will be

Page 73: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

same color as adjacent wall, or same color as doors, as directed.

Paintable sealants at frames shall be same color as wall.

d) A designated color may be required in one or more types and sheens

of paint depending upon paint system specified for each specific

surface.

e) Matching colors shall be exact. Manufacturers nearest standard color

will not be acceptable.

10.1 SPECIALTIES

10.2 10400: IDENTIFYING DEVICES

A. STAINLESS STEEL SIGNAGE: Type 304, built-up, 3 mm (1/8”) thick front

plate and 1.0 mm (gauge 20) thick side plates, 25 mm average stroke. Size of

anchorage dowels shall be as required for the fixation of masonry surface. For

main building identification lettering at facade, to be approved by Architect.

B. FIRE EXIT SIGNS: White acrylic letters and green acrylic background; 2 Hours

duration; complete with 1 X 8 W Fluorescent lamp and Sealed Maintenance-Free

Nickel Cadmium Battery. For all fire exit doors.

10.3 10520: FIRE-PROTECTION SPECIALTIES

A. MANUFACTURERS: : Subject to compliance with requirements, manufacturers

offering products that may be incorporated into the Work include, but are not

limited to, the list provided in Section 10520.

1. Available Products: Subject to compliance with requirements, products that

may be incorporated into the Work include, but are not limited to, the products

specified in the FireProtection Cabinet Schedule.

2. Products: Subject to compliance with requirements, provide one of the

products indicated for each designation in the Fire-Protection Cabinet

Schedule.

B. MATERIALS:

1. Cold-Rolled Steel Sheet: Carbon steel, complying with ASTM A 366/A

366M, commercial quality, stretcher leveled, temper rolled.

C. FIRE-PROTECTION CABINETS

Page 74: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

1. Cabinet Construction: Provide manufacturer's standard box (tub), with trim,

frame, door, and hardware to suit cabinet type, trim style, and door style

indicated. Weld joints and grind smooth. Miter and weld perimeter door

frames.

D. PORTABLE, HAND-CARRIED FIRE EXTINGUISHERS

1. Fire Extinguishers: Type, size, and capacity for each fire protection cabinet

and mounting bracket indicated.

a) Valves: Manufacturer's standard.

b) Handles and Levers: Stainless steel.

c) Instruction Labels: Include pictorial marking system complying with

NFPA 10, Appendix B and bar coding for documenting fire

extinguisher location, inspections, maintenance and recharging.

2. Multipurpose Dry-Chemical Type in Steel Container: UL-rated 4-A:60-B:C,

10-lb nominal capacity with mono-ammonium phosphate-based dry chemical

in enameled steel container.

12.1 FURNISHINGS

12.2 12356: COUNTERTOPS

A. GENERAL:

1. Submit Manufacturer's Standard Color Charts for countertops showing the

manufacturer's recommended color and finish selections.

2. Submit Manufacturer's Instructions for countertops including special

provisions required to install equipment components and system packages.

Include all special notices detailing impedances, hazards and safety

precautions.

3. Provide the manufacturer's standard type countertops or as indicated on the

drawings. Accomplish fastenings to permit removal and replacement of

individual countertops without affecting the remainder of the installation.

B. MATERIALS

1. Construct countertops and backsplash of 20mm thick granite of approved

color.

2. 1.2mm thick Stainless Steel Kitchen Sinks:

Page 75: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

16.1 MECHANICAL / ELECTRICAL

16.2 15145 PIPING

A. WATER SUPPLY SYSTEM

1. Cold Water lines: PPR PIPES with Approved Fittings

2. Faucet and Accessories: Chrome finish solid brass

B. SANITARY DISPOSAL

1. Pipes: UPVC schedule 40

C. STORM DRAINAGE

1. Pipes: UPVC schedule 40

2. Catch Basins: In-site or pre-cast concrete.

16.3 15451: PLUMBING FIXTURES AND TRIMS

A. GENERAL REQUIREMENTS FOR PLUMBING FIXTURES

1. General for all sanitary plumbing fixtures unless otherwise specified.

2. Fixtures: Free from imperfections, true as to line, angles, curves, and color,

smooth. watertight and quiet in operation. See Summary of Materials and

Finishes.

3. Location, Type, Color and Finishes: per architectural drawings

B. LAVATORY FAUCETS

1. Body Material: Commercial, solid brass.

2. Finish: Polished chrome plate.

3. Maximum Flow Rate: 0.5 gpm.

4. Centers: 4 inches.

5. Mounting: Deck, concealed.

Valve Handle(s): Not required.

6. Inlet(s): NPS 3/8 tubing, plain end.

7. Spout: Rigid type.

Page 76: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

8. Spout Outlet: Aerator

C. SINK FAUCETS

1. Body Material: Commercial, brass escutcheon, chrome plated.

2. Finish: Polished chrome plate.

3. Maximum Flow Rate: 1.8 gpm, unless otherwise indicated.

4. Mixing Valve: Single control. e) Backflow Protection Device for Hose Outlet:

Required.

5. Centers: 4 inches.

6. Mounting: Deck.

7. Handle(s): Lever.

8. Inlet(s): NPS 3/8 plain-end tubing.

9. Spout Type: Swing, round tubular.

10. Spout Outlet: Restricted flow aerator.

11. Vacuum Breaker: Required.

12. Operation: Washerless cartridge.

13. Drain: Crumb cup

D. FLUSHOMETERS/FLUSHVALVES

1. Urinal (As per approval of architect)

E. WATERCLOSETS

(As per approval of architect)

F. URINALS

(As per approval of architect)

LAVATORIES (As per approval of architect)

G. KITCHEN SINKS

1. Stainless Steel, single drain bowl, with overall size of 560mm x 635mm (22”

x 25”), for all kitchenettes or approved equal. Provide chrome finish single

lever kitchen faucet with P-trap, angle valves, strainers and all other fittings,

or approved equal to complete.

2. Kitchen Sink, 2-Compartment, P5A:

Page 77: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

a) Overall Dimensions: 32 inch by 18 inch.

b) Metal Thickness: 18 gauge

c) Faucet(s): See Section 2.3

H. FLOOR DRAINS

1. Stainless Steel, 100mm x 100mm (4” x 4”). For all floor drains and slop sinks.

Note: Verify roughing in dimensions and installation procedures from manufacturer before

proceeding with final set of pipe inlets and mounting hardware.

16.1 ELECTRICAL

16.2 16100: WIRING METHODS

A. GENERAL: Where specifications of any type of material or equipment are in

question, such materials shall conform to the standard specifications set by the

following:

1. U.S. UNDERWRITERS LABORATORIES

2. U.S. NATIONAL BOARD OF FIRE UNDERWRITER

3. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

4. INSULATED POWER CABLE

5. AMERICAN STANDARDS ASSOCIATION

6. BUREAU OF STANDARDS, DEPARTMENT OF TRADE

7. PHILIPPINE NATIONAL STANDARDS

B. CONDUITS: As indicated in the Electrical (E) Plans

1. Rigid steel conduits (RSC): shall be hot dipped galvanized, standard weight

pipes made of mild steel smooth circular bore. It shall be in standard length of

3.05 meters including coupling, reamed and threaded on each end.

2. Intermediate Metallic Conduit (IMC).

3. Non-metallic conduit (PVC): CS40 smooth wall non-metallic conduit

conforming to Philippine National Standards No. 14 for PVC Pipes. Conduit

shall be in standard length of 3.05 meters including coupling

C. SWITCHES, PANELBOARDS AND CIRCUIT BREAKERS

Page 78: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

1. Circuit Breakers Molded case circuit breakers shall be Japan-made. No

bracing on handles of single pole breakers shall be allowed in lieu of two- or

three-pole types.

2. Metal Enclosures and Cabinets Panelboard enclosures, telephone cabinets, bus

bar gutters, pull boxes, and wire gutters for feeders shall be locally fabricated

by reputable manufacturers.

3. Safety Switches:

All safety switches shall be rated as shown in the plans and shall be

fusible type unless noted otherwise. 3

All safety switches rated at 60A and above shall be spring

D. WIRES AND CABLES:

No conductor shall be less than 3.5 mm2 in size unless otherwise specified. Wires

and cables shall be insulated for 600 volts. Feeders, sub-feeders and branch circuit

wires and cables shall be soft drawn copper, annealed and of 98% conductivity,

type THWN. All joints or splices for No. 8 or larger shall be made with a double

indent mechanical compression connector. Branch circuit splices shall be

soldered. A soldered joint shall be carefully soldered without use of acid. After

the conductors have been made mechanically and electrically secured, the entire

joint shall be covered with rubber and plastic tapes to make the insulation of the

joint or splice equal to the original insulation of the conductor.

16.3 16120: CONDUCTORS AND CABLES

A. CONDUCTORS AND CABLES

1. Copper Conductors: Comply with NEMA WC 70.Conductor Insulation:

2. Comply with NEMA WC 70 for Types THHN-THWN, XHHW.

3. Secondary Voltage Wires, Cables, and Connectors: connector):

a) General: Provide electrical wires, cables, and connectors of manufacturer's

standard materials, as indicated by published product information;

designed and constructed as recommended by manufacturer, for a

complete installation, and for application indicated. Provide copper

conductors rated 600 Volts with conductivity of not less than 98% at 68o

F. 1

b) Building Wires: Provide manufactured wires of sizes, ampacity ratings,

and materials for applications and services indicated. Where not indicated,

provide proper wire selection as determined by Contractor to comply with

project's installation requirements, NEC and NEMA standards. Select

Page 79: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

from the following UL types, those wires with construction features which

fulfill project requirements:

c) Type THW: For dry and wet locations; 600V, maximum operating

temperature 75o C (167o F). Insulation, flame retardant, moisture and heat

resistant, thermoplastic; conductor, annealed copper.

d) Type THWN: For dry and wet locations; 600V, maximum operating

temperature 75o C (167o F). Insulation, flame retardant, moisture and heat

resistant, thermoplastic; outer covering, nylon jacket; conductor, annealed

copper.

e) Type XHHW (Underground Feeders): For dry and wet locations; 600V,

maximum operating temperature 75o C (167o F). Insulation, moisture and

heat resistant rubber; outer covering, moisture resistant, flame retardant,

nonmetallic covering; conductor, annealed copper.

f) Type THHN (Interior Branch Circuits): For dry and damp locations; 600V,

maximum operating temperature 90o C (194o F). Insulation, flame

retardant, heat resistant, thermoplastic; outer covering, nylon jacket;

conductor, annealed copper.

4. Cables: Provide UL type factory-fabricated cables of sizes, ampacity ratings,

and materials and jacketing/sheathing as indicated for services indicated.

Where not indicated, provide proper selection as determined by Contractor to

comply with installation requirements, NEC and NEMA standards.

5. Conductors No. 10 and smaller shall be solid and conductors larger than No.

10 shall be stranded. Fire alarm wiring shall be stranded.

6. Conductors shall be of solid, high electrical conductivity copper with a cross-

section area corresponding to standard AWG sizes.

7. The insulation shall be of highly compressed magnesium oxide that will

provide proper spacing for conductors. Thickness of insulation shall be at least

55 mils for all cable from 14 AWG through 250 MCM.

B. CONNECTORS AND SPLICES

1. Description: Factory-fabricated connectors and splices of size, ampacity

rating, material, type, and class for application and service indicated.

2. Joints in solid conductors shall be spliced using Ideal "Wirenuts", 3M

Company "Scotchlock" or T&B "Piggy" connectors in junction boxes, outlet

boxes and lighting fixtures.

3. "Sta-kon" or other permanent type crimp connectors shall not be used for

branch circuit connections.

4. Joints in stranded conductors shall be spliced by approved mechanical

connectors and gum rubber tape or friction tape. Solderless mechanical

Page 80: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

connectors for splices and taps, provided with U/L approved insulating covers,

may be used instead of mechanical connectors plus tape.

5. Conductors, in all cases, shall be continuous from outlet to outlet and no

splicing shall be made except within outlet or junction boxes, troughs and

gutters.

C. SLEEVES FOR CABLES

1. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40,

galvanized steel, plain ends.

16.4 16140: WIRING DEVICES

A. OUTLET BOXES:

1. Standards: NEC Article No. 314; UL.

2. Material: Pressed steel, zinc coated.

3. Minimum Size: 4 inch square or octagon; depth as required.

4. Extension Rings: To suit various conditions.

5. Hardware: Grounding screw and connectors as required by wiring method.

6. Other Types: As required to suit conditions

B. PULL AND JUNCTION BOX

1. Standards: NEC Article No. 314; ASTM A123; UL.

2. Material: Galvanized steel, code gauge.

3. Cover: Same material as box, screw on type, maximum size 300 sq. in. in one

piece

C. CONVENIENCE RECEPTACLE (STANDARD)

1. Provide mock-up/sample for approval of the architect.

2. Standards: NEC Article No. 406; Fed. Spec. W-C-596D as verified by UL and

NEMA tests WD-1, 3.02 through 3.10 and UL tests UL498.

3. Type: Duplex, 2 pole, 3 wire, with U slot ground.

4. Construction: Heavy duty, industrial specification grade.

5. Contacts: 20 ampere, phosphor bronze, double wiping.

6. Wiring Terminal Type: Back and side. [Option: Plug-in connector with pig-

tails]

7. Grounding Terminals: Green screw.

8. Other Types: As shown or required to match plugs for equipment furnished by

Owner or other trades.

Page 81: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

D. LOCAL SWITCHES

1. Standards: NEC Article No. 404; NEMA; UL.

2. Construction: Heavy duty, industrial specification grade, 20A at 120/277V, 2

hp at 240V, 1 hp at 120V.

3. Type: Flush, quiet, AC, totally enclosed brush tumbler, toggle handle, single

pole, 3-way and 4- way as shown.

4. Modifications: Pilot light, key operation, interchangeable type as shown.

5. Wiring Type: Back and side, for #10 AWG if required.

6. Other Types: As shown or specified.

7. Provide mock-up/sample for approval of the architect.

16.5 16442: PANELBOARDS

A. DISTRIBUTION PANELBOARDS

1. Doors: Secured with vault-type latch with tumbler lock; keyed alike. Omit for

fused- switch panelboards.

2. Main Overcurrent Protective Devices: Circuit breaker.

3. Branch Overcurrent Protective Devices:

4. 4General: Except as otherwise indicated, provide panelboards, bolt-on

breakers, integral common trip, enclosures and ancillary components, of types,

sizes, and ratings indicated, which comply with manufacturer's standard

materials; design and construction in accordance with published product

information; equip with proper number of unit panelboard devices as required

for complete installation. Where types, sizes, or ratings are not indicated,

comply with NEC, UL and established industry standards for those

applications indicated.

5. Provide molded case main and branch circuit bolt-on breaker types for each

circuit, with toggle handles that indicate when tripped.

6. Where multiple pole breakers are indicated, provide with integral common trip

so overload on one pole will trip all poles simultaneously.

7. Minimum short circuit rating for branch circuit breakers shall be as noted on

the Drawings. Series ratings will not be acceptable

8. Select enclosures as noted on the Drawings fabricated by the same

manufacturer as the panelboards, which mate and match properly with the

panelboards.

16.6 16511: INTERIOR LIGHTING

A. LIGHTING FIXTURES

Page 82: Section X. Technical Specifications · 2019-03-11 · Section X. Technical Specifications SECTION 01000 EXPLANATION FOR THE SPECIFICATIONS 1.0 INTRODUCTION The Drawings and Specifications

1. General: Provide lighting fixtures, of sizes, types and ratings indicated;

complete with, but not limited to, housings, energy efficient ballasts, starters,

wiring, poles and standards.

2. Wiring: Provide electrical wiring within fixture suitable for connecting to

branch circuit wiring.

3. Lamps

All lamps of a particular type used on this Project shall be by one

manufacturer.

All lamps of a particular type shall be from one production run.

Provide fluorescent lamps of energy saving types and wattages as

indicated on the Drawings.

Provide LED lamps in types and wattages indicated on the Drawings.

Provide incandescent lamps in types and wattages as indicated on the

Drawings.

4. Interior Lighting Fixture Types:

General: Fixtures must comply with minimum requirements as stated

herein. Review Architectural Drawings and Specifications to verify

ceiling types, modules, suspension systems appropriate to installation.

Refer to the Fixture Schedule on the Drawings for specific fixture

requirements.

Submit mock-up / sample product for approval.

5. Examination:

Examine areas and conditions under which lighting fixtures are to be

installed, and substrate for supporting lighting fixtures.

Notify Engineer in writing of conditions detrimental to proper

completion of the work