FOUNDATION DETAIL
SCALE 1/2"=1'-0"
SECTION A-A - BASEPLATE
FOUNDATION DETAIL
SCALE 3/8"=1'-0"
SECTION B-B
SECTION C-C
ANCHOR BOLTS
(6) REQ'D. PER FOOTING
FOUNDATION PLAN
SCALE 3/8"=1'-0"
SECTION R-R
SCALE 1/2"=1'-0"
A
A
BB
CC
B B
THESE PLANS ARE SUBJECT TO
FEDERAL COPYRIGHT LAWS
ANY USE OF SAME WITHOUT THE
EXPRESS WRITTEN PERMISSION
OF VFS, LLC IS PROHIBITED
SHEET NUMBER:
CA1 of 2
SHEET TITLE:
FOUNDATION PLAN
SCALE:
JOB NUMBER:
DRAWN BY: CHECKED BY:
44522
AS SHOWN
137 Applewood Drive.
Ilion, New York 13357
Phone: 315.865.0262
SITE:
JJ SULLIVAN
229 RIVER STREET
GUILFORD, CT
16'-0" x 36'-0"
(2) COLUMN CANOPY
JKS LRP
3'-6" SQUARE PIER
2'-2"
PIER
1'-10"
EMBEDMENT
(10) #5 BARS x 9'-6" LONG
AT 6" C/C (TOP AND BOTTOM)
8"
BU
RY
12'-0"
3'-0"
3'-0"
(#) #7 VERT. BARS
(#) #7 VERT. BARS
#4 HORZ. TIES AT 12" CENTERS
3" C
LEA
R
ANCHOR BOLT TYP.
HIGH POINT OF GRADE
(4) #4 HORZ. BARS AT 16" CENTERS
EACH WAY (4) FOUR LAYERS
#4 VERT. BARS AT CORNERS
AND AT CENTER OF EACH SIDE
1 1/2" x 30" LONG HEADED ANCHOR
ROD WITH LEVELING NUTS & WASHERS
(ASTM F1554 GRADE 36) ON TOP OF &
BELOW BASE PLATE
8" THREADED
2'-6"
FOOTING NOTES
1. OWNER / GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR FOOTING AND ANCHOR BOLT INSTALLATION.
2. ALL FOOTINGS SHALL BE CAST ON LEVEL UNDISTURBED SOIL, ROCK OR PROPERLY COMPACTED SUBGRADE.
BOTTOM OF FOOTING TO BE ABOVE WATER TABLE. FOOTING SIZE BASED ON MINIMUM 2000 PSF SOIL BEARING
CAPACITY AT BASE AND 150 PSF PER FOOT OF DEPTH LATERAL BEARING CAPACITY. CONTRACTOR SHALL BE
RESPONSIBLE FOR VERIFYING ALL SOIL PARAMETERS.
3. FOOTING CONCRETE SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 3000 PSI.
4. TOPS OF ALL FOOTINGS ARE ASSUMED TO BE AT SAME ELEVATION. OWNER / GENERAL CONTRACTOR SHALL
PROVIDE BURIAL DEPTH FROM HIGH GRADE UNDER CANOPY. WHERE TOPS OF FOOTINGS ARE AT DIFFERENT
ELEVATIONS, THE OWNER / GENERAL CONTRACTOR SHALL PROVIDE THE CANOPY MANUFACTURER WITH ALL
FOOTING AND GRADE ELEVATIONS PRIOR TO CANOPY FABRICATION. VARIATIONS FROM DESIGN ELEVATIONS
MAY RESULT IN INADEQUATE CLEARANCE AND UNDER SIZED FOOTINGS.
5. OWNER / GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PLACING NON-SHRINK GROUT UNDER ALL
COLUMN BASES AFTER CANOPY IS LEVELED AND SECURED.
6. FOOTING REINFORCING STEEL SHALL BE ASTM A615 GRADE 60 DEFORMED BILLET STEEL BARS WITH SPACING
AS SHOWN ON DRAWING.
7. FOOTINGS ARE ASSUMED TO BE CONSTRAINED BY DRIVE MAT CONCRETE. WHERE THIS CONDITION DOES NOT
EXIST, THE OWNER SHALL NOTIFY CANOPY MANUFACTURER.
8. ANCHOR BOLTS SHALL BE PLACED IN ACCORDANCE WITH THIS DRAWING. TEMPLATES SHALL BE USED TO
ENSURE PROPER PLACEMENT OF ANCHOR BOLTS. ANCHOR BOLTS ARE TO BE INSTALLED SUCH THAT A MINIMUM
OF 7" OF THREAD IS EXPOSED ABOVE TOP OF FOOTING. BOTTOM OF THREADS SHALL NOT END MORE THAN 3/4"
ABOVE TOP OF FOOTER.
#4 HORZ. TIES AT 12" CENTERS
(#) #7 VERT. BARS
PLATE 1"x20"x20"
WITH GUSSETS
(DETAIL D1/CA1)
1'-10"
EM
BED
MEN
T
1'-0"
MIN
.
LOW POINT OF GRADE
(4) #3 TIES-TOP 12" AND
AT 12" O.C. THEREAFTER
6" LOCAL FROST
LINE (MIN.)
4'-0"
TO
H
IG
H PO
IN
T
OF G
RAD
E
TEK 5
COLUMN
6"x6" COVER PLATE
5"x5" HAND HOLE
HAND HOLE & COVER DETAIL
D2
CA1
4'-0"
TO
H
IG
H PO
IN
T
OF G
RAD
E
COLUMN
6"x8" HAND
HOLE COVER
TEK 5 TYP.
4"x6" HAND HOLE
HAND HOLE & COVER DETAIL
D2
CA1
0
9/30/20
JKS
PERMIT / APPROVAL
REVISION HISTORY
REV DATE BY DESCRIPTION
8"
8"
SEE FOUNDATION DETAIL (TYP)
LAWRENCE R. PILON, PE
51 MAPLEVIEW DR.
PENNELLVILLE, NY.
LICENSE #017661
36'-3"
16'-0"
2
12
XABT1 (TEMPLATE)
-XAB (1
1
2
" x 30" ANCHORBOLT)
FOR ANCHOR BOLT SHIPMENT
8"
20"
2"
8"
2"
2"
16"
2"
20"
WOOD TEMPLATE
8" 8"
TOP OF ALL PIERS
AT SAME ELEVATION
CONCRETE DRIVE
8"
2'-6"
FO
UN
DATIO
N
(13) #5 BARS x 4'-6" LONG
AT 9 1/4" C/C (TOP AND BOTTOM)
5'-0"
SECTION B-B - PIER
2'-6" 2'-6"
8'-0" 2'-0"
10'-0"
3" CLEAR TYP.
16'-0"
CONCRETE DRIVE
3'-6" SQUARE PIER
3'-6"
3'-6"
(20) #6 VERTICAL BARS
WITH 12" 90 HOOK
3"
3"
3"
1'-0"
TYP
(U
NO
)
#4 HORZ. TIES
AROUND PERIMETER
(6) SIX LAYERS
SPACING AS SHOWN BELOW
4'-8"
4'-0"
8"
2'-0" 32'-0" 2'-3"
12'-0"
4'-0"
10'-0"
5'-0"
3'-6"
3'-6"
#4 HORZ. TIES
AROUND PERIMETER
(6) SIX LAYERS
SPACING AS SHOWN
TOP OF FOOTING
NON-SHRINK GROUT TO BE
APPLIED & SUPPLIED AFTER
CANOPY IS LEVEL & SECURED
(BY OTHERS)
BASEPLATE
ANCHOR BOLTS:
1
1
2
" x 30" LONG HEADED
ANCHOR ROD W/LEVELING
NUTS & WASHERS (F1554 GR 36)
ON TOP OF & BELOW BASE PLATE
CONDUIT AS REQ'D (BY OTHERS)
1
4
"
TYP.
5
16
"
(8) GUSSETS 3/8"x4"x4"
COLUMN
BASEPLATE DETAIL
D1
1"
2"
20" x 20"
CA1
50"
12"
ELEVATION
SCALE 5/16"=1'-0"
FRAMING PLAN
SECTION T-T
SCALE 5/16"=1'-0"
DETAIL U
SCALE .05 : 1
DETAIL V
SCALE .05 : 1
SECTION W-W
SCALE 5/16"=1'-0"
FASCIA DETAIL AT GUTTER SIDE
DECK DETAIL
U
V
Y
AA
THESE PLANS ARE SUBJECT TO
FEDERAL COPYRIGHT LAWS
ANY USE OF SAME WITHOUT THE
EXPRESS WRITTEN PERMISSION
OF VFS, LLC IS PROHIBITED
SHEET NUMBER:
CA2 of 2
SHEET TITLE:
FRAMING PLAN
SCALE:
JOB NUMBER:
DRAWN BY: CHECKED BY:
44522
AS SHOWN
137 Applewood Drive.
Ilion, New York 13357
Phone: 315.865.0262
SITE:
JJ SULLIVAN
229 RIVER STREET
GUILFORD, CT
16'-0" x 36'-0"
(2) COLUMN CANOPY
JKS LRP
STEEL NOTES
1. DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL CONFORM TO THE LATEST AISC
SPECIFICATIONS. DESIGN, FABRICATION AND ERECTION OF COLD FORMED STEEL SECTIONS SHALL
CONFORM TO THE LATEST AISI SPECIFICATIONS.
2. STRUCTURAL MATERIALS:
WIDE FLANGE SECTIONS - ASTM A992 OR A572 GRADE 50 (Fy = 50 KSI)
ANGLES / CHANNELS - ASTM A36 (Fy = 36 KSI)
HOLLOW STRUCTURAL SECTIONS (TUBE) - ASTM A500 GRADE B (Fy = 46 KSI)
PIPE SECTIONS - ASTM A53, GRADE B (Fy = 35 KSI)
PLATE - ASTM A36 (Fy = 36 KSI)
ROOF DECK - ASTM A653, GRADE 50 (Fy = 50 KSI), GALVANIZED (G60) WITH FULL COAT OF POLYESTER
PAINT BAKED ON OVER AN EPOXY PRIMER.
STEEL OUTRIGGERS - ASTM A653 GR. CS (Fy = 25 KSI), GALVANIZED (G90) PER ASTM 924
STRUCTURAL BOLTS - ASTM A325
ANCHOR BOLTS - ASTM F1554 GR. 36; ASTM A36; OR ASTM A307 MATERIAL (Fy = 36 KSI)
3. WELDING OF STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH LATEST ANSI / AWS D1.1
4. FIELD CONNECTIONS SHALL BE BOLTED CONNECTIONS UNLESS SPECIFIED ON DRAWING.
5. ALL STRUCTURAL BOLTED CONNECTIONS SHALL USE ASTM A325 BOLTS. BOLTED JOINTS SHALL BE
TIGHTENED TO SNUG TIGHT PER LATEST RCSC SPECIFICATION.
6. STRUCTURAL STEEL SHALL BE SHOP COATED WITH A RED-OXIDE RUST INHIBITIVE PRIMER. FIELD
TOUCH-UP, FINISH PAINTING, AND MAINTENANCE SHALL BE THE RESPONSIBILITY OF THE OWNER
(UNLESS OTHERWISE SPECIFIED).
7. DESIGN LOADS PER 2018 CT BUILDING CODE (2015 IBC W/ CT AMENDMENTS) REQUIREMENTS:
RISK CATEGORY II
ROOF LIVE LOAD = 30 PSF
FLAT ROOF SNOW LOAD = 30 PSF
BASED ON GROUND SNOW LOAD= 30 PSF
WIND LOADS:
LATERAL = +/- 35 PSF (MWFRS)(USING 0.6 W FOR ASD)
UPLIFT = +/- 20 PSF (MWFRS)(USING 0.6 W FOR ASD)
BASED ON 135 MPH ULTIMATE WIND SPEED PER ASCE 7 EXPOSURE "B"
IMPORTANCE FACTOR = 1.0
SEISMIC LOADS:
OCCUPANCY CATEGORY II, SITE CLASS "D" ASSUMED
SEISMIC DESIGN CATEGORY "B"
Sds = 0.188G (Ss = 0.176, Fa = 1.6), Sd1 = 0.098G (S1 = 0.061, Fv = 2.4)
SEISMIC FORCE RESISTING SYSTEM IS NON-BLDG INVERTED PENDULUM - CANTILEVERED COLUMN, R = 2
Cs = 0.094, DESIGN BASE SHEAR = CsxW = 0.5 KIPS / COLUMN USING EQUIVALENT LATERAL FORCE
PROCEDURE
DEAD LOADS:
DECK / GUTTER / LIGHTS - 5 PSF
FASCIA - 15 PLF
STRUCTURAL STEEL - SELF WT
CONCRETE - 145 PCF
8. CANOPY USE GROUP M / CONSTRUCTION TYPE II-B
BOLT TABLE
MK.
QTY.
TYPE OF BOLT NO. OF LOCATIONS
A 4
3/4" DIA. X 2 1/2" BOLTS A-325
2
B 8
3/4" DIA. X 2 1/2" BOLTS A-325
3
C 4
3/4" DIA. X 2" BOLTS A-325
3
D 3
3/4" DIA. X 2" BOLTS A-325
3
E 2
3/4" DIA. X 2" BOLTS A-325
3
ALL STRUCTURAL BOLTED CONNECTIONS SHALL USE ASTM A-325 BOLTS.
BOLTED JOINTS SHALL BE TIGHTENED TO SNUG TIGHT PER LATEST RCSC SPECIFICATION.
TURN MARK NUMBERS ON BEAMS THE SAME AS SHOWN ON PLAN
18GA.x2"x2" GALV. KNEE BRACE (#KB1) LOCATE
AT EACH PURLIN AND FASTEN TO NEAREST OUTRIGGER
18GA.x2"x2" GALV. KNEE BRACE (#KB1) LOCATE
AT 8'-0" O.C. AND FASTEB TO NEAREST OUTRIGGER
TOP OF PIER
ABOVE CONCRETE DRIVE
0
9/30/20
JKS
PERMIT / APPROVAL
REVISION HISTORY
REV DATE BY DESCRIPTION
EXTERIOR DOWNSPOUT SEE DETAIL GX/E1
(SEE FOUNDATION PLAN FOR DIRECTION)
INTERIOR PVC DOWNSPOUT
SEE DETAIL G11/CA2
DECK PANEL 20GA.x3"x16"
IRG WHITE EMBOSSED
LAWRENCE R. PILON, PE
51 MAPLEVIEW DR.
PENNELLVILLE, NY.
LICENSE #017661
8"
8"
TOP OF PIER
ABOVE
CONCRETE DRIVE
* ALL STRUCTURAL STEEL *
TO BE HOT DIP GALVANIZED
GUTTER
FASCIA
3"x4" OUTLET
3"x4" ELBOW
3"x4" DOWNSPOUT
COLUMN
DECK
DOWNSPOUT DETAIL
3"x4" ELBOW
36'-0"
36'-0"
1
1
2
"
DECK
PURLIN
FASCIA: ACM
COLOR: PROGRAM WHITE
FASCIA
2'-0" 32'-0" 2'-3"
36'-3"
12'-0"
4'-0"
16'-0"
3'-0"
10'-4"
2'-8"
CB1
W14x30
CB1
W14x30
PB2
W10x26
PB1
W10x26
COLUMN (TYP)
HSS-12"x12"x1/2"
PURLIN
2-1/2" x 18GA x 5'-0" CEE STUD
ATTACH AT FIRST / LAST 4 PANELS
EACH END OF CANOPY
(2) #14 x 7/8" LAPTEK
12" OC
3
16
"
PURLIN
PURLIN
CROSSBEAM
CROSSBEAM
3
4
" A-325 BOLTS & NUTS
(4 PER CONNECTION)
CROSSBEAM TO PURLIN CONNECTION
S21
PL-1/4"
STIFFENER
TYP
CA2
( ) PLACES
CROSSBEAM
3/4" A-325 BOLT & NUT
ANGLE 3x3x3/16"
PURLIN
1/4" STIFFENER
CROSSBEAM BRACE DETAIL
2
S45
3/16"
CA2
CROSSBEAM
CROSSBEAM1/4" STIFFENER
(NS / FS)
CAP PLATE
COLUMN
TYP
3
16
"
1
4
"
PL-
3
4
" A-325 BOLTS & NUTS
(8 PER CONNECTION)
3
8
" GUSSET
CROSSBEAM TO COLUMN CONNECTION
3/4" x 14" x 24"
S11
CA2
ANGLE 3x3x3/16"
PURLIN
3
4
" A-325 BOLTS & NUTS
ANGLE LATERAL BRACE
S31
CA2
#12 X 1-1/4" TEK 5 W/ WASHER
(3) PER DECK PAN AT PURLIN
S11
CA2
S21
CA2
S21
CA2
S45
CA2
SA7-a14
L-3"x3"x3/16"
LATERAL BRACE
(TYP 4 PLCS)
S31
CA2
SA7-a122
L-3"x3"x3/16"
LATERAL BRACE
(TYP 3 PLCS)
S31
CA2
S31
CA2
SA7-a147
L-3"x3"x3/16"
LATERAL BRACE
(TYP 2 PLCS)
S31
CA2
S31
CA2
6
"
1"
CANOPY INSTALLER TO FIELD
CUT & BEND TO FORM
OVERFLOW OPENING
CANOPY
GUTTER
CA2
FIELD CUT GUTTER OVERFLOW DETAIL
G3
G3
CA2
G3
CA2
10'-0"12'-0"10'-0"
36'-0"
3'-0"
CROSSBEAM
19'-9" TO
TO
P O
F PIER
19'-9"
GUTTER
7
1
2
"
5"
DECK
18GA BACKER
(FULL HEIGHT)
18GA ZEE x 35" LONG
AT 24" OC
GUTTER HANGER
18GA HAT CHANNEL
1-1/2" TALL x 24" LONG
(3) #10x3/4" TEKS PER CHANNEL
18GA
KNEE BRACE
AT 24" OC
ALL FASTENERS #10x3/4" TEKS AT 24"OC
UNLESS NOTED OTHERWISE
19'-9
7 8
"
3'-0"
SEE DOWNSPOUT DETAIL