SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Equipment supports and hangers. B. Related Requirements: 1. Section 055000 "Metal Fabrications" for structural-steel shapes and plates for trapeze hangers for pipe and equipment supports. 2. Section 230548 Vibration and Seismic Controls for HVAC for vibration isolation devices. 3. Section 233113 Metal Ducts for duct hangers and supports. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product. B. Shop Drawings: Show fabrication and installation details and include calculations for the following; include Product Data for components: 1. Equipment supports and hangers. 1.4 INFORMATIONAL SUBMITTALS A. Welding certificates. 1.5 QUALITY ASSURANCE A. Structural-Steel Welding Qualifications: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural Welding Code - Steel." B. Pipe Welding Qualifications: Qualify procedures and operators according to ASME Boiler and Pressure Vessel Code, Section IX. PART 2 - PRODUCTS 2.1 EQUIPMENT SUPPORTS A. Description: Welded, shop- or field-fabricated equipment support or hangers made from structural carbon-steel shapes or threaded rod with vibration isolation as specified in Section 23 05 48 Vibration and Seismic Controls for HVAC. ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation 197

SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC EQUIPMENT

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes: 1. Equipment supports and hangers.

B. Related Requirements:

1. Section 055000 "Metal Fabrications" for structural-steel shapes and plates for trapeze hangers for pipe and equipment supports.

2. Section 230548 Vibration and Seismic Controls for HVAC for vibration isolation devices.

3. Section 233113 Metal Ducts for duct hangers and supports.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. Shop Drawings: Show fabrication and installation details and include calculations for the following; include Product Data for components: 1. Equipment supports and hangers.

1.4 INFORMATIONAL SUBMITTALS

A. Welding certificates.

1.5 QUALITY ASSURANCE

A. Structural-Steel Welding Qualifications: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural Welding Code - Steel."

B. Pipe Welding Qualifications: Qualify procedures and operators according to ASME Boiler and

Pressure Vessel Code, Section IX.

PART 2 - PRODUCTS

2.1 EQUIPMENT SUPPORTS

A. Description: Welded, shop- or field-fabricated equipment support or hangers made from

structural carbon-steel shapes or threaded rod with vibration isolation as specified in Section 23 05 48 Vibration and Seismic Controls for HVAC.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

197

Page 2: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2.2 MATERIALS

A. Aluminum: ASTM B221.

B. Carbon Steel: ASTM A1011/A1011M.

C. Structural Steel: ASTM A36/A36M, carbon-steel plates, shapes, and bars; galvanized.

D. Stainless Steel: ASTM A240/A240M.

E. Threaded Rods: Continuously threaded. Zinc-plated or galvanized steel for indoor applications and stainless steel for outdoor applications. Mating nuts and washers of similar materials as rods.

F. Grout: ASTM C1107/C1107M, factory-mixed and -packaged, dry, hydraulic-cement, nonshrink

and nonmetallic grout; suitable for interior and exterior applications.

1. Properties: Nonstaining, noncorrosive, and nongaseous. 2. Design Mix: 5000-psi, 28-day compressive strength.

PART 3 - EXECUTION

3.1 APPLICATION

A. Comply with requirements in Section 078413 "Penetration Firestopping" for firestopping materials and installation for penetrations through fire-rated walls, ceilings, and assemblies.

B. Strength of Support Assemblies: Where not indicated, select sizes of components so strength

will be adequate to carry present and future static loads within specified loading limits. Minimum static design load used for strength determination shall be weight of supported components plus 200 lb.

3.2 EQUIPMENT SUPPORTS

A. Fabricate structural-steel stands to suspend equipment from structure overhead or to support equipment

above floor. Use of threaded rod with high strength screw anchor is acceptable for hanging HVAC equipment.

B. Grouting: Place grout under supports for equipment and make bearing surface smooth.

C. Provide lateral bracing, to prevent swaying, for equipment supports.

3.3 METAL FABRICATIONS

A. Cut, drill, and fit miscellaneous metal fabrications for equipment supports.

B. Fit exposed connections together to form hairline joints. Field weld connections that cannot be shop welded because of shipping size limitations.

C. Field Welding: Comply with AWS D1.1/D1.1M procedures for shielded, metal arc welding;

appearance and quality of welds; and methods used in correcting welding work; and with the following:

1. Use materials and methods that minimize distortion and develop strength and corrosion

resistance of base metals.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

198

Page 3: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2. Obtain fusion without undercut or overlap. 3. Remove welding flux immediately. 4. Finish welds at exposed connections so no roughness shows after finishing and so

contours of welded surfaces match adjacent contours.

3.4 ADJUSTING

A. Hanger Adjustments: Adjust hangers to distribute loads equally on attachments.

B. Trim excess length of continuous-thread hanger and support rods to 1-1/2 inches.

3.5 PAINTING

A. Touchup: Clean field welds and abraded areas of shop paint. Paint exposed areas immediately after erecting hangers and supports. Use same materials as used for shop painting. Comply with SSPC-PA 1 requirements for touching up field-painted surfaces.

1. Apply paint by brush or spray to provide a minimum dry film thickness of 2.0 mils.

B. Touchup: Comply with requirements in Section 099123 Interior Painting for cleaning and

touchup painting of field welds, bolted connections, and abraded areas of shop paint on miscellaneous metal.

C. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply

galvanizing-repair paint to comply with ASTM A780/A780M.

3.6 HANGER AND SUPPORT SCHEDULE

A. Specific hanger and support requirements are in Sections specifying piping systems and

equipment.

B. Comply with MSS SP-58 for pipe-hanger selections and applications that are not specified in piping system Sections.

C. Use hangers and supports with galvanized metallic coatings for piping and equipment that will

not have field-applied finish.

D. Use nonmetallic coatings on attachments for electrolytic protection where attachments are in direct contact with copper tubing.

E. Use carbon-steel metal framing systems and attachments for general service applications.

F. Building Attachments: Unless otherwise indicated and except as specified in piping system

Sections, install the following types:

1. Steel or Malleable Concrete Inserts (MSS Type 18): For upper attachment to suspend equipment hangers from concrete ceiling.

2. Side-Beam or Channel Clamps (MSS Type 20): For attaching to bottom flange of beams, channels, or angles.

3. Center-Beam Clamps (MSS Type 21): For attaching to center of bottom flange of beams. 4. C-Clamps (MSS Type 23): For structural shapes. 5. Top-Beam Clamps (MSS Type 25): For top of beams if hanger rod is required tangent to

flange edge.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

199

Page 4: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

6. Side-Beam Clamps (MSS Type 27): For bottom of steel I-beams. 7. Steel-Beam Clamps with Eye Nuts (MSS Type 28): For attaching to bottom of steel I-

beams for heavy loads. 8. Linked-Steel Clamps with Eye Nuts (MSS Type 29): For attaching to bottom of steel I-

beams for heavy loads, with link extensions. 9. Malleable-Beam Clamps with Extension Pieces (MSS Type 30): For attaching to

structural steel. 10. Welded-Steel Brackets: For support of pipes from below or for suspending from above

by using clip and rod. Use one of the following for indicated loads:

a. Light (MSS Type 31): 750 lb. b. Medium (MSS Type 32): 1500 lb. c. Heavy (MSS Type 33): 3000 lb.

11. Side-Beam Brackets (MSS Type 34): For sides of steel or wooden beams. 12. Plate Lugs (MSS Type 57): For attaching to steel beams if flexibility at beam is required. 13. Horizontal Travelers (MSS Type 58): For supporting piping systems subject to linear

horizontal movement where headroom is limited.

G. Spring Hangers and Supports: Unless otherwise indicated and except as specified in piping system Sections, install the following types:

1. Restraint-Control Devices (MSS Type 47): Where indicated to control piping movement. 2. Spring Cushions (MSS Type 48): For light loads if vertical movement does not exceed 1-

1/4 inches. 3. Spring-Cushion Roll Hangers (MSS Type 49): For equipping Type 41, roll hanger with

springs. 4. Spring Sway Braces (MSS Type 50): To retard sway, shock, vibration, or thermal

expansion in piping systems. 5. Variable-Spring Hangers (MSS Type 51): Preset to indicated load and limit variability

factor to 25 percent to allow expansion and contraction of piping system from hanger. 6. Variable-Spring Base Supports (MSS Type 52): Preset to indicated load and limit

variability factor to 25 percent to allow expansion and contraction of piping system from base support.

7. Variable-Spring Trapeze Hangers (MSS Type 53): Preset to indicated load and limit variability factor to 25 percent to allow expansion and contraction of piping system from trapeze support.

H. Use mechanical-expansion anchors instead of building attachments where required in concrete

construction. END OF SECTION 230529

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

200

Page 5: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

SECTION 230548 - VIBRATION AND SEISMIC CONTROLS FOR HVAC

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Elastomeric isolation pads. 2. Spring hangers. 3. Restraints - rigid type. 4. Restraints - cable type. 5. Restraint accessories.

B. Related Requirements:

1. Section 210548 "Vibration and Seismic Controls for Fire-Suppression Piping and Equipment" for devices for fire-suppression equipment and systems.

2. Section 220548 "Vibration and Seismic Controls for Plumbing Piping and Equipment"

for devices for plumbing equipment and systems.

1.3 DEFINITIONS

A. Designated Seismic System: An HVAC component that requires design in accordance with

ASCE/SEI 7, Ch. 13, and for which the Component Importance Factor is greater than 1.0.

B. IBC: International Building Code.

C. OSHPD: Office of Statewide Health Planning and Development (for the State of California owned and regulated medical facilities).

1.4 ACTION SUBMITTALS

A. Product Data: For each type of product.

1. Include rated load, rated deflection, and overload capacity for each vibration isolation

device.

1.5 INFORMATIONAL SUBMITTALS

A. Coordination Drawings: Show coordination of vibration isolation device installation and seismic bracing for HVAC piping and equipment with other systems and equipment in the vicinity, including other supports and restraints, if any.

B. Qualification Data: For testing agency.

C. Welding certificates.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

201

Page 6: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

D. Field quality-control reports.

1.6 QUALITY ASSURANCE

A. Testing Agency Qualifications: An independent agency, with the experience and capability to conduct testing indicated, be an NRTL as defined by OSHA in 29 CFR 1910.7, and be acceptable to authorities having jurisdiction.

B. Welding Qualifications: Qualify procedures and personnel in accordance with

AWS D1.1/D1.1M, "Structural Welding Code - Steel."

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Consequential Damage: Provide additional seismic restraints for suspended HVAC components or anchorage of floor-, roof-, or wall-mounted HVAC components as indicated in ASCE/SEI 7- 16 so that failure of a non-essential or essential HVAC component will not cause failure of any other essential architectural, mechanical, or electrical building component.

B. Fire/Smoke Resistance: Seismic-restraint devices that are not constructed of ferrous metals must

have a maximum flame-spread index of 25 and maximum smoke-developed index of 50 when tested by an NRTL in accordance with ASTM E84 or UL 723, and be so labeled.

C. Component Supports:

1. Load ratings, features, and applications of all reinforcement components must be based

on testing standards of a nationally recognized testing agency. 2. All component support attachments must comply with force and displacement resistance

requirements of ASCE/SEI 7-16 Section 13.6.

2.2 ELASTOMERIC ISOLATION PADS

A. Elastomeric Isolation Pads:

1. Acceptable Manufacturers: Kinetics Noise Control, Inc., Vibration Mountings and Control, Inc. and Mason Industries, Inc.

2. Fabrication: Single or multiple layers of sufficient durometer stiffness for uniform loading over pad area.

3. Size: Factory or field cut to match requirements of supported equipment. 4. Pad Material: Oil and water resistant with elastomeric properties. Neoprene rubber,

silicone rubber, or other elastomeric material. 5. Surface Pattern: Smooth, ribbed, or waffle pattern. 6. Infused nonwoven cotton or synthetic fibers. 7. Load-bearing metal plates adhered to pads. 8. Sandwich-Core Material: elastomeric.

a. Surface Pattern: Smooth, ribbed, or waffle pattern. b. Infused nonwoven cotton or synthetic fibers.

2.3 SPRING HANGERS

A. Combination Coil-Spring and Elastomeric-Insert Hanger with Spring and Insert in

Compression: For hanging HVAC equipment.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

202

Page 7: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

1. Acceptable Manufacturers: Kinetics Noise Control, Inc., Vibration Mountings and Control, Inc, and Mason Industries, Inc.

2. Frame: Steel, fabricated for connection to threaded hanger rods and to allow for a

maximum of 30 degrees of angular hanger-rod misalignment without binding or reducing isolation efficiency.

3. Outside Spring Diameter: Not less than 80 percent of the compressed height of the spring at rated load.

4. Minimum Additional Travel: 50 percent of the required deflection at rated load. 5. Lateral Stiffness: More than 80 percent of rated vertical stiffness. 6. Overload Capacity: Support 200 percent of rated load, fully compressed, without

deformation or failure. 7. Elastomeric Element: Molded, oil-resistant rubber or neoprene. Steel-washer-reinforced

cup to support spring and bushing projecting through bottom of frame. 8. Adjustable Vertical Stop: Steel washer with neoprene washer "up-stop" on lower

threaded rod. 9. Self-centering hanger-rod cap to ensure concentricity between hanger rod and support

spring coil. 2.4 RESTRAINTS - RIGID TYPE

A. Acceptable Manufacturers: Hilti, Inc., Vibration Mountings and Control, Inc, and Isolation

Technology, Inc.

B. Description: Shop- or field-fabricated bracing assembly made of AISI S110-07-S1 slotted steel channels, ANSI/ASTM A53/A53M steel pipe as per NFPA 13, or other rigid steel brace member. Includes accessories for attachment to braced component at one end and to building structure at the other end and other matching components and with corrosion-resistant coating; rated in tension, compression, and torsion forces.

2.5 RESTRAINTS - CABLE TYPE

A. Acceptable Manufacturers: Gripple, Inc., Vibration Mountings and Control, Inc, and Loos &

Co.

B. Seismic-Restraint Cables: ASTM A1023/A1023M galvanized or ASTM A603 galvanized-steel cables. End connections made of steel assemblies with thimbles, brackets, swivel, and bolts designed for seismic-restraining cable service; with fittings attached by means of poured socket, swaged socket or mechanical (Flemish eye) loop.

C. Restraint cable assembly with cable fittings must comply with ASCE/SEI 19. All cable fittings

and complete cable assembly must maintain the minimum cable breaking force. U-shaped cable clips and wedge-type end fittings do not comply and are unacceptable.

2.6 RESTRAINT ACCESSORIES

A. Acceptable Manufacturers: Hilti, Inc., Mason Industries, Inc, and Loos & Co.

B. Hanger-Rod Stiffener: Reinforcing steel angle clamped to hanger rod. Non-metallic stiffeners

are unacceptable.

C. Hinged and Swivel Brace Attachments: Multifunctional steel connectors for attaching hangers to

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

203

Page 8: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

rigid channel bracings and restraint cables.

D. Bushings for Floor-Mounted Equipment Anchor Bolts: Neoprene bushings designed for rigid equipment mountings, and matched to type and size of anchor bolts and studs.

E. Bushing Assemblies for Wall-Mounted Equipment Anchorage: Assemblies of neoprene

elements and steel sleeves designed for rigid equipment mountings, and matched to type and size of attachment devices used.

F. Resilient Isolation Washers and Bushings: One-piece, molded, oil and water-resistant

neoprene, with a flat washer face.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine areas and equipment to receive vibration isolation and seismic control devices for compliance with requirements for installation tolerances and other conditions affecting performance of the Work.

B. Examine roughing-in of reinforcement and cast-in-place anchors to verify actual locations

before installation.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 APPLICATIONS

A. Hanger-Rod Stiffeners: Install where indicated or scheduled on Drawings to receive them and where required to prevent buckling of hanger rods due to seismic forces.

B. Strength of Support and Seismic-Restraint Assemblies: Where not indicated, select sizes of

components so strength is adequate to carry present and future static and seismic loads within specified loading limits.

3.3 INSTALLATION OF VIBRATION-CONTROL AND SEISMIC-RESTRAINT DEVICES

A. Provide vibration-control devices for systems and equipment where indicated in Equipment

Schedules or Vibration-Control Devices Schedules, where indicated on Drawings, or where Specifications indicate they are to be installed on specific equipment and systems.

B. Provide seismic-restraint devices for systems and equipment where indicated in Equipment

Schedules or Seismic-Restraint Devices Schedules, where indicated on Drawings, where Specifications indicate they are to be installed on specific equipment and systems, and where required by applicable codes.

C. Coordinate location of embedded connection hardware with supported equipment attachment

and mounting points and with requirements for concrete reinforcement and formwork specified in Section 033000 "Cast-in-Place Concrete."

D. Installation of vibration isolators must not cause any change of position of equipment, piping, or

ductwork resulting in stresses or misalignment.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

204

Page 9: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

E. Comply with requirements in Section 077200 "Roof Accessories" for installation of roof curbs, equipment supports, and roof penetrations.

F. Install seismic-restraint cables so they do not bend across edges of adjacent equipment or

building structure.

G. Install seismic-restraint devices using methods approved by an agency acceptable to authorities having jurisdiction that provides required submittals for component.

H. Install bushing assemblies for anchor bolts for floor-mounted equipment, arranged to provide

resilient media between anchor bolt and mounting hole in concrete base.

I. Install bushing assemblies for mounting bolts for wall-mounted equipment, arranged to provide resilient media where equipment or equipment-mounting channels are attached to wall.

J. Attachment to Structure: If specific attachment is not indicated, anchor bracing to structure at

flanges of beams, at upper truss chords of bar joists, or at concrete members.

K. Mechanical Anchor Bolts:

1. Identify position of reinforcing steel and other embedded items prior to drilling holes for anchors. Do not damage existing reinforcing or embedded items during coring or drilling. Notify structural engineer if reinforcing steel or other embedded items are encountered during drilling. Locate and avoid prestressed tendons, electrical and telecommunications conduit, and gas lines.

2. Do not drill holes in concrete or masonry until concrete, mortar, or grout has achieved full design strength.

3. Wedge-Type Anchor Bolts: Protect threads from damage during anchor installation. Heavy-duty sleeve anchors shall be installed with sleeve fully engaged in the structural element to which anchor is to be fastened.

4. Adhesive-Type Anchor Bolts: Clean holes to remove loose material and drilling dust prior to installation of adhesive. Place adhesive in holes proceeding from the bottom of the hole and progressing toward the surface in such a manner as to avoid introduction of air pockets in the adhesive.

5. Set anchors to manufacturer's recommended torque, using a torque wrench. 6. Install zinc-coated steel anchors for interior and stainless steel anchors for exterior

applications.

3.4 ADJUSTING

A. Adjust isolators after system is at operating weight.

B. Adjust limit stops on restrained-spring isolators to mount equipment at normal operating height.

After equipment installation is complete, adjust limit stops so they are out of contact during normal operation.

3.5 FIELD QUALITY CONTROL

A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.

B. Manufacturer's Field Service: Engage a factory-authorized service representative to test and

inspect components, assemblies, and equipment installations, including connections.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

205

Page 10: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

C. Tests and Inspections: 1. Perform tests and inspections. 2. Provide evidence of recent calibration of test equipment by a testing agency acceptable to

authorities having jurisdiction. 3. Schedule test with Owner, through Architect, before connecting anchorage device to restrained component (unless postconnection testing has been approved), and with at least seven days' advance notice. 4. Obtain Architect's approval before transmitting test loads to structure. Provide temporary

load-spreading members. 5. Test no fewer than four of each type and size of installed anchors and fasteners selected

by Architect. 6. Test to 90 percent of rated proof load of device. 7. Measure isolator restraint clearance. 8. Measure isolator deflection. 9. Verify snubber minimum clearances.

D. Remove and replace malfunctioning units and retest as specified above.

E. Units will be considered defective if they do not pass tests and inspections.

F. Prepare test and inspection reports.

END OF SECTION 230548

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

206

Page 11: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

SECTION 230553 - IDENTIFICATION FOR HVAC EQUIPMENT

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Equipment labels. 2. Warning signs and labels. 3. Warning tape. 4. Duct labels. 5. Stencils. 6. Warning tags.

1.2 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. Samples: For color, letter style, and graphic representation required for each identification

material and device.

C. Equipment-Label Schedule: Include a listing of all equipment to be labeled with the proposed content for each label.

PART 2 - PRODUCTS

2.1 EQUIPMENT LABELS

A. Plastic Labels for Equipment:

1. Acceptable Manufacturers: Seton Identification Products. 2. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving,

1/8 inch thick, with predrilled holes for attachment hardware. 3. Letter and Background Color: As indicated for specific application under Part 3. 4. Maximum Temperature: Able to withstand temperatures of up to 160 deg F. 5. Minimum Label Size: Length and width vary for required label content, but not less than

2-1/2 by 3/4 inch. 6. Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24

inches, 1/2 inch for viewing distances of up to 72 inches, and proportionately larger lettering for greater viewing distances. Include secondary lettering two-thirds to three- fourths the size of principal lettering.

7. Fasteners: Stainless steel rivets or self-tapping screws. 8. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.

B. Label Content: Include equipment’s drawing designation or unique equipment number, Drawing

numbers where equipment is indicated (plans, details, and schedules), and the Specification Section number and title where equipment is specified.

2.2 WARNING SIGNS AND LABELS

A. Acceptable Manufacturers: Seton Identification Products. B. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/8

inch thick, with predrilled holes for attachment hardware.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

207

Page 12: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

C. Letter and Background Color: As indicated for specific application under Part 3.

D. Maximum Temperature: Able to withstand temperatures of up to 160 deg F.

E. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch.

F. Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24 inches, 1/2 inch

for viewing distances of up to 72 inches, and proportionately larger lettering for greater viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal lettering.

G. Fasteners: Stainless steel rivets or self-taping screws.

H. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.

I. Arc-Flash Warning Signs: Provide arc-flash warning signs in locations and with content in

accordance with requirements of OSHA and NFPA70E and other applicable codes and standards.

J. Label Content: Include caution and warning information plus emergency notification

instructions.

2.3 WARNING TAPE

A. Acceptable Manufacturers: Seton Identification Products.

B. Material: Vinyl.

C. Minimum Thickness: 0.005 inch.

D. Letter, Pattern, and Background Color: As indicated for specific application under Part 3.

E. Waterproof Adhesive Backing: Suitable for indoor or outdoor use.

F. Maximum Temperature: 160 deg F.

G. Minimum Width: 2 inches.

2.4 DUCT LABELS

A. Acceptable Manufacturers: Seton Identification Products.

B. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/8 inch thick, and having predrilled holes for attachment hardware.

C. Letter and Background Color: As indicated for specific application under Part 3.

D. Maximum Temperature: Able to withstand temperatures up to 160 deg F.

E. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch.

F. Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24 inches, 1/2 inch

for viewing distances of up to 72 inches, and proportionately larger lettering for greater

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

208

Page 13: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal lettering.

G. Fasteners: Stainless steel rivets or self-tapping screws.

H. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.

I. Duct Label Contents: Include identification of duct service using same designations or

abbreviations as used on Drawings. Also include the following:

1. Duct size. 2. Flow-Direction Arrows: Include flow-direction arrows on main distribution ducts.

Arrows may be either integral with label or may be applied separately.

J. Stencils for Ducts:

1. Acceptable Manufacturers: Brimar Industries, Inc. 2. Lettering Size: Minimum letter height of 1-1/4 inches for viewing distances of up to 15 ft.

and proportionately larger lettering for greater viewing distances. 3. Stencil Material: Fiberboard or metal. 4. Stencil Paint: Exterior, gloss, acrylic enamel. Paint may be in pressurized spray-can form. 5. Identification Paint: Exterior, acrylic enamel. Paint may be in pressurized spray-can form. 6. Letter and Background Color: Color as indicated for specific application under Part 3.

K. Stencils for Access Panels and Door Labels, Equipment Labels, and Similar Operational

Instructions:

1. Acceptable Manufacturers: Brimar Industries, Inc. 2. Lettering Size: Minimum letter height of 1/2 inch for viewing distances of up to 72

inches and proportionately larger lettering for greater viewing distances. 3. Stencil Material: Fiberboard or metal. 4. Stencil Paint: Exterior, gloss, acrylic enamel. Paint may be in pressurized spray-can form. 5. Identification Paint: Exterior, acrylic enamel. Paint may be in pressurized spray-can form. 6. Letter and Background Color: As indicated for specific application under Part 3.

PART 3 - EXECUTION

3.1 PREPARATION

A. Clean piping and equipment surfaces of incompatible primers, paints, and encapsulants, as well as dirt, oil, grease, release agents, and other substances that could impair bond of identification devices.

3.2 INSTALLATION, GENERAL REQUIREMENTS

A. Coordinate installation of identifying devices with completion of covering and painting of

surfaces where devices are to be applied.

B. Coordinate installation of identifying devices with locations of access panels and doors.

C. Install identifying devices before installing acoustical ceilings and similar concealment.

D. Locate identifying devices so that they are readily visible from the point of normal approach.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

209

Page 14: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3.3 INSTALLATION OF EQUIPMENT LABELS, WARNING SIGNS, AND LABELS

A. Permanently fasten labels on each item of mechanical equipment.

B. Sign and Label Colors:

1. White letters on an ANSI Z535.1 safety-blue background.

C. Locate equipment labels where accessible and visible.

D. Arc-Flash Warning Signs: Provide arc-flash warning signs on electrical disconnects and other equipment where arc-flash hazard exists, as indicated on Drawings, and in accordance with requirements of OSHA and NFPA 70E, and other applicable codes and standards.

3.4 INSTALLATION OF WARNING TAPE

A. Warning Tape Color and Pattern: Yellow background with black diagonal stripes.

B. Install warning tape on pipes and ducts, with cross-designated walkways providing less than 6 ft.

of clearance.

C. Locate tape so as to be readily visible from the point of normal approach.

3.5 INSTALLATION OF DUCT LABELS

A. Install self-adhesive duct labels showing service and flow direction with permanent adhesive on

air ducts.

1. Provide labels in the following color codes:

a. For air supply ducts: White letters on blue background. b. For air return ducts: White letters on blue background. c. For exhaust, outside, relief, return, and mixed air ducts: White letters on blue

background.

B. Stenciled Duct-Label Option: Stenciled labels showing service and flow direction may be provided instead of plastic-laminated duct labels, at Installer's option.

1. For all air ducts: Black letters on white background.

C. Locate label near each point where ducts enter into and exit from concealed spaces and at

maximum intervals of 20 ft. where exposed or are concealed by removable ceiling system.

D. Stenciled Access Panels and Door Labels, Equipment Labels, and Similar Operational Instructions:

1. Black letters on White background.

END OF SECTION 230553

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

210

Page 15: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Testing, Adjusting, and Balancing of Air Systems:

a. Variable-air-volume systems. 2. Testing, adjusting, and balancing of equipment. 3. Testing, adjusting, and balancing of existing HVAC systems and equipment. 4. Duct leakage tests verification. 5. UFAD plenum leakage tests verification. 6. HVAC-control system verification.

1.3 DEFINITIONS

A. AABC: Associated Air Balance Council.

B. NEBB: National Environmental Balancing Bureau.

C. TAB: Testing, adjusting, and balancing.

D. TABB: Testing, Adjusting, and Balancing Bureau.

E. TAB Specialist: An independent entity meeting qualifications to perform TAB work.

F. TDH: Total dynamic head.

G. UFAD: Underfloor air distribution.

1.4 INFORMATIONAL SUBMITTALS

A. Qualification Data: Within 30 days of Contractor's Notice to Proceed, submit documentation

that the TAB specialist and this Project's TAB team members meet the qualifications specified in "Quality Assurance" Article.

B. Contract Documents Examination Report: Within 30 days of Contractor's Notice to Proceed,

submit the Contract Documents review report, as specified in Part 3.

C. Strategies and Procedures Plan: Within 30 days of Contractor’s Notice to Proceed, submit TAB strategies and step-by-step procedures, as specified in "Preparation" Article.

D. System Readiness Checklists: Within 30 days of Contractor's Notice to Proceed, submit system

readiness checklists, as specified in "Preparation" Article E. Examination Report: Submit a summary report of the examination review required in

"Examination" Article.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

211

Page 16: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

F. Certified TAB reports.

G. Sample report forms.

H. Instrument calibration reports, to include the following:

1. Instrument type and make. 2. Serial number. 3. Application. 4. Dates of use. 5. Dates of calibration.

1.5 QUALITY ASSURANCE

A. TAB Specialists Qualifications, Certified by NEBB:

1. TAB Field Supervisor: Employee of the TAB specialist and certified by NEBB. 2. TAB Technician: Employee of the TAB specialist and certified by NEBB.

B. ASHRAE/IES 90.1 Compliance: Applicable requirements in ASHRAE/IES 90.1, Section 6.7.2.3 -

"System Balancing."

C. Code and AHJ Compliance: TAB is required to comply with governing codes and requirements of authorities having jurisdiction.

1.6 FIELD CONDITIONS

A. Partial Owner Occupancy: Owner may occupy completed areas of building before Substantial

Completion. Cooperate with Owner during TAB operations to minimize conflicts with Owner's operations.

PART 2 - PRODUCTS (Not Applicable)

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine the Contract Documents to become familiar with Project requirements and to discover conditions in systems designs that may preclude proper TAB of systems and equipment.

B. Examine installed systems for balancing devices, such as test ports, gauge cocks, thermometer

wells, flow-control devices, balancing valves and fittings, and manual volume dampers. Verify that locations of these balancing devices are applicable for intended purpose and are accessible.

C. Examine the approved submittals for HVAC systems and equipment.

D. Examine design data, including HVAC system descriptions, statements of design assumptions

for environmental conditions and systems output, and statements of philosophies and assumptions about HVAC system and equipment controls.

E. Examine ceiling plenums and underfloor air plenums used for HVAC to verify that they are

properly separated from adjacent areas and sealed.

F. Examine equipment performance data, including fan and pump curves.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

212

Page 17: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

1. Relate performance data to Project conditions and requirements, including system effects

that can create undesired or unpredicted conditions that cause reduced capacities in all or part of a system.

2. Calculate system-effect factors to reduce performance ratings of HVAC equipment when

installed under conditions different from the conditions used to rate equipment performance. To calculate system effects for air systems, use tables and charts found in AMCA 201, "Fans and Systems," or in SMACNA's "HVAC Systems - Duct Design." Compare results with the design data and installed conditions.

G. Examine system and equipment installations and verify that field quality-control testing,

cleaning, and adjusting specified in individual Sections have been performed.

H. Examine test reports specified in individual system and equipment Sections.

I. Examine HVAC equipment and verify that bearings are greased, belts are aligned and tight, filters are clean, and equipment with functioning controls is ready for operation.

J. Examine terminal units, such as variable-air-volume boxes, and verify that they are accessible

and their controls are connected and functioning.

K. Examine control valves for proper installation for their intended function of isolating, throttling, diverting, or mixing fluid flows.

L. Examine heat-transfer coils for correct piping connections and for clean and straight fins.

M. Examine operating safety interlocks and controls on HVAC equipment.

N. Examine control dampers for proper installation for their intended function of isolating, throttling, diverting, or mixing air flows.

O. Report deficiencies discovered before and during performance of TAB procedures. Observe and

record system reactions to changes in conditions. Record default set points if different from indicated values.

3.2 PREPARATION

A. Prepare a TAB plan that includes the following:

1. Equipment and systems to be tested. 2. Strategies and step-by-step procedures for balancing the systems. 3. Instrumentation to be used. 4. Sample forms with specific identification for all equipment.

B. Perform system-readiness checks of HVAC systems and equipment to verify system readiness

for TAB work. Include, at a minimum, the following:

1. Airside:

a. Verify that leakage and pressure tests on air distribution systems have been satisfactorily completed.

b. Duct systems are complete with terminals installed. c. Volume, smoke, and fire dampers are open and functional.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

213

Page 18: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

d. Clean filters are installed. e. Fans are operating, free of vibration, and rotating in correct direction. f. Variable-frequency controllers' startup is complete and safeties are verified. g. Automatic temperature-control systems are operational. h. Ceilings are installed. i. Windows and doors are installed. j. Suitable access to balancing devices and equipment is provided.

3.3 GENERAL PROCEDURES FOR TESTING AND BALANCING

A. Perform testing and balancing procedures on each system in accordance with the procedures

contained in NEBB's Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems and in this Section.

B. Cut insulation, ducts, pipes, and equipment casings for installation of test probes to the

minimum extent necessary for TAB procedures.

1. After testing and balancing, patch probe holes in ducts with same material and thickness as used to construct ducts.

2. Install and join new insulation that matches removed materials. Restore insulation,

coverings, vapor barrier, and finish in accordance with Section 230713 "Duct Insulation," Section 230716 "HVAC Equipment Insulation," and Section 230719 "HVAC Piping Insulation."

C. Mark equipment and balancing devices, including damper-control positions, valve position

indicators, fan-speed-control levers, and similar controls and devices, with paint or other suitable, permanent identification material to show final settings.

D. Take and report testing and balancing measurements in inch-pound (IP) units.

3.4 TESTING, ADJUSTING, AND BALANCING OF HVAC EQUIPMENT

A. Test, adjust, and balance HVAC equipment indicated on Drawings, including, but not limited

to, the following:

1. Terminal units. 2. Existing Convectors (Only testing for owner evaluation, no balancing or system

modification).

3.5 GENERAL PROCEDURES FOR BALANCING AIR SYSTEMS

A. Prepare test reports for both fans and outlets. Obtain manufacturer's outlet factors and

recommended testing procedures. Crosscheck the summation of required outlet volumes with required fan volumes.

B. Prepare schematic diagrams of systems' Record drawings duct layouts.

C. For variable-air-volume systems, develop a plan to simulate diversity.

D. Determine the best locations in main and branch ducts for accurate duct-airflow measurements.

E. Check airflow patterns from the outdoor-air louvers and dampers and the return- and exhaust-air dampers through the supply-fan discharge and mixing dampers.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

214

Page 19: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

F. Locate start-stop and disconnect switches, electrical interlocks, and motor starters.

G. Verify that motor starters are equipped with properly sized thermal protection.

H. Check dampers for proper position to achieve desired airflow path.

I. Check for airflow blockages.

J. Check condensate drains for proper connections and functioning.

K. Check for proper sealing of air-handling-unit components.

3.6 PROCEDURES FOR VARIABLE-AIR-VOLUME SYSTEMS

A. Adjust the variable-air-volume systems as follows: 1. Verify that the system static pressure sensor is located two-thirds of the distance down

the duct from the fan discharge. 2. Verify that the system is under static pressure control. 3. Select the terminal unit that is most critical to the supply-fan airflow. Measure inlet static

pressure, and adjust system static pressure control set point so the entering static pressure for the critical terminal unit is not less than the sum of the terminal-unit manufacturer's recommended minimum inlet static pressure plus the static pressure needed to overcome terminal-unit discharge system losses.

4. Calibrate and balance each terminal unit for maximum and minimum design airflow as follows:

a. Adjust controls so that terminal is calling for maximum airflow. Some controllers

require starting with minimum airflow. Verify calibration procedure for specific project. b. Measure airflow and adjust calibration factor as required for design maximum

airflow. Record calibration factor. c. When maximum airflow is correct, balance the air outlets downstream from

terminal units. d. Adjust controls so that terminal is calling for minimum airflow. e. Measure airflow and adjust calibration factor as required for design minimum

airflow. Record calibration factor. If no minimum calibration is available, note any deviation from design airflow.

f. On constant volume terminals, in critical areas where room pressure is to be maintained, verify that the airflow remains constant over the full range of full cooling to full heating. Note any deviation from design airflow or room pressure.

5. After terminals have been calibrated and balanced, test and adjust system for total

airflow. Adjust fans to deliver total design airflows within the maximum allowable fan speed listed by fan manufacturer.

a. Set outside-air, return-air, and relief-air dampers for proper position that simulates

minimum outdoor-air conditions. b. Set terminals for maximum airflow. If system design includes diversity, adjust

terminals for maximum and minimum airflow, so that connected total matches fan selection and simulates actual load in the building.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

215

Page 20: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

c. Where duct conditions allow, measure airflow by main Pitot-tube traverse. If necessary, perform multiple Pitot-tube traverses close to the fan and prior to any outlets, to obtain total airflow.

d. Where duct conditions are unsuitable for Pitot-tube traverse measurements, a coil traverse may be acceptable.

6. Measure fan static pressures as follows:

a. Measure static pressure directly at the fan outlet or through the flexible connection. b. Measure static pressure directly at the fan inlet or through the flexible connection. c. Measure static pressure across each component that makes up the air-handling

system. d. Report any artificial loading of filters at the time static pressures are measured.

7. Set final return and outside airflow to the fan while operating at maximum return airflow

and minimum outdoor airflow.

a. Balance the return-air ducts and inlets. b. Verify that terminal units are meeting design airflow under system maximum flow.

8. Re-measure the inlet static pressure at the most critical terminal unit, and adjust the

system static pressure set point to the most energy-efficient set point to maintain the optimum system static pressure. Record set point and give to controls Contractor.

9. Verify final system conditions as follows:

a. Re-measure and confirm that minimum outdoor, return, and relief airflows are

within design. Readjust to match design if necessary. b. Re-measure and confirm that total airflow is within design. c. Re-measure final fan operating data, speed, volts, amps, and static profile. d. Mark final settings. e. Test system in economizer mode. Verify proper operation and adjust if necessary.

Measure and record all operating data. f. Verify tracking between supply and return fans.

3.7 DUCT LEAKAGE TESTS

A. Witness the duct leakage testing performed by Installer.

B. Verify that proper test methods are used and that leakage rates are within specified limits.

C. Report deficiencies observed.

3.8 HVAC CONTROLS VERIFICATION

A. In conjunction with system balancing, perform the following:

1. Verify HVAC control system is operating within the design limitations. 2. Confirm that the sequences of operation are in compliance with Contract Documents. 3. Verify that controllers are calibrated and function as intended. 4. Verify that controller set points are as indicated. 5. Verify the operation of lockout or interlock systems. 6. Verify the operation of valve and damper actuators. 7. Verify that controlled devices are properly installed and connected to correct controller.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

216

Page 21: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

8. Verify that controlled devices travel freely and are in position indicated by controller: open, closed, or modulating.

9. Verify location and installation of sensors to ensure that they sense only intended temperature, humidity, or pressure.

B. Reporting: Include a summary of verifications performed, remaining deficiencies, and

variations from indicated conditions.

3.9 PROCEDURES FOR TESTING, ADJUSTING, AND BALANCING EXISTING SYSTEMS

A. Perform a preconstruction inspection of existing equipment that is to remain and be reused. 1. Measure and record the operating speed, airflow, and static pressure of each fan and

equipment with fan(s). 2. Measure and record flows, temperatures, and pressures of existing hydronic convector

system. Compare the values to design or nameplate information, where information is available.

3. Measure motor voltage and amperage. Compare the values to motor nameplate information.

4. Check the condition of filters. 5. Check the condition of coils. 6. Check the operation of the drain pan and condensate-drain trap. 7. Check bearings and other lubricated parts for proper lubrication. 8. Report on the operating condition of the equipment and the results of the measurements

taken. Report deficiencies.

B. TAB After Construction: Before performing testing and balancing of renovated existing systems, inspect existing equipment that is to remain and be reused to verify that existing equipment has been cleaned and refurbished in accordance with renovation scope indicated by Contract Documents. Verify the following:

1. New filters are installed. 2. Coils are clean and fins combed. 3. Drain pans are clean. 4. Fans are clean. 5. Bearings and other parts are properly lubricated. 6. Deficiencies noted in the preconstruction report are corrected.

C. Perform testing and balancing of existing systems to the extent that existing systems are

affected by the renovation work.

1. Compare the indicated airflow of the renovated work to the measured fan airflows, and determine the new fan speed and the face velocity of filters and coils.

2. Verify that the indicated airflows of the renovated work result in filter and coil face velocities and fan speeds that are within the acceptable limits defined by equipment manufacturer.

3. Balance each air outlet.

3.10 PROGRESS REPORTING

A. Initial Construction-Phase Report: Based on examination of the Contract Documents as

specified in "Examination" Article, prepare a report on the adequacy of design for system- balancing devices. Recommend changes and additions to system-balancing devices, to facilitate

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

217

Page 22: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

proper performance measuring and balancing. Recommend changes and additions to HVAC systems and general construction to allow access for performance-measuring and -balancing devices.

3.11 FINAL REPORT

A. General: Prepare a certified written report; tabulate and divide the report into separate sections

for tested systems and balanced systems.

1. Include a certification sheet at the front of the report's binder, signed and sealed by the certified testing and balancing engineer.

2. Include a list of instruments used for procedures, along with proof of calibration. 3. Certify validity and accuracy of field data.

B. Final Report Contents: In addition to certified field-report data, include the following:

1. Manufacturers' test data. 2. Field test reports prepared by system and equipment installers. 3. Other information relative to equipment performance; do not include Shop Drawings and

Product Data.

C. General Report Data: In addition to form titles and entries, include the following data:

1. Title page. 2. Name and address of the TAB specialist. 3. Project name. 4. Project location. 5. Architect's name and address. 6. Engineer's name and address. 7. Contractor's name and address. 8. Report date. 9. Signature of TAB supervisor who certifies the report. 10. Table of Contents with the total number of pages defined for each section of the report.

Number each page in the report. 11. Summary of contents, including the following:

a. Indicated versus final performance. b. Notable characteristics of systems. c. Description of system operation sequence if it varies from the Contract

Documents.

12. Nomenclature sheets for each item of equipment. 13. Data for terminal units, including manufacturer's name, type, size, and fittings. 14. Notes to explain why certain final data in the body of reports vary from indicated values.

D. System Diagrams: Include schematic layouts of air distribution systems. Present each system

with single-line diagram and include the following:

1. Quantities of outdoor, supply, return, and exhaust airflows. 2. Duct, outlet, and inlet sizes. 3. Terminal units. 4. Balancing stations. 5. Position of balancing devices.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

218

Page 23: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

E. Convector Test Reports:

1. Coil Data:

a. System identification. b. Location. c. Coil type. d. Number of rows. e. Fin spacing in fins per inch o.c. f. Make and model number. g. Face area in sq. ft.. h. Tube size in NPS. i. Tube and fin materials. j. Circuiting arrangement.

2. Test Data (Indicated and Actual Values):

a. Control valve operation. b. Water flow rate in gpm. c. Water pressure differential in feet of head or psig. d. Entering-water temperature in deg F. e. Leaving-water temperature in deg F.

F. Round, Flat-Oval, and Rectangular Duct Traverse Reports: Include a diagram with a grid

representing the duct cross-section and record the following:

1. Report Data:

a. System fan and air-handling-unit number. b. Location and zone. c. Traverse air temperature in deg F. d. Duct static pressure in inches wg. e. Duct size in inches. f. Duct area in sq. ft.. g. Indicated airflow rate in cfm. h. Indicated velocity in fpm. i. Actual airflow rate in cfm. j. Actual average velocity in fpm. k. Barometric pressure in psig.

G. Air-Terminal-Device Reports:

1. Unit Data:

a. System and air-handling unit identification. b. Location and zone. c. Apparatus used for test. d. Area served. e. Make. f. Number from system diagram. g. Type and model number. h. Size. i. Effective area in sq. ft..

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

219

Page 24: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2. Test Data (Indicated and Actual Values):

a. Airflow rate in cfm. b. Air velocity in fpm. c. Preliminary airflow rate as needed in cfm. d. Preliminary velocity as needed in fpm. e. Final airflow rate in cfm. f. Final velocity in fpm. g. Space temperature in deg F.

H. Instrument Calibration Reports:

1. Report Data:

a. Instrument type and make. b. Serial number. c. Application. d. Dates of use. e. Dates of calibration.

3.12 VERIFICATION OF TAB REPORT

A. The TAB specialist's test and balance engineer shall conduct the inspection in the presence of

Construction Manager.

B. Construction Manager shall randomly select measurements, documented in the final report, to be rechecked. Rechecking shall be limited to the lesser of either 10 % percent of the total measurements recorded or the extent of measurements that can be accomplished in a normal 8- hour business day.

C. If rechecks yield measurements that differ from the measurements documented in the final

report by more than the tolerances allowed, the measurements shall be noted as "FAILED."

D. If the number of "FAILED" measurements is greater than 10% percent of the total measurements checked during the final inspection, the TAB shall be considered incomplete and shall be rejected.

E. If recheck measurements find the number of failed measurements noncompliant with

requirements indicated, proceed as follows:

1. TAB specialists shall recheck all measurements and make adjustments. Revise the final report and balancing device settings to include all changes; resubmit the final report and request a second final inspection. All changes shall be tracked to show changes made to previous report.

2. If the second final inspection also fails, Owner may pursue others Contract options to complete TAB work.

F. Prepare test and inspection reports.

3.13 ADDITIONAL TESTS

A. Within 90 days of completing TAB, perform additional TAB to verify that balanced conditions

are being maintained throughout and to correct unusual conditions.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

220

Page 25: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

B. Seasonal Periods: If initial TAB procedures were not performed during near-peak summer and

winter conditions, perform additional TAB during near-peak summer and winter conditions. END OF SECTION 230593

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

221

Page 26: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

SECTION 230713 - DUCT INSULATION

PART 1 - GENERAL

1.1 SUMMARY

A. Section includes insulating the following duct services:

1. Indoor, concealed supply and outdoor air. 2. Indoor, concealed return located in unconditioned space. 3. Indoor, concealed exhaust between isolation damper and penetration of building exterior.

B. Related Sections:

1. Section 230716 "HVAC Equipment Insulation." 2. Section 230719 "HVAC Piping Insulation." 3. Section 233113 "Metal Ducts" for duct liners.

1.2 ACTION SUBMITTALS

A. Product Data: For each type of product indicated. Include thermal conductivity, water vapor

permeance thickness, and jackets (both factory- and field-applied if any).

B. Shop Drawings: Include plans, elevations, sections, details, and attachments to other work.

1. Detail application of protective shields, saddles, and inserts at hangers for each type of insulation and hanger.

2. Detail insulation application at elbows, fittings, dampers, specialties and flanges for each type of insulation.

3. Detail application of field-applied jackets. 4. Detail application at linkages of control devices.

C. Samples: For each type of insulation and jacket indicated. Identify each Sample, describing

product and intended use. Sample sizes are as follows:

1. Sheet Form Insulation Materials: 12 inches square. 2. Manufacturer's Color Charts: For products where color is specified, show the full range of

colors available for each type of finish material.

1.3 INFORMATIONAL SUBMITTALS

A. Qualification Data: For qualified Installer. Include dates, materials, sealers, cements, and jackets,

with requirements indicated.

B. Material Test Reports: From a qualified testing agency acceptable to authorities having jurisdiction indicating, interpreting, and certifying test results for compliance of insulation of tests and test methods employed.

1.4 DELIVERY, STORAGE, AND HANDLING

A. Packaging: Insulation material containers are to be marked with the manufacturer's name,

appropriate ASTM standard designation, type and grade, and maximum use temperature. 1.5 COORDINATION

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

222

Page 27: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

A. Coordinate sizes and locations of supports, hangers, and insulation shields specified in Section 230529 "Hangers and Supports for HVAC Piping and Equipment."

B. Coordinate clearance requirements with duct Installer for duct insulation application. Before

preparing ductwork Shop Drawings, establish and maintain clearance requirements for installation of insulation and field-applied jackets and finishes and for space required for maintenance.

1.6 SCHEDULING

A. Schedule insulation application after pressure testing systems. Insulation application may begin

on segments that have satisfactory test results. PART 2 - PRODUCTS

2.1 INSULATION MATERIALS

A. Comply with requirements in "Duct Insulation Schedule, General," "Indoor Duct and Plenum

Insulation Schedule," and "Aboveground, Outdoor Duct and Plenum Insulation Schedule" articles for where insulating materials are to be applied.

B. Products do not contain asbestos, lead, mercury, or mercury compounds.

C. Products that come in contact with stainless steel have a leachable chloride content of less than

50 ppm when tested in accordance with ASTM C871.

D. Insulation materials for use on austenitic stainless steel are qualified as acceptable in accordance with ASTM C795.

E. Foam insulation materials do not use CFC or HCFC blowing agents in the manufacturing

process.

F. Glass-Fiber Blanket: Glass fibers bonded with a thermosetting resin; suitable for maximum use temperature up to 450 deg F in accordance with ASTM C411. Comply with ASTM C553, Type II, and ASTM C1290, Type III with factory-applied FSK jacket. Factory-applied jacket requirements are specified in "Factory-Applied Jackets" Article.

1. Acceptable Manufacturers: Johns Manville, Knauf Insulation, and Owens Corning.

2.2 ADHESIVES

A. Materials are compatible with and recommended by the manufacturer of the insulation

materials, jackets, and substrates and for bonding insulation to itself and to surfaces to be insulated unless otherwise indicated.

B. Glass-Fiber and Mineral Wool Adhesive: Comply with MIL-A-3316C, Class 2, Grade A.

1. Acceptable Manufacturers: Foster Brand, Childers Brand and Mon-Eco Industries, Inc.

2.3 MASTICS AND COATINGS

A. Vapor-Retarder Mastic: Water based; suitable for indoor use on below ambient services.

1. Acceptable Manufacturers: Foster Brand, Childers Brand and Knauf Insulation.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

223

Page 28: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2. Water-Vapor Permeance: Comply with ASTM C755, Section 7.2.2, Table 2, for insulation type and service conditions.

3. Service Temperature Range: Minus 20 to plus 180 deg F. 4. Comply with MIL-PRF-19565C, Type II, for permeance requirements. 5. Color: White

2.4 SEALANTS

A. FSK and Metal Jacket Flashing Sealants:

1. Acceptable Manufacturers: Foster Brand, Childers Brand and Mon-Eco Industries, Inc. 2. Materials are compatible with insulation materials, jackets, and substrates. 3. Fire- and water-resistant, flexible, elastomeric sealant. 4. Service Temperature Range: Minus 40 to plus 250 deg F. 5. Color: Aluminum.

B. ASJ Flashing Sealants, and Vinyl and PVC Jacket Flashing Sealants:

1. Acceptable Manufacturers: Foster Brand and Childers Brand. 2. Materials are compatible with insulation materials, jackets, and substrates. 3. Fire- and water-resistant, flexible, elastomeric sealant. 4. Service Temperature Range: Minus 40 to plus 250 deg F. 5. Color: White.

2.5 FIELD-APPLIED FABRIC-REINFORCING MESH

A. Woven Glass-Fiber Mesh: Approximately 6 oz./sq. yd. with a thread count of 5 strands by 5

strands/sq. in. for covering ducts.

1. Acceptable Manufacturers: Foster Brand and Childers Brand.

B. Woven Polyester Mesh: Approximately 1 oz./sq. yd. with a thread count of 10 strands by 10 strands/sq. in., in a Leno weave, for ducts.

1. Acceptable Manufacturers: Foster Brand, Vimasco Corporation, and Childers Brand.

2.6 TAPES

A. ASJ Tape: White vapor-retarder tape matching factory-applied jacket with acrylic adhesive,

complying with ASTM C1136.

1. Acceptable Manufacturers: 3M Industrial Adhesives, Knauf Insulation, and Avery Dennison Corporation

2. Width: 3 inches. 3. Thickness: 11.5 mils. 4. Adhesion: 90 ounces force/inch in width. 5. Elongation: 2 percent. 6. Tensile Strength: 40 lbf/inch in width. 7. ASJ Tape Disks and Squares: Precut disks or squares of ASJ tape.

B. FSK Tape: Foil-face, vapor-retarder tape matching factory-applied jacket with acrylic adhesive;

complying with ASTM C1136.

1. Acceptable Manufacturers: 3M Industrial Adhesives, Knauf Insulation, and Avery Dennison Corporation.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

224

Page 29: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2. Width: 3 inches. 3. Thickness: 6.5 mils. 4. Adhesion: 90 ounces force/inch in width. 5. Elongation: 2 percent. 6. Tensile Strength: 40 lbf/inch in width. 7. FSK Tape Disks and Squares: Precut disks or squares of FSK tape.

C. PVC Tape: White vapor-retarder tape matching field-applied PVC jacket with acrylic adhesive;

suitable for indoor and outdoor applications.

1. Acceptable Manufacturers: 3M Industrial Adhesives and Ideal Tape Co., Inc.. 2. Width: 2 inches. 3. Thickness: 6 mils. 4. Adhesion: 64 ounces force/inch in width. 5. Elongation: 500 percent. 6. Tensile Strength: 18 lbf/inch in width.

D. Aluminum-Foil Tape: Vapor-retarder tape with acrylic adhesive.

1. Acceptable Manufacturers: 3M Industrial Adhesives, Knauf Insulation, and Avery

Dennison Corporation. 2. Width: 2 inches 3. Thickness: 3.7 mils 4. Adhesion: 100 ounces force/inch in width. 5. Elongation: 5 percent. 6. Tensile Strength: 34 lbf/inch in width.

2.7 SECUREMENTS

A. Insulation Pins and Hangers:

1. Capacitor-Discharge-Weld Pins: Copper- or zinc-coated steel pin, fully annealed for

capacitor-discharge welding, 0.135-inch-diameter shank, length to suit depth of insulation indicated.

a. Acceptable Manufacturers: AGM Industries Inc., Gemco, and Midwest Fasteners,

Inc.

2. Cupped-Head, Capacitor-Discharge-Weld Pins: Copper- or zinc-coated steel pin, fully annealed for capacitor-discharge welding, 0.135-inch-diameter shank, length to suit depth of insulation indicated with integral 1-1/2-inch galvanized carbon-steel washer.

a. Acceptable Manufacturers: AGM Industries Inc., Gemco, and Midwest Fasteners,

Inc.

3. Metal, Adhesively Attached, Perforated-Base Insulation Hangers: Baseplate welded to projecting spindle that is capable of holding insulation, of thickness indicated, securely in position indicated when self-locking washer is in place. Comply with the following requirements:

a. Acceptable Manufacturers: AGM Industries Inc., Gemco, and Midwest Fasteners,

Inc. b. Baseplate: Perforated, galvanized carbon-steel sheet, 0.030 inch thick by 2 inches

square.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

225

Page 30: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

c. Spindle: Stainless steel, fully annealed, 0.106-inch-diameter shank, length to suit depth of insulation indicated.

d. Adhesive: Recommended by hanger manufacturer. Product with demonstrated capability to bond insulation hanger securely to substrates indicated without damaging insulation, hangers, and substrates.

4. Nonmetal, Adhesively Attached, Perforated-Base Insulation Hangers: Baseplate fastened to

projecting spindle that is capable of holding insulation, of thickness indicated, securely in position indicated when self-locking washer is in place. Comply with the following requirements:

a. Acceptable Manufacturers: Gemco, and Midwest Fasteners, Inc. b. Baseplate: Perforated, nylon sheet, 0.030 inch thick by 1-1/2 inches in diameter. c. Spindle: Nylon, 0.106-inch-diameter shank, length to suit depth of insulation

indicated, up to 2-1/2 inches. d. Adhesive: Recommended by hanger manufacturer. Product with demonstrated

capability to bond insulation hanger securely to substrates indicated without damaging insulation, hangers, and substrates.

5. Self-Sticking-Base Insulation Hangers: Baseplate welded to projecting spindle that is

capable of holding insulation, of thickness indicated, securely in position indicated when self-locking washer is in place. Comply with the following requirements:

a. Acceptable Manufacturers: AGM Industries Inc., Gemco, and Midwest Fasteners,

Inc. b. Baseplate: Galvanized carbon-steel sheet, 0.030 inch thick by 2 inches square. c. Spindle: Stainless steel, fully annealed, 0.106-inch-diameter shank, length to suit

depth of insulation indicated. d. Adhesive-backed base with a peel-off protective cover.

6. Insulation-Retaining Washers: Self-locking washers formed from 0.016-inch-thick,

stainless steel sheet, with beveled edge sized as required to hold insulation securely in place but not less than 1-1/2 inches in diameter.

a. Acceptable Manufacturers: AGM Industries Inc., Gemco, and Midwest Fasteners,

Inc. b. Protect ends with capped self-locking washers incorporating a spring steel insert to

ensure permanent retention of cap in exposed locations.

7. Nonmetal Insulation-Retaining Washers: Self-locking washers formed from 0.016-inch- thick nylon sheet, with beveled edge sized as required to hold insulation securely in place but not less than 1-1/2 inches in diameter.

a. Acceptable Manufacturers: Gemco, and Midwest Fasteners, Inc.

B. Staples: Outward-clinching insulation staples, nominal 3/4-inch-wide, stainless steel or Monel.

C. Wire: 0.062-inch soft-annealed, stainless steel. a. Acceptable Manufacturers: John Mansville, RPR Products, and C&F Wire.

2.8 CORNER ANGLES

A. PVC Corner Angles: 30 mils thick, minimum 1 by 1 inch, PVC in accordance with

ASTM D1784, Class 16354-C. White or color-coded to match adjacent surface.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

226

Page 31: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

B. Aluminum Corner Angles: 0.040 inch thick, minimum 1 by 1 inch, aluminum in accordance with ASTM B209, Alloy 3003, 3005, 3105, or 5005; Temper H-14.

C. Stainless-Steel Corner Angles: 0.024 inch thick, minimum 1 by 1 inch, stainless steel in

accordance with ASTM A167 or ASTM A240/A240M, Type 304.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates and conditions for compliance with requirements for installation tolerances and other conditions affecting performance of insulation application.

1. Verify that systems to be insulated have been tested and are free of defects. 2. Verify that surfaces to be insulated are clean and dry.

B. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Surface Preparation: Clean and dry surfaces to receive insulation. Remove materials that will

adversely affect insulation application.

3.3 GENERAL INSTALLATION REQUIREMENTS

A. Install insulation materials, accessories, and finishes with smooth, straight, and even surfaces;

free of voids throughout the length of ducts and fittings.

B. Install insulation materials, vapor barriers or retarders, jackets, and thicknesses required for each item of duct system as specified in insulation system schedules.

C. Install accessories compatible with insulation materials and suitable for the service. Install

accessories that do not corrode, compress, or otherwise damage insulation or jacket.

D. Install insulation with longitudinal seams at top and bottom of horizontal runs.

E. Install multiple layers of insulation with longitudinal and end seams staggered.

F. Keep insulation materials dry during application and finishing. Replace insulation materials that get wet during storage or in the installation process before being properly covered and sealed in accordance with Contract Documents.

G. Install insulation with tight longitudinal seams and end joints. Bond seams and joints with

adhesive recommended by insulation material manufacturer.

H. Install insulation with least number of joints practical.

I. Where vapor barrier is indicated, seal joints, seams, and penetrations in insulation at hangers, supports, anchors, and other projections with vapor-barrier mastic.

1. Install insulation continuously through hangers and around anchor attachments. 2. For insulation application where vapor barriers are indicated, extend insulation on anchor

legs from point of attachment to supported item to point of attachment to structure. Taper and seal ends at attachment to structure with vapor-barrier mastic.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

227

Page 32: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3. Install insert materials and install insulation to tightly join the insert. Seal insulation to

insulation inserts with adhesive or sealing compound recommended by insulation material manufacturer.

J. Apply adhesives, mastics, and sealants at manufacturer's recommended coverage rate and wet

and dry film thicknesses.

K. Install insulation with factory-applied jackets as follows:

1. Draw jacket tight and smooth, but not to the extent of creating wrinkles or areas of compression in the insulation.

2. Cover circumferential joints with 3-inch-wide strips, of same material as insulation jacket. Secure strips with adhesive and outward clinching staples along both edges of strip, spaced 4 inches o.c.

3. Overlap jacket longitudinal seams at least 1-1/2 inches. Clean and dry surface to receive self-sealing lap. Staple laps with outward clinching staples along edge at 2 inches o.c.

a. For below ambient services, apply vapor-barrier mastic over staples.

4. Cover joints and seams with tape, according to insulation material manufacturer's written

instructions, to maintain vapor seal. 5. Where vapor barriers are indicated, apply vapor-barrier mastic on seams and joints and at

ends adjacent to duct flanges and fittings.

L. Cut insulation in a manner to avoid compressing insulation.

M. Finish installation with systems at operating conditions. Repair joint separations and cracking due to thermal movement.

N. Repair damaged insulation facings by applying same facing material over damaged areas.

Extend patches at least 4 inches beyond damaged areas. Adhere, staple, and seal patches similar to butt joints.

3.4 PENETRATIONS

A. Insulation Installation at Interior Wall and Partition Penetrations (That Are Not Fire Rated):

Install insulation continuously through walls and partitions.

B. Insulation Installation at Fire-Rated Wall and Partition Penetrations: Terminate insulation at fire damper sleeves for fire-rated wall and partition penetrations. Externally insulate damper sleeves to match adjacent insulation and overlap duct insulation at least 2 inches.

1. Comply with requirements in Section 078413 "Penetration Firestopping."

C. Insulation Installation at Floor Penetrations:

1. Duct: For penetrations through fire-rated assemblies, terminate insulation at fire damper sleeves and externally insulate damper sleeve beyond floor to match adjacent duct insulation. Overlap damper sleeve and duct insulation at least 2 inches.

2. Seal penetrations through fire-rated assemblies. Comply with requirements in

Section 078413 "Penetration Firestopping."

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

228

Page 33: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3.5 INSTALLATION OF FLEXIBLE ELASTOMERIC AND POLYOLEFIN INSULATION

A. Comply with manufacturer's written installation instructions and ASTM C1710.

B. Seal longitudinal seams and end joints with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated.

C. Square and Rectangular Ducts and Plenums:

1. Provide 1/4 inch more per side for a tight, compression fit. 2. Cut sheet insulation with the following dimensions:

a. Width of duct plus 1/4 inch, one piece. b. Height of duct plus 1/4 inch, plus thickness of insulation, two pieces. c. Width of duct plus 1/4 inch, plus 2 times the thickness of insulation, one piece.

3. Insulate the bottom of the duct with the sheet from (a) above, then the sides with the two

sheets from (b) above, and finally the top of the duct with the sheet from (c) above. 4. Insulation without self-adhering backing:

a. Apply 100 percent coverage of manufacturer adhesive on the metal surface, then

the insulation, except for the last 1/4 inch where sheets will butt together. b. Roll sheet down into position. c. Press two sheets together under compression and apply adhesive at the butt joint to

seal the two sheets together.

5. Insulation with self-adhering backing:

a. Peel back release paper in 6- to 8-inch increments and line up sheet. b. Press firmly to activate adhesive. c. Align material and continue to line up correctly, pressing firmly while slowly

removing release paper. d. Allow 1/4-inch overlap for compression at butt joints. e. Apply adhesive at the butt joint to seal the two sheets together.

6. Insulate duct brackets following manufacturer's written installation instructions.

D. Circular Ducts:

1. Determine the circumference of the duct, using a strip of insulation the same thickness as to be used.

2. Cut the sheet to the required size. 3. Apply 100 percent coverage of manufacturer adhesive on the metal surface then the

insulation. 4. Apply manufacturer adhesive to the cut surfaces along 100 percent of the longitudinal

seam. Press together the seam at the ends and then the middle. Close the entire seam starting from the middle.

3.6 INSTALLATION OF GLASS-FIBER AND MINERAL-WOOL INSULATION

A. Blanket Insulation Installation on Ducts and Plenums: Secure with adhesive and insulation pins.

B. Comply with manufacturer's written installation instructions.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

229

Page 34: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

1. Apply adhesives according to manufacturer's recommended coverage rates per unit area, for 50 percent coverage of duct and plenum surfaces.

2. Apply adhesive to entire circumference of ducts and to all surfaces of fittings and transitions.

3. Install either capacitor discharge weld pins and speed washers or cupped-head, capacitor discharge weld pins on sides and bottom of horizontal ducts and sides of vertical ducts as follows:

a. On duct sides with dimensions 18 inches and smaller, place pins along longitudinal

centerline of duct. Space 3 inches maximum from insulation end joints, and 16 inches o.c.

b. On duct sides with dimensions larger than 18 inches, place pins 16 inches o.c. each way, and 3 inches maximum from insulation joints. Install additional pins to hold insulation tightly against surface at cross bracing.

c. Pins may be omitted from top surface of horizontal, rectangular ducts and plenums. d. Do not over compress insulation during installation. e. Impale insulation over pins and attach speed washers. f. Cut excess portion of pins extending beyond speed washers or bend parallel with

insulation surface. Cover exposed pins and washers with tape matching insulation facing.

4. For ducts and plenums with surface temperatures below ambient, install a continuous

unbroken vapor barrier. Create a facing lap for longitudinal seams and end joints with insulation by removing 2 inches from one edge and one end of insulation segment. Secure laps to adjacent insulation section with 1/2-inch outward-clinching staples, 1 inch o.c. Install vapor barrier consisting of factory- or field-applied jacket, adhesive, vapor- barrier mastic, and sealant at joints, seams, and protrusions.

a. Repair punctures, tears, and penetrations with tape or mastic to maintain vapor-

barrier seal. b. Install vapor stops for ductwork and plenums operating below 50 deg F at 18-foot

intervals. Vapor stops consist of vapor-barrier mastic applied in a Z-shaped pattern over insulation face, along butt end of insulation, and over the surface. Cover insulation face and surface to be insulated a width equal to two times the insulation thickness, but not less than 3 inches.

5. Overlap unfaced blankets a minimum of 2 inches on longitudinal seams and end joints.

At end joints, secure with steel bands spaced a maximum of 18 inches o.c.

6. Install insulation on rectangular duct elbows and transitions with a full insulation section for each surface. Install insulation on round and flat-oval duct elbows with individually mitered gores cut to fit the elbow.

7. Insulate duct stiffeners, hangers, and flanges that protrude beyond insulation surface with

6-inch-wide strips of same material used to insulate duct. Secure on alternating sides of stiffener, hanger, and flange with pins spaced 6 inches o.c.

C. Board Insulation Installation on Ducts and Plenums: Secure with adhesive and insulation pins.

1. Apply adhesives according to manufacturer's recommended coverage rates per unit area, for

50 percent coverage of duct and plenum surfaces.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

230

Page 35: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2. Apply adhesive to entire circumference of ducts and to all surfaces of fittings and

transitions. 3. Install either capacitor-discharge-weld pins and speed washers or cupped-head, capacitor-

discharge-weld pins on sides and bottom of horizontal ducts and sides of vertical ducts as follows:

a. On duct sides with dimensions 18 inches and smaller, place pins along longitudinal

centerline of duct. Space 3 inches maximum from insulation end joints, and 16 inches o.c.

b. On duct sides with dimensions larger than 18 inches, space pins 16 inches o.c. each way, and 3 inches maximum from insulation joints. Install additional pins to hold insulation tightly against surface at cross bracing.

c. Pins may be omitted from top surface of horizontal, rectangular ducts and plenums. d. Do not over compress insulation during installation.

e. Cut excess portion of pins extending beyond speed washers or bend parallel with insulation surface. Cover exposed pins and washers with tape matching insulation facing.

4. For ducts and plenums with surface temperatures below ambient, install a continuous

unbroken vapor barrier. Create a facing lap for longitudinal seams and end joints with insulation by removing 2 inches from one edge and one end of insulation segment. Secure laps to adjacent insulation section with 1/2-inch outward-clinching staples, 1 inch o.c. Install vapor barrier consisting of factory- or field-applied jacket, adhesive, vapor- barrier mastic, and sealant at joints, seams, and protrusions.

a. Repair punctures, tears, and penetrations with tape or mastic to maintain vapor-

barrier seal. b. Install vapor stops for ductwork and plenums operating below 50 deg F at 18-foot

intervals. Vapor stops consist of vapor-barrier mastic applied in a Z-shaped pattern over insulation face, along butt end of insulation, and over the surface. Cover insulation face and surface to be insulated a width equal to two times the insulation thickness, but not less than 3 inches.

5. Install insulation on rectangular duct elbows and transitions with a full insulation section for

each surface. Groove and score insulation to fit as closely as possible to outside and inside radius of elbows. Install insulation on round and flat-oval duct elbows with individually mitered gores cut to fit the elbow.

6. Insulate duct stiffeners, hangers, and flanges that protrude beyond insulation surface with

6-inch-wide strips of same material used to insulate duct. Secure on alternating sides of stiffener, hanger, and flange with pins spaced 6 inches o.c.

3.7 FIELD-APPLIED JACKET INSTALLATION

A. Where glass-cloth jackets are indicated, install directly over bare insulation or insulation with

factory-applied jackets.

1. Draw jacket smooth and tight to surface with 2-inch overlap at seams and joints. 2. Embed glass cloth between two 0.062-inch-thick coats of lagging adhesive. 3. Completely encapsulate insulation with coating, leaving no exposed insulation.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

231

Page 36: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

B. Where FSK jackets are indicated, install as follows:

1. Draw jacket material smooth and tight. 2. Install lap or joint strips with same material as jacket. 3. Secure jacket to insulation with manufacturer's recommended adhesive. 4. Install jacket with 1-1/2-inch laps at longitudinal seams and 3-inch-wide joint strips at

end joints. 5. Seal openings, punctures, and breaks in vapor-retarder jackets and exposed insulation

with vapor-barrier mastic.

C. Where PVC jackets are indicated, install with 1-inch overlap at longitudinal seams and end joints; for horizontal applications, install with longitudinal seams along top and bottom of tanks and vessels. Seal with manufacturer's recommended adhesive.

1. Apply two continuous beads of adhesive to seams and joints, one bead under lap and the

finish bead along seam and joint edge.

D. Where metal jackets are indicated, install with 2-inch overlap at longitudinal seams and end joints. Overlap longitudinal seams arranged to shed water. Seal end joints with weatherproof sealant recommended by insulation manufacturer. Secure jacket with stainless-steel bands 12 inches o.c. and at end joints.

3.8 FIRE-RATED INSULATION SYSTEM INSTALLATION

A. Comply with manufacturer's written installation instructions.

B. Where fire-rated insulation system is indicated, secure system to ducts and duct hangers and supports to maintain a continuous fire rating.

C. Insulate duct access panels and doors to achieve same fire rating as duct.

D. Install firestopping at penetrations through fire-rated assemblies. Fire-stop systems are specified in

Section 078413 "Penetration Firestopping."

3.9 FINISHES

A. Insulation with ASJ, Glass-Cloth, or Other Paintable Jacket Material: Paint jacket with paint system identified below and as specified in Section 099113 "Exterior Painting" and Section 099123 "Interior Painting."

1. Flat Acrylic Finish: two finish coats over a primer that is compatible with jacket material and

finish coat paint. Add fungicidal agent to render fabric mildew proof.

a. Finish Coat Material: Interior, flat, latex-emulsion size.

B. Flexible Elastomeric Thermal Insulation: After adhesive has fully cured, apply two coats of insulation manufacturer's recommended protective coating.

C. Color: Final color as selected by Architect. Vary first and second coats to allow visual

inspection of the completed Work.

D. Do not field paint aluminum or stainless-steel jackets.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

232

Page 37: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3.10 FIELD QUALITY CONTROL

A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.

B. Perform tests and inspections.

C. Tests and Inspections:

1. Inspect ductwork, randomly selected by Architect, by removing field-applied jacket and insulation in layers in reverse order of their installation. Extent of inspection is limited to one location(s) for each duct system defined in the "Duct Insulation Schedule, General" Article.

D. All insulation applications will be considered defective Work if sample inspection reveals

noncompliance with requirements.

3.11 DUCT INSULATION SCHEDULE, GENERAL A. Plenums and Ducts Requiring Insulation:

1. Indoor, concealed supply and outdoor air. 2. Indoor, concealed return located in unconditioned space. 3. Indoor, concealed exhaust between isolation damper and penetration of building exterior.

B. Items Not Insulated:

1. Fibrous-glass ducts. 2. Metal ducts with duct liner of sufficient thickness to comply with energy code and

ASHRAE/IESNA 90.1. 3. Factory-insulated flexible ducts. 4. Factory-insulated plenums and casings. 5. Flexible connectors. 6. Vibration-control devices. 7. Factory-insulated access panels and doors.

3.12 INDOOR DUCT AND PLENUM INSULATION SCHEDULE

A. Concealed, round and flat-oval, supply-air duct insulation is the following:

1. Glass-Fiber Blanket: 1-1/2 inches thick and 1.5 lb/cu. ft. nominal density.

B. Concealed, round and flat-oval, return-air duct insulation is the following: 1. Glass-Fiber Blanket: 1-1/2 inches thick and 1.5 lb/cu. ft. nominal density.

C. Concealed, round and flat-oval, exhaust-air duct insulation is the following:

1. Glass-Fiber Blanket: 2 inches thick and 1.5 lb/cu. ft. nominal density.

D. Concealed, rectangular, supply-air duct insulation is the following: 1. Glass-Fiber Blanket: 1-1/2 inches thick and 1.5 lb/cu. ft. nominal density.

E. Concealed, rectangular, return-air duct insulation is the following:

1. Glass-Fiber Blanket: 1-1/2 inches thick and 1.5 lb/cu. ft. nominal density.

F. Concealed, rectangular, exhaust-air duct insulation between isolation damper and penetration of building exterior is the following: 1. Glass-Fiber Blanket: 2 inches thick and 1.5 lb/cu. ft. nominal density.

END OF SECTION 230713

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

233

Page 38: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

SECTION 230923 - DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Extension of existing Trane DDC system for monitoring and controlling of HVAC

systems. 2. Delivery of selected control devices to equipment and systems manufacturers for factory

installation and to HVAC systems installers for field installation.

B. Related Requirements: 1. Section 230993.11 "Sequence of Operations for HVAC DDC" for control sequences in

DDC systems. 2. Communications Cabling:

a. Section 260523 "Control-Voltage Electrical Power Cables" for balanced twisted

pair communications cable. b. Section 271513 "Communications Copper Horizontal Cabling" for balanced

twisted pair communications cable. c. Section 271523 "Communications Optical Fiber Horizontal Cabling" for optical

fiber communications cable.

3. Section 260553 "Identification for Electrical Systems" for identification requirements for electrical components.

4. Section 270553 "Identification for Communications Systems" for identification requirements for communications components.

1.3 DEFINITIONS

A. Algorithm: A logical procedure for solving a recurrent mathematical problem. A prescribed set

of well-defined rules or processes for solving a problem in a finite number of steps.

B. Analog: A continuously varying signal value, such as current, flow, pressure, or temperature.

C. BACnet Specific Definitions:

1. BACnet: Building Automation Control Network Protocol, ASHRAE 135. A communications protocol allowing devices to communicate data over and services over a network.

2. BACnet Interoperability Building Blocks (BIBBs): BIBB defines a small portion of BACnet functionality that is needed to perform a particular task. BIBBs are combined to build the BACnet functional requirements for a device.

3. BACnet/IP: Defines and allows using a reserved UDP socket to transmit BACnet messages over IP networks. A BACnet/IP network is a collection of one or more IP subnetworks that share the same BACnet network number.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

234

Page 39: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

4. BACnet Testing Laboratories (BTL): Organization responsible for testing products for compliance with ASHRAE 135, operated under direction of BACnet International.

5. PICS (Protocol Implementation Conformance Statement): Written document that identifies the particular options specified by BACnet that are implemented in a device.

D. Binary: Two-state signal where a high signal level represents ON" or "OPEN" condition and a

low signal level represents "OFF" or "CLOSED" condition. "Digital" is sometimes used interchangeably with "Binary" to indicate a two-state signal.

E. Controller: Generic term for any standalone, microprocessor-based, digital controller residing

on a network, used for local or global control. Three types of controllers are indicated: Network Controller, Programmable Application Controller, and Application-Specific Controller.

F. Control System Integrator: An entity that assists in expansion of existing enterprise system and

support of additional operator interfaces to I/O being added to existing enterprise system.

G. COV: Changes of value.

H. DDC System Provider: Authorized representative of, and trained by, DDC system manufacturer and responsible for execution of DDC system Work indicated.

I. Distributed Control: Processing of system data is decentralized and control decisions are made at

subsystem level. System operational programs and information are provided to remote subsystems and status is reported back. On loss of communication, subsystems shall be capable of operating in a standalone mode using the last best available data.

J. DOCSIS: Data-Over Cable Service Interface Specifications.

K. E/P: Voltage to pneumatic.

L. Gateway: Bidirectional protocol translator that connects control systems that use different communication protocols.

M. HLC: Heavy load conditions.

N. I/O: System through which information is received and transmitted. I/O refers to analog input

(AI), binary input (BI), analog output (AO) and binary output (BO). Analog signals are continuous and represent control influences such as flow, level, moisture, pressure, and temperature. Binary signals convert electronic signals to digital pulses (values) and generally represent two-position operating and alarm status. "Digital," (DI and (DO), is sometimes used interchangeably with "Binary," (BI) and (BO), respectively.

O. I/P: Current to pneumatic.

P. LAN: Local area network.

Q. LNS: LonWorks Network Services.

R. LON Specific Definitions:

1. FTT-10: Echelon Transmitter-Free Topology Transceiver. 2. LonMark: Association comprising suppliers and installers of LonTalk products.

Association provides guidelines for implementing LonTalk protocol to ensure interoperability through a standard or consistent implementation.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

235

Page 40: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3. LonTalk: An open standard protocol developed by the Echelon Corporation that uses a "Neuron Chip" for communication. LonTalk is a register trademark of Echelon.

4. LonWorks: Network technology developed by Echelon. 5. Node: Device that communicates using CEA-709.1-C protocol and that is connected to a

CEA-709.1-C network. 6. Node Address: The logical address of a node on the network, consisting of a Domain

number, Subnet number, and Node number. "Node number" portion of an address is a number assigned to device during installation, is unique within a subnet, and is not a factory-set unique Node ID.

7. Node ID: A unique 48-bit identifier assigned at factory to each CEA-709.1-C device. Sometimes called a "Neuron ID."

8. Program ID: An identifier (number) stored in a device (usually EEPROM) that identifies node manufacturer, functionality of device (application and sequence), transceiver used, and intended device usage.

9. Standard Configuration Property Type (SCPT): Pronounced "skip-it." A standard format type maintained by LonMark International for configuration properties.

10. Standard Network Variable Type (SNVT): Pronounced "snivet." A standard format type maintained by LonMark used to define data information transmitted and received by individual nodes. "SNVT" is used in two ways. It is an acronym for "Standard Network Variable Type" and is often used to indicate a network variable itself (i.e., it can mean "a network variable of a standard network variable type").

11. Subnet: Consists of a logical grouping of up to 127 nodes, where logical grouping is defined by node addressing. Each subnet is assigned a number, which is unique within aDomain. See "Node Address."

12. TP/FT-10: Free Topology Twisted Pair network defined by CEA-709.3 and is most common media type for a CEA-709.1-C control network.

13. TP/XF-1250: High-speed, 1.25-Mbps, twisted-pair, doubly terminated bus network defined by "LonMark Interoperability Guidelines" typically used only to connect multiple TP/FT-10 networks.

14. User-Defined Configuration Property Type (UCPT): Pronounced "U-Keep-It." A Configuration Property format type that is defined by device manufacturer.

15. User-Defined Network Variable Type (UNVT): Network variable format defined by device manufacturer. UNVTs create non-standard communications that other vendors' devices may not correctly interpret and may negatively impact system operation. UNVTs are not allowed.

S. Low Voltage: As defined in NFPA 70 for circuits and equipment operating at less than 50 V or

for remote-control, signaling power-limited circuits.

T. Mobile Device: A data-enabled phone or tablet computer capable of connecting to a cellular data network and running a native control application or accessing a web interface.

U. Modbus TCP/IP: An open protocol for exchange of process data.

V. MS/TP: Master-slave/token-passing, IEE 8802-3. Datalink protocol LAN option that uses

twisted-pair wire for low-speed communication.

W. MTBF: Mean time between failures.

X. Network Controller: Digital controller, which supports a family of programmable application controllers and application-specific controllers, that communicates on peer-to-peer network for transmission of global data.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

236

Page 41: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

Y. Network Repeater: Device that receives data packet from one network and rebroadcasts it to

another network. No routing information is added to protocol.

Z. Peer to Peer: Networking architecture that treats all network stations as equal partners.

AA. POT: Portable operator's terminal.

BB. PUE: Performance usage effectiveness.

CC. RAM: Random access memory.

DD. RF: Radio frequency.

EE. Router: Device connecting two or more networks at network layer.

FF. Server: Computer used to maintain system configuration, historical and programming database.

GG. TCP/IP: Transport control protocol/Internet protocol.

HH. UPS: Uninterruptible power supply.

II. USB: Universal Serial Bus.

JJ. User Datagram Protocol (UDP): This protocol assumes that the IP is used as the underlying protocol.

KK. VAV: Variable air volume.

LL. WLED: White light emitting diode.

1.4 ACTION SUBMITTALS

A. Multiple Submissions:

1. If multiple submissions are required to execute work within schedule, first submit a coordinated schedule clearly defining intent of multiple submissions. Include a proposed date of each submission with a detailed description of submittal content to be included in each submission.

2. Clearly identify each submittal requirement indicated and in which submission the information will be provided.

3. Include an updated schedule in each subsequent submission with changes highlighted to easily track the changes made to previous submitted schedule.

B. Product Data: For each type of product include the following:

1. Construction details, material descriptions, dimensions of individual components and

profiles, and finishes. 2. Operating characteristics, electrical characteristics, and furnished accessories indicating

process operating range, accuracy over range, control signal over range, default control signal with loss of power, calibration data specific to each unique application, electrical power requirements, and limitations of ambient operating environment, including temperature and humidity.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

237

Page 42: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3. Product description with complete technical data, performance curves, and product

specification sheets. 4. Installation, operation and maintenance instructions including factors effecting

performance. 5. Bill of materials of indicating quantity, manufacturer, and extended model number for

each unique product. a. DDC controllers. b. Enclosures. c. Accessories. d. Instruments. e. Control dampers.

6. When manufacturer's product datasheets apply to a product series rather than a specific

product model, clearly indicate and highlight only applicable information. 7. Each submitted piece of product literature shall clearly cross reference specification and

drawings that submittal is to cover.

C. Software Submittal:

1. Cross-referenced listing of software to be loaded on each operator workstation, server, gateway, and DDC controller.

2. Description and technical data of all software provided, and cross-referenced to products in which software will be installed.

3. Operating system software, operator interface and programming software, color graphic software, DDC controller software, maintenance management software, and third-party software.

4. Include a flow diagram and an outline of each subroutine that indicates each program variable name and units of measure.

5. Listing and description of each engineering equation used with reference source. 6. Listing and description of each constant used in engineering equations and a reference

source to prove origin of each constant. 7. Description of operator interface to alphanumeric and graphic programming. 8. Description of each network communication protocol. 9. Description of system database, including all data included in database, database capacity

and limitations to expand database. 10. Description of each application program and device drivers to be generated, including

specific information on data acquisition and control strategies showing their relationship to system timing, speed, processing burden and system throughout.

11. Controlled Systems: Instrumentation list with element name, type of device, manufacturer, model number, and product data. Include written description of sequence of operation including schematic diagram.

D. Shop Drawings:

1. General Requirements:

a. Include cover drawing with Project name, location, Owner, Architect, Contractor

and issue date with each Shop Drawings submission. b. Include a drawing index sheet listing each drawing number and title that matches

information in each title block.

2. Include plans, elevations, sections, and mounting details where applicable.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

238

Page 43: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

clearances, method of field assembly, components, and location and size of each field connection.

4. Detail means of vibration isolation and show attachments to rotating equipment. 5. Plan Drawings indicating the following:

a. Screened backgrounds of walls, structural grid lines, HVAC equipment, ductwork,

and piping. b. Room names and numbers with coordinated placement to avoid interference with

control products indicated. c. Each desktop workstation, server, gateway, router, DDC controller, control panel

instrument connecting to DDC controller, and damper and valve connecting to DDC controller, if included in Project.

d. Exact placement of products in rooms, ducts, and piping to reflect proposed installed condition.

e. Network communication cable and raceway routing. f. Proposed routing of wiring, cabling, conduit, and tubing, coordinated with building

services for review before installation.

6. Schematic drawings for each controlled HVAC system indicating the following:

a. I/O points labeled with point names shown. Indicate instrument range, normal operating set points, and alarm set points. Indicate fail position of each damper and valve, if included in Project.

b. I/O listed in table format showing point name, type of device, manufacturer, model number, and cross-reference to product data sheet number.

c. A graphic showing location of control I/O in proper relationship to HVAC system. d. Wiring diagram with each I/O point having a unique identification and indicating

labels for all wiring terminals. e. Unique identification of each I/O that shall be consistently used between different

drawings showing same point. f. Elementary wiring diagrams of controls for HVAC equipment motor circuits

including interlocks, switches, relays, and interface to DDC controllers. g. Narrative sequence of operation. h. Graphic sequence of operation, showing all inputs and output logical blocks.

7. DDC system network riser diagram indicating the following:

a. Each device connected to network with unique identification for each. b. Interconnection of each different network in DDC system. c. For each network, indicate communication protocol, speed and physical means of

interconnecting network devices, such as copper cable type, or optical fiber cable type. Indicate raceway type and size for each.

d. Each network port for connection of an operator workstation or other type of operator interface with unique identification for each.

8. DDC system electrical power riser diagram indicating the following:

a. Each point of connection to field power with requirements

(volts/phase//hertz/amperes/connection type) listed for each. b. Each control power supply including, as applicable, transformers, power-line

conditioners, transient voltage suppression and high filter noise units, DC power supplies, and UPS units with unique identification for each.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

239

Page 44: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

connection type) listed for each. d. Power wiring type and size, race type, and size for each.

9. Monitoring and control signal diagrams indicating the following:

a. Control signal cable and wiring between controllers and I/O. b. Point-to-point schematic wiring diagrams for each product.

10. Color graphics indicating the following:

a. Itemized list of color graphic displays to be provided. b. For each display screen to be provided, a true color copy showing layout of

pictures, graphics, and data displayed. c. Intended operator access between related hierarchical display screens.

E. System Description:

1. Full description of DDC system architecture, network configuration, operator interfaces and

peripherals, servers, controller types and applications, gateways, routers and other network devices, and power supplies.

2. Complete listing and description of each report, log and trend for format and timing, and

events which initiate generation.

3. System and product operation under each potential failure condition including, but not limited to, the following: a. Loss of power. b. Loss of network communication signal. c. Loss of controller signals to inputs and outpoints. d. Operator workstation failure. e. Server failure. f. Gateway failure. g. Network failure h. Controller failure. i. Instrument failure. j. Control damper and valve actuator failure.

4. Complete bibliography of documentation and media to be delivered to Owner. 5. Description of testing plans and procedures. 6. Description of Owner training.

F. Samples:

1. For each of the following exposed product, installed in finished space for approval of

selection of aesthetic characteristics: a. Motion instruments specified in Section 230923.21 "Motion Instruments." b. Pressure instruments specified in Section 230923.23 "Pressure Instruments." c. Temperature instruments specified in Section 230923.27 "Temperature

Instruments."

1.5 INFORMATIONAL SUBMITTALS

A. Coordination Drawings:

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

240

Page 45: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

1. Plan drawings and corresponding product installation details, drawn to scale, on which

the following items are shown and coordinated with each other, using input from installers of the items involved:

a. Product installation location shown in relationship to room, duct, pipe and

equipment. b. Structural members to which products will be attached. c. Wall-mounted instruments located in finished space showing relationship to light

switches, fire-alarm devices and other installed devices. d. Size and location of wall access panels for products installed behind walls and

requiring access.

2. Reflected ceiling plans and other details, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved:

a. Ceiling components. b. Size and location of access panels for products installed above inaccessible ceiling

assemblies and requiring access. c. Items penetrating finished ceiling including the following:

1) Lighting fixtures. 2) Air outlets and inlets. 3) Speakers. 4) Sprinklers. 5) Access panels. 6) Motion sensors. 7) Pressure sensors. 8) Temperature sensors and other DDC control system instruments.

B. Qualification Data:

1. Systems Provider Qualification Data:

a. Resume of project manager assigned to Project. b. Resumes of application engineering staff assigned to Project. c. Resumes of installation and programming technicians assigned to Project. d.

Resumes of service technicians assigned to Project. e. Brief description of past project including physical address, floor area, number of

floors, building system cooling and heating capacity, and building's primary function.

f. Description of past project DDC system, noting similarities to Project scope and complexity indicated.

g. Names of staff assigned to past project that will also be assigned to execute work of this Project.

h. Owner contact information for past project including name, phone number, and e- mail address.

i. Contractor contact information for past project including name, phone number, and e- mail address.

j. Architect contact information for past project including name, phone number, and e- mail address.

2. Manufacturer's qualification data.

3. Testing agency's qualifications data.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

241

Page 46: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

C. Welding certificates.

D. Product Certificates:

1. Data Communications Protocol Certificates: Certifying that each proposed DDC system component complies with ASHRAE 135.

2. Data Communications Protocol Certificates: Certifying that each proposed DDC system component complies with LonWorks.

E. Preconstruction Test Reports: For each separate test performed.

F. Source quality-control reports.

G. Field quality-control reports.

H. Sample Warranty: For manufacturer's warranty. 1.6 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For DDC system to include in emergency, operation, and

maintenance manuals.

1. In addition to items specified in Section 017823 "Operation and Maintenance Data," include the following:

a. Project Record Drawings of as-built versions of submittal Shop Drawings provided in

electronic PDF format. b. Testing and commissioning reports and checklists of completed final versions of

reports, checklists, and trend logs. c. As-built versions of submittal Product Data. d. Names, addresses, e-mail addresses, and 24-hour telephone numbers of Installer

and service representatives for DDC system and products. e. Operator's manual with procedures for operating control systems including logging

on and off, handling alarms, producing point reports, trending data, overriding computer control, and changing set points and variables.

f. Programming manuals with description of programming language and syntax, of statements for algorithms and calculations used, of point database creation and modification, of program creation and modification, and of editor use.

g. Engineering, installation, and maintenance manuals that explain how to:

1) Design and install new points, panels, and other hardware. 2) Perform preventive maintenance and calibration. 3) Debug hardware problems. 4) Repair or replace hardware.

h. Documentation of all programs created using custom programming language

including set points, tuning parameters, and object database. i. Backup copy of graphic files, programs, and database on electronic media such as

DVDs. j. List of recommended spare parts with part numbers and suppliers.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

242

Page 47: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

k. Complete original-issue documentation, installation, and maintenance information for furnished third-party hardware including computer equipment and sensors.

l. Complete original-issue copies of furnished software, including operating systems, custom programming language, operator workstation software, and graphics software.

m. Licenses, guarantees, and warranty documents. n. Recommended preventive maintenance procedures for system components,

including schedule of tasks such as inspection, cleaning, and calibration; time between tasks; and task descriptions.

o. Owner training materials.

1.7 MAINTENANCE MATERIAL SUBMITTALS

A. Furnish extra materials and parts that match products installed and that are packaged with

protective covering for storage and identified with labels describing contents.

B. Include product manufacturers' recommended parts lists for proper product operation over four- year period following warranty period. Parts list shall be indicated for each year.

C. Furnish parts, as indicated by manufacturer's recommended parts list, for product operation

during one-year period following warranty period.

D. Furnish quantity indicated of matching product(s) in Project inventory for each unique size and type of following: 1. Programmable Application Controller: One. 2. Application-Specific Controller: One. 3. Room Temperature Sensor: One.

1.8 QUALITY ASSURANCE

A. DDC System Manufacturer Qualifications:

1. Nationally recognized manufacturer of DDC systems and products. 2. DDC systems with similar requirements to those indicated for a continuous period of five

years within time of bid. 3. DDC systems and products that have been successfully tested and in use on at least three

past projects. 4. Having complete published catalog literature, installation, operation, and maintenance

manuals for all products intended for use. 5. Having full-time in-house employees for the following:

a. Product research and development. b. Product and application engineering. c. Product manufacturing, testing, and quality control. d. Technical support for DDC system installation training, commissioning, and

troubleshooting of installations. e. Owner operator training.

B. DDC System Provider Qualifications:

1. Authorized representative of, and trained by, DDC system manufacturer. 2. Demonstrated past experience with installation of DDC system products being installed

for period within three consecutive years before time of bid.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

243

Page 48: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3. Demonstrated past experience on five projects of similar complexity, scope, and value. 4. Each person assigned to Project shall have demonstrated past experience. 5. Staffing resources of competent and experienced full-time employees that are assigned to

execute work according to schedule. 6. Service and maintenance staff assigned to support Project during warranty period. 7. Product parts inventory to support on-going DDC system operation for a period of not

less than five years after Substantial Completion. 8. DDC system manufacturer's backing to take over execution of Work if necessary to

comply with requirements indicated. Include Project-specific written letter, signed by manufacturer's corporate officer, if requested.

C. Testing Agency Qualifications: Member company of NETA.

1. Testing Agency's Field Supervisor: Certified by NETA to supervise on-site testing.

1.9 WARRANTY

A. Manufacturer's Warranty: Manufacturer and Installer agree to repair or replace products that fail

in materials or workmanship within specified warranty period.

1. Failures shall be adjusted, repaired, or replaced at no additional cost or reduction in service to Owner.

2. Include updates or upgrades to software and firmware if necessary to resolve deficiencies.

a. Install updates only after receiving Owner's written authorization.

3. Warranty service shall occur during normal business hours and commence within 24

hours of Owner's warranty service request. 4. Warranty Period: Two year(s) from date of Substantial Completion.

a. For Gateway: Two-year parts and labor warranty for each.

PART 2 - PRODUCTS

2.1 DDC SYSTEM MANUFACTURERS

1. Contractor shall extend existing Trane DDC system to control VAV box located above Meeting Room 109. All other mechanical equipment and sensors are existing and shall be reused.

2.2 PERFORMANCE REQUIREMENTS

A. DDC System Speed:

1. Response Time of Connected I/O:

a. AI point values connected to DDC system shall be updated at least every five seconds for use by DDC controllers. Points used globally shall also comply with this requirement.

b. BI point values connected to DDC system shall be updated at least every five seconds for use by DDC controllers. Points used globally shall also comply with this requirement.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

244

Page 49: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

c. AO points connected to DDC system shall begin to respond to controller output commands within two second(s). Global commands shall also comply with this requirement.

d. BO point values connected to DDC system shall respond to controller output commands within two second(s). Global commands shall also comply with this requirement.

2. Display of Connected I/O:

a. Analog point COV connected to DDC system shall be updated and displayed at

least every five seconds for use by operator. b. Binary point COV connected to DDC system shall be updated and displayed at

least every five seconds for use by operator. c. Alarms of analog and digital points connected to DDC system shall be displayed

within 15 seconds of activation or change of state. d. Graphic display refresh shall update within four seconds. e. Point change of values and alarms displayed from workstation to workstation when

multiple operators are viewing from multiple workstations shall not exceed graphic refresh rate indicated.

B. Input Point Displayed Accuracy: Input point displayed values shall meet following end-to-end

overall system accuracy, including errors associated with meter, sensor, transmitter, lead wire or cable, and analog to digital conversion.

1. Flow:

a. Air (Terminal Units): Within 5 percent of design flow rate.

2. Temperature, Dew Point: a. Air: Within 1 deg F. b. Space: Within 1 deg F.

3. Temperature, Dry Bulb:

a. Air: Within 1 deg F. b. Space: Within 1 deg F. c. Temperature Difference: Within 0.25 deg F.

4. Temperature, Wet Bulb:

a. Air: Within 1 deg F. b. Space: Within 1 deg F.

C. Precision of I/O Reported Values: Values reported in database and displayed shall have

following precision:

1. Current: a. Milliamperes: Nearest 1/100th of a milliampere. b. Amperes: Nearest 1/10th of an ampere up to 100 A; nearest ampere for 100 A and

more.

2. Energy: a. Electric Power:

1) Rate (Watts): Nearest 1/10th of a watt through 1000 W.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

245

Page 50: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2) Rate (Kilowatts): Nearest 1/10th of a kilowatt through 1000 kW; nearest

kilowatt above 1000 kW. 3) Usage (Kilowatt-Hours): Nearest kilowatt through 10,000 kW; nearest 10

kW between 10,000 and 100,000 kW; nearest 100 kW for above 100,000 kW.

b. Thermal, Rate:

1) Heating: For Btu/h, nearest Btu/h up to 1000 Btu/h; nearest 10 Btu/h

between 1000 and 10,000 Btu/h; nearest 100 Btu/h for above 10,000 Btu/h. For Mbh, round to nearest Mbh up to 1000 Mbh; nearest 10 Mbh between 1000 and 10,000 Mbh; nearest 100 Mbh above 10,000 Mbh.

2) Cooling: For tons, nearest ton up to 1000 tons; nearest 10 tons between 1000 and 10,000 tons; nearest 100 tons above 10,000 tons.

c. Thermal, Usage:

3. Flow:

1) Heating: For Btu, nearest Btu up to 1000 Btu; nearest 10 Btu between 1000 and 10,000 Btu; nearest 100 Btu for above 10,000 Btu. For Mbtu, round to nearest Mbtu up to 1000 Mbtu; nearest 10 Mbtu between 1000 and 10,000 Mbtu; nearest 100 Mbtu above 10,000 Mbtu.

2) Cooling: For ton-hours, nearest ton-hours up to 1000 ton-hours; nearest 10 ton-hours between 1000 and 10,000 ton-hours; nearest 100 tons above 10,000 tons.

a. Air: Nearest 1/10th of a cfm through 100 cfm; nearest cfm between 100 and 1000 cfm; nearest 10 cfm between 1000 and 10,000 cfm; nearest 100 cfm above 10,000 cfm.

4. Moisture (Relative Humidity):

a. Relative Humidity (Percentage): Nearest 1 percent.

5. Level: Nearest 1/100th of an inch through 10 inches; nearest 1/10 of an inch between 10 and 100 inches; nearest inch above 100 inches.

6. Speed:

a. Rotation (rpm): Nearest 1 rpm. b. Velocity: Nearest 1/10th fpm through 100 fpm; nearest fpm between 100 and

1000 fpm; nearest 10 fpm above 1000 fpm.

7. Position, Dampers and Valves (Percentage Open): Nearest 1 percent.

8. Pressure: a. Air, Ducts and Equipment: Nearest 1/10th in. w.c.. b. Space: Nearest 1/100th in. w.c..

9. Temperature:

a. Air, Ducts and Equipment: Nearest 1/10th of a degree. b. Space: Nearest 1/10th of a degree.

10. Voltage: Nearest 1/10 volt up to 100 V; nearest volt above 100 V.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

246

Page 51: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

D. Control Stability: Control variables indicated within the following limits:

1. Flow:

a. Air, Terminal Units: Within 5bpercent of design flow rate.

2. Moisture (Relative Humidity): a. Air: Within 2 percent RH.

b. Space: Within 2 percent RH.

3.

Level: Within 2 percent of reading.

4.

Pressure: a. Air, Ducts and Equipment: 1 percent of instrument range. b.

Space:

Within

1 percent of instrument range.

5.

Temperature, Dew Point: a. Air: Within 1 deg F.

b. Space: Within 1 deg F.

6.

Temperature, Dry Bulb: a. Air: Within 1 deg F.

b. Space: Within 1 deg F.

7.

Temperature, Wet Bulb: a. Air: Within 1 deg F. b. Space: Within 1 deg F.

E. Environmental Conditions for Controllers, Gateways, and Routers:

1. Products shall operate without performance degradation under ambient environmental temperature, pressure and humidity conditions encountered for installed location.

a. If product alone cannot comply with requirement, install product in a protective

enclosure that is isolated and protected from conditions impacting performance. Enclosure shall be internally insulated, electrically heated, cooled and ventilated as required by product and application.

2. Products shall be protected with enclosures satisfying the following minimum

requirements unless more stringent requirements are indicated. Products not available with integral enclosures complying with requirements indicated shall be housed in protective secondary enclosures. Installed location shall dictate the following NEMA 250 enclosure requirements:

a. Indoors, Heated with Filtered Ventilation: Type 1. b. Indoors, Heated and Air Conditioned: Type 1. c. Within Duct Systems and Air-Moving Equipment Not Exposed to Possible

Condensation: Type 2.

F. Environmental Conditions for Instruments and Actuators:

1. Instruments and actuators shall operate without performance degradation under the ambient environmental temperature, pressure, humidity, and vibration conditions

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

247

Page 52: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

specified and encountered for installed location.

a. If instruments and actuators alone cannot comply with requirement, install instruments and actuators in protective enclosures that are isolated and protected from conditions impacting performance. Enclosure shall be internally insulated, electrically heated, cooled, and ventilated as required by instrument and application.

2. Instruments, actuators and accessories shall be protected with enclosures satisfying the

following minimum requirements unless more stringent requirements are indicated. Instruments and actuators not available with integral enclosures complying with requirements indicated shall be housed in protective secondary enclosures. Installed location shall dictate the following NEMA 250 enclosure requirements:

a. Indoors, Heated with Filtered Ventilation: Type 1. b. Indoors, Heated with Non-Filtered Ventilation: Type 2. c.Indoors, Heated and Air-

conditioned: Type 1. d. Within Duct Systems and Air-Moving Equipment Not Exposed to Possible

Condensation: Type 2.

G. DDC System Reliability:

1. Design, install and configure DDC controllers, to yield a MTBF of at least 40,000 hours, based on a confidence level of at least 90 percent. MTBF value shall include any failure for any reason to any part of products indicated.

2. If required to comply with MTBF indicated, include DDC system and product redundancy to maintain DCC system, and associated systems and equipment that are being controlled, operational and under automatic control.

3. Critical systems and equipment that require a higher degree of DDC system redundancy than MTBF indicated shall be indicated on Drawings.

H. Electric Power Quality:

1. Power-Line Surges:

a. Protect DDC system products connected to ac power circuits from power-line

surges to comply with requirements of IEEE C62.41. b. Do not use fuses for surge protection. c. Test protection in the normal mode and in the common mode, using the following

two waveforms:

1) 10-by-1000-mic.sec. waveform with a peak voltage of 1500 V and a peak current of 60 A.

2) 8-by-20-mic.sec. waveform with a peak voltage of 1000 V and a peak current of 500 A.

2. Power Conditioning:

a. Protect DDC system products connected to ac power circuits from irregularities

and noise rejection. Characteristics of power-line conditioner shall be as follows:

1) At 85 percent load, output voltage shall not deviate by more than plus or minus 1 percent of nominal when input voltage fluctuates between minus 20 percent to plus 10 percent of nominal.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

248

Page 53: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

by more than plus or minus 3 percent of nominal. 3) Accomplish full correction of load switching disturbances within five

cycles, and 95 percent correction within two cycles of onset of disturbance. 4) Total harmonic distortion shall not exceed 3-1/2 percent at full load.

3. Ground Fault: Protect products from ground fault by providing suitable grounding.

Products shall not fail due to ground fault condition.

I. Backup Power Source:

1. HVAC systems and equipment served by a backup power source shall have associated DDC system products that control such systems and equipment also served from a backup power source.

J. Continuity of Operation after Electric Power Interruption:

1. Equipment and associated factory-installed controls, field-installed controls, electrical

equipment, and power supply connected to building normal and backup power systems shall automatically return equipment and associated controls to operating state occurring immediately before loss of normal power, without need for manual intervention by operator when power is restored either through backup power source or through normal power if restored before backup power is brought online.

2.3 DDC SYSTEM WIRELESS NETWORKS

A. Use an open industry standard and technology used by multiple DDC system manufacturers

technology to create a wireless mesh network to provide wireless connectivity for network devices at multiple system levels including communications from programmable application controllers and application-specific controllers to temperature sensors and from network controllers to programmable application controllers and application-specific controllers.

B. Installer shall design wireless networks to comply with DDC system performance requirements

indicated. Wireless network devices shall co-exist on same network with hardwired devices.

C. Hardwired controllers shall be capable of retrofit to wireless devices with no special software.

D. A wireless coordinator shall provide a wireless interface between programmable application controllers, application-specific controllers, and network controllers.

E. Wireless Coordinators:

1. Each wireless mesh network shall use wireless coordinator(s) for initiation and formation

of network. 2. Use direct sequence spread spectrum RF technology. 3. Operate on the 2.4-GHz ISM Band. 4. Comply with IEEE 802.15.4 for low-power, low duty-cycle RF transmitting systems. 5. FCC compliant to 47 CFR 15, Subpart B, Class A. 6. Operate as a bidirectional transceiver with sensors and routers to confirm and

synchronize data transmission. 7. Capable of communication with sensors and routers up to a maximum distance of 250

feet in line of sight.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

249

Page 54: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

verification of operation.

F. Wireless Temperature Sensors:

1. Wireless temperature sensors shall sense and transmit room temperatures, temperature set point, room occupancy notification and low battery condition to an associated router.

2. Use direct sequence spread spectrum RF technology. 3. Operate on the 2.4-GHz ISM Band. 4. Comply with IEEE 802.15.4 for low-power, low duty-cycle RF transmitting systems. 5. FCC compliant to CFR 15, Subpart B, Class A. 6. Include set point adjustment between 55 to 85 deg F. 7. Multiple sensors shall be able to report to a router connected to a DDC controller for

averaging or high and low selection.

G. One-to-One Wireless Network Receivers:

1. One-to-one wireless receivers shall receive wireless RF signals containing temperature data from multiple wireless room temperature sensors and communicate information to programmable application controllers or application-specific controllers.

a. Use direct sequence spread spectrum RF technology. b. Operate on the 2.4-GHz

ISM Band. c. Comply with IEEE 802.15.4 for low-power, low duty-cycle RF transmitting

systems. d. FCC compliant to 47 CFR 15, Subpart B, Class A. e. Operate as a bidirectional transceiver with the sensors to confirm and synchronize

data transmission. f. Capable of communication up to a distance of 200 feet. g. Include visual indication of the following:

1) Power. 2) Receiver activity. 3) Wireless RF transmission from wireless sensors. 4) No transmission, weak signal, adequate signal or excellent signal.

H. One-to-One Wireless Network Sensors:

1. One-to-one wireless sensors shall sense and report room temperatures to one-to-one

receiver.

a. Use direct sequence spread spectrum RF technology. b. Operate on the 2.4-GHz ISM Band.

c. Comply with IEEE 802.15.4 for low-power, low duty-cycle RF transmitting systems.

d. FCC compliant to CFR 15, Subpart B, Class A. e. Include set point adjustment between 55 to 85 deg F.

2.4 SYSTEM SOFTWARE

A. System Software Minimum Requirements:

1. Real-time multitasking and multiuser 64-bit operating system that allows concurrent

multiple operator workstations operating and concurrent execution of multiple real-time programs and custom program development.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

250

Page 55: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2. Operating system shall be capable of operating DOS and Microsoft Windows

applications. 3. Database management software shall manage all data on an integrated and non-redundant

basis. Additions and deletions to database shall be without detriment to existing data. Include cross linkages so no data required by a program can be deleted by an operator until that data have been deleted from respective programs.

4. Network communications software shall manage and control multiple network communications to provide exchange of global information and execution of global programs.

5. Operator interface software shall include day-to-day operator transaction processing, alarm and report handling, operator privilege level and data segregation control, custom programming, and online data modification capability.

6. Scheduling software shall schedule centrally based time and event, temporary, and exception day programs.

B. Operator Interface Software:

1. Minimize operator training through use of English language prorating and English

language point identification. 2. Minimize use of a typewriter-style keyboard through use of a pointing device similar to a

mouse. 3. Operator sign-off shall be a manual operation or, if no keyboard or mouse activity takes

place, an automatic sign-off. 4. Automatic sign-off period shall be programmable from one to 60 minutes in one-minute

increments on a per operator basis. 5. Operator sign-on and sign-off activity shall be recorded and sent to printer. 6. Security Access:

a. Operator access to DDC system shall be under password control. b. An alphanumeric password shall be field assignable to each operator. c. Operators shall be able to access DDC system by entry of proper password. d. Operator password shall be same regardless of which computer or other interface

means is used. e. Additions or changes made to passwords shall be updated automatically. f. Each operator shall be assigned an access level to restrict access to data and

functions the operator is cable of performing. g. Software shall have at least five access levels. h. Each menu item shall be assigned an access level so that a one-for-one

correspondence between operator assigned access level(s) and menu item access level(s) is required to gain access to menu item.

i. Display menu items to operator with those capable of access highlighted. Menu and operator access level assignments shall be online programmable and under password control.

7. Data Segregation:

a. Include data segregation for control of specific data routed to a workstation, to an

operator or to a specific output device, such as a printer.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

251

Page 56: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

b. Include at least 32 segregation groups. c. Segregation groups shall be selectable such as "fire points," "fire points on second

floor," "space temperature points," "HVAC points," and so on. d. Points shall be assignable to multiple segregation groups. Display and output of

data to printer or monitor shall occur where there is a match of operator or peripheral segregation group assignment and point segregations.

e. Alarms shall be displayed and printed at each peripheral to which segregation allows, but only those operators assigned to peripheral and having proper authorization level will be allowed to acknowledge alarms.

f. Operators and peripherals shall be assignable to multiple segregation groups and all assignments are to be online programmable and under password control.

8. Operators shall be able to perform commands including, but not limited to, the following:

a. Start or stop selected equipment. b. Adjust set points. c. Add, modify, and delete time programming. d. Enable and disable process execution. e. Lock and unlock alarm reporting for each point. f. Enable and disable totalization for each point. g. Enable and disable trending for each point. h. Override control loop set points. i. Enter temporary override schedules. j. Define holiday schedules. k. Change time and date. l. Enter and modify analog alarm limits. m. Enter and modify analog warning limits. n. View limits. o. Enable and disable demand limiting. p. Enable and disable duty cycle. q. Display logic programming for each control sequence.

9. Reporting:

a. Generated automatically and manually. b. Sent to displays, printers and disk files. c. Types of Reporting:

1) General listing of points. 2) List points currently in alarm. 3) List of off-line points. 4) List points currently in override status. 5) List of disabled points. 6) List points currently locked out. 7) List of items defined in a "Follow-Up" file. 8) List weekly schedules. 9) List holiday programming. 10) List of limits and deadbands.

10. Summaries: For specific points, for a logical point group, for an operator selected

group(s), or for entire system without restriction due to hardware configuration.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

252

Page 57: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

C. Project-Specific Graphics: Graphics documentation including, but not limited to, the following:

1. Site plan showing each building, and additional site elements, which are being controlled or monitored by DDC system.

2. Plan for spaces in work area:

a. Room layouts with room identification and name. b. Locations and identification of all monitored and controlled HVAC equipment and

other equipment being monitored and controlled by DDC system. c. Location and identification of each hardware point being controlled or monitored

by DDC system.

3. Control schematic for each of following, including a graphic system schematic representation, with point identification, set point and dynamic value indication, sequence of operation, and control logic diagram.

4. Graphic display for each piece of equipment connected to DDC system through a data communications link. Include dynamic indication of all points associated with equipment.

5. DDC system network riser diagram that shows schematic layout for entire system including all networks and all controllers, and other network devices.

D. Customizing Software:

1. Software to modify and tailor DDC system to specific and unique requirements of

equipment installed, to programs implemented and to staffing and operational practices planned.

2. Online modification of DDC system configuration, program parameters, and database using menu selection and keyboard entry of data into preformatted display templates.

3. As a minimum, include the following modification capability:

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

253

Page 58: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

a. Operator assignment shall include designation of operator passwords, access levels, point segregation and auto sign-off.

b. Peripheral assignment capability shall include assignment of segregation groups and operators to consoles and printers, designation of backup workstations and printers, designation of workstation header points and enabling and disabling of print- out of operator changes.

c. System configuration and diagnostic capability shall include communications and peripheral port assignments, DDC controller assignments to network, DDC controller enable and disable, assignment of command trace to points and application programs and initiation of diagnostics.

d. System text addition and change capability shall include English or native language descriptors for points, segregation groups and access levels and action messages for alarms, run time and trouble condition.

e. Time and schedule change capability shall include time and date set, time and occupancy schedules, exception and holiday schedules and daylight savings time schedules.

f. Point related change capability shall include the following:

1) System and point enable and disable. 2) Run-time enable and disable. 3) Assignment of points to segregation groups, calibration tables, lockout, and

run time and to a fixed I/O value. 4) Assignment of alarm and warning limits.

g. Application program change capability shall include the following:

1) Enable and disable of software programs. 2) Programming changes. 3) Assignment of comfort limits, global points, time and event initiators, time

and event schedules and enable and disable time and event programs.

4. Software shall allow operator to add points, or groups of points, to DDC system and to link them to energy optimization and management programs. Additions and modifications shall be online programmable using operator workstation, downloaded to other network devices and entered into their databases. After verification of point additions and associated program operation, database shall be uploaded and recorded on hard drive and disk for archived record.

5. Include high-level language programming software capability for implementation of custom DDC programs. Software shall include a compiler, linker, and up- and down-load capability.

6. Include a library of DDC algorithms, intrinsic control operators, arithmetic, logic and relational operators for implementation of control sequences. Also include, as a minimum, the following:

a. Proportional control (P). b. Proportional plus integral (PI). c. Proportional plus integral plus derivative (PID). d. Adaptive and intelligent self-learning control.

1) Algorithm shall monitor loop response to output corrections and adjust loop

response characteristics according to time constant changes imposed.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

254

Page 59: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2) Algorithm shall operate in a continuous self-learning manner and shall retain in memory a stored record of system dynamics so that on system shut down and restart, learning process starts from where it left off.

7. Fully implemented intrinsic control operators including sequence, reversing, ratio, time

delay, time of day, highest select AO, lowest select AO, analog controlled digital output, analog control AO, and digitally controlled AO.

8. Logic operators such as "And," "Or," "Not," and others that are part of a standard set available with a high-level language.

9. Arithmetic operators such as "Add," "Subtract," "Multiply," "Divide," and others that are part of a standard set available with a high-level language.

10. Relational operators such as "Equal To," "Not Equal To," "Less Than," "Greater Than," and others that are part of a standard set available with a high-level language.

E. Alarm Handling Software:

1. Include alarm handling software to report all alarm conditions monitored and transmitted

through DDC controllers, and other network devices. 2. Include first in, first out handling of alarms according to alarm priority ranking, with

most critical alarms first, and with buffer storage in case of simultaneous and multiple alarms.

3. Alarm handling shall be active at all times to ensure that alarms are processed even if an operator is not currently signed on to DDC system.

4. Alarms display shall include the following:

a. Indication of alarm condition such as "Abnormal Off," "Hi Alarm," and "Low Alarm."

b. "Analog Value" or "Status" group and point identification with native language point descriptor such as "Space Temperature, Building 110, 2nd Floor, Room 212."

c. Discrete per point alarm action message, such as "Call Maintenance Dept. Ext- 5561."

d. Include extended message capability to allow assignment and printing of extended action messages. Capability shall be operator programmable and assignable on a per point basis.

5. Alarms shall be directed to appropriate operator workstations, printers, and individual

operators by privilege level and segregation assignments. 6. Send e-mail alarm messages to designated operators. 7. Send e-mail, page, text and voice messages to designated operators for critical alarms. 8. Alarms shall be categorized and processed by class.

a. Class 1:

1) Associated with fire, security and other extremely critical equipment monitoring functions; have alarm, trouble, return to normal, and acknowledge conditions printed and displayed.

2) Unacknowledged alarms to be placed in unacknowledged alarm buffer. 3) All conditions shall cause an audible sound and shall require individual

acknowledgment to silence audible sound.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

255

Page 60: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

b. Class 2:

1) Critical, but not life-safety related, and processed same as Class 1 alarms, except do not require individual acknowledgment.

2) Acknowledgement may be through a multiple alarm acknowledgment.

c. Class 3:

1) General alarms; printed, displayed and placed in unacknowledged alarm buffer queues.

2) Each new alarm received shall cause an audible sound. Audible sound shall be silenced by "acknowledging" alarm or by pressing a "silence" key.

3) Acknowledgement of queued alarms shall be either on an individual basis or through a multiple alarm acknowledgement.

4) Alarms returning to normal condition shall be printed and not cause an audible sound or require acknowledgment.

d. Class 4:

1) Routine maintenance or other types of warning alarms. 2) Alarms to be printed only, with no display, no audible sound and no

acknowledgment required.

9. Include an unacknowledged alarm indicator on display to alert operator that there are unacknowledged alarms in system. Operator shall be able to acknowledge alarms on an individual basis or through a multiple alarm acknowledge key, depending on alarm class.

10. To ensure that no alarm records are lost, it shall be possible to assign a backup printer to accept alarms in case of failure of primary printer.

F. Reports and Logs:

1. Include reporting software package that allows operator to select, modify, or create

reports using DDC system I/O point data available. 2. Each report shall be definable as to data content, format, interval and date. 3. Report data shall be sampled and stored on DDC controller, within storage limits of DDC

controller, and then uploaded to archive on server for historical reporting. 4. Operator shall be able to obtain real-time logs of all I/O points by type or status, such as

alarm, point lockout, or normal. 5. Reports and logs shall be stored on server hard drives in a format that is readily

accessible by other standard software applications, including spreadsheets and word processing.

6. Reports and logs shall be readily printed and set to be printed either on operator command or at a specific time each day.

G. Standard Reports: Standard DDC system reports shall be provided and operator shall be able to

customize reports later.

1. All I/O: With current status and values. 2. Alarm: All current alarms, except those in alarm lockout. 3. Disabled I/O: All I/O points that are disabled. 4. Alarm Lockout I/O: All I/O points in alarm lockout, whether manual or automatic. 5. Alarm Lockout I/O in Alarm: All I/O in alarm lockout that are currently in alarm.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

256

Page 61: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

6. Logs:

a. Alarm history. b. System messages. c. System events. d. Trends.

H. Custom Reports: Operator shall be able to easily define any system data into a daily, weekly,

monthly, or annual report. Reports shall be time and date stamped and shall contain a report title.

I. Tenant Override Reports: Prepare Project-specific reports.

1. Weekly report showing daily total time in hours that each tenant has requested after-

hours HVAC. 2. Monthly report showing daily total time in hours that each tenant has requested after-

hours HVAC. 3. Annual summary report that shows after-hours HVAC usage on a monthly basis.

J. Standard Trends:

1. Trend all I/O point present values, set points, and other parameters indicated for trending. 2. Trends shall be associated into groups, and a trend report shall be set up for each group. 3. Trends shall be stored within DDC controller and uploaded to hard drives automatically

on reaching 75 percent of DDC controller buffer limit, or by operator request, or by archiving time schedule.

4. Preset trend intervals for each I/O point after review with Owner. 5. Trend intervals shall be operator selectable from 10 seconds up to 60 minutes. Minimum

number of consecutive trend values stored at one time shall be 100 per variable. 6. When drive storage memory is full, most recent data shall overwrite oldest data. 7. Archived and real-time trend data shall be available for viewing numerically and

graphically by operators.

K. Custom Trends: Operator shall be able to define a custom trend log for any I/O point in DDC system.

1. Each trend shall include interval, start time, and stop time. 2. Data shall be sampled and stored on DDC controller, within storage limits of DDC

controller, and then uploaded to archive on server hard drives. 3. Data shall be retrievable for use in spreadsheets and standard database programs.

L. Programming Software:

1. Include programming software to execute sequences of operation indicated. 2. Include programming routines in simple and easy to follow logic with detailed text

comments describing what the logic does and how it corresponds to sequence of operation.

3. Programming software shall be one of the following:

a. Graphic Based: Programming shall use a library of function blocks made from preprogrammed code designed for DDC control systems.

1) Function blocks shall be assembled with interconnection lines that represent

to control sequence in a flowchart.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

257

Page 62: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

logical results of each function block.

b. Menu Based: Programming shall be done by entering parameters, definitions, conditions, requirements and constraints.

c. Line by Line and Text Based: Programming shall declare variable types such as local, global, real, integer, and so on, at the beginning of the program. Use descriptive comments frequently to describe programming code.

4.

Include means for detecting programming errors and testing software control strategies with a simulation tool before implementing in actual control. Simulation tool may be inherent with programming software or as a separate product.

M.

Database Management Software: 1. Where a separate SQL database is used for information storage, DDC system shall

include database management software that separates database monitoring and managing functions by supporting multiple separate windows.

2. Database secure access shall be accomplished using standard SQL authentication including ability to access data for use outside of DDC system applications.

3. Database management function shall include summarized information on trend, alarm, event, and audit for the following database management actions: a. Backup. b. Purge. c. Restore.

4. Database management software shall support the following: a. Statistics: Display database server information and trend, alarm, event, and audit information on database. b. Maintenance: Include method of purging records from trend, alarm, event and audit databases by supporting separate screens for creating a backup before purging, selecting database, and allowing for retention of a selected number of day's data. c. Backup: Include means to create a database backup file and select a storage location. d. Restore: Include a restricted means of restoring a database by requiring operator to

have proper security level.

5. Database management software shall include information of current database activity, including the following:

a. Ready. b. Purging record from a database. c. Action failed. d. Refreshing statistics. e. Restoring database. f. Shrinking a database. g. Backing up a database. h. Resetting Internet information services. i. Starting network device manager. j. Shutting down the network device manager. k. Action successful.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

258

Page 63: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

6. Database management software monitoring functions shall continuously read database information once operator has logged on.

7. Include operator notification through on-screen pop-up display and e-mail message when database value has exceeded a warning or alarm limit.

8. Monitoring settings window shall have the following sections:

a. Allow operator to set and review scan intervals and start times. b. E-mail: Allow operator to create and review e-mail and phone text messages to be

delivered when a warning or an alarm is generated. c. Warning: Allow operator to define warning limit parameters, set reminder

frequency and link e-mail message. d. Alarm: Allow operator to define alarm limit parameters, set reminder frequency

and link e-mail message. e. Database Login: Protect system from unauthorized database manipulation by

creating a read access and a write access for each of trend, alarm, event and audit databases as well as operator proper security access to restore a database.

9. Monitoring settings taskbar shall include the following informational icons:

a. Normal: Indicates by color and size, or other easily identifiable means that all

databases are within their limits. b. Warning: Indicates by color and size, or other easily identifiable means that one or

more databases have exceeded their warning limit. c. Alarm: Indicates by color and size, or other easily identifiable means that one or

more databases have exceeded their alarm limit.

2.5 ASHRAE 135 GATEWAYS

A. Include gateways to connect BACnet to legacy systems, existing non-BACnet devices, and

existing non-BACnet DDC-controlled equipment, only when specifically requested and approved by Owner.

B. Include with each gateway an interoperability schedule showing each point or event on legacy

side that BACnet "client" will read, and each parameter that BACnet network will write to. Describe this interoperability of BACnet services, or BIBBs, defined in ASHRAE 135, Annex K.

C. Gateway Minimum Requirements:

1. Read and view all readable object properties on non-BACnet network to BACnet network

and vice versa where applicable. 2. Write to all writeable object properties on non-BACnet network from BACnet network

and vice versa where applicable. 3. Include single-pass (only one protocol to BACnet without intermediary protocols)

translation from non-BACnet protocol to BACnet and vice versa. 4. Comply with requirements of Data Sharing Read Property, Data Sharing Write Property,

Device Management Dynamic Device Binding-B, and Device Management Communication Control BIBBs according to ASHRAE 135.

5. Hardware, software, software licenses, and configuration tools for operator-to-gateway communications.

6. Backup programming and parameters on CD media and the ability to modify, download, backup, and restore gateway configuration.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

259

Page 64: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2.6 ASHRAE 135 PROTOCOL ANALYZER

A. Analyzer and required cables and fittings for connection to ASHRAE 135 network.

B. Analyzer shall include the following minimum capabilities:

1. Capture and store to a file data traffic on all network levels. 2. Measure bandwidth usage. 3. Filtering options with ability to ignore select traffic.

2.7 CEA-709.1-C NETWORK HARDWARE A. Routers:

1. Network routers, including routers configured as repeaters, shall comply with

requirements of CEA-709.1-C and include connection between two or more CEA-709.3 TP/FT-10 channels or between two or more CEA-709.3 TP/FT-10 channels and a TP/XF- 1250 channel.

2. IP Routers:

a. Perform layer three routing of CEA-709.1-C packets over an IP network according to

CEA-852-B. b. Include appropriate connection to the IP network and connections to CEA-709.3

TP/FT-10 or TP/XF-1250 network. c. Support the Dynamic Host Configuration Protocol for IP configuration and use of an

CEA-852-B Configuration Server (for CEA-852-B configuration), but shall not rely on these services for configuration.

d. Capable of manual configuration via a console RS-232 port.

B. Gateways:

1. Perform bidirectional protocol translation from one non-CEA-709.1-C protocol to CEA- 709.1-C.

2. Incorporate a network connection to a TP/FT-10 network according to CEA-709.3 and a connection for a non-CEA-709.1-C network.

2.8 DDC CONTROLLERS

A. DDC system shall consist of a combination of network controllers, programmable application

controllers and application-specific controllers to satisfy performance requirements indicated.

B. DDC controllers shall perform monitoring, control, energy optimization and other requirements indicated.

C. DDC controllers shall use a multitasking, multiuser, real-time digital control microprocessor

with a distributed network database and intelligence.

D. Each DDC controller shall be capable of full and complete operation as a completely independent unit and as a part of a DDC system wide distributed network.

E. Environment Requirements:

1. Controller hardware shall be suitable for the anticipated ambient conditions. 2. Controllers located in conditioned space shall be rated for operation at 32 to 120 deg F.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

260

Page 65: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

F. Power and Noise Immunity:

1. Controller shall operate at 90 to 110 percent of nominal voltage rating and shall perform an orderly shutdown below 80 percent of nominal voltage.

2. Operation shall be protected against electrical noise of 5 to 120 Hz and from keyed radios

with up to 5 W of power located within 36 inches of enclosure.

G. DDC Controller Spare Processing Capacity:

1. Include spare processing memory for each controller. RAM, PROM, or EEPROM will implement requirements indicated with the following spare memory:

a. Network Controllers: 50 percent. b. Programmable Application Controllers: Not less than 60 percent. c. Application-Specific Controllers: Not less than 70 percent.

2. Memory shall support DDC controller's operating system and database and shall include

the following:

a. Monitoring and control. b. Energy management, operation and optimization applications. c. Alarm management. d. Historical trend data of all connected I/O points. e. Maintenance applications. f. Operator interfaces. g. Monitoring of manual overrides.

H. DDC Controller Spare I/O Point Capacity: Include spare I/O point capacity for each controller as

follows:

1. Network Controllers: a. 10 percent of each AI, AO, BI, and BO point connected to controller. b. Minimum Spare I/O Points per Controller:

1) AIs: Two. 2) AOs: Two. 3) BIs: Three. 4) BOs: Three.

2. Programmable Application Controllers:

a. 10 percent of each AI, AO, BI, and BO point connected to controller. b. Minimum Spare I/O Points per Controller:

1) AIs: Two. 2) AOs: Two. 3) BIs: Three. 4) BOs: Three.

3. Application-Specific Controllers:

a. 10 percent of each AI, AO, BI, and BO point connected to controller. b. Minimum Spare I/O Points per Controller:

1) AIs: Two. 2) AOs: Two. 3) BIs: Two. 4) BOs: Two.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

261

Page 66: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

I. Maintenance and Support: Include the following features to facilitate maintenance and support:

1. Mount microprocessor components on circuit cards for ease of removal and replacement. 2. Means to quickly and easily disconnect controller from network. 3. Means to quickly and easily access connect to field test equipment. 4. Visual indication that controller electric power is on, of communication fault or trouble,

and that controller is receiving and sending signals to network.

J. General Requirements for CEA-709.1-C DDC Controllers:

1. Controllers shall be LonMark certified. 2. Distinguishable and accessible switch, button, or pin, when pressed shall broadcast its 48-

bit Node ID and Program ID over network. 3. TP/FT-10 transceiver according to CEA-709.3 and connections for TP/FT-10 control

network wiring. 4. TP/XF-1250 transceiver according to CEA-709.3 and connections for TP/XF-1250

control network wiring. 5. Communicate using CEA-709.1-C protocol. 6. Controllers configured into subnets, as required, to comply with performance

requirements indicated. 7. Network communication through LNS network management and database standard for

CEA-709.1-C network devices. 8. Locally powered, not powered through network connection. 9. Functionality required to support applications indicated, including, but not limited to, the

following: a. Input and outputs indicated and as required to support sequence of operation and application in which it is used. SNVTs shall have meaningful names identifying the value represented by an SNVT. Unless an SNVT of an appropriate engineering type is unavailable, all network variables shall be of an SNVT with engineering units appropriate to value the variable represents.

b. Configurable through SCPTs defined in LonMark SCPT List, operator-defined UCPTs, network configuration inputs (NCIs) of an SNVT type defined in LonMark SNVT List, NCIs of an operator-defined network variable type, or hardware settings on controller itself for all settings and parameters used by application in which it is used.

10. Programmable controllers shall conform to LonMark Interoperability Guidelines and have LonMark certification.

K. Inpu t and Output Point Interface:

1.

Hardwired input and output points shall connect to network, programmable application and application-specific controllers.

2. Input and output points shall be protected so shorting of point to itself, to another point, or to ground will not damage controller.

3. Input and output points shall be protected from voltage up to 24 V of any duration so that contact will not damage controller.

4. AIs: a. AIs shall include monitoring of low-voltage (zero- to 10-V dc), current (4 to 20

mA) and resistance signals from thermistor and RTD sensors.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

262

Page 67: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

b. AIs shall be compatible with, and field configurable to, sensor and transmitters

installed. c. Controller AIs shall perform analog-to-digital (A-to-D) conversion with a

minimum resolution of 8 bits or better to comply with accuracy requirements indicated.

d. Signal conditioning including transient rejection shall be provided for each AI. e. Capable of being individually calibrated for zero and span. f. Incorporate common-mode noise rejection of at least 50 dB from zero to 100 Hz

for differential inputs, and normal-mode noise rejection of at least 20 dB at 60 Hz from a source impedance of 10000 ohms.

5. AOs:

a. Controller AOs shall perform analog-to-digital (A-to-D) conversion with a

minimum resolution of 8 bits or better to comply with accuracy requirements indicated. b. Output signals shall have a range of zero- to 10-V dc as required to include proper

control of output device. c. Capable of being individually calibrated for zero and span. d. AOs shall not exhibit a drift of greater than 0.4 percent of range per year.

6. BIs:

a. Controller BIs shall accept contact closures and shall ignore transients of less than

5-ms duration. b. Isolation and protection against an applied steady-state voltage of up to 180-V ac

peak. c. BIs shall include a wetting current of at least 12 mA to be compatible with

commonly available control devices and shall be protected against effects of contact bounce and noise.

d. BIs shall sense "dry contact" closure without external power (other than that provided by the controller) being applied.

e. Pulse accumulation input points shall comply with all requirements of BIs and accept up to 10 pulses per second for pulse accumulation. Buffer shall be provided to totalize pulses. Pulse accumulator shall accept rates of at least 20 pulses per second. The totalized value shall be reset to zero on operator's command.

7. BOs:

a. Controller BOs shall include relay contact closures or triac outputs for momentary and maintained operation of output devices.

1) Relay contact closures shall have a minimum duration of 0.1 second. Relays

shall include at least 180 V of isolation. Electromagnetic interference suppression shall be provided on all output lines to limit transients to non- damaging levels. Minimum contact rating shall be 1 A at 24-V ac.

2) Triac outputs shall include at least 180 V of isolation. Minimum contact

rating shall be 1 A at 24-V ac.

b. BOs shall include for two-state operation or a pulsed low-voltage signal for pulse- width modulation control.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

263

Page 68: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

c. BOs shall be selectable for either normally open or normally closed operation. d. Include tristate outputs (two coordinated BOs) for control of three-point floating-

type electronic actuators without feedback. e. Limit use of three-point floating devices to VAV terminal unit control applications,

and other applications indicated on Drawings. Control algorithms shall operate actuator to one end of its stroke once every 24 hours for verification of operator tracking.

2.9 PROGRAMMABLE APPLICATION CONTROLLERS

A. General Programmable Application Controller Requirements:

1. Include adequate number of controllers to achieve performance indicated. 2. Controller shall have enough memory to support its operating system, database, and

programming requirements. 3. Data shall be shared between networked controllers and other network devices. 4. Operating system of controller shall manage input and output communication signals to

allow distributed controllers to share real and virtual object information and allow for central monitoring and alarms.

5. Controllers that perform scheduling shall have a real-time clock. 6. Controller shall continually check status of its processor and memory circuits. If an

abnormal operation is detected, controller shall assume a predetermined failure mode and generate an alarm notification.

7. Controllers shall be fully programmable.

B. Communication:

1. Programmable application controllers shall communicate with other devices on network.

C. Operator Interface:

1. Controller shall be equipped with a service communications port for connection to a portable operator's workstation.

2. Local Keypad and Display:

a. Equip controller with local keypad and digital display for interrogating and editing data.

b. Use of keypad and display shall require security password.

D. Serviceability:

1. Controller shall be equipped with diagnostic LEDs or other form of local visual indication of power, communication, and processor.

2. Wiring and cable connections shall be made to field-removable, modular terminal strips or to a termination card connected by a ribbon cable.

3. Controller shall maintain BIOS and programming information in event of a power loss for at least 72 hours.

2.10 APPLICATION-SPECIFIC CONTROLLERS

A. Description: Microprocessor-based controllers, which through hardware or firmware design are

dedicated to control a specific piece of equipment. Controllers are not fully user-programmable but are configurable and customizable for operation of equipment they are designed to control.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

264

Page 69: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

1. Capable of standalone operation and shall continue to include control functions without being connected to network.

2. Data shall be shared between networked controllers and other network devices.

B. Communication: Application-specific controllers shall communicate with other application specific controller and devices on network, and to programmable application and network controllers.

C. Operator Interface: Controller shall be equipped with a service communications port for

connection to a portable operator's workstation. Connection shall extend to port on space temperature sensor that is connected to controller.

D. Serviceability:

1. Controller shall be equipped with diagnostic LEDs or other form of local visual

indication of power, communication, and processor. 2. Wiring and cable connections shall be made to field-removable, modular terminal strips or

to a termination card connected by a ribbon cable. 3. Controller shall use nonvolatile memory and maintain all BIOS and programming

information in event of power loss.

2.11 CONTROLLER SOFTWARE

A. General Controller Software Requirements:

1. Software applications shall reside and operate in controllers. Editing of applications shall

occur at operator workstations. 2. I/O points shall be identified by up to 30-character point name and up to 16-character

point descriptor. Same names shall be used at operator workstations. 3. Control functions shall be executed within controllers using DDC algorithms. 4. Controllers shall be configured to use stored default values to ensure fail-safe operation.

Default values shall be used when there is a failure of a connected input instrument or loss of communication of a global point value.

B. Security:

1. Operator access shall be secured using individual security passwords and user names. 2. Passwords shall restrict operator to points, applications, and system functions as assigned

by system manager. 3. Operator log-on and log-off attempts shall be recorded. 4. System shall protect itself from unauthorized use by automatically logging off after last

keystroke. The delay time shall be operator-definable.

C. Scheduling: Include capability to schedule each point or group of points in system. Each schedule shall consist of the following:

1. Weekly Schedule:

a. Include separate schedules for each day of week. b. Each schedule should include the capability for start, stop, optimal start, optimal

stop, and night economizer. c. Each schedule may consist of up to 10 events. d. When a group of objects are scheduled together, include capability to adjust start

and stop times for each member.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

265

Page 70: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2. Exception Schedules:

a. Include ability for operator to designate any day of the year as an exception

schedule. b. Exception schedules may be defined up to a year in advance. Once an exception

schedule is executed, it will be discarded and replaced by regular schedule for that day of week.

3. Holiday Schedules:

a. Include capability for operator to define up to 99 special or holiday schedules. b. Schedules may be placed on scheduling calendar and will be repeated each year. c. Operator shall be able to define length of each holiday period.

D. System Coordination:

1. Include standard application for proper coordination of equipment. 2. Application shall include operator with a method of grouping together equipment based

on function and location. 3. Group may then be used for scheduling and other applications.

E. Binary Alarms:

1. Each binary point shall be set to alarm based on operator-specified state. 2. Include capability to automatically and manually disable alarming.

F. Analog Alarms:

1. Each analog object shall have both high and low alarm limits. 2. Alarming shall be able to be automatically and manually disabled.

G. Alarm Reporting:

1. Operator shall be able to determine action to be taken in event of an alarm. 2. Alarms shall be routed to appropriate operator workstations based on time and other

conditions. 3. Alarm shall be able to start programs, print, be logged in event log, generate custom

messages, and display graphics.

H. Remote Communication:

1. System shall have ability to dial out in the event of an alarm.

I. Electric Power Demand Limiting:

1. Demand-limiting program shall monitor building or other operator-defined electric power

consumption from signals connected to electric power meter or from a watt transducer or current transformer.

2. Demand-limiting program shall predict probable power demand such that action can be

taken to prevent exceeding demand limit. When demand prediction exceeds demand limit, action will be taken to reduce loads in a predetermined manner. When demand prediction indicates demand limit will not be exceeded, action will be taken to restore loads in a predetermined manner.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

266

Page 71: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3. Demand reduction shall be accomplished by the following means:

a. Reset air-handling unit supply temperature set points. b. Reset space temperature set points. c. De-energize equipment based on priority.

4. Demand-limiting parameters, frequency of calculations, time intervals, and other relevant

variables shall be based on the means by which electric power service provider computes demand charges.

5. Include demand-limiting prediction and control for any individual meter monitored by

system or for total of any combination of meters.

6. Include means operator to make the following changes online: a. Addition and deletion of loads controlled. b. Changes in demand intervals. c. Changes in demand limit for meter(s). d. Maximum shutoff time for equipment. e. Minimum shutoff time for equipment. f. Select rotational or sequential shedding and restoring. g. Shed and restore priority.

7. Include the following information and reports, to be available on an hourly, daily,

weekly, monthly and annual basis: a. Total electric consumption. b. Peak demand. c. Date and time of peak demand. d. Daily peak demand.

J. Maintenance Management: System shall monitor equipment status and generate maintenance

messages based on operator-designated run-time, starts, and calendar date limits.

K. Sequencing: Include application software based on sequences of operation indicated to properly sequence chillers, boilers, and other applicable HVAC equipment.

L. Control Loops:

1. Support any of the following control loops, as applicable to control required:

a. Two-position (on/off, open/close, slow/fast) control. b. Proportional control. c. Proportional plus integral (PI) control. d. Proportional plus integral plus derivative (PID) control.

1) Include PID algorithms with direct or reverse action and anti-windup. 2) Algorithm shall calculate a time-varying analog value used to position an

output or stage a series of outputs. 3) Controlled variable, set point, and PID gains shall be operator-selectable.

e. Adaptive (automatic tuning).

M. Staggered Start: Application shall prevent all controlled equipment from simultaneously

restarting after a power outage. Order which equipment (or groups of equipment) is started, along with the time delay between starts, shall be operator-selectable.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

267

Page 72: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

N. Energy Calculations:

1. Include software to allow instantaneous power or flow rates to be accumulated and converted to energy usage data.

2. Include an algorithm that calculates a sliding-window average (rolling average). Algorithm shall be flexible to allow window intervals to be operator specified (such as 15, 30, or 60 minutes).

3. Include an algorithm that calculates a fixed-window average. A digital input signal shall define start of window period (such as signal from utility meter) to synchronize fixed- window average with that used by utility.

O. Anti-Short Cycling:

1. BO points shall be protected from short cycling. 2. Feature shall allow minimum on-time and off-time to be selected.

P. On and Off Control with Differential:

1. Include an algorithm that allows a BO to be cycled based on a controlled variable and set

point. 2. Algorithm shall be direct- or reverse-acting and incorporate an adjustable differential.

Q. Run-Time Totalization:

1. Include software to totalize run-times for all BI and BO points. 2. A high run-time alarm shall be assigned, if required, by operator.

2.12 RELAYS

A. General-Purpose Relays:

1. Acceptable Manufacturers: Eaton, Seimens Industry, Inc., and Allen Bradley. 2. Relays shall be heavy duty and rated for at least 10 A at 250-V ac and 60 Hz. 3. Relays shall be either double pole double throw (DPDT) or three-pole double throw,

depending on the control application. 4. Use a plug-in-style relay with an eight-pin octal plug for DPDT relays and an 11-pin

octal plug for three-pole double-throw relays. 5. Construct the contacts of either silver cadmium oxide or gold. 6. Enclose the relay in a clear transparent polycarbonate dust-tight cover. 7. Relays shall have LED indication and a manual reset and push-to-test button. 8. Performance:

a. Mechanical Life: At least 10 million cycles. b. Electrical Life: At least 100,000 cycles at rated load. c. Pickup Time: 15 ms or less. d. Dropout Time: 10 ms or less. e. Pull-in Voltage: 85 percent of rated voltage. f. Dropout Voltage: 50 percent of nominal rated voltage. g. Power Consumption: 2 VA. h. Ambient Operating Temperatures: Minus 40 to 115 deg F.

9. Equip relays with coil transient suppression to limit transients to non-damaging levels. 10. Plug each relay into an industry-standard, 35-mm DIN rail socket. Plug all relays located in

control panels into sockets that are mounted on a DIN rail.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

268

Page 73: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

11. Relay socket shall have screw terminals. Mold into the socket the coincident screw terminal numbers and associated octal pin numbers.

B. Multifunction Time-Delay Relays:

1. Acceptable Manufacturers: Eaton, Seimens Industry, Inc., and Allen Bradley. 2. Relays shall be continuous duty and rated for at least 10 A at 240-V ac and 60 Hz. 3. Relays shall be DPDT relay with up to eight programmable functions to provide on/off

delay, interval and recycle timing functions. 4. Use a plug-in-style relay with either an 8- or 11-pin octal plug. 5. Construct the contacts of either silver cadmium oxide or gold. 6. Enclose the relay in a dust-tight cover. 7. Include knob and dial scale for setting delay time. 8. Performance:

a. Mechanical Life: At least 10 million cycles. b. Electrical Life: At least 100,000 cycles at rated load. c. Timing Ranges: Multiple ranges from 0.1 seconds to 100 minutes. d. Repeatability: Within 2 percent. e. Recycle Time: 45 ms. f. Minimum Pulse Width Control: 50 ms. g. Power Consumption: 5 VA or less at 120-V ac. h. Ambient Operating Temperatures: Minus 40 to 115 deg F.

9. Equip relays with coil transient suppression to limit transients to non-damaging levels. 10. Plug each relay into an industry-standard, 35-mm DIN rail socket. Plug all relays located in

control panels into sockets that are mounted on a DIN rail. 11. Relay socket shall have screw terminals. Mold into the socket the coincident screw

terminal numbers and associated octal pin numbers.

C. Latching Relays:

1. Acceptable Manufacturers: Eaton, Seimens Industry, Inc., and Allen Bradley. 2. Relays shall be continuous duty and rated for at least 10 A at 250-V ac and 60 Hz. 3. Relays shall be either DPDT or three-pole double throw, depending on the control

application. 4. Use a plug-in-style relay with a multibladed plug. 5. Construct the contacts of either silver cadmium oxide or gold. 6. Enclose the relay in a clear transparent polycarbonate dust-tight cover. 7. Performance:

a. Mechanical Life: At least 10 million cycles. b. Electrical Life: At least 100,000 cycles at rated load. c. Pickup Time: 15 ms or less. d. Dropout Time: 10 ms or less. e. Pull-in Voltage: 85 percent of rated voltage. f. Dropout Voltage: 50 percent of nominal rated voltage. g. Power Consumption: 2 VA. h. Ambient Operating Temperatures: Minus 40 to 115 deg F.

8. Equip relays with coil transient suppression to limit transients to non-damaging levels.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

269

Page 74: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

9. Plug each relay into an industry-standard, 35-mm DIN rail socket. Plug all relays located in control panels into sockets that are mounted on a DIN rail.

10. Relay socket shall have screw terminals. Mold into the socket the coincident screw terminal numbers and associated octal pin numbers.

D. Current Sensing Relay:

1. Acceptable Manufacturers: Eaton, Functional Devices, Inc., Square D. 2. Monitors ac current. 3. Independent adjustable controls for pickup and dropout current. 4. Energized when supply voltage is present and current is above pickup setting. 5. De-energizes when monitored current is below dropout current. 6. Dropout current is adjustable from 50 to 95 percent of pickup current. 7. Include a current transformer, if required for application. 8. House current sensing relay and current transformer in its own enclosure. Use

NEMA 250, Type 12 enclosure for indoors and NEMA 250, Type 4 for outdoors.

E. Combination On-Off Status Sensor and On-Off Relay:

1. Acceptable Manufacturers: Functional Devices, Inc., and Veris Industries. 2. Description:

a. On-off control and status indication in a single device. b. LED status indication of activated relay and current trigger. c. Closed-Open-Auto override switch located on the load side of the relay.

3. Performance:

a. Ambient Temperature: Minus 30 to 140 deg F. b. Voltage Rating: Single-phase loads rated for 300-V ac. Three-phase loads rated for

600-V ac.

4. Status Indication:

a. Current Sensor: Integral sensing for single-phase loads up to 20 A and external solid or split sensing ring for three-phase loads up to 150 A.

b. Current Sensor Range: As required by application. c. Current Set Point: Adjustable. d. Current Sensor Output:

1) Solid-state, single-pole double-throw contact rated for 30-V ac and dc and

for 0.4 A. 2) Solid-state, single-pole double-throw contact rated for 120-V ac and 1.0 A. 3) Analog, zero- to 5- or 10-V dc. 4) Analog, 4 to 20 mA, loop powered.

5. Relay: Single-pole double-throw, continuous-duty coil; rated for 10-million mechanical

cycles.

6. Enclosure: NEMA 250, Type 1 enclosure.

2.13 CONTROL WIRE AND CABLE

A. Wire: Single conductor control wiring above 24 V.

1. Wire size shall be at least No. 18 AWG.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

270

Page 75: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2. Conductor shall be 7/24 soft annealed copper strand with 2- to 2.5-inch lay. 3. Conductor insulation shall be 600 V, Type THWN or Type THHN, and 90 deg C

according to UL 83. 4. Conductor colors shall be black (hot), white (neutral), and green (ground). 5. Furnish wire on spools.

B. Single Twisted Shielded Instrumentation Cable above 24 V:

1. Wire size shall be a minimum No. AWG. 2. Conductors shall be a twisted, 7/24 soft annealed copper strand with a 2- to 2.5-inch lay. 3. Conductor insulation shall have a Type THHN/THWN or Type TFN rating. 4. Shielding shall be 100 percent type, 0.35/0.5-mil aluminum/Mylar tape, helically applied

with 25 percent overlap, and aluminum side in with tinned copper drain wire. 5. Outer jacket insulation shall have a 600-V, 90-deg C rating and shall be Type TC cable. 6. For twisted pair, conductor colors shall be black and white. For twisted triad, conductor

colors shall be black, red and white. 7. Furnish wire on spools.

C. Single Twisted Shielded Instrumentation Cable 24 V and Less:

1. Wire size shall be a minimum No. 22 AWG. 2. Conductors shall be a twisted, 7/24 soft annealed copper stranding with a 2- to 2.5-inch

lay. 3. Conductor insulation shall have a nominal 15-mil thickness, constructed from flame-

retardant PVC. 4. Shielding shall be 100 percent type, 1.35-mil aluminum/polymer tape, helically applied

with 25 percent overlap, and aluminum side in with tinned copper drain wire. 5. Outer jacket insulation shall have a 300-V, 105-deg C rating and shall be Type PLTC

cable. 6. For twisted pair, conductor colors shall be black and white. For twisted triad, conductor

colors shall be black, red and white. 7. Furnish wire on spools.

D. LAN and Communication Cable: Comply with DDC system manufacturer requirements for

network being installed.

1. Cable shall be balanced twisted pair. 2. Comply with the following requirements and for balanced twisted pair cable described in

Section 260523 "Control-Voltage Electrical Power Cables.

a. Cable shall be plenum rated. b. Cable shall have a unique color that is different from other cables used on Project.

2.14 ACCESSORIES

A. Damper Blade Limit Switches:

1. Sense positive open and/or closed position of the damper blades. 2. NEMA 250, Type 13, oil-tight construction. 3. Arrange for the mounting application. 4. Additional waterproof enclosure when required by its environment. 5. Arrange to prevent "over-center" operation. B. Instrument Enclosures:

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

271

Page 76: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

1. Acceptable Manufacturers: Hammond Mfg. Co., Inc., Hoffman, and Saginaw Control and Engineering.

2. Include instrument enclosure for secondary protection to comply with requirements indicated in "Performance Requirements" Article.

3. NRTL listed and labeled to UL 50. 4. Sized to include at least 25 percent spare area on subpanel. 5. Instrument(s) mounted within enclosure on internal subpanel(s). 6. Enclosure face with engraved, laminated phenolic nameplate for each instrument within

enclosure. 7. Enclosures housing pneumatic instruments shall include main pressure gauge and a

branch pressure gauge for each pneumatic device, installed inside. 8. Enclosures housing multiple instruments shall route tubing and wiring within enclosure in

a raceway having a continuous removable cover. 9. Enclosures larger than 12 inches shall have a hinged full-size face cover. 10. Equip enclosure with lock and common key.

2.15 IDENTIFICATION

A. Control Equipment, Instruments, and Control Devices:

1. Self-adhesive label bearing unique identification.

a. Include instruments with unique identification identified by equipment being

controlled or monitored, followed by point identification.

2. Letter size shall be as follows: a. DDC Controllers: Minimum of 0.5 inch high. b. Enclosures: Minimum of 0.5 inch high. c. Accessories: Minimum of 0.25 inch high. d. Instruments: Minimum of 0.25 inch high. e. Control Damper and Valve Actuators: Minimum of 0.25 inch high.

3. Legend shall consist of white lettering on black background. 4. Laminated acrylic or melamine plastic sign shall be engraved phenolic consisting of three

layers of rigid laminate. Top and bottom layers are color-coded black with contrasting white center exposed by engraving through outer layer and shall be fastened with drive pins.

5. Instruments, control devices, and actuators with Project-specific identification tags having unique identification numbers following requirements indicated and provided by original manufacturer do not require additional identification.

B. Raceway and Boxes:

1. Comply with requirements for identification specified in Section 260553 "Identification

for Electrical Systems." 2. Paint cover plates on junction boxes and conduit same color as the tape banding for

conduits. After painting, label cover plate "HVAC Controls," using an engraved phenolic tag.

C. Equipment Warning Labels:

1. Self-adhesive label with pressure-sensitive adhesive back and peel-off protective jacket. 2. Lettering size shall be at least 14-point type with white lettering on red background.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

272

Page 77: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3. Warning label shall read "CAUTION-Equipment operated under remote automatic

control and may start or stop at any time without warning. Switch electric power disconnecting means to OFF position before servicing."

4. Lettering shall be enclosed in a white line border. Edge of label shall extend at least 0.25 inch beyond white border.

2.16 SOURCE QUALITY CONTROL

A. Testing Agency: Engage a qualified testing agency to evaluate the following according to

industry standards for each product, and to verify DDC system reliability specified in performance requirements:

1. DDC controllers.

B. Product(s) will be considered defective if they do not pass tests and inspections.

C. Prepare test and inspection reports.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates and conditions for compliance with requirements for installation tolerances

and other conditions affecting performance of the Work.

1. Verify compatibility with and suitability of substrates.

B. Examine roughing-in for products to verify actual locations of connections before installation.

1. Examine roughing-in for instruments installed in piping to verify actual locations of connections before installation.

2. Examine roughing-in for instruments installed in duct systems to verify actual locations of connections before installation.

C. Examine walls, floors, roofs, and ceilings for suitable conditions where product will be

installed.

D. Prepare written report, endorsed by Installer, listing conditions detrimental to performance of the Work.

E. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 DDC SYSTEM INTERFACE WITH OTHER SYSTEMS AND EQUIPMENT

A. Communication Interface to Equipment with Integral Controls:

1. DDC system shall have communication interface with equipment having integral controls and having a communication interface for remote monitoring or control.

2. Equipment to Be Connected: a. Air-terminal units specified in Section 233600 "Air Terminal Units."

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

273

Page 78: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3.3 DDC SYSTEM INTERFACE WITH EXISTING SYSTEMS

A. Interface with Existing Systems:

1. DDC systems shall interface with existing Trane building controls to achieve integration. 2. Monitoring and Control of DDC System by Existing Control System:

a. DDC system performance requirements shall be satisfied when monitoring and

controlling DDC system by existing control system. b. Operator of existing system shall be able to upload, download, monitor, trend,

control and program every input and output point in DDC system from existing control system using existing control system software and operator workstations.

c. Remote monitoring and control from existing control system shall not require operators of existing control system to learn new software.

d. Interface of DDC system into existing control system shall be transparent to operators of existing control system and allow operators to program, monitor, and control DDC system from any operator workstation connected to existing control system.

3. Integration of Existing Control System into DDC System:

a. Existing control system performance requirements shall be satisfied when

monitoring and controlling existing control system through DDC system. b. Operator shall be able to upload, download, monitor, alarm, report, trend, control

and program every input and output point in existing system from DDC system using operator workstations and software provided. The combined systems shall share one database.

c. Interface of existing control system I/O points into DDC system shall be transparent to operators. All operational capabilities shall be identical regardless of whether I/O already exists or I/O is being installed.

B. Integration with Existing Enterprise System:

1. DDC system shall interface with an existing enterprise system to adhere to Owner

standards already in-place and to achieve integration.

2. Owner's control system integrator will provide the following services:

a. Enterprise system expansion and development of graphics, logs, reports, trends and other operational capabilities of enterprise system for I/O being added to DDC control system for use by enterprise system operators.

b. Limited assistance during commissioning to extent of DDC system integration with existing enterprise system.

c. Prepare on-site demonstration mockup of integration of DDC system to be installed with existing system before installing DDC system.

3. Engage Owner's control system integrator to provide the following services:

a. Enterprise system expansion and development of graphics, logs, reports, trends and

other operational capabilities of enterprise system for I/O being added to DDC control system for use by enterprise system operators.

b. Limited assistance during commissioning to extent of DDC system integration with existing enterprise system.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

274

Page 79: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

installed with existing system before installing DDC system.

3.4 CONTROL DEVICES FOR INSTALLATION BY INSTALLERS

A. Deliver selected control devices, specified in indicated HVAC instrumentation and control device Sections, to identified equipment and systems manufacturers for factory installation and to identified installers for field installation.

3.5 CONTROL DEVICES FOR EQUIPMENT MANUFACTURER FACTORY INSTALLATION

A. Deliver the following to terminal unit manufacturer for factory installation. Include installation instructions to terminal unit manufacturer.

1. Application-specific controller. 2. Electric damper actuator. Damper actuators are specified in Section 230923.12 "Control

Dampers." 3. Unit-mounted flow and pressure sensors, transmitters, and transducers. Flow sensors,

transmitters, and transducers are specified in Section 230923.14 "Flow Instruments." Pressure sensors, switches, and transmitters are specified in Section 230923.23 "Pressure Instruments."

4. Unit-mounted temperature sensors. Air-temperature sensors, switches, and transmitters are specified in Section 230923.27 "Temperature Instruments."

5. Relays.

3.6 GENERAL INSTALLATION REQUIREMENTS

A. Install products to satisfy more stringent of all requirements indicated.

B. Install products level, plumb, parallel, and perpendicular with building construction.

C. Support products, tubing, piping wiring and raceways. Brace products to prevent lateral movement and sway or a break in attachment when subjected to forces.

D. If codes and referenced standards are more stringent than requirements indicated, comply with

requirements in codes and referenced standards.

E. Fabricate openings and install sleeves in ceilings, floors, roof, and walls required by installation of products. Before proceeding with drilling, punching, and cutting, check for concealed work to avoid damage. Patch, flash, grout, seal, and refinish openings to match adjacent condition.

F. Firestop Penetrations Made in Fire-Rated Assemblies: Comply with requirements in

Section 078413 "Penetration Firestopping."

G. Seal penetrations made in acoustically rated assemblies. Comply with requirements in Section 079200 "Joint Sealants."

H. Welding Requirements:

1. Restrict welding and burning to supports and bracing.

2. No equipment shall be cut or welded without approval. Welding or cutting will not be approved if there is risk of damage to adjacent Work.

3. Welding, where approved, shall be by inert-gas electric arc process and shall be

performed by qualified welders according to applicable welding codes.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

275

Page 80: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

4. If requested on-site, show satisfactory evidence of welder certificates indicating ability to perform welding work intended.

I. Fastening Hardware:

1. Stillson wrenches, pliers, and other tools that damage surfaces of rods, nuts, and other

parts are prohibited for work of assembling and tightening fasteners.

2. Tighten bolts and nuts firmly and uniformly. Do not overstress threads by excessive force or by oversized wrenches.

3. Lubricate threads of bolts, nuts and screws with graphite and oil before assembly.

J. If product locations are not indicated, install products in locations that are accessible and that

will permit service and maintenance from floor, equipment platforms, or catwalks without removal of permanently installed furniture and equipment.

K. Corrosive Environments:

1. Avoid or limit use of materials in corrosive airstreams and environments, including, but

not limited to, the following: a. Laboratory exhaust-air streams. b. Process exhaust-air streams.

2. When conduit is in contact with a corrosive airstream and environment, use Type 316

stainless steel conduit and fittings or conduit and fittings that are coated with a corrosive- resistant coating that is suitable for environment. Comply with requirements for installation of raceways and boxes specified in Section 260533 "Raceways and Boxes for Electrical Systems."

3. Where instruments are located in a corrosive airstream and are not corrosive resistant

from manufacturer, field install products in NEMA 250, Type 4X enclosure constructed of Type 316L stainless steel.

3.7 ELECTRIC POWER CONNECTIONS

A. Connect electrical power to DDC system products requiring electrical power connections.

B. Design of electrical power to products not indicated with electric power is delegated to DDC

system provider and installing trade. Work shall comply with NFPA 70 and other requirements indicated.

C. Comply with requirements in Section 262816 "Enclosed Switches and Circuit Breakers" for

electrical power circuit breakers.

D. Comply with requirements in Section 260519 "Low-Voltage Electrical Power Conductors and Cables" for electrical power conductors and cables.

E. Comply with requirements in Section 260533 "Raceways and Boxes for Electrical Systems" for

electrical power raceways and boxes.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

276

Page 81: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3.8 IDENTIFICATION

A. Identify system components, wiring, cabling, and terminals. Comply with requirements in Section 260553 "Identification for Electrical Systems" for identification products and installation.

B. Install self-adhesive labels with unique identification on face for each of the following:

1. DDC controller. 2. Enclosure. 3. Accessory.

C. Install unique instrument identification on face of each instrument connected to a DDC

controller.

D. Install unique identification on face of each control damper actuator connected to a DDC controller.

E. Where product is installed above accessible tile ceiling, also install matching identification on

face of ceiling grid located directly below.

F. Where product is installed above an inaccessible ceiling, also install identification on face of access door directly below.

G. Warning Labels and Signs:

1. Shall be permanently attached to equipment that can be automatically started by DDC

control system. 2. Shall be located in highly visible location near power service entry points.

3.9 CONTROL WIRE, CABLE AND RACEWAYS INSTALLATION

A. Comply with NECA 1.

B. Wire and Cable Installation:

1. Comply with installation requirements in Section 260523 "Control-Voltage Electrical Power Cables."

2. Comply with installation requirements in Section 271313 "Communications Copper Backbone Cabling."

3. Comply with installation requirements in Section 271513 "Communications Copper Horizontal Cabling."

4. Install cables with protective sheathing that is waterproof and capable of withstanding continuous temperatures of 90 deg C with no measurable effect on physical and electrical properties of cable.

a. Provide shielding to prevent interference and distortion from adjacent cables and

equipment.

5. Terminate wiring in a junction box.

a. Clamp cable over jacket in junction box. b. Individual conductors in the stripped section of the cable shall be slack between

the clamping point and terminal block.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

277

Page 82: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

6. Terminate field wiring and cable not directly connected to instruments and control devices having integral wiring terminals using terminal blocks.

7. Install signal transmission components according to IEEE C2, REA Form 511a, NFPA 70, and as indicated.

8. Use shielded cable to transmitters. 9. Use shielded cable to temperature sensors. 10. Perform continuity and meager testing on wire and cable after installation.

C. Conduit Installation:

1. Comply with Section 260533 "Raceways and Boxes for Electrical Systems" for control-

voltage conductors. 2. Comply with Section 270528 "Pathways for Communications Systems" for balanced

twisted pair cabling and optical fiber installation. 3.10 FIELD QUALITY CONTROL

A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.

B. Manufacturer's Field Service: Engage a factory-authorized service representative to test and

inspect components, assemblies, and installations, including connections.

C. Perform the following tests and inspections:

1. Perform each visual and mechanical inspection and electrical test stated in NETA Acceptance Testing Specification. Certify compliance with test parameters.

2. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

3. Testing of Pneumatic and Air-Signal Tubing:

a. Test for leaks and obstructions. b. Disconnect each pipe and tubing line before a test is performed, and blowout dust,

dirt, trash, condensate and other foreign materials with compressed air. Use commercially pure compressed air or nitrogen as distributed in gas cylinders. Air from an oil-free compressor with an air dryer is an acceptable alternative for the test.

c. After foreign matter is expelled and line is free from obstructions, plug far end of tubing run.

d. Connect a pressure source to near end of run with a needle valve between air supply and tubing run.

e. Connect a pressure gauge accurate to within 0.5 percent of test between the shutoff needle valve and tubing run under test.

f. For system pressures above 30 psig, apply a pressure of 1.5 times operating pressure. Record pressure in tubing run every 10 minutes for one hour. Allowable drop in pressure in one-hour period shall not exceed 1 psig.

g. For system pressures 30 psig and below, apply a pressure of 2.0 times operating pressure to piping and tubing run. Record pressure in tubing run every 5 minute for one hour. Allowable drop in pressure in one-hour period shall not exceed 0.5 psig.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

278

Page 83: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

D. Testing:

1. Perform preinstallation, in-progress, and final tests, supplemented by additional tests, as necessary.

2. Preinstallation Cable Verification: Verify integrity and serviceability for new cable lengths before installation. This assurance may be provided by using vendor verification documents, testing, or other methods. As a minimum, furnish evidence of verification for cable attenuation and bandwidth parameters.

3. In-Progress Testing: Perform standard tests for correct pair identification and termination during installation to ensure proper installation and cable placement. Perform tests in addition to those specified if there is any reason to question condition of material furnished and installed. Testing accomplished is to be documented by agency conducting tests. Submit test results for Project record.

4. Final Testing: Perform final test of installed system to demonstrate acceptability as installed. Testing shall be performed according to a test plan supplied by DDC system manufacturer. Defective Work or material shall be corrected and retested. As a minimum, final testing for cable system, including spare cable, shall verify conformance of attenuation, length, and bandwidth parameters with performance indicated.

5. Test Equipment: Use an optical fiber time domain reflectometer for testing of length and optical connectivity.

6. Test Results: Record test results and submit copy of test results for Project record.

3.11 DDC SYSTEM I/O CHECKOUT PROCEDURES

A. Check installed products before continuity tests, leak tests and calibration.

B. Check instruments for proper location and accessibility.

C. Check instruments for proper installation on direction of flow, elevation, orientation, insertion depth, or other applicable considerations that will impact performance.

D. Check instrument tubing for proper isolation, fittings, slope, dirt legs, drains, material and

support.

E. Control Damper Checkout:

1. For pneumatic dampers, verify that pressure gauges are provided in each air line to damper actuator and positioner.

2. Verify that control dampers are installed correctly for flow direction. 3. Verify that proper blade alignment, either parallel or opposed, has been provided. 4. Verify that damper frame attachment is properly secured and sealed. 5. Verify that damper actuator and linkage attachment is secure. 6. Verify that actuator wiring is complete, enclosed and connected to correct power source. 7. Verify that damper blade travel is unobstructed.

F. Instrument Checkout:

1. Verify that instrument is correctly installed for location, orientation, direction and operating clearances.

2. Verify that attachment is properly secured and sealed. 3. Verify that conduit connections are properly secured and sealed. 4. Verify that wiring is properly labeled with unique identification, correct type and size and

is securely attached to proper terminals.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

279

Page 84: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

5. Inspect instrument tag against approved submittal. 6. For instruments with tubing connections, verify that tubing attachment is secure and

isolation valves have been provided. 7. For flow instruments, verify that recommended upstream and downstream distances have

been maintained. 8. For temperature instruments:

a. Verify sensing element type and proper material. b. Verify length and insertion.

3.12 DDC SYSTEM I/O ADJUSTMENT, CALIBRATION AND TESTING:

A. Calibrate each instrument installed that is not factory calibrated and provided with calibration documentation.

B. Provide a written description of proposed field procedures and equipment for calibrating each

type of instrument. Submit procedures before calibration and adjustment.

C. For each analog instrument, make a three-point test of calibration for both linearity and accuracy.

D. Equipment and procedures used for calibration shall comply with instrument manufacturer's

written instructions.

E. Provide diagnostic and test equipment for calibration and adjustment.

F. Field instruments and equipment used to test and calibrate installed instruments shall have accuracy at least twice the instrument accuracy being calibrated. An installed instrument with an accuracy of 1 percent shall be checked by an instrument with an accuracy of 0.5 percent.

G. Calibrate each instrument according to instrument instruction manual supplied by manufacturer.

H. If after calibration indicated performance cannot be achieved, replace out-of-tolerance instruments.

I. Comply with field testing requirements and procedures indicated by ASHRAE's Guideline 11,

"Field Testing of HVAC Control Components," in the absence of specific requirements, and to supplement requirements indicated.

J. Analog Signals:

1. Check analog voltage signals using a precision voltage meter at zero, 50, and 100

percent. 2. Check analog current signals using a precision current meter at zero, 50, and 100 percent. 3. Check resistance signals for temperature sensors at zero, 50, and 100 percent of operating

span using a precision-resistant source.

K. Digital Signals:

1. Check digital signals using a jumper wire. 2. Check digital signals using an ohmmeter to test for contact making or breaking.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

280

Page 85: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

L. Control Dampers:

1. Stroke and adjust control dampers following manufacturer's recommended procedure, from 100 percent open to 100 percent closed and back to 100 percent open.

2. Stroke control dampers with pilot positioners. Adjust damper and positioner following manufacturer's recommended procedure, so damper is 100 percent closed, 50 percent closed and 100 percent open at proper air pressure.

3. Check and document open and close cycle times for applications with a cycle time less than 30 seconds.

4. For control dampers equipped with positive position indication, check feedback signal at multiple positions to confirm proper position indication.

M. Meters: Check sensors at zero, 50, and 100 percent of Project design values.

N. Sensors: Check sensors at zero, 50, and 100 percent of Project design values.

O. Switches: Calibrate switches to make or break contact at set points indicated.

P. Transmitters:

1. Check and calibrate transmitters at zero, 50, and 100 percent of Project design values. 2. Calibrate resistance temperature transmitters at zero, 50, and 100 percent of span using a

precision-resistant source.

3.13 DDC SYSTEM CONTROLLER CHECKOUT

A. Verify power supply.

1. Verify voltage, phase and hertz. 2. Verify that protection from power surges is installed and functioning. 3. Verify that ground fault protection is installed. 4. If applicable, verify if connected to UPS unit. 5. If applicable, verify if connected to a backup power source. 6. If applicable, verify that power conditioning units, transient voltage suppression and

high-frequency noise filter units are installed.

B. Verify that wire and cabling is properly secured to terminals and labeled with unique identification.

C. Verify that spare I/O capacity is provided.

3.14 DDC CONTROLLER I/O CONTROL LOOP TESTS

A. Testing:

1. Test every I/O point connected to DDC controller to verify that safety and operating control set points are as indicated and as required to operate controlled system safely and at optimum performance.

2. Test every I/O point throughout its full operating range. 3. Test every control loop to verify operation is stable and accurate. 4. Adjust control loop proportional, integral and derivative settings to achieve optimum

performance while complying with performance requirements indicated. Document testing of each control loop's precision and stability via trend logs.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

281

Page 86: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

5. Test and adjust every control loop for proper operation according to sequence of

operation. 6. Test software and hardware interlocks for proper operation. Correct deficiencies. 7. Operate each analog point at the following:

a. Upper quarter of range. b. Lower quarter of range. c. At midpoint of range.

8. Exercise each binary point. 9. For every I/O point in DDC system, read and record each value at operator workstation,

at DDC controller and at field instrument simultaneously. Value displayed at operator workstation, at DDC controller and at field instrument shall match.

10. Prepare and submit a report documenting results for each I/O point in DDC system and include in each I/O point a description of corrective measures and adjustments made to achieve desire results.

3.15 DDC SYSTEM VALIDATION TESTS

A. Perform validation tests before requesting final review of system. Before beginning testing, first

submit Pretest Checklist and Test Plan.

B. After approval of Test Plan, execute all tests and procedures indicated in plan.

C. After testing is complete, submit completed test checklist.

D. Pretest Checklist: Submit the following list with items checked off once verified: 1. Detailed explanation for any items that are not completed or verified. 2. Required mechanical installation work is successfully completed and HVAC equipment

is working correctly. 3. HVAC equipment motors operate below full-load amperage ratings. 4. Required DDC system components, wiring, and accessories are installed. 5. Installed DDC system architecture matches approved Drawings. 6. Control electric power circuits operate at proper voltage and are free from faults. 7. Required surge protection is installed. 8. DDC system network communications function properly, including uploading and

downloading programming changes. 9. Using BACnet protocol analyzer, verify that communications are error free. 10. Each controller's programming is backed up. 11. Equipment, products, tubing, wiring cable, and conduits are properly labeled. 12. All I/O points are programmed into controllers. 13. Testing, adjusting, and balancing work affecting controls is complete. 14. Dampers and actuators zero and span adjustments are set properly. 15. Each control damper and actuator goes to failed position on loss of power. 16. Valves and actuators zero and span adjustments are set properly. 17. Each control valve and actuator goes to failed position on loss of power. 18. Meter, sensor and transmitter readings are accurate and calibrated. 19. Control loops are tuned for smooth and stable operation. 20. View trend data where applicable. 21. Each controller works properly in standalone mode. 22. Safety controls and devices function properly.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

282

Page 87: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

23. Interfaces with fire-alarm system function properly. 24. Electrical interlocks function properly. 25. Operator workstations and other interfaces are delivered, all system and database

software is installed, and graphic are created. 26. Record Drawings are completed.

E. Test Plan:

1. Prepare and submit a validation test plan including test procedures for performance

validation tests. 2. Test plan shall address all specified functions of DDC system and sequences of operation. 3. Explain detailed actions and expected results to demonstrate compliance with

requirements indicated. 4. Explain method for simulating necessary conditions of operation used to demonstrate

performance. 5. Include a test checklist to be used to check and initial that each test has been successfully

completed. 6. Submit test plan documentation 10 business days before start of tests.

F. Validation Test:

1. Verify operating performance of each I/O point in DDC system.

a. Verify analog I/O points at operating value. b. Make adjustments to out-of-tolerance I/O points.

1) Identify I/O points for future reference. 2) Simulate abnormal conditions to demonstrate proper function of safety

devices. 3) Replace instruments and controllers that cannot maintain performance

indicated after adjustments.

2. Simulate conditions to demonstrate proper sequence of control.

3. Readjust settings to design values and observe ability of DDC system to establish desired conditions.

4. After 24 Hours following Initial Validation Test:

a. Re-check I/O points that required corrections during initial test. b. Identify I/O points that still require additional correction and make corrections

necessary to achieve desired results.

5. After 24 Hours of Second Validation Test:

a. Re-check I/O points that required corrections during second test. b. Continue validation testing until I/O point is normal on two consecutive tests.

6. Completely check out, calibrate, and test all connected hardware and software to ensure

that DDC system performs according to requirements indicated.

7. After validation testing is complete, prepare and submit a report indicating all I/O points that required correction and how many validation re-tests it took to pass. Identify adjustments made for each test and indicate instruments that were replaced.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

283

Page 88: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

G. DDC System Response Time Test:

1. Simulate HLC.

a. Heavy load shall be an occurrence of 50 percent of total connected binary COV, one-half of which represent an "alarm" condition, and 50 percent of total connected analog COV, one-half of which represent an "alarm" condition, that are initiated simultaneously on a one-time basis.

2. Initiate 10 successive occurrences of HLC and measure response time to typical alarms

and status changes.

3. Measure with a timer having at least 0.1-second resolution and 0.01 percent accuracy.

4. Purpose of test is to demonstrate DDC system, as follows:

a. Reaction to COV and alarm conditions during HLC. b. Ability to update DDC system database during HLC.

5. Passing test is contingent on the following:

a. Alarm reporting at printer beginning no more than 2 seconds after the initiation

(time zero) of HLC. b. All alarms, both binary and analog, are reported and printed; none are lost. c. Compliance with response times specified.

6. Prepare and submit a report documenting HLC tested and results of test including time

stamp and print out of all alarms.

H. DDC System Network Bandwidth Test:

1. Test network bandwidth usage on all DDC system networks to demonstrate bandwidth usage under DDC system normal operating conditions and under simulated HLC.

2. To pass, none of DDC system networks shall use more than 70 percent of available bandwidth under normal and HLC operation.

3.16 DDC SYSTEM WIRELESS NETWORK VERIFICATION

A. DDC system Installer shall design wireless DDC system networks to comply with performance

requirements indicated.

B. Installer shall verify wireless network performance through field testing and shall document results in a field test report.

C. Testing and verification of all wireless devices shall include, but not be limited to, the

following: 1. Speed. 2. Online status. 3. Signal strength.

3.17 FINAL REVIEW

A. Submit written request to Architect and Construction Manager when DDC system is ready for

final review. Written request shall state the following:

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

284

Page 89: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

1. DDC system has been thoroughly inspected for compliance with contract documents and

found to be in full compliance. 2. DDC system has been calibrated, adjusted and tested and found to comply with

requirements of operational stability, accuracy, speed and other performance requirements indicated.

3. DDC system monitoring and control of HVAC systems results in operation according to sequences of operation indicated.

4. DDC system is complete and ready for final review.

B. Review by Architect and Construction Manager shall be made after receipt of written request. A field report shall be issued to document observations and deficiencies.

C. Take prompt action to remedy deficiencies indicated in field report and submit a second written

request when all deficiencies have been corrected. Repeat process until no deficiencies are reported.

D. Should more than two reviews be required, DDC system manufacturer and Installer shall

compensate entity performing review for total costs, labor and expenses, associated with third and subsequent reviews. Estimated cost of each review shall be submitted and approved by DDC system manufacturer and Installer before making the review.

E. Prepare and submit closeout submittals when no deficiencies are reported.

F. A part of DDC system final review shall include a demonstration to parties participating in final

review.

1. Provide staff familiar with DDC system installed to demonstrate operation of DDC system during final review.

2. Provide testing equipment to demonstrate accuracy and other performance requirements

of DDC system that is requested by reviewers during final review.

3. Demonstration shall include, but not be limited to, the following:

a. Accuracy and calibration of 10 I/O points randomly selected by reviewers. If review finds that some I/O points are not properly calibrated and not satisfying performance requirements indicated, additional I/O points may be selected by reviewers until total I/O points being reviewed that satisfy requirements equals quantity indicated.

b. HVAC equipment and system hardwired and software safeties and life-safety functions are operating according to sequence of operation. Up to 10 I/O points shall be randomly selected by reviewers. Additional I/O points may be selected by reviewers to discover problems with operation.

c. Correct sequence of operation after electrical power interruption and resumption after electrical power is restored for randomly selected HVAC systems.

d. Operation of randomly selected dampers and valves in normal-on, normal-off and failed positions.

e. Reporting of alarm conditions for randomly selected alarms, including different classes of alarms, to ensure that alarms are properly received by operators an operator workstations.

f. Trends, summaries, logs and reports set-up for Project.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

285

Page 90: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

g. For up to three HVAC systems randomly selected by reviewers, use graph trends to show that sequence of operation is executed in correct manner and that HVAC systems operate properly through complete sequence of operation including different modes of operations indicated. Show that control loops are stable and operating at set points and respond to changes in set point of 20 percent or more.

h. Software's ability to communicate with controllers, operator workstations, uploading and downloading of control programs.

i. Software's ability to edit control programs off-line. j. Data entry to show Project-specific customizing capability including parameter

changes. k. Step through penetration tree, display all graphics, demonstrate dynamic update,

and direct access to graphics. l. Execution of digital and analog commands in graphic mode. m. Spreadsheet and curve plot software and its integration with database. n. Online user guide and help functions. o. Multitasking by showing different operations occurring simultaneously on four

quadrants of split screen. p. System speed of response compared to requirements indicated. q. For Each Programmable Application Controller:

1) Memory: Programmed data, parameters, trend and alarm history collected during normal operation is not lost during power failure.

2) Operator Interface: Ability to connect directly to each type of digital controller with a portable workstation and mobile device. Show that maintenance personnel interface tools perform as indicated in manufacturer's technical literature.

3) Standalone Ability: Demonstrate that controllers provide stable and reliable standalone operation using default values or other method for values normally read over network.

4) Electric Power: Ability to disconnect any controller safely from its power source.

5) Wiring Labels: Match control drawings. 6) Network Communication: Ability to locate a controller's location on

network and communication architecture matches Shop Drawings. 7) Nameplates and Tags: Accurate and permanently attached to control panel

doors, instrument, actuators, and devices.

r. For Each Operator Workstation: 1) I/O points lists agree with naming conventions. 2) Graphics are complete. 3) UPS unit, if applicable, operates.

s. Communications and Interoperability: Demonstrate proper interoperability of data

sharing, alarm and event management, trending, scheduling, and device and network management. Use ASHRAE 135 protocol analyzer to help identify devices, view network traffic, and verify interoperability. Requirements must be met even if only one manufacturer's equipment is installed.

1) Data Presentation: On each operator workstation, demonstrate graphic

display capabilities.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

286

Page 91: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

readable object property of any device on network. 3) Set Point and Parameter Modifications: Show ability to modify set points

and tuning parameters indicated. Modifications are made with messages and write services initiated by an operator using workstation graphics, or by completing a field in a menu with instructional text.

4) Peer-to-Peer Data Exchange: Network devices are installed and configured to perform without need for operator intervention to implement Project sequence of operation and to share global data.

5) Alarm and Event Management: Alarms and events are installed and prioritized according to Owner. Demonstrate that time delays and other logic are set up to avoid nuisance tripping. Show that operators with sufficient privileges are permitted.

6) Schedule Lists: Schedules are configured for start and stop, mode change, occupant overrides, and night setback as defined in sequence of operations.

7) Schedule Display and Modification: Ability to display any schedule with start and stop times for calendar year. Show that all calendar entries and schedules are modifiable from any connected operator workstation by an operator with sufficient privilege.

8) Archival Storage of Data: Data archiving is handled by operator workstation and server and local trend archiving and display is accomplished.

9) Modification of Trend Log Object Parameters: Operator with sufficient privilege can change logged data points, sampling rate, and trend duration.

10) Device and Network Management:

a) Display of network device status. b) Display of BACnet Object Information. c) Silencing devices transmitting erroneous data. d) Time synchronization. e) Remote device re-initialization. f) Backup and restore network device programming and master

database(s). g) Configuration management of routers.

3.18 ADJUSTING

A. Occupancy Adjustments: When requested within 12 months from date of Substantial

Completion, provide on-site assistance in adjusting system to suit actual occupied conditions. Provide up to two visits to Project during other-than-normal occupancy hours for this purpose.

3.19 SOFTWARE SERVICE AGREEMENT

A. Technical Support: Beginning at Substantial Completion, service agreement shall include

software support for one year.

B. Upgrade Service: At Substantial Completion, update software to latest version. Install and program software upgrades that become available within one year from date of Substantial Completion. Upgrading software shall include operating system and new or revised licenses for using software.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

287

Page 92: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

I. Upgrade Notice: At least 30 days to allow Owner to schedule and access system and to

upgrade computer equipment if necessary. END OF SECTION 230923

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

288

Page 93: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

SECTION 230993.11 - SEQUENCE OF OPERATIONS FOR HVAC DDC

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section includes control sequences for DDC for HVAC systems, subsystems, and equipment.

B. Related Requirements:

1. Section 230923 "DDC Systems for HVAC" for control equipment. 1.3 DEFINITIONS

A. Analog Output: Proportional output signal (zero- to 10-V dc, 4 to 20 mA).

B. Binary Output: On/off output signal or contact closure.

C. DDC: Direct digital control.

D. Digital Output: Data output that must be interpreted digitally. 1.4 ACTION SUBMITTALS

A. Product Data:

1. An instrumentation list for each controlled system. Label each element of the controlled system in table format. Show, in the table element name, type of device, manufacturer, model number, and control device product data sheet number.

2. A complete description of the operation of the control system, including sequences of operation. Include and reference a schematic diagram of the controlled system.

B. Shop Drawings:

1. Riser diagrams showing control network layout, communication protocol, and wire types. 2. Schematic diagram of each controlled system. Include all control points labeled with

point names shown or listed. Show the location of control elements in the system. 3. Wiring diagram for each controlled system. Show all control elements labels. Where a

control element is the same as that shown on the control system schematic, label with the same name. Label all terminals.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

289

Page 94: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

1.5 TERMINAL UNIT OPERATING SEQUENCE

A. Variable-Air-Volume Terminal Air Units:

1. Space Temperature:

a. Input: 1) Device: Air-temperature sensor. 2) Location: Space. 3) Transference: DDC controller.

b. Output:

1) Device: Analog output. 2) Location: Control damper. 3) Input Transference: Control damper.

c. Action: Modulate damper to maintain the following space temperature set points:

1) Occupied Cooling Temperature: 70 deg F. 2) Occupied Heating Temperature: 70 deg F. 3) Unoccupied Cooling Temperature: 75 deg F. 4) Unoccupied Heating Temperature: 65 deg F. 5) Modulate damper actuator from full open to minimum position. 6) If occupied space temperature is not maintained, modulate damper actuator

from minimum position to 100 percent open. 7) Reverse the sequence for full heating to full cooling.

B. Sequence Control:

1. Space Temperature:

a. Input:

1) Device: Air-temperature sensor. 2) Location: Space. 3) Transference: DDC controller.

b. Output:

1) Device: Analog output. 2) Location: Control damper. 3) Input Transference: Control dampers.

c. Action: Modulate dampers to maintain the following space temperature set points:

1) Occupied Cooling Temperature: 70 deg F. 2) Occupied Heating Temperature: 70 deg F. 3) Unoccupied Cooling Temperature: 75 deg F. 4) Unoccupied Heating Temperature: 65 deg F. 5) Modulate damper actuator from open to minimum position. 6) If occupied space temperature is not maintained, modulate damper actuator

from minimum position to 100 percent open. 7) Reverse the sequence for full heating to full cooling.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

290

Page 95: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

C. In

1.

dicate the following on the operator's workstation display terminal:

DDC system graphic. 2. DDC system on-off indication (operating or not operating). 3. DDC system occupied/unoccupied mode. 4. Outdoor-air-temperature indication.

5.

Variable-Air-Volume Terminal Air Units:

a. Space/area served. b. Space occupied/unoccupied. c. Space temperature indication. d. Space temperature set point. e. Space cooling and heating temperature set point, occupied. f. Space cooling and heating temperature set point, unoccupied. g. Air-damper position as percentage open.

6. Sequence Control:

a. Space/area served. b. Space occupied/unoccupied. c. Space temperature indication. d. Space temperature set point, occupied. e. Space temperature set point, unoccupied. f. Damper position as percentage open.

PART 2 - PRODUCTS (Not Applicable)

PART 3 - EXECUTION (Not Applicable)

END OF SECTION 230993.11

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

291

Page 96: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

SECTION 233113 - METAL DUCTS PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY

A. Section Includes:

1. Single-wall rectangular ducts and fittings. 2. Single-wall round ducts and fittings. 3. Sheet metal materials. 4. Duct liner. 5. Sealants and gaskets. 6. Hangers and supports. 7. Seismic-restraint devices.

B. Related Sections:

1. Section 230593 "Testing, Adjusting, and Balancing for HVAC" for testing, adjusting, and balancing requirements for metal ducts.

2. Section 233116 "Nonmetal Ducts" for fibrous-glass ducts, thermoset fiber-reinforced plastic ducts, thermoplastic ducts, PVC ducts, and concrete ducts.

3. Section 233119 "HVAC Casings" for factory- and field-fabricated casings for mechanical equipment.

4. Section 233300 "Air Duct Accessories" for dampers, sound-control devices, duct- mounting access doors and panels, turning vanes, and flexible ducts.

1.3 DEFINITIONS

A. OSHPD: Office of Statewide Health Planning and Development (State of California).

1.4 ACTION SUBMITTALS

A. Product Data: For each type of the following products:

1. Liners and adhesives. 2. Sealants and gaskets. 3. Seismic-restraint devices.

B. Shop Drawings:

1. Fabrication, assembly, and installation, including plans, elevations, sections, components, and attachments to other work.

2. Factory- and shop-fabricated ducts and fittings. 3. Duct layout indicating sizes, configuration, liner material, and static-pressure classes. 4. Elevation of top of ducts. 5. Dimensions of main duct runs from building grid lines. 6. Fittings.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

292

Page 97: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

7. Reinforcement and spacing. 8. Seam and joint construction. 9. Penetrations through fire-rated and other partitions. 10. Equipment installation based on equipment being used on Project. 11. Locations for duct accessories, including dampers, turning vanes, and access doors and

panels. 12. Hangers and supports, including methods for duct and building attachment, and vibration

isolation.

1.5 INFORMATIONAL SUBMITTALS

A. Coordination Drawings: A single set of plans or BIM model, drawn to scale, showing the items described in this Section, and coordinated with all building trades.

B. Field quality-control reports.

1.6 QUALITY ASSURANCE PART

2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Delegated Duct Design: Duct construction, including sheet metal thicknesses, seam and joint

construction, reinforcements, and hangers and supports, shall comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" and with performance requirements and design criteria indicated in "Duct Schedule" Article.

B. Structural Performance: Duct hangers and supports shall withstand the effects of gravity loads

and stresses within limits and under conditions described in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible,"

C. Airstream Surfaces: Surfaces in contact with airstream shall comply with requirements in

ASHRAE 62.1.

D. ASHRAE Compliance: Applicable requirements in ASHRAE 62.1, Section 5 - "Systems and Equipment," and Section 7 - "Construction and System Startup."

E. ASHRAE/IES Compliance: Applicable requirements in ASHRAE/IES 90.1, Section 6.4.4 -

"HVAC System Construction and Insulation."

F. Duct Dimensions: Unless otherwise indicated, all duct dimensions indicated on Drawings are inside clear dimensions and do not include insulation or duct wall thickness.

2.2 SINGLE-WALL RECTANGULAR DUCTS AND FITTINGS

A. General Fabrication Requirements: Comply with SMACNA's "HVAC Duct Construction

Standards - Metal and Flexible" based on indicated static-pressure class unless otherwise indicated.

1. Construct ducts of galvanized sheet steel unless otherwise indicated.

B. Transverse Joints: Fabricate joints in accordance with SMACNA's "HVAC Duct Construction

Standards - Metal and Flexible," Figure 2-1, "Rectangular Duct/Transverse Joints," for static- pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

293

Page 98: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

1. For ducts with longest side less than 36 inches, select joint types in accordance with Figure 2-1.

2. For ducts with longest side 36 inches or greater, use flange joint connector Type T-22, T- 24, T-24A, T-25a, or T-25b. Factory-fabricated flanged duct connection system may be used if submitted and approved by engineer of record.

C. Longitudinal Seams: Select seam types and fabricate in accordance with SMACNA's "HVAC

Duct Construction Standards - Metal and Flexible," Figure 2-2, "Rectangular Duct/Longitudinal Seams," for static-pressure class, applicable sealing requirements, materials involved, duct- support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible." All longitudinal seams shall be Pittsburgh lock seams unless otherwise specified for specific application.

D. Elbows, Transitions, Offsets, Branch Connections, and Other Duct Construction: Select types

and fabricate in accordance with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Ch. 4, "Fittings and Other Construction," for static-pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."

2.3 SINGLE-WALL ROUND DUCTS AND FITTINGS

A. General Fabrication Requirements: Comply with SMACNA's "HVAC Duct Construction

Standards - Metal and Flexible," Ch. 3, "Round, Oval, and Flexible Duct," based on indicated static-pressure class unless otherwise indicated.

1. Construct ducts of galvanized sheet steel unless otherwise indicated.

B. Flat-Oval Ducts: Indicated dimensions are the duct width (major dimension) and diameter of the

round sides connecting the flat portions of the duct (minor dimension).

C. Transverse Joints: Select joint types and fabricate in accordance with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 3-1, "Round Duct Transverse Joints," for static-pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."

1. Transverse Joints in Ducts Larger Than 60 Inches in Diameter: Flanged.

D. Longitudinal Seams: Select seam types and fabricate in accordance with SMACNA's "HVAC

Duct Construction Standards - Metal and Flexible," Figure 3-2, "Round Duct Longitudinal Seams," for static-pressure class, applicable sealing requirements, materials involved, duct- support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."

1. Fabricate round ducts larger than 90 inches in diameter with butt-welded longitudinal

seams. 2. Fabricate flat-oval ducts larger than 72 inches in width (major dimension) with butt-

welded longitudinal seams.

E. Tees and Laterals: Select types and fabricate in accordance with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 3-5, "90 Degree Tees and Laterals," and Figure 3-6, "Conical Tees," for static-pressure class, applicable sealing requirements, materials

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

294

Page 99: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."

2.4 SHEET METAL MATERIALS

A. General Material Requirements: Comply with SMACNA's "HVAC Duct Construction

Standards - Metal and Flexible" for acceptable materials, material thicknesses, and duct construction methods unless otherwise indicated. Sheet metal materials shall be free of pitting, seam marks, roller marks, stains, discolorations, and other imperfections.

B. Galvanized Sheet Steel: Comply with ASTM A653/A653M.

1. Galvanized Coating Designation: G60 2. Finishes for Surfaces Exposed to View: Mill phosphatized. 3. Coating Materials: Acceptable to authorities having jurisdiction for use on ducts listed

and labeled by an NRTL for compliance with UL 181, Class 1.

C. Carbon-Steel Sheets: Comply with ASTM A1008/A1008M, with oiled, matte finish for exposed ducts.

D. Stainless-Steel Sheets: Comply with ASTM A480/A480M, Type 304 or 316, as indicated in

"Duct Schedule" Article; cold rolled, annealed, sheet. Exposed surface finish shall be No. 2B, No. 2D, No. 3, or No. 4 as indicated in "Duct Schedule" Article.

E. Aluminum Sheets: Comply with ASTM B209 Alloy 3003, H14 temper; with mill finish for

concealed ducts, and standard, one-side bright finish for duct surfaces exposed to view.

F. Reinforcement Shapes and Plates: ASTM A36/A36M, steel plates, shapes, and bars; black and galvanized.

1. Where black- and galvanized-steel shapes and plates are used to reinforce aluminum

ducts, isolate the different metals with butyl rubber, neoprene, or EPDM gasket materials.

G. Tie Rods: Galvanized steel, 1/4-inch-minimum diameter for lengths 36 inches or less; 3/8-inch- minimum diameter for lengths longer than 36 inches.

2.5 DUCT LINER

A. Fibrous-Glass Duct Liner: Comply with ASTM C1071, NFPA 90A, or NFPA 90B; and with

NAIMA AH124, "Fibrous Glass Duct Liner Standard."

1. Acceptable Manufacturers: Johns Mansville, Owens Corning, and Knauf Insulation. 2. Maximum Thermal Conductivity:

a. Type I, Flexible: 0.27 Btu x in./h x sq. ft. x deg F at 75 deg F mean temperature. b. Type II, Rigid: 0.23 Btu x in./h x sq. ft. x deg Fat 75 deg F mean temperature.

B. Insulation Pins and Washers:

1. Cupped-Head, Capacitor-Discharge-Weld Pins: Copper- or zinc-coated steel pin, fully

annealed for capacitor-discharge welding, 0.135-inch-diameter shank, length to suit depth of insulation indicated with integral 1-1/2-inch galvanized carbon-steel washer.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

295

Page 100: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2. Insulation-Retaining Washers: Self-locking washers formed from 0.016-inch-thick

stainless steel; with beveled edge sized as required to hold insulation securely in place, but not less than 1-1/2 inches in diameter.

C. Shop Application of Duct Liner: Comply with SMACNA's "HVAC Duct Construction

Standards - Metal and Flexible," Figure 7-11, "Flexible Duct Liner Installation."

1. Adhere a single layer of indicated thickness of duct liner with at least 90 percent adhesive coverage at liner contact surface area. Attaining indicated thickness with multiple layers of duct liner is prohibited.

2. Apply adhesive to transverse edges of liner facing upstream that do not receive metal nosing.

3. Butt transverse joints without gaps, and coat joint with adhesive. 4. Fold and compress liner in corners of rectangular ducts or cut and fit to ensure butted-

edge overlapping. 5. Do not apply liner in rectangular ducts with longitudinal joints, except at corners of ducts,

unless duct size and dimensions of standard liner make longitudinal joints necessary. 6. Secure liner with mechanical fasteners 4 inches from corners and at intervals not

exceeding 12 inches transversely; at 3 inches from transverse joints and at intervals not exceeding 18 inches longitudinally.

7. Secure transversely oriented liner edges facing the airstream with metal nosings that have either channel or "Z" profiles or are integrally formed from duct wall. Fabricate edge facings at the following locations:

a. Fan discharges. b. Intervals of lined duct preceding unlined duct. c. Upstream edges of transverse joints in ducts where air velocities are higher than

2500 fpm or where indicated.

8. Secure insulation between perforated sheet metal inner duct of same thickness as specified for outer shell. Use mechanical fasteners that maintain inner duct at uniform distance from outer shell without compressing insulation.

a. Sheet Metal Inner Duct Perforations: 3/32-inch diameter, with an overall open area of

23 percent.

9. Terminate inner ducts with buildouts attached to fire-damper sleeves, dampers, turning vane assemblies, or other devices. Fabricated buildouts (metal hat sections) or other buildout means are optional; when used, secure buildouts to duct walls with bolts, screws, rivets, or welds.

2.6 SEALANT AND GASKETS

A. General Sealant and Gasket Requirements: Surface-burning characteristics for sealants and

gaskets shall be a maximum flame-spread index of 25 and a maximum smoke-developed index of 50 when tested in accordance with UL 723; certified by an NRTL.

B. Two-Part Tape Sealing System:

1. Tape: Woven cotton fiber impregnated with mineral gypsum and modified

acrylic/silicone activator to react exothermically with tape to form hard, durable, airtight seal.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

296

Page 101: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2. Tape Width: 4 inches 3. Sealant: Modified styrene acrylic. 4. Water resistant. 5. Mold and mildew resistant. 6. Maximum Static-Pressure Class: 10 inch wg, positive and negative. 7. Service: Indoor and outdoor. 8. Service Temperature: Minus 40 to plus 200 deg F. 9. Substrate: Compatible with galvanized sheet steel (both PVC coated and bare), stainless

steel, or aluminum.

C. Water-Based Joint and Seam Sealant:

1. Application Method: Brush on. 2. Solids Content: Minimum 65 percent. 3. Shore A Hardness: Minimum 20. 4. Water resistant. 5. Mold and mildew resistant. 6. VOC: Maximum 75 g/L (less water). 7. Maximum Static-Pressure Class: 10 inch wg, positive and negative. 8. Service: Indoor or outdoor. 9. Substrate: Compatible with galvanized sheet steel (both PVC coated and bare), stainless

steel, or aluminum sheets.

D. Solvent-Based Joint and Seam Sealant:

1. Application Method: Brush on. 2. Base: Synthetic rubber resin. 3. Solvent: Toluene and heptane. 4. Solids Content: Minimum 60 percent. 5. Shore A Hardness: Minimum 60. 6. Water resistant. 7. Mold and mildew resistant. 8. Maximum Static-Pressure Class: 10-inch wg, positive or negative. 9. Service: Indoor or outdoor. 10. Substrate: Compatible with galvanized sheet steel (both PVC coated and bare), stainless

steel, or aluminum sheets.

E. Flanged Joint Sealant: Comply with ASTM C920.

1. General: Single-component, acid-curing, silicone, elastomeric. 2. Type: S. 3. Grade: NS. 4. Class: 25. 5. Use: O.

F. Flange Gaskets: Butyl rubber, neoprene, or EPDM polymer with polyisobutylene plasticizer.

G. Round Duct Joint O-Ring Seals:

1. Seal shall provide maximum leakage class of 3 cfm/100 sq. ft. at 1-inch wg and shall be rated for10-inch wg static-pressure class, positive or negative.

2. EPDM O-ring to seal in concave bead in coupling or fitting spigot. 3. Double-lipped, EPDM O-ring seal, mechanically fastened to factory-fabricated couplings

and fitting spigots.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

297

Page 102: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2.7 HANGERS AND SUPPORTS

A. Hanger Rods for Noncorrosive Environments: Galvanized-steel rods and nuts.

B. Hanger Rods for Corrosive Environments: Electrogalvanized, all-thread rods or galvanized rods with threads painted with zinc-chromate primer after installation.

C. Strap and Rod Sizes: Comply with SMACNA's "HVAC Duct Construction Standards - Metal

and Flexible," Table 5-1, "Rectangular Duct Hangers Minimum Size," and Table 5-2, "Minimum Hanger Sizes for Round Duct."

D. Steel Cables for Galvanized-Steel Ducts: Galvanized steel complying with ASTM A603.

E. Steel Cables for Stainless-Steel Ducts: Stainless steel complying with ASTM A492.

F. Steel Cable End Connections: Galvanized-steel assemblies with brackets, swivel, and bolts designed for duct hanger service; with an automatic-locking and clamping device.

G. Duct Attachments: Sheet metal screws, blind rivets, or self-tapping metal screws; compatible

with duct materials.

H. Trapeze and Riser Supports:

1. Supports for Galvanized-Steel Ducts: Galvanized-steel shapes and plates. 2. Supports for Stainless-Steel Ducts: Stainless-steel shapes and plates. 3. Supports for Aluminum Ducts: Aluminum or galvanized steel coated with zinc chromate.

PART 3 - EXECUTION

3.1 DUCT INSTALLATION

A. Drawing plans, schematics, and diagrams indicate general location and arrangement of duct

system. Indicated duct locations, configurations, and arrangements were used to size ducts and calculate friction loss for air-handling equipment sizing and for other design considerations. Install duct systems as indicated unless deviations to layout are approved on Shop Drawings and coordination drawings.

B. Install ducts in accordance with SMACNA's "HVAC Duct Construction Standards - Metal and

Flexible" unless otherwise indicated.

C. Install ducts in maximum practical lengths with fewest possible joints.

D. Install factory- or shop-fabricated fittings for changes in direction, size, and shape and for branch connections.

E. Unless otherwise indicated, install ducts vertically and horizontally, and parallel and

perpendicular to building lines.

F. Install ducts close to walls, overhead construction, columns, and other structural and permanent enclosure elements of building.

G. Install ducts with a clearance of 1 inch, plus allowance for insulation thickness.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

298

Page 103: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

H. Route ducts to avoid passing through transformer vaults and electrical equipment rooms and

enclosures.

I. Where ducts pass through non-fire-rated interior partitions and exterior walls and are exposed to view, cover the opening between the partition and duct or duct insulation with sheet metal flanges of same metal thickness as the duct. Overlap openings on four sides by at least 1-1/2 inches.

J. Install fire, and smoke dampers where indicated on Drawings and as required by code, and by

local authorities having jurisdiction. Comply with requirements in Section 233300 "Air Duct Accessories" for fire and smoke dampers and specific installation requirements of the damper UL listing.

K. Install heating coils, cooling coils, air filters, dampers, and all other duct-mounted accessories in

air ducts where indicated on Drawings.

L. Protect duct interiors from moisture, construction debris and dust, and other foreign materials both before and after installation.

M. Elbows: Use long-radius elbows wherever they fit.

1. Fabricate 90-degree rectangular mitered elbows to include turning vanes. 2. Fabricate 90-degree round elbows with a minimum of three segments for 12 inches and

smaller and a minimum of five segments for 14 inches and larger.

N. Branch Connections: Use lateral or conical branch connections. 3.2 DUCT SEALING

A. Seal ducts for duct static-pressure, seal classes, and leakage classes specified in "Duct

Schedule" Article in accordance with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."

B. Seal ducts at a minimum to the following seal classes in accordance with SMACNA's "HVAC

Duct Construction Standards - Metal and Flexible":

1. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible." 2. Outdoor, Supply-Air Ducts: Seal Class A. 3. Outdoor, Exhaust Ducts: Seal Class C. 4. Outdoor, Return-Air Ducts: Seal Class C. 5. Unconditioned Space, Supply-Air Ducts in Pressure Classes 2-Inch wg and Lower: Seal

Class B. 6. Unconditioned Space, Supply-Air Ducts in Pressure Classes Higher Than 2-Inch wg: Seal

Class A. 7. Unconditioned Space, Exhaust Ducts: Seal Class C. 8. Unconditioned Space, Return-Air Ducts: Seal Class B. 9. Conditioned Space, Supply-Air Ducts in Pressure Classes 2-Inch wg and Lower: Seal

Class C. 10. Conditioned Space, Supply-Air Ducts in Pressure Classes Higher Than 2-Inch wg: Seal

Class B. 11. Conditioned Space, Exhaust Ducts: Seal Class B. 12. Conditioned Space, Return-Air Ducts: Seal Class C.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

299

Page 104: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3.3 HANGER AND SUPPORT INSTALLATION

A. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible,"

Chapter 5, "Hangers and Supports."

B. Building Attachments: Concrete inserts, powder-actuated fasteners, or structural-steel fasteners appropriate for construction materials to which hangers are being attached.

1. Where practical, install concrete inserts before placing concrete. 2. Install powder-actuated concrete fasteners after concrete is placed and completely cured. 3. Use powder-actuated concrete fasteners for standard-weight aggregate concretes or for

slabs more than 4 inches thick. 4. Do not use powder-actuated concrete fasteners for lightweight-aggregate concretes or for

slabs less than 4 inches thick.

C. Hanger Spacing: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Table 5-1, "Rectangular Duct Hangers Minimum Size," and Table 5-2, "Minimum Hanger Sizes for Round Duct," for maximum hanger spacing; install hangers and supports within 24 inches of each elbow and within 48 inches of each branch intersection.

D. Hangers Exposed to View: Threaded rod and angle or channel supports.

E. Support vertical ducts with steel angles or channel secured to the sides of the duct with welds,

bolts, sheet metal screws, or blind rivets; support at each floor and at a maximum intervals of 16 feet.

F. Install upper attachments to structures. Select and size upper attachments with pull-out, tension,

and shear capacities appropriate for supported loads and building materials where used.

3.4 CONNECTIONS

A. Make connections to equipment with flexible connectors complying with Section 233300 "Air Duct Accessories."

B. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for

branch, outlet and inlet, and terminal unit connections.

3.5 PAINTING

A. Paint interior of metal ducts that are visible through registers and grilles and that do not have duct liner. Apply one coat of flat, black, latex paint over a compatible galvanized-steel primer. Paint materials and application requirements are specified in Section 099113 "Exterior Painting" and Section 099123 "Interior Painting."

3.6 FIELD QUALITY CONTROL

A. Perform tests and inspections.

B. Leakage Tests:

1. Comply with SMACNA's "HVAC Air Duct Leakage Test Manual." Submit a test report for each test.

2. Test the following systems:

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

300

Page 105: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

a. Ducts with a Pressure Class Higher Than 3-Inch wg: Test representative duct sections, totaling no less than 25 percent of total installed duct area for each designated pressure class.

b. Supply Ducts with a Pressure Class of 2-6 Inch wg: Test representative duct sections totaling no less than 25 percent of total installed duct area for each designated pressure class.

c. Supply Ducts with a Pressure Class of 6 Inch wg or Higher: Test representative duct sections totaling no less than 100 percent of total installed duct area for each designated pressure class.

d. Return Ducts with a Pressure Class of 2 Inch wg or Higher: Testing N/A. e. Exhaust Ducts with a Pressure Class of 2 Inch wg or Higher: Testing N/A

3. Disassemble, reassemble, and seal segments of systems to accommodate leakage testing and

for compliance with test requirements. 4. Testing of each duct section is to be performed with access doors, coils, filters, dampers, and

other duct-mounted devices in place as designed. No devices are to be removed or blanked off so as to reduce or prevent additional leakage.

5. Test for leaks before applying external insulation. 6. Conduct tests at static pressures equal to maximum design pressure of system or section

being tested. If static-pressure classes are not indicated, test system at maximum system design pressure. Do not pressurize systems above maximum design operating pressure.

7. Give seven days' advance notice for testing.

C. Duct System Cleanliness Tests:

1. Visually inspect duct system to ensure that no visible contaminants are present. 2. Test sections of metal duct system, chosen randomly by Owner, for cleanliness in

accordance with "Description of Method 3 - NADCA Vacuum Test" in NADCA ACR, "Assessment, Cleaning and Restoration of HVAC Systems."

a. Acceptable Cleanliness Level: Net weight of debris collected on the filter media

shall not exceed 0.75 mg/100 sq. cm.

D. Duct system will be considered defective if it does not pass tests and inspections.

E. Prepare test and inspection reports.

3.7 DUCT CLEANING

A. Clean new duct system(s) before testing, adjusting, and balancing.

B. For cleaning of existing ductwork, see Section 230130.52 "Existing HVAC Air Distribution System Cleaning."

C. Use duct cleaning methodology as indicated in NADCA ACR.

D. Use service openings for entry and inspection.

1. Provide openings with access panels appropriate for duct static-pressure and leakage class at dampers, coils, and any other locations where required for inspection and cleaning access. Provide insulated panels for insulated or lined duct. Patch insulation and liner as recommended by duct liner manufacturer. Comply with Section 233300 "Air Duct Accessories" for access panels and doors.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

301

Page 106: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2. Disconnect and reconnect flexible ducts as needed for cleaning and inspection. 3. Remove and reinstall ceiling to gain access during the cleaning process.

E. Particulate Collection and Odor Control:

1. When venting vacuuming system inside the building, use HEPA filtration with 99.97 percent collection efficiency for 0.3-micron-size (or larger) particles.

2. When venting vacuuming system to outdoors, use filter to collect debris removed from HVAC system, and locate exhaust downwind and away from air intakes and other points of entry into building.

F. Clean the following components by removing surface contaminants and deposits:

1. Air outlets and inlets (registers, grilles, and diffusers). 2. Supply, return, and exhaust fans including fan housings, plenums (except ceiling supply and

return plenums), scrolls, blades or vanes, shafts, baffles, dampers, and drive assemblies. 3. Air-handling unit internal surfaces and components including mixing box, coil section,

air wash systems, spray eliminators, condensate drain pans, humidifiers and dehumidifiers, filters and filter sections, and condensate collectors and drains.

4. Coils and related components. 5. Return-air ducts, dampers, actuators, and turning vanes except in ceiling plenums and

mechanical equipment rooms. 6. Supply-air ducts, dampers, actuators, and turning vanes. 7. Dedicated exhaust and ventilation components and makeup air systems.

G. Mechanical Cleaning Methodology:

1. Clean metal duct systems using mechanical cleaning methods that extract contaminants from within duct systems and remove contaminants from building.

2. Use vacuum-collection devices that are operated continuously during cleaning. Connect vacuum device to downstream end of duct sections so areas being cleaned are under negative pressure.

3. Use mechanical agitation to dislodge debris adhered to interior duct surfaces without damaging integrity of metal ducts, duct liner, or duct accessories.

4. Clean fibrous-glass duct liner with HEPA vacuuming equipment; do not permit duct liner to get wet. Replace fibrous-glass duct liner that is damaged, deteriorated, or delaminated or that has friable material, mold, or fungus growth.

5. Clean coils and coil drain pans in accordance with NADCA ACR. Keep drain pan operational. Rinse coils with clean water to remove latent residues and cleaning materials; comb and straighten fins.

6. Provide drainage and cleanup for wash-down procedures. 7. Antimicrobial Agents and Coatings: Apply EPA-registered antimicrobial agents if fungus is

present. Apply antimicrobial agents in accordance with manufacturer's written instructions after removal of surface deposits and debris.

3.8 STARTUP

A. Air Balance: Comply with requirements in Section 230593 "Testing, Adjusting, and Balancing

for HVAC."

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

302

Page 107: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3.9 DUCT SCHEDULE

A. Fabricate ducts with galvanized sheet steel except as otherwise indicated and as follows:

1. Fabricate all ducts to achieve SMACNA pressure class, seal class, and leakage class as

indicated below.

B. Supply Ducts:

1. Terminal Units: a. Pressure Class: Positive 2 inch wg. b. Minimum SMACNA Seal Class: A. c. SMACNA Leakage Class for Rectangular: 12. d. SMACNA Leakage Class for Round and Flat Oval: 12.

C. Return Ducts:

1. Ducts Connected to Air-Handling Units: a. Pressure Class: Positive or negative 2 inch wg. b. Minimum SMACNA Seal Class: A. c. SMACNA Leakage Class for Rectangular: 24 d. SMACNA Leakage Class for Round and Flat Oval: 24

D. Exhaust Ducts:

1. Ducts Connected to Air-Handling Units:

a. Pressure Class: Positive or negative 2 inch wg. b. Minimum SMACNA Seal Class: A c. SMACNA Leakage Class for Rectangular: 12 d. SMACNA Leakage Class for Round and Flat Oval: 12

E. Elbow Configuration:

1. Rectangular Duct: Comply with SMACNA's "HVAC Duct Construction Standards -

Metal and Flexible," Figure 4-2, "Rectangular Elbows."

a. Velocity 1000 fpm or Lower:

1) Radius Type RE 1 with minimum 0.5 radius-to-diameter ratio. 2) Mitered Type RE 4 without vanes.

b. Velocity 1000 to 1500 fpm:

1) Radius Type RE 1 with minimum 1.0 radius-to-diameter ratio. 2) Radius Type RE 3 with minimum 0.5 radius-to-diameter ratio and two

vanes. 3) Mitered Type RE 2 with vanes complying with SMACNA's "HVAC Duct

Construction Standards - Metal and Flexible," Figure 4-3, "Vanes and Vane Runners," and Figure 4-4, "Vane Support in Elbows."

c. Velocity 1500 fpm or Higher:

1) Radius Type RE 1 with minimum 1.5 radius-to-diameter ratio.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

303

Page 108: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

2) Radius Type RE 3 with minimum 1.0 radius-to-diameter ratio and two vanes.

3) Mitered Type RE 2 with vanes complying with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 4-3, "Vanes and Vane Runners," and Figure 4-4, "Vane Support in Elbows."

2. Rectangular Duct: Comply with SMACNA's "HVAC Duct Construction Standards -

Metal and Flexible," Figure 4-2, "Rectangular Elbows."

a. Radius Type RE 1 with minimum 1.5 radius-to-diameter ratio. b. Radius Type RE 3 with minimum 1.0 radius-to-diameter ratio and two vanes. c. Mitered Type RE 2 with vanes complying with SMACNA's "HVAC Duct

Construction Standards - Metal and Flexible," Figure 4-3, "Vanes and Vane Runners," and Figure 4-4, "Vane Support in Elbows."

3. Round Duct: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and

Flexible," Figure 3-4, "Round Duct Elbows."

a. Minimum Radius-to-Diameter Ratio and Elbow Segments: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Table 3- 1, "Mitered Elbows." Elbows with less than 90-degree change of direction have proportionately fewer segments.

1) Velocity 1000 fpm or Lower: 0.5 radius-to-diameter ratio and three

segments for 90-degree elbow. 2) Velocity 1000 to 1500 fpm: 1.0 radius-to-diameter ratio and four segments

for 90-degree elbow. 3) Velocity 1500 fpm or Higher: 1.5 radius-to-diameter ratio and five segments

for 90-degree elbow. 4) Radius-to Diameter Ratio: 1.5.

b. Round Elbows, 12 Inches and Smaller in Diameter: Stamped or pleated.

END OF SECTION 233113

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

304

Page 109: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

SECTION 233300 - AIR DUCT ACCESSORIES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Manual volume dampers. 2. Fire dampers. 3. Duct-mounted access doors.

1.3 ACTION SUBMITTALS

A. Shop Drawings: For duct accessories. Include plans, elevations, sections, details, and

attachments to other work.

1. Detail duct accessories' fabrication and installation in ducts and other construction. Include dimensions, weights, loads, and required clearances; and method of field assembly into duct systems and other construction. Include the following:

a. Special fittings. b. Manual volume damper installations. c. Fire-damper, smoke-damper, combination fire- and smoke-damper, ceiling, and

corridor-damper installations, including sleeves; and duct-mounted access doors and remote damper operators.

d. Include diagrams for power, signal, and control wiring. 1.4 INFORMATIONAL SUBMITTALS

A. Coordination Drawings: Reflected ceiling plans, or BIM model, drawn to scale, on which

ceiling-mounted access panels and access doors required for access to duct accessories are shown and coordinated with each other, using input from installers of the items involved.

1.5 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For air duct accessories to include in operation and

maintenance manuals.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

305

Page 110: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Comply with NFPA 90A and NFPA 90B.

B. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for

acceptable materials, material thicknesses, and duct construction methods unless otherwise indicated. Sheet metal materials shall be free of pitting, seam marks, roller marks, stains, discolorations, and other imperfections.

2.2 MANUAL VOLUME DAMPERS

A. Standard, Steel, Manual Volume Dampers:

1. Acceptable Manufacturers: Ruskin, McGill, and Greenheck.

2. Performance: a. Leakage Rating Class III: Leakage not exceeding 40 cfm/sq. ft. against 1-inch wg

differential static pressure.

3. Construction: a. Linkage out of airstream. b. Suitable for horizontal or vertical airflow applications.

4. Frames:

a. Hat-shaped, 16-gauge-thick, galvanized sheet steel. b. Mitered and welded corners. c. Flanges for attaching to walls and flangeless frames for installing in ducts.

5. Blades:

a. Multiple or single blade. b. Parallel- or opposed-blade design. c. Stiffen damper blades for stability. d. Galvanized steel; 16 gauge thick.

6. Blade Axles: Galvanized steel.

7. Bearings:

a. Oil-impregnated stainless steel sleeve. b. Dampers mounted with vertical blades to have thrust bearing at each end of every

blade.

8. Tie Bars and Brackets: Galvanized steel.

9. Locking device to hold damper blades in a fixed position without vibration.

B. Jackshaft:

1. Size: 0.5-inch diameter.

2. Material: Galvanized-steel pipe rotating within pipe-bearing assembly mounted on supports at each mullion and at each end of multiple-damper assemblies.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

306

Page 111: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3. Length and Number of Mountings: As required to connect linkage of each damper in

multiple-damper assembly.

C. Damper Hardware:

1. Zinc-plated, die-cast core with dial and handle, made of 3/32-inch-thick zinc-plated steel, and a 3/4-inch hexagon locking nut.

2. Include center hole to suit damper operating-rod size. 3. Include elevated platform for insulated duct mounting.

2.3 FIRE DAMPERS

A. Acceptable Manufacturers: Greenheck Fan Corporation, Ruskin Company, Cesco Products and

United Enertech.

B. Type: dynamic; rated and labeled in accordance with UL 555 by an NRTL.

C. Closing rating in ducts up to 4-inch wg static pressure class and minimum 2000 fpm velocity.

D. Fire Rating: 1 1/2 hours.

E. Frame: Curtain type with blades outside airstream; fabricated with roll-formed galvanized steel; with mitered and interlocking corners; gauge in accordance with UL listing.

F. Mounting Sleeve: Factory- or field-installed, galvanized sheet steel; gauge in accordance with

UL listing.

G. Mounting Orientation: Vertical or horizontal as indicated.

H. Blades: Roll-formed interlocking. Material gauge is to be in accordance with UL listing.

I. Horizontal Dampers: Include blade lock and stainless steel closure spring.

J. Heat-Responsive Device: 1. Replaceable, 165 deg F rated, fusible links.

2.4 DUCT-MOUNTED ACCESS DOORS

A. Acceptable Manufacturers: Ruskin, McGill, Flexmaster USA, Inc., and United Enertech.

B. Duct-Mounted Access Doors: Fabricate access panels in accordance with SMACNA's "HVAC

Duct Construction Standards - Metal and Flexible"; Figure 7-2 (7-2M), "Duct Access Doors and Panels," and Figure 7-3, "Access Doors - Round Duct."

1. Door:

a. Double wall, rectangular. b. Galvanized sheet metal with insulation fill and thickness as indicated for duct

pressure class. c. 24-gauge-thick galvanized steel door panel. d. Vision panel.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

307

Page 112: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

e. Hinges and Latches: 1-by-1-inch butt or piano hinge and cam latches. f. Fabricate doors airtight and suitable for duct pressure class.

2. Frame: Galvanized sheet steel, with bend-over tabs and foam gaskets.

a. 24-gauge-thick galvanized steel or 0.032-inch-thick aluminum frame.

3. Number of Hinges and Locks:

a. Access Doors Less Than 12 Inches Square: No hinges and two sash locks. b. Access Doors up to 18 Inches Square: Continuous and two sash locks. c. Access Doors up to 24 by 48 Inches: Continuous and two compression latches with

outside and inside handles. 2.5 MATERIALS

A. Galvanized Sheet Steel: Comply with ASTM A653/A653M.

1. Galvanized Coating Designation: G60. 2. Exposed-Surface Finish: Mill phosphatized.

B. Stainless Steel Sheets: Comply with ASTM A480/A480M, Type 304, and having a No. 2 finish

for concealed ducts.

C. Aluminum Sheets: Comply with ASTM B209, Alloy 3003, Temper H14; with mill finish for concealed ducts and standard, one-side bright finish for exposed ducts.

D. Extruded Aluminum: Comply with ASTM B221, Alloy 6063, Temper T6.

E. Reinforcement Shapes and Plates: Galvanized-steel reinforcement where installed on

galvanized sheet metal ducts; compatible materials for aluminum and stainless steel ducts.

F. Tie Rods: Galvanized steel, 1/4-inch minimum diameter for lengths 36 inches or less; 3/8-inch minimum diameter for lengths longer than 36 inches.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install duct accessories in accordance with applicable details in SMACNA's "HVAC Duct

Construction Standards - Metal and Flexible" for metal ducts and in NAIMA AH116 for fibrous-glass ducts.

B. Install duct accessories of materials suited to duct materials; use galvanized-steel accessories in

galvanized-steel and fibrous-glass ducts, stainless steel accessories in stainless steel ducts, and aluminum accessories in aluminum ducts.

C. Where multiple damper sections are necessary to achieve required dimensions, provide

reinforcement to fully support damper assembly when fully closed at full system design static pressure.

D. Install volume dampers at points on supply, return, and exhaust systems where branches extend

from larger ducts. Where dampers are installed in ducts having duct liner, install dampers with hat channels of same depth as liner, and terminate liner with nosing at hat channel.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

308

Page 113: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

E. Set dampers to fully open position before testing, adjusting, and balancing.

F. Install test holes at fan inlets and outlets and elsewhere as indicated and as needed for testing and balancing.

G. Install fire dampers in accordance with UL listing.

H. Install duct access doors on sides of ducts to allow for inspecting, adjusting, and maintaining

accessories and equipment at the following locations:

1. On both sides of duct coils. 2. Upstream from duct filters. 3. At outdoor-air intakes and mixed-air plenums. 4. At drain pans and seals. 5. Downstream from manual volume dampers, control dampers, backdraft dampers, and

equipment. 6. Adjacent to and close enough to fire or smoke dampers, to reset or reinstall fusible links.

Access doors for access to fire or smoke dampers having fusible links shall be pressure relief access doors and shall be outward operation for access doors installed upstream from dampers and inward operation for access doors installed downstream from dampers.

7. Control devices requiring inspection. 8. Elsewhere as indicated.

I. Install access doors with swing against duct static pressure.

J. Access Door Sizes:

1. One-Hand or Inspection Access: 8 by 5 inches. 2. Two-Hand Access: 12 by 6 inches. 3. Head and Hand Access: 18 by 10 inches. 4. Head and Shoulders Access: 21 by 14 inches. 5. Body Access: 25 by 14 inches. 6. Body plus Ladder Access: 25 by 17 inches.

K. Label access doors according to Section 230553 "Identification for HVAC Piping and

Equipment" to indicate the purpose of access door.

L. For fans developing static pressures of 5 inches wg and more, cover flexible connectors with loaded vinyl sheet held in place with metal straps.

M. Install duct test holes where required for testing and balancing purposes.

N. Install thrust limits at centerline of thrust, symmetrical on both sides of equipment. Attach thrust

limits at centerline of thrust and adjust to a maximum of 1/4-inch movement during start and stop of fans.

3.2 FIELD QUALITY CONTROL A. Tests and Inspections:

1. Operate dampers to verify full range of movement.

2. Inspect locations of access doors, and verify that size and location of access doors are

adequate to perform required operation.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

309

Page 114: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3. Operate fire, smoke, and combination fire and smoke dampers to verify full range of

movement and that proper heat-response device is installed.

4. Inspect turning vanes for proper and secure installation, and verify that vanes do not move or rattle.

5. Operate remote damper operators to verify full range of movement of operator and

damper. END OF SECTION 233300

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

310

Page 115: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

SECTION 233346 - FLEXIBLE DUCTS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Insulated flexible ducts.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. Shop Drawings: For flexible ducts.

1. Include plans showing locations and mounting and attachment details.

1.4 INFORMATIONAL SUBMITTALS

A. Coordination Drawings: Reflected ceiling plans, drawn to scale, on which ceiling-mounted access panels and access doors required for access to duct accessories are shown and coordinated with each other, using input from installers of the items involved.

PART 2 - PRODUCTS

2.1 ASSEMBLY DESCRIPTION

A. Comply with NFPA 90A, "Installation of Air Conditioning and Ventilating Systems," and with

NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Systems."

B. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for acceptable materials, material thicknesses, and duct construction methods unless otherwise indicated. Sheet metal materials shall be free of pitting, seam marks, roller marks, stains, discolorations, and other imperfections.

C. Comply with the Air Diffusion Council's "ADC Flexible Air Duct Test Code FD 72-R1."

D. Comply with ASTM E96/E96M, "Test Methods for Water Vapor Transmission of Materials."

2.2 INSULATED FLEXIBLE DUCTS

A. Acceptable Manufacturers: Flexmaster, Thermaflex, and Ward Industries.

B. Insulated, Flexible Duct: UL 181, Class 1, aluminum laminate and polyester film with latex

adhesive supported by helically wound, spring-steel wire; fibrous-glass insulation; aluminized vapor-barrier film.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

311

Page 116: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

1. Pressure Rating: 10-inch wg positive and 1.0-inch wg negative. 2. Maximum Air Velocity: 4000 fpm. 3. Temperature Range: Minus 20 to plus 210 deg F. 4. Insulation R-Value: Comply with ASHRAE/IES 90.1

2.3 FLEXIBLE DUCT CONNECTORS

A. Clamps: Stainless-steel band with cadmium-plated hex screw to tighten band with a worm-gear

action in sizes 3 through 18 inches, to suit duct size. PART 3 - EXECUTION

3.1 INSTALLATION

A. Install flexible ducts according to applicable details in SMACNA's "HVAC Duct Construction

Standards - Metal and Flexible" for metal ducts and in NAIMA AH116, "Fibrous Glass Duct Construction Standards," for fibrous-glass ducts.

B. Install in indoor applications only. Flexible ductwork should not be exposed to UV lighting.

C. Connect diffusers to ducts or taps with maximum 60-inch lengths of flexible duct clamped or

strapped in place.

D. Install duct test holes where required for testing and balancing purposes.

E. Installation:

1. Install ducts fully extended. 2. Do not bend ducts across sharp corners. 3. Bends of flexible ducting shall not exceed a minimum of one duct diameter. 4. Avoid contact with metal fixtures, water lines, pipes, or conduits. 5. Install flexible ducts in a direct line, without sags, twists, or turns.

F. Supporting Flexible Ducts:

1. Suspend flexible ducts with bands 1-1/2 inches wide or wider and spaced a maximum of 48 inches apart. Maximum centerline sag between supports shall not exceed 1/2 inch per 12 inches.

2. Install extra supports at bends placed approximately one duct diameter from center line of

the bend.

3. Ducts may rest on ceiling joists or truss supports. Spacing between supports shall not exceed the maximum spacing per manufacturer's written installation instructions.

4. Vertically installed ducts shall be stabilized by support straps at a maximum of 72 inches o.c.

END OF SECTION 233346

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

312

Page 117: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

SECTION 233600 - AIR TERMINAL UNITS

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes: 1. Modulating, single-duct air terminal units.

1.2 ACTION SUBMITTALS

A. Product Data: For each type of air terminal unit.

1. Include construction details, material descriptions, dimensions of individual components

and profiles, and finishes for air terminal units. 2. Include rated capacities, operating characteristics, electrical characteristics, and furnished

specialties and accessories.

B. Shop Drawings: For air terminal units.

1. Include plans, elevations, sections, and mounting details. 2. Include details of equipment assemblies. Indicate dimensions, weights, loads, required

clearances, method of field assembly, components, and location and size of each field connection.

3. Include diagrams for power, signal, and control wiring. 4. Hangers and supports, including methods for duct and building attachment, and vibration

isolation.

1.3 INFORMATIONAL SUBMITTALS

A. Coordination Drawings: Floor plans and other details, or BIM model, drawn to scale, indicating the items described in this Section, and coordinated with all building trades.

B. Field quality-control reports.

1.4 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For air terminal units to include in emergency, operation, and

maintenance manuals.

1. In addition to items specified in Section 017823 "Operation and Maintenance Data," include the following: a. Instructions for resetting minimum and maximum air volumes. b. Instructions for adjusting software set points.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a

Qualified Electrical Testing Laboratory, and marked for intended location and application.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

313

Page 118: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

B. ASHRAE 62.1 Compliance: Applicable requirements in ASHRAE 62.1, Section 5 - "Systems and Equipment," and Section 7 - "Construction and System Start-up."

C. ASHRAE/IES 90.1 Compliance: Applicable requirements in ASHRAE/IES 90.1, "Section 6 -

Heating, Ventilating, and Air Conditioning." 2.2 MODULATING, SINGLE-DUCT AIR TERMINAL UNITS

A. Acceptable Manufacturers: Trane, METALAIRE, Inc., and Johnson Controls, Inc.

B. Description: Volume-damper assembly inside unit casing with control components inside a

protective metal shroud.

C. Casing: Minimum 22-gauge-thick galvanized steel.

1. Casing Liner: Comply with requirements in "Casing Liner" Article below for Casing Liner, Fibrous Glass Paragraph.

2. Air Inlet: Round stub connection or S-slip and drive connections for duct attachment. 3. Air Outlet: S-slip and drive connections. 4. Access: Removable panels for access to parts requiring service, adjustment, or

maintenance; with airtight gasket.

D. Volume Damper: Galvanized steel with peripheral gasket and self-lubricating bearings.

1. Maximum Damper Leakage: AHRI 880 rated, 2 percent of nominal airflow at 3-inch wg inlet static pressure.

E. Velocity Sensors: Multipoint array with velocity inlet sensors.

F. Electronic Controls:

1. Electronic Damper Actuator: 24 V, spring-return closed. 2. Electronic Thermostat: Wall-mounted electronic type with temperature set-point display in

Fahrenheit and Celsius. 3. Electronic Air Volume Controller: Pressure-independent analog electronic controller,

factory calibrated and field adjustable to minimum and maximum air volumes; provides consistent airflow to the space in response to electronic thermostat signal while compensating for inlet static-pressure variations of up to 4 inches wg; includes a multipoint velocity sensor at air inlet.

G. Direct Digital Controls:

1. Terminal Unit Controller: Pressure-independent, VAV controller and integrated actuator,

and electronic airflow transducer with multipoint velocity sensor at air inlet, factory calibrated to minimum and maximum air volumes.

a. Occupied and unoccupied operating mode. b. Remote reset of airflow or temperature set points. c. Adjusting and monitoring with portable terminal. d. Communication with temperature-control system specified in Section 230923

"Direct Digital Control (DDC) System for HVAC."

2. Room Sensor: Wall mounted with temperature set-point adjustment and access for connection of portable operator terminal.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

314

Page 119: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3. Terminal Unit Controller, Section 230923: Controller is to be factory mounted and wired by air terminal manufacturer; unit controllers, integrated actuators, and room sensors to be furnished under Section 230923 "Direct Digital Controls (DDC) for HVAC."

H. Control Sequence: See Section 230993.11 Sequence of Operation for HVAC for control

sequences.

2.3 CASING LINER

A. Casing Liner, Fibrous Glass: Fibrous-glass duct liner, complying with ASTM C1071, NFPA 90A or NFPA 90B, and with NAIMA AH124.

1. Minimum Thickness: 1/2 inch.

a. Maximum Thermal Conductivity:

1) Type I, Flexible: 0.27 Btu x in./h x sq. ft. x deg F at 75 deg F mean

temperature. 2) Type II, Rigid: 0.23 Btu x in./h x sq. ft. x deg F at 75 deg F mean

temperature. 2. Foil-Faced Liner: Minimum 0.001-inch reinforced, nonporous aluminum foil applied to

matted insulation airstream face. 3. Solid Metal Liner: Solid galvanized sheet metal encapsulating matted insulation face

from airstream. 4. Perforated Metal Liner: Perforated galvanized sheet metal encapsulating matted

insulation face from airstream. 5. Water-Based Liner Adhesive: Comply with NFPA 90A or NFPA 90B and with

ASTM C916.

2.4 SOURCE QUALITY CONTROL

A. AHRI 880: Test and rate assembled air terminal units in accordance with AHRI 880.

PART 3 - EXECUTION

3.1 INSTALLATION, GENERAL

A. Comply with Section 230529 "Hangers and Supports for HVAC Piping and Equipment" and Section 233113 "Metal Ducts" for hangers and supports.

B. Install air terminal units according to NFPA 90A.

C. Install air terminal units level and plumb. Maintain sufficient clearance for normal service and

maintenance.

D. Install wall-mounted thermostats.

3.2 DUCTWORK CONNECTIONS

A. Comply with requirements in Section 233113 Metal Ducts for connecting ducts to air terminal units.

B. Make connections to air terminal units with flexible connectors complying with requirements in

Section 233300 "Air Duct Accessories."

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

315

Page 120: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3.3 ELECTRICAL CONNECTIONS

A. Install field power to each air terminal unit electrical power connection. Coordinate with air terminal unit manufacturer and installers.

B. Connect wiring in accordance with Section 260519 "Low-Voltage Electrical Power Conductors

and Cables."

C. Ground equipment in accordance with Section 260526 "Grounding and Bonding for Electrical Systems."

D. Install electrical devices furnished by manufacturer, but not factory mounted, in accordance

with NFPA 70 and NECA 1.

E. Install nameplate for each electrical connection, indicating electrical equipment designation and circuit number feeding connection.

1. Nameplate shall be laminated acrylic or melamine plastic signs, as specified in

Section 260553 "Identification for Electrical Systems." 3.4 CONTROL CONNECTIONS

A. Install control and electrical power wiring to field-mounted control devices.

B. Connect control wiring in accordance with Section 260523 "Control-Voltage Electrical Power

Cables." 3.5 IDENTIFICATION

A. Label each air terminal unit with drawing designation, nominal airflow, maximum and

minimum factory-set airflows. Comply with requirements in Section 230553 "Identification for HVAC Equipment" for equipment labels and warning signs and labels.

3.6 STARTUP SERVICE

A. Perform startup service.

1. Complete installation and startup checks in accordance with manufacturer's written instructions.

2. Verify that inlet duct connections are as recommended by air terminal unit manufacturer to achieve proper performance.

3. Verify that controls and control enclosure are accessible. 4. Verify that control connections are complete. 5. Verify that nameplate and identification tag are visible. 6. Verify that controls respond to inputs as specified.

3.7 ADJUSTING

A. Comply with requirements in Section 230593 "Testing, Adjusting, and Balancing for HVAC"

for air terminal unit testing, adjusting, and balancing.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

316

Page 121: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

3.8 FIELD QUALITY CONTROL

A. Testing Agency: Contractor will engage a qualified testing agency to perform tests and

inspections.

B. Manufacturer's Field Service: Engage a factory-authorized service representative to test and inspect components, assemblies, and equipment installations, including connections.

C. Perform the following tests and inspections:

1. After installing air terminal units and after electrical circuitry has been energized, test for

compliance with requirements. 2. Leak Test: After installation, fill water coils and test for leaks. Repair leaks and retest

until no leaks exist. 3. Operational Test: After electrical circuitry has been energized, start units to confirm

proper motor rotation and unit operation. 4. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and

equipment.

D. Air terminal unit will be considered defective if it does not pass tests and inspections.

E. Prepare test and inspection reports.

3.9 DEMONSTRATION

A. Train Owner's maintenance personnel to adjust, operate, and maintain air terminal units.

END OF SECTION 233600

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

317

Page 122: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

SECTION 233713.13 - AIR DIFFUSERS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes: 1. Rectangular and square ceiling diffusers.

B. Related Requirements:

1. Section 233300 "Air Duct Accessories" for fire and smoke dampers and volume-control dampers not integral to diffusers.

2. Section 233713.23 "Air Registers and Grilles" for adjustable-bar register and grilles, fixed-face registers and grilles, and linear bar grilles.

3. Section 233713.43 "Security Registers and Grilles" for security registers and security grilles.

4. Section 233716 "Fabric Air-Diffusion Devices" for continuous tubular diffusers.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product.

1. Data Sheet: Indicate materials of construction, finish, and mounting details; and performance data including throw and drop, static-pressure drop, and noise ratings.

2. Diffuser Schedule: Indicate drawing designation, room location, quantity, model number,

size, and accessories furnished.

1.4 INFORMATIONAL SUBMITTALS

A. Source quality-control reports.

PART 2 - PRODUCTS

2.1 SQUARE CEILING DIFFUSERS

A. Acceptable Manufacturers: Price Industries, Titus, Tuttle & Bailey.

B. Devices shall be specifically designed for variable-air-volume flows.

C. Material: Aluminum

D. Finish: White, powder coat.

E. Face Size: 24 by 24 inches.

F. Mounting: Surface

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

318

Page 123: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

G. Pattern: Adjustable

H. Dampers: Radial Opposed Blade

I. Accessories:

1. Equalizing grid. 2. Safety chain. 3. Sectorizing baffles. 4. Operating rod extension.

2.2 SOURCE QUALITY CONTROL

A. Verification of Performance: Rate diffusers according to ASHRAE 70, "Method of Testing for Rating the Performance of Air Outlets and Inlets."

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine areas where diffusers are installed for compliance with requirements for installation tolerances and other conditions affecting performance of equipment.

B. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A. Install diffusers level and plumb.

B. Ceiling-Mounted Outlets and Inlets: Drawings indicate general arrangement of ducts, fittings,

and accessories. Air outlet and inlet locations have been indicated to achieve design requirements for air volume, noise criteria, airflow pattern, throw, and pressure drop. Make final locations where indicated, as much as practical. For units installed in lay-in ceiling panels, locate units in the center of panel. Where architectural features or other items conflict with installation, notify Architect for a determination of final location.

C. Install diffusers with airtight connections to ducts and to allow service and maintenance of

dampers, air extractors, and fire dampers.

3.3 ADJUSTING

A. After installation, adjust diffusers to air patterns indicated, or as directed, before starting air balancing.

END OF SECTION 233713.13

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

319

Page 124: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

SECTION 233713.23 - REGISTERS AND GRILLES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Fixed face grille.

B. Related Requirements:

1. Section 233300 "Air Duct Accessories" for fire and smoke dampers and volume-control dampers not integral to registers and grilles.

2. Section 233713.13 "Air Diffusers" for various types of air diffusers. 3. Section 233713.43 "Security Registers and Grilles" for security registers and security

grilles. 4. Section 233716 "Fabric Air-Diffusion Devices" for continuous tubular diffusers.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product.

1. Data Sheet: Indicate materials of construction, finish, and mounting details; and

performance data including throw and drop, static-pressure drop, and noise ratings.

2. Register and Grille Schedule: Indicate drawing designation, room location, quantity, model number, size, and accessories furnished.

B. Samples: For each exposed product and for each color and texture specified. Smallest size

register and grille indicated.

C. Samples for Initial Selection: For registers and grilles with factory-applied color finishes. Smallest size register and grille indicated.

D. Samples for Verification: For registers and grilles, in manufacturer's standard sizes to verify

color selected. Smallest size register and grille indicated.

1.4 INFORMATIONAL SUBMITTALS

A. Coordination Drawings: Reflected ceiling plans, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved:

1. Ceiling suspension assembly members. 2. Method of attaching hangers to building structure. 3. Size and location of initial access modules for acoustical tile. 4. Ceiling-mounted items including lighting fixtures, diffusers, grilles, speakers, sprinklers,

access panels, and special moldings. 5. Duct access panels.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

320

Page 125: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

B. Source quality-control reports.

PART 2 – PRODUCTS

2.1 GRILLES

A. Fixed Face Grille [B]: 1. Acceptable Manufacturers: Price Industries, Titus, Tuttle and Bailey. 2. Material: Aluminum 3. Finish: White, powder coat. 4. Face Blade Arrangement: 45-degree, spaced 1/2 inch apart. 5. Face Arrangement: Perforated core. 6. Core Construction: Removable 7. Frame: 1-inch wide. 8. Mounting: Lay in.

2.2 REGISTER

A. Face Register [C]:

1. Acceptable Manufacturers: Price Industries, Titus, Tuttle and Bailey. 2. Material: Aluminum 3. Finish: White, powder coat. 4. Face Blade Arrangement: 45-degree, spaced 1/2 inch apart. 5. Face Arrangement: Perforated core. 6. Core Construction: Removable. 7. Frame:1-inch wide. 8. Mounting: Lay-in. 9. Damper Type: Adjustable opposed blade.

2.2 SOURCE QUALITY CONTROL

A. Verification of Performance: Rate registers and grilles according to ASHRAE 70, "Method of

Testing for Rating the Performance of Air Outlets and Inlets."

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine areas where registers and grilles are installed for compliance with requirements for installation tolerances and other conditions affecting performance of equipment.

B. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A. Install registers and grilles level and plumb.

B. Outlets and Inlets Locations: Drawings indicate general arrangement of ducts, fittings, and accessories. Air outlet and inlet locations have been indicated to achieve design requirements for air volume, noise criteria, airflow pattern, throw, and pressure drop. Make final locations where indicated, as much as practical. For units installed in lay-in ceiling panels, locate units in the center of panel. Where architectural features or other items conflict with installation, notify Architect for a determination of final location.

ITB NO. 21-04-84 Juvenile & Domestic Relations Court Office and Sheriff Security Station Renovation

321

Page 126: SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC … · 2021. 6. 7. · 4. Pad Mate rial: Oil and water resistant with elastomeric properties. Neoprene rubber, silicone rubber, or other

C. Install registers and grilles with airtight connections to ducts and to allow service and

maintenance of dampers, air extractors, and fire dampers. 3.3 ADJUSTING

A. After installation, adjust registers and grilles to air patterns indicated, or as directed, before

starting air balancing. END OF SECTION 233713.23