41
SECTION 15810 DUCTWORK AND ACCESSORIES i PART 1 GENERAL...................................................................................................................1 1.1 SCOPE ............................................................................................................................................. 1 1.2 RELATED SECTIONS ................................................................................................................... 1 1.3 SHOP DRAWINGS ......................................................................................................................... 1 1.4 REFERENCES ................................................................................................................................ 2 1.5 REGULATIONS ............................................................................................................................. 4 1.6 GENERAL ARRANGEMENT ....................................................................................................... 4 1.7 QUALITY ASSURANCE ............................................................................................................... 4 1.8 DELIVERY, STORAGE AND HANDLING ................................................................................. 5 1.9 REGULATIONS ............................................................................................................................. 5 1.10 WORKING DRAWINGS AND EQUIPMENT MANUALS ......................................................... 5 PART 2 PRODUCTS ................................................................................................................6 2.1 DUCTWORK GENERAL............................................................................................................... 6 2.2 SEAL CLASSIFICATION .............................................................................................................. 6 2.3 SEALANT ....................................................................................................................................... 7 2.4 TAPE ............................................................................................................................................... 7 2.5 DUCT LEAKAGE........................................................................................................................... 7 2.6 FITTINGS ........................................................................................................................................ 7 2.7 FIRESTOPPING.............................................................................................................................. 8 2.8 STAINLESS STEEL........................................................................................................................ 8 2.9 THERMOSET FRP DUCTS AND FITTINGS ............................................................................... 9 2.10 MECHANICAL LINER AND FASTENERS: .............................................................................. 13 2.11 SHEET METAL PLENUMS:........................................................................................................ 14 2.12 FRP PLENUMS............................................................................................................................. 14 2.13 LOUVERS ..................................................................................................................................... 14 2.14 BLANK OFF PANELS ................................................................................................................. 15 2.15 STATIONARY BLADE MITERED CORNER PENTHOUSE. .................................................. 15 2.16 ROOF CURB ................................................................................................................................. 17 2.17 MOTORIZED DAMPERS ............................................................................................................ 18 2.18 FRP MOTORIZED DAMPERS .................................................................................................... 18 2.19 DAMPER ELECTRICAL MOTOR ACTUATOR ....................................................................... 19 2.20 BACKDRAFT DAMPERS ........................................................................................................... 20 2.21 SINGLE- AND MULTI-BLADED BALANCING DAMPERS ................................................... 23 2.22 FIRE DAMPERS ........................................................................................................................... 24 2.23 SUPPLY GRILLE ......................................................................................................................... 25 2.24 RETURN GRILLE ........................................................................................................................ 25 2.25 DOOR TRANSFER LOUVRE...................................................................................................... 26 2.26 ROUND GRILLE .......................................................................................................................... 26 2.27 INSTRUMENT TEST PORTS ...................................................................................................... 27 2.28 DUCT INSPECTION DOORS ...................................................................................................... 27 2.29 DUCTWORK HANGERS AND SUPPORTS .............................................................................. 27 2.30 DUCT SEALING MATERIALS ................................................................................................... 29 2.31 INSULATION ............................................................................................................................... 30

SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

  • Upload
    letuong

  • View
    214

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

SECTION 15810DUCTWORK AND ACCESSORIES

i

PART 1 GENERAL...................................................................................................................1

1.1 SCOPE............................................................................................................................................. 11.2 RELATED SECTIONS ................................................................................................................... 11.3 SHOP DRAWINGS......................................................................................................................... 11.4 REFERENCES ................................................................................................................................ 21.5 REGULATIONS ............................................................................................................................. 41.6 GENERAL ARRANGEMENT ....................................................................................................... 41.7 QUALITY ASSURANCE ............................................................................................................... 41.8 DELIVERY, STORAGE AND HANDLING ................................................................................. 51.9 REGULATIONS ............................................................................................................................. 51.10 WORKING DRAWINGS AND EQUIPMENT MANUALS ......................................................... 5

PART 2 PRODUCTS ................................................................................................................6

2.1 DUCTWORK GENERAL............................................................................................................... 62.2 SEAL CLASSIFICATION .............................................................................................................. 62.3 SEALANT ....................................................................................................................................... 72.4 TAPE ............................................................................................................................................... 72.5 DUCT LEAKAGE........................................................................................................................... 72.6 FITTINGS........................................................................................................................................ 72.7 FIRESTOPPING.............................................................................................................................. 82.8 STAINLESS STEEL........................................................................................................................ 82.9 THERMOSET FRP DUCTS AND FITTINGS............................................................................... 92.10 MECHANICAL LINER AND FASTENERS: .............................................................................. 132.11 SHEET METAL PLENUMS:........................................................................................................ 142.12 FRP PLENUMS............................................................................................................................. 142.13 LOUVERS..................................................................................................................................... 142.14 BLANK OFF PANELS ................................................................................................................. 152.15 STATIONARY BLADE MITERED CORNER PENTHOUSE. .................................................. 152.16 ROOF CURB................................................................................................................................. 172.17 MOTORIZED DAMPERS ............................................................................................................ 182.18 FRP MOTORIZED DAMPERS.................................................................................................... 182.19 DAMPER ELECTRICAL MOTOR ACTUATOR ....................................................................... 192.20 BACKDRAFT DAMPERS ........................................................................................................... 202.21 SINGLE- AND MULTI-BLADED BALANCING DAMPERS................................................... 232.22 FIRE DAMPERS........................................................................................................................... 242.23 SUPPLY GRILLE ......................................................................................................................... 252.24 RETURN GRILLE ........................................................................................................................ 252.25 DOOR TRANSFER LOUVRE...................................................................................................... 262.26 ROUND GRILLE .......................................................................................................................... 262.27 INSTRUMENT TEST PORTS...................................................................................................... 272.28 DUCT INSPECTION DOORS...................................................................................................... 272.29 DUCTWORK HANGERS AND SUPPORTS .............................................................................. 272.30 DUCT SEALING MATERIALS................................................................................................... 292.31 INSULATION ............................................................................................................................... 30

Page 2: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

SECTION 15810DUCTWORK AND ACCESSORIES

ii

PART 3 EXECUTION ............................................................................................................30

3.1 MATERIALS................................................................................................................................. 303.2 DUCTWORKS .............................................................................................................................. 303.3 ULTRAVIOLET PROTECTION.................................................................................................. 323.4 ULTRAVIOLET PROTECTION.................................................................................................. 323.5 DUCTWORK SUPPORT.............................................................................................................. 323.6 LOUVERS..................................................................................................................................... 333.7 GRILLES ....................................................................................................................................... 333.8 DAMPERS..................................................................................................................................... 333.9 EQUIPMENT SUPPORTS............................................................................................................ 343.10 SEALING ...................................................................................................................................... 343.11 FLEXIBLE DUCTS....................................................................................................................... 343.12 FLEXIBLE CONNECTIONS ....................................................................................................... 343.13 DUCT EXPANSION JOINTS....................................................................................................... 353.14 INSTRUMENT TEST PORTS...................................................................................................... 353.15 TURNING VANES ....................................................................................................................... 353.16 LEAKAGE TEST .......................................................................................................................... 363.17 SOUND ATTENUATORS............................................................................................................ 363.18 PAINTING..................................................................................................................................... 363.19 BALANCING................................................................................................................................ 373.20 DUCTWORK TESTING............................................................................................................... 373.21 EQUIPMENT TESTING............................................................................................................... 383.22 COMMISSIONING....................................................................................................................... 383.23 TRAINING .................................................................................................................................... 383.24 MANUFACTURER’S SERVICES ............................................................................................... 38

Page 3: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-1DUCTWORK AND ACCESSORIES (ADD#5)

SECTION 15810DUCTWORK AND ACCESSORIES

PART 1 GENERAL

1.1 SCOPE

.1 Supply, install, and satisfactorily operate a complete ducting and ventilatingsystem equipment to the full intent of the Drawings and Specification.

1.2 RELATED SECTIONS

.1 Basic Mechanical Materials and Methods: Section 15050

.2 Fans and Accessories: Section 15815

.3 Electrical: Division 16

1.3 SHOP DRAWINGS

.1 Submit shop drawings and samples of duct fittings for approval;

.1 Plenums and plenum related items showing physical dimensions, joints,sealants, door construction and hardware.

.2 Factory fabricated ducts, fittings and joining systems (FRP and Metal).

.3 Firewall duct penetrations; fire and smoke dampers; access doors.

.4 Dampers (all types)

.5 Fire dampers

.6 Louvers

.7 Grilles/Diffusers

.2 Submit control-wiring diagrams for automatic dampers and other automatedductwork accessories.

.3 Sound Attenuator Certified Test Data:

.1 Dynamic insertion loss

.2 Self noise power levels

.3 Static pressure loss

Page 4: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-2DUCTWORK AND ACCESSORIES (ADD#5)

.4 Dimensions and weights

.4 Coordination drawings: provide plans drawn to scale, on which the followingitems are shown and coordinated with each other, using input from installers onthe items involved:

.1 Duct installation in congested spaces, indicating coordination with generalconstruction, building components and other building services. Indicateproposed changes to duct layout.

.2 Suspended ceiling components.

.3 Structural members to which duct will be attached.

.4 Penetrations of smoke barriers and fire-rated construction.

.5 Submit changes or alteration in ductwork layout, with supporting calculationshowing that the modified design will not increase total pressure, before workcommences. Submittals for proposed changes shall be stamped for approval bythe engineer prior to commencement of work.

1.4 REFERENCES

.1 Comply with the latest revision of the following codes, standards andspecifications, except where more stringent requirements have been specifiedherein.

.1 American Society for Testing Materials (ASTM)

.1 C 582: Contact-moulded Reinforced Thermosetting Plastic (RTP)Laminated for Corrosion-Resisdence Equipment

.2 D 2310 – Machine-Made Reinforced Thermosetting Resin Pipe.

.3 D 2412: Standard Test Method for Determination of ExternalLoading Characteristics of Plastic Pipe by Parallel-Plate Loading.

.4 D 2996: Filament-Wound ‘Fiberglass’ (Glass Fiber ThermosettingResin) pipe and Fittings.

.5 D 3982: Contact-Moulded ‘Fiberglass’ (Glass Fibre ReinforcedThermosetting Resin) Duct and Hoods.

.6 E 84: Standard Test Method for Surface Burning Characteristic ofBuilding Materials.

Page 5: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-3DUCTWORK AND ACCESSORIES (ADD#5)

.7 C 518 - Standard Test Method for Steady-State ThermalTransmission, Transmission Properties by Means of the HeatFlow Meter Apparatus. *Addendum #2

.2 National Fire Protection Association (NFPA)

.1 90A: Standard for Installation of AC and Ventilation Systems

.2 90B: Standard for Installation of Warm Air Heating and ACSystems

.3 255: Building Materials, Test of Burning Characteristics (same asASTM E84)

.3 Sheet Metal and Air Conditioning Contractors National Association, Inc.(SMACNA)

.1 HVAC Duct Construction Standards – Metal and Flexible

.2 HVAC Duct Systems Design

.3 Thermoset FRP Duct Construction Manual

.4 Fire, Smoke and Radiation Damper Installation Guide for HVACSystems

.4 ASHRAE:

.1 ASHRAE Standard 51.

.2 ASHRAE Standard 62.

.5 Underwriters Laboratories (UL)

.1 UL 181: Factory Made Air Ducts and Air Connectors

.2 UL 555: Standard for Safety Fire Dampers

.3 UL 723: Test for Surface Burning Characteristics of BurningMaterials (ASTM E84)

.4 S102: Standard Method of Test for Surface BurningCharacteristics of Building Materials and Assemblies*Addendum #2

.6 Canadian General Standards Board (CGSB):

.1 41.22: Fibreglass-Reinforced Plastic Corrosion- ResistantEquipment *Addendum #2

Page 6: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-4DUCTWORK AND ACCESSORIES (ADD#5)

1.5 REGULATIONS

.1 Conform to all codes, by-laws, etc. of Provincial and Municipal authorities havingjurisdiction.

.2 No additional compensation will be awarded for carrying out any conditionsembodied in such regulations.

.3 When the work as shown and as specified exceeds the minimum requirements ofsuch regulations, the Drawings and/or Specifications shall govern.

.4 Provide all permits, inspections, and certificates required for this Section.

1.6 GENERAL ARRANGEMENT

.1 All mechanical equipment, ductwork and fittings specified herein, in related sectionsabove and shown on the Drawings indicates the general arrangement.

.2 Co-ordinate the work under this Section with all other trades, in particular thestructural work and make all necessary changes or additions to the runs toaccommodate structural conditions, piping, ductwork, mechanical equipment, etc.

.3 Install the systems and apparatus in a practical and first-class manner andguarantee all work and apparatus against defects of workmanship and materialand make good any and all defects that may develop.

1.7 QUALITY ASSURANCE

.1 Industry Standards:

.1 Unless otherwise indicated or specified in the Contract Documents, sheetmetal ductwork shall be constructed and installed in accordance with theSMACNA duct construction standard relevant to ductwork system beingprovided. These standards are herein referenced as the SMACNA Manual,unless otherwise indicated in the Contract Documents.

.2 Comply with the ASHRAE Fundamentals Handbook recommendations,except as otherwise indicated in the Contract Documents.

.3 NFPA Compliance: NFPA 90A and NFPA 90B.

.2 Manufacturers: Firms regularly engaged in manufacture of ductwork products ofthe types, materials, and sizes required, whose products have been satisfactorilyused in similar service for a minimum of 5 years.

.3 Suppliers of duct and fitting components shall provide on request the followinginformation:

.1 Laboratory performance data for duct, including leakage rate, burstingstrength, collapse strength, seam strength, and pressure loss.

.2 Laboratory performance data for fittings, including zero length dynamiclosses.

Page 7: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-5DUCTWORK AND ACCESSORIES (ADD#5)

.4 The installer shall be a firm with a minimum of 3 years’ experience of successfulinstallation on ductwork systems similar to that required for this Contract.

.5 Changes or alterations to layout or configuration of duct system shall be:

.1 Specifically approved in writing by the Consultant.

.2 Proposed layout shall provide original design results, without increasingsystem total pressure.

1.8 DELIVERY, STORAGE AND HANDLING

.1 Protection:.1 Use all means necessary to protect pipes and appurtenances before, during,

and after installation and to protect the installed work of other trades from thework of this Section.

.2 Replacements:.1 In the event of damage to piping and appurtenances, immediately make all

repairs necessary to the approval of the Consultant, at no additional cost tothe Region.

.3 Protect ductwork from dirt, water, and debris. During storage on the Site, keepends of ductwork covered to prevent foreign objects and water from enteringductwork.

.4 Deliver sealant materials to the Site in their original unopened containers labeledwith the manufacturer, Product name and designation, colour, expiration periodfor use, pot life, curing time, and mixing instructions for multi componentmaterials.

.5 Store and handle sealant materials in compliance with the manufacturers’recommendations to prevent deterioration or damage due to moisture, high or lowtemperatures, contaminants, or other causes.

.6 Deliver and store stainless steel sheets with mill applied adhesive protectivepaper, maintained through fabrication and installation.

1.9 REGULATIONS

.1 Conform to all applicable codes (including but not limited to. those listed insubsection 1.4) No additional compensation will be awarded for carrying out anyconditions embodied in such regulations.

.2 When the requirements of the Contract Documents exceed the minimumrequirements of such regulations, the requirements of the Contract Documentsshall govern.

.3 Provide all permits, inspections, and certificates required for this Section.

1.10 WORKING DRAWINGS AND EQUIPMENT MANUALS

.1 Submit working Drawings for review for all items included in this Section.

.2 Submit all manuals required under this section.

Page 8: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-6DUCTWORK AND ACCESSORIES (ADD#5)

PART 2 PRODUCTS

2.1 DUCTWORK GENERAL

.1 Ductwork located in dry well and control rooms shall be stainless steel. Ductworklocated in wet wells, supply and exhaust ductwork from the wet well shall beThermoset FRP.

.2 Install ductwork as shown on the Drawings. Duct sizes shown on the Drawings areclear internal dimensions.

.3 Ductwork to be adequately strong and sufficiently rigid to resist all normalshocks, reinforced at all points where necessary to prevent vibration ormovement, and securely fastened in place.

.4 Ensure ducts are airtight and all joints gasketted or caulked and made inaccordance with the best standards of the trades.

.5 Elbows and other changes in ductwork direction to have centreline radius at leastequal to the duct depth or diameter. Where possible, all transitions in duct sizewill be made with an angle not exceeding 30 degrees. Supply and install dampersin all ducts as indicated.

.6 Install flexible duct connector where the ductwork connects to ventilationequipment (i.e. Fan). Acceptable manufacturer: Duro Dyne Canada Inc.

.1 Insulated Ductwork: Metal Fab with Durolon flex connector c/w grip-loc.

.2 Uninsulated Ductwork: Metal Fab with Durolon flex connector c/w grip-loc.

.3 Provide exterior coat on flex connectors to protect against UV and ozoneweathering and chemical exposure.

.4 All metal parts shall be 316L grade stainless steel. *Addendum#5

2.2 SEAL CLASSIFICATION

.1 Classification as follows:

Maximum Pressure Pa SMACNA Seal Class> 1000 A750 B500 C250 C125 C

Page 9: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-7DUCTWORK AND ACCESSORIES (ADD#5)

.2 Seal classification:

.1 Class A: longitudinal seams, transverse joints, duct wall penetrations andconnections made airtight with sealant and tape.

.2 Class B: longitudinal seams, transverse joints and connections made airtightwith sealant tape or combination thereof.

.3 Class C: transverse joints and connections made air tight with gaskets,sealant tape or combination thereof. Longitudinal seams unsealed.

2.3 SEALANT

.1 Sealant: oil resistant, polymer type flame resistant duct sealant. Temperaturerange of minus 30° C to plus 93° C.

2.4 TAPE

.1 Tape: polyvinyl treated, open weave fiberglass tape, 50 mm wide.

2.5 DUCT LEAKAGE

.1 In accordance with SMACNA HVAC Duct Leakage Test Manual.

2.6 FITTINGS

.1 Fabrication: to SMACNA.

.2 Radiused elbows:

.1 Rectangular: Centreline radius: 1.5 times width of duct.

.2 Round: smooth radius or five piece. Centreline radius: 1.5 times diameter.

.3 Mitred elbows, rectangular:

.1 To 400 mm: with single thickness turning vanes.

.2 Over 400 mm: with double thickness turning vanes.

.4 Branches:

.1 Rectangular main and branch: with radius on branch 1.5 times width of ductor 450 entry on branch.

.2 Round main and branch: enter main duct at 450 with conical connection.

.3 Provide volume control damper in branch duct near connection to main duct.

Page 10: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-8DUCTWORK AND ACCESSORIES (ADD#5)

.4 Main duct branches: with volume control damper.

.5 Transitions:

.1 Diverging: 200 maximum included angle.

.2 Converging: 300 maximum included angle.

.6 Offsets:

.1 Full short radiused elbows as indicated.

.7 Obstruction deflectors: maintain full cross-sectional area. Maximum includedangles: as for transitions.

2.7 FIRESTOPPING

.1 Retaining angles around duct, on both sides of fire separation.

.2 Firestopping material and installation must not distort duct.

2.8 STAINLESS STEEL

.1 To ASTM A480/A480M, Type 304.

.2 Finish: No 4. finish on exposed side of duct in finished areas, No. 3 finish orlower where concealed.

.3 Thickness, fabrication and reinforcement: to SMACNA.

.4 Joints: to SMACNA and be continuous inert gas welded. * Addendum #5

.5 Rectangular ductwork shall be shop fabricated form Gauge 22, Grade 304Lstainless steel, ASTM A167, ASTM A480 and ASTM 480M with a #4 finishwhere bare (uncovered) and exposed in finished areas and a #2B finishelsewhere, with, unless otherwise specified, metal gauges in accordance withSMACNA HVAC Duct Construction Standards Metal and Flexible. Thestainless steel thickness shall be factory stenciled on the material. Air ductand fitting connections shall be flanged with stainless steel bolt, washers andnuts, and EPDM gaskets; no duct sealer. Fitting gauge shall be one metalgauge heavier than the duct they associated with. Duct system performanceshall meet SMACNA’s Leakage Class 3 requirements at the system designstatic pressure. No sharp points allowed at the duct connections. * Addendum#5

.6 For round ductwork, use Flexmaster Canada Ltd “SPIRA-DUCT” spiralmechanically locked flat seam, single wall duct fabricated from stainless steel toASTM A480/A480M with metal gauges in accordance with SMACNA. Fitting and

Page 11: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-9DUCTWORK AND ACCESSORIES (ADD#5)

couplings are to be factory made “SPIROSAFE” stainless steel fittings one metalgauge heaver that the duct they are associated with and equipped with a captive U-profile flexible EPDM rubber gasket secured to the connecting duct by means of 2 to6 sheet metal screws, no duct sealer. Duct system performance is to meetSMACNA’s Leakage Class 3 requirements at the system design static pressure.

.7 Fittings to be “Uniform” manufactured by the “United Sheet Metal Co.Inc.,” Columbus, Ohio or equivalents from Elgen Manufacturing company,or Ductmate Canada. * Addendum #5

.8 Elbows up to and including 254 mm dia. to be 20 ga die-stamped smooth, two-piece. Elbows 280 mm and greater diameter to be five-piece.

.9 Field joints to be slip joint type secured with sheet metal screws and sealed asfurther specified. * Addendum #5

.10 Supports: Stainless steel angles, channels, rods and related supporting materials.

.11 Fasteners: Use S.S. rivets, screws and bolts throughout.

.12 Reinforcement: Provide stainless steel reinforcement shapes and plates whererequired.

.13 Tie Rods: Use stainless steel, 1/4 inch minimum diameter fasteners for ductwork36 inch or less in length; use 3/8 inch minimum diameter for lengths longer than36 in.

.14 Unless specified otherwise, adhere to the following gauge sizes:

U.S. Standard Gauge for Low, Medium and High Pressure Duct

Duct Diameter (mm) Low Medium High

up to 305 26 24 22305 to 760 24 22 20760 to 1370 22 20 181370 to 2130 20 18 162130 and up 18 16 14

2.9 THERMOSET FRP DUCTS AND FITTINGS

GENERAL:Fiberglass Reinforced Plastic (FRP) – Rectangular and Round: Factory fabricateddouble-wall insulated duct and fittings in accordance with CAN/CGSB 41.22 andthe SMACNA manual entitled "THERMOSET FRP DUCT CONSTRUCTIONMANUAL", pigment coloured as selected from the manufacturer’s standardcolours, with thixotropic resin paste sealed and fibreglass cloth and resin

Page 12: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-10DUCTWORK AND ACCESSORIES (ADD#5)

overwrapped bell and spigot joints for round ducts, air-tight gasketed flanged jointswith type 316 stainless steel bolts, lock washers and nuts for rectangular ducts andtype 316 stainless steel support hardware outdoors or non-metallic support systemsindoors.

Acceptable manufacturers are:a. Monoxivent Inc. (Hybrid-CF interior and UnderDuct exterior)b. Precisioneering Ltd.c. Industrial Plastic Fabricators Ltd. *Addendum #2

.1 Resin:

.1 Thermoset FRP Resin: Manufacture duct with Monoxivent 824 modifiedacrylic resin that complies with UL 181, Class 1, maximum flame-spreadindex of 25 and maximum smoke-developed index of 50 when tested by anNRTL according to ASTM E 84.

.2 The use of liners to achieve the indicated smoke and flame spreaddevelopment will not be accepted.

.2 Insulation:

.1 Double-Wall Insulated Duct: Inner and outer duct complying withrequirements for “Round Duct” description. Square air ducts shall alsobe double-walled c/w internal thermal insulation. Closed CellPolyurethane Foam insulation with maximum thermal conductivity of0.14 BTU x in. / h x sq. ft. x deg. F at 75 deg. F mean temperature:

R7 1” THK

R10 1” THK *Addendum #2

.3 Reinforcement:

.1 Surfacing Veil shall be “C” glass veil with a silane finish and a styrenesoluble binder.

.2 Chopped Strand Mat shall be Type E Glass with a minimum 1-1/2 ounce persquare foot with silane finish and styrene soluble binder.

.3 Woven Roving shall be Type E glass minimum 24 ounces per square yard.

.4 Continuous Roving for a filament binding shall be Type E glass with a silanefinish.

.4 Construction:

Page 13: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-11DUCTWORK AND ACCESSORIES (ADD#5)

.1 Fabricate joints, seams, transitions, reinforcement, elbows, branchconnections, and access doors and panels, according to SMACNA’s“Thermoset FRP Duct Construction Manual” Chapter 7, “Requirements”.

.2 FRP ductwork shall be design safety factor of 10 to 1 for pressure and 5 to 1for vacuum

.3 Out of roundness of duct shall be limited to ±1/4”

.4 Round Duct: Filament wound minimum Thickness:

2” to 20” diameter 0.125” THK

22” to 36” diameter 0.1875” THK

38” to 96” diameter 0.25” THK

.5 FRP duct shall be factory assembled to the greatest possible extent, witha minimum number of field joints.

.6 Maximum allowable deflection for any size ductwork shall be 12 mm(0.47”) between supports and for any size of duct under worst caseoperating conditions.

.7 Length of flanged duct sections shall not vary more than 12 mm (0.47”)at 21 degrees C. *Addendum #2

.8 Un-flanged duct sections shall be square on the ends in relation to thecenter axis within 3 mm (0.118”) up to and including 600 mm (24”)diameter and within 4.76 mm (0.187”) for all diameters greater than 600mm. *Addendum #5

.9 Duct construction (“Hybrid CF” Duct) shall include Vinylester Interior– Fire Retardant Corrosion Liner; Modified Acrylic Structural Layer –Class 1 Rated for Low Smoke & Low Flame; Modified Acrylic Exterior– Class 1 Rated for Low Smoke & Low Flame; Exterior Coating –Factory Applied Corrosion Resistant Gel Coat. *Addendum #2

.5 Lamination:

.1 All ductwork shall have any interior and exterior “C” veil liner 10 mil thick.

.2 Structural layer shall be fabricated toward Winding or Hand lay-up Standard.

.3 Exterior:

.1 Below ground to have a “C” veil layer.

Page 14: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-12DUCTWORK AND ACCESSORIES (ADD#5)

.2 Above ground to have a “C” veil layer and White paraffinated gelcoat with UV inhibitors

.6 Design Pressure Ratings:

.1 All FRP duct, fittings, and flanges shall have a design internal pressure ratingof 25 psi as specified in ASTM D 2310.

.7 Fittings:

.1 All fittings shall be made out of the same resin and having the same strengthas the FRP ductwork

.2 The internal diameter of all fittings shall be equal to the adjacent duct

.3 The tolerance on angles of all fittings shall be – 1o up to and including 24”diameter and – ‰o for 30” diameter and above.

.4 Elbows Centerline radius shall be 1-1/2 times the diameter. Elbows 45degrees or less shall be at least one (1) miter/two (2) gore. Elbowsgreater than 45 degrees shall be at least two (2) miter/three (3) gore.*Addendum #2

.8 Elbows:

.1 Elbows Centerline radius shall be 1-1/2 times the width or diameter.

.2 Fabricate 45-degree elbows with a minimum of two (2) segments and 90-degree round elbows with a minimum of three (3) segments.

.3 Square elbows shall be equipped with either single or double thicknessturning vanes with a radius of 4.5”, and a separation of 3.25”, pre-assembledon runners constructed per SMACNA Accepted Industry Practice forIndustrial Duct Design. Vanes shall be securely attached to the runners.

.9 Drains:

.1 When required, formed drain pockets with a minimum of NPS 1” threadedpipe connections

.10 Joints:

.1 Field Joints to be Butt & Wrap type for wet lay-up method.

.2 Field joint kits sent out in bulk form with an extra 20% material for waste

.3 Resin to be same as duct

Page 15: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-13DUCTWORK AND ACCESSORIES (ADD#5)

.11 Flanges:

.1 Provide flanged connections as required to air ducts, flexible connectors,expansion joints, vessels, demisters, fans, silencers and other locations asshown. All FRP duct connections shall be flanged in this contract.

.2 Flanges shall be hand lay-up construction. Dimensions shall be inaccordance with PS 15-69 – Table 2 and the duct dimension schedule.

.3 Flange faces shall be perpendicular to the axis of the duct within 0.5degree.

.4 Flange faces shall be flat to within 0.0313" (0.8mm) up to and including18" (457mm) diameter and within 0.0625" (1.6mm) for 20" (508mm)diameter and larger.

.5 Gaskets shall be EPDM/Neoprene, full face and minimum 0.125"(3.2mm) thickness.

.6 Bolts, nuts and washers shall be Type 316 stainless steel.*Addendum #2

.12 Double-Wall Round and Square Insulated Duct:

.1 Inner duct-complying with requirements for “Single Wall FRP Duct”description.

.2 Outer Duct: Thermoset FRP Resin: Manufacture entire outer duct withapproved resin that complies with ASTM E84, Class 1, maximum flame-spread index of 25 and maximum smoke-developed index of 50. Outerduct shall comply with all other requirements for “Single Wall FRPDuct” description other than interior corrosion liner.

.3 Insulation: (1) Closed Cell Polyurethane Foam insulation with maximumthermal conductivity of 0.14 BTU x in. / h x sq. ft. x deg F at 75 deg. Fmean temperature (R-Value of 10 – 1” THICKNESS). *Addendum #2

2.10 MECHANICAL LINER AND FASTENERS:

.1 Liners: Internal duct liners shall be 1 inch thick fiberglass Type I or II per ASTM1071 and have a thermal conductivity (k-value) of 0.26 at 75 deg. F. Liners shallcomply with NFPA 90A and 90B and with NAIMA AH124 and have a maximumflame-spread index of 25 and smoke-developed index of 50 when testedaccording to ASTM E84. Liners shall be treated with an EPA approved biocideto resist bacterial and fungal growth. All surfaces exposed to the air stream shallbe coated to prevent erosion of glass fibers.

Page 16: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-14DUCTWORK AND ACCESSORIES (ADD#5)

.2 Mechanical Fasteners: stainless steel, suitable for adhesive, mechanical orwelding attachment (self-stick adhesive fasteners are not permitted). Providefasteners that will not damage the liner when applied as recommended by themanufacturer, that do not cause leakage within the duct and that will sustain a 50-pound tensile dead load perpendicular to duct wall.

.3 Liner Adhesive: Non-oxidizing, vinyl acrylic, water-based adhesive used to bondinsulation to sheet metal surfaces. Operational temperature range -20 to +160F;curing time 24 hours. Manufactured by United McGill, type Uni-Tack. Complywith NFPA 90A and 90B and with ASTM C916

2.11 SHEET METAL PLENUMS:

.1 Fabricate from minimum 18-gauge metal of same material as ductwork.

.2 Brace with frame of same material for rigidity.

.3 Line with sound attenuation material where indicated.

.4 Air duct shall be connected to the plenum with a 45 degrees eccentric transitionpiece. Transition piece shall be continuation of the duct and be of similar shapeas the duct (either round or rectangular).

2.12 FRP PLENUMS

.1 Plenums shall be factory built using thickness and standards as per SMANCAFRP Manual. Insulated FRP plenums shall be pre-insulated double wall type withstandard 25mm (1”) insulation thickness and k factory of 0.14 and an R value of8.

.2 Air duct shall be connected to the plenum with a 45 degrees eccentric transitionpiece. Transition piece shall be continuation of the duct and be of similar shapeas the duct (either round or rectangular).

2.13 LOUVERS

.1 General:

.1 Refer to drawings for intake and exhaust louver locations and size.

.2 Finish: Full strength fluoropolymer coating (Kynar 500 PVDF resin), colourto be selected by Owner from manufacturers standard colour chart.

.3 Submit comprehensive louver performance data including airflow resistance,water penetration, Sound Transmission Class (STC), Outdoor IndoorTransmission Class (OITC) and free area for approval.

.2 Stationary Louvers

Page 17: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-15DUCTWORK AND ACCESSORIES (ADD#5)

.1 Furnish and install stationary drainable louvers of the size and shapeindicated on the drawings. The louvers shall be constructed entirely ofwelded extruded aluminium (2.06 mm wall thickness) assembly; alloy 6063-T5 extruded 150 mm aluminium blades (2.06 mm wall thickness) positionedat a 35” angle; including integral flange for mounting on wall.

.2 Welded Assembly: Join stationary blade, head, sill and jamb frames withfillet welds concealed from view. Louver blades shall be joined to each jambframe with fillet welds produced with the Pulsed Gas Metal Arc Welding(GMAW/Mig) process.

.3 High performance frame system with drainable head to collect and removewater; drain gutter in each blade.

.4 Louver performance shall be based on test and procedures in accordance withAMCA publication 511 and comply with the requirements of the AMCACertified Rating Program

.5 Louvers shall be designed to withstand a 25-psf-wind load.

.6 Each louver shall be fitted with a removable 13mm mesh bird screen. Birdscreen shall be expanded aluminium construction and suitable for interiormounting.

.7 Minimum free area: 57% based on 48 in. wide x 48 in. high.

.8 Louvers shall be supplied with continuous blade section to give theappearance of invisible mullions.

.9 Acceptable manufacturer: Airolite K6096, Arrow United EA605, RuskinELF6375, equivalent from E.H.Price.

2.14 BLANK OFF PANELS

.1 Provide blank off panels with 50mm thick polystyrene attenuation/insulation asindicated on drawings.

.2 Panels shall be fabricated 0.063” aluminium panel, finished with two coats ofpaint to match wall colour.

.3 Panels installed in Wet Wells and Pump Rooms shall be coated with 4 mil PVC.Coat all end cuts with PVC coating to maintain a fully coated surface. All bolts,nuts and screws shall be cadmium plated and PVC painted after installation.

2.15 STATIONARY BLADE MITERED CORNER PENTHOUSE.

.1 Fabrication:

Page 18: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-16DUCTWORK AND ACCESSORIES (ADD#5)

.1 All Welded Construction.

.2 Roof: With aluminum louvers: Aluminum: 063 inch (1.6 mm)

.3 Frame Structural Support: With Aluminum Louvers: ExtrudedAluminum, 1‰ x 4 x 1‰ inches (38 x 102 x 38mm). Material: Extrudedaluminum, Alloy 6063-T6.

.4 Blades: Style: Z-blades, 102 mm depth, at 39 deg. Wall Thickness:0.081 inch (2.1 mm), nominal. Material: Extruded aluminum, Alloy6063-T6.

.5 Corner: Mitered, with extruded aluminum louvers 0.080 (2) the corners arewelded on the rear of blade.

.6 Inside curb (Throat) Size: 1050 mm wide by 1050 mm long.

.7 Height: 457 mm.

.8 Integral perimeter caulking stop.

.9 50 mm insulated roof and roof curb.

.2 Performance Data:

.1 Refer to drawings

.2 Free Area: min 49.1%

.3 Pressure drop: less than 63 Pa.

.3 Design Loading: 0.96 kPa.

.4 Design Windload: Per Code. At 145 kph.

.5 Design Windload: Incorporate structural supports required to withstand wind loadof 11.07 pounds per square foot (0.53 kPa).

.6 Louvers shall be factory engineered to withstand the specified seismic loads.

.1 Minimum design loads shall be calculated to comply with ASCE – 7, or localrequirements of Authority Having Jurisdiction (AHJ).

.7 ACCESSORIES

.1 Hinged Frame: Continuous piano hinge attached to channel sub-frame.

.2 Security Bars:

Page 19: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-17DUCTWORK AND ACCESSORIES (ADD#5)

.1 Location: Front.

.2 Construction: Aluminum, 3/4 inch x 1/2 inch (19 mm x 13 mm),welded to louver.

.3 Bird Screen: Aluminum: Aluminum, 5/8 inches by 0.040 inch (16 mm by 1mm), expanded and flattened. Frame: Removable. Re-wireable.

.4 Extended Sills: Formed aluminum, Alloy 3003. Minimum nominalthickness 0.081 inch (2.1 mm).

.5 Visible Mullions: Manufacturer’s standard horizontal or vertical visiblemullions for architectural accent as indicated on drawings.

.6 FINISHES

.1 Anodized Finishes:

.1 Class I Clear Anodized. Comply with AluminumAssociation AA-C21A41. Clear anodized finish 215-R1.Apply finish following chemical etching and pretreatment.Minimum Thickness: 0.7 mils (0.018 mm), 60 minuteanodizing process.

.8 Manufacturers:

.1 Ruskin, Model: PHM.

.2 EH Price, Model MCZE 439.

.3 Greenheck.

2.16 ROOF CURB

.1 Designation: Strachan SPS - for louvered penthouse (pitched roof); Ellis SPS andSouthport SPS – for Wet Well air duct roof penetrations (flat roof).

.2 All welded aluminium construction with welded corners and with seams joined bycontinuous water and air tight welds, internally reinforced with angles; chemicallytreated factory installed lap-joint wooden nailer, 51 mm flashing flange, 25 mminternal rigid insulation, curb seal, liner (double shell), electrostatically appliedpowder, colour equal to penthouse or duct colour.

.3 For roof penetrations of air duct: fully mitered 3" cant and step to match deckinsulation thickness.

.4 For pitched roof – confirm roof “rise-run” at the site before ordering.

.5 Heights: Strachan SPS - 300 mm; Ellis SPS and Southport SPS – 200 mm.

Page 20: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-18DUCTWORK AND ACCESSORIES (ADD#5)

.6 Manufacturers: Greenheck Models GPIP (pitched roof) and GPS (flat roof),Thybar Corp., or approved equivalent.

2.17 MOTORIZED DAMPERS

.1 Dampers to be automatic (motorized) as shown on the Drawings and installed inlouvre frames, wall sleeves or transition boxes as required.

.2 All internal duct dampers to be of aluminum construction. Blades to be parallelaction with blade linkage. Frames and blades to be a minimum 2.05mm (0.081”)6063-T6/T52extruded aluminium. Blades to be a single unit foil design, 100mm(4”) wide with the pin-lock an integral section within the blade core. Overlapblades and seal with extruded silicon fitted into dovetail shaped slots in bothframes and blades. Frames to be 6063-T6/T52 extruded aluminium channel withreinforcing bosses and groove inserts for silicon seals. Linkage hardware is to beof non-corrosive reinforced material or cadmium plated steel.

.3 Acceptable Manufacturer: Arrow United Industries Model OBDAF-207, Tamcoseries 1000 from T.A. Morrison Co., or equivalent from Ruskin.

.4 Dampers installed behind exterior louvres, building walls or roof to be ofinsulated construction. Damper blades shall be 150mm (6”) wide, double walled,6063-T6/T52 extruded aluminium 2.05mm (0.081”) nominal wall thickness.Blades shall be injected with two part polyurethane (CFC) free foam and de-bridged for thermal isolation. The insulation shall have a minimum R-value of1.3. Frame shall be 125mm (5”) wide, 6063T6/T52 extruded aluminium channel,2.05mm (0.081”) nominal, thermally broken. Provide extruded silicone rubberblade edge seal that fits into a ribbed groove insert in blades with extrudedpolycarbonate seal at jambs.

.5 Acceptable Manufacturer: Arrow United Industries Model AFDTI-25LT, TamcoSeries 9000 by T.A. Morrison Co., CDTI-50BF by Ruskin

.6 Dampers to be duct-mounted, front-mount or rear-mount according to the airflowand as per the drawings.

.7 Accessories: electrical actuator.

2.18 FRP MOTORIZED DAMPERS

.1 Furnish and install, at locations shown on plans or in accordance withschedules.

.2 Fiberglass airfoil design multi-blade control dampers. Dampers shall be ofpultruded construction and comply with ASTM D4385-84A, ASTM E-84, andASME/ANSI RTP1-1989.

Page 21: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-19DUCTWORK AND ACCESSORIES (ADD#5)

.3 Material used in construction shall be a flame retardant vinyl ester basedsubstance with a Class I flame spread rate of 25 or less. All material in airstreammust meet or exceed required contamination concentration. Bearing designshall be based on system pressure and shall be of a Teflon based material.

.4 All exposed glass shall be coated with resin compatible with that leakage, usedin the pultrusion process and covered with surfacing veil. No exposed cut edgesare acceptable.

.5 Damper blades shall be minimum 1/4" (6) thick of a hollow airfoil shape andcontain pultruded slot for insertion of optional blade seal.

.6 Adhesive type seals are not acceptable.

.7 Frame shall be 8 inch deep X 23/16" inch flanged style, minimum 1/4" thick (203 x56 x 6).

.8 The fiberglass axles shall be minimum 3/4" (19) diameter constructed of a vinylester based material, combined with continuous strand roving, and complete withsurfacing veil.

.9 Damper design shall withstand minimum 14” W.G. and 4000 FPM velocitybased on minimum 40” (1016) blade length.

.10 Submittal information shall include published performance based on AMCAStandard 500 testing illustrating damper pressure drop, and static pressure designcharacteristics range of damper sizes. Data from one size sample acceptable.

.11 Accessories: electrical actuator.

.12 Manufacturer:

.1 Swartwout Model 1108AF,

.2 M.K.Plastics Model K-PD or

.3 Approved equivalent.

2.19 DAMPER ELECTRICAL MOTOR ACTUATOR

.1 The damper actuator shall be proportional or On-Off electric type with built-in internal mechanical spring return mechanism and position indicators.Actuator shall be suitable for either direct-coupled over the shaftconnection or with connecting linkage, closed on power-fail conditionand shall be designed so it can be used for either clockwise orcounterclockwise operation. Actuator is to be installed out of air streamand be fail-closed.

Page 22: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-20DUCTWORK AND ACCESSORIES (ADD#5)

.2 The actuator torque rating shall be at least 125% of the torque required toopen or close damper under maximum design air flow conditions.Provide the data in the submission.

.3 The actuator shall be suitable for operation from 1ph, 120 VAC, 60 Hzsource (only one power source to be required for one damper), CSA orULC certified, intended for indoor or outdoor installation, and rated forarea classification. All shall be a NEMA 4 Type for general applicationareas; in Wet Well rooms the enclosure shall be explosion proof typesuitable for the Class 1 Zone 1 Group D application.

.4 The actuator motor shall be equipped with built-in internal overload andthermal protection and shall have open/close position indication auxiliaryadjustable limit switch: two SPDT, 120 VAC, 3A contacts. The actuatorshall be provided with terminal blocks or minimum 1 m long markedelectrical wires for connection purposes. Refer to Control Sequence forspecific damper control function and Division 13 for wiring.

.5 Provide all accessories as required including shaft, arm, joints, push-rods,clips, mounting brackets and miscellaneous hardware for complete unit.Mount the electric motor on the damper frame and provide all brackets,reinforcing, etc., necessary.

.6 Actuators shall be cUL approved and have a 5 years warranty.

.7 Acceptable product:

.1 Belimo.

.2 Honeywell.

.3 Siemens Bldg. Management Systems.

.4 RCS (for dampers requiring high torque).

2.20 BACKDRAFT DAMPERS

.1 General:

.1 Dampers to be located as shown on the drawings, and installed in louverframes or wall sleeves as required.

.2 Testing and ratings to be in accordance with AMCA Standard 500-D.

.3 Damper Manufacturer’s printed application and performance data includingpressure, velocity and temperature limitations shall be submitted for approval

Page 23: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-21DUCTWORK AND ACCESSORIES (ADD#5)

showing damper suitable for pressures to 10 in. wg (2491 Pa), velocities to3500 fpm (18 m/s) and temperatures to 180°F (82 C).

.4 Back draft dampers shall be gravity operated multi leaf style.

.5 Designation: air duct systems with mechanical exhaust fans.

.2 Metal Construction:

.1 Dampers shall consist of: 18 ga. (1.3 mm) stainless steel frame with 89 mm(3-1/2”) depth.

.2 Blades from 0.6 mm (0.025”) roll-formed aluminum; 4.8 mm (3/16”) dia.plated steel, full length, axles turning in acetal bearings.

.3 Damper shall be equipped with extruded vinyl blade seals; and internal 1.6mm (0.064”) aluminum tie bar (onblade) with spring assist.

.4 Paint Finish: Hi Pro Polyester.

.5 All Gaskets: EPDM.

.6 Manufacturer: Greenheck model WD-300 and WD-100, Carnes, Ruskin, orapproved equivalent.

.3 FRP Construction:

.1 All FRP fabrication shall meet or exceed quality requirements of PS15-69and ASME/ANSI RTP-1; tests and procedures performed in accordance withAMCA Publication 511 and the test method per AMCA Standard 500-89;shall bear the AMCA Seal.

.2 For fiberglass v-groove blade design backdraft dampers, dampers shall be ofthe pultruded construction and comply with ASTM D4385-84. Material usedin construction shall be a flame retardant vinyl ester based resin with a ClassI flame spread rate of 25 or less. All materials in the airstream must meet orexceed required contamination concentrations.

.3 Frame and Blades: Vinyl Ester FRP.

.4 Axle: Vinyl Ester FRP or 316 SS.

.5 Bearing design shall be based on system pressure and shall be of a Teflonbased material with graphite impregnation. All exposed glass shall be coatedwith resin compatible to that used in the pultrusion process. No exposed ornon-coated edges are acceptable.

.6 Internal Hardware: 316 SS.

Page 24: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-22DUCTWORK AND ACCESSORIES (ADD#5)

.7 Max Operating Temperature: 90°C (200°F).

.8 Max System Pressure: 7.5 kPa (30” WC).

.9 Resin System: Fire Retardant Vinyl Ester with MEKP Cure System.

.10 Connections: Flanges shall be integral part of the damper and be to NBS PS1569 Table 2 for Standard Ductwork.

.11 External Coating: Gel Cost with UV Inhibitors; colour shall be as the ductcolour.

.12 Gasket: EPDM.

.13 Face to Face: minimum 305 mm (12").

.14 Indicator of the blade position shall be provided.

.15 Damper blades shall be a minimum of 1/8" (3) thick single skin design.

.16 All surfaces of the blade shall utilize surfacing veils. Open contact or handlayup blades are not acceptable. Damper frame shall be 8" deep x 23/16"(203 x 56) flanged style minimum 1/4" (6) thick.

.17 Fiberglass axles shall be minimum 3/4" (19) diameter pultruded constructionof a vinyl ester based resin combined with continuous strand roving andcomplete with surfacing veil.

.18 Damper linkage shall be FRP internal face linkage.

.19 Standard damper construction shall withstand 10" SP and 2,000 FPM basedon a 24" (610) blade length. Submittal information shall include publishedperformance data based on AMCA Standard 500 testing illustratingmaximum pressure data, flow ratings, and leakage characteristics for a fullrange of damper sizes.

.20 Weighted backdraft dampers shall be designed to relieve at pressure of 25 Paminimum.

.21 Actuator:

.1 Back draft damper: counterweight arm of 316 stainless steelthreaded rod with adjustable counterweight nuts.

.2 Damper: locking quadrant hand level through 500 mm dia.,aluminium worm gear for larger than 500 mm dia.; chain wheeloperator for dampers located above 1700 mm above finish floor.

Page 25: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-23DUCTWORK AND ACCESSORIES (ADD#5)

.22 Manufacturer:

.1 M.K. Plastics (horizontal, square & rectangular).

.2 Swartwount, Model 426

.3 Belco Manufacturing Co. Models 301/302 (vertical, round) &Model 401(horizontal, round).

.4 Or approved equivalent.

2.21 SINGLE- AND MULTI-BLADED BALANCING DAMPERS

.1 Metal Construction:

.1 Factory manufactured of material compatible with duct.

.2 Balancing dampers (BD) shall be installed in each fan inlet or outlet (subjectof available room), before any air distribution point and be equal in size tothe duct size. BD shall be provided regardless of if a balancing damper isshown in drawings or not. Confirm before duct supply.

.3 Damper style, either single-bladed or multi-bladed, shall be based on the ductsize.

.4 Opposed blade (multi-bladed style): configuration, metal thickness andconstruction to recommendations of SMACNA.

.5 Maximum blade height (multi-bladed style): 100 mm.

.6 Bearings: Self-lubricating nylon.

.7 Linkage: Shaft extension, shaft-off bracket with hand-locking quadrant (allstyles) and locking operator.

.8 Channel frame and damper blade of same material as adjacent duct, completewith angle stop.

.9 For isolation applications on air handling units discharge ductwork, providevinyl blade seals.

.10 Manufacturer and Model: Nailor Industries Inc.: Model 1090 (round up to610 mm dia.), 1820CR (round up to 1150 mm dia.), Model 1870(rectangular); or approved equal.

.2 FRP Construction:

.1 Material of Construction:

.1 Body, damper plate and shaft shall be made of FRP; furnished withlocking quadrant damper allowing for permanent position set;fasteners shall be made of stainless steel.

.2 Damper shall allow for less than 5% airflow restriction; 95% airsealing; 90” damperplate operation; can be installed eithervertically or horizontally.

Page 26: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-24DUCTWORK AND ACCESSORIES (ADD#5)

.3 Damper shall have bell end sockets and have minimum socketdepth of 2 inches or more.

.4 Damper shall be applicable up to 60”C service.

.5 UV treated..2 Fabricate in accordance to SMACNA Standard.

.3 Dampers shall be of same material and gauge as duct.

.4 Provide a method of locking the dampers in place once the system has beenbalanced.

.5 Manufacturer: Belco Model 202, Swartwout, MK Plastics Model K-RD-501or approved equivalent.

2.22 FIRE DAMPERS

.1 Fire dampers: To bear label of ULC, meet requirements of Ontario BuildingCode (OBC) and ANSI/NFPA (Fire) 90A-02, 92A, 92B & 101, UL 555 & 555S.

.2 Mild steel, factory fabricated for fire rating requirement to maintain integrity offire wall and/or fire separation.

.3 Top hinged, offset, for round or square ductwork, interlocking type or roll doortype, sized to maintain full duct cross section.

.4 Fusible link actuated, having negator-spring-closing operator for multi-leaf typeor roll door type in horizontal position with vertical air flow. Fusible linkconforming to ULC-S505-1974. Blades to be out of air stream.

.5 40 x 40 x 3 mm retaining angle iron frame, on full perimeter of fire damper, onboth sides of fire separation being pierced.

.6 Furnish fire dampers and frames constructed of same material as duct in whichthey are installed.

.7 Furnish “Type B” fire dampers for rectangular or square ductwork, “Type C” firedampers for square ductwork, and “Type CR” fire dampers for round ductwork.Damper shall be located in the mid of sleeve, in walls.

.8 Accessories: Factory fabricated and certified wall/duct sleeve, retaining angels,duct access door, and access door in concealing construction as required stainlesssteel hardware.

.9 Acceptable Manufacturer: Greenheck Model FD-150 Type B, CR and C, Ruskin(Model IBD or FDR25SS), or Nailer Industries.

Page 27: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-25DUCTWORK AND ACCESSORIES (ADD#5)

2.23 SUPPLY GRILLE

.1 Furnish and install air supply grilles of the sizes and mounting types indicated onthe plans and outlet schedule.

.2 The grille shall have individually adjustable blades on 3/4” centers. Allconstruction shall be of #316 stainless steel with a 1-1/4” wide border on all sideswith mitered corners. The front set of blades shall run parallel to the longdimension of the grille. The grille shall be available with countersunk screw holesfor a clean, unobtrusive appearance.

.3 The finish shall be Satin Polish (SP).

.4 The integral volume control damper shall be of the opposed blade type and shallbe constructed of cold rolled stainless steel. The damper shall be operable fromthe register face. The damper shall be 316 S.S.

.5 The manufacturer shall provide published performance data tested in accordancewith ANSI/ASHRAE Standard 70-1991 at isothermal conditions.

.6 Acceptable Manufacturer:

.1 Tuttle & Bailey, Model T54 DSS (all 316 S.S. construction)

.2 EH Price,

.3 Titus,

.4 Ruskin.

2.24 RETURN GRILLE

.1 Furnish and install air return grilles of the sizes and mounting types indicated onthe plans and outlet schedule.

.2 The grille shall have provide 45 degrees fixed blades on 3/4” centers. Allconstruction shall be of #316 stainless steel with a 1-1/4” wide border on all sideswith mitered corners. The front set of blades shall run parallel to the longdimension of the grille. The grille shall be available with countersunk screw holesfor a clean, unobtrusive appearance.

.3 The finish shall be Satin Polish (SP).

.4 The integral volume control damper shall be of the opposed blade type and shallbe constructed of cold rolled stainless steel. The damper shall be operable fromthe register face. The damper shall be 316 S.S.

.5 The manufacturer shall provide published performance data tested in accordancewith ANSI/ASHRAE Standard 70-1991 at isothermal conditions.

Page 28: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-26DUCTWORK AND ACCESSORIES (ADD#5)

.6 Acceptable Manufacturer:

.1 Tuttle & Bailey, Model T70DSS (all 316 S.S. construction)

.2 EH Price,

.3 Titus,

.4 Ruskin.

2.25 DOOR TRANSFER LOUVRE

.1 Material: 18 gauge 316 stainless steel frame and louvre blades.

.2 Frame: Mitered and welded corners; screws fastened through prepared frameinto louvre core leaving corridor side of frame free of fasteners.

.3 Construction:

.1 Frame: Mitered and welded corners, with countersunk mountingholes.

.2 Door: For 1-3/4” thick door.

.3 Fasteners: #8 x 3/4” Phillips flathead screws all stainless steel.

.4 Finish: #4.

.5 Quantities, sizes and shapes are shown on the Drawings.

.4 Acceptable Product:

.1 AJ MFG, Model SSDG (316 S.S.);

.2 Air Louvres-Activar Construction Products Group, Inc.,700TL (316 S.S.);

.3 Greenheck Fan Corporation. * Addendum #5

2.26 ROUND GRILLE

.1 Wall mounted type, all heavy gauge aluminium construction, mill finish, S.S.hardware.

.2 Acceptable product:

.1 Price, Model RPG (SMP Frame), Tuttle & Bailey, Greenheck, or approvedequivalent.

Page 29: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-27DUCTWORK AND ACCESSORIES (ADD#5)

2.27 INSTRUMENT TEST PORTS

.1 Duro-Dyne of Canada #1P1 or 1P2 (to suit the thickness of the insulation) orapproved equal, leak-proof instrument test ports for round or rectangular ducts asrequired, each complete with a neoprene expansion plug.

2.28 DUCT INSPECTION DOORS

.1 General:

.1 Insulated, gasketed, and at least 375 mm by 375 mm when duct dimensionsare large enough.

.2 On ductwork where largest side dimension is less than 400 mm, furnishinspection doors at least 200 mm by 200 mm.

.3 Complete with necessary hardware.

.4 Fabricated of same material as ductwork.

.5 Quantity: one door for each air leg.

.2 Round Spin in Type Access Doors:

.1 Size: 450 mm and 600 mm diameter will be acceptable in lieu of comparablysized square or rectangular access doors specified herein.

.2 Complete with insulation, spin in frame, inner door, attachment cable,gaskets, three latches, and pull ring.

.3 Casing and Plenum Access Doors:

.1 Size: 1425 mm high by 600 mm wide minimum where possible.

.2 Complete with hardware, hinges, seals, and latch handles.

.4 Manufacturers:

.1 Same as air dust manufacturer.

2.29 DUCTWORK HANGERS AND SUPPORTS

.1 General:

.1 Strap hangers: of same material as duct but next sheet metal thicknessheavier than duct. Maximum size duct supported by strap hanger: 500 mm.

.2 Attachments, hangers, and supports for ductwork shall be in accordance withSMACNA Manual referenced for type of duct system being installed.

Page 30: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-28DUCTWORK AND ACCESSORIES (ADD#5)

.3 Duct hanging system shall be composed of three elements; upper attachmentto building, hanger itself, and lower attachment to duct.

.4 Wire hangers are not acceptable.

.5 Hangers: Stainless steel angle to following table:

Duct Size

(mm)

Angle Size

(mm)

Rod Size

(mm)

Spacing

(mm)

Up to 750 25 x 25 x 3 6 3000

751 to 1050 40 x 40 x 3 6 3000

1051 to 1500 40 x 40 x 3 10 3000

1501 to 2100 50 x 50 x 3 10 2500

2101 to 2400 50 x 50 x 5 10 2500

2401 & over 50 x 50 x 6 15 2500

.2 Construction Materials: Supporting devices including, but not limited to, anglesused for support and bracing, base plates, rods, hangers, straps, screws, bolts shallbe as follows:

.1 Indoors and Outdoors: Stainless steel, Grade 316L.

.2 Aluminum Ductwork Indoors and Outdoors: Carbon steel,hot-dipped galvanized after fabrication.

.3 Stainless Steel Ductwork Indoor and Outdoors: Stainless steel,same ASTM Grade as ductwork.

.3 Building Attachments:

.1 Concrete inserts, powder-actuated fasteners, or structural steel fastenersappropriate for building materials.

.2 Do not use powder-actuated concrete fasteners for lightweight aggregateconcrete or for slabs less than 102 mm thick.

.3 Upper Attachment (Concrete):

.1 Drive pin fastener and expansion nail anchor may be used for ductsup to 450 mm maximum dimension.

.2 Threaded stud fastener may be used for ducts up to 900 mmmaximum dimension.

Page 31: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-29DUCTWORK AND ACCESSORIES (ADD#5)

.3 Concrete attachments shall be made of stainless steel.

.4 Acceptable Product: Myatt, Grinnell, Hunt.

.4 For steel joist: manufactured joist clamp steel plate washer.

.1 Acceptable Product: Myatt, Grinnell, Hunt.

.5 For steel beams: manufactured beam clamps:

.1 Acceptable Product: Myatt, Grinnell, Hunt.

.4 Duct Fasteners: Sheet metal screws, blind rivets, or self-tapping metal screws;compatible with duct materials and conforming to requirements of ParagraphDUCTWORK FASTENERS.

.5 Trapeze and Riser Supports: Stainless steel shapes conforming to ASTM A276 /A276M.

2.30 DUCT SEALING MATERIALS

.1 General: The term sealant used here is not limited to materials of adhesive ormastic nature, but also includes tapes and combinations of open weave fabricstrips and mastics.

.2 Adhesives, Cements, Sealant, and Installation Accessories: As recommended byduct manufacturer for application.

.3 Solvent-Based Sealants:

.1 Ultraviolet light resistant.

.2 Mildew resistant.

.3 Flashpoint: Greater than 21 degrees C, SETA CC.

.4 Manufacturers and Products:

.1 Hardcast, Inc.; Versagrip 102.

.2 Rectorseal; AT-33.]

.4 Water-Based Sealants:

.1 Listed by manufacturer as nonflammable in wet and dry state.

.2 Manufacturer and Product: Rectorseal; Airlok 181.

Page 32: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-30DUCTWORK AND ACCESSORIES (ADD#5)

.5 Tape: Polycoated, flame retardant, 50 mm wide.

.1 Thickness and elongation: 0.3 mm and 12%.

.2 Tensile strength: 535.7 kg/m width.

.3 Acceptable product:

.1 Shurtap PC-21F.

.2 MACtac-PAF.

.3 Or approved equivalent

2.31 INSULATION

.1 Refer to Section 15080 – Mechanical Insulation.

.2 Provide insulation jacket for internal and external ducts as specified.

PART 3 EXECUTION

3.1 MATERIALS

.1 Safely deliver materials to the site.

.2 Handle materials at all times with care to avoid damage.

.3 Load, unload, and move materials into place by means of hoists, ropes orskidways in such a manner as to avoid shock.

.4 Do not drop or roll materials against one another.

.5 Properly store equipment on site.

.6 Protect equipment against weather, damage and theft to the satisfaction of theEngineer.

3.2 DUCTWORKS

.1 Install ducts straight and plumb, following building lines.

.2 Do not install in front of equipment or controls in such manner as to interfere withoperation, servicing or repairs.

.3 Provide ductwork adequately strong and sufficiently rigid to resist all normalshocks, reinforced at all joints where necessary to prevent vibration or movement,and securely fastened in place.

.4 All ducts to be airtight and all joints caulked and made in accordance with thebest standards of the trade.

Page 33: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-31DUCTWORK AND ACCESSORIES (ADD#5)

.5 Where possible make all transitions in ductwork size with an angle not exceeding15 degrees.

.6 Provide elbows and other changes in ductwork direction having centreline radiusat least equal to 1.5 times the duct depths.

.7 FRP ductwork shall be installed in accordance with SMACNA FRP Manual andManufacturer’s instructions.

.8 Penetrations:

.1 Provide duct sleeves or prepared openings for duct mains, duct branches, andducts passing through roofs, walls and ceilings.

.2 Clearances:

.1 For un-insulated ducts, allow 25 mm clearance between duct andsleeve, except at grilles, registers, and diffusers.

.2 For insulated ducts, allow 25 mm clearance between insulation andsleeve, except at grilles, registers, and diffusers.

.3 Roof penetrations via roof curbs: seal the duct and roof curb clearance withflexible material (after installation) to be watertight. Provide galvanizedflashing collar around duct and above roof curb. Refer to standard detaildrawings.

.4 Closure Collars:

.1 Minimum 102 mm wide on each side of walls or floors wheresleeves or prepared openings are installed.

.2 Fit collars snugly around ducts and insulation.

.3 Same gauge and material as duct.

.4 Grind edges of collar smooth to preclude tearing or puncturinginsulation covering or vapor barrier.

.5 Use fasteners with maximum 152 mm centers on collars.

.5 Packing: Mineral fiber in spaces between sleeve or opening and duct or ductinsulation.

Page 34: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-32DUCTWORK AND ACCESSORIES (ADD#5)

.9 Concealment:

.1 Wherever possible in finished and occupied spaces, conceal ductwork fromview by locating in mechanical shafts, hollow wall construction, or abovesuspended ceiling.

.2 Do not encase horizontal runs in solid partitions, except as specificallyshown.

.3 Limit clearance to 25 mm where furring is shown for enclosure orconcealment of ducts, but allow for insulation thickness, if any.

.10 Coordination with Other Trades:

.1 Coordinate duct installation with installation of accessories, dampers, coilframes, equipment, controls, and other associated work of ductwork system.

.2 Ductwork shall be configured, positioned, and installed to permit installationof light fixtures as indicated on Drawings.

.3 Coordinate ductwork layout with suspended ceiling, lighting and sprinklerhead layouts and similar finished work.

.4 Electrical Equipment Spaces: Do not run ductwork through transformervaults and other electrical equipment spaces and enclosures.

3.3 ULTRAVIOLET PROTECTION

.1 All exposed to outdoor pipe, duct, and fittings shall be protected from ultravioletrays by the addition of Cyasborn UV-9 to the wax coat of the product. Protectionapplies to both FRP and Stainless Steel ducting. * Addendum #5

3.4 ULTRAVIOLET PROTECTION

.1 All exposed to outdoor pipe, duct, and fittings shall be protected fromultraviolet rays by the addition of Cyasborn UV-9 to the wax coat of theproduct. * Addendum #5

3.5 DUCTWORK SUPPORT

.1 Material for ductwork support shall match ductwork.

.2 Support all ductwork at intervals not exceeding 2300 mm.

.3 Do not use perforated straps or similar hangers for the support of ductwork orequipment installed under this Section.

Page 35: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-33DUCTWORK AND ACCESSORIES (ADD#5)

.4 Do not use explosives to insert anchors.

.5 Brace vertical ducts to walls with steel straps finished as required.

.6 Support for FRP Ductwork shall be designed by FRP Ductwork manufacturer.Install in accordance with SMACNA FRP manual and Manufacturer’sinstructions.

3.6 LOUVERS

.1 Coordinate exact location and size of louver openings with General Contractorand install level and in line with other building components. Seal perimeter oflouvers and brick vents against building structure by packing any cracks with fireretarding insulation. Seal perimeter with silicone caulking, colour to matchlouver.

.2 Provide insulated blank off panels as required and blank off air tight againstlouver and other duct sections or plenums.

3.7 GRILLES

.1 Provide duct, where needed, to install grilles.

.2 Fasteners: Stainless steel screws and nut, and resilient neoprene washers betweenaluminum and head of bolt or between nut, stainless steel washer and aluminumgrille body.

3.8 DAMPERS

.1 Install where indicated.

.2 Install in accordance with recommendations of SMACNA and Manufacturer’sinstructions.

.3 Seal multiple damper modules with silicon sealant.

.4 Coordinate damper flange drilling patterns with the flange patterns of ducts andair handling equipment, before supply, or drill the holes in the field.

.5 Upon system start up, ensure that dampers operate properly.

.6 Install fire dampers in accordance with the requirements of Ontario BuildingCode (OBC) whether or not shown on the drawings and manufacturer’s writteninstruction.

.7 Provide access panels in ductwork to enable resetting of fire dampers.

Page 36: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-34DUCTWORK AND ACCESSORIES (ADD#5)

.8 Where dual speed fans are specified and a motorized damper is needed to obtaindesign flows, air balancing in both flow scenarios.

.9 Installation of dampers must be in accordance with manufacturer’s currentinstallation guidelines, provided with each damper shipment.

.10 Intermediate or tubular steel structural support is required to resist appliedpressure loads for dampers that consist of two or more sections in both height andwidth.

3.9 EQUIPMENT SUPPORTS

.1 Mount equipment supported above floors on approved welded galvanized structuralsteel framework with diagonal bracing and floor and wall plates.

.2 Unless otherwise shown on the Drawings, construct framework of 75 x 75 x6 mm angles.

.3 Hang suspended equipment on 13 mm minimum diameter stainless steel hangerroads attached to the building structure.

.4 All equipment supports in Wet Well and Dry Well shall be fabricated from316 Stainless Steel. * Addendum #5

3.10 SEALING

.1 Apply sealant to outside of joint to Manufacturer’s recommendations.

.2 Apply in a neat way for ducting system appearance.

.3 Taping of exposed ducts shall not be accepted.

3.11 FLEXIBLE DUCTS

.1 Maximum length of flexible duct shall be 2 m.

3.12 FLEXIBLE CONNECTIONS

.1 Install in following locations:

.1 Inlets and outlets to supply air units and fans.

.2 Inlets and outlets of exhaust and return air fans.

.3 As indicated.

.2 Length of connection: Not less than 100 mm.

.3 Minimum distance between metal parts when system in operation: 75 mm.

Page 37: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-35DUCTWORK AND ACCESSORIES (ADD#5)

.4 Install in accordance with recommendations of SMACNA.

.5 When fan is running:

.1 Ducting on each side of flexible connection to be in alignment.

.2 Ensure slack material in flexible connection.

3.13 DUCT EXPANSION JOINTS

.1 Install as a minimum of one (1) expansion joint in each outdoor and indoorexhaust run.

.2 Support the duct immediately upstream and downstream from the duct expansionjoint.

.3 Insulate joints as specified.

3.14 INSTRUMENT TEST PORTS

.1 General:

.1 Install in accordance with recommendations of SMACNA and in accordancewith Manufacturer’s instructions.

.2 Locate probe inlets sufficient distance from elbows or transition sections toensure stable readings of non-turbulent air and install 75 mm (3") fromcorners and at 150 mm (6") centres across long side of duct.

.3 Install probe inlets in ductwork at locations as specified under Part 2 -Products.

.2 Locations:

.1 For traverse readings:

.1 At ducted inlets wall supply and exhaust fans.

.2 For temperature readings:

.1 At outside air intakes.

3.15 TURNING VANES

.1 Install in accordance with recommendations of SMACNA.

.2 Install where indicated.

.3 Damper Actuators - Install where indicated.

.4 Install in accordance with Manufacturer’s instructions.

Page 38: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-36DUCTWORK AND ACCESSORIES (ADD#5)

.5 Provide channel fasteners or steel plate support for actuator mounting. Connectwith damper mechanism. Adjust linkage and tighten connection points asrequired.

.6 Upon system start-up, ensure that dampers operate properly without any tensioncaused by mechanical misalignment.

3.16 LEAKAGE TEST

.1 In accordance with SMACNA HVAC Duct Leakage Test Manual.

.2 Do leakage tests in sections.

.3 Make trial leakage tests as instructed to demonstrate workmanship.

.4 Install no additional ductwork until trial test has been passed.

.5 Test section minimum of 30 m long with not less than three (3) branch takeoffsand two (2) 90° elbows.

.6 Complete test before insulation or concealment.

3.17 SOUND ATTENUATORS

.1 Install where shown and in accordance with applicable SMACNA Manualand manufacturer’s recommendations.

.2 Provide dielectric separation where attenuator material differs fromconnected duct system. * Addendum #5

3.18 PAINTING

.1 Clean and remove all rust, dirt, grease and oil from piping, ductwork, equipment andsupports, whether such items are to be painted or not.

.2 Except where otherwise indicated, shop paint all items of equipment suppliedunder this Section with one primer coat and two finish coats.

.3 Except where otherwise indicated, paint all steel work, other than galvanized,plated, plastic coated or stainless steel. All painting will be performed under thisSection.

.4 Retouch all scratched and marred finish and primer coats to the satisfaction of theRegion.

.5 Paint the interior of all metal ductwork behind grilles and registers with one coatof flat black paint so that bare sheet metal cannot be seen through the grille orregister.

Page 39: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-37DUCTWORK AND ACCESSORIES (ADD#5)

.6 Apply two coats of paint to exposed duct work in generator room the samecolour as the walls. * Addendum #5

3.19 BALANCING

.1 The Contractor will demonstrate the satisfactory operation of each unit and systemsupplied under this Section to the satisfaction of the Engineer. Any unit or systemmay be rejected as not acceptable on the basis of failure to meet the Specifications,particularly with respect to capacity or performance, or by virtue of sub-standardworkmanship in manufacturer or installation, or by virtue of un-repaired damage, orin the case of rotating machines by virtue of vibration or excessively rough or noisyoperation. The Contractor will correct any flaw or fault to the satisfaction of theEngineer.

.2 Balance the air systems to the satisfaction of the Engineer and submit a writtenreport.

.3 Balance the air systems using proper air metering instruments. Set all dampers,grilles, and belt drives to give the required capacity plus or minus five percent in anygiven determination.

.4 Make air volume flow rate measurements with all fans and the heating andventilating units operating according to the control requirements of thisSpecification.

.5 Include in the balancing report the volumetric flow of all fans, grilles, fan staticpressures, rpm of all rotating equipment and all motor amperages. The Regionmay retain the services of an external Ventilation Engineering firm to verify theresults of volumetric flow data submitted by the Contractor. If the Contractor’svolumetric flow data deviates more than plus or minus five (5) percent from theVentilation Engineering firm’s results, the Contractor is required to make allrequired adjustments and/or modifications to the entire system to meet the intentof the contract. On completion, the Contractor is required to rebalance the systemand resubmit a new report of the entire system. The Ventilation Engineering firmwill retest the ventilation system to confirm the Contractor’s results. The cost forthe retesting by the Ventilation Engineering firm shall be borne by the Contractor.

3.20 DUCTWORK TESTING

.1 After completion of installation, provide testing to demonstrate compliance withoperating requirements.

.2 Inspect and test ductwork for air leakage at joints and connections to equipment,under normal operating conditions. Provide systems leakage tests to SMACNAClass 12 requirements.

Page 40: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-38DUCTWORK AND ACCESSORIES (ADD#5)

.3 Test ductwork before ducts are insulated, painted or concealed.

.4 Test to demonstrate that the equipment and work is not defective electrically,mechanically, or otherwise and is safe and satisfactory.

.5 Immediately correct defects discovered during tests and retest systems tocomplete satisfaction of Consultant.

3.21 EQUIPMENT TESTING

.1 Refer to Section 01800 – Equipment Testing and Starting of Systems for detailsof testing.

.2 After completion of installation, provide testing to demonstrate compliance withoperating requirements.

.3 Test to demonstrate that the equipment and work is not defective electrically,mechanically, or otherwise and is safe and satisfactory.

3.22 COMMISSIONING

.1 Commission equipment in accordance with general requirements and inaccordance with Division 1.

.2 Certify commissioning in accordance with Division 1.

3.23 TRAINING

.1 Training (non-consecutive days) – according to Section 01830, refer for details.

.2 Allows one (1), 8-hour, session for each system. The schedule shall be discussedwith and approved by the Owner. The sessions shall be completed prior tocommissioning.

3.24 MANUFACTURER’S SERVICES

.1 Additionally to Section 01640 Manufacturers Services requirements,Manufacturer’s representative for the equipment specified shall be present at thejobsite for installation assistance, inspection and certification of the installation,equipment testing, startup assistance and training of the City’s personnel, for theperiod of (at each site):

.1 Minimum 8 hours - installation assistance and certification.

.2 Up to 8 hours – testing.

Page 41: SECTION 15810 DUCTWORK AND ACCESSORIES … · city of toronto sps upgrades and rehabilitation-group 5 contract no. mcp13-08 november 2016 15810-1 ductwork and accessories (add#5)

CITY OF TORONTOSPS UPGRADES AND REHABILITATION-GROUP 5CONTRACT NO. MCP13-08NOVEMBER 2016

15810-39DUCTWORK AND ACCESSORIES (ADD#5)

.3 8 hours – training.

.4 Note: for the Strachan SPS site the above time values shall be multiplied by2.

END OF SECTION