FOR CONSTRUCTION SECTION 15420 PLUMBING VALVES PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with Division, General Requirements and all documents referred to therein. B. Provide and install all valves as indicated on the Drawings and as specified. 1.02 SUBMITTALS A. Shop Drawings and Product Data: 1. Refer to General Requirements and Section 15010 for procedure and additional submittal requirements. 2. Furnish shop drawings and product data for valves. PART 2 - PRODUCTS 2.01 GENERAL A. Provide valves of same manufacturer for all plumbing systems, including valves furnished with equipment. B. For copper tubing, provide solder-joint valves, or IPS-to-Copper adapter, sized for use with tubing and respective valve. C. For flanged valves, provide companion flanges of same PSI rating-class of valve being used. D. Provide valves rated not less than 16 bar working pressure for plumbing systems unless indicated otherwise. E. Provide valve materials suitable for service and temperature of respective systems, especially with respect to discs, plugs, balls, linings, gaskets, and lubricants of globes valves, plug cocks, ball valves, etc. F. Provide valves at points shown and as required for complete isolation of equipment, branches off mains arranged so as to give complete and regulation control of piping systems throughout the building. Install valves, with neat appearance and grouping, so that all parts are easily accessible for maintenance. G. Provide valves as specified in valve schedule below. Figure numbers listed are given as standard for type and construction. Valves for Burj Dubai – Dubai Mall Hotel, Dubai, United Arab Emirates Plumbing Valve MEP Spec-For Construction (Date of Issue: Jan 2006) 15420.1

Section 15420

Embed Size (px)

DESCRIPTION

plumbing valves

Citation preview

SECTION 16110F

SECTION 15420

PLUMBING VALVES

PART 1 - GENERAL

1.01 WORK INCLUDED

A. Comply with Division, General Requirements and all documents referred to therein.

B. Provide and install all valves as indicated on the Drawings and as specified.

1.02 SUBMITTALS

A.Shop Drawings and Product Data:

1.Refer to General Requirements and Section 15010 for procedure and additional submittal requirements.

2.Furnish shop drawings and product data for valves.

PART 2 - products

2.01 GENERAL

A.Provide valves of same manufacturer for all plumbing systems, including valves furnished with equipment.

B.For copper tubing, provide solder-joint valves, or IPS-to-Copper adapter, sized for use with tubing and respective valve.

C.For flanged valves, provide companion flanges of same PSI rating-class of valve being used.

D.Provide valves rated not less than 16 bar working pressure for plumbing systems unless indicated otherwise.

E.Provide valve materials suitable for service and temperature of respective systems, especially with respect to discs, plugs, balls, linings, gaskets, and lubricants of globes valves, plug cocks, ball valves, etc.

F.Provide valves at points shown and as required for complete isolation of equipment, branches off mains arranged so as to give complete and regulation control of piping systems throughout the building. Install valves, with neat appearance and grouping, so that all parts are easily accessible for maintenance.

G.Provide valves as specified in valve schedule below. Figure numbers listed are given as standard for type and construction. Valves for similar service shall be of one manufacturer, including valves furnished with equipment.

H.Provide composition discs for bronze globes, angles or checks. Provide bronze discs for IBBM globes, angles, or checks except where otherwise specified or approved at recommendation of the manufacturer.

I.Wheel handles to be non-heating style cast from malleable iron ASTM A197.

J.Mark each valve at the factory with the following minimum information, engraved, stamped or cast on each valve or metal tag permanently attached to the valve.

1.Manufacturer's name.

2.Catalog or Figure number.

3.Size and pressure class.

4.Arrows shall indicate direction of flow on check, globe, angle, non-return and eccentric plug valves.

5.Valves for fire protection systems shall be UL approved and shall bear the UL label.2.02 VALVES TAGS AND CHARTS

A.Provide valve identification in accordance with Section 15010 and 15190.

2.03 SAFETY AND RELIEF VALVES

A.Consolidated or Watts, type and size as applicable, constructed and rated in accordance with ASME, and so stamped.

B.Use Temperature and Pressure Relief valves for water heaters set with temperature relief at 210 F, Watts Model (40XL).

C. Valves shall have capacity to relieve maximum possible generated energy while maintaining pressure in protected equipment at no more than 10 percent above vessel working pressure.

D.Drain from relief valves shall spill to adjacent floor drain or to mop receptor.

2.04 VALVE SCHEDULES

Description

1.Gate Vales:

50 mm or smaller

bronze body and wedge, with soldered brazed or threaded ends to suit. Rising stem type with a union bonnet.

65 mm and largerflanged iron body, bronze mounted, bronze stem, OS&Y, TFE imp.

2. Butterfly Valves:

65 mm through 150 mm with flanged

end body for all services up to and

including 2,000 kPa. Valve body shall

be Bronze.

Valves

shall be bi-directional and provide

bubble-tight shut-off and dead-end

service at full rated working pressure. Disc seal (EPDM) shall be rated for service up to 100 degrees C.

3.Globe Valves:

50 mm and smaller,

bronze body, screwed ends, rising

stem, TFE imp. Stem material to

ASTM B62.

65 mm and larger,

flanged iron body bronze mounted,

bronze rising stem, TFE imp.

asbestos-free packing.

4.Ball Valves:

6 mm to 50 mm WOG bronze body, screwed ends,

teflon seats and seals..

5.Check Valves:

50 mm and smaller

bronze

body, screwed ends, swing type.

65 mm and larger

iron body,

bronze mounted, flanged, swing type.

Provide silent, double center guided, conical spring type silent check valve on pumps discharge.

6.Gas cocks, AGA approved, UL listed:

Line valves 50 mm and

smaller, square head,

cock wrench bronze.

Line valves 65 mm and larger, short pattern, lubricated plug, including operating wrench.

7.Air vent (manual):

Same as gate valve (50mm and below)

8.Bib taps:

Brass for gardens, planters and plantrooms. Chrome plated or stainless steel for sinks in kitchens and utilities rooms.

9.Strainers:

For 50 mm and below, Y-type with stainless steel screen, 26 swg with 0.8 peforations. Screwed ends.

For above 50 mm, Y-type sinle basket. 20 mesh stainless steel screen, bolted cover. Flanged end.

2.05 FLOW METERING AND BALANCING VALVES

A.Provide as indicated on drawings preso B-Plus series flow metering and balancing value. Valve shall be installed on hot water return piping.

2.06 BACKFLOW PREVENTERS

A.Reduced pressure principle, conforming to AWWA C506 and ASSE Standard 1013.

B.Complete assembly with two spring-loaded toggle lever check valves, automatically operating pressure differential relief valve, shut-off valves and test cocks. All internal parts of check and relief valves must be removable or replaceable without removal of the unit from the line.

C.On domestic water service: Epoxy coated cast iron check valve bodies with bronze check seat and stainless steel relief valve seats. Install and maintained in accordance with DEWA requirements.

2.07 DOUBLE DETECTOR CHECK VALVE

A.UL listed, FM approved epoxy coated ductile iron, check valve bodies with bronze replaceable seats, 300 series stainless steel chemically resistant rubber check valve disc, stainless check components cover bolts, 1,100 kPa, with meter on bypass. Install and maintain in accordance with DEWA and Civil Defence Regulations. Cross-Connection Control, Department of Health and Water Authority requirements.

B.Provide on fire standpipe and sprinkler services.

2.08 PRESSURE REDUCING VALVE SET

A. Each pressure reducing valve set shall be completed with pressure reducing or pressure regulating valve, isolating valves, pressure gauges on inlet and outlet, pressure relief valve on outlet and filter on inlet.

B. Each pressure reducing valve shall contain loading neoprene diaphragm and a full floating, self aligning, ignition resistant seat and shall be of the single stage, pressure reduction type with provision for manually adjusting the delivery pressure. The valve shall fail safe to the low pressure.

C. Valves shall be capable of operating at the maintaining automatically the respective delivery pressure and flow rates as indicated and shall not be liable to creep. Valves shall also be capable of maintaining the pre-set down stream pressure under static condition.

D. The filter one ach inlet to a pressure reducing valve shall be of replaceable porous sintered metal type.2.09 PRESSURE RELIEF VALVESA. Each pressure relief valve shall be of the fully enclosed type and fitting with hand easing gear.

B. Each pressure relief valve in a pressure reducing station shall have a flow capacity equal to that of the pressure reducing valve.

C. Pressure relief valves in locations other than reducing stations shall have flow capacities equal to that of the associated equipment.2.010 SOLENOID VALVESA. Each solenoid valve shall be of the packless type with coils wound for 230 volt AC operation and requiring power to open and of adequate capacity to ensure that the valve shall open with maximum pressure differential that will be encountered in the installation.

B. Each valve shall have a bronze body screwed to BS 21, stainless steel disc and stainless steel seat unless indicated otherwise for the service.

C. Solenoid valve shall be installed strictly in accordance with the manufacturers instructions.

D. The valve shall be suitable for the system working pressure and of minimum PN 16.2.011 MOTORISED VALVES (ELECTRIC)A. Provide for each valve, as indicated in the drawings, electric motorized valve operator (or actuator), attached to and supported by valve.B. Mount valve operators at factory or at site under manufacturers supervision.C. Provide manual override which allows manual operation in the event of power failure. Provide limit switches to give remote indication of valve/actuator piston position. Limit switches shall be of quick-break type, capable of being accurately and closely set, and mechanically connected to moving valve at all times following its position.D. Position indicating lights at control panel or control console shall operate as follows:

1. Red light glows when valve is completely closed;

2. Green light glows when valve is completely open;

3. Both lights glow when valve is neither completely open or closed. When valve is stopped in an intermediate position or when valve is travelling from one position to another.

4. Electrical connections, disconnect switches, conduit and power wiring for motors and remote push buttons and indicating lights shall be provided in this Contract.

PART 3 - EXECUTION3.01 INSTALLATION

A.Provide all equipment with shutoff valves. Provide all valves strainers, check valves, except control valves and unless specifically sized, of same size as the pipes in which they are installed unless otherwise indicated. Provide fixture stops.

B.All hand-controlled line valves are to be gate, ball or butterfly valves, except where throttling control or frequent operation is required, provide globe or angle valves, unless otherwise shown or specified. Install all globe and angle valves to close against the pressure.

C.Position gate valves so that stems are in any suitable angle from horizontal to upright position. Install valves only in accessible locations. Do not install valves with stems pointing downwards unless specifically indicated.

D.Wherever possible, install valves accessible from floor level. Provide operating handles for all valves and cocks. Provide adequate clearance for easy operation.

E.Support line valves at the valve in addition to regularly spaced pipe supports shown and specified.

F.Provide drain valves and hose adapters at all low points, etc.

G.Install swing checks and gravity closing lift checks in horizontal position.

H.Provide discharge pipe from all relief and safety valves. Extend to over approved drain receptacle with air gap.

I.Provide ball valves to isolate shock absorbers.

J.Provide open-ended line valves with plugs or blind flanges.

K.Where required for access provide access doors in accordance with Section 15010.

3.02 TESTING

A.Test valve bonnets for tightness. Test operate valves from closed-to-open-to-closed position while valve is under test pressure.

B.Test automatic valves including solenoid, pressure relief valves, safety valves and temperature and pressure relief valves for proper operation at settings indicated.

C.Insure that valves are field checked for packing and lubricant and that disc is for service intended. Replace leaking packing. Service valves which do not operate smoothly and properly with suitable lubricant before placing in operation.

D.Test relief valves, safety relief valves, safety valves and temperature and pressure relief valves three times.

END OF SECTION

Burj Dubai Dubai Mall Hotel, Dubai, United Arab Emirates

Plumbing Valve

MEP Spec-For Construction (Date of Issue: Jan 2006)

15420.5