Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Section 1.0

Lighting Depth

Page 2: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Section 1.2

Grocery Space

Page 3: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

1.1 Introduction into the Lighting Space The lighting redesign for Wegmans Fairfax focuses on four different spaces; The spaces selected for the lighting depth work are the grocery shopping area, the market café, the open office, and the exterior facade/parking lot lighting. The lighting design will work at enhancing Wegmans marketing and Architectural European/Village Open Market Theme. For the grocery shopping area a daylight study will be performed and skylights will be incorporated into the lighting design giving the space natural light and decreasing the dependency on electric light. Cost and performance examinations will be evaluated when appropriate throughout the depth of the lighting analysis. 1.2 Grocery Space 1.2.1 Introduction This large 40,000 square foot space is the main shopping area for customers. More than 60,000 products, compared to an average of just over 40,000 (according to the Food Marketing Institute) in most supermarkets. This space will provide the customer with the typical grocery items found in a supermarket but it also includes many specialty items. To incorporate the large variety products there is a need for a variety of different displays which requires different lighting solutions. 1.2.2 Design Criteria: (Designed to Food Display Recommendations) Appearance of Space and Luminaires: The space needs to be aesthetically appealing and inviting to the customers therefore the luminaires can not be obtrusive and must be incorporated into the architecture. The accent luminaires are brought into the architecture by hiding them under the copper canopy along the perimeter of the space and are intermixed with the decorated hanging scaffolding in the center. The general ambient luminaire fixtures are high enough not to be obtrusive to the space.

Figure 1.1.1 First Floor Plan Red Shaded Area Represents Grocery Area

Page 4: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Color Appearance (and Color Contrast): Good color-rendering is important, with illuminances with a minimum of 50fc. Usually fluorescent is recommended for fresh vegetables, fruits, and meats. In fluorescent lamps; good color-rendering of 3000-4100K are used for different fresh food displays. Other lamp sources such as metal halide, white high-pressure sodium, and halogen lamp types could be used. Daylight Integration: Must minimize direct glare from the skylights integrated in design option two. Direct Glare: A distraction due to direct glare might cause customers to avoid products and put an unattractive appearance on the products and make it unable to read product descriptions or prices. It is also important not provide direct glare in the customers faces as they circulate through the space. Consideration must be taken into account for direct glare surrounding the cashier stations. Light Distribution on Surfaces: Should be designed to attract customers to the displays and make them want to buy the products displayed. Light Distribution on Task Plane: It is important to have uniform light distribution on the room surfaces. Uniformity makes traveling the space easier well you glance at the displays. Shadows: It is important not to have shadows so that the aesthetics of the space are appealing to the customers and there is no creation of unappealing sales locations. Radiant Heat: Use moderate illuminances (50fc) as light temperatures could have a negative effects and cause discoloration in fresh meats. All fresh food should have their radiant heat should be minimized. If halogen lamps are used for accent lighting use lamps with dichroic cool beam reflector coatings to reduce emitted radiant heat. Design Criteria Continued: Horizontal Luminance: Assumed Illuminances for Typical Areas in Malls. Food Displays: 50fc Circulation and eating areas: 10 Fc Cashier Areas: 30-50 Fc

Page 5: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

1.2.3 Schematic Design Concept Development The grocery space is a functional space serving as a main sales floor for anything from the typical cereal and milk to the not so typical large selection of imported international foods, books, and home furnishings. Because of the large variety of displays in the space and because of the frequent changing needs in space it was important to incorporate a highly flexible lighting system that can be changed as the displays changed Design Goals A primary goal of the grocery space was to implement energy efficient techniques into the space, reducing the power consumption with the reduction of electric light. Implementing energy efficient techniques secondary goals were created; first to incorporate daylighting and its controls into the space. Secondly it was important to find a fixture which could have flexibility with dimming capabilities. While energy concerns were a major concern with the space it was also very important to maintain a high level of visual clarity and high level of visual performance. The skylights bring natural light into the store, brightening the visual environment. It was also very important while implementing the new design goals not to affect the way Wegmans sells it merchandise or conducts its business. 1.2.4 Equipment Used for Solutions with & without Daylight

Luminaire Lamp Ballast

Key Description Manufacturer Type/Watts CRI/CCT Type Start Voltage Input

Watts

F2 4' High Bay Pendant, Direct HE Williams (2) LF T5HO,

54W (Sylvania) 82/3500 Electronic, Dimming

Prog. Start 277 125

F3 2' Wall Washer, Wall Mounted Zumbtobel (1) T5, 14W 85/3500 Electronic,

Dimming Prog. Start 277 17

Page 6: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Grocery Luminaire Plan All luminaires that are marked in black are F2 and all luminaires in green are F3.

Control Equipment & Zones The lighting system for the grocery space will be controlled by 3-level on/off daylighting control module using photocells located at two different positions in the grocery space. The controls will simply be set-up to set a certain percentage of the luminaires off when the daylight levels reach the lighting requirements of 50fc. The photocells are placed at critical points and send signals back to the daylighting control module which is set on 30 minute time delay meaning that for a certain percentage of the luminaires to be dimmed or turned on/off the light levels must go above/below light level requirements for thirty minutes. The thirty time delay element is to insure that the lights are do not flicker back and forth and create an uncomfortable illuminated environment and waste more energy than it saves. Also after midnight 50% of all F2 will be turned off and all F3 will be turned off. Store hours are from 6am till midnight

Page 7: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Analysis without Daylighting Only analyzing the electric light, the space had an average illuminance of 56fc at full-output which meets the suggested levels set forth by the IES. W

Control Equipment Zone

Key Description Voltage/Load Coverage Quantity Manufacturer

1, 2 LS-1 Provides automatic ON/Off switching 24VDC All F2 1 Wattstopper (LC-203)

1 PS-1 Measure incoming daylight light levels and sends light levels back to LS-1 N/A F2 in

Zone 1 Wattstopper (LS-290c)

2 PS-2 Measure incoming daylight light levels and sends light levels back to LS-1 N/A F2 in

Zone 2 1 Wattstopper (LS-290c)

3 TS-2 Automatically turns lights off at present time, countdown

120VAC, 60Hz, 0-800W All B1 1 Wattstopper

(TS-200)

Zone 1 Zone 2

Page 8: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

1.2.5 Daylighting Study and Analysis The incorporation of daylight was analyzed using SkyCalc: Skylight Design Assistant and AGI-32 to determine the optimal amount of skylights for the space. To analyze the amount of daylight being provided at different times of the year, four days were analyzed to give a wide range to show how the lighting system will have to be flexible for the changing seasons. The four dates analyzed were March 21, June 21, September 21, and December 21. For each day 3 times were analyzed with each time being calculated for three different sky conditions (clear, partly cloudy, and overcast). In the end a total of thirty-six scenarios were tested and hypothesized for throughout the year. The average amount of clear, partly cloudy, and overcast conditions for each month was accumulated from www.cityrating.com. It is also important to remember that my study only analyzed the potential benefits of daylight from the hours of 9am to 3pm because these are the times that it was assumed could improve the system most. The electric lights will be controlled by a 3-level switching and will be controlled by two photocells placed at their critical point locations. The final amount of skylights chosen was forty-nine because this provided the best energy savings solutions as discussed in section 3.0. A second energy analysis which incorporates the mechanical system is completed in section 3.0. Skylight 1586 square feet of skylight or 4.9 percent skylight to floor ratio was chosen because this optimized the energy savings with causing major problems with any other building system. The Sunoptics Prismatic model Cool-optics skylight was chosen due to its ability to maximize visible light transmission while maintaining a relative low solar heat gain coefficient for the amount of visible light transmitted. Refer to section 4.0 for skylight and roof framing plan.

Key Description Manufacturer U-Value Shading Coefficient

Visible Light Transmission

Solar Heat Gain

Coefficient

S1 Flat Style Venting Style with Thermal Break, Acrylic Glazing Only Sunoptics 0.35 0.32 0.67 0.375

Page 9: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Typical Sky Conditions

# of Days with Sky Condition Month Clear Partly Cloudy Overcast

January 7 7 17 February 7 6 16 March 7 8 16 April 7 9 14 May 7 10 14 June 6 12 12 July 8 11 12 August 8 11 12 September 9 9 12 October 11 8 12 November 7 8 15 December 7 7 17

Sky Conditons For Fairfax, VA

0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

1 2 3 4 5 6 7 8 9 10 11 12

Month

% o

f Mon

th OvercastPartly CloudyClear

Page 10: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Day lighting Analysis and Energy Analysis After the accumulated illuminances averages from each scenario were performed in AGI32 for a sample portion of the space then the critical point had to be found. To find the critical point first a target Illuminance with full-electric light had to be determined. The target illuminance specified for this study was 50fc (Grocery Store Recommendation by IES). After determining the target illuminance it was found which luminaires could be switched may be switched off and how long this condition could occur. To calculate this the following equation was used: % dimmed = Target Illuminance – (Undimmed Illuminance + Daylight Illuminance) Dimmed Illuminance After determining the dimming levels that are required for the ballasts, it is necessary to convert the ballast factor into the input watts. From this it is possible to show the energy saving that will result from the control implemented into the new daylighting system.

Month/Day Type of Day # of Hours of Condition

% of Electric Light Output Required

March 21 Clear 6 0 March 21 Cloudy 6 0 March 21 Overcast 6 17.5 June 21 Clear 6 0 June 21 Cloudy 6 0 June 21 Overcast 6 0

September 21 Clear 6 17.5 September 21 Cloudy 6 31.5 September 21 Overcast 6 31.5 December 21 Clear 6 31.5 December 21 Cloudy 6 61.5 December 21 Overcast 6 61.5

Page 11: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Month/Day Type of Day Total Kwh Cost/kwh Total Cost Saved

Feb/ March/April Clear 1329.552 $0.117 $155.56 Feb/ March/April Cloudy 1456.176 $0.117 $170.37 Feb/ March/April Overcast 2912.352 $0.117 $340.75 May/June/July Clear 1329.552 $0.117 $155.56 May/June/July Cloudy 2089.296 $0.117 $244.45 May/June/July Overcast 2405.856 $0.117 $281.49

August/Sept/Oct Clear 1772.736 $0.117 $207.41 August/Sept/Oct Cloudy 1772.736 $0.117 $207.41 August/Sept/Oct Overcast 2279.232 $0.117 $266.67

Nov/Dec/Jan Clear 1329.552 $0.117 $155.56 Nov/Dec/Jan Cloudy 1392.864 $0.117 $162.97 Nov/Dec/Jan Overcast 3102.288 $0.117 $362.97

Total Cost Saved/Year $2,711.15

Day lighting Summary After analyzing the amount of electric light that could be dimmed on any particular day for the 6-hour period analyzed on each day a study was determined to see how much kwh/month could be saved. Estimating the total kwh per month from a power consumption weekly summary from previous a similarly building Wegmans owns and operates I was able to come up with monthly power consumption estimates. From the total power consumption estimate another assumption was made that the grocery space lighting loads would be responsible for twelve percent of the total power consumption of the entire building. This assumption was based on the estimate that forty percent of the total building power is dedicated to lighting loads and then from that a percentage of the total load taking into account hours of operation during the study and the percentage based on square footages. In the end a total cost estimate was completed using the total kWh of the dimmed system and then multiplying it by the percent of total light output required then multiplying that by the cost/kwh and you end up with the total cost saved per period of time. A total cost savings of $2,715.15 was accomplished by implementing the skylights and its daylight controls into the new lighting designed system. 1.2.6 Comparison between Two Systems The redesign of the grocery space was completed with two different solutions, one with skylights and one without; therefore a cost analysis was performed in order to determine the more cost effective methods for the lighting design. The annual energy consumption costs and the initial costs including materials and labor were analyzed. The cost for the additional air-handling unit to handle the additional solar heat gain from the skylights

Page 12: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

was also included into the initial costs for solution number as was an allotment for the cross-bracing which was added to the structural roof framing system. Cost information was collected from the 2005 R.S. Means Electrical Cost Data and 2005 R.S. Means Assemblies Cost Data.

Solution # 1 (Used Electrical R.S. Mean’s unless specified)

Item Priced Unit Quantity Material Labor Total Bare Costs Catalog #

* High Bay Industrial Linear Fluorescent, T5HO, 54W, 4' Ea 253 $74.00 $65.00 $139.00 16510-440-3200

** Linear Fluorescent Wall Washer F2 Ea 60 $28.00 $38.50 $66.50 16510-440-2400

* Used the 4' long two 60 Watt HO Pendant Mounted Industrial Fluorescent Fixtures (16510,3200)

** Used Surfaced Mounted Wall Washer 40W

Solution # 2 (Used Electrical R.S. Mean unless specified)

Item Priced Unit Quantity Material Labor Total Bare Costs Catalog #

* High Bay Industrial Linear Fluorescent, T5HO, 54W, 4' Ea 253 $74.00 $65.00 $139.00 16510-440-3200

** Linear Fluorescent Wall Washer F2 Ea 60 $28.00 $38.50 $66.50 16510-440-2400

** Unit Skylight (30S.F.- 65S.F.) Ea 49 $43.50 $4.04 $47.54 08652-1300

(Assembly Estimate)

3000 CFM Ea 1 $3,900.00 $590.00 $4,490.00 15720-0910 (Mech Estimator)

Flat Estimate for new cross braces for skylights ** From Construction Manager on Wegmans Fairfax Project $2,000.00 N/A

* Used the 4' long two 60 Watt HO Pendant Mounted Industrial Fluorescent Fixtures (16510,3200)

** Used Surfaced Mounted Wall Washer 40W

Page 13: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Total System Costs Solution # 1 (Used Electrical R.S. Mean unless specified)

Item Priced Unit Quantity Total Including O&P Total Costs

* High Bay Industrial Linear Fluorescent, T5HO, 54W, 4' Ea 253 $178.00 $45,034.00

** Linear Fluorescent Wall Washer F2 Ea 60 $88.00 $5,280.00

Total Cost Estimate of Solution # 1 $50,314.00

Solution # 2 (Used Electrical R.S. Mean unless specified)

Item Priced Unit Quantity Total Including O&P Total Costs

* High Bay Industrial Linear Fluorescent, T5HO, 54W, 4' Ea 253 $178.00 $45,034.00

** Linear Fluorescent Wall Washer F2 Ea 60 $88.00 $5,280.00

** Unit Skylight (30S.F.- 65S.F.) Ea 49 $52.29 $2,562.41

3000 CFM Ea 1 $4,939.00 $4,939.00

Flat Estimate for new cross braces for skylights ** From Construction Manager on Wegmans Fairfax Project $2,000.00

Total Cost Estimate of Solution # 2 $59,815.41

Solution 2 had a higher initial cost by $9501.41 but this amount is small enough that an owner with the ability to spend a little bit higher upfront costs can see significant payback in the future. The payback in the future will come from the decreased use of electric light due to the installation of skylights in solution 2. An estimated savings of $2711.15 annually was calculated earlier in the daylight analysis. Annual Energy Consumption Saving per/yr: $2711.15 Additonal Initial Cost in Solution 2: $9501.41 Payback Period: $9501.41 / $2711.15 = 3.5 years

Page 14: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

1.2.7 Analysis of System Light Loss Factors

Luminaire Initial Lumens

Mean (Design) Lumens

LLD Maintenance Category

Cleaning Interval LDD RSDD BF Total LLF

F2 5000 4650 0.93 IV 6 months, Medium 0.84 0.98 0.99 0.758

F3 1350 1269 0.94 IV 6 month, Medium 0.88 0.96 0.98 0.778

Panel Boards With the new lighting design for the grocery space the lighting loads changed and an analysis of this impact was completed. Three (3) different 277V panel boards tied into the existing lighting loads to the grocery space; PP1, PP5, and PPGEM all fed 277V lighting loads, with PPGEM only feeding the emergency fixtures. But in the new Panel Board design I removed all most all lighting loads from those existing panel boards and placed them on PPEM2. PPEM2 is a panel board that is completely dedicated to lighting and in the event of power failure can be back-up by the 500kw emergency generator. All of the loads associated with fixture F2 is placed on PPEM2 and all of fixture F3’s lighting loads will be placed on PP5.

Page 15: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Circuit Calculations for PPEM2 Luminaire Total Watts per fixture VA Volts Amps Brk. Size Circuit #

F2 12 125 1500 277 5.42 20 1 F2 9 125 1125 277 4.06 20 3 F2 12 125 1500 277 5.42 20 5 F2 12 125 1500 277 5.42 20 7 F2 10 125 1250 277 4.51 20 9 F2 10 125 1250 277 4.51 20 11 F2 10 125 1250 277 4.51 20 13 F2 12 125 1500 277 5.42 20 15 F2 10 125 1250 277 4.51 20 17 F2 10 125 1250 277 4.51 20 19 F2 10 125 1250 277 4.51 20 21 F2 10 125 1250 277 4.51 20 23

F2 10 125 1250 277 4.51 20 25 F2 12 125 1500 277 5.42 20 27 F2 10 125 1250 277 4.51 20 29 F2 11 125 1375 277 4.96 20 2 F2 12 125 1500 277 5.42 20 4 F2 10 125 1250 277 4.51 20 6 F2 10 125 1250 277 4.51 20 8 F2 10 125 1250 277 4.51 20 10 F2 11 125 1375 277 4.96 20 12 F2 10 125 1250 277 4.51 20 14 F2 10 125 1250 277 4.51 20 16 253 10 125 1250 277 4.51 20 18

Total 31625 Total 114.17

Circuit Calculations for PP5 Luminaire Total Watts per fixture VA Volts Amps Brk Size Circuit #

F3 30 17 510 277 1.84 20 2 F3 30 17 510 277 1.84 20 4

Total 1020 Total 3.68

Page 16: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Power Density

Key No. of Fixtures Input Watts Input Watts

F2 253 125 31625

F3 60 17 1020

Total Wattage (W) 32645

Square Footage of

Space(Sq.ft.): 39900 Power

Density (W/SQ.FT.)

0.82

The grocery space satisfies the ASHRAE 90.1 Power density requirements of 1.5 W/SQ. FT. Design Performance Calculations Results

Page 17: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Conclusions: In conclusion I found that both design solutions were energy proved to be energy efficient systems. Solution 2 however optimized the energy consumption by decreasing the amount of electric light even more than solution 1. The skylights were able to provide a natural light to the space for the first time and make the space overall more comfortable for its occupants in the grocery space.

Page 18: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Section 1.3

The Front End Offices

Page 19: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

1.3 Front End Offices 1.3.1 Introduction The front end offices are located on the first floor and serve dual purposes. First, they serve as a workspace for the front end shift managers. Secondly, they serve as a waiting area for people interviewing for jobs or meeting in private offices. The space consists of 350 square feet which features four work stations, a waiting area, and an access corridor to 5 offices. There are pictures of Wegmans accomplishments and pictures along the outside perimeter of the space.

Figure 1.3.1 First Floor Plan

Shaded Area represents location of Open office

Figure 1.3.2 Open Office Furniture Plan

Page 20: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

1.3.2 Design Criteria Requirements: (Designed to Office Recommendations) Appearance of Space and luminaires This space occupies managers of the store. The front end space should be illuminated with importance for a visually welcoming appeal. Color Appearance: The CRI should be at a minimum of 75 so there is good color to execute paper tasks and VDT tasks which are performed in this space. Since this space occupies the managers of the store, it should be illuminated with importance. The wood furnishings in the space push the design towards the 3500K range for a CCT. Direct Glare: For optimal working conditions, direct glare should be avoided. Direct glare on an individual in the workspace can decrease an individual’s efficiency. Light Distribution on Surfaces: Even distribution is needed on the immediate workspace so proper luminance ratios can be achieved. Even distributions will lead to higher worker efficiencies as they work amongst the immediate workspace. Light Distribution on Task Plane: A uniform distribution on the task plane will help with the efficiency on paper tasks performed by individuals. Uniform light distribution on task plan also is important in obtaining proper luminance ratios. Luminance of Room Surfaces: Recommended maximum luminances for task to background are 3 to 1, and task to field of view is 10:1. Reflected Glare: With VDT screens present, reflected glare should be minimized. To keep reflected glare minimized, the luminance ratio between the VDT screen and the field of view should be kept at recommended values. Source /Task/Eye Geometry: Proper placement of light sources and work stations should be evaluated. Keeping VDT screens away from direct glare is essential. For example, a VDT screen angled towards a window should be avoided.

Page 21: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

1.3.2 Design Criteria Requirements Continued System Control and Flexibility: The ability to perform paper tasks and VDT tasks should be obtained with complete occupant comfort and with out having to change conditions. The lighting system also should integrate dimming controls and occupant sensors into the design. Horizontal Illuminance: The recommendation for the illuminance on the work plane is 30 Fc-50Fc. Vertical Illuminance: It is recommended to have a vertical illuminance of 5 Fc. The presence of VDT screens in the space makes this value very important in illuminating the space appropriately. 1.3.3 Schematic Design Concept Development The office area is largely a functional space, with work stations, a waiting area, and a circulation corridor. There was however a significant importance with the appearance in this space, due to the fact that the space doubles as a waiting area for possible future employees and clients. It was crucial to improve the light levels and appearance for the front end shift managers who use the work stations. It was key to have a visually appealing and comfortable feel to the overall area. Design Goals The office space is first and foremost used as a work space. Therefore, the space should be comfortable. It is important to maintain a visually conducive working environment. Each work station should be provided with task lighting so that the individual worker will have the ability to control the illuminance levels to their own personal desired light level. Special consideration should also be taken into account with VDT screen at each work station. It was also important in the lighting design to separate the space into the two distinct functions of the space; the work area and the waiting /circulation area. What this does is add appeal to visitors and create a more visually interesting space for the waiting area, while also effectively leads people through the space.

Figure 1.3.3 Sketch of Cubicle

Page 22: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

1.3.4 Equipment Luminaire Schedule

Luminaire Lamp Ballast Key Description Manufacturer Type/Watts CRI/CCT Type Start

F1 Ciros 4', Pendant Mounted, Indirect/Direct Litecontrol (2) T8, 32W 82/3000K electronic

dimmable PS

B1 Low Voltage Recessed downlight, 10 degree

reflector Erco (1) MR16, 50W

, (Phillips) 82/3500K N/A N/A

T1 Low Voltage, Adjustable, table top Erco (1) CFL, 26W

(Sylvania) 100/3000K N/A N/A

* All Lamps are to be provided by General Electric (unless noted) * All ballasts are to be provided by Advance Transformer (unless noted)

* Select Fixtures shall be selected as Emergency fixtures and shall have battery packs and emergency ballasts *Cut sheets for luminaires, lamps, and ballasts can be found in Appendix A1

*Start under the ballast column indicates the ballast starting method

Visible Open Office Luminaires

F1 B1 T1

Page 23: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Control Equipment & Zones Controls will control luminaires F1 and B1 in the space. A passive infrared occupancy sensor will control all the linear fluorescent fixtures (F1) in the open office and will be set to a 15 minute delay before extinguishing luminaires. Fixture (F1) will also be controlled by a dimming wall switch which has programmable dimming levels and a manual wall switch override. A time switch with manual override will control the wall spot luminaire (B1), the fixture will be set to run between the hours of operation of the store from which is (6:30am -12am). The task lighting at each desk (T1) will be controlled at each work station by the user with a toggle switch which can be fully illuminated or dimmed to 50 percent.

Control Equipment Zone

Key Description Voltage/Load Coverage Quantity Manufacturer

1 OC-1 Passive Infrared , dense wide angle lens 24VDC, 19mA All F1 1 Wattstopper

(CX-100)

1 DC-1 Automatic Dimming, Manuel

Override, Integrates occupancy sensor

24VDC All F1 1 Wattstopper (LCD-203)

2 TS-1 Automatically turns lights off at present time, countdown

120VAC, 60Hz, 0-800W All B1 1 Wattstopper

(TS-200)

Reflected Ceiling Plan & Control Zone Location

Page 24: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

1.3.5 Analysis Light Loss Factors

Luminaire Initial Lumens

Mean (Design) Lumens LLD Maintenance

Category Cleaning Interval LDD RSDD BF Total

LLF

F1 5000 4650 0.93 II 12 months, Clean 0.94 0.91 0.98 0.780

B1 ***Assumed 0.95 for LLD 0.95 III 12 months, Clean 0.91 0.96 1.00 0.830

T1 1710 1548 0.91 IV 3, months, clean 0.97 0.98 1 0.861

Power Density

Open Office

Key No. of Fixtures Input Watts Input Watts

F1 4 70 280

B1 2 50 100

T1 4 26 104

Total Wattage (W) 484

Square Footage of Space(Sq.ft.): 440

Power Density (W/Sq.ft) 1.1

The Open Office Space satisfies the ASHRAE 90.1 Power Density Requirements of 1.1 W/SQ. FT.

Page 25: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Panel Boards With the new lighting design for the open office, the lighting loads changed and an analysis of this impact was completed. Three (3) different panelboards tied into the existing lighting loads to the open office. PP1 and PPGEM both fed 277V lighting loads, with PPGEM only feeding the emergency fixtures. But, in the new panel board design, I removed all lighting loads off of PP1 and placed all loads on to PPEM1 (circuit 3). PPEM1 is the new panel board which was redesigned in my emergency generation study in the electrical depth. Luminaires B1 and T1 tie into panelboard LV6C (circuit 3). All private offices which were specified with the same fixtures were also included into the calculations to be consistent with the existing design. I chose to keep all lighting loads in the open office and the private offices on the same circuit because of the size of the total loads and the close proximity to each other.

Circuit Calculations for PPEM1 Luminaire Total Watts per fixture VA Volts Amps Breaker Size Circuit #

F1 45 70 3150 277 11.37 20 A 3 Lighting Load 3150 Sub-total 11.37

Total VA 3937.50 Total Amps 14.21*** Note: Lighting Load x 1.25 = Total VA

Circuit Calculations for LV6C

Luminaire Total Watts per fixture VA Volts Amps Breaker Size Circuit # B1 3 50 150 120 1.25 20 3 T1 14 26 364 120 3.03 20 3

Lighting Load 514 Sub-total 4.28 Total VA 642.50 Total 5.35

*** Note: Lighting Load x 1.25 = Total VA

Page 26: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Renderings **Note All Renderings were produced in AGI.32-v1dot7.1.73 Figure 1.2.4 depicts the Open Office as it would be seen from the north end of the space or from the Perishable manager’s office door. On the left side of the picture you see both the 8.5” x 4’ linear fluorescent indirect/direct fixtures which provide the ambient light to the space and the on the desk you see the task lighting which provides the user control over their work plane illuminance. On the far walls you see recessed halogen that spots the artwork and exhibits on the wall in the waiting area.

Figure 1.2.4 Rendering of Open Office

w/ task lighting on

Figure 1.2.5 Rendering of Open Office

w/task lighting on

Page 27: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Design Performance Calculations Results **Note All Calculations were performed in AGI.32-v1dot7.1.73 Desktop Typical (w/no Task Lighting)

Location Avg/Max/Min Illuminance (Fc) Average 20.66

Max 23.4 Typ. Work

Plane Min 15.5

Figure 1.2.6 Rendering of Open Office Distribution on exhibits

Figure 1.2.7 Rendering of Desktop

Distribution on Work plane

Calculations to the right show a typical office illuminance values at a desk without task lighting. The average illuminance of 20.66 is meant to provide high ambient light levels for office tasks. User has control to add 10 to 25 foot-candles for the occupant comfort with office tasks. Uniform distribution is provided on work plane and max/min ratio is 1.51 so uniform

Page 28: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Desktop Typical (w/ Task Lighting – (Task Lighting @Full Output)

Task Lighting - 50% Output Location Avg/Max/Min Illuminance (Fc)

Average 51.6 Max 62.5 Min 29.6

Typ. Work Plane

Max/Min 2.11

Desktop Typical (w/ Task Lighting– (Task Lighting @50%Output)

Task Lighting - Full Output - 100% Output Location Avg/Max/Min Illuminance (Fc)

Average 61.4 Max 78.1 Min 30.59

Typ. Work Plane

Max/Min 2.55

This provides more task illumination for the individuals who need more foot-candles to perform work place tasks like a paper task. The max min is still very reasonable and within its limits. And, it meets the high side recommendation for paper tasks by providing over 50Fc.

This scenery provides an even higher average illuminance. This scenery might help, for example, a user who might be a little older and needs a little extra light to see the detail on a paper. This design is still within the recommended luminance ratios.

Page 29: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Workplane (w Task Lighting) Circulation Space

Location Avg/Max/Min Illuminance

(Fc) Average 10.2

Max 20 Circulation

Space

Min 6.8

The circulation space had an average of 10.2Fc which is a little high, but is due to the close proximity to the work area and the size of the room. It does meet the minimum requirements of the IES of 5Fc for people to circulate through space safely.

Page 30: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Conclusion The lighting design of the Wegmans Fairfax Front End Offices created an effective working environment for the building employees and guests. The indirect/direct lighting provides the ambient light to the space while the task lighting provides additional illuminance to perform paper tasks as needed. Also, in this space there are recessed spots pointed onto the artwork providing a showcase to the exhibits and Wegmans achievements while also providing light along the walls to guide people through the space to the individual private offices. The system provides flexibility to the end user to have control over their work station and keep their lighting levels to what fits them best. The solution also provided minimal glare and kept the luminance ratios in the desired limits, leading to a very comfortable working environment. With the employees feeling comfortable with their work environment, and all other variables remaining the same, this lighting solution should lead to increased productivity.

Page 31: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Section 1.4

Front Facade

Page 32: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

1.4 Front Facade 1.4.1 Introduction The North (front) façade of Wegmans Fairfax is very important to the entire design of Wegmans Fairfax. The architectural and marketing theme Wegmans has developed inside there stores is being brought to the outside of the stores in an attempt to promote and attract business. The architecture attracts customers into the main entrances with the arches and a clock tower which stands high in the center of both entrances.

Figure 1.4.1 to the right shows the site plan with landscaping. Red Shaded Area represents Work Parameters

Figure 1.4.2 below shows an architectural perspective of the front (north façade of Wegmans Fairfax.

Page 33: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

1.4.2 Design Criteria Requirements: Appearance of Space & Luminaires: The parking lot, facade, and landscaped regions are the first and last impression each customer is left with when shopping at Wegmans. Wegmans feels it is important for this space to appear attractive while also providing light for proper security. Direct Glare: Direct glare must be minimized for the safety of individuals operating motorized vehicles within the parking lot or adjacent roads. Light Distribution on Surfaces: It is important to maintain uniform distributions throughout the lot, which will help protect individuals from safety concerns. As a general rule, the luminance ratios should not exceed 20:1. Light Pollution/Trespass: All upward flux emission should be minimized with the parking lot and street lighting systems. All parking lot and street lighting should have luminaires with full cutoff at the horizontal plane. All non-target illumination should also be minimized on architectural and sign lighting. The outdoor lighting systems must also be conscience of not allowing any potentially undesirable of amount light to the neighboring properties. Modeling of Faces or Objects: Safety is the number one factor for Wegmans in the design of the outside space. Helping with the sense of security it is important that faces, individuals, and other objects are properly lit so that each individual can clearly see their surroundings. Peripheral Detection: Suitable illuminance levels should be provided for individuals entering or exiting the building and individuals driving motorized vehicles to provide adequate light for awareness of their surroundings on the property. Points of Interest: The entrances should be the brightest part of the space leading customers into the building. Also, signs and other special architectural features should be highlighted as appropriate. Shadows: Shadows will occur in general due to large objects or when illuminance is not even. Shadows could cause accidents by blacking out an area or due to the large difference in luminance ratios.

Page 34: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Source/Eye/Task: It is important that individuals have safe driving conditions. Analyzing the parking lot for proper illuminance, luminance values and minimization of glare will help conclude whether individuals can drive safely through space. Horizontal Illuminance: Minimum horizontal illuminance of 5 Fc is recommended. Generally the heavily traveled egress paths should pay close attention to the horizontal illuminance. Vertical Illuminance: Minimum vertical illuminance of 2.5 Fc is recommended. Power Allowance Requirements: As per ASHRAE 90.1 design regulations Building Entrance with Canopy: 3 W/ft2 Building Façade: 0.25 W/ft2 Parking Area: 0.2 W/ft2

1.4.3 Schematic Design Concept Development The goal of the façade design was to emulate the overall architecture theme. The lighting scheme had two simple goals in mind. First, it was important for the lighting design to accent the existing architecture and showcase the exterior facade. Secondly, since there is activity 24 hours a day it is important for the safety of customers and employees to have proper lighting in the pathways and parking lot. The first specific part of the front façade that I wanted to highlight was the two entrance ways on either end; to provide an orientation to the customers and lead them into the store. To highlight the entrance ways, the architectural columns are highlighted with decorative sconces that distribute light up and down the columns and attention is drawn into these areas. The columns and arch entrance ways are a focus of the highlighted architecture. Under the canopy downlights in the ceiling surface provide the ambient light to the area as while as creating a bright light that leads customers into the entrance ways. The clock tower was the second specific feature chosen to accent the architecture. This is the beacon or focus of the exterior architecture and it is something Wegmans and its architect have chosen as a symbol or “recognizer” for their stores. Therefore, it is important for the clock tower to be shown at night. To do this, I used a compact wall washers secured on either side of the clock tower to highlight it at night and maintained the self illuminating clock.

Page 35: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

The remaining luminaires I choose to light from the front facade and front drive way again to show off the architecture, draw customers into the building and to maintain safety along the front driveway. Decorative sconces were that distributed the light up and down were also used in between the front windows and decorative. 1.4.4 Equipment Luminaire Schedule

Luminaire Lamp Ballast Key Description Manufacturer Type/Watts CRI/CCT Type Start

Voltage

A-1 Wall mounted, Up/Down Bega (6620MH)

(1) Metal Halide, 70 W 82/3000

N/A Autotransformer

Built in 120

A-2 Wall mounted, Up/Down Bega (6615MH)

(1) Metal Halide, 39W 82/3000

N/A Autotransformer

Built in 120

A-3 Wall-Mounted, uplight, clear

specular reflector, cut-off visor

Elliptapar (Style 151)

(1) Metal Halide, 70 W 85/3000

N/A Autotransformer

Built in 120

A-4 Wall Mounted Downlight Elliptapar (Style 151)

(1) Metal Halide, 70 W 88/4200

N/A Autotransformer

Built in 120

B-2 Recessed, downlight, Reflector Silver

Erco (81042)

(1) Metal Halide, 35W 81/3000

N/A Autotransformer

Built in 120

P-1 15' Pole Mounted, Full-Cutoff

Street Works (MEM series)

(1) Meal Halide, 150W 70/3500 Ansi Ballast type

M102 277

* All Lamps are to be provided by General Electric (unless noted) * All ballasts are to be provided by Advance Transformer (unless noted)

* Select Fixtures shall be selected as Emergency fixtures and shall have battery packs and emergency ballasts *Cutsheets for luminaires, lamps, and ballasts can be found in Appendix A1

*Start under the ballast column indicates the ballast starting method

Visible Open Office Luminaires A-1 & A-2 A-3 & A-4 B-2

Page 36: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Front and Driveway Luminaire Plan Front Facade Luminaire Section Plan

Page 37: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Control Equipment & Zones To control the outdoor lights three (3) different zones were created. The first zone is for the façade lighting. It is controlled by a timer switch astronomically set to turn on/off at a preset times, which can be programmed for the changing seasons and changing times of darkness. The second zone controls the main parking lot lighting; this zone will be controlled by a photocell on the roof positioned towards the northern sky. The third zone will control select parking lot luminaires and will be on its on astronomical clock but will be left on throughout the night for safety of the site. All zones will have a manual override control. This meets ASHRAE 90.1 requirements with the inclusion of the automatic shut-off controls for the parking lot and façade luminaires. 1.3.5 Analysis Light Loss Factors

Luminaire Initial Lumens

Mean (Design) Lumens LLD Maintenance

Category Cleaning Interval LDD RSDD BF Total

LLF

A-1 7000 5600 0.80 V 6 months, Dirty 0.82 0.85 1.00 0.558

A-2 3400 2600 0.95 V 6 months, Dirty 0.82 0.85 1.00 0.662

A-3 7000 5600 0.80 IV 24, months, dirty 065 0.65 1.00 0.338

A-4 7000 5600 0.80 V 24, months, dirty 0.7 0.65 1.00 0.364

B-2 3300 2700 0.82 IV 6 months, dirty 0.82 0.92 0.90 0.556

P-1 12000 8300 0.69 V 24, months, dirty 0.7 0.75 1.00 0.363

Page 38: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Power Density

Front Façade (Advertising Sign Exempt) (ASHRAE Allowance: 0.25 W/SQ.FT.)

Key No. of Fixtures Input Watts Input Watts

A-1 9 83 747

A--3 2 85 170

Total Wattage (W) 917 Square Footage of Space (SQ.FT.):

3713 Power Density

(W/SQ.FT) 0.25

Under Canopy (ASHRAE Allowance: 3.0 W/SQ.FT.)

Key No. of Fixtures Input Watts Input Watts

A-2 4 83 332

B-2 8 88 704

Total Wattage (W) 1036 Square Footage of Space (SQ.FT.):

1200 Power Density

(W/SQ.FT.) 0.86

Parking Lot Lighting (ASHRAE Allowance: 0.2 W/SQ.FT.)

Key No. of Fixtures Input Watts Input Watts

P-1 5 150 750

Total Wattage (W) 750 Square Footage of Space (SQ.FT.):

5436 Power Density

(W/SQ.FT.) 0.14

Page 39: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

The front façade redesign met all the ASHRAE 90.1 Power Density Allowances. Panel Boards With the new lighting design for the Front Façade, the lighting loads changed and an analysis of this impact was completed. Two different Panels tied into the existing lighting loads PPGEM and LV6C. With the modifications made to my panel boards in my electrical redesign all new 277V lighting loads will be sent to PPEM1 because PPGEM was replaced. Luminaire lighting loads from fixture P-1 is placed on panel board PPEM1. Then LV6C is still exists as before the redesign and is equipped to handle the new lighting loads from luminaires A-1, A-2, A-4, and B-2 all tie into the existing panel LV6C and are placed on circuit 40. While A-3 will ties in circuit 38 with the lighting load from the self illuminating clock which remained the same as in existing conditions.

Circuit Calculations for PPEM1 Luminaire Total Watts per fixture VA Volts Amps Brkr Size Wire # Circuit #

P-1 5 174 870 277 3.14 20 12 5 Lighting Load 870 Sub-total 3.14

Lighting Load x 1.25 1087.50 Total 3.93 *** Note: Lighting Load x 1.25 = Total VA

Circuit Calculations for LV6C Luminaire Total Watts per fixture VA Volts Amps Brkr Size Wire # Circuit #

A-1 9 83 747 120 6.23 40 12 40 A-2 4 83 332 120 2.77 20 12 40 A-3 2 85 170 120 1.42 20 12 38 A-4 4 85 340 120 2.83 20 12 40 B-2 8 45 360 120 3.00 20 12 40

Lighting Load 1949 Sub-total 16.24Lighting Load x 1.25 2436.25 Total 20.30

*** Note: Lighting Load x 1.25 = Total VA

Page 40: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Renderings

Figure 1-4-3 Exterior Façade

Figure 1-4-4 Exterior Façade

Figure 1-4-5 Exterior Façade

Figure 1-4-6 Clock Tower

Page 41: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Design Performance Calculations Results **Note All Calculations were performed in AGI.32-v1dot7.1.73 Under Canopy

Page 42: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Front Drive Way Wegmans Sign Calculations

Page 43: Section 1.0 Lighting Depth - Pennsylvania State University · enhancing Wegmans marketing and Architectural European/Village Open Market ... If halogen lamps are used for accent lighting

Joseph Lookup Senior Thesis 2005 Wegmans Fairfax

Calculation Averages

Location Avg/Max/Min Illuminance (Fc)Average 16.2

Max 25.57 Min 8.7

CANOPY ENTRANCES

Max/Min 2.94

Location Avg/Max/Min Illuminance (Fc)Average 7.77

Max 12 Min 4.2

FRONT DRIVEWAY

Max/Min 3.05

Location Avg/Max/Min Illuminance (Fc)Average 7.77

Max 12 Min 4.2

Wegmans Sign (Vertical)

Max/Min 3.05 Conclusion The design solution for this was simple; to show off the architecture and highlight the entrances specifically. The parking lot and sidewalk were illuminated properly for pedestrian and motor vehicular safety.