SECTION 10 21 13 TOILET COMPARTMENTS PART 1 - GENERAL 1.1 SUMMARY A. Description of scope and intent: 1. Contractor to provide all material, labor, and tools required to complete the installation of specified system. 2. Any omission of reference to items required to complete the full operation al and functional system specified in the section does r»ot relieve the con tractor of the obligation to provide same. 3. To provide installation of all items, including delivery, dispersing to the proper locations within the building, and affixing in place, 4. Installation shall be accomplished by workers skilled in their craft who will perform their work in a professional manner and will leave the premises safe, orderly and clean. 5. Drawings and general provisions of Contract, including General and Sup plementary Conditions and Division 1 Specification Sections, apply to this Section 6. Contractor is responsible for coordination of work included in this specifi cation with all other specification sections related to furnishing of all mate rials, labor, permits, fees and services necessary for completion of work in this section. B. This Section includes toilet compartments and screens as follows: 1. Type: Metal, Stainless steel 2. Compartment Style: Overhead braced and floor anchored. 3. Screen Style: Wall anchored 1.2 SUBMITTALS A. Product Data: For each type and style of toilet compartment and screen specified. Include details of construction relative to materials, fabrication, and installation Include construction details, material descriptions, dimensions of individual components and profiles, and finishes. B. Shop Drawings: Include plans, elevations, sections, details, and attachments to other work. 1. Show locations of cutouts for compartment-mounted toilet accessories, if applicable. 2. Show locations of réinforcements for compartment-mounted grab bars. 3. Show locations of centerlines of fixtures (field verified) PCI Utilities Building HMM No. 367820 1021 1 3 - 1

SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 21 13

TOILET COMPARTMENTS

PART 1 - GENERAL

1.1 SUMMARY

A. Description of scope and intent:

1. Contractor to provide all material, labor, and tools required to complete the installation of specified system.

2. Any omission of reference to items required to complete the full operation­al and functional system specified in the section does r»ot relieve the con­tractor of the obligation to provide same.

3. To provide installation of all items, including delivery, dispersing to the proper locations within the building, and affixing in place,

4. Installation shall be accomplished by workers skilled in their craft who will perform their work in a professional manner and will leave the premises safe, orderly and clean.

5. Drawings and general provisions of Contract, including General and Sup­plementary Conditions and Division 1 Specification Sections, apply to this Section

6. Contractor is responsible for coordination of work included in this specifi­cation with all other specification sections related to furnishing of all mate­rials, labor, permits, fees and services necessary for completion of work in this section.

B. This Section includes toilet compartments and screens as follows:

1. Type: Metal, Stainless steel2. Compartment Style: Overhead braced and floor anchored.3. Screen Style: Wall anchored

1.2 SUBMITTALS

A. Product Data: For each type and style of toilet compartment and screen specified. Include details of construction relative to materials, fabrication, and installation Include construction details, material descriptions, dimensions of individual components and profiles, and finishes.

B. Shop Drawings: Include plans, elevations, sections, details, and attachments to other work.1. Show locations of cutouts for compartment-mounted toilet accessories, if

applicable.2. Show locations of réinforcements for compartment-mounted grab bars.3. Show locations of centerlines of fixtures (field verified)

PCI Utilities Building HMM No. 367820

1021 1 3 - 1

Page 2: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

i

SECTION 10 21 13

TOILET COMPARTMENTS

C. Samples for Verification: For the following products, in manufacturer's standard sizes unless otherwise indicated:

1. Each type of material, color, and finish required for units, prepared on 6-inch square Samples of same thickness and material indicated for Work.

2. Each type of hardware and accessory.

D. Coordination Drawings: Before distribution to installers, submit coordination drawings specified under “Coordination” for information.

E. Product Certificates: For each type of toilet compartment, from manufacturer.

F. Maintenance Data: Submit for each product specified in this section. Include instructions for cleaning and preventive maintenance

1.3 QUALITY ASSURANCE

A. Installer’s Qualifications: A company regularly engaged in installation ofproducts specified in this section, with a minimum of five (5) years documented experience.

B. Regulatory Requirements: Products and finished installations to be used by handicapped persons must comply with requirements of the Florida Building Code (FBC) and the Americans with Disabilities Act (ADA)

1.4 PROJECT CONDITIONS

A. Field Measurements: Verify actual locations of walls, columns, ceilings, and other construction contiguous with toilet compartments by field measurements

' before fabrication and indicate measurements on Shop Drawings.

B. Coordinate fabrication schedule with construction progress to avoid delaying the Work.

PART 2 - PRODUCTS

2.1 METAL UNITS

A. Available Manufacturers: Subject to compliance with requirements,manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. All American Metal Corp.2. Ampco Products, Inc. ^3. Bobrick Washroom Equipment, Inc.4. General Partitions Mfg. Corp.5. Global Steel Products Corp.

PCI Utilities Building HMM No. 367820

1021 1 3 - 2

Page 3: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 21 13

TOILET COMPARTMENTS

6. Metpar Corp.

B. Stainless-Steel Units: Facing sheets and closures fabricated from ASTM A 666, Type 304, stainless-steel sheet, leveled to stretcher-leveled flatness.

1. Stainless-Steel Facing Sheet Thicknesses: Specified thicknesses asfollows:

a. Pilasters, Braced at Both Ends: Manufacturer's standard thickness, but not less than 0.038 inch.

b. Panels: Manufacturer's standard thickness, but not less than 0.0312 inch

c. Doors: Manufacturer's standard thickness, but not less than 0.0312 inch.

d. Wall-Flung Urinal Screens: Manufacturer's standard thickness tomatch panels

2. Stainless Steel Finish: No. 4 bright, satin brushed on exposed faces. Exposed surfaces are protected from damage by application of strippable, temporary protective covering before shipment.

C. Door, Panel, and Pilaster Construction: Seamless, metal facing sheets are pressure laminated to core material. Units have continuous, interlocking molding strip or lapped and formed edge closures. Exposed surfaces are free of pitting, seam marks, roller marks, stains, discolorations, telegraphing of core material, or other imperfections. Corners are sealed by welding or clips. Exposed welds are ground smooth.

1. Core Material: Manufacturer's standard sound-deadening honeycomb of resin-impregnated kraft paper in thickness required to provide finished thickness of 1 inch for doors and panels and 1-1/4 inches for pilasters.

2. Grab-Bar Reinforcement: Provide concealed internal reinforcement for grab bars mounted on units.

3. Tapping Reinforcement: Provide concealed reinforcement for tapping(threading) at locations where machine screws are used for attaching items to units.

4. Urinal-Screen Construction: Match panel construction

D. Pilaster Shoes and Sleeve Caps: Stainless steel, ASTM A 666, Type 302 or 304, not less than 0.031 inch specified thickness and 3 inches high, finished to match hardware.

E. Brackets (Fittings):

1. Stirrup type: Ear or U-brackets, Manufacturer’s standard design, stainless steel.

PCI Utilities Building HMM No. 367820

1021 1 3 - 3

Page 4: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 21 13

TOILET COMPARTMENTS

2.2 ACCESSORIES

A. Hardware and Accessories: Manufacturer's standard design, heavy-dutyoperating hardware and accessories.

1. Material: Stainless steel.

B. Anchorages and Fasteners: Manufacturer's standard exposed fasteners ofstainless steel or chrome-plated steel or brass, finished to match hardware, with theft-resistant-type heads. Provide hex-type bolts for through-bolt applications. For concealed anchors, use hot-dip galvanized or other rust-resistant, protective-coated steel.

C. Overhead Bracing: Manufacturer's standard continuous, extruded-aluminumhead rail with anti-grip profile and in manufacturer's standard finish.

2.3 FABRICATION

A. Overhead-Braced Units: Provide manufacturer's standard corrosion-resistant supports, leveling mechanism, and anchors at pilasters to suit floor conditions. Provide shoes at pilasters to conceal supports and leveling mechanism.

B. Floor-Anchored Units: Provide manufacturer's standard corrosion-resistantanchoring assemblies with leveling adjustment nuts at pilasters for structural connection to floor. Provide shoes at pilasters to conceal anchorage.

C. Door Size and Swings: Unless otherwise indicated, provide 24-inch- wide in­swinging doors for standard toilet compartments and 36-inch- wide out-swinging doors with a minimum 32-inch- wide clear opening for compartments indicated to be accessible to people with disabilities.

1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees.

2. Latch and Keeper: Manufacturer's standard surface-mounted latch unit designed for emergency access and with combination rubber-faced door strike and keeper. Provide units that comply with accessibility requirements of authorities having jurisdiction at compartments indicated to be accessible to people with disabilities.

3. Coat Hook: Manufacturer's standard combination hook and rubber-tipped bumper, sized to prevent door from hitting compartment-mounted accessories. Locate on compartment side panel, not back of door, where applicable.

4. Door Bumper: Manufacturer's standard rubber-tipped bumper at out-swinging doors.

5. Door Pull: Manufacturer's standard unit at out-swinging doors that complies with accessibility requirements of authorities having jurisdiction. Provide units on both sides of doors at compartments indicated to be accessible to people with disabilities.

PCI Utilities Building HMM No. 367820

1021 1 3 - 4

Page 5: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

I I

SECTION 10 21 13

TOILET COMPARTMENTS

PART 3 - EXECUTION

3.1 INSTALLATION

A. General: Comply with manufacturer's written installation instructions. Install units rigid, straight, level, and plumb. Secure units in position with manufacturer's recommended anchoring devices.

1. Maximum Clearances:a. Pilasters and Panels: 1/2 inch.b. Panels and Walls: 1 inch.

2. Stirrup Brackets: Secure panels to walls and to pilasters with no fewer than three brackets with one attached at midpoint and others near top and bottom of panel.a. Locate wall brackets so holes for wall anchors occur in masonry or

tile joints.b. Align brackets at pilasters with brackets at walls.

B. Wall-Hung Urinal Screens: Attach with anchoring devices to suit supporting structure. Set units level and plumb and to resist lateral impact.

C. Overhead-Braced Units: Secure pilasters to floor and level, plumb, and tighten. Set pilasters with anchors penetrating not less than 1-3/4 inches into structural floor unless otherwise indicated in manufacturer's written instructions. Secure continuous head rail to each pilaster with no fewer than two fasteners. Hang doors to align tops of doors with tops of panels, and adjust so tops of doors are parallel with overhead brace when doors are in closed position.

D. Floor-Anchored Units: Set pilasters with anchors penetrating not less than 2 inches into structural floor unless otherwise indicated in manufacturer's written instructions. Level, plumb, and tighten pilasters. Hang doors and adjust so tops of doors are level with tops of pilasters when doors are in closed position.

3.2 ADJUSTING

A. Hardware Adjustment: Adjust and lubricate hardware according tomanufacturers written instructions for proper operation. Set hinges on in­swinging doors to hold doors open approximately 30 degrees from closed position when unlatched. Set hinges on out-swinging doors to return doors to fully closed position.

B. Provide final protection and maintain conditions that ensure toilet compartmentsand screens are without damage or deterioration at the time of SubstantialCompletion

PCI Utilities Building HMM No. 367820

1021 1 3 - 5

Page 6: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 21 13

TOILET COMPARTMENTS

C. Field touch-up of finished surfaces will not be permitted. Replace damagedcomponents

4.0 SCHEDULE

A. Provide stainless steel standard stalls and handicap stalls as indicated on plan.

B. Wall-Hung Urinal Screens: Attach with anchoring devices to suit supporting structure. Set units level and plumb and to resist lateral impact.

C. Field verify location of plumbing fixtures and note on shop drawings along with compartment dimensions.

D. Coordinate blocking locations.

END OF SECTION 10 21 13

PCI Utilities Building HMM No. 367820

1021 1 3 - 6

Page 7: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 28 13

TOILET ACCESSORIES

PART 1 - GENERAL

1.1 SUM M ARY

A. Description of scope and intent:

1. Contractor to provide all material, labor, and tools required to complete the installation of specified system.

2. Any omission of reference to items required to complete the full opera­tional and functional system specified in the section does not relieve the contractor of the obligation to provide same.

3. To provide installation of all items, including delivery, dispersing to the proper locations within the building, and affixing in place.

4 . Installation shall be accomplished by workers skilled in their craft who will perform their work in a professional manner and will leave the premises safe, orderly and clean.

5. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section

6. Contractor is responsible for coordination of work included in this specifi­cation with all other specification sections related to furnishing of all ma­terials, labor, permits, fees and services necessary for completion of work in this section.

B. This section includes:

1. Toilet accessories.2. Under lavatory guards.3. Custodial accessories.

1.2 SUBMITTALS

A. Product Data: Include construction details, material descriptions and thickness, dimensions, profiles, fastening and mounting methods, specified options, and finishes for each type of accessory specified.

B. Setting Drawings: For cutouts required in other work; include templates, substrate preparation instructions, and directions for preparing cutouts and installing anchoring devices.

C. Product Schedule: Indicating types, quantities, sizes and installation locations by room of each accessory required. Use designations indicated in the Toilet Accessory Schedule and room designations indicated on Drawings in accessory schedule.

PCI Utilities Building MM No. 367820

1028 1 3 - 1

Page 8: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 2813

TOILET ACCESSORIES

D. Provide maintenance data for accessories; include in maintenance manuals specified in Division 1. Provide lists of replacement parts and service recommendations.

E. Product Certificate: Signed by manufacturer certifying that products furnished meet or exceed the specified requirements.

1.3 QUALITY ASSURANCE

A. Product Options: Accessory requirements, including those for materials, finishes, dimensions, capacities, and performance, are éstablished by specific products indicated in the Toilet Accessory Schedule.

B. Interior Toilet Room Accessories shall conform to ADA and all other applicable codes for provisions of the physically handicapped.

1.4 COORDINATION

A. Coordinate accessory locations with other work to prevent interference with clearances required for access by disabled persons, proper installation, adjustment, operation, cleaning, and servicing of accessories. Notify the Architect in writing of any conflicts concerning product placement for resolution. Do not proceed without resolution.

B. Deliver inserts and anchoring devices set into concrete or masonry as required to prevent delaying the Work.

1.5 WARRANTY

A. General Warranty: Special warranty specified in this Article shall not deprive Owner of other rights Owner may have under other provisions of the Contract Documents and shall be in addition to, and run concurrent with, other warranties made by Contractor under requirements of the Contract Documents.

1. Minimum Warranty Period: 15 yëars from date of SubstantialCompletion.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Basis of Design:

PCI Utilities Building MM No. 367820

10 28 1 3 - 2

Page 9: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 28 13

TOILET ACCESSORIES

1. Manufacturers: The Basis of Design, subject to compliance with requirements, of the following manufacturers offering accessories that may be incorporated into the Work include, but are not limited to, the following:

2. Toilet Accessories:

a. Undersink Piping Cover: Basis of Design: TRUEBRO, INC.; Lav Shield, White.

b. Toilet Accessories and Grab Bars: Basis of Design: Bradley, Bobrick or equal by others.

B. Products: Subject to compliance with requirements, products that may beincorporated into the Work include, but are not limited to, those indicated in the Toilet and Bath Accessory Schedule at the end of Part 3.

2.2 MATERIALS

A. Stainless Steel: ASTM A666, Type 304, with No. 4 finish (satin), in 0.0312- inch minimum nominal thickness, unless otherwise indicated.

B. Concealed Galvanized Steel Sheet: ASTM A 653/A 653M, G90.

C. Chromium Plating: ASTM B 456, Service Condition Number SC 2 (moderate service), nickel plus chromium electrodeposited on base metal.

D. Galvanized Steel Mounting Devices: ASTM A 153/A 153M, hot-dip galvanized after fabrication.

E. Fasteners: Screws, bolts, and other devices of same material as accessory unit, tamper and theft resistant when exposed, and of galvanized steel when concealed.

2.3 FABRICATION

A. General: One, maximum 1-1/2-inch-diameter, unobtrusive stampedmanufacturer logo, as approved by Architect, is permitted on exposed face of accessories. On interior surface not exposed to view or back surface of each accessory, provide printed, waterproof label or stamped nameplate indicating manufacturer's name and product model number.

B. Surface-Mounted Toilet Accessories: Unless otherwise indicated, fabricate units with tight seams and joints, and exposed edges rolled. Hang doors and access panels with continuous stainless-steel hinge. Provide concealed anchorage where possible.

PCI Utilities Building MM No. 367820

1028 1 3 - 3

Page 10: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

I

SECTION 10 28 13

TOILET ACCESSORIES

C. Keys: Provide universal keys for internal access to accessories for servicing and re-supplying. Provide minimum of three (3) keys to Owner’s representative.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install accessories according to manufacturers' written instructions, using fasteners appropriate to substrate indicated and recommended by unit manufacturer. Install units level, plumb, and firmly anchored in locations and at heights indicated.

B. Secure mirrors to walls in concealed, tamper-resistant manner with special hangers, toggle bolts, or screws. Set units level, plumb, and square at locations indicated, according to manufacturer’s written instructions for substrate indicated.

C. Install grab bars to withstand a downward load of at least 250 lbs., when tested according to method in ASTM F 446.

D. Correct unsatisfactory substrate conditions before start of accessory installation.

E. Beginning of installation means installer’s acceptance of surfaces/ substrate.

3.2 A d ju s t an d c le a n

A. Adjust accessories for unencumbered, smooth operation and verify that mechanisms function properly. Replace damaged or defective items.

B. Remove temporary labels and protective coatings.

C. Clean and polish exposed surfaces according to manufacturers written recommendations.

3.3 TOILET AND BATH ACCESSORY SCHEDULE

A. Paper Towel Dispenser: Satin finish stainless steel, 400 “C” fold capacity with cabinet slots, knob latch and piano hinge.

Bobrick #B2620With Bobrick #B-277 Contura surface mounted waste receptacle below

PCI Utilities Building MM No. 367820

1028 1 3 - 4

Page 11: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

I

SECTION 10 28 13

TOILET ACCESSORIES

B. Soap Dispenser: Vertical tank, satin finish, stainless steel, 40 fl.oz. capacity.

Bobrick #B-2111 Classic Series, surface mounted.

C. Toilet Tissue Dispenser: Stainless steel, double jumbo roll dispenser.

Bobrick #B-2892 Classic series, surface mounted

D. Grab Bar: 42” long, 1 %“ O.D. Satin finish, 18 gauge, 304 stainless steel with concealed mounting and snap flange.

E. Grab Bar: 36" long, 1 %“ O.D. Satin finish, 18 gauge, 304 stainless steel with concealed mounting and snap flange.

F. Tilt Mirror: Stainless steel framed, 16” wide x 30” deep adjustable tilt.

G. Vertical Grab Bar: 18”, 1 %” O.D., Satin finish, 18 gauge, 304 stainless steel.

*As manufactured by Bradley, Bobrick, American Standard

END OF SECTION 10 28 13

PCI Utilities Building MM No. 367820

1 0 2 8 1 3 - 5

Page 12: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

1

SECTION 10 44 00

FIRE-PROTECTION SPECIALTIES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General andSupplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following:

1. Portable fire extinguishers.2. Fire-protection cabinets for the following:

a. Portable fire extinguishers.

1.3 SUBMITTALS

A. Product Data: Include construction details, material descriptions, dimensions ofindividual components and profiles, and finishes for fire-protection cabinets.

1. Fire Extinguishers: Include rating and classification.2. Fire-Protection Cabinets: Include roughing-in dimensions, details showing

mounting methods, relationships of box and trim to surrounding construction, door hardware, cabinet type, trim style, and panel style.

B. Samples for Initial Selection: For fire-protection cabinets with factory-applied color finishes.

C. Samples for Verification: For each type of exposed factory-applied color finish required for fire-protection cabinets, prepared on Samples of size indicated below.

1. Size: 6 by 6 inches square.

D. Maintenance Data: For fire extinguishers to include in maintenance manuals.

1.4 QUALITY ASSURANCE

A. Source Limitations: Obtain fire extinguishers and fire-protection cabinets through one source from a single manufacturer.

B. NFPA Compliance: Fabricate and label fire extinguishers to comply withNFPA 10, "Portable Fire Extinguishers."

PCI Utilities Building HMM No. 367820

10 44 0 0 - 1

Page 13: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 44 00

FIRE-PROTECTION SPECIALTIES

C. Fire Extinguishers: Listed and labeled for type, rating, and classification by an independent testing agency acceptable to authorities having jurisdiction.

1. Provide fire extinguishers approved, listed, and labeled by FMG.

1.5 COORDINATION

A. Coordinate size of fire-protection cabinets to ensure that type and capacity offire extinguishers indicated are accommodated.

1.6 WARRANTY

A. Special Warranty: Manufacturer's standard form in which manufacturer agreesto repair or replace components of portable fire extinguishers that fail in materials or workmanship within specified warranty period.

1. Failures include, but are not limited to, the following:

a. Failure of hydrostatic test according to NFPA 10.b. Faulty operation of valves or release levers.

2. Warranty Period: Six years from date of Substantial Completion.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection:

1. Available Manufacturers: Subject to compliance with requirements,manufacturers offering products that may be incorporated into the Work include, but are not limited to, manufacturers specified.

2.2 MATERIALS

A. Transparent Acrylic Sheet: ASTM D4802, Category A-1 (cell-cast sheet), 3 mm thick, with Finish 1 (smooth or polished).

2.3 PORTABLE FIRE EXTINGUISHERS

A. Available Manufacturers:

1. JL Industries, Inc.2. Kidde Fyrnetics.3. Larsen's Manufacturing Company.

B. General: Provide fire extinguishers of type, size, and capacity for each [fire- protection cabinet] indicated.

PCI Utilities Building HMM No. 367820

1044 0 0 - 2

Page 14: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

I

SECTION 10 44 00

FIRE-PROTECTION SPECIALTIES

1. Handles and Levers: Manufacturer's standard.2. Instruction Labels: Include pictorial marking system complying with

NFPA10, Appendix B and bar coding for documenting fire extinguisher location, inspections, maintenance, and recharging.

C. Multipurpose Dry-Chemical Type in Aluminum Container: Size as indicated on the Life Safety Plan, with mono-ammonium phosphate-based dry chemical in enameled-aluminum container.

2.4 FIRE-PROTECTION CABINET

A. Available Manufacturers:

1. JL Industries, Inc.2. Kidde Fyrnetics.3. Larsen's Manufacturing Company.

B. Cabinet Type: Suitable for fire extinguisher.

,C. Cabinet Construction: Nonrated, except where location of cabinet installation isindicated in a fire-rated wall.

D. Cabinet Material: Aluminum sheet.

E. Semi - Recessed Cabinet: Cabinet box semi recessed in walls with 2-1/2”rolled trim.

F. Door Style: Fully glazed, frameless, backless, acrylic panel.

G. Door Glazing: Acrylic sheet.

1. Acrylic Sheet Color: Clear transparent acrylic sheet.

H. Door Hardware: Manufacturer's standard door-operating hardware of proper type for cabinet type, trim style, and door material and style indicated.

1. Provide projecting lever handle with cam-action latch.2. Provide manufacturer's standard hinge permitting door to open 180

degrees.

I. Accessories:

1. Mounting Bracket: Manufacturer's standard steel, designed to secure fire extinguisher to fire-protection cabinet, of sizes required for types andcapacities of fire extinguishers indicated, with plated or baked-enamelfinish.

2. Lettered Door Handle: One-piece, cast-iron door handle with the word "FIRE" embossed into face.

3. Door Lock: Cam lock that allows door to be opened during emergency by pulling sharply on door handle.

PCI Utilities Building HMM No. 367820

10 44 0 0 - 3

Page 15: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 44 00

FIRE-PROTECTION SPECIALTIES

4. Identification: Lettering complying with authorities having jurisdiction for letter style, size, spacing, and location. Locate as indicated by Architect.

a. Identify fire extinguisher in fire-protection cabinet with the words "FIRE EXTINGUISHER."

(1) Location: Applied to cabinet door.(2) Application Process: Silk-screened.(3) Lettering Color: Red.(4) Orientation: Horizontal.

J. Finishes:

1. Manufacturer's standard baked-enamel paint for the following:

a. Exterior of cabinet trim, except for those surfaces indicated to receive another finish.

b. Interior of cabinet.

2.5 FABRICATION

A. Fire-Protection Cabinets: Provide manufacturer's standard box (tub), with trim, frame, door, and hardware to suit cabinet type, trim style, and door style indicated.

1. Weld joints and grind smooth.

B. Cabinet Doors: Fabricate doors according to manufacturer's standards, from materials indicated and coordinated with cabinet types and trim styles selected.

2.6 FINISHES, GENERAL

A. Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes.

B. Finish fire-protection cabinets after assembly.

C. Appearance of Finished Work: Variations in appearance of abutting or adjacent pieces are acceptable if they are within one-half of the range of approved Samples. Noticeable variations in the same piece are not acceptable. Variations in appearance of other components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast.

2.7 ALUMINUM FINISHES

A. Surface Preparation: Clean surfaces of dirt, oil, grease, mill scale, rust, andother contaminants that could impair paint bond using manufacturer's standard methods.

PCI Utilities Building HMM No. 367820

10 44 0 0 - 4

Page 16: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

I

SECTION 10 44 00

FIRE-PROTECTION SPECIALTIES

B. Baked-Enamel Finish: Immediately after cleaning and pretreating, applymanufacturer's standard two-coat, baked-enamel finish consisting of prime coat and thermosetting topcoat. Comply with paint manufacturer's written instructions for applying and baking to achieve a minimum dry film thickness of 2 mils.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine walls and partitions for suitable framing depth and blocking where recessed cabinets will be installed.

B. Examine fire extinguishers for proper charging and tagging.

1. Remove and replace damaged, defective, or undercharged units.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Prepare recesses for recessed fire-protection cabinets as required by type and size of cabinet and trim style.

3.3 INSTALLATION

A. General: Install fire-protection specialties in locations and at mounting heightsindicated or, if not indicated, at heights indicated below:

1. Fire-Protection Cabinets: 54 inches above finished floor to top of cabinet.

B. Fire-Protection Cabinets: Fasten fire-protection cabinets to structure, square and plumb.

1. Unless otherwise indicated, provide recessed fire-protection cabinets.2. Fasten mounting brackets to inside surface of fire-protection cabinets,

square and plumb.

3.4 ADJUSTING AND CLEANING

A. Remove temporary protective coverings and strippable films, if any, as fire-protection specialties are installed, unless otherwise indicated in manufacturer's written installation instructions.

B. Adjust fire-protection cabinet doors to operate easily without binding. Verify that integral locking devices operate properly.

PCI Utilities Building HMM No. 367820

10 44 0 0 - 5

Page 17: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 44 00

FIRE-PROTECTION SPECIALTIES

C. On completion of fire-protection cabinet installation, clean interior and exterior surfaces as recommended by manufacturer.

D. Touch up marred finishes, or replace fire-protection cabinets that cannot be restored to factory-finished appearance. Use only materials and procedures recommended or furnished by fire-protection cabinet manufacturer.

END OF SECTION 10 44 00

PCI Utilities Building HMM No. 367820

1044 0 0 - 6

Page 18: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

I

SECTION 10 51 13

METAL LOCKERS

PART 1 - GENERAL

1.1 SUM M ARY

A. Description of scope and intent:

1. Contractor to provide all product, material, labor, and tools required to complete the installation of this specified system.

2. Any omission of reference to items required to complete the full operation­al and functional system specified in the section does not relieve the con­tractor of the obligation to provide same.

3. To provide installation of all items, including delivery, dispersing to the proper locations within the building, and affixing in place.

4. Installation shall be accomplished by workers skilled in their craft who will perform their work in a professional manner and will leave the premises safe, orderly and clean.

5. Drawings and general provisions of Contract, including General and Sup­plementary Conditions and Division 1 Specification Sections, apply to this Section

6. Contractor is responsible for coordination of work included in this specifi­cation with all other specification sections related to furnishing of all mate­rials, labor, permits, fees and services necessary for completion of work in this section.

B. This Section includes the following:

1. Standard metal lockers, single tier.

1.2 SUBMITTALS

A. Product Data: Fore each type of product indicated. Include constructiondetails, material descriptions, dimensions of individual components and profiles, and finishes.

B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other Work.

1. Where applicable, show locker fillers, trim, base, sloping tops, and accessories.

2. Include locker identification system and numbering sequence.

C. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available for units with factory-applied color finishes.

D. Qualification Data: For qualified Installer.

PCI Utilities Building MM No. 367820

1051 1 3 - 1

Page 19: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 51 13

METAL LOCKERS

E. Maintenance Data: For adjusting, repairing, and replacing locker doors and latching mechanisms to include in maintenance manuals specified in Division 1.

F. Warranty: Sample of special warranty

1.3 QUALITY ASSURANCE

A. Installer Qualifications: Manufacturer's authorized representative who is trained and approved for installation of units required for this Project.

B. Source Limitations: Obtain locker units and accessories through one source from a single manufacturer.

C. Regulatory Requirements: Where metal lockers are indicated to comply with accessibility requirements, comply with Florida Building code (FBC) and the U.S. Architectural & Transportation Barriers Compliance Board's "Americans with Disabilities Act (ADA)

1.4 DELIVERY, STORAGE, AND HANDLING

A. Do not deliver lockers until spaces to receive them are clean, dry, and ready for locker installation.

B. Protect lockers from damage during delivery, handling, storage, and installation.

1.5 COORDINATION

A. Coordinate size and location of CMU bases. Concrete masonry unit requirements are specified in Division 4 Section "Masonry Units."

B. Coordinate sizes and locations of framing, blocking, furring, reinforcements, and other related units of work specified in other Sections to ensure that metal lockers can be supported and installed as indicated.

1.6 WARRANTY

A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of metal lockers that fail in materials or workmanship, excluding finish, within specified warranty period.

1. Failures include, but are not limited to, the following:

a. Structural failures.b. Faulty operation of latches and other door hardware.

2. Damage from deliberate destruction and vandalism is excluded.

PCI Utilities Building MM No. 367820

1051 1 3 - 2

Page 20: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

î

SECTION 10 51 13

METAL LOCKERS

3. Warranty Period for Knocked-Down Metal Lockers: Minimum of one (1) year from date of Substantial Completion.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Available Manufacturers: Subject to compliance with requirements,manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. Interior/Medart.2. Lyon Metal Products, Inc.3. Penco Products, Inc.; Subsidiary of Vesper Corporation.4. Republic Storage Systems Co., Inc.5. Tennsco Corp.

2.2 MATERIALS

A. Cold-Rolled Steel Sheet: ASTM A 1008/A 1008M, Commercial Steel (CS),Type B, suitable for exposed applications.

B. Metallic-Coated Steel Sheet: ASTM A 653/A 653M, Commercial Steel (CS),Type B; with A60 zinc-iron, alloy (galvannealed) coating designation.

C. Stainless-Steel Sheet: ASTM A 666, Type 304, stretcher-leveled standard of flatness. Roller-apply texture to doors in manufacturer's standard pattern.

D. Steel Tube: ASTM A 500, cold rolled.

E. Fasteners: Zinc- or nickel-plated steel, slotless-type exposed bolt heads, andself-locking nuts or lock washers for nuts on moving parts.

F. Anchors: Material, type, and size required for secure anchorage to each substrate.

1. Provide nonferrous-metal or hot-dip galvanized anchors and inserts oninside face of exterior walls, and elsewhere as indicated, for corrosion resistance.

2. Provide toothed-steel or lead expansion sleeves for drilled-in-placeanchors.

2.3 STANDARD METAL LOCKERS

PCI Utilities Building MM No. 367820

1051 1 3 - 3

Page 21: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 51 13

METAL LOCKERS

A. Basis-of-Design Product: Subject to compliance with requirements, provide double tiered lockers mounted to a CMU base; 60” ht; 12” width; 16” depth; Penco Products, Inc. “Vanguard” lockers, or equivalent, with recessed handle.

B. Material: Cold-rolled steel sheet.

C. Body: Assembled by riveting or bolting body components together. Fabricate from unperforated steel sheet as follows:

1. Tops, Bottoms, and Intermediate Dividers: Minimum 24 gauge, with single bend at sides.

2. Backs and Sides: Minimum 24 gauge, with full-height, double-flanged connections.

3. Shelves: Minimum 24 gauge, with double bend at front and single bend at sides and back.

D. Frames: Channel formed; fabricated from minimum 16 gauge steel sheet; lapped and factory welded at corners; with top and bottom main frames factory welded into vertical main frames. Form continuous, integral door strike full height on vertical main frames.

1. Cross Frames between Tiers: Channel formed and fabricated from same material as main frames; welded to vertical main frames.

2. Frame Vents: Fabricate face frames with vents.

E. Doors: One piece; fabricated from minimum 16 gauge steel sheet; formed into channel shape with double bend at vertical edges and with right-angle single bend at horizontal edges.

1. Doors less than 12 inches wide may be fabricated from minimum 18 gauge steel sheet.

2. Reinforcement: Manufacturer's standard reinforcing angles, channels, or stiffeners for doors more than 15 inches wide; welded to inner face of doors.

3. Stiffeners: Manufacturer's standard full-height stiffener fabricated from minimum 20 gauge steel sheet; welded to inner face of doors.

4. Door Style: Vented panel as follows:

a. Louvered Vents: No fewer than six louver openings at top andbottom for single-tier; three louver openings at top and bottom for double-tier; two louver openings at top and bottom, or three louver openings at top or bottom, for triple-tier lockers.

F. Hinges: Welded to door and attached to door frame with no fewer than two factory-installed rivets per hinge that are completely concealed and tamper resistant when door is closed; fabricated to swing 180 degrees.

PCI Utilities Building MM No. 367820

1051 1 3 - 4

Page 22: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 51 13

METAL LOCKERS

1. Knuckle Hinges: Steel, full loop, five or seven knuckles, tight pin;minimum 2 inches high. Provide no fewer than three hinges for each door more than 42 inches high.

G. Recessed Door Handle and Latch: Stainless-steel cup with integral door pull,recessed so locking device does not protrude beyond face of door; pry andvandal resistant.

1. Multipoint Latching: Finger-lift latch control designed for use with built-in combination locks, built-in key locks, or padlocks; positive automatic latching and prelocking.

a. Latch Hooks: Equip doors 42 inches and higher with three latch hooks and doors less than 42 inches high with two latch hooks;fabricated from 0.105-inch nominal-thickness steel sheet; welded or riveted to full-height door strikes; with resilient silencer on each latch hook.

H. Equipment: Equip each metal locker with identification plate and the following unless otherwise indicated:

1. Single-Tier Units: Shelf, one double-prong ceiling hook, and two single­prong wall hooks.

I. Accessories:

1. Continuous Sloping Tops: Fabricated from manufacturer's standardthickness, but not less than 18 gauge steel sheet.

a. Closures: Vertical -end type.b. Sloping-top corner fillers, mitered.

2. Filler Panels: Fabricated from manufacturer's standard thickness, but not less than 20 gauge steel sheet.

3. Finished End Panels: Fabricated from not less than 16 gauge steel sheet.

J. Number Plates: Manufacturer's standard etched, embossed, or stamped,aluminum number plates with numerals at least 3/8 inch high. Number lockersin sequence. Attach plates to each locker door, near top, centered, with at leasttwo aluminum rivets.

K. Finish: powder coat.

1. Color(s): As selected by Architect from manufacturer's full range

2.4 FABRICATION

PCI Utilities Building MM No. 367820

1051 1 3 - 5

Page 23: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 51 13

METAL LOCKERS

A. Fabricate metal lockers square, rigid, and without warp and with metal faces flat and free of dents or distortion. Make exposed metal edges safe to touch and free of sharp edges and burrs.

1. Form body panels, doors, shelves, and accessories from one-piece steel1 sheet unless otherwise indicated.

2. Provide fasteners, filler plates, supports, clips, and closures as required for complete installation.

B. Fabricate each metal locker with an individual door and frame; individual top, bottom, and back; and common intermediate uprights separating compartments. Factory weld frame members of each metal locker together to form a rigid, one-piece assembly.

C. Knocked-Down Construction: Fabricate metal lockers using nuts, bolts, screws, or rivets for nominal assembly at Project site.

D. Accessible Lockers: Fabricate as follows: (1 per toilet room)

1. Locate bottom shelf no lower than 15 inches above the floor.2. Where hooks, coat rods, or additional shelves are provided, locate no

higher than 48 inches above the floor.

E. Hooks: Manufacturer's standard ball-pointed type, aluminum or steel; zincplated.

F. Identification Plates: Manufacturer's standard, etched, embossed, or stamped aluminum plates, with numbers and letters at least 3/8 inch high.

G. Continuous Sloping Tops: Fabricated in lengths as long as practical, without visible fasteners at splice locations; finished to match lockers.

1. Sloping-top corner fillers, mitered.

H. Filler Panels: Fabricated in an unequal leg angle shape; finished to match lockers. Provide slip-joint filler angle formed to receive filler panel.

I. Finished End Panels: Designed for concealing unused penetrations andfasteners, except for perimeter fasteners, at exposed ends of nonrecessed metal lockers; finished to match lockers.

1. Provide one-piece panels for locker ends, if ends are exposed.

2.5 FINISHES, GENERAL

A. Finish all steel surfaces and accessories, except prefinished stainless steel andchrome-plated surfaces.

PCI Utilities Building MM No. 367820

1051 1 3 - 6

Page 24: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 51 13

METAL LOCKERS

B. Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes.

C. Protect mechanical finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping.

D. Appearance of Finished Work: Variations in appearance of abutting or adjacent pieces are acceptable if they are within one-half of the range of approved Samples. Noticeable variations in the same piece are not acceptable. Variations in appearance of other components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast.

2.6 STEEL SHEET FINISHES

A. Factory finish steel surfaces and accessories except stainless-steel and chrome-plated surfaces.

B. Powder-Coat Finish: Immediately after cleaning and pretreating,electrostatically apply manufacturer's standard, baked-polymer, thermosetting powder finish. Comply with resin manufacturer's written instructions for application, baking, and minimum dry film thickness.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine CMU bases for suitable conditions where metal lockers are to beinstalled.

B. Examine walls, floors, and support bases, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of the Work.

C. Prepare written report, endorsed by Installer, listing conditions detrimental to performance of the Work.

D. Proceed with installation only after unsatisfactory conditions have been corrected.

1. Beginning of installation indicates installer’s acceptance of substrate andsite conditions.

3.2 INSTALLATION

PCI Utilities Building MM No. 367820

1051 1 3 - 7

Page 25: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 51 13

METAL LOCKERS

A. General: Install level, plumb, and true; shim as required, using concealed shims.

1. Anchor locker runs at ends and at intervals recommended bymanufacturer, but not more than 36 inches o.c. or unless noted otherwise.Using concealed fasteners, install anchors through backup reinforcing plates, channels, or blocking as required to prevent metal distortion.

2. Anchor single rows of metal lockers to walls near top of lockers and to CMU base.

B. Knocked-Down Metal Lockers: Assemble with standard fasteners, with noexposed fasteners on door faces or face frames.

C. Equipment and Accessories: Fit exposed connections of trim, fillers, and closures accurately together to form tight, hairline joints, with concealed fasteners and splice plates.

1. Attach hooks with at least two fasteners.2. Identification Plates: Identify metal lockers with identification indicated on

Drawings.

a. Attach plates to each locker door, near top, centered, with at least two aluminum rivets.

3. Attach filler panels with concealed fasteners. Locate filler panels where indicated on Drawings.

4. Attach sloping-top units to metal lockers, with closures at exposed ends.5. Attach finished end panels with fasteners only at perimeter to conceal

exposed ends of nonrecessed metal lockers.

3.3 ADJUSTING, CLEANING, AND PROTECTION

A. Clean, lubricate, and adjust hardware. Adjust doors and latches to operate easily without binding

B. Clean interior and exposed exterior surfaces and polish stainless steel and nonferrous-metal surfaces.

C. Protect lockers from damage, abuse, dust, dirt, stain, or paint. Do not permit locker use during construction.

D. Touch up marred finishes, or replace locker units that cannot be restored to factory-finished appearance. Use only materials and procedures recommended or furnished by locker manufacturer.

3.4 METAL LOCKER SCHEDULE

PCI Utilities Building MM No. 367820

10 51 1 3 - 8

Page 26: SECTION 10 21 13 TOILET COMPARTMENTS · 1. Hinges: Manufacturer's standard self-closing type that can be adjusted to hold doors open at any angle up to 90 degrees. 2. Latch and Keeper:

SECTION 10 51 13

METAL LOCKERS

A. Provide single tier lockers on CMU base as indicated on drawings and interiorelevations; each opening: 12" w x 16"d x 60"h; solid door with louvers;continuous sloped top. Include one ADA compliant locker per room.

B. Coordinate with mason for CMU base. Refer to detail drawings.

C. Provide all necessary accessories to create a fully finished installation. Anchor to base and wall as necessary to prevent lockers from falling or shifting if impacted.

END OF SECTION 10 51 13