Upload
amaya-kirk
View
70
Download
4
Tags:
Embed Size (px)
DESCRIPTION
Secondary effects on output side of VSD and mitigation methods. The secondary effects of VSD’s. Supply grid. VSD. Motor cable. Motor. . . . Excess energy. High. -. frequency radiated. Insulation stress. . Mains line high. -. due to. and conducted emissions. through partial. - PowerPoint PPT Presentation
Citation preview
Secondary effects on output side of VSD and
mitigation methods
The secondary effects of VSD’s
Mains line high-frequency conducted emissions
Harmonics Leakage current
Excess energy due to regenerative braking
Heat High-frequency
radiated emissions
High-frequency radiated and conducted emissions
Leakage current
Insulation stress through partial discharges
Bearing stress (pitting through electrical discharges)
Acoustic switching noise
Supply grid VSD Motor cable Motor
Topic Outline
• How Variable Frequency Drives (VFDs) cause du/dt– VFD Output Voltage and Current– Motor Cable Affects Pulse Shape (ringing and double pulsing)– Voltage Waveform Comparison– IEC vs. NEMA Rise-Time Calculations
• The effects on the motor– Motor Windings– Motor Insulation and enhancement– Insulation Damage– Partial Discharge– Effects of Common-mode voltages (leakage currents)– Bearing failures
• Output filters and performance of Danfoss filters– Output Reactors– Output du/dt Filter– Sinusoidal Filter– Motor Termination Unit
How VFDs Cause du/dt
• VFD Output Voltage and Current• Motor Cable Affects Pulse Shape• Voltage Waveform Comparison• IEC vs. NEMA Rise-Time Calculations
VFD output voltage and current
The switching of the inverter IGBTs produces variable width pulses
The motor sees an approximated voltage sine wave
Motor cable affects pulse shape
• Short rise-times cause pulse distortion as they propagate along the length of the motor cable
• The cable can be represented as a string of series/parallel inductors and capacitors
(1/ LC ) m/sA pulse travels at a speed equal to
Voltage Pulse Leaving VFD
• Each pulse represents 1 “edge” in the PWM waveform
• Pulse enters drive-end of cable @ t=0 and rises to Ud in time tr
After One Cable Propagation
• Time = tr + tp
• Pulse travels along cable to motor and is reflected back because motor’s high frequency impedance is higher than that of the cable
• Result: Voltage rises 2 times greater than peak
After Two Cable Propagations
• Time = 2tr + 2tp
• Reflected pulse returns to drive
• Result is a negative current pulse which is changed into a negative voltage pulse as it travels back to the motor
After Three Cable Propagations
• Time = 2tr + 3tp
• The 2nd reflection returning from drive in reverse polarity is reflected and doubled at the motor
• Counteracts original motor voltage increase
• If 2tp is less than tr, the voltage never reaches 2Ud
• With longer motor cables, reflection arrives too late to reduce peak voltage
Example of Waveform at Motor
Cable length = 42 m
Motor peak voltage is a function of cable length and rise time
Voltage Waveform Comparison
Cable Length = 0.5 m
*no overshoot
Cable Length = 4.0 m
*some overshoot
Cable Length = 42.0 m
*almost 100% overshoot
[changed scope setup]
Based on 460 VAC test supply
Motor terminal overvoltagesVoltage ringing overshoot occurs at the motor terminals due to pulse reflection phenomena in the long motor cable.
Simulation showing the inverter output voltage and the motor terminal voltage with a 200m shielded cable.
Overvoltages higher than 2Vdc
Simulation showing the inverter output voltage and the motor terminal voltage with a 200m shielded cable and a double pulsing.
Double pulsing
Installations with long motor cablesLong motor cables have both internal and external effects:
External effects:• motor insulation stress (increase possibility of double pulsing) can be
eliminated by using sine-wave filters• leakage current can not be eliminated by sine-wave filters, only by
filters with DC link connection. To reduce it is possible to use unshielded cables
Internal effects:• heating of the frequency converter because of current ringing in the
motor cable can be eliminated by using sine-wave filters• saturation of the RFI filter because of the high leakage current can be
avoided by extra common-mode inductance – either on the input, or at the output by using a filter with DC link connection
IEC vs. NEMA
• IEC defined by: IEC60034-17 1998• IEC calculations result in approximately twice the value of
NEMA calculations
IEC vs. NEMA
• NEMA defined by: MGI part 30:1998
The Effects of du/dt on the motor
• Motor Windings• Motor Insulation• Enhanced Motor Insulation• Insulation Damage• Failure Mechanism – Partial Discharge
Motor Windings
• Two types of winding (low voltage motors):– Random wound: turns of round section wire are randomly
located in the coil forming process (low power)– Form wound: preformed coils are layered up uniformly
(higher power)
Motor Insulation
Elements of random and form wound insulation systems:
• Phase to ground insulation – slot liner and closure• Phase to phase insulation – slot separator and end-winding• Inter-turn insulation – slot and end-winding• Impregnating varnish – slot and end-winding
Typical slot cross section area for Random winding and Form winding
Motor Insulation
• Class F or H provides mechanical strength and electrical insulation and resistance to environmental contamination
Partially wound stator core with random winding
Partially wound stator core with form winding
Enhanced Motor Insulation
• Reinforcement of slot liners, slot closures, slot separators, inter-phase barriers, end-winding bracing and possibly special winding wire
Completed random winding
Insulation damage
Possible Causes for Insulation Damage:
1. Breakdown between coil and stator core
Normally not a problem when slot liners are used
2. Phase to phase failure in the slots or end windings
Normally not a problem when inter-phase barriers are used or if the motor is form wound
3. Inter-turn failure between adjacent conductors in the stator winding
Most probable cause of insulation failure due to non-uniform distribution of voltage along the stator winding, associated with short rise times of incident voltage pulses as generated by VFDs
Insulation damage
• Voltage over-shoot stresses the insulation between motor windings
Propagation of a voltage pulse through motor windings
Motor insulation breakdownIf the overvoltages are severe they can eventually cause the failure of the motor insulation.
Following aggravating factors are usually associated with the insulation failure:
• old motors with poor insulation (retrofit)
• applications with intensive regenerative braking that
causes the rise of the DC-link voltage
• aggressive environments (heat, humidity, chemical atmosphere)
Partial Discharge
Effects:• Motor insulation system degrades, causing premature aging, when
continuously subject to partial discharge• Insulation material gets thinner at discharge points until breakdown
occurs
To ensure no motor insulation degradation: The applied voltage needs to be less than the partial discharge inception voltage
1. The peak value of the applied voltage is lower than the actual breakdown voltage of the insulation system
2. The local electric field intensity that is created in a void or cavity is sufficient to exceed the breakdown strength in air (Partial Discharge Inception Voltage)
Common-mode voltage generation
In a pulsewidth-modulated voltage-source inverter (PWM-VSI) the common-mode voltage is always either +/- Vdc/6 (during an active vector) or +/- Vdc/2 (during a zero-vector).
Secondary effects (PWM and dv/dt)
The leakage current path
C
C
MLongCable
Vdc/2
Vdc/2
L
L
(o)
(+)
(-)
Rectifier Inverter
Mains line RFI filter
Load
Heatsink
Shaft voltage and bearing currents
CM
Csr
Csf
CrfED
Stator winding
Motor frame
Shaft
Ground
ZrgZfg
Load
Capacitive coupling caused by the common-mode voltage
Shaft voltage and bearing currents
Csf
ED
Stator winding
Motor frame
ED
Magnetic coupling
Crf1
Crf2
Shaft and frame impedance
Inductive coupling caused by the high dv/dt
Bearing failure
The shaft voltage causes electrical discharges in the bearing. Eventually the bearing fails because of electrical discharge machining (EDM)
Aggravating factors:• Rotor eccentricity• Eccentric load, for example a belt drive• Poor motor and load grounding• Insulated/not grounded load (for example a fan)• Dry atmosphere and applications where electrostatic charges can easily build-up, for example in the textile industry
Output filters
– Output Reactors– Motor Termination Unit– du/dt Filter– Sinusoidal Filter
Output Reactors
• Used to reduce du/dt• Can extend the duration of over-shoot if incorrectly selected
(double pulsing)• Reduces efficiency (0.5%)
Rise Time = 5 s Peak Voltage = 792 V
du/dt = 158 V/s
Motor Termination Unit• Series resistive/capacitive filters• As the capacitor charges, the current through the circuit reduces –
losses in resistor limited to the rising edge duration• Efficiency losses: 0.5 – 1.0%• Not a popular device
Peak Voltage = 800 V
du/dt FilterAdvantages:• Protects the motor against voltage peaks and high du/dt values
hence prolongs the motor lifetime• Allows the use of motors which are not specifically designed for
converter operation, for example in retrofit applications
L
L
L
M3~
PE
98
97
96
VLT Filter
W1
V1
U1
W2
V2
U2
CC
C
C
Application areas:• The typical application areas for dv/dt filters are:• Applications with frequent regenerative braking• Motors that are not rated for frequency converter operation and fed through very short motor
cables (less than 15 meters)• Motors placed in aggressive environments or running at high temperatures• Installations using old motors (retrofit) or general purpose motors according to IEC 60034-17
du/dt Filterdv/dt limit curves
150m
150m dv/dt filter
50m
50m dv/dt filter15m
15m dv/dt filter
0
0,2
0,4
0,6
0,8
1
1,2
1,4
1,6
1,8
0 0,5 1 1,5 2 2,5 3
tr [us]
Up
ea
k [
V]
IEC60034-25 A
IEC60034-17
Output du/dt Filter
Output voltage and current
Output Sine-wave FilterAdvantages:• Protects the motor against voltage peaks hence prolongs the lifetime• Reduces the losses in the motor• Eliminates acoustic switching noise from the motor • Reduces semiconductor losses in the drive with long motor cables• Decreases electromagnetic emissions from motor cables by
eliminating high frequency ringing in the cable• Reduces electromagnetic interference from unshielded motor cables• Reduces the bearing current thus prolonging the lifetime of the motor
L
L
L
M3~
PE
98
97
96
VLT Filter
W1
V1
U1
W2
V2
U2
CC
C
C
Output Sine-wave FilterThe typical applications of sine-wave filters are:• Applications where the acoustic switching noise from the motor has to be eliminated • Retrofit installations with old motors with poor insulation• Applications with frequent regenerative braking and motors that are not rated for
frequency converter operation• Applications where the motor is placed in aggressive environments or running at high
temperatures• Applications with motor cables above 100 meters up to 200 meters. The use of motor
cables longer than 200 meters depends on the specific application. (No influence on EMC performance)
• Applications where service interval on the motor has to be increased
L
L
L
M3~
PE
98
97
96
VLT Filter
W1
V1
U1
W2
V2
U2
CC
C
C
Output Sine-wave Filter
Output voltage and current
Output Sine-wave Filter
Relative Sound pressure measurements with and without filter
Filter drawings and infohttp://dd.danfoss.net/DD-CAT_ProductsServices_Products/PowerOptions/index.htm
Performance
Output Filter with DC-link
Connection
dv/dt Filte
rs
Sine-wave Filters
Output Filters
for Unshiel
ded Cables
Physical size (relative) 160% 60% 100% 30%
Cost (relative) 200% 40% 100% 30%
Losses (relative) 150% 50% 100% 10%
dv/dt according to NAMUR NE38 & IEC60034 X X X
Nominal cable length unlimited 50m 300m TBD
EMV compatible with unshielded cables ++ + ++
Limitations of leaking current ++
HF noise emissions from the motor cable ++ - - (+) ++
Motor insulations stress reduction ++ + ++
Motor bearing stress reduction ++ - + +
Multiple motors running in parallel ++ +
Reduced acoustic switching noise from motor ++ - +
20082008