16
Second Correlating Revision No. 1-NFPA 30-2016 [ Section No. 16.4.1 [Excluding any Sub-Sections] ] National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 10 12/12/2016 12:13 PM Page 1 of 16

Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

Second Correlating Revision No. 1-NFPA 30-2016 [ Section No. 16.4.1

[Excluding any Sub-Sections] ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 10 12/12/2016 12:13 PM

Page 1 of 16

Page 2: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

Where automatic sprinkler systems or low-expansion foam-water sprinkler systems are used toprotect storage of liquids, Figure 16.4.1(a), Figure 16.4.1(b), or Figure 16.4.1(c), whichever isapplicable, and the appropriate table in Section 16.5 shall be used to determine protectioncriteria.

Figure 16.4.1(a) Fire Protection Criteria Decision Tree for Miscible and NonmiscibleFlammable and Combustible Liquids in Metal Containers.

Figure 16.4.1(b) Fire Protection Criteria Decision Tree for Miscible and NonmiscibleFlammable and Combustible Liquids in Nonmetallic Containers.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 10 12/12/2016 12:13 PM

Page 2 of 16

Page 3: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

Figure 16.4.1(c) Fire Protection Criteria Decision Tree for Miscible Flammable andCombustible Liquids in Nonmetallic Containers.

Supplemental Information

File Name Description

Figure_16.4.1_a_.pdf

Submitter Information Verification

Submitter Full Name: Janna Shapiro

Organization: National Fire Protection Assoc

Street Address:

City:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 10 12/12/2016 12:13 PM

Page 3 of 16

Page 4: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

Protect using Table

16.5.2.1, 16.5.2.3, or

16.5.2.8

Page 4 of 16

Page 5: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

State:

Zip:

Submittal Date: Tue Oct 25 09:48:30 EDT 2016

Committee Statement

CommitteeStatement:

This correlating revision reverses the action to accept PC 67 and create SR 212.Because SR 210 failed ballot, SR 212 is no longer necessary.

Committee Comment No. 212-NFPA 30-2016 [Section No. 16.4.1 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 10 12/12/2016 12:13 PM

Page 5 of 16

Page 6: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

Second Correlating Revision No. 2-NFPA 30-2016 [ Section No. 16.5.1

[Excluding any Sub-Sections] ]

Paragraphs 16.5.2.1 through 16.5.2.12 and their related tables, Table 16.5.2.1 through Table16.5.2.12, shall be used to determine the protection criteria and storage arrangement for theapplicable liquid class, container type, and storage configuration, as described in 16.5.2.1through 16.5.2.12 and subject to the provisions of 16.5.1.

Submitter Information Verification

Submitter Full Name: Janna Shapiro

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 10:02:37 EDT 2016

Committee Statement

CommitteeStatement:

This correlating revision reverses the action to accept PC 52 and create SR 202.Because SR 210 failed ballot, SR 202 is no longer necessary.

Second Revision No. 202-NFPA 30-2016 [Section No. 16.5.1 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 10 12/12/2016 12:13 PM

Page 6 of 16

Page 7: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

Second Correlating Revision No. 3-NFPA 30-2016 [ Section No. 16.5.1.1

[Excluding any Sub-Sections] ]

Table 16.5.2.1 through Table 16.5.2.12 shall apply only to stable liquids.

Submitter Information Verification

Submitter Full Name: Janna Shapiro

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 10:05:57 EDT 2016

Committee Statement

CommitteeStatement:

This correlating revision reverses the action to accept PC 53 and create SR 203.Because SR 210 failed ballot, SR 203 is no longer necessary.

Second Revision No. 203-NFPA 30-2016 [Section No. 16.5.1.1 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 10 12/12/2016 12:13 PM

Page 7 of 16

Page 8: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

Second Correlating Revision No. 4-NFPA 30-2016 [ Section No. 16.5.1.11 ]

16.5.1.11

The “Fire Test Ref.” number given for each entry in Table 16.5.2.1 through Table 16.5.2.12shall be used to identify in Sections Section D.2 the information on the fire tests on which theprotection criteria for that entry are based.

Submitter Information Verification

Submitter Full Name: Janna Shapiro

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 10:11:58 EDT 2016

Committee Statement

CommitteeStatement:

This correlating revision reverses the action to accept PC 54 and create SR 204.Because SR 210 failed ballot, SR 204 is no longer necessary.

Committee Comment No. 204-NFPA 30-2016 [Section No. 16.5.1.11]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 10 12/12/2016 12:13 PM

Page 8 of 16

Page 9: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

Second Correlating Revision No. 5-NFPA 30-2016 [ New Section after 16.6.3 ]

Supplemental Information

File Name Description

30-SCR-5_current_16.6.4.docx

Submitter Information Verification

Submitter Full Name: Janna Shapiro

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 10:16:40 EDT 2016

Committee Statement

CommitteeStatement:

This correlating revision reverses the action to reject PC 57 but create related SR211. Because SR 210 failed ballot, SR 211 is no longer necessary.

Committee Comment No. 211-NFPA 30-2016 [New Section after 16.6.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 10 12/12/2016 12:13 PM

Page 9 of 16

Page 10: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

SCR-5, delete the following text: 16.6.4 Fire Protection System Design Scheme “E.”

16.6.4.1

Sprinklers and horizontal barriers shall be installed in accordance with Figure 16.6.4.1(a) or Figure 16.6.4.1(b), whichever is applicable. Horizontal barriers shall be of plywood having a minimum thickness of 3⁄8 in. (10 mm) or of sheet metal of minimum 22 gauge thickness. All liquid storage shall be located beneath a barrier.

Figure 16.6.4.1(a) Single-Row Rack Sprinkler Layout for Design Scheme "E."

Page 10 of 16

Page 11: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

Figure 16.6.4.1(b) Double-Row Rack Sprinkler Layout for Design Scheme "E."

Page 11 of 16

Page 12: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

16.6.4.2

Vertical baffles shall not be installed between in-rack sprinklers.

16.6.4.3

In-rack sprinklers shall meet the following requirements:

Page 12 of 16

Page 13: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

(1) In-rack sprinklers shall be intermediate temperature–rated, pendent sprinklers with a nominal K-factor of 25.2 and shall be listed as extended coverage control mode density/area storage sprinklers.

(2) In-rack sprinklers shall be positioned in a transverse flue below each barrier level.

(3) In-rack sprinklers shall not be positioned within 3.5 ft (1 m) of a rack upright.

(4) The minimum in-rack sprinkler discharge pressure shall not be less than a gauge pressure of 30 psi (207 kPa).

(5) Where one level of in-rack sprinklers is installed, the design shall include the 3 most hydraulically remote sprinklers on a single line.

(6) Where two levels of in-rack sprinklers are installed, the design shall include the 3 most hydraulically remote sprinklers on a single line, and the 2 most hydraulically remote sprinklers on the next adjacent level.

(7) Where three or more levels of in-rack sprinklers are installed, the design shall include the 3 most hydraulically remote sprinklers on a single line, and the 2 most hydraulically remote sprinklers on the next two adjacent levels.

(8) Foam-water sprinkler protection shall be permitted to be substituted for water sprinkler protection, provided the same design criteria is used, and that the sprinkler is listed for use with foam.

16.6.4.4

If there are adjacent bays of in-rack arrays that are not dedicated to storage of liquids, the barrier and in-rack sprinkler protection shall be extended at least 6 ft (1.8 m) beyond the area devoted to liquid storage.

16.6.4.5

Ceiling sprinkler demand shall not be included in the hydraulic calculations for in-rack sprinklers.

16.6.4.6

Water demand at point of supply shall be calculated separately for in-rack and ceiling sprinklers and shall be based on the greater demand.

16.6.4.7

Ceiling sprinklers shall meet the following requirements:

(1) Ceiling sprinkler protection shall be designed to protect the surrounding occupancy.

(2) Any sprinkler type shall be acceptable.

(3) If standard spray sprinklers are used, they shall be capable of providing not less than 0.30 gpm/ft2 over 3000 ft2 (8 mm/min over 270 m2) when supplied with water. Design area can be reduced to 2000 ft2 when using a preprimed foam-water system installed in accordance with NFPA 16 and maintained in accordance with NFPA 25.

(4) If the liquid storage does not extend to the full height of the rack, protection for commodities stored above the top horizontal barrier shall meet the requirements of NFPA 13 for the commodities stored, based on the full height of the rack.

16.6.4.8

A 500 gpm (1900 L/min) hose stream allowance shall be provided.

Page 13 of 16

Page 14: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

Second Correlating Revision No. 6-NFPA 30-2016 [ New Section after D.2 ]

Supplemental Information

File Name Description

30-SCR-6_current_D.3.docx

Submitter Information Verification

Submitter Full Name: Janna Shapiro

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 10:19:59 EDT 2016

Committee Statement

CommitteeStatement:

This correlating revision reverses the action to reject PC 65 but create related SR206. Because SR 210 failed ballot, SR 206 is no longer necessary.

Committee Comment No. 206-NFPA 30-2016 [New Section after D.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 10 12/12/2016 12:13 PM

Page 14 of 16

Page 15: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

SCR-6, delete the following text: D.3 Design Criteria for Sprinkler Protection of Single- and Double-Row Rack Storage of Class II and Class III Liquids.

Fire protection criteria in 16.5.2.13, Table 16.5.2.13, and 16.6.4 are based on a fullscale fire test documented in the Underwriters Laboratories Inc. report, “Class II Combustible Liquids in 55-Gallon Steel Drums Stored in Racks with Continuous Combustible Horizontal Barriers Protected by K=25.2 EC In-Rack Sprinklers.”

Page 15 of 16

Page 16: Second Correlating Revision No. 1-NFPA 30-2016 [ Section ......ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce Contact Burn Injuries, 2003 (reapproved

Second Correlating Revision No. 7-NFPA 30-2016 [ Section No. I.1.2.6 ]

I.1.2.6 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA19428-2959.

ASTM C1055, Standard Guide for Heated System Surface Conditions that Produce ContactBurn Injuries, 2003 (reapproved 2014).

ASTM D4206, Standard Test Method for Sustained Burning of Liquid Mixtures Using the SmallScale Open-Cup Apparatus, 1996 (reapproved 2013).

ASTM D4207, Standard Test Method for Sustained Burning of Low Viscosity Liquid Mixturesby the Wick Test, 1991 (withdrawn 1998) .

ASTM D4956, Standard Specification for Retroreflective Sheeting for Traffic Control, 2013.

ASTM D6469, Standard Guide for Microbial Contamination in Fuels and Fuel Systems, 2014.

ASTM E119, Standard Test Methods for Fire Tests of Building Construction and Materials,2015 2016 .

ASTM E502, Standard Test Method for Selection and Use of ASTM Standards for theDetermination of Flash Point of Chemicals by Closed Cup Methods, 2007e1 (reapproved2013).

Manual on Flash Point Standards and Their Use, 1992.

Submitter Information Verification

Submitter Full Name: Janna Shapiro

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 10:28:23 EDT 2016

Committee Statement

CommitteeStatement:

This correlating revision reverses the action to accept PC 6 and create SR 3.Because PC 5 (proposed addition of ASTM E 1529 to A.22.5.2.4) was rejected, SR 3(addition of reference to Annex I) is no longer necessary.

Second Revision No. 3-NFPA 30-2016 [Section No. I.1.2.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 10 12/12/2016 12:13 PM

Page 16 of 16