Version 6 SE8300 Series Installation Guide 24 Vac Low Voltage Commercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 2 Terminal Identification & Function 3 Terminal identification 3 Wiring 4 Typical Applications 5 2 pipe systems cooling and/or heating 6 4 pipe systems cooling and heating 7 2 pipe systems cooling or heating with reheat 7 Remote Sensor Accessories 8 Home Screen Display 9 How to Enter Setup Screen 10 Appendix 11 Support 12

SE8300 Series Installation Guide - Schneider Electric

  • Upload
    others

  • View
    11

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SE8300 Series Installation Guide - Schneider Electric

Version 6

SE8300 Series Installation Guide24 Vac Low Voltage Commercial and Hotel/Lodging HVAC Fan Coil Applications

CONTENTS

Installation 2Terminal Identification & Function 3 Terminal identification 3 Wiring 4Typical Applications 5 2 pipe systems cooling and/or heating 6 4 pipe systems cooling and heating 7 2 pipe systems cooling or heating with reheat 7Remote Sensor Accessories 8Home Screen Display 9How to Enter Setup Screen 10Appendix 11Support 12

Page 2: SE8300 Series Installation Guide - Schneider Electric

2

Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017

• If replacing an existing Room Controller, label wires before removal of Controller.

• Electronic controls are static sensitive devices. Discharge yourself correctly before manipulating and installing Room Controller.

• A short circuit or wrong wiring may permanently damage Room Controller or equipment.

• All SE8300 series controls are designed for use as operating controls only and are not safety devices. Tampering with the devices or unintended application of the devices will result in a void of warranty.

• This device must be installed to provide a separation distance of at least 8in (20cm) from all persons and must not be located or operating in conjunction with any other antenna or transmitter.

Figure-1 Open the cover

Figure-2 Install the base

Figure-3 Reinstall cover

INSTALLATION

Location

• Do not install on outside wall.• Do not install in areas with direct heat source.• Do no install near any air discharge grill.• Do not install in areas exposed to direct sunlight.• Ensure Controller has sufficient air circulation.

• Ensure wall surface is flat and clean.

Installation

1. Remove security screw (if any) on bottom of Room Controller cover.

2. Open unit by pulling on bottom side of Room Controller (Figure 1).3. Read FCC ID and IC label installed in cover before installing any

wireless product.4. Ensure correct side of base faces up. 5. Pull cables 6in (15cm) out from wall.6. Align base and mark location of two mounting holes on wall.7. Install anchors in wall (Figure 2).8. Insert cable in central hole of base.9. Insert screws in mounting holes on each side of base.10. Strip each wire 1/4in ( 0.6cm) from end.11. Insert each wire and screw according to wiring chart.12. Gently push excess wiring back into hole.13. Gently align cover to top of base and snap in place from bottom

(Figure 3).14. Install security screw.

Page 3: SE8300 Series Installation Guide - Schneider Electric

3

Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017

CLEANING SE8300 ROOM CONTROLLER

• Use a soft, pre-moistened lint-free cloth for cleaning.• Avoid getting moisture in openings.• Do not spray anything directly on SE8000 Room Controller or use compressed air.• Do not use caustic/corrosive products, ammonia, solvents or any cleaning product containing alcohol or grit.• Never use tools directly on the touchscreen.• Never use paint on SE8000 Room Controller.• Do not drop or crush SE8000 Room Controller, or allow SE8000 Room Controller to come into contact with

liquids.• Do not use a damaged device (such as one with a cracked screen).• Functionality guarantees are no longer valid if the glass on the screen is broken.Failure to comply with these recommendations will result in damage to the unit and void the manufacturer’s warranty.

Page 4: SE8300 Series Installation Guide - Schneider Electric

4

Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017

SE83xxU

Description / ApplicationUsed in applications

2 & 4 Pipe 2 & 4 Pipe 2 & 4 Pipe

Control Type = On/Off Control Type = Floating Control Type = Analog

Internal Temperature X X X

Internal Humidity Model Dependent Model Dependent Model Dependent

1- BO1 Not used Not used Not used

2- BO2 Fan-L Fan-L Fan-L

3- BO3 Fan-M Fan-M Fan-M

4- BO4 Fan-H Fan-H Fan-H

5- RC / 24 V~ Hot 24 V~ Hot 24 V~ Hot 24 V~ Hot

6- C / 24 V~ Com 24 V~ Com 24 V~ Com 24 V~ Com

7- RH Aux Heat Aux Heat Aux Heat

8- BO8 Aux Heat Aux Heat Aux Heat

9- UO9 Normally Close Cool Valve Close Cool Valve Not used

10- UO10 Normally Close Heat Valve Close Heat Valve Not used

11- UO11 Normally Open Cool Valve Open Cool Valve Analog Heat valve

12- UO12 Normally Open Heat Valve Open Heat Valve Analog Cool Valve

13- RS485 + BACnet MS-TP + BACnet MS-TP + BACnet MS-TP +

14- RS485 - BACnet MS-TP - BACnet MS-TP - BACnet MS-TP -

15- RS485 Ref BACnet MS-TP Ref BACnet MS-TP Ref BACnet MS-TP Ref

16- UI16 UI16 Function UI16 Function UI16 Function

17- UI17 UI17 Function UI17 Function UI17 Function

18 Scom Common Common Common

19- UI19 UI19 Function UI19 Function UI19 Function

20- UI20 Remote Room Sensor Remote Room Sensor Remote Room Sensor

21 Scom Common Common Common

22- UI22 Remote Supply Sensor Remote Supply Sensor Remote Supply Sensor

23- UI23 Not used Not used Not used

24- UI24 Not used Not used Not used

TERMINAL IDENTIFICATION AND FUNCTION

Terminal identification

Page 5: SE8300 Series Installation Guide - Schneider Electric

5

Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017

Wiring

Main outputs wiring2 Pipe Applications 4 Pipe Applications

Control type = On-Off

2 Pipe Applications

OR

Heating / Cooling valve

Com24Vac

UO9

UO11

ComOpenClose

Com24Vac0-10Vdc

Com24 Vac0-10 Vdc

Com24 Vac0-10 Vdc

Com24Vac

Com24Vac

ComOpenClose

ComOpenClose

4 Pipe Applications

Heating valve

Cooling valveOR

ORUO10 NC

UO12 NO

UO 09 NC

UO11 NO

ComOpenClose

Com24Vac0-10Vdc

Com24 Vac0-10 Vdc

Com24 Vac0-10 Vdc

Com24Vac

Com24Vac

ComOpenClose

ComOpenClose

Floating control

2 Pipe Applications 4 Pipe Applications

Heating / Cooling valveUO11

UO9

ComOpenClose

Com24Vac0-10Vdc

Com24 Vac0-10 Vdc

Com24 Vac0-10 Vdc

Com24Vac

Com24Vac

ComOpenClose

ComOpenClose

Heating valve

Cooling valve

UO12

UO10

UO11

UO9

ComOpenClose

Com24Vac0-10Vdc

Com24 Vac0-10 Vdc

Com24 Vac0-10 Vdc

Com24Vac

Com24Vac

ComOpenClose

ComOpenClose

Analog control

Heating / Cooling valve

UO12

ComOpenClose

Com24Vac0-10Vdc

Com24 Vac0-10 Vdc

Com24 Vac0-10 Vdc

Com24Vac

Com24Vac

ComOpenClose

ComOpenClose

Heating valve

Cooling valve

UO11

UO12

ComOpenClose

Com24Vac0-10Vdc

Com24 Vac0-10 Vdc

Com24 Vac0-10 Vdc

Com24Vac

Com24Vac

ComOpenClose

ComOpenClose

BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 Vac)

C (Common)

3 Speed 2 Speed Single speed

HIGH HIGH

MED

LOW LOW

HIGH

Power & Fan ( All models )

24 VacTransformer

3 Speed 2 Speed Single speed

HIGH HIGH

MED

LOW LOW

HIGH

RC (24 Vac)

C (Common)

RH

BO8 - Aux Heat

BO8 Auxiliary output wiringDry contact to end device 24 Vac maximum

R

RC (24 Vac)

C (Common)

RH

BO8 - Aux Heat

24 Vac power to relay

R

Page 6: SE8300 Series Installation Guide - Schneider Electric

6

Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017

TYPICAL APPLICATIONS

Schematic Wiring Settings

2 pipe system cooling and/or heating Control type = On / Off

Cooling / Heating

Valve

3 Speed Fan

Sensor

Normally ClosedOn/Off

Room TemperatureControl Thermostat

BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 Vac)

C (Common)

RH

BO8 - Aux Heat

UO9 NC

UO10

UO11

UO12

24 Vac fan relays

24 Vac Transformer

HIGH

MED

LOW

Common

UI 19

Normally Closed

Optional supply watertemperature sensor

2

3

4

5

6

7

8

9

10

11

12

18

19

Mandatory• Pipe no = 2 pipes• CntrltTyp = On/Off• Fan Menu = 0 (L-M-H)• FL time = N/A

If cooling only set:• SeqOpera = Cooling only

If heating only set:• SeqOpera = Heating only

If heat / cool auto-changeover with a local water temperature sensor set:• SeqOpera = Cooling only• UI19 = COS

2 pipe system cooling and/or heatingControl type = Floating

Page 7: SE8300 Series Installation Guide - Schneider Electric

7

Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017

Schematic Wiring Settings

Cooling / Heating

Valve

3 Speed Fan

Sensor

Modulating Floating

Room TemperatureControl Thermostat

BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 Vac)

C (Common)

RH

BO8 - Aux Heat

UO9

UO10

UO11

UO12

24 Vac fan relays

24 Vac Transformer

HIGH

MED

LOW

Common

UI19

Normally Closed

Optional supply watertemperature sensor

2

3

4

5

6

7

8

9

10

11

12

18

19

Mandatory• Pipe no = 2 pipes• CntrltTyp = Floating• Fan Menu = (L-M-H)• FL time = as per actuator

If cooling only set:• SeqOpera = Cooling only

If heating only set:• SeqOpera = Heating only

If heat / cool auto-changeover with a local water temperature sensor set:• SeqOpera = Cooling only• UI19 = COS

2 pipe system cooling and/or heatingControl type = Analog

Cooling / Heating

Valve

3 Speed Fan

Sensor

Modulating Analog

Room TemperatureControl Thermostat

BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 Vac)

C (Common)

RH

BO8 - Aux Heat

UO9

UO10

UO11

UO12

24 Vac fan relays

24 Vac Transformer

HIGH

MED

LOW

Common

UI 19

Normally Closed

Optional supply watertemperature sensor

2

3

4

5

6

7

8

9

10

11

12

18

19

0 to 10Vdc

Mandatory• Pipe no = 2 pipes• CntrltTyp = Analog• Fan Menu = (L-M-H)• RA/DA = as per actuator

If cooling only set:• SeqOpera = Cooling only

If heating only set:• SeqOpera = Heating only

If heat / cool auto-changeover with a local water temperature sen-sor set:• SeqOpera = Cooling only• UI19 = COS

4 pipe system cooling and heatingControl type = On / Off

Heating

Valve

3 Speed FanNormally Closed

On/Off

Room TemperatureControl Thermostat

Cooling

Valve

Mandatory• Pipe no = 4 pipes• CntrltTyp = On/Off• Fan Menu = (L-M-H)• SeqOpera = Cool/Heat

BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 Vac)

C (Common)

RH

BO8 - Aux Heat

UO9 NC

UO10

UO11 NC

UO12

24 Vac fan relays

24 Vac Transformer

HIGH

MED

LOW

Heating

2

3

4

5

6

7

8

9

10

11

12Cooling

Normally Closed

Page 8: SE8300 Series Installation Guide - Schneider Electric

8

Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017

Schematic Wiring Settings

4 pipe system cooling and heatingControl type = Floating

Heating

Valve

3 Speed Fan Modulating Floating

Room TemperatureControl Thermostat

Cooling

Valve

BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 Vac)

C (Common)

RH

BO8 - Aux Heat

UO9

UO10

UO11

UO12

24 Vac fan relays

24 Vac Transformer

HIGH

MED

LOW

Heating

2

3

4

5

6

7

8

9

10

11

12 Cooling

Mandatory• Pipe no = 4 pipes• CntrltTyp = Floating• Fan Menu = (L-M-H)• FL time = as per actuator• SeqOpera = Cool/Heat

4 pipe system cooling and heatingControl type = Analog

Heating

Valve

3 Speed Fan Modulating Analog

Room TemperatureControl Thermostat

Cooling

Valve

BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 Vac)

C (Common)

RH

BO8 - Aux Heat

UO9

UO10

UO11

UO12

24 Vac fan relays

24 Vac Transformer

HIGH

MED

LOW

Heating

2

3

4

5

6

7

8

9

10

11

12 Cooling

0 to 10Vdc

0 to 10Vdc

Mandatory• Pipe no = 4 pipes• CntrltTyp = Analog• Fan Menu = (L-M-H)• RA/DA = as per actuator• SeqOpera = Cool/Heat

2 pipe system cooling or heating with reheatControl type = Floating

ElectricReheat

3 Speed FanModulating Floationg

Room TemperatureControl Thermostat

Cooling / Heating

Valve

Sensor

BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 Vac)

C (Common)

RH

BO8 - Aux Heat

UO9

UO10

UO11

UO12

24 Vac fan relays

24 Vac Transformer

HIGH

MED

LOW

SCom

UI 19Optional supply watertemperature sensor

2

3

4

5

6

7

8

9

10

11

12

18

19

ElectricReheat

Normally Closed

Mandatory• Pipe no = 2 pipes• CntrltTyp = Floating• Fan Menu = (L-M-H)• FL time = as per actuator• SeqOpera = Cool/Reheat• UI19 = COS

Page 9: SE8300 Series Installation Guide - Schneider Electric

9

Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017

REMOTE SENSOR ACCESSORIES

Model no. Description

S3010W1000 Wall mounted temperature sensor

S3020W1000 Wall mounted temperature sensor with override button and occupancy status LED

The SE8300 Room Controller is compatible with remote mount temperature sensors using 10K type 2 NTC thermistors.

Note:If one or multiple sensor(s) is/are connected into the RS terminal, the internal temperature sensor is automatically disabled. Disconnecting the sensor(s) in the RS terminal will re-activate the internal sensor.

Features:• Each sensor can be configured for various averaging combinations (refer to S3000 series remote sensors for more details)• Optional occupancy led• Optional override key

Wiring example of single remote room sensor:

Common

UI 20

BO8

24 Vac Com

UI17

SE8300Series Controller

S3020W1045Remote wiring 1 sensorS2-1= On, S2-2=On

S3010W1045Remote wiring 1 sensorS2-1= On, S2-2=On

SCom

RS

Aux

C

DI

SCom

RSOR

Temperature vs. resistance chart for 10 Kohm NTC thermistor (R25°C = 10KΩ±3%, B25/85°C = 3975K±1.5%)

ºC ºF Kohm ºC ºF Kohm ºC ºF Kohm ºC ºF Kohm ºC ºF Kohm

-40 -40 324.3197 -20 -4 94.5149 0 32 32.1910 20 68 12.4601 40 104 5.3467

-35 -31 234.4009 -15 5 71.2430 5 41 25.1119 25 77 10.0000 45 113 4.3881

-30 -22 171.3474 -10 14 54.1988 10 50 19.7390 30 86 8.0694 50 122 3.6202

-25 -13 126.6109 -5 23 41.5956 15 59 15.6286 35 95 6.5499 55 131 3.0016

Dip switchsetting for:1 sensor

S2-1 = ON

S2-2 = ON

ON

1 2

Page 10: SE8300 Series Installation Guide - Schneider Electric

10

Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017

Date Time

Occupancy Status Fan Status

System Status

Up ArrowRaise Temperature Setpoint

Actual SetpointRoom Indoor Temperature

Room Indoor Humidity

Outdoor Temperature

Down ArrowLower Temperature Setpoint

System ModeSelect system mode

Temperature UnitsSelect Celsius or Fahrenheit

HelpEnter help screen

LanguageSelect preferred language

Fan ModeSelect fan mode

HOME SCREEN DISPLAY

Hospitality User Interface Shown

Short Network Message

Note: User HMI is configurable and allows display functions such as Date, Time, Humidity, Outdoor Temperature, Setpoint, and others to be enabled or disabled by setting various parameters.

Page 11: SE8300 Series Installation Guide - Schneider Electric

11

Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017

Return to home screen

1/2 Setup

Network

Configuration

Setpoints - Display

Service view

Test outputs

Language selection

Discover Mode The Controller becomes discoverable on the wireless

ZigBee® network for 1 minute (this

button is hidden if ZigBee® settings are not configured)

HOW TO ENTER SET-UP SCREEN

Touch and hold this point for 3 seconds to enter set-up mode

SET-UP SCREEN DISPLAY

General Note:

Adjustable parameter

Non-adjustable parameter

Note: If a configuration/installer password is activated to prevent unauthorised access to the configuration menu parameters, a password entry prompt shows to prevent access to device configuration components.

Enter BACnet® & ZigBee® network settings

Enter parameter configuration menu

Enter setpoint & display settings

Enter output testing mode

Enter status and service view

For more information on using and configuring the functions of the HMI, refer to the following document:SE8300 User Interface Guide

Enter language selection

Page 12: SE8300 Series Installation Guide - Schneider Electric

12

Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017

APPENDIX A TERMINAL CORRESPONDENCE

The terminals of a SE8300 are identified differently and have a wider range of possible functions compared to those of any of the SE7000 series Room Controllers. Nonetheless, there is a direct correspondence of functions between the terminals of the SE7000 series and the SE8300 series. Consult the table below to verify the appropriate terminal when replacing a SE7000 Room Control-ler with a SE8300 Room Controller.

SE7000 SE8300

Terminal name Terminal ID Terminal name Terminal ID

Binary Input 1 BI1 Universal Input 16 UI16

Binary Input 2 BI2 Universal Input 17 UI17

Universal Input 3 UI3 Universal Input 19 UI19

Sensor Common Scom Terminal 18 Common COM

Remote Sensor RS Universal Input 20 UI20 - RS

Sensor Common Scom Terminal 21 Common COM

Mix/Supply Sensor MS Universal Input 22 UI22 - SS

APPENDIX B POWER OUTAGE CLOCK RESET

In the event of a power outage, SE8300 Room Controllers retain the correct time as long as the duration of the power outage is not prolonged. Depending on the duration of the power outage, the Room Controllers internal clock may need to be updated or reset completely. The following table gives an indication of the expected clock performance after a power outage of a given duration.

Outage duration Room Controller behavior0 - 24 hours Clock functions are normal

24 - 36 hours Clock accuracy not guaranteed, time may need to be adjusted

36 - 72 hours Clock no longer increments and will need to be adjusted when power is restored.

72+ hours Clock functions are fully reset, and will need to be reinitialized as per a new installation.

Page 13: SE8300 Series Installation Guide - Schneider Electric

13

Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017

Technical SupportFor any issues with SmartStruxure Solution or SmartStruxure Lite, contact Schneider Electric Technical Support according to your region.

North America (NAM) Product Support

Building Management Systems

[email protected]

Field Devices

[email protected]

Global Product Support

Building Management Systems

[email protected]

Field Devices

[email protected]

Schneider Electric is the global specialist in energy management and automation. With rev-

enues of ~€25 billion in FY2016, our 160,000+ employees serve customers in over 100 coun-

tries, helping them to manage their energy and process in ways that are safe, reliable, efficient

and sustainable. From the simplest of switches to complex operational systems, our technol-

ogy, software and services improve the way our customers manage and automate their opera-

tions. Our connected technologies reshape industries, transform cities and

enrich lives.

At Schneider Electric, we call this Life Is On.