700A11Geothermal Heat Pump
3-5 ton (variable speed)
Submittal Data
English Language/IP Units
SD2700ANA 02/21
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 2 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Model Nomenclature
N V V 036 C 1 0 1 C T L 0 J1 2 3 4-6 7 8 9 10 11 12 13 14 15
Model N – 7 Series Water-to-Air
Compressor Type V – Variable Speed
Cabinet Configuration V – Vertical H – Horizontal
Unit Capacity MBTU’s 036,048,060
Vintage C– 036-060
Voltage 1 – 208-230/60/1
Hot Water Options 0 – No Hot Water 1 – Hot Water Generation with Factory Installed Pump
Blower Motor Options 1 – Variable Speed ECM Blower 2 – High Static Variable Speed ECM (036 Only)
Air Coil Option N – All Aluminum PinnaCoil™
Controls Option J – Aurora Variable Speed Control K – Aurora VS Control w/ Performance Monitoring L – Aurora Variable Speed Control with UPC1 M – Aurora VS Control w/ Performance Monitoring and UPC1
Filter Options 0 – 2 inch MERV11 Filter 1 – AlpinePure 411 (Vertical Only)
Return Air Configuration L – Left R – Right
Discharge Configuration T – Top (Vertical) B – Bottom (Vertical) R – Rear (Vertical) S – Side (Horizontal) E – End (Horizontal)
Water Coax C – Copper N – CuproNickel
Rev.: 1/22/2021
Notes:1 UPC is not compatible with Symphony or IntelliZone2
N16
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 3 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Energy Star Rating CriteriaIn order for water-source heat pumps to be Energy Star rated they must meet or exceed the minimum efficiency requirements listed below. Tier 3 represents the current minimum efficiency water source heat pumps must have in order to be Energy Start rated. Tier 3: 1/1/2012 – No Effective End Date Published
Water-to-Air EER COPGround Loop 17.1 3.6Ground Water 21.1 4.1
Water-to-WaterGround Loop 16.1 3.1Ground Water 20.1 3.5
Energy Star Compliance Table
ModelTier 3
Ground Water Ground Loop
036 Yes Yes
048 Yes Yes
060 Yes Yes
6/1/12
Variable Speed ECM MotorAHRI/ASHRAE/ISO 13256-1English (IP) Units
ModelCapacity
Modulation
Flow Rate Clg/Htg
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling EWT 86°F
Heating EWT 68°F
Cooling EWT 59°F
Heating EWT 50°F
Cooling Full Load 77°F Part Load 68°F
Heating Full Load 32°F Part Load 41°F
cfm Capacity
Btuh EER
Btuh/W Capacity
Btuh COP
Capacity Btuh
EER Btuh/W
Capacity Btuh
COP Capacity
Btuh EER
Btuh/W Capacity
Btuh COP
036Full
1300/1500 32,300 17.7 51,000 5.3 38,000 31.2 41,700 4.5 35,800 21.6 32,900 3.5
Part 11,000 21.1 17,000 7.6 12,500 50.0 14,000 5.9 13,400 39.0 12,000 5.1
048Full
1500/1800 40,700 16.9 67,000 4.9 49,000 30.0 55,200 4.0 45,000 20.0 43,500 3.4
Part 16,000 24.0 24,000 7.8 19,000 56.0 19,000 6.0 18,000 43.5 16,300 5.1
060Full
1800/2200 50,000 15.9 79,000 4.9 60,000 27.1 66,000 4.3 56,000 19.1 51,700 3.4
Part 20,100 22.3 29,100 7.6 22,500 55.0 23,000 5.8 22,800 40.0 20,000 5.1
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature 1/15/21
Heating capacities based upon 68°F DB, 59°F WB entering air temperature
All ratings based upon 208V operation
AHRI/ISO 13256-1 Performance Ratings
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 4 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Top Air Discharge
Vertical Top Flow Model
Overall Cabinet Water ConnectionsElectrical
ConnectionsDischarge Connection
duct flange installed (±0.10 in)
Return Connectionusing std deluxe filter rack
(±0.10 in)
AWidth
BDepth
CHeight
DLoop
In
ELoop Out
FHWG
In
GHWG Out
HCond- ensate
Loop Water FPT
HWG Sweat (I.D.)
I 1/2 in. cond
J 1/2 in. cond
K 3/4 in. cond L M
NSupply Width
OSupply Depth
P QR
Return Depth
SReturn Height
TLow
VoltageExt
PumpPower Supply
036in. 25.6 31.6 54.4 2.3 7.3 15.9 18.9 10.6 1 in.
Swivel1/2 in. Female
14.3 9.8 12.3 6.9 1.1 18.0 18.0 3.8 1.7 28.1 30.0 1.7
cm. 65.0 80.3 138.2 5.8 18.5 40.4 48.0 26.9 36.3 24.9 31.2 17.5 2.8 45.7 45.7 9.7 4.3 71.4 76.2 4.3
048in. 25.6 31.6 54.4 2.3 7.3 15.9 18.9 10.6 1 in.
Swivel1/2 in. Female
14.3 9.8 12.3 6.9 1.1 18.0 18.0 3.8 1.7 28.1 30.0 1.7
cm. 65.0 80.3 138.2 5.8 18.5 40.4 48.0 26.9 36.3 24.9 31.2 17.5 2.8 45.7 45.7 9.7 4.3 71.4 76.2 4.3
060in. 25.6 31.6 58.4 2.3 7.3 15.9 18.9 10.6 1 in.
Swivel1/2 in. Female
14.3 9.8 12.3 6.9 1.1 18.0 18.0 3.8 1.7 28.1 34.0 1.7
cm. 65.0 80.3 148.3 5.8 18.5 40.4 48.0 26.9 36.3 24.9 31.2 17.5 2.8 45.7 45.7 9.7 4.3 71.4 86.4 4.3
Condensate is 3/4 in. PVC female glue socket and is switchable from side to frontUnit shipped with deluxe 2 in. (field adjustable to 1 in.) duct collar/filter rack extending from unit 3.25 in. and is suitable for duct connection.Discharge flange is field installed and extends 1 in. [25.4mm] from cabinetDecorative molding and/or water connections extend 1.2 in. [30.5mm] beyond front of cabinet.Louvered vents in the compressor section right side access panel extend 1/2 in. [12.7 mm] from side of cabinet. Allow 6" clearance for venting.
6/29/12
LEFT RETURN RIGHT RETURN
FRONT
TOP TOP
A D E H FI K J G
1.9in[4.8cm]
1.9in[4.8cm]
M
R
Q
N
OL
RN
O
L
P Q
RIGHT SIDEB
C
B
LEFT SIDE
S
T
S
T
C
Vertical Dimensional Data
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 5 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Bottom Air Discharge
Bottomflow Models
Overall Cabinet
Water Connections Electrical KnockoutsDischarge Connection
duct flange installed (±0.10 in)
Return Connectionusing std deluxe filter rack
(±0.10 in)1 2 3 4 5Loop Water FPT
HWG Sweat (I.D.)
I1/2 in. cond
J1/2 in. cond
K3/4 in. cond
AWidth
BDepth
CHeight
DIn
EOut
FHWG
In
GHWG Out
HCond-ensate
Low Voltage
Ext Pump
Power Supply
L MN
Supply Width
OSupply Depth
P QR
Return Depth
SReturn Height
T
036-060
in. 25.5 31.5 62.5 43.4 48.4 57.0 60.0 3.1 1 in. Swivel
1/2 in. Female
51.1 55.6 53.6 9.1 4.8 13.4 13.6 1.7 1.8 28.1 34.0 5.6
cm. 64.8 80.0 158.8 110.2 122.9 144.8 152.4 7.9 129.8 141.2 136.1 23.1 12.2 34.0 34.5 4.3 4.6 71.4 86.4 14.2
Condensate is 3/4 in. PVC female glue socket and is switchable from side to frontUnit shipped with deluxe 2 in. (field adjustable to 1 in.) duct collar/filter rack extending from unit 3.25 in. and is suitable for duct connection.Water connections extend 1.2 in. [30.5mm] beyond front of cabinet.Louvered vents in the compressor section right side access panel extend 1/2 in. [12.7 mm] from side of cabinet. Allow 6" clearance for venting.
4/30/12
LEFT SIDE RIGHT SIDE
B
C
S
T T
B
C
S
LEFT RETURN RIGHT RETURN
R Q
LN
O
P
A
FRONT
D
E
FG
H
JKI
1.90(4.7 cm)
1.70(4.3 cm)
1
2
3
4
5
RIGHT BOTTOM DISCHARGE FLOOR FOOT PRINT
R
O
N
L
M
LEFT BOTTOM DISCHARGE FLOOR FOOT PRINT
Q
Vertical Dimensional Data cont.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 6 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Rear Air Discharge
Verti-cal Rear
Discharge Model
Overall Cabinet Water ConnectionsElectrical
ConnectionsDischarge Connection
duct flange installed (±0.10 in)
Return Connectionusing std deluxe filter rack
(±0.10 in)
AWidth
BDepth
CHeight
DLoop
In
ELoop Out
FHWG
In
GHWG Out
HCond- ensate
Loop Water FPT
HWG Sweat (I.D.)
I1/2 in. cond
J1/2 in. cond
K 3/4 in. cond
LSupply Width
MSupply Depth
N O P QR
Return Depth
SReturn Height
TLow
VoltageExt
PumpPower Supply
036in. 25.6 31.6 54.4 2.3 7.3 15.9 18.9 10.6 1 in.
Swivel1/2 in. Female
14.3 9.8 12.3 13.3 13.6 39.4 9.1 8.1 1.7 28.1 30.0 1.7
cm. 65.0 80.3 138.2 5.8 18.5 40.4 48.0 26.9 36.3 24.9 31.2 33.8 34.5 100.1 23.1 20.6 4.3 71.4 76.2 4.3
048in. 25.6 31.6 54.4 2.3 7.3 15.9 18.9 10.6 1 in.
Swivel1/2 in. Female
14.3 9.8 12.3 13.3 13.6 39.4 9.1 8.1 1.7 28.1 30.0 1.7
cm. 65.0 80.3 138.2 5.8 18.5 40.4 48.0 26.9 36.3 24.9 31.2 33.8 34.5 100.1 23.1 20.6 4.3 71.4 76.2 4.3
060in. 25.6 31.6 58.4 2.3 7.3 15.9 18.9 10.6 1 in.
Swivel1/2 in. Female
14.3 9.8 12.3 13.3 13.6 43.4 9.1 8.1 1.7 28.1 34.0 1.7
cm. 65.0 80.3 148.3 5.8 18.5 40.4 48.0 26.9 36.3 24.9 31.2 33.8 34.5 110.2 23.1 20.6 4.3 71.4 86.4 4.3
Condensate is 3/4 in. PVC female glue socket and is switchable from side to frontUnit shipped with deluxe 2 in. (field adjustable to 1 in.) duct collar/filter rack extending from unit 3.25 in. and is suitable for duct connection.Discharge flange is field installed and extends 1 in. [25.4mm] from cabinetDecorative molding and/or water connections extend 1.2 in. [30.5mm] beyond front of cabinet.Louvered vents in the compressor section right side access panel extend 1/2 in. [12.7 mm] from side of cabinet. Allow 6" clearance for venting.
6/29/12
REAR VIEWLEFT RETURN
SIDE VIEWRIGHT RETURN
SIDE VIEWLEFT RETURN
REAR VIEWRIGHT RETURN
FRONT
C C C C
A A
A
B B
D
EH
F G
JKI
L
M
N
M
N
PO QQ R R
S S
T T
1.90 in. [4.8 cm]1.90 in.
[4.8 cm]
2 ft [61 cm]Primary Service Access
Vertical Dimensional Data cont.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 7 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Units Not Shown Above L O
Right Return End Dischargein 2.8 4.6
cm 7.1 11.8
Right Return Side Dischargein 4.9 6.9
cm 12.4 17.5
Left Return End Dischargein 4.9 7.6
cm 12.4 19.4
Left Return Side Dischargein 2.8 6.9
cm 7.1 17.5
Horizontal Models
Overall Cabinet Water Connections
Electrical ConnectionsDischarge Connection
duct flange installed (±0.10 in)
Return Connectionusing std deluxe filter rack
(±0.10 in)
I 1/2 in. cond
J 1/2 in. cond
K 3/4 in. cond
AWidth
BDepth
CHeight
DIn
EOut
FHWG
In
GHWG Out
HCond- ensate
Loop Water FPT
HWG Sweat (I.D.)
Low Voltage
Ext Pump
Power Supply
LM
Supply Height
NSupply Depth
O PQ
Return Depth
RReturn Height
S
036in. 25.6 77.0 21.3 2.3 7.3 15.9 18.9 0.8 1 in.
Swivel1/2 in.
Female
14.3 9.8 12.3 SEE CHART
13.6 13.2 SEE CHART
2.8 40.4 18.9 1.3
cm. 65.0 195.6 54.1 5.8 18.5 40.4 48.0 2.0 36.3 24.9 31.2 34.5 33.5 7.1 102.6 48.0 3.3
048in. 25.6 77.0 21.3 2.3 7.3 15.9 18.9 0.8 1 in.
Swivel1/2 in.
Female
14.3 9.8 12.3 SEE CHART
13.6 13.2 SEE CHART
2.8 40.4 18.9 1.3
cm. 65.0 195.6 54.1 5.8 18.5 40.4 48.0 2.0 36.3 24.9 31.2 34.5 33.5 7.1 102.6 48.0 3.3
060in. 25.6 82.0 21.3 2.3 7.3 15.9 18.9 0.8 1 in.
Swivel1/2 in.
Female
14.3 9.8 12.3 SEE CHART
13.6 13.2 SEE CHART
2.8 45.4 18.9 1.3
cm. 65.0 208.3 54.1 5.8 18.5 40.4 48.0 2.0 36.3 24.9 31.2 34.5 33.5 7.1 115.3 48.0 3.3
Condensate is 3/4 in. PVC female glue socket and is switchable from side to frontUnit shipped with deluxe 2 in. (field adjustable to 1 in.) duct collar/filter rack extending from unit 3.25 in. and is suitable for duct connection.Discharge flange is field installed and extends 1 in. [25.4mm] from cabinetDecorative molding and/or water connections extend 1.2 in. [30.5mm] beyond front of cabinet.Louvered vents in the compressor section right side access panel extend 1/2 in. [12.7 mm] from side of cabinet. Allow 6" clearance for venting.
6/29/12
2 ft [61 cm]Primary Service Access
B
C
2.1in[5.4cm]
H
LON
M
S
R
QP
MOUNT (2) HANGER BRACKETSAS SHOWN TO ALLOW ACCESSTO FILTER
AS SHOWN LR UNIT (RR UNIT ON OPPOSITE SIDE—SAME DIMENSIONS)
SIDE DISHCARGE VIEW END VIEW
TOP VIEW
A
S
FRONT VIEW
D E F GI K J
1.9in[4.8cm]
OL
Horizontal Dimensional Data
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 8 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Model036 048 060
Compressor (1 each) Variable Speed Scroll
Factory Charge R410a, oz [kg] Vertical (Aluminum tube and fin air coil)
90 [2.55] 120 [3.40] 140 [3.96]
Factory Charge R410a, oz [kg] Horizontal (Aluminum tube and fin air coil)
86 [2.44] 108 [3.06] 148 [4.19]
ECM Blower Motor & Blower
Blower Motor Type/Speeds ECM Variable Speed
Blower Motor- hp [W] ECM 1/2 [373] 1 [746] 1 [746]
High Static Blower Motor - hp [W] ECM 1 [746] n/a n/a
Blower Wheel Size (Dia x W), in. [mm] ECM11 x 10
[279 x 254] 11 x 10
[279 x 254] 11 x 10
[279 x 254]
High Static Blower Wheel Size - [Dia. x W], in. [mm] ECM11 x 10
[279 x 254] n/a n/a
Coax and Water Piping
Water Connections Size - Swivel - in [mm] 1” [25.4] 1” [25.4] 1” [25.4]
HWG Connection Size - Female Sweat I.D. - in [mm] 1/2” [12.7] 1/2” [12.7] 1/2” [12.7]
Coax & Piping Water Volume - gal [l] 1.3 [4.9] 2.3 [8.7] 2.3 [8.7]
Vertical
Air Coil Dimensions (H x W), in. [mm]32 x 25
[813 x 635]32 x 25
[813 x 635]36 x 25
[914 x 635] Air Coil Total Face Area, ft2 [m2] 5.6 [0.570] 5.6 [0.570] 6.3 [0.641]
Air Coil Tube Size, in [mm] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5]
Air Coil Number of rows 3 3 4
Filter Standard - 2” [51mm] Pleated MERV11 Throwaway, in [mm] 32 x 30 [813 x 762] 32 x 30 [813 x 762] 36 x 30 [914 x 762]
Weight - Operating, lb [kg] 331 [150] 354 [161] 372 [169]
Weight - Packaged, lb [kg] 351 [159] 374 [170] 392 [178]
Horizontal
Air Coil Dimensions (H x W), in. [mm] 20 x 40 [508 x 1016] 20 x 40 [508 x 1016] 20 x 4 [508 x 1143]
Air Coil Total Face Area, ft2 [m2] 5.6 [0.570] 5.6 [0.570] 6.3 [0.641]
Air Coil Tube Size, in [mm] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5]
Air Coil Number of rows 3 3 4
Filter Standard - 2” [51mm] Pleated MERV11 Throwaway, in [mm]1 - 20 x 20 [508 x 508] 1 - 20 x 22 [508 x 559]
1 - 20 x 20 [508 x 508] 1 - 20 x 22 [508 x 559]
1 - 20 x 25 [508 x 635] 1 - 20 x 22 [508 x 559]
Weight - Operating, lb [kg] 365 [166] 388 [176] 402 [182]
Weight - Packaged, lb [kg] 395 [179] 418 [190] 432 [196]
*Bottom fl ow 036-060 models use the 2in. [51mm] MERV 11throwaway in. [mm] 36 x 30 [914 x 762] fi lter.
12/3/2020
Physical Data
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
Auxiliary Heat Ratings
Auxiliary Heat Electrical Data
Electrical Data
SD2700ANA 02/21 9 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
ModelkW
StagesBtu/h
Min CFMModel Compatibility
208V 230V 208V 230V 036 048 060
EAL(H)10* 7.2 9.6 2 24,600 32,700 1100 • • •
EAL(H)15* 10.8 14.4 3 36,900 49,100 1250 • • •
EAL(H)20* 14.4 19.2 4 49,200 65,500 1500 • •
Air flow level for auxiliary heat (Aux) must be above the minimum cfm in this tableOrder the “H” part number when installed on horizontal and vertical rear discharge units
11/30/17
ModelSupply Circuit
Heater Amps Min Circuit Amp Max Fuse (USA) Max Fuse (CAN) Max CKT BRK
208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V
EAL(H)10* Single 34.7 40 53.3 60 60 60 60 60 60 60
EAL(H)15*
Single 52.0 60 75 85 80 90 80 90 70 100
L1/L2 34.7 40 53.3 60 60 60 60 60 60 60
L3/L4 17.3 20 21.7 25 25 25 25 25 20 30
EAL(H)20*
Single 69.3 80 96.7 110 100 110 100 110 100 100
L1/L2 34.7 40 53.3 60 60 60 60 60 60 60
L3/L4 34.7 40 43.3 50 45 50 45 50 40 50
All heaters rated single phase 60 cycle and include unit fan loadAll fuses type “D” time delay (or HACR circuit breaker in USA)
11/30/17
ModelRated
VoltageVoltageMin/Max
Compressor Drive HWG Pump FLA
Ext Loop FLA
Blower Motor FLA
Total Unit FLA
Minimum Circuit Amp
Max Fuse HACR
Breaker LRA CMCC RLAInternal Breaker
036 208-230/60/1 187/253 10.2 18.0 22.0 30.0 0.4 5.4 4.0 31.8 37.3 40
*036 208-230/60/1 187/253 10.2 18.0 22.0 30.0 0.4 5.4 7.0 34.8 40.3 45
048 208-230/60/1 187/253 12.0 23.5 28.0 35.0 0.4 5.4 7.0 40.8 47.8 50
060 208-230/60/1 187/253 12.0 30.0 33.0 40.0 0.4 5.4 7.0 45.8 54.1 60
*With optional 1 hp Variable Speed ECM MotorRated Voltage of 208/230/60/1HACR circuit breaker in USA onlyAll fuses Class RK-5
3/26/12
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 10 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Blower Performance Data
ECM Speed Info
1▶ 2 ◀ G 3 4 5 6 7 8 9 10 11 12
Option ◀▶ Enter ◙
ECM Speed Info
1 2 G▶ 3 ◀ Lo 4 5 6 7 8 9 10 11 12
Option ◀▶ Enter ◙
ECM Speed Info
1 2 G 3 Lo 4 5▶ 6 ◀ Hi 7 8 9 10 11 12
Option ◀▶ Enter ◙
ECM Speed Info
1 2 G 3 Lo 4 5 6 Hi 7 8 9▶10 ◀ Aux 11 12
Option ◀▶ Enter ◙
ECM Speed Info
Blower Only Speed 3Lo Compressor 6Hi Compressor 9Aux Heat 10
Want To Change?
YesOption ◀▶
NoEnter ◙
Cooling Airflow Setup
--- ECM Only ---The airflow will be
adjusted by the chosenamount in cooling mode.
Adjustment:-15%
Want To Change?
YesOption ◀▶
NoEnter ◙
Cooling Airflow Setup
--- ECM Only ---The airflow will be
adjusted by the chosenamount in cooling mode.
Adjustment:-15%
Change ▼▲ Enter ◙
Setting Blower Speed - Variable Speed ECM The ABC board’s Yellow Config LED will flash the current ECM blower speed selections for G, low, and high continuously with a short pause in between. The speeds can also be confirmed with the AID Tool under the Setup/ECM Setup screen. The Aux will not be flashed but can be viewed in the AID Tool. The ECM blower motor speeds can be field adjusted with or without using an AID Tool.
Variable speed ECM Setup without an AID ToolThe blower speeds for G only, Low (Y1), and High (Y2/Aux) can be adjusted directly at the Aurora ABC board which utilizes the push button (SW1) on the ABC board. This procedure is outlined in the ECM Configuration Mode portion of the Aurora ‘Base’ Control System section. The Aux cannot be set manually without an AID Tool.
Variable speed ECM Setup with an AID ToolA much easier method utilizes the AID Tool to change the airflow using the procedure below. First navigate to the Setup screen and then select ECM Setup. This screen displays the current ECM settings. It allows the technician to enter the setup screens to change the ECM settings. Change
the highlighted item using the ◄ and ► buttons and then press the ◙ button to select the item.
Selecting YES will enter ECM speed setup, while selecting NO will return to the previous screen.
ECM Speed Setup - These screens allow the technician to select the G, low, high, and auxiliary heat blower speed for the ECM blower motor. Change the highlighted item using the ▲ and ▼ buttons. Press the ◙ button to select the speed.
After the auxiliary heat speed setting is selected the AID Tool will automatically transfer back to the ECM Setup screen.
Cooling Airflow Setup - These screens allow the technician to select -15%, -10%, -5%, None or +5% change from the heating airflow. Change the adjustment percentage using the ▲ and ▼ buttons. Press the ◙ button to save the change.
Variable Speed ECM Blower Motor
ModelAir Flow
Max ESP
Speed 1
Speed 2
Speed 3
Speed 4
Speed 5
Speed 6
Speed 7
Speed 8
Speed 9
Speed 10
Speed 11
Speed 12
036 0.50285 380
G525
L675 815 980 1100 1220 1330 1440
H1540 Aux
1575
036 w/1hp* 0.75480 565
G665
L 761 870 1000 1100 1200 1300 1410
H1520 Aux
1630
048 0.75475 620
G730
L850 1020 1140 1270 1400 1520 1650
H1790 Aux
1925
060 0.75400 600
G830
L1050 1230 1400 1560 1700 1870 2010
H2140 Aux
2265
**VS Compressor Speed 1-2 3-4 5-6 7-8 9-10 11-12
** VS Compressor speed is given for the factory default cfm settings. When the cfm default settings are changed it will change the relationship to the compressor speed that is shown in the table. In cooling mode compressor speeds 10-12 are only available when SuperBoost mode is selected at the thermostat.* Optional 1 hp Variable Speed ECMFactory settings are at recommended L , H and Aux positions“G” may be located anywhere within the airflow table“L” setting should be located within the boldface cfm range“H” setting MUST be located within the shaded cfm range“Aux” setting MUST be equal to or greater than “H” setting“Aux” setting MUST be equal to or greater than the minimum allowable cfm for the auxiliary heater kit (see auxiliary heat ratings table)Cfm is controlled within 5% up to the maximum ESPMax ESP includes allowance for wet coil and standard filter
6/7/12
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 11 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Model GPMPressure Drop (psi)
30°F 50°F 70°F 90°F 110°F
36
11.5 3.60 3.30 3.10 2.90 2.709.0 2.30 2.10 2.00 1.90 1.707.0 1.50 1.40 1.30 1.20 1.106.0 1.20 1.15 1.10 1.05 1.004.5 0.70 0.66 0.64 0.60 0.55
48
13.5 4.60 4.40 4.10 3.80 3.5010.5 2.90 2.70 2.50 2.30 2.207.5 1.70 1.60 1.50 1.40 1.306.0 1.20 1.10 1.00 0.96 0.914.0 0.62 0.61 0.60 0.58 0.56
60
17.0 6.40 6.00 5.60 5.20 4.8013.5 4.60 4.40 4.10 3.80 3.509.5 2.20 2.10 2.00 1.80 1.707.5 1.70 1.60 1.50 1.40 1.305.0 0.68 0.62 0.58 0.55 0.53
12/02/20
Operating Limits
Defi nitions
Abbreviations and Definitionscfm = airflow, cubic feet/minuteEWT = entering water temperature, Fahrenheitgpm = water flow in gallons/minuteWPD = water pressure drop, psi and feet of waterEAT = entering air temperature, Fahrenheit (dry bulb/wet bulb)HC = air heating capacity, MBtu/hTC = total cooling capacity, MBtu/hSC = sensible cooling capacity, MBtu/hkW = total power unit input, kilowattsHR = total heat of rejection, MBtu/hHE = total heat of extraction, MBtu/h
HWC = hot water generator capacity, MBtu/hEER = Energy Efficient Ratio = Btu output/Watt inputCOP = Coefficient of Performance = Btu output/Btu inputLWT = leaving water temperature, °FLAT = leaving air temperature, °FTH = total heating capacity, MBtu/hLC = latent cooling capacity, MBtu/hS/T = sensible to total cooling ratio
Operating LimitsCooling Heating
(°F) (°C) (°F) (°C)
Air Limits
Min. Ambient Air 45 7.2 45 7.2
Rated Ambient Air 80 26.7 70 21.1
Max. Ambient Air 100 37.8 85 29.4
Min. Entering Air 50 10.0 40 4.4
Rated Entering Air db/wb 80.6/66.2 27/19 68 20.0
Max. Entering Air db/wb 110/83 43/28.3 80 26.7
Water Limits
Min. Entering Water 30 -1.1 20 -6.7
Normal Entering Water 50-110 10-43.3 30-70 -1.1
Max. Entering Water 120 48.9 90 32.2
NOTE: Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependent upon three primary factors: 1) water temperature, 2) return air temperature, and 3) ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation.
Pressure Drop
Notes to Performance Data TablesThe following notes apply to all performance data tables:• Performance ratings are based on 80°F DB/67°F WB EAT
for cooling and 70°F DB EAT for heating.• Three flow rates are shown for each unit. The lowest
flow rate shown is used for geothermal open loop/well water systems with a minimum of 50°F EWT. The middle flow rate shown is the minimum geothermal closed loop flow rate. The highest flow rate shown is optimum for geothermal closed loop systems and the suggested flow rate for boiler/tower applications.
• The hot water generator numbers are based on a flow rate of 0.4 gpm/ton of rated capacity with an EWT of 90°F.
• Entering water temperatures below 40°F assumes 15% antifreeze solution.
• For non-standard EAT conditions, apply the appropriate Correction Factor tables.
• Interpolation between EWT, gpm, and cfm data is
permissible, extrapolation is not.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 12 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Correction Factor Tables
Heating Capacity Corrections
Ent Air DB °FHeating Corrections
Htg Cap Power Heat of Ext
45 1.062 0.739 1.158
50 1.050 0.790 1.130
55 1.037 0.842 1.096
60 1.025 0.893 1.064
65 1.012 0.945 1.030
68 1.005 0.976 1.012
70 1.000 1.000 1.000
75 0.987 1.048 0.970
80 0.975 1.099 0.930
11/10/09
Air Flow Corrections (Compressor Speeds 1-3)Airflow Cooling Heating
CFM Per Ton of Clg
% of Nominal Total Cap Sens Cap Power Heat of Rej Htg Cap Power Heat of Ext
240 60 0.940 0.740 0.967 0.951 0.943 1.106 0.902
275 69 0.950 0.783 0.973 0.959 0.953 1.088 0.918
300 75 0.960 0.827 0.978 0.967 0.962 1.070 0.935
325 81 0.970 0.870 0.984 0.975 0.972 1.053 0.951
350 88 0.980 0.913 0.989 0.984 0.981 1.035 0.967
375 94 0.990 0.957 0.995 0.992 0.991 1.018 0.984
400 100 1.000 1.000 1.000 1.000 1.000 1.000 1.000
425 106 1.030 1.022 1.024 1.026 1.009 0.982 1.016
450 113 1.060 1.045 1.048 1.051 1.019 0.965 1.033
475 119 1.091 1.067 1.071 1.077 1.028 0.947 1.049
500 125 1.121 1.089 1.095 1.103 1.038 0.930 1.065
520 130 1.151 1.111 1.110 1.129 1.047 0.912 1.082
6/29/12
Air Flow Corrections (Compressor Speeds 4-12)Airflow Cooling Heating
CFM Per Ton of Clg
% of Nominal Total Cap Sens Cap Power Heat of Rej Htg Cap Power Heat of Ext
240 60 0.928 0.747 0.936 0.929 0.961 1.097 0.938
275 69 0.940 0.789 0.946 0.941 0.967 1.081 0.948
300 75 0.952 0.831 0.957 0.953 0.974 1.064 0.959
325 81 0.964 0.873 0.968 0.965 0.980 1.048 0.969
350 88 0.976 0.916 0.979 0.976 0.987 1.032 0.979
375 94 0.988 0.958 0.989 0.988 0.993 1.016 0.990
400 100 1.000 1.000 1.000 1.000 1.000 1.000 1.000
425 106 1.020 1.023 1.004 1.018 1.010 0.966 1.018
450 113 1.056 1.042 1.008 1.035 1.020 0.932 1.036
475 119 1.072 1.079 1.011 1.053 1.029 0.898 1.054
500 125 1.087 1.095 1.015 1.070 1.039 0.865 1.071
520 130 1.099 1.113 1.019 1.088 1.049 0.831 1.089
6/14/12
Cooling Capacity Corrections Entering Air WB
°F
Total Clg Cap
Sensible Cooling Capacity Multipliers - Entering DB °FPower Input
Heat of Rejection60 65 70 75 80 80.6 85 90 95 100
55 0.898 0.723 0.866 1.048 1.185 * * * * * * 0.985 0.913
60 0.912 0.632 0.880 1.078 1.244 1.260 * * * * 0.994 0.927
63 0.945 0.768 0.960 1.150 1.175 * * * * 0.996 0.954
65 0.976 0.694 0.881 1.079 1.085 1.270 * * * 0.997 0.972
66.2 0.983 0.655 0.842 1.040 1.060 1.232 * * * 0.999 0.986
67 1.000 0.616 0.806 1.000 1.023 1.193 1.330 1.480 * 1.000 1.000
70 1.053 0.693 0.879 0.900 1.075 1.205 1.404 * 1.003 1.044
75 1.168 0.687 0.715 0.875 1.040 1.261 1.476 1.007 1.141
NOTE: *Sensible capacity equals total capacity at conditions shown. 4/22/12
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 13 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Catalog performance can be corrected for antifreeze use. Please use the following table and note the example given.
Antifreeze Type Antifreeze % by wt Heating Cooling Pressure Drop
EWT - °F [°C] 30 [-1.1] 90 [32.2] 30 [-1.1]
Water 0 1.000 1.000 1.000
Ethylene Glycol
10 0.973 0.991 1.075
20 0.943 0.979 1.163
30 0.917 0.965 1.225
40 0.890 0.955 1.324
50 0.865 0.943 1.419
Propylene Glycol
10 0.958 0.981 1.130
20 0.913 0.969 1.270
30 0.854 0.950 1.433
40 0.813 0.937 1.614
50 0.770 0.922 1.816
Ethanol
10 0.927 0.991 1.242
20 0.887 0.972 1.343
30 0.856 0.947 1.383
40 0.815 0.930 1.523
50 0.779 0.911 1.639
Methanol
10 0.957 0.986 1.127
20 0.924 0.970 1.197
30 0.895 0.951 1.235
40 0.863 0.936 1.323
50 0.833 0.920 1.399
WARNING: Gray area represents antifreeze concentrations greater than 35% by weight and should be avoided due to the extreme performance penalty they represent.
Antifreeze Correction ExampleAntifreeze solution is Propylene Glycol 20% by weight. Determine the corrected heating and cooling performance at 30°F
and 90°F respectively as well as pressure drop at 30°F for a 036 operating at 100% capacity.
The corrected cooling capacity at 90°F would be: 35,200 Btu/h x 0.969 = 34,109 Btu/h
The corrected heating capacity at 30°F would be: 37,400 Btu/h x 0.913 = 34,146 Btu/h
The corrected pressure drop at 30°F and 11.5 gpm would be: 7.9 feet of head x 1.270 = 10.03 feet of head
Antifreeze Corrections
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 14 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
036 - 50% Part Load
EWT
°F
Flow
gpm
WPD HEATING - EAT 70°FEWT
°F
Flow
gpm
WPD COOLING - EAT 80/67 °F
PSI FTAirflow
cfm
HC
MBtuh
Power
kW
HE
MBtuh
LAT
°FCOP
HWC
MBtuhPSI FT
Airflow
cfm
TC
MBtuh
SC
MBtuh
S/T
Ratio
Power
kW
HR
MBtuhEER
HWC
MBtuh
20
3.0 0.30 0.7Operation not recommended
20
2.5 0.15 0.4
Operation not recommended4.5 0.70 1.6 3.5 0.46 1.1
5.5 1.09 2.5550 12.7 1.43 7.8 91.4 2.61 2.2
5.0 0.77 1.8750 12.8 1.26 8.5 85.8 2.98 1.8
30
3.0 0.30 0.7550 13.3 1.19 9.2 92.3 3.26 2.3
30
2.5 0.15 0.3500 18.3 12.5 0.68 0.57 20.2 32.2 -
750 13.8 1.22 9.7 87.1 3.31 2.0 650 18.6 13.7 0.74 0.59 20.7 31.5 -
4.5 0.68 1.6550 13.6 1.20 9.5 92.9 3.33 2.6
3.5 0.45 1.0500 18.5 12.6 0.68 0.54 20.4 34.3 -
750 14.2 1.23 10.0 87.5 3.38 2.2 650 18.8 13.8 0.73 0.57 20.8 33.1 -
5.5 1.06 2.4550 15.0 1.43 10.1 95.3 3.07 2.7
5.0 0.75 1.7500 18.6 12.6 0.68 0.52 20.4 35.6 -
750 15.1 1.26 10.8 88.6 3.51 2.2 650 19.1 13.8 0.72 0.55 21.0 34.7 -
40
3.0 0.29 0.7550 15.6 1.21 11.4 96.2 3.77 2.5
40
2.5 0.14 0.3500 20.4 13.3 0.65 0.51 22.1 39.7 -
750 16.1 1.23 11.9 89.9 3.83 2.2 650 20.8 14.5 0.70 0.53 22.6 38.9 -
4.5 0.66 1.5550 16.1 1.21 11.9 97.0 3.88 2.8
3.5 0.44 1.0500 20.6 13.4 0.65 0.49 22.3 42.3 -
750 16.6 1.24 12.4 90.5 3.94 2.3 650 21.0 14.7 0.70 0.51 22.8 41.1 -
5.5 1.02 2.4550 16.9 1.24 12.7 98.5 3.99 2.8
5.0 0.73 1.7500 20.8 13.4 0.65 0.47 22.4 43.9 -
750 17.5 1.27 13.2 91.6 4.05 2.4 650 21.3 14.7 0.69 0.50 22.9 42.9 -
50
3.0 0.28 0.6550 17.8 1.23 13.7 100.0 4.27 2.8
50
2.5 0.14 0.3500 22.2 13.6 0.61 0.45 23.7 49.7 -
750 18.4 1.24 14.2 92.7 4.34 2.3 650 22.8 15.0 0.66 0.46 24.4 50.1 -
4.5 0.64 1.5550 18.5 1.23 14.3 101.1 4.41 3.0
3.5 0.42 1.0500 22.4 13.7 0.61 0.44 23.9 51.4 -
750 19.0 1.24 14.8 93.5 4.49 2.5 650 23.0 15.1 0.66 0.44 24.5 51.9 -
5.5 0.99 2.3550 19.3 1.26 15.0 102.5 4.51 3.1
5.0 0.70 1.6500 22.8 14.0 0.62 0.43 24.2 52.7 -
750 19.9 1.27 15.6 94.6 4.59 2.8 650 23.4 15.5 0.66 0.44 24.9 53.2 -
60
3.0 0.27 0.6550 20.2 1.24 16.0 104.0 4.77 3.0
60
2.5 0.13 0.3500 20.0 13.4 0.67 0.59 22.0 34.0 1.0
750 20.7 1.25 16.4 95.6 4.85 2.5 650 20.6 14.8 0.72 0.60 22.6 34.3 1.0
4.5 0.62 1.4550 21.0 1.24 16.8 105.4 4.97 3.2
3.5 0.41 0.9500 20.2 13.5 0.67 0.57 22.2 35.2 1.1
750 21.5 1.25 17.3 96.6 5.05 2.7 650 20.8 14.9 0.72 0.59 22.8 35.5 1.1
5.5 0.96 2.2550 21.8 1.27 17.4 106.6 5.03 3.3
5.0 0.68 1.6500 20.5 13.8 0.67 0.57 22.5 36.1 1.2
750 22.3 1.28 17.9 97.5 5.11 2.8 650 21.1 15.3 0.73 0.58 23.1 36.4 1.2
70
3.0 0.26 0.6550 22.6 1.26 18.3 108.0 5.25 3.2
70
2.5 0.13 0.3500 17.8 13.2 0.74 0.73 20.3 24.4 1.3
750 22.9 1.27 18.6 98.3 5.28 2.6 650 18.6 14.9 0.80 0.86 21.5 21.6 1.3
4.5 0.60 1.4550 23.6 1.26 19.3 109.7 5.50 3.4
3.5 0.40 0.9500 18.0 13.3 0.74 0.71 20.4 25.3 1.4
750 24.0 1.25 19.7 99.6 5.61 2.9 650 18.5 14.7 0.80 0.73 21.0 25.5 1.4
5.5 0.93 2.1550 24.2 1.28 19.8 110.7 5.53 3.5
5.0 0.66 1.5500 18.3 13.6 0.75 0.71 20.7 25.9 1.5
750 24.6 1.28 20.2 100.4 5.63 2.9 650 18.8 15.1 0.80 0.72 21.3 26.1 1.5
80
3.0 0.25 0.6550 24.8 1.28 20.4 111.8 5.67 3.4
80
2.5 0.13 0.3500 16.7 12.3 0.73 0.90 19.8 18.6 1.9
750 25.2 1.28 20.8 101.1 5.78 2.8 650 17.2 13.6 0.79 0.92 20.3 18.7 2.0
4.5 0.57 1.3550 26.0 1.28 21.7 113.8 5.98 3.6
3.5 0.38 0.9500 16.8 12.3 0.73 0.88 19.8 19.2 2.1
750 26.3 1.27 22.0 102.5 6.09 3.0 650 17.3 13.7 0.79 0.89 20.4 19.4 2.1
5.5 0.90 2.1550 26.4 1.30 21.9 114.4 5.94 3.8
5.0 0.64 1.5500 17.1 12.6 0.74 0.87 20.1 19.7 2.2
750 26.7 1.29 22.2 102.9 6.05 3.2 650 17.6 14.0 0.80 0.89 20.6 19.9 2.5
90
3.0 0.24 0.6550 27.1 1.31 22.6 115.5 6.07 3.6
90
2.5 0.12 0.3500 15.6 11.3 0.73 1.07 19.2 14.6 2.6
750 27.3 1.29 22.9 103.7 6.19 2.9 650 16.0 12.5 0.78 1.09 19.7 14.7 2.6
4.5 0.55 1.3550 28.4 1.30 24.0 117.9 6.44 3.8
3.5 0.37 0.9500 15.7 11.4 0.72 1.04 19.2 15.1 2.7
750 28.6 1.28 24.3 105.3 6.57 3.2 650 16.1 12.6 0.78 1.06 19.7 15.2 2.7
5.5 0.87 2.0550 28.6 1.32 24.1 118.1 6.34 4.1
5.0 0.61 1.4500 16.7 12.0 0.72 1.06 20.3 15.8 2.8
750 28.7 1.30 24.3 105.4 6.47 3.4 650 16.4 12.9 0.79 1.05 20.0 15.6 2.8
100
3.0 0.23 0.5
Operation not recommended
100
2.5 0.12 0.3500 14.5 10.9 0.75 1.29 18.9 11.2 3.1650 14.9 12.0 0.81 1.32 19.4 11.3 3.1
4.5 0.53 1.2 3.5 0.35 0.8500 14.6 10.9 0.75 1.26 18.9 11.7 3.2650 15.1 12.1 0.80 1.28 19.4 11.7 3.2
5.5 0.84 1.9 5.0 0.59 1.4500 14.9 11.2 0.75 1.25 19.1 11.9 3.3650 15.3 12.4 0.81 1.27 19.6 12.0 3.3
110
3.0 0.22 0.5
110
2.5 0.11 0.3500 13.5 10.4 0.77 1.51 18.6 8.9 3.0650 13.8 11.5 0.83 1.54 19.1 9.0 3.0
4.5 0.51 1.2 3.5 0.34 0.8500 13.6 10.5 0.77 1.47 18.6 9.2 3.3650 14.0 11.6 0.83 1.50 19.1 9.3 3.2
5.5 0.80 1.9 5.0 0.57 1.3500 13.8 10.8 0.78 1.46 18.8 9.5 3.4650 14.2 11.9 0.84 1.49 19.3 9.5 3.4
120
3.0 0.22 0.5
120
2.5 0.11 0.2500 12.6 10.6 0.84 1.93 19.1 6.5 4.3650 12.8 11.6 0.90 1.97 19.6 6.5 4.4
4.5 0.49 1.1 3.5 0.33 0.8500 12.7 10.7 0.84 1.82 18.9 7.0 4.4650 12.9 11.6 0.90 1.87 19.3 6.9 4.4
5.5 0.77 1.8 5.0 0.55 1.3500 12.8 10.7 0.83 1.76 18.8 7.3 4.6650 13.1 11.6 0.89 1.82 19.3 7.2 4.6
Performance capacities shown in thousands of Btuh. 11/2/20
Performance Data
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 15 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
036 - 100% Full Load
EWT
°F
Flow
gpm
WPD HEATING - EAT 70°FEWT
°F
Flow
gpm
WPD COOLING - EAT 80/67 °F
PSI FTAirflow
cfm
HC
MBtuh
Power
kW
HE
MBtuh
LAT
°FCOP
HWC
MBtuhPSI FT
Airflow
cfm
TC
MBtuh
SC
MBtuh
S/T
Ratio
Power
kW
HR
MBtuhEER
HWC
MBtuh
20
5.5 1.09 2.5Operation not recommended
20
4.5 0.70 1.6
Operation not recommended8.0 2.69 6.2 7.0 1.70 3.9
11.5 3.51 8.11150 28.0 3.01 17.8 92.6 2.73 4.7
9.0 2.81 6.51500 28.9 2.91 19.0 87.8 2.91 4.3
30
5.5 1.06 2.51150 31.4 2.77 21.9 95.3 3.32 5.2
30
4.5 0.68 1.61000 35.0 23.9 0.68 0.96 38.2 36.4 -
1500 32.3 2.87 22.5 90.0 3.30 4.8 1300 35.6 26.2 0.73 1.00 39.0 35.6 -
8.0 2.61 6.01150 32.2 2.81 22.6 95.9 3.35 5.3
7.0 1.65 3.81000 35.4 24.1 0.68 0.91 38.6 38.8 -
1500 33.1 2.90 23.2 90.5 3.35 4.8 1300 36.0 26.3 0.73 0.96 39.3 37.4 -
11.5 3.41 7.91150 32.8 3.03 22.5 96.4 3.17 5.4
9.0 2.73 6.31000 35.6 24.1 0.68 0.89 38.7 40.2 -
1500 33.8 2.93 23.8 90.9 3.38 5.0 1300 36.5 26.3 0.72 0.93 39.7 39.2 -
40
5.5 1.02 2.41150 36.3 2.82 26.7 99.2 3.77 5.6
40
4.5 0.66 1.51000 37.0 25.7 0.70 1.15 40.9 32.1 -
1500 37.4 2.89 27.5 93.1 3.79 5.0 1300 37.7 28.1 0.75 1.20 41.8 31.4 -
8.0 2.53 5.91150 37.4 2.88 27.6 100.1 3.82 5.8
7.0 1.60 3.71000 37.4 26.0 0.69 1.09 41.1 34.2 -
1500 38.6 2.94 28.6 93.8 3.85 5.1 1300 38.1 28.4 0.74 1.15 42.0 33.2 -
11.5 3.31 7.61150 38.2 2.90 28.3 100.7 3.85 5.9
9.0 2.65 6.11000 37.7 26.0 0.69 1.06 41.3 35.5 -
1500 39.4 2.97 29.3 94.3 3.89 5.2 1300 38.6 28.4 0.74 1.11 42.3 34.7 -
50
5.5 0.99 2.31150 41.2 2.87 31.4 103.1 4.21 6.0
50
4.5 0.64 1.51000 37.4 25.3 0.68 1.34 41.9 28.0 -
1500 42.4 2.91 32.5 96.2 4.27 5.6 1300 39.4 28.2 0.72 1.41 44.1 28.0 -
8.0 2.46 5.71150 42.7 2.93 32.7 104.4 4.26 6.5
7.0 1.55 3.61000 38.2 25.6 0.67 1.26 42.5 30.3 -
1500 44.0 2.97 33.9 97.2 4.34 5.7 1300 40.2 28.5 0.71 1.32 44.7 30.4 -
11.5 3.20 7.41150 43.6 2.96 33.5 105.1 4.32 6.6
9.0 2.56 5.91000 38.5 27.4 0.71 1.23 42.7 31.4 -
1500 45.0 3.00 34.8 97.8 4.40 6.8 1300 40.6 30.4 0.75 1.29 45.0 31.5 -
60
5.5 0.93 2.21150 45.2 2.89 35.4 106.4 4.59 6.1
60
4.5 0.62 1.41000 35.9 25.4 0.71 1.53 41.1 23.4 1.9
1500 46.7 2.91 36.8 98.8 4.70 5.7 1300 37.7 28.3 0.75 1.60 43.1 23.5 2.0
8.0 2.38 5.51150 47.3 2.97 37.1 108.0 4.66 6.7
7.0 1.50 3.51000 36.8 25.7 0.70 1.46 41.7 25.2 2.1
1500 48.8 2.99 38.6 100.1 4.78 5.8 1300 38.5 28.6 0.74 1.52 43.7 25.4 2.1
11.5 3.10 7.21150 48.4 3.00 38.2 109.0 4.73 6.9
9.0 2.48 5.71000 37.1 27.1 0.73 1.42 42.0 26.1 2.0
1500 50.0 3.02 39.7 100.9 4.86 6.0 1300 39.0 30.1 0.77 1.49 44.0 26.2 2.2
70
5.5 0.90 2.11150 49.3 2.91 39.4 109.7 4.97 6.6
70
4.5 0.60 1.41000 34.4 25.6 0.74 1.92 41.0 17.9 2.7
1500 51.0 3.02 40.7 101.5 4.95 6.2 1300 36.5 29.5 0.81 1.91 43.0 19.1 2.9
8.0 2.30 5.31150 51.9 3.01 41.6 111.8 5.06 6.9
7.0 1.45 3.41000 35.3 25.9 0.73 1.66 41.0 21.3 3.1
1500 53.5 3.01 43.3 103.1 5.22 6.4 1300 36.9 28.7 0.78 1.71 42.7 21.5 3.1
11.5 3.00 6.91150 53.2 3.04 42.8 112.8 5.12 7.6
9.0 2.40 5.51000 35.7 26.9 0.75 1.61 41.2 22.1 3.2
1500 55.0 3.03 44.7 104.0 5.32 6.6 1300 37.3 29.8 0.80 1.68 43.0 22.2 3.3
80
5.5 0.87 0.11150 52.7 2.96 42.6 112.5 5.21 7.2
80
4.5 0.57 1.31000 32.9 25.3 0.77 2.00 39.7 16.5 4.0
1500 54.6 2.94 44.5 103.7 5.44 6.1 1300 34.2 28.2 0.82 2.06 41.2 16.6 4.0
8.0 2.22 5.11150 55.8 3.08 45.3 114.9 5.31 7.5
7.0 1.40 3.21000 33.8 25.6 0.76 1.93 40.4 17.5 4.2
1500 57.7 3.05 47.3 105.6 5.54 6.3 1300 35.1 28.4 0.81 1.98 41.9 17.7 4.2
11.5 2.90 6.71150 57.4 3.12 46.7 116.2 5.39 7.7
9.0 2.32 5.41000 34.1 26.3 0.77 1.89 40.6 18.1 4.4
1500 59.4 3.08 48.9 106.6 5.66 7.2 1300 35.6 29.1 0.82 1.95 42.2 18.3 4.4
90
5.5 0.84 1.91150 56.2 3.02 45.9 115.2 5.45 7.4
90
4.5 0.55 1.31000 31.3 25.1 0.80 2.27 39.0 13.8 5.3
1500 58.2 2.97 48.0 105.9 5.74 6.7 1300 32.4 27.9 0.86 2.32 40.3 14.0 5.3
8.0 2.14 5.01150 59.7 3.15 48.9 118.1 5.55 7.8
7.0 1.35 3.11000 32.2 25.4 0.79 2.20 39.7 14.6 5.6
1500 61.8 3.10 51.2 108.2 5.85 7.2 1300 33.4 28.2 0.84 2.26 41.1 14.8 5.6
11.5 2.79 6.51150 61.6 3.20 50.7 119.6 5.64 8.6
9.0 2.24 5.21000 32.8 24.9 0.76 2.17 40.2 15.1 5.9
1500 63.7 3.12 53.1 109.3 5.98 7.9 1300 33.8 28.4 0.84 2.21 41.3 15.3 5.6
100
5.5 0.80 1.8
Operation not recommended
100
4.5 0.53 1.21000 29.1 24.2 0.83 2.62 38.1 11.1 6.81300 30.0 26.8 0.89 2.67 39.1 11.3 6.7
8.0 2.07 4.8 7.0 1.30 3.01000 30.1 24.5 0.81 2.57 38.9 11.7 7.11300 31.1 27.2 0.87 2.61 40.0 11.9 7.0
11.5 2.69 6.2 9.0 2.16 5.01000 30.4 24.4 0.80 2.53 39.0 12.0 7.51300 31.4 27.0 0.86 2.57 40.2 12.2 6.2
110
5.5 0.77 1.8
110
4.5 0.51 1.21000 26.9 23.3 0.87 2.98 37.1 9.0 8.11300 27.7 25.8 0.93 3.01 37.9 9.2 8.0
8.0 1.99 4.6 7.0 1.25 2.91000 27.9 23.5 0.84 2.95 38.0 9.5 8.51300 28.7 26.1 0.91 2.97 38.9 9.7 8.5
11.5 2.59 6.0 9.0 2.07 4.81000 28.2 23.2 0.82 2.90 38.1 9.7 8.91300 29.0 25.6 0.88 2.93 39.0 9.9 8.1
120
5.5 0.73 1.7
120
4.5 0.49 0.81000 23.9 22.7 0.95 3.54 36.0 6.7 9.91300 24.4 24.8 1.02 3.62 36.7 6.7 10.2
8.0 1.91 4.4 7.0 1.20 2.81000 24.2 22.9 0.95 3.35 35.6 7.2 10.31300 24.6 24.9 1.01 3.43 36.3 7.2 10.5
11.5 2.49 5.8 9.0 1.99 4.61000 24.4 22.9 0.94 3.24 35.4 7.5 10.71300 24.9 24.9 1.00 3.34 36.3 7.5 10.7
Performance capacities shown in thousands of Btuh. 11/2/20
Performance Data cont.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 16 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
048 - 50% Part Load
EWT
°F
Flow
gpm
WPD HEATING - EAT 70°FEWT
°F
Flow
gpm
WPD COOLING - EAT 80/67 °F
PSI FTAirflow
cfm
HC
mBtuh
Power
kW
HE
MBtuh
LAT
°FCOP
HWC
MBtuhPSI FT
Airflow
cfm
TC
MBtuh
SC
MBtuh
S/T
Ratio
Power
kW
HR
MBtuhEER
HWC
MBtuh
20
3.5 0.56 1.3Operation not recommended
20
3.0 0.47 1.1
Operation not recommended5.0 0.97 2.2 4.5 0.81 1.9
6.5 1.37 3.2650 16.5 1.83 10.3 93.6 2.65 2.4
6.0 1.16 2.7900 16.9 1.65 11.3 87.4 3.00 3.1
30
3.5 0.55 1.3650 16.7 1.57 11.4 93.9 3.12 2.7
30
3.0 0.45 1.1500 23.9 14.1 0.59 0.57 25.8 42.0 -
900 17.3 1.60 11.9 87.8 3.17 2.4 750 24.3 15.5 0.64 0.59 26.3 41.1 -
5.0 0.94 2.2650 18.1 1.64 12.5 95.8 3.22 3.0
4.5 0.79 1.8500 24.2 14.3 0.59 0.54 26.0 44.8 -
900 18.6 1.66 13.0 89.2 3.30 2.6 750 24.6 15.6 0.63 0.57 26.5 43.2 -
6.5 1.33 3.1650 18.8 1.86 12.5 96.8 2.96 3.1
6.0 1.12 2.6500 24.3 14.3 0.59 0.52 26.1 46.4 -
900 19.2 1.68 13.5 89.8 3.35 2.6 750 24.9 15.6 0.63 0.55 26.8 45.3 -
40
3.5 0.53 1.2650 19.8 1.61 14.3 98.3 3.61 3.0
40
3.0 0.44 1.0500 27.0 18.1 0.67 0.49 28.6 55.3 -
900 20.5 1.62 14.9 91.1 3.70 2.6 750 27.5 19.7 0.72 0.51 29.2 54.1 -
5.0 0.91 2.1650 21.4 1.67 15.7 100.5 3.75 3.3
4.5 0.77 1.8500 27.3 18.2 0.67 0.46 28.9 58.9 -
900 22.1 1.67 16.4 92.8 3.88 2.8 750 27.8 19.9 0.72 0.49 29.4 57.2 -
6.5 1.29 3.0650 22.1 1.68 16.4 101.5 3.85 3.4
6.0 1.09 2.5500 27.5 18.2 0.66 0.45 29.0 61.2 -
900 22.9 1.70 17.1 93.5 3.95 2.8 750 28.1 19.9 0.71 0.47 29.7 59.8 -
50
3.5 0.51 1.2650 22.9 1.65 17.3 102.7 4.08 3.3
50
3.0 0.43 1.0500 25.8 16.3 0.63 0.68 28.1 38.1 -
900 23.7 1.65 18.0 94.3 4.21 2.8 750 26.6 19.2 0.72 0.71 29.0 37.7 -
5.0 0.88 2.0650 24.7 1.70 18.9 105.2 4.26 3.6
4.5 0.74 1.7500 26.3 16.4 0.62 0.59 28.3 45.0 -
900 25.7 1.69 19.9 96.4 4.45 3.0 750 27.1 19.3 0.71 0.61 29.2 44.2 -
6.5 1.25 2.9650 25.7 1.71 19.8 106.6 4.40 3.8
6.0 1.06 2.4500 26.5 16.4 0.62 0.55 28.4 48.0 -
900 26.5 1.71 20.7 97.3 4.54 3.3 750 27.3 19.3 0.71 0.58 29.3 47.1 -
60
3.5 0.50 1.1650 25.7 1.71 19.9 106.6 4.41 3.7
60
3.0 0.41 1.0500 24.7 15.9 0.64 0.83 27.6 29.8 1.2
900 26.7 1.70 20.9 97.4 4.60 3.0 750 25.5 18.7 0.73 0.87 28.5 29.5 1.2
5.0 0.85 2.0650 27.8 1.75 21.9 109.7 4.66 3.9
4.5 0.72 1.7500 25.1 16.0 0.64 0.74 27.7 34.2 1.3
900 28.9 1.73 23.0 99.8 4.90 3.3 750 25.9 18.9 0.73 0.77 28.5 33.6 1.3
6.5 1.21 2.8650 29.0 1.77 23.0 111.3 4.82 4.1
6.0 1.02 2.4500 25.4 16.1 0.63 0.70 27.8 36.4 1.4
900 30.1 1.75 24.1 100.9 5.05 3.5 750 26.2 18.9 0.72 0.73 28.7 35.9 1.4
70
3.5 0.48 1.1650 28.5 1.77 22.5 110.7 4.73 4.0
70
3.0 0.40 0.9500 23.7 15.5 0.65 0.98 27.0 24.2 1.7
900 31.1 1.77 25.1 102.0 5.15 3.3 750 24.6 18.3 0.74 1.03 28.1 23.9 1.8
5.0 0.83 1.9650 31.0 1.80 24.8 114.1 5.04 4.3
4.5 0.70 1.6500 23.9 15.7 0.65 0.89 27.0 27.0 1.9
900 32.2 1.77 26.1 103.1 5.33 3.6 750 24.7 18.4 0.75 0.93 27.8 26.7 1.9
6.5 1.17 2.7650 32.4 1.82 26.2 116.1 5.21 4.5
6.0 0.99 2.3500 24.4 15.8 0.65 0.85 27.2 28.7 1.9
900 33.6 1.78 27.5 104.6 5.53 3.7 750 25.1 18.5 0.74 0.88 28.1 28.5 2.0
80
3.5 0.46 1.1650 30.5 1.87 24.1 113.4 4.78 4.2
80
3.0 0.39 0.9500 22.6 15.0 0.66 1.16 26.5 19.5 2.5
900 31.6 1.83 25.4 102.6 5.06 3.5 750 23.3 17.6 0.76 1.21 27.4 19.3 2.5
5.0 0.80 1.8650 33.1 1.89 26.6 117.1 5.14 4.5
4.5 0.67 1.6500 22.7 15.2 0.67 1.07 26.3 21.1 2.6
900 34.4 1.84 28.1 105.4 5.48 3.8 750 23.4 17.8 0.76 1.12 27.2 20.9 2.7
6.5 1.13 2.6650 34.8 1.91 28.3 119.5 5.34 4.8
6.0 0.96 2.2500 23.2 15.3 0.66 1.03 26.7 22.6 2.8
900 36.2 1.86 29.8 107.2 5.71 4.0 750 23.9 18.0 0.75 1.07 27.6 22.3 3.2
90
3.5 0.45 1.0650 32.4 1.96 25.7 116.1 4.84 4.5
90
3.0 0.37 0.9500 21.4 14.5 0.68 1.33 26.0 16.1 3.4
900 33.6 1.92 27.1 104.6 5.14 3.7 750 22.1 17.0 0.77 1.38 26.8 16.0 3.4
5.0 0.77 1.8650 35.2 1.97 28.5 120.1 5.23 4.8
4.5 0.65 1.5500 21.4 14.6 0.68 1.26 25.7 17.0 3.5
900 36.7 1.91 30.1 107.7 5.63 4.0 750 22.0 17.2 0.78 1.31 26.5 16.9 3.6
6.5 1.09 2.5650 37.1 1.99 30.3 122.9 5.46 5.2
6.0 0.92 2.1500 20.5 13.8 0.67 1.27 24.8 16.1 3.7
900 38.7 1.93 32.1 109.8 5.88 4.3 750 22.7 17.4 0.77 1.26 27.0 18.0 3.7
100
3.5 0.43 1.0
Operation not recommended
100
3.0 0.36 0.8500 19.3 13.3 0.69 1.56 24.6 12.4 4.3750 19.9 15.6 0.78 1.62 25.5 12.3 4.3
5.0 0.74 1.7 4.5 0.62 1.4500 19.2 13.4 0.70 1.52 24.4 12.7 4.4750 19.8 15.8 0.80 1.58 25.2 12.6 4.4
6.5 1.05 2.4 6.0 0.89 2.1500 19.9 13.6 0.68 1.46 24.9 13.6 4.6750 20.5 16.0 0.78 1.53 25.7 13.4 4.6
110
3.5 0.41 1.0
110
3.0 0.35 0.8500 17.2 12.1 0.70 1.78 23.3 9.7 5.0750 17.7 14.2 0.80 1.85 24.1 9.6 5.0
5.0 0.71 1.6 4.5 0.60 1.4500 17.0 12.2 0.72 1.77 23.0 9.6 5.4750 17.6 14.4 0.82 1.85 23.9 9.5 5.4
6.5 1.01 2.3 6.0 0.86 2.0500 17.8 12.4 0.70 1.72 23.7 10.4 5.8750 18.3 14.6 0.80 1.79 24.4 10.2 5.8
120
3.5 0.40 0.9
120
3.0 0.33 0.8500 16.0 12.8 0.80 2.22 23.6 7.2 6.4750 16.4 13.9 0.85 2.27 24.1 7.2 6.5
5.0 0.68 1.6 4.5 0.58 1.3500 16.2 12.9 0.80 2.09 23.4 7.7 6.6750 16.5 14.0 0.85 2.15 23.8 7.7 6.6
6.5 0.97 2.2 6.0 0.82 1.9500 16.4 12.9 0.79 2.03 23.3 8.1 6.8750 16.7 14.0 0.84 2.09 23.8 8.0 6.8
Performance capacities shown in thousands of Btuh. 11/2/20
Performance Data cont.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 17 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
048 - 100% Full Load
EWT
°F
Flow
gpm
WPD HEATING - EAT 70°FEWT
°F
Flow
gpm
WPD COOLING - EAT 80/67 °F
PSI FTAirflow
cfm
HC
mBtuh
Power
kW
HE
MBtuh
LAT
°FCOP
HWC
MBtuhPSI FT
Airflow
cfm
TC
MBtuh
SC
MBtuh
S/T
Ratio
Power
kW
HR
MB-
tuh
EERHWC
MBtuh
20
6.5 1.40 3.2Operation not recommended
20
5.5 1.05 2.4
Operation not recommended10.0 2.85 6.6 8.0 2.00 4.6
13.5 4.79 11.11500 39.4 4.05 25.6 94.3 2.86 6.05
10.5 2.94 6.81800 39.7 3.97 26.2 90.4 2.93 5.6
30
6.5 1.36 3.21500 39.9 3.84 26.7 94.6 3.04 6.6
30
5.5 1.02 2.41000 42.8 28.0 0.65 1.20 46.9 35.7 -
1800 41.2 3.90 27.9 91.2 3.10 6.1 1400 43.6 30.8 0.70 1.25 47.9 35.0 -
10.0 2.77 6.41500 43.0 4.01 29.3 96.6 3.14 6.8
8.0 1.94 4.51000 43.4 28.3 0.65 1.14 47.3 38.1 -
1800 44.4 4.04 30.6 92.8 3.22 6.1 1400 44.1 30.9 0.70 1.20 48.2 36.8 -
13.5 4.65 10.71500 45.4 4.18 31.1 98.0 3.18 6.9
10.5 2.85 6.61000 43.6 28.3 0.65 1.10 47.4 39.5 -
1800 45.7 4.10 31.7 93.5 3.27 6.3 1400 44.7 30.9 0.69 1.16 48.7 38.5 -
40
6.5 1.32 3.11500 45.4 4.00 31.8 98.0 3.33 7.0
40
5.5 0.99 2.31000 44.7 29.0 0.65 1.42 49.5 31.4 -
1800 46.9 4.02 33.2 94.1 3.42 6.2 1400 45.5 31.7 0.70 1.48 50.6 30.8 -
10.0 2.69 6.21500 49.0 4.15 34.9 100.3 3.46 7.3
8.0 1.88 4.31000 45.2 29.2 0.65 1.35 49.8 33.5 -
1800 50.7 4.15 36.6 96.1 3.58 6.4 1400 46.0 31.9 0.69 1.42 50.9 32.5 -
13.5 4.51 10.41500 50.6 4.18 36.4 101.2 3.55 7.5
10.5 2.77 6.41000 45.5 29.2 0.64 1.31 50.0 34.8 -
1800 52.4 4.21 38.0 96.9 3.65 6.5 1400 46.6 31.9 0.69 1.37 51.2 34.0 -
50
6.5 1.28 3.01500 51.0 4.15 36.9 101.5 3.61 7.5
50
5.5 0.96 2.21000 45.7 27.8 0.61 1.84 52.0 24.8 -
1800 52.7 4.15 38.5 97.1 3.72 7.0 1400 47.1 32.8 0.70 1.92 53.7 24.5 -
10.0 2.60 6.01500 55.0 4.28 40.4 104.0 3.77 8.2
8.0 1.82 4.21000 46.7 27.9 0.60 1.60 52.1 29.3 -
1800 57.1 4.26 42.6 99.4 3.93 7.2 1400 48.1 32.9 0.68 1.67 53.8 28.8 -
13.5 4.37 10.11500 57.1 4.31 42.4 105.3 3.88 8.4
10.5 2.68 6.21000 47.0 27.9 0.59 1.50 52.1 31.3 -
1800 59.0 4.31 44.3 100.3 4.01 8.6 1400 48.4 32.9 0.68 1.58 53.8 30.6 -
60
6.5 1.24 2.91500 57.1 4.32 42.3 105.2 3.87 7.6
60
5.5 0.93 2.21000 43.9 27.2 0.62 2.06 50.9 21.3 2.6
1800 59.1 4.29 44.5 100.4 4.04 7.1 1400 45.2 32.1 0.71 2.15 52.6 21.1 2.8
10.0 2.52 5.81500 61.7 4.42 46.7 108.1 4.09 8.4
8.0 1.76 4.11000 44.6 27.4 0.62 1.83 50.8 24.4 2.9
1800 64.1 4.37 49.2 103.0 4.30 7.2 1400 45.9 32.3 0.70 1.91 52.5 24.1 2.9
13.5 4.23 9.81500 64.4 4.46 49.1 109.7 4.23 8.6
10.5 2.60 6.01000 45.1 27.5 0.61 1.73 51.0 26.0 2.8
1800 66.7 4.41 51.6 104.3 4.43 7.4 1400 46.5 32.4 0.70 1.81 52.6 25.7 3.0
70
6.5 1.20 2.81500 63.1 4.48 47.8 109.0 4.13 8.1
70
5.5 0.90 2.11000 42.0 26.7 0.63 2.27 49.7 18.5 3.4
1800 67.8 4.49 52.5 104.9 4.43 7.5 1400 43.7 31.7 0.73 2.27 51.4 19.3 3.7
10.0 2.44 5.61500 68.5 4.56 52.9 112.3 4.40 8.6
8.0 1.71 3.91000 42.4 26.9 0.63 2.06 49.5 20.7 3.9
1800 71.2 4.48 55.9 106.6 4.65 7.9 1400 43.8 31.7 0.72 2.15 51.1 20.4 3.9
13.5 4.09 9.51500 63.7 4.28 49.1 109.3 4.36 9.4
10.5 2.51 5.81000 43.2 27.1 0.63 1.96 49.9 22.0 3.9
1800 74.3 4.51 58.9 108.2 4.83 8.2 1400 44.5 31.8 0.71 2.04 51.5 21.8 4.1
80
6.5 1.16 2.71500 68.3 4.71 52.3 112.2 4.25 9.0
80
5.5 0.87 2.01000 39.8 25.7 0.65 2.54 48.5 15.6 5.4
1800 71.0 4.63 55.2 106.5 4.50 7.7 1400 41.0 30.2 0.74 2.65 50.1 15.5 5.4
10.0 2.35 5.41500 74.2 4.76 58.0 115.8 4.57 9.5
8.0 1.65 3.81000 40.0 26.0 0.65 2.36 48.1 16.9 5.7
1800 77.2 4.64 61.4 109.7 4.88 7.9 1400 41.2 30.6 0.74 2.46 49.6 16.8 5.7
13.5 3.95 9.11500 78.0 4.81 61.6 118.1 4.75 9.6
10.5 2.42 5.61000 40.9 26.2 0.64 2.26 48.6 18.1 5.9
1800 81.1 4.68 65.1 111.7 5.08 9.0 1400 42.2 30.8 0.73 2.36 50.2 17.9 5.9
90
6.5 1.12 2.61500 73.5 4.93 56.7 115.4 4.37 9.7
90
5.5 0.84 1.91000 37.6 24.8 0.66 2.82 47.2 13.3 6.7
1800 76.4 4.82 60.0 109.3 4.64 8.6 1400 38.8 29.1 0.75 2.93 48.7 13.2 6.6
10.0 2.27 5.21500 79.9 4.96 63.0 119.4 4.73 9.5
8.0 1.59 3.71000 37.6 25.1 0.67 2.67 46.7 14.1 7.0
1800 83.3 4.80 66.9 112.8 5.09 8.9 1400 38.6 29.5 0.76 2.77 48.0 14.0 7.0
13.5 3.81 8.81500 84.4 5.01 67.3 122.1 4.93 10.4
10.5 2.34 5.41000 37.3 24.9 0.67 2.59 46.1 14.4 7.3
1800 87.9 4.85 71.4 115.2 5.31 9.7 1400 39.8 29.8 0.75 2.67 48.9 14.9 7.4
100
6.5 1.08 2.5
Operation not recommended
100
5.5 0.81 1.91000 35.1 23.9 0.68 3.14 45.8 11.2 8.91400 36.2 28.1 0.78 3.27 47.3 11.1 8.8
10.0 2.19 5.1 8.0 1.53 3.51000 34.9 24.2 0.69 3.05 45.3 11.4 9.31400 36.0 28.5 0.79 3.17 46.8 11.3 9.2
13.5 3.67 8.5 10.5 2.25 5.21000 36.2 24.6 0.68 2.94 46.2 12.3 9.81400 37.3 28.9 0.77 3.07 47.7 12.1 8.2
110
6.5 1.04 2.4
110
5.5 0.78 1.81000 32.7 23.1 0.71 3.45 44.5 9.5 10.61400 33.6 27.0 0.80 3.59 45.9 9.4 10.5
10.0 2.11 4.9 8.0 1.47 3.41000 32.2 23.3 0.72 3.43 43.9 9.4 11.11400 33.3 27.5 0.82 3.58 45.5 9.3 11.1
13.5 3.53 8.2 10.5 2.17 5.01000 33.8 23.8 0.70 3.33 45.1 10.1 11.61400 34.7 27.9 0.80 3.47 46.5 10.0 10.5
120
6.5 1.00 2.3
120
5.5 0.75 1.71000 30.9 24.4 0.79 4.15 45.0 7.4 12.81400 31.5 26.6 0.84 4.25 46.0 7.4 13.1
10.0 2.02 4.7 8.0 1.42 3.31000 31.3 24.6 0.79 3.93 44.7 8.0 13.21400 31.8 26.7 0.84 4.03 45.6 7.9 13.6
13.5 3.39 7.8 10.5 2.08 4.81000 31.5 24.6 0.78 3.80 44.5 8.3 13.81400 32.2 26.7 0.83 3.92 45.6 8.2 14.0
Performance capacities shown in thousands of Btuh. 11/2/20
Performance Data cont.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 18 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
060 - 50% Part Load
EWT
°F
Flow
gpm
WPD HEATING - EAT 70°FEWT
°F
Flow
gpm
WPD COOLING - EAT 80/67 °F
PSI FTAirflow
cfm
HC
mBtuh
Power
kW
HE
MBtuh
LAT
°FCOP
HWC
MBtuhPSI FT
Airflow
cfm
TC
MBtuh
SC
MBtuh
S/T
Ratio
Power
kW
HR
MBtuhEER
HWC
MBtuh
20
4.5 0.63 1.5Operation not recommended
20
4.0 0.43 1.0
Operation not recommended6.3 1.17 2.7 6.0 1.22 2.8
8.5 1.94 4.5850 21.0 2.18 13.5 92.9 2.82 3.4
7.5 1.80 4.21100 21.4 2.02 14.5 88.0 3.10 3.1
30
4.5 0.61 1.4850 23.8 2.01 16.9 95.9 3.47 3.9
30
4.0 0.42 1.0700 31.5 18.0 0.57 0.76 34.1 41.2 -
1100 24.6 2.03 17.7 90.7 3.54 3.4 950 32.1 19.7 0.61 0.80 34.8 40.3 -
6.3 1.14 2.6850 23.6 2.03 16.7 95.7 3.40 4.1
6.0 1.18 2.7700 32.0 18.1 0.57 0.73 34.4 44.0 -
1100 24.5 2.06 17.4 90.6 3.48 3.5 950 32.5 19.8 0.61 0.77 35.1 42.4 -
8.5 1.89 4.4850 24.8 2.22 17.2 97.0 3.27 4.2
7.5 1.75 4.0700 32.1 18.1 0.56 0.70 34.5 45.6 -
1100 25.3 2.06 18.3 91.3 3.60 3.6 950 32.9 19.8 0.60 0.74 35.4 44.5 -
40
4.5 0.60 1.4850 27.5 2.05 20.5 100.0 3.94 4.3
40
4.0 0.41 0.9700 32.5 20.5 0.63 0.81 35.3 39.9 -
1100 28.4 2.06 21.3 93.9 4.03 3.7 950 33.2 22.4 0.68 0.85 36.1 39.1 -
6.3 1.10 2.5850 27.7 2.08 20.6 100.2 3.90 4.5
6.0 1.15 2.6700 32.9 20.7 0.63 0.77 35.5 42.5 -
1100 28.5 2.09 21.4 94.0 4.00 3.8 950 33.5 22.6 0.67 0.81 36.3 41.3 -
8.5 1.83 4.2850 28.6 2.09 21.5 101.2 4.02 4.7
7.5 1.70 3.9700 33.2 20.7 0.62 0.75 35.7 44.2 -
1100 29.4 2.10 22.3 94.7 4.11 3.9 950 33.9 22.6 0.67 0.79 36.6 43.2 -
50
4.5 0.58 1.3850 31.3 2.09 24.2 104.1 4.39 4.7
50
4.0 0.40 0.9700 33.7 22.2 0.66 0.84 36.6 40.3 -
1100 32.2 2.09 25.0 97.1 4.51 3.9 950 34.7 25.2 0.73 0.88 37.7 39.3 -
6.3 1.07 2.5850 31.8 2.13 24.5 104.6 4.38 4.9
6.0 1.11 2.6700 33.8 22.4 0.66 0.81 36.6 41.9 -
1100 32.5 2.12 25.3 97.4 4.50 4.1 950 34.8 25.4 0.73 0.85 37.7 41.2 -
8.5 1.77 4.1850 32.8 2.14 25.5 105.7 4.48 5.2
7.5 1.64 3.8700 33.9 22.4 0.66 0.79 36.6 42.8 -
1100 33.5 2.13 26.2 98.2 4.61 4.6 950 34.9 25.4 0.73 0.83 37.7 42.0 -
60
4.5 0.56 1.3850 35.3 2.13 28.0 108.5 4.86 5.1
60
4.0 0.38 0.9700 32.7 21.9 0.67 1.03 36.2 31.8 1.5
1100 36.1 2.11 28.9 100.4 5.01 4.2 950 33.7 24.7 0.73 1.08 37.4 31.3 1.6
6.3 1.03 2.4850 36.4 2.17 29.0 109.7 4.92 5.3
6.0 1.08 2.5700 32.9 22.1 0.67 1.00 36.3 33.0 1.7
1100 37.0 2.14 29.7 101.1 5.07 4.5 950 33.9 25.0 0.74 1.04 37.4 32.5 1.7
8.5 1.72 4.0850 37.3 2.19 29.8 110.6 5.00 5.6
7.5 1.59 3.7700 33.0 22.1 0.67 0.98 36.3 33.9 1.8
1100 37.9 2.16 30.5 101.9 5.15 4.7 950 34.0 25.0 0.74 1.02 37.5 33.3 1.8
70
4.5 0.54 1.2850 39.3 2.17 31.9 112.8 5.31 5.4
70
4.0 0.37 0.9700 31.7 21.6 0.68 1.22 35.9 26.0 2.1
1100 38.6 2.15 31.3 102.5 5.26 4.5 950 33.0 24.7 0.75 1.39 37.7 23.7 2.3
6.3 1.00 2.3850 41.0 2.20 33.5 114.6 5.45 5.8
6.0 1.04 2.4700 31.9 21.8 0.68 1.18 36.0 27.0 2.4
1100 41.4 2.16 34.1 104.9 5.63 4.8 950 32.9 24.5 0.74 1.24 37.1 26.6 2.4
8.5 1.66 3.8850 41.8 2.23 34.1 115.5 5.49 6.0
7.5 1.54 3.6700 32.1 21.9 0.68 1.16 36.1 27.7 2.5
1100 42.2 2.18 34.8 105.5 5.67 5.0 950 33.1 24.6 0.74 1.21 37.2 27.4 2.5
80
4.5 0.52 1.2850 42.9 2.23 35.3 116.7 5.64 5.8
80
4.0 0.36 0.8700 29.9 21.2 0.71 1.45 34.8 20.6 3.1
1100 43.3 2.18 35.8 106.4 5.81 4.8 950 30.8 23.6 0.77 1.50 35.9 20.5 3.2
6.3 0.97 2.2850 45.3 2.27 37.6 119.3 5.86 6.2
6.0 1.00 2.3700 30.1 21.4 0.71 1.41 35.0 21.3 3.3
1100 45.5 2.20 38.0 108.3 6.06 5.1 950 31.0 23.9 0.77 1.47 36.1 21.2 3.4
8.5 1.60 3.7850 45.8 2.30 38.0 119.9 5.85 6.6
7.5 1.49 3.4700 30.3 21.5 0.71 1.39 35.1 21.8 3.5
1100 46.0 2.23 38.4 108.7 6.05 5.4 950 31.3 24.1 0.77 1.44 36.2 21.7 4.0
90
4.5 0.50 1.2850 46.5 2.29 38.6 120.6 5.94 6.2
90
4.0 0.34 0.8700 28.0 20.7 0.74 1.68 33.8 16.7 4.4
1100 46.6 2.23 39.0 109.2 6.12 5.0 950 28.9 23.0 0.80 1.73 34.8 16.7 4.4
6.3 0.93 2.2850 49.6 2.33 41.6 124.0 6.24 6.6
6.0 0.97 2.2700 28.4 20.9 0.74 1.64 34.0 17.3 4.6
1100 49.6 2.24 41.9 111.7 6.48 5.4 950 29.2 23.3 0.80 1.70 35.0 17.2 4.6
8.5 1.55 3.6850 49.9 2.36 41.8 124.4 6.19 7.1
7.5 1.43 3.3700 28.2 19.4 0.69 1.67 33.9 16.9 4.8
1100 49.8 2.28 42.0 111.9 6.40 5.8 950 29.5 23.5 0.80 1.67 35.2 17.7 4.8
100
4.5 0.48 1.1
Operation not recommended
100
4.0 0.33 0.8700 26.1 20.1 0.77 2.02 33.0 12.9 5.4950 26.9 22.2 0.83 2.07 34.0 13.0 5.4
6.3 0.90 2.1 6.0 0.93 2.2700 26.4 20.3 0.77 1.99 33.2 13.3 5.5950 27.2 22.5 0.83 2.04 34.2 13.3 5.5
8.5 1.49 3.4 7.5 1.38 3.2700 26.7 20.6 0.77 1.96 33.4 13.6 5.8950 27.6 22.8 0.83 2.01 34.4 13.7 5.8
110
4.5 0.47 1.1
110
4.0 0.32 0.7700 24.2 19.6 0.81 2.36 32.2 10.2 6.3950 24.9 21.5 0.86 2.41 33.2 10.4 6.3
6.3 0.86 2.0 6.0 0.90 2.1700 24.5 19.8 0.81 2.34 32.5 10.5 6.8950 25.3 21.7 0.86 2.38 33.4 10.6 6.8
8.5 1.43 3.3 7.5 1.33 3.1700 24.8 20.1 0.81 2.30 32.7 10.8 7.2950 25.6 22.0 0.86 2.35 33.6 10.9 7.2
120
4.5 0.45 1.0
120
4.0 0.31 0.7700 23.6 19.3 0.82 2.88 33.4 8.2 8.2950 24.1 21.0 0.87 2.95 34.2 8.2 8.2
6.3 0.83 1.9 6.0 0.86 2.0700 23.9 19.4 0.81 2.73 33.2 8.8 8.4950 24.3 21.1 0.87 2.80 33.8 8.7 8.4
8.5 1.38 3.2 7.5 1.28 3.0700 24.1 19.4 0.81 2.64 33.1 9.1 8.7950 24.6 21.1 0.86 2.72 33.9 9.0 8.7
Performance capacities shown in thousands of Btuh. 11/2/20
Performance Data cont.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 19 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
060 - 100% Full Load
EWT
°F
Flow
gpm
WPD HEATING - EAT 70°FEWT
°F
Flow
gpm
WPD COOLING - EAT 80/67 °F
PSI FTAirflow
cfm
HC
mBtuh
Power
kW
HE
MBtuh
LAT
°FCOP
HWC
MBtuhPSI FT
Airflow
cfm
TC
MBtuh
SC
MBtuh
S/T
Ratio
Power
kW
HR
MBtuhEER
HWC
MBtuh
20
8.5 2.00 4.6Operation not recommended
20
6.5 1.21 2.8
Operation not recommended13.0 3.52 8.1 10.0 2.70 6.2
17.0 6.55 15.11800 47.9 5.26 29.9 94.6 2.67 8.1
13.5 4.20 9.72200 48.9 5.23 31.1 90.6 2.74 7.5
30
8.5 1.95 4.51800 48.2 4.41 33.2 94.8 3.21 8.4
30
6.5 1.17 2.71500 59.6 37.0 0.62 1.75 65.5 34.1 -
2200 49.4 4.64 33.5 90.8 3.12 7.8 1800 60.7 40.6 0.67 1.82 66.9 33.4 -
13.0 3.42 7.91800 51.6 4.45 36.4 96.6 3.40 8.6
10.0 2.62 6.11500 60.4 37.3 0.62 1.66 66.1 36.4 -
2200 53.0 4.74 36.9 92.3 3.28 7.9 1800 61.4 40.8 0.66 1.75 67.3 35.1 -
17.0 6.36 14.71800 52.5 4.81 36.1 97.0 3.20 8.8
13.5 4.08 9.41500 60.7 37.3 0.61 1.61 66.2 37.7 -
2200 53.6 4.78 37.3 92.6 3.29 8.0 1800 62.2 40.8 0.66 1.69 68.0 36.8 -
40
8.5 1.90 4.41800 56.0 4.58 40.4 98.8 3.58 8.9
40
6.5 1.14 2.61500 60.6 39.5 0.65 2.04 67.5 29.7 -
2200 57.3 4.77 41.0 94.1 3.52 8.2 1800 61.8 43.2 0.70 2.12 69.0 29.1 -
13.0 3.32 7.71800 59.6 4.65 43.7 100.6 3.75 9.2
10.0 2.55 5.91500 61.3 39.9 0.65 1.94 67.9 31.7 -
2200 60.9 4.85 44.4 95.6 3.68 8.4 1800 62.4 43.5 0.70 2.03 69.4 30.7 -
17.0 6.17 14.31800 60.5 4.74 44.3 101.1 3.74 9.5
13.5 3.96 9.11500 61.8 39.9 0.65 1.88 68.2 32.9 -
2200 61.9 4.90 45.1 96.0 3.70 8.6 1800 63.2 43.5 0.69 1.97 69.9 32.1 -
50
8.5 1.85 4.31800 63.8 4.75 47.6 102.8 3.93 9.5
50
6.5 1.10 2.51500 61.6 41.7 0.68 2.19 69.1 28.1 -
2200 65.2 4.90 48.4 97.4 3.90 8.6 1800 62.8 45.3 0.72 2.33 70.8 27.0 -
13.0 3.21 7.41800 67.5 4.85 51.0 104.7 4.08 9.9
10.0 2.47 5.71500 62.2 42.1 0.68 2.14 69.5 29.0 -
2200 68.9 4.97 51.9 99.0 4.06 8.9 1800 63.5 45.8 0.72 2.28 71.2 27.9 -
17.0 5.98 13.81800 68.6 4.90 51.9 105.3 4.10 10.3
13.5 3.83 8.91500 62.8 42.6 0.68 2.11 70.0 29.8 -
2200 70.1 5.02 53.0 99.5 4.09 9.3 1800 64.1 46.2 0.72 2.24 71.7 28.6 -
60
8.5 1.80 4.21800 72.5 4.94 55.7 107.3 4.30 10.1
60
6.5 1.07 2.51500 59.2 40.9 0.69 2.46 67.6 24.0 3.1
2200 74.1 5.02 57.0 101.2 4.33 9.0 1800 60.7 44.4 0.73 2.62 69.6 23.1 3.1
13.0 3.11 7.21800 75.9 5.02 58.7 109.0 4.43 10.6
10.0 2.39 5.51500 59.8 41.3 0.69 2.42 68.0 24.7 2.9
2200 77.5 5.08 60.1 102.6 4.47 9.5 1800 61.3 44.9 0.73 2.57 70.1 23.9 2.9
17.0 5.79 13.41800 77.5 5.08 60.2 109.9 4.47 11.1
13.5 3.71 8.61500 60.4 41.7 0.69 2.37 68.5 25.4 2.7
2200 79.3 5.14 61.7 103.4 4.52 9.9 1800 61.9 45.3 0.73 2.53 70.5 24.5 2.7
70
8.5 1.75 4.01800 81.3 5.12 63.8 111.8 4.65 10.6
70
6.5 1.03 2.41500 56.7 40.1 0.71 2.74 66.1 20.7 4.6
2200 81.5 5.15 63.9 104.3 4.64 9.5 1800 58.1 44.0 0.76 3.20 69.0 18.2 4.6
13.0 3.01 7.01800 84.2 5.19 66.5 113.3 4.76 11.2
10.0 2.31 5.31500 57.3 40.5 0.71 2.69 66.5 21.3 4.3
2200 86.1 5.20 68.4 106.3 4.85 10.0 1800 59.1 43.9 0.74 2.86 68.9 20.7 4.3
17.0 5.60 12.91800 86.4 5.25 68.5 114.4 4.82 11.9
13.5 3.59 8.31500 57.8 40.8 0.71 2.64 66.9 21.9 4.2
2200 88.4 5.25 70.5 107.2 4.93 10.6 1800 59.7 44.4 0.74 2.81 69.3 21.2 4.1
80
8.5 1.68 3.91800 90.5 5.41 72.1 116.6 4.90 11.8
80
6.5 0.99 2.31500 52.9 38.8 0.73 3.13 63.6 16.9 6.1
2200 92.6 5.38 74.2 109.0 5.05 9.9 1800 54.9 42.2 0.77 3.34 66.3 16.4 6.1
13.0 2.91 6.71800 92.7 5.48 74.0 117.7 4.96 12.2
10.0 2.23 5.21500 53.5 39.2 0.73 3.07 64.0 17.4 5.8
2200 94.9 5.42 76.4 109.9 5.13 10.6 1800 55.4 42.6 0.77 3.27 66.6 17.0 5.8
17.0 5.41 12.51800 95.5 5.54 76.6 119.1 5.05 12.6
13.5 3.47 8.01500 54.0 39.6 0.73 3.02 64.3 17.9 5.5
2200 97.9 5.48 79.2 111.2 5.24 11.2 1800 56.0 43.0 0.77 3.22 67.0 17.4 5.5
90
8.5 1.60 3.71800 99.8 5.70 80.3 121.3 5.13 11.7
90
6.5 0.96 2.21500 49.1 37.6 0.77 3.53 61.1 13.9 8.2
2200 102.2 5.62 83.0 113.0 5.33 10.3 1800 51.3 40.8 0.80 3.76 64.1 13.6 8.2
13.0 2.80 6.51800 101.1 5.76 81.4 122.0 5.14 12.6
10.0 2.15 5.01500 49.7 37.9 0.76 3.46 61.4 14.4 7.8
2200 103.6 5.64 84.3 113.6 5.38 11.1 1800 51.7 41.2 0.80 3.68 64.3 14.1 7.8
17.0 5.22 12.11800 104.5 5.83 84.6 123.8 5.25 13.4
13.5 3.34 7.71500 50.7 38.2 0.75 3.50 62.6 14.5 7.3
2200 107.3 5.70 87.9 115.2 5.52 11.9 1800 52.3 41.6 0.80 3.62 64.7 14.4 7.4
100
8.5 1.55 3.6
Operation not recommended
100
6.5 0.92 2.11500 44.7 36.4 0.81 4.02 58.4 11.1 10.31800 46.9 39.5 0.84 4.29 61.5 10.9 10.3
13.0 2.70 6.2 10.0 2.07 4.81500 45.2 36.7 0.81 3.94 58.6 11.5 9.71800 47.3 39.9 0.84 4.20 61.7 11.3 9.8
17.0 5.03 11.6 13.5 3.22 7.51500 45.6 37.1 0.81 3.87 58.8 11.8 9.21800 47.8 40.3 0.84 4.13 61.9 11.6 9.2
110
8.5 1.50 3.5
110
6.5 0.89 2.11500 40.3 35.2 0.87 4.52 55.7 8.9 13.01800 42.4 38.2 0.90 4.82 58.9 8.8 13.1
13.0 2.60 6.0 10.0 2.00 4.61500 40.7 35.5 0.87 4.42 55.8 9.2 12.31800 42.9 38.6 0.90 4.72 59.0 9.1 12.4
17.0 4.84 11.2 13.5 3.10 7.21500 41.1 35.9 0.87 4.35 55.9 9.5 11.61800 43.3 39.0 0.90 4.64 59.1 9.3 11.7
120
8.5 1.40 3.2
120
6.5 0.85 2.01500 38.7 34.1 0.88 5.54 57.6 7.0 16.11800 39.6 37.1 0.94 5.67 58.9 7.0 16.2
13.0 2.50 5.8 10.0 1.92 4.41500 39.2 34.4 0.88 5.24 57.1 7.5 15.21800 39.9 37.3 0.93 5.38 58.3 7.4 15.3
17.0 4.65 10.7 13.5 2.98 6.91500 39.6 34.4 0.87 5.07 56.9 7.8 14.31800 40.4 37.3 0.92 5.23 58.2 7.7 14.5
Performance capacities shown in thousands of Btuh. 11/2/20
Performance Data cont.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 20 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Wiring Schematics
Aurora Variable Speed
97P842-01A
Vio
let(14)
RVRVCCCC
Condensate
TTYellow
(117)
Yellow(116)
FP1
Orange(121)
Orange(120)
RV
Black(15)
Green(11 )Brown(115)
NO TE 2
NOTE 1
Unit Power 208-230/60/1
L2 L1
CCT2 T1
Red208V
GG
5A C
ircuit Breaker
5A C
ircuit Breaker
Black(3 )
Black(2 )
Gray/White(4)
1
2PB1
2
11
2PB1
2
1
PS
1
3
2
Bla
Red
Black
L1 aV
AID Tool
Communicating Thermostat
To Master onVS Drive
B
123
A-B+
C 123
A-B+
C
TT Brown(127)Brown(126)
T Purple(131)Purple(130)
GNDOUT5DC
324
Green(13 4)White(133)Brown(132)
Brown(102)
Brown(101)
Black(1 04)
Black(1 03)
Violet(8)
Violet(7)
Brown(10)
Orange(9)
SUC
PSU
C P
AUXILIARY HEAT CT
BLOWER CT
PERFORMANCEOPTION
324
FLOW METER
Black/White(5)
TTHW HW
White
White
BlackBlack
OrangeOrange
HOT WATEROPTION
Red
Black
Circuit Breaker
Circuit Breaker
BlueBlue
BlueBlue
Pump Slave Input/Output
Home Automation
Smar t Gr id
Future Use
Dehumidification Output
Accessory 2 Output
Analog Output 0-10VDC
NOTE: 8
NOTE: 9
208-230/60/1
Pump
GGG
PumpPumpExt Pump
1/2 hp Total Ext Pump
1/2 hp Total
Gray(136)
Gray(135)
White(129)White(128)
T
SCT
P8
MOT
OR P6
RS48
5 P7
ZONE P9
ABC
STEP
PER
ANA
ACC2
DHDI
V
NO
CO
M
K6
NO
CO
M
K5
C R L1 L1 L2 L2P1
2P1
0P5
P11
CR(-)(+) CR(-)(+) CR(-)(+)
P4P2
K1K2
K3
HA2
HA1
SGI
LOO
PVS
DAT
AVS
PUM
PPU
MPSL
AVE
P3
V+CRTXRX +5
P14
LLT
P1LA
TFL
OW
LWT
EWT
43
FAN
43
CT1
21
AUX
21
StatusG
DISC
HP1
6
P17
P18
P15
(Aurora Expansion Board)AXB™
See Figure 1 for DHW wiring.
SW1
Modbus Add. IDFuture Use
12345
ONOFF
Future UseAcc 2 – Dip 4Acc 2 – Dip 5
CT2
SCT
P8
MOT
OR P6
RS48
5 P7
ZONE P9
ABC
STEP
PER
ANA
ACC2
DHDI
V
NO
CO
M
K6
NO
CO
M
K5
C R L1 L1 L2 L2P1
2P1
0P5
P11
CR(-)(+) CR(-)(+) CR(-)(+)
P4P2
K1K2
K3
HA2
HA1
SGI
LOO
PVS
DAT
AVS
PUM
PPU
MPSL
AVE
P3
V+CRTXRX +5
P14
LLT
P1LA
TFL
OW
LWT
EWT
43
FAN
43
CT1
21
AUX
21
StatusG
DISC
HP1
6
P17
P18
P15
(Aurora Expansion Board)AXB™
See Figure 1 for DHW wiring.
SW1
Modbus Add. IDFuture Use
12345
ONOFF
Future UseAcc 2 – Dip 4Acc 2 – Dip 5
CT2
CS
+5C
S+5
21
CC
INOU
T
Pink(140)
Pink(139)
VS
GND24 VAC
0-10DC
12
3
R
C
ABC BOARD
AXB BOARD
MODULATING VALVE
12
Red
WhiteGreen
NO TE: 13
VARIABLE SPEED PUMP
LOW VOLTAGESEE 97P927-01
VARIABLE SPEED PUMP
LOW VOLTAGESEE 97P927-01
VARIABLE SPEED PUMP
HIGH VOLTAGE
SEE 97P927-01
VARIABLE SPEED PUMP
HIGH VOLTAGE
SEE 97P927-01
SW1
P5JW2
P9
LO
O/B
Y2WDH
P8 P7
RS485 NET RS485 NET
P6
RS485 EXP
P3
Com1LED5
Com2LED5
Test Mode
P1
ALMALGACC COMACC NOACC NC
RC
G
EH2CEH1CCOC R - +C R - +
CC2 CC F C R F FG CC CCGCC2HI
CC2LO
CC2G REVREVFP1 FP1
Aurora Base Control(ABC)
K1-RV Relay
K2-CC Relay
K3-CC2 Relay
K4-Fan RelayK5-Alarm Relay
K6-Acc Relay
YC
R
ESLS
P2EH1
GG GG
Y1
SW1
P5JW2
P9
LO
O/B
Y2WDH
P8 P7
RS485 NET RS485 NET
P6
RS485 EXP
P3
Com1LED5
Com2LED5
Test Mode
P1
ALMALGACC COMACC NOACC NC
RC
G
EH2CEH1CCOC R - +C R - +
CC2 CC F C R F FG CC CCGCC2HI
CC2LO
CC2G REVREVFP1 FP1
Aurora Base Control(ABC)
K1-RV Relay
K2-CC Relay
K3-CC2 Relay
K4-Fan RelayK5-Alarm Relay
K6-Acc Relay
YC
R
ESLS
P2EH1
G G
Y1
SW1
P5JW2
P9
LO
O/B
Y2WDH
P8 P7
RS485 NET RS485 NET
P6
RS485 EXP
P3
Com1LED5
Com2LED5
Test Mode
P1
ALMALGACC COMACC NOACC NC
RC
G
EH2CEH1CCOC R - +C R - +
CC2 CC F C R F FG CC CCGCC2HI
CC2LO
CC2G REVREVFP1 FP1
Aurora Base Control(ABC)
K1-RV Relay
K2-CC Relay
K3-CC2 Relay
K4-Fan RelayK5-Alarm Relay
K6-Acc Relay
YC
R
ESLS
P2EH1
G G
Y1
Perfect Speed Blower Motor
Grn
4 23 1
PWM
P13 Connects Here
P112 3 4 51
Not U
sed
COM
Feed
back
15 10163 815 10163 8
Perfect Speed Blower Motor
Grn
4 23 1
PWM
P13 Connects Here
P112 3 4 51
Not U
sed
COM
Feed
back
15 10163 8NOTE 14
Perfect Speed Blower Motor
Grn
4 23 1
PWM
P13 Connects Here
P112 3 4 51
Not U
sed
COM
Feed
back
15 10163 8NOTE 14
RVO
range(121)
RV
B
W1W1W1W1
MoMoMoMo
H2
VR
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 21 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Wiring Schematics cont.
Aurora Variable Speed cont.
97P842-01A
NOTE 7NOTE 7
NOTE 6NOTE 6
Page 1Page 1
Transformer
24V
Transformer
24V
ECM BlowerMotor
P112 3 4 51
Green(10 7)
16 112 15 10
PWM
C1 C2R G
33
CFM
To P2 on Electric Heat Board
TTRVRV
HP
Black(125)
Black(124)
Blue(123)
Blue(122)
LP
Black(119)
Black(118)
FP2
TTYellow
(117)
Yellow(116)
FP1
Orange(121)
Orange(120)
RV
Violet(111)
Blue(110)
Yellow(109)
Green/Yellow(108)
Black/White
Yellow
Red208V
1C
21
C2
43
24
32
1C
24
32
1C
24
32
Black(1 13)
PS3
Brown(106)
Blue240V
Black
L1 and L2 on VS Drive
12
L1L2
Black(1 14)
Black(1 12)
Orange(105)
BLOWERCURRENT
TRANSDUCER(CT)
Red
Black
r
r
NOCOM
K6 RelayConnects to L2 and NO on AXB Board
L2
NOCOM
K6 RelayConnects to L2 and NO on AXB Board
L2
Figure 1:Optional Internal
Hot Water Generation Pump Wiring Schematic
DHW Pump
Blue(137)
Blue(138)
Cabinet HW Switch
3
21
PurpleDHW Pump
Blue(137)
Blue(138)
Cabinet HW Switch
3
21
Purple
NOCOM
K6 RelayConnects to L2 and NO on AXB Board
L2
Figure 1:Optional Internal
Hot Water Generation Pump Wiring Schematic
DHW Pump
Blue(137)
Blue(138)
Cabinet HW Switch
3
21
Purple
Communicating Thermostat Dual Fuel Wiring DiagramUsing Field Installed Relay
24 VDC
R f rom Foss il Fue l Furnac e
To Foss il Fuel Furnac e W input
EH1
C
ABCBoard
Note 12 : Fi eld inst al led SPST dual fuel rela y (R equi re d for dual fuel inst all ati on)
5 – Low voltage wiring CLASS 2 .
NotesNotes
3 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is requ ired.
1 - Switch blue and red wires for 208V operation. 2 - The b lk/wh and gray/wh wires are removed when A ux Heat is installed
4 – Variable speed pump low voltage harness provided with V ariab le Speed Flow Center.
6 - Wires provided fo r Auxiliary Heat low voltage control. Wires are secured a t blower.7 – When Auxilia ry Heat is field installed the harness will t hen be connected to the auxiliary heat unit. The auxilia ry heat un it will then power the blower. Refer to EAS/EA M/EAL Auxiliary Heat kit installation instructions.
9 – Fie ld Connected : Refer to Installa tion Manual and Auxilia ry Heat Instructions for Current Transducer insta llation .10 – Communication cab le routed through Ferrite Toro id four times.11 – Compressor power cable routed through Ferrite Toroid th ree times.12 - Fie ld installed SPST relay required for dual fuel installation.
Notes
3 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is requ ired.
1 - Switch blue and red wires for 208V operation. 2 - The b lk/wh and gray/wh wires are removed when A ux Heat is installed
4 – Variable speed pump low voltage harness provided with V ariab le Speed Flow Center.
6 - Wires provided fo r Auxiliary Heat low voltage control. Wires are secured a t blower.7 – When Auxilia ry Heat is field installed the harness will t hen be connected to the auxiliary heat unit. The auxilia ry heat un it will then power the blower. Refer to EAS/EA M/EAL Auxiliary Heat kit installation instructions.
9 – Fie ld Connected : Refer to Installa tion Manual and Auxilia ry Heat Instructions for Current Transducer insta llation .10 – Communication cab le routed through Ferrite Toro id four times.11 – Compressor power cable routed through Ferrite Toroid th ree times.12 - Fie ld installed SPST relay required for dual fuel installation.13 - Wiring harness supplied with va lve.
23
P9
54
1
L2 L1 L2 L1
Green
P112 3 4 51
VioletBlue
BrownOrange
HE1 TS1TS1HE1 TS1
HE3 TS3TS3HE3 TS3
HE2 TS2TS2HE2 TS2
HE4 TS4TS4HE4 TS4
Connects to variable speed ECM motor only
60 AMP BRK1
60 AMP BRK2
GGGG
K1
K2
K3
K4
NO
NO
NO
NO
EA Series PCB
P241 2 3C
G
G
G
G
K5
NO
K6
NO
K7
NO
K8
NO
Gray
Yellow
GrayYellow
Black
Pink
Black
Pink
Pink
Pink
Gray
Black
Yellow
Gray
Black
Yellow
41 2 3CP1
COMCOM
COM COM
COM COM
COMCOM
Aux heat staging
FB1
FB2
FB3
FB4
P3 on Aurora ABC Board
P3EH2C EH1 CCO P3EH2C EH1 CCO
Light emitting diode - Green
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField l ine voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal
Thermal Limit Switch
Field wire lug
GroundHE -
PB -
Heater element
Power block
Legend
N.O., N.C.
G
L1
Breaker
1 2 3PTS
Electric Heat RelayK*
Fused BackupFB
K*
Fused BackupFB
Light emitting diode - Green
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField l ine voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal
Thermal Limit Switch
Field wire lug
GroundHE -
PB -
Heater element
Power block
Legend
N.O., N.C.
G
L1
Breaker
1 2 3PTS
Electric Heat RelayK*
Fused BackupFB
2 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when sing le source power is required .
1 - Use copper conductors.
3 – Jumpers wires a re Factory Installed, and arerequired fo r auxiliary heat operation. 4 – Low voltage wiring CLASS 2 .
2 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when sing le source power is required .
1 - Use copper conductors.
3 – Jumpers wires a re Factory Installed, and arerequired fo r auxiliary heat operation. 4 – Low voltage wiring CLASS 2 .
NOTE 3
With optional EA Series 20kW Auxiliary Electric Heat Shown
CFM
P13
P4
SW1
P3
SW2
On
Future Use L Output Type
CC – Dual/SingleAcc – Dip 5Acc – Dip 4
RV – B/OFP2 – 15°F/30°FFP1 – 15°F/30°F
Test Mode
F1-3A
C
PWM
12345678
EH2C
Off
Faul tLED1
R
StatusLED3
ConfigLED2
REVREVFP1 FP1 FP2 FP2 LPS LPSHPSHPS
F
R
C
CCGY1
YY
GGG
CFM
P13
P4
SW1
P3
SW2
On
Future Use L Output Type
CC – Dual/SingleAcc – Dip 5Acc – Dip 4
RV – B/OFP2 – 15°F/30°FFP1 – 15°F/30°F
Test Mode
F1-3A
C
PWM
12345678
EH2C
Off
Faul tLED1
R
StatusLED3
ConfigLED2
REVREVFP1 FP1 FP2 FP2 LPS LPSHPSHPS
F
R
C
CCGY1
Y
G
CFM
P13
P4
SW1
P3
SW2
On
Future Use L Output Type
CC – Dual/SingleAcc – Dip 5Acc – Dip 4
RV – B/OFP2 – 15°F/30°FFP1 – 15°F/30°F
Test Mode
F1-3A
C
PWM
12345678
EH2C
Off
Faul tLED1
R
StatusLED3
ConfigLED2
REVREVFP1 FP1 FP2 FP2 LPS LPSHPSHPS
F
R
C
CCGY1
Y
G
8 – Brown blower power wire rou ted through Current Transducer two times.
14 - On units with the NIDEC ECM motor the P13 harness connects to the jumper harness on the motor.
RVO
range(121)
RV
B
W1W1W1W1
MMMM
H2
VVVVR
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 22 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Wiring Schematics cont.
Aurora Variable Speed Drive/EEV Wiring
97P842-01B
Unit Power 208-230/60/1
L2L1
CCT1
T2
L2L1
CCT1
T2
GG
TT TT
Compressor Ambient
Discharge Line Temp
Suction Pressure(Red Plug)
Discharge Pressure(Green Plug)
Bla
ck
Bro
wn
Blu
e
Bla
ck
Bro
wn
Blu
e
Red
RedBla
ck
Bla
ck
Master
123
EEV2
1234
S-Am
bien
t
1 2
S-D
1 2
P-O
1 2 3 4
P-C
1 2 3 4
RLY-
1
1 2 3
BCO
M O R B+A- C+ - + -
COM
5 VD
COU
T
N/A
COM
5 VD
COU
T
N/A
(+) (-)
12
L1L2
DanfossVariable Speed
Drive
12
T1T2
T3 31
2T1
T2T3 3
1 2+ -
TT
Entering Water Temp
EWT
Bla
ck
Bla
ck
2 13 4
COM
OUT
5 VD
CN/
A
2 13 4
COM
OUT
5 VD
CN/
A
2 13 4
COM
OUT
5 VD
CN/
A
2 13 4
COM
OUT
5 VD
CN/
A
To Aurora Board
RS485 EXP
C
R
(-)
(+)
RS485 EXP
C
R
(-)
(+)
ABC P6
RS485 EXP
C
R
(-)
(+)
ABC P6To AXB Board
ABC
(+)
(-)
R
C
AXB P9
C
S-AU
X
Metal Flexible Conduit
B+
C
R
(-)
(+) Green
White
Red
Black
5VAC
Circuit Breaker
Circuit Breaker
Ferrite Toroid
Ferrite Toroid
Black
Black
Red
Red G
NOTE 11
NOTE 10
White Blue
Red GreenBlack Black Red
BlueWhite
EEV CONTROL BOARD EEV CONTROL BOARD
EEV COIL
LAT
SUCT ION TEMP
EEV COMM
NOT USED
NOT USED
EEV CONTROL BOARD
EEV COIL
LAT
SUCT ION TEMP
EEV COMM
NOT USED
NOT USED
EEV 1
MASTER
EEV 2
EXT. FAN
S_AMBIENTS_AUXS_D
P_O
P_C
RLY 1
L1L2
EEV 1
MASTER
EEV 2
EXT. FAN
S_AMBIENTS_AUXS_D
P_O
P_C
RLY 1
L1L2
VARIABLE SPEED DRIVE END VIEWS
T1
T2
T3
T1
T2
T3
EEV 1
MASTER
EEV 2
EXT. FAN
S_AMBIENTS_AUXS_D
P_O
P_C
RLY 1
L1L2
VARIABLE SPEED DRIVE END VIEWS
T1
T2
T3
POWER TO VS DRIVE
POWER TO COMPRESSOR
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 23 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Aurora Variable Speed Drive/EEV Wiring cont.
Wiring Schematics cont.
97P842-01B
T1T3
T2
T1T3
T2
Red
ack Suct
ion T
emp
KM2
1 2
EEV
Outpu
tKM
9
1 2 3 4
GND S2
12 V
DC X1 X2 Y1
Danfoss EEV Control
Powe
rKM
4
1 2 3 4RB+ A-C
Leav
ing A
ir Te
mp
(LAT
)KM
3
1 2GN
D S2
5
TTB
lack
Bla
ck
TTB
lack
Bla
ck
Suction Line Temp
Discharge Air Temp
Y2
1 2 3 4
+ X1 X2 Y15
Y2
1 2 3 4
+ X1 X2 Y15
Y2
Ora
nge
Red
Yello
w
Bla
ck
Gra
y
Bipolar Stepper Motor
VS Compressor
Blue
Green
Red Connector (4 Pin)
Current Transducer (CT)
Thermistor
Light emitting diode - Green
Relay coil
Capacitor w/ bleed res is tor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesJunctionQuick connect terminal
Wire nut
Field wire lug
Ground
Fuse
CC -CO -K6 -K5 -CR3 -CR4 -
F1 and F2 -
WCL -
HE -HP -
LP -
PB1, PB2 - PS -RV -SW1 -SW1 -SW2 -
TS -
Compressor ContactorCondensate overflow sensorDHW pump relayLoop pump relay
Fuses
Water Coil Limit Sensor
Heater elementHigh pressure switch
Low pressure switch
Power blocksPower stripReversing Valve coilDIP package 5 position AXBTEST MODE ABC BoardDIP package 8 position ABC Board
Thermal limit switch
Legend
Relay Contacts-N.O., N.C.
GG
TT
132P
132P
L1L1
PSC Fan Speed RelayPSC Fan Power Relay
ER1 to ER4 - Aux heat stage relays
HWL - Hot water limit sensorSC - Start Contactor
Start RelaySR -
CS - Compressor Solenoid
Current Transducer (CT)
Thermistor
Light emitting diode - Green
Relay coil
Capacitor w/ bleed res is tor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesJunctionQuick connect terminal
Wire nut
Field wire lug
Ground
Fuse
CC -CO -K6 -K5 -CR3 -CR4 -
F1 and F2 -
WCL -
HE -HP -
LP -
PB1, PB2 - PS -RV -SW1 -SW1 -SW2 -
TS -
Compressor ContactorCondensate overflow sensorDHW pump relayLoop pump relay
Fuses
Water Coil Limit Sensor
Heater elementHigh pressure switch
Low pressure switch
Power blocksPower stripReversing Valve coilDIP package 5 position AXBTEST MODE ABC BoardDIP package 8 position ABC Board
Thermal limit switch
Legend
Relay Contacts-N.O., N.C.
G
T
132P
L1
PSC Fan Speed RelayPSC Fan Power Relay
ER1 to ER4 - Aux heat stage relays
HWL - Hot water limit sensorSC - Start Contactor
Start RelaySR -
CS - Compressor Solenoid
SW1-4 SW1-5 DESCRIPTIONON ON Cycles with BlowerOFF ON Cycles with CC rst stage compressor or compressor spd 1-12ON OFF Cycles with CC2 second stage of compressor or comp spd 7-12OFF OFF Cycles with DH from ABC board
AXB Accessory 2 DIP Se ngs
DESCRIPTION SW2-4 SW2-5Cycle with Blower ON ONCycle with Compressor OFF OFFWater Valve Slow Opening ON OFFCycle with Comm. T-stat Hum Cmd OFF ON
ABC SW2 Accessory Relay
Black
Yellow Orange
Blue Color identif icat ion tape on wire.
Black Black
Yellow Orange
HA2
HA1
HOM
ESM
ART
GRID
AXB P4
HA2
HA1
HOM
ESM
ART
GRID
AXB P4WATER SIREN
HOME AUTOMATION ACCESSORIES
HA2
HA1
HOM
ESM
ART
GRID
AXB P4WATER SIREN
HOME AUTOMATION ACCESSORIES
CC2
EH1
Facto
ry
Fault
ALG
ALMLSES AC
C c
S tatus
AURORA BASE CONTROL™
RV – K1
CC2
CC – K2
CC Hi – K3
Fan – K4
Alarm – K5
Acc – K6
ACC
no
ACC
nc
O/BCRLO G Y1 Y2 W DH
3A-F
use
O/BCRLO G Y1 Y2 W DHO/BCRLO G Y1 Y2 W DH
LOG
HICCGCCFGFR
HPHPLP
FP2FP2FP1
REVREV
CFM
PWM
ECM PWM
Facto
ry
Factory Fan Connection
R R
CC
C
RS 4
85
EH2C
EH1C
CO
(+)(-)RCRS
485
Exp
Facto
ry
Com1
Com2
Config
GG
GG
G
YR
SW1 Test
FP1 – 15oF/30oF
JW2 - Alarm
P11
P5
P2 P1
P8
P7
P9
P6
P3
SW2
P13P4 FP2 – 15oF/30oF
RV – B/O
ACC – Dip 4
ACC – Dip 5
CC – Dual/Single
L – Pulse/Continuous
Reheat/Normal
Facto
ry U
se
Field ConnectionsField Connections
C
LP
FP1
F
CC
G
Y1
1
2
3
4
5
6
7
8
Off On
N/A
RS48
5 NE
T
CC2
EH1
Facto
ry
Fault
ALG
ALMLSES AC
C c
S tatus
AURORA BASE CONTROL™
RV – K1
CC2
CC – K2
CC Hi – K3
Fan – K4
Alarm – K5
Acc – K6
ACC
no
ACC
nc
O/BCRLO G Y1 Y2 W DH
3A-F
use
O/BCRLO G Y1 Y2 W DH
LOG
HICCGCCFGFR
HPHPLP
FP2FP2FP1
REVREV
CFM
PWM
ECM PWM
Facto
ry
Factory Fan Connection
R R
CC
C
RS 4
85
EH2C
EH1C
CO
(+)(-)RCRS
485
Exp
Facto
ry
Com1
Com2
Config
G
G
G
YR
SW1 Test
FP1 – 15oF/30oF
JW2 - Alarm
P11
P5
P2 P1
P8
P7
P9
P6
P3
SW2
P13P4 FP2 – 15oF/30oF
RV – B/O
ACC – Dip 4
ACC – Dip 5
CC – Dual/Single
L – Pulse/Continuous
Reheat/Normal
Facto
ry U
se
Field ConnectionsField Connections
C
LP
FP1
F
CC
G
Y1
1
2
3
4
5
6
7
8
Off On
N/A
RS48
5 NE
T
LED3
LED2LED1
Slow FlashFast FlashFlash Code
Fault - Loss of Charge Flash Code 71Safe Mode - Suction Temperature Sensor Flash Code 72
Fault - High Drive Temperature Flash Code 58Fault - Drive Internal Error MOC/AOC Flash Code 59Fault - Multiple Safe Modes Flash Code 61
Fault - Over Current Flash Code 56Fault - Over/Under Voltage Flash Code 57
Flash Code 54Fault - Compressor Out of Envelope Flash Code 55
Fault - Condensing Pressure SensorFault - Low Supply Voltage
Derate - Low Condensing Pressure Flash Code 44Derate - High Condensing Pressure Flash Code 45Derate - Outer Power Limit Flash Code 46
Derate - Drive Temperature Flash Code 41Derate - High Discharge Temperature Flash Code 42Derate - Low Suction Temperature Flash Code 43
Alarm - Home Automation 1 Flash Code 23Alarm - Home Automation 2 Flash Code 24Fault - EEV Error Flash Code 25
Aurora LED Flash Codes1 second on and 1 second off
No Software Overide OFF
100 milliseconds on and 100 milliseconds off100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating
Random Start Delay (Alternating Colors)Status LED (LED1, Green) Fast FlashConfiguration LED (LED 2, Yellow) Fast FlashFault LED (LED 3, Red) Fast Flash
Configuration LED (LED 2, Yellow)
Fault LED (LED 1, Red)Normal Mode OFFInput Fault Lockout Flash Code 1
Slow FlashStatus LED (LED 3, Green)
Normal Mode ONControl is Non - Functional OFFTest Mode Slow Flash
Freeze Detection - FP1 Flash Code 5
Flash Code 2Low Pressure Lockout Flash Code 3Freeze Detection- FP2 Flash Code 4
High Pressure Lockout
Future UseDehumidification Mode
DIP Switch Overide
Flash Code 3Future Use Flash Code 4Load Shed Flash Code 5
Reserved Flash Code 6Condensate Overflow Lockout Flash Code 7Over/Under Voltage Shutdown Flash Code 8Future Use Flash Code 9Fault- FP1 and FP2 Sensor Error Flash Code 11Future Use Flash Code 12Non-Critical AXB Sensor Error Flash Code 13Critical AXB Sensor Error Flash Code 14
Flash Code 2
Safe Mode - Ambient Temperature Sensor Flash Code 49Future Use Flash Code 17Non-Critical Communication Error Flash Code 18
Alarm - Hot Water Flash Code 15Fault Variable Speed Pump Flash Code 16
Fault LED (LED 1, Red) Cont.
ESD Flash Code 6Future Use Flash Code 7
Flash Code 19Alarm - Low Loop Pressure Flash Code 21Fault - Communication ECM Fan Motor Error Flash Code 22
Fault - Discharge Temperature Sensor Flash Code 51Fault - Suction Pressure Sensor Flash Code 52
Fault - Critical Communication Error
Flash Code 53
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 24 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Wiring Schematics cont.
Aurora Variable Speed with UPC
97P842-02A
Vio
let(14)
Transforme
2
Transforme
2
TTRVRV
CCCC
H
Condensate
Black(124)
Blue(123)
Blue(122)
LP
Black(119)
Black(118)
FP2
TTYellow
(117)
Yellow(116)
FP1
Orange(121)
Orange(120)
RV
Black(15)
Green(11 )Brown(115)
NOTE 2
NOTE 1
Unit Power 208-230/60/1
L2 L1
CCT2 T1
Red208V
GG
5A C
ircuit Breaker
5A C
ircuit Breaker
Black(3 )
Black(2 )
Gray/White(4)
1
2PB1
2
11
2PB1
2
1
Black(1 13
PS
1
3
2
Blue240V
Black
Red
Black
L1 and L2 on VS Drive
12
L1L2
To Master onVS Drive
Black(1 14)
123
A-B+
C 123
A-B+
C
TT Brown(127)Brown(126)
T Purple(131)Purple(130)
GNDOUT5DC
324
Green(13 4)White(133)Brown(132)
Brown(102)Brown(101)
Black(1 04)
Black(1 03)
Violet(8)
Violet(7)
Brown(10)
Orange(9)
SUC
PSU
C P
AUXILIARY HEAT CT
BLOWER CT
PERFORMANCEOPTION
324
FLOW METER
Black(1 12)
Black/White(5)
TTHW HW
White
White
BlackBlack
OrangeOrange
HOT WATEROPTION
O
BLOWCURRE
TRANSDU(CT)
Red
Black
Circuit Breaker
Circuit Breaker
BlueBlue
BlueBlue
Pump Slave Input/Output
Home Automation
Smar t Gr id
Future Use
Dehumidification Output
Accessory 2 Output
Analog Output 0-10VDC
NOTE: 8
NOTE: 9
208-230/60/1
Pump
GGG
PumpPumpExt Pump
1/2 hp Total Ext Pump
1/2 hp Total
Gray(136)
Gray(135)
White(129)White(128)
T
SCT
P8
MOT
OR P6
RS48
5 P7
ZONE P9
ABC
STEP
PER
ANA
ACC2
DHDI
V
NO
CO
M
K6
NO
CO
M
K5
C R L1 L1 L2 L2P1
2P1
0P5
P11
CR(-)(+) CR(-)(+) CR(-)(+)
P4P2
K1K2
K3
HA2
HA1
SGI
LOO
PVS
DAT
AVS
PUM
PPU
MPSL
AVE
P3
V+CRTXRX +5
P14
LLT
P1LA
TFL
OW
LWT
EWT
43
FAN
43
CT1
21
AUX
21
StatusG
DISC
HP1
6
P17
P18
P15
(Aurora Expansion Board)AXB™
See Figure 1 for DHW wiring.
SW1
Modbus Add. IDFuture Use
12345
ONOFF
Future UseAcc 2 – Dip 4Acc 2 – Dip 5
CT2
SCT
P8
MOT
OR P6
RS48
5 P7
ZONE P9
ABC
STEP
PER
ANA
ACC2
DHDI
V
NO
CO
M
K6
NO
CO
M
K5
C R L1 L1 L2 L2P1
2P1
0P5
P11
CR(-)(+) CR(-)(+) CR(-)(+)
P4P2
K1K2
K3
HA2
HA1
SGI
LOO
PVS
DAT
AVS
PUM
PPU
MPSL
AVE
P3
V+CRTXRX +5
P14
LLT
P1LA
TFL
OW
LWT
EWT
43
FAN
43
CT1
21
AUX
21
StatusG
DISC
HP1
6
P17
P18
P15
(Aurora Expansion Board)AXB™
See Figure 1 for DHW wiring.
SW1
Modbus Add. IDFuture Use
12345
ONOFF
Future UseAcc 2 – Dip 4Acc 2 – Dip 5
CT2
CS
+5C
S+5
21
CC
INOU
T
Pink(140)Pink(139)
VS
GND24 VAC
0-10DC
12
3
R
C
ABC BOARD
AXB BOARD
MODULATING VALVE
12
Red
WhiteGreen
NO TE: 13
UPC ControllerUPC Controller
ZS Sensor
VARIABLE SPEED PUMP
LOW VOLTAGESEE 97P927-01
VARIABLE SPEED PUMP
LOW VOLTAGESEE 97P927-01
VARIABLE SPEED PUMP
HIGH VOLTAGESEE 97P927-01
VARIABLE SPEED PUMP
HIGH VOLTAGESEE 97P927-01
SW1
P5JW2
P9
LO
O/B
Y2WDH
P8 P7
RS485 NET RS485 NET
P6
RS485 EXP
P3
FutuL Outp
CC – DuaAcc Acc
RVFP2 – 15°FFP1 – 15°F
Com1LED5
Com2LED5
Test Mode
P1
ALMALGACC COMACC NOACC NC
RC
G
EH2CEH1CCOC R - +C R - +
StatusLED3
CoLE
CC2 CC F C R F FG CC CCGCC2HI
CC2LO
CC2G REVREVFP1 FP1 FP2 FP2 LPS LPSHPS
Aurora Base Control(ABC)
K1-RV Relay
K2-CC Relay
K3-CC2 Relay
K4-Fan RelayK5-Alarm Relay
K6-Acc Relay
CCGY1C
R
ESLS
P2EH1
GG GG
GGG
Y1
SW1
P5JW2
P9
LO
O/B
Y2WDH
P8 P7
RS485 NET RS485 NET
P6
RS485 EXP
P3
FutuL Outp
CC – DuaAcc Acc
RVFP2 – 15°FFP1 – 15°F
Com1LED5
Com2LED5
Test Mode
P1
ALMALGACC COMACC NOACC NC
RC
G
EH2CEH1CCOC R - +C R - +
StatusLED3
CoLE
CC2 CC F C R F FG CC CCGCC2HI
CC2LO
CC2G REVREVFP1 FP1 FP2 FP2 LPS LPSHPS
Aurora Base Control(ABC)
K1-RV Relay
K2-CC Relay
K3-CC2 Relay
K4-Fan RelayK5-Alarm Relay
K6-Acc Relay
CCGY1C
R
ESLS
P2EH1
G G
G
Y1
SW1
P5JW2
P9
LO
O/B
Y2WDH
P8 P7
RS485 NET RS485 NET
P6
RS485 EXP
P3
FutuL Outp
CC – DuaAcc Acc
RVFP2 – 15°FFP1 – 15°F
Com1LED5
Com2LED5
Test Mode
P1
ALMALGACC COMACC NOACC NC
RC
G
EH2CEH1CCOC R - +C R - +
StatusLED3
CoLE
CC2 CC F C R F FG CC CCGCC2HI
CC2LO
CC2G REVREVFP1 FP1 FP2 FP2 LPS LPSHPS
Aurora Base Control(ABC)
K1-RV Relay
K2-CC Relay
K3-CC2 Relay
K4-Fan RelayK5-Alarm Relay
K6-Acc Relay
CCGY1C
R
ESLS
P2EH1
G G
G
Y1
Perfect Speed Blower Motor
Grn
4 23 1
PWM
P13 Connects Here
P112 3 4 51
Not U
sed
COM
Feed
back
15 10163 815 10163 8
Perfect Speed Blower Motor
Grn
4 23 1
PWM
P13 Connects Here
P112 3 4 51
Not U
sed
COM
Feed
back
15 10163 8NOTE 14
Perfect Speed Blower Motor
Grn
4 23 1
PWM
P13 Connects Here
P112 3 4 51
Not U
sed
COM
Feed
back
15 10163 8NOTE 14
meme
H
))Black(1
24)
1
O
WRE
SDCT
FutFutFutFututputputputpF tFFF
DuaDuaDuaDuatttt
AccAccAccAccAccAccAccAcc
RRRR5555°°°°5555°°°°
CCCCLLLL
PS
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 25 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Wiring Schematics cont.
Aurora Variable Speed with UPC cont.
97P842-02A
NOTE 7NOTE 7
NOTE 6NOTE 6
Page 1Page 1
Transformer
24V
Transformer
24V
ECM BlowerMotor
P112 3 4 51
Green(10 7)
16 112 15 10
PWM
C1 C2R G
33
CFM
To P2 on Electric Heat Board
TT
HP
Black(125)
Black(124)
Blue(123)
Blue(122)
LP
Black(119)
Black(118)
FP2
Yll
(117)Vio let(111)
Blue(110)
Yellow(109)
Green/Yellow(108)
Black/White
Yellow
1C
21
C2
43
24
32
1C
24
32
1C
24
32
Black(1 13)
Brown(106)
Blue240V
ack
and L2 on VS Drive
12
L1L2
Black(1 14)
Black(1 12)
Orange(105)
BLOWERCURRENT
TRANSDUCER(CT)
NOCOM
K6 RelayConnects to L2 and NO on AXB Board
L2
NOCOM
K6 RelayConnects to L2 and NO on AXB Board
L2
Figure 1:Optional Internal
Hot Water Generation Pump Wiring Schematic
DHW Pump
Blue(137)
Blue(138)
Cabinet HW Switch
3
21
PurpleDHW Pump
Blue(137)
Blue(138)
Cabinet HW Switch
3
21
Purple
NOCOM
K6 RelayConnects to L2 and NO on AXB Board
L2
Figure 1:Optional Internal
Hot Water Generation Pump Wiring Schematic
DHW Pump
Blue(137)
Blue(138)
Cabinet HW Switch
3
21
Purple
Communicating Thermostat Dual Fuel Wiring DiagramUsing Field Installed Relay
24 VDC
R f rom Foss il Fue l Furnac e
To Foss il Fuel Furnac e W input
EH1
C
ABCBoard
Note 12 : Fi eld inst al led SPST dual fuel rela y (R equi re d for dual fuel inst all ati on)
5 – Low voltage wiring CLASS 2 .
NotesNotes
3 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is required.
1 - Switch blue and red wires for 208V operation. 2 - The b lk/wh and gray/wh wires are removed when A ux Heat is installed
4 – Variable speed pump low voltage harness provided with V ariab le Speed Flow Center.
6 - Wires provided fo r Auxiliary Heat low voltage control. Wires are secured a t blower.7 – When Auxilia ry Heat is field installed the harness will t hen be connected to the auxiliary heat un it. The auxilia ry heat un it will then power the blower. Refer to EAS/EAM/EAL Auxiliary Heat kit insta llation inst ructions. 8 – Brown blower power wire rou ted through Current Transducer two times.9 – Fie ld Connected : Refer to Installa tion Manual and Auxilia ry Heat Instructions fo r Curren t Transducer installa tion.10 – Communication cab le routed through Ferrite Toro id four times.11 – Compressor power cable routed through Ferrite Toroid th ree times.12 - Fie ld installed SPST relay required for dual fuel installation.
Notes
3 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is required.
1 - Switch blue and red wires for 208V operation. 2 - The b lk/wh and gray/wh wires are removed when A ux Heat is installed
4 – Variable speed pump low voltage harness provided with V ariab le Speed Flow Center.
6 - Wires provided fo r Auxiliary Heat low voltage control. Wires are secured a t blower.7 – When Auxilia ry Heat is field installed the harness will t hen be connected to the auxiliary heat un it. The auxilia ry heat un it will then power the blower. Refer to EAS/EAM/EAL Auxiliary Heat kit insta llation inst ructions. 8 – Brown blower power wire rou ted through Current Transducer two times.9 – Fie ld Connected : Refer to Installa tion Manual and Auxilia ry Heat Instructions fo r Curren t Transducer installa tion.10 – Communication cab le routed through Ferrite Toro id four times.11 – Compressor power cable routed through Ferrite Toroid th ree times.12 - Fie ld installed SPST relay required for dual fuel installation.13 - Wiring harness supplied with va lve.
23
P9
54
1
L2 L1 L2 L1
Green
P112 3 4 51
VioletBlue
BrownOrange
HE1 TS1TS1HE1 TS1
HE3 TS3TS3HE3 TS3
HE2 TS2TS2HE2 TS2
HE4 TS4TS4HE4 TS4
Connects to variable speed ECM motor only
60 AMP BRK1
60 AMP BRK2
GGGG
K1
K2
K3
K4
NO
NO
NO
NO
EA Series PCB
P141 2 3C
G
G
G
G
K5
NO
K6
NO
K7
NO
K8
NO
Gray
Yellow
GrayYellow
Black
Pink
Black
Pink
Pink
Pink
Gray
Black
Yellow
Gray
Black
Yellow
41 2 3C P2
COMCOM
COM COM
COM COM
COMCOM
Aux heat staging
FB1
FB2
FB3
FB4
P3 on Aurora ABC Board
P3EH2C EH1 CCO P3EH2C EH1 CCO
Light emitting diode - Green
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField l ine voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal
Thermal Limit Switch
Field wire lug
GroundHE -
PB -
Heater element
Power block
Legend
N.O., N.C.
G
L1
Breaker
1 2 3PTS
Electric Heat RelayK*
Fused BackupFB
K*
Fused BackupFB
Light emitting diode - Green
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField l ine voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal
Thermal Limit Switch
Field wire lug
GroundHE -
PB -
Heater element
Power block
Legend
N.O., N.C.
G
L1
Breaker
1 2 3PTS
Electric Heat RelayK*
Fused BackupFB
2 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is requ ired.
1 - Use copper conductors.
3 – Jumpers wires are Factory Installed, and arerequired fo r auxiliary heat operation. 4 – Low voltage wiring CLASS 2 .
2 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is requ ired.
1 - Use copper conductors.
3 – Jumpers wires are Factory Installed, and arerequired fo r auxiliary heat operation. 4 – Low voltage wiring CLASS 2 .
NOTE 3
With optional EA Series 20kW Auxiliary Electric Heat Shown
23
P9
54
1
L2 L1 L2 L1
Green
P112 3 4 51
VioletBlue
BrownOrange
HE1 TS1
HE3 TS3
HE2 TS2
HE4 TS4
Connects to variable speed ECM motor only
60 AMP BRK1
60 AMP BRK2
GG
K1
K2
K3
K4
NO
NO
NO
NO
EA Series PCB
P141 2 3C
G
G
G
G
K5
NO
K6
NO
K7
NO
K8
NO
Gray
Yellow
GrayYellow
Black
Pink
Black
Pink
Pink
Pink
Gray
Black
Yellow
Gray
Black
Yellow
41 2 3C P2
COMCOM
COM COM
COM COM
COMCOM
Aux heat staging
FB1
FB2
FB3
FB4
P3 on Aurora ABC Board
P3EH2C EH1 CCO
Light emitting diode - Green
Polarized connector
Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField l ine voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal
Thermal Limit Switch
Field wire lug
GroundHE -
PB -
Heater element
Power block
Legend
N.O., N.C.
G
L1
Breaker
1 2 3PTS
Electric Heat RelayK*
Fused BackupFB
2 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is requ ired.
1 - Use copper conductors.
3 – Jumpers wires are Factory Installed, and arerequired fo r auxiliary heat operation. 4 – Low voltage wiring CLASS 2 .
NOTE 3
With optional EA Series 20kW Auxiliary Electric Heat Shown
P12
CFM
P13
P4
SW2
On
Future Use L Output Type
CC – Dual/SingleAcc – Dip 5Acc – Dip 4
RV – B/OFP2 – 15°F/30°FFP1 – 15°F/30°F
F1-3A
C
PWM
12345678
Off
Faul tLED1
R
StatusLED3
ConfigLED2
1 FP2 FP2 LPS LPSHPSHPS
F
R
C
CCGY1
YY
GGG
CFM
P13
P4
SW2
On
Future Use L Output Type
CC – Dual/SingleAcc – Dip 5Acc – Dip 4
RV – B/OFP2 – 15°F/30°FFP1 – 15°F/30°F
F1-3A
C
PWM
12345678
Off
Faul tLED1
R
StatusLED3
ConfigLED2
1 FP2 FP2 LPS LPSHPSHPS
F
R
C
CCGY1
Y
G
CFM
P13
P4
SW2
On
Future Use L Output Type
CC – Dual/SingleAcc – Dip 5Acc – Dip 4
RV – B/OFP2 – 15°F/30°FFP1 – 15°F/30°F
F1-3A
C
PWM
12345678
Off
Faul tLED1
R
StatusLED3
ConfigLED2
1 FP2 FP2 LPS LPSHPSHPS
F
R
C
CCGY1
Y
G
14 - On units with the NIDEC ECM motor the P13 harness connects to the jumper harness on the motor.
ce
)Bl
k(119)
2 ove
14
1 1
2 L
CCCC
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.:
Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 26 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Wiring Schematics cont.
Aurora UPC To ABC - P8
Yellow
Brown
Green
Blue
White
Black
Orange
Red
Devices Must Be Wired in Daisy Chain Configuration
GNDRNET+RNET-
+12V
GNDRNET+RNET-
+12V
GNDRNET+RNET-
+12V
ZS Sensor 1Addr: 0
1 2 3 4 5 6 7 8
ZS Sensor 2Addr: 1
ZS Sensor 3Addr: 2
BACnet or N2 Network
Connections
2W
4W
RNET LOCAL ACCESS
POWER
GND
24 VAC
FORM AT BATT
TEN’S
ONE’S
TXLED1
RXLED2
TXLED6
RXLED7
P OWERLED3
RUNLED4
ERRLED5
0
5
23
87
1
4
9
6
0
5
23
87
1
4
9
6
LON ADAPTER
PORT
NET+
NET-
COM
NET+
NET-
N/C
N/C
Signal
GNDRNET+RNET-+12V
GNDLN+LN-+12
/S
ON
12
34
56
78
Optional LON Add-On Module
A
N/C
N/C
Signal
Service
ECH
ELON
12
Net
LED1
LED2
LED3
LED4
Tx
Rx
LON OC
MAC Address Setting
Communication Options
NET
+
NET
-
CO
M
NET
+
NET
-
CO
M
12
1 2
LON Network Connections
Devices Must Be Wired in Daisy Chain
Configuration
Page 1
DIP Switch Value
1248
ON
1234
ZS Sensor Information
Each ZS sensor must have a unique address, but the addresses do not need to be sequential. Use the DIP switches on the back of the ZS sensor to set an address from 0 to 4. (0 is the factory default.) Each DIP switch has the value shown in the figure to the left. Turn on as many DIP switches as you need so that their total value equals the address.
Zone Sensors can be wired in daisy chain as show or in a star or hybrid configuration. Maximum of 5 sensors per UPC. Maximum allowable load 210mA. See the UPC install manual for possible sensor combinations.
LegendFactory Low Voltage WiringField Low Voltage Wiring
12345678 RJ45 Connector
Notes
NOTE 1
1. Use DIP Switches 5 – 8 to change communication protocol and DIP switches 1 – 2 to change BACnet baud rate
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 27 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
General Furnish and install WaterFurnace Water Source Heat
Pumps, as indicated on the plans. Equipment shall be
completely assembled, piped and internally wired.
Capacities and characteristics as listed in the schedule and
the specifications that follow. The reverse cycle heating/
cooling units shall be either suspended type with horizontal
air inlet and discharge or floor mounted type with
horizontal air inlet and vertical upflow, downflow, or rear
air discharge. Units shall be AHRI/ISO 13256-1 certified and
listed by a nationally recognized safety-testing laboratory
or agency, such as ETL Testing Laboratory. Each unit shall
be computer run-tested at the factory with conditioned
water and operation verified to catalog data. Each unit shall
be mounted on a pallet and shipped in a corrugated box
or stretch-wrapped. The units shall be designed to operate
with entering liquid temperature between 20°F and 120°F
[-6.7°C and 48.9°C].
Casing and Cabinet The cabinet shall be fabricated from heavy-gauge
galvanized steel and finished with corrosion-resistant
powder coating. This corrosion protection system shall
meet the stringent 1000 hour salt spray test per ASTM
B117. The interior shall be insulated with 1/2-inch thick,
multi-density, cleanable aluminum foil coated glass fiber
with edges sealed or tucked under flanges to prevent
the introduction of glass fibers into the discharge air.
Standard cabinet panel insulation must meet NFPA 90A
requirements, air erosion and mold growth limits of UL-
181, stringent fungal resistance test per ASTM-C1071 and
ASTM G21, and shall meet zero level bacteria growth per
ASTM G22. Unit insulation must meet these stringent
requirements or unit(s) will not be accepted.
One (horizontal) to two (vertical) blower and three
compressor compartment access panels shall be ‘lift-out’
removable with supply and return ductwork in place. The
front access panel shall be lift-out to provide easy access
to the electrical/compressor section. The control box
shall be hinged and removable to allow easy access to the
compressor. The internal component layout shall provide for
service access from the front side for restricted installations.
A duct collar shall be provided on the supply air opening.
Standard size 2 in. [5.1 cm] MERV 11 pleated filters shall
be provided with each unit. Vertical and horizontal units
shall have a return air filter rack/duct collar which is field
convertible from 2 in. [5.1 cm] to 1 in. [2.5 cm]. The upflow
vertical units shall have a removable insulated divider panel
between the air handling section and the compressor
section to minimize the transmission of compressor noise
and to permit operational service testing without air
bypass. Vertical units shall be supplied with left or right
horizontal air inlet and top, bottom, or rear vertical air
discharge. Horizontal units shall be supplied with left or
right air inlet and side or end air discharge.
The compressor shall be double isolation mounted using
selected durometer grommets to provide vibration free
compressor mounting.
The drain pan shall be of plastic construction to inhibit
corrosion and bacterial growth. Drain outlet shall be
located on pan as to allow complete and unobstructed
drainage of condensate. The unit as standard will be
supplied with solid-state electronic condensate overflow
protection. Mechanical float switches WILL NOT be
accepted. Vertical units shall be furnished with a PVC
slip condensate drain connection and an internal factory
installed condensate trap.
Refrigerant Circuit All units shall contain a sealed refrigerant circuit including
a hermetic motor-compressor, discharge line muffler,
bidirectional electronic expansion valve, finned tube air-
to-refrigerant heat exchanger, reversing valve, coaxial tube
water-to-refrigerant heat exchanger, optional hot water
generator coil, and service ports. Compressors shall be
high-efficiency variable speed scroll type designed for heat
pump duty and mounted on double vibration isolators.
Compressor motors shall be permanent magnet type. The
all-aluminum PinnaCoil shall be sized for low-face velocity
and constructed of aluminum fins bonded to aluminum
tubes in a staggered pattern not less than three rows
deep for enhanced performance. All models shall include
discharge mufflers to help quiet compressor discharge gas
pulsations.
Refrigerant to air heat exchangers shall utilize tube
construction rated to withstand 600 psig (4135 kPa)
refrigerant working pressure. Refrigerant to water heat
exchangers shall be of copper (cupronickel optional) inner
water tube and steel refrigerant outer tube design, rated to
withstand 600 psig (4135 kPa) working refrigerant pressure
and 450 psig (3101 kPa) working water pressure. An
electronic expansion valve shall provide proper superheat
over the entire liquid temperature range with minimal
“hunting.” The valve shall operate bidirectionally without
the use of check valves.
All units shall have the source coaxial tube refrigerant-to
water heat exchanger and the optional hot water generator
coil coated with ThermaShield insulation. Refrigerant
suction lines shall be insulated to prevent condensation at
low liquid temperatures.
Engineering Guide Specifi cations
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 28 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Blower Motor and Assembly The blower shall be a direct drive centrifugal type with a
dynamically balanced wheel. The housing and wheel shall
be designed for quiet low outlet velocity operation. The
blower housing shall be removable from the unit without
disconnecting the supply air ductwork for servicing of the
blower motor. The blower motor shall be a variable-speed
ECM type. The ECM blower motor shall be soft starting,
shall maintain constant cfm over its operating static range,
and shall provide 12 cfm settings. The blower motor shall
be isolated from the housing by rubber grommets. The
motor shall be permanently lubricated, have thermostatic
overload protection and be long-life ball bearing type.
ElectricalA control box shall be located within the unit compressor
compartment and shall contain a 75VA transformer, 24 Volt
activated, 2 pole compressor contactor, circuit breakers for
protecting loop pumps and compressor drive, removable
terminal block for thermostat wiring, variable speed
compressor drive and solid-state controller for complete
unit operation. Electromechanical operation WILL NOT
be accepted. Units shall be name-plated for use with time
delay fuses or HACR circuit breakers. Unit controls shall
be communicating type and provide heating or cooling
as required by the remote thermostat/sensor. An Aurora
Advanced VS Control, a microprocessor based controller,
interfaces with a digital communicating thermostat to monitor
and control unit operation shall be provided. The control shall
provide operational sequencing, blower speed control, blower
failure, high and low pressure switch monitoring, freeze
detection, hot water limit thermistor sensing, condensate
overflow sensing, auxiliary heat staging, lockout mode control,
hot water and loop pump control, LED status and fault
indicators, fault memory, field selectable options, compressor
envelope management, energy consumption measurement,
and accessory output. The fault signals shall be plain English
text and displayed on the thermostat.
The Aurora Advanced VS Control shall also feature an On
Peak input signal for utility controlled demand programs,
intelligent hot water generation with user adjustable
temperature limit, loop pump linking for multiple units
driving a common flow center and up to two optional home
automation inputs to drive dedicated alarms for sump pump,
security system, and smoke/CO2 or dirty air filter sensors.
As standard, the energy and refrigerant monitoring kits will
provide real time data including total power consumption,
refrigerant superheat and subcooling. Optional performance
monitoring kit to provide real time data including, entering
and leaving water temperature, flow rate and heat of
extraction/rejection capacity data. The capability for
communicating to advanced zoning packages with up to
six zones shall also be provided with complete fault and
information display on the zoning MasterStat.
A detachable terminal block with screw terminals will be provided for field control wiring. All units shall have knockouts for entrance of low and line voltage wiring. The blower motor and control box shall be harness plug wired for easy removal.
An optional Aurora Interface Diagnostic (AID) Tool shall communicate with the Aurora control allowing quick and easy access to setup, monitoring, and troubleshooting of any Aurora control. The device shall include the features of ECM airflow setup, VS pump and modulating water valve setup, fault description and history, manual operation capability, sensor readings, timings, and other diagnostic tools.
Option: An Aurora Unitary Protocol Converter (UPC) shall be included that communicates directly with the Aurora Heat Pump Control and allows access/control of a variety of internal Aurora heat pump operations such as sensors, relay operation, faults and other information. In turn, the UPC shall convert the internal Aurora Modbus protocol to BACnet MS/TP protocol for communication over a HAS system. Additional individual unit configuration items such as ECM fan speeds or freeze protection settings shall be directly available over the HAS without the need for access
to the actual heat pump.
Piping Supply and return water connections shall be 1 in. [25.4 mm]
FPT brass swivel fittings, which provide a union and eliminate
the need for pipe wrenches and sealants when making field
connections. The optional hot water generator shall have
sweat type connections. All source water piping shall be
insulated to prevent condensation at low liquid temperatures.
On the vertical units, the condensate connection shall be a
3/4 in. [19.1 mm] PVC socket with internally-trapped hose
that can be routed to front or side locations.
Hanger Kit(field-installed horizontal units only)
The hanger kit shall consist of galvanized steel brackets,
bolts, lock washers, and isolators and shall be designed to
fasten to the unit bottom panel for suspension from 3/8-
inch threaded rods. All unit size shall include six brackets
hanging brackets.
Options and Accessories Cupronickel Heat Exchanger
An optional cupronickel water-to-refrigerant heat
exchanger shall be provided.
Engineering Guide Specifi cations cont.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 29 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Hot Water Generator
An optional ThermaShield coated heat reclaiming hot water
generator coil of vented double-wall copper construction
suitable for potable water shall be provided. The coil and
hot water circulating pump shall be factory mounted inside
the unit with integral electronic high limit temperature
monitoring and external on/off switch. Hot water set point
is selectable through the AID Tool.
AlpinePure 411–Rack 4 in. Pleated Filter Accessory A 4 in. [102 mm] thick MERV 11 filter and filter rack shall be
provided in lieu of the standard filter and rack.
Thermostat (field-installed)
A communicating auto-changeover electronic digital
thermostat shall be provided. The thermostat shall offer
variable speed heating and cooling staging with precise
temperature control. An OFF-HEAT-AUTO-COOL-EMERG
system switch, OFF-AUTO-INTERMITTENT blower switch,
and indicating display shall be provided. The thermostat
shall display in °F or °C. The thermostat shall provide real
time energy consumption data of the unit.
Color Touchscreen Thermostat (field-installed)
A color touchscreen communicating auto-changeover
electronic digital thermostat shall be provided. The
thermostat shall offer variable speed heating and cooling
staging with precise temperature control. An OFF-
HEAT-AUTO-COOL-EMERG system switch, OFF-AUTO-
INTERMITTENT blower switch, and indicating display shall
be provided. The thermostat shall display in °F or °C. The
thermostat shall provide real time and historical energy
consumption data of the unit.
Electronic Air Cleaner (field-installed)
A 1 in. [25 mm] electronic air cleaner, cleanable 97%
efficiency at 0.3 microns and larger, shall be provided in
lieu of the standard throwaway filter. The initial pressure
drop across the filter shall not exceed 0.2 in. w.g. at 300
fpm force velocity.
Electrostatic Air Cleaner (field-installed) A 1 in. [25 mm] electrostatic air cleaner, cleanable 90%
efficiency, shall be provided in lieu of the standard
throwaway filter. The initial pressure drop across the filter
shall not exceed 0.15 in. w.g. at 300 fpm force velocity.
AlpinePure MERV 13 Filter (field-installed)
A 2 in. [50 mm] thick MERV 13 filter shall be provided in
lieu of the standard filter and fits the factory filter rack.
The filter maintains MERV 13 rating in full ASHRAE 52.2
independent testing as required for LEED® certification.
Helps fulfill a full credit under the LEED rating system.
AlpinePure Drain Pan Treatment (field-installed)
Provides dependable, sustained time-release protection
from slime build-up and foul smelling odors in the drain
pan. Also adds a light, pleasant scent to the air.
Earth Loop Flow Center (field-installed)
A self-contained module shall provide all liquid flow, fill
and connection requirements for ground source closed
loop systems up to 20 gpm. The pumps shall be wired to
a power block located in the nearest unit. The heat pump
units shall contain low voltage pump linking control so that
two units may share one flow center.
Auxiliary Heater (field-installed)
An electric resistance heater shall provide supplemental
and/or emergency heating capability. Vertical units shall
have the control panel and resistance heater coil assembly
mounted internally. For horizontal units, the control panel
shall be mounted internally while the resistance heater
coil assembly shall be mounted externally. A low voltage
plug shall be provided in each unit for quick auxiliary heat
connection. The heater shall operate in sequenced stages
as controlled by the unit’s microprocessor. The heater shall
feed line voltage power to the unit blower and transformer
to provide emergency heat capability in the event of an
open compressor circuit breaker.
Engineering Guide Specifi cations cont.
WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.: Engineer:
Project Name: Unit Tag:
SD2700ANA 02/21 30 Page _____ of _____
7 Series 700A113-5 Ton 60Hz
Pages: Description: Date: By:
Misc Updated with Aluminum Air Coils 04 Dec 2020 MA
16-19 Updated wiring schematics (UPMXL) 12 Sept 2019 MA
24,25 Updated Wiring Schematics, Engineering Specifications to include UPC option 21 Nov 2017 MA
All Misc. Updates 9 Dec 2016 MA
All Misc. Updates, Performance Data Update 12 Aug 2016 MA
All Electric heating updates, multiple areas effected 07 Jan 2015 MA
20 - 23 Updated Wiring Diagrams 31 May 2013 DS
27 Added Revision Guide 31 May 2013 DS
Revision Guide