700A11Geothermal Heat Pump

3-5 ton (variable speed)

Submittal Data

English Language/IP Units

SD2700ANA 02/21

Page 2: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.:

Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 2 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Model Nomenclature

N V V 036 C 1 0 1 C T L 0 J1 2 3 4-6 7 8 9 10 11 12 13 14 15

Model N – 7 Series Water-to-Air

Compressor Type V – Variable Speed

Cabinet Configuration V – Vertical H – Horizontal

Unit Capacity MBTU’s 036,048,060

Vintage C– 036-060

Voltage 1 – 208-230/60/1

Hot Water Options 0 – No Hot Water 1 – Hot Water Generation with Factory Installed Pump

Blower Motor Options 1 – Variable Speed ECM Blower 2 – High Static Variable Speed ECM (036 Only)

Air Coil Option N – All Aluminum PinnaCoil™

Controls Option J – Aurora Variable Speed Control K – Aurora VS Control w/ Performance Monitoring L – Aurora Variable Speed Control with UPC1 M – Aurora VS Control w/ Performance Monitoring and UPC1

Filter Options 0 – 2 inch MERV11 Filter 1 – AlpinePure 411 (Vertical Only)

Return Air Configuration L – Left R – Right

Discharge Configuration T – Top (Vertical) B – Bottom (Vertical) R – Rear (Vertical) S – Side (Horizontal) E – End (Horizontal)

Water Coax C – Copper N – CuproNickel

Rev.: 1/22/2021

Notes:1 UPC is not compatible with Symphony or IntelliZone2

N16

Page 3: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 3 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Energy Star Rating CriteriaIn order for water-source heat pumps to be Energy Star rated they must meet or exceed the minimum efficiency requirements listed below. Tier 3 represents the current minimum efficiency water source heat pumps must have in order to be Energy Start rated. Tier 3: 1/1/2012 – No Effective End Date Published

Water-to-Air EER COPGround Loop 17.1 3.6Ground Water 21.1 4.1

Water-to-WaterGround Loop 16.1 3.1Ground Water 20.1 3.5

Energy Star Compliance Table

ModelTier 3

Ground Water Ground Loop

036 Yes Yes

048 Yes Yes

060 Yes Yes

6/1/12

Variable Speed ECM MotorAHRI/ASHRAE/ISO 13256-1English (IP) Units

ModelCapacity

Modulation

Flow Rate Clg/Htg

Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump

Cooling EWT 86°F

Heating EWT 68°F

Cooling EWT 59°F

Heating EWT 50°F

Cooling Full Load 77°F Part Load 68°F

Heating Full Load 32°F Part Load 41°F

cfm Capacity

Btuh EER

Btuh/W Capacity

Btuh COP

Capacity Btuh

EER Btuh/W

Capacity Btuh

COP Capacity

Btuh EER

Btuh/W Capacity

Btuh COP

036Full

1300/1500 32,300 17.7 51,000 5.3 38,000 31.2 41,700 4.5 35,800 21.6 32,900 3.5

Part 11,000 21.1 17,000 7.6 12,500 50.0 14,000 5.9 13,400 39.0 12,000 5.1

048Full

1500/1800 40,700 16.9 67,000 4.9 49,000 30.0 55,200 4.0 45,000 20.0 43,500 3.4

Part 16,000 24.0 24,000 7.8 19,000 56.0 19,000 6.0 18,000 43.5 16,300 5.1

060Full

1800/2200 50,000 15.9 79,000 4.9 60,000 27.1 66,000 4.3 56,000 19.1 51,700 3.4

Part 20,100 22.3 29,100 7.6 22,500 55.0 23,000 5.8 22,800 40.0 20,000 5.1

Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature 1/15/21

Heating capacities based upon 68°F DB, 59°F WB entering air temperature

All ratings based upon 208V operation

AHRI/ISO 13256-1 Performance Ratings

Page 4: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 4 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Top Air Discharge

Vertical Top Flow Model

Overall Cabinet Water ConnectionsElectrical

ConnectionsDischarge Connection

duct flange installed (±0.10 in)

Return Connectionusing std deluxe filter rack

(±0.10 in)

AWidth

BDepth

CHeight

DLoop

In

ELoop Out

FHWG

In

GHWG Out

HCond- ensate

Loop Water FPT

HWG Sweat (I.D.)

I 1/2 in. cond

J 1/2 in. cond

K 3/4 in. cond L M

NSupply Width

OSupply Depth

P QR

Return Depth

SReturn Height

TLow

VoltageExt

PumpPower Supply

036in. 25.6 31.6 54.4 2.3 7.3 15.9 18.9 10.6 1 in.

Swivel1/2 in. Female

14.3 9.8 12.3 6.9 1.1 18.0 18.0 3.8 1.7 28.1 30.0 1.7

cm. 65.0 80.3 138.2 5.8 18.5 40.4 48.0 26.9 36.3 24.9 31.2 17.5 2.8 45.7 45.7 9.7 4.3 71.4 76.2 4.3

048in. 25.6 31.6 54.4 2.3 7.3 15.9 18.9 10.6 1 in.

Swivel1/2 in. Female

14.3 9.8 12.3 6.9 1.1 18.0 18.0 3.8 1.7 28.1 30.0 1.7

cm. 65.0 80.3 138.2 5.8 18.5 40.4 48.0 26.9 36.3 24.9 31.2 17.5 2.8 45.7 45.7 9.7 4.3 71.4 76.2 4.3

060in. 25.6 31.6 58.4 2.3 7.3 15.9 18.9 10.6 1 in.

Swivel1/2 in. Female

14.3 9.8 12.3 6.9 1.1 18.0 18.0 3.8 1.7 28.1 34.0 1.7

cm. 65.0 80.3 148.3 5.8 18.5 40.4 48.0 26.9 36.3 24.9 31.2 17.5 2.8 45.7 45.7 9.7 4.3 71.4 86.4 4.3

Condensate is 3/4 in. PVC female glue socket and is switchable from side to frontUnit shipped with deluxe 2 in. (field adjustable to 1 in.) duct collar/filter rack extending from unit 3.25 in. and is suitable for duct connection.Discharge flange is field installed and extends 1 in. [25.4mm] from cabinetDecorative molding and/or water connections extend 1.2 in. [30.5mm] beyond front of cabinet.Louvered vents in the compressor section right side access panel extend 1/2 in. [12.7 mm] from side of cabinet. Allow 6" clearance for venting.

6/29/12

LEFT RETURN RIGHT RETURN

FRONT

TOP TOP

A D E H FI K J G

1.9in[4.8cm]

1.9in[4.8cm]

M

R

Q

N

OL

RN

O

L

P Q

RIGHT SIDEB

C

B

LEFT SIDE

S

T

S

T

C

Vertical Dimensional Data

Page 5: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 5 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Bottom Air Discharge

Bottomflow Models

Overall Cabinet

Water Connections Electrical KnockoutsDischarge Connection

duct flange installed (±0.10 in)

Return Connectionusing std deluxe filter rack

(±0.10 in)1 2 3 4 5Loop Water FPT

HWG Sweat (I.D.)

I1/2 in. cond

J1/2 in. cond

K3/4 in. cond

AWidth

BDepth

CHeight

DIn

EOut

FHWG

In

GHWG Out

HCond-ensate

Low Voltage

Ext Pump

Power Supply

L MN

Supply Width

OSupply Depth

P QR

Return Depth

SReturn Height

T

036-060

in. 25.5 31.5 62.5 43.4 48.4 57.0 60.0 3.1 1 in. Swivel

1/2 in. Female

51.1 55.6 53.6 9.1 4.8 13.4 13.6 1.7 1.8 28.1 34.0 5.6

cm. 64.8 80.0 158.8 110.2 122.9 144.8 152.4 7.9 129.8 141.2 136.1 23.1 12.2 34.0 34.5 4.3 4.6 71.4 86.4 14.2

Condensate is 3/4 in. PVC female glue socket and is switchable from side to frontUnit shipped with deluxe 2 in. (field adjustable to 1 in.) duct collar/filter rack extending from unit 3.25 in. and is suitable for duct connection.Water connections extend 1.2 in. [30.5mm] beyond front of cabinet.Louvered vents in the compressor section right side access panel extend 1/2 in. [12.7 mm] from side of cabinet. Allow 6" clearance for venting.

4/30/12

LEFT SIDE RIGHT SIDE

B

C

S

T T

B

C

S

LEFT RETURN RIGHT RETURN

R Q

LN

O

P

A

FRONT

D

E

FG

H

JKI

1.90(4.7 cm)

1.70(4.3 cm)

1

2

3

4

5

RIGHT BOTTOM DISCHARGE FLOOR FOOT PRINT

R

O

N

L

M

LEFT BOTTOM DISCHARGE FLOOR FOOT PRINT

Q

Vertical Dimensional Data cont.

Page 6: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 6 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Rear Air Discharge

Verti-cal Rear

Discharge Model

Overall Cabinet Water ConnectionsElectrical

ConnectionsDischarge Connection

duct flange installed (±0.10 in)

Return Connectionusing std deluxe filter rack

(±0.10 in)

AWidth

BDepth

CHeight

DLoop

In

ELoop Out

FHWG

In

GHWG Out

HCond- ensate

Loop Water FPT

HWG Sweat (I.D.)

I1/2 in. cond

J1/2 in. cond

K 3/4 in. cond

LSupply Width

MSupply Depth

N O P QR

Return Depth

SReturn Height

TLow

VoltageExt

PumpPower Supply

036in. 25.6 31.6 54.4 2.3 7.3 15.9 18.9 10.6 1 in.

Swivel1/2 in. Female

14.3 9.8 12.3 13.3 13.6 39.4 9.1 8.1 1.7 28.1 30.0 1.7

cm. 65.0 80.3 138.2 5.8 18.5 40.4 48.0 26.9 36.3 24.9 31.2 33.8 34.5 100.1 23.1 20.6 4.3 71.4 76.2 4.3

048in. 25.6 31.6 54.4 2.3 7.3 15.9 18.9 10.6 1 in.

Swivel1/2 in. Female

14.3 9.8 12.3 13.3 13.6 39.4 9.1 8.1 1.7 28.1 30.0 1.7

cm. 65.0 80.3 138.2 5.8 18.5 40.4 48.0 26.9 36.3 24.9 31.2 33.8 34.5 100.1 23.1 20.6 4.3 71.4 76.2 4.3

060in. 25.6 31.6 58.4 2.3 7.3 15.9 18.9 10.6 1 in.

Swivel1/2 in. Female

14.3 9.8 12.3 13.3 13.6 43.4 9.1 8.1 1.7 28.1 34.0 1.7

cm. 65.0 80.3 148.3 5.8 18.5 40.4 48.0 26.9 36.3 24.9 31.2 33.8 34.5 110.2 23.1 20.6 4.3 71.4 86.4 4.3

Condensate is 3/4 in. PVC female glue socket and is switchable from side to frontUnit shipped with deluxe 2 in. (field adjustable to 1 in.) duct collar/filter rack extending from unit 3.25 in. and is suitable for duct connection.Discharge flange is field installed and extends 1 in. [25.4mm] from cabinetDecorative molding and/or water connections extend 1.2 in. [30.5mm] beyond front of cabinet.Louvered vents in the compressor section right side access panel extend 1/2 in. [12.7 mm] from side of cabinet. Allow 6" clearance for venting.

6/29/12

REAR VIEWLEFT RETURN

SIDE VIEWRIGHT RETURN

SIDE VIEWLEFT RETURN

REAR VIEWRIGHT RETURN

FRONT

C C C C

A A

A

B B

D

EH

F G

JKI

L

M

N

M

N

PO QQ R R

S S

T T

1.90 in. [4.8 cm]1.90 in.

[4.8 cm]

2 ft [61 cm]Primary Service Access

Vertical Dimensional Data cont.

Page 7: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 7 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Units Not Shown Above L O

Right Return End Dischargein 2.8 4.6

cm 7.1 11.8

Right Return Side Dischargein 4.9 6.9

cm 12.4 17.5

Left Return End Dischargein 4.9 7.6

cm 12.4 19.4

Left Return Side Dischargein 2.8 6.9

cm 7.1 17.5

Horizontal Models

Overall Cabinet Water Connections

Electrical ConnectionsDischarge Connection

duct flange installed (±0.10 in)

Return Connectionusing std deluxe filter rack

(±0.10 in)

I 1/2 in. cond

J 1/2 in. cond

K 3/4 in. cond

AWidth

BDepth

CHeight

DIn

EOut

FHWG

In

GHWG Out

HCond- ensate

Loop Water FPT

HWG Sweat (I.D.)

Low Voltage

Ext Pump

Power Supply

LM

Supply Height

NSupply Depth

O PQ

Return Depth

RReturn Height

S

036in. 25.6 77.0 21.3 2.3 7.3 15.9 18.9 0.8 1 in.

Swivel1/2 in.

Female

14.3 9.8 12.3 SEE CHART

13.6 13.2 SEE CHART

2.8 40.4 18.9 1.3

cm. 65.0 195.6 54.1 5.8 18.5 40.4 48.0 2.0 36.3 24.9 31.2 34.5 33.5 7.1 102.6 48.0 3.3

048in. 25.6 77.0 21.3 2.3 7.3 15.9 18.9 0.8 1 in.

Swivel1/2 in.

Female

14.3 9.8 12.3 SEE CHART

13.6 13.2 SEE CHART

2.8 40.4 18.9 1.3

cm. 65.0 195.6 54.1 5.8 18.5 40.4 48.0 2.0 36.3 24.9 31.2 34.5 33.5 7.1 102.6 48.0 3.3

060in. 25.6 82.0 21.3 2.3 7.3 15.9 18.9 0.8 1 in.

Swivel1/2 in.

Female

14.3 9.8 12.3 SEE CHART

13.6 13.2 SEE CHART

2.8 45.4 18.9 1.3

cm. 65.0 208.3 54.1 5.8 18.5 40.4 48.0 2.0 36.3 24.9 31.2 34.5 33.5 7.1 115.3 48.0 3.3

Condensate is 3/4 in. PVC female glue socket and is switchable from side to frontUnit shipped with deluxe 2 in. (field adjustable to 1 in.) duct collar/filter rack extending from unit 3.25 in. and is suitable for duct connection.Discharge flange is field installed and extends 1 in. [25.4mm] from cabinetDecorative molding and/or water connections extend 1.2 in. [30.5mm] beyond front of cabinet.Louvered vents in the compressor section right side access panel extend 1/2 in. [12.7 mm] from side of cabinet. Allow 6" clearance for venting.

6/29/12

2 ft [61 cm]Primary Service Access

B

C

2.1in[5.4cm]

H

LON

M

S

R

QP

MOUNT (2) HANGER BRACKETSAS SHOWN TO ALLOW ACCESSTO FILTER

AS SHOWN LR UNIT (RR UNIT ON OPPOSITE SIDE—SAME DIMENSIONS)

SIDE DISHCARGE VIEW END VIEW

TOP VIEW

A

S

FRONT VIEW

D E F GI K J

1.9in[4.8cm]

OL

Horizontal Dimensional Data

Page 8: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 8 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Model036 048 060

Compressor (1 each) Variable Speed Scroll

Factory Charge R410a, oz [kg] Vertical (Aluminum tube and fin air coil)

90 [2.55] 120 [3.40] 140 [3.96]

Factory Charge R410a, oz [kg] Horizontal (Aluminum tube and fin air coil)

86 [2.44] 108 [3.06] 148 [4.19]

ECM Blower Motor & Blower

Blower Motor Type/Speeds ECM Variable Speed

Blower Motor- hp [W] ECM 1/2 [373] 1 [746] 1 [746]

High Static Blower Motor - hp [W] ECM 1 [746] n/a n/a

Blower Wheel Size (Dia x W), in. [mm] ECM11 x 10

[279 x 254] 11 x 10

[279 x 254] 11 x 10

[279 x 254]

High Static Blower Wheel Size - [Dia. x W], in. [mm] ECM11 x 10

[279 x 254] n/a n/a

Coax and Water Piping

Water Connections Size - Swivel - in [mm] 1” [25.4] 1” [25.4] 1” [25.4]

HWG Connection Size - Female Sweat I.D. - in [mm] 1/2” [12.7] 1/2” [12.7] 1/2” [12.7]

Coax & Piping Water Volume - gal [l] 1.3 [4.9] 2.3 [8.7] 2.3 [8.7]

Vertical

Air Coil Dimensions (H x W), in. [mm]32 x 25

[813 x 635]32 x 25

[813 x 635]36 x 25

[914 x 635] Air Coil Total Face Area, ft2 [m2] 5.6 [0.570] 5.6 [0.570] 6.3 [0.641]

Air Coil Tube Size, in [mm] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5]

Air Coil Number of rows 3 3 4

Filter Standard - 2” [51mm] Pleated MERV11 Throwaway, in [mm] 32 x 30 [813 x 762] 32 x 30 [813 x 762] 36 x 30 [914 x 762]

Weight - Operating, lb [kg] 331 [150] 354 [161] 372 [169]

Weight - Packaged, lb [kg] 351 [159] 374 [170] 392 [178]

Horizontal

Air Coil Dimensions (H x W), in. [mm] 20 x 40 [508 x 1016] 20 x 40 [508 x 1016] 20 x 4 [508 x 1143]

Air Coil Total Face Area, ft2 [m2] 5.6 [0.570] 5.6 [0.570] 6.3 [0.641]

Air Coil Tube Size, in [mm] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5]

Air Coil Number of rows 3 3 4

Filter Standard - 2” [51mm] Pleated MERV11 Throwaway, in [mm]1 - 20 x 20 [508 x 508] 1 - 20 x 22 [508 x 559]

1 - 20 x 20 [508 x 508] 1 - 20 x 22 [508 x 559]

1 - 20 x 25 [508 x 635] 1 - 20 x 22 [508 x 559]

Weight - Operating, lb [kg] 365 [166] 388 [176] 402 [182]

Weight - Packaged, lb [kg] 395 [179] 418 [190] 432 [196]

*Bottom fl ow 036-060 models use the 2in. [51mm] MERV 11throwaway in. [mm] 36 x 30 [914 x 762] fi lter.

12/3/2020

Physical Data

Page 9: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

Auxiliary Heat Ratings

Auxiliary Heat Electrical Data

Electrical Data

SD2700ANA 02/21 9 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

ModelkW

StagesBtu/h

Min CFMModel Compatibility

208V 230V 208V 230V 036 048 060

EAL(H)10* 7.2 9.6 2 24,600 32,700 1100 • • •

EAL(H)15* 10.8 14.4 3 36,900 49,100 1250 • • •

EAL(H)20* 14.4 19.2 4 49,200 65,500 1500 • •

Air flow level for auxiliary heat (Aux) must be above the minimum cfm in this tableOrder the “H” part number when installed on horizontal and vertical rear discharge units

11/30/17

ModelSupply Circuit

Heater Amps Min Circuit Amp Max Fuse (USA) Max Fuse (CAN) Max CKT BRK

208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V

EAL(H)10* Single 34.7 40 53.3 60 60 60 60 60 60 60

EAL(H)15*

Single 52.0 60 75 85 80 90 80 90 70 100

L1/L2 34.7 40 53.3 60 60 60 60 60 60 60

L3/L4 17.3 20 21.7 25 25 25 25 25 20 30

EAL(H)20*

Single 69.3 80 96.7 110 100 110 100 110 100 100

L1/L2 34.7 40 53.3 60 60 60 60 60 60 60

L3/L4 34.7 40 43.3 50 45 50 45 50 40 50

All heaters rated single phase 60 cycle and include unit fan loadAll fuses type “D” time delay (or HACR circuit breaker in USA)

11/30/17

ModelRated

VoltageVoltageMin/Max

Compressor Drive HWG Pump FLA

Ext Loop FLA

Blower Motor FLA

Total Unit FLA

Minimum Circuit Amp

Max Fuse HACR

Breaker LRA CMCC RLAInternal Breaker

036 208-230/60/1 187/253 10.2 18.0 22.0 30.0 0.4 5.4 4.0 31.8 37.3 40

*036 208-230/60/1 187/253 10.2 18.0 22.0 30.0 0.4 5.4 7.0 34.8 40.3 45

048 208-230/60/1 187/253 12.0 23.5 28.0 35.0 0.4 5.4 7.0 40.8 47.8 50

060 208-230/60/1 187/253 12.0 30.0 33.0 40.0 0.4 5.4 7.0 45.8 54.1 60

*With optional 1 hp Variable Speed ECM MotorRated Voltage of 208/230/60/1HACR circuit breaker in USA onlyAll fuses Class RK-5

3/26/12

Page 10: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 10 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Blower Performance Data

ECM Speed Info

1▶ 2 ◀ G 3 4 5 6 7 8 9 10 11 12

Option ◀▶ Enter ◙

ECM Speed Info

1 2 G▶ 3 ◀ Lo 4 5 6 7 8 9 10 11 12

Option ◀▶ Enter ◙

ECM Speed Info

1 2 G 3 Lo 4 5▶ 6 ◀ Hi 7 8 9 10 11 12

Option ◀▶ Enter ◙

ECM Speed Info

1 2 G 3 Lo 4 5 6 Hi 7 8 9▶10 ◀ Aux 11 12

Option ◀▶ Enter ◙

ECM Speed Info

Blower Only Speed 3Lo Compressor 6Hi Compressor 9Aux Heat 10

Want To Change?

YesOption ◀▶

NoEnter ◙

Cooling Airflow Setup

--- ECM Only ---The airflow will be

adjusted by the chosenamount in cooling mode.

Adjustment:-15%

Want To Change?

YesOption ◀▶

NoEnter ◙

Cooling Airflow Setup

--- ECM Only ---The airflow will be

adjusted by the chosenamount in cooling mode.

Adjustment:-15%

Change ▼▲ Enter ◙

Setting Blower Speed - Variable Speed ECM The ABC board’s Yellow Config LED will flash the current ECM blower speed selections for G, low, and high continuously with a short pause in between. The speeds can also be confirmed with the AID Tool under the Setup/ECM Setup screen. The Aux will not be flashed but can be viewed in the AID Tool. The ECM blower motor speeds can be field adjusted with or without using an AID Tool.

Variable speed ECM Setup without an AID ToolThe blower speeds for G only, Low (Y1), and High (Y2/Aux) can be adjusted directly at the Aurora ABC board which utilizes the push button (SW1) on the ABC board. This procedure is outlined in the ECM Configuration Mode portion of the Aurora ‘Base’ Control System section. The Aux cannot be set manually without an AID Tool.

Variable speed ECM Setup with an AID ToolA much easier method utilizes the AID Tool to change the airflow using the procedure below. First navigate to the Setup screen and then select ECM Setup. This screen displays the current ECM settings. It allows the technician to enter the setup screens to change the ECM settings. Change

the highlighted item using the ◄ and ► buttons and then press the ◙ button to select the item.

Selecting YES will enter ECM speed setup, while selecting NO will return to the previous screen.

ECM Speed Setup - These screens allow the technician to select the G, low, high, and auxiliary heat blower speed for the ECM blower motor. Change the highlighted item using the ▲ and ▼ buttons. Press the ◙ button to select the speed.

After the auxiliary heat speed setting is selected the AID Tool will automatically transfer back to the ECM Setup screen.

Cooling Airflow Setup - These screens allow the technician to select -15%, -10%, -5%, None or +5% change from the heating airflow. Change the adjustment percentage using the ▲ and ▼ buttons. Press the ◙ button to save the change.

Variable Speed ECM Blower Motor

ModelAir Flow

Max ESP

Speed 1

Speed 2

Speed 3

Speed 4

Speed 5

Speed 6

Speed 7

Speed 8

Speed 9

Speed 10

Speed 11

Speed 12

036 0.50285 380

G525

L675 815 980 1100 1220 1330 1440

H1540 Aux

1575

036 w/1hp* 0.75480 565

G665

L 761 870 1000 1100 1200 1300 1410

H1520 Aux

1630

048 0.75475 620

G730

L850 1020 1140 1270 1400 1520 1650

H1790 Aux

1925

060 0.75400 600

G830

L1050 1230 1400 1560 1700 1870 2010

H2140 Aux

2265

**VS Compressor Speed 1-2 3-4 5-6 7-8 9-10 11-12

** VS Compressor speed is given for the factory default cfm settings. When the cfm default settings are changed it will change the relationship to the compressor speed that is shown in the table. In cooling mode compressor speeds 10-12 are only available when SuperBoost mode is selected at the thermostat.* Optional 1 hp Variable Speed ECMFactory settings are at recommended L , H and Aux positions“G” may be located anywhere within the airflow table“L” setting should be located within the boldface cfm range“H” setting MUST be located within the shaded cfm range“Aux” setting MUST be equal to or greater than “H” setting“Aux” setting MUST be equal to or greater than the minimum allowable cfm for the auxiliary heater kit (see auxiliary heat ratings table)Cfm is controlled within 5% up to the maximum ESPMax ESP includes allowance for wet coil and standard filter

6/7/12

Page 11: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 11 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Model GPMPressure Drop (psi)

30°F 50°F 70°F 90°F 110°F

36

11.5 3.60 3.30 3.10 2.90 2.709.0 2.30 2.10 2.00 1.90 1.707.0 1.50 1.40 1.30 1.20 1.106.0 1.20 1.15 1.10 1.05 1.004.5 0.70 0.66 0.64 0.60 0.55

48

13.5 4.60 4.40 4.10 3.80 3.5010.5 2.90 2.70 2.50 2.30 2.207.5 1.70 1.60 1.50 1.40 1.306.0 1.20 1.10 1.00 0.96 0.914.0 0.62 0.61 0.60 0.58 0.56

60

17.0 6.40 6.00 5.60 5.20 4.8013.5 4.60 4.40 4.10 3.80 3.509.5 2.20 2.10 2.00 1.80 1.707.5 1.70 1.60 1.50 1.40 1.305.0 0.68 0.62 0.58 0.55 0.53

12/02/20

Operating Limits

Defi nitions

Abbreviations and Definitionscfm = airflow, cubic feet/minuteEWT = entering water temperature, Fahrenheitgpm = water flow in gallons/minuteWPD = water pressure drop, psi and feet of waterEAT = entering air temperature, Fahrenheit (dry bulb/wet bulb)HC = air heating capacity, MBtu/hTC = total cooling capacity, MBtu/hSC = sensible cooling capacity, MBtu/hkW = total power unit input, kilowattsHR = total heat of rejection, MBtu/hHE = total heat of extraction, MBtu/h

HWC = hot water generator capacity, MBtu/hEER = Energy Efficient Ratio = Btu output/Watt inputCOP = Coefficient of Performance = Btu output/Btu inputLWT = leaving water temperature, °FLAT = leaving air temperature, °FTH = total heating capacity, MBtu/hLC = latent cooling capacity, MBtu/hS/T = sensible to total cooling ratio

Operating LimitsCooling Heating

(°F) (°C) (°F) (°C)

Air Limits

Min. Ambient Air 45 7.2 45 7.2

Rated Ambient Air 80 26.7 70 21.1

Max. Ambient Air 100 37.8 85 29.4

Min. Entering Air 50 10.0 40 4.4

Rated Entering Air db/wb 80.6/66.2 27/19 68 20.0

Max. Entering Air db/wb 110/83 43/28.3 80 26.7

Water Limits

Min. Entering Water 30 -1.1 20 -6.7

Normal Entering Water 50-110 10-43.3 30-70 -1.1

Max. Entering Water 120 48.9 90 32.2

NOTE: Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependent upon three primary factors: 1) water temperature, 2) return air temperature, and 3) ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation.

Pressure Drop

Notes to Performance Data TablesThe following notes apply to all performance data tables:• Performance ratings are based on 80°F DB/67°F WB EAT

for cooling and 70°F DB EAT for heating.• Three flow rates are shown for each unit. The lowest

flow rate shown is used for geothermal open loop/well water systems with a minimum of 50°F EWT. The middle flow rate shown is the minimum geothermal closed loop flow rate. The highest flow rate shown is optimum for geothermal closed loop systems and the suggested flow rate for boiler/tower applications.

• The hot water generator numbers are based on a flow rate of 0.4 gpm/ton of rated capacity with an EWT of 90°F.

• Entering water temperatures below 40°F assumes 15% antifreeze solution.

• For non-standard EAT conditions, apply the appropriate Correction Factor tables.

• Interpolation between EWT, gpm, and cfm data is

permissible, extrapolation is not.

Page 12: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 12 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Correction Factor Tables

Heating Capacity Corrections

Ent Air DB °FHeating Corrections

Htg Cap Power Heat of Ext

45 1.062 0.739 1.158

50 1.050 0.790 1.130

55 1.037 0.842 1.096

60 1.025 0.893 1.064

65 1.012 0.945 1.030

68 1.005 0.976 1.012

70 1.000 1.000 1.000

75 0.987 1.048 0.970

80 0.975 1.099 0.930

11/10/09

Air Flow Corrections (Compressor Speeds 1-3)Airflow Cooling Heating

CFM Per Ton of Clg

% of Nominal Total Cap Sens Cap Power Heat of Rej Htg Cap Power Heat of Ext

240 60 0.940 0.740 0.967 0.951 0.943 1.106 0.902

275 69 0.950 0.783 0.973 0.959 0.953 1.088 0.918

300 75 0.960 0.827 0.978 0.967 0.962 1.070 0.935

325 81 0.970 0.870 0.984 0.975 0.972 1.053 0.951

350 88 0.980 0.913 0.989 0.984 0.981 1.035 0.967

375 94 0.990 0.957 0.995 0.992 0.991 1.018 0.984

400 100 1.000 1.000 1.000 1.000 1.000 1.000 1.000

425 106 1.030 1.022 1.024 1.026 1.009 0.982 1.016

450 113 1.060 1.045 1.048 1.051 1.019 0.965 1.033

475 119 1.091 1.067 1.071 1.077 1.028 0.947 1.049

500 125 1.121 1.089 1.095 1.103 1.038 0.930 1.065

520 130 1.151 1.111 1.110 1.129 1.047 0.912 1.082

6/29/12

Air Flow Corrections (Compressor Speeds 4-12)Airflow Cooling Heating

CFM Per Ton of Clg

% of Nominal Total Cap Sens Cap Power Heat of Rej Htg Cap Power Heat of Ext

240 60 0.928 0.747 0.936 0.929 0.961 1.097 0.938

275 69 0.940 0.789 0.946 0.941 0.967 1.081 0.948

300 75 0.952 0.831 0.957 0.953 0.974 1.064 0.959

325 81 0.964 0.873 0.968 0.965 0.980 1.048 0.969

350 88 0.976 0.916 0.979 0.976 0.987 1.032 0.979

375 94 0.988 0.958 0.989 0.988 0.993 1.016 0.990

400 100 1.000 1.000 1.000 1.000 1.000 1.000 1.000

425 106 1.020 1.023 1.004 1.018 1.010 0.966 1.018

450 113 1.056 1.042 1.008 1.035 1.020 0.932 1.036

475 119 1.072 1.079 1.011 1.053 1.029 0.898 1.054

500 125 1.087 1.095 1.015 1.070 1.039 0.865 1.071

520 130 1.099 1.113 1.019 1.088 1.049 0.831 1.089

6/14/12

Cooling Capacity Corrections Entering Air WB

°F

Total Clg Cap

Sensible Cooling Capacity Multipliers - Entering DB °FPower Input

Heat of Rejection60 65 70 75 80 80.6 85 90 95 100

55 0.898 0.723 0.866 1.048 1.185 * * * * * * 0.985 0.913

60 0.912 0.632 0.880 1.078 1.244 1.260 * * * * 0.994 0.927

63 0.945 0.768 0.960 1.150 1.175 * * * * 0.996 0.954

65 0.976 0.694 0.881 1.079 1.085 1.270 * * * 0.997 0.972

66.2 0.983 0.655 0.842 1.040 1.060 1.232 * * * 0.999 0.986

67 1.000 0.616 0.806 1.000 1.023 1.193 1.330 1.480 * 1.000 1.000

70 1.053 0.693 0.879 0.900 1.075 1.205 1.404 * 1.003 1.044

75 1.168 0.687 0.715 0.875 1.040 1.261 1.476 1.007 1.141

NOTE: *Sensible capacity equals total capacity at conditions shown. 4/22/12

Page 13: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 13 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Catalog performance can be corrected for antifreeze use. Please use the following table and note the example given.

Antifreeze Type Antifreeze % by wt Heating Cooling Pressure Drop

EWT - °F [°C] 30 [-1.1] 90 [32.2] 30 [-1.1]

Water 0 1.000 1.000 1.000

Ethylene Glycol

10 0.973 0.991 1.075

20 0.943 0.979 1.163

30 0.917 0.965 1.225

40 0.890 0.955 1.324

50 0.865 0.943 1.419

Propylene Glycol

10 0.958 0.981 1.130

20 0.913 0.969 1.270

30 0.854 0.950 1.433

40 0.813 0.937 1.614

50 0.770 0.922 1.816

Ethanol

10 0.927 0.991 1.242

20 0.887 0.972 1.343

30 0.856 0.947 1.383

40 0.815 0.930 1.523

50 0.779 0.911 1.639

Methanol

10 0.957 0.986 1.127

20 0.924 0.970 1.197

30 0.895 0.951 1.235

40 0.863 0.936 1.323

50 0.833 0.920 1.399

WARNING: Gray area represents antifreeze concentrations greater than 35% by weight and should be avoided due to the extreme performance penalty they represent.

Antifreeze Correction ExampleAntifreeze solution is Propylene Glycol 20% by weight. Determine the corrected heating and cooling performance at 30°F

and 90°F respectively as well as pressure drop at 30°F for a 036 operating at 100% capacity.

The corrected cooling capacity at 90°F would be: 35,200 Btu/h x 0.969 = 34,109 Btu/h

The corrected heating capacity at 30°F would be: 37,400 Btu/h x 0.913 = 34,146 Btu/h

The corrected pressure drop at 30°F and 11.5 gpm would be: 7.9 feet of head x 1.270 = 10.03 feet of head

Antifreeze Corrections

Page 14: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 14 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

036 - 50% Part Load

EWT

°F

Flow

gpm

WPD HEATING - EAT 70°FEWT

°F

Flow

gpm

WPD COOLING - EAT 80/67 °F

PSI FTAirflow

cfm

HC

MBtuh

Power

kW

HE

MBtuh

LAT

°FCOP

HWC

MBtuhPSI FT

Airflow

cfm

TC

MBtuh

SC

MBtuh

S/T

Ratio

Power

kW

HR

MBtuhEER

HWC

MBtuh

20

3.0 0.30 0.7Operation not recommended

20

2.5 0.15 0.4

Operation not recommended4.5 0.70 1.6 3.5 0.46 1.1

5.5 1.09 2.5550 12.7 1.43 7.8 91.4 2.61 2.2

5.0 0.77 1.8750 12.8 1.26 8.5 85.8 2.98 1.8

30

3.0 0.30 0.7550 13.3 1.19 9.2 92.3 3.26 2.3

30

2.5 0.15 0.3500 18.3 12.5 0.68 0.57 20.2 32.2 -

750 13.8 1.22 9.7 87.1 3.31 2.0 650 18.6 13.7 0.74 0.59 20.7 31.5 -

4.5 0.68 1.6550 13.6 1.20 9.5 92.9 3.33 2.6

3.5 0.45 1.0500 18.5 12.6 0.68 0.54 20.4 34.3 -

750 14.2 1.23 10.0 87.5 3.38 2.2 650 18.8 13.8 0.73 0.57 20.8 33.1 -

5.5 1.06 2.4550 15.0 1.43 10.1 95.3 3.07 2.7

5.0 0.75 1.7500 18.6 12.6 0.68 0.52 20.4 35.6 -

750 15.1 1.26 10.8 88.6 3.51 2.2 650 19.1 13.8 0.72 0.55 21.0 34.7 -

40

3.0 0.29 0.7550 15.6 1.21 11.4 96.2 3.77 2.5

40

2.5 0.14 0.3500 20.4 13.3 0.65 0.51 22.1 39.7 -

750 16.1 1.23 11.9 89.9 3.83 2.2 650 20.8 14.5 0.70 0.53 22.6 38.9 -

4.5 0.66 1.5550 16.1 1.21 11.9 97.0 3.88 2.8

3.5 0.44 1.0500 20.6 13.4 0.65 0.49 22.3 42.3 -

750 16.6 1.24 12.4 90.5 3.94 2.3 650 21.0 14.7 0.70 0.51 22.8 41.1 -

5.5 1.02 2.4550 16.9 1.24 12.7 98.5 3.99 2.8

5.0 0.73 1.7500 20.8 13.4 0.65 0.47 22.4 43.9 -

750 17.5 1.27 13.2 91.6 4.05 2.4 650 21.3 14.7 0.69 0.50 22.9 42.9 -

50

3.0 0.28 0.6550 17.8 1.23 13.7 100.0 4.27 2.8

50

2.5 0.14 0.3500 22.2 13.6 0.61 0.45 23.7 49.7 -

750 18.4 1.24 14.2 92.7 4.34 2.3 650 22.8 15.0 0.66 0.46 24.4 50.1 -

4.5 0.64 1.5550 18.5 1.23 14.3 101.1 4.41 3.0

3.5 0.42 1.0500 22.4 13.7 0.61 0.44 23.9 51.4 -

750 19.0 1.24 14.8 93.5 4.49 2.5 650 23.0 15.1 0.66 0.44 24.5 51.9 -

5.5 0.99 2.3550 19.3 1.26 15.0 102.5 4.51 3.1

5.0 0.70 1.6500 22.8 14.0 0.62 0.43 24.2 52.7 -

750 19.9 1.27 15.6 94.6 4.59 2.8 650 23.4 15.5 0.66 0.44 24.9 53.2 -

60

3.0 0.27 0.6550 20.2 1.24 16.0 104.0 4.77 3.0

60

2.5 0.13 0.3500 20.0 13.4 0.67 0.59 22.0 34.0 1.0

750 20.7 1.25 16.4 95.6 4.85 2.5 650 20.6 14.8 0.72 0.60 22.6 34.3 1.0

4.5 0.62 1.4550 21.0 1.24 16.8 105.4 4.97 3.2

3.5 0.41 0.9500 20.2 13.5 0.67 0.57 22.2 35.2 1.1

750 21.5 1.25 17.3 96.6 5.05 2.7 650 20.8 14.9 0.72 0.59 22.8 35.5 1.1

5.5 0.96 2.2550 21.8 1.27 17.4 106.6 5.03 3.3

5.0 0.68 1.6500 20.5 13.8 0.67 0.57 22.5 36.1 1.2

750 22.3 1.28 17.9 97.5 5.11 2.8 650 21.1 15.3 0.73 0.58 23.1 36.4 1.2

70

3.0 0.26 0.6550 22.6 1.26 18.3 108.0 5.25 3.2

70

2.5 0.13 0.3500 17.8 13.2 0.74 0.73 20.3 24.4 1.3

750 22.9 1.27 18.6 98.3 5.28 2.6 650 18.6 14.9 0.80 0.86 21.5 21.6 1.3

4.5 0.60 1.4550 23.6 1.26 19.3 109.7 5.50 3.4

3.5 0.40 0.9500 18.0 13.3 0.74 0.71 20.4 25.3 1.4

750 24.0 1.25 19.7 99.6 5.61 2.9 650 18.5 14.7 0.80 0.73 21.0 25.5 1.4

5.5 0.93 2.1550 24.2 1.28 19.8 110.7 5.53 3.5

5.0 0.66 1.5500 18.3 13.6 0.75 0.71 20.7 25.9 1.5

750 24.6 1.28 20.2 100.4 5.63 2.9 650 18.8 15.1 0.80 0.72 21.3 26.1 1.5

80

3.0 0.25 0.6550 24.8 1.28 20.4 111.8 5.67 3.4

80

2.5 0.13 0.3500 16.7 12.3 0.73 0.90 19.8 18.6 1.9

750 25.2 1.28 20.8 101.1 5.78 2.8 650 17.2 13.6 0.79 0.92 20.3 18.7 2.0

4.5 0.57 1.3550 26.0 1.28 21.7 113.8 5.98 3.6

3.5 0.38 0.9500 16.8 12.3 0.73 0.88 19.8 19.2 2.1

750 26.3 1.27 22.0 102.5 6.09 3.0 650 17.3 13.7 0.79 0.89 20.4 19.4 2.1

5.5 0.90 2.1550 26.4 1.30 21.9 114.4 5.94 3.8

5.0 0.64 1.5500 17.1 12.6 0.74 0.87 20.1 19.7 2.2

750 26.7 1.29 22.2 102.9 6.05 3.2 650 17.6 14.0 0.80 0.89 20.6 19.9 2.5

90

3.0 0.24 0.6550 27.1 1.31 22.6 115.5 6.07 3.6

90

2.5 0.12 0.3500 15.6 11.3 0.73 1.07 19.2 14.6 2.6

750 27.3 1.29 22.9 103.7 6.19 2.9 650 16.0 12.5 0.78 1.09 19.7 14.7 2.6

4.5 0.55 1.3550 28.4 1.30 24.0 117.9 6.44 3.8

3.5 0.37 0.9500 15.7 11.4 0.72 1.04 19.2 15.1 2.7

750 28.6 1.28 24.3 105.3 6.57 3.2 650 16.1 12.6 0.78 1.06 19.7 15.2 2.7

5.5 0.87 2.0550 28.6 1.32 24.1 118.1 6.34 4.1

5.0 0.61 1.4500 16.7 12.0 0.72 1.06 20.3 15.8 2.8

750 28.7 1.30 24.3 105.4 6.47 3.4 650 16.4 12.9 0.79 1.05 20.0 15.6 2.8

100

3.0 0.23 0.5

Operation not recommended

100

2.5 0.12 0.3500 14.5 10.9 0.75 1.29 18.9 11.2 3.1650 14.9 12.0 0.81 1.32 19.4 11.3 3.1

4.5 0.53 1.2 3.5 0.35 0.8500 14.6 10.9 0.75 1.26 18.9 11.7 3.2650 15.1 12.1 0.80 1.28 19.4 11.7 3.2

5.5 0.84 1.9 5.0 0.59 1.4500 14.9 11.2 0.75 1.25 19.1 11.9 3.3650 15.3 12.4 0.81 1.27 19.6 12.0 3.3

110

3.0 0.22 0.5

110

2.5 0.11 0.3500 13.5 10.4 0.77 1.51 18.6 8.9 3.0650 13.8 11.5 0.83 1.54 19.1 9.0 3.0

4.5 0.51 1.2 3.5 0.34 0.8500 13.6 10.5 0.77 1.47 18.6 9.2 3.3650 14.0 11.6 0.83 1.50 19.1 9.3 3.2

5.5 0.80 1.9 5.0 0.57 1.3500 13.8 10.8 0.78 1.46 18.8 9.5 3.4650 14.2 11.9 0.84 1.49 19.3 9.5 3.4

120

3.0 0.22 0.5

120

2.5 0.11 0.2500 12.6 10.6 0.84 1.93 19.1 6.5 4.3650 12.8 11.6 0.90 1.97 19.6 6.5 4.4

4.5 0.49 1.1 3.5 0.33 0.8500 12.7 10.7 0.84 1.82 18.9 7.0 4.4650 12.9 11.6 0.90 1.87 19.3 6.9 4.4

5.5 0.77 1.8 5.0 0.55 1.3500 12.8 10.7 0.83 1.76 18.8 7.3 4.6650 13.1 11.6 0.89 1.82 19.3 7.2 4.6

Performance capacities shown in thousands of Btuh. 11/2/20

Performance Data

Page 15: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 15 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

036 - 100% Full Load

EWT

°F

Flow

gpm

WPD HEATING - EAT 70°FEWT

°F

Flow

gpm

WPD COOLING - EAT 80/67 °F

PSI FTAirflow

cfm

HC

MBtuh

Power

kW

HE

MBtuh

LAT

°FCOP

HWC

MBtuhPSI FT

Airflow

cfm

TC

MBtuh

SC

MBtuh

S/T

Ratio

Power

kW

HR

MBtuhEER

HWC

MBtuh

20

5.5 1.09 2.5Operation not recommended

20

4.5 0.70 1.6

Operation not recommended8.0 2.69 6.2 7.0 1.70 3.9

11.5 3.51 8.11150 28.0 3.01 17.8 92.6 2.73 4.7

9.0 2.81 6.51500 28.9 2.91 19.0 87.8 2.91 4.3

30

5.5 1.06 2.51150 31.4 2.77 21.9 95.3 3.32 5.2

30

4.5 0.68 1.61000 35.0 23.9 0.68 0.96 38.2 36.4 -

1500 32.3 2.87 22.5 90.0 3.30 4.8 1300 35.6 26.2 0.73 1.00 39.0 35.6 -

8.0 2.61 6.01150 32.2 2.81 22.6 95.9 3.35 5.3

7.0 1.65 3.81000 35.4 24.1 0.68 0.91 38.6 38.8 -

1500 33.1 2.90 23.2 90.5 3.35 4.8 1300 36.0 26.3 0.73 0.96 39.3 37.4 -

11.5 3.41 7.91150 32.8 3.03 22.5 96.4 3.17 5.4

9.0 2.73 6.31000 35.6 24.1 0.68 0.89 38.7 40.2 -

1500 33.8 2.93 23.8 90.9 3.38 5.0 1300 36.5 26.3 0.72 0.93 39.7 39.2 -

40

5.5 1.02 2.41150 36.3 2.82 26.7 99.2 3.77 5.6

40

4.5 0.66 1.51000 37.0 25.7 0.70 1.15 40.9 32.1 -

1500 37.4 2.89 27.5 93.1 3.79 5.0 1300 37.7 28.1 0.75 1.20 41.8 31.4 -

8.0 2.53 5.91150 37.4 2.88 27.6 100.1 3.82 5.8

7.0 1.60 3.71000 37.4 26.0 0.69 1.09 41.1 34.2 -

1500 38.6 2.94 28.6 93.8 3.85 5.1 1300 38.1 28.4 0.74 1.15 42.0 33.2 -

11.5 3.31 7.61150 38.2 2.90 28.3 100.7 3.85 5.9

9.0 2.65 6.11000 37.7 26.0 0.69 1.06 41.3 35.5 -

1500 39.4 2.97 29.3 94.3 3.89 5.2 1300 38.6 28.4 0.74 1.11 42.3 34.7 -

50

5.5 0.99 2.31150 41.2 2.87 31.4 103.1 4.21 6.0

50

4.5 0.64 1.51000 37.4 25.3 0.68 1.34 41.9 28.0 -

1500 42.4 2.91 32.5 96.2 4.27 5.6 1300 39.4 28.2 0.72 1.41 44.1 28.0 -

8.0 2.46 5.71150 42.7 2.93 32.7 104.4 4.26 6.5

7.0 1.55 3.61000 38.2 25.6 0.67 1.26 42.5 30.3 -

1500 44.0 2.97 33.9 97.2 4.34 5.7 1300 40.2 28.5 0.71 1.32 44.7 30.4 -

11.5 3.20 7.41150 43.6 2.96 33.5 105.1 4.32 6.6

9.0 2.56 5.91000 38.5 27.4 0.71 1.23 42.7 31.4 -

1500 45.0 3.00 34.8 97.8 4.40 6.8 1300 40.6 30.4 0.75 1.29 45.0 31.5 -

60

5.5 0.93 2.21150 45.2 2.89 35.4 106.4 4.59 6.1

60

4.5 0.62 1.41000 35.9 25.4 0.71 1.53 41.1 23.4 1.9

1500 46.7 2.91 36.8 98.8 4.70 5.7 1300 37.7 28.3 0.75 1.60 43.1 23.5 2.0

8.0 2.38 5.51150 47.3 2.97 37.1 108.0 4.66 6.7

7.0 1.50 3.51000 36.8 25.7 0.70 1.46 41.7 25.2 2.1

1500 48.8 2.99 38.6 100.1 4.78 5.8 1300 38.5 28.6 0.74 1.52 43.7 25.4 2.1

11.5 3.10 7.21150 48.4 3.00 38.2 109.0 4.73 6.9

9.0 2.48 5.71000 37.1 27.1 0.73 1.42 42.0 26.1 2.0

1500 50.0 3.02 39.7 100.9 4.86 6.0 1300 39.0 30.1 0.77 1.49 44.0 26.2 2.2

70

5.5 0.90 2.11150 49.3 2.91 39.4 109.7 4.97 6.6

70

4.5 0.60 1.41000 34.4 25.6 0.74 1.92 41.0 17.9 2.7

1500 51.0 3.02 40.7 101.5 4.95 6.2 1300 36.5 29.5 0.81 1.91 43.0 19.1 2.9

8.0 2.30 5.31150 51.9 3.01 41.6 111.8 5.06 6.9

7.0 1.45 3.41000 35.3 25.9 0.73 1.66 41.0 21.3 3.1

1500 53.5 3.01 43.3 103.1 5.22 6.4 1300 36.9 28.7 0.78 1.71 42.7 21.5 3.1

11.5 3.00 6.91150 53.2 3.04 42.8 112.8 5.12 7.6

9.0 2.40 5.51000 35.7 26.9 0.75 1.61 41.2 22.1 3.2

1500 55.0 3.03 44.7 104.0 5.32 6.6 1300 37.3 29.8 0.80 1.68 43.0 22.2 3.3

80

5.5 0.87 0.11150 52.7 2.96 42.6 112.5 5.21 7.2

80

4.5 0.57 1.31000 32.9 25.3 0.77 2.00 39.7 16.5 4.0

1500 54.6 2.94 44.5 103.7 5.44 6.1 1300 34.2 28.2 0.82 2.06 41.2 16.6 4.0

8.0 2.22 5.11150 55.8 3.08 45.3 114.9 5.31 7.5

7.0 1.40 3.21000 33.8 25.6 0.76 1.93 40.4 17.5 4.2

1500 57.7 3.05 47.3 105.6 5.54 6.3 1300 35.1 28.4 0.81 1.98 41.9 17.7 4.2

11.5 2.90 6.71150 57.4 3.12 46.7 116.2 5.39 7.7

9.0 2.32 5.41000 34.1 26.3 0.77 1.89 40.6 18.1 4.4

1500 59.4 3.08 48.9 106.6 5.66 7.2 1300 35.6 29.1 0.82 1.95 42.2 18.3 4.4

90

5.5 0.84 1.91150 56.2 3.02 45.9 115.2 5.45 7.4

90

4.5 0.55 1.31000 31.3 25.1 0.80 2.27 39.0 13.8 5.3

1500 58.2 2.97 48.0 105.9 5.74 6.7 1300 32.4 27.9 0.86 2.32 40.3 14.0 5.3

8.0 2.14 5.01150 59.7 3.15 48.9 118.1 5.55 7.8

7.0 1.35 3.11000 32.2 25.4 0.79 2.20 39.7 14.6 5.6

1500 61.8 3.10 51.2 108.2 5.85 7.2 1300 33.4 28.2 0.84 2.26 41.1 14.8 5.6

11.5 2.79 6.51150 61.6 3.20 50.7 119.6 5.64 8.6

9.0 2.24 5.21000 32.8 24.9 0.76 2.17 40.2 15.1 5.9

1500 63.7 3.12 53.1 109.3 5.98 7.9 1300 33.8 28.4 0.84 2.21 41.3 15.3 5.6

100

5.5 0.80 1.8

Operation not recommended

100

4.5 0.53 1.21000 29.1 24.2 0.83 2.62 38.1 11.1 6.81300 30.0 26.8 0.89 2.67 39.1 11.3 6.7

8.0 2.07 4.8 7.0 1.30 3.01000 30.1 24.5 0.81 2.57 38.9 11.7 7.11300 31.1 27.2 0.87 2.61 40.0 11.9 7.0

11.5 2.69 6.2 9.0 2.16 5.01000 30.4 24.4 0.80 2.53 39.0 12.0 7.51300 31.4 27.0 0.86 2.57 40.2 12.2 6.2

110

5.5 0.77 1.8

110

4.5 0.51 1.21000 26.9 23.3 0.87 2.98 37.1 9.0 8.11300 27.7 25.8 0.93 3.01 37.9 9.2 8.0

8.0 1.99 4.6 7.0 1.25 2.91000 27.9 23.5 0.84 2.95 38.0 9.5 8.51300 28.7 26.1 0.91 2.97 38.9 9.7 8.5

11.5 2.59 6.0 9.0 2.07 4.81000 28.2 23.2 0.82 2.90 38.1 9.7 8.91300 29.0 25.6 0.88 2.93 39.0 9.9 8.1

120

5.5 0.73 1.7

120

4.5 0.49 0.81000 23.9 22.7 0.95 3.54 36.0 6.7 9.91300 24.4 24.8 1.02 3.62 36.7 6.7 10.2

8.0 1.91 4.4 7.0 1.20 2.81000 24.2 22.9 0.95 3.35 35.6 7.2 10.31300 24.6 24.9 1.01 3.43 36.3 7.2 10.5

11.5 2.49 5.8 9.0 1.99 4.61000 24.4 22.9 0.94 3.24 35.4 7.5 10.71300 24.9 24.9 1.00 3.34 36.3 7.5 10.7

Performance capacities shown in thousands of Btuh. 11/2/20

Performance Data cont.

Page 16: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 16 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

048 - 50% Part Load

EWT

°F

Flow

gpm

WPD HEATING - EAT 70°FEWT

°F

Flow

gpm

WPD COOLING - EAT 80/67 °F

PSI FTAirflow

cfm

HC

mBtuh

Power

kW

HE

MBtuh

LAT

°FCOP

HWC

MBtuhPSI FT

Airflow

cfm

TC

MBtuh

SC

MBtuh

S/T

Ratio

Power

kW

HR

MBtuhEER

HWC

MBtuh

20

3.5 0.56 1.3Operation not recommended

20

3.0 0.47 1.1

Operation not recommended5.0 0.97 2.2 4.5 0.81 1.9

6.5 1.37 3.2650 16.5 1.83 10.3 93.6 2.65 2.4

6.0 1.16 2.7900 16.9 1.65 11.3 87.4 3.00 3.1

30

3.5 0.55 1.3650 16.7 1.57 11.4 93.9 3.12 2.7

30

3.0 0.45 1.1500 23.9 14.1 0.59 0.57 25.8 42.0 -

900 17.3 1.60 11.9 87.8 3.17 2.4 750 24.3 15.5 0.64 0.59 26.3 41.1 -

5.0 0.94 2.2650 18.1 1.64 12.5 95.8 3.22 3.0

4.5 0.79 1.8500 24.2 14.3 0.59 0.54 26.0 44.8 -

900 18.6 1.66 13.0 89.2 3.30 2.6 750 24.6 15.6 0.63 0.57 26.5 43.2 -

6.5 1.33 3.1650 18.8 1.86 12.5 96.8 2.96 3.1

6.0 1.12 2.6500 24.3 14.3 0.59 0.52 26.1 46.4 -

900 19.2 1.68 13.5 89.8 3.35 2.6 750 24.9 15.6 0.63 0.55 26.8 45.3 -

40

3.5 0.53 1.2650 19.8 1.61 14.3 98.3 3.61 3.0

40

3.0 0.44 1.0500 27.0 18.1 0.67 0.49 28.6 55.3 -

900 20.5 1.62 14.9 91.1 3.70 2.6 750 27.5 19.7 0.72 0.51 29.2 54.1 -

5.0 0.91 2.1650 21.4 1.67 15.7 100.5 3.75 3.3

4.5 0.77 1.8500 27.3 18.2 0.67 0.46 28.9 58.9 -

900 22.1 1.67 16.4 92.8 3.88 2.8 750 27.8 19.9 0.72 0.49 29.4 57.2 -

6.5 1.29 3.0650 22.1 1.68 16.4 101.5 3.85 3.4

6.0 1.09 2.5500 27.5 18.2 0.66 0.45 29.0 61.2 -

900 22.9 1.70 17.1 93.5 3.95 2.8 750 28.1 19.9 0.71 0.47 29.7 59.8 -

50

3.5 0.51 1.2650 22.9 1.65 17.3 102.7 4.08 3.3

50

3.0 0.43 1.0500 25.8 16.3 0.63 0.68 28.1 38.1 -

900 23.7 1.65 18.0 94.3 4.21 2.8 750 26.6 19.2 0.72 0.71 29.0 37.7 -

5.0 0.88 2.0650 24.7 1.70 18.9 105.2 4.26 3.6

4.5 0.74 1.7500 26.3 16.4 0.62 0.59 28.3 45.0 -

900 25.7 1.69 19.9 96.4 4.45 3.0 750 27.1 19.3 0.71 0.61 29.2 44.2 -

6.5 1.25 2.9650 25.7 1.71 19.8 106.6 4.40 3.8

6.0 1.06 2.4500 26.5 16.4 0.62 0.55 28.4 48.0 -

900 26.5 1.71 20.7 97.3 4.54 3.3 750 27.3 19.3 0.71 0.58 29.3 47.1 -

60

3.5 0.50 1.1650 25.7 1.71 19.9 106.6 4.41 3.7

60

3.0 0.41 1.0500 24.7 15.9 0.64 0.83 27.6 29.8 1.2

900 26.7 1.70 20.9 97.4 4.60 3.0 750 25.5 18.7 0.73 0.87 28.5 29.5 1.2

5.0 0.85 2.0650 27.8 1.75 21.9 109.7 4.66 3.9

4.5 0.72 1.7500 25.1 16.0 0.64 0.74 27.7 34.2 1.3

900 28.9 1.73 23.0 99.8 4.90 3.3 750 25.9 18.9 0.73 0.77 28.5 33.6 1.3

6.5 1.21 2.8650 29.0 1.77 23.0 111.3 4.82 4.1

6.0 1.02 2.4500 25.4 16.1 0.63 0.70 27.8 36.4 1.4

900 30.1 1.75 24.1 100.9 5.05 3.5 750 26.2 18.9 0.72 0.73 28.7 35.9 1.4

70

3.5 0.48 1.1650 28.5 1.77 22.5 110.7 4.73 4.0

70

3.0 0.40 0.9500 23.7 15.5 0.65 0.98 27.0 24.2 1.7

900 31.1 1.77 25.1 102.0 5.15 3.3 750 24.6 18.3 0.74 1.03 28.1 23.9 1.8

5.0 0.83 1.9650 31.0 1.80 24.8 114.1 5.04 4.3

4.5 0.70 1.6500 23.9 15.7 0.65 0.89 27.0 27.0 1.9

900 32.2 1.77 26.1 103.1 5.33 3.6 750 24.7 18.4 0.75 0.93 27.8 26.7 1.9

6.5 1.17 2.7650 32.4 1.82 26.2 116.1 5.21 4.5

6.0 0.99 2.3500 24.4 15.8 0.65 0.85 27.2 28.7 1.9

900 33.6 1.78 27.5 104.6 5.53 3.7 750 25.1 18.5 0.74 0.88 28.1 28.5 2.0

80

3.5 0.46 1.1650 30.5 1.87 24.1 113.4 4.78 4.2

80

3.0 0.39 0.9500 22.6 15.0 0.66 1.16 26.5 19.5 2.5

900 31.6 1.83 25.4 102.6 5.06 3.5 750 23.3 17.6 0.76 1.21 27.4 19.3 2.5

5.0 0.80 1.8650 33.1 1.89 26.6 117.1 5.14 4.5

4.5 0.67 1.6500 22.7 15.2 0.67 1.07 26.3 21.1 2.6

900 34.4 1.84 28.1 105.4 5.48 3.8 750 23.4 17.8 0.76 1.12 27.2 20.9 2.7

6.5 1.13 2.6650 34.8 1.91 28.3 119.5 5.34 4.8

6.0 0.96 2.2500 23.2 15.3 0.66 1.03 26.7 22.6 2.8

900 36.2 1.86 29.8 107.2 5.71 4.0 750 23.9 18.0 0.75 1.07 27.6 22.3 3.2

90

3.5 0.45 1.0650 32.4 1.96 25.7 116.1 4.84 4.5

90

3.0 0.37 0.9500 21.4 14.5 0.68 1.33 26.0 16.1 3.4

900 33.6 1.92 27.1 104.6 5.14 3.7 750 22.1 17.0 0.77 1.38 26.8 16.0 3.4

5.0 0.77 1.8650 35.2 1.97 28.5 120.1 5.23 4.8

4.5 0.65 1.5500 21.4 14.6 0.68 1.26 25.7 17.0 3.5

900 36.7 1.91 30.1 107.7 5.63 4.0 750 22.0 17.2 0.78 1.31 26.5 16.9 3.6

6.5 1.09 2.5650 37.1 1.99 30.3 122.9 5.46 5.2

6.0 0.92 2.1500 20.5 13.8 0.67 1.27 24.8 16.1 3.7

900 38.7 1.93 32.1 109.8 5.88 4.3 750 22.7 17.4 0.77 1.26 27.0 18.0 3.7

100

3.5 0.43 1.0

Operation not recommended

100

3.0 0.36 0.8500 19.3 13.3 0.69 1.56 24.6 12.4 4.3750 19.9 15.6 0.78 1.62 25.5 12.3 4.3

5.0 0.74 1.7 4.5 0.62 1.4500 19.2 13.4 0.70 1.52 24.4 12.7 4.4750 19.8 15.8 0.80 1.58 25.2 12.6 4.4

6.5 1.05 2.4 6.0 0.89 2.1500 19.9 13.6 0.68 1.46 24.9 13.6 4.6750 20.5 16.0 0.78 1.53 25.7 13.4 4.6

110

3.5 0.41 1.0

110

3.0 0.35 0.8500 17.2 12.1 0.70 1.78 23.3 9.7 5.0750 17.7 14.2 0.80 1.85 24.1 9.6 5.0

5.0 0.71 1.6 4.5 0.60 1.4500 17.0 12.2 0.72 1.77 23.0 9.6 5.4750 17.6 14.4 0.82 1.85 23.9 9.5 5.4

6.5 1.01 2.3 6.0 0.86 2.0500 17.8 12.4 0.70 1.72 23.7 10.4 5.8750 18.3 14.6 0.80 1.79 24.4 10.2 5.8

120

3.5 0.40 0.9

120

3.0 0.33 0.8500 16.0 12.8 0.80 2.22 23.6 7.2 6.4750 16.4 13.9 0.85 2.27 24.1 7.2 6.5

5.0 0.68 1.6 4.5 0.58 1.3500 16.2 12.9 0.80 2.09 23.4 7.7 6.6750 16.5 14.0 0.85 2.15 23.8 7.7 6.6

6.5 0.97 2.2 6.0 0.82 1.9500 16.4 12.9 0.79 2.03 23.3 8.1 6.8750 16.7 14.0 0.84 2.09 23.8 8.0 6.8

Performance capacities shown in thousands of Btuh. 11/2/20

Performance Data cont.

Page 17: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 17 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

048 - 100% Full Load

EWT

°F

Flow

gpm

WPD HEATING - EAT 70°FEWT

°F

Flow

gpm

WPD COOLING - EAT 80/67 °F

PSI FTAirflow

cfm

HC

mBtuh

Power

kW

HE

MBtuh

LAT

°FCOP

HWC

MBtuhPSI FT

Airflow

cfm

TC

MBtuh

SC

MBtuh

S/T

Ratio

Power

kW

HR

MB-

tuh

EERHWC

MBtuh

20

6.5 1.40 3.2Operation not recommended

20

5.5 1.05 2.4

Operation not recommended10.0 2.85 6.6 8.0 2.00 4.6

13.5 4.79 11.11500 39.4 4.05 25.6 94.3 2.86 6.05

10.5 2.94 6.81800 39.7 3.97 26.2 90.4 2.93 5.6

30

6.5 1.36 3.21500 39.9 3.84 26.7 94.6 3.04 6.6

30

5.5 1.02 2.41000 42.8 28.0 0.65 1.20 46.9 35.7 -

1800 41.2 3.90 27.9 91.2 3.10 6.1 1400 43.6 30.8 0.70 1.25 47.9 35.0 -

10.0 2.77 6.41500 43.0 4.01 29.3 96.6 3.14 6.8

8.0 1.94 4.51000 43.4 28.3 0.65 1.14 47.3 38.1 -

1800 44.4 4.04 30.6 92.8 3.22 6.1 1400 44.1 30.9 0.70 1.20 48.2 36.8 -

13.5 4.65 10.71500 45.4 4.18 31.1 98.0 3.18 6.9

10.5 2.85 6.61000 43.6 28.3 0.65 1.10 47.4 39.5 -

1800 45.7 4.10 31.7 93.5 3.27 6.3 1400 44.7 30.9 0.69 1.16 48.7 38.5 -

40

6.5 1.32 3.11500 45.4 4.00 31.8 98.0 3.33 7.0

40

5.5 0.99 2.31000 44.7 29.0 0.65 1.42 49.5 31.4 -

1800 46.9 4.02 33.2 94.1 3.42 6.2 1400 45.5 31.7 0.70 1.48 50.6 30.8 -

10.0 2.69 6.21500 49.0 4.15 34.9 100.3 3.46 7.3

8.0 1.88 4.31000 45.2 29.2 0.65 1.35 49.8 33.5 -

1800 50.7 4.15 36.6 96.1 3.58 6.4 1400 46.0 31.9 0.69 1.42 50.9 32.5 -

13.5 4.51 10.41500 50.6 4.18 36.4 101.2 3.55 7.5

10.5 2.77 6.41000 45.5 29.2 0.64 1.31 50.0 34.8 -

1800 52.4 4.21 38.0 96.9 3.65 6.5 1400 46.6 31.9 0.69 1.37 51.2 34.0 -

50

6.5 1.28 3.01500 51.0 4.15 36.9 101.5 3.61 7.5

50

5.5 0.96 2.21000 45.7 27.8 0.61 1.84 52.0 24.8 -

1800 52.7 4.15 38.5 97.1 3.72 7.0 1400 47.1 32.8 0.70 1.92 53.7 24.5 -

10.0 2.60 6.01500 55.0 4.28 40.4 104.0 3.77 8.2

8.0 1.82 4.21000 46.7 27.9 0.60 1.60 52.1 29.3 -

1800 57.1 4.26 42.6 99.4 3.93 7.2 1400 48.1 32.9 0.68 1.67 53.8 28.8 -

13.5 4.37 10.11500 57.1 4.31 42.4 105.3 3.88 8.4

10.5 2.68 6.21000 47.0 27.9 0.59 1.50 52.1 31.3 -

1800 59.0 4.31 44.3 100.3 4.01 8.6 1400 48.4 32.9 0.68 1.58 53.8 30.6 -

60

6.5 1.24 2.91500 57.1 4.32 42.3 105.2 3.87 7.6

60

5.5 0.93 2.21000 43.9 27.2 0.62 2.06 50.9 21.3 2.6

1800 59.1 4.29 44.5 100.4 4.04 7.1 1400 45.2 32.1 0.71 2.15 52.6 21.1 2.8

10.0 2.52 5.81500 61.7 4.42 46.7 108.1 4.09 8.4

8.0 1.76 4.11000 44.6 27.4 0.62 1.83 50.8 24.4 2.9

1800 64.1 4.37 49.2 103.0 4.30 7.2 1400 45.9 32.3 0.70 1.91 52.5 24.1 2.9

13.5 4.23 9.81500 64.4 4.46 49.1 109.7 4.23 8.6

10.5 2.60 6.01000 45.1 27.5 0.61 1.73 51.0 26.0 2.8

1800 66.7 4.41 51.6 104.3 4.43 7.4 1400 46.5 32.4 0.70 1.81 52.6 25.7 3.0

70

6.5 1.20 2.81500 63.1 4.48 47.8 109.0 4.13 8.1

70

5.5 0.90 2.11000 42.0 26.7 0.63 2.27 49.7 18.5 3.4

1800 67.8 4.49 52.5 104.9 4.43 7.5 1400 43.7 31.7 0.73 2.27 51.4 19.3 3.7

10.0 2.44 5.61500 68.5 4.56 52.9 112.3 4.40 8.6

8.0 1.71 3.91000 42.4 26.9 0.63 2.06 49.5 20.7 3.9

1800 71.2 4.48 55.9 106.6 4.65 7.9 1400 43.8 31.7 0.72 2.15 51.1 20.4 3.9

13.5 4.09 9.51500 63.7 4.28 49.1 109.3 4.36 9.4

10.5 2.51 5.81000 43.2 27.1 0.63 1.96 49.9 22.0 3.9

1800 74.3 4.51 58.9 108.2 4.83 8.2 1400 44.5 31.8 0.71 2.04 51.5 21.8 4.1

80

6.5 1.16 2.71500 68.3 4.71 52.3 112.2 4.25 9.0

80

5.5 0.87 2.01000 39.8 25.7 0.65 2.54 48.5 15.6 5.4

1800 71.0 4.63 55.2 106.5 4.50 7.7 1400 41.0 30.2 0.74 2.65 50.1 15.5 5.4

10.0 2.35 5.41500 74.2 4.76 58.0 115.8 4.57 9.5

8.0 1.65 3.81000 40.0 26.0 0.65 2.36 48.1 16.9 5.7

1800 77.2 4.64 61.4 109.7 4.88 7.9 1400 41.2 30.6 0.74 2.46 49.6 16.8 5.7

13.5 3.95 9.11500 78.0 4.81 61.6 118.1 4.75 9.6

10.5 2.42 5.61000 40.9 26.2 0.64 2.26 48.6 18.1 5.9

1800 81.1 4.68 65.1 111.7 5.08 9.0 1400 42.2 30.8 0.73 2.36 50.2 17.9 5.9

90

6.5 1.12 2.61500 73.5 4.93 56.7 115.4 4.37 9.7

90

5.5 0.84 1.91000 37.6 24.8 0.66 2.82 47.2 13.3 6.7

1800 76.4 4.82 60.0 109.3 4.64 8.6 1400 38.8 29.1 0.75 2.93 48.7 13.2 6.6

10.0 2.27 5.21500 79.9 4.96 63.0 119.4 4.73 9.5

8.0 1.59 3.71000 37.6 25.1 0.67 2.67 46.7 14.1 7.0

1800 83.3 4.80 66.9 112.8 5.09 8.9 1400 38.6 29.5 0.76 2.77 48.0 14.0 7.0

13.5 3.81 8.81500 84.4 5.01 67.3 122.1 4.93 10.4

10.5 2.34 5.41000 37.3 24.9 0.67 2.59 46.1 14.4 7.3

1800 87.9 4.85 71.4 115.2 5.31 9.7 1400 39.8 29.8 0.75 2.67 48.9 14.9 7.4

100

6.5 1.08 2.5

Operation not recommended

100

5.5 0.81 1.91000 35.1 23.9 0.68 3.14 45.8 11.2 8.91400 36.2 28.1 0.78 3.27 47.3 11.1 8.8

10.0 2.19 5.1 8.0 1.53 3.51000 34.9 24.2 0.69 3.05 45.3 11.4 9.31400 36.0 28.5 0.79 3.17 46.8 11.3 9.2

13.5 3.67 8.5 10.5 2.25 5.21000 36.2 24.6 0.68 2.94 46.2 12.3 9.81400 37.3 28.9 0.77 3.07 47.7 12.1 8.2

110

6.5 1.04 2.4

110

5.5 0.78 1.81000 32.7 23.1 0.71 3.45 44.5 9.5 10.61400 33.6 27.0 0.80 3.59 45.9 9.4 10.5

10.0 2.11 4.9 8.0 1.47 3.41000 32.2 23.3 0.72 3.43 43.9 9.4 11.11400 33.3 27.5 0.82 3.58 45.5 9.3 11.1

13.5 3.53 8.2 10.5 2.17 5.01000 33.8 23.8 0.70 3.33 45.1 10.1 11.61400 34.7 27.9 0.80 3.47 46.5 10.0 10.5

120

6.5 1.00 2.3

120

5.5 0.75 1.71000 30.9 24.4 0.79 4.15 45.0 7.4 12.81400 31.5 26.6 0.84 4.25 46.0 7.4 13.1

10.0 2.02 4.7 8.0 1.42 3.31000 31.3 24.6 0.79 3.93 44.7 8.0 13.21400 31.8 26.7 0.84 4.03 45.6 7.9 13.6

13.5 3.39 7.8 10.5 2.08 4.81000 31.5 24.6 0.78 3.80 44.5 8.3 13.81400 32.2 26.7 0.83 3.92 45.6 8.2 14.0

Performance capacities shown in thousands of Btuh. 11/2/20

Performance Data cont.

Page 18: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 18 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

060 - 50% Part Load

EWT

°F

Flow

gpm

WPD HEATING - EAT 70°FEWT

°F

Flow

gpm

WPD COOLING - EAT 80/67 °F

PSI FTAirflow

cfm

HC

mBtuh

Power

kW

HE

MBtuh

LAT

°FCOP

HWC

MBtuhPSI FT

Airflow

cfm

TC

MBtuh

SC

MBtuh

S/T

Ratio

Power

kW

HR

MBtuhEER

HWC

MBtuh

20

4.5 0.63 1.5Operation not recommended

20

4.0 0.43 1.0

Operation not recommended6.3 1.17 2.7 6.0 1.22 2.8

8.5 1.94 4.5850 21.0 2.18 13.5 92.9 2.82 3.4

7.5 1.80 4.21100 21.4 2.02 14.5 88.0 3.10 3.1

30

4.5 0.61 1.4850 23.8 2.01 16.9 95.9 3.47 3.9

30

4.0 0.42 1.0700 31.5 18.0 0.57 0.76 34.1 41.2 -

1100 24.6 2.03 17.7 90.7 3.54 3.4 950 32.1 19.7 0.61 0.80 34.8 40.3 -

6.3 1.14 2.6850 23.6 2.03 16.7 95.7 3.40 4.1

6.0 1.18 2.7700 32.0 18.1 0.57 0.73 34.4 44.0 -

1100 24.5 2.06 17.4 90.6 3.48 3.5 950 32.5 19.8 0.61 0.77 35.1 42.4 -

8.5 1.89 4.4850 24.8 2.22 17.2 97.0 3.27 4.2

7.5 1.75 4.0700 32.1 18.1 0.56 0.70 34.5 45.6 -

1100 25.3 2.06 18.3 91.3 3.60 3.6 950 32.9 19.8 0.60 0.74 35.4 44.5 -

40

4.5 0.60 1.4850 27.5 2.05 20.5 100.0 3.94 4.3

40

4.0 0.41 0.9700 32.5 20.5 0.63 0.81 35.3 39.9 -

1100 28.4 2.06 21.3 93.9 4.03 3.7 950 33.2 22.4 0.68 0.85 36.1 39.1 -

6.3 1.10 2.5850 27.7 2.08 20.6 100.2 3.90 4.5

6.0 1.15 2.6700 32.9 20.7 0.63 0.77 35.5 42.5 -

1100 28.5 2.09 21.4 94.0 4.00 3.8 950 33.5 22.6 0.67 0.81 36.3 41.3 -

8.5 1.83 4.2850 28.6 2.09 21.5 101.2 4.02 4.7

7.5 1.70 3.9700 33.2 20.7 0.62 0.75 35.7 44.2 -

1100 29.4 2.10 22.3 94.7 4.11 3.9 950 33.9 22.6 0.67 0.79 36.6 43.2 -

50

4.5 0.58 1.3850 31.3 2.09 24.2 104.1 4.39 4.7

50

4.0 0.40 0.9700 33.7 22.2 0.66 0.84 36.6 40.3 -

1100 32.2 2.09 25.0 97.1 4.51 3.9 950 34.7 25.2 0.73 0.88 37.7 39.3 -

6.3 1.07 2.5850 31.8 2.13 24.5 104.6 4.38 4.9

6.0 1.11 2.6700 33.8 22.4 0.66 0.81 36.6 41.9 -

1100 32.5 2.12 25.3 97.4 4.50 4.1 950 34.8 25.4 0.73 0.85 37.7 41.2 -

8.5 1.77 4.1850 32.8 2.14 25.5 105.7 4.48 5.2

7.5 1.64 3.8700 33.9 22.4 0.66 0.79 36.6 42.8 -

1100 33.5 2.13 26.2 98.2 4.61 4.6 950 34.9 25.4 0.73 0.83 37.7 42.0 -

60

4.5 0.56 1.3850 35.3 2.13 28.0 108.5 4.86 5.1

60

4.0 0.38 0.9700 32.7 21.9 0.67 1.03 36.2 31.8 1.5

1100 36.1 2.11 28.9 100.4 5.01 4.2 950 33.7 24.7 0.73 1.08 37.4 31.3 1.6

6.3 1.03 2.4850 36.4 2.17 29.0 109.7 4.92 5.3

6.0 1.08 2.5700 32.9 22.1 0.67 1.00 36.3 33.0 1.7

1100 37.0 2.14 29.7 101.1 5.07 4.5 950 33.9 25.0 0.74 1.04 37.4 32.5 1.7

8.5 1.72 4.0850 37.3 2.19 29.8 110.6 5.00 5.6

7.5 1.59 3.7700 33.0 22.1 0.67 0.98 36.3 33.9 1.8

1100 37.9 2.16 30.5 101.9 5.15 4.7 950 34.0 25.0 0.74 1.02 37.5 33.3 1.8

70

4.5 0.54 1.2850 39.3 2.17 31.9 112.8 5.31 5.4

70

4.0 0.37 0.9700 31.7 21.6 0.68 1.22 35.9 26.0 2.1

1100 38.6 2.15 31.3 102.5 5.26 4.5 950 33.0 24.7 0.75 1.39 37.7 23.7 2.3

6.3 1.00 2.3850 41.0 2.20 33.5 114.6 5.45 5.8

6.0 1.04 2.4700 31.9 21.8 0.68 1.18 36.0 27.0 2.4

1100 41.4 2.16 34.1 104.9 5.63 4.8 950 32.9 24.5 0.74 1.24 37.1 26.6 2.4

8.5 1.66 3.8850 41.8 2.23 34.1 115.5 5.49 6.0

7.5 1.54 3.6700 32.1 21.9 0.68 1.16 36.1 27.7 2.5

1100 42.2 2.18 34.8 105.5 5.67 5.0 950 33.1 24.6 0.74 1.21 37.2 27.4 2.5

80

4.5 0.52 1.2850 42.9 2.23 35.3 116.7 5.64 5.8

80

4.0 0.36 0.8700 29.9 21.2 0.71 1.45 34.8 20.6 3.1

1100 43.3 2.18 35.8 106.4 5.81 4.8 950 30.8 23.6 0.77 1.50 35.9 20.5 3.2

6.3 0.97 2.2850 45.3 2.27 37.6 119.3 5.86 6.2

6.0 1.00 2.3700 30.1 21.4 0.71 1.41 35.0 21.3 3.3

1100 45.5 2.20 38.0 108.3 6.06 5.1 950 31.0 23.9 0.77 1.47 36.1 21.2 3.4

8.5 1.60 3.7850 45.8 2.30 38.0 119.9 5.85 6.6

7.5 1.49 3.4700 30.3 21.5 0.71 1.39 35.1 21.8 3.5

1100 46.0 2.23 38.4 108.7 6.05 5.4 950 31.3 24.1 0.77 1.44 36.2 21.7 4.0

90

4.5 0.50 1.2850 46.5 2.29 38.6 120.6 5.94 6.2

90

4.0 0.34 0.8700 28.0 20.7 0.74 1.68 33.8 16.7 4.4

1100 46.6 2.23 39.0 109.2 6.12 5.0 950 28.9 23.0 0.80 1.73 34.8 16.7 4.4

6.3 0.93 2.2850 49.6 2.33 41.6 124.0 6.24 6.6

6.0 0.97 2.2700 28.4 20.9 0.74 1.64 34.0 17.3 4.6

1100 49.6 2.24 41.9 111.7 6.48 5.4 950 29.2 23.3 0.80 1.70 35.0 17.2 4.6

8.5 1.55 3.6850 49.9 2.36 41.8 124.4 6.19 7.1

7.5 1.43 3.3700 28.2 19.4 0.69 1.67 33.9 16.9 4.8

1100 49.8 2.28 42.0 111.9 6.40 5.8 950 29.5 23.5 0.80 1.67 35.2 17.7 4.8

100

4.5 0.48 1.1

Operation not recommended

100

4.0 0.33 0.8700 26.1 20.1 0.77 2.02 33.0 12.9 5.4950 26.9 22.2 0.83 2.07 34.0 13.0 5.4

6.3 0.90 2.1 6.0 0.93 2.2700 26.4 20.3 0.77 1.99 33.2 13.3 5.5950 27.2 22.5 0.83 2.04 34.2 13.3 5.5

8.5 1.49 3.4 7.5 1.38 3.2700 26.7 20.6 0.77 1.96 33.4 13.6 5.8950 27.6 22.8 0.83 2.01 34.4 13.7 5.8

110

4.5 0.47 1.1

110

4.0 0.32 0.7700 24.2 19.6 0.81 2.36 32.2 10.2 6.3950 24.9 21.5 0.86 2.41 33.2 10.4 6.3

6.3 0.86 2.0 6.0 0.90 2.1700 24.5 19.8 0.81 2.34 32.5 10.5 6.8950 25.3 21.7 0.86 2.38 33.4 10.6 6.8

8.5 1.43 3.3 7.5 1.33 3.1700 24.8 20.1 0.81 2.30 32.7 10.8 7.2950 25.6 22.0 0.86 2.35 33.6 10.9 7.2

120

4.5 0.45 1.0

120

4.0 0.31 0.7700 23.6 19.3 0.82 2.88 33.4 8.2 8.2950 24.1 21.0 0.87 2.95 34.2 8.2 8.2

6.3 0.83 1.9 6.0 0.86 2.0700 23.9 19.4 0.81 2.73 33.2 8.8 8.4950 24.3 21.1 0.87 2.80 33.8 8.7 8.4

8.5 1.38 3.2 7.5 1.28 3.0700 24.1 19.4 0.81 2.64 33.1 9.1 8.7950 24.6 21.1 0.86 2.72 33.9 9.0 8.7

Performance capacities shown in thousands of Btuh. 11/2/20

Performance Data cont.

Page 19: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 19 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

060 - 100% Full Load

EWT

°F

Flow

gpm

WPD HEATING - EAT 70°FEWT

°F

Flow

gpm

WPD COOLING - EAT 80/67 °F

PSI FTAirflow

cfm

HC

mBtuh

Power

kW

HE

MBtuh

LAT

°FCOP

HWC

MBtuhPSI FT

Airflow

cfm

TC

MBtuh

SC

MBtuh

S/T

Ratio

Power

kW

HR

MBtuhEER

HWC

MBtuh

20

8.5 2.00 4.6Operation not recommended

20

6.5 1.21 2.8

Operation not recommended13.0 3.52 8.1 10.0 2.70 6.2

17.0 6.55 15.11800 47.9 5.26 29.9 94.6 2.67 8.1

13.5 4.20 9.72200 48.9 5.23 31.1 90.6 2.74 7.5

30

8.5 1.95 4.51800 48.2 4.41 33.2 94.8 3.21 8.4

30

6.5 1.17 2.71500 59.6 37.0 0.62 1.75 65.5 34.1 -

2200 49.4 4.64 33.5 90.8 3.12 7.8 1800 60.7 40.6 0.67 1.82 66.9 33.4 -

13.0 3.42 7.91800 51.6 4.45 36.4 96.6 3.40 8.6

10.0 2.62 6.11500 60.4 37.3 0.62 1.66 66.1 36.4 -

2200 53.0 4.74 36.9 92.3 3.28 7.9 1800 61.4 40.8 0.66 1.75 67.3 35.1 -

17.0 6.36 14.71800 52.5 4.81 36.1 97.0 3.20 8.8

13.5 4.08 9.41500 60.7 37.3 0.61 1.61 66.2 37.7 -

2200 53.6 4.78 37.3 92.6 3.29 8.0 1800 62.2 40.8 0.66 1.69 68.0 36.8 -

40

8.5 1.90 4.41800 56.0 4.58 40.4 98.8 3.58 8.9

40

6.5 1.14 2.61500 60.6 39.5 0.65 2.04 67.5 29.7 -

2200 57.3 4.77 41.0 94.1 3.52 8.2 1800 61.8 43.2 0.70 2.12 69.0 29.1 -

13.0 3.32 7.71800 59.6 4.65 43.7 100.6 3.75 9.2

10.0 2.55 5.91500 61.3 39.9 0.65 1.94 67.9 31.7 -

2200 60.9 4.85 44.4 95.6 3.68 8.4 1800 62.4 43.5 0.70 2.03 69.4 30.7 -

17.0 6.17 14.31800 60.5 4.74 44.3 101.1 3.74 9.5

13.5 3.96 9.11500 61.8 39.9 0.65 1.88 68.2 32.9 -

2200 61.9 4.90 45.1 96.0 3.70 8.6 1800 63.2 43.5 0.69 1.97 69.9 32.1 -

50

8.5 1.85 4.31800 63.8 4.75 47.6 102.8 3.93 9.5

50

6.5 1.10 2.51500 61.6 41.7 0.68 2.19 69.1 28.1 -

2200 65.2 4.90 48.4 97.4 3.90 8.6 1800 62.8 45.3 0.72 2.33 70.8 27.0 -

13.0 3.21 7.41800 67.5 4.85 51.0 104.7 4.08 9.9

10.0 2.47 5.71500 62.2 42.1 0.68 2.14 69.5 29.0 -

2200 68.9 4.97 51.9 99.0 4.06 8.9 1800 63.5 45.8 0.72 2.28 71.2 27.9 -

17.0 5.98 13.81800 68.6 4.90 51.9 105.3 4.10 10.3

13.5 3.83 8.91500 62.8 42.6 0.68 2.11 70.0 29.8 -

2200 70.1 5.02 53.0 99.5 4.09 9.3 1800 64.1 46.2 0.72 2.24 71.7 28.6 -

60

8.5 1.80 4.21800 72.5 4.94 55.7 107.3 4.30 10.1

60

6.5 1.07 2.51500 59.2 40.9 0.69 2.46 67.6 24.0 3.1

2200 74.1 5.02 57.0 101.2 4.33 9.0 1800 60.7 44.4 0.73 2.62 69.6 23.1 3.1

13.0 3.11 7.21800 75.9 5.02 58.7 109.0 4.43 10.6

10.0 2.39 5.51500 59.8 41.3 0.69 2.42 68.0 24.7 2.9

2200 77.5 5.08 60.1 102.6 4.47 9.5 1800 61.3 44.9 0.73 2.57 70.1 23.9 2.9

17.0 5.79 13.41800 77.5 5.08 60.2 109.9 4.47 11.1

13.5 3.71 8.61500 60.4 41.7 0.69 2.37 68.5 25.4 2.7

2200 79.3 5.14 61.7 103.4 4.52 9.9 1800 61.9 45.3 0.73 2.53 70.5 24.5 2.7

70

8.5 1.75 4.01800 81.3 5.12 63.8 111.8 4.65 10.6

70

6.5 1.03 2.41500 56.7 40.1 0.71 2.74 66.1 20.7 4.6

2200 81.5 5.15 63.9 104.3 4.64 9.5 1800 58.1 44.0 0.76 3.20 69.0 18.2 4.6

13.0 3.01 7.01800 84.2 5.19 66.5 113.3 4.76 11.2

10.0 2.31 5.31500 57.3 40.5 0.71 2.69 66.5 21.3 4.3

2200 86.1 5.20 68.4 106.3 4.85 10.0 1800 59.1 43.9 0.74 2.86 68.9 20.7 4.3

17.0 5.60 12.91800 86.4 5.25 68.5 114.4 4.82 11.9

13.5 3.59 8.31500 57.8 40.8 0.71 2.64 66.9 21.9 4.2

2200 88.4 5.25 70.5 107.2 4.93 10.6 1800 59.7 44.4 0.74 2.81 69.3 21.2 4.1

80

8.5 1.68 3.91800 90.5 5.41 72.1 116.6 4.90 11.8

80

6.5 0.99 2.31500 52.9 38.8 0.73 3.13 63.6 16.9 6.1

2200 92.6 5.38 74.2 109.0 5.05 9.9 1800 54.9 42.2 0.77 3.34 66.3 16.4 6.1

13.0 2.91 6.71800 92.7 5.48 74.0 117.7 4.96 12.2

10.0 2.23 5.21500 53.5 39.2 0.73 3.07 64.0 17.4 5.8

2200 94.9 5.42 76.4 109.9 5.13 10.6 1800 55.4 42.6 0.77 3.27 66.6 17.0 5.8

17.0 5.41 12.51800 95.5 5.54 76.6 119.1 5.05 12.6

13.5 3.47 8.01500 54.0 39.6 0.73 3.02 64.3 17.9 5.5

2200 97.9 5.48 79.2 111.2 5.24 11.2 1800 56.0 43.0 0.77 3.22 67.0 17.4 5.5

90

8.5 1.60 3.71800 99.8 5.70 80.3 121.3 5.13 11.7

90

6.5 0.96 2.21500 49.1 37.6 0.77 3.53 61.1 13.9 8.2

2200 102.2 5.62 83.0 113.0 5.33 10.3 1800 51.3 40.8 0.80 3.76 64.1 13.6 8.2

13.0 2.80 6.51800 101.1 5.76 81.4 122.0 5.14 12.6

10.0 2.15 5.01500 49.7 37.9 0.76 3.46 61.4 14.4 7.8

2200 103.6 5.64 84.3 113.6 5.38 11.1 1800 51.7 41.2 0.80 3.68 64.3 14.1 7.8

17.0 5.22 12.11800 104.5 5.83 84.6 123.8 5.25 13.4

13.5 3.34 7.71500 50.7 38.2 0.75 3.50 62.6 14.5 7.3

2200 107.3 5.70 87.9 115.2 5.52 11.9 1800 52.3 41.6 0.80 3.62 64.7 14.4 7.4

100

8.5 1.55 3.6

Operation not recommended

100

6.5 0.92 2.11500 44.7 36.4 0.81 4.02 58.4 11.1 10.31800 46.9 39.5 0.84 4.29 61.5 10.9 10.3

13.0 2.70 6.2 10.0 2.07 4.81500 45.2 36.7 0.81 3.94 58.6 11.5 9.71800 47.3 39.9 0.84 4.20 61.7 11.3 9.8

17.0 5.03 11.6 13.5 3.22 7.51500 45.6 37.1 0.81 3.87 58.8 11.8 9.21800 47.8 40.3 0.84 4.13 61.9 11.6 9.2

110

8.5 1.50 3.5

110

6.5 0.89 2.11500 40.3 35.2 0.87 4.52 55.7 8.9 13.01800 42.4 38.2 0.90 4.82 58.9 8.8 13.1

13.0 2.60 6.0 10.0 2.00 4.61500 40.7 35.5 0.87 4.42 55.8 9.2 12.31800 42.9 38.6 0.90 4.72 59.0 9.1 12.4

17.0 4.84 11.2 13.5 3.10 7.21500 41.1 35.9 0.87 4.35 55.9 9.5 11.61800 43.3 39.0 0.90 4.64 59.1 9.3 11.7

120

8.5 1.40 3.2

120

6.5 0.85 2.01500 38.7 34.1 0.88 5.54 57.6 7.0 16.11800 39.6 37.1 0.94 5.67 58.9 7.0 16.2

13.0 2.50 5.8 10.0 1.92 4.41500 39.2 34.4 0.88 5.24 57.1 7.5 15.21800 39.9 37.3 0.93 5.38 58.3 7.4 15.3

17.0 4.65 10.7 13.5 2.98 6.91500 39.6 34.4 0.87 5.07 56.9 7.8 14.31800 40.4 37.3 0.92 5.23 58.2 7.7 14.5

Performance capacities shown in thousands of Btuh. 11/2/20

Performance Data cont.

Page 20: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.:

Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 20 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Wiring Schematics

Aurora Variable Speed

97P842-01A

Vio

let(14)

RVRVCCCC

Condensate

TTYellow

(117)

Yellow(116)

FP1

Orange(121)

Orange(120)

RV

Black(15)

Green(11 )Brown(115)

NO TE 2

NOTE 1

Unit Power 208-230/60/1

L2 L1

CCT2 T1

Red208V

GG

5A C

ircuit Breaker

5A C

ircuit Breaker

Black(3 )

Black(2 )

Gray/White(4)

1

2PB1

2

11

2PB1

2

1

PS

1

3

2

Bla

Red

Black

L1 aV

AID Tool

Communicating Thermostat

To Master onVS Drive

B

123

A-B+

C 123

A-B+

C

TT Brown(127)Brown(126)

T Purple(131)Purple(130)

GNDOUT5DC

324

Green(13 4)White(133)Brown(132)

Brown(102)

Brown(101)

Black(1 04)

Black(1 03)

Violet(8)

Violet(7)

Brown(10)

Orange(9)

SUC

PSU

C P

AUXILIARY HEAT CT

BLOWER CT

PERFORMANCEOPTION

324

FLOW METER

Black/White(5)

TTHW HW

White

White

BlackBlack

OrangeOrange

HOT WATEROPTION

Red

Black

Circuit Breaker

Circuit Breaker

BlueBlue

BlueBlue

Pump Slave Input/Output

Home Automation

Smar t Gr id

Future Use

Dehumidification Output

Accessory 2 Output

Analog Output 0-10VDC

NOTE: 8

NOTE: 9

208-230/60/1

Pump

GGG

PumpPumpExt Pump

1/2 hp Total Ext Pump

1/2 hp Total

Gray(136)

Gray(135)

White(129)White(128)

T

SCT

P8

MOT

OR P6

RS48

5 P7

ZONE P9

ABC

STEP

PER

ANA

ACC2

DHDI

V

NO

CO

M

K6

NO

CO

M

K5

C R L1 L1 L2 L2P1

2P1

0P5

P11

CR(-)(+) CR(-)(+) CR(-)(+)

P4P2

K1K2

K3

HA2

HA1

SGI

LOO

PVS

DAT

AVS

PUM

PPU

MPSL

AVE

P3

V+CRTXRX +5

P14

LLT

P1LA

TFL

OW

LWT

EWT

43

FAN

43

CT1

21

AUX

21

StatusG

DISC

HP1

6

P17

P18

P15

(Aurora Expansion Board)AXB™

See Figure 1 for DHW wiring.

SW1

Modbus Add. IDFuture Use

12345

ONOFF

Future UseAcc 2 – Dip 4Acc 2 – Dip 5

CT2

SCT

P8

MOT

OR P6

RS48

5 P7

ZONE P9

ABC

STEP

PER

ANA

ACC2

DHDI

V

NO

CO

M

K6

NO

CO

M

K5

C R L1 L1 L2 L2P1

2P1

0P5

P11

CR(-)(+) CR(-)(+) CR(-)(+)

P4P2

K1K2

K3

HA2

HA1

SGI

LOO

PVS

DAT

AVS

PUM

PPU

MPSL

AVE

P3

V+CRTXRX +5

P14

LLT

P1LA

TFL

OW

LWT

EWT

43

FAN

43

CT1

21

AUX

21

StatusG

DISC

HP1

6

P17

P18

P15

(Aurora Expansion Board)AXB™

See Figure 1 for DHW wiring.

SW1

Modbus Add. IDFuture Use

12345

ONOFF

Future UseAcc 2 – Dip 4Acc 2 – Dip 5

CT2

CS

+5C

S+5

21

CC

INOU

T

Pink(140)

Pink(139)

VS

GND24 VAC

0-10DC

12

3

R

C

ABC BOARD

AXB BOARD

MODULATING VALVE

12

Red

WhiteGreen

NO TE: 13

VARIABLE SPEED PUMP

LOW VOLTAGESEE 97P927-01

VARIABLE SPEED PUMP

LOW VOLTAGESEE 97P927-01

VARIABLE SPEED PUMP

HIGH VOLTAGE

SEE 97P927-01

VARIABLE SPEED PUMP

HIGH VOLTAGE

SEE 97P927-01

SW1

P5JW2

P9

LO

O/B

Y2WDH

P8 P7

RS485 NET RS485 NET

P6

RS485 EXP

P3

Com1LED5

Com2LED5

Test Mode

P1

ALMALGACC COMACC NOACC NC

RC

G

EH2CEH1CCOC R - +C R - +

CC2 CC F C R F FG CC CCGCC2HI

CC2LO

CC2G REVREVFP1 FP1

Aurora Base Control(ABC)

K1-RV Relay

K2-CC Relay

K3-CC2 Relay

K4-Fan RelayK5-Alarm Relay

K6-Acc Relay

YC

R

ESLS

P2EH1

GG GG

Y1

SW1

P5JW2

P9

LO

O/B

Y2WDH

P8 P7

RS485 NET RS485 NET

P6

RS485 EXP

P3

Com1LED5

Com2LED5

Test Mode

P1

ALMALGACC COMACC NOACC NC

RC

G

EH2CEH1CCOC R - +C R - +

CC2 CC F C R F FG CC CCGCC2HI

CC2LO

CC2G REVREVFP1 FP1

Aurora Base Control(ABC)

K1-RV Relay

K2-CC Relay

K3-CC2 Relay

K4-Fan RelayK5-Alarm Relay

K6-Acc Relay

YC

R

ESLS

P2EH1

G G

Y1

SW1

P5JW2

P9

LO

O/B

Y2WDH

P8 P7

RS485 NET RS485 NET

P6

RS485 EXP

P3

Com1LED5

Com2LED5

Test Mode

P1

ALMALGACC COMACC NOACC NC

RC

G

EH2CEH1CCOC R - +C R - +

CC2 CC F C R F FG CC CCGCC2HI

CC2LO

CC2G REVREVFP1 FP1

Aurora Base Control(ABC)

K1-RV Relay

K2-CC Relay

K3-CC2 Relay

K4-Fan RelayK5-Alarm Relay

K6-Acc Relay

YC

R

ESLS

P2EH1

G G

Y1

Perfect Speed Blower Motor

Grn

4 23 1

PWM

P13 Connects Here

P112 3 4 51

Not U

sed

COM

Feed

back

15 10163 815 10163 8

Perfect Speed Blower Motor

Grn

4 23 1

PWM

P13 Connects Here

P112 3 4 51

Not U

sed

COM

Feed

back

15 10163 8NOTE 14

Perfect Speed Blower Motor

Grn

4 23 1

PWM

P13 Connects Here

P112 3 4 51

Not U

sed

COM

Feed

back

15 10163 8NOTE 14

RVO

range(121)

RV

B

W1W1W1W1

MoMoMoMo

H2

VR

Page 21: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.:

Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 21 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Wiring Schematics cont.

Aurora Variable Speed cont.

97P842-01A

NOTE 7NOTE 7

NOTE 6NOTE 6

Page 1Page 1

Transformer

24V

Transformer

24V

ECM BlowerMotor

P112 3 4 51

Green(10 7)

16 112 15 10

PWM

C1 C2R G

33

CFM

To P2 on Electric Heat Board

TTRVRV

HP

Black(125)

Black(124)

Blue(123)

Blue(122)

LP

Black(119)

Black(118)

FP2

TTYellow

(117)

Yellow(116)

FP1

Orange(121)

Orange(120)

RV

Violet(111)

Blue(110)

Yellow(109)

Green/Yellow(108)

Black/White

Yellow

Red208V

1C

21

C2

43

24

32

1C

24

32

1C

24

32

Black(1 13)

PS3

Brown(106)

Blue240V

Black

L1 and L2 on VS Drive

12

L1L2

Black(1 14)

Black(1 12)

Orange(105)

BLOWERCURRENT

TRANSDUCER(CT)

Red

Black

r

r

NOCOM

K6 RelayConnects to L2 and NO on AXB Board

L2

NOCOM

K6 RelayConnects to L2 and NO on AXB Board

L2

Figure 1:Optional Internal

Hot Water Generation Pump Wiring Schematic

DHW Pump

Blue(137)

Blue(138)

Cabinet HW Switch

3

21

PurpleDHW Pump

Blue(137)

Blue(138)

Cabinet HW Switch

3

21

Purple

NOCOM

K6 RelayConnects to L2 and NO on AXB Board

L2

Figure 1:Optional Internal

Hot Water Generation Pump Wiring Schematic

DHW Pump

Blue(137)

Blue(138)

Cabinet HW Switch

3

21

Purple

Communicating Thermostat Dual Fuel Wiring DiagramUsing Field Installed Relay

24 VDC

R f rom Foss il Fue l Furnac e

To Foss il Fuel Furnac e W input

EH1

C

ABCBoard

Note 12 : Fi eld inst al led SPST dual fuel rela y (R equi re d for dual fuel inst all ati on)

5 – Low voltage wiring CLASS 2 .

NotesNotes

3 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is requ ired.

1 - Switch blue and red wires for 208V operation. 2 - The b lk/wh and gray/wh wires are removed when A ux Heat is installed

4 – Variable speed pump low voltage harness provided with V ariab le Speed Flow Center.

6 - Wires provided fo r Auxiliary Heat low voltage control. Wires are secured a t blower.7 – When Auxilia ry Heat is field installed the harness will t hen be connected to the auxiliary heat unit. The auxilia ry heat un it will then power the blower. Refer to EAS/EA M/EAL Auxiliary Heat kit installation instructions.

9 – Fie ld Connected : Refer to Installa tion Manual and Auxilia ry Heat Instructions for Current Transducer insta llation .10 – Communication cab le routed through Ferrite Toro id four times.11 – Compressor power cable routed through Ferrite Toroid th ree times.12 - Fie ld installed SPST relay required for dual fuel installation.

Notes

3 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is requ ired.

1 - Switch blue and red wires for 208V operation. 2 - The b lk/wh and gray/wh wires are removed when A ux Heat is installed

4 – Variable speed pump low voltage harness provided with V ariab le Speed Flow Center.

6 - Wires provided fo r Auxiliary Heat low voltage control. Wires are secured a t blower.7 – When Auxilia ry Heat is field installed the harness will t hen be connected to the auxiliary heat unit. The auxilia ry heat un it will then power the blower. Refer to EAS/EA M/EAL Auxiliary Heat kit installation instructions.

9 – Fie ld Connected : Refer to Installa tion Manual and Auxilia ry Heat Instructions for Current Transducer insta llation .10 – Communication cab le routed through Ferrite Toro id four times.11 – Compressor power cable routed through Ferrite Toroid th ree times.12 - Fie ld installed SPST relay required for dual fuel installation.13 - Wiring harness supplied with va lve.

23

P9

54

1

L2 L1 L2 L1

Green

P112 3 4 51

VioletBlue

BrownOrange

HE1 TS1TS1HE1 TS1

HE3 TS3TS3HE3 TS3

HE2 TS2TS2HE2 TS2

HE4 TS4TS4HE4 TS4

Connects to variable speed ECM motor only

60 AMP BRK1

60 AMP BRK2

GGGG

K1

K2

K3

K4

NO

NO

NO

NO

EA Series PCB

P241 2 3C

G

G

G

G

K5

NO

K6

NO

K7

NO

K8

NO

Gray

Yellow

GrayYellow

Black

Pink

Black

Pink

Pink

Pink

Gray

Black

Yellow

Gray

Black

Yellow

41 2 3CP1

COMCOM

COM COM

COM COM

COMCOM

Aux heat staging

FB1

FB2

FB3

FB4

P3 on Aurora ABC Board

P3EH2C EH1 CCO P3EH2C EH1 CCO

Light emitting diode - Green

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField l ine voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal

Thermal Limit Switch

Field wire lug

GroundHE -

PB -

Heater element

Power block

Legend

N.O., N.C.

G

L1

Breaker

1 2 3PTS

Electric Heat RelayK*

Fused BackupFB

K*

Fused BackupFB

Light emitting diode - Green

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField l ine voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal

Thermal Limit Switch

Field wire lug

GroundHE -

PB -

Heater element

Power block

Legend

N.O., N.C.

G

L1

Breaker

1 2 3PTS

Electric Heat RelayK*

Fused BackupFB

2 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when sing le source power is required .

1 - Use copper conductors.

3 – Jumpers wires a re Factory Installed, and arerequired fo r auxiliary heat operation. 4 – Low voltage wiring CLASS 2 .

2 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when sing le source power is required .

1 - Use copper conductors.

3 – Jumpers wires a re Factory Installed, and arerequired fo r auxiliary heat operation. 4 – Low voltage wiring CLASS 2 .

NOTE 3

With optional EA Series 20kW Auxiliary Electric Heat Shown

CFM

P13

P4

SW1

P3

SW2

On

Future Use L Output Type

CC – Dual/SingleAcc – Dip 5Acc – Dip 4

RV – B/OFP2 – 15°F/30°FFP1 – 15°F/30°F

Test Mode

F1-3A

C

PWM

12345678

EH2C

Off

Faul tLED1

R

StatusLED3

ConfigLED2

REVREVFP1 FP1 FP2 FP2 LPS LPSHPSHPS

F

R

C

CCGY1

YY

GGG

CFM

P13

P4

SW1

P3

SW2

On

Future Use L Output Type

CC – Dual/SingleAcc – Dip 5Acc – Dip 4

RV – B/OFP2 – 15°F/30°FFP1 – 15°F/30°F

Test Mode

F1-3A

C

PWM

12345678

EH2C

Off

Faul tLED1

R

StatusLED3

ConfigLED2

REVREVFP1 FP1 FP2 FP2 LPS LPSHPSHPS

F

R

C

CCGY1

Y

G

CFM

P13

P4

SW1

P3

SW2

On

Future Use L Output Type

CC – Dual/SingleAcc – Dip 5Acc – Dip 4

RV – B/OFP2 – 15°F/30°FFP1 – 15°F/30°F

Test Mode

F1-3A

C

PWM

12345678

EH2C

Off

Faul tLED1

R

StatusLED3

ConfigLED2

REVREVFP1 FP1 FP2 FP2 LPS LPSHPSHPS

F

R

C

CCGY1

Y

G

8 – Brown blower power wire rou ted through Current Transducer two times.

14 - On units with the NIDEC ECM motor the P13 harness connects to the jumper harness on the motor.

RVO

range(121)

RV

B

W1W1W1W1

MMMM

H2

VVVVR

Page 22: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 22 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Wiring Schematics cont.

Aurora Variable Speed Drive/EEV Wiring

97P842-01B

Unit Power 208-230/60/1

L2L1

CCT1

T2

L2L1

CCT1

T2

GG

TT TT

Compressor Ambient

Discharge Line Temp

Suction Pressure(Red Plug)

Discharge Pressure(Green Plug)

Bla

ck

Bro

wn

Blu

e

Bla

ck

Bro

wn

Blu

e

Red

RedBla

ck

Bla

ck

Master

123

EEV2

1234

S-Am

bien

t

1 2

S-D

1 2

P-O

1 2 3 4

P-C

1 2 3 4

RLY-

1

1 2 3

BCO

M O R B+A- C+ - + -

COM

5 VD

COU

T

N/A

COM

5 VD

COU

T

N/A

(+) (-)

12

L1L2

DanfossVariable Speed

Drive

12

T1T2

T3 31

2T1

T2T3 3

1 2+ -

TT

Entering Water Temp

EWT

Bla

ck

Bla

ck

2 13 4

COM

OUT

5 VD

CN/

A

2 13 4

COM

OUT

5 VD

CN/

A

2 13 4

COM

OUT

5 VD

CN/

A

2 13 4

COM

OUT

5 VD

CN/

A

To Aurora Board

RS485 EXP

C

R

(-)

(+)

RS485 EXP

C

R

(-)

(+)

ABC P6

RS485 EXP

C

R

(-)

(+)

ABC P6To AXB Board

ABC

(+)

(-)

R

C

AXB P9

C

S-AU

X

Metal Flexible Conduit

B+

C

R

(-)

(+) Green

White

Red

Black

5VAC

Circuit Breaker

Circuit Breaker

Ferrite Toroid

Ferrite Toroid

Black

Black

Red

Red G

NOTE 11

NOTE 10

White Blue

Red GreenBlack Black Red

BlueWhite

EEV CONTROL BOARD EEV CONTROL BOARD

EEV COIL

LAT

SUCT ION TEMP

EEV COMM

NOT USED

NOT USED

EEV CONTROL BOARD

EEV COIL

LAT

SUCT ION TEMP

EEV COMM

NOT USED

NOT USED

EEV 1

MASTER

EEV 2

EXT. FAN

S_AMBIENTS_AUXS_D

P_O

P_C

RLY 1

L1L2

EEV 1

MASTER

EEV 2

EXT. FAN

S_AMBIENTS_AUXS_D

P_O

P_C

RLY 1

L1L2

VARIABLE SPEED DRIVE END VIEWS

T1

T2

T3

T1

T2

T3

EEV 1

MASTER

EEV 2

EXT. FAN

S_AMBIENTS_AUXS_D

P_O

P_C

RLY 1

L1L2

VARIABLE SPEED DRIVE END VIEWS

T1

T2

T3

POWER TO VS DRIVE

POWER TO COMPRESSOR

Page 23: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 23 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Aurora Variable Speed Drive/EEV Wiring cont.

Wiring Schematics cont.

97P842-01B

T1T3

T2

T1T3

T2

Red

ack Suct

ion T

emp

KM2

1 2

EEV

Outpu

tKM

9

1 2 3 4

GND S2

12 V

DC X1 X2 Y1

Danfoss EEV Control

Powe

rKM

4

1 2 3 4RB+ A-C

Leav

ing A

ir Te

mp

(LAT

)KM

3

1 2GN

D S2

5

TTB

lack

Bla

ck

TTB

lack

Bla

ck

Suction Line Temp

Discharge Air Temp

Y2

1 2 3 4

+ X1 X2 Y15

Y2

1 2 3 4

+ X1 X2 Y15

Y2

Ora

nge

Red

Yello

w

Bla

ck

Gra

y

Bipolar Stepper Motor

VS Compressor

Blue

Green

Red Connector (4 Pin)

Current Transducer (CT)

Thermistor

Light emitting diode - Green

Relay coil

Capacitor w/ bleed res is tor

Switch - Condensate overflow

Switch - High pressure

Switch - Low pressure

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesJunctionQuick connect terminal

Wire nut

Field wire lug

Ground

Fuse

CC -CO -K6 -K5 -CR3 -CR4 -

F1 and F2 -

WCL -

HE -HP -

LP -

PB1, PB2 - PS -RV -SW1 -SW1 -SW2 -

TS -

Compressor ContactorCondensate overflow sensorDHW pump relayLoop pump relay

Fuses

Water Coil Limit Sensor

Heater elementHigh pressure switch

Low pressure switch

Power blocksPower stripReversing Valve coilDIP package 5 position AXBTEST MODE ABC BoardDIP package 8 position ABC Board

Thermal limit switch

Legend

Relay Contacts-N.O., N.C.

GG

TT

132P

132P

L1L1

PSC Fan Speed RelayPSC Fan Power Relay

ER1 to ER4 - Aux heat stage relays

HWL - Hot water limit sensorSC - Start Contactor

Start RelaySR -

CS - Compressor Solenoid

Current Transducer (CT)

Thermistor

Light emitting diode - Green

Relay coil

Capacitor w/ bleed res is tor

Switch - Condensate overflow

Switch - High pressure

Switch - Low pressure

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField line voltage wiringOptional blockDC Voltage PCB tracesJunctionQuick connect terminal

Wire nut

Field wire lug

Ground

Fuse

CC -CO -K6 -K5 -CR3 -CR4 -

F1 and F2 -

WCL -

HE -HP -

LP -

PB1, PB2 - PS -RV -SW1 -SW1 -SW2 -

TS -

Compressor ContactorCondensate overflow sensorDHW pump relayLoop pump relay

Fuses

Water Coil Limit Sensor

Heater elementHigh pressure switch

Low pressure switch

Power blocksPower stripReversing Valve coilDIP package 5 position AXBTEST MODE ABC BoardDIP package 8 position ABC Board

Thermal limit switch

Legend

Relay Contacts-N.O., N.C.

G

T

132P

L1

PSC Fan Speed RelayPSC Fan Power Relay

ER1 to ER4 - Aux heat stage relays

HWL - Hot water limit sensorSC - Start Contactor

Start RelaySR -

CS - Compressor Solenoid

SW1-4 SW1-5 DESCRIPTIONON ON Cycles with BlowerOFF ON Cycles with CC rst stage compressor or compressor spd 1-12ON OFF Cycles with CC2 second stage of compressor or comp spd 7-12OFF OFF Cycles with DH from ABC board

AXB Accessory 2 DIP Se ngs

DESCRIPTION SW2-4 SW2-5Cycle with Blower ON ONCycle with Compressor OFF OFFWater Valve Slow Opening ON OFFCycle with Comm. T-stat Hum Cmd OFF ON

ABC SW2 Accessory Relay

Black

Yellow Orange

Blue Color identif icat ion tape on wire.

Black Black

Yellow Orange

HA2

HA1

HOM

ESM

ART

GRID

AXB P4

HA2

HA1

HOM

ESM

ART

GRID

AXB P4WATER SIREN

HOME AUTOMATION ACCESSORIES

HA2

HA1

HOM

ESM

ART

GRID

AXB P4WATER SIREN

HOME AUTOMATION ACCESSORIES

CC2

EH1

Facto

ry

Fault

ALG

ALMLSES AC

C c

S tatus

AURORA BASE CONTROL™

RV – K1

CC2

CC – K2

CC Hi – K3

Fan – K4

Alarm – K5

Acc – K6

ACC

no

ACC

nc

O/BCRLO G Y1 Y2 W DH

3A-F

use

O/BCRLO G Y1 Y2 W DHO/BCRLO G Y1 Y2 W DH

LOG

HICCGCCFGFR

HPHPLP

FP2FP2FP1

REVREV

CFM

PWM

ECM PWM

Facto

ry

Factory Fan Connection

R R

CC

C

RS 4

85

EH2C

EH1C

CO

(+)(-)RCRS

485

Exp

Facto

ry

Com1

Com2

Config

GG

GG

G

YR

SW1 Test

FP1 – 15oF/30oF

JW2 - Alarm

P11

P5

P2 P1

P8

P7

P9

P6

P3

SW2

P13P4 FP2 – 15oF/30oF

RV – B/O

ACC – Dip 4

ACC – Dip 5

CC – Dual/Single

L – Pulse/Continuous

Reheat/Normal

Facto

ry U

se

Field ConnectionsField Connections

C

LP

FP1

F

CC

G

Y1

1

2

3

4

5

6

7

8

Off On

N/A

RS48

5 NE

T

CC2

EH1

Facto

ry

Fault

ALG

ALMLSES AC

C c

S tatus

AURORA BASE CONTROL™

RV – K1

CC2

CC – K2

CC Hi – K3

Fan – K4

Alarm – K5

Acc – K6

ACC

no

ACC

nc

O/BCRLO G Y1 Y2 W DH

3A-F

use

O/BCRLO G Y1 Y2 W DH

LOG

HICCGCCFGFR

HPHPLP

FP2FP2FP1

REVREV

CFM

PWM

ECM PWM

Facto

ry

Factory Fan Connection

R R

CC

C

RS 4

85

EH2C

EH1C

CO

(+)(-)RCRS

485

Exp

Facto

ry

Com1

Com2

Config

G

G

G

YR

SW1 Test

FP1 – 15oF/30oF

JW2 - Alarm

P11

P5

P2 P1

P8

P7

P9

P6

P3

SW2

P13P4 FP2 – 15oF/30oF

RV – B/O

ACC – Dip 4

ACC – Dip 5

CC – Dual/Single

L – Pulse/Continuous

Reheat/Normal

Facto

ry U

se

Field ConnectionsField Connections

C

LP

FP1

F

CC

G

Y1

1

2

3

4

5

6

7

8

Off On

N/A

RS48

5 NE

T

LED3

LED2LED1

Slow FlashFast FlashFlash Code

Fault - Loss of Charge Flash Code 71Safe Mode - Suction Temperature Sensor Flash Code 72

Fault - High Drive Temperature Flash Code 58Fault - Drive Internal Error MOC/AOC Flash Code 59Fault - Multiple Safe Modes Flash Code 61

Fault - Over Current Flash Code 56Fault - Over/Under Voltage Flash Code 57

Flash Code 54Fault - Compressor Out of Envelope Flash Code 55

Fault - Condensing Pressure SensorFault - Low Supply Voltage

Derate - Low Condensing Pressure Flash Code 44Derate - High Condensing Pressure Flash Code 45Derate - Outer Power Limit Flash Code 46

Derate - Drive Temperature Flash Code 41Derate - High Discharge Temperature Flash Code 42Derate - Low Suction Temperature Flash Code 43

Alarm - Home Automation 1 Flash Code 23Alarm - Home Automation 2 Flash Code 24Fault - EEV Error Flash Code 25

Aurora LED Flash Codes1 second on and 1 second off

No Software Overide OFF

100 milliseconds on and 100 milliseconds off100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating

Random Start Delay (Alternating Colors)Status LED (LED1, Green) Fast FlashConfiguration LED (LED 2, Yellow) Fast FlashFault LED (LED 3, Red) Fast Flash

Configuration LED (LED 2, Yellow)

Fault LED (LED 1, Red)Normal Mode OFFInput Fault Lockout Flash Code 1

Slow FlashStatus LED (LED 3, Green)

Normal Mode ONControl is Non - Functional OFFTest Mode Slow Flash

Freeze Detection - FP1 Flash Code 5

Flash Code 2Low Pressure Lockout Flash Code 3Freeze Detection- FP2 Flash Code 4

High Pressure Lockout

Future UseDehumidification Mode

DIP Switch Overide

Flash Code 3Future Use Flash Code 4Load Shed Flash Code 5

Reserved Flash Code 6Condensate Overflow Lockout Flash Code 7Over/Under Voltage Shutdown Flash Code 8Future Use Flash Code 9Fault- FP1 and FP2 Sensor Error Flash Code 11Future Use Flash Code 12Non-Critical AXB Sensor Error Flash Code 13Critical AXB Sensor Error Flash Code 14

Flash Code 2

Safe Mode - Ambient Temperature Sensor Flash Code 49Future Use Flash Code 17Non-Critical Communication Error Flash Code 18

Alarm - Hot Water Flash Code 15Fault Variable Speed Pump Flash Code 16

Fault LED (LED 1, Red) Cont.

ESD Flash Code 6Future Use Flash Code 7

Flash Code 19Alarm - Low Loop Pressure Flash Code 21Fault - Communication ECM Fan Motor Error Flash Code 22

Fault - Discharge Temperature Sensor Flash Code 51Fault - Suction Pressure Sensor Flash Code 52

Fault - Critical Communication Error

Flash Code 53

Page 24: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.:

Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 24 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Wiring Schematics cont.

Aurora Variable Speed with UPC

97P842-02A

Vio

let(14)

Transforme

2

Transforme

2

TTRVRV

CCCC

H

Condensate

Black(124)

Blue(123)

Blue(122)

LP

Black(119)

Black(118)

FP2

TTYellow

(117)

Yellow(116)

FP1

Orange(121)

Orange(120)

RV

Black(15)

Green(11 )Brown(115)

NOTE 2

NOTE 1

Unit Power 208-230/60/1

L2 L1

CCT2 T1

Red208V

GG

5A C

ircuit Breaker

5A C

ircuit Breaker

Black(3 )

Black(2 )

Gray/White(4)

1

2PB1

2

11

2PB1

2

1

Black(1 13

PS

1

3

2

Blue240V

Black

Red

Black

L1 and L2 on VS Drive

12

L1L2

To Master onVS Drive

Black(1 14)

123

A-B+

C 123

A-B+

C

TT Brown(127)Brown(126)

T Purple(131)Purple(130)

GNDOUT5DC

324

Green(13 4)White(133)Brown(132)

Brown(102)Brown(101)

Black(1 04)

Black(1 03)

Violet(8)

Violet(7)

Brown(10)

Orange(9)

SUC

PSU

C P

AUXILIARY HEAT CT

BLOWER CT

PERFORMANCEOPTION

324

FLOW METER

Black(1 12)

Black/White(5)

TTHW HW

White

White

BlackBlack

OrangeOrange

HOT WATEROPTION

O

BLOWCURRE

TRANSDU(CT)

Red

Black

Circuit Breaker

Circuit Breaker

BlueBlue

BlueBlue

Pump Slave Input/Output

Home Automation

Smar t Gr id

Future Use

Dehumidification Output

Accessory 2 Output

Analog Output 0-10VDC

NOTE: 8

NOTE: 9

208-230/60/1

Pump

GGG

PumpPumpExt Pump

1/2 hp Total Ext Pump

1/2 hp Total

Gray(136)

Gray(135)

White(129)White(128)

T

SCT

P8

MOT

OR P6

RS48

5 P7

ZONE P9

ABC

STEP

PER

ANA

ACC2

DHDI

V

NO

CO

M

K6

NO

CO

M

K5

C R L1 L1 L2 L2P1

2P1

0P5

P11

CR(-)(+) CR(-)(+) CR(-)(+)

P4P2

K1K2

K3

HA2

HA1

SGI

LOO

PVS

DAT

AVS

PUM

PPU

MPSL

AVE

P3

V+CRTXRX +5

P14

LLT

P1LA

TFL

OW

LWT

EWT

43

FAN

43

CT1

21

AUX

21

StatusG

DISC

HP1

6

P17

P18

P15

(Aurora Expansion Board)AXB™

See Figure 1 for DHW wiring.

SW1

Modbus Add. IDFuture Use

12345

ONOFF

Future UseAcc 2 – Dip 4Acc 2 – Dip 5

CT2

SCT

P8

MOT

OR P6

RS48

5 P7

ZONE P9

ABC

STEP

PER

ANA

ACC2

DHDI

V

NO

CO

M

K6

NO

CO

M

K5

C R L1 L1 L2 L2P1

2P1

0P5

P11

CR(-)(+) CR(-)(+) CR(-)(+)

P4P2

K1K2

K3

HA2

HA1

SGI

LOO

PVS

DAT

AVS

PUM

PPU

MPSL

AVE

P3

V+CRTXRX +5

P14

LLT

P1LA

TFL

OW

LWT

EWT

43

FAN

43

CT1

21

AUX

21

StatusG

DISC

HP1

6

P17

P18

P15

(Aurora Expansion Board)AXB™

See Figure 1 for DHW wiring.

SW1

Modbus Add. IDFuture Use

12345

ONOFF

Future UseAcc 2 – Dip 4Acc 2 – Dip 5

CT2

CS

+5C

S+5

21

CC

INOU

T

Pink(140)Pink(139)

VS

GND24 VAC

0-10DC

12

3

R

C

ABC BOARD

AXB BOARD

MODULATING VALVE

12

Red

WhiteGreen

NO TE: 13

UPC ControllerUPC Controller

ZS Sensor

VARIABLE SPEED PUMP

LOW VOLTAGESEE 97P927-01

VARIABLE SPEED PUMP

LOW VOLTAGESEE 97P927-01

VARIABLE SPEED PUMP

HIGH VOLTAGESEE 97P927-01

VARIABLE SPEED PUMP

HIGH VOLTAGESEE 97P927-01

SW1

P5JW2

P9

LO

O/B

Y2WDH

P8 P7

RS485 NET RS485 NET

P6

RS485 EXP

P3

FutuL Outp

CC – DuaAcc Acc

RVFP2 – 15°FFP1 – 15°F

Com1LED5

Com2LED5

Test Mode

P1

ALMALGACC COMACC NOACC NC

RC

G

EH2CEH1CCOC R - +C R - +

StatusLED3

CoLE

CC2 CC F C R F FG CC CCGCC2HI

CC2LO

CC2G REVREVFP1 FP1 FP2 FP2 LPS LPSHPS

Aurora Base Control(ABC)

K1-RV Relay

K2-CC Relay

K3-CC2 Relay

K4-Fan RelayK5-Alarm Relay

K6-Acc Relay

CCGY1C

R

ESLS

P2EH1

GG GG

GGG

Y1

SW1

P5JW2

P9

LO

O/B

Y2WDH

P8 P7

RS485 NET RS485 NET

P6

RS485 EXP

P3

FutuL Outp

CC – DuaAcc Acc

RVFP2 – 15°FFP1 – 15°F

Com1LED5

Com2LED5

Test Mode

P1

ALMALGACC COMACC NOACC NC

RC

G

EH2CEH1CCOC R - +C R - +

StatusLED3

CoLE

CC2 CC F C R F FG CC CCGCC2HI

CC2LO

CC2G REVREVFP1 FP1 FP2 FP2 LPS LPSHPS

Aurora Base Control(ABC)

K1-RV Relay

K2-CC Relay

K3-CC2 Relay

K4-Fan RelayK5-Alarm Relay

K6-Acc Relay

CCGY1C

R

ESLS

P2EH1

G G

G

Y1

SW1

P5JW2

P9

LO

O/B

Y2WDH

P8 P7

RS485 NET RS485 NET

P6

RS485 EXP

P3

FutuL Outp

CC – DuaAcc Acc

RVFP2 – 15°FFP1 – 15°F

Com1LED5

Com2LED5

Test Mode

P1

ALMALGACC COMACC NOACC NC

RC

G

EH2CEH1CCOC R - +C R - +

StatusLED3

CoLE

CC2 CC F C R F FG CC CCGCC2HI

CC2LO

CC2G REVREVFP1 FP1 FP2 FP2 LPS LPSHPS

Aurora Base Control(ABC)

K1-RV Relay

K2-CC Relay

K3-CC2 Relay

K4-Fan RelayK5-Alarm Relay

K6-Acc Relay

CCGY1C

R

ESLS

P2EH1

G G

G

Y1

Perfect Speed Blower Motor

Grn

4 23 1

PWM

P13 Connects Here

P112 3 4 51

Not U

sed

COM

Feed

back

15 10163 815 10163 8

Perfect Speed Blower Motor

Grn

4 23 1

PWM

P13 Connects Here

P112 3 4 51

Not U

sed

COM

Feed

back

15 10163 8NOTE 14

Perfect Speed Blower Motor

Grn

4 23 1

PWM

P13 Connects Here

P112 3 4 51

Not U

sed

COM

Feed

back

15 10163 8NOTE 14

meme

H

))Black(1

24)

1

O

WRE

SDCT

FutFutFutFututputputputpF tFFF

DuaDuaDuaDuatttt

AccAccAccAccAccAccAccAcc

RRRR5555°°°°5555°°°°

CCCCLLLL

PS

Page 25: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.:

Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 25 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Wiring Schematics cont.

Aurora Variable Speed with UPC cont.

97P842-02A

NOTE 7NOTE 7

NOTE 6NOTE 6

Page 1Page 1

Transformer

24V

Transformer

24V

ECM BlowerMotor

P112 3 4 51

Green(10 7)

16 112 15 10

PWM

C1 C2R G

33

CFM

To P2 on Electric Heat Board

TT

HP

Black(125)

Black(124)

Blue(123)

Blue(122)

LP

Black(119)

Black(118)

FP2

Yll

(117)Vio let(111)

Blue(110)

Yellow(109)

Green/Yellow(108)

Black/White

Yellow

1C

21

C2

43

24

32

1C

24

32

1C

24

32

Black(1 13)

Brown(106)

Blue240V

ack

and L2 on VS Drive

12

L1L2

Black(1 14)

Black(1 12)

Orange(105)

BLOWERCURRENT

TRANSDUCER(CT)

NOCOM

K6 RelayConnects to L2 and NO on AXB Board

L2

NOCOM

K6 RelayConnects to L2 and NO on AXB Board

L2

Figure 1:Optional Internal

Hot Water Generation Pump Wiring Schematic

DHW Pump

Blue(137)

Blue(138)

Cabinet HW Switch

3

21

PurpleDHW Pump

Blue(137)

Blue(138)

Cabinet HW Switch

3

21

Purple

NOCOM

K6 RelayConnects to L2 and NO on AXB Board

L2

Figure 1:Optional Internal

Hot Water Generation Pump Wiring Schematic

DHW Pump

Blue(137)

Blue(138)

Cabinet HW Switch

3

21

Purple

Communicating Thermostat Dual Fuel Wiring DiagramUsing Field Installed Relay

24 VDC

R f rom Foss il Fue l Furnac e

To Foss il Fuel Furnac e W input

EH1

C

ABCBoard

Note 12 : Fi eld inst al led SPST dual fuel rela y (R equi re d for dual fuel inst all ati on)

5 – Low voltage wiring CLASS 2 .

NotesNotes

3 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is required.

1 - Switch blue and red wires for 208V operation. 2 - The b lk/wh and gray/wh wires are removed when A ux Heat is installed

4 – Variable speed pump low voltage harness provided with V ariab le Speed Flow Center.

6 - Wires provided fo r Auxiliary Heat low voltage control. Wires are secured a t blower.7 – When Auxilia ry Heat is field installed the harness will t hen be connected to the auxiliary heat un it. The auxilia ry heat un it will then power the blower. Refer to EAS/EAM/EAL Auxiliary Heat kit insta llation inst ructions. 8 – Brown blower power wire rou ted through Current Transducer two times.9 – Fie ld Connected : Refer to Installa tion Manual and Auxilia ry Heat Instructions fo r Curren t Transducer installa tion.10 – Communication cab le routed through Ferrite Toro id four times.11 – Compressor power cable routed through Ferrite Toroid th ree times.12 - Fie ld installed SPST relay required for dual fuel installation.

Notes

3 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is required.

1 - Switch blue and red wires for 208V operation. 2 - The b lk/wh and gray/wh wires are removed when A ux Heat is installed

4 – Variable speed pump low voltage harness provided with V ariab le Speed Flow Center.

6 - Wires provided fo r Auxiliary Heat low voltage control. Wires are secured a t blower.7 – When Auxilia ry Heat is field installed the harness will t hen be connected to the auxiliary heat un it. The auxilia ry heat un it will then power the blower. Refer to EAS/EAM/EAL Auxiliary Heat kit insta llation inst ructions. 8 – Brown blower power wire rou ted through Current Transducer two times.9 – Fie ld Connected : Refer to Installa tion Manual and Auxilia ry Heat Instructions fo r Curren t Transducer installa tion.10 – Communication cab le routed through Ferrite Toro id four times.11 – Compressor power cable routed through Ferrite Toroid th ree times.12 - Fie ld installed SPST relay required for dual fuel installation.13 - Wiring harness supplied with va lve.

23

P9

54

1

L2 L1 L2 L1

Green

P112 3 4 51

VioletBlue

BrownOrange

HE1 TS1TS1HE1 TS1

HE3 TS3TS3HE3 TS3

HE2 TS2TS2HE2 TS2

HE4 TS4TS4HE4 TS4

Connects to variable speed ECM motor only

60 AMP BRK1

60 AMP BRK2

GGGG

K1

K2

K3

K4

NO

NO

NO

NO

EA Series PCB

P141 2 3C

G

G

G

G

K5

NO

K6

NO

K7

NO

K8

NO

Gray

Yellow

GrayYellow

Black

Pink

Black

Pink

Pink

Pink

Gray

Black

Yellow

Gray

Black

Yellow

41 2 3C P2

COMCOM

COM COM

COM COM

COMCOM

Aux heat staging

FB1

FB2

FB3

FB4

P3 on Aurora ABC Board

P3EH2C EH1 CCO P3EH2C EH1 CCO

Light emitting diode - Green

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField l ine voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal

Thermal Limit Switch

Field wire lug

GroundHE -

PB -

Heater element

Power block

Legend

N.O., N.C.

G

L1

Breaker

1 2 3PTS

Electric Heat RelayK*

Fused BackupFB

K*

Fused BackupFB

Light emitting diode - Green

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField l ine voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal

Thermal Limit Switch

Field wire lug

GroundHE -

PB -

Heater element

Power block

Legend

N.O., N.C.

G

L1

Breaker

1 2 3PTS

Electric Heat RelayK*

Fused BackupFB

2 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is requ ired.

1 - Use copper conductors.

3 – Jumpers wires are Factory Installed, and arerequired fo r auxiliary heat operation. 4 – Low voltage wiring CLASS 2 .

2 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is requ ired.

1 - Use copper conductors.

3 – Jumpers wires are Factory Installed, and arerequired fo r auxiliary heat operation. 4 – Low voltage wiring CLASS 2 .

NOTE 3

With optional EA Series 20kW Auxiliary Electric Heat Shown

23

P9

54

1

L2 L1 L2 L1

Green

P112 3 4 51

VioletBlue

BrownOrange

HE1 TS1

HE3 TS3

HE2 TS2

HE4 TS4

Connects to variable speed ECM motor only

60 AMP BRK1

60 AMP BRK2

GG

K1

K2

K3

K4

NO

NO

NO

NO

EA Series PCB

P141 2 3C

G

G

G

G

K5

NO

K6

NO

K7

NO

K8

NO

Gray

Yellow

GrayYellow

Black

Pink

Black

Pink

Pink

Pink

Gray

Black

Yellow

Gray

Black

Yellow

41 2 3C P2

COMCOM

COM COM

COM COM

COMCOM

Aux heat staging

FB1

FB2

FB3

FB4

P3 on Aurora ABC Board

P3EH2C EH1 CCO

Light emitting diode - Green

Polarized connector

Factory Low voltage wiringFactory Line voltage wiringField low voltage wiringField l ine voltage wiringOptional blockDC Voltage PCB tracesInternal junctionQuick connect terminal

Thermal Limit Switch

Field wire lug

GroundHE -

PB -

Heater element

Power block

Legend

N.O., N.C.

G

L1

Breaker

1 2 3PTS

Electric Heat RelayK*

Fused BackupFB

2 - Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is requ ired.

1 - Use copper conductors.

3 – Jumpers wires are Factory Installed, and arerequired fo r auxiliary heat operation. 4 – Low voltage wiring CLASS 2 .

NOTE 3

With optional EA Series 20kW Auxiliary Electric Heat Shown

P12

CFM

P13

P4

SW2

On

Future Use L Output Type

CC – Dual/SingleAcc – Dip 5Acc – Dip 4

RV – B/OFP2 – 15°F/30°FFP1 – 15°F/30°F

F1-3A

C

PWM

12345678

Off

Faul tLED1

R

StatusLED3

ConfigLED2

1 FP2 FP2 LPS LPSHPSHPS

F

R

C

CCGY1

YY

GGG

CFM

P13

P4

SW2

On

Future Use L Output Type

CC – Dual/SingleAcc – Dip 5Acc – Dip 4

RV – B/OFP2 – 15°F/30°FFP1 – 15°F/30°F

F1-3A

C

PWM

12345678

Off

Faul tLED1

R

StatusLED3

ConfigLED2

1 FP2 FP2 LPS LPSHPSHPS

F

R

C

CCGY1

Y

G

CFM

P13

P4

SW2

On

Future Use L Output Type

CC – Dual/SingleAcc – Dip 5Acc – Dip 4

RV – B/OFP2 – 15°F/30°FFP1 – 15°F/30°F

F1-3A

C

PWM

12345678

Off

Faul tLED1

R

StatusLED3

ConfigLED2

1 FP2 FP2 LPS LPSHPSHPS

F

R

C

CCGY1

Y

G

14 - On units with the NIDEC ECM motor the P13 harness connects to the jumper harness on the motor.

ce

)Bl

k(119)

2 ove

14

1 1

2 L

CCCC

Page 26: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.:

Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 26 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Wiring Schematics cont.

Aurora UPC To ABC - P8

Yellow

Brown

Green

Blue

White

Black

Orange

Red

Devices Must Be Wired in Daisy Chain Configuration

GNDRNET+RNET-

+12V

GNDRNET+RNET-

+12V

GNDRNET+RNET-

+12V

ZS Sensor 1Addr: 0

1 2 3 4 5 6 7 8

ZS Sensor 2Addr: 1

ZS Sensor 3Addr: 2

BACnet or N2 Network

Connections

2W

4W

RNET LOCAL ACCESS

POWER

GND

24 VAC

FORM AT BATT

TEN’S

ONE’S

TXLED1

RXLED2

TXLED6

RXLED7

P OWERLED3

RUNLED4

ERRLED5

0

5

23

87

1

4

9

6

0

5

23

87

1

4

9

6

LON ADAPTER

PORT

NET+

NET-

COM

NET+

NET-

N/C

N/C

Signal

GNDRNET+RNET-+12V

GNDLN+LN-+12

/S

ON

12

34

56

78

Optional LON Add-On Module

A

N/C

N/C

Signal

Service

ECH

ELON

12

Net

LED1

LED2

LED3

LED4

Tx

Rx

LON OC

MAC Address Setting

Communication Options

NET

+

NET

-

CO

M

NET

+

NET

-

CO

M

12

1 2

LON Network Connections

Devices Must Be Wired in Daisy Chain

Configuration

Page 1

DIP Switch Value

1248

ON

1234

ZS Sensor Information

Each ZS sensor must have a unique address, but the addresses do not need to be sequential. Use the DIP switches on the back of the ZS sensor to set an address from 0 to 4. (0 is the factory default.) Each DIP switch has the value shown in the figure to the left. Turn on as many DIP switches as you need so that their total value equals the address.

Zone Sensors can be wired in daisy chain as show or in a star or hybrid configuration. Maximum of 5 sensors per UPC. Maximum allowable load 210mA. See the UPC install manual for possible sensor combinations.

LegendFactory Low Voltage WiringField Low Voltage Wiring

12345678 RJ45 Connector

Notes

NOTE 1

1. Use DIP Switches 5 – 8 to change communication protocol and DIP switches 1 – 2 to change BACnet baud rate

Page 27: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 27 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

General Furnish and install WaterFurnace Water Source Heat

Pumps, as indicated on the plans. Equipment shall be

completely assembled, piped and internally wired.

Capacities and characteristics as listed in the schedule and

the specifications that follow. The reverse cycle heating/

cooling units shall be either suspended type with horizontal

air inlet and discharge or floor mounted type with

horizontal air inlet and vertical upflow, downflow, or rear

air discharge. Units shall be AHRI/ISO 13256-1 certified and

listed by a nationally recognized safety-testing laboratory

or agency, such as ETL Testing Laboratory. Each unit shall

be computer run-tested at the factory with conditioned

water and operation verified to catalog data. Each unit shall

be mounted on a pallet and shipped in a corrugated box

or stretch-wrapped. The units shall be designed to operate

with entering liquid temperature between 20°F and 120°F

[-6.7°C and 48.9°C].

Casing and Cabinet The cabinet shall be fabricated from heavy-gauge

galvanized steel and finished with corrosion-resistant

powder coating. This corrosion protection system shall

meet the stringent 1000 hour salt spray test per ASTM

B117. The interior shall be insulated with 1/2-inch thick,

multi-density, cleanable aluminum foil coated glass fiber

with edges sealed or tucked under flanges to prevent

the introduction of glass fibers into the discharge air.

Standard cabinet panel insulation must meet NFPA 90A

requirements, air erosion and mold growth limits of UL-

181, stringent fungal resistance test per ASTM-C1071 and

ASTM G21, and shall meet zero level bacteria growth per

ASTM G22. Unit insulation must meet these stringent

requirements or unit(s) will not be accepted.

One (horizontal) to two (vertical) blower and three

compressor compartment access panels shall be ‘lift-out’

removable with supply and return ductwork in place. The

front access panel shall be lift-out to provide easy access

to the electrical/compressor section. The control box

shall be hinged and removable to allow easy access to the

compressor. The internal component layout shall provide for

service access from the front side for restricted installations.

A duct collar shall be provided on the supply air opening.

Standard size 2 in. [5.1 cm] MERV 11 pleated filters shall

be provided with each unit. Vertical and horizontal units

shall have a return air filter rack/duct collar which is field

convertible from 2 in. [5.1 cm] to 1 in. [2.5 cm]. The upflow

vertical units shall have a removable insulated divider panel

between the air handling section and the compressor

section to minimize the transmission of compressor noise

and to permit operational service testing without air

bypass. Vertical units shall be supplied with left or right

horizontal air inlet and top, bottom, or rear vertical air

discharge. Horizontal units shall be supplied with left or

right air inlet and side or end air discharge.

The compressor shall be double isolation mounted using

selected durometer grommets to provide vibration free

compressor mounting.

The drain pan shall be of plastic construction to inhibit

corrosion and bacterial growth. Drain outlet shall be

located on pan as to allow complete and unobstructed

drainage of condensate. The unit as standard will be

supplied with solid-state electronic condensate overflow

protection. Mechanical float switches WILL NOT be

accepted. Vertical units shall be furnished with a PVC

slip condensate drain connection and an internal factory

installed condensate trap.

Refrigerant Circuit All units shall contain a sealed refrigerant circuit including

a hermetic motor-compressor, discharge line muffler,

bidirectional electronic expansion valve, finned tube air-

to-refrigerant heat exchanger, reversing valve, coaxial tube

water-to-refrigerant heat exchanger, optional hot water

generator coil, and service ports. Compressors shall be

high-efficiency variable speed scroll type designed for heat

pump duty and mounted on double vibration isolators.

Compressor motors shall be permanent magnet type. The

all-aluminum PinnaCoil shall be sized for low-face velocity

and constructed of aluminum fins bonded to aluminum

tubes in a staggered pattern not less than three rows

deep for enhanced performance. All models shall include

discharge mufflers to help quiet compressor discharge gas

pulsations.

Refrigerant to air heat exchangers shall utilize tube

construction rated to withstand 600 psig (4135 kPa)

refrigerant working pressure. Refrigerant to water heat

exchangers shall be of copper (cupronickel optional) inner

water tube and steel refrigerant outer tube design, rated to

withstand 600 psig (4135 kPa) working refrigerant pressure

and 450 psig (3101 kPa) working water pressure. An

electronic expansion valve shall provide proper superheat

over the entire liquid temperature range with minimal

“hunting.” The valve shall operate bidirectionally without

the use of check valves.

All units shall have the source coaxial tube refrigerant-to

water heat exchanger and the optional hot water generator

coil coated with ThermaShield insulation. Refrigerant

suction lines shall be insulated to prevent condensation at

low liquid temperatures.

Engineering Guide Specifi cations

Page 28: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 28 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Blower Motor and Assembly The blower shall be a direct drive centrifugal type with a

dynamically balanced wheel. The housing and wheel shall

be designed for quiet low outlet velocity operation. The

blower housing shall be removable from the unit without

disconnecting the supply air ductwork for servicing of the

blower motor. The blower motor shall be a variable-speed

ECM type. The ECM blower motor shall be soft starting,

shall maintain constant cfm over its operating static range,

and shall provide 12 cfm settings. The blower motor shall

be isolated from the housing by rubber grommets. The

motor shall be permanently lubricated, have thermostatic

overload protection and be long-life ball bearing type.

ElectricalA control box shall be located within the unit compressor

compartment and shall contain a 75VA transformer, 24 Volt

activated, 2 pole compressor contactor, circuit breakers for

protecting loop pumps and compressor drive, removable

terminal block for thermostat wiring, variable speed

compressor drive and solid-state controller for complete

unit operation. Electromechanical operation WILL NOT

be accepted. Units shall be name-plated for use with time

delay fuses or HACR circuit breakers. Unit controls shall

be communicating type and provide heating or cooling

as required by the remote thermostat/sensor. An Aurora

Advanced VS Control, a microprocessor based controller,

interfaces with a digital communicating thermostat to monitor

and control unit operation shall be provided. The control shall

provide operational sequencing, blower speed control, blower

failure, high and low pressure switch monitoring, freeze

detection, hot water limit thermistor sensing, condensate

overflow sensing, auxiliary heat staging, lockout mode control,

hot water and loop pump control, LED status and fault

indicators, fault memory, field selectable options, compressor

envelope management, energy consumption measurement,

and accessory output. The fault signals shall be plain English

text and displayed on the thermostat.

The Aurora Advanced VS Control shall also feature an On

Peak input signal for utility controlled demand programs,

intelligent hot water generation with user adjustable

temperature limit, loop pump linking for multiple units

driving a common flow center and up to two optional home

automation inputs to drive dedicated alarms for sump pump,

security system, and smoke/CO2 or dirty air filter sensors.

As standard, the energy and refrigerant monitoring kits will

provide real time data including total power consumption,

refrigerant superheat and subcooling. Optional performance

monitoring kit to provide real time data including, entering

and leaving water temperature, flow rate and heat of

extraction/rejection capacity data. The capability for

communicating to advanced zoning packages with up to

six zones shall also be provided with complete fault and

information display on the zoning MasterStat.

A detachable terminal block with screw terminals will be provided for field control wiring. All units shall have knockouts for entrance of low and line voltage wiring. The blower motor and control box shall be harness plug wired for easy removal.

An optional Aurora Interface Diagnostic (AID) Tool shall communicate with the Aurora control allowing quick and easy access to setup, monitoring, and troubleshooting of any Aurora control. The device shall include the features of ECM airflow setup, VS pump and modulating water valve setup, fault description and history, manual operation capability, sensor readings, timings, and other diagnostic tools.

Option: An Aurora Unitary Protocol Converter (UPC) shall be included that communicates directly with the Aurora Heat Pump Control and allows access/control of a variety of internal Aurora heat pump operations such as sensors, relay operation, faults and other information. In turn, the UPC shall convert the internal Aurora Modbus protocol to BACnet MS/TP protocol for communication over a HAS system. Additional individual unit configuration items such as ECM fan speeds or freeze protection settings shall be directly available over the HAS without the need for access

to the actual heat pump.

Piping Supply and return water connections shall be 1 in. [25.4 mm]

FPT brass swivel fittings, which provide a union and eliminate

the need for pipe wrenches and sealants when making field

connections. The optional hot water generator shall have

sweat type connections. All source water piping shall be

insulated to prevent condensation at low liquid temperatures.

On the vertical units, the condensate connection shall be a

3/4 in. [19.1 mm] PVC socket with internally-trapped hose

that can be routed to front or side locations.

Hanger Kit(field-installed horizontal units only)

The hanger kit shall consist of galvanized steel brackets,

bolts, lock washers, and isolators and shall be designed to

fasten to the unit bottom panel for suspension from 3/8-

inch threaded rods. All unit size shall include six brackets

hanging brackets.

Options and Accessories Cupronickel Heat Exchanger

An optional cupronickel water-to-refrigerant heat

exchanger shall be provided.

Engineering Guide Specifi cations cont.

Page 29: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 29 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Hot Water Generator

An optional ThermaShield coated heat reclaiming hot water

generator coil of vented double-wall copper construction

suitable for potable water shall be provided. The coil and

hot water circulating pump shall be factory mounted inside

the unit with integral electronic high limit temperature

monitoring and external on/off switch. Hot water set point

is selectable through the AID Tool.

AlpinePure 411–Rack 4 in. Pleated Filter Accessory A 4 in. [102 mm] thick MERV 11 filter and filter rack shall be

provided in lieu of the standard filter and rack.

Thermostat (field-installed)

A communicating auto-changeover electronic digital

thermostat shall be provided. The thermostat shall offer

variable speed heating and cooling staging with precise

temperature control. An OFF-HEAT-AUTO-COOL-EMERG

system switch, OFF-AUTO-INTERMITTENT blower switch,

and indicating display shall be provided. The thermostat

shall display in °F or °C. The thermostat shall provide real

time energy consumption data of the unit.

Color Touchscreen Thermostat (field-installed)

A color touchscreen communicating auto-changeover

electronic digital thermostat shall be provided. The

thermostat shall offer variable speed heating and cooling

staging with precise temperature control. An OFF-

HEAT-AUTO-COOL-EMERG system switch, OFF-AUTO-

INTERMITTENT blower switch, and indicating display shall

be provided. The thermostat shall display in °F or °C. The

thermostat shall provide real time and historical energy

consumption data of the unit.

Electronic Air Cleaner (field-installed)

A 1 in. [25 mm] electronic air cleaner, cleanable 97%

efficiency at 0.3 microns and larger, shall be provided in

lieu of the standard throwaway filter. The initial pressure

drop across the filter shall not exceed 0.2 in. w.g. at 300

fpm force velocity.

Electrostatic Air Cleaner (field-installed) A 1 in. [25 mm] electrostatic air cleaner, cleanable 90%

efficiency, shall be provided in lieu of the standard

throwaway filter. The initial pressure drop across the filter

shall not exceed 0.15 in. w.g. at 300 fpm force velocity.

AlpinePure MERV 13 Filter (field-installed)

A 2 in. [50 mm] thick MERV 13 filter shall be provided in

lieu of the standard filter and fits the factory filter rack.

The filter maintains MERV 13 rating in full ASHRAE 52.2

independent testing as required for LEED® certification.

Helps fulfill a full credit under the LEED rating system.

AlpinePure Drain Pan Treatment (field-installed)

Provides dependable, sustained time-release protection

from slime build-up and foul smelling odors in the drain

pan. Also adds a light, pleasant scent to the air.

Earth Loop Flow Center (field-installed)

A self-contained module shall provide all liquid flow, fill

and connection requirements for ground source closed

loop systems up to 20 gpm. The pumps shall be wired to

a power block located in the nearest unit. The heat pump

units shall contain low voltage pump linking control so that

two units may share one flow center.

Auxiliary Heater (field-installed)

An electric resistance heater shall provide supplemental

and/or emergency heating capability. Vertical units shall

have the control panel and resistance heater coil assembly

mounted internally. For horizontal units, the control panel

shall be mounted internally while the resistance heater

coil assembly shall be mounted externally. A low voltage

plug shall be provided in each unit for quick auxiliary heat

connection. The heater shall operate in sequenced stages

as controlled by the unit’s microprocessor. The heater shall

feed line voltage power to the unit blower and transformer

to provide emergency heat capability in the event of an

open compressor circuit breaker.

Engineering Guide Specifi cations cont.

Page 30: SD2700ANA - WaterFurnace

WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.

Contractor: P.O.: Engineer:

Project Name: Unit Tag:

SD2700ANA 02/21 30 Page _____ of _____

7 Series 700A113-5 Ton 60Hz

Pages: Description: Date: By:

Misc Updated with Aluminum Air Coils 04 Dec 2020 MA

16-19 Updated wiring schematics (UPMXL) 12 Sept 2019 MA

24,25 Updated Wiring Schematics, Engineering Specifications to include UPC option 21 Nov 2017 MA

All Misc. Updates 9 Dec 2016 MA

All Misc. Updates, Performance Data Update 12 Aug 2016 MA

All Electric heating updates, multiple areas effected 07 Jan 2015 MA

20 - 23 Updated Wiring Diagrams 31 May 2013 DS

27 Added Revision Guide 31 May 2013 DS

Revision Guide