PROJECT NOTES
1. IN CASE OF A DIMENSIONAL QUESTION OR DISCREPANCY. SUBMIT A REQUEST FOR INFORMATION (RFI) TO THE CONSTRUCTION COORDINATOR.
2. ONE HOUR FIRE RATED TEMPORARY CONSTRUCTION PARTITIONS SHALL BE UTILIZED WHEN CONSTRUCTION DURATION EXCEEDS 48 HOURS. PLASTIC BARRIERS ARE ACCEPTABLE WHEN CONSTRUCTION DURATION IS LESS THAN 48 HOURS. STICKY WALK-OFF DUST MATS SHALL BE PROVIDED AT ALL ENTRANCES TO CONSTRUCTION SITES.
3. SUBMIT ALL CHANGE ORDERS TO PROJECT MANAGER AND SECURE PROJECT MANAGER'S APPROVAL PRIOR TO THE COMMENCEMENT OF WORK.
PROJECT SEQUENCING
THE PROJECT IS INTENDED TO BE COMPLETED IN ONE PHASE.
SCOPE OF WORK
PROJECT DIRECTORY
DESIGN MANAGER:
KIDEST ALBAARI, PMPPH: (313) 577-3038EMAIL:[email protected]
FTCH ARCHITECT/ ENGINEERS:
THIS PROJECT RENOVATES ROOM 328 AND 330, ON THE THIRD FLOOR OF THE WAYNE STATE UNIVERSITY'S RICHARD COHN BUILDING IN DETROIT, MICHIGAN. SCOPE INCLUDES ARCHITECTURAL, FIRE ALARM, ELECTRICAL, AND MECHANICAL UPGRADES AND RECONFIGURATION FOR NEW STUDENT COMMONS SPACE THAT WILL TAKE OVER BOTH ROOMS 328 AND 330. THE SPACE WILL RECEIVE NEW FINISHES AND FURNITURE
THIS PROJECT WILL BE ISSUED UNDER TWO SEPARATE RPF'S AND IN TURN TWO SEPERATE CONTRACTS.1. GENERAL CONTRACTING CONTRACT2. FURNITURE, FURNISHINGS, AND EQUIPMENT CONTRACT FOR THE
PROCURMENT AND INSTALLATION OF THE FURNITURE PACKAGE SPECIFIED IN SECTION 125000
THE RESPONSIBILITY OF EACH CONTRACT; OWNER, GENERAL CONTRACTOR, AND FURNITURE VENDOR IS DEFINED UNDER SECTION 011100
JULIET JAKOBOWSKI MAES, AIA, LEED AP, PROJECT DIRECTOR
PH: (248) 324-1229
EMAIL: [email protected]
VINCENT J. MATTINA III, AIA, CDT, ARCHITECT / PROJECT MANAGER
PH: (248) 826-7683
EMAIL: [email protected]
CARLA M. TAMBOER, INTERIOR DESIGNER
PH: (616) 464-3894
EMAIL: [email protected]
JAMES A. MILOCH, PE, LEED AP, ELECTRICAL ENGINEER
PH: (248) 324-2127
EMAIL: [email protected]
RENEE M. ZACCAGNI, PE, LEED GA, MECHANICAL ENGINEER
PH: (248) 324-2110
EMAIL: [email protected]
c o n s t r u c t o r s
a r c h i t e c t s
s c i e n t i s t s
e n g i n e e r s
Hard copy is intended to be24"x36" when plotted. Scale(s)
indicated and graphic quality maynot be accurate for any other size.
PROJECT NO.
Drawn By
Designer
Reviewer
Manager
f i s h b e c k, t h o m p s o n, c a r r & h u b e r, i n c.
PLO
T IN
FO
:
© C o p y r i g h t 2 0 1 9A l l R i g h t s R e s e r v e d
www.ftch.com
Engineers Scientists Architects Constructors
Fishbeck, Thompson, Carr & Huber, Inc.
(800) 456-3824
ACM ALUMINUM COMPOSITE MATERIALAFF ABOVE FINISHED FLOORAHU AIR HANDLING UNITAL ALUMINUMALT ALTERNATEBF BARRIER FREEBRG BEARINGCJ CONTROL JOINTCL CENTERLINECW CURTAINWALLCLG CEILINGCMU CONCRETE MASONRY UNITCO CLEANOUTCONC CONCRETECONST CONSTRUCTIONCONT CONTINUOUSDIA DIAMETERDN DOWNDS DOWNSPOUT
EF EXHAUST FANEL ELEVATIONEJ EXPANSION JOINTEQ EQUALEWC ELECTRIC WATER COOLERFD FLOOR DRAINFRT FIRE RETARDANT TREATEDFT FOOT/FEETGA GUAGE/GAGEGALV GALVANIZEDGC GENERAL CONTRACTORHB HOSE BIBBHP HIGH POINTHORIZ HORIZONTALHVAC HEATING VENTILATING AIR
CONDITIONINGID INSIDE DIAMETERIE INVERT ELEVATIONIMP INSULATED METAL PANEL
IN INCH/INCHESINSUL INSULATIONLAV LAVATORYLED LIGHT EMITTING DIODELLH LONG LEG HORIZONTALLLV LONG LEG VERTICALLP LOW POINTMFR MANUFACTURERMAX MAXIMUMMEZZ MEZZANINEMIN MINIMUMMO MASONRY OPENINGMTD MOUNTEDN/A NOT APPLICABLENC NOISE CRITERIANIC NOT IN CONTRACTNO NUMBER
NRC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALEOC ON CENTEROD OUTSIDE DIAMETEROH OVERHEADOPP OPPOSITEORD OVERFLOW ROOF DRAINOS OUTSIDEPERP PERPENDICULARPL PLATEPSF POUNDS PER SQUARE FOOTPSI POUNDS PER SQUARE INCHPVC POLYVINYL CHLORIDER RADIUSREQD REQUIREDRD ROOF DRAINSCH SCHEDULESF SQUARE FOOT
SGT STRUCTURAL GLAZED TILESIM SIMILARSP SPACE/SPACINGSQ SQUARESS STAINLESS STEELSTD STANDARDTAN TANGENTTYP TYPICALUL UNDERWRITER'S LABORATORYUNO UNLESS NOTED OTHERWISEVERT VERTICALVTR VENT THROUGH ROOFW/ WITHWC WATER CLOSETWH WATER HEATERW/O WITHOUTWP WEATHERPROOFWT WEIGHT
GENERAL ABBREVIATIONS
SEAL
PROJECT INFORMATION
R E V I S I O N S
Wa
yn
e S
tate
Un
ive
rsit
y5
55
7 C
ass A
ve, D
etr
oit,
MI
48
20
2
Co
hn
Bu
ildin
g S
tud
en
t C
om
mo
ns
Issued for Permits and Bids - October 31, 2019
190812
5557 Cass Ave, Detroit, MI 48202
Cohn Building Student Commons
Wayne State University
VJM
WSU Project Number: 048-291367
39500 MacKenzie Drive, Suite 100, Novi, Michigan 48377
www.ftch.com
WS
U P
RO
JE
CT
NU
MB
ER
: 048-2
91367
10/31/2019 Permits and Bids
C:\W
ork
\Re
vit\2
019
_A
_19
081
2_vjm
attin
a.r
vt
10
/31/2
01
9 9
:59
:50
AM
G101.1
COVER SHEET
DRAWING INDEX
G101.1 COVER SHEETLS101 LIFE SAFETY PLANA701 FLOOR FINISH PLANSE201 THIRD FLOOR POWER AND SYSTEMS PLAN
60' -
6"
32' - 6"
19' -
0"
7' -0"
11' -
0"
25' - 6"
19' -
0"
6' -0"
6' -0"
1
ACDFH
2
3
4
5
6
7
8
9
10
11
12
13
14
15
B
1218 SF
STUDENT
COMMONS
80
FIRE SHUTTER
G
FIRE SHUTTER
1HR
ON GRADE
LOCATION OF DUMPSTER
EXISTING TRASH CORRAL
1HR
2HR
1HR
1HR
1HR
1HR
1HR
OCCUPANCY
ITEM CODE SECTION
REMARKSUL NO.
(HOURS)
RATINGITEM
FIRE RESISTANCE RATINGS OF STRUCTURAL ELEMENTS
TYPE OF CONSTRUCTION
BUILDING USE GROUP
CODES
(SEC. 1023.2)EXISTING1STAIR ENCLOSURES
(SEC. 713.4)EXISTING2SHAFT ENCLOSURES
(TABLE 601)EXISTING0INT.
(TABLE 601)EXISTING1INT.
ROOF CONSTRUCTION 1 EXISTING (TABLE 601)
(INCL. AMENDMENTS)
(TABLE 601)
(TABLE 601)
(TABLE 601)
(TABLE 601)
EXISTING
EXISTING
EXISTING
EXISTING
1
0
1
1
FLOOR CONSTRUCTION
NONBEARING WALLS - EXT.
BEARING WALLS - EXT.
STRUCTURAL FRAME
CONSTRUCTION TYPE: II-A (ASSUMED) NON-SPRINKLERED (MBC-SEC: 602) TYPE II (III) (ASSUMED) NON-SPRINKLERED (NFPA: 7.2.1.1)
BUILDING USE (MBC-SEC: 304)
MIXED USE NON-SEPARATED: B - BUSINESS / A-3 - ASSEMBLY
2012 NFPA 101 LIFE SAFETY CODE2015 MICHIGAN REHABILITATION CODE (AS AMENDED) - Chapters 7 & 82015 MICHIGAN MECHANICAL CODE (AS AMENDED)2015 MICHIGAN PLUMBING CODE (AS AMENDED)2017 NATIONAL ELECTRIC CODE (NEC) (AS AMENDED - MICHIGAN AMENDMENTS PART 8 RULES)2015 MICHIGAN ENERGY CODE
INTERNATIONAL ENERGY CONSERVATION CODE - 2009, SECTION 501.1ANSI/ASHRAE/IESNA STANDARD 90.1-2007 (AS AMENDED)
2015 INTERNATIONAL FIRE CODEBARRIER FREE REQUIREMENTS:
AMERICANS WITH DISABILITIES ACT (ADA)MBC-2015, CHAPTER 11ICC A117.1-2009, EXCEPT SECTIONS 611 & 707
EGRESS COMPONENTS WITHIN THE WORK AREA (TABLE 1005.3)
OCCUPANCY 80
AREA OF RENOVATION: 80 PEOPLE x 0.2"/PERSON = 16 INCHES
PROVIDED: 2 DOORS @ 33 INCHES CLEAR = 66 INCHES
FIRST THRU THIRD FLOOR: 690 PEOPLE x 0.3"/PERSON = 207 INCHES (44 MIN.)
PROVIDED: 2 STAIR @82 INCHES CLEAR = 164 INCHES
STAIRWAYS 0.3" OTHER COMPONENTS 0.2"
1 STAIR @44 INCHES CLEAR = 44 INCHES
THE DRAWINGS HAVE BEEN PREPARED IN ACCORDANCE WITH THE FOLLOWING
CODES, NOTIFY THE ARCHITECT OF ANY CONFLICTS
CLASSIFICATION OF WORKCLASSIFICATION TYPE (MRC-CHAPTER 5)
LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT.
OCCUPANT LOAD:
2012 NFPA 101 LIFE SAFETY CODE, TABLE 7.3.1.22015 MICHIGAN BUILDING CODE, TABLE 1004.1.2
ASSEMBLY UNCONCENTRATED (TABLES AND CHAIRS)1 / 15 NET (IN AREA OF RENOVATION)
CURRENT BUILDING OCCUPANCY (ASSUMED): GROUND FLOOR: 208 OCCFIRST FLOOR: 209 OCCSECOND FLOOR: 209 OCCTHIRD FLOOR: 209 OCCTOTAL: 835 OCC
OCCUPANTS ADDED BY RENOVATION: GROUND FLOOR: 0 OCCFIRST FLOOR: 0 OCCSECOND FLOOR: 0 OCCTHIRD FLOOR: 63 OCCTOTAL: 63 OCC
PROPOSED BUILDING OCCUPANCY INCLUDING REOVATION:GROUND FLOOR: 208 OCCFIRST FLOOR: 209 OCCSECOND FLOOR: 209 OCCTHIRD FLOOR: 272 OCCTOTAL: 898 OCC
THE PROPOSED BUILDING OCCUPANCY HAS INCREASED BY 7.5%
PLUMBING FIXTURE REQUIREMENTS:
PER THE MICHIGAN REHABILITATION CODE FOR EXISTING BUILDINGS, SECTION 810 MINIMUM FIXTURES. WHERE THE OCCUPANT LOAD OF THE STORY IS INCREASED BY MORE THAN 20 PERCENT, PLUMBING FIXTURES FOR THE STORY SHALL BE PROVIDED IN QUANTITIES SPECIFIED IN THE INTERNATIONAL PLUMBING CODE BASED ON INCREASED OCCUPANT LOAD.
PROJECT COMPLIES: NO MODIFICATIONS TO THE PLUMBING FIXTURE COUNT IS REQUIRED.
MEANS OF EGRESS IN WORK AREAS:
A MINIMUM OF TWO MEANS OF EGRESS ARE PROVIDED FROM ALL RENOVATION AREAS.
COMMON PATH OF TRAVEL: 75' WITHOUT SPRINKLERS (TABLE 1006.2.1)PROJECT COMPLIES (MBC) (NFPA)
EXIT ACCESS TRAVEL DISTANCE: 200' WITHOUT SPRINKLERS (TABLE 1017.2)PROJECT COMPLIES
(NFPA 8.3.3.11)U4191CORRIDOR WALLS IN AREA OF RENOVATION
LIFE SAFTEY KEY
BUILDING CODE INFORMATION
TOTAL: 208 INCHES - PROJECT COMPLIES
THIRD FLOOR: 272 PEOPLE x 0.2"/PERSON = 54.4 INCHES
PROVIDED: 10 DOORS @ 33 INCHES CLEAR = 330 INCHES
c o n s t r u c t o r s
a r c h i t e c t s
s c i e n t i s t s
e n g i n e e r s
Hard copy is intended to be24"x36" when plotted. Scale(s)
indicated and graphic quality maynot be accurate for any other size.
PROJECT NO.
Drawn By
Designer
Reviewer
Manager
f i s h b e c k, t h o m p s o n, c a r r & h u b e r, i n c.
PLO
T IN
FO
:
© C o p y r i g h t 2 0 1 9A l l R i g h t s R e s e r v e d
www.ftch.com
R E V I S I O N S
Wa
yn
e S
tate
Un
ive
rsit
y5
55
7 C
ass A
ve, D
etr
oit,
MI
48
20
2
Co
hn
Bu
ildin
g S
tud
en
t C
om
mo
ns
190812
VJM
KEY PLAN
NORTH
WS
U P
RO
JE
CT
NU
MB
ER
: 048-2
91367
10/31/2019 Permits and Bids
C:\W
ork
\Revit\2
019
_A
_1
90
812
_ja
pym
an.r
vt
10
/31/2
01
9 8
:54
:21
AM
LS101
LIFE SAFETY PLANS
YF/CT
WTB
JP
NORTH
SCALE: 1/16" = 1'-0"
THIRD FLOOR LIFE SAFETY PLAN
#
33' - 3"
1-HOUR WALL
2-HOUR WALL
OCCUPANT COUNT
TRAVEL DISTANCE
LVT2
LVT1
PLANKDIRECTION
PLANKDIRECTION
LVT2
PLANKDIRECTION
LVT1
PLANKDIRECTION
LVT1
LVT1
VWC1
7'-10"
P2
P1
P1
C2
C2
C3C3
C1
C3
C3
C3C3
C4 C4
C4
C4
C5
C5
C5
C5
C5
C5
C5
C5
C5
C5
C5
C5
C5
C6
C6 C6
C6 C6
C6 C6
C6
C6
C6 C6
C6
C7
C7
C7
C7
T1
T2
T2
T3
T3 T3
T4
T5
2'-0"
11 3/4"
ALIGN
7'-10"
R 2
' - 5
"
R 5
' - 0
"
c o n s t r u c t o r s
a r c h i t e c t s
s c i e n t i s t s
e n g i n e e r s
Hard copy is intended to be24"x36" when plotted. Scale(s)
indicated and graphic quality maynot be accurate for any other size.
PROJECT NO.
Drawn By
Designer
Reviewer
Manager
f i s h b e c k, t h o m p s o n, c a r r & h u b e r, i n c.
PLO
T IN
FO
:
© C o p y r i g h t 2 0 1 9A l l R i g h t s R e s e r v e d
www.ftch.com
R E V I S I O N S
Wa
yn
e S
tate
Un
ive
rsit
y5
55
7 C
ass A
ve, D
etr
oit,
MI
48
20
2
Co
hn
Bu
ildin
g S
tud
en
t C
om
mo
ns
190812
VJM
KEY PLAN
NORTH
WS
U P
RO
JE
CT
NU
MB
ER
: 048-2
91367
10/31/2019 Permits and Bids
C:\W
ork
\Revit\2
019
_A
_1
90
812
_ja
pym
an.r
vt
10
/31/2
01
9 8
:54
:10
AM
A701
FLOOR FINISH PLANS
YF/CT
WTB
CT
NORTH
SCALE: 1/4" = 1'-0"
THIRD FLOOR FINISH PLAN
• ALL WALLS TO BE FACED WITH PLASTIC LAMINATE (PL1) UNLESS NOTED OTHERWISE.
NOTES
AV
A
TV
AV
AV
K
W
W
KK
K
USB
9"
USB9"
9"USB
1
USB9"
USB
9"
2
2
2
2
2
USB
USB 9"
USB
USB
USB
9"
9"
2
2
2
USB
USB
USB
USB
USB
USB
USB
USB
48"
48"
48"
48"
48"
45"
45"USB
46"
46"
46"
46"
30"
30"
30"30"
DIGITAL BULLETINBOARD. COORDINATE ALL REQUIREMENTS WITHTHE WSU A/V PREFERREDVENDOR.
72"67"
LP-3B
LP-3BA
ELP-3B
LP-3B-35AP
AP
LP-3B-23
LP-3B-31
LP-3B-5
LP-3B-3
3
2D
6D
4
34"USB
USBUSB
USB
60"
1
LP-3B-12
LP-3B-37
5
5
5
5
ACD
7
8
9
10
B
6
c o n s t r u c t o r s
a r c h i t e c t s
s c i e n t i s t s
e n g i n e e r s
Hard copy is intended to be24"x36" when plotted. Scale(s)
indicated and graphic quality maynot be accurate for any other size.
PROJECT NO.
Drawn By
Designer
Reviewer
Manager
f i s h b e c k, t h o m p s o n, c a r r & h u b e r, i n c.
PLO
T IN
FO
:
© C o p y r i g h t 2 0 1 9A l l R i g h t s R e s e r v e d
www.ftch.com
R E V I S I O N S
Wa
yn
e S
tate
Un
ive
rsit
y5557 C
ass A
ve, D
etr
oit, M
I 48202
Co
hn
Bu
ildin
g S
tud
en
t C
om
mo
ns
190812
VJM
KEY PLAN
NORTH
WS
U P
RO
JE
CT
NU
MB
ER
: 048-2
91367
10/31/2019 Permits and Bids
C:\W
ork
\Revit\2
019
_E
_1
90812
_JM
5.r
vt
10/3
1/2
01
9 1
1:4
7:0
8 A
M
E201
THIRD FLOOR POWER ANDSYSTEMS PLAN
JAM
RMM
CJM
NORTH
SCALE: 1/4" = 1'-0"
THIRD FLOOR POWER AND SYSTEMS PLAN
NOTES
1.
2.
3.
4.
REFER TO DRAWING E001 FOR THE ELECTRICAL GENERAL NOTES AND REQUIREMENTS.
CIRCUIT NUMBERS ARE SHOWN FOR GROUPING PURPOSES ONLY. UTILIZE CIRCUITS MADE AVAILABLE THROUGH DEMOLITION OR SPARE CIRCUIT BREAKERS. ALL BRANCH CIRCUIT WIRING SHALL BE NEW.
PROVIDE WIRING DEVICE COVERPLATE SAMPLES FOR REVIEW DURING THE SHOP DRAWING SUBMITTAL PROCESS.
ALL DATA CABLING AND ASSOCIATED RACEWAYS SHALL BE INSTALLED PER WAYNE STATE STANDARDS FOR COMMUNICATIONS INFRASTUCTURE - 29 JULY 2019.
KEY NOTES
1 FIRE ALARM CONTROL MODULE TO RELEASE FIRESHUTTERS UPON FIRE ALARM ACTIVATION.
2 MOUNT HORIZONTALLY IN THE VERTICAL PORTION OFTHE BENCH.
3 POWER FEED FOR FURNITURE "D" TABLE, REFER TO THECONNECTRAC DETAIL ON E501.
4 LOW VOLTAGE FEED FOR FURNITURE "D" TABLE. REFERTO THE CONNECTRAC DETAIL ON E501.
5 4#12, #12 GRD, 3/4"C.
6 RELOCATED WIRELESS ACCESS POINT.
WIRING DEVICES - MANUAL POWER SWITCH SCHEDULE
SYMBOL DESCRIPTION MANUFACTURER CATALOG NO. REMARKS
KKEYED MANUAL SWITCH PROVIDED BY FIRE
SHUTTERMANUFACTURER
WIRING DEVICES - RECEPTACLE SCHEDULE
SYMBOL DESCRIPTION MANUFACTURER CATALOG NO. REMARKS
DUPLEX RECEPTACLE HUBBELL HBL5362I MOUNT 18" AFF, UNO
DUPLEX RECEPTACLE (ABOVECOUNTER)
HUBBELL HBL5362I MOUNT HORIZONTALLY ABOVE COUNTER; 2-INCHES ABOVEBACKSPLASH, UNO
USBDUPLEX RECEPTACLE WITH TWO USBCHARGING PORTS
HUBBELL USB8300I MOUNT 18" AFF, UNO
USBDUPLEX RECEPTACLE WITH TWO USBCHARGING PORTS (ABOVE COUNTER)
HUBBELL USB8300I MOUNT HORIZONTALLY ABOVE COUNTER; 2-INCHES ABOVEBACKSPLASH, UNO
USBDOUBLE DUPLEX RECEPTACLE WITHFOUR USB CHARGING PORTS
HUBBELL (2) USB8300I MOUNT AT 18" AFF, UNO
2-GANG RECESSED WALL BOX FORVIDEO MONITOR POWER AND DATAWITH DUPLEX RECEPTACLE
LEGRANDWIREMOLD
EFSB2 MOUNT AT 18" AFF, UNO; PROVIDE (1) HUBBELL #HBL5362IDUPLEX RECEPTACLE