BUILDING DATA NOT TO SCALE DESCRIPTION OF WORK THE PROJECT SCOPE INCLUDES THE REPLACEMENT OF ONE EXISTING 60-TON AIR COOLED CHILLER. THE CHILLER WILL BE REPLACED WITH A NEW HIGH EFFICIENCY AIR COOLED SCROLL CHILLER. ALL BAS CONTROL OF EQUIPMENT TO REMAIN. REMOVAL AND REPLACEMENT OF BAS CONTROLS AS REQUIRED TO COMPLETE THE FINAL INSTALLATION. MRS. IDA D. WRIGHT MRS. LINDA CUTHBERT MR. CARL G. PERSIS MR. RUBEN COLON MS. JAMIE M. HAYNES DR. RONALD "SCOTT" FRITZ SCHOOL BOARD MEMBERS CHAIRMAN VICE CHAIRMAN MEMBER MEMBER MEMBER SUPERINTENDENT A. SURVEY PARCEL ID XXX B. LEGAL DESCRIPTION XXX C. OCCUPANCY TYPE XXX D. CONSTRUCTION TYPE TYPE XXX E. RISK CATEGORY N/A F. AUTOMATIC SPRINKLER N/A G. BUILDING AREA N/A H. BUILDING HEIGHT N/A I. OCCUPANT LOAD N/A LOCATION MAP ENGINEERS & CONSULTANTS VCS Project NO. 2047721 650 ROBERTS ROAD, EDGEWATER, FLORIDA 32141 REPLACE CHILLER BLDG. 7 INDIAN RIVER ELEMENTARY SCHOOL Engineer's Statement of Compliance To the best of my knowledge, these drawings and the project manual are complete and comply with the Florida Building Code. MECHANICAL TRISTAR ENGINEERING GROUP, INC. 14522 SALINGER ROAD ORLANDO, FLORIDA 32828 407-567-9795 JUAN C. PESANTE, P.E. [email protected]WWW.TRISTARFL.COM VOLUSIA COUNTY SCHOOLS VOLUSIA COUNTY SCHOOLS VOLUSIA COUNTY SCHOOLS THE SCHOOL BOARD OF VOLUSIA COUNTY FLORIDA 200 North Clara Avenue Deland, Florida 32720 BID SET JANUARY 21, 2020 ROBERT L. SYMMES RLS RLS G000 COVER SHEET REPLACE CHILLER BLDG. 7 VCS PROJECT NO. 2047721 650 ROBERTS ROAD EDGEWATER, FLORIDA 32141 2019-016 01/21/2020 Engineer INDIAN RIVER ELEMENTARY SCHOOL NO. DATE DESCRIPTION DRAWING NO. SHEET TITLE AE PROJECT NUMBER DRAWN BY DESIGNED BY ARCH/ENGR OF RECORD ISSUE DATE DOCUMENT HISTORY REVISIONS R O B E R T L . S Y M M E S F L P E # 8 8 4 1 7
SCHOOL BOARD INDIAN RIVER ELEMENTARY SCHOOLMEMBERS … · the drawings indicate the general arrangement of mechanical and electrical syste\്s and other work. make reasonable modifications
DESCRIPTION OF WORKTHE PROJECT SCOPE INCLUDES THE REPLACEMENT OF ONE EXISTING 60-TON AIR COOLED CHILLER. THE CHILLER WILL BEREPLACED WITH A NEW HIGH EFFICIENCY AIR COOLED SCROLL CHILLER. ALL BAS CONTROL OF EQUIPMENT TO REMAIN.REMOVAL AND REPLACEMENT OF BAS CONTROLS AS REQUIRED TO COMPLETE THE FINAL INSTALLATION.
MRS. IDA D. WRIGHTMRS. LINDA CUTHBERTMR. CARL G. PERSISMR. RUBEN COLONMS. JAMIE M. HAYNES
DR. RONALD "SCOTT" FRITZ
SCHOOL BOARDMEMBERS
CHAIRMANVICE CHAIRMAN
MEMBERMEMBERMEMBER
SUPERINTENDENT
A. SURVEY PARCEL ID XXX
B. LEGAL DESCRIPTION XXX
C. OCCUPANCY TYPE XXX
D. CONSTRUCTION TYPE TYPE XXX
E. RISK CATEGORY N/A
F. AUTOMATIC SPRINKLER N/A
G. BUILDING AREA N/A
H. BUILDING HEIGHT N/A
I. OCCUPANT LOAD N/A
LOCATION MAP
ENGINEERS & CONSULTANTS
VCS Project NO. 2047721650 ROBERTS ROAD, EDGEWATER, FLORIDA 32141
REPLACE CHILLERBLDG. 7
INDIAN RIVER ELEMENTARY SCHOOL
Engineer's Statement of ComplianceTo the best of my knowledge, these drawings and the project manual are complete and comply withthe Florida Building Code.
STRAINER - BASKET TYPE W/ DRAIN VALVE, HOSE BIBB, & CAP
AutoCAD SHX Text
DEMOLITION
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
< X >
AutoCAD SHX Text
EXISTING TO BE REMOVED
AutoCAD SHX Text
< R >
AutoCAD SHX Text
CAP EXISTING
AutoCAD SHX Text
< C >
AutoCAD SHX Text
DEMOLITION PIPING
AutoCAD SHX Text
DEMOLITION EQUIPMENT OR DUCT
AutoCAD SHX Text
EXISTING - NEW LOCATION
AutoCAD SHX Text
< NL >
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY MATERIALS AND CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY MATERIALS AND LABOR TO PROVIDE A COMPLETE, OPERATIONAL SYSTEM. 2. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO CONSTRUCTION AND CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO CONSTRUCTION AND CORRECT, AS REQUIRED, TO MEET ALL THE CODES, REGULATIONS, AND DISCREPANCIES BETWEEN EXISTING WORK SHOWN ON DRAWINGS AND WHAT IS INSTALLED ON SITE. 3. CONTRACTOR SHALL COORDINATE WORK WITH ALL OTHER TRADES. CONTRACTOR SHALL COORDINATE WORK WITH ALL OTHER TRADES. 4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING AND VERIFYING DIMENSIONS THE CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING AND VERIFYING DIMENSIONS PRIOR TO ORDERING MATERIALS AND INSTALLING EQUIPMENT. THE DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF MECHANICAL AND ELECTRICAL SYSTEMS AND OTHER WORK. MAKE REASONABLE MODIFICATIONS IN LAYOUT AND COMPONENTS TO PREVENT CONFLICT WITH WORK OF OTHER TRADES. SIGNIFICANT MODIFICATIONS IN LAYOUT AND COMPONENTS SHALL RECEIVE PRIOR REVIEW BY A/E. SUCH MODIFICATIONS SHALL NOT BE GROUNDS FOR ADDITIONAL COMPENSATION TO CONTRACTOR. 5. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS (INCLUDING EXISTING PIPE ROUTING AND CONTRACTOR SHALL SUBMIT SHOP DRAWINGS (INCLUDING EXISTING PIPE ROUTING AND EQUIPMENT LOCATIONS) TO ARCHITECT/ENGINEER FOR REVIEW PRIOR TO THE INSTALLATION OR PURCHASING OF ANY EQUIPMENT/MATERIALS. 6. THE CONTRACTOR IS EXPECTED TO ORDER ALL MATERIALS IN SUFFICIENT LEAD TIME THE CONTRACTOR IS EXPECTED TO ORDER ALL MATERIALS IN SUFFICIENT LEAD TIME TO AVOID DELAYING THE COMPLETION OF THE PROJECT. DELAY IN DELIVERIES WILL NOT BE CONSIDERED A JUSTIFIABLE REASON FOR SUBMISSION OF SUBSTITUTE MATERIALS. 7. THE CONTRACTOR PROVIDING THE EQUIPMENT SHALL BE RESPONSIBLE FOR ALL COST THE CONTRACTOR PROVIDING THE EQUIPMENT SHALL BE RESPONSIBLE FOR ALL COST INCURRED BY THE CONTRACTOR AND SUBCONTRACTORS TO MODIFY THE BUILDING PROVISIONS TO ACCEPT THE FURNISHED EQUIPMENT.
AutoCAD SHX Text
%%UGENERAL NOTES - HVAC
AutoCAD SHX Text
TRISTAR ENGINEERING GROUP, INC. 14522 SALINGER ROAD ORLANDO, FLORIDA 32828 407-567-9795 CA LIC No: 31573
1. CHILLERS TO HAVE AUTO-RESTART IN THE EVENT OF A POWER FAILURE
2. FACTORY INSTALLED FLOW SWITCH
3. START-UP PROVIDED BY CERTIFIED TECHNICIAN
4. COVER EVAPORATOR WITH FACTORY-INSTALLED 1.25" ARMAFLEX OR EQUAL INSULATION
5. PROVIDE CONDENSER COIL COATING THAT MEETS OR EXCEEDS AN ASTM B-117 5,000 HR SALT SPRAY TEST
6. FACTORY INSTALLED WATER STRAINER
7. PROVIDE LOUVERED PANELS TO COVER THE COMPLETE CONDENSER COIL AND SERVICE AREA BENEATH THE CONDENSER
8. PROVIDE 10 YEARS PARTS, LABOR, AND REFRIGERANT WARRANTY
9. PROVIDE 10 YEAR MAINTENANCE AGREEMENT
10. CHILLER MOUNTED ON FACTORY PROVIDE MOULDED ELASTOMERIC ISOLATORS
11. TEST AND BALANCE TO MEASURE AND ADJUST FLOW TO DESIGN FLOW RATE.
KEY NOTES - DEMOLITION
KEY NOTES - NEW WORK
GENERAL NOTES
REPL
ACE
CHILL
ER B
LDG.
7VC
S PR
OJEC
T NO
. 204
7721
650
RO
BER
TS R
OAD
EDG
EWAT
ER, F
LOR
IDA
3214
1
2019-01601/21/2020
Engineer
INDI
AN R
IVER
ELE
MENT
ARY
SCHO
OLNO
.DA
TEDE
SCRI
PTIO
N
DRAWING NO.
SHEE
T TI
TLE
AE PROJECT NUMBER
DRAWN BYDESIGNED BY
ARCH/ENGR OF RECORD
ISSUE DATE
DOCU
MENT
HIS
TORY
REV
ISIO
NS
R O B E R T L . S Y M M E SF L P E # 8 8 4 1 7
HVAC
PLA
N - D
EMOL
ITIO
N &
NEW
M101
ROBERT L. SYMMES
RLS RLS
AutoCAD SHX Text
EXISTING 60-TON CHILLER TO BE REMOVED
AutoCAD SHX Text
NEW POWER CONNECTION
AutoCAD SHX Text
EXISTING ELECTRICAL CONDUIT FROM SERVCE DISCONNECT UNDERSLAB TO CHILLER. EXTEND TO NEW CHILLER CONNECTION.
AutoCAD SHX Text
CH-1
AutoCAD SHX Text
EXISTING ELECTRICAL CONDUIT FROM SERVCE DISCONNECT UNDERSLAB TO CHILLER
AutoCAD SHX Text
%%UHVAC PLAN - DEMOLITION
AutoCAD SHX Text
SCALE: 3/8" = 1'-0"
AutoCAD SHX Text
1
AutoCAD SHX Text
M101
AutoCAD SHX Text
N
AutoCAD SHX Text
%%UHVAC PLAN - NEW WORK PLAN
AutoCAD SHX Text
SCALE: 3/8" = 1'-0"
AutoCAD SHX Text
2
AutoCAD SHX Text
M101
AutoCAD SHX Text
4" CHWS & R UNDERGROUND TO PUMP ROOM
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
AUTOMATIC AIR VENT
AutoCAD SHX Text
5
AutoCAD SHX Text
PRESSURE GAUGE - CHWS TO CHWR
AutoCAD SHX Text
6
AutoCAD SHX Text
THERMOMETER
AutoCAD SHX Text
EXISTING CALIBRATED MANUAL BALANCING VALVE TO BE REMOVED
AutoCAD SHX Text
EXISTING ISOLATION VALVE TO REMAIN
AutoCAD SHX Text
EXISTING Y-STRAINER TO BE REMOVED
AutoCAD SHX Text
4
AutoCAD SHX Text
5
AutoCAD SHX Text
6
AutoCAD SHX Text
4" CHWS UNDER 4" CHWR.REMOVE EXISTING PIPE FROM ISOLATION VALVE TO CHILLER OUTLET. ISOLATION VALVE TO REMAIN.
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
5
AutoCAD SHX Text
EXISTING ISOLATION VALVE TO REMAIN.
AutoCAD SHX Text
PROVIDE KINETICS NOISE CONTROL MODEL FTC FLEX CONNECTORS FOR BOTH SUPPLY AND RETURN CONNECTIONS.
AutoCAD SHX Text
7
AutoCAD SHX Text
EXISTING DUPLEX POWER OUTLET TO REMAIN
AutoCAD SHX Text
7
AutoCAD SHX Text
8
AutoCAD SHX Text
EXISTING CONDENSING UNIT ON CONCRETE PAD TO REMAIN.
AutoCAD SHX Text
8
AutoCAD SHX Text
9
AutoCAD SHX Text
EXISTING CONDENSER DISCONNECT TO REMAIN.
AutoCAD SHX Text
9
AutoCAD SHX Text
10
AutoCAD SHX Text
EXISTING TVSS TO REMAIN.
AutoCAD SHX Text
10
AutoCAD SHX Text
11
AutoCAD SHX Text
CH-1 DISCONNECT TO REMAIN.
AutoCAD SHX Text
11
AutoCAD SHX Text
6
AutoCAD SHX Text
7
AutoCAD SHX Text
8
AutoCAD SHX Text
9
AutoCAD SHX Text
10
AutoCAD SHX Text
6
AutoCAD SHX Text
EXISTING DUPLEX POWER OUTLET TO REMAIN
AutoCAD SHX Text
7
AutoCAD SHX Text
EXISTING CONDENSING UNIT ON CONCRETE PAD TO REMAIN.
AutoCAD SHX Text
8
AutoCAD SHX Text
EXISTING CONDENSER DISCONNECT TO REMAIN.
AutoCAD SHX Text
9
AutoCAD SHX Text
EXISTING TVSS TO REMAIN.
AutoCAD SHX Text
10
AutoCAD SHX Text
CH-1 DISCONNECT TO REMAIN.
AutoCAD SHX Text
4" CHWS & R UNDERGROUND TO PUMP ROOM
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
12
AutoCAD SHX Text
12
AutoCAD SHX Text
EXISTING BAS CHWS & R TEMPERATURE SENSORS TO BE REUSED.
AutoCAD SHX Text
11
AutoCAD SHX Text
INSTALL EXISTING SUPPLY AND RETURN TEMPERATURE SENSORS AFTER CHILLER REPLACEMENT IS COMPLETE. PROVIDE NEW WELLS AS REQUIRED.
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
5
AutoCAD SHX Text
11
AutoCAD SHX Text
12
AutoCAD SHX Text
CONTRACTOR TO PROVIDE AND PULL NEW ELECTRICAL WIRE TO ACCOMMODATE LOCATION OF CH-1 POWER SUPPLY.
AutoCAD SHX Text
12
AutoCAD SHX Text
1. PIPING PIPING 1.1. REINSTALL PIPING FROM EVAPORATOR TO FLANGED VALVE. REPAIR OR REINSTALL PIPING FROM EVAPORATOR TO FLANGED VALVE. REPAIR OR REPLACE INSULATION AND JACKETING AS REQUIRED. 1.2. PIPE INSULATION - OWENS CORNING FOAMGLAS ONE PIPE INSULATION, 0.31 PIPE INSULATION - OWENS CORNING FOAMGLAS ONE PIPE INSULATION, 0.31 BTU IN/H FT2 °F, 1-1/2" THICKNESS.1.3. JACKET - GLT PRODUCTS ALUMINUM ROLL JACKETING, 3003 ALLOY, 0.016 JACKET - GLT PRODUCTS ALUMINUM ROLL JACKETING, 3003 ALLOY, 0.016 INCHES THICK WITH 3 MIL THICK POLYFILM MOISTURE BARRIER HEAT LAMINATED TO THE INTERIOR SURFACE. 2. VALVES VALVES 2.1. KEYSTONE, FIG. 222, CAST IRON, LUG-BODY, EPDM LINER, ALUMINUM KEYSTONE, FIG. 222, CAST IRON, LUG-BODY, EPDM LINER, ALUMINUM BRONZE DISC AND STEM WITH LOCKABLE HANDLE. 3. GAUGE AND VALVES GAUGE AND VALVES 3.1. BALL VALVES, APOLLO 77-140 SERIES, 2-PIECE BRONZE BODY FULL PORT BALL VALVES, APOLLO 77-140 SERIES, 2-PIECE BRONZE BODY FULL PORT BALL VALVE, 316 SS BALL & STEM, STEM EXTENSION FOR INSTALLATION IN INSULATED PIPING. 3.2. GAUGE - WIKA 233.54, 4" FACE, STAINLESS STEEL LIQUID FILLED CASE, GAUGE - WIKA 233.54, 4" FACE, STAINLESS STEEL LIQUID FILLED CASE, BOURDON TUBE, 0-60 PSI RANGE. 3.3. AP ARMAFLEX BLACK LAPSEAL TUBE INSULATION, 0.245 BTU IN/H FT2 F. AP ARMAFLEX BLACK LAPSEAL TUBE INSULATION, 0.245 BTU IN/H FT2 °F.4. AUTOMATIC AIR VENT AUTOMATIC AIR VENT 4.1. WATTS FV-4M1, 3/4", BRASS BODY AND COVER AND SILICONE RUBBER WATTS FV-4M1, 3/4", BRASS BODY AND COVER AND SILICONE RUBBER SEAL. HIGH TEMPERATURE RESISTANT POLYETHYLENE FLOAT. 5. CONTROLS CONTROLS 5.1. CONTROL POINTS FOR NEW CHILLER SHALL BE EQUIVALENT TO THE CONTROL POINTS FOR NEW CHILLER SHALL BE EQUIVALENT TO THE EXISTING CHILLER CONTROL POINTS. AT MINIMUM, CHWS & R TEMPERATURE, STATUS, START/STOP AND GENERAL ALARM SHALL BE AVAILABLE THROUGH THE EXISTING CONTROL SYSTEM FOR THE REPLACED CHILLER.
AutoCAD SHX Text
13
AutoCAD SHX Text
I-BEAM SUPPORTS AND CONCRETE BASES TO REMAIN FOR SUPPORT OF NEW CHILLER.
AutoCAD SHX Text
13
AutoCAD SHX Text
NEW THERMOMETER AND WELL. PROVIDE FOR CHWS & CHWR
AutoCAD SHX Text
NEW PRESSURE GAUGE - CHWS TO CHWR
AutoCAD SHX Text
NEW AUTOMATIC AIR VENT
AutoCAD SHX Text
PROVIDE NEW PIPING ON CHWR FROM ISOLATION VALVE TO CHILLER INLET AS REQUIRED.
AutoCAD SHX Text
PROVIDE NEW PIPING ON CHWS FROM ISOLATION VALVE TO CHILLER CONNECTION, AS REQUIRED.
AutoCAD SHX Text
N
AutoCAD SHX Text
TRISTAR ENGINEERING GROUP, INC. 14522 SALINGER ROAD ORLANDO, FLORIDA 32828 407-567-9795 CA LIC No: 31573