Upload
others
View
8
Download
0
Embed Size (px)
Citation preview
Schneider Electric Brands
AS-i Metal Enclosed DOL Starters
Class 8340
CONTENTS
Description PageProduct Configuration and Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2–7Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8–9General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9–11Electrical Specifications and Data Bus Information Exchange . . . . . . . . . . . . . . 11–14Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15–22Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersDecentralized Systems
© 2001–2002 Schneider Electric All Rights Reserved2
3/02
INTRODUCTION TO AS-I DIRECT-ON-LINE (DOL) STARTERS
Decentralization of Machine Starters
These pre-assembled, ready-to-use, enclosed starters communicate with and are controlled by the AS-i bus. They are designed for building decentralized electrical installations, that is, the starters are installed adjacent to the associated motor. This decentralization of the starters provides obvious advantages for power distribution to motors not grouped together—for example, motors driving a conveyor system.
Power can be distributed either by prefabricated trunking or by cable.
These starters integrate all the functions necessary for the management of motors (control, protection, isolation, etc.) and contain:
• a thermal-magnetic protector combined with a local operator interface for manual disconnect
• a low-consumption contactor (non-reversing) or contactor pair (reversing)
• an electronic control device
Although designed primarily for use with three-phase AC motors, AS-i DOL starters can also be used with single-phase or DC motors. For these applications, the three phases of the internal thermal-magnetic protector is wired in series (each phase sensing the same current) to avoid tripping due to a perceived phase failure.
Centralized systemIn this example, cabling the motor equipment requires approximately 1640 ft (500 m)of 4 x 16 AWG (4 x 1.5 mm ) cable.2
Decentralized systemThe decentralized system uses only 260 ft (80 m) of 4 x 12 AWG (4 x 4 mm ) cable. This results in cost savings in terms of installation labor as well as cable and cable ducts. This installation is also more flexible—it is easier to add a motor.
2
Automation control panel
Motor starters
Power distributioncables
Motor
Sensor
PLC
Machinery
PLC AS-i busStarter
Powerdistributioncable
Motor
Sensor
Machinery
Distribution panel
Power disconnect
Power disconnect
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersImportant Information
33/02 © 2001–2002 Schneider Electric All Rights Reserved
Important Application Information for AS-i DOL Starters
AS-i based direct-on-line (DOL) starters combine the following components into one package:
• A GV2 manual starter containing a manual disconnect, an instantaneous magnetic trip mechanism, and a Class 10 ambient-compensated, bi-metallic thermal overload relay
• An appropriately sized K-line contactor
• An AS-i communications interface board
• Related plugs and connectors for bus and power and for auxiliary inputs such as sensors or limit switches
An Important User Consideration when Applying DOL Starters:
Users must provide in their application any appropriate branch circuit protection (circuit breaker, fusing, etc.) to meet all local and national codes, in particular, the National Electrical Code (NEC) or Canadian Electrical Code (CEC).
The instantaneous magnetic trip mechanism in the GV2 manual starter is a high fault current trip mechanism, particularly for short circuit conditions in a motor circuit. The magnetic trip mechanism is not a circuit breaker as defined in NEC section 430. It is up to the user to provide appropriate branch circuit protection to meet all NEC, CEC, or local electrical code requirements. This step is also necessary for meeting Type 2 coordination in motor branch circuits.
For additional information on Type 2 coordination, refer to Square D product data bulletin 0140PD9202, Understanding Type 2 Coordinated Protection in Motor Branch Circuits.
Internal View of the Starter
J 10
J 11
J 2
+ -J 5
5 4
2 1
3
1. GV2-M or GV2-P manual motor starter
2. Electronic communication card
3. Earth (ground) terminal
4. Relay
5. Contactor used (see table)
LF•M•00D•••U LF•M•16D•••U
All others
non-reversing starters
LP4-K12015BW3 LP4-K09015BW3
reversing starters LP5-K12015BW3 LP5-K09015BW
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersFeatures and Options
© 2001–2002 Schneider Electric All Rights Reserved4
3/02
Connection through Plug-In Connectors, A74 Option Shown
Cable gland connection is provided as standard, refer to page 19.
1. Yellow LED:
— Steady on when the motor is running
2. Red LED:
— Flashing when there is a motor fault (overload or short-circuit) or internal starter fault
— Steady on when there is a data exchange fault
3. Green LED:
— Steady on when power is available on the AS-i bus
— Flashing when data intended for the starter is received via the bus
4. Knock-outs for cable glands (supplied) for the connector cable (if any) of an auxiliary power supply unit (A79 option only)
5. Power supply daisy chaining male connector (A74 option)
6. Three-position rotary disconnect-switch control knob.
— O: Opened manually
— |: Closed
— Trip: Tripped
7. Key-operated bus/Local switch (A79 option)
8. Reversing starter (LF2):
— Three-position selector switch with center spring-loaded position
— Functional assignment:
• Position 1 forward
• Position 0 off
• Position 2 reverse (A79 option)
Non-reversing starter (LF1):
— Push buttons
— Functional assignment: Pulsed run (jogging)
9. Precut for auxiliary relay output cable gland (not supplied)
10. Female M12 connector for sensor connection (not supplied with dust cap)
11. Male M12 connector for AS-i bus and auxiliary power supply unit (if any) connection
12. Motor power supply female connector (A74 option)
13. Reset pushbutton switch
14. Off pushbutton switch
1 2 3 4
6
12
11 10 9
1 2 3 4
13
14
5
87
12
11 10 9 87
5
Starter with Rotary Control Knob Starter with Pushbutton Control
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersControl
53/02 © 2001–2002 Schneider Electric All Rights Reserved
Motor Control and Protection
Starters with a rotary control knob provide the following functions:
• Load break disconnect switch with padlockable control knob
• IP55 degree of protection, double insulation
• Opening of the enclosure is mechanically inhibited when the starter is switched on or when in the off position and padlocked.
Starters with pushbutton control provide the following functions:
• Pushbutton resetting of the protection device
• Pushbutton stop
• IP55 degree of protection, double insulation
Local Controls
On standard DOL starters, stop and reset functions are possible from the front of the enclosure. The stop command is achieved by actuating the internal manual starter button, which provides the isolation function. Depending on the type of starter, the stop command is issued by either:
• a rotary control knob
• a black pushbutton
If an overload occurs, it is possible to reset the internal thermal-magnetic protector after the motor cools down.
Depending on the type of starter, the restart command is issued by either:
• a rotary control knob
• a blue reset pushbutton
Integral Local/Bus Control (user option A79)
This starter option includes a two-position local/bus key operated selector switch which enables either of the following functions:
• Bus: the PLC controls the motor starter
• Local: the Start/Stop commands override commands from the PLC
It also has:
• For reversing starters (LF2), a three-position, spring return to zero, selector switch:
— Position 1: starting direction 1 (forward)
— Position 0: stop
— Position 2: starting direction 2 (reverse)
• For non-reversing starters (LF1), a pushbutton which performs a jogging operation
A79 Option
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersControl
© 2001–2002 Schneider Electric All Rights Reserved6
3/02
Pushbutton Station Control
To achieve manual local start control from a pushbutton control station connected to the AS-i bus, use AS-i pushbutton control stations, catalog number XALS200• or an equivalent part. These can be found in the AS-i Bus catalog 8340CT0001.
Actuation of the pushbutton is transmitted to the programmable controller (message 1), which passes it on to the starter (message 2).
Local Signalling
Three LEDs located on the enclosure cover provide visual indication of the operating states. For details, see page 4.
Important User Information
• This starter features continual self-checking to ensure correct operation.
• This starter does not process external safety functions.
• Use only hard-wired, electromechanical emergency stops and machine safety circuits. Electrical codes EN/IEC 60204-1 Section 9.2.5.4 and applicable NEC and CEC standards do not currently allow these functions via a network (i.e. the AS-i bus).
• An independent safety device is required to re-establish the supply voltage to the starter after a supply failure.
• The starter control operator (rotary knob or pushbutton) does not act as an emergency stop when the machine incorporates other actuators. The control operators are black to conform with the standard EN 60204 Section 10.2.1
• Starters with rotary control knobs are not emergency stops–they are padlockable in the on position.
Loss of Control
When communication is interrupted, the PLC no longer controls the starter. The factory default configuration is set to stop the motor. However, the starter can be configured via the AS-i bus to one of the following default conditions:
• set to stop the motor (applications: potentially dangerous movements)
• set to start the motor in direction 1 (applications: extraction fans, pumps)
• set the motor to run at the setting immediately before the loss of control (application: suction grippers)
US
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersWith Relays or Sensors
73/02 © 2001–2002 Schneider Electric All Rights Reserved
Output Control Relay
An output control relay is used to control a lamp, a solenoid valve, and so forth via the AS-i bus using a 24 Vdc, 1 A relay with a single pole, double throw (SPDT), single break contact, see page 21.
Starters with a Sensor Connected
Two 3-wire type PNP sensors (50 mA max.) or two 2-wire limit switches can be connected directly to the starter. The information supplied by the sensor/limit switch is returned on the AS-i bus.
Alternatively, the sensor signal can be processed locally for establishing a reflex motor stop. Selection of this feature is made by DIP switches.
Reflex Stop
A reflex stop occurs whenever the first sensor detects a component. When a new start command is received via the AS-i bus, the motor restarts but stops again following the next detection. In the case of a reversing starter, the detector stops the motor regardless of its running direction.
M M
M
AS-i bus
Power Supply
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersCatalog Number Structure
© 2001–2002 Schneider Electric All Rights Reserved8
3/02
SELECTION
Catalog Number Structure
LF 1 M M 03D A79A74 U
Product Family
LF – AS-i direct-on-line (DOL) starter
Contactor Type
1 – non-reversing
2 – reversing
Enclosure Type
M – metal enclosed
Through the Door Control Type
M – pushbutton control (IP65)
P – rotary handle control (IP55)
Manual Motor Starter Thermal Trip Range
00D – none
02D – 0.16 to 0.25 amps
03D – 0.25 to 0.40 amps
04D – 0.40 to 0.63 amps
05D – 0.63 to 1.0 amps
06D – 1.0 to 1.6 amps
07D – 1.6 to 2.5 amps
08D – 2.5 to 4.0 amps
10D – 4.0 to 6.3 amps
14D – 6.0 to 10.0 amps
16D – 9.0 to 14.0 amps
User Selectable Options
blank – no user options selected
A74 – pluggable power and motor connectors
A79 – local/bus control key operated selector switch
A79A74 – both user options selected
Documentation
U – U.S. documentation, U.S. product markings
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersStarter Selection and Ratings
93/02 © 2001–2002 Schneider Electric All Rights Reserved
GENERAL SPECIFICATIONS
Starter Selection
Adjustable Thermal Trip Range (Amps)
Non-Reversing, Pushbutton Control
Non-Reversing, Rotary Control
Reversing, Pushbutton Control
Reversing, Rotary Control
0.16 to 0.25 LF1MM02D(1)U LF1MP02D(1)U LF2MM02D(1)U LF2MP02D(1)U
0.25 to 0.40 LF1MM03D(1)U LF1MP03D(1)U LF2MM03D(1)U LF2MP03D(1)U
0.40 to 0.63 LF1MM04D(1)U LF1MP04D(1)U LF2MM04D(1)U LF2MP04D(1)U
0.63 to 1.0 LF1MM05D(1)U LF1MP05D(1)U LF2MM05D(1)U LF2MP05D(1)U
1.0 to 1.6 LF1MM06D(1)U LF1MP06D(1)U LF2MM06D(1)U LF2MP06D(1)U
1.6 to 2.5 LF1MM07D(1)U LF1MP07D(1)U LF2MM07D(1)U LF2MP07D(1)U
2.5 to 4.0 LF1MM08D(1)U LF1MP08D(1)U LF2MM08D(1)U LF2MP08D(1)U
4.0 to 6.3 LF1MM10D(1)U LF1MP10D(1)U LF2MM10D(1)U LF2MP10D(1)U
6.0 to 10.0 LF1MM14D(1)U LF1MP14D(1)U LF2MM14D(1)U LF2MP14D(1)U
9.0 to 14.0 LF1MM16D(1)U LF1MP16D(1)U LF2MM16D(1)U LF2MP16D(1)U
(1) Insert the appropriate suffix from the following user options into the catalog number above:
User Option Suffix Description
blank No user options selected.
A74 Pluggable power and motor connectors.
A79 Local / bus control key operated selector switch.
A79A74 Both user options as described above.
Examples of correct catalog number sequences:
• LF1MM03DU • LF1MM03DA79U
• LF1MM03DA74U • LF1MM03DA79A74U
Ratings
Catalog Number
Adjustable Thermal Trip
Range (A)
Maximum Horsepower Ratings (Hp) Standard Power Ratings (kW)
Three Phase, 50/60 Hz, AC-3
Single Phase Three Phase
115 Vac 230 Vac 200 Vac 230 Vac 480 Vac 575 Vac 220/230
Vac400/415
Vac
LF•M•02D•••U 0.16 to 0.25 — 0.06
LF•M•03D•••U 0.25 to 0.40 0.06 0.09
LF•M•04D•••U 0.40 to 0.63 — 0.12 / 0.18
LF•M•05D•••U 0.63 to 1.0 1/2 1/2 0.09 / 0.12 0.25
LF•M•06D•••U 1.0 to 1.6 1/10 3/4 1 0.18 / 0.25 0.37 / 0.55
LF•M•07D•••U 1.6 to 2.5 1/6 1/2 1/2 1 1-1/2 0.37 0.75
LF•M•08D•••U 2.5 to 4.0 1/8 1/3 3/4 1 2 3 0.55 / 0.75 1.1 / 1.5
LF•M•10D•••U 4.0 to 6.3 1/4 1/2 1-1/2 1-1/2 3 5 1.1 2.2
LF•M•14D•••U 6.0 to 10.0 1/2 1-1/2 2 3 5 5 1.5 3 / 4
LF•M•16D•••U 9.0 to 14.0 3/4 2 3 3 7.5 10 2.2 / 3 5.5
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersEnvironmental Specifications
© 2001–2002 Schneider Electric All Rights Reserved10
3/02
UL/CSA:
Environment
Conforming to Standards IEC 60204-1, EN 60204-1, IEC 60974-4-1, EN 60974-4-1
Product Certifications Pending AS-i
Protective Treatment Standard version“TC”, see IEC style contactors and starters in the DigestPlus Selector on the Square D website, www.SquareD.com
Degree of Protection conforming to IEC 60529
Starters with rotary control knob
IP 55
Starters with pushbutton control
IP 55
Ambient Air Temperature conforming to IEC 60439-1
Storage –40 °F to +176 °F (–40 °C to +80 °C)
Operation +23 °F to +104 °F (–5 °C to +40 °C)
Maximum Operating Altitude Without derating 6562 ft (2000 m)
Operating Positionwithout derating
In relation to normal vertical mounting plane
Flame Resistance of Equipment Conforming to IEC 60695-2-1 1760 °F (960 °C)
Shock Resistance(semi-sinusoidal, 11 ms) conforming to IEC 60068-2-27
Contactor poles open 10 g
Contactor poles closed 15 g
Vibration Resistance 5 to 150 Hzconforming to IEC 60068-2-6
Contactor poles open 2 g
Contactor poles closed 4 g
Safety Separation of Circuits Conforming to VDE 0106 and IEC 60536
SELV (Safety Extra Low Voltage), up to 400 V
Immunity to Non-Dissipating Shockwave (Uimp) Conforming to IEC 60947-4-16 kV: power2.5 kV: AS-i, 24 V, and sensor
Chemical ResistanceAvoid the following chemicals coming into contact with the enclosure: strong bases (various detergents), aromatic hydrocarbons, alcohol, chlorine solvents, ketones.
Electromagnetic Compatibility
Immunity to Electrostatic Discharge Conforming to IEC 61000-4-2 EN 61000-4-2
8 kV: in air (level 3)4 kV: in indirect mode (level 2)
Immunity to Fast Transient Currents Conforming to IEC 61000-4-4 EN 61000-4-4
2 kV: power, AS-i, 24 V, and sensor (level 3)
Immunity to Dissipated Surge Conforming to IEC 61000-4-5 EN 61000-4-5
4 kV/2 kV: power (level 4)2 kV/0.5 kV: AS-i, 24 V, and sensor (level 2)
Immunity to Conducted Radio-Frequency Disturbance Conforming to IEC 61000-4-6 ENV 50 141
10 V/m
Immunity to Radiated Radio-Frequency DisturbanceConforming to IEC 61000-4-3 ENV 50 140 and ENV 50 204 (GSM)
10 V/m
Radio-Conducted and Radio-Radiated Rejection ENV 55 011/CISPR11 (G1) Class B
30˚ 30˚
90˚ 90˚
File E164862CCN: NLDX
File 170MCCN: NLDX.7
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersCabling and Electrical Specifications
113/02 © 2001–2002 Schneider Electric All Rights Reserved
ELECTRICAL SPECIFICATIONS
Cabling
Type of Starter LF1 LF2
Power Supply Cabling
Screw clamp terminals
Minimum Maximum Minimum Maximum
Solid cable1 x16 AWG(1 x 1.5 mm2)
2 x10 AWG(2 x 6 mm2)
1 x16 AWG(1 x 1.5 mm2)
2 x10 AWG(2 x 6 mm2)
Flexible cable without cable end
1 x16 AWG(1 x 1.5 mm2)
2 x10 AWG(2 x 6 mm2)
1 x16 AWG(1 x 1.5 mm2)
2 x10 AWG(2 x 6 mm2)
Flexible cable with cable end
1 x16 AWG(1 x 1.5 mm2)
2 x12 AWG(2 x 4 mm2)
1 x16 AWG(1 x 1.5 mm2)
2 x12 AWG(2 x 4 mm2)
Tightening torque (1)15 lb-in. (1.7 N•m)
15 lb-in. (1.7 N•m)
15 lb-in. (1.7 N•m)
15 lb-in. (1.7 N•m)
Cable gland Clamping capacity 0.39 in. (10 mm) 0.59 in. (15 mm) 0.39 in. (10 mm) 0.59 in. (15 mm)
Motor CablingScrew clamp terminals
Minimum Maximum Minimum Maximum
Solid cable1 x16 AWG(1 x 1.5 mm2)
2 x12 AWG(2 x 4 mm2)
1 x16 AWG(1 x 1.5 mm2)
1 x12 AWG(1 x 4 mm2)
Flexible cable without cable end
1 x16 AWG(1 x 1.5 mm2)
2 x12 AWG(2 x 4 mm2)
1 x16 AWG(1 x 1.5 mm2)
1 x12 AWG(1 x 4 mm2)
Flexible cable with cable end
1 x16 AWG(1 x 1.5 mm2)
1 x16 AWG + 1 x14 AWG(1 x 1.5 mm2) + (1 x 2.5 mm2)
1 x16 AWG(1 x 1.5 mm2)
1 x14 AWG(1 x 2.5 mm2)
Tightening torque (1)7.1 lb-in. (0.8 N•m)
7.1 lb-in. (0.8 N•m)
7.1 lb-in. (0.8 N•m)
7.1 lb-in. (0.8 N•m)
Cable gland Clamping capacity 0.39 in. (10 mm) 0.59 in. (15 mm) 0.39 in. (10 mm) 0.59 in. (15 mm)
Auxiliary 24 V Supply and Output Control Relay Cabling
Screw clamp terminals
Minimum Maximum Minimum Maximum
Solid cable22 AWG (0.5 mm2)
16 AWG (1.5 mm2)
22 AWG (0.5 mm2)
16 AWG (1.5 mm2)
Flexible cable without cable end
22 AWG (0.5 mm2)
16 AWG (1.5 mm2)
22 AWG (0.5 mm2)
16 AWG (1.5 mm2)
Flexible cable with cable end
22 AWG (0.5 mm2)
16 AWG (1.5 mm2)
22 AWG (0.5 mm2)
16 AWG (1.5 mm2)
Tightening torque (2)6.2 lb-in. (0.7 N•m)
6.2 lb-in. (0.7 N•m)
6.2 lb-in. (0.7 N•m)
6.2 lb-in. (0.7 N•m)
Cable gland Clamping capacity 0.39 in. (10 mm) 0.59 in. (15 mm) 0.39 in. (10 mm) 0.59 in. (15 mm)
(1) Phillips No. 2 or flat screwdriver ∅ 5.5.(2) Flat screwdriver ∅ 3.5.
Pole Electrical Specifications
Utilization CategoryConforming to IEC 60947-2 A
Conforming to IEC 60947-4-1 (motor starter) AC-3
Rated Operational Voltage (Ue) Conforming to IEC 60947 415 V
Rated Insulation Voltage (Ui) Conforming to IEC 60947 415 V
Rated Operational Frequency Conforming to IEC 60947 50/60 Hz
Breaking Capacity (Ics and Icu) Conforming to IEC 60947-2230/240 V > 100 kA
400/415 V > 100 kA
Phase Failure Sensitivity Conforming to IEC 60947-4-1 and 7-2-1-5-2 Yes
Other Specifications
Starters with Rotary Control Knob Manual starter/thermal-magnetic protector type GV2P See the Square D Digest [1]
Starters with Pushbutton Control Manual starter/thermal-magnetic protector type GV2P See the Square D Digest [1]
Non-Reversing Starters Contactor LP4K0905BW3 or LP4K1205BW3 See the Square D Digest [1]
Reversing Starters Reversing contactor pair LP5K0905BW3 or LP5K1205BW3 See the Square D Digest [1]
[1] Also see the DigestPlus Selector on the Square D website, www.SquareD.com.
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersSensor, Relay, and Current Consumption Specifications
© 2001–2002 Schneider Electric All Rights Reserved12
3/02
Sensor Inputs
Cabling M12
Nominal Input Values
Voltage 24 Vdc
Maximum current available per sensor 50 mA
Sensor supply (including ripple) 19–30 V
Input Value Limits
At state 1> 12.6 Vdc
> 4.9 mA
At state 0> 5 Vdc
< 2.1 mA
Input Impedance > 2 kΩ
Filtering TimeTypical 7 ms
Maximum 9.8 ms
Maximum Number of Sensors 2
Proximity Sensor Compatibility 2-wire/3-wire Yes
Isolation with respect to AS-i Bus None
Input Type3-wire PNP, 2-wire solid-state, or2-wire limit switches
Output Control Relay
Operating Voltage Limit
24 Vac
24 Vdc
Thermal Current (Ith) at 104 °F (40 °C)
5 A
Response TimeLatching < 10 ms
Unlatching < 10 ms
Contact Type C/O (single pole, double throw, single break)
Integral ProtectionAgainst overloads and short-circuits
None; use of a “fast-blow” fuse recommended as required by NEC and other local codes.
Against DC or AC inductive overvoltagesProtected against transient voltages associated with inductive loads
Isolation
RMS voltage between output and earth or between output and internal logic
1500 Vac, 50/60 Hz, duration 60 s
Insulation resistance between output terminals and AS-i bus
> 1000 MΩ
Current Consumption
Type of Starter
Starter Configured for Supply from AS-i Bus
Starter Configured for Supply from an External 24 Vdc Source
LF1 LF2 LF1 LF2
From the AS-i bus
De-energized 80 mA 90 mA 80 mA 90 mA
Inrush 190 mA 200 mA 80 mA 90 mA
Energized 110 mA 120 mA 80 mA 90 mA
With sensor Sensor consumption (50 mA max.) + 15 mA (signal = 1)
Relay 25 mA
From the External 24 Vdc Supply
De-energized — — 0 0
Inrush — — 110 mA 110 mA
Energized — — 30 mA 30 mA
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersShort Circuit Current
133/02 © 2001–2002 Schneider Electric All Rights Reserved
The starters are suitable for use on a circuit having an available fault current not exceeding the lesser of the value from the table above and:
• the fuse short circuit current rating when protected by a fuse in a group fusing application
• the circuit breaker short circuit current rating when protected by a circuit breaker in group installation
Maximum RMS Short Circuit Current
Adjustable Thermal Trip Setting Range
(amps)Push Button Control
Max RMS, kARotary Handle Control
Max RMS, kA
480 V 600 V 480 V 600 V
0.16–0.25 LF•MM02D•••U 50 30 LF•MP02D•••U 50 30
0.25–0.40 LF•MM03D•••U 50 30 LF•MP03D•••U 50 30
0.40–0.63 LF•MM04D•••U 50 30 LF•MP04D•••U 50 30
0.63–1.0 LF•MM05D•••U 50 30 LF•MP05D•••U 50 30
1.0–1.6 LF•MM06D•••U 50 30 LF•MP06D•••U 50 30
1.6–2.5 LF•MM07D•••U 50 30 LF•MP07D•••U 50 30
2.5–4.0 LF•MM08D•••U 50 30 LF•MP08D•••U 50 30
4.0–6.3 LF•MM10D•••U 50 30 LF•MP10D•••U 50 30
6–10 LF•MM14D•••U 30 30 LF•MP14D•••U 50 30
9–14 LF•MM16D•••U 25 10 LF•MP16D•••U 50 18
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersData Exchange Consumption
© 2001–2002 Schneider Electric All Rights Reserved14
3/02
Data Bus Information Exchange
AS-i profile is 7.D. SW2 is a four slot DIP switch on the AS-i communication board inside the DOL starter.
Input (states)Bit value = 0 = 1
Status D0 (E) Not ready or fault Ready
Status D1 (E) Stopped Running
If SW2 Position 3 = OFF and SW2 Position 4 = OFF
Status D2 (E) Sensor 1 signal absent Sensor 1 signal present
Status D3 (E) Sensor 2 signal absent Sensor 1 signal present
If SW2 Position 3 = ON and SW2 Position 4 = OFF
Status D2 (E) No fault Fault
Status D3 (E) Sensor 1 signal absent Sensor 1 signal present
If SW2 Position 3 = OFF and SW2 Position 4 = ON
Status D2 (E) Sensor 1 signal absent Sensor 1 signal present
Status D3 (E) Command by bus Local command
If SW2 Position 3 = ON and SW2 Position 4 = ON
Status D2 (E) No fault Fault
Status D3 (E) Command by bus Local command
Output (commands)Bit value = 0 = 1
Command D0 (S) Forward stop Forward run
Command D1 (S) Reverse stop (1) Reverse run (1)
Command D2 (S) Auxiliary relay disabled Auxiliary relay enabled
Command D3 (S) Unused Unused
ParametersBit value = 0 = 1 (value by fault)
Parameter P0Watch dog disabled(Status holding)
Watch dog enabled(Default position)
Parameter P1 Run default position Stop default position
Parameter P2 Unused Unused
Parameter P3 Reflex function inhibited Reflex function enabled
(1) Applicable to LF2 model only.
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersDimensions—Rotary Knob Control
153/02 © 2001–2002 Schneider Electric All Rights Reserved
DIMENSIONS
1 or 2-direction starters with rotary control – Metal enclosureWith cable glandLFiMPiiD
With HARTING plug-in connectors (A74) – Metal enclosureLFiMPiiDA74
(1) M12 male connector for connection to the AS-i bus(2) M12 female connector for sensor connection
0.33
(8,5
)0.28(7)
0.51 (13)
7.04 (179)4.92 (125)
7.83
(19
9)9.
05 (
230)
9.64
(24
5)
6.89 (175)
(1)
8.62 (219)
(2)
7.04 (179)
4.92 (125)
(1)
7.83
(19
9)
9.05
(23
0)
9.64
(24
5)
6.89 (175)
8.62 (219) 2.36(60)
0.33
(8,5
)0.28(7)
0.51 (13) (2)
Dim.: in. (mm)
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersDimensions—Rotary Knob Control
© 2001–2002 Schneider Electric All Rights Reserved16
3/02
1 or 2-direction starters with rotary control – Metal enclosureWith cable glandLFiMPiiDA79
With HARTING plug-in connectors (A74) – Metal enclosureLFiMPiiDA79A74
(1) M12 male connector for connection to the AS-i bus(2) M12 female connector for sensor connection
0.33
(8,5
)0.28(7)
0.51 (13) (1) (2)
7.83
(19
9)
9.05
(23
0)
9.64
(24
5)
6.89 (175)
8.62 (219)7.04 (179)
4.92 (125)
7.04 (179)
4.92 (125)
(1) (2)
7.83
(19
9)
0.33
(8,5
)
9.05
(23
0)
9.64
(24
5)
6.89 (175)0.28(7)
0.51 (13)
8.62 (219) 2.36 (60)
Dim.: in. (mm)
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersDimensions—Pushbutton Control
173/02 © 2001–2002 Schneider Electric All Rights Reserved
1 or 2-direction starters with pushbutton control – Metal enclosureWith cable glandLFiMMiiDD
With HARTING plug-in connectors (A74) – Metal enclosureLFiMMiiDA74
(1) M12 male connector for connection to the AS-i bus(2) M12 female connector for sensor connection
0.33
(8,5
)0.28(7)
0.51 (13)
5.70 (145)
4.92 (125)
7.83
(19
9)
9.05
(23
0)
9.64
(24
5)
6.89 (175)
(1)
8.62 (219)
0.33
(8,5
)0.28(7)
0.51 (13)
5.70 (145)
4.92 (125)
(1)
7.83
(19
9)
9.05
(23
0)
9.64
(24
5)
6.89 (175)
8.62 (219) 2.36 (60)
(2)
(2)
Dim.: in. (mm)
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersDimensions—Pushbutton Control
© 2001–2002 Schneider Electric All Rights Reserved18
3/02
1 or 2-direction starters with pushbutton control – Metal enclosureWith cable glandLFiMMiiDA79
With HARTING plug-in connectors (A74) – Metal enclosureLFiMMiiDA79A74
(1) M12 male connector for connection to the AS-i bus(2) M12 female connector for sensor connection
0.33
(8,5
)0.28(7)
0.51 (13) (1) (2)
6.7 (169)
4.92 (125)
7.83
(19
9)
9.05
(23
0)
9.64
(24
5)
6.89 (175)
8.62 (219)
6.7 (169)
4.92 (125)
(1) (2)
7.83
(19
9)
9.05
(23
0)
9.64
(24
5)
6.89 (175)
8.62 (219) 2.36 (60)
0.33
(8,5
)0.28(7)
0.51 (13)
Dim.: in. (mm)
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersConnection Overview
193/02 © 2001–2002 Schneider Electric All Rights Reserved
Connection through Cable Glands
Cable glands with gaskets and M12 connector systems must be installed as shown in order to meet IP55 rating.
Knock-outs on the upper part can be used for other methods of connection (e.g., a 24 V power cable through a cable gland instead of an M12 connector).
J 10
1L1 3L2 5L3
2T1 4T2 6T3
J 11
J 2
24V auxiliary powersupply cable (option)
Auxilary relayoutput cable (option)
Power interconnectioncable (option)
Cable gland
Sensors
Bus AS-i+ 24V auxiliary power
Motorcable
Powercable
Cable gland
Gasket
Cable gland
+ Ð J 5
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersConnection with Plug-In Connectors
© 2001–2002 Schneider Electric All Rights Reserved20
3/02
Connection through Plug-In Connector (HARTING Type)
Configuration of the connectors to be fitted to cables (order separately).
• Telemecanique connection kits:
— power input = LA9LFFM40
— motor connection = LA9LFMM + LA9LFM15 (1.5 mm2) or LA9LFM25 (2.5 mm2)
— crimp tool and insertion tool = AT1PAH
• HARTING connection kits:
Applications
The starter does not require an auxiliary supply to operate the contactors, since current provided by the AS-i bus (yellow cable) is sufficient. Again, this reduces the cabling required.
However, depending on the application, it is possible to supply the contactor coils by an external 24 Vdc source. Selection is made by repositioning a jumper within the starter.
Prospective current consumptions are listed on page 12.
Description Straight backshell Plug to crimp 6 contacts, 400 V
Socket to crimp 6 contacts, 400 V
Male contacts 2.5 mm2 (to crimp)
Female contacts 4 mm2 (to crimp)
Power input female connector
09-30-006-0442 (PG21) 09-30-006-0443 (PG29)
09-33-006-2702 09-33-000-6207
Male connector for motor connection
09-20-003-1440 09-12-005-3001 09-33-000-6102
US
1. Power unit (1)
2. Auxiliary relay (e.g. light column)
3. XZLC122C1: Splitter
4. XZCR1511040Ai: Extension
5. XZCB1ii02i: Black ribbon cable for auxiliary power supply
6. XZCG1403D: Two-cable tap-off box
7. XZCB1ii01i: Yellow ribbon cable for AS-i bus
8. XZCG01205D: Single cable tap-off box
1
M
2
3
4
6
7
7
8 5
LA9LFFM40
LA9LFMM
I
4 x 4
4 x 2.5(4 x 1.5 )
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersSensor Connection
213/02 © 2001–2002 Schneider Electric All Rights Reserved
Sensor Connection
Three types of sensors can be connected directly to the starter using the 5-pin M12 female connector:
The use of sensors equipped with M12 connectors facilitates installation.
For reflex stop (see page 7), you must use sensor 1 (PNP-NO or a dry NO contact on pin 4).
For two-sensor connections, use M12 splitter XZ-LC1220 C1.
For a single-sensor connection, connect directly to the M12 female connector on the enclosure. Use the No. 1 sensor channel.
Auxiliary Relay Output
Single pole, double throw (SPDT), single break contact.
2 1
3 45
2 1
3 45
+2 1
3 45
Limit switch 2-wire sensor 3-wire sensor PNP
Sensor 1
Sensor 2
Sensor 2
Sensor 1
Sensor 2
Sensor 1–
–
1. Power supply +2. No. 2 sensor input3. Power supply –4. No. 1 sensor input5. ground s2 1
3 45
COMNC NOJ2
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersBlock Diagrams
© 2001–2002 Schneider Electric All Rights Reserved22
3/02
Block Diagrams
See “Important Application Information for AS-i DOL Starters” on page 3.
Non-reversing direct-on-line starters with sensor
Reversing direct-on-line starters with sensor
1/L1
– Q
3/L2
5/L3
– KM
U WV
2/T
1
6/T
3
4/T
2
M
– K3
Sensor M12
M12 AS-iAS-i –
AS-i +
– KM
AS
-i –
AS
-i +
24 V
AS
-i
0 V
AS
-i
GV2 open
GV2 tripped
KM
Local Bus
Sensor 1 signal
Sensor 2 signal
NO COM NC
Forward command
Consumption reduction
Auxiliary relay command
AS-i 24 V ext.
AS-i 24 V ext.
24 V ext.
0 V ext.
GV2
GV2 GV2 KM
I
Local/bus
21 0
1/L1
– Q
3/L2
5/L3
– KM1 – KM2
U WV
2/T
1
6/T
3
4/T
2
M
– KM1
– K3
Sensor M12
M12 AS-iAS-i –
AS-i +
– KM2
AS
-i –
AS
-i +
24 V
AS
-i
0 V
AS
-i
GV2 open
GV2 tripped
KM1
KM2
Local Bus
Sensor 1 signal
Sensor 2 signal
NO COM NC
Forward command
Reverse command
Consumption reduction
Auxiliary relay command
AS-i 24 V ext.
AS-i 24 V ext.
24 V ext.
0 V ext.
GV2
GV2 GV2 KM1 KM2
Local Bus
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
AS-i Metal Enclosed DOL StartersWiring Diagrams
233/02 © 2001–2002 Schneider Electric All Rights Reserved
WIRING DIAGRAMS
(1) Short Circuit Protection Device. See “Important Application Information for AS-i DOL Starters” on page 3.
i Starters without sensor with contactor supply via the AS-i bus
i Starters with sensor and 24 V DC auxiliary supply
1L1
3L2
5L3
2T1
4T2
6T3
1L1
3L2
5L3
2T1
4T2
6T3
U WV
M
SCPD (1)
U WV
M
1L1
3L2
5L3
J2 N
CJ2
CO
M
J2 N
O
2T1
4T2
6T3
J5–
J5+
1L1
3L2
5L3
2T1
4T2
6T3
U WV
M
U WV
M
a 24 V
SCPD (1)
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com
Catalog No. 8340CT0101R2/02 March 2002 Replaces 8340CT0101 dated 05/01.© 2001–2002 Schneider Electric All Rights Reserved
Square D Company8001 Highway 64 EastKnightdale, NC 275451-888-SquareD(1-888-778-2733)www.SquareD.com
Schneider Canada Inc.19 Waterman Avenue, M4B 1 Y2Toronto, Ontario1-800-565-6699www.schneider-electric.ca
Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com