www.schneider-electric.com Altivar 212 Variable speed drives for asynchronous motors LONWORKS ® communication manual VW3 A21 212 01/2011 S1A53848

Schneider ATV212

Embed Size (px)

Citation preview

Page 1: Schneider ATV212

Altivar 212Variable speed drives for asynchronous motors

LONWORKSreg communication manualVW3 A21 212012011

S1A

5384

8

wwwschneider-electriccom

The information provided in this documentation contains general descriptions andor technical characteristics of the performance of the products contained herein This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications It is the duty of any such user or integrator to perform the appropriate and complete risk analysis evaluation and testing of the products with respect to the relevant specific application or use thereof Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein If you have any suggestions for improvements or amendments or have found errors in this publication please notify us

No part of this document may be reproduced in any form or by any means electronic or mechanical including photocopying without express written permission of Schneider Electric

All pertinent state regional and local safety regulations must be observed when installing and using this product For reasons of safety and to help ensure compliance with documented system data only the manufacturer should perform repairs to components

When devices are used for applications with technical safety requirements the relevant instructions must be followed

Failure to use Schneider Electric software or approved software with our hardware products may result in injury harm or improper operating results

Failure to observe this information can result in injury or equipment damage

copy 2011 Schneider Electric All rights reserved

2 S1A53848 012011

Table of Contents

Table of Contents

Safety Information 5About the Book 6

Chapter 1 Introduction 9

Chapter 2 Hardware setup 11Receipt 12Opening the drive 13Installing the LonWorks communication card in ATV212 15Hardware description 16Use of open Style Connector 16Description of terminals 17

Chapter 3 Connecting to the bus 19Topology 20Cable routing practices 21Connecting the LonWorks connector 22

Chapter 4 Configuration 23Communication parameters 24Configuration of the control 26Configuring the behaviour on configuration interruption 31

Chapter 5 Diagnostics 33Communication detected fault 34List of type supported by ATV212 Service LED 35Troubleshooting 36

Chapter 6 Functional profile 37Objects supported 38LonMark Node Object profile 38LonMark Variable Speed Motor Drive profile 39

Chapter 7 Network variables and configuration properties 41List of network variables and configuration properties 42Commands and setpoints 44Status and output velocity 48Alarms 51Measurements 52Monitoring of digital inputs 53Monitoring of analog inputs 53Control of digital outputs 53Emergency 54Adjustment 55Parameter access 58Identification 60Network management 61

S1A53848 012011 3

Table of Contents

4 S1A53848 012011

sect

Safety Information

Safety Information

Important Information

NOTICERead these instructions carefully and look at the equipment to become familiar with the device before trying to install operate or maintain it The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure

PLEASE NOTEThe word ldquodriverdquo as used in this manual refers to the controller portion of the adjustable speed drive as defined by NEC

Electrical equipment should be installed operated serviced and maintained only by qualified personnel No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material

The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed

This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety message that follow this symbol to avoid possible injury or death

DANGERDANGER indicates an imminently hazardous situation which if not avoided will result in death or serious injury

WARNINGWARNING indicates a potentially hazardous situation which if not avoided can result in death serious injury or equipment damage

CAUTIONCAUTION indicates a potentially hazardous situation which if not avoided can result in injury or equipment damage

CAUTIONCAUTION used without the safety alert symbol indicates a potentially hazardous situation which if not avoided can result in equipment damage

S1A53848 012011 5

About the Book

About the Book

At a Glance

Document ScopeThe purpose of this document is to

bull install the card in the drivebull show you how to configure the Altivar 212 to use LONWORKSreg for monitoring and control

NOTE Read and understand this document and all related documents (see below) before installing operating or maintaining your ATV212

Validity NoteThis documentation is valid for the Altivar 212 LONWORKS fieldbus

Related Documents

You can download the latest versions of these technical publications and other technical information on wwwschneider-electriccom

Product Related Information

Title of Documentation Reference Number

ATV212 Quick Start S1A53825

ATV212 Installation manual S1A53832

ATV212 Programming manual S1A53838

ATV212 Modbus manual S1A53844

ATV212 Metasys N2 manual S1A53846

ATV212 Apogeacutee FLN P1 manual S1A53847

ATV212 BACnet manual S1A53845

ATV212 other option manuals see wwwschneider-electriccom

DANGERUNINTENDED EQUIPMENT OPERATIONbull Read and understand this manual before installing or operating the Altivar 212 drivebull Any changes made to the parameter settings must be performed by qualified personnelFailure to follow these instructions will result in death or serious injury

6 S1A53848 012011

About the Book

(1) For additional information refer to NEMA ICS 11 (latest edition) ldquoSafety Guidelines for the Application Installation and Maintenance of Solid State Controlrdquo and to NEMA ICS 71 (latest edition) ldquoSafety Standards for Construction and Guide for Selection Installation and Operation of Adjustable-Speed Drive Systemsrdquo

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHbull Read and understand this manual before installing or operating the drive Installation adjustment repair

and maintenance must be performed by qualified personnelbull The user is responsible for compliance with all international and national electrical code requirements with

respect to grounding of all equipmentbull Many parts of this drive including the printed circuit boards operate at the line voltage DO NOT TOUCH

Use only electrically insulated toolsbull DO NOT touch unshielded components or terminal strip screw connections with voltage presentbull DO NOT short across terminals PA+ and PCndash or across the DC bus capacitorsbull Before servicing the drive

- Disconnect all power including external control power that may be present- Place a ldquoDO NOT TURN ONrdquo label on all power disconnects- Lock all power disconnects in the open position- WAIT 15 MINUTES to allow the DC bus capacitors to discharge- Measure the voltage of the DC bus between the PA+ and PCndash terminals to ensure that the voltage is

less than 42 Vdc- If the DC bus capacitors do not discharge completely contact your local Schneider Electric

representative Do not repair or operate the drivebull Install and close all covers before applying power or starting and stopping the driveFailure to follow these instructions will result in death or serious injury

WARNINGDAMAGE DRIVE EQUIPMENT Do not operate or install any drive or drive accessory that appears damagedFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROL bull The designer of any control scheme must consider the potential failure modes of control paths and for

certain critical control functions provide a means to achieve a safe state during and after a path failureExamples of critical control functions are emergency stop and overtravel stop

bull Separate or redundant control paths must be provided for critical control functionsbull System control paths may include communication links Consideration must be given to the implications

of unanticipated transmission delays or failures of the link (1)Failure to follow these instructions can result in death serious injury or equipment damage

S1A53848 012011 7

About the Book

8 S1A53848 012011

S1A53848 012011

Introduction

1

Introduction

Thank you for purchasing the LONWORKSreg option card (VW3 A21 212) for Altivar 212 drive

By installing this card into the Altivar 212 data communication can be made with a host computer or other device via LONWORKSreg network

The communication card has an open-style 3-pin connector for connection to the network It supports free topology (TPFT-10) at 78 kbits

Data exchanges give access to all Altivar 212 functions

bull Control (start stop reset setpoint)bull Monitoring (status current voltage thermal state)bull Diagnostics (alarms)

The LONWORKS resource files (XIF) that provide the network configuration tools (LonMakerreg) with device information are available on wwwschneider-electriccom

LONWORKSreg LONMARKreg LonMakerreg Neuron are trademarks of Echelon Corporation registered in the United States and other countries

LONMARKreg and LONMARKreg Logo are managed granted and used by LONMARKreg International under a license granted by Echelon Corporation

9

Introduction

10 S1A53848 012011

S1A53848 012011

Hardware setup

2

Hardware setup

Whats in this ChapterThis chapter contains the following topics

Topic Page

Receipt 12

Opening the drive 13

Hardware description 16

Use of open Style Connector 16

Description of terminals 17

11

Hardware setup

Receiptbull Check that the card reference printed on the label is the same as that on the delivery note corresponding

to the purchase orderbull Remove the option card from its packaging and check that it has not been damaged in transitbull The LONWORKS card is shipped together with the following accessories On opening the packing case

check to see if the following accessories are contained or not- 1 cabling label- 3 neuron ID labels (barcode EAN128)- 1 screw

12 S1A53848 012011

Hardware setup

Opening the drive

1 Any procedure in this section must be performed when product is powered off

2 Open the ATV212 front cover

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHRead and understand the instructions in About the book chapter before performing the procedure in this section

Failure to follow these instructions will result in death or serious injury

ATV212H products up to 22 kW Turn the screw on the front panel 90deg counter-clockwise to align the dot on the screw with the unlock position

To avoid damaging the screw do not apply excessive force or turn the screw more than 90deg

ATV212H products from 22 kWRemove the screwsLift off the cover

Pull the front panel toward youand swing it open to the left

Screw

S1A53848 012011 13

Hardware setup

ATV212W up to 75 kW ATV212W above 75 kW

14 S1A53848 012011

Hardware setup

Installing the LONWORKS communication card in ATV212

Note To install or remove the terminal board make it slide in or out in parallel with board

DANGERUNINTENDED EQUIPMENT OPERATION

Do not plug or unplug the terminal board while drive is powered

Check the tightening of the mounting screw after any manipulation on the terminal board

Failure to follow these instructions will result in death or serious injury

1 Open the ATV212 front cover remove the terminal board mounting screw and take off the ATV212 standard terminal board See paragraph How to open the front cover page 13 Be careful not to lose the terminal board mounting screw when removed since it may be used again On drives from 075 to 22 kW the board features a plastic tag to hold the mounting screw in place

2 Make the power and control wiring connections before installing communication card

3 Install the LONWORKS communication card Fit the board mounting screw (M3 tapping type) and tighten to 07 to 08 Nm

4 Stick the cabling label for communication card on the standard cabling label stuck on front cover (internal side) ATV212 And stick the communication card nameplate close to the standard nameplate Be careful not to cover slits on the ATV212 enclosure

B A GND SCR

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

P24M

NETA SHLD NETB GE

ON ORKS RL W S1A58023

VIBSink

PTCSource

SW100 SW200

VW3A21212

SERVICE LED

SERVICE SW

S1A53848 012011 15

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 2: Schneider ATV212

The information provided in this documentation contains general descriptions andor technical characteristics of the performance of the products contained herein This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications It is the duty of any such user or integrator to perform the appropriate and complete risk analysis evaluation and testing of the products with respect to the relevant specific application or use thereof Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein If you have any suggestions for improvements or amendments or have found errors in this publication please notify us

No part of this document may be reproduced in any form or by any means electronic or mechanical including photocopying without express written permission of Schneider Electric

All pertinent state regional and local safety regulations must be observed when installing and using this product For reasons of safety and to help ensure compliance with documented system data only the manufacturer should perform repairs to components

When devices are used for applications with technical safety requirements the relevant instructions must be followed

Failure to use Schneider Electric software or approved software with our hardware products may result in injury harm or improper operating results

Failure to observe this information can result in injury or equipment damage

copy 2011 Schneider Electric All rights reserved

2 S1A53848 012011

Table of Contents

Table of Contents

Safety Information 5About the Book 6

Chapter 1 Introduction 9

Chapter 2 Hardware setup 11Receipt 12Opening the drive 13Installing the LonWorks communication card in ATV212 15Hardware description 16Use of open Style Connector 16Description of terminals 17

Chapter 3 Connecting to the bus 19Topology 20Cable routing practices 21Connecting the LonWorks connector 22

Chapter 4 Configuration 23Communication parameters 24Configuration of the control 26Configuring the behaviour on configuration interruption 31

Chapter 5 Diagnostics 33Communication detected fault 34List of type supported by ATV212 Service LED 35Troubleshooting 36

Chapter 6 Functional profile 37Objects supported 38LonMark Node Object profile 38LonMark Variable Speed Motor Drive profile 39

Chapter 7 Network variables and configuration properties 41List of network variables and configuration properties 42Commands and setpoints 44Status and output velocity 48Alarms 51Measurements 52Monitoring of digital inputs 53Monitoring of analog inputs 53Control of digital outputs 53Emergency 54Adjustment 55Parameter access 58Identification 60Network management 61

S1A53848 012011 3

Table of Contents

4 S1A53848 012011

sect

Safety Information

Safety Information

Important Information

NOTICERead these instructions carefully and look at the equipment to become familiar with the device before trying to install operate or maintain it The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure

PLEASE NOTEThe word ldquodriverdquo as used in this manual refers to the controller portion of the adjustable speed drive as defined by NEC

Electrical equipment should be installed operated serviced and maintained only by qualified personnel No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material

The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed

This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety message that follow this symbol to avoid possible injury or death

DANGERDANGER indicates an imminently hazardous situation which if not avoided will result in death or serious injury

WARNINGWARNING indicates a potentially hazardous situation which if not avoided can result in death serious injury or equipment damage

CAUTIONCAUTION indicates a potentially hazardous situation which if not avoided can result in injury or equipment damage

CAUTIONCAUTION used without the safety alert symbol indicates a potentially hazardous situation which if not avoided can result in equipment damage

S1A53848 012011 5

About the Book

About the Book

At a Glance

Document ScopeThe purpose of this document is to

bull install the card in the drivebull show you how to configure the Altivar 212 to use LONWORKSreg for monitoring and control

NOTE Read and understand this document and all related documents (see below) before installing operating or maintaining your ATV212

Validity NoteThis documentation is valid for the Altivar 212 LONWORKS fieldbus

Related Documents

You can download the latest versions of these technical publications and other technical information on wwwschneider-electriccom

Product Related Information

Title of Documentation Reference Number

ATV212 Quick Start S1A53825

ATV212 Installation manual S1A53832

ATV212 Programming manual S1A53838

ATV212 Modbus manual S1A53844

ATV212 Metasys N2 manual S1A53846

ATV212 Apogeacutee FLN P1 manual S1A53847

ATV212 BACnet manual S1A53845

ATV212 other option manuals see wwwschneider-electriccom

DANGERUNINTENDED EQUIPMENT OPERATIONbull Read and understand this manual before installing or operating the Altivar 212 drivebull Any changes made to the parameter settings must be performed by qualified personnelFailure to follow these instructions will result in death or serious injury

6 S1A53848 012011

About the Book

(1) For additional information refer to NEMA ICS 11 (latest edition) ldquoSafety Guidelines for the Application Installation and Maintenance of Solid State Controlrdquo and to NEMA ICS 71 (latest edition) ldquoSafety Standards for Construction and Guide for Selection Installation and Operation of Adjustable-Speed Drive Systemsrdquo

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHbull Read and understand this manual before installing or operating the drive Installation adjustment repair

and maintenance must be performed by qualified personnelbull The user is responsible for compliance with all international and national electrical code requirements with

respect to grounding of all equipmentbull Many parts of this drive including the printed circuit boards operate at the line voltage DO NOT TOUCH

Use only electrically insulated toolsbull DO NOT touch unshielded components or terminal strip screw connections with voltage presentbull DO NOT short across terminals PA+ and PCndash or across the DC bus capacitorsbull Before servicing the drive

- Disconnect all power including external control power that may be present- Place a ldquoDO NOT TURN ONrdquo label on all power disconnects- Lock all power disconnects in the open position- WAIT 15 MINUTES to allow the DC bus capacitors to discharge- Measure the voltage of the DC bus between the PA+ and PCndash terminals to ensure that the voltage is

less than 42 Vdc- If the DC bus capacitors do not discharge completely contact your local Schneider Electric

representative Do not repair or operate the drivebull Install and close all covers before applying power or starting and stopping the driveFailure to follow these instructions will result in death or serious injury

WARNINGDAMAGE DRIVE EQUIPMENT Do not operate or install any drive or drive accessory that appears damagedFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROL bull The designer of any control scheme must consider the potential failure modes of control paths and for

certain critical control functions provide a means to achieve a safe state during and after a path failureExamples of critical control functions are emergency stop and overtravel stop

bull Separate or redundant control paths must be provided for critical control functionsbull System control paths may include communication links Consideration must be given to the implications

of unanticipated transmission delays or failures of the link (1)Failure to follow these instructions can result in death serious injury or equipment damage

S1A53848 012011 7

About the Book

8 S1A53848 012011

S1A53848 012011

Introduction

1

Introduction

Thank you for purchasing the LONWORKSreg option card (VW3 A21 212) for Altivar 212 drive

By installing this card into the Altivar 212 data communication can be made with a host computer or other device via LONWORKSreg network

The communication card has an open-style 3-pin connector for connection to the network It supports free topology (TPFT-10) at 78 kbits

Data exchanges give access to all Altivar 212 functions

bull Control (start stop reset setpoint)bull Monitoring (status current voltage thermal state)bull Diagnostics (alarms)

The LONWORKS resource files (XIF) that provide the network configuration tools (LonMakerreg) with device information are available on wwwschneider-electriccom

LONWORKSreg LONMARKreg LonMakerreg Neuron are trademarks of Echelon Corporation registered in the United States and other countries

LONMARKreg and LONMARKreg Logo are managed granted and used by LONMARKreg International under a license granted by Echelon Corporation

9

Introduction

10 S1A53848 012011

S1A53848 012011

Hardware setup

2

Hardware setup

Whats in this ChapterThis chapter contains the following topics

Topic Page

Receipt 12

Opening the drive 13

Hardware description 16

Use of open Style Connector 16

Description of terminals 17

11

Hardware setup

Receiptbull Check that the card reference printed on the label is the same as that on the delivery note corresponding

to the purchase orderbull Remove the option card from its packaging and check that it has not been damaged in transitbull The LONWORKS card is shipped together with the following accessories On opening the packing case

check to see if the following accessories are contained or not- 1 cabling label- 3 neuron ID labels (barcode EAN128)- 1 screw

12 S1A53848 012011

Hardware setup

Opening the drive

1 Any procedure in this section must be performed when product is powered off

2 Open the ATV212 front cover

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHRead and understand the instructions in About the book chapter before performing the procedure in this section

Failure to follow these instructions will result in death or serious injury

ATV212H products up to 22 kW Turn the screw on the front panel 90deg counter-clockwise to align the dot on the screw with the unlock position

To avoid damaging the screw do not apply excessive force or turn the screw more than 90deg

ATV212H products from 22 kWRemove the screwsLift off the cover

Pull the front panel toward youand swing it open to the left

Screw

S1A53848 012011 13

Hardware setup

ATV212W up to 75 kW ATV212W above 75 kW

14 S1A53848 012011

Hardware setup

Installing the LONWORKS communication card in ATV212

Note To install or remove the terminal board make it slide in or out in parallel with board

DANGERUNINTENDED EQUIPMENT OPERATION

Do not plug or unplug the terminal board while drive is powered

Check the tightening of the mounting screw after any manipulation on the terminal board

Failure to follow these instructions will result in death or serious injury

1 Open the ATV212 front cover remove the terminal board mounting screw and take off the ATV212 standard terminal board See paragraph How to open the front cover page 13 Be careful not to lose the terminal board mounting screw when removed since it may be used again On drives from 075 to 22 kW the board features a plastic tag to hold the mounting screw in place

2 Make the power and control wiring connections before installing communication card

3 Install the LONWORKS communication card Fit the board mounting screw (M3 tapping type) and tighten to 07 to 08 Nm

4 Stick the cabling label for communication card on the standard cabling label stuck on front cover (internal side) ATV212 And stick the communication card nameplate close to the standard nameplate Be careful not to cover slits on the ATV212 enclosure

B A GND SCR

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

P24M

NETA SHLD NETB GE

ON ORKS RL W S1A58023

VIBSink

PTCSource

SW100 SW200

VW3A21212

SERVICE LED

SERVICE SW

S1A53848 012011 15

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN ltFEFF9ad854c18cea51fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e30593002537052376642306e753b8cea3092670059279650306b4fdd306430533068304c3067304d307e3059300230c730b930af30c830c330d730d730ea30f330bf3067306e53705237307e305f306f30d730eb30fc30d57528306b9069305730663044307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e30593002gt KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 3: Schneider ATV212

Table of Contents

Table of Contents

Safety Information 5About the Book 6

Chapter 1 Introduction 9

Chapter 2 Hardware setup 11Receipt 12Opening the drive 13Installing the LonWorks communication card in ATV212 15Hardware description 16Use of open Style Connector 16Description of terminals 17

Chapter 3 Connecting to the bus 19Topology 20Cable routing practices 21Connecting the LonWorks connector 22

Chapter 4 Configuration 23Communication parameters 24Configuration of the control 26Configuring the behaviour on configuration interruption 31

Chapter 5 Diagnostics 33Communication detected fault 34List of type supported by ATV212 Service LED 35Troubleshooting 36

Chapter 6 Functional profile 37Objects supported 38LonMark Node Object profile 38LonMark Variable Speed Motor Drive profile 39

Chapter 7 Network variables and configuration properties 41List of network variables and configuration properties 42Commands and setpoints 44Status and output velocity 48Alarms 51Measurements 52Monitoring of digital inputs 53Monitoring of analog inputs 53Control of digital outputs 53Emergency 54Adjustment 55Parameter access 58Identification 60Network management 61

S1A53848 012011 3

Table of Contents

4 S1A53848 012011

sect

Safety Information

Safety Information

Important Information

NOTICERead these instructions carefully and look at the equipment to become familiar with the device before trying to install operate or maintain it The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure

PLEASE NOTEThe word ldquodriverdquo as used in this manual refers to the controller portion of the adjustable speed drive as defined by NEC

Electrical equipment should be installed operated serviced and maintained only by qualified personnel No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material

The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed

This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety message that follow this symbol to avoid possible injury or death

DANGERDANGER indicates an imminently hazardous situation which if not avoided will result in death or serious injury

WARNINGWARNING indicates a potentially hazardous situation which if not avoided can result in death serious injury or equipment damage

CAUTIONCAUTION indicates a potentially hazardous situation which if not avoided can result in injury or equipment damage

CAUTIONCAUTION used without the safety alert symbol indicates a potentially hazardous situation which if not avoided can result in equipment damage

S1A53848 012011 5

About the Book

About the Book

At a Glance

Document ScopeThe purpose of this document is to

bull install the card in the drivebull show you how to configure the Altivar 212 to use LONWORKSreg for monitoring and control

NOTE Read and understand this document and all related documents (see below) before installing operating or maintaining your ATV212

Validity NoteThis documentation is valid for the Altivar 212 LONWORKS fieldbus

Related Documents

You can download the latest versions of these technical publications and other technical information on wwwschneider-electriccom

Product Related Information

Title of Documentation Reference Number

ATV212 Quick Start S1A53825

ATV212 Installation manual S1A53832

ATV212 Programming manual S1A53838

ATV212 Modbus manual S1A53844

ATV212 Metasys N2 manual S1A53846

ATV212 Apogeacutee FLN P1 manual S1A53847

ATV212 BACnet manual S1A53845

ATV212 other option manuals see wwwschneider-electriccom

DANGERUNINTENDED EQUIPMENT OPERATIONbull Read and understand this manual before installing or operating the Altivar 212 drivebull Any changes made to the parameter settings must be performed by qualified personnelFailure to follow these instructions will result in death or serious injury

6 S1A53848 012011

About the Book

(1) For additional information refer to NEMA ICS 11 (latest edition) ldquoSafety Guidelines for the Application Installation and Maintenance of Solid State Controlrdquo and to NEMA ICS 71 (latest edition) ldquoSafety Standards for Construction and Guide for Selection Installation and Operation of Adjustable-Speed Drive Systemsrdquo

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHbull Read and understand this manual before installing or operating the drive Installation adjustment repair

and maintenance must be performed by qualified personnelbull The user is responsible for compliance with all international and national electrical code requirements with

respect to grounding of all equipmentbull Many parts of this drive including the printed circuit boards operate at the line voltage DO NOT TOUCH

Use only electrically insulated toolsbull DO NOT touch unshielded components or terminal strip screw connections with voltage presentbull DO NOT short across terminals PA+ and PCndash or across the DC bus capacitorsbull Before servicing the drive

- Disconnect all power including external control power that may be present- Place a ldquoDO NOT TURN ONrdquo label on all power disconnects- Lock all power disconnects in the open position- WAIT 15 MINUTES to allow the DC bus capacitors to discharge- Measure the voltage of the DC bus between the PA+ and PCndash terminals to ensure that the voltage is

less than 42 Vdc- If the DC bus capacitors do not discharge completely contact your local Schneider Electric

representative Do not repair or operate the drivebull Install and close all covers before applying power or starting and stopping the driveFailure to follow these instructions will result in death or serious injury

WARNINGDAMAGE DRIVE EQUIPMENT Do not operate or install any drive or drive accessory that appears damagedFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROL bull The designer of any control scheme must consider the potential failure modes of control paths and for

certain critical control functions provide a means to achieve a safe state during and after a path failureExamples of critical control functions are emergency stop and overtravel stop

bull Separate or redundant control paths must be provided for critical control functionsbull System control paths may include communication links Consideration must be given to the implications

of unanticipated transmission delays or failures of the link (1)Failure to follow these instructions can result in death serious injury or equipment damage

S1A53848 012011 7

About the Book

8 S1A53848 012011

S1A53848 012011

Introduction

1

Introduction

Thank you for purchasing the LONWORKSreg option card (VW3 A21 212) for Altivar 212 drive

By installing this card into the Altivar 212 data communication can be made with a host computer or other device via LONWORKSreg network

The communication card has an open-style 3-pin connector for connection to the network It supports free topology (TPFT-10) at 78 kbits

Data exchanges give access to all Altivar 212 functions

bull Control (start stop reset setpoint)bull Monitoring (status current voltage thermal state)bull Diagnostics (alarms)

The LONWORKS resource files (XIF) that provide the network configuration tools (LonMakerreg) with device information are available on wwwschneider-electriccom

LONWORKSreg LONMARKreg LonMakerreg Neuron are trademarks of Echelon Corporation registered in the United States and other countries

LONMARKreg and LONMARKreg Logo are managed granted and used by LONMARKreg International under a license granted by Echelon Corporation

9

Introduction

10 S1A53848 012011

S1A53848 012011

Hardware setup

2

Hardware setup

Whats in this ChapterThis chapter contains the following topics

Topic Page

Receipt 12

Opening the drive 13

Hardware description 16

Use of open Style Connector 16

Description of terminals 17

11

Hardware setup

Receiptbull Check that the card reference printed on the label is the same as that on the delivery note corresponding

to the purchase orderbull Remove the option card from its packaging and check that it has not been damaged in transitbull The LONWORKS card is shipped together with the following accessories On opening the packing case

check to see if the following accessories are contained or not- 1 cabling label- 3 neuron ID labels (barcode EAN128)- 1 screw

12 S1A53848 012011

Hardware setup

Opening the drive

1 Any procedure in this section must be performed when product is powered off

2 Open the ATV212 front cover

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHRead and understand the instructions in About the book chapter before performing the procedure in this section

Failure to follow these instructions will result in death or serious injury

ATV212H products up to 22 kW Turn the screw on the front panel 90deg counter-clockwise to align the dot on the screw with the unlock position

To avoid damaging the screw do not apply excessive force or turn the screw more than 90deg

ATV212H products from 22 kWRemove the screwsLift off the cover

Pull the front panel toward youand swing it open to the left

Screw

S1A53848 012011 13

Hardware setup

ATV212W up to 75 kW ATV212W above 75 kW

14 S1A53848 012011

Hardware setup

Installing the LONWORKS communication card in ATV212

Note To install or remove the terminal board make it slide in or out in parallel with board

DANGERUNINTENDED EQUIPMENT OPERATION

Do not plug or unplug the terminal board while drive is powered

Check the tightening of the mounting screw after any manipulation on the terminal board

Failure to follow these instructions will result in death or serious injury

1 Open the ATV212 front cover remove the terminal board mounting screw and take off the ATV212 standard terminal board See paragraph How to open the front cover page 13 Be careful not to lose the terminal board mounting screw when removed since it may be used again On drives from 075 to 22 kW the board features a plastic tag to hold the mounting screw in place

2 Make the power and control wiring connections before installing communication card

3 Install the LONWORKS communication card Fit the board mounting screw (M3 tapping type) and tighten to 07 to 08 Nm

4 Stick the cabling label for communication card on the standard cabling label stuck on front cover (internal side) ATV212 And stick the communication card nameplate close to the standard nameplate Be careful not to cover slits on the ATV212 enclosure

B A GND SCR

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

P24M

NETA SHLD NETB GE

ON ORKS RL W S1A58023

VIBSink

PTCSource

SW100 SW200

VW3A21212

SERVICE LED

SERVICE SW

S1A53848 012011 15

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 4: Schneider ATV212

Table of Contents

4 S1A53848 012011

sect

Safety Information

Safety Information

Important Information

NOTICERead these instructions carefully and look at the equipment to become familiar with the device before trying to install operate or maintain it The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure

PLEASE NOTEThe word ldquodriverdquo as used in this manual refers to the controller portion of the adjustable speed drive as defined by NEC

Electrical equipment should be installed operated serviced and maintained only by qualified personnel No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material

The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed

This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety message that follow this symbol to avoid possible injury or death

DANGERDANGER indicates an imminently hazardous situation which if not avoided will result in death or serious injury

WARNINGWARNING indicates a potentially hazardous situation which if not avoided can result in death serious injury or equipment damage

CAUTIONCAUTION indicates a potentially hazardous situation which if not avoided can result in injury or equipment damage

CAUTIONCAUTION used without the safety alert symbol indicates a potentially hazardous situation which if not avoided can result in equipment damage

S1A53848 012011 5

About the Book

About the Book

At a Glance

Document ScopeThe purpose of this document is to

bull install the card in the drivebull show you how to configure the Altivar 212 to use LONWORKSreg for monitoring and control

NOTE Read and understand this document and all related documents (see below) before installing operating or maintaining your ATV212

Validity NoteThis documentation is valid for the Altivar 212 LONWORKS fieldbus

Related Documents

You can download the latest versions of these technical publications and other technical information on wwwschneider-electriccom

Product Related Information

Title of Documentation Reference Number

ATV212 Quick Start S1A53825

ATV212 Installation manual S1A53832

ATV212 Programming manual S1A53838

ATV212 Modbus manual S1A53844

ATV212 Metasys N2 manual S1A53846

ATV212 Apogeacutee FLN P1 manual S1A53847

ATV212 BACnet manual S1A53845

ATV212 other option manuals see wwwschneider-electriccom

DANGERUNINTENDED EQUIPMENT OPERATIONbull Read and understand this manual before installing or operating the Altivar 212 drivebull Any changes made to the parameter settings must be performed by qualified personnelFailure to follow these instructions will result in death or serious injury

6 S1A53848 012011

About the Book

(1) For additional information refer to NEMA ICS 11 (latest edition) ldquoSafety Guidelines for the Application Installation and Maintenance of Solid State Controlrdquo and to NEMA ICS 71 (latest edition) ldquoSafety Standards for Construction and Guide for Selection Installation and Operation of Adjustable-Speed Drive Systemsrdquo

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHbull Read and understand this manual before installing or operating the drive Installation adjustment repair

and maintenance must be performed by qualified personnelbull The user is responsible for compliance with all international and national electrical code requirements with

respect to grounding of all equipmentbull Many parts of this drive including the printed circuit boards operate at the line voltage DO NOT TOUCH

Use only electrically insulated toolsbull DO NOT touch unshielded components or terminal strip screw connections with voltage presentbull DO NOT short across terminals PA+ and PCndash or across the DC bus capacitorsbull Before servicing the drive

- Disconnect all power including external control power that may be present- Place a ldquoDO NOT TURN ONrdquo label on all power disconnects- Lock all power disconnects in the open position- WAIT 15 MINUTES to allow the DC bus capacitors to discharge- Measure the voltage of the DC bus between the PA+ and PCndash terminals to ensure that the voltage is

less than 42 Vdc- If the DC bus capacitors do not discharge completely contact your local Schneider Electric

representative Do not repair or operate the drivebull Install and close all covers before applying power or starting and stopping the driveFailure to follow these instructions will result in death or serious injury

WARNINGDAMAGE DRIVE EQUIPMENT Do not operate or install any drive or drive accessory that appears damagedFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROL bull The designer of any control scheme must consider the potential failure modes of control paths and for

certain critical control functions provide a means to achieve a safe state during and after a path failureExamples of critical control functions are emergency stop and overtravel stop

bull Separate or redundant control paths must be provided for critical control functionsbull System control paths may include communication links Consideration must be given to the implications

of unanticipated transmission delays or failures of the link (1)Failure to follow these instructions can result in death serious injury or equipment damage

S1A53848 012011 7

About the Book

8 S1A53848 012011

S1A53848 012011

Introduction

1

Introduction

Thank you for purchasing the LONWORKSreg option card (VW3 A21 212) for Altivar 212 drive

By installing this card into the Altivar 212 data communication can be made with a host computer or other device via LONWORKSreg network

The communication card has an open-style 3-pin connector for connection to the network It supports free topology (TPFT-10) at 78 kbits

Data exchanges give access to all Altivar 212 functions

bull Control (start stop reset setpoint)bull Monitoring (status current voltage thermal state)bull Diagnostics (alarms)

The LONWORKS resource files (XIF) that provide the network configuration tools (LonMakerreg) with device information are available on wwwschneider-electriccom

LONWORKSreg LONMARKreg LonMakerreg Neuron are trademarks of Echelon Corporation registered in the United States and other countries

LONMARKreg and LONMARKreg Logo are managed granted and used by LONMARKreg International under a license granted by Echelon Corporation

9

Introduction

10 S1A53848 012011

S1A53848 012011

Hardware setup

2

Hardware setup

Whats in this ChapterThis chapter contains the following topics

Topic Page

Receipt 12

Opening the drive 13

Hardware description 16

Use of open Style Connector 16

Description of terminals 17

11

Hardware setup

Receiptbull Check that the card reference printed on the label is the same as that on the delivery note corresponding

to the purchase orderbull Remove the option card from its packaging and check that it has not been damaged in transitbull The LONWORKS card is shipped together with the following accessories On opening the packing case

check to see if the following accessories are contained or not- 1 cabling label- 3 neuron ID labels (barcode EAN128)- 1 screw

12 S1A53848 012011

Hardware setup

Opening the drive

1 Any procedure in this section must be performed when product is powered off

2 Open the ATV212 front cover

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHRead and understand the instructions in About the book chapter before performing the procedure in this section

Failure to follow these instructions will result in death or serious injury

ATV212H products up to 22 kW Turn the screw on the front panel 90deg counter-clockwise to align the dot on the screw with the unlock position

To avoid damaging the screw do not apply excessive force or turn the screw more than 90deg

ATV212H products from 22 kWRemove the screwsLift off the cover

Pull the front panel toward youand swing it open to the left

Screw

S1A53848 012011 13

Hardware setup

ATV212W up to 75 kW ATV212W above 75 kW

14 S1A53848 012011

Hardware setup

Installing the LONWORKS communication card in ATV212

Note To install or remove the terminal board make it slide in or out in parallel with board

DANGERUNINTENDED EQUIPMENT OPERATION

Do not plug or unplug the terminal board while drive is powered

Check the tightening of the mounting screw after any manipulation on the terminal board

Failure to follow these instructions will result in death or serious injury

1 Open the ATV212 front cover remove the terminal board mounting screw and take off the ATV212 standard terminal board See paragraph How to open the front cover page 13 Be careful not to lose the terminal board mounting screw when removed since it may be used again On drives from 075 to 22 kW the board features a plastic tag to hold the mounting screw in place

2 Make the power and control wiring connections before installing communication card

3 Install the LONWORKS communication card Fit the board mounting screw (M3 tapping type) and tighten to 07 to 08 Nm

4 Stick the cabling label for communication card on the standard cabling label stuck on front cover (internal side) ATV212 And stick the communication card nameplate close to the standard nameplate Be careful not to cover slits on the ATV212 enclosure

B A GND SCR

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

P24M

NETA SHLD NETB GE

ON ORKS RL W S1A58023

VIBSink

PTCSource

SW100 SW200

VW3A21212

SERVICE LED

SERVICE SW

S1A53848 012011 15

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 5: Schneider ATV212

sect

Safety Information

Safety Information

Important Information

NOTICERead these instructions carefully and look at the equipment to become familiar with the device before trying to install operate or maintain it The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure

PLEASE NOTEThe word ldquodriverdquo as used in this manual refers to the controller portion of the adjustable speed drive as defined by NEC

Electrical equipment should be installed operated serviced and maintained only by qualified personnel No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material

The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed

This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety message that follow this symbol to avoid possible injury or death

DANGERDANGER indicates an imminently hazardous situation which if not avoided will result in death or serious injury

WARNINGWARNING indicates a potentially hazardous situation which if not avoided can result in death serious injury or equipment damage

CAUTIONCAUTION indicates a potentially hazardous situation which if not avoided can result in injury or equipment damage

CAUTIONCAUTION used without the safety alert symbol indicates a potentially hazardous situation which if not avoided can result in equipment damage

S1A53848 012011 5

About the Book

About the Book

At a Glance

Document ScopeThe purpose of this document is to

bull install the card in the drivebull show you how to configure the Altivar 212 to use LONWORKSreg for monitoring and control

NOTE Read and understand this document and all related documents (see below) before installing operating or maintaining your ATV212

Validity NoteThis documentation is valid for the Altivar 212 LONWORKS fieldbus

Related Documents

You can download the latest versions of these technical publications and other technical information on wwwschneider-electriccom

Product Related Information

Title of Documentation Reference Number

ATV212 Quick Start S1A53825

ATV212 Installation manual S1A53832

ATV212 Programming manual S1A53838

ATV212 Modbus manual S1A53844

ATV212 Metasys N2 manual S1A53846

ATV212 Apogeacutee FLN P1 manual S1A53847

ATV212 BACnet manual S1A53845

ATV212 other option manuals see wwwschneider-electriccom

DANGERUNINTENDED EQUIPMENT OPERATIONbull Read and understand this manual before installing or operating the Altivar 212 drivebull Any changes made to the parameter settings must be performed by qualified personnelFailure to follow these instructions will result in death or serious injury

6 S1A53848 012011

About the Book

(1) For additional information refer to NEMA ICS 11 (latest edition) ldquoSafety Guidelines for the Application Installation and Maintenance of Solid State Controlrdquo and to NEMA ICS 71 (latest edition) ldquoSafety Standards for Construction and Guide for Selection Installation and Operation of Adjustable-Speed Drive Systemsrdquo

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHbull Read and understand this manual before installing or operating the drive Installation adjustment repair

and maintenance must be performed by qualified personnelbull The user is responsible for compliance with all international and national electrical code requirements with

respect to grounding of all equipmentbull Many parts of this drive including the printed circuit boards operate at the line voltage DO NOT TOUCH

Use only electrically insulated toolsbull DO NOT touch unshielded components or terminal strip screw connections with voltage presentbull DO NOT short across terminals PA+ and PCndash or across the DC bus capacitorsbull Before servicing the drive

- Disconnect all power including external control power that may be present- Place a ldquoDO NOT TURN ONrdquo label on all power disconnects- Lock all power disconnects in the open position- WAIT 15 MINUTES to allow the DC bus capacitors to discharge- Measure the voltage of the DC bus between the PA+ and PCndash terminals to ensure that the voltage is

less than 42 Vdc- If the DC bus capacitors do not discharge completely contact your local Schneider Electric

representative Do not repair or operate the drivebull Install and close all covers before applying power or starting and stopping the driveFailure to follow these instructions will result in death or serious injury

WARNINGDAMAGE DRIVE EQUIPMENT Do not operate or install any drive or drive accessory that appears damagedFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROL bull The designer of any control scheme must consider the potential failure modes of control paths and for

certain critical control functions provide a means to achieve a safe state during and after a path failureExamples of critical control functions are emergency stop and overtravel stop

bull Separate or redundant control paths must be provided for critical control functionsbull System control paths may include communication links Consideration must be given to the implications

of unanticipated transmission delays or failures of the link (1)Failure to follow these instructions can result in death serious injury or equipment damage

S1A53848 012011 7

About the Book

8 S1A53848 012011

S1A53848 012011

Introduction

1

Introduction

Thank you for purchasing the LONWORKSreg option card (VW3 A21 212) for Altivar 212 drive

By installing this card into the Altivar 212 data communication can be made with a host computer or other device via LONWORKSreg network

The communication card has an open-style 3-pin connector for connection to the network It supports free topology (TPFT-10) at 78 kbits

Data exchanges give access to all Altivar 212 functions

bull Control (start stop reset setpoint)bull Monitoring (status current voltage thermal state)bull Diagnostics (alarms)

The LONWORKS resource files (XIF) that provide the network configuration tools (LonMakerreg) with device information are available on wwwschneider-electriccom

LONWORKSreg LONMARKreg LonMakerreg Neuron are trademarks of Echelon Corporation registered in the United States and other countries

LONMARKreg and LONMARKreg Logo are managed granted and used by LONMARKreg International under a license granted by Echelon Corporation

9

Introduction

10 S1A53848 012011

S1A53848 012011

Hardware setup

2

Hardware setup

Whats in this ChapterThis chapter contains the following topics

Topic Page

Receipt 12

Opening the drive 13

Hardware description 16

Use of open Style Connector 16

Description of terminals 17

11

Hardware setup

Receiptbull Check that the card reference printed on the label is the same as that on the delivery note corresponding

to the purchase orderbull Remove the option card from its packaging and check that it has not been damaged in transitbull The LONWORKS card is shipped together with the following accessories On opening the packing case

check to see if the following accessories are contained or not- 1 cabling label- 3 neuron ID labels (barcode EAN128)- 1 screw

12 S1A53848 012011

Hardware setup

Opening the drive

1 Any procedure in this section must be performed when product is powered off

2 Open the ATV212 front cover

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHRead and understand the instructions in About the book chapter before performing the procedure in this section

Failure to follow these instructions will result in death or serious injury

ATV212H products up to 22 kW Turn the screw on the front panel 90deg counter-clockwise to align the dot on the screw with the unlock position

To avoid damaging the screw do not apply excessive force or turn the screw more than 90deg

ATV212H products from 22 kWRemove the screwsLift off the cover

Pull the front panel toward youand swing it open to the left

Screw

S1A53848 012011 13

Hardware setup

ATV212W up to 75 kW ATV212W above 75 kW

14 S1A53848 012011

Hardware setup

Installing the LONWORKS communication card in ATV212

Note To install or remove the terminal board make it slide in or out in parallel with board

DANGERUNINTENDED EQUIPMENT OPERATION

Do not plug or unplug the terminal board while drive is powered

Check the tightening of the mounting screw after any manipulation on the terminal board

Failure to follow these instructions will result in death or serious injury

1 Open the ATV212 front cover remove the terminal board mounting screw and take off the ATV212 standard terminal board See paragraph How to open the front cover page 13 Be careful not to lose the terminal board mounting screw when removed since it may be used again On drives from 075 to 22 kW the board features a plastic tag to hold the mounting screw in place

2 Make the power and control wiring connections before installing communication card

3 Install the LONWORKS communication card Fit the board mounting screw (M3 tapping type) and tighten to 07 to 08 Nm

4 Stick the cabling label for communication card on the standard cabling label stuck on front cover (internal side) ATV212 And stick the communication card nameplate close to the standard nameplate Be careful not to cover slits on the ATV212 enclosure

B A GND SCR

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

P24M

NETA SHLD NETB GE

ON ORKS RL W S1A58023

VIBSink

PTCSource

SW100 SW200

VW3A21212

SERVICE LED

SERVICE SW

S1A53848 012011 15

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 6: Schneider ATV212

About the Book

About the Book

At a Glance

Document ScopeThe purpose of this document is to

bull install the card in the drivebull show you how to configure the Altivar 212 to use LONWORKSreg for monitoring and control

NOTE Read and understand this document and all related documents (see below) before installing operating or maintaining your ATV212

Validity NoteThis documentation is valid for the Altivar 212 LONWORKS fieldbus

Related Documents

You can download the latest versions of these technical publications and other technical information on wwwschneider-electriccom

Product Related Information

Title of Documentation Reference Number

ATV212 Quick Start S1A53825

ATV212 Installation manual S1A53832

ATV212 Programming manual S1A53838

ATV212 Modbus manual S1A53844

ATV212 Metasys N2 manual S1A53846

ATV212 Apogeacutee FLN P1 manual S1A53847

ATV212 BACnet manual S1A53845

ATV212 other option manuals see wwwschneider-electriccom

DANGERUNINTENDED EQUIPMENT OPERATIONbull Read and understand this manual before installing or operating the Altivar 212 drivebull Any changes made to the parameter settings must be performed by qualified personnelFailure to follow these instructions will result in death or serious injury

6 S1A53848 012011

About the Book

(1) For additional information refer to NEMA ICS 11 (latest edition) ldquoSafety Guidelines for the Application Installation and Maintenance of Solid State Controlrdquo and to NEMA ICS 71 (latest edition) ldquoSafety Standards for Construction and Guide for Selection Installation and Operation of Adjustable-Speed Drive Systemsrdquo

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHbull Read and understand this manual before installing or operating the drive Installation adjustment repair

and maintenance must be performed by qualified personnelbull The user is responsible for compliance with all international and national electrical code requirements with

respect to grounding of all equipmentbull Many parts of this drive including the printed circuit boards operate at the line voltage DO NOT TOUCH

Use only electrically insulated toolsbull DO NOT touch unshielded components or terminal strip screw connections with voltage presentbull DO NOT short across terminals PA+ and PCndash or across the DC bus capacitorsbull Before servicing the drive

- Disconnect all power including external control power that may be present- Place a ldquoDO NOT TURN ONrdquo label on all power disconnects- Lock all power disconnects in the open position- WAIT 15 MINUTES to allow the DC bus capacitors to discharge- Measure the voltage of the DC bus between the PA+ and PCndash terminals to ensure that the voltage is

less than 42 Vdc- If the DC bus capacitors do not discharge completely contact your local Schneider Electric

representative Do not repair or operate the drivebull Install and close all covers before applying power or starting and stopping the driveFailure to follow these instructions will result in death or serious injury

WARNINGDAMAGE DRIVE EQUIPMENT Do not operate or install any drive or drive accessory that appears damagedFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROL bull The designer of any control scheme must consider the potential failure modes of control paths and for

certain critical control functions provide a means to achieve a safe state during and after a path failureExamples of critical control functions are emergency stop and overtravel stop

bull Separate or redundant control paths must be provided for critical control functionsbull System control paths may include communication links Consideration must be given to the implications

of unanticipated transmission delays or failures of the link (1)Failure to follow these instructions can result in death serious injury or equipment damage

S1A53848 012011 7

About the Book

8 S1A53848 012011

S1A53848 012011

Introduction

1

Introduction

Thank you for purchasing the LONWORKSreg option card (VW3 A21 212) for Altivar 212 drive

By installing this card into the Altivar 212 data communication can be made with a host computer or other device via LONWORKSreg network

The communication card has an open-style 3-pin connector for connection to the network It supports free topology (TPFT-10) at 78 kbits

Data exchanges give access to all Altivar 212 functions

bull Control (start stop reset setpoint)bull Monitoring (status current voltage thermal state)bull Diagnostics (alarms)

The LONWORKS resource files (XIF) that provide the network configuration tools (LonMakerreg) with device information are available on wwwschneider-electriccom

LONWORKSreg LONMARKreg LonMakerreg Neuron are trademarks of Echelon Corporation registered in the United States and other countries

LONMARKreg and LONMARKreg Logo are managed granted and used by LONMARKreg International under a license granted by Echelon Corporation

9

Introduction

10 S1A53848 012011

S1A53848 012011

Hardware setup

2

Hardware setup

Whats in this ChapterThis chapter contains the following topics

Topic Page

Receipt 12

Opening the drive 13

Hardware description 16

Use of open Style Connector 16

Description of terminals 17

11

Hardware setup

Receiptbull Check that the card reference printed on the label is the same as that on the delivery note corresponding

to the purchase orderbull Remove the option card from its packaging and check that it has not been damaged in transitbull The LONWORKS card is shipped together with the following accessories On opening the packing case

check to see if the following accessories are contained or not- 1 cabling label- 3 neuron ID labels (barcode EAN128)- 1 screw

12 S1A53848 012011

Hardware setup

Opening the drive

1 Any procedure in this section must be performed when product is powered off

2 Open the ATV212 front cover

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHRead and understand the instructions in About the book chapter before performing the procedure in this section

Failure to follow these instructions will result in death or serious injury

ATV212H products up to 22 kW Turn the screw on the front panel 90deg counter-clockwise to align the dot on the screw with the unlock position

To avoid damaging the screw do not apply excessive force or turn the screw more than 90deg

ATV212H products from 22 kWRemove the screwsLift off the cover

Pull the front panel toward youand swing it open to the left

Screw

S1A53848 012011 13

Hardware setup

ATV212W up to 75 kW ATV212W above 75 kW

14 S1A53848 012011

Hardware setup

Installing the LONWORKS communication card in ATV212

Note To install or remove the terminal board make it slide in or out in parallel with board

DANGERUNINTENDED EQUIPMENT OPERATION

Do not plug or unplug the terminal board while drive is powered

Check the tightening of the mounting screw after any manipulation on the terminal board

Failure to follow these instructions will result in death or serious injury

1 Open the ATV212 front cover remove the terminal board mounting screw and take off the ATV212 standard terminal board See paragraph How to open the front cover page 13 Be careful not to lose the terminal board mounting screw when removed since it may be used again On drives from 075 to 22 kW the board features a plastic tag to hold the mounting screw in place

2 Make the power and control wiring connections before installing communication card

3 Install the LONWORKS communication card Fit the board mounting screw (M3 tapping type) and tighten to 07 to 08 Nm

4 Stick the cabling label for communication card on the standard cabling label stuck on front cover (internal side) ATV212 And stick the communication card nameplate close to the standard nameplate Be careful not to cover slits on the ATV212 enclosure

B A GND SCR

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

P24M

NETA SHLD NETB GE

ON ORKS RL W S1A58023

VIBSink

PTCSource

SW100 SW200

VW3A21212

SERVICE LED

SERVICE SW

S1A53848 012011 15

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002000740069006c0020006b00760061006c00690074006500740073007500640073006b007200690076006e0069006e006700200065006c006c006500720020006b006f007200720065006b007400750072006c00e60073006e0069006e0067002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 7: Schneider ATV212

About the Book

(1) For additional information refer to NEMA ICS 11 (latest edition) ldquoSafety Guidelines for the Application Installation and Maintenance of Solid State Controlrdquo and to NEMA ICS 71 (latest edition) ldquoSafety Standards for Construction and Guide for Selection Installation and Operation of Adjustable-Speed Drive Systemsrdquo

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHbull Read and understand this manual before installing or operating the drive Installation adjustment repair

and maintenance must be performed by qualified personnelbull The user is responsible for compliance with all international and national electrical code requirements with

respect to grounding of all equipmentbull Many parts of this drive including the printed circuit boards operate at the line voltage DO NOT TOUCH

Use only electrically insulated toolsbull DO NOT touch unshielded components or terminal strip screw connections with voltage presentbull DO NOT short across terminals PA+ and PCndash or across the DC bus capacitorsbull Before servicing the drive

- Disconnect all power including external control power that may be present- Place a ldquoDO NOT TURN ONrdquo label on all power disconnects- Lock all power disconnects in the open position- WAIT 15 MINUTES to allow the DC bus capacitors to discharge- Measure the voltage of the DC bus between the PA+ and PCndash terminals to ensure that the voltage is

less than 42 Vdc- If the DC bus capacitors do not discharge completely contact your local Schneider Electric

representative Do not repair or operate the drivebull Install and close all covers before applying power or starting and stopping the driveFailure to follow these instructions will result in death or serious injury

WARNINGDAMAGE DRIVE EQUIPMENT Do not operate or install any drive or drive accessory that appears damagedFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROL bull The designer of any control scheme must consider the potential failure modes of control paths and for

certain critical control functions provide a means to achieve a safe state during and after a path failureExamples of critical control functions are emergency stop and overtravel stop

bull Separate or redundant control paths must be provided for critical control functionsbull System control paths may include communication links Consideration must be given to the implications

of unanticipated transmission delays or failures of the link (1)Failure to follow these instructions can result in death serious injury or equipment damage

S1A53848 012011 7

About the Book

8 S1A53848 012011

S1A53848 012011

Introduction

1

Introduction

Thank you for purchasing the LONWORKSreg option card (VW3 A21 212) for Altivar 212 drive

By installing this card into the Altivar 212 data communication can be made with a host computer or other device via LONWORKSreg network

The communication card has an open-style 3-pin connector for connection to the network It supports free topology (TPFT-10) at 78 kbits

Data exchanges give access to all Altivar 212 functions

bull Control (start stop reset setpoint)bull Monitoring (status current voltage thermal state)bull Diagnostics (alarms)

The LONWORKS resource files (XIF) that provide the network configuration tools (LonMakerreg) with device information are available on wwwschneider-electriccom

LONWORKSreg LONMARKreg LonMakerreg Neuron are trademarks of Echelon Corporation registered in the United States and other countries

LONMARKreg and LONMARKreg Logo are managed granted and used by LONMARKreg International under a license granted by Echelon Corporation

9

Introduction

10 S1A53848 012011

S1A53848 012011

Hardware setup

2

Hardware setup

Whats in this ChapterThis chapter contains the following topics

Topic Page

Receipt 12

Opening the drive 13

Hardware description 16

Use of open Style Connector 16

Description of terminals 17

11

Hardware setup

Receiptbull Check that the card reference printed on the label is the same as that on the delivery note corresponding

to the purchase orderbull Remove the option card from its packaging and check that it has not been damaged in transitbull The LONWORKS card is shipped together with the following accessories On opening the packing case

check to see if the following accessories are contained or not- 1 cabling label- 3 neuron ID labels (barcode EAN128)- 1 screw

12 S1A53848 012011

Hardware setup

Opening the drive

1 Any procedure in this section must be performed when product is powered off

2 Open the ATV212 front cover

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHRead and understand the instructions in About the book chapter before performing the procedure in this section

Failure to follow these instructions will result in death or serious injury

ATV212H products up to 22 kW Turn the screw on the front panel 90deg counter-clockwise to align the dot on the screw with the unlock position

To avoid damaging the screw do not apply excessive force or turn the screw more than 90deg

ATV212H products from 22 kWRemove the screwsLift off the cover

Pull the front panel toward youand swing it open to the left

Screw

S1A53848 012011 13

Hardware setup

ATV212W up to 75 kW ATV212W above 75 kW

14 S1A53848 012011

Hardware setup

Installing the LONWORKS communication card in ATV212

Note To install or remove the terminal board make it slide in or out in parallel with board

DANGERUNINTENDED EQUIPMENT OPERATION

Do not plug or unplug the terminal board while drive is powered

Check the tightening of the mounting screw after any manipulation on the terminal board

Failure to follow these instructions will result in death or serious injury

1 Open the ATV212 front cover remove the terminal board mounting screw and take off the ATV212 standard terminal board See paragraph How to open the front cover page 13 Be careful not to lose the terminal board mounting screw when removed since it may be used again On drives from 075 to 22 kW the board features a plastic tag to hold the mounting screw in place

2 Make the power and control wiring connections before installing communication card

3 Install the LONWORKS communication card Fit the board mounting screw (M3 tapping type) and tighten to 07 to 08 Nm

4 Stick the cabling label for communication card on the standard cabling label stuck on front cover (internal side) ATV212 And stick the communication card nameplate close to the standard nameplate Be careful not to cover slits on the ATV212 enclosure

B A GND SCR

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

P24M

NETA SHLD NETB GE

ON ORKS RL W S1A58023

VIBSink

PTCSource

SW100 SW200

VW3A21212

SERVICE LED

SERVICE SW

S1A53848 012011 15

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 8: Schneider ATV212

About the Book

8 S1A53848 012011

S1A53848 012011

Introduction

1

Introduction

Thank you for purchasing the LONWORKSreg option card (VW3 A21 212) for Altivar 212 drive

By installing this card into the Altivar 212 data communication can be made with a host computer or other device via LONWORKSreg network

The communication card has an open-style 3-pin connector for connection to the network It supports free topology (TPFT-10) at 78 kbits

Data exchanges give access to all Altivar 212 functions

bull Control (start stop reset setpoint)bull Monitoring (status current voltage thermal state)bull Diagnostics (alarms)

The LONWORKS resource files (XIF) that provide the network configuration tools (LonMakerreg) with device information are available on wwwschneider-electriccom

LONWORKSreg LONMARKreg LonMakerreg Neuron are trademarks of Echelon Corporation registered in the United States and other countries

LONMARKreg and LONMARKreg Logo are managed granted and used by LONMARKreg International under a license granted by Echelon Corporation

9

Introduction

10 S1A53848 012011

S1A53848 012011

Hardware setup

2

Hardware setup

Whats in this ChapterThis chapter contains the following topics

Topic Page

Receipt 12

Opening the drive 13

Hardware description 16

Use of open Style Connector 16

Description of terminals 17

11

Hardware setup

Receiptbull Check that the card reference printed on the label is the same as that on the delivery note corresponding

to the purchase orderbull Remove the option card from its packaging and check that it has not been damaged in transitbull The LONWORKS card is shipped together with the following accessories On opening the packing case

check to see if the following accessories are contained or not- 1 cabling label- 3 neuron ID labels (barcode EAN128)- 1 screw

12 S1A53848 012011

Hardware setup

Opening the drive

1 Any procedure in this section must be performed when product is powered off

2 Open the ATV212 front cover

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHRead and understand the instructions in About the book chapter before performing the procedure in this section

Failure to follow these instructions will result in death or serious injury

ATV212H products up to 22 kW Turn the screw on the front panel 90deg counter-clockwise to align the dot on the screw with the unlock position

To avoid damaging the screw do not apply excessive force or turn the screw more than 90deg

ATV212H products from 22 kWRemove the screwsLift off the cover

Pull the front panel toward youand swing it open to the left

Screw

S1A53848 012011 13

Hardware setup

ATV212W up to 75 kW ATV212W above 75 kW

14 S1A53848 012011

Hardware setup

Installing the LONWORKS communication card in ATV212

Note To install or remove the terminal board make it slide in or out in parallel with board

DANGERUNINTENDED EQUIPMENT OPERATION

Do not plug or unplug the terminal board while drive is powered

Check the tightening of the mounting screw after any manipulation on the terminal board

Failure to follow these instructions will result in death or serious injury

1 Open the ATV212 front cover remove the terminal board mounting screw and take off the ATV212 standard terminal board See paragraph How to open the front cover page 13 Be careful not to lose the terminal board mounting screw when removed since it may be used again On drives from 075 to 22 kW the board features a plastic tag to hold the mounting screw in place

2 Make the power and control wiring connections before installing communication card

3 Install the LONWORKS communication card Fit the board mounting screw (M3 tapping type) and tighten to 07 to 08 Nm

4 Stick the cabling label for communication card on the standard cabling label stuck on front cover (internal side) ATV212 And stick the communication card nameplate close to the standard nameplate Be careful not to cover slits on the ATV212 enclosure

B A GND SCR

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

P24M

NETA SHLD NETB GE

ON ORKS RL W S1A58023

VIBSink

PTCSource

SW100 SW200

VW3A21212

SERVICE LED

SERVICE SW

S1A53848 012011 15

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 9: Schneider ATV212

S1A53848 012011

Introduction

1

Introduction

Thank you for purchasing the LONWORKSreg option card (VW3 A21 212) for Altivar 212 drive

By installing this card into the Altivar 212 data communication can be made with a host computer or other device via LONWORKSreg network

The communication card has an open-style 3-pin connector for connection to the network It supports free topology (TPFT-10) at 78 kbits

Data exchanges give access to all Altivar 212 functions

bull Control (start stop reset setpoint)bull Monitoring (status current voltage thermal state)bull Diagnostics (alarms)

The LONWORKS resource files (XIF) that provide the network configuration tools (LonMakerreg) with device information are available on wwwschneider-electriccom

LONWORKSreg LONMARKreg LonMakerreg Neuron are trademarks of Echelon Corporation registered in the United States and other countries

LONMARKreg and LONMARKreg Logo are managed granted and used by LONMARKreg International under a license granted by Echelon Corporation

9

Introduction

10 S1A53848 012011

S1A53848 012011

Hardware setup

2

Hardware setup

Whats in this ChapterThis chapter contains the following topics

Topic Page

Receipt 12

Opening the drive 13

Hardware description 16

Use of open Style Connector 16

Description of terminals 17

11

Hardware setup

Receiptbull Check that the card reference printed on the label is the same as that on the delivery note corresponding

to the purchase orderbull Remove the option card from its packaging and check that it has not been damaged in transitbull The LONWORKS card is shipped together with the following accessories On opening the packing case

check to see if the following accessories are contained or not- 1 cabling label- 3 neuron ID labels (barcode EAN128)- 1 screw

12 S1A53848 012011

Hardware setup

Opening the drive

1 Any procedure in this section must be performed when product is powered off

2 Open the ATV212 front cover

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHRead and understand the instructions in About the book chapter before performing the procedure in this section

Failure to follow these instructions will result in death or serious injury

ATV212H products up to 22 kW Turn the screw on the front panel 90deg counter-clockwise to align the dot on the screw with the unlock position

To avoid damaging the screw do not apply excessive force or turn the screw more than 90deg

ATV212H products from 22 kWRemove the screwsLift off the cover

Pull the front panel toward youand swing it open to the left

Screw

S1A53848 012011 13

Hardware setup

ATV212W up to 75 kW ATV212W above 75 kW

14 S1A53848 012011

Hardware setup

Installing the LONWORKS communication card in ATV212

Note To install or remove the terminal board make it slide in or out in parallel with board

DANGERUNINTENDED EQUIPMENT OPERATION

Do not plug or unplug the terminal board while drive is powered

Check the tightening of the mounting screw after any manipulation on the terminal board

Failure to follow these instructions will result in death or serious injury

1 Open the ATV212 front cover remove the terminal board mounting screw and take off the ATV212 standard terminal board See paragraph How to open the front cover page 13 Be careful not to lose the terminal board mounting screw when removed since it may be used again On drives from 075 to 22 kW the board features a plastic tag to hold the mounting screw in place

2 Make the power and control wiring connections before installing communication card

3 Install the LONWORKS communication card Fit the board mounting screw (M3 tapping type) and tighten to 07 to 08 Nm

4 Stick the cabling label for communication card on the standard cabling label stuck on front cover (internal side) ATV212 And stick the communication card nameplate close to the standard nameplate Be careful not to cover slits on the ATV212 enclosure

B A GND SCR

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

P24M

NETA SHLD NETB GE

ON ORKS RL W S1A58023

VIBSink

PTCSource

SW100 SW200

VW3A21212

SERVICE LED

SERVICE SW

S1A53848 012011 15

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002000740069006c0020006b00760061006c00690074006500740073007500640073006b007200690076006e0069006e006700200065006c006c006500720020006b006f007200720065006b007400750072006c00e60073006e0069006e0067002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 10: Schneider ATV212

Introduction

10 S1A53848 012011

S1A53848 012011

Hardware setup

2

Hardware setup

Whats in this ChapterThis chapter contains the following topics

Topic Page

Receipt 12

Opening the drive 13

Hardware description 16

Use of open Style Connector 16

Description of terminals 17

11

Hardware setup

Receiptbull Check that the card reference printed on the label is the same as that on the delivery note corresponding

to the purchase orderbull Remove the option card from its packaging and check that it has not been damaged in transitbull The LONWORKS card is shipped together with the following accessories On opening the packing case

check to see if the following accessories are contained or not- 1 cabling label- 3 neuron ID labels (barcode EAN128)- 1 screw

12 S1A53848 012011

Hardware setup

Opening the drive

1 Any procedure in this section must be performed when product is powered off

2 Open the ATV212 front cover

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHRead and understand the instructions in About the book chapter before performing the procedure in this section

Failure to follow these instructions will result in death or serious injury

ATV212H products up to 22 kW Turn the screw on the front panel 90deg counter-clockwise to align the dot on the screw with the unlock position

To avoid damaging the screw do not apply excessive force or turn the screw more than 90deg

ATV212H products from 22 kWRemove the screwsLift off the cover

Pull the front panel toward youand swing it open to the left

Screw

S1A53848 012011 13

Hardware setup

ATV212W up to 75 kW ATV212W above 75 kW

14 S1A53848 012011

Hardware setup

Installing the LONWORKS communication card in ATV212

Note To install or remove the terminal board make it slide in or out in parallel with board

DANGERUNINTENDED EQUIPMENT OPERATION

Do not plug or unplug the terminal board while drive is powered

Check the tightening of the mounting screw after any manipulation on the terminal board

Failure to follow these instructions will result in death or serious injury

1 Open the ATV212 front cover remove the terminal board mounting screw and take off the ATV212 standard terminal board See paragraph How to open the front cover page 13 Be careful not to lose the terminal board mounting screw when removed since it may be used again On drives from 075 to 22 kW the board features a plastic tag to hold the mounting screw in place

2 Make the power and control wiring connections before installing communication card

3 Install the LONWORKS communication card Fit the board mounting screw (M3 tapping type) and tighten to 07 to 08 Nm

4 Stick the cabling label for communication card on the standard cabling label stuck on front cover (internal side) ATV212 And stick the communication card nameplate close to the standard nameplate Be careful not to cover slits on the ATV212 enclosure

B A GND SCR

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

P24M

NETA SHLD NETB GE

ON ORKS RL W S1A58023

VIBSink

PTCSource

SW100 SW200

VW3A21212

SERVICE LED

SERVICE SW

S1A53848 012011 15

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 11: Schneider ATV212

S1A53848 012011

Hardware setup

2

Hardware setup

Whats in this ChapterThis chapter contains the following topics

Topic Page

Receipt 12

Opening the drive 13

Hardware description 16

Use of open Style Connector 16

Description of terminals 17

11

Hardware setup

Receiptbull Check that the card reference printed on the label is the same as that on the delivery note corresponding

to the purchase orderbull Remove the option card from its packaging and check that it has not been damaged in transitbull The LONWORKS card is shipped together with the following accessories On opening the packing case

check to see if the following accessories are contained or not- 1 cabling label- 3 neuron ID labels (barcode EAN128)- 1 screw

12 S1A53848 012011

Hardware setup

Opening the drive

1 Any procedure in this section must be performed when product is powered off

2 Open the ATV212 front cover

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHRead and understand the instructions in About the book chapter before performing the procedure in this section

Failure to follow these instructions will result in death or serious injury

ATV212H products up to 22 kW Turn the screw on the front panel 90deg counter-clockwise to align the dot on the screw with the unlock position

To avoid damaging the screw do not apply excessive force or turn the screw more than 90deg

ATV212H products from 22 kWRemove the screwsLift off the cover

Pull the front panel toward youand swing it open to the left

Screw

S1A53848 012011 13

Hardware setup

ATV212W up to 75 kW ATV212W above 75 kW

14 S1A53848 012011

Hardware setup

Installing the LONWORKS communication card in ATV212

Note To install or remove the terminal board make it slide in or out in parallel with board

DANGERUNINTENDED EQUIPMENT OPERATION

Do not plug or unplug the terminal board while drive is powered

Check the tightening of the mounting screw after any manipulation on the terminal board

Failure to follow these instructions will result in death or serious injury

1 Open the ATV212 front cover remove the terminal board mounting screw and take off the ATV212 standard terminal board See paragraph How to open the front cover page 13 Be careful not to lose the terminal board mounting screw when removed since it may be used again On drives from 075 to 22 kW the board features a plastic tag to hold the mounting screw in place

2 Make the power and control wiring connections before installing communication card

3 Install the LONWORKS communication card Fit the board mounting screw (M3 tapping type) and tighten to 07 to 08 Nm

4 Stick the cabling label for communication card on the standard cabling label stuck on front cover (internal side) ATV212 And stick the communication card nameplate close to the standard nameplate Be careful not to cover slits on the ATV212 enclosure

B A GND SCR

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

P24M

NETA SHLD NETB GE

ON ORKS RL W S1A58023

VIBSink

PTCSource

SW100 SW200

VW3A21212

SERVICE LED

SERVICE SW

S1A53848 012011 15

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 12: Schneider ATV212

Hardware setup

Receiptbull Check that the card reference printed on the label is the same as that on the delivery note corresponding

to the purchase orderbull Remove the option card from its packaging and check that it has not been damaged in transitbull The LONWORKS card is shipped together with the following accessories On opening the packing case

check to see if the following accessories are contained or not- 1 cabling label- 3 neuron ID labels (barcode EAN128)- 1 screw

12 S1A53848 012011

Hardware setup

Opening the drive

1 Any procedure in this section must be performed when product is powered off

2 Open the ATV212 front cover

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHRead and understand the instructions in About the book chapter before performing the procedure in this section

Failure to follow these instructions will result in death or serious injury

ATV212H products up to 22 kW Turn the screw on the front panel 90deg counter-clockwise to align the dot on the screw with the unlock position

To avoid damaging the screw do not apply excessive force or turn the screw more than 90deg

ATV212H products from 22 kWRemove the screwsLift off the cover

Pull the front panel toward youand swing it open to the left

Screw

S1A53848 012011 13

Hardware setup

ATV212W up to 75 kW ATV212W above 75 kW

14 S1A53848 012011

Hardware setup

Installing the LONWORKS communication card in ATV212

Note To install or remove the terminal board make it slide in or out in parallel with board

DANGERUNINTENDED EQUIPMENT OPERATION

Do not plug or unplug the terminal board while drive is powered

Check the tightening of the mounting screw after any manipulation on the terminal board

Failure to follow these instructions will result in death or serious injury

1 Open the ATV212 front cover remove the terminal board mounting screw and take off the ATV212 standard terminal board See paragraph How to open the front cover page 13 Be careful not to lose the terminal board mounting screw when removed since it may be used again On drives from 075 to 22 kW the board features a plastic tag to hold the mounting screw in place

2 Make the power and control wiring connections before installing communication card

3 Install the LONWORKS communication card Fit the board mounting screw (M3 tapping type) and tighten to 07 to 08 Nm

4 Stick the cabling label for communication card on the standard cabling label stuck on front cover (internal side) ATV212 And stick the communication card nameplate close to the standard nameplate Be careful not to cover slits on the ATV212 enclosure

B A GND SCR

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

P24M

NETA SHLD NETB GE

ON ORKS RL W S1A58023

VIBSink

PTCSource

SW100 SW200

VW3A21212

SERVICE LED

SERVICE SW

S1A53848 012011 15

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN ltFEFF9ad854c18cea51fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e30593002537052376642306e753b8cea3092670059279650306b4fdd306430533068304c3067304d307e3059300230c730b930af30c830c330d730d730ea30f330bf3067306e53705237307e305f306f30d730eb30fc30d57528306b9069305730663044307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e30593002gt KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 13: Schneider ATV212

Hardware setup

Opening the drive

1 Any procedure in this section must be performed when product is powered off

2 Open the ATV212 front cover

DANGERHAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASHRead and understand the instructions in About the book chapter before performing the procedure in this section

Failure to follow these instructions will result in death or serious injury

ATV212H products up to 22 kW Turn the screw on the front panel 90deg counter-clockwise to align the dot on the screw with the unlock position

To avoid damaging the screw do not apply excessive force or turn the screw more than 90deg

ATV212H products from 22 kWRemove the screwsLift off the cover

Pull the front panel toward youand swing it open to the left

Screw

S1A53848 012011 13

Hardware setup

ATV212W up to 75 kW ATV212W above 75 kW

14 S1A53848 012011

Hardware setup

Installing the LONWORKS communication card in ATV212

Note To install or remove the terminal board make it slide in or out in parallel with board

DANGERUNINTENDED EQUIPMENT OPERATION

Do not plug or unplug the terminal board while drive is powered

Check the tightening of the mounting screw after any manipulation on the terminal board

Failure to follow these instructions will result in death or serious injury

1 Open the ATV212 front cover remove the terminal board mounting screw and take off the ATV212 standard terminal board See paragraph How to open the front cover page 13 Be careful not to lose the terminal board mounting screw when removed since it may be used again On drives from 075 to 22 kW the board features a plastic tag to hold the mounting screw in place

2 Make the power and control wiring connections before installing communication card

3 Install the LONWORKS communication card Fit the board mounting screw (M3 tapping type) and tighten to 07 to 08 Nm

4 Stick the cabling label for communication card on the standard cabling label stuck on front cover (internal side) ATV212 And stick the communication card nameplate close to the standard nameplate Be careful not to cover slits on the ATV212 enclosure

B A GND SCR

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

P24M

NETA SHLD NETB GE

ON ORKS RL W S1A58023

VIBSink

PTCSource

SW100 SW200

VW3A21212

SERVICE LED

SERVICE SW

S1A53848 012011 15

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f007500720020006400650073002000e90070007200650075007600650073002000650074002000640065007300200069006d007000720065007300730069006f006e00730020006400650020006800610075007400650020007100750061006c0069007400e90020007300750072002000640065007300200069006d007000720069006d0061006e0074006500730020006400650020006200750072006500610075002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 14: Schneider ATV212

Hardware setup

ATV212W up to 75 kW ATV212W above 75 kW

14 S1A53848 012011

Hardware setup

Installing the LONWORKS communication card in ATV212

Note To install or remove the terminal board make it slide in or out in parallel with board

DANGERUNINTENDED EQUIPMENT OPERATION

Do not plug or unplug the terminal board while drive is powered

Check the tightening of the mounting screw after any manipulation on the terminal board

Failure to follow these instructions will result in death or serious injury

1 Open the ATV212 front cover remove the terminal board mounting screw and take off the ATV212 standard terminal board See paragraph How to open the front cover page 13 Be careful not to lose the terminal board mounting screw when removed since it may be used again On drives from 075 to 22 kW the board features a plastic tag to hold the mounting screw in place

2 Make the power and control wiring connections before installing communication card

3 Install the LONWORKS communication card Fit the board mounting screw (M3 tapping type) and tighten to 07 to 08 Nm

4 Stick the cabling label for communication card on the standard cabling label stuck on front cover (internal side) ATV212 And stick the communication card nameplate close to the standard nameplate Be careful not to cover slits on the ATV212 enclosure

B A GND SCR

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

P24M

NETA SHLD NETB GE

ON ORKS RL W S1A58023

VIBSink

PTCSource

SW100 SW200

VW3A21212

SERVICE LED

SERVICE SW

S1A53848 012011 15

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f0074002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a00610020006c0061006100640075006b006100730074006100200074007900f6007000f60079007400e400740075006c006f0073007400750073007400610020006a00610020007600650064006f007300740075007300740061002000760061007200740065006e002e00200020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 15: Schneider ATV212

Hardware setup

Installing the LONWORKS communication card in ATV212

Note To install or remove the terminal board make it slide in or out in parallel with board

DANGERUNINTENDED EQUIPMENT OPERATION

Do not plug or unplug the terminal board while drive is powered

Check the tightening of the mounting screw after any manipulation on the terminal board

Failure to follow these instructions will result in death or serious injury

1 Open the ATV212 front cover remove the terminal board mounting screw and take off the ATV212 standard terminal board See paragraph How to open the front cover page 13 Be careful not to lose the terminal board mounting screw when removed since it may be used again On drives from 075 to 22 kW the board features a plastic tag to hold the mounting screw in place

2 Make the power and control wiring connections before installing communication card

3 Install the LONWORKS communication card Fit the board mounting screw (M3 tapping type) and tighten to 07 to 08 Nm

4 Stick the cabling label for communication card on the standard cabling label stuck on front cover (internal side) ATV212 And stick the communication card nameplate close to the standard nameplate Be careful not to cover slits on the ATV212 enclosure

B A GND SCR

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

PLC

VIA UVIB U I

PTCSW100

SinkPLC

SourceSW102

I U

SW101Term

SW103

P24M

NETA SHLD NETB GE

ON ORKS RL W S1A58023

VIBSink

PTCSource

SW100 SW200

VW3A21212

SERVICE LED

SERVICE SW

S1A53848 012011 15

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 16: Schneider ATV212

Hardware setup

Hardware description

Use of open Style Connector

GeneralUse the open style connector to connect the drive to LONWORKS fieldbus Connection details are given in the Connecting to the bus section page 19

CC

GE FLA

RJ45

FLB FLC

F R RES

NETA NETBSHLD

VIB PP P24M

LONWORKS OpenStyle connector

Selector switch SW100- VIB function (VIBPTC)- Logic for F R RES terminal (SINKSOURCE)

RJ45 port

Service LED

Terminal board mounting screw hole (M3 screw)

Connector to drive

VIBSINK

PTCSOURCE

SW200 (1)Commissioning button

(1) The SW200 switch enables to send the network address to the master

DANGERUNINTENDED EQUIPMENT OPERATIONbull Modify only the setting of the switches when the product is switched offbull Do not change the setting of the SW100 unless your system is wired for SINK logicFailure to follow these instructions will result in death or serious injury

CAUTIONRISK OF BODY INJURYUse a screwdriver to change the position of the switchesFailure to follow these instructions can result in injury or equipment damage

16 S1A53848 012011

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002000740069006c0020006b00760061006c00690074006500740073007500640073006b007200690076006e0069006e006700200065006c006c006500720020006b006f007200720065006b007400750072006c00e60073006e0069006e0067002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f00630068007700650072007400690067006500200044007200750063006b006500200061007500660020004400650073006b0074006f0070002d0044007200750063006b00650072006e00200075006e0064002000500072006f006f0066002d00470065007200e400740065006e002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 17: Schneider ATV212

Hardware setup

Description of terminals

(1) Voltage conversion(2) PTC (Positive Temperature Coefficient) Resettable thermal fuse resistor for over current protection

Terminal symbol

Function Electrical specifications Internal circuits

CC Control circuit equipotential terminal - -

VIB

Multifunction programmable analog input It has speed setpoint function in the default setting (0 to 50 Hz frequency with 0 to 10 Vdc input) In addition this terminal can be used as PTC (2) input by setting switch SW100 and the parameters [Mot PTC selection] F645 and [PTC resistor value] F646

Voltage 10 Vdc Internal impedance 30 kΩ

PP Voltage supply for reference potentiometer

Voltage 10 VdcMax current 10 mAProtected against short circuits

F

Multifunctional programmable logic inputIt has forward rotation function in default settingON forward rotation driveOFF slowdown and stop

No voltage contact input24 Vdc5 mA or lessSINKSOURCE can be selected with SW100

RMultifunctional programmable logic input It has Preset speed 1 in default setting

RESMultifunctional programmable logic input It has Fault Reset in default setting

P24M 24 VDC power supply output24 Vdc50 mA

NETALONWORKS transmission data reception data

No polarity

SHLDLONWORKS communication shield terminal

This terminal is not connected to any other circuit of the card Ground this terminal in a location separated from the ground of power line

NETBLONWORKS transmission data reception data

No polarity

GE Grounding terminalPlease connect to network ground

FLAFLBFLC

Multifunctional programmable relay contact outputs Default setting is set to detect the activation of the drive protection functionContact across FLA-FLC is closed and FLB-FLC is open during normal operation

30 Vdc 05 A 250 Vac 1 A(cos ϕ = 1)250 Vac 05A(cos ϕ = 04)

PP

+24V

(1)

F R RES

SINKSOURCE

(2)

Sparkgap

S1A53848 012011 17

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 18: Schneider ATV212

Hardware setup

18 S1A53848 012011

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 19: Schneider ATV212

S1A53848 012011

Connecting to the bus

3

Connecting to the bus

Whats in this ChapterThis chapter contains the following topics

Topic Page

Topology 20

Cable routing practices 21

Card connector pinout 22

Connecting the LONWORKS connector 22

19

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f0074002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a00610020006c0061006100640075006b006100730074006100200074007900f6007000f60079007400e400740075006c006f0073007400750073007400610020006a00610020007600650064006f007300740075007300740061002000760061007200740065006e002e00200020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 20: Schneider ATV212

Connecting to the bus

TopologyThe LONWORKS card supports free topology (TPFT-10) wiring and operates as well with bus loop or star topologies

Free topology systemFree topology has many advantages

1 The installer is free to select the method of wiring that best suits the installation reducing the need for advanced planning and allowing last minute changes at the installation site

2 If installers have been trained to use one style of wiring for all installations free topology technology can be introduced without requiring retraining

3 Retrofit installations with existing wiring plants can be accommodated with minimal if any rewiring

Typical wiring topologies

Star topology

Doubly terminated bus topology

Termination

Termination Termination

Termination

Loop topology

Termination

Mixed topology

20 S1A53848 012011

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f00630068007700650072007400690067006500200044007200750063006b006500200061007500660020004400650073006b0074006f0070002d0044007200750063006b00650072006e00200075006e0064002000500072006f006f0066002d00470065007200e400740065006e002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 21: Schneider ATV212

Connecting to the bus

Cable routing practices

Network wiring guidelinesWhen wiring Altivar 212 drives to a LONWORKS network observe the following guidelines

bull Avoid areas of high temperature moisture vibration or other mechanical stressbull Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or

twisting the cablebull Use cable ducts raceways or other structures to protect the cable Route the power cables apart from

these structuresbull Avoid sources of electrical interference that can induce noise into the cable Use the maximum practicable

separation from such sources

Cable routing guidelinesWhen planning cable routing within a building follow these guidelines

bull Maintain a minimum separation of 1 m (33 ft) from the following equipment- air conditioners and large blowers- elevators and escalators- radios and televisions- intercom and security systems- fluorescent incandescent and neon lighting fixtures

bull Maintain a minimum separation of 3 m (98 ft) from the following equipment- line and motor power wiring- transformers- generators- alternators

Electrical equipment rooms or large electrical equipment line-upsWhen wiring in electrical equipment rooms or large electrical equipment line-ups observe the following guidelines for cable segregation and separation of circuits

bull Use metallic conduit for drive wiring Route control network and power wiring in separate conduitsbull Separate non-metallic conduits or cable trays carrying power wiring from metallic conduit carrying low-level

control network wiring by at least 305 mm (12 in)bull Separate metallic conduits carrying power wiring or low-level control network wiring by at least 76 mm

(3 in)bull Whenever power and control wiring cross the metallic conduits and non-metallic conduits or trays will cross

at right anglesbull If necessary use filters to attenuate conducted emissions from the drive to the line to help prevent

interference with telecommunication radio and sensitive electronic equipment Consult the Altivar catalog for selection and application of these filters

DANGERUNINTENDED EQUIPMENT OPERATION DUE TO IMPROPER WIRING PRACTICESbull Follow the wiring practices described in this document in addition to those already required by the National

Electrical Code and local electrical codesbull Check the power connections before energizing the drivebull If replacing another drive verify that all wiring connections to the ATV212 drive comply with all wiring

instructions in this manualFailure to follow these instructions will result in death or serious injury

S1A53848 012011 21

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN ltFEFF9ad854c18cea51fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e30593002537052376642306e753b8cea3092670059279650306b4fdd306430533068304c3067304d307e3059300230c730b930af30c830c330d730d730ea30f330bf3067306e53705237307e305f306f30d730eb30fc30d57528306b9069305730663044307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e30593002gt KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 22: Schneider ATV212

Connecting to the bus

Connecting the LONWORKS connector

Card connector pinoutThe figure and the table below show the pin-outs of the card connectors and the removable LONWORKS female connector attaches to the network cable

Wiringbull Cable sheath should be peeled off by about 10 mm (039 in)bull For wiring work use a fat blade screwdriver with a 06 mm (0024 in) thick and 35 mm (014 in) width

bladebull Tightening torque for the terminal block is 05 to 06 Nmiddotm (442 to 531 lbin)

NETA NETB

SHLD

22 S1A53848 012011

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 23: Schneider ATV212

S1A53848 012011

Configuration

4

Configuration

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication parameters 24

Configuration of the control 26

Configuring the behaviour on configuration interruption 31

23

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 24: Schneider ATV212

Configuration

Communication parameters

Access to the parameters

ConfigurationConfigure the following parameter Select LONWORKS communication protocol by setting [Network protocol] (F829) to 5 [LonWorks] This parameter can only be modified when the motor is stopped

Note On ATV21 F829 is set to 1 for LONWORKS protocol

When disconnecting the card the drive displays Err5 following a factory set time-out of 3 seconds

If the drive displays Err5

bull Check that F829 = 5bull Check that the LONWORKS card is connectedbull Check that standard IO card is not connected instead of LONWORKS card

The baud rate is fixed 78000 bits

Modifications will be taken into account by the drive after power cycled

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Remote spd ref 2] (F207) [EXTENDED MENU] F--- submenu of [PROGRAMMING MENU] Programming mode

Other parameters [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

DANGERUNINTENDED EQUIPMENT OPERATIONRefer to laquoSerial communication parametersraquo in the Altivar 212 Programming manual for more information on how to set these serial communication parametersFailure to follow these instructions will result in death or serious injury

Parameters Possible values Default value

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input1 [HMI] Graphic display terminal2 [Communication] Serial communication

0

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

1 [Ref source VIA] VIA2 [Ref source VIB] VIB3 [HMI reference] Graphic display terminal4 [Serial com ref] Serial communication5 [+- Speed] +- speed from external contact

2

[Remote spd ref 2] (F207)Remote mode secondary speed reference source

1 [VIA]2 [VIB]3 [HMI] Graphic display terminal4 [Communication] Serial communication5 [+- Speed] +- speed from external contact

2

[Com channel choice] (F807)Communication channel choice

0 [RJ45]1 [Open style]

1

[Network protocol] (F829)Communication protocol

1 [Mdb RTU] Modbusreg RTU protocol2 [Metasys N2] Metasysreg N2 protocol3 [Apogee P1] APOGEEreg FLN P1 protocol4 [BACnet] BACnetreg protocol5 [Lonworks] LONWORKSreg protocol

1

24 S1A53848 012011

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f006200650020005000440046002000700065007200200075006e00610020007300740061006d007000610020006400690020007100750061006c0069007400e00020007300750020007300740061006d00700061006e0074006900200065002000700072006f006f0066006500720020006400650073006b0074006f0070002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f0074002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a00610020006c0061006100640075006b006100730074006100200074007900f6007000f60079007400e400740075006c006f0073007400750073007400610020006a00610020007600650064006f007300740075007300740061002000760061007200740065006e002e00200020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 25: Schneider ATV212

Configuration

Command and speed reference channelsCMOd and FMOd drive parameters are used to set the channel for command and speed reference (first source)

F207 drive parameter is used to set the second source of speed reference Switching between source 1 and 2 is done by F200 parameter or logical input when set to this function

F807 sets the communication channel (RJ45 or Open Style network connector)

0

12

1

23

45

1

23

45

LOCREM

0

1

Commands CMOd

LONWORKScommands

Operationpanel

Commands

Setpoint

LONWORKSsetpoint

Logic input F R or RESF111 F113 configured to 48 [Forced local]

Logic input F R or RESF111 F113

configured to38 [Frequency source]

Operationpanel

LONWORKScommands

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

Setpoint FMOd

Terminals

Operationpanel

OFF

ON

REM

LOC

REM

LOC

REM

LOC

REM

LOC

ON

OFF

ON

OFF

F807 [Com channel choice]

RJ45 channel Modbus

Network channel

parameter F829 [Network protocol]

LONWORKSsetpoint

ON

OFF

VIA

Setpoint FMOd

Operationpanel

LONWORKSsetpoint

VIB

UPDOWN

VIA

Setpoint FMOd

S1A53848 012011 25

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f00630068007700650072007400690067006500200044007200750063006b006500200061007500660020004400650073006b0074006f0070002d0044007200750063006b00650072006e00200075006e0064002000500072006f006f0066002d00470065007200e400740065006e002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 26: Schneider ATV212

Configuration

Configuration of the controlThe drive can be controlled (command and speed reference) by the LONWORKS network as well as by many other canals

bull IObull Terminal (Local terminal Graphic Keypad)bull RJ45 communication (Modbus)

The following figure shows the configuration for the command canal (Cmd SetPoint) and speed reference canal (Speed SetPoint)

The ATV212 can receive commands and speed setpoint from the LONWORKS network or from the terminals (F R RES VIB)

The LOCREM key of the drive HMI is available to switch the control to the HMI

Input F R RES can be configured to switch the control from the LONWORKS to the terminals

Control by the LONWORKS

Commands and setpoint come from the LONWORKS network

The LOCREM key is active

LOCREM

Commands

Setpoint

Operation panel

LONWORKS commands

LOC

REM

LOC

REM

Operation panel

LONWORKS setpoint

26 S1A53848 012011

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 27: Schneider ATV212

Configuration

Control by terminals monitoring by the LONWORKS networkCommands and setpoint come from the terminals

The drive is monitored by the LONWORKS network

The LOCREM key is active

Access to the parameters

Description

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 27

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f00630068007700650072007400690067006500200044007200750063006b006500200061007500660020004400650073006b0074006f0070002d0044007200750063006b00650072006e00200075006e0064002000500072006f006f0066002d00470065007200e400740065006e002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 28: Schneider ATV212

Configuration

Control by the LONWORKS network switching to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands and the setpoint come from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Operation panel

LONWORKS setpoint

UPDOWN

VIB

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

28 S1A53848 012011

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 29: Schneider ATV212

Configuration

Command by the LONWORKS network setpoint by the LONWORKS network or the terminals switch by a logic inputThe commands come from the LONWORKS networkThe setpoint comes from the LONWORKS network if logic input R is OFFThe setpoint comes from the terminals if logic input R is ONThe function 48 [Forced local] is assigned to the logic input RThe LOCREM key is valid

Access to the parameters

Description

0

12

23

45

LOCREM

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

SetpointLONWORKS

setpoint

Setpoint FMOd

OFF

Operationpanel

VIB

REM

LOC

REM

LOCOFF

ON

LONWORKScommands

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

2 [Communication] Serial communication

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

S1A53848 012011 29

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f00630068007700650072007400690067006500200044007200750063006b006500200061007500660020004400650073006b0074006f0070002d0044007200750063006b00650072006e00200075006e0064002000500072006f006f0066002d00470065007200e400740065006e002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt ESP 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 FRA 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 ITA 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 JPN ltFEFF9ad854c18cea51fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e30593002537052376642306e753b8cea3092670059279650306b4fdd306430533068304c3067304d307e3059300230c730b930af30c830c330d730d730ea30f330bf3067306e53705237307e305f306f30d730eb30fc30d57528306b9069305730663044307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e30593002gt KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 30: Schneider ATV212

Configuration

Setpoint by the LONWORKS network switching commands to terminals by logic inputThe commands and the setpoint come from the LONWORKS network if logic input R is OFFThe commands come from the LONWORKS network if logic input R is OFFThe commands come from the terminals if logic input R is ONThe setpoint comes from the LONWORKS networkThe function 48 [Forced local] is assigned to the logic input R

The LOCREM key is valid

Access to the parameters

Description

0

12

LOCREM

23

45

Commands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpointSetpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

Logic input Rconfigured to [Forced local]

F112 = 48

Switch to local

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F112) [IO MENU] IO submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

4 [Serial com ref] Serial communication

[LI R selection] (F112)R Logic Input Function

48 [Forced local] Forced switching from remote to local control

30 S1A53848 012011

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 31: Schneider ATV212

Configuration

Configuring the behaviour on configuration interruption

Access to the parameters

ConfigurationIf you want the drive to switch to terminal control in case of LONWORKS communication interruption configure

0

12

23

45

LOCREMCommands CMOd

Operation panel

LONWORKS commands

Terminals

Operation panel

LONWORKS setpoint

UPDOWN

ON

Operationpanel

Commands

Setpoint

LONWORKS commands

LONWORKS setpoint

Setpoint FMOd

OFF

ON

OFF Operationpanel

VIB

REM

LOC

REM

LOC

LONWORKS communication interruption

Network communicationinterruption

(nciRcvHrBt)

Parameters Location

[Command mode sel] (CMOd)[Frequency mode sel] (FMOd)

[PROGRAMMING MENU] Programming mode

[Com channel choice] (F851) [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter Setting

[Command mode sel] (CMOd)Remote mode startstop control source

0 [Logic inputs] Control terminal logic input

[Frequency mode sel] (FMOd)Remote mode primary speed reference source

2 [Ref source VIB] VIB

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release

S1A53848 012011 31

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 32: Schneider ATV212

Configuration

32 S1A53848 012011

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f007500720020006400650073002000e90070007200650075007600650073002000650074002000640065007300200069006d007000720065007300730069006f006e00730020006400650020006800610075007400650020007100750061006c0069007400e90020007300750072002000640065007300200069006d007000720069006d0061006e0074006500730020006400650020006200750072006500610075002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 33: Schneider ATV212

S1A53848 012011

Diagnostics

5

Diagnostics

Whats in this ChapterThis chapter contains the following topics

Topic Page

Communication detected fault 34

List of type supported by ATV212 Service LED 35

Troubleshooting 36

33

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 34: Schneider ATV212

Diagnostics

Communication detected fault

Configure the heartbeatThe activity on the LONWORKS network is controlled according to the LONWORKS configuration property Receive Heartbeat Time (nciRcvHrtBt)

nciRcvHrtBt is the time out value on the reception of 3 input network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

Refer to the description of this network variable

Configure the drive behaviourbull If you want to ignore LONWORKS communication interruption set nciRcvHrtBt to 0bull If you want the drive to react on LONWORKS communication interruption set the parameter [Com fault

setting] (F851) accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode

Parameter description Possible value Defaultvalue

[Com fault setting] (F851)Drive behavior after a communication interruption

0 [Ramp stp (FCmod)] Communication release (no trip)1 [No active] Deceleration stop (no trip)2 [Ramp stop] Deceleration stop (no trip)3 [Freewheel] Coast stop (no trip)4 [Err5 or Err8] Trip (error 8)

4

WARNINGLOSS OF CONTROLIf nciRcvHrtBt is set to 0 communication control will be inhibitedFor safety reasons inhibiting the communication interruption detection should be restricted to the debugphase or to special applicationFailure to follow these instructions can result in death serious injury or equipment damage

WARNINGLOSS OF CONTROLKnow and understand the setting of parameter F851 This parameter controls the behavior of the drive in the event of a network communication interruption If the value of F851 is 0 1 2 or 3 the drive will not trip on an Err8Failure to follow these instructions can result in death serious injury or equipment damage

34 S1A53848 012011

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 35: Schneider ATV212

Diagnostics

List of type supported by ATV212 Service LED

Cases Display Description and solutions

a LED momentarily turns ON then continues to be OFF

NormalWhen the program is in the condition of Configured status LED momentarily turns ON when the inverter is turned ON Then the LED continues to be OFFThe LONWORKS neuron chip indicates Configured status that means the normal condition

b LED blinks every 1 second UnconfiguredThis is a normal action of the Unconfigured deviceConfigure the LONWORKS card through the LONWORKS network

If the device is not Unconfigured internal application program is broken Download the application through the LONWORKS network If it remains the card needs to be replaced

c Although the inverter is turned on LED remains OFF

AbnormalCheck the connection between the inverter and the option card If abnormality is not found after checking the card needs to be replaced

d LED continues to be ON

e LED is ON then OFF when the inverter is turned on then it continues to be ON

AbnormalApplication program of the LONWORKS neuron chip is abnormalDownload the application through the LONWORKS network If it remains the card needs to be replaced

f LED blinks during 05 second AbnormalA watch dog is suspectedIf the same indication appears after resetting the power the card needs to be replaced

g LED flickers(Approximately 10Hz to 30Hz)

AbnormalThe LONWORKS neuron chip is abnormal The card needs to be replaced

ON

OFF

ONOFF

ONOFF

ONOFF

ONOFF

ON

OFFg

f

e

d

c

b

1 s 2 s 3 s 4 s 5 s

ON

OFFa

S1A53848 012011 35

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 36: Schneider ATV212

Diagnostics

Troubleshooting

Phenomenon Description and solutions

No reply from the LONWORKS card

Check for proper termination resistor(s) installed on the network After checking the service LED status see the previous section

Errors in network variable Check the inverter parameter settingCheck the network cables are not near the power cables

36 S1A53848 012011

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002000740069006c0020006b00760061006c00690074006500740073007500640073006b007200690076006e0069006e006700200065006c006c006500720020006b006f007200720065006b007400750072006c00e60073006e0069006e0067002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f0073002000640065002000410064006f0062006500200050004400460020007000610072006100200063006f006e00730065006700750069007200200069006d0070007200650073006900f3006e002000640065002000630061006c006900640061006400200065006e00200069006d0070007200650073006f0072006100730020006400650020006500730063007200690074006f00720069006f00200079002000680065007200720061006d00690065006e00740061007300200064006500200063006f00720072006500630063006900f3006e002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 37: Schneider ATV212

S1A53848 012011

Functional profile

6

Functional profile

Whats in this ChapterThis chapter contains the following topics

Topic Page

Objects supported 38

LonMark Node Object profile 38

LonMark Variable Speed Motor Drive profile 39

37

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 38: Schneider ATV212

Functional profile

Objects supportedThe LONWORKS card for ATV212 complies to the LonMark functional profile variable Speed Motor Drive (specification 6010-11)

According to this profile 2 objects are supported

bull the node object (specification 0000-20)bull the variable speed motor drive object

LONMARK Node Object profile

NodeObject

VSDobject

Mandatory Network Variables

Node Object0020_00

nviRequestSNVT_obj_request

Optional Network Variables

Configuration PropertiesnciLocation SNVT_str_asc

InputNetworkVariables

OutputNetworkVariables

nvoStatusSNVT_obj_status

38 S1A53848 012011

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 39: Schneider ATV212

Functional profile

LONMARK Variable Speed Motor Drive profile

Mandatory Network Variables

Variable Speed Motor Drive

nviDrvSpeedStpt (SNVT_switch)

Optional Network Variables

nviDrvSpeedScale (SNVT_lev_percent)nvoDrvCurnt (SNVT_amp)nvoDrvRunHours (SNVT_time_hour)

Manufacturer Network Variables

Manufacturer Configuration Properties

Input Network Variables

Output Network Variables

nvoDrvSpeed (SNVT_lev_percent)

nviInvSetFreq (SNVT_freq_hz)nviResetFault (SNVT_switch)nviRelay1 (SNVT_switch)nviEmergOverride (SNVT_hvac_emerg)nviParamCmd (SNVT_preset)

nvoDrvFeedback (SNVT_switch)nvoInvOutFreq (SNVT_freq_hz)nvoStatusWord (SNVT_state)nvoDrvAlarm (SNVT_switch)nvoAlarmWord (SNVT_state)nvoDrvEnergy (SNVT_elec_kwh_l)nvoTorque (SNVT_lev_percent)nvoDigitalIn1 (SNVT_switch)nvoDigitalIn2 (SNVT_switch)nvoAnalogIn2 (SNVT_lev_percent)nvoEmergStatus (SNVT_hvac_emerg)nvoParamResp (SNVT_preset)nvoTypeVer (SNVT_str_asc)

Mandatory Configuration Properties

nciMaxSpeed (SNVT_lev_percent)nciMinSpeed (SNVT_lev_percent)nciNmlSpeed (SNVT_rpm)nciNmlFreq (SNVT_freq_hz)nciRampUpTm (SNVT_time_sec)nciRampDownTm (SNVT_time_sec)

nciPwUpOutTm (SNVT_time_sec)

Optional Configuration Properties

nciLocation (SNVT_str_asc)nciDrvSpeedScale (SNVT_lev_percent)nciRcvHrtBt (SNVT_time_sec)nciMinOutTm (SNVT_time_sec)nciSndHrBt (SNVT_time_sec)

S1A53848 012011 39

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f0073002000640065002000410064006f0062006500200050004400460020007000610072006100200063006f006e00730065006700750069007200200069006d0070007200650073006900f3006e002000640065002000630061006c006900640061006400200065006e00200069006d0070007200650073006f0072006100730020006400650020006500730063007200690074006f00720069006f00200079002000680065007200720061006d00690065006e00740061007300200064006500200063006f00720072006500630063006900f3006e002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 40: Schneider ATV212

Functional profile

40 S1A53848 012011

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 41: Schneider ATV212

S1A53848 012011

Network variables and configuration properties

7

Network variables and configuration properties

Whats in this ChapterThis chapter contains the following topics

Topic Page

List of network variables and configuration properties 42

Commands and setpoints 44

Status and output velocity 48

Alarms 51

Measurements 52

Monitoring of digital inputs 53

Monitoring of analog inputs 53

Control of digital outputs 53

Emergency 54

Adjustment 55

Parameter access 58

Identification 60

Network management 61

41

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 42: Schneider ATV212

Network variables and configuration properties

List of network variables and configuration properties

Commands and setpoints

Status and output velocity

Alarms

Measurements

Monitoring of digital inputs

Monitoring of analog inputs

Control of digital outputs

Name SNVT Definition Description

nviDrvSpeedStpt SNVT_lev_percent Drive Speed Setpoint Variable Speed Motor Drive object (M)

nviDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Variable Speed Motor Drive object (O)

nviInvSetFreq SNVT_freq_hz Frequency setpoint Manufacturer specific

nviResetFault SNVT_switch Detected fault reset command Manufacturer specific

nviRequest SNVT_obj_request Object Request Node object (M)

Name SNVT Definition Description

nvoDrvSpeed SNVT_lev_percent Drive Speed Feedback Variable Speed Motor Drive object (M)

nvoDrvFeedback SNVT_switch Drive velocity feedback Manufacturer specific

nvoInvOutFreq SNVT_freq_hz Output frequency Manufacturer specific

nvoStatusWord SNVT_state Drive status Manufacturer specific

nvoStatus SNVT_obj_status Object Status Node object (M)

Name SNVT Definition Description

nvoDrvAlarm SNVT_switch Alarm code Manufacturer specific

nvoAlarmWord SNVT_state Alarm status Manufacturer specific

Name SNVT Definition Description

nvoDrvCurnt SNVT_amp Drive Output Current Variable Speed Motor Drive object (O)

nvoDrvRunHours SNVT_time_hour Drive Total Running Hours Variable Speed Motor Drive object (O)

nvoDrvEnergy SNVT_elec_kwh_l Energy consumption Manufacturer specific

nvoTorque SNVT_lev_percent Torque Manufacturer specific

Name SNVT Definition Description

nvoDigitalIn1 SNVT_switch State of digital input F Manufacturer specific

nvoDigitalIn2 SNVT_switch State of digital input R Manufacturer specific

Name SNVT Definition Description

nvoAnalogIn2 SNVT_lev_percent Value of analog input VIB Manufacturer specific

Name SNVT Definition Description

nviRelay1 SNVT_switch Command of relay FLA Manufacturer specific

42 S1A53848 012011

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 43: Schneider ATV212

Network variables and configuration properties

Emergency

Adjustment

Parameter access

Identification

Network management

Name SNVT Definition Description

nviEmergOverride SNVT_hvac_emerg Emergency command Manufacturer specific

nvoEmergStatus SNVT_hvac_emerg Emergency feedback Manufacturer specific

Name SNVT Definition Description

nciMaxSpeed SNVT_lev_percent Maximum Motor Speed Variable Speed Motor Drive object (M)

nciMinSpeed SNVT_lev_percent Minimum Motor Speed Variable Speed Motor Drive object (M)

nciNmlSpeed SNVT_rpm Nominal Motor Speed in RPM Variable Speed Motor Drive object (M)

nciDrvSpeedScale SNVT_lev_percent Drive Speed Setpoint Scaling Default value for nviDrvSpeedScale

nciNmlFreq SNVT_freq_hz Nominal Motor Frequency Variable Speed Motor Drive object (M)

nciRampUpTm SNVT_time_sec Minimum Ramp Up Time Variable Speed Motor Drive object (M)

nciRampDownTm SNVT_time_sec Minimum Ramp Down Time Variable Speed Motor Drive object (M)

Name SNVT Definition Description

nviParamCmd SNVT_preset Parameter access command Manufacturer specific

nvoParamResp SNVT_preset Parameter access response Manufacturer specific

Name SNVT Definition Description

nciLocation SNVT_str_asc Location Label Variable Speed Motor Drive object (O)

nvoTypeVer SNVT_str_asc Drive identification Manufacturer specific

Name SNVT Definition Description

nciSndHrtBt SNVT_time_sec Send Heartbeat Time Variable Speed Motor Drive object (M)

nciRcvHrtBt SNVT_time_sec Receive Heartbeat Time Variable Speed Motor Drive object (O)

nciMinOutTm SNVT_time_sec Minimum Send Time Variable Speed Motor Drive object (O)

nciPwUpOutTm SNVT_time_sec Initial inhibition time Manufacturer specific

S1A53848 012011 43

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 44: Schneider ATV212

Network variables and configuration properties

Commands and setpoints

Drive Speed Setpoint (nviDrvSpeedStpt)This input network variable provides startstop control and velocity setpoint

Range

The default value (AUTO) will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat timeThe network variable nviInvSetFreq permits the control of the drive by a frequency setpoint instead of percentage

Drive Speed Setpoint Scaling (nviDrvSpeedScale)This input network variable provides scaling for nviDrvSpeedStptNegative values indicate a motor direction in reverse

For example if the nviDrvSpeedStpt value is 50 and nviDrvSpeedScale is -150 then the actual speed setpoint is -75 or 075 times the nominal speed in the reverse direction

Default value is determined by nciDrvSpeedScale This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Default Value for nviDrvSpeedScale (nciDrvSpeedScale)This configuration property is used as the default value for nviDrvSpeedScaleWhen the LONWORKS card is initialized this network variable returns to default value (100)

Name nviDrvSpeedStpt

SNVT reference SNVT_lev_percent

SNVT index 81

Definition Drive Speed Setpoint

Unit 05

Default value AUTO (0xFF)

State Value Command Comment

0 (FALSE) NA Stop The drive is stopped the drive function is disabled and power is not applied to the motor0xFF NA AUTO controlled stop

1 (TRUE) 0 0 The drive function is enabled and power may be applied to the motor1 (TRUE) 1 200 05 1000

1 (TRUE) 201 255 1000

Name nviDrvSpeedScale

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Drive Speed Setpoint Scaling

Name nciDrvSpeedScale

SCPT reference SCPTdefScale

SCPT index 162

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 1638300x7FFF = +163835 invalid value

Definition Default Value for nviDrvSpeedScale

Default value 100000

44 S1A53848 012011

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 45: Schneider ATV212

Network variables and configuration properties

Frequency setpoint (nviInvSetFreq)This variable is the frequency setpoint alternative to the percentage velocity setpoint (value of SNVT_Swith nviDrvSpeedStpt)

When the setting value of nviDrvSpeedScale is negative the motor reverse-rotates

The drive is operated according to nciDrvSpeed when the variable is 32767 Hz

The default value is 0x7FFF = 3 2767 Hz invalid It will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time

Speed Setpoint provided by nviInvSetFreq is limited by value of nciMaxSpeed and nciMinSpeed

Range

Name nviInvSetFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 2000 Hz 0x7FFF = 32767 Hz invalid

Definition Frequency setpoint

nviInvSetFreq nviDrvSpeedStpt Operation

state value

NA 0 NA 0Hz

32767Hz (0x7FFF) 1 value Drive the speed provided by ldquonviDrvSpeedStptrdquo

00 to 32766 Hz 1 NA Drive the speed provided by ldquonviInvSetFreqrdquo

S1A53848 012011 45

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 46: Schneider ATV212

Network variables and configuration properties

Reset command (nviResetFault)The reset command resets the drive when the drive is in fault state and if the resetable detected fault has been cleared

Range

Object request (nviRequest)This input network variable provides the mechanism to request an operation or a mode for a functional block within the drive

Name nviResetFault

SNVT reference SNVT_switch

SNVT index 95

Format No Reset NA100

Definition Detected fault reset command

State Value Command Comment0 any Invalid

1 gt 0 Reset command Value must be gt0 to perform the reset command not only state set to 1

1 0 Invalid (no command)

Name nviRequest

SNVT reference SNVT_obj_request

SNVT index 92

Definition Object request

No Member name Description

255 RQ_NUL Invalid value

object_id Stores the object ID

0 RQ_NORMAL If the specified functional block was in the disabled state this request cancels that state and returns the functional block to normal operation If the functional block was already in the normal state a request to enter the normal state is not an error After device reset the state of functional blocks on the device is application-specific(Mandatory for LonMark Node Object)

1 RQ_DISABLED Makes the drive object invalid and brings the motor to a controlled stop(Mandatory for LonMark Variable Speed Motor Drive profile)

2 RQ_UPDATE_STATUS Request the object status (nvoStatus) to be updated(Mandatory for LonMark Node Object)

5 RQ_REPORT_MASK Changes to 1bit (disabled in_alarm report_mask) supported by object status (nvoStatus) (Mandatory for LonMark Node Object)

7 RQ_ENABLE Makes the drive object valid(Mandatory for LonMark Variable Speed Motor Drive profile)

9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to 0

10 RQ_CLEAR_ALARM Detected fault reset commandClears to 0 in_alarm bit of object status (nvoStatus)(Mandatory for LonMark Variable Speed Motor Drive profile)

3 RQ_SELF_TEST Not supported

4 RQ_UPDATE_ALARM Not supported

6 RQ_OVERRIDE Not supported

8 RQ_RMV_OVERRIDE Not supported

11 RQ_ALARM_NOTIFY_ENABLED Not supported

46 S1A53848 012011

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 47: Schneider ATV212

Network variables and configuration properties

12 RQ_ALARM_NOTIFY_DISABLED Not supported

13 RQ_MANUAL_CTRL Not supported

14 RQ_REMOTE_CTRL Not supported

15 RQ_PROGRAM Not supported

16 RQ_CLEAR_RESET Not supported

17 RQ_RESET Not supported

S1A53848 012011 47

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f00630068007700650072007400690067006500200044007200750063006b006500200061007500660020004400650073006b0074006f0070002d0044007200750063006b00650072006e00200075006e0064002000500072006f006f0066002d00470065007200e400740065006e002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 48: Schneider ATV212

Network variables and configuration properties

Status and output velocity

Drive Speed Feedback (nvoDrvSpeed)This output network variable provides the speed of the drive as a percentage of the nominal speed

This value is transmitted immediately when its value has changed significantly

Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This LONWORKS network variable is linked to the drive parameter [Operation frequency] (FD00)

Drive Velocity feedback (nvoDrvFeedback)This variable monitors Stopped Running status of the drive and the output velocity of as a percentage of the nominal speed of the drive (unit = 05) It is the output image of nviDrvSpeedStpt

Output frequency (nvoInvOutFreq)This variable monitors the output velocity (01 Hz unit) of the drive

Name nvoDrvSpeed

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 to 1638300x7FFF = +163835 invalid

Definition Drive Speed Feedback

Name nvoDrvFeedback

SNVT reference SNVT_switch

SNVT index 95

Format Stopped Running Actual speed

Unit of value 05

Range of value 0 1275

Definition Drive velocity feedback

State Description

0 (FALSE) Stopped

1 (TRUE) Running

Value Description

0 255 00 1275value = Drive Frequency nciNmlFreq abs (nviDrvSpeedScale)

Name nvoInvOutFreq

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01Hz

Definition Output frequency

48 S1A53848 012011

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 49: Schneider ATV212

Network variables and configuration properties

Drive status (nvoStatusWord)This variable monitors the status of the drive by a bit field

Name nvoStatusWord

SNVT reference SNVT_state

SNVT index 83

Definition Drive status

Bit nb Description Link to ATV212 internal parameter

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Warning0 [No warning]1 [Warning]

Inverter operating status (Fd01)bit 2

2 Running0 [Stopped]1 [Running]

Inverter operating status (Fd01)bit 10

3 Rotation0 [Forward]1 [Reverse]

Inverter operating status (Fd01)bit 9

4 Ready0 [Disable]1 [Enable]

Inverter operating status (Fd01)bit 13

5 Command from the network0 [Not from the network]1 [From the network]

Inverter operating command mode status (FE45)

6 Setpoint from the network0 [Not from the network]1 [From the network]

Inverter operating setpoint mode status (FE46) = 4

7 At setpoint0 [Setpoint not reached (accelerating or decelerating)]1 [Setpoint reached]

8 to 15 [Reserved]

S1A53848 012011 49

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 50: Schneider ATV212

Network variables and configuration properties

Object Status (nvoStatus)This output network variable indicates various status within the drive

Name nvoStatus

SNVT reference SNVT_obj_status

SNVT index 93

Definition Object Status

No Member name Description

object_id Returns the value written to object_id of object request (nviRequest)(Mandatory for LonMark Node Object)

0 invalid_id 1 means requested ID is not implemented in the drive(Mandatory for LonMark Node Object)

1 invalid_request 1 means request is not implemented in the drive

2 disabled 1 means object disabledUnder the disabled stateOutput network variables belonging to the functional block are not propagated to the network However it must be possible to poll the output network variables of a functional block in this stateThe functional block must not respond to any updates received on its input network variables but it must support reading and writing of any configuration properties belonging to the functional blockIf the functional block was already in the disabled state a request to disable the functional block is not an errorIf the Node Object functional block is disabled any other request to the Node Object functional block are not disabledStatus and alarm reporting via the ldquonvoStatusrdquo outputs is not disabled when the Node Object functional block is disabled

3 out_of_limits Not supported

4 open_circuit Not supported

5 out_of_service Not supported

6 mechanical fault Not supported

7 feedback_failure Not supported

8 over_range Not supported

9 under_range Not supported

10 electrical_fault Not supported

11 unable_to_measure Not supported

12 comm_failure Not supported

13 fail_self_test Not supported

14 self_test_in_progress Not supported

15 locked_out Not supported

16 manual_control Not supported

17 in_alarm 1 means the drive is in detected fault or in alarm condition

18 in_override Not supported

19 report_mask 1 means nvoStatus is an event maskWhen RQ_REPORT_MASK is required by nvi_request nvoStatus reports as 1 the supported status bit (disabled in_alarm report_mask)(Mandatory for LonMark Node Object)

20 programming_mode Not supported

21 programming_fail Not supported

22 alarm_notify_disabled Not supported

23 reset_complete Not supported

24-31 Reserved Reserved Bits

50 S1A53848 012011

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 51: Schneider ATV212

Network variables and configuration properties

Alarms

Alarm code (nvoDrvAlarm)This variable monitors the fault state of the drive

Range

This LONWORKS network variable is linked to the drive parameters

State Operating status (Fd01) bit 1

Fault code Alarm information monitor (FC90)

Alarm status (nvoAlarmWord)This variable monitors the fault state of the drive by the bit 0 and additional detail by bits 1 6 Bit 0 is redundant with nvoDrvAlarm

Name nvoDrvAlarm

SNVT reference SNVT_switch

SNVT index 95

Format Normal Alarm donrsquot care

State Value Status

0 0 No fault

1 200 (0xC8) Fault

-1 (0xFF) 0 200 Invalid

Name nvoAlarmWord

SNVT reference SNVT_state

SNVT index 83

Format 16 booleans

Bit nb Description ATV212 mapping

0 Detected fault0 [No fault]1 [Fault]

Inverter operating status (Fd01)bit 1

1 Supply detected fault (supply overvoltage phase loss )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 8 30

2 Drive detected fault (overheat power module fault hardware memory internal communication resistor )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 13 16 37 38 39 47 52 33 34 18 19 20 21 22 23 25 26 51 53 55 56 58

3 Motor detected fault (faults downstream of the drive braking overvoltage phase loss overheating )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 1 2 3 4 5 6 7 14 9 10 11 12 32 84 46 40 85 86

4 Process detected fault (overload underload )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 29 57

5 External detected fault (inputs outputs encoder contactor brake )0 [No fault]1 [Fault]

Trip code monitor (FC90) = 15 17 50 54 36 43 44

6 Communication interruption0 [No fault]1 [Fault]

Trip code monitor (FC90) = 24 27

7 to 15 [Reserved]

S1A53848 012011 51

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002000740069006c0020006b00760061006c00690074006500740073007500640073006b007200690076006e0069006e006700200065006c006c006500720020006b006f007200720065006b007400750072006c00e60073006e0069006e0067002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f00630068007700650072007400690067006500200044007200750063006b006500200061007500660020004400650073006b0074006f0070002d0044007200750063006b00650072006e00200075006e0064002000500072006f006f0066002d00470065007200e400740065006e002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 52: Schneider ATV212

Network variables and configuration properties

Measurements

Drive Output Current (nvoDrvCurnt)This output network variable provides the drive output current (01 A)

This value is transmitted immediately when its value has changed significantly Additionally this network variable will also be transmitted as a heartbeat output on a regular basis as specified by the Maximum Send Time (nciSndHrtBt) configuration value

This value will be updated no faster than the Minimum Send Time (nciMinOutTm)

Drive Total Running Hours (nvoDrvRunHours)This output network variable provides the total operation time for the motor in running hours

This value is transmitted immediately when its value has changed

Energy consumption (nvoDrvEnergy)This variable monitors the energy cumulative consumption of the drive

If an overflow occurred the value returns to 0

Torque actual value (nvoTorque)This variable monitors the motor torque The unit is 0005 of Nominal motor torque The Nominal motor torque is not accessible as a drive parameter It is the result of the other characteristics

This LONWORKS network variable is linked to the drive parameter [Output torque] (FE18)

Name nvoDrvCurnt

SNVT reference SNVT_amp

SNVT index 1

Unit 01 A

Range 0 3 27660x7FFF = +3 2767 invalid

Definition Drive Output Current

Name nvoDrvPwr

SNVT reference SNVT_time_hour

SNVT index 124

Unit 1 h

Range 0 65 534 h0xFFFF = 65 535 h invalid

Definition Drive Total Running Hours

Name nvoDrvEnergy

SNVT reference SNVT_elec_kwh_l

SNVT index 146

Unit 01 kWh

Range 0 42 949 6729 kWh

Definition Energy consumption

Name nvoTorque

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005 of Nominal motor torque

Range 0 163830

52 S1A53848 012011

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f0073002000640065002000410064006f0062006500200050004400460020007000610072006100200063006f006e00730065006700750069007200200069006d0070007200650073006900f3006e002000640065002000630061006c006900640061006400200065006e00200069006d0070007200650073006f0072006100730020006400650020006500730063007200690074006f00720069006f00200079002000680065007200720061006d00690065006e00740061007300200064006500200063006f00720072006500630063006900f3006e002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 53: Schneider ATV212

Network variables and configuration properties

Monitoring of digital inputs

Monitoring of digital input F (nvoDigitalIn1)This variable monitors the value of digital input F

This LONWORKS network variable is linked to the drive parameter Value of input F [Input terminal information] (Fd06)

Monitoring of digital input R (nvoDigitalIn2)This variable monitors the value of digital input R

This LONWORKS network variable is linked to the drive parameter Value of input R [Input terminal information] (Fd06)

Monitoring of analog inputs

Monitoring of analog input VIB (nvoAnalogIn2)This variable monitors the analog input VIB ()

This LONWORKS network variable is linked to the drive parameter [Analog input value VIB monitor] (FE36)

The adjustment of analogue input is possible by setting the parameters F472 and F473 (refer to ATV212 programming manual)

Control of digital outputs

Control of relay FL (nviRelay1)This variable enables the command of relay FL of the drive if it is assigned to parameter F132 at 38

This LONWORKS network variable is linked to the drive parameter Relay FL [Terminal Output Data] (FA50) bit 0

Name nvoDigitalIn1

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input F

Name nvoDigitalIn2

SNVT reference SNVT_switch

SNVT index 95

Definition Value of the digital input R

Name nvoAnalogIn2

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range 0000 100000

Definition Value of the analog input VIB

Name nviRelay1

SNVT reference SNVT_switch

SNVT index 95

Definition Command of relay FL

S1A53848 012011 53

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f006200650020005000440046002000700065007200200075006e00610020007300740061006d007000610020006400690020007100750061006c0069007400e00020007300750020007300740061006d00700061006e0074006900200065002000700072006f006f0066006500720020006400650073006b0074006f0070002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 54: Schneider ATV212

Network variables and configuration properties

Emergency

Emergency command (nviEmergOverride)This variable produces an emergency stop of the drive

The emergency state disappears after the trip has been released by nviEmergOverride with value 0

Then it is possible to reset the drive by nviResetFault or a local command

Emergency stop can be configured by parameter [Ext fault stop Mode] (F603) to coast stop slowdown stop or emergency DC braking

Emergency status (nvoEmergStatus)This variable monitors the emergency status of the drive It provides the response against an emergency stop of the inverter (nviEmergOverride) When the node received ldquonviEmergOverriderdquo it propagates the information to the network

Name nviEmergOverride

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 Drive trip release EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

Name nvoEmergStatus

SNVT reference SNVT_hvac_emerg

SNVT index 103

Value Action Comment

0 No emergency stop EMERG_NORMAL (No Emergency mode)

1 Emergency stop EMERG_PRESSURIZE (Emergency pressurize mode)

2 EMERG_DEPRESSURIZE (Emergency depressurize mode)

3 EMERG_ PURGE (Emergency purge mode)

4 EMERG_SHUTDOWN (Emergency shutdown mode)

5 EMERG_FIRE

6 0xFF

54 S1A53848 012011

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 55: Schneider ATV212

Network variables and configuration properties

Adjustment

Maximum Motor Speed (nciMaxSpeed)This configuration property is used to define the maximum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Motor Frequency (nciNmlFreq) configuration value The value of the maximum speed must be validated against the value of the minimum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Upper limit freq] (UL)nciMaxSpeed is also subject to the UL limitationsBy editing nciMaxSpeed the LONWORKS card changes the UL automatically

Minimum Motor Speed (nciMinSpeed)This configuration property is used to define the minimum speed of the motor

The value is entered as a percent of nominal speed in RPM as defined by the Nominal Speed (nciNmlSpeed) configuration value The value of the minimum speed must be validated against the value of the maximum speed as follows

-163840 y minimum speed y maximum speed y 163830

This LONWORKS configuration property is linked to the drive parameter [Low limit frequency] (LL)By editing nciMinSpeed the LONWORKS card changes the LL automatically

Name nciMaxSpeed

SCPT reference SCPTmaxSetpoint

SCPT index 50

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 100000

Definition Maximum Motor Speed

Name nciMinSpeed

SCPT reference SCPTminSetpoint

SCPT index 53

SNVT reference SNVT_lev_percent

SNVT index 81

Unit 0005

Range -163840 163830163 835 = 32 767 = 0x7FFF invalid

Default value 0000

Definition Minimum Motor Speed

S1A53848 012011 55

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 56: Schneider ATV212

Network variables and configuration properties

Nominal Motor Speed in RPM (nciNmlSpeed)This configuration property is used to provide the nominal speed of the motor in RPM This value is necessary to determine the minimum and maximum speed for the motor based on the configuration properties nciMinSpeed nciMaxSpeed (entered as percent of nominal speed)

Nominal Motor Frequency (nciNmlFreq)

This configuration property is used to provide the nominal frequency of the motor It should be set to the rated frequency of the motor This value must be set correctly because the number of motor pole is calculated from this value and nciNmlSpeed

Minimum Ramp Up Time (nciRampUpTm)This configuration property determines the ramp up time of the motor

This LONWORKS configuration property is linked to the drive parameter [Acceleration time 1] (ACC)

Name nciNmlSpeed

SCPT reference SCPTnomRPM

SCPT index 158

SNVT reference SNVT_rpm

SNVT index 102

Unit rpm

Range 0 65534 rpm (65535 rpm is invalid)

Definition Nominal Motor Speed in RPM

Default value 1800 rpm

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciNmlFreq

SCPT reference SCPTnomFreq

SCPT index 159

SNVT reference SNVT_freq_hz

SNVT index 76

Unit 01 Hz

Range 00 1000 Hz (65535 Hz is invalid)

Definition Nominal Motor Frequency

Default value 600 Hz

WARNINGLOSS OF CONTROLChanging this value while the motor is running may cause the motor running at unexpected speedFailure to follow these instructions can result in death serious injury or equipment damage

Name nciRampUpTm

SCPT reference SCPTrampUpTm

SCPT index 160

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Acceleration time 1] (ACC) limitation (The value out of range is invalid)

Definition Minimum Ramp Up Time

Default value 100 s

56 S1A53848 012011

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 57: Schneider ATV212

Network variables and configuration properties

Minimum Ramp Down Time (nciRampDownTm)This configuration property determines the ramp down time of the motor

This LONWORKS configuration property is linked to the drive parameter [Deceleration time 1] (dEC)

Name nciRampDownTm

SCPT reference SCPTrampDownTm

SCPT index 161

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 01 to [Deceleration time 1] (dEC) (The value out of range is invalid)

Definition Minimum Ramp Down Time

Default value 100 s

S1A53848 012011 57

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 58: Schneider ATV212

Network variables and configuration properties

Parameter access

nviParamCmd nvoParamRespA controller node can monitor or modify any drive parameter by supporting the Parameter access command and the Parameter access response functions These functions allow a controller complete access to the features of the drive and the ability to configure drives with predefined settings using the network variables nviParamCmd and nvoParamResp

The following definitions describe how the fields of SNVT_preset are used by the LONWORKS card of the drive

LearnThis field contains the function code for the ATV212 The values for this field are

Any other value in this field will result in an error message in the Parameter access response

SelectorThis field contains the drive parameter communication number written in decimal notation that is to be written or read Requests for undefined parameters will result in an error message in the Parameter access response

The controlling device should compare the parameter address of the response message to the requested parameter address to determine that the information received is the requested information and not a response to another controller or from another drive

The drive parameters are described in the Altivar 212 programming manual and Modbus communication manual with their logic address and possible values

ValueThis array contains the parameter information to and from the drive All drive parameters use INT or UINT (16 bit words signed or unsigned)

The most significant byte of data will be stored in value [2] and the least significant byte of data will be stored in value [3]

In the event of an error message the drive will send 0xFF in value [0] and an error code in value [3]

Error codes

Day Hour Minute Second MillisecondThe time fields are not supported by the LONWORKS card The drive will respond to parameter access requests as soon as they are received Any values in the time fields of the Parameter access command will be ignored All time fields will be set to ldquo0rdquo in the Parameter access response

Name nviParamCmd Name nvoParamResp

SNVT reference SNVT_preset SNVT reference SNVT_preset

SNVT index 94 SNVT index 94

Format Structure 14 bytes Format Structure 14 bytes

Definition Parameter access command Definition Parameter access response

Value Element Action

3 LN_REPORT_VALUE Read command

2 LN_LEARN_VALUE Write command (to the EEPROM)

Code Meaning

1 Illegal function for the addressed node

2 Illegal parameter address

3 Illegal data value

4 Illegal access (writing prohibited)

58 S1A53848 012011

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002000740069006c0020006b00760061006c00690074006500740073007500640073006b007200690076006e0069006e006700200065006c006c006500720020006b006f007200720065006b007400750072006c00e60073006e0069006e0067002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 59: Schneider ATV212

Network variables and configuration properties

Example 1 Read accessA controller node reads the value of Trip code (address FC90) Now OL1 trip (trip code is 13 decimal) occurs The value is 000D hex The controller node sendsreceives the following data

Example 2 Write accessThe controller node writes cumulative energy clear command (address FA20) The data value is 0002 hex The controller node sendsreceives the following data

Note After sending cumulative energy clear command 0000 hex should be re-written into FA20

Example 3 Illegal accessIllegal data is written to the inverter parameter [Motor 2 rated Volt] (F171) (Base frequency voltage address 0171)

The upper limit value is 3300V (200 V class) In case of writing 3600V the unit of this parameter is 01V and the data value is converted to hex so the value is 0E10 hex The controller node sendsreceives the following data (out of range error)

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_REPORT_VALUE LN_REPORT_VALUE

selector FC90 hex FC90 hex

value[0] NA 00 hex

value[1] NA 00 hex

value[2] NA 00 hex

value[3] NA 0D hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector FA20 hex FA20 hex

value[0] 00 hex 00 hex

value[1] 00 hex 00 hex

value[2] 00 hex 00 hex

value[3] 02 hex 02 hex

day hour minute second millisecond NA 0

Field Send (nviParamCmd) Receive (nviParamResp)

learn LN_LEARN_VALUE LN_LEARN_VALUE

selector 0171 hex 0171 hex

value[0] 00 hex FF hex

value[1] 00 hex 00 hex

value[2] 0E hex 00 hex

value[3] 10 hex 03 hex

day hour minute second millisecond NA 0

S1A53848 012011 59

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002000740069006c0020006b00760061006c00690074006500740073007500640073006b007200690076006e0069006e006700200065006c006c006500720020006b006f007200720065006b007400750072006c00e60073006e0069006e0067002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt DEU 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 ESP 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f007500720020006400650073002000e90070007200650075007600650073002000650074002000640065007300200069006d007000720065007300730069006f006e00730020006400650020006800610075007400650020007100750061006c0069007400e90020007300750072002000640065007300200069006d007000720069006d0061006e0074006500730020006400650020006200750072006500610075002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 60: Schneider ATV212

Network variables and configuration properties

Identification

Location Label (nciLocation)This configuration property can optionally be used to provide more descriptive physical location information than can be provided by the Neuron Chips 6 byte location string The string may be loaded from the LONWORKS network

Identification (nvoTypeVer)This variable provides identification data from the drive (Brand commercial reference version)

The string is composed of Brand space commercial reference space V major revision (1 character) minor revision (maximum 2 characters)

Example

Telemeca ATV212H075N4 V183

Name nciLocation

SCPT reference SCPT_Location

SCPT index 17

SNVT reference SNVT_str_asc

SNVT index 36

Range Any NULL terminated ASCII string of 31 bytes total length (30 bytes ares available because 31th byte is a NULL)

Default value The default value is an ASCII string containing all zeros (0)

Definition Location Label

Name nvoTypeVer

SNVT reference SNVT_str_asc

SNVT index 36

Format ASCII string (ended by NULL terminator)

Definition Identification of the drive

60 S1A53848 012011

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 61: Schneider ATV212

Network variables and configuration properties

Network management

Send Heartbeat Time (nciSndHrtBt)This configuration property defines the maximum period of time that expires before automatic update of the network variables

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Receive Heartbeat Time (nciRcvHrtBt)This configuration property is used to control the maximum time that elapses after the last update of at least one of the network variables

bull Drive Speed Setpoint (nviDrvSpeedStpt)bull Drive Speed Setpoint Scaling (nviDrvSpeedScale)bull Frequency setpoint (nviInvSetFreq)

When these variables are not updated within the heartbeat time the LONWORKS card will detect a communication interruption and nviDrvSpeed nviDrvSpeedScale and nviInvSetFreq will return to their initial value The timer starts when drive receive the first update of one of these network variables

It is possible to configure the behaviour of the drive in case of LONWORKS communication interruption please refer to page 34

Name nciSndHrtBt

SCPT reference SCPTmaxSendTime

SCPT index 49

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)

Default value 00 (no automatic update)

Definition Send Heartbeat Time

Name nciRcvHrtBt

SCPT reference SCPTmaxRcvTime

SCPT index 48

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 s (65535 s is invalid)00 (no interruption detection)

Default value 00 (no interruption detection)

Definition Receive Heartbeat Time

S1A53848 012011 61

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f0074002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a00610020006c0061006100640075006b006100730074006100200074007900f6007000f60079007400e400740075006c006f0073007400750073007400610020006a00610020007600650064006f007300740075007300740061002000760061007200740065006e002e00200020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 62: Schneider ATV212

Network variables and configuration properties

Minimum Send Time (nciMinOutTm)This configuration property defines the minimum period of time between automatic network variable transmissions This function is active prior to nciSndHrtBt

Power supply start waiting time (nciPwUpOutTm)Waiting time until the drive starts transmission after reset or power on

When a setting value is 0 transmission will start after the initialization of the LONWORKS card is finished

This configuration property freezes the transmission of the network variables concerned by nciSndHrtBt

bull nvoDrvSpeedbull nvoDrvCurntbull nvoDrvRunHoursbull nvoStatusWordbull nvoDrvFeedbackbull nvoInvOutFreqbull nvoDrvAlarmbull nvoTorquebull nvoDrvEnergybull nvoDigitalIn1bull nvoDigitalIn2bull nvoAnalogIn2

Name nciMinOutTm

SCPT reference SCPTminSendTime

SCPT index 52

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 65534 s (65535 s is invalid)

Default value 05 s

Definition Minimum Send Time

Name nciPwUpOutTm

SCPT reference SCPTpwrUpDelay

SCPT index 72

SNVT reference SNVT_time_sec

SNVT index 107

Unit 01 s

Range 00 6 5534 sValues 3000 6 5534 are limited to 3000 s00 Transmission starts immediately after initialisation of the LONWORKS card is finished

Default value 00 s

Definition Power supply start waiting time

62 S1A53848 012011

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f00630068007700650072007400690067006500200044007200750063006b006500200061007500660020004400650073006b0074006f0070002d0044007200750063006b00650072006e00200075006e0064002000500072006f006f0066002d00470065007200e400740065006e002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 63: Schneider ATV212

Network variables and configuration properties

S1A53848 012011 63

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f0074002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a00610020006c0061006100640075006b006100730074006100200074007900f6007000f60079007400e400740075006c006f0073007400750073007400610020006a00610020007600650064006f007300740075007300740061002000760061007200740065006e002e00200020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 64: Schneider ATV212

S1A53848 012011

ATV212_Lonworks_manual_EN_S1A53848_01

  • Altivar 212
  • Table of Contents
  • Safety Information
  • About the Book
  • Introduction
  • Hardware setup
    • Receipt
    • Opening the drive
    • Installing the LonWorks communication card in ATV212
    • Hardware description
    • Use of open Style Connector
    • Description of terminals
      • Connecting to the bus
        • Topology
        • Cable routing practices
        • Connecting the LonWorks connector
          • Configuration
            • Communication parameters
            • Configuration of the control
            • Configuring the behaviour on configuration interruption
              • Diagnostics
                • Communication detected fault
                • List of type supported by ATV212 Service LED
                • Troubleshooting
                  • Functional profile
                    • Objects supported
                    • LonMark Node Object profile
                    • LonMark Variable Speed Motor Drive profile
                      • Network variables and configuration properties
                        • List of network variables and configuration properties
                        • Commands and setpoints
                        • Status and output velocity
                        • Alarms
                        • Measurements
                        • Monitoring of digital inputs
                        • Monitoring of analog inputs
                        • Control of digital outputs
                        • Emergency
                        • Adjustment
                        • Parameter access
                        • Identification
                        • Network management
                            • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False CreateJDFFile false Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice