25
1 2 4 5=3X4 6 = % Excise Duty 7= (3X4X6) 8= % sales & other taxes 9=(5+7) X 8 10=(5+7+9) (I) SWITCHYARD PART A Supply and Erection of 220kV Switch Yard Equipments considering 31mm/KV creepage distance due to marine atmosphere of site (as per respective Technical Specifications and relevant special conditions ) suitable for 2 Bus system 1 220 KV Indoor GIS Equipment (Separate Enclosure for Each Phase shall be considered) 1.1 3- Ø 220 kV, 2000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Line bay Module comprising Sets 10 Circuit breaker Current transformer 1500-1200-600/1A ( no. of cores as per TS) -1 no for each phase Line side Disconnector with one maintenance earthing switch High speed/Fast Acting Line Earthing switch Bus Disconnector with Earthing switch (Bus side common earthing switch for two bus) Bus Disconnector without Earthing switch SF6 Gas Insulated Bus Duct (GIB) from respective GIS bay module up to SF6 to Air insulated polymer housed bushings including required support structures and other accessories LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Bus bar Module comprising Sets 2 3 X Single phase Voltage transformer 220KV/ SQRT 3//110V/ SQRT 3 - sagrigated from bus bar unit High speed/Fast Acting Earthing switch Bus Disconnector with Earthing switch All other items as per technical specification 1.3 3- Ø 220 kV, 2000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Bus Coupler bay Module comprising Set 1 Circuit breaker Current transformer 1500-1200-600/1A ( no. of cores as per TS) -1 no for each phase Bus Disconnector with one Earthing switch -2 nos. LCC Panel All other items as per technical specification Total EXW Price 1 EXW Unit price 1 Excise Duty Taxes and Duties 220KV GIS KALAWAD SUBSTATION Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country 3 Unit of Measurement Quantity Sr No Sales and other Taxes Description Page 1 of 25

Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

1 2 4 5=3X46 = % Excise

Duty7= (3X4X6)

8= % sales & other taxes

9=(5+7) X 8

10=(5+7+9)

(I) SWITCHYARD PART

A Supply and Erection of 220kV Switch Yard Equipments considering 31mm/KV creepage distance due to marine atmosphere of site (as per respective Technical Specifications and relevant special conditions ) suitable for 2 Bus system

1 220 KV Indoor GIS Equipment (Separate Enclosure for Each Phase shall be considered)

1.1 3- Ø 220 kV, 2000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Line bay Module comprising Sets 10

Circuit breaker

Current transformer 1500-1200-600/1A ( no. of cores as per TS) -1 no for each phase Line side Disconnector with one maintenance earthing switch

High speed/Fast Acting Line Earthing switch

Bus Disconnector with Earthing switch (Bus side common earthing switch for two bus)Bus Disconnector without Earthing switch

SF6 Gas Insulated Bus Duct (GIB) from respective GIS bay module up to SF6 to Air insulated polymer housed bushings including required support structures and other accessoriesLCC Panel

All other items as per technical specification

1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Bus bar Module comprising Sets 2

3 X Single phase Voltage transformer 220KV/ SQRT 3//110V/ SQRT 3 -sagrigated from bus bar unit

High speed/Fast Acting Earthing switch

Bus Disconnector with Earthing switch

All other items as per technical specification

1.3 3- Ø 220 kV, 2000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Bus Coupler bay Module comprising Set 1

Circuit breaker

Current transformer 1500-1200-600/1A ( no. of cores as per TS) -1 no for each phase Bus Disconnector with one Earthing switch -2 nos.

LCC Panel

All other items as per technical specification

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

3

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

Page 1 of 25

Page 2: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

1.4 3- Ø 220 kV, 2000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - 220/66 KV Transformer bay Module comprising Sets 3

Circuit breaker

Current transformer 1500-1200-600/1A ( no. of cores as per TS)-1 no for each phase

Transformer side Disconnector with one maintenance earthing switch Earthing switch

Bus Disconnector with Earthing switch (Bus side common earthing switch for two bus)Bus Disconnector without Earthing switch

SF6 Gas Insulated Bus Duct (GIB) from respective GIS bay module up to SF6 to Air insulated polymer housed bushings including required support structures and other accessoriesLCC Panel

All other items as per technical specification

1.5 3- Ø 220 kV, 2000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear for 400/220 KV Transformer bay Module comprising Sets 3

Circuit breaker

Current transformer 1500-1200-600/1A ( no. of cores as per TS)-1 no for each phase Transformer side Disconnector with one maintenance earthing switch

Earthing switch

Bus Disconnector with Earthing switch (Bus side common earthing switch for two bus)Bus Disconnector without Earthing switch

SF6 Gas Insulated Bus Duct (GIB) from respective GIS bay module up to SF6 to Air insulated polymer housed bushings including required support structures and other accessoriesLCC Panel

All other items as per technical specification

2 Supply and Erection of 220kV outdoor Equipments considering 31mm/KV creepage distance due to marine atmosphere of site as per respective technical specifications suitable for 2 Bus system.

2.1 Polymer housed Surge Arrester 198kV, 10kA, Cl-3 with structure and clamp connectors

Nos. 39

2.2 220kV Composite solid core station post insulator with structure and clamp connectors

Nos. 30

2.3 220kV Composite solid core station post insulator with high level structure and clamp connectors (Total height: 6.8mtr.)

Nos. 9

2.4 220kV SF6 to Air insulated polymer housed bushing 1- Phase with structure and clamp connectors Nos. 48

Page 2 of 25

Page 3: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

B Supply and Erection of Galvanised Structure /Material for 220kV Switch Yard suitable to marine atmosphere (as per respective Technical Specifications and relevant special conditions ) suitable for 2 Bus scheme.

1 Gantry structures GI as per BOM, Steel & A/B part MT 42.92 Gantry structures GI as per BOM, Bolt nut part MT 2.43 Lighting Mast structure - Steel & A/B part MT 33.84 Lighting Mast structure - Bolt nut part MT 1.4

Note: The weight of structures may vary as per design of structure.

5 Stringing of Flyover bus with Following Conductor for all the three phases with required Silicon Rubber Insulators, hardwares & accessories, spacers provided at every 5.0 mtr. interval (Suitable for 350mm spacing)etc. complete as per relevant standards and approved drawings with Jumpers for continuous Bus Arrangement.

5.1-B Break Up of Supply Items for Erection of above workAL-59 Conductor Rmtr. 900Silicon Rubber Insulator string-120KN No. 60Double Tension H/W & Acc with Sag Plate.suitable for Twin AL-59 cond. & 120kN SRI

No. 15

Double Tension H/W & Acc without Sag Plate.suitable for Twin AL-59 cond. & 120kN SRI

No. 15

Spacers suitable for Twin AL-59 (350mm Spacing) No. 756 Droppers (including required suspension string with hardware & accessories, if

any) & Jumpers (including Equipment to Equipment) with Following conductor as per standards and approved drawings with provision of required spacers (Suitable for 350mm spacing) at every 5.0 mtr. interval.

6-B Break Up of Supply Items for Erection of above workAL-59 Conductor RMtr 1770Silicon Rubber Insulator string-120KN No. 30Single Suspension H/W & Acc. Suitable to Twin AL-59 conductor No. 30Spacers suitable for Twin AL-59 (350mm Spacing) conductor No. 108Fire Wedge Connectors suitable for AL-59 Conductor to AL-59 conductor No. 110

7 Stringing of Earth Wire with 7/3.15 GS wire with required hardwares accessories etc. complete as per standards and approved drawings as per DSLP Calculation,if required free of cost.

Page 3 of 25

Page 4: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

C Supply and Erection of 66kV Switch Yard Equipments considering 31mm/KV creepage distance due to marine atmosphere of site (as per respective Technical Specifications and relevant special conditions ) suitable for 2 Bus system

1 66 KV GIS Indoor Equipment 1.1 3- Ø 66 kV, 1600 A, 25 kA-3 sec, metal enclosed SF6 Gas Insulated

Switchgear - Line bay Module comprising Sets 10

Surge Arrester 60kV,10kA, Class 3 suitable for connection of 66kV Power Cable-1 no for each phase (To be provided at Outside GIS building)Circuit breakerCurrent transformer 600-300/1A ( no. of cores as per TS)Line side Disconnector with one maintenance earthing switch

High speed/Fast Acting Line Earthing switch Voltage Transformer, 66KV/√3//110V/√3, 3 CBus Disconnector with Earthing switch (Bus side common earthing switch for two bus)Bus Disconnector without Earthing SwitchLCC Panel All other items as per technical specification

1.2 3- Ø 66 kV, 2000 A, 25 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Bus bar Module comprising

Sets 2

3 X Single phase Voltage transformer 66KV/ SQRT 3//110V/ SQRT 3 -sagrigated from bus bar unit High speed/Fast Acting Earthing switch Bus Disconnector with Earthing switch

All other items as per technical specification

1.3 3- Ø 66 kV, 1600 A, 25 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Bus Coupler bay Module comprising

Set 1

Circuit breaker Current transformer 1500-1200/1 ( no. of cores as per TS)Bus Disconnector with one Earthing switch -2 nos.LCC Panel All other items as per technical specification

1.4 3- Ø 66 kV, 1600 A, 25 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - 220/66 KV Transformer bay Module comprising

Sets 3

Circuit breakerCurrent transformer 1500-1200/1A ( no. of cores as per TS) Transformer side Disconnector with one maintenance earthing switch Earthing switch Bus Disconnector with Earthing switch (Bus side common earthing switch for two bus)Bus Disconnector without Earthing Switch

Page 4 of 25

Page 5: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

LCC Panel All other items as per technical specification

1.5 3- Ø 66 kV, 1600 A, 25 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - 66/11 KV Transformer bay Module comprising Set 1

Circuit breaker

Current transformer 100-50/1A ( no. of cores as per TS)

Transformer side Disconnector with one maintenance earthing switch Earthing switch

Bus Disconnector with Earthing switch (Bus side common earthing switch for two bus)Bus Disconnector without Earthing Switch

LCC Panel

All other items as per technical specification

2 Supply and Erection of 66kV outdoor Equipments considering 31mm/KV creepage distance due to marine atmosphere of site as per respective technical specifications suitable for 2 Bus system.

2.1 Polymer housed Surge Arrester 60kV, 10KA, Class 3 with structure suitable to hold 66kv,630sqmm. XLPE power cable and clamp connectors suitable for Single AL-59 conductor -1 no for each phase

Nos. 3

2.2 Polymer housed Surge Arrester 60kV, 10KA, Class 3 with high level structure (Total height :8mtr.) and clamp connectors suitable for connection of 4" IPS pipe -1 no for each phase

Nos. 9

2.3 66kV composite solid core station post insulator with high level structure suitable to hold 66kv,630sqmm. XLPE power cable(3+1) (Total height :8mtr.) and clamp connectors suitable for connection of 4" IPS pipe

Nos. 9

2.4 66kV composite solid core station post insulator with high level structure (Total height :5.5 mtr.) and clamp connectors suitable for connection of 4"IPS Pipe. Nos. 9

2.5 Installation of 4" IPS Heavy Duty Al. Tube (Sh.80) with required Corona Bell, Jointing Sleeves, Homogeneous argon welding jointing etc. arrangement as per standard and complete as per approved drawings for all three phases.

Rmtr LS

2.6 Connectors suitable for 4" IPS pipe to 66kv,630 Sq.mm XLPE Power Cable Nos. 302.7 Connectors suitable for 4" IPS pipe to Twin AL-59 Conductor Nos. 92.8 Connectors suitable for Single AL-59 conductor to 630Sq.mm. ,66kv XLPE Power

CableNos. 3

D Testing & Maintenance Equipment shall be provided as per Annexure-B as below

Testing & Maintenance Equipment for GIS 1 Gas filling and Evacuating Plant for GIS as per - DILO make (Model 3-001-4-

R002)set 1

2 Gas Recovery unit, DILO make (Model B057R17) with required accessories namely Pressure tank storage capacity 70Kg, Rubber Hose and packing with heat

set 1

Page 5 of 25

Page 6: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

3 Dew point measurement meter- DILO Make (Model 3-035-R020) set 14 SF6 gas leakage detector - DILO Make (Model 3-033-R002) set 15 Computer set with UPS dust cover etc as per technical specifications ( for officer in

charge) set 1

6 A-4 size mono laser printer as per technical specifications.( for officer In charge) set 1

7 Earth Resistance Tester Digital GE-OHM C make Model no EN 61557/VDE 0413 or updated version with better features.

No 1

8 Insulation Resistance Tester (Test volt upto 5kV, Range 100kohm to 10 Tohm), Megger Make, Model-S1568

No 1

9 LCM Kit (Range :Total leakage current- 200µA to 9mA, Resistive leakage current- 1µA to 9mA) Make : Doble- LCM 500(Wireless)

No 1

10 Insulation Diagnostic Analyzer, Model: IDAX300 Megger make No 111 Measurement system for testing overhead lines and high voltage cables to

determine parameters of voltage class upto 400KV namely, Impedence(Z), line No 1

12 Clip on meter AC/DC V/I/OHM -0-1000V, 0-25A Meco/Rishabh/ Motwane Make No 1

13 Motor and manual Operated Oil BDV testing Kit –Megger(OTS 100AF)/BAUR (DTA100C) make with 0-100kV range, auto cut off feature, with standard ball -cup

No 1

14 Hydraulic Platform with Loading Capcity of 350kg. and height of 10m (Firefly Energy Ltd Make,Model-A.N.I.L)/(VANJAX Make, Model-VXLTM-350/11000)

No. 1

15 Emergency Power Supply Unit (Make- Aux Power- Wavelength system & solution,Output voltage-220V DC)

No. 1

16 Portable hand-held PD measurement kit with all required accessories suitable for GIS- Doble make (Model DFA100)

No. 1

17 CB Analyzer with 6-Channel DCRM kit with all required accessories suitable for GIS Model: HiSAC-Ultima –SCOPE make with suitable Laptop

No. 1

18 Tan Delta Kit- Doble Make (Model-M4100)/ Megger (Delta-4000) No. 119 GPS Instrument (Trimble JUNO SA handheld GPS) No. 120 Hydraulic Pallet Truck (Wont Ind Equip.-Type: W-HOPT 25) No. 1E EOT Crane of suitable capacity (minimum 5T safe working load) with single

hook and double girder arrangement. Contractor shall submit the capacity calculation of the crane. There shall be provision for lifting arrangement of EOT crane for maintenance purpose. However, Contractor shall submit the capacity calculation of the crane considering erection and maintenance of largest GIS component / assembly.

Nos. 1

F Visual Monitoring System (VMS) as per technical specification. (Alongwith local PC monitoring set up, remote end PC monitoring set up shall be in the scope of supply)

Lump sum LS

G Ventilation system (for maintaining positive pressure) shall be provided for following building as per Technical Specifications

a) 220 & 66 KV GIS Hall Lump sum LS

Page 6 of 25

Page 7: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

H Fire Detection and Alarm System as per Technical Specification Lump sum LS

I Supply and installation of Portable and wheel/trolley mounted fire extinguishers for Control room, 220&66kV GIS Hall, Relay panel room of GIS Hall,Transformers,Reactors and other Strategic locations as per Technical Specification.1) Dry chemical powder type of 9 Kg. capacity. No. 52) Dry chemical powder type of 25 Kg. capacity. No. 33) Dry chemical powder type of 50 Kg. capacity. No. 34) Carbon dioxide ( CO2) gas type of capacity 6.5 Kg. capacity No. 85) Carbon dioxide (CO2) gas type of capacity 22.5 Kg. capacity No. 56) Mechanical Foam type of capacity 9 LT. No. 37) Mechanical Foam type of capacity 50 LT. No. 3

J Supply and installation of Tower/Split Air Conditioner Machine at following Locations.

A) 3 Ton Capacity Split AC (5 star rating and reputed make)1) LCC Room of 220&66kV GIS Nos. 11

B) 3Ton Capacity Tower AC (5 star rating and reputed make)1) SCADA Control Room Nos. 22) Conference Room Nos. 2

C) 1.5 Ton Capacity Split AC (5 star rating and reputed make)1) Testing Lab Nos. 22) Admin. Offices Nos. 73) Reception cum Waiting Room Nos. 34) Security Officer Cabin Nos. 1

Page 7 of 25

Page 8: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

K Supply and Erection of General purpose equipments and materials as per respective technical specifications and relevant special conditions.

1 Suitable arrangement of 11KV connection (A) from 5 MVA station TR to one no. of 11kV/415V, 500 kVA distribution transformer which comprises of: 1) 22 kV outdoor CT having ratio 300-150/1-1-0.577A, STC: 25 kA – 3 sec, BIL 55/150 kVp.2) 22 kV outdoor VCB, 1250A, STC: 25 kA – 3 sec, BIL 55/150 kVp.3) 22 kV outdoor Isolator, 630A, STC: 25 kA – 3 sec.4) 9 KV LA5) 22KV outdoor PT having ratio 22kv/√3- 110v/√3- 2 corewith support structure, insulated conductor and DP structure with DO fuse, 22kV BPIs arrangement including Dist box suitable to dist transformer. and (B) from separate 11 KV express feeder (feeder termination shall be arranged by GETCO) to another 11kV/415V, 500 kVA distribution transformer which comprises of:1) 22 kV outdoor Isolator, 630A, STC: 25 kA – 3 sec.2) 9 KV LAwith support structure, insulated conductor and DP structure with DO fuse, 22kV BPIs arrangement including Dist box suitable to dist transformer. (11KV Power Cable shall be supplied by GETCO, however Laying of cable is in the scope of bidder)

Package LS

2 66/11kV 5MVA Station Transformer with oil and accessories having 11kv Side Cable Box arrangement as per specification.NOTE: 5 MVA 66/11.55 KV Station Transformer bushings shall be having creepage distance of 31 mm/KV. Also 66 KV Bushing shall be with polymer insulator instead of porcelain. Required type test reports as per applicable standards shall be submitted.

Nos. 1

3 Distribution Transformer 11kV/415V,500 kVA with suitable Dist. Box and its fixing -mounting arrangement as per drg. No. GETCO/E/2S-STD/P-031/LTD R0 Dtd. 11-03-15. Required LT Distribution boxes with LT cable and changeover switch supply is in the scope of bidder.

Set 2

4 DG set 250 KVA suitable for Outdoor plinth mounting with required panels and accessories as per Technical Specification. Set 1

Page 8 of 25

Page 9: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

5 Providing major spares and Tools & Tackles as per 'Annexure-A' as below

(A) 220 kV Gas Insulated Switchgear

1 General

1.1 SF6 gas Pressure Relief Devices, 3 Nos. - One each used in Bay Module,CB Module and Bus Bar Module

Nos. 3

1.2 SF6 Pressure gauge cum switch or density monitors and pressure switch 3 Nos. - One each used in Bay Module,CB Module and Bus Bar Module

Nos. 3

1.3 “O” Rings or Seals of original material & Size used in Single Phase GIS Module of each type (Bay Module,CB Module and Bus Bar Module)

Set 1

1.4 Molecular sieve in tamper,moisture & leak proof packing. Weight of each packing shall be equal to that to be used in GIS Module consists of 3 phase 1 bay

Set 1

1.5 All types of Control Valves for SF6 gas with coupler, 3 Nos. - One each used in Bay Module,CB Module and Bus Bar Module

Nos. 3

1.6 Covers/Shields with all accessories necessary to close a compartment in case of dismantling of any part of the Enclosure so that system can be pressurised and dielectrically tested for all 3 Phase. ( 3 phase required , one complete bay)

Set 1

1.7 Locking device to keep the Dis-connectors (Isolators) and Earthing switches in close or open position in case of removal of the driving Mechanism for one complete bay.(3 Phase)

Set 1

1.8 Each type of Insulator cones which support bus bar used in single bay for line , Transformer & Bus bar module

Set 1

1.9 SF6 to air bushing Nos. 3

1.10 Motor of Each type and rating used in CB,Disconnector,HSE and Earth switch used in 1-phase module

Set 1

1.11 Limit switches and Aux. Switches of each type used in CB,Disconnector,HSE and Earth switch used in 1-phase module

Set 1

2.0 For GIS 220 kV Circuit Breaker

2.1 Complete Circuit Breaker pole with interrupter, main circuit, enclosure and operating mechanism

No. 1

2.2 Trip coil assembly used in CB Module (3 Phase) Nos. 6

2.3 Closing coil assembly used in CB Module (3 Phase) Nos. 3

2.4 Relays, Power contactors, push buttons, timers & MCBs etc of each type & rating provided in LCC of one bay module

Set 1

3 For GIS 220 kV ISOLATORS 3.1 Complete set of single phase dis-connector including main circuit, enclosure,

driving mechanism etc.Nos. 3

3.2 High speed/Fast acting fault making grounding switch (3 nos of single phase) including main circuit , enclosure and driving mechanism etc.

No. 1

3.3 Single phase Earthing switch including main circuit, enclosure, driving mechanism etc.

No. 1

Page 9 of 25

Page 10: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

4.0 For GIS 220 KV CURRENT TRANSFORMER

4.1 CTs used in one module - complete for Transformer Bay and Line Bay/Bus Coupler Bay with enclosure (Single phase requirement)

Set 1

5.0 For GIS 220kV Potential Transformer 5.1 Gas Insulated Complete 1-Ph PT (Single phase requirement) No. 1

6 Spares for E O T crane

6.1 Hoist Motor No. 1

6.2 C.T. Motor No. 1

6.3 L.T.Motor No. 1

6.4 All type of Limit switches used in EOT crane Set 1

6.5 All type of brakes used in EOT crane Set 1

(B) 66 kV Gas Insulated Switchgear

1 General

1.1 SF6 gas Pressure Relief Devices, 3 Nos. - One each used in Bay Module,CB Module and Bus Bar Module

Nos. 3

1.2 SF6 Pressure gauge cum switch or density monitors and pressure switch 3 Nos. - One each used in Bay Module,CB Module and Bus Bar Module

Nos. 3

1.3 “O” Rings or Seals of original material & Size used in GIS Module of one bay (Bay Module,CB Module and Bus Bar Module)

Set 1

1.4 Molecular sieve in tamper,moisture & leak proof packing. Weight of each packing shall be equal to that to be used in GIS Module for 1 bay

Set 1

1.5 All types of Control Valves for SF6 gas with coupler, 3 Nos. - One each used in Bay Module,CB Module and Bus Bar Module

Nos. 3

1.6 Covers/Shields with all accessories necessary to close a compartment in case of dismantling of any part of the Enclosure so that system can be pressurised and dielectrically tested for one complete bay

Set 1

1.7 Locking device to keep the Dis-connectors (Isolators) and Earthing switches in close or open position in case of removal of the driving Mechanism for one complete bay.

Set 1

1.8 Each type of Insulator cones which support bus bar used for line , Transformer & Bus bar module

Set 1

1.9 Motor of Each type and rating used in CB,Disconnector,HSE and Earth switch used in one complete bay

Set 1

1.10 Limit switches and Aux. Switches of each type used in CB,Disconnector,HSE and Earth switch used in one complete bay

Set 1

2.0 For GIS 66 kV Circuit Breaker

2.1 Complete Circuit Breaker pole with interrupter, main circuit, enclosure and operating mechanism

No. 1

2.2 Trip coil assembly used in CB Module Nos. 2

2.3 Closing coil assembly used in CB Module Nos. 1

Page 10 of 25

Page 11: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

2.4 Relays, Power contactors, push buttons, timers & MCBs etc of each type & rating provided in LCC of one bay module

Set 1

3 For GIS 66 kV ISOLATORS

3.1 Complete set of 3 phase dis-connector including main circuit, enclosure, driving mechanism etc.for one bay

Nos. 1

3.2 High speed/Fast acting fault making grounding switch including main circuit , enclosure and driving mechanism etc. for one complete bay.

No. 1

3.3 Three phase Earthing switch including main circuit, enclosure, driving mechanism etc.

No. 1

4.0 For GIS 66 KV CURRENT TRANSFORMER

4.1 CTs used in one module - complete for Transformer Bay and Line Bay/Bus Coupler Bay with enclosure

Set 1

5.0 For GIS 66kV Potential Transformer

5.1 Gas Insulated Complete 1-Ph PT No. 1

(C) DG set ( portable three phase 415V 10 KVA Honda / Kirlosakar make) set 1

(D) Welding M/C: Input volt.230-440V(single/two phase), 50Hz, Insulation class A, 200 Amp. With 30 m welding cable

set 1

(E) Tools & Tackles (General)

1 Earthing Rod (Highly insulated FRP telescopic Earthing/ Discharge Rod. with cable suitable for 400 & 220kV Switchyard- National Make

Nos 18

2 Spanner [Ring, Fixed, Box] Fix=10x11,12x13,14x15,,16x17Ring=10x11,12x13,14x15,16x17 Tubular=12x13,14x15,16x17,18x19 Screw driver=827I,927 Nut driver= 7mm - Taparia/Gedore/Zalani Make

Set 3

3 Steel Roller -Size 1" Nos 10

4 Aluminium Roller -Size 4" Nos 5

5 One/two/three Wheel pulley -Size 1" (Gadore) Nos 2

6 Winch Machine with Handle -05 Ton Capacity Nos 2

7 Hydraulic Press Machine with Dog, panther, zebra & moose dye sets--100 Ton Capacity ( Hydraulic force ent. / Techno spent )

Nos 2

8 Hand drill Wolf Make 240 V Capacity :-Hole up to 31 mm , Single Phase Nos 1

9 Drill Machine -5/8" Dia Wolf Make Standing Drill machine having 3 Feet Pillar & suitable for making Holes up to ¾”. Motor

Nos 2

10 Chain pulley block -5 tonne capacity (Morries) Nos 2

11 Wire rope pulley block -02 Tonne (Morries) Set 1

12 Tent-Standard quality water proof Tent made from H.D.P.E. Materials with 5 Nos of bamboos Rods and having capacity of 8 to 10 Person to stay & size 10 Ft x 10Ft Multipurpose

Set 1

13 Water pump (Crompton Make) Set -5 HP with hose pipe of 30 m Crompton Make Nos 2

Page 11 of 25

Page 12: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

15 Crowbar -1.5 Mtr Nos 5 16 Crowbar -1.0 Mtr Nos 5 17 Hammer with wooden handle -10Kg Nos 1 18 Pickaxe ( Trikam) -2 '' width with handle Nos 5 19 Pawda[shovel] -12 '' width with handle Nos 5 20 Axe (Kuhadi) with handle Nos 5 21 Sythe (Dharia) with handle Nos 10 22 Tar Poline (Tad Patri) 5X5 m (HDPE), 200 GSM Nos 5 23 Nylon Rope -0.5" Dia -100 mtrs (Garware Make) Bundle 1 24 Nylon Rope 0.75" Dia -100 mtrs (Garware Make) Bundle 1 25 Nylon Rope -1" Dia -100 mtrs (Garware Make) Bundle 1

26 Aluminium Ladder -15 ft. Aluminium folding factory ladder (Heavy duty) made from high tensile aluminium alloy design no 152 AFFL 15 Ft height (4.56 mtrs) specification section= 15/8” X 1.1/4” Steps= 15/8 X 1.1/4 12”Center to Center

Set 1

27 Telescopic aluminium ladder(3 sections) with platform -25 ft Nos 1

28 Hot air blower (Wolf Make)

Small Capacity =1.5m3/min, Nos 1 Big Capacity =2.0m3/min Nos 1

29 Vaccum cleaner -Eureka Forbes Make (Industrial) Nos 1

Safety Tools

1 Full body Harness as per technical specification Nos 152 Halmet with ISI mark of reputed make Nos 103 Hand Gloves Hand gloves of quality as per IS certification 4770 & test potential

7500Volt Pair 6

4 Gum boot (Pair) -Size 8,9,10. -Standard make Pair for each size

3

Display Boards and others

1 Single line diagram drawn with radium paint on a board of approx size of 1200x900 mm with fixing arrangement on control room wall.

Set 1

2 Gas Single line diagram drawn with radium paint on a board of approx size of 1200x900 mm with fixing arrangement on wall of 220kV GIS Hall.

Set 1

3 Key board with hook for different keys of each equipments/panels/cubicles with SLD drawn with color approx size 2'x2'

Set 1

6 Supply of Furniture, RO Water Filter System, Water Cooler Etc. as per 'Annexure-C' as below

1 Furniture for 220/66KV S/S NO 15 a) Cushioned chair of Godrej make no. Ch-1018D NO 2

b) Steel rack of size 30"X36"X15" with three partitions, prepared 20 gauges NO 1

c) Providing Control Room Table modular 5X5 Panta work surface with pedestal CPU Trolley & Key Board tray of Godrej or equivalent

NO4

d) Office table with SDU & pedestal 5026 Godrej make NO 2

Page 12 of 25

Page 13: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

e) Modular workstations of Godrej make or equivalent 4X2 Panta work surface with pedestal CPU trolley & keyboard Tray or equivalent

NO40

f) Revolving chair PCH -5D02-STAR R-MID BACK NO 2g) Wooden sofa set- 3 seated as per drawing. NO 2g) Wooden sofa set- 2 seated as per drawing. NO 1 h) Conference table of 'Godrej' make of "Encarta conference table' of approved design and make. FOR 25 SEAT.

Sq.meter40

i) providing and fixing laminated table as per design with laminated post formed top, drawers/shutters with facility of lock, key , board tray, wire manger, t.w. foot rest. The same shall be made with 12mm thick ply wood. All exposed edges shall

Sq.meter10

j) T.W. partition 75mm thick with vinyl polished , soft board , electrical rack way etc complete as per drawing.

Sq.meter1.75

k)Providing and fixing laminated reception table with premium black granite top as per detail drg. All edges shall be mirror polished.( 5 feet x 3.5 feet)

no2

m) Providing t.w corner/central tepoy as per design with laminated top with 9mm thick bronze glass etc with malemine polish etc complete.(size 2.5 feet x 2.5 feet)

No.1

2 RO water filter system 25Ltr. Capacity Reputed make No. 13 Water Cooler Providing & installing SHRIRAM USHA or equivalent make water

cooler of 40Ltr./hr. capacity suitable to operate on 230V+10% , 50Hz. Single phase AC supply with hermetically sealed type suction cooled compressor with

No.1

4 42" , Sony or equivalent make flat LCD TV as per the specification 7 Supply and Erection of Fire stand with 4 buckets including concreting as per our

drawing & Instruction of E. I. C. Set 1

8 Providing of Insulating Mat (Size2000x1000x2mm) as per Technical Specification No. 100

L Supply and installation of materials for Illumination system in all respect as per respective specifications and special conditions (Important Note: Concealed wiring shall be considered for Indoor Illumination)

Indoor Illumination1 Providing & Fixing of Energy Efficient LED type (Techhnical spec Cl No. 2.10.4.8-I

LED 3 type) Indoor decorative luminaries as per design calculation, with respect to required lux level & relevant tender drgs.as per technical spec. Scope also includes providing and fixing of 15/5 A plug, Portable Emergency Light, Bell, Fan, Ex- Fan, DC Point,Occupancy & Light Level Sensor with requisite MCBs and DC 100W lamp , DC Plug etc all items as per Ann-4 in following rooms

i SCADA Control Room Package LSii Lab Package LSiii Reception Package LSiv Conference Room Package LSv Admin Offices Package LSvi LCC Rooms Package LSvii Security Officer Cabin Package LS

Page 13 of 25

Page 14: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

2 Providing & Fixing of Energy Efficient LED Type (Techhnical spec Cl No. 2.10.4.8-I LED 1 or I LED 2 type) Indoor decorative luminaries as per design calculation, with respect to required lux level & relevant tender drgs.as per technical spec. Scope also includes providing and fixing of 15/5 A plug, Portable Emergency Light, Bell, Fan, Ex- Fan, DC Point, Occupancy & Light Level Sensor with requisite MCBs and DC 100W lamp , DC Plug etc all items as per Ann-4 in following rooms

i LV Room Package LSii Store Room Package LSiii Ramp Slope Package LSiv Pantry Package LSv Passage (Corridor) Package LSvi Ramp Slopes Package LSvii Veranda Package LSviii WCs Package LSix Toilets Package LSx AHU Rooms Package LSxi Security Cabin Package LSxii Battery Room Package LS3 Providing & Fixing of Energy Efficient LED type (Techhnical spec Cl No. 2.10.4.8-I

LED4 Type) Indoor decorative luminaries as per design calculation, with respect to required lux level & relevant tender drgs., and required industrial grade point wiring as per technical spec. Scope also includes providing and fixing of 15/5 A plug, Portable Emergency Light, Bell, Fan, Ex- Fan, DC Point,Occupancy & Light Level Sensor with requisite MCBs and DC 100W lamp , DC Plug etc all items as per Ann-4 in following room.

i GIS Room Package LS4 Providing & Fixing of Energy Efficient LED Type (Techhnical spec Cl No. 2.10.4.8-I

LED 1 or I LED 2 type) Indoor decorative luminaries as per design calculation, with respect to required lux level & relevant tender drgs.as per technical spec. Scope also includes providing and fixing of 15/5 A plug, Portable Emergency Light, Bell, Fan, Ex- Fan, DC Point, Occupancy & Light Level Sensor with requisite MCBs and DC 100W lamp , DC Plug etc all items as per Ann-4 in following room.

i Store building Package LS

Page 14 of 25

Page 15: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

Outdoor Illumination5 Providing and fixing of flood light luminaries as per design for whole switch yard

area (i.e 220 & 66kV) with Energy Efficient LED type (Techhnical spec Cl No. 2.10.4.8-I LED 5 Type) Outdoor luminaries as per design calculation, with respect to required lux level & relevant tender drgs., and required industrial grade point wiring as per technical spec.& ancillaries and suitable for mounting on structure at appropriate height as per specifications TS illuminations cl. no 2.10.4.8 with necessary GI fabrication & GI bolt nuts to fix control gear box at the structure with complete internal and external wiring to J. box ,Dist panel/section feeder pillar etc with supply of required 3 c x 2.5 mm2 copper armoured cable (as per spec ) .The scope includes supply and erection of all the materials required for satisfactory functioning of above work.

Package LS

6 Providing and installation of Energy efficient LED type post top lantern for main gate and road from main gate to switchyard via control room as per design with Philips/CGL/Bajaj/GE/Oshram make & ancillaries suitable for mounting on Gate pillars and 4.5 mtr poles with necessary GI fabrication & GI bolt nuts to fix control gear box with complete internal and external wiring to J.box,Dist panel/section feeder pillar, fixing terminal etc. with supply of required 3 c x 2.5 mm2 copper armoured cable as per spec .This also includes the supply and erection of required 4.5 mtr poles and its foundation work as per spec and earthing with main mesh. The scope includes supply and erection of all the materials required for satisfactory functioning of above work.

Package LS

7 Providing and fixing of street light luminaries for reamaining area (like road, near whole compound wall/fencing area etc.) of switch yard complete as per design with Philips/CGL/Bajaj/GE/Oshram or Similar make LED lamp & ancillaries suitable for mounting on 7.0 mtr swaged poles as per spec.TS illuminations cl. no 2.10.4.8 (S-LED) at appropriate height with necessary GI fabrication & GI bolt nuts to fix control gear box with complete internal and external wiring to J. box ,dist panel/section feeder pillar, fixing terminal etc with supply of required 3 c x 2.5 mm2 copper armoured cable (as per spec). This also includes the supply and erection of 7.0 mtr swaged pole and foundation work as per spec. as well as earthing with main mesh. The scope includes supply and erection of all the materials required for satisfactory functioning of above work.

Package LS

8 Providing & Fixing of Energy Efficient Indoor 2x36 Tube light for Quaters (4 Nos.) in all the rooms, passages complete (ref. Ann-4 Item (F)) as per technical spec with required casing caping point wiring as per technical spec. Scope also includes providing and fixing of 15/5 A plug, Portable Emergency Light, Bell, Fan, Ex- Fan,with requisite MCBs and as per Ann-4 Item (F) in following amenities

1 Drawing room of Type IV Qtr Package LS2 Bedroom 1of Type IV Qtr Package LS3 Bedroom 2 of Type IV Qtr Package LS

Page 15 of 25

Page 16: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

9 Providing & Fixing of Energy Efficient Indoor luminaries in all the rooms, passages Qtr (4 Nos.) complete (ref. Ann-4 Item (F)) as per technical spec Cl No. 2.10.4.8 (CFL type) with required casing caping point wiring as per technical spec. Scope also includes providing and fixing of 15/5 A plug, as per Ann-4 Item (F) in following rooms--- With supply and fixing of 3 KW Geyser (Instant type Sphere hot make ) Arrangement in bathroom or attached toilet blocks

1 Passage for Type IV Qtr Package LS2 Toilet common for Type IV Qtr Package LS3 Toilet attached to Room No1 for Type IV Qtr Package LS4 Kitchen for Type IV Qtr Package LS5 Store for Type IV Qtr Package LS10 Supply and Erection of main lighting Panel ACP-1 as per Specifications. Set

comprises minimum 4 nos.of such panels qty may be more if required as per design. Scope also includes the providing and erection of cable (size as per design requirement) and 25x6 GI strip for earthing with main mesh

Set 1

11 Supply and Erection of main lighting Panel ACP-2 as per Specifications Set comprises minimum 4 nos.of such panels qty may be more if required as per design. Scope also includes the providing and erection of cable (size as per design requirement) and 25x6 GI strip for earthing with main mesh

Set 1

12 Supply and Erection of main lighting Panel ACP-3 as per Specifications Set comprises minimum 4 nos.of such panels qty may be more if required as per design. Scope also includes the providing and erection of cable (size as per design requirement) and 25x6 GI strip for earthing with main mesh

Set 1

13 Supply and Erection of main lighting Panel ACP-4 as per Specifications Set comprises minimum 4 nos.of such panels qty may be more if required as per design.Scope also includes the providing and erection of cable (size as per design requirement) and 25x6 GI strip for earthing with main mesh

Set 1

14 Supply and Erection of main Yard light Dist. Board as per designed capacity ratings.Scope also includes providing and erection of cable (size as per design requirement) and 50x6 GI strip for earthing with main mesh

Nos 2

15 Supply and Erection of Lighting Transformers as per designed capacity.Scope also includes the providing and erection of 50x6 GI strip for earthing with main mesh. Please refer the drawing "General Schematic for Illumination" in the TS Illumination.

Set 1

16 Providing of concreting in 1:2:4 mix including muffing for erection of pole & Dist boxes panels including excavation of HR/SR as per approved drawing. Package LS

17 Providing & fixing of ' B ' Class ISI marked GI pipe of 25 mm inner diameter for cable looping, road crossing with necessary elbow / band to J. Box etc. Package LS

Page 16 of 25

Page 17: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

18 Providing and fixing of GI clamp (25mm wide GI strip with 6 mm GI nut bolts) on structure at approx. 1 or 2 Mtr. Interval for clamping of cable. Clamp should be fix in such a way that cable can be easily mount inside it & sustain standing on structure. This also includes required other materials,accessories etc.required for complete functioning of Illumination system of whole project. Please refer the drawing "General Schematic for Illumination" in the TS Illumination.

Package LS

M

1 Supply and Installation of earthing strips/round bars for earthmat (including digging of 600 mm depth) and riser connections as shown below as per standard equipment earthing philosophy. It includes fixing arrangement with two bolt arrangement and jointing,welding etc.complete.

a) 75 x 10 mm GI strip. RMt. 8100b) 50 x 6 mm GI strip. RMt. 2700c) 40 mm dia steel rod RMt. 13000d) 40mm dia 3mtr long steel rod Nos. 160e) 75X10 mm CU Flat RMt. 140

2 Providing and installing Check pit as per drawing and instruction of Engineer In charge with provision of earth chamber. Nos. 6

3 Supply, Installation, Testing and Commissioning of maintenance free treated earth electrodes, as per attached drawing no. GETCO/E/P-021 (2 OF 2) R2 dated 04-06-15 and Technical specifications GETCO/E/TS-Maintenance free earth pits /R1 dated 04-06-15.

Nos. 114

4 Providing BB masonry inspection chamber (man hole) incl.light type CI cover as per GETCO drawing no P021

Nos. 114

5 Design of earthgrid for whole switchyard using computer computer algorithmsfor modeling grounding systems as per Cl. 16.8 of IEEE-80.

Package LS

6 Earthing Adequacy study for whole switchyard after commisioning earthmat in all respect(Scope as per annexure-E)

Package LS

N Supply and Erection of Ladder Type Cable Trays and Accessories as per respective Technical Specifications and relevant special conditions. 

Width of tray450mm Rmtr. 80

Note: Extra earth should be removed away from the site s/s premises or refilling earthing pits if required. All required materials for this job such as Copper Bonded Earthing Steel Rods, CI cover with frame,cement,sand, Ground Enhancement Material, gravel, bricks etc. to be supplied by the contractor.

Note: The quantities of the ACP's mentioned in the schedule of requirement are based on std. requirement, which shall be finalized during detail engineering. The bidder has to assess the qty. of ACP's at the time of quoting the bid. The qty of ACP's finalized during detail engineering is binding to the bidder & no any extra payment shall be made. In all the case the decision of GETCO will be final.

Supply and installation of materials for Earthing system in all respect as per respective specifications and special conditions (Successful bidder has to submit the complete design and BOQ for approval)

Page 17 of 25

Page 18: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

350mm Rmtr. 80

O On-Line Transformer Intelligent condition monitoring system (OTICM) as per Technical Specification

Lump sum LS

1

2

3

4

5

6

7

8

9

10

11

12

13

14

All the equipment structures, Gantry structures and LM structures shall have GI coating considering marine atmosphere as per specifications.

Lightning Masts shall be provided for GIS Buildings, Switchyard area ,Control room area etc. as per DSLP Calculation.

66 KV Power cable Termination at GIS end along with cable termination kit supply shall be in the scope of bidder. However, at other end same shall be in the GETCO Scope.

66 KV Power cable Supply & Laying shall be in the GETCO scope.

All outdoor equipments LA,CVT, BPI, SF6 bushings etc shall be polymer housed and have creepage distance of 31 mm/KV.

Length: Standard length of tray is 2500mm, Height is 75mm, Thickness is 2mm (min.)

5 MVA 66/11.55 KV Station Transformer and 11/0.433 kv Distribution Transformers shall be painted with anti-corrosive PU based paint having minimum 50 micron coating considering saline atmosphere.

1) 66KV cable details (size, no. of runs, conductor type, etc.) for Line & Transformer bays :a) 3 runs X 630 sq.mm -66 KV power cable per phase for Transformer (Total 9 + 1 spare) . b) 1 run X 630 sq.mm -66 KV power cable per phase for Line and 66/11kv station transformer. (Total 3 + 1 spare).

External surface of GIS enclosure shall be painted with anti-corrosive PU based paint having minimum 50 micron coating.

Submission of study report of Very Fast Transient Over Voltage (VFTO) shall be in the scope of bidder.

5 MVA 66/11 KV transformers shall be supplied with 31 mm/KV creepage with polymer bushings on 66 KV side.

Successful bidder has to depute his expert to site annually for the period of five years from the date of commissioning to inspect GIS for carrying out status evaluatrion of GIS performance.This is intended to share the operational challenges and confirming the maintenances followed by GETCO.

Mounting channels to be grouted in flooring for GIS support shall be designed and verified by GIS OEM only. No local fabrication is allowed for such fixing arrangement.

Note: Cross, Tees, Elbows, Coupler plates, Bends, Reducer etc. required for complete installation of Ladder Type Tray are included in the Scope.

Supply & Erection of 160 MVA, 220/66kv Transformers are not in the scope of bidder, but bidder will erect the items other than the scope of transformer manufacturer and witness during the erection and testing of the same and provide all the result in as built drawings/documents.

SPECIAL NOTES:

LCC of 220kV and 66kV GIS shall be front openable. LCC shall be installed in such a way that facing of front side of LCC and GIS module is same. Opposite to LCC panel, C&R panels shall be arranged exactly in line with GIS module. Sufficient maintenance space shall be kept between LCC & C&R panel.

Page 18 of 25

Page 19: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

Sr No

DescriptionUnit of

MeasurementQuantity

1 220kV ,4400PF CVT (having two windings with VA burden 50 & 50 and accuracy of 0.2 & 3P class for metering & Protection core respectively.The arrangement of metering core shall be provided in seperate sealable compartment with locking facility. Clamp/connectors & supporting structure shall also be supplied.. The interconnection from HF terminal of CVT to PLCC coupling device shall be made using 16 Sq.mm PVC insulated stranded (non flexible strands) copper cable.

No. 10

2 220kV, 0.5mH, 1250Amp Wave Trap with Blocking Band of, Band-(I)-100-160 & Band-(II) 150-500KHz and R min = 570 Ohm with pedestal mounting arrangement having mounting pedestal , composite solid core post insulator, support structure and also alongwith clamp/connectors and require accessories.

No. 8

3 Modular coupling device for Phase to Phase coupling arrangement ( A9BS-1 No. & A9BT-1 No.) for PLCC signal connectivity of Make: ABB, Type: MCD-80 Set 2

4 Carrier Terminal Equipment with Dual 19” rack of 40Watt Single Channel, Fully Programmable Carrier Equipment Type ETL-41 of ABB Make suitable to operate on 220V DC (i.e depending on S/s battery voltage) and with 4-Wire table telephone for ETL, Dummy Load Print P3LK, 75 Ohm Cylindrical Load and 4 Nos. of UHF Gland , Emergency jack handset as per technical Specification.

No. 2

5 Protection coupler Make: ABB, Type: NSD-50 with 2 coded & 2 uncoded command arrangement & perfectly match with above carrier terminal description of which given at Sr. No. 4

No. 4

6 FSK Data Modem with stand alone 19" rack with power supply module ,Make: ABB & Type: NSK 5, Programmable for both Baud Rate (50 to 2400 Baud) and VFT Channel Centre Frequency operating on input DC supply 220V DC and fully compatible with Carrier terminal description of which given at Sr. No. 4 above.

No. 1

7 FSK Data Modem Make: ABB & Type: NSK 5, Programmable for both Baud Rate (50 to 2400 Baud) and VFT Channel Centre Frequency and fully compatible with Carrier terminal description of which given at Sr. No. 4 above. No. 1

8 75 Ohm, unbalanced armoured co-axial cable for PLCC signal connectivity (frequency band 50 KHz to 500 KHz) having armour of Min.1.4 mm dia. GI wire and coverage of 70% to be laid by providing UHF gland on both the ends of main cable length from PLCC carrier room to bay gentry and loop cable for Ph to Ph coupling arrangement.

KM 0.36

(II) PLCC PART

Page 19 of 25

Page 20: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

9 PLCC Exchange of Make: MATRIX, Type Eternity 10S suitable for both PLCC Dialling and Express Communication connectivity with Universal slot architecture and Hot stand by Power supply suitable to operate on 220V DC (i.e depending on S/s battery voltage) , switch and CPU card having configuration for 16 Nos. of Trunks & 16 Nos. of Subscribers along with Digital Key phones- 2 Nos. & 2 Wire telephone instruments of reputed make.

No. 1

10 DAS PC with printer as per technical specification No. 1

11 DAS Meters network wiring complete up to RS 485 to RS 232 Convertor of DAS PC using (Complete Job)a) 3 core communication cable (as per specification given hereunder) Mtr. 100b) RS 485 to RS 232 Converter (as per specification given hereunder) No. 1

Sr No Description

Unit of Measurement

Quantity

A Supply, Erection, Testing and Commissioning of Protection equipments and materials as per respective technical specifications and relevant special conditions and suitable for Two Main Bus system on 400kV side

1 GPS based Time Syncronising Unit (IEC 61850 compatible) Set 1B Supply, Erection, Testing and Commissioning of Protection equipments and

materials as per respective technical specifications and relevant special conditions and suitable for Two Main Bus system on 220kV side

1 Control & Protection panels for 220KV Bays ( Control Voltage - 220V DC ) as per tech specifications & suitable for GIS switchgear modules with following break up

1) Control & Protection panel for Line Set 102) Control & Protection panel for Transformer without Differential (For 400/220kV ICT LV)

Set 3

3) Control & Protection panel for Transformer with Differential (220/66kV) Set 34) Control & Protection panel for BC Set 15) Busbar Protection - (Central Unit - 28 bays, Peripheral Units - 17 Bays) [CU shall be mounted in one of the bay control & protection panel while PUs shall be mounted in respective bay control and protection panels as shown in panel GA drawing]

Set 1

B Supply, Erection, Testing and Commissioning of Protection equipments and materials as per respective technical specifications and relevant special conditions and suitable for Two Main Bus system on 66kV side

1 Control & Protection panels for 66KV Bays ( Control Voltage - 220V DC ) as per tech specifications & suitable for GIS switchgear modules with following break up

1) Control & Protection Panel for Line Set 102) Control & Protection Panel for Buscoupler Set 13) Control & Protection Panel for Transformer W/O Differential Relay ( for 220/66KV TRF)

Set 3

(II) PROTECTION PART

Page 20 of 25

Page 21: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

4) Control & Protection Panel for Transformer with Differential Relay ( for 66/11KV TRF)

Set 1

5) Under Frequency Panel Set 1B1 Supply, Erection, Testing and Commissioning of Protection equipments and

materials as per respective technical specifications and relevant special conditions and suitable for Single Bus system on 11kV side

2 SCADA comaptible Control & Protection panels for 11KV Bays with Bay Control & Protection Relay ( Control Voltage - 220V DC ) as per tech specifications & suitable for conventional switchgear modules with following break up

1) Control & Protection Panel for 66/11KV TRF LV Set 1C Supply, Erection, Testing & Commissioning of General purpose equipments and

materials as per respective technical specifications and relevant special conditions and suitable for Two Main Bus system on 400kV, 220kV and 66kV side

1 Battery set - 220 V, 450Ah at ECV -1.14, C5 Duly cycle {1.2 V, 180 cells, (174 For Battery set and 6 Spare) } Ni-CAD Battery Set (Equivalent to 480Ah as per C5 duty cycle at ECV - 1.0) with Two Step Two Tier FRP stand of adequate size (Rating is tentative for estimation purpose please refer Remarks)

No. 2#

2 Battery Charger - 220 V (Float - 100A / Boost - 100A) - (SCADA compatible)Suitable to Ni-CAD Battery set and shall be able to charge Battery set as per requirement during float / boost mode as well as it shall supply to load as per rated voltage of load components. (Rating is tentative for estimation purpose please refer Remarks)

No. 2#

3 DCDB-220 V with 35 Feeder No. 24 DCDB-220 V with 20 Feeder No. 25 DCDB-220 V with 20 Feeder (For PLCC Panels) No. 26 SCADA compatible LTPB compatible for 400KV Substation and suitable for GIS

switchgear module and related accessories as per specifications but not less than the requirement of specification

No. 1

D Supply, Installation, Testing and Commissioning of materials/item for Power Cable and Control Cable including preparation of wiring schedule on the basis of GIS and LCC requirement and referring to typical philosophy. However, final Cable philosophy shall be derived during detailed engineering and got approved.(Please refer Remarks)

Page 21 of 25

Page 22: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

1 Supply and Laying of 1.1 kV FRLSH PVC armoured copper/Aluminum control/LT power cable in trench including binding/clamping of cable with PVC locable wire tie as per requirement including supply and fixing of identification tags at both ends and at distance of every 100mtr.(Note :- Aluminium cables of size 185 mm2 & above shall be XLPE type)

1) 2c x 2.5 mm2, armoured copper control cable Mtr. LS$2) 2c x 4 mm2 , armoured copper control cable Mtr. LS$3) 4cx2.5 mm2, armoured copper control cable Mtr. LS$4) 4c x 4 mm2 , armoured copper control cable Mtr. LS$5) 7c x 2.5 mm2, armoured copper control cable Mtr. LS$6) 12c x 2.5 mm2, armoured copper control cable Mtr. LS$7) 12c x 4 mm2, armoured copper control cable Mtr. LS$8) 19c x 2.5 mm2 , armoured copper control cable Mtr. LS$9) 27c x 2.5 mm2, armoured copper control cable Mtr. LS$10A) 1 x 50 mm2 , armoured copper cable Mtr. LS$10B) 4C x 10 mm2 , armoured copper control cable Mtr. LS$11) 4 x 10 mm2 , armoured Al. LT power cable Mtr. LS$12) 3.5 x 25 mm2 , armoured Al. LT power cable Mtr. LS$13) 3.5 x 50 mm2 , armoured Al. LT power cable Mtr. LS$14) 3.5 x 120 mm2 , armoured Al. LT power cable Mtr. LS$15) 1C x 150 mm2 ,armoured Al. LT power cable Mtr. LS$16) 1C x 240 mm2 , armoured Al. LT power cable Mtr. LS$17) 1C x 300 mm2 , armoured Al. LT power cable Mtr. LS$18) 3.5 x 300 mm2 , armoured Al. LT power cable Mtr. LS$

2 Termination of the Control and Power cable at panel / MK box/equipment including PVC binding, dressing, shaping, drilling of holes in panels for glands nuts, providing of glands for following size. The work also includes looping in Panel and MK box by using crimping type lugs of suitable size with ferruling (machine printed) with proper size of copper cable wire. The loops should be bunched by using button tape and proper shaping etc.

1) cables from 2 core to 7 core of 2.5 & 4.0 Sq.mm size No. LS$2) cables above 7 core No. LS$

3 Laying of 1.1kv FRLSH PVC/XLPE armored Al. LT power cable in ground by digging trench of suitable width and 450 mm depth with providing and fixing of brick and sand layer covering the cable in any type of soil and Laying of 1.1kv PVC armored copper control cable in heavy duty PVC pipe of suitable size from plinth level of respective equipments to burried in ground by digging trench of suitable width and 450 mm depth in any type of soil including supply and fixing of Pipe and identification tags at distance of every 100 Mtrs for following size

1) Control Cables upto 7 core Mtr. LS$2) Control Cables above 7 core and all LT cables Mtr. LS$

Page 22 of 25

Page 23: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

3a Supply, Erection, Testing and Commissioning of Modular Multi-diameter Cable sealing system as per respective technical specification and relevant special conditions wherever the electrical / instrumentation / communication / LT Power cable underground and over-ground enter or leave bay kiosks / control room of substations / cable trench / basement.

LS 1

4 Providing and fixing of suitable BOX type GI perforated tray with necessary clamps and couplings for control cable of PT/CVT etc. equipments including fixing with structures up to plinth level as per instruction of Engineer-in-charge.

1) 220 kV Switch Yard Mtr. 100Note:

(III) SCADA PARTSr No

DescriptionUnit of

MeasurementQuantity

A Supply, Erection, Testing and Commissioning of SCADA equipments and materials as per respective technical specifications and relevant special conditions and suitable for Two Main Bus system on 220kV and 66kV side

1 Bay Control Unit / RTU for Substation Auxiliaries # Nos 1#2 HMI Server computer with required softwares Nos 23 DR workstation PC No. 14 Gateway for remote control with software No 15 Gateway for RTU Data with software No 16 SCADA software (For Local as well as Remort control centre) No 17 Ethernet Fiber Switches* Nos 168 Line Interface unit - 2 Cable entry, 12 ports Nos 169 Line Interface unit - 4 Cable entry, 16 ports Nos 110 Line Interface unit - 8 Cable entry, 32 ports Nos 111 Laser Jet colour Printer Nos 112 Laser Jet Printer Nos 113 3 KVA UPS with Battery having Auto changeover scheme for seamless

changeover (Battery - 12V SMF Battery set, Ah rating and Nos.shall be suitable for 2 hours back-up as per UPS DC Voltage rating)

Nos 2

& 1CX240 size cables for incoming AC supply are to be considered as per rating of LT Panel board.

# Battery and Charger sizings are tentative as they are derived on the basis of available data of

in BOQ). Battery and charger sizing shall be got approved during detailed engineering

philosophies are for reference only. However basic requirement like, 4 Sq.mm cable for CT-PT- CVT wiring

Other than GIS-LCC-Panel cables, typical philosophies may be referred.

trip coil, LCC, DC Drives, GIS Module etc. Bidder has to derive Battery and Charger sizing based on

- CVT wiring and 2.5 Sq.mm for Control wiring is to be followed as per philosophy. Also, 1CX300

Battery & Charger sizing shall be carried out considering future 400-220-66KV bay as per layout.$ Quantity and size of cables shall be derived by bidder based on GIS & LCC requirement. Typical

their GIS component rating & design and accordingly it shall be quoted (size not less than shown

before finalization. Accordingly dimensions of LV Room, Battery room etc. shall be finalized.

Page 23 of 25

Page 24: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

14 Armoured Fibre Optic Cable with HDPE duct (Mutli mode) MTR. 100015 Panel for mounting SCADA equipments Nos 116 Panel for mounting Station Auxiliaries BCU/RTU Nos 117 Furniture for SCADA equipments Set 118 Panel for Mounting Spares Nos 1

Spares for SCADA and Protection 1 Bay Control Unit Nos 12 Line Interface unit - 8 Cable entry, 32 ports Nos 13 Ethernet fiber switch Nos 14 Busbar Protection Peripheral Unit Nos 15 Busbar Protection Central Unit (For 28 bays) Nos 1

Note:

Sr No Description

Unit of Measurement

Quantity

A Supply, Erection, Testing and Commissioning of SCADA equipments and materials as per respective technical specifications and relevant special conditions.

1 HMI Server computer with required softwares Nos 22 DR workstation PC Nos 13 Ethernet Fiber Switch* Nos 24 Laser Jet colour Printer Nos 15 Laser Jet Printer Nos 16 3 KVA UPS with Battery having Auto changeover scheme for seamless

changeover (Battery - 12V SMF Battery set, Ah rating and Nos.shall be suitable for 2 hours back-up as per UPS DC Voltage rating)

Nos 2

7 Panel for mounting SCADA equipments Nos 18 Furniture for SCADA equipments Set 1

3) # BCU for station Auxiliary shall have sufficient I/Os as per list or otherwise suitable RTU shall be provided.

(V) SCADA BOQ for Remote Control Centre - 220KV NYARA Substation

4) Contractor shall be responsible for necessary co-ordination with FOTE and OPGW supplier & erection agency to establish remote connectivity and over all operation from Master Control Centre through SCADA system.

1) Any material/equipment accessories which are not listed in BOQ or scope of supply but required to complete the job shall be included and shown in technical bid.2)*Ethernet switches shall have as many spare ports as utilized ports.

Page 24 of 25

Page 25: Schedule - 2 - GUVNL · LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated ... (Total height :8mtr.)

Total EXW

Price1

EXW Unit

price1 Excise DutyTaxes and

Duties

220KV GIS KALAWAD SUBSTATION

Schedule No. 2 - Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country

Unit of Measurement

QuantitySr No Sales and other TaxesDescription

Note:

Grand Summary

Name of Bidder

Signature of Bidder

1 Specify currencies in accordance with ITB 19.

NOTE:

1) Any material/equipment accessories which are not listed in BOQ or scope of supply but required to complete the job shall be included and shown in technical bid.2)*Ethernet switches shall have as many spare ports as utilized ports.

(2) The bidder shall specify the applicable local taxes description and rates.

(3) Bidder shall quote for all the items as per BoQ

(1) the taxes & duties for bought out items shall be included in EXW price for Indian Bidder and in CIF price for Foreign Bidder for which bidder shall provide break up of taxes & duties considered in the Unit ExW price ot Unit CIF price of such bought out items to know the taxes & duties component to avail deemed export benefit, if applicable during contract period due to change in GoI import export policy

TOTAL of Column 10 to be carried forward to Schedule No. 5.

3) Contractor shall be responsible for necessary co-ordination with FOTE and OPGW supplier & erection agency to establish remote connectivity and over all operation from Master Control Centre through SCADA system.

Page 25 of 25