Upload
olivia-higgins
View
244
Download
2
Tags:
Embed Size (px)
Citation preview
SCCR Codes and Standards
Including:
Basic Principles
NEC® 409 and UL 508A
How to Determine the SCCR of an Industrial Enclosure
2
Agenda
Introduction and Basics
National Electric Code 2005
Underwriters Laboratories
Determining SCCR
How to Increase SCCR
Mersen Tools
3
Short Circuit Current– An overcurrent usually defined as being in excess of ten times normal
continuous rating usually caused by insulation breakdown or wiring error
Short Circuit Current Rating (SCCR)– The prospective symmetrical fault current at a nominal voltage to
which an apparatus or system is able to be connected without sustaining damage exceeding the defined acceptance criteria
Available Fault Current– The maximum short circuit current that could flow in an unprotected
circuit
Definitions
4
SCCR is now an important factor when considering UL 508A and the NEC. SCCR is important to you because:
– By knowing about SCCR and available fault currents you will create safer working conditions for the personnel who work on or around electrical equipment
– You will be able to ensure compliance with the NEC and UL
– You can simplify your inspection approval process
Why is SCCR important?QA
&
5
Everybody
Industrial Facilities
Manufacturing Facilities
Contractors
Panel Builders
System Integrators
OEMs
Etc…
Who will be affected?QA
&
6
NEC® Article 409 – Industrial Control Panels– Introduced in the 2005 NEC, “Industrial Control Panels”
require panels to be clearly marked with a short circuit current rating, SCCR
UL 508A – Industrial Control Panels– Listed panels will require the SCCR to be clearly
marked on the panel effective April 25, 2006
The changes are already in placeWhen will the changes be enforced?Q
A&
7
National Electric Code – 2011
The National Electric Code is a standard for the safe installation of electrical wiring and equipment
Part of the NFPA (National Fire Protection Association)
Not a U.S. Law but is mandated by local or state officials
Articles Related to SCCR– Article 230
– Article 409
– Article 670
8
NEC Article 230 - Services
230.1 - Scope– This article covers service conductors and equipment for control
and protection of services and their installation requirements
230.82– Equipment Connected to the Supply Side of Service Disconnect– Only the following equipment shall be permitted to be connected to
the supply side of the service disconnecting means:• (3) – Meter disconnect switches nominally rated not in excess of 600
volts that have a short circuit current rating equal to or greater than the available short circuit current,…
9
NEC Article 409 – Industrial Control Panels
409.1 – Scope– This article covers industrial control panels intended for general use
and operating at 600 volts or less
409.110 – Marking– An industrial control panel shall be marked with the following
information that is plainly visible after installation: • (4) Short circuit current rating of the industrial control panel based on
one of the following:– a. Short circuit current rating of a listed and labeled assembly
– b. Short circuit current rating established utilizing an approved method
10
NEC Article 430 – Motors, Motor Circuits, and Controllers
430.1 – Scope– This article covers motors, motor branch circuit and feeder
conductors and their protection, motor overload protection, motor control circuits, motor controllers, and motor control centers
430.7(D) – Multimotor and Combination Load Equipment
430.8 – Markings– A controller shall be marked with the manufacturer’s name or
identification, the voltage, the current or horsepower rating, the short circuit current rating, and other necessary data to properly indicate the applications for which it is suitable
11
NEC Article 670 – Industrial Machinery
670.1 – Scope– This article covers the definition of, the nameplate data for, and the
size and overcurrent protection of supply conductors to industrial machinery
670.3 – Machine Nameplate Data– (A) Permanent Nameplate. A permanent nameplate shall be
attached to the control equipment enclosure or machine and shall be plainly visible after installation. The nameplate shall include the following information: (1)…(5)
• (4) Short circuit current rating of the machine industrial control panel based on one of the following:
– a. Short circuit current rating of a listed and labeled machine control enclosure or assembly
– b. Short circuit current rating established utilizing and approved method
12
Underwriters Laboratories
Independent Testing Company
Offer 3rd Party Certification
Consistent with NEC
Relative Articles– UL 98 Disconnect Switch
– UL 248 Low Voltage Fuses
– UL 508 Industrial Control Equipment
– UL 512 Fuse Blocks
– UL 1059 Terminal Blocks (PDB)
– UL 1449 Surge Protective Devices
13
UL 508A – Industrial Control Panels
Guideline for construction and general design
Manufacturers that adhere to the requirements are eligible for UL508A Listing of their product
Four Parts of UL 508A– Part 1: General Use
– Part 2: Specific Use• Enclosures, Elevator Control, Industrial Machinery, Flame Control,
Crane Control, Marine Use, Service Equipment Use, AC and Refrigeration
– Part 3: Specific Component Requirements
– Part 4: Short Circuit Current Ratings
14
UL 508A – Industrial Control Panels
Industrial control panel assemblies:– May include motor controllers, overload relays, fused disconnects,
circuit breakers, pushbuttons, switches, timers, indicators, wiring, terminals, enclosures, etc…
– Will be rated 600V or less
– Where ambient temperatures do not exceed 40°C
UL 508A does not include panels for Hazardous Locations “NRBX”, which are covered under UL 698A
15
Four Step Process
How do you determine the SCCR of an industrial control panel?Q
A&
16
It’s as easy as 1…2…3
Step 1: Assign a SCCR to each component in the power circuit
Step 2: Assign a SCCR to each branch circuit
Step 3: Assign a SCCR to the feeder circuit
Step 4: Consider the current-limiting effects of the feeder over-current protection devices (OCPD)
Before we apply the standard:Power Electrical Symbols
Power Circuit vs. Control CircuitBranch Circuit vs. Feeder Circuit
17
Power Electrical Symbols
Fuse
PushbuttonElectric MotorMotor StarterCircuit Breaker
RelayPower Transformer
Fused Disconnect Switch
NC
NO
NO NC
18
Control Circuit vs. Power Circuit
Power Circuit Power Circuit
Control Circuit
Control Circuit
19
Branch Circuit vs. Feeder Circuit
Branch Circuit #1 Branch Circuit #2
Feeder Circuit
20
Applying the Standard
Let’s analyze an example circuit
21
Example Circuit
22
Step 1: Assign a SCCR to each component in the power circuit
SCCR of a component shall be established by one of the following:
1. SCCR marked on the component or on instructions provided with the component
2. SCCR can be determined by the voltage rating of the component and the assumed short circuit current from Table SB4.1
3. SCCR for a load controller, motor overload relay, or combination motor controller can be determined by type testing under the procedure specified by UL508 and as described in the manufacturers procedure
23
QA
&All Power Circuit ComponentsWhat Components Do I Look For?
Including disconnect switches, branch circuit protective devices, branch circuit fuse holders, load controllers, motor overload relays, terminal blocks, and bus bars, shall have a short circuit current rating expressed in amperes or kilo amperes and volts
Exception No. 1: Power transformers, reactors, current transformers, dry-type capacitors, resistors, varistors, and voltmeters are not required to have a short circuit current rating
24
QA
&
In today’s industry short circuit current ratings are usually listed in kilo-amperes, or kA
On the product label or in the product manual
Where do I find the SCCR of my components?
25
If the component SCCR is not listed on the product label or in the product manual use Table SB4.1
26
Mersen Resources for Determining SCCR
27
Control Circuit
10kA
200kA
5kA
200kA
200kA
65kA
Unknown
100kA
200kA
NA
200kA
28
12A (5HP = 3.7kW) Motor Starter does not have a labeled SCCR and is also not listed in product manual
29
SB4.1 5kA
Control Circuit
10kA
200kA
5kA
200kA
200kA
65kA
100kA
200kA
NA
200kA
30
Step 2: Assign a SCCR to each Branch Circuit
Make a pass of each branch circuit– The lowest component SCCR value will be equal to the branch
SCCR
In this case we have three branch circuits to analyze
31
Branch 1 Branch 2 Branch 3
SB4.1 5kA
Control Circuit
10kA
200kA
5kA
200kA
200kA
65kA
100kA
200kA
NA
200kA
32
Branch 1 First Pass SCCR =
10kA
200kA
Branch 1
10kA
33
Branch 2 First Pass SCCR = 5kA
5kA
200kA
NA
Control Circuit
Branch 2
200kA
34
Branch 3 First Pass SCCR = 5kA
Branch 3
SB4.1
5kA
65kA
35
Step 3: Assign a SCCR to the Feeder Circuit
Make a pass of the feeder circuit and determine the lowest SCCR value
36
Feeder Circuit SCCR = 100kA
Feeder
100kA
200kA
200kA
37
Step 4 is pivotal when attempting to increase panel SCCRUL 508A, SB4.3 – Feeder Components that limit the short circuit current available– Power Transformer– Circuit Breaker– Fuse
Compare the Ip of the feeder OCPD to the SCCR of the feeder and each branch circuit– If the Ip of the feeder OCPD is not greater than the SCCR of the
feeder or branch then the feeder or branch will have an SCCR equal to the appropriate Ip column on SB4.2
The panel SCCR would be equal to that of the component with the lowest SCCR; in this case 5kA (Electronic Motor Controller & 12A Motor Starter)
What if we stopped now?
QA
&
38
Step 4: Consider the current-limiting effects of the feeder over-current protection devices
Power Transformer– Use SB4.3.1
Circuit Breaker– The panel builder must select the current limiting breaker based on
the published peak let-thru curve data provided by the breaker manufacturer. Listed breakers rated 15A or 20A, 600V or less, also labeled “current limiting” are able to limit the current to 5kA and 10kA respectively.
Fuse– Refer to UL 508A Table SB4.2 to determine the Ip of the fuse
– Class CC, G, J, L, RK1, RK5 or T
39
Feeder OCPD
In this example the feeder overcurrent protection device is an AJT60– Class J
– 60A
– 600V
– Time Delay
Feeder
100kA
200kA
200kA
40
Class J 60A
– 50kA peak Ip = 8kA
– 100kA peak Ip = 10kA
– 200kA peak Ip = 16kA
41
Ip = 10kA @ 100kA
Branch 1 = 10kA
Branch 2 = 5kA
Branch 3 = 5kA
SB4.1 5kA
Control Circuit
10kA
200kA
5kA
200kA
200kA
65kA
100kA
200kA
NA
200kA
42
Branch 1 Second Pass SCCR =
10kA
200kA
Branch 1 = 10kA
Ip = 10kA @ 100kA
Branch 1 = 100kA
100kA
43
Branch 1 = 100kA
Branch 2 = 5kA
Branch 3 = 5kA
SB4.1 5kA
Control Circuit
10kA
200kA
5kA
200kA
200kA
65kA
100kA
200kA
NA
200kA
Ip = 10kA @ 100kA
44
Panel SCCR is still 5kA
Summary– Feeder SCCR = 100kA
– Branch 1 SCCR = 100kA (was 10kA)
– Branch 2 SCCR = 5kA
– Branch 3 SCCR = 5kA
Branches 2 and 3 are limiting our panel SCCR
Lets examine Branch 2 in more detail…
45
Branch 2
In this case the Power Transformer is a component that limits short circuit current available
Using UL508A SB4.3.1 we can determine the current limiting capabilities of the power transformer
Power Transformer Specs– 5KVA– 480V – Pri– 120V – Sec 5kA
200kA
NA
Control Circuit
Branch 2 = 5kA
200kA
46
The current limiting effects of a Power Transformer
UL508A SB4.3.1– For branch circuit supplied by a power transformer with an isolated
secondary winding, the short circuit current rating on the line side of the transformer shall be one of the following:
XFMR Rating Secondary Voltage Secondary Devices SCCR on line side of transformerless than or
= 10kVAless than or
= 5kVAgreater than
10kVAUse lowest SCCR of secondary current
components--
not specified greater than or = 5kA Use rating on primary overcurrent device
120V maximum greater than or = 2kA Use rating on primary overcurrent device
47
Branch 2 Second Pass SCCR =
According to SB4.3.1 our branch power transformer will limit the let-thru current to 2kA
Branch SCCR is equal to our primary overcurrent device
– ATQR25
200kA
5kA
200kA
NA
Control Circuit
Branch 2 = 5kA
200kA
Branch 2 = 200kA
48
Branch 1 = 100kA
Branch 2 = 200kA
Branch 3 = 5kA
SB4.1 5kA
Control Circuit
10kA
200kA
5kA
200kA
200kA
65kA
100kA
200kA
NA
200kA
Ip = 10kA @ 100kAPanel SCCR is 5kA
Limiting Factor is Branch 3
49
Panel SCCR is still 5kA
Summary– Feeder SCCR = 100kA
– Branch 1 SCCR = 100kA (was 10kA)
– Branch 2 SCCR = 200kA (was 5kA)
– Branch 3 SCCR = 5kA
Branch 3 is the limiting factor in our panel!
50
1. Upgrade to components with higher SCCR
2. Add sub-feeder fuses
3. Upgrade feeder overcurrent protection device with a higher current limiting device
4. Consider type tested components, i.e., components that have been tested by the manufacturer under specific conditions and witnessed by UL
There are four methods that could be utilized
What can I do to increase my panel SCCR?Q
A&
51
Option 1: Upgrade to components with higher SCCR
Ip = 10kA @ 100kA
Branch 3 = 5kA
SB4.1
5kA
65kA
10kA
Branch 3 = 65kA
Solution– Replace the un-labeled motor starter
with one that has a SCCR of 10kA
Now we can utilize the current limiting capabilities of the feeder OCPD
52
Option 2: Add a sub-feeder fuse
SB4.1
5kA
65kA
Branch 3 = 5kA
By adding a sub-feeder fuse, the standard allows you to use this fuse as your current limiting feeder protection
In this case lets add a Class CC 20A Fuse– ATDR20
53
Class CC 20A
– 50kA peak Ip = 3kA
– 100kA peak Ip = 4kA
– 200kA peak Ip = 5kA
54
Option 2: Add a sub-feeder fuse
SB4.1
5kA
65kA
Branch 3 = 5kA
Branch 3 = 65kAClass CC, 20A
– ATDR20
– Ip = 4kA @ 100kA Fault
This sub-feeder fuse will allow the panel SCCR to be increased to 65kA because once again the MCCB becomes the limiting device
55
Feeder
100kA
200kA
200kA
Option 3: Upgrade feeder OCPD
Not applicable for this example. We are using the most current limiting device
Use option 3 if you are using a circuit breaker as your feeder overcurrent protective device
56
Option 4: Consider type tested components
65kA
SB4.1
5kA
Branch 3 = 5kASome manufacturers “type test”
fuses or circuit breakers with their motor starters to achieve a higher SCCR rating when used in combination
Each major controller manufacturer type tests their components on an annual basis. Results are available on UL.com
57
Option 4: Consider type tested components
Example:– 12A Motor Starter and 15A MCCB are both Schneider products
(Square D, Telemecanique)
– 12A IEC Contactor• Part # LC1D12
– OVLD Relay, 5.5–8A• Part # LRD12
– 15A Circuit Breaker• Part # GJL36015
58
UL provides links to each manufacturers website displaying the SCCR testing results. (www.ul.com/controlequipment/shortcircuit.html)
Component Type
Component Manufacturer Component Catalog Designation
Component kA
Component Amps
Combination kA
Combination Volts
ICB Square D GJL36015M03 - 15 65 480MC Telemecanique LC1D12 5 12OLR Telemecanique LRD10 5 4 - 6OLR Telemecanique LRD12 5 5.5 - 8OLR Telemecanique LRD14 5 7 - 10OLR Telemecanique LRD16 5 9 - 13OLR Telemecanique LRD1510 5 4 - 6OLR Telemecanique LRD1512 5 5.5 - 8OLR Telemecanique LRD1514 5 7 - 10OLR Telemecanique LRD1516 5 9 - 13
F Any Class CC 200 30 100 480MC Telemecanique LC1D12 5 12 1 0 0 4 8 0
OLR Telemecanique LRD01 5 0.10 - 0.16 1 0 0 4 8 0
OLR Telemecanique LRD02 5 0.16 - 0.25 1 0 0 4 8 0
OLR Telemecanique LRD03 5 0.25 - 0.40 1 0 0 4 8 0
OLR Telemecanique LRD04 5 0.40 - 0.63 1 0 0 4 8 0
OLR Telemecanique LRD05 5 0.63 - 1 1 0 0 4 8 0
OLR Telemecanique LRD06 5 1 - 1.6 1 0 0 4 8 0
OLR Telemecanique LRD07 5 1.6 - 2.5 1 0 0 4 8 0
OLR Telemecanique LRD08 5 2.5 - 4 1 0 0 4 8 0
OLR Telemecanique LRD10 5 4 - 6 1 0 0 4 8 0
OLR Telemecanique LRD12 5 5.5 - 8 1 0 0 4 8 0
OLR Telemecanique LRD14 5 7 - 10 1 0 0 4 8 0
OLR Telemecanique LRD16 5 9 - 13 1 0 0 4 8 0
OLR Telemecanique LRD1508 5 2.5 - 4 1 0 0 4 8 0
OLR Telemecanique LRD1510 5 4 - 6 1 0 0 4 8 0
OLR Telemecanique LRD1512 5 5.5 - 8 1 0 0 4 8 0
OLR Telemecanique LRD1514 5 7 - 10 1 0 0 4 8 0
OLR Telemecanique LRD1516 5 9 - 13 1 0 0 4 8 0
59
This information is also available by viewing the Mersen USFM vs. Circuit Breaker Comparison Sheet available on our website
60
Option 4: Consider using type tested components
Branch 3 = 5kA
200kA
5kA
Branch 3 = 100kAReplace the 15A circuit breaker
with the USFMCCI and the ATDR20
The USFMCCI + ATDR25 combined with the Telemecanique Motor Starter yields a SCCR of 100kA
61
Panel SCCR is now 100kA
Summary– Feeder SCCR = 100kA
– Branch 1 SCCR = 100kA (was 10kA)
– Branch 2 SCCR = 200kA (was 5kA)
– Branch 3 SCCR = 100kA (was 5kA)
By using option 4 we were able to remove the circuit breaker in Branch 3 and replace it with fusing in order to increase our panel SCCR
62
Questions and Answers