193
Save 40% by Complying with Standard 90.1-2019 McHenry Wallace Jr., PE, LEED ® -AP Joseph Deringer, AIA, LEED ® -AP © 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

Save 40% by Complying with Standard 90.1-2019 - ASHRAE

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Save 40% by Complying with Standard 90.1-2019

McHenry Wallace Jr., PE, LEED®-APJoseph Deringer, AIA, LEED®-AP

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

2

Copyright Materials

• Copyright 2019, 2020 by ASHRAE. All rights reserved. No part of thispresentation may be reproduced without written permission from ASHRAE,nor may any part of this presentation be reproduced, stored in a retrievalsystem or transmitted in any form or by any means (electronic, photocopying,recording or other) without written permission from ASHRAE.

• ASHRAE has compiled this presentation with care, but ASHRAE has notinvestigated and ASHRAE expressly disclaims any duty to investigate anyproduct, service, process, procedure, design or the like, that may bedescribed herein. The appearance of any technical data or editorial material inthis presentation does not constitute endorsement, warranty or guaranty byASHRAE of any product, service, process, procedure, design or the like.ASHRAE does not warrant that the information in this publication is free oferrors. The user assumes the entire risk of the use of the use of anyinformation in this presentation.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

3

About the Instructors

McHenry Wallace Jr., PE, Member ASHRAE, LEED® AP, has been a mechanical contractor, consulting engineer and a registered engineer in Texas for over 30 years. Mack is heavily involved on the front lines of the energy conservation industry, having served for the past 18 years on the ASHRAE Standard 90.1 Committee. He was the engineer of record for many award-winning projects, including the Historic Preservation of the Texas State Capitol Building. Mack was director of design/build services for TXU Energy and responsible for developing and guaranteeing the energy savings on many projects. He has trained hundreds of engineers and architects, world-wide, on ASHRAE 90.1 and is the co-author of the new publication Significant Changes to International Energy Conservation Code and ANSI/ASHRAE/IES Standard 90.1. Currently, Mack has his own company, WiseWatt LLP and Leads the Mechanical Design Group for JACOBS in South Korea and is Technical Principal Mechanical for Federal Solutions.

Joseph Deringer, AIA, LEED® AP, is Executive Director of the Institute for the Sustainable Performance of Buildings (SuPerB). Mr. Deringer has over 35 years’ experience in the design, analysis and simulation of sustainable, energy-efficient buildings worldwide. His work has focused especially on energy codes, design assistance, training and the development of interactive online design and training tools. He has over 20 years’ involvement in developing energy codes for buildings, and has helped 7 countries develop 1st generation energy codes. Mr. Deringer has served on ASHRAE’s Standard 90.1 committee for 15 years and chaired its envelope subcommittee for 10 years. He is also active as international energy and environmental consultant to the World Bank, UNDP, and USAID, consulting on projects in over a dozen countries in Southeast Asia, the Caribbean, Latin America, the Middle East, and Eastern Europe. He is a member of IBPSA-USA, AIA, IES, ASHRAE and USGBC.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

4

AIA/CES Registered Provider

• ASHRAE is a Registered Provider with The American Institute ofArchitects Continuing Education Systems. Credit earned oncompletion of this program will be reported to CES Records forAIA members. Certificates of Attendance for non-AIA membersare available on request.

• This program is registered with the AIA/CES for continuingprofessional education. As such, it does not include content thatmay be deemed or construed to be an approval or endorsementby the AIA of any material of construction or any method ormanner of handling, using, distributing, or dealing in any materialor product. Questions related to specific materials, methods, andservices will be addressed at the conclusion of this presentation.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

5

3

GBCI cannot guarantee that course sessions will be delivered to you as submitted to GBCI. However, any course found to be in violation of the standards of the program, or otherwise contrary to the mission of GBCI, shall be removed. Your course evaluations will help us uphold these standards.

Course ID: 920020736

Save 40% by Complying withStandard 90.1-2019

By ASHRAE

Approved for:

3General CE hours

0LEED-specific hours

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

6

Course Outline

Introduction§4 Administration & Enforcement§5 Building Envelope§6 HVAC & Mechanical§7 Service Water Heating§8 Power§9 Lighting§10 Other Equipment§11 & Appendix G – Whole Building ComplianceSummary

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

7

Learning Objectives

• Describe the background and development of Standard90.1, its requirements and compliance paths

• Describe updated requirements from previous versions ofthe standard for key technical sections of the standard:

– Lighting, Building Envelope, HVAC, SWH, Power, and Other Equipment

• Describe the changes made to the Standard in 2016 and2019 with context for understanding and applying thechanges.

• Explore ways to improve system energy performance inbuildings

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

8

Energy Code Adoption Dec-2018

As of Dec 2018

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

9

Historical Efficiency Improvements

ASHRAE 90.1-2016ASHRAE

90.1-2016 ASHRAE90.1-2019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

10

Integrated Building Design

Lighting

Envelope

Plug Load

HVAC

Outside Air

People

Service Water

Heating

Parking Garage

ExteriorLighting

MINIMIZETHE HVAC LOAD

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

11

Integrating BIM & BEM to Deliver High-Performance Buildings

BEMBEM BEM BEM

BIM

Ideal time for

Integrated Design

BEM

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

12 © 2019 ASHRAE Learning Institute12 © 2012 ASHRAE Learning Institute

Comfort Chart

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

13 © 2019 ASHRAE Learning Institute13 © 2012 ASHRAE Learning Institute

Comfort Chart New City for 2016 CZ -1

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

14

ASHRAE Standard 209-2018

General Requirements1. Climate and Site Analysis2. Benchmarking3. Energy Charrette4. Establish Energy Performance Goals

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

15

New 9 Climate Zones –Standards 169-2013 & 90.1-2016 & 2019

Std 90.1-2016, with 9 Climate Zone Tables

New since 2016

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

16

World Climate Zones for Standards 169-2013 & 90.1-2016

Note two new Climate Zones:

CZ 0A: (Extremely Hot Humid) represented as white areas in South America, Africa, India, and South Asia.

CZ 0B: (Extremely Hot Dry) shown as gray areas in Africa, Saudi peninsula, Pakistan, India, and Australia.

New since 2016

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

17

Organization of Standard 90.1Foreword1 Purpose2 Scope3 Definitions, Abbreviations and Acronyms 4 Administration and Enforcement5 Building Envelope6 Heating, Ventilating and Air-Conditioning (HVAC)7 Service Water Heating8 Power9 Lighting10 Other Equipment11 Energy Cost Budget (ECB) Method12 Normative References

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

18

Appendices

• Normative Appendix A: Rated R-Value of Insulation and Assembly U-Factor, C-Factor, and F-Factor Determinations

• Informative Appendix B: (Retained for Future Use)• Normative Appendix C: Methodology for Building Envelope Trade-Off

Option in Section 5.6• Informative Appendix D: (Retained for Future Use)• Informative Appendix E: Informative References• Informative Appendix F: U.S. Department of Energy Minimum Energy

Efficiency Requirements• Normative Appendix G: Performance Rating Method• Informative Appendix H: Addenda Description Information• Annex 1: Reference Standard Reproduction Annex—ASHRAE

Standard 169

Items & Structure Revised in 2019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

19

Section 4

ADMINISTRATION & ENFORCEMENTSection 4:ADMINISTRATION AND ENFORCEMENT

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

20

Section 4.2.1 Compliance Paths

In 2016 a 3rd Path was Added (Same in 2019)

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

21

Appendix G: 2016 – 2019 Performance Rating Method

Appendix G: 2016 & 2019 Modeling Requirements

90.1-2016 & 2019 Mandatory Requirements (§ 5.4, 6.4, 7.4, 8.4, 9.4,

10.4) with exceptions

90.1-2016 & 2019 Prescriptive Requirements (From 90.1-2004)

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

22

For Performance Rating Method (App. G) Revised Calculation for “Index of Merit”

• Performance rating method: a calculation procedure thatgenerates an index of merit for the performance of buildingdesigns that substantially exceeds the energy efficiency levelsrequired by this standard or when using the performance ratingmethod as an alternative path for minimum standard compliancein accordance with Section 4.2.1.1

• 2019 – for new buildings and alterations/additions• When using Appendix G, the Performance Cost Index (PCI)

shall be less than or equal to the Performance Cost IndexTarget (PCIt) when calculated in accordance with the following:

% Savings = 100 x [(PCIt – PCI)/ PCIt]

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

23

Calculation to Comply Using Appendix G• PCIt = [BBUEC + (BPF X BBREC)]- PNA / BBP

Where • PCIt = Performance Cost Index Target• PCI = Performance Cost Index= [Proposed Building

Performance]/[Baseline Building Performance]• BBUEC = Baseline Building Unregulated Energy Cost• BPF = Building Performance Factor from Table 4.2.1.1*• BBREC = Baseline Building Regulated Energy Cost• PNA = Proposed renewable energy contribution not

allowed for compliance (New 2019)• BBP = Baseline Building Performance

*Table 4.2.1.1 – For building types not listed use “all others.”For multi-use buildings use area-weighted average.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

24

PNA – New for 2019• We do not want Renewables to result in worse walls or

mechanical systems• Therefore the savings from renewables to show

compliance is limited to 5%• PBP = Proposed Building Performance including the

reduced, annual purchased energy cost associatedwith all on-site renewable energy generation systems

• PBPnre = Proposed Building Performance without anycredit for reduced annual energy costs from on-siterenewable energy generation systems.

• Renewable contribution = PBPnre – PBP• Renewable Fraction = ( - PBP)/BBP if<=5 PNA=0 -

if>5• PNA = Renewable Contribution – (0.5 x BBP)

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

25

Table 4.2.1.1:2019 Building Performance Factors (BPFs)

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

26

Example – Show Compliance

Inputs– An office building in Chicago(CZ-5A)– Area = 50,000 ft2 - Office Building– Proposed Building Performance has been calculated at =

$32,000/year– BBP = $49,000/year BBP = Baseline Building Performance– BBREC = $34,000/year BBREC = Baseline Building Regulated Energy

Cost– BBUEC = $15,000/year Baseline Building Unregulated Energy Cost

Lookup– 2019: From Table 4.2.1.1, for Office in Climate Zone 5A, the BPF = 0.51– 2016: From Table 4.2.1.1, for Office in Climate Zone 5A, the BPF = 0.60

Calculations (next slide)

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

27

Example – Show ComplianceCalculations 1. PCI = Performance Cost Index= [Proposed Building

Performance]/[Baseline Building Performance]PCI = $32,000/$49,000 = 0.65

2. PCIt = [BBUEC + (BPF X BBREC)] / BBPWhere PCIt = Performance Cost Index Target

PCIt = [$15,000 + (0.51 X $34,000)]/$49,000 = 0.66

3. Since PCI at 0.65 < PCIt at 0.66, the building complies4. Savings = 100 x [(PCIt – PCI)/ PCIt]

= 100 x [(0.66 - 0.65)/ 0.66] = 1.5 % Same Building in 2016 saved 9.7%

If we added renewables we could only count a maximum of 5% for compliance.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

28

2010 - BPFs for Use with LEED 4

Thanks to : Michael Rosenberg PNNL - Jun 2016 ASHRAE Journal

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

29

Federal Projects

Federal projects must use 30% less energy than the current addition of 90.1. The calculation used is not the calculation from 90.1. The calculation, shown above, is based on consumption and does not include unregulated loads. It has been recently based on 90.1-2013, but in November, 2019, it is based on 90.1-2016.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

30

Section 4.2.5 Verification,Testing, & Commissioning Major expansion

of requirements In 2019)

90.1-2019 has a Major Expansion of Section 4.2.5 Requirements

For Verification, Testing & Commissioning of:

• Building Systems,• Controls• The Building Envelope

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

31

Building Systems Verification & Testing Requirements (§ 4.2.5.1 )

Verification or functional performance testing (FPT) to confirm compliance with required provisions of this standard shall be performed on building systems, controls, and the building envelopeas required by Sections • 5.9.1 - Building Envelope,• 6.9.1 - Heating, Ventilating and Air Conditioning,• 7.9.1 - Service Water Heating,• 8.9.1 – Power,• 9.9.1 – Lighting,• 10.9.1 - Other Equipment,• 11.2(d) - Energy Cost Budget Method (identified systems…)• G1.21(e). Performance Rating Performance (identified systems…)

New for 2019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

32

Building Commissioning Requirements (§ 4.2.5.2)

Commissioning shall be performed on building systems, controls, and the building envelopeas required by Sections • 5.9.2 - Building Envelope,• 6.9.2 - Heating, Ventilating and Air Conditioning,• 7.9.2 - Service Water Heating,• 8.9.2 – Power,• 9.9.2 – Lighting,• 10.9.2 - Other Equipment,• 11.2(d) - Energy Cost Budget Method (identified systems…)• G1.21(e). Performance Rating Performance (identified systems…)

New for 2019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

33

BUILDING ENVELOPEREQUIREMENTS IN 90.1-2019

Joseph Deringer, AIA, LEED®[email protected]

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

34

Structure of EnvelopePrescriptive Requirements

432 independent prescriptive requirements across 3 key categories:

1. Climate location (8) 8 zones from 2004 to 2013 26 zones before 2004

2. Space ConditioningCategories (3) Non-residential Residential Semi-heated

3. Classes of Construction (18) Opaque elements (14) Fenestration (4)

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

35

Climates Zones by New Mexico Counties

Zone 5B except:• Chaves 3B• Dona Ana 3B• Eddy 3B• Hidalgo 3B• Lea 3B• Luna 3B• Otero 3B

• Curry 4B• DeBaca 4B• Bernalillo 4B• Grant 4B• Guadalupe 4B• Lincoln 4B• Quay 4B• Roosevelt 4B• Sierra 3B• Socorro 4B• Union 4B• Valencia 4B• Catron 4B2016 & 2019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

36

Climate Zones by Texas Counties

New CZ 1 Counties:

• Cameron• Hidalgo• Willacy

New CZ 2 Counties:• Dallas• Ellis• Johnson• Navarro• Tarrant

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

37

Climate Zones by Georgia Counties

Georgia is Zone 3A Except: 42 southern counties are in Zone 2A

Atlanta,Fulton County 3A – Table 5.5-3

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

38

Envelope Classes of Construction:Opaque Portions (1)

• Roofs– Insulation above roof decks– Metal building roofs– Attic roofs with wood/steel

framing

• Above-grade walls– Mass walls– Metal building walls– Steel frame walls– Wood frame walls

• Below-grade walls

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

39

Fenestration Construction Classes

• In 2004– Fixed– Operable

• In 2007– Nonmetal framing (all)– Metal framing (curtain wall/storefront)– Metal framing (all other)– Metal framing (entrance door)

• In 2013 & 2016– Nonmetal framing, all– Metal framing, fixed– Metal framing, operable– Metal framing, entrance door

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

40

BUILDING ENVELOPE MANDATORY

REQUIREMENTSSection 5.4 of 90.1-2019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

41

Mandatory Provisions:for the Building Envelope

§ 5.4.1 Insulation – When required in 5.5 or5.6, it shall comply with the product information and installation requirements in §5.8.1.1 thru 5.8.1.9

§ 5.4.2 Fenestration and doors – Productinformation and installation requirements are in §5.8.2

§ 5.4.3 Air Leakage – Through 90.1-2007 hasbeen covered directly in §5.4.3 • Weak and not effective, until 2010

Refinement to include sectional garage doors added in 2013.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

42

Continuous Air BarrierMandatory Requirement

• §5.4.3.1 The entire building envelope shall bedesigned and constructed with a continuous airbarrier.

• Exceptions:– Semi-heated spaces in climate zones 1 thru 6,

except as required to complete the continuous airbarrier of an adjacent conditioned space.

– Single wythe concrete masonry buildings in climatezone 2B.

• The Requirement includes provisions for:– Design of Continuous Air Barrier (CAB)– Installation of Continuous Air Barrier (CAB)– Acceptable Materials & Assemblies

Revised for 2019!

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

43

5.4.3.1.1 Whole Building Air Leakage(New Mandatory Requirement)

• Whole-building pressurization testing shall beconducted…

– In accordance with ASTM E779 or ASTM E1827– by an independent third party.

• Where a building contains both conditioned spaceand semiheated space compliance shall be shown:– separately for the conditioned space and for the

semiheated space…or

– for the conditioned space and for the semiheated spacetogether…

New for 2019!

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

44

Exceptions to…5.4.3.1.1 Whole Building Air Leakage

For buildings having over 50,000 ft2of gross conditioned floor area, • air leakage testing shall be

permitted to be conducted onless than the whole building,

• Provided…

New for 2019!

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

45

Air Leakage: Testing, Acceptable Materials, and AssembliesNew in

2019

Table 5.8.3.1 Maximum Air Leakage for Materials and Assemblies

Continuous Air Barrier

Maximum air leakage, cfm/ft2 (L/s●m2)

Minimum Test Pressure, psf (Pa) Test Method

Materialsa 0.004 (0.02) 1.57 (75) ASTM E2178

Assembliesb 0.04 (0.2) 1.57 (75)

ASTM E2357, ASTM E1677, ASTM E1680 ASTM E283

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

46

Air Leakage: Testing, Acceptable Materials, and AssembliesNew in

2019Table 5.8.3.2 Maximum Air Leakage for Fenestration and Doors

Fenestration and Door Products Maximum air

leakage, cfm/ft2 (L/s●m2)

Minimum Test Pressure, psf

(Pa) Test Methods

glazed swinging entrance doors, glazed power-operating sliding entrance doors , glazed power-operated folding entrance doors, and revolving doors

1.0 (5.1) 1.57 (75) AAMA/WDMA/CSA 101/I.S.2/A440, NFRC 400, or ASTM E283;

curtainwall and storefront glazing 0.06 (0.3) 1.57 (75) NRFC 400 or ASTM 283 unit skylights having condensation weepage openings

0.3 (1.5) 1.57 (75) AAMA/WDMA/CSA

101/I.S.2/A440 or NFRC 400

OR

0.5 (2.5) 6.24 (300) AAMA/WDMA/CSA 101/I.S.2/A440

nonswinging doors intended for vehicular access and material transportation, with a minimum opening rate of 32 in/s (0.8 m/s)

1.3 (6.6) 1.57 (75) ANSI/DASMA 105,

NFRC 400, or ASTM E283

other opaque nonswinging doors, glazed sectional garage doors, and upward acting glazed nonswinging 0.4 (2.0) 1.57 (75)

ANSI/DASMA 105, NFRC 400, or ASTM

E283 all other products

0.2 1.57 (75) AAMA/WDMA/CSA

101/I.S.2/A440 or NFRC 400

OR

0.3 (1.5) 6.24 (300) AAMA/WDMA/CSA

101/I.S.2/A440

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

47

Air Leakage: Vestibules,Refined Exceptions in 2016 & 2019

Exceptions to 5.4.3.4: 1. Building entrances Doors in building entrances with revolving doors.2. Doors not intended to be used as a building entrance door, such asmechanical or electrical equipment rooms.3. Doors opening directly from a dwelling unit.4. Building entrances Doors in buildings located in Climate Zones 1 and or2.5. Building entrances Doors in buildings located in Climate Zones 3 or 4that are less than four stories above grade and less than 10,000 ft2 (1000m2) in area.6. Building entrances in buildings located in Climate Zones 5, 6, 7, or 8that are less than 1000 ft2 (100 m2) in area. Doors used primarily tofacilitate vehicular movement or material handling and adjacent personneldoors.7. Doors that open directly from a space that is less than 3000 ft2 (300 m2)in area and is separate from the building entrance.8. Semiheated spaces.9. Enclosed elevator lobbies for building entrances directly from parkinggarages

New in 2016

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

48

Fenestration & Doors (1)

• Rating of Fenestration Products (§5.8.2.1)• Labeling of Fenestration Products(§5.8.2.2)• Labeling of Doors (§5.8.2.3)• U-factor (§5.8.2.4)• Solar Heat Gain Coefficient (§5.8.2.5)• Visible Light Transmittance (§5.8.2.6)

Mandatory provisions:

NFRC shall be used to determine compliance for:– U-Factor: NFRC 100– Solar Heat Gain Coefficient: NFRC 200– Visible Light Transmittance: NFRC 200– Air Leakage: NFRC 400

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

49

Commissioning of the Building Envelope (§ 5.9.2)

The energy performance of the building envelope shall be commissionedin accordance with Section 4.2.5.2.

Commissioning reporting shall comply with Section 4.2.5.2.2.

Informative Note: See Appendix E for commissioning references.

New for 2019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

50

PRESCRIPTIVEBUILDING ENVELOPE

OPTIONSection 5.5 of 90.1-2013

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

51

Prescriptive Option

• For given location (climate zone),one table contains all envelopeprescriptive requirements

(Shown is Table 5.5-4 for ClimateZone 4)

• Opaque envelope elements on top

• Fenestration on the bottom

• Fenestration limits for theprescriptive option require that:

• Windows are not more than than 40%but since 2013, WWR limit has beenset separately in each table.

• Skylights are now less than 3%.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

52

Opaque Stringency IncreasesFrom 2004 to 2019 - Roofs

0

5

10

15

20

25

30

35

40

0 1 2 3 4 5 6 7 8

Insu

latio

n R

-Val

ue

Climate Zone

Roof Insulation R-Values –Insulation Above Deck

90.1-200490.1-200790.1-201090.1-201390.1-201690.1-2019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

53

Opaque Stringency IncreasesFrom 2004 to 2019 - Walls

0

2

4

6

8

10

12

14

16

18

20

CZ 2 CZ 3 CZ 4 CZ 5 CZ 6 CZ 7 CZ 8

R-V

alue

of C

ontin

uous

Insu

latio

n

Continuous Wall Insulation R-Values -Steel Stud Walls

90.1-200490.1-200790.1-201090.1-201390.1-201690.1-2019

An R-Value = 13 is required between the steel studs in ALL climate locations.

In addition, in most climate locations, a layer of continuous insulation is ALSO required outside the studs. These additional continuous R-Values are shown here.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

54

Table 5.5-0:Climate Zone 0 (A,B) Opaque Elements only

New climate zone adopted in 2016.

Categories of Categories of Construction

Space Conditioning Categories

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

55

Table 5.5-1:Climate Zone 1 (A,B) Opaque Elements only

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

56

Table 5.5-2:Climate Zone 2 (A,B) Opaque Elements only

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

57

Table 5.5-3:Climate Zone 3 (A,B,C) Opaque Elements only

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

58

Table 5.5-4:Climate Zone 4 (A,B,C) Opaque Elements only

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

59

Table 5.5-5:Climate Zone 5 (A,B,C) Opaque Elements only

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

60

Table 5.5-6:Climate Zone 6 (A,B) Opaque Elements only

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

61

Table 5.5-7:Climate Zone 7 (A,B) Opaque Elements only

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

62

Table 5.5-8:Climate Zone 8 (*) Opaque Elements only

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

63

Compliance Using R-Values

• Compliance uses only the thermal transmittanceof the insulation added in two locations:– Within framing cavities– As continuous insulation without framing breaks

• Thermal transmittance not included for:– Other building materials in the assembly– Air films

• Insulation extent:– Over entire area of surface– To level of intended R-value rating

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

64

Compliance Using U-Factors, C-Factors, F-Factors

• Compliance is for the entire assembly

• Pre-Calculated Values in Appendix Ashall be used:– For U-Factors: Tables A2.2–A2.5, A3.1A-

A3.1C, A3.2-A3.4, A5.2-A5.4– For C-Factors: Tables 4.2– For F-Factors: Tables A6.3

• For assemblies significantly differentfrom those in Appendix A:– Values may be calculated.– Must be approved by building official.– Must use rules in Appendix A9.– Summary tabulation of required procedures

is shown in Table 5-H of the User’s Manual.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

65

Roof Solar Reflectanceand Thermal Emittance (1)

5.5.3.1.1 Roof Solar Reflectance and Thermal Emittance. Roofs, in climate zones 0 through 3 shall have one of the following:a. A minimum three-year-aged solar reflectance of 0.55, and a

minimum three-year-aged thermal emittance of 0.75 whentested in accordance with CRRC Standard S100.

b. A minimum Solar Reflectance Index of 64 when determinedin accordance with the Solar Reflectance Index method inASTM E1980 using a convection coefficient of 2.1BTU/h⋅ft2, based on three-year-aged solar reflectance andthree-year-aged thermal emittance tested in accordancewith CRRC S100 Standard.

c. Increased roof insulation levels found in Table 5.5.3.1.1.(next slide)

New approach adopted in 2010, refined since then.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

66

Roof Solar Reflectanceand Thermal Emittance (2)

5.5.3.1.1 Roof Solar Reflectance and Thermal Emittance. Roofs, in climate zones 0 through 3 shall have one of the following:c. increased roof insulation levels found in Table

5.5.3.1.1.

Added Climate Zone 0 in 2016, no change to table in 2019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

67

Fenestration:Prescriptive Requirements

Items Covered:• Compliance Method

– SHGC and U-value criteria– Rated – NFRC standards– Unrated – Alternate

procedures provided

• Credits / Exceptions– Credit for permanent

external shading– Street Level Fenestration

exempt from SHGCrequirements, if severalconditions are met.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

68

Glazing Types

• Spectral control – transmitlight, reject near-IR heat

• Equal daylight with only 50%of solar gain

• IG to minimize SHGC

Technology:• Selective absorbers

– Blue-green tints

• Selective reflectors– Modified low-E coatings– Coated glass and plastic– Multi-layer dielectric Transmittance -vs- Wavelength

Source: LBNL, Building Technology

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

69

Light-to-Solar Gain Ratio for insulating glass units for all glasses in LBNL International Glazing Data Base (IGDB)

Light-to-Solar Gain RatioLSG = 2.0

Tvis

SHGC

CZ 1-3 CZ 4-6CZ 7-8 non-res.

New in 2013: VT/SHGC ≥ 1.10 Req. in 2013

LSG = 1.0

LSG: Light-to-Solar Gain Ratio = VT / SHGC

CZ 1-3

New in 2016: SHGC = 22 for CZ 0New in 2019: multiple new SHGC limits (shown in green)

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

70

Fenestration Prescriptive Req.:90.1-2004 thru 90.1-2019

0

0.2

0.4

0.6

0.8

1

1.2

1.4

0 1 2 3 5 5 6 7 8

Ass

embl

y U

-Fac

tor

Climate Zone

Fenestration Assembly U‐Factor

200420072010201320162019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

71

Fenestration Prescriptive Req.:90.1-2004 thru 90.1-2019

0.000.050.100.150.200.250.300.350.400.450.50

0 1 2 3 4 5 6 7 8

SHG

C

Climate Zone

Fenestration SHGC

200420072010201320162019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

72

Table 5.5-4:Climate Zone 4 (A,B,C) Fenestration Elements only

Nonresidential Residential Semiheated

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

73

Minimum Skylight Fenestration Area

5.5.4.2.3 Minimum Skylight Fenestration Area. In any enclosed space in a building that is four stories or less and that is:

a. greater than 2,500 ft2 and,b. directly under a roof with ceiling heights greater than 15 ft, andc. one of the following space types: office, lobby, atrium, concourse,

corridor, storage (including non-refrigerated warehouse), gymnasium,fitness/exercise area, playing area, gymnasium seating area, conventionexhibit/event space, courtroom, automotive service, fire station engine room,manufacturing corridor/transition and bay areas, retail, library reading andstack areas, distribution/sorting area, transportation baggage and seatingareas, or workshop,

The total daylight area under skylights shall be a minimum of half the floor area and either:

a. provide a minimum skylight area to daylight area under skylights of 3%with a skylight VT of at least 0.40 or

b. provide a minimum skylight effective aperture of at least 1%.

New in 2016, no change for 2019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

74

Fenestration Orientation

5.5.4.5 Fenestration Orientation. The vertical fenestration shall comply with either (a) or (b):a. For Climate Zones 0 through 8,

AW � (AT)/4 and AE � (AT)/4b. For Climate Zones 0 through 3

AW x SHGCW � (AT x SHGCC)/4 and AE x SHGCE � (AT x SHGCC)/4

c. For Climate Zones 4 through 8AW x SHGCW � (AT x SHGCC)/5 and AE x SHGCE � (AT x SHGCC)/5

New in 2016, no change for 2019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

75

Credit for External Shading

• Credit is limited to overhangs

• Credit is not provided for otherexternal shading devices such as:Vertical fins, or Non-permanentdevices such as awnings.

• The SHGC of the proposed buildingmay be reduced by a multiplier listedin Table 5.5.4.4.1

• The same multiplier is applied to allorientations.

– Exception: In latitudes >10o, separatemultipliers are to be applied to the northorientation

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

76

External Shading Credit Part 2

Select multiplier from Table 5.5.4.4.1 based upon PF calculated.

Table 5.5.4.4.1 SHGC Multipliers for Permanent Projections

Projection Factor SHGC Multiplier (All Orientations)

SHGC Multiplier (North-Oriented)

0 - 0.10 1.00 1.00

<0.10 - 0.20 0.91 0.95

<0.20 - 0.30 0.82 0.91

<0.30 - 0.40 0.74 0.87

<0.40 - 0.50 0.67 0.84

<0.50 - 0.60 0.61 0.81

<0.60 - 0.70 0.56 0.78

<0.70 - 0.80 0.51 0.76

<0.80 - 0.90 0.47 0.75

<0.90 - 1.00 0.44 0.73

SHGC Multipliers

0

0.2

0.4

0.6

0.8

1

1.2

0 -0.10

<0.10- 0.20

<0.20- 0.30

<0.30- 0.40

<0.40- 0.50

<0.50- 0.60

<0.60- 0.70

<0.70- 0.80

<0.80- 0.90

<0.90- 1.00

Projection factors (PF)

Mul

tiplie

rs

Graphic presentation of table values

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

77

Building Envelope Trade-off Option

Section 5.6 in 90.1-2013

Very new approach adopted in 2013. First change since 90.1-1999.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

78

THANK YOU!

Any Questions on the Building Envelope?

Joseph Deringer, AIA, LEED®[email protected]

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

79

Section 8: POWER

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

80

8.4.3 Electrical Energy MonitoringH

VAC

SY

STEM

S

HVAC

INTE

RIO

R

LIG

HTI

NG

LIGHTING

EXTE

RIO

R

LIG

HTI

NG

SITE

REC

EPTA

CLE

C

IRC

UIT

S

PLUGS

TOTA

L EL

ECTR

ICAL

EN

ERG

Y

WHOLE BUILDING

Tenants separately monitored from total building, 10% of load can be other loads from same panel, report and store for minimum 36 months. 2016 – Connect to DDC system

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

81

8.6.1 Computer Room Systems

Power distribution systems and equipment onlyserving a computer room with IT equipmentload greater than 10 kW shall comply withASHRAE Standard 90.4, Energy Standard forData Centers.

2019 - All requirements for Data Centers havebeen removed from 90.1. Only remaininginformation is for for computer/com/data roomsin buildings other than Data Centers.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

82

Section 10: OTHER EQUIPMENT

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

83

Pump Requirement from Section 10

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

84

10.4.3 Elevators

Lighting• >=35lm/W

Ventilation• <=0.33 W/cfm

Standby Mode• After 15min – de-energize lighting/ventilation

Design Documents• List-Usage category from ISO 25745-2 and

energy efficiency per ISO 25745-2, table 7

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

85

10.4.4 Escalators and Moving Walks

Shall automatically slow to the minimum permitted speed when not conveying passengers

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

86

10.4.5 Air Curtains New for 2019• Air Curtains can now replace the requirement

for vestibules• Exceptions 9 and 10 to 5.4.3.3

9. Self-closing doors in buildings in Climate Zones 0,3, and 4 that have an air curtain complying withSection 10.4.5.

10. Self-closing doors in buildings 15 stories or less inClimate Zones 5 through 8 that have an air curtaincomplying with Section 10.4.5.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

87

10.4.7 Pumps – Clean Water New 2019

• Adds new DOE pump rules to 90.1 – enforced Jan 27, 2020• Covered Pumps: Pumps with a Best Efficiency Point (BEP),

definition added to section 4, pump power input between 1 and200 horsepower (hp); BEP rate of flow of 25 gallons per minute(gpm) or greater; BEP head of 459 feet or less; temperaturebetween 14 and 248 F; and nominal speeds of 1,800 and3,600 revolutions per minute (rpm)

• The general pump types covered by these regulations include:– End suction closed coupled, End suction frame mounted,

In-line, Radially split multistage in-line diffuser casing,Submersible turbine

• Any of these type pumps distributed in the US must have a PEI≤ 1. PEI = performance of pump / minimum from tables

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

88

Section 9: LIGHTING

Source of image: eLAD, LBNL, SuPerB, Vaidya, Deringer, et al.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

89

Section 9: Lighting

9.1 General Information 9.2 Compliance Paths9.3 Simplified Building (New)9.4 Mandatory Provisions

– Controls– Exterior Lighting

9.5 Building Area Method Compliance Path (“Prescriptive” wording not used)

9.6 Alternative Compliance Path: Space-by-Space Method

9.7 Submittals 9.9 Verification, Testing, & Commissioning (New)

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

90

Changes in RequirementsFrom 1999 to 2004• Major reduction in lighting power density requirements

From 2004 to 2007• Exterior lighting equipment has new efficacy requirements• Definitions – several added for clarity

From 2007 to 2010• Reduction in lighting power density requirements• Refinements in control requirements

From 2010 to 2013• Reduction in lighting power density requirements• Refinements in control requirements

From 2013 to 2019• Major reduction in lighting power density requirements• Refinements in control requirements• Simplified Compliance

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

91

§ 9.1 General: Scope of Requirements

• Requirements apply to: (§9.1.1)

– Interior spaces of buildings– Exterior building features– Exterior building grounds lighting provided through the building’s

electrical service

• Requirements apply to:– New construction– Alterations to existing buildings (§9.1.2)

– the lighting requirements are triggered only when 20% or more ofthe connected load in a space or area are replaced (§9.1.2)

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

92

Lighting Power Trade-Offs

• Separate requirements exist for:– Exterior– Interior

• Each system must comply separately with theirrespective requirements

• Trade-offs between the two are not allowed

• Trade-offs are only permitted:– Interior lighting – among spaces– Exterior lighting – among some (safety excluded)

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

93

Installed Interior Lighting Power

Include in calculations all power used by a luminaire:

Reference: Lighting Control § 9.1.3 User Manual pg. 9-6 and 9-7

• Lamps

• Ballasts

• Transformers

• Control devices

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

94

Compliance Paths and Process (§9.2)

Mandatory provisions mustalways be met, plus

Prescriptive interior lightingpower allowances permituse of: Building area method

Space-by-space method

Section 11 Energy CostBudget Method

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

95

§9.3 SIMPLIFIED BUILDINGMETHOD

COMPLIANCE PATHInterior & Exterior Lighting For:

Office BuildingsRetail BuildingsSchool Buildings

New for 2019!

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

96

9.3.1-1 Simplified Building Method forOffice Buildings New for 2019!

Table 9.3.1-1 Simplified Building Method for Office Buildings

Interior Space Type Interior Lighting Power Allowance

Controls (All lights in the space shall be controlled)

All spaces in office buildings other than parking garages, stairwells, and corridors

0.70 W/ft2 (7.5 W/m2)

All lighting shall be automatically controlled to turn off when the building is either unoccupied or scheduled to be unoccupied.

Exception: Lighting load not exceeding 0.02 W/ft2 (0.2 W/m2) multiplied by the gross lighted area of the building shall be permitted to operate at all times.

Each space shall have a manual control device that allows the occupant to reduce lighting power by a minimum of 50% and to turn the lighting off.

Office spaces less than or equal to 250 ft2 (23.2 m2), classrooms, conference rooms, meeting rooms, training rooms, storage rooms, and break rooms

These spaces shall also be controlled by manual-on occupant sensors.

Office spaces greater than 250 ft2 (23.2 m2) and restrooms

These spaces shall also be controlled by occupant sensors.

Stairwells and corridors in office buildings and parking garages

These spaces shall also be controlled by occupant sensors that reduce the lighting power by a minimum of 50% when no activity is detected for not longer than 20 minutes and be controlled to turn off when the building is either unoccupied or scheduled to be unoccupied.

Parking garages 0.13 W/ft2 (1.4 W/m2)

All lighting shall be automatically controlled to turn off during garage non-operating hours. Lighting shall also be controlled by occupant sensors. Controls shall reduce the power by a minimum of 50% when no activity is detected for not longer than 20 minutes. No device shall control more than 3600 ft2 (334 m2).

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

97

§9.4 MANDATORYIncludes:

9.4.1 Lighting Control9.4.1.1 Interior Lighting Controls9.4.1.2 Parking Garage Lighting Control9.4.1.3 Special Applications9.4.1.4 Exterior Lighting Control

9.4.2 Exterior Building Lighting Power9.4.3 Functional Testing

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

98

9.4.1.1Interior Lighting Controls

General a. Local Controlb. Restricted to Manual Onc. Restricted to partial automatic ONd. Bi-level lighting controle. Automatic daylight responsive

controls for sidelightingf. Automatic daylight responsive

controls for toplightingg. Automatic partial OFF

(full OFF complies)h. Automatic full OFFi. Scheduled shutoff

ON

OFF

70%

30%

20 minutes

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

99

9.4.1.1 INTERIOR LIGHTING CONTROLS a. Local Control

• There shall be one or more manuallighting controls in the space thatcontrols all of the lighting in the space.

• Each control device shall control anarea:

1. No larger than 2500 ft2 if the spaceis <10,000 ft2

2. No larger than 10,000 ft otherwise.

9,000 ft2 office requires 4 controls

11,000 ft2 office requires 2 controls

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

100

9.4.1.1 INTERIOR LIGHTING CONTROLS e. Automatic daylight responsive controls for sidelighting

In any space where the combined input power of all general lighting completely or partially within the primary and secondary sidelighted areas is 300 W or greater, The general lighting in the primary sidelighted areas and secondary sidelighted areas shall be controlled by photocontrols.

Major New Requirement, 2013

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

101

9.4.1.1 INTERIOR LIGHTING CONTROLS f. Automatic daylight responsive controls for toplighting

The control system shall have the following characteristics:

1. The calibration adjustments shall be readilyaccessible;

2. The photocontrol shall reduce electric lighting inresponse to available daylight using continuousdimming or with:

a. at least one control step that is between 50% and 70% ofdesign lighting power,

b. a second control point between 20% and 40% of designlighting power or the lowest dimming level the technologyallows, and

c. a third control point that turns off all the controlled lighting.

3. General lighting in overlapping toplighted andsidelighted daylight areas shall be controlledtogether with general lighting under skylights &roof monitors.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

102

9.4.1.1 INTERIOR LIGHTING CONTROLS e. Automatic daylight responsive controls for sidelighting

Refined Interpretation, 2019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

103

§9.4.2 Exterior BuildingLighting Power

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

104

Exterior Building Lighting Power §9.4.2 Revised

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

105

Table 9.4.2-2 Exterior Lighting Power Requirements, Base Site Allowance & Part 1, Tradable

Table 9.4.2-2 Individual Lighting Power Allowances for Building Exteriors

Zone 0 Zone 1 Zone 2 Zone 3 Zone 4

Base Site Allowance (Base allowance may be used in tradable or nontradable surfaces.) No allowance 350 W 400 W 500 W 900 W

Tradable Surfaces (LPD allowances for uncovered parking areas, building grounds, building entrances, exits and loading docks, canopies and overhangs, and outdoor sales areas may be traded.) Uncovered Parking Areas Parking areas and drives No allowance 0.03 W/ft2 0.04 W/ft2 0.06 W/ft2 0.08 W/ft2 Building Grounds Walkways/ramps less than 10 ft wide No allowance 0.5 W/linear

foot 0.5 W/linear

foot 0.6 W/linear

foot 0.7 W/linear

foot Walkways/ramps 10 ft wide or greater Plaza areas Special feature areas

No allowance 0.10 W/ft2 0.10 W/ft2 0.11 W/ft2 0.14 W/ft2

Dining areas No allowance 0.65 W/ft2 0.65 W/ft2 0.75 W/ft2 0.95 W/ft2 Stairways No allowance 0.60 W/ft2 0.70 W/ft2 0.70 W/ft2 0.70 W/ft2 Pedestrian tunnels No allowance 0.12 W/ft2 0.12 W/ft2 0.14 W/ft2 0.21 W/ft2 Landscaping No allowance 0.03 W/ft2 0.04 W/ft2 0.04 W/ft2 0.04 W/ft2 Building Entrances, Exits, and Loading Docks Pedestrian and vehicular entrances and exits

No allowance 14 W/lin ft of opening

14 W/lin ft of opening

21 W/lin ft of opening

21 W/lin ft of opening

Entry canopies No allowance 0.20 W/ft2 0.20 W/ft2 0.20 W/ft2 0.20 W/ft2 Loading docks No allowance 0.35 W/ft2 0.35 W/ft2 0.35 W/ft2 0.35 W/ft2 Sales Canopies Free standing and attached No allowance 0.4 W/ft2 0.4 W/ft2 0.6 W/ft2 0.7 W/ft2 Outdoor Sales Open areas (including vehicle sales lots) No allowance 0.2 W/ft2 0.2 W/ft2 0.2 W/ft2 0.2 W/ft2 Street frontage for vehicle sales lots in addition to “open area” allowance

No allowance No allowance 7 W/lin ft 7 W/lin ft 21 W/lin ft

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

106

Table 9.4.2-2 Exterior Lighting Power Requirements, Part 2, Nontradable

Nontradable Surfaces (LPD allowances for the following applications can be used only for the specific application and cannot be traded between surfaces or with other exterior lighting. The following allowances are in addition to any allowance otherwise permitted in the “Tradable Surfaces” section of this table.) Building facades (The allowance for each illuminated façade orientation shall be calculated by multiplying the allowance value by the entire façade area or façade length for that orientation.)

No allowance No allowance 0.1 W/ft2 of façade area or 2.5 W/linear

foot of façade length

0.15 W/ft2 of façade area or 3.75 W/linear foot of façade

length

0.2 W/ft2 of façade area or 5.0 W/linear

foot of façade length

Automated teller machines and night depositories

No allowance 135 W per location plus

45 W per additional ATM per location

135 W per location plus

45 W per additional ATM per location

135 W per location plus

45 W per additional ATM per location

135 W per location plus

45 W per additional ATM per location

Uncovered entrances and gatehouse inspection stations at guarded facilities

No allowance 0.5 W/ft2 0.5 W/ft2 0.5 W/ft2 0.5 W/ft2

Uncovered loading areas for law enforcement, fire, ambulance, and other emergency service vehicles

No allowance 0.35 W/ft2 0.35 W/ft2 0.35 W/ft2 0.35 W/ft2

Drive-through windows/doors No allowance 200 W per drive-through

200 W per drive-through

200 W per drive-through

200 W per drive-through

Parking near 24-hour retail entrances No allowance 400 W per main entry

400 W per main entry

400 W per main entry

400 W per main entry

Roadway/parking entry, trail head, and toilet facility, or other locations approved by the authority having jurisdiction

A single luminaire of 25 W or less

No additional allowance

No additional allowance

No additional allowance

No additional allowance

For areas that are not listed in this table or are not comparable to areas listed in this table, use the comparable interior space type from Table 9.6.1 as modified by factors in this row

No allowance 65% of the interior

lighting power allowance

value

65% of the interior

lighting power allowance

value

80% of the interior

lighting power allowance

value

100% of the interior

lighting power allowance

value

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

107

§9.9.1 Functional TestingFor:• Occupancy sensors• Automatic time switches• Daylighting Controls

Limits on who can do it …

A major expansion of previous requirements!Most extensive functional testing in 90.1-2013.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

108

§9.9.2 Commissioning ofLighting System

The energy performance of the building lighting shall be commissioned in accordance with Section 4.2.5.2.

Commissioning reporting shall comply with Section 4.2.5.2.2.

Informative Note: See Appendix E for commissioning references.

A major expansion of previous commissioning requirements in 2019!

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

109

§9.5 BuildingArea Method

A Compliance Path

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

110

TABLE 9.5.1 Lighting Power Densities Using the Building Area Method, LPD, W/ft2

Building Area 2001 2004 2007 2010 2013 2016 2019 2019 Pct Less than 2001

2019 Pct Less than 2004

2019 Pct Less than 2016

Automotive facility 1.50 0.90 0.90 0.82 0.80 0.71 0.75 50% 17% ‐3%Convention center 1.40 1.20 1.20 1.08 1.01 0.76 0.64 46% 47% 9%Courthouse 1.40 1.20 1.20 1.05 1.01 0.90 0.79 36% 34% 10%Dining: Bar lounge/leisure 1.50 1.30 1.30 0.99 1.01 0.90 0.80 40% 38% 9%Dining: Cafeteria/fast food 1.80 1.40 1.40 0.90 0.90 0.79 0.76 56% 46% 2%Dining: Family 1.90 1.60 1.60 0.89 0.95 0.78 0.71 59% 56% 5%Dormitory 1.50 1.00 1.00 0.61 0.57 0.61 0.53 59% 47% 5%Exercise center 1.40 1.00 1.00 0.84 0.65 0.72 54% 28% ‐5%Fire station 0.71 0.67 0.53 0.56 ‐2%Gymnasium 1.70 1.10 1.10 1.00 0.94 0.68 0.76 60% 31% ‐5%Health‐care clinic 1.60 1.00 1.00 0.87 0.90 0.82 0.81 49% 19% 1%Hospital 1.20 1.20 1.21 1.05 1.05 0.96 20% 9%Hotel/Motel 1.70 1.00 1.00 1.00 0.87 0.75 0.56 56% 44% 14%Library 1.50 1.30 1.30 1.18 1.19 0.78 0.83 48% 36% ‐4%Manufacturing facility 2.20 1.30 1.30 1.11 1.17 0.90 0.82 59% 37% 7%Motel 2.00 1.00 1.00 0.88 0%Motion picture theater 1.60 1.20 1.20 0.83 0.76 0.83 0.44 48% 63% 32%Multifamily 1.00 0.70 0.70 0.60 0.51 0.68 0.45 32% 36% 16%Museum 1.60 1.10 1.10 1.06 1.02 1.06 0.55 34% 50% 54%Office 1.30 1.00 1.00 0.90 0.82 0.79 0.64 39% 36% 12%Parking garage 0.30 0.30 0.30 0.25 0.21 0.15 0.18 50% 40% ‐0.5%Penitentiary 1.20 1.00 1.00 0.97 0.81 0.75 0.69 38% 31% 5%Performing arts theater 1.50 1.60 1.60 1.39 1.89 1.18 0.84 21% 48% 40%Police station 1.30 1.00 1.00 0.96 0.87 0.80 0.66 38% 34% 11%Post office 1.60 1.10 1.10 0.87 0.87 0.67 0.65 58% 41% 1%Religious building 2.20 1.30 1.30 1.05 1.00 0.94 0.67 57% 48% 25%Retail 1.90 1.50 1.50 1.40 1.26 1.06 0.84 44% 44% 23%School/university 1.50 1.20 1.20 0.99 0.87 0.81 0.72 46% 40% 7%Sports arena 1.50 1.10 1.10 0.78 0.91 0.87 0.76 42% 31% 10%Town hall 1.40 1.10 1.10 0.92 0.89 0.80 0.69 43% 37% 9%Transportation 1.20 1.00 1.00 0.77 0.70 0.61 0.50 49% 50% 7%Warehouse 1.20 0.80 0.80 0.66 0.66 0.48 0.45 60% 44% 1%Workshop 1.70 1.40 1.40 1.20 1.19 0.90 0.91 47% 35% ‐1%

Stringency from 2001 to 2019Building Area Method, Table 9.5.1 Revised

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

111

Doing the Calculations

90.1-2004 Lighting power allowance = 1.00 x 9000 = 9,000 W

Building type = office

Lighting power density =

1.0 W/ft² (in 2004)0.64 W/ft² (in 2019)

Gross lighted area = 100 ft x 90 ft = 9,000 ft²

90.1-2010 Lighting power allowance = 0.90 x 9000 = 8,100 W90.1-2013 Lighting power allowance = 0.82 x 9000 = 7,380 W90.1-2016 Lighting power allowance = 0.79 x 9000 = 7,110 W90.1-2019 Lighting power allowance = 0.64 x 9000 = 5,760 W

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

112

In-Class Exercise Ltg-1: Determine Lighting Power Limits• For the 30,000 ft² building shown below, use the Building

Area Method and Table 9.5.1 to determine the 90.1-2019lighting power limit(s) for the building.

• The building has retail on the ground level and offices on thesecond and third levels.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

113

§9.6Space-by-Space

Method

tenant tenant tenant tenant

tenanttenanttenanttenant

common area

common area

common area

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

114

Space-by-Space Method (4)Table 9.6.1, Part

Revised

Lobby Facility for the visually impaired (and not used primarily by the staff)3

1.69 4 REQ REQ REQ REQ ADD2 ADD2

Elevator 0.65 6 REQ REQ REQ ADD2 ADD2Hotel 0.51 5 REQ REQ REQ ADD2 ADD2Motion picture theater 0.23 5 REQ REQ REQ ADD2 ADD2 Performing arts theater 1.25 6 REQ REQ REQ REQ ADD2 ADD2 All other lobbies 0.84 4 REQ REQ REQ REQ ADD2 ADD2 Locker Room 0.52 6 REQ ADD1 ADD1 REQ REQ REQ REQ Lounge/Breakroom Healthcare facility 0.42 6 REQ ADD1 ADD1 REQ REQ REQ REQ All other lounges/breakrooms 0.59 4 REQ ADD1 ADD1 REQ REQ REQ REQ Office Enclosed and ≤250 ft2 0.74 8 REQ ADD1 ADD1 REQ REQ REQ REQ

Enclosed and >250 ft2 0.66 8 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2

Open plan 0.61 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2 Parking Area, Interior 0.15 4 See Section 9.4.1.2 Pharmacy Area 1.66 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2 Restroom Facility for the visually impaired (and not used primarily by the staff)3

1.26 8 REQ REQ REQ

All other restrooms 0.63 8 REQ REQ REQ Sales Area4 1.05 6 REQ ADD1 ADD1 REQ REQ ADD2 ADD2

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

115

LPDs: 2013-2016Space by Space MethodTable 9.6.1 (Part 1)

Revised

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

116

Additional InteriorLighting Power (§9.6.2)

• Room Cavity Ratio (RCR) Threshold

• Decorative Lighting

• Retail Display Lighting

• Controls Adjustment

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

117

THANK YOU!

ANY

QUESTIONS? OPT 1

OPT 3

OPT 2

OPT 4

Fisheye View looking South - Falsecolor

Source, TWGI

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

118

HVAC & MECHANICALSection 6:

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

119

Compliance

New 2019 Section 6.9 Commissioning

6.6 is modified to reference 90.4

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

120

6.4.1 Minimum Equipment Efficiency

Tables 6.8.1-1 through 6.8.1-22–list mandatory minimum

equipment efficiency requirements

When more than one requirement

is listed, you must comply

with both requirements

In 2019 the tables were

cleaned up and new testing

procedures were used. 9 more

tables now exist.

If the equipment is not listed or if

it is operated outside the listed range, it can be

used without requirements

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

121

6.4.1.3 Ceiling Fans New 2019

Large-diameter ceiling fans shall be rated in accordance with 10CFR 430 Appendix U or AMCA 230. The following data shall beprovided:

a. Blade span (blade tip diameter).b. Rated airflow and power consumption at the maximum

speed.6.4.1.3.1 The data provided shall meet one of the following

requirements:1. is determined by an independent laboratory; or2. is included in a database published by the U.S. DOE; or3. is certified under a program meeting the requirements of

Section 6.4.1.5.Exception to 6.4.1.3Ceiling fans not covered in the scope of 10 CFR Part 430.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

122

Some New Definitions in 2019

• occupied-standby mode: when a zone is scheduledto be occupied and an occupant sensor indicates nooccupants are within the zone.

• off-mode power consumption (PW,OFF): the powerconsumption when the unit is connected to its mainpower source but is neither providing cooling norheating to the building it serves.

• on-site electricity generation systems: systemslocated at the building site that generate electricity,including but not limited to generators, combinedheat and power systems, fuel cells, and on-siterenewable energy systems.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

123

Definitions Continued

• standby power mode consumption (PW, SB): thepower used by a product or appliance when enabledbut in the standby operating mode (Refer to 10 CFR430).

• SERR series energy recovery ratio

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

124

2019 – Change from EER to CEER for window units

Room air conditionerswithout louvered sides

<6000 Btu/h 10.0 CEER ANSI/AHAM R

AC-1≥6000 Btu/h and <8000 Btu/h

10.0 CEER

≥8,000 Btu/h and <11,000 Btu/h

9.6 CEER

≥11,000 Btu/h and <14,000 Btu/h

9.5 CEER

New definition 2019 - Combined Energy Efficiency Ratio (CEER): a ratio of the total cooling one year divided by the total energy from active, standby, and off modes (see CCOPC for SI equivalent) as specified in 10 CFR 430.23.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

125

6.4.3.3.2 Setback—Changed in 2016

• Setup• Cooling

• Setback• Heating

CZ-2-8 55°F

90°FCZ-1b,2b,3b

2016—All zones at least 10°F below heating set point and at least 5°F above set point

2004–2013

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

126

6.4.3.3.5 Hotel/Motel Guest Rooms

Hotel/motel with over 50 guest rooms

Set Point Control –Unoccupied for 20minutes – reset 4°F up and down Unoccupied and unrented - >=80°F cooling and <=60°heating when unoccupied for 16 hours or 20 minutes with network control

Vent Control

Exhaust and OA supply will automatically be shut-down/off within 20 minutes of room being unoccupied. Humidity control is allowed

Captive Key Card

Captive key card system comply with these requirements. (Slot for room key near door)

New for 2016 Modified in 2019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

127

6.5.1.1.4 Dampers

Exhaust/relief, and outdoor air dampers shall meet the requirements of Section Table 6.4.3.4.3. Return dampers shall meet the requirements of motorized exhaust/relief dampers in Table 6.4.3.4.3.

Exceptions to 6.5.1.1.41. Exhaust/relief and outdoor air intake dampers on

systems intended to operate continuously.

Return dampers were changed to meet only the motorized requirements of the table and the exception was added for systems with 24/7 operation. Exception added for payback not for good operation.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

128

Table 6.4.3.4.3 Maximum Damper Leakage (HVAC Mandatory Section)

Table 6.4.3.4.3 Maximum Damper Leakagea,b, cfm per ft2 at 1.0 in. of water (I-P)

Climate Zone

Outdoor Air Intake Exhaust/Relief

Nonmotorizeda Motorized NonmotorizedcMotorized

0, 1, 2Any height 20 4 20 43Any height 20 10 20 104, 5B, 5CFewer than three stories 20d 10 20 10Three or more stories 20d 10 20d 105A, 6, 7, 8Fewer than three stories 20d 4 20 4Three or more stories 20d 4 20d 4

See notes for exceptions:

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

129

6.4.3.6 Humidification and Dehumidification Control – Modified 20196.4.3.6.1 DehumidificationHumidistatic controls shall not use mechanical cooling to reduce the humidity below the lower of a dew point of 55°F or relative humidity of 60% in the coldest zone served by the system.(Informative Note: Lower humidity is permitted when operating mechanical cooling for temperature control.)6.4.3.6.2 HumidificationHumidistatic controls shall not use fossil fuel or electricity to produce relative humidity above 30% in the warmest zone served by the system.6.4.3.6.3 Control InterlockWhere a zone is served by a system or systems with both humidification and dehumidification capability, means (such as limit switches, mechanical stops, or, for DDC systems, software programming) shall be provided capable of and configured to prevent simultaneous operation of humidification and dehumidification equipment.Exceptions for special spaces requiring close humidity control remain.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

130

6.4.3.9 Heated and Cooled 2016 Vestibules

Heating allowed only when the outdoor temperature is below 45ºF and with a maximum set point temperature of 60°F.Cooling minimum set point 85°F.Good exception for using transfer air.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

131

6.4.3.11 Chilled-Water Plant Monitoring

• New chilled-water plants shall measure the energy useand efficiency of the plant:– Water-cooled plants >1500 tons capacity for CZ5 through 8, 3C, 4C, and

>1000 tons in all other zones– Air-cooled plants >860 tons capacity for CZ5 through 8, 3C, 4C, and

>570 tons in all other zones

• The efficiency shall be calculated in kw/ton (COP)• 15 min data displayed graphically hour, day, month, and

year• Maintain a minimum of 36 months

New for 2016

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

132

6.4.3.12 Economizer Fault Detection and Diagnostics (FDD)

New for 2016

Air-cooled DX

systems

Sensors to monitor OA, SA,

RA

Display value of

each sensor

Status: Free

cooling available,

economizer enabled,

Compressor enabled, heating enabled,

Mixed-air low-limit

cycle active

System can initiate each

mode for testing

System reports to operators

Faults: Air sensor fault, economizer mode not

matching controls, damper not modulating,

excess OA

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

133

Misc. Changes to 6.4 New 2019

• 6.4.5 Walk- In Coolers and Freezers– m. a requirement for the doors to meet the undated requirements of

Tabels 6.8.1-18 thru 20.

• 6.4.7 Liquid to Liquid Heat Exchangers– The empty table for liquid to liquid heat exchangers in Section 6.8

has been removed and a reference to AHRI 400 Section 12 hasbeen added here.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

134

DOAS TERMs

New for 2016

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

135

6.8.1-15 DX-DOAS Units

New for 2016

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

136

6.8.1-16 DX-DOAS Units—2

New for 2016

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

137

PRESCRIPTIVE SECTION6.5

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

138

HVAC Prescriptive Requirements 6.5.2.1 Zone Reheat Limitation (with DDC-2013)• Deadband does

not exceed thelarger of

– 20% of designpeak airflow

– ASHRAE 62.1• Reheated air can

be 50% of designpeak airflow

• Air betweendeadband and fullheating or coolingis modulated

Updated 2019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

139

6.5.2.1 Zone Controls

1. The minimum primary outdoor airflow rate required to meetthe Simplified Procedure ventilation requirements of ASHRAEStandard 62.1 for the zone and is permitted to be theaverage airflow rate as allowed by ASHRAE Standard 62.1.

Eliminated a set minimum airflow and tied the airflow requirement to a new Simplified Procedure in ASHRAE 62.1

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

140

EXCEPTIONS: • WARM-UP OR SETBACK• LABS

6.5.2.1.1 Overhead Supply Air Temperatures Limited

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

141

Heating Control

6.5.2.5 Preheat coils

• Preheat coils must be off when mechanicalcooling or economizer is in operation

6.5.2.6 Ventilation Air Heating Control (New 2016)• Ventilation units operating with other heating and

cooling systems shall not supply air above 60°Fwhen building load or OA temperature indicate themajority of zones require cooling

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

142

6.5.3.1.2 Fan Motor Selection- Modified in 2019

• 1. For each fan less than 6 bhp, the selected fan motor shall be no largerthan the first available motor with a nameplate rating size greater than 1.5times the bhp.

• 2. For each fan 6 bhp and larger, the selected fan motor shall be no largerthan the first available motor with a nameplate rating greater than 1.3 timesthe bhp.

• The fan bhp must be indicated on the design documents to allow forcompliance verification by the building official.

• Exceptions to 6.5.3.1.2• 1. Motors equipped with electronic speed control devices to vary the fan

airflow as a function of load. • 2. Systems complying with Section 6.5.3.1.1, Option 1.• 3. Fans with motor nameplate horsepower of less than 1 hp.• 4. Fans with a fan nameplate electrical input power of less than 0.89 kW.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

143

6.5.3.1.3 Fan Efficiency –Modified in 2019

Each fan and fan array shall have a fan energy index (FEI) of 1.00 or higher. Each fan and fan array used for a variable-air-volume system that meets the requirements of Section 6.5.3.2.1 shall have an FEI of 0.95 or higher. The FEI for fan arrays shall be calculated in accordance with AMCA 208 Annex C.Exceptions to 6.5.3.1.31. Fans that are not embedded fans with a motor nameplate

horsepower of less than 1.0 hp (0.75 kW) or with a fannameplate electrical input power of less than 0.89 kW.

2. Embedded fans and fan arrays with a combined motornameplate horsepower of 5 hp or less or with a fan systemelectrical input power of 4.1 kW or less. (Continued)

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

144

Exceptions to 6.5.3.1.3 (continued)

3. Embedded fans that are part of equipment listed underSection 6.4.1.1.4. Embedded fans included in equipment bearing a third-party-certified seal for air or energy performance of theequipment package.5. Ceiling fans6. Fans used for moving gases at temperatures above 482°F.7. Fans used for operation in explosive atmospheres.8. Reversible fans used for tunnel ventilation.9. Fans outside the scope of AMCA 208.10. Fans that are intended to only operate during emergencyconditions.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

145

New Fan definitions added in 2019• ceiling fan: a nonportable (permanently installed) device suspended from a

ceiling or overhead structure for circulating air via the rotation of fan blades.• ceiling fan, large-diameter: a ceiling fan that is greater than or equal to 84.5

inches (2.15 m) in diameter.• fan, embedded: a fan that is part of a manufactured assembly where the

assembly includes functions other than air movement.• fan array: multiple fans in parallel between two plenum sections in an air

distribution system.• fan energy index (FEI): the ratio of the electric input power of a reference fan

to the electric input power of the actual fan as calculated per AMCA 208.• fan nameplate electrical input power: the nominal electrical input power

rating stamped on a fan assembly nameplate.• fan system electrical power: the sum of the fan electrical power of all fans

that are required to operate at fan system design conditions to supply airfrom the heating or cooling source to the conditioned spaces and/or return itto the source or exhaust it to the outdoors.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

146

Return and Relief Control

6.5.3.2.4 Return and Relief Fan ControlReturn and relief fans used to meet Section 6.5.1.1.5 shall comply with all of the following:

a. Relief air rate shall be controlled to maintain buildingpressure either directly, or indirectly through differentialsupply-return airflow tracking. Systems with constant-speedor multispeed supply fans shall also be allowed to control therelief system based on outdoor air damper position.

b. Fans shall have variable-speed control or other devices thatwill result in total return/relief fan system demand of no morethan 30% of total design power at 50% of total design fan flow.

New for 2016

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

147

Parallel-Flow FP-VAV New for 2016

6.5.3.4 Parallel-Flow Fan-Powered VAV Air Terminal ControlParallel-flow fan-powered VAV air terminals shall have automatic controlsconfigured toa. turn off the terminal fan except when space heating is required or if

required for ventilation;b. turn on the terminal fan as the first stage of heating before the heating

coil is activated; andc. during heating for warmup or setback temperature control, either

1. operate the terminal fan and heating coil without primary air or2. reverse the terminal damper logic and primary air.

.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

148

Temperature Reset Controls –Modified 2019

-SA

X

0.25

In CZ 0 THRU 3B, 3C AND 4 THROUGH 8.

<3000 CFM 2A<10,000 CFM

CZ 0 THRU 3A > 80% OA WITH ENERGY RECOVERY

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

149

6.5.3.7 Ventilation Design New for 2016The outdoor air design should be based on 62.1 or 170 or a standard or code.

The design must limit OA to no more than 135% of the calculated OA or

The design can return to the required OA with a single set point adjustment or

The system includes exhaust energy recovery (Section 6.5.6.1)

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

150

6.5.3.8 Occupied Standby Controls 2019Zones serving only room(s) that are required to have Automatic Partial OFF or Automatic Full OFF lighting controls per section 9.4.1.1, where the ASHRAE Standard 62.1 occupancy category permits ventilation air to be reduced to zero when the space is in occupied-standby mode, and when using the Ventilation Rate Procedure, shall meet the following within 5 minutes of all room(s) in that zone entering occupied-standby mode.

a. Active heating setpoint shall be setback at least 1°F, andb. Active cooling setpoint shall be setup at least 1°F, andc. All airflow supplied to the zone shall be shut -off whenever the space

temperature is between the active heating and cooling set pointsException to 6.5.3.8

1.Multiple zone systems without automatic zone flow control dampers

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

151

HVAC Prescriptive Section 6.5.4Hydronic System Design and Control

• 6.5.4.2 Variable flow required for systems• More than 3 control valves• 30% design wattage at 50% flow for pump sizes per Table 6.5.4.2• Modulate to <25% or minimum allowed by manufacturer• Controlled as a function of flow or pressure differential at end of system

with set point not more than 110% of critical circuit pressure drop andDDC set point reset

• Or with DDC a function of valve positionExceptions: Variable speed not required:• 50% of heat from electric boilers• On primary pumps in primary/secondary system• Coil pump for freeze protection or heat recovery coil

2016

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

152

Table 6.5.4.2 Pump Flow Control

New for 2016

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

153

6.5.4.7 Plant Delta-T

Chilled Water Coil Selection—Water-Side Delta-T minimum 15°F with leaving

water temperature minimum 57°FExceptions: 1.Too many

rows—air-side pressure drop

exceeding 0.70” –

2. Too small—less than5000 cfm

3. Constantvolume system

4. Coilsselected at maximum

delta-T allowed by chiller –

5. Passive coils

6. Enteringwater

temperature above 50°F –7. Entering airtemperaturebelow 65°F

New for 2016

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

154

6.5.5 Heat Rejection Equipment

Fans over 7.5 HP

Reduce to 2/3speed or less

Demand reduction to 30% wattage at

50% airflow

Automatically change speeds to

control leaving temperature

Above not required in Climate Zones 1

& 2, or for some condenser systems

Multicell towers run all the fans you can and all at the same

speed

Do not use centrifugal fans on open towers over 1100 gpm unless

ducted

Towers must turn down to handle the smallest pump or 50% design flow

5 HP

Modified in 2016 New Tables added in 2019

Tables 6.8.1-9 through 16 and 19 added

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

155

6.5.6 Energy Recovery(Table change 2016requirements modified 2019 see all 4 - 6.5.6 slides)

Many Exceptions, including any system that has less than 75% of the usable exhaust air discharge within 20 ft of each other

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

156

6.5.6 Energy Recovery

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

157

6.5.6.1 Energy Recovery – New 2019• 6.5.6.1.1 Nontransient dwelling units• Nontransient dwelling units shall be provided with outdoor air energy recovery

ventilation systems. For nontransient dwelling units, energy recovery systemsshall result in an enthalpy recovery ratio of at least 50% at cooling designcondition and at least 60% at heating design condition. The energy recoverysystem shall provide the required enthalpy recovery ratio at both heating andcooling design conditions, unless one mode is not required for the climate zoneby the exceptions below.

• Exceptions to 6.5.6.1.1:1. Nontransient dwelling units in Climate Zone 3C.2. Nontransient dwelling units with no more than 500 ft2 of conditioned

floor area in Climate Zone 0, 1, 2, 3, 4C, and 5C.3. Enthalpy recovery ratio requirements at heating design condition in

Climate Zones 0, 1, and 2.4. Enthalpy recovery ratio requirements at cooling design condition in

Climate Zones 4, 5, 6, 7, 8.

•© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

158

6.5.6.1.2 Spaces other than nontransientdwelling units – Changes for 2019• The energy recovery system shall provide the required enthalpy

recovery ratio at both heating and cooling design conditions,unless one mode is not required for the climate zone by theexceptions below.

3. Where more than 60% of the outdoor air heating energy is provided from site-recovered energy or site-solar energy in Climate Zones 5 through 8.4. Enthalpy recovery ratio requirements at heating design condition in Climate Zones0, 1, and 2.5. Enthalpy recovery ratio requirements at cooling design condition in Climate Zones3C, 4C, 5B, 5C, 6B, 7, and 8.6. Heating energy recovery for sSystems in Climate Zones 0 through 4 requiringdehumidification during heating mode that employ energy recovery and have aminimum SERR of 0.40.7. Indoor pool dehumidifiers meeting Section 6.5.6.4.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

159

6.5.6.3 Heat Recovery for Space Conditioning New 2019

Where heating water is used for space heating, a condenser heat recovery system shall be installed provided all of the following are true:a. The building is an acute inpatient hospital, where the building or portion ofa building is used on a 24-hour basis for the inpatient medical, obstetric, orsurgical care for patients.b. The total design chilled water capacity for the acute inpatient hospital,either air cooled or water cooled, required at cooling design conditionsexceeds 3,600,000 Btu/h (1,100 kW) of cooling. (300 tons)c. Simultaneous heating and cooling occurs above 60°F (16°C) outdoor airtemperature.The required heat recovery system shall have a cooling capacity that is atleast 7% of the total design chilled water capacity of the acute inpatienthospital at peak design conditions.

Exceptions to 6.5.6.31. Buildings that provide ≥ 60% of their reheat energy from on-siterenewable energy or site-recovered energy.2. Buildings in climate zones 5C, 6B, 7, & 8.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

160

6.5.6.4 Indoor Pool Dehumidifier Energy Recovery New 2019An indoor pool dehumidifier serving a natatorium with a heated indoor pool over 500 ft2 in size shall include one of the following:a. an exhaust air sensible energy recovery system with a sensible energy

recovery ratio of at least 50%,

b. a condenser heat recovery system capable of and configured to use100% of the heat generated through dehumidification to heat the poolwater when there is a pool water heating load, or

c. an exhaust air energy recovery system that results in an enthalpyrecovery ratio of at least 50%.

Exception to 6.5.6.4 –Natatoriums heated by on-site renewable energy or site recovered energy capable of and configured to provide at least 60% of the annual heating energy required.

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

161

6.5.7 Exhaust Systems

New for 2016

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

162

6.5.7 Exhaust Systems cont.

New for 2016

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

163

SERVICE WATER HEATINGSection 7:

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

164

SWH Section 7Compliance Path

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

165

Requirements for RecirculationSystems and Remote Heaters

Only test procedures changed in 2019

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

166

HVAC Section 6.3 Simplified Approach• Purpose

– To ease complexity and compliance burden for 80% of building permits

• Consistent with prescriptive requirements (the problem)

• In 2019 the requirements lists a thru s, not so simple

• Fits on two pages– Compliance form is one page

• 6.3.1 Limited to …– Buildings with one or two stories– Buildings less than 25,000 ft2

– Single-zone systems– Air-cooled or evaporatively cooled condenser

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

167

THANK YOU!

ANY QUESTIONS?Mack Wallace

[email protected]

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

168

Appendices: The following slides will not be

presented, but are “extra” slides included for the information and use

by the participants!

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

169

CBECS 2012 Breakdown of Energy Use

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

170

Building Electrical EUI – CBECS 2012

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

171

Comfort Chart

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

172

Comfort Chart

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

173

Comfort Chart

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

174

Comfort Chart

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

175

Comfort Chart

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

176

Climate Consultant: Temperature and Dew Point

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

177

Rules Used to Set Prescriptive Criteria

• Envelope prescriptiverequirements are based oneconomic optimization (LCC)

• Separate LCC analysis foreach envelope component

• Separate approaches havebeen used for:– Opaque– Fenestration

LCC Theory

0

5000

10000

15000

20000

25000

30000

35000

40000

45000

50000

0 5 10 15 20 25 30 35 40 45 50

Energy Conservation Measure

LCC

($)

First CostsEnergy CostsLCC

Fenestration

0

10000

20000

30000

40000

50000

60000

70000

80000

90000

0 10 20 30 40 50 60 70 80 90 100 110

Construction Option

Dol

lars First Costs

EnergyLCC

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

178

Appendix G:Class Exercise – Show Compliance

• A mixed use building in Chicago(CZ-5A)• Area = 50,000 ft2• Retail = 10,000 ft2• Apartments = 40,000 ft2• Proposed building performance = $32,000/year• BBP = $49,000/year• BBREC = $34,000/year• BBUEC = $15,000/year

Thanks to : Michael Rosenberg PNNL - Jun 2016 ASHRAE Journal

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

179

Appendix G: 2010 - BDFs for your use

Thanks to : Michael Rosenberg PNNL - Jun 2016 ASHRAE Journal

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

180

Appendix G: 2013 - BDFs for your use

Thanks to : Michael Rosenberg PNNL - Jun 2016 ASHRAE Journal

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

181

U-Factor Compliance CalculationAbove-grade Wall Example

An example U-Factor calculation is shown for a steel-framed wall, using the effective R-Value Method.

Layer R-Value Data SourceExt. air film 0.17 § A9.4.14 in. face brick 0.25 ASHRAE HB0.75 in. air space 0.90 Tables A9.4A

and A9.4BRigid insulation 7.00 Mfgr’s dataFraming/cavity 9.60 Table A9.2B0.625 in. gyp. bd. 0.56 Table A9.4BInt. air film 0.68 § A9.4.1

Total R-Value 19.16U-Factor 0.052

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

182

HC Calculation Above-grade Wall Example

The HC is the sum of the density times the specific heat times the thickness for each layer of the wall. The calculation can be structured in tabular form as shown below.

Item Weight (lb/ft 2 )

Fraction of Wall

Specific Heat (Btu/lb °F)

HC (Btu/ft 2°F)

8" Partially Grouted CMU(105 lb/ft 3 )

47.00 1.00 0.20 9.40

2X4 Wood Studs 9.30 0.22 0.33 0.46 R-11 Batt 0.25 0.78 0.30 0.06 5/8" gypsum board 2.60 1.00 0.26 0.68 Total 10.60

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

183

Lighting Functional Testing:Occupancy Sensors (1)

a. Occupant Sensors1. Certify that the sensor has been located and aimed in

accordance with manufacturer recommendations.

2. For projects with up to seven (7) occupancy sensors, alloccupancy sensors shall be tested.

3. For projects with more than seven (7) occupancy sensors,testing shall be done for each unique combination ofsensor type and space geometry.

Expanded, 2013

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

184

Functional Testing:Automatic Time Switches (1)

1. Confirm that the automatic time-switch control isprogrammed with appropriate schedules for weekday,weekend and holiday (as applicable).

2. Document for the owner the automatic time-switchprogramming, including weekday, weekend and holidayschedules, as well as all setup and preference programsettings.

3. Verify that correct time and date are properly set in thetime switch.

4. Verify that any battery backup (as applicable) is installedand energized.

Expanded,2013

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

185

Functional Testing:Automatic Time Switches (2)

5. Verify that the override time limit is set to no more than two (2)hours.

6. Simulate occupied condition. Verify and document thefollowing:a) All lights can be turned on and off by their respective area

control switch.b) The switch only operates lighting in the enclosed space in which

the switch is located.

7. Simulate unoccupied condition. Verify and document thefollowing:a) All nonexempt lighting turns off.b) Manual override switch allows only the lights in the enclosed

space where the override switch is located to turn on or remainon until the next scheduled shut-off occurs.

Expanded,2013

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

186

Functional Testing:Who Can Do…

Individuals responsible for functional testing shall:

• Not be directly involved in either the design orconstruction of the project

• Provide documentation certifying that the installedlighting controls meet or exceed all documentedperformance criteria.

Expanded, 2013

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

187

Example ASHRAE 62.1 Simplified

52’

50’

Conf Break

Office

1400 CFM

180 CFM 300 CFM

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

188

ASHRAE 62.1 Simplified Procedure

• Breakroom – 10 People –300 Sq Ft – Design CFM300

• Conference Room – 12people -300 Sq Ft –Design CFM 180

• Open Office – 25 Peopleincluding hotel space –2000 Sq Ft – Design CFM1400

• First we calculatethe people diversity,D. We know that thetotal amount ofpeople that will be inthe space at anyone time is 23 = Ps.

• Sum of Zones = 15+ 15 + 25 = 55

• D= 23/47 = 0.49

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

189

Calculation 62.1 Simplified

• Breakroom - 5cfm/person 0.12CFM/SF

• Conf Rm – 5CFM/person 0.06CFM/SF

• Office – 5cfm/person 0.06CFM/SF

• Next calculate the Uncorrectedoutdoor air intake Vou =D∑(10x5)+(300x0.12)+(12x5)+(300x0.06)+(25x5)+(2000x0.06)

• Vou=D(86+78+245)=Dx409CFM• Vou = 0.49x(409CFM)= 201• D<0.60• Ev = 0.88xD+0.22 = 0.65• Vot=Vou/Ev=201/0.65=310CFM

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

190

The 62.1 required minimum Zone airflow (New)

• Vpz-min = minimum primary airflow = Voz x 1.5• Voz = Vbz/Ez• The Ez is either 1 or 0.8 see next slide.• Vbz for Breakroom = 86• Vbz for Conf. Rm = 78• Vbz for Office = 245• Min primary air supply at Ez = 1, could be 0.8(next slide)• Breakroom = 129• Conf. Rm = 117• Office = 368

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

191

Evaluation and Certificate

ASHRAE values your comments about this course. You willreceive your Certificate of Attendance when you finish the onlinecourse evaluation form at this URL:https://www.ashrae.org/2020may26

Be sure to add your appropriate license numbers.

If you have any questions about ASHRAE Certificates, pleasecontact Kelly Arnold, Coordinator Professional Development, [email protected] you have any questions about ASHRAE courses, pleasecontact Tiffany Cox, Course Administrator, [email protected].

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

192

Explore ASHRAE Learning Institute Courses

https://www.ashrae.org/instructor-led-courses

Find a Topic that Fits You: Commissioning Energy Efficiency Environmental Quality HVAC&R Applications Standards and Guidelines

See all the ways to learn and grow with ASHRAE at: https://www.ashrae.org/professional-development/learning-portal

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.

193

ASHRAE Certification

Visit www.ashrae.org/certification to learn more:

More than 3,000 certifications earned to-dateElevate your reputation among peers, in the workplace and among clientsNEW! Digital Badging:

– Embedded metadata uniquely linked to you– Shareable in electronic media, including LinkedIn and email– Instant recognition, with real-time, third-part verification

© 2020 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.