Sanitary Tee

Embed Size (px)

DESCRIPTION

Sanitary Tee

Citation preview

  • While running departments and teaching classes the following questions have been asked and many times theanswer seems confusing. The following is an interpretation and/or explanation of the 2009 I codes and 2008NEC and as always it is up to the building official to interpret the intent of the code.

    John England has been teaching inspectors and building officials for over 16 years. For further information on this code question email [email protected]. Visit our website at https://ibcode.com/Downloads_Articles.html for an archive of code questions.

    Question: A sanitary (drainage) tee can only be installed

    A. Horizontal to Horizontal B. Vertical to Horizontal C. Horizontal to VerticalD. Vertical to Vertical

    Code SectionsPlumbing Code 706.3 Table 706.3 IRC P3005.1 Table 3005.1Answer:OneofthemostoftennotedcodeviolationsistheimproperplacementofSanitaryTee's,Wye&1/8Bendsand Combo's.

    Asanitaryteemaynotbeinstalledonitsbackwiththesideopeninginaverticalposition.Thereasonisthatthewastewillhitthebottomofthehorizontalpipeandsplashbackupstreaminthehorizontalpipe.Thiscanleadtosolidsbeingdepositedontheupstreamsidethatwouldcauseaclogintheline.WhenconnectingaverticaldroptoahorizontalrunyoumustuseeitheraWye&1/8bend(45deg),oraSanitarycombo,(AcomboisacombinationWye&1/8bendreadymadeinonefitting).Thepurposeistoformalongradiusbendtoinsurethewasteisdirectedinthedownstreamdirectionasitentersthehorizontalrun.

    Whenconnectingahorizontalrun,suchasawastearmtoaventstack or vertical riser, you must use a SANITARY TEE. The use of acombo in this position would put the vent stack inlet well belowthe horizontal pipe and causes a restriction that prevents vent airfrom getting into the horizontal line.

    NOTE: This only applies to the drainage system - Sanitary Tees are permitted in the venting system.

    Code Questionof the Week

    August 24, 2010

    Slide Number 1