22
2013 Electrical Inspection using Infrared Thermography, 111 Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov, Level 3 Thermographer, ME, CET

Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

2013

Electrical Inspection using Infrared Thermography, 111 Something Dr. TJ

[SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov, Level 3 Thermographer, ME, CET

Page 2: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

1

INTRODUCTION

The purpose of this inspection was to identify any thermal patterns and temperatures that may indicate

electrical wear or failure. This inspection was completed utilizing the “FLIR” S660 handheld thermal

imaging system.

Infrared inspections are used to locate areas in need of maintenance. These anomalies can be located with

infrared imaging systems because of their increased or decreased temperature. The temperature rise of a

detected anomaly is measured and then the I.R. and the digital reference images are taken for

documentation. The report may contain references to demonstrate the appropriate working condition of

some equipment. Any anomalies are labeled as faults within the report.

The report is limited to the size and extent of inspection at the time it was conducted and as such is not

meant to be a warranty nor guarantee. It does not relieve concerned parties from their obligations.

Factors such as environmental and consumption fluctuations make it impossible to accurately predict

when an anomaly will result in a system failure. We suggest preventative maintenance to ensure

uninterrupted functioning of all electrical apparatus and motors at the above location.

PRIORITY Chart

HIGH Repair Immediately

MEDIUM Repair within 30 Days

LOW Repair within 6 months

REFERENCE For reference only

NOTE Visual anomalies, Electrical code violations

ACTION ITEMS SUMMARY

Designation Fault Action Pg.

Splitter #4 Misaligned B phase contacts Clean, lube, exercise, torque 2

P-1 Faulty Fuse Replace all 3 fuses, service fds 3

DS-A Loose connection on fuse clips Clean, lube, torque 4

LP-3B Misaligned B phase contacts Clean, exercise, lube, torque 5

Transformer ITA Misaligned C phase contacts Clean, exercise, lube, torque 6

Note Debris in lower level Mech Rm. Keep Electrical Rooms clean 7

Page 3: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

2

FAULT #1

PRIORITY LOCATION EQUIPMENT

Medium Main Electrical Room 100 A FUSED DISCONNECT SWITCH

A r1

32.9

50.1 °C

35

40

45

50

PARAMETERS ANALYSIS AND RECOMMENDATION

Date 06/06/2013

Filename IR_2648.jpg

Max Temperature 57.0 °C

Min Temperature 29.1 °C

Ar1 Max. Temperature 57.0 °C

Atmospheric

Temperature

21.2 °C

Object Distance 1.6 m

Image Camera Type ThermaCam SC660

Wes

Emissivity 0.91

Equipment: ITE, V7E-3633 100 A FUSED DISCONNECT SWITCH 120/208 VAC 3ph. 60 Hz

Designation: Splitter #4

Loads A:34a B:35a C:33a

Fault Analysis: Thermal variance detected across B phase line side on main contacts migrating to switch mechanism, fuse clip and conductor.

Recommendation: Service 100 Amp FUSED DISCONNECT SWITCH. Clean Lubricate, exercise, torque as required and rescan.

Page 4: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

3

FAULT #2

PRIORITY LOCATION EQUIPMENT

LOW Lower level mechanical room 30A FUSED DISCONNECT SWITCH

A r1

35.0

86.0 °C

40

60

80

PARAMETERS ANALYSIS AND RECOMMENDATION

Date 06/06/2013

Filename IR_2650.jpg

Max Temperature 90.1 °C

Min Temperature 24.2 °C

Ar1 Max. Temperature 90.1 °C

Atmospheric

Temperature

21.2 °C

Object Distance 1.6 m

Image Camera Type ThermaCam SC660

Wes

Emissivity 0.91

Equipment: Siemens ID361 30 amp FUSED DISCONNECT SWITCH, 600 VAC 3ph. 60 Hz

Designation: P-1

Loads A:13 a B:14 a C:15 a

Fault Analysis: Thermal variance detected across B Phase fuse barrel.

Recommendation: Service 30 Amp FUSED DISCONNECT SWITCH and replace fuses.

Page 5: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

4

FAULT #3

PRIORITY LOCATION EQUIPMENT

Low Library Server Room 100A FUSED DISCONNECT SWITCH

A r1

29.9

57.9 °C

40

50

PARAMETERS ANALYSIS AND RECOMMENDATION

Date 06/06/2013

Filename IR_2657.jpg

Max Temperature 64.2 °C

Min Temperature 25.8 °C

Ar1 Max. Temperature 64.2 °C

Atmospheric

Temperature

21.2 °C

Object Distance 1.6 m

Image Camera Type ThermaCam SC660

Wes

Emissivity 0.91

Equipment: FPE-1136SN 100 amp FUSED DISCONNECT SWITCH, 600 VAC 3ph. 60 Hz

Designation: DS-A

Loads A:19a B:24a C:35a

Fault Analysis: Thermal variance detected across phases A and C line side on fuse clips migrating to main contacts

Recommendation: Service 100 Amp FUSED DISCONNECT SWITCH. Clean, lubricate, exercise n torque. All 3 fuses should be uniform. Rescan.

Page 6: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

5

FAULT #4

PRIORITY LOCATION EQUIPMENT

Low 2nd

Floor Electrical room 100A FUSED DISCONNECT SWITCH

A r1

29.3

38.5 °C

30

35

PARAMETERS ANALYSIS AND RECOMMENDATION

Date 06/06/2013

Filename IR_2659.jpg

Max Temperature 39.8 °C

Min Temperature 25.3 °C

Ar1 Max.

Temperature

39.8 °C

Atmospheric

Temperature

21.2 °C

Object Distance 1.6 m

Image Camera Type ThermaCam SC660

Wes

Emissivity 0.91

Equipment: CEB, A3036A 100 amp FUSED DISCONNECT SWITCH, 600 VAC , 3ph., 60 Hz

Designation: LP-3B

Loads A:20a B:17a C:25a

Fault Analysis: Thermal variance detected across phase B line side on main contacts migrating to switch mechanism, fuse barrel and conductor

Recommendation: Service 100 Amp FUSED DISCONNECT SWITCH. Clean, lubricate, exercise and torque. Rescan.

Page 7: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

6

FAULT #5

PRIORITY LOCATION EQUIPMENT

Medium 1st

Floor A, Music Room 118 100 A FUSED DISCONNECT SWITCH

A r1

27.0

60.5 °C

30

40

50

60

PARAMETERS ANALYSIS AND RECOMMENDATION

Date 06/06/2013

Filename IR_2662.jpg

Max Temperature 63.8 °C

Min Temperature 23.7 °C

Ar1 Max.

Temperature

63.8 °C

Atmospheric

Temperature

21.2 °C

Object Distance 1.6 m

Image Camera Type ThermaCam SC660

Wes

Emissivity 0.91

Equipment: CEB,A3036A 100 amp FUSED DISCONNECT SWITCH, 600 VAC 3ph. 60 Hz

Designation: Transformer ITA

Loads A:8a B:9a C:8a

Fault Analysis: Thermal variance detected across C phase line side on main contacts, migrating to switch mechanism, fuse barrel and conductor

Recommendation: Service 100 Amp FUSED DISCONNECT SWITCH. Clean lubricate, exercise and torque. Rescan

Page 8: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

7

Notes

Note #1

Main Electrical Room, Main Switchboard

600 amp FUSED DISCONNECT SWITCH Designation: Office Building Riser

Rug and brush were left inside switch enclosure IRIS Tech removed debris. (no action required)

Note #2

Lower level Mechanical Room

Refer to:

Ontario Electrical Safety Code Rule 2-316

Working Space around Electrical Equipment

Ontario Electrical Safety Code Rule 2-316 Flammable Material near electrical equipment

Action Required: Remove all debris from electrical room.

Page 9: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

8

Equipment List

Location Units Equipment Inspected Condition Priority Level

Image #

1 floor main electrical room

1 1600 A

air circuit breaker

Yes Satisfactory

1 switch board consisting of:

Yes Satisfactory

3 600 A fused disconnect switch

Yes note 1 None DC 2647

3 400 A fused disconnect switch

Yes Satisfactory

8 200 A fused disconnect switch

Yes Satisfactory

6 100 A

fused disconnect switch

Yes Fault #1 Medium IR 2648, DC 2649

1 300 A transfer switch Yes Satisfactory

1 25 KVA

dry type transformer

Yes Satisfactory

Page 10: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

9

1 30 KVA

dry type transformer

Yes Satisfactory

1 300 KVA

dry type transformer

Yes Satisfactory

3 splitter Yes Satisfactory

2 contactor Yes Satisfactory

3 distribution panel

Yes Satisfactory

4 200 A fused disconnect switch

Yes Satisfactory

1 100 fused disconnect switch

Yes Satisfactory

5 30 A fused disconnect switch

Yes Satisfactory

1 floor mechanical room

5 splitter Yes note 2 None DC 2652, 2653, 2654

2 chillers Yes Satisfactory

Page 11: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

10

2 400 A fused disconnect switch

Yes Satisfactory

1 100 A fused disconnect switch

Yes Satisfactory

3 60 A fused disconnect switch

Yes Satisfactory

12 30 A fused disconnect switch

Yes Fault #2 Low IR 2650, DC 2651

2 control panel Yes Satisfactory

1 combo motor control

Yes Satisfactory

2 1.5 HP

motor Yes Satisfactory

1 7.5 HP

motor Yes Satisfactory

6 15 HP

motor Yes Satisfactory

penthouse elevator room

2 control panel Yes Satisfactory

1 splitter Yes Satisfactory

Page 12: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

11

2 100 A fused disconnect switch

Yes Satisfactory

3 30 A fused disconnect switch

Yes Satisfactory

penthouse mechanical room

1 10 KVA

dry type transformer

Yes Satisfactory

1 splitter Yes Satisfactory

2 control panel Yes Satisfactory

2 combo motor control

Yes Satisfactory

1 distribution panel

Yes Satisfactory

1 100 A fused disconnect switch

Yes Satisfactory

1 30 A fused disconnect switch

Yes Satisfactory

penthouse mechanical room

10 combo motor control

Yes Satisfactory

Page 13: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

12

1 60 A fused disconnect switch

Yes Satisfactory

3 7.5 HP

motor Yes Satisfactory

1 5 HP motor Yes Satisfactory

1 0.33 HP

motor Yes Satisfactory

3 2 HP motor Yes Satisfactory

penthouse MUA P-12 room

2 splitter Yes Satisfactory

5 combo motor control

Yes Satisfactory

penthouse cooling tower

1 60 A fused disconnect switch

Yes Satisfactory

penthouse MUA room

1 5 KVA

dry type transformer

Yes Satisfactory

1 15 KVA

dry type transformer

Yes Satisfactory

4 distribution panel

Yes Satisfactory

Page 14: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

13

3 splitter Yes Satisfactory

10 combo motor control

Yes Satisfactory

1 starters Yes Satisfactory

lower level B elevator lobby

1 distribution panel

Yes Satisfactory

lower level B by mechanical room

3 distribution panel

Yes Satisfactory

lower level B east entrance

1 distribution panel

Yes Satisfactory

1 floor B elevator lobby

1 distribution panel

Yes Satisfactory

1 floor B by 106 1 distribution panel

Yes Satisfactory

1 floor B by telephone room

1 distribution panel

Yes Satisfactory

1 floor B main lobby

1 distribution panel

Yes Satisfactory

1 floor B by theatre office

1 distribution panel

Yes Satisfactory

1 floor A by janitor 1 distribution panel

Yes Satisfactory

Page 15: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

14

3 floor A by stairwell

1 distribution panel

Yes Satisfactory

2 floor B elevator lobby

1 distribution panel

Yes Satisfactory

3 floor B elevator lobby

2 distribution panel

Yes Satisfactory

3 floor B by 303 1 distribution panel

Yes Satisfactory

lower level B theatre

1 distribution panel

Yes Satisfactory

lower level B library

2 distribution panel

Yes Satisfactory

lower 1 floor B library

2 distribution panel

Yes Satisfactory

lower 2 floor B library

2 distribution panel

Yes Satisfactory

lower 1 floor B library server room

1 splitter Yes Satisfactory

2 distribution panel

Yes Satisfactory

1 100 A

fused disconnect switch

Yes Fault #3 Low IR 2657, DC 2658

Page 16: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

15

4 30 A fused disconnect switch

Yes Satisfactory

1 motor control Yes Satisfactory

1 floor B theatre electrical room

1 150 KVA

dry type transformer

Yes Satisfactory

2 splitter Yes Satisfactory

1 400 A fused disconnect switch

Yes Satisfactory

1 200 A fused disconnect switch

Yes Satisfactory

1 100 A fused disconnect switch

Yes Satisfactory

3 30 A fused disconnect switch

Yes Satisfactory

1 floor B electrical room

3 200 A fused disconnect switch

Yes Satisfactory

3 100 A fused disconnect switch

Yes Satisfactory

Page 17: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

16

1 60 A fused disconnect switch

Yes Satisfactory

2 splitter Yes Satisfactory

1 75 KVA

dry type transformer

Yes Satisfactory

1 floor child care 2 distribution panel

Yes Satisfactory

3 floor B electrical room

1 15 KVA

dry type transformer

Yes Satisfactory

1 30 A fused disconnect switch

Yes Satisfactory

2 floor B electrical room

1 75 KVA

dry type transformer

Yes Satisfactory

1 30 KVA

fused disconnect switch

Yes Satisfactory

1 9 KVA

fused disconnect switch

Yes Satisfactory

2 splitter Yes Satisfactory

Page 18: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

17

3 distribution panel

Yes Satisfactory

2 200 A fused disconnect switch

Yes Satisfactory

4 100 A

fused disconnect switch

Yes Fault #4 Low IR 2659, DC 2660

2 60 A fused disconnect switch

Yes Satisfactory

1 30 A fused disconnect switch

Yes Satisfactory

2 floor City hallway 2 distribution panel

Yes Satisfactory

3 floor B IT room 1 30 A fused disconnect switch

Yes Satisfactory

lower level B elevator room

1 100 A fused disconnect switch

Yes Satisfactory

1 30 A fused disconnect switch

Yes Satisfactory

lower level A 019 electrical room

1 100 A fused disconnect

Yes Satisfactory

Page 19: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

18

switch

1 30 A fused disconnect switch

Yes Satisfactory

3 60 A fused disconnect switch

Yes Satisfactory

1 15 KVA

dry type transformer

Yes Satisfactory

1 75 KVA

dry type transformer

Yes Satisfactory

1 splitter Yes Satisfactory

1 distribution panel

Yes Satisfactory

lower level A 019 electrical room

1 distribution panel

Yes Satisfactory

lower level B air duct room

4 combo motor control

Yes Satisfactory

lower level A elevator room

2 100 A fused disconnect switch

Yes Satisfactory

2 30 A fused disconnect switch

Yes Satisfactory

Page 20: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

19

1 splitter Yes Satisfactory

lower level A 021 room

1 splitter Yes Satisfactory

2 60 A fused disconnect switch

Yes Satisfactory

6 30 A fused disconnect switch

Yes Satisfactory

1 contactor Yes Satisfactory

1 floor A 118 musical room

2 splitters Yes Satisfactory

2 distribution panel

Yes Satisfactory

1 75 KVA

dry type transformer

Yes Satisfactory

1 200 A fused disconnect switch

Yes Satisfactory

4 100 A

fused disconnect switch

Yes Fault #5 Medium IR 2662, DC 2663

Page 21: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

20

3 60 A fused disconnect switch

Yes Satisfactory

2 floor A 210 room hallway

1 distribution panel

Yes Satisfactory

2 floor A 210 room electrical room

1 75 KVA

dry type transformer

Yes Satisfactory

1 distribution panel

Yes Satisfactory

1 splitter Yes Satisfactory

1 200 A fused disconnect switch

Yes Satisfactory

2 100 A fused disconnect switch

Yes Satisfactory

5 60 A fused disconnect switch

Yes Satisfactory

3 floor A 310 room electrical closet

1 splitter Yes Satisfactory

1 distribution panel

Yes Satisfactory

2 100 A fused disconnect switch

Yes Satisfactory

Page 22: Sample Report 111 Something Dr. - Infrared Thermography … · 2014. 4. 7. · Thermography, 111 2013 using Infrared Something Dr. TJ [SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov,

Infrared Imaging Solutions Inc 1-877-526-IRIS

21

3 60 A fused disconnect switch

Yes Satisfactory

Lower level tractor room

1 60 A fused disconnect switch

Yes Satisfactory

Lower level compressor room

1 15 KVA

dry type transformer

Yes Satisfactory

1 distribution panel

Yes Satisfactory

1 splitter Yes Satisfactory

1 control panel Yes Satisfactory

3 30 A fused disconnect switch

Yes Satisfactory

Lower level sump pump room

1 100 A fused disconnect switch

Yes Satisfactory

1 distribution panel

Yes Satisfactory