SAMPLE DRAWING
SINGLE LINE DRAWING FDR LARGE DG'SWITH PRIMARY LINE PROTECTION
REQUIRED PROTECTION
DEV2527324650/51V50/51N59678187B87T50/51
FUNCTIONSYNCH CHECKUNDER VOLTAGEDIRECTIONAL POWER
NEG SEQUENCE OCINST & TD OC VOLT RES INST & TD OC GROUNDOVER VOLTAGE DIRECTIONAL DCOVER/UNDER FREQBUS DIFFERENTIALTRANS DIFFERENTIAL
INST. & TIME O.C.
GENERATOR PROTECTIONREQUIREDOVER/UNDER VOLTAGE OVER/UNDER FREQUENCY NEGATIVE SEQUENCE REVERSE POWERVOLTAGE RESTRAINT OVER CURRENT LOSS OF EXCITATION
RECOMMENDED
GROUND PROTECTION DIFFERENTIAL PROTECTION
TWO MICROPROCESSOR RELAYS MAY BE USED. IF UNE MICROPROCESSOR RELAY IS USED, THE RELAY ALARM MUST TRIP THE BREAKER.
SAMPLE DRAWING
SINGLE LINE DRAWING FOR DG'S WITH SECONDARY LINE PROTECTION
REQUIRED PROTECTION
DEV25273256/51V50/51N5967468150/51V87B87T
FUNCTIONSYNCH CHECKUNDER VOLTAGE
DIRECTIONAL POWER INST & TD OC VOLT RES INST & TD OC GROUNDOVER VOLTAGEDIRECTIONAL OCNEG SEQUENCE OC OVER/UNDER FREQ INST & TD OCBUS DIFFERENTIAL TRANS DIFFERENTIAL
a
1
**ISOLATION TRANSFORMER MAY NOT BE REQUIRED IF :A) HARMONIC REQUIRMENTS ARE MET AND TESTED ANDB) NEUTRAL REATORS PROVIDE EFFECTIVELY
GROUNDED SYSTEM ANDc) FAULTS ON THE LIPA SYSTEM CAN BE
SELECTIVELY DETECTED.
TWO MICROPROCCESSOR RELAYS MAY BE USED IF ONE MICROPROCCESSOR RELAY IS USED, THE RELAY ALARM TRIP THE BREAKER.
GENERATOR PROTECTIONREQUIRED
OVER/UNDER VOLTAGE OVER/UNDER FREQUENCY NEGATIVE SEQUENCE REVERSE POWERVOLTAGE RESTRAINT OVER CURRENT LOSS OF EXCITATIONRECOMMENDED
GROUND PROTECTION DIFFERENTIAL PROTECTION