53
Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for any particular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document. Calculation Report Title Sample Calculation Flyer Project Cableizer Flyer 2019 Description Sample calculation to show various kind of cable types in different possible arrangements, with different frequencies, number of phases, backfills, in ducts plus a heat source and sink. Created 2019-08-15 12:20 Arrangement Arrangement type Buried cables Activated options None Active systems A, B, C, D, E, F, G, H, I Statistics Number of iterations of the solver N calc 37 Sum of currents from all systems I sum A 2555.9 Sum of average conductor temperatures from all systems θ sum °C 401.5 Number of overheated electrical systems NΔθ sum - 0 Sum of losses from all systems W sum W/m 177.2

Sample Calculation Flyer - Cableizer

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Sample Calculation Flyer - Cableizer

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Calculation Report

Title Sample Calculation FlyerProject Cableizer Flyer 2019Description Sample calculation to show various kind of cable types in different possible

arrangements, with different frequencies, number of phases, backfills, in ducts plusa heat source and sink.

Created 2019-08-15 12:20

ArrangementArrangement type Buried cables

Activated options None

Active systems A, B, C, D, E, F, G, H, I

Statistics

Number of iterations of the solver Ncalc 37

Sum of currents from all systems Isum A 2555.9

Sum of average conductor temperatures from all systems θsum °C 401.5

Number of overheated electrical systems NΔθsum - 0

Sum of losses from all systems Wsum W/m 177.2

Page 2: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 2

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Systems

Following systems are active in the arrangement:

System Object Current Ic max Temp. θc Losses Wsys

System A N2XS(FL)2Y 630Cu/50RCu mm2 110/64kV 500.0 A 62.8 °C 57.2 W/m

System B N2XS(FL)2Y 630Cu/50RCu mm2 110/64kV 450.0 A 56.2 °C 22.6 W/m

System C N2XS(FL)2Y 630Cu/50RCu mm2 110/64kV 800.0 A 66.6 °C 43.4 W/m

System D N2XS2Y 240Cu/25RCu mm2 20/12kV 240.0 A 50.3 °C 15.6 W/m

System E 33kV, XKDT-FT 3x150 mm2 RM35 200.0 A 64.1 °C 19.0 W/m

System F SOLARpower Alu-ATA 1x240/31 2 x 182.9(365.8)

60.0 °C 19.4 W/m

System G FO Rampion 0.1 A 47.6 °C 0.0 W/m

System H Heat sink 15.2 °C -40.0 W/m

System I Heat source 36.4 °C 40.0 W/m

Objects

Following objects are used:

- 33kV, XKDT-FT 3x150 mm2 RM35- N2XS(FL)2Y 630Cu/50RCu mm2 110/64kV- SOLARpower Alu-ATA 1x240/31- FO Rampion- N2XS2Y 240Cu/25RCu mm2 20/12kV

AmbientAmbient temperature θa °C 15.0

Thermal resistivity of soil ρ4 K.m/W 1.0

BackfillCalculation method acc. IEC 60287-2-1 ed2.0

Backfill Area 1

Thermal resistivity backfill ρb K.m/W 0.8

Horizontal center of backfill xb mm -500.0

Vertical center of backfill Lb mm 1000.0

Height of the backfill hb mm 400.0

Width of the backfill wb mm 600.0

Geometric factor for backfill Gb 2.0478

Equivalent radius of backfill rb mm 253.82

Backfill Area 2

Thermal resistivity backfill ρb K.m/W 0.8

Horizontal center of backfill xb mm 1000.0

Vertical center of backfill Lb mm 1230.0

Diameter of the backfill db mm 450.0

Page 3: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 3

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Geometric factor for backfill Gb 2.3833

Equivalent radius of backfill rb mm 225.0

Approximate temperature field

Page 4: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 4

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

System A (High voltage cable)

AmpacityName of cable N2XS(FL)2Y 630Cu/50RCu mm2 110/64kV

Permissible current rating Ic A 500.0

Operating voltage Uo kV 110.0

System frequency f Hz 50.0

Number of sources in system Nc 3

Number of conductors combined ncc 1

LoadContinuous load LF p.u. 1.0

TemperaturesTemperature of conductor θc °C 1: 62.8 | 2: 53.3 | 3: 57.6

Temperature of screen/sheath θs °C 1: 58.2 | 2: 48.9 | 3: 53.1

External temperature of the object θe °C 1: 56.9 | 2: 48.1 | 3: 52.0

Duct

Mean temperature of the medium in the duct θdm °C 1: 56.4 | 2: 47.7 | 3: 51.5

Temperature of duct inner wall θdi °C 1: 55.8 | 2: 47.4 | 3: 51.1

Temperature of duct outer wall θde °C 1: 54.9 | 2: 46.8 | 3: 50.3

Temperature rises

Temperature rise of conductor Δθc K 1: 37.4 | 2: 27.8 | 3: 33.3

Temperature rise by dielectric losses Δθd K 1: 0.4 | 2: 0.4 | 3: 0.4

Temperature rise by other buried objects Δθp K 1: 10.4 | 2: 10.6 | 3: 9.3

Critical soil temperature rise Δθx K 0.0

LossesOhmic

Conductor losses Wc W/m 1: 8.924 | 2: 8.678 | 3: 8.789

Screen and sheath losses Ws W/m 1: 13.966 | 2: 5.693 | 3: 10.438

Ohmic losses per phase WI W/m 1: 22.890 | 2: 14.372 | 3: 19.228

Page 5: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 5

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Dielectric

Dielectric losses Wd W/m 1: 0.235 | 2: 0.235 | 3: 0.235

Total

Total losses per phase Wt W/m 1: 23.125 | 2: 14.606 | 3: 19.462

Total losses per object Wtot W/m 1: 23.125 | 2: 14.606 | 3: 19.462

Total losses of the system Wsys W/m 57.193

ArrangementMaterial of duct pipe Md Plastic duct made of PE (Polyethylene)

Inside / outside diameter of duct Did/Dod mm 140.0 / 150.0

Equivalent diameter of a group of cables Deq mm 85.0

Thermal resistivity of duct material ρd K.m/W 3.500

Thermal resistivity of bentonite filling ρdfillK.m/W 0.700

Specific heat capacity of duct material σd J/K.m³ 2400000.0

Absorption coefficient of solar radiation σsun 0.4

Center position of duct 1 x1 / y1 mm 920.0 / 1150.0

Center position of duct 2 x2 / y2 mm 920.0 / 1310.0

Center position of duct 3 x3 / y3 mm 1080.0 / 1310.0

Separation of conductors in a system sc mm 160.00

Separation of cables sc2 mm 179.6

Depth of laying of sources Lc mm 1: 1150.0 | 2: 1310.0 | 3: 1310.0

Substitution coefficient u u 1: 15.333 | 2: 17.467 | 3: 17.467

Thermal ResistancesThermal resistance to ambient T4μ K.m/W 1: 1.275 | 2: 1.454 | 3: 1.336

Thermal resistance of medium in the duct T4i K.m/W 0.048

Thermal resistance of the duct wall T4ii K.m/W 0.038

Correction of thermal resistance for backfill T4db K.m/W 1: 0.188 | 2: 0.297 | 3: 0.223

Number of loaded objects in backfill Nb 1: 2.47 | 2: 3.92 | 3: 2.94

Mutual heating coefficient Feq 1: 167.507 | 2: 252.235 | 3: 178.734

Other characteristicsEarthing

Earthing of cable screen/sheath Both sides

Variation of spacing No variation

Loss Factors

Loss factor of screen and sheath λ1 1: 1.565 | 2: 0.656 | 3: 1.188

Page 6: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 6

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Loss factor by circulating currents λ1c 1: 1.565 | 2: 0.656 | 3: 1.188

Loss factor for solid bonding λ1cb 1: 1.565 | 2: 0.656 | 3: 1.188

Parameter ξ for calculation of loss factor ξcb 1: 0.187 | 2: 0.025 | 3: 0.029

Loss factor for single point bonding λ1es 1: 0.021 | 2: 0.022 | 3: 0.022

Loss factor of armour λ2 0.000

Conductor resistance

AC resistance of conductor at operating temperature Rc Ω/km 1: 3.570e-02 | 2: 3.471e-02 | 3: 3.516e-02

DC resistance of conductor at operating temperature RcDC Ω/km 1: 3.306e-02 | 2: 3.201e-02 | 3: 3.248e-02

Skin effect factor of conductor ys 1: 0.0710 | 2: 0.0754 | 3: 0.0734

Factor for skin effect on conductor xs 1: 1.9496 | 2: 1.9815 | 3: 1.9669

Proximity effect factor of conductors yp 1: 0.0087 | 2: 0.0091 | 3: 0.0090

Factor for proximity effect of conductors xp 1: 1.9496 | 2: 1.9815 | 3: 1.9669

Electrical parametersApparent power at injecting point SG kW 95263

Resistances

Electrical resistance of screen Rsc Ω/km 1: 0.4032 | 2: 0.3903 | 3: 0.3961

Electrical resistance of sheath Rsh Ω/km 1: 0.5423 | 2: 0.5246 | 3: 0.5326

Electrical resistance of screen||sheath Rs Ω/km 1: 0.2312 | 2: 0.2238 | 3: 0.2271

Electrical stress

Electrical stress on inner/outer side of insulation Estress kV 5.172 / 2.440

Radius to point x in insulation rx mm 16.35 / 34.65

Line-to-ground voltage Ue kV 63.51

Page 7: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 7

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Capacitance

Capacitive load current IC A/km 3.69

Charging capacity CC kvar/km 703.92

Capacitive earth short-circuit current ICe A/km 11.08

Inductances

Inductance of phase 1 L1 mH/km (0.5933-0.1201j)

Inductance of phase 2 L2 mH/km 0.524

Inductance of phase 3 L3 mH/km (0.5933+0.1201j)

Mean inductance of the phases Lm mH/km 0.5702

Vacuum permeability μ0 H/m 1.25664e-06

Distance between phases a12,23,3

1

mm 160.000 / 160.000 / 226.274

Geometric mean radius GMR mm 11.649

Geometric mean radius factor KGMR 0.774

Number of wires in conductor ncw 91

Reactances

Reactance of conductor Xc Ω/km 0.1791

Reactance of screen/sheath Xs Ω/km 0.0898

Mutual reactance Xm Ω/km 0.0436

Reduction factor RF 1: 0.9321 | 2: 0.9280 | 3: 0.9299

Impedances and Admittance

Positive sequence impedance Zpos Ω/km (0.0357+0.1791j)

Negative sequence impedance Zneg Ω/km (0.0357+0.1791j)

Admittance Y S/km (1.0701-5.3696j)

Surge Impedance SI Ω 55.49

Surge velocity of propagation cSI km/s 189605.4

Page 8: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 8

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Conductance and Susceptance

Conductance G S/km 1.0701

Susceptance B S/km -5.3696

Voltage drop Vdrop V/A/km 1: 0.1909 | 2: 0.1893 | 3: 0.1900

Short circuit currentsDuration of short-circuit tk s 0.1 | 0.2 | 0.3 | 0.5 | 1.0 | 2.0 | 3.0 | 5.0

Conductor

Permissible short-circuit current Ik kA 315.22 | 223.20 | 182.44 | 141.55 | 100.40 | 71.30 | 58.40 | 45.47

Short-circuit current (adiabatic) IkAD kA 314.17 | 222.15 | 181.39 | 140.50 | 99.35 | 70.25 | 57.36 | 44.43

Initial temperature θki °C 63.0

Final temperature θkf °C 250.0

Specific short-circuit parameter Kk A.s½/mm² 225.6

Reciprocal of temperature coefficient of resistance βk K 234

Specific heat capacity of metallic component σkc J/K.m³ 3.45e+06

Electrical resistivity of metallic component ρk20 Ω.m 1.7241e-08

Heat loss allowance factor εk 1.023

Cross-sectional area of current carrying component Sk mm² 630.00

Imperfect contact thermal factor Fk 0.9

Thermal property constant A Ak (mm²/s)½ 0.5914

Non-adiabatic constant C1 Ck1 mm/m 2464

Thermal property constant B Bk mm²/s 2.9283e-04

Non-adiabatic constant C2 Ck2 K.m.mm²/J 1.22

Thermal resistivity of adjacent material ρki K.m/W 3.5

Specific heat capacity of adjacent material σki J/K.m³ 2.40e+06

Screen

Permissible short-circuit current Ik kA 23.26 | 16.79 | 13.92 | 11.03 | 8.12 | 6.04 | 5.12 | 4.18

Short-circuit current (adiabatic) IkAD kA 22.06 | 15.60 | 12.74 | 9.87 | 6.98 | 4.93 | 4.03 | 3.12

Initial temperature θki °C 58.0

Final temperature θkf °C 200.0

Specific short-circuit parameter Kk A.s½/mm² 225.6

Reciprocal of temperature coefficient of resistance βk K 234

Page 9: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 9

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Specific heat capacity of metallic component σkc J/K.m³ 3.45e+06

Electrical resistivity of metallic component ρk20 Ω.m 1.7241e-08

Heat loss allowance factor εk 1.339

Cross-sectional area of current carrying component Sk mm² 0.665 x 74

Imperfect contact thermal factor Fk 0.7

Thermal property constant A Ak (mm²/s)½ 0.4123

Non-adiabatic constant C1 Ck1 mm/m 2464

Thermal property constant B Bk mm²/s 2.0416e-04

Non-adiabatic constant C2 Ck2 K.m.mm²/J 1.22

Thermal resistivity of adjacent material ρki K.m/W 6.0

Specific heat capacity of adjacent material σki J/K.m³ 2.00e+06

Sheath

Permissible short-circuit current Ik kA 17.80 | 13.40 | 11.44 | 9.45 | 7.43 | 5.96 | 5.28 | 4.57

Short-circuit current (adiabatic) IkAD kA 14.86 | 10.51 | 8.58 | 6.64 | 4.70 | 3.32 | 2.71 | 2.10

Initial temperature θki °C 58.0

Final temperature θkf °C 150.0

Specific short-circuit parameter Kk A.s½/mm² 148.1

Reciprocal of temperature coefficient of resistance βk K 228

Specific heat capacity of metallic component σkc J/K.m³ 2.50e+06

Electrical resistivity of metallic component ρk20 Ω.m 2.8264e-08

Heat loss allowance factor εk 2.174

Cross-sectional area of current carrying component Sk mm² 60.154

Imperfect contact thermal factor Fk 0.9

Thermal contact factor Mk s½ 1.012

Thickness of screen, sheath or armour δk mm 0.25

Thermal resistivity of the layer located above ρk2 K.m/W 6.0

Thermal resistivity of the layer located below ρk3 K.m/W 3.5

Specific heat capacity of layer located below σk2 J/K.m³ 2.00e+06

Specific heat capacity of layer located above σk3 J/K.m³ 2.40e+06

System B (High voltage cable)

AmpacityName of cable N2XS(FL)2Y 630Cu/50RCu mm2 110/64kV

Permissible current rating Ic A 450.0

Page 10: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 10

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Operating voltage Uo kV 110.0

System frequency f Hz 50.0

Number of sources in system Nc 3

Number of conductors combined ncc 1

LoadContinuous load LF p.u. 1.0

TemperaturesTemperature of conductor θc °C 1: 56.2 | 2: 54.4 | 3: 54.8

Temperature of screen/sheath θs °C 1: 52.6 | 2: 50.8 | 3: 51.2

External temperature of the object θe °C 1: 52.1 | 2: 50.4 | 3: 50.8

Temperature rises

Temperature rise of conductor Δθc K 1: 17.5 | 2: 16.4 | 3: 16.4

Temperature rise by dielectric losses Δθd K 1: 0.5 | 2: 0.5 | 3: 0.5

Temperature rise by other buried objects Δθp K 1: 23.7 | 2: 23.0 | 3: 23.4

Critical soil temperature rise Δθx K 0.0

LossesOhmic

Conductor losses Wc W/m 1: 7.114 | 2: 7.076 | 3: 7.085

Screen and sheath losses Ws W/m 1: 0.422 | 2: 0.099 | 3: 0.116

Ohmic losses per phase WI W/m 1: 7.536 | 2: 7.175 | 3: 7.201

Dielectric

Dielectric losses Wd W/m 1: 0.235 | 2: 0.235 | 3: 0.235

Total

Total losses per phase Wt W/m 1: 7.771 | 2: 7.410 | 3: 7.436

Total losses per object Wtot W/m 1: 7.771 | 2: 7.410 | 3: 7.436

Total losses of the system Wsys W/m 22.616

ArrangementCenter position of cable 1 x1 / y1 mm -500.0 / 1100.0

Center position of cable 2 x2 / y2 mm -635.1 / 1100.0

Center position of cable 3 x3 / y3 mm -364.9 / 1100.0

Separation of conductors in a system sc mm 135.10

Separation of cables sc2 mm 170.2

Depth of laying of sources Lc mm 1100.0

Page 11: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 11

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Substitution coefficient u u 25.870

Thermal ResistancesThermal resistance to ambient T4μ K.m/W 1: 1.725 | 2: 1.663 | 3: 1.661

Correction of thermal resistance for backfill T4db K.m/W 1: 0.512 | 2: 0.537 | 3: 0.535

Number of loaded objects in backfill Nb 1: 7.85 | 2: 8.23 | 3: 8.20

Mutual heating coefficient Feq 1: 266.176 | 2: 133.836 | 3: 133.836

Other characteristicsEarthing

Earthing of cable screen/sheath Single side

Substitution coefficient λ0 for eddy-currents λ0 1: 0.00908 | 2: 0.0023 | 3: 0.00229

Substitution coefficient Δ1 for eddy-currents Δ1 1: 0.000633 | 2: -0.0694 | 3: 0.0924

Substitution coefficient Δ2 for eddy-currents Δ2 1: 0 | 2: 4.14e-05 | 3: 4.05e-05

Substitution coefficient m0 for eddy-currents m0 Hz.m/Ω 1: 0.1386 | 2: 0.1394 | 3: 0.1392

Substitution coefficient β1 for eddy-currents β1 118.1852

Substitution coefficient gs for eddy-currents gs 1.0106

Loss Factors

Loss factor of screen and sheath λ1 1: 0.059 | 2: 0.014 | 3: 0.016

Loss factor by circulating currents λ1c 0.000

Loss factor by eddy currents λ1e 1: 0.059 | 2: 0.014 | 3: 0.016

Loss factor for single point bonding λ1es 1: 0.059 | 2: 0.014 | 3: 0.016

Loss factor of armour λ2 0.000

Page 12: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 12

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Conductor resistance

AC resistance of conductor at operating temperature Rc Ω/km 1: 3.513e-02 | 2: 3.494e-02 | 3: 3.499e-02

DC resistance of conductor at operating temperature RcDC Ω/km 1: 3.233e-02 | 2: 3.213e-02 | 3: 3.218e-02

Skin effect factor of conductor ys 1: 0.0740 | 2: 0.0749 | 3: 0.0747

Factor for skin effect on conductor xs 1: 1.9715 | 2: 1.9777 | 3: 1.9762

Proximity effect factor of conductors yp 1: 0.0127 | 2: 0.0128 | 3: 0.0128

Factor for proximity effect of conductors xp 1: 1.9715 | 2: 1.9777 | 3: 1.9762

Electrical parametersApparent power at injecting point SG kW 85737

Resistances

Electrical resistance of screen Rsc Ω/km 1: 0.3954 | 2: 0.3929 | 3: 0.3935

Electrical resistance of sheath Rsh Ω/km 1: 0.5316 | 2: 0.5282 | 3: 0.5290

Electrical resistance of screen||sheath Rs Ω/km 1: 0.2267 | 2: 0.2253 | 3: 0.2256

Electrical stress

Electrical stress on inner/outer side of insulation Estress kV 5.172 / 2.440

Radius to point x in insulation rx mm 16.35 / 34.65

Line-to-ground voltage Ue kV 63.51

Capacitance

Capacitive load current IC A/km 3.69

Charging capacity CC kvar/km 703.92

Capacitive earth short-circuit current ICe A/km 11.08

Inductances

Inductance of phase 1 L1 mH/km (0.4902+0j)

Inductance of phase 2 L2 mH/km (0.5595+0.2401j)

Page 13: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 13

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Inductance of phase 3 L3 mH/km (0.5595-0.2401j)

Mean inductance of the phases Lm mH/km 0.5353

Vacuum permeability μ0 H/m 1.25664e-06

Distance between phases a12,23,3

1

mm 135.100 / 270.200 / 135.100

Geometric mean radius GMR mm 11.649

Geometric mean radius factor KGMR 0.774

Number of wires in conductor ncw 91

Reactances

Reactance of conductor Xc Ω/km 0.1682

Reactance of screen/sheath Xs Ω/km 0.0792

Mutual reactance Xm Ω/km 0.0436

Reduction factor RF 1: 0.9440 | 2: 0.9434 | 3: 0.9435

Impedances and Admittance

Positive sequence impedance Zpos Ω/km (0.0351+0.1682j)

Negative sequence impedance Zneg Ω/km (0.0351+0.1682j)

Admittance Y S/km (1.1901-5.6973j)

Surge Impedance SI Ω 53.77

Surge velocity of propagation cSI km/s 189605.4

Conductance and Susceptance

Conductance G S/km 1.1901

Susceptance B S/km -5.6973

Voltage drop Vdrop V/A/km 1: 0.1817 | 2: 0.1814 | 3: 0.1815

Short circuit currentsDuration of short-circuit tk s 0.1 | 0.2 | 0.3 | 0.5 | 1.0 | 2.0 | 3.0 | 5.0

Conductor

Permissible short-circuit current Ik kA 322.36 | 228.26 | 186.57 | 144.76 | 102.67 | 72.91 | 59.73 | 46.50

Page 14: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 14

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Short-circuit current (adiabatic) IkAD kA 321.28 | 227.18 | 185.49 | 143.68 | 101.60 | 71.84 | 58.66 | 45.44

Initial temperature θki °C 56.0

Final temperature θkf °C 250.0

Specific short-circuit parameter Kk A.s½/mm² 225.6

Reciprocal of temperature coefficient of resistance βk K 234

Specific heat capacity of metallic component σkc J/K.m³ 3.45e+06

Electrical resistivity of metallic component ρk20 Ω.m 1.7241e-08

Heat loss allowance factor εk 1.023

Cross-sectional area of current carrying component Sk mm² 630.00

Imperfect contact thermal factor Fk 0.9

Thermal property constant A Ak (mm²/s)½ 0.5914

Non-adiabatic constant C1 Ck1 mm/m 2464

Thermal property constant B Bk mm²/s 2.9283e-04

Non-adiabatic constant C2 Ck2 K.m.mm²/J 1.22

Thermal resistivity of adjacent material ρki K.m/W 3.5

Specific heat capacity of adjacent material σki J/K.m³ 2.40e+06

Screen

Permissible short-circuit current Ik kA 23.83 | 17.20 | 14.26 | 11.30 | 8.32 | 6.19 | 5.24 | 4.28

Short-circuit current (adiabatic) IkAD kA 22.60 | 15.98 | 13.05 | 10.11 | 7.15 | 5.05 | 4.13 | 3.20

Initial temperature θki °C 53.0

Final temperature θkf °C 200.0

Specific short-circuit parameter Kk A.s½/mm² 225.6

Reciprocal of temperature coefficient of resistance βk K 234

Specific heat capacity of metallic component σkc J/K.m³ 3.45e+06

Electrical resistivity of metallic component ρk20 Ω.m 1.7241e-08

Heat loss allowance factor εk 1.339

Cross-sectional area of current carrying component Sk mm² 0.665 x 74

Imperfect contact thermal factor Fk 0.7

Thermal property constant A Ak (mm²/s)½ 0.4123

Non-adiabatic constant C1 Ck1 mm/m 2464

Thermal property constant B Bk mm²/s 2.0416e-04

Page 15: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 15

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Non-adiabatic constant C2 Ck2 K.m.mm²/J 1.22

Thermal resistivity of adjacent material ρki K.m/W 6.0

Specific heat capacity of adjacent material σki J/K.m³ 2.00e+06

Sheath

Permissible short-circuit current Ik kA 18.43 | 13.87 | 11.84 | 9.79 | 7.69 | 6.17 | 5.46 | 4.73

Short-circuit current (adiabatic) IkAD kA 15.38 | 10.88 | 8.88 | 6.88 | 4.86 | 3.44 | 2.81 | 2.18

Initial temperature θki °C 53.0

Final temperature θkf °C 150.0

Specific short-circuit parameter Kk A.s½/mm² 148.1

Reciprocal of temperature coefficient of resistance βk K 228

Specific heat capacity of metallic component σkc J/K.m³ 2.50e+06

Electrical resistivity of metallic component ρk20 Ω.m 2.8264e-08

Heat loss allowance factor εk 2.174

Cross-sectional area of current carrying component Sk mm² 60.154

Imperfect contact thermal factor Fk 0.9

Thermal contact factor Mk s½ 1.012

Thickness of screen, sheath or armour δk mm 0.25

Thermal resistivity of the layer located above ρk2 K.m/W 6.0

Thermal resistivity of the layer located below ρk3 K.m/W 3.5

Specific heat capacity of layer located below σk2 J/K.m³ 2.00e+06

Specific heat capacity of layer located above σk3 J/K.m³ 2.40e+06

System C (High voltage cable)

AmpacityName of cable N2XS(FL)2Y 630Cu/50RCu mm2 110/64kV

Permissible current rating Ic A 800.0

Operating voltage Uo kV 110.0

System frequency f Hz 16.7

Number of sources in system Nc 2

Number of conductors combined ncc 1

LoadContinuous load LF p.u. 1.0

TemperaturesTemperature of conductor θc °C 1: 66.6 | 2: 66.3

Temperature of screen/sheath θs °C 1: 55.6 | 2: 55.3

Page 16: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 16

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

External temperature of the object θe °C 1: 54.4 | 2: 54.1

Duct

Mean temperature of the medium in the duct θdm °C 1: 53.9 | 2: 53.6

Temperature of duct inner wall θdi °C 1: 53.4 | 2: 53.1

Temperature of duct outer wall θde °C 1: 51.9 | 2: 51.6

Temperature rises

Temperature rise of conductor Δθc K 1: 38.2 | 2: 37.7

Temperature rise by dielectric losses Δθd K 1: 0.1 | 2: 0.1

Temperature rise by other buried objects Δθp K 1: 13.4 | 2: 13.5

Critical soil temperature rise Δθx K 0.0

LossesOhmic

Conductor losses Wc W/m 1: 21.612 | 2: 21.590

Screen and sheath losses Ws W/m 1: 0.035 | 2: 0.035

Ohmic losses per phase WI W/m 1: 21.646 | 2: 21.625

Dielectric

Dielectric losses Wd W/m 1: 0.059 | 2: 0.059

Total

Total losses per phase Wt W/m 1: 21.705 | 2: 21.684

Total losses per object Wtot W/m 1: 21.705 | 2: 21.684

Total losses of the system Wsys W/m 43.389

ArrangementMaterial of duct pipe Md Plastic duct made of PVC (Polyvinylchlorid)

Inside / outside diameter of duct Did/Dod mm 140.0 / 150.0

Equivalent diameter of a group of cables Deq mm 85.0

Thermal resistivity of duct material ρd K.m/W 6.000

Thermal resistivity of bentonite filling ρdfillK.m/W 0.700

Specific heat capacity of duct material σd J/K.m³ 1700000.0

Absorption coefficient of solar radiation σsun 0.6

Center position of duct 1 x1 / y1 mm -1200.0 / 1900.0

Center position of duct 2 x2 / y2 mm -1200.0 / 1700.0

Separation of conductors in a system sc mm 200.00

Page 17: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 17

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Depth of laying of sources Lc mm 1: 1900.0 | 2: 1700.0

Substitution coefficient u u 1: 25.333 | 2: 22.667

Thermal ResistancesThermal resistance to ambient T4μ K.m/W 1: 1.085 | 2: 1.067

Thermal resistance of medium in the duct T4i K.m/W 0.048

Thermal resistance of the duct wall T4ii K.m/W 0.066

Mutual heating coefficient Feq 18.000

Other characteristicsEarthing

Earthing of cable screen/sheath Single side

Loss Factors

Loss factor of screen and sheath λ1 1: 0.002 | 2: 0.002

Loss factor by circulating currents λ1c 0.000

Loss factor by eddy currents λ1e 1: 0.002 | 2: 0.002

Loss factor for single point bonding λ1es 1: 0.002 | 2: 0.002

Loss factor of armour λ2 0.000

Conductor resistance

AC resistance of conductor at operating temperature Rc Ω/km 1: 3.377e-02 | 2: 3.373e-02

DC resistance of conductor at operating temperature RcDC Ω/km 1: 3.348e-02 | 2: 3.344e-02

Skin effect factor of conductor ys 1: 0.0081 | 2: 0.0081

Factor for skin effect on conductor xs 1: 1.1197 | 2: 1.1203

Proximity effect factor of conductors yp 1: 0.0005 | 2: 0.0005

Factor for proximity effect of conductors xp 1: 1.1197 | 2: 1.1203

Electrical parametersApparent power at injecting point SG kW 88000

Resistances

Electrical resistance of screen Rsc Ω/km 1: 0.3996 | 2: 0.3992

Page 18: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 18

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Electrical resistance of sheath Rsh Ω/km 1: 0.5373 | 2: 0.5368

Electrical resistance of screen||sheath Rs Ω/km 1: 0.2292 | 2: 0.2289

Electrical stress

Electrical stress on inner/outer side of insulation Estress kV 4.479 / 2.113

Radius to point x in insulation rx mm 16.35 / 34.65

Line-to-ground voltage Ue kV 55.00

Capacitance

Capacitive load current IC A/km 1.07

Charging capacity CC kvar/km 117.55

Capacitive earth short-circuit current ICe A/km 2.14

Inductances

Mean inductance of the phases Lm mH/km 0.5686

Vacuum permeability μ0 H/m 1.25664e-06

Mean distance between the phases am mm 200.000

Geometric mean radius GMR mm 11.649

Geometric mean radius factor KGMR 0.774

Number of wires in conductor ncw 91

Reactances

Reactance of conductor Xc Ω/km 0.05967

Reactance of screen/sheath Xs Ω/km 0.0347

Mutual reactance Xm Ω/km 0.0145

Reduction factor RF 1: 0.9887 | 2: 0.9887

Impedances and Admittance

Positive sequence impedance Zpos Ω/km (0.0338+0.0597j)

Negative sequence impedance Zneg Ω/km (0.0338+0.0597j)

Admittance Y S/km (7.1843-12.6941j)

Surge Impedance SI Ω 55.41

Page 19: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 19

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Surge velocity of propagation cSI km/s 189605.4

Conductance and Susceptance

Conductance G S/km 7.1843

Susceptance B S/km -12.6941

Voltage drop Vdrop V/A/km 1: 0.1128 | 2: 0.1127

Short circuit currentsDuration of short-circuit tk s 0.1 | 0.2 | 0.3 | 0.5 | 1.0 | 2.0 | 3.0 | 5.0

Conductor

Permissible short-circuit current Ik kA 311.15 | 220.32 | 180.08 | 139.72 | 99.10 | 70.38 | 57.65 | 44.88

Short-circuit current (adiabatic) IkAD kA 310.11 | 219.28 | 179.04 | 138.69 | 98.07 | 69.34 | 56.62 | 43.86

Initial temperature θki °C 67.0

Final temperature θkf °C 250.0

Specific short-circuit parameter Kk A.s½/mm² 225.6

Reciprocal of temperature coefficient of resistance βk K 234

Specific heat capacity of metallic component σkc J/K.m³ 3.45e+06

Electrical resistivity of metallic component ρk20 Ω.m 1.7241e-08

Heat loss allowance factor εk 1.023

Cross-sectional area of current carrying component Sk mm² 630.00

Imperfect contact thermal factor Fk 0.9

Thermal property constant A Ak (mm²/s)½ 0.5914

Non-adiabatic constant C1 Ck1 mm/m 2464

Thermal property constant B Bk mm²/s 2.9283e-04

Non-adiabatic constant C2 Ck2 K.m.mm²/J 1.22

Thermal resistivity of adjacent material ρki K.m/W 3.5

Specific heat capacity of adjacent material σki J/K.m³ 2.40e+06

Screen

Permissible short-circuit current Ik kA 23.52 | 16.98 | 14.07 | 11.16 | 8.21 | 6.11 | 5.17 | 4.22

Short-circuit current (adiabatic) IkAD kA 22.31 | 15.77 | 12.88 | 9.98 | 7.05 | 4.99 | 4.07 | 3.15

Initial temperature θki °C 56.0

Final temperature θkf °C 200.0

Page 20: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 20

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Specific short-circuit parameter Kk A.s½/mm² 225.6

Reciprocal of temperature coefficient of resistance βk K 234

Specific heat capacity of metallic component σkc J/K.m³ 3.45e+06

Electrical resistivity of metallic component ρk20 Ω.m 1.7241e-08

Heat loss allowance factor εk 1.339

Cross-sectional area of current carrying component Sk mm² 0.665 x 74

Imperfect contact thermal factor Fk 0.7

Thermal property constant A Ak (mm²/s)½ 0.4123

Non-adiabatic constant C1 Ck1 mm/m 2464

Thermal property constant B Bk mm²/s 2.0416e-04

Non-adiabatic constant C2 Ck2 K.m.mm²/J 1.22

Thermal resistivity of adjacent material ρki K.m/W 6.0

Specific heat capacity of adjacent material σki J/K.m³ 2.00e+06

Sheath

Permissible short-circuit current Ik kA 18.09 | 13.62 | 11.62 | 9.61 | 7.55 | 6.05 | 5.36 | 4.64

Short-circuit current (adiabatic) IkAD kA 15.10 | 10.68 | 8.72 | 6.75 | 4.78 | 3.38 | 2.76 | 2.14

Initial temperature θki °C 56.0

Final temperature θkf °C 150.0

Specific short-circuit parameter Kk A.s½/mm² 148.1

Reciprocal of temperature coefficient of resistance βk K 228

Specific heat capacity of metallic component σkc J/K.m³ 2.50e+06

Electrical resistivity of metallic component ρk20 Ω.m 2.8264e-08

Heat loss allowance factor εk 2.174

Cross-sectional area of current carrying component Sk mm² 60.154

Imperfect contact thermal factor Fk 0.9

Thermal contact factor Mk s½ 1.012

Thickness of screen, sheath or armour δk mm 0.25

Thermal resistivity of the layer located above ρk2 K.m/W 6.0

Thermal resistivity of the layer located below ρk3 K.m/W 3.5

Specific heat capacity of layer located below σk2 J/K.m³ 2.00e+06

Specific heat capacity of layer located above σk3 J/K.m³ 2.40e+06

Page 21: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 21

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

System D (Medium voltage cable)

AmpacityName of cable N2XS2Y 240Cu/25RCu mm2 20/12kV

Permissible current rating Ic A 240.0

Operating voltage Uo kV 20.0

System frequency f Hz 50.0

Number of sources in system Nc 3

Number of conductors combined ncc 3

LoadContinuous load LF p.u. 1.0

TemperaturesTemperature of conductor θc °C 50.3

Temperature of screen/sheath θs °C 48.7

External temperature of the object θe °C 48.3

Duct

Mean temperature of the medium in the duct θdm °C 45.5

Temperature of duct inner wall θdi °C 42.7

Temperature of duct outer wall θde °C 42.0

Temperature rises

Temperature rise of conductor Δθc K 16.3

Temperature rise by dielectric losses Δθd K 0.2

Temperature rise by other buried objects Δθp K 19.0

Critical soil temperature rise Δθx K 0.0

LossesOhmic

Conductor losses Wc W/m 4.968

Screen and sheath losses Ws W/m 0.191

Ohmic losses per phase WI W/m 5.159

Dielectric

Dielectric losses Wd W/m 0.055

Page 22: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 22

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Total

Total losses per phase Wt W/m 5.213

Total losses per object Wtot W/m 5.213

Total losses of the system Wsys W/m 15.640

ArrangementMaterial of duct pipe Md Plastic duct made of PE (Polyethylene)

Inside / outside diameter of duct Did/Dod mm 120.0 / 130.0

Thermal resistivity of duct material ρd K.m/W 3.500

Specific heat capacity of duct material σd J/K.m³ 2400000.0

Absorption coefficient of solar radiation σsun 0.4

Center position of duct 1 x1 / y1 mm 500.0 / 800.0

Separation of conductors in a system sc mm 40.44

Depth of laying of sources Lc mm 800.0

Substitution coefficient u u 12.308

Thermal ResistancesThermal resistance to ambient T4μ K.m/W 0.510

Thermal resistance of medium in the duct T4i K.m/W 0.361

Thermal resistance of the duct wall T4ii K.m/W 0.045

Mutual heating coefficient Feq 1.000

Other characteristicsEarthing

Earthing of cable screen/sheath Both sides

Variation of spacing No variation

Loss Factors

Loss factor of screen and sheath λ1 0.038

Loss factor by circulating currents λ1c 0.038

Loss factor for solid bonding λ1cb 0.038

Loss factor for single point bonding λ1es 0.009

Loss factor of armour λ2 0.000

Conductor resistance

AC resistance of conductor at operating temperature Rc Ω/km 8.624e-02

DC resistance of conductor at operating temperature RcDC Ω/km 8.438e-02

Skin effect factor of conductor ys 0.0114

Page 23: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 23

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Factor for skin effect on conductor xs 1.2204

Proximity effect factor of conductors yp 0.0107

Factor for proximity effect of conductors xp 1.2204

Electrical parametersApparent power at injecting point SG kW 8314

Resistances

Electrical resistance of screen Rsc Ω/km 0.8017

Electrical resistance of screen||sheath Rs Ω/km 0.8017

Electrical stress

Electrical stress on inner/outer side of insulation Estress kV 2.618 / 1.709

Radius to point x in insulation rx mm 10.35 / 15.85

Line-to-ground voltage Ue kV 11.55

Capacitance

Capacitive load current IC A/km 1.18

Charging capacity CC kvar/km 41.01

Capacitive earth short-circuit current ICe A/km 3.55

Inductances

Mean inductance of the phases Lm mH/km 0.3436

Vacuum permeability μ0 H/m 1.25664e-06

Mean distance between the phases am mm 40.440

Geometric mean radius GMR mm 7.258

Geometric mean radius factor KGMR 0.768

Number of wires in conductor ncw 37

Reactances

Reactance of conductor Xc Ω/km 0.1079

Reactance of screen/sheath Xs Ω/km 0.0517

Page 24: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 24

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Reduction factor RF 0.9979

Impedances and Admittance

Positive sequence impedance Zpos Ω/km (0.0862+0.1079j)

Negative sequence impedance Zneg Ω/km (0.0862+0.1079j)

Admittance Y S/km (4.5185-5.6546j)

Surge Impedance SI Ω 32.45

Surge velocity of propagation cSI km/s 189605.4

Conductance and Susceptance

Conductance G S/km 4.5185

Susceptance B S/km -5.6546

Voltage drop Vdrop V/A/km 0.2159

Short circuit currentsDuration of short-circuit tk s 0.1 | 0.2 | 0.3 | 0.5 | 1.0 | 2.0 | 3.0 | 5.0

Conductor

Permissible short-circuit current Ik kA 125.51 | 88.95 | 72.75 | 56.50 | 40.15 | 28.58 | 23.46 | 18.32

Short-circuit current (adiabatic) IkAD kA 124.84 | 88.27 | 72.08 | 55.83 | 39.48 | 27.91 | 22.79 | 17.65

Initial temperature θki °C 50.0

Final temperature θkf °C 250.0

Specific short-circuit parameter Kk A.s½/mm² 225.6

Reciprocal of temperature coefficient of resistance βk K 234

Specific heat capacity of metallic component σkc J/K.m³ 3.45e+06

Electrical resistivity of metallic component ρk20 Ω.m 1.7241e-08

Heat loss allowance factor εk 1.038

Cross-sectional area of current carrying component Sk mm² 240.00

Imperfect contact thermal factor Fk 0.9

Thermal property constant A Ak (mm²/s)½ 0.5914

Non-adiabatic constant C1 Ck1 mm/m 2464

Page 25: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 25

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Thermal property constant B Bk mm²/s 2.9283e-04

Non-adiabatic constant C2 Ck2 K.m.mm²/J 1.22

Thermal resistivity of adjacent material ρki K.m/W 3.5

Specific heat capacity of adjacent material σki J/K.m³ 2.40e+06

Screen

Permissible short-circuit current Ik kA 10.05 | 7.27 | 6.04 | 4.81 | 3.56 | 2.66 | 2.26 | 1.86

Short-circuit current (adiabatic) IkAD kA 9.44 | 6.68 | 5.45 | 4.22 | 2.99 | 2.11 | 1.72 | 1.34

Initial temperature θki °C 49.0

Final temperature θkf °C 150.0

Specific short-circuit parameter Kk A.s½/mm² 225.6

Reciprocal of temperature coefficient of resistance βk K 234

Specific heat capacity of metallic component σkc J/K.m³ 3.45e+06

Electrical resistivity of metallic component ρk20 Ω.m 1.7241e-08

Heat loss allowance factor εk 1.391

Cross-sectional area of current carrying component Sk mm² 0.665 x 36

Imperfect contact thermal factor Fk 0.7

Thermal property constant A Ak (mm²/s)½ 0.4861

Non-adiabatic constant C1 Ck1 mm/m 2464

Thermal property constant B Bk mm²/s 2.4066e-04

Non-adiabatic constant C2 Ck2 K.m.mm²/J 1.22

Thermal resistivity of adjacent material ρki K.m/W 4.75

Specific heat capacity of adjacent material σki J/K.m³ 2.20e+06

System E (Medium voltage cable)

AmpacityName of cable 33kV, XKDT-FT 3x150 mm2 RM35

Permissible current rating Ic A 200.0

Operating voltage Uo kV 30.0

System frequency f Hz 50.0

Number of sources in system Nc 1

Number of conductors combined ncc 3

LoadContinuous load LF p.u. 1.0

Page 26: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 26

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

TemperaturesTemperature of conductor θc °C 64.1

Temperature of screen/sheath θs °C 57.2

Temperature of armour θar °C 57.2

Temperature of 1st armour layer θar1°C 57.2

Temperature of 2nd armour layer θar2°C 57.2

External temperature of the object θe °C 55.9

Duct

Mean temperature of the medium in the duct θdm °C 52.9

Temperature of duct inner wall θdi °C 49.9

Temperature of duct outer wall θde °C 49.0

Temperature rises

Temperature rise of conductor Δθc K 26.8

Temperature rise by dielectric losses Δθd K 0.3

Temperature rise by other buried objects Δθp K 22.3

Critical soil temperature rise Δθx K 0.0

LossesOhmic

Conductor losses Wc W/m 5.854

Screen and sheath losses Ws W/m 0.131

Armour losses WA W/m 0.267

Ohmic losses per phase WI W/m 6.253

Dielectric

Dielectric losses Wd W/m 0.072

Total

Total losses per phase Wt W/m 6.325

Page 27: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 27

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Total losses per object Wtot W/m 18.975

Total losses of the system Wsys W/m 18.975

ArrangementMaterial of duct pipe Md Plastic duct made of PP (Polypropylene)

Inside / outside diameter of duct Did/Dod mm 140.0 / 150.0

Thermal resistivity of duct material ρd K.m/W 4.500

Specific heat capacity of duct material σd J/K.m³ 1800000.0

Absorption coefficient of solar radiation σsun 0.6

Center position of duct 1 x1 / y1 mm -600.0 / 900.0

Separation of conductors in a system sc mm 40.00

Depth of laying of sources Lc mm 900.0

Substitution coefficient u u 12.000

Thermal ResistancesThermal resistance to ambient T4μ K.m/W 0.614

Thermal resistance of medium in the duct T4i K.m/W 0.316

Thermal resistance of the duct wall T4ii K.m/W 0.049

Correction of thermal resistance for backfill T4db K.m/W 0.210

Number of loaded objects in backfill Nb 3.22

Mutual heating coefficient Feq 1.000

Other characteristicsEarthing

Earthing of cable screen/sheath Both sides, regular transposition

Variation of spacing No variation

Loss Factors

Loss factor of screen and sheath λ1 0.022

Loss factor by circulating currents λ1c 0.022

Loss factor for solid bonding λ1cb 0.022

Loss factor for single point bonding λ1es 0.050

Loss factor of armour λ2 0.046

Conductor resistance

AC resistance of conductor at operating temperature Rc Ω/km 1.464e-01

DC resistance of conductor at operating temperature RcDC Ω/km 1.455e-01

Page 28: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 28

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Skin effect factor of conductor ys 0.0039

Factor for skin effect on conductor xs 0.9293

Proximity effect factor of conductors yp 0.0021

Factor for proximity effect of conductors xp 0.9293

Electrical parametersApparent power at injecting point SG kW 6000

Resistances

Electrical resistance of screen Rsc Ω/km 0.5753

Electrical resistance of screen||sheath Rs Ω/km 0.5753

Electrical resistance of armour RA Ω/km 0.6386

Electrical stress

Electrical stress on inner/outer side of insulation Estress kV 3.141 / 1.521

Radius to point x in insulation rx mm 7.60 / 15.70

Line-to-ground voltage Ue kV 17.32

Capacitance

Capacitive load current IC A/km 1.04

Charging capacity CC kvar/km 54.20

Capacitive earth short-circuit current ICe A/km 3.13

Inductances

Mean inductance of the phases Lm mH/km 0.4014

Vacuum permeability μ0 H/m 1.25664e-06

Mean distance between the phases am mm 40.000

Geometric mean radius GMR mm 5.376

Geometric mean radius factor KGMR 0.768

Number of wires in conductor ncw 37

Page 29: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 29

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Reactances

Reactance of conductor Xc Ω/km 0.1261

Reactance of screen/sheath Xs Ω/km 0.0436

Mutual reactance Xm Ω/km 0.0436

Reduction factor RF 0.9971

Impedances and Admittance

Positive sequence impedance Zpos Ω/km (0.1464+0.1261j)

Negative sequence impedance Zneg Ω/km (0.1464+0.1261j)

Admittance Y S/km (3.9215-3.3786j)

Surge Impedance SI Ω 45.76

Surge velocity of propagation cSI km/s 189605.4

Conductance and Susceptance

Conductance G S/km 3.9215

Susceptance B S/km -3.3786

Voltage drop Vdrop V/A/km 0.3234

Short circuit currentsDuration of short-circuit tk s 0.1 | 0.2 | 0.3 | 0.5 | 1.0 | 2.0 | 3.0 | 5.0

Conductor

Permissible short-circuit current Ik kA 74.98 | 53.16 | 43.50 | 33.81 | 24.05 | 17.16 | 14.10 | 11.03

Short-circuit current (adiabatic) IkAD kA 74.47 | 52.66 | 42.99 | 33.30 | 23.55 | 16.65 | 13.60 | 10.53

Initial temperature θki °C 64.0

Final temperature θkf °C 250.0

Specific short-circuit parameter Kk A.s½/mm² 225.6

Reciprocal of temperature coefficient of resistance βk K 234

Specific heat capacity of metallic component σkc J/K.m³ 3.45e+06

Electrical resistivity of metallic component ρk20 Ω.m 1.7241e-08

Heat loss allowance factor εk 1.047

Page 30: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 30

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Cross-sectional area of current carrying component Sk mm² 150.00

Imperfect contact thermal factor Fk 0.9

Thermal property constant A Ak (mm²/s)½ 0.5914

Non-adiabatic constant C1 Ck1 mm/m 2464

Thermal property constant B Bk mm²/s 2.9283e-04

Non-adiabatic constant C2 Ck2 K.m.mm²/J 1.22

Thermal resistivity of adjacent material ρki K.m/W 3.5

Specific heat capacity of adjacent material σki J/K.m³ 2.40e+06

Screen

Permissible short-circuit current Ik kA 16.33 | 11.79 | 9.78 | 7.75 | 5.71 | 4.25 | 3.60 | 2.94

Short-circuit current (adiabatic) IkAD kA 15.47 | 10.94 | 8.93 | 6.92 | 4.89 | 3.46 | 2.82 | 2.19

Initial temperature θki °C 57.0

Final temperature θkf °C 200.0

Specific short-circuit parameter Kk A.s½/mm² 225.6

Reciprocal of temperature coefficient of resistance βk K 234

Specific heat capacity of metallic component σkc J/K.m³ 3.45e+06

Electrical resistivity of metallic component ρk20 Ω.m 1.7241e-08

Heat loss allowance factor εk 1.345

Cross-sectional area of current carrying component Sk mm² 0.636 x 54

Imperfect contact thermal factor Fk 0.7

Thermal property constant A Ak (mm²/s)½ 0.4123

Non-adiabatic constant C1 Ck1 mm/m 2464

Thermal property constant B Bk mm²/s 2.0416e-04

Non-adiabatic constant C2 Ck2 K.m.mm²/J 1.22

Thermal resistivity of adjacent material ρki K.m/W 6.0

Specific heat capacity of adjacent material σki J/K.m³ 2.00e+06

Armour

Permissible short-circuit current Ik kA 47.96 | 34.15 | 28.04 | 21.91 | 15.77 | 11.47 | 9.60 | 7.79

Short-circuit current (adiabatic) IkAD kA 47.17 | 33.36 | 27.23 | 21.10 | 14.92 | 10.55 | 8.61 | 6.67

Initial temperature θki °C 57.0

Final temperature θkf °C 200.0

Page 31: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 31

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Specific short-circuit parameter Kk A.s½/mm² 78.23

Reciprocal of temperature coefficient of resistance βk K 202

Specific heat capacity of metallic component σkc J/K.m³ 3.80e+06

Electrical resistivity of metallic component ρk20 Ω.m 1.38e-07

Heat loss allowance factor εk 1.168

Cross-sectional area of current carrying component Sk mm² 288.000

Imperfect contact thermal factor Fk 0.0

Thermal contact factor Mk s½ 0.08561

Thickness of screen, sheath or armour δk mm 1.2

Thermal resistivity of the layer located above ρk2 K.m/W 6.0

Thermal resistivity of the layer located below ρk3 K.m/W 5.0

Specific heat capacity of layer located below σk2 J/K.m³ 1.70e+06

Specific heat capacity of layer located above σk3 J/K.m³ 1.70e+06

System F (Low voltage cable)

AmpacityName of cable SOLARpower Alu-ATA 1x240/31

Permissible current rating Ic A 2 x 182.9 (365.8)

Operating voltage Uo kV 1.0

System frequency f Hz 0.0

Number of sources in system Nc 4

Number of conductors combined ncc 4

LoadContinuous load LF p.u. 1.0

TemperaturesTemperature of conductor θc °C 60.0

Temperature of screen/sheath θs °C 59.2

External temperature of the object θe °C 58.8

Duct

Mean temperature of the medium in the duct θdm °C 55.0

Temperature of duct inner wall θdi °C 51.1

Temperature of duct outer wall θde °C 50.0

Page 32: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 32

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Temperature rises

Temperature rise of conductor Δθc K 22.2

Temperature rise by dielectric losses Δθd K 0.0

Temperature rise by other buried objects Δθp K 22.8

Critical soil temperature rise Δθx K 0.0

LossesOhmic

Conductor losses Wc W/m 4.854

Ohmic losses per phase WI W/m 4.854

Total

Total losses per phase Wt W/m 4.854

Total losses per object Wtot W/m 4.854

Total losses of the system Wsys W/m 19.418

ArrangementMaterial of duct pipe Md Plastic duct made of PP (Polypropylene)

Inside / outside diameter of duct Did/Dod mm 120.0 / 130.0

Thermal resistivity of duct material ρd K.m/W 4.500

Specific heat capacity of duct material σd J/K.m³ 1800000.0

Absorption coefficient of solar radiation σsun 0.6

Center position of duct 1 x1 / y1 mm -400.0 / 910.0

Separation of conductors in a system sc mm 32.95

Depth of laying of sources Lc mm 910.0

Substitution coefficient u u 14.000

Thermal ResistancesThermal resistance to ambient T4μ K.m/W 0.629

Thermal resistance of medium in the duct T4i K.m/W 0.395

Thermal resistance of the duct wall T4ii K.m/W 0.057

Correction of thermal resistance for backfill T4db K.m/W 0.205

Number of loaded objects in backfill Nb 3.14

Mutual heating coefficient Feq 1.000

Other characteristicsEarthing

Earthing of cable screen/sheath Both sides

Page 33: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 33

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Variation of spacing No variation

Loss Factors

Loss factor of screen and sheath λ1 0.000

Loss factor by circulating currents λ1c 0.000

Loss factor of armour λ2 0.000

Conductor resistance

Resistance of conductor at operating temperature Rc Ω/km 1.452e-01

Electrical parametersApparent power at injecting point SG kW 365.8

Resistances

Electrical resistance of screen Rsc Ω/km 0.8453

Electrical resistance of screen||sheath Rs Ω/km 0.8453

Electrical stress

Electrical stress on inner/outer side of insulation Estress kV 0.335 / 0.276

Radius to point x in insulation rx mm 8.97 / 10.88

Line-to-ground voltage Ue kV 0.58

Capacitance

Inductances

Mean inductance of the phases Lm mH/km 0.3129

Voltage drop Vdrop V/A/km 0.2613

Short circuit currentsDuration of short-circuit tk s 0.1 | 0.2 | 0.3 | 0.5 | 1.0 | 2.0 | 3.0 | 5.0

Conductor

Permissible short-circuit current Ik kA 80.61 | 57.18 | 46.79 | 36.38 | 25.90 | 18.48 | 15.20 | 11.90

Short-circuit current (adiabatic) IkAD kA 80.02 | 56.58 | 46.20 | 35.78 | 25.30 | 17.89 | 14.61 | 11.32

Initial temperature θki °C 60.0

Final temperature θkf °C 250.0

Specific short-circuit parameter Kk A.s½/mm² 148.1

Reciprocal of temperature coefficient of resistance βk K 228

Specific heat capacity of metallic component σkc J/K.m³ 2.50e+06

Electrical resistivity of metallic component ρk20 Ω.m 2.8264e-08

Page 34: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 34

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Heat loss allowance factor εk 1.052

Cross-sectional area of current carrying component Sk mm² 240.00

Imperfect contact thermal factor Fk 0.9

Thermal property constant A Ak (mm²/s)½ 0.8162

Non-adiabatic constant C1 Ck1 mm/m 2464

Thermal property constant B Bk mm²/s 4.0410e-04

Non-adiabatic constant C2 Ck2 K.m.mm²/J 1.22

Thermal resistivity of adjacent material ρki K.m/W 3.5

Specific heat capacity of adjacent material σki J/K.m³ 2.40e+06

Screen

Permissible short-circuit current Ik kA 11.33 | 8.19 | 6.79 | 5.40 | 3.99 | 3.01 | 2.58 | 2.17

Short-circuit current (adiabatic) IkAD kA 10.75 | 7.60 | 6.20 | 4.81 | 3.40 | 2.40 | 1.96 | 1.52

Initial temperature θki °C 59.0

Final temperature θkf °C 180.0

Specific short-circuit parameter Kk A.s½/mm² 148.1

Reciprocal of temperature coefficient of resistance βk K 228

Specific heat capacity of metallic component σkc J/K.m³ 2.50e+06

Electrical resistivity of metallic component ρk20 Ω.m 2.8264e-08

Heat loss allowance factor εk 1.425

Cross-sectional area of current carrying component Sk mm² 38.720

Imperfect contact thermal factor Fk 0.5

Thermal contact factor Mk s½ 0.2811

Thickness of screen, sheath or armour δk mm 0.5

Thermal resistivity of the layer located above ρk2 K.m/W 6.0

Thermal resistivity of the layer located below ρk3 K.m/W 3.5

Specific heat capacity of layer located below σk2 J/K.m³ 2.00e+06

Specific heat capacity of layer located above σk3 J/K.m³ 2.40e+06

System G (Low voltage cable)

AmpacityName of cable FO Rampion

Permissible current rating Ic A 0.1

Operating voltage Uo kV 0.4

System frequency f Hz 50.0

Page 35: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 35

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Number of sources in system Nc 1

Number of conductors combined ncc 1

LoadContinuous load LF p.u. 1.0

TemperaturesTemperature of conductor θc °C 47.6

Temperature of screen/sheath θs °C 47.6

External temperature of the object θe °C 47.6

Duct

Mean temperature of the medium in the duct θdm °C 47.6

Temperature of duct inner wall θdi °C 47.6

Temperature of duct outer wall θde °C 47.6

Temperature rises

Temperature rise of conductor Δθc K 4.3

Temperature rise by dielectric losses Δθd K 0.0

Temperature rise by other buried objects Δθp K 28.3

Critical soil temperature rise Δθx K 0.0

LossesOhmic

Conductor losses Wc W/m 0.001

Ohmic losses per phase WI W/m 0.001

Dielectric

Dielectric losses Wd W/m 0.000

Total

Total losses per phase Wt W/m 0.001

Total losses per object Wtot W/m 0.001

Total losses of the system Wsys W/m 0.001

ArrangementMaterial of duct pipe Md Plastic duct made of PE (Polyethylene)

Inside / outside diameter of duct Did/Dod mm 140.0 / 150.0

Page 36: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 36

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Thermal resistivity of duct material ρd K.m/W 3.500

Specific heat capacity of duct material σd J/K.m³ 2400000.0

Absorption coefficient of solar radiation σsun 0.4

Center position of duct 1 x1 / y1 mm 1080.0 / 1150.0

Depth of laying of sources Lc mm 1150.0

Substitution coefficient u u 15.333

Thermal ResistancesThermal resistance to ambient T4μ K.m/W 6776.977

Thermal resistance of medium in the duct T4i K.m/W 1.257

Thermal resistance of the duct wall T4ii K.m/W 0.038

Correction of thermal resistance for backfill T4db K.m/W 6776.541

Number of loaded objects in backfill Nb 89324.64

Mutual heating coefficient Feq 1.000

Other characteristicsEarthing

Earthing not considered

Loss Factors

Loss factor of screen and sheath λ1 0.000

Loss factor by circulating currents λ1c 0.000

Loss factor of armour λ2 0.000

Conductor resistance

AC resistance of conductor at operating temperature Rc Ω/km 6.386e+01

DC resistance of conductor at operating temperature RcDC Ω/km 6.386e+01

Skin effect factor of conductor ys 0.0000

Factor for skin effect on conductor xs 0.0444

Proximity effect factor of conductors yp 0.0000

Factor for proximity effect of conductors xp 0.0397

Electrical parametersApparent power at injecting point SG kW 0.040

Page 37: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 37

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Resistances

Electrical resistance of screen Rsc Ω/km 83.2600

Electrical resistance of screen||sheath Rs Ω/km 83.2600

Electrical stress

Electrical stress on inner/outer side of insulation Estress kV 0.449 / 0.126

Radius to point x in insulation rx mm 0.70 / 2.50

Line-to-ground voltage Ue kV 0.40

Capacitance

Capacitive load current IC A/km 0.01

Charging capacity CC kvar/km 0.01

Capacitive earth short-circuit current ICe A/km 0.01

Vacuum permeability μ0 H/m 1.25664e-06

Geometric mean radius GMR mm 0.390

Geometric mean radius factor KGMR 0.779

Number of wires in conductor ncw 1

Voltage drop Vdrop V/A/km 114.9493

Short circuit currentsDuration of short-circuit tk s 0.1 | 0.2 | 0.3 | 0.5 | 1.0 | 2.0 | 3.0 | 5.0

Conductor

Permissible short-circuit current Ik kA 0.16 | 0.12 | 0.10 | 0.08 | 0.06 | 0.05 | 0.04 | 0.04

Short-circuit current (adiabatic) IkAD kA 0.14 | 0.10 | 0.08 | 0.06 | 0.04 | 0.03 | 0.03 | 0.02

Initial temperature θki °C 48.0

Final temperature θkf °C 160.0

Specific short-circuit parameter Kk A.s½/mm² 148.1

Reciprocal of temperature coefficient of resistance βk K 228

Specific heat capacity of metallic component σkc J/K.m³ 2.50e+06

Electrical resistivity of metallic component ρk20 Ω.m 2.8264e-08

Heat loss allowance factor εk 1.824

Cross-sectional area of current carrying component Sk mm² 0.50

Imperfect contact thermal factor Fk 0.9

Thermal property constant A Ak (mm²/s)½ 0.8162

Page 38: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 38

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Non-adiabatic constant C1 Ck1 mm/m 2464

Thermal property constant B Bk mm²/s 4.0410e-04

Non-adiabatic constant C2 Ck2 K.m.mm²/J 1.22

Thermal resistivity of adjacent material ρki K.m/W 3.5

Specific heat capacity of adjacent material σki J/K.m³ 2.40e+06

Screen

Permissible short-circuit current Ik kA 0.73 | 0.52 | 0.43 | 0.34 | 0.25 | 0.19 | 0.16 | 0.13

Short-circuit current (adiabatic) IkAD kA 0.70 | 0.49 | 0.40 | 0.31 | 0.22 | 0.16 | 0.13 | 0.10

Initial temperature θki °C 48.0

Final temperature θkf °C 180.0

Specific short-circuit parameter Kk A.s½/mm² 73.29

Reciprocal of temperature coefficient of resistance βk K 980

Specific heat capacity of metallic component σkc J/K.m³ 3.76e+06

Electrical resistivity of metallic component ρk20 Ω.m 7e-07

Heat loss allowance factor εk 1.347

Cross-sectional area of current carrying component Sk mm² 8.639

Imperfect contact thermal factor Fk 0.5

Thermal contact factor Mk s½ 0.2202

Thickness of screen, sheath or armour δk mm 0.5

Thermal resistivity of the layer located above ρk2 K.m/W 3.5

Thermal resistivity of the layer located below ρk3 K.m/W 3.5

Specific heat capacity of layer located below σk2 J/K.m³ 2.40e+06

Specific heat capacity of layer located above σk3 J/K.m³ 2.40e+06

System H (heat sink)

TemperaturesTemperature of heat source θhs °C 15.18

Temperature rises

Temperature rise by other buried objects Δθp K 23.0

Critical soil temperature rise Δθx K 0.0

LossesHeat accumulation by heat sink Whs W/m -40.000

ArrangementCenter position of heat source x / y mm 1900.0 / 900.0

Page 39: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 39

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

External diameter of heat source Dhs mm 100.0

Depth of laying of sources Lc mm 900.0

Substitution coefficient u u 18.000

Thermal ResistancesThermal resistance to ambient T4iii K.m/W 0.570

Mutual heating coefficient Feq 1.000

System I (heat source)

TemperaturesTemperature of heat source θhs °C 36.42

Temperature rises

Temperature rise by other buried objects Δθp K 0.2

Critical soil temperature rise Δθx K 0.0

LossesHeat release by heat source Whs W/m 40.000

ArrangementCenter position of heat source x / y mm 1700.0 / 700.0

External diameter of heat source Dhs mm 100.0

Depth of laying of sources Lc mm 700.0

Substitution coefficient u u 14.000

Thermal ResistancesThermal resistance to ambient T4iii K.m/W 0.530

Mutual heating coefficient Feq 1.000

Page 40: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 40

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Cable: 33kV, XKDT-FT 3x150 mm2 RM35Cable is used in following systems: E

General DataRated line-to-line voltage Un kV 30.0

Value of U0 for determination of test voltages U0 kV 18.0

Highest voltage for equipment Um kV 36.0

System frequency f Hz 50.0

Manufacturer Brugg Cables

ConductorNumber of conductors in object nc 3

Cross-sectional area of conductor Ac mm² 150.0

Material of conductor Mc Copper

Construction of conductor cconstr Round, stranded

Coating of wires Rco - plain

Skin effect coefficient ks 1.0

Proximity effect coefficient kp 1.0

Electrical resistivity of conductor material ρc Ω.m 1.7241e-08

DC resistance of conductor at 20°C Rco Ω/m 0.000124

Temperature coefficient of conductor material αc 1/K 0.00393

Specific heat capacity of conductor material σc J/K.m³ 3450000.0

External diameter of conductor dc mm 14.0

Thickness of s.c. tape wrapped around conductor tct mm 0

InsulationMaterial of insulation Mi Crosslinked polyethylene (XLPE)

Thickness of conductor shield tcs mm 0.6

Thickness of insulation tins mm 8.1

Thickness of insulation screen tis mm 0.4

Thickness of insulation between conductors t mm 18.2000

Max. conductor temperature θcmax °C 90.0

Max. emergency overload conductor temperature θcmaxeo °C 130.0

Max. short-circuit conductor temperature θcmaxsc °C 250.0

Page 41: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 41

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Relative permittivity of insulation εi 2.5000

Loss factor of insulation tanδi 0.0040

Thermal resistivity of insulation ρi K.m/W 3.5

Specific heat capacity of insulation material σi J/K.m³ 2400000.0

Capacitance of insulation Cb µF/km 0.1917

Vacuum permittivity ε0 F/m 8.85419e-12

Radius below the insulation rF mm 7.60

Radius of the insulation rI mm 15.70

ScreenThickness of screen bedding tscb mm 0.6

Specific heat capacity of screen bedding σscb J/K.m³ 2000000.0

Type of screen Round wires

Material of screen Msc Copper

Diameter of screen wires tsc mm 0.9

Number of screen wires nsw 54

Electrical resistance of screen Rsc Ω/km 0.5019

Specific heat capacity of screen material σsc J/K.m³ 3450000.0

Thickness of screen serving tscs mm 2.4

Specific heat capacity of screen serving σscs J/K.m³ 2000000.0

FillerMaterial of filler Mf Shaped polyvinyl chloride (PVC)

Thickness of filler/belt insulation tf mm 0.1

Thermal resistivity of filler ρf K.m/W 6.0

Specific heat capacity of filler σf J/K.m³ 1700000.0

ArmourConstruction of armour aconstr Steel wires, flat

Electrical resistance of 1st armour layer RA1Ω/km 0.5469

Thickness of 1st armour df1mm 1.2

Width of flat wires of 1st armour wf1mm 6.0

Number of wires of 1st armour na140

Length of lay of 1st armour pa1mm 500.0

Effective length per unit lay length of 1st armour Fa1mm 1.14

Cross-sectional area of armour Aa mm² 288.0

Specific heat capacity of armour material σar J/K.m³ 3800000.0

JacketMaterial of jacket Mj Polyvinyl chloride (PVC, ST1/2)

Thickness of jacket tj mm 4.10

External diameter of object De mm 96.99

Thermal resistivity of jacket material ρj K.m/W 5.0

Specific heat capacity of jacket material σj J/K.m³ 1700000.0

Page 42: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 42

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Internal thermal resistancesThermal resistance between one conductor and sheath T1 K.m/W 1.168

Thermal resistance between sheath and armour T2 K.m/W 0.000

Thermal resistance between sheath and 1st armour layer T21K.m/W 0.000

Thermal resistance of material between armour layers T22K.m/W 0.000

Thermal resistance of jacket T3 K.m/W 0.070

Thickness of insulation to sheath t1 mm 12.200

Thickness of bedding under armour t2 mm 0.000

Thickness of serving over armour t3 mm 4.100

Geometric factor G1 G1 1.8470

External diameter of the filler Df mm 86.3880

Factor αM αM 0.3105

Factor βM βM -0.0189

Factor XG XG 0.8714

Factor YG YG 0.3407

MechanicalMass of object m kg/m 14.51

Heat energy content Hc MJ/m 169.83

kWh/m 47.18

Factor of permissible pull fppc N/mm² 40.0

Permissible pull force on cable Fppc daN 1152.0

Page 43: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 43

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Cable: N2XS(FL)2Y 630Cu/50RCu mm2 110/64kVCable is used in following systems: A, B, C

General DataRated line-to-line voltage Un kV 110.0

Value of U0 for determination of test voltages U0 kV 64.0

Highest voltage for equipment Um kV 123.0

System frequency f Hz 50.0

Description XDRCU-ALT

ConductorNumber of conductors in object nc 1

Cross-sectional area of conductor Ac mm² 630.0

Material of conductor Mc Copper

Construction of conductor cconstr Round, stranded

Coating of wires Rco - plain

Skin effect coefficient ks 1.0

Proximity effect coefficient kp 1.0

Electrical resistivity of conductor material ρc Ω.m 1.7241e-08

DC resistance of conductor at 20°C Rco Ω/m 2.83e-05

Temperature coefficient of conductor material αc 1/K 0.00393

Specific heat capacity of conductor material σc J/K.m³ 3450000.0

External diameter of conductor dc mm 30.1

Thickness of s.c. tape wrapped around conductor tct mm 0.1

InsulationMaterial of insulation Mi Crosslinked polyethylene (XLPE)

Thickness of conductor shield tcs mm 1.2

Thickness of insulation tins mm 18.3

Thickness of insulation screen tis mm 1.0

Thickness of insulation between conductors t mm 41.2000

Max. conductor temperature θcmax °C 90.0

Max. emergency overload conductor temperature θcmaxeo °C 130.0

Max. short-circuit conductor temperature θcmaxsc °C 250.0

Page 44: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 44

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Relative permittivity of insulation εi 2.5000

Loss factor of insulation tanδi 0.0010

Thermal resistivity of insulation ρi K.m/W 3.5

Specific heat capacity of insulation material σi J/K.m³ 2400000.0

Capacitance of insulation Cb µF/km 0.1852

Vacuum permittivity ε0 F/m 8.85419e-12

Radius below the insulation rF mm 16.35

Radius of the insulation rI mm 34.65

ScreenThickness of screen bedding tscb mm 1.0

Specific heat capacity of screen bedding σscb J/K.m³ 2000000.0

Type of screen Round wires

Material of screen Msc Copper

Diameter of screen wires tsc mm 0.92

Number of screen wires nsw 74

Electrical resistance of screen Rsc Ω/km 0.3505

Specific heat capacity of screen material σsc J/K.m³ 3450000.0

Thickness of screen serving tscs mm 0.6

Specific heat capacity of screen serving σscs J/K.m³ 2000000.0

SheathMaterial of sheath Msh Aluminium

Thickness of the sheath tsh mm 0.25

Corrugated sheath - No

Mean diameter of sheath ds mm 76.59

Mean external diameter of the sheath Ds mm 76.84

Electrical resistance of sheath Rsh Ω/km 0.4699

Specific heat capacity of sheath material σsh J/K.m³ 2500000.0

JacketMaterial of jacket Mj Polyethylene (LD/MDPE, ST3)

Thickness of jacket tj mm 4.10

External diameter of object De mm 85.04

Thermal resistivity of jacket material ρj K.m/W 3.5

Specific heat capacity of jacket material σj J/K.m³ 2400000.0

Internal thermal resistancesThermal resistance between one conductor and sheath T1 K.m/W 0.505

Thermal resistance between sheath and armour T2 K.m/W 0.000

Thermal resistance between sheath and 1st armour layer T21K.m/W 0.000

Thermal resistance of material between armour layers T22K.m/W 0.000

Page 45: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 45

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Thermal resistance of jacket T3 K.m/W 0.056

Thickness of insulation to sheath t1 mm 22.200

Thickness of bedding under armour t2 mm 0.000

Thickness of serving over armour t3 mm 4.100

MechanicalMass of object m kg/m 10.73

Heat energy content Hc MJ/m 180.44

kWh/m 50.12

Factor of permissible pull fppc N/mm² 60.0

Permissible pull force on cable Fppc daN 3780.0

Page 46: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 46

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Cable: SOLARpower Alu-ATA 1x240/31Cable is used in following systems: F

General DataRated line-to-line voltage Un kV 1.0

Value of U0 for determination of test voltages U0 kV 0.6

Highest voltage for equipment Um kV 1.2

System frequency f Hz 0.0

ConductorNumber of conductors in object nc 1

Cross-sectional area of conductor Ac mm² 240.0

Material of conductor Mc Aluminium

Construction of conductor cconstr Round, stranded

Skin effect coefficient ks 1.0

Proximity effect coefficient kp 0.8

Electrical resistivity of conductor material ρc Ω.m 2.8264e-08

DC resistance of conductor at 20°C Rco Ω/m 0.000125

Temperature coefficient of conductor material αc 1/K 0.00403

Specific heat capacity of conductor material σc J/K.m³ 2500000.0

External diameter of conductor dc mm 17.95

Thickness of s.c. tape wrapped around conductor tct mm 0

InsulationMaterial of insulation Mi Crosslinked polyethylene (XLPE)

Thickness of conductor shield tcs mm 0

Thickness of insulation tins mm 1.9

Thickness of insulation screen tis mm 0.0

Thickness of insulation between conductors t mm 3.8000

Max. conductor temperature θcmax °C 90.0

Max. emergency overload conductor temperature θcmaxeo °C 130.0

Max. short-circuit conductor temperature θcmaxsc °C 250.0

Relative permittivity of insulation εi 2.5000

Loss factor of insulation tanδi 0.0040

Page 47: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 47

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Thermal resistivity of insulation ρi K.m/W 3.5

Specific heat capacity of insulation material σi J/K.m³ 2400000.0

Capacitance of insulation Cb µF/km 0.7243

Vacuum permittivity ε0 F/m 8.85419e-12

Radius below the insulation rF mm 8.97

Radius of the insulation rI mm 10.88

ScreenThickness of screen bedding tscb mm 1.2

Specific heat capacity of screen bedding σscb J/K.m³ 2000000.0

Type of screen Tapes

Material of screen Msc Aluminium

Diameter of screen tsc mm 0.5

Electrical resistance of screen Rsc Ω/km 0.7300

Specific heat capacity of screen material σsc J/K.m³ 2500000.0

JacketMaterial of jacket Mj Polyethylene (HDPE, ST7)

Thickness of jacket tj mm 1.90

External diameter of object De mm 28.95

Thermal resistivity of jacket material ρj K.m/W 3.5

Specific heat capacity of jacket material σj J/K.m³ 2400000.0

Internal thermal resistancesThermal resistance between one conductor and sheath T1 K.m/W 0.165

Thermal resistance between sheath and armour T2 K.m/W 0.000

Thermal resistance between sheath and 1st armour layer T21K.m/W 0.000

Thermal resistance of material between armour layers T22K.m/W 0.000

Thermal resistance of jacket T3 K.m/W 0.078

Thickness of insulation to sheath t1 mm 3.100

Thickness of bedding under armour t2 mm 0.000

Thickness of serving over armour t3 mm 1.900

MechanicalMass of object m kg/m 1.09

Heat energy content Hc MJ/m 13.06

kWh/m 3.63

Factor of permissible pull fppc N/mm² 30.0

Page 48: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 48

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Permissible pull force on cable Fppc daN 720.0

Page 49: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 49

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Cable: FO RampionWarning! Resistance for aluminium conductors of sizes below 10 mm2 is acc. to ASTM B231-04.Cable is used in following systems: G

General DataRated line-to-line voltage Un V 400

Value of U0 for determination of test voltages U0 V 230

Highest voltage for equipment Um V 440

System frequency f Hz 50.0

Manufacturer Prysmian

Description Fake electrical cable for FO trail

ConductorNumber of conductors in object nc 1

Cross-sectional area of conductor Ac mm² 0.5

Material of conductor Mc Aluminium

Construction of conductor cconstr Round, stranded

Skin effect coefficient ks 1.0

Proximity effect coefficient kp 0.8

Electrical resistivity of conductor material ρc Ω.m 2.8264e-08

DC resistance of conductor at 20°C Rco Ω/m 0.05747

Temperature coefficient of conductor material αc 1/K 0.00403

Specific heat capacity of conductor material σc J/K.m³ 2500000.0

External diameter of conductor dc mm 1.0

Thickness of s.c. tape wrapped around conductor tct mm 0.1

InsulationMaterial of insulation Mi High density polyethylene (HDPE)

Thickness of conductor shield tcs mm 0.1

Thickness of insulation tins mm 1.8

Thickness of insulation screen tis mm 0.0

Thickness of insulation between conductors t mm 4.0000

Max. conductor temperature θcmax °C 80.0

Max. emergency overload conductor temperature θcmaxeo °C 80.0

Page 50: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 50

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Max. short-circuit conductor temperature θcmaxsc °C 160.0

Relative permittivity of insulation εi 2.3000

Loss factor of insulation tanδi 0.0010

Thermal resistivity of insulation ρi K.m/W 3.5

Specific heat capacity of insulation material σi J/K.m³ 2400000.0

Capacitance of insulation Cb µF/km 0.1005

Vacuum permittivity ε0 F/m 8.85419e-12

Radius below the insulation rF mm 0.70

Radius of the insulation rI mm 2.50

ScreenType of screen Tapes

Material of screen Msc Stainless steel

Diameter of screen tsc mm 0.5

Electrical resistance of screen Rsc Ω/km 81.0243

Specific heat capacity of screen material σsc J/K.m³ 3760000.0

JacketMaterial of jacket Mj Polyethylene (HDPE, ST7)

Thickness of jacket tj mm 2.00

External diameter of object De mm 10.00

Thermal resistivity of jacket material ρj K.m/W 3.5

Specific heat capacity of jacket material σj J/K.m³ 2400000.0

Internal thermal resistancesThermal resistance between one conductor and sheath T1 K.m/W 0.897

Thermal resistance between sheath and armour T2 K.m/W 0.000

Thermal resistance between sheath and 1st armour layer T21K.m/W 0.000

Thermal resistance of material between armour layers T22K.m/W 0.000

Thermal resistance of jacket T3 K.m/W 0.285

Thickness of insulation to sheath t1 mm 2.000

Thickness of bedding under armour t2 mm 0.000

Thickness of serving over armour t3 mm 2.000

MechanicalMass of object m kg/m 0.13

Factor of permissible pull fppc N/mm² 30.0

Permissible pull force on cable Fppc daN 1.5

Page 51: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 51

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Cable: N2XS2Y 240Cu/25RCu mm2 20/12kVCable is used in following systems: D

General DataRated line-to-line voltage Un kV 20.0

Value of U0 for determination of test voltages U0 kV 12.0

Highest voltage for equipment Um kV 24.0

System frequency f Hz 50.0

Description acc. VDE 0276 / HD 620 5-C

ConductorNumber of conductors in object nc 1

Cross-sectional area of conductor Ac mm² 240.0

Material of conductor Mc Copper

Construction of conductor cconstr Round, stranded

Coating of wires Rco - plain

Skin effect coefficient ks 1.0

Proximity effect coefficient kp 1.0

Electrical resistivity of conductor material ρc Ω.m 1.7241e-08

DC resistance of conductor at 20°C Rco Ω/m 7.54e-05

Temperature coefficient of conductor material αc 1/K 0.00393

Specific heat capacity of conductor material σc J/K.m³ 3450000.0

External diameter of conductor dc mm 18.9

Thickness of s.c. tape wrapped around conductor tct mm 0.1

InsulationMaterial of insulation Mi Crosslinked polyethylene (XLPE)

Thickness of conductor shield tcs mm 0.8

Thickness of insulation tins mm 5.5

Thickness of insulation screen tis mm 0.4

Thickness of insulation between conductors t mm 13.6000

Max. conductor temperature θcmax °C 90.0

Max. emergency overload conductor temperature θcmaxeo °C 130.0

Max. short-circuit conductor temperature θcmaxsc °C 250.0

Page 52: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 52

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Relative permittivity of insulation εi 2.5000

Loss factor of insulation tanδi 0.0040

Thermal resistivity of insulation ρi K.m/W 3.5

Specific heat capacity of insulation material σi J/K.m³ 2400000.0

Capacitance of insulation Cb µF/km 0.3263

Vacuum permittivity ε0 F/m 8.85419e-12

Radius below the insulation rF mm 10.35

Radius of the insulation rI mm 15.85

ScreenThickness of screen bedding tscb mm 0.6

Specific heat capacity of screen bedding σscb J/K.m³ 2000000.0

Type of screen Round wires

Material of screen Msc Copper

Diameter of screen wires tsc mm 0.92

Number of screen wires nsw 36

Electrical resistance of screen Rsc Ω/km 0.7204

Specific heat capacity of screen material σsc J/K.m³ 3450000.0

JacketMaterial of jacket Mj Polyethylene (LD/MDPE, ST3)

Thickness of jacket tj mm 2.45

External diameter of object De mm 40.44

Thermal resistivity of jacket material ρj K.m/W 3.5

Specific heat capacity of jacket material σj J/K.m³ 2400000.0

Internal thermal resistancesThermal resistance between one conductor and sheath T1 K.m/W 0.322

Thermal resistance between sheath and armour T2 K.m/W 0.000

Thermal resistance between sheath and 1st armour layer T21K.m/W 0.000

Thermal resistance of material between armour layers T22K.m/W 0.000

Thermal resistance of jacket T3 K.m/W 0.072

Thickness of insulation to sheath t1 mm 7.400

Thickness of bedding under armour t2 mm 0.000

Thickness of serving over armour t3 mm 2.450

MechanicalMass of object m kg/m 3.30

Heat energy content Hc MJ/m 34.91

kWh/m 9.70

Page 53: Sample Calculation Flyer - Cableizer

Title: Sample Calculation Flyer 2019-08-15 12:20 / page 53

Cableizer specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability, accuracy, or fitness for anyparticular purpose. In no event shall Cableizer be liable to any party for any damages arising out of the use of information in this document.

Factor of permissible pull fppc N/mm² 60.0

Permissible pull force on cable Fppc daN 1440.0