8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
1/63
NetSure 501 AC0Training Slides
Allon Pan
Product Manager, DC Asia-Pacific
Kevin Yang
Design Project Manager, DC Asia-Pacific
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
2/63
Telecom Sales Training Sep 29
Agenda
ACTURA Flex 48420 Introduction
Large System Concept
Product Roadmap
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
3/63
Telecom Sales Training Sep 29
- Mobile base station
- Small exchange station
- Satellite communication
- Data communication
-
Generally: Sites requiring DC power with load max 20.4 kW
Applications
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
4/63
Telecom Sales Training Sep 29
System Principles
AC Input Terminals
C Class SPD
Rectifier ACBreakers
Rectifiers
Back Board Control Unit
Priority load
LLVD(Optional)
Non-priority Load
BLVD
Battery 1
Battery n
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
5/63
Telecom Sales Training Sep 29
Key Benefits High power and battery density
Up to 20.4kW and 660Ah in 1 cabinet Front Access
Can be mounted against wall and with cabinets on either side
Minimum floor space required
High flexibility and wide variety of ordering options Output power, system: 1.7 20.4 kW
Standard or advanced controller
Configurable number of distribution circuit breakers, and sizes Configurable number of battery circuit breakers, and sizes
With or without Priority and Non-Priority Low Voltage Disconnect
Various AC options with/without SPD and AC breakers
1800 or 2000 mm cabinets, 600 and 400mm depths
Single cabinet solution, with or without batteries
Extended battery cabinet available
Based on Global Building Block (Rectifier and Controller) Utilizes UL approved rectifier R48-1800
Hot pluggable rectifier and controller (ACU or SCU)
Wide operating range Input voltage range (85-300Vac)
Input temperature range (-5 to +55C)
Suitable for harsh conditions
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
6/63
Telecom Sales Training Sep 29
600 x 600 x 2000mm (WxDxH) cabinet Up to 20.4kW (12 x 1700W) + 4 x 165Ah (or 5 x 100Ah) batteries
Battery shelves adjustable to cater for different battery sizes
600 x 400 x 2000mm (WxDxH) cabinet
Up to 20.4kW (12 x 1700W) + 5 x 100Ah batteries
Battery shelves adjustable to cater for different battery sizes
600 x 600 x 1800mm (WxDxH) cabinet
Up to 20.4kW + 3 x 165Ah (or 4 x 100Ah) batteries
Battery shelves adjustable to cater for different battery sizes
High Power and Battery Density, Small Footprint
Save site floor space, save site construction cost
Value added to Customer:
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
7/63
Telecom Sales Training Sep 29
Friendly to Maintain and Monitor
Front access
Hot replaceable rectifiers and controllers
User-friendly controller unit with fault alarms and history log
Remote monitoring applicable
SM-IOSM-BAT
RS485
Site SM-AC
TCP/IP
ACU
EXMG,ENECPSMS
SiteScan
Web Browser
Nform
HTTP, SNMP
EEM protocol
Save maintaining time, save site visiting labour
Value added to Customer:
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
8/63
Telecom Sales Training Sep 29
Flexible and Scalable Power System
Fullfill various demand of capacity and functionality
1.7 kW
3 cabinet sizes600W x 600D x 2000H (mm)600W x 400D x 2000H (mm)600W x 600D x 1800H (mm)
Batteries, 12V front terminal
In 600 deep, 2000 high5 x 100 Ah (500 Ah)
4 x 165 Ah (660 Ah)
In 400 deep, 2000 high5 x 100 Ah (500 Ah)
In 600 deep, 1800 high4 x 100 Ah (400 Ah)3 x 165 Ah (495 Ah)
2m cabinet 2m cabinet 1.8 cabinet 1.8mcabinet
20.4 kW
Value added to Customer:
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
9/63
Telecom Sales Training Sep 29
Wide AC Input Range
R48-1800 Advantages: DC power output at 85 300 Vac input
Non-destructive 0 415 Vac input
No need to over-dimension the power system in order tocope with input voltage / output voltage peaks
Value added to Customer:
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
10/63
Telecom Sales Training Sep 29
Wide Operating Temperature Range
R48-1800 Advantages: Rectifier Operating temperature: -40C ~ 80C
System Operating temperature: -5C ~ 55C
No need to over-dimension the power system in order tocope with temperature
Value added to Customer:
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
11/63
Telecom Sales Training Sep 29
Emerson Brand Total Solution of Surge Protection
Protect investment, reduce down time
Value added to Customer:
AC Input
Rectifier
Rectifier
Rectifier
AC powerdistribution
unit
DC powerdistribution
unit
Standardcontrol unit
Batterygroup
I/BSPD
II/CSPD
MODEM
RJ11
SPD
48V Output
RS232
RJ11
5~10m
PSTN
Remote monitoring host
Note:
I, II, III are based on IEC standard
B, C, D are based on German VDE standard
DINVED0675-6: 1989-11 (draft)
Dist.SPD
II/D SPD Built-in Rectifier
ANYGUARDEmerson Brand
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
12/63
Telecom Sales Training Sep 29
Main and Extension Battery cabinets
Double the batteries to sustain long time AC fault
Value added to Customer:
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
13/63
Telecom Sales Training Sep 29
System Components
Cabinet
Multi Function Unit (MFU)
SCU (M500D, M501D) and ACU (M800D)
Rectifier (R48-1800)
Extension Distribution Unit (DU)
Rectifier sub-rack
Excellence, Duration
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
14/63
Telecom Sales Training Sep 29
Multi Function Unit (MFU)
Maximum 19 positions, configurable for AC breakers, SPD andHigh/Low Priority Load breakers (max 10 load breakers)
Front access AC input terminals
3 x 70mm2 and 7 x 25mm2 positive load connections
Optional BLVD and LLVD contactors
ACU or SCU controller options
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
15/63
Telecom Sales Training Sep 29
MFU Configuration
No. Component Description
1 AC Main
Single Phase 220, Phase-phase 220V,
Three Phase 220/380V,
Single feed
2 SPDAC side 8/20 us 20kA,5 times /
AC side 8/20 us 40kA, 1 time
3 AC input cable Max 35sq mm
4 AC input terminals Rating Current 125A
5 Rectifier AC input MCB Rating Current 16A
6 BLVD contactor 200A or 400A optional
7 LLVD contactor 200A or 400A optional
8 Shunt 500A/75mV9 Cable to battery 25sq mm
10 Battery MCB 100A / 200A MCB (up to 5 battery MCBs)
11 Load MCB Selected according to users requirement
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
16/63
Telecom Sales Training Sep 29
Multi Function Unit Detail
Load breakers
Positive Common
Surge Protection
AC Input terminals
AC Input breakers
Back Board
Alarm Connector Board
Controller Slot
LLVD
BLVD
LLVD Negative
BLVD Negative
Battery Negative
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
17/63
Telecom Sales Training Sep 29
Extension Distribution Unit (DU)
3U high, 23 wide
Maximum 28 positions configurable for Low or High Priority Loadbreakers (18mm type)
7 x 70mm2 and 32 x 25mm2 positive common connections
Circuit breaker alarm monitoring
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
18/63
Telecom Sales Training Sep 29
Distribution Unit Detail
LLVD Bus Bar
BLVD Bus Bar
Load Breakers Cage ClampTerminal
CB Alarm Board
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
19/63
Telecom Sales Training Sep 29
Rectifiers: R48-1800
DSP (Digital Signaling Processor)Means fewer components, optimized operation andactive load sharing for increased reliability
Compliant with global standardsDelivers quality, performance and reliability no matterwhat the application or location demands
High efficiency, up to 91%Reduces power consumption for lower operating costsHot pluggable
Facilitates future extensions
Wide input voltage range (85V to 300V)Operates in the most demanding environments where
input voltage changesWide temperature operating range (-40C to +80C)
Meets the harshest climatic environment requirements
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
20/63
Telecom Sales Training Sep 29
Rectifier Technical Data
Input voltage window
Non-destructive voltage
Power factor
THD
Output voltage
Output power
Max output currentEfficiency
Temperature range
RH (non-condensing)
EMC
Safety
DimensionsWeight
IEC / EN / UL 60950
86H (2U) x 84.5W (2U) x 272D (mm)1.8 kg
-42 to -58 VDC
91%
0 to 95%
-40 to +80 C
R48-1800
1700 W
35.4 A
EN 300 386:2001, class B
85 to 300 VAC
0 to 415 VAC
0.99
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
21/63
Telecom Sales Training Sep 29
Rectifier Lay-Out
Protection indicatorAlarm indicator
Bolt
Power Indicator
Handle
Input Socket
Output Socket
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
22/63
Telecom Sales Training Sep 29
BCU - Battery Connection Unit
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
23/63
Telecom Sales Training Sep 29
BCU DetailsEnclosure
-48V DC Bus
Battery MCB
Up to 5 x 100A
Or
Up to 5 x 200A
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
24/63
Telecom Sales Training Sep 29
Controller SCU / ACU
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
25/63
Telecom Sales Training Sep 29
ACU&SCU Hardware Interfaces
3 LEDs to
indicate alarms andoperation conditions
DC power input
19-60 V
1 RS 485 for
communicationwith SM
2 Temp. sensor
inputs
Ethernet, RJ 45
HTTP, SNMP, FTP1 RS 232 DB 9 port
8 outgoing
alarm/control
relays
8 digital inputs for generic
alarms
Connector board
Bi-BLVD
Bi-LLVD
10 Digital in for DU
4 Digital in for BCU
2 LVD for disconnect of batteries and load
1 RS 232 for Console
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
26/63
Telecom Sales Training Sep 29
Connector Board
User interface board- 8 outgoing alarm relay contacts- 8 incoming digital inputs- 2 temperature sensor inputs- 2 RS232 (for modem / PC interface)- 1 Ethernet port (used with ACU only)- 1 RS485 port (used with ACU only)
Connector board
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
27/63
Telecom Sales Training Sep 29
Back Board
Interfaces the controller to the power supply system- Distribution CB alarm inputs- Battery CB alarm inputs- System shunt- System voltage measurement- CAN bus for rectifier communication
- LLVD & BLVD contactor driver outputs
Back Board
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
28/63
Telecom Sales Training Sep 29
SCU / ACU Features
Function SCU ACU
Local Display Yes (128X64) Yes (128X64)
Web No Yes
SNMP No DC Power MIB
EEM protocol Yes Yes
SOC/TPE protocol Yes Yes
YDN 23 protocol Yes NoActive Alarms on LCD Yes Yes
Alarm History Yes 200 Yes 400
Statistics/Logs Basic battery log Advanced battery &Events log
PLC function AND/OR/XOR ../NOT/TIMER/LEVEL
Firmware download No Yes TELNET
Energy Savings No Yes
Alarm relay output Yes 8 Yes 8
Power Split No Yes
SM Support No Yes 13 SM Units
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
29/63
Telecom Sales Training Sep 29
SCU / ACU Features, ContinuedFunction SCU ACU
Temp charging Yes YesBoost charging Yes Yes
Battery current limitation Yes Yes
Battery discharge test Const current/Volt level Const current/Volt level
Battery prediction Yes Yes
Battery tables 10 10
Current walk in settings Yes Yes
External alarm inputs 8 8
LVD 2 2
System Voltage Yes Yes
Battery Currents Yes 2 Yes 2
Battery Fuse Input 4 4
Distribution Alarm Inputs 10 10
Distribution Currents 1 1
Temperature Sensor 2 2
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
30/63
Telecom Sales Training Sep 29
July August October November
August
Internal LaunchDatasheetPricingPresentation
September 1stAvailable to offer to
customers
M1 M2 M3
October 1stAccept first
orders
Pilot
Mass
ProductionPrototypes
September
Market Introduction Milestones
M3
November 15thFirst deliveries
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
31/63
Telecom Sales Training Sep 29
Marketing Collateral
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
32/63
Telecom Sales Training Sep 29
Product Positioning
Optima 48200
Flex 48420(Basic)
Flex 48330
Flex 48420(Max)
6.4 + 3.2kW330Ah batteriesOpen Rack (1.6m)Ext DU optional
8.5 + 1.7kW495Ah batteriesCabinet (1.8m)Ext DU optional
12.8 + 3.2kW660Ah batteries
Cabinet (2m)
18.7 + 1.7kW660Ah batteries
Cabinet (2m)Ext DU optional
Capacity / Features
Price
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
33/63
Telecom Sales Training Sep 29
Agenda
Small BTS Introduction
Large System Concept
Product Roadmap
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
34/63
Telecom Sales Training Sep 29
Goals of Program
Develop a cost effective, high performancereplacement for ACTURA Flex 48800 and SilcarLPS and MPS systems
Combine all products into a single platform if
possible, improving production and supportlogistics and reducing cost
Utilise new 100A rectifier GBB and AdvancedControl Unit (ACU)
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
35/63
Telecom Sales Training Sep 29
Large System Concept
Replacement for Flex 48800and existing LPS and MPS
Maximum 48 x 100A rectifiermodules (max 5760A @ 48V)
Minimum 1, Maximum 8cabinets (Rectifier and DU)
Maximum 32 battery breakers /fuses
LVD external to cabinet (atbatteries), or using trip coils(manual reset) on BCB incabinets
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
36/63
Telecom Sales Training Sep 29
Two basic cabinet types
Rectifier Cabinet Distribution Cabinet
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
37/63
Telecom Sales Training Sep 29
Large System Rect Cabinet - Constraints
Maximum 16 rectifier modules per rectifier cabinet
Maximum 4 x NT4 fuses or NS250 breakers per cabinet(battery or load)
Built in AC distribution in rectifier cabinet
Max 2 AC DU, each with AC input terminals and 8 3-pole rectifierbreakers
A + B AC feed possible
2 x 3U DC CB DU or 1 x 6U DC fuse DU per rectifier
cabinet
Rectifier Cabinet
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
38/63
Telecom Sales Training Sep 29
Rectifier CabinetLayout
Positive Bar
NT4 Fuse /NS250 breaker
Battery Shunt
Negative Bar
2 x 3U DU/1 x 6U DU
ACU
2 x AC DU
Rectifiers
Maximum 16 rectifier
modules per rectifier cabinet
Maximum 4 x NT4 fuses orNS250 breakers per cabinet(battery or load)
Built in AC distribution in
rectifier cabinetMax 2 AC DU, each withAC input terminals and 8 3-pole rectifier breakers
A + B AC feed possible
2 x 3U DC CB DU or 1 x 6UDC fuse DU per rectifiercabinet
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
39/63
Telecom Sales Training Sep 29
Large System DU Cabinet - Constraints
Maximum 4 x NT4 fuses or NS250 breakers percabinet (battery or load)
Possibility to mount the following:
6-8U high DU with 6 x NT2 fuses
3 U high DU with up to 35 HOD breakers (CBI) 3U high DU with up to 28 LOD breakers (ABB)
Possible to plug in or add DUs in field?
Distribution
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
40/63
Telecom Sales Training Sep 29
DistributionCabinet Layout
Positive Bar
NT4 Fuse /NS250 breaker
Battery Shunt
Negative Bar
3 x 6U DU, or6 x 3U DU, orcombination
Maximum 4 x NT4 fuses or
NS250 breakers percabinet (battery or load)
Possibility to mount thefollowing:
6-8U high DU with 6 x
NT2 fuses 3 U high DU with up to
35 HOD breakers(CBI)
3U high DU with up to28 LOD breakers
(ABB) Possible to plug in or
add DUs in field?
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
41/63
Telecom Sales Training Sep 29
High Ohmic Distribution Unit
Up to 35 breakers perDU (3U high)
15A or 2 pole 30A HighOhmic breakers
Up to 2 x DU per
Rectifier Cabinet Up to 6 x DU per
Distribution Cabinet
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
42/63
Telecom Sales Training Sep 29
Low Ohmic Distribution Unit
3U high, 23 wide
Maximum 28 positions configurable for Low or HighPriority Load breakers (18mm type)
Ratings 3A to 100A (18mm), 125A (27mm)
7 x 70mm2 and 32 x 25mm2 positive commonconnections
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
43/63
Telecom Sales Training Sep 29
Fuse Distribution Unit
6U high, 23 wide
Maximum 6 Fuses (NT2) up to 630A
Positive Connections via Positive Common Barat top of cabinet
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
44/63
Telecom Sales Training Sep 29
Typical 2 cabinet layout
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
45/63
Telecom Sales Training Sep 29
Example 3 cabinet layouts
2 Rec + 1 DU 2 DU + 1 Rec 3 Rec
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
46/63
Telecom Sales Training Sep 29
Example 5 cabinet layouts
2 Rec + 3 DU 3 Rec + 2 DU
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
47/63
Telecom Sales Training Sep 29
Example 5 cabinet layouts
5 Rec
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
48/63
Telecom Sales Training Sep 29
LPS Implementation
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
49/63
Telecom Sales Training Sep 29
MPS Implementation
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
50/63
Telecom Sales Training Sep 29
Large Rectifier R48-5800
Faceplate
Horizontal in 23 inch cabinet Vertical in 23 inch cabinet
Rectifier R48-5800
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
51/63
Telecom Sales Training Sep 29
Rectifier Technical Data
Product Name R48-5800
Input voltage window 260 to 530 VAC (Full power from 304 to 530 Vac)
Non-destructive voltage 0 to 600 VAC
Power factor 0.99
THD
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
52/63
Telecom Sales Training Sep 29
ACU (Advanced Controller Unit)
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
53/63
Telecom Sales Training Sep 29
ACU Technical Data Part I
Function ACU
Local Display Yes (128X64)
Web Yes
SNMP DC Power MIB
EEM protocol Yes
SOC/TPE protocol Yes
YDN 23 protocol Yes
Active Alarms on LCD Yes
Alarm History Yes 400
Statistics/Logs Advanced battery & Events log
PLC function AND/OR/XOR/NOT/TIMER/LEVEL
Firmware download Yes TELNETEnergy Savings Yes
Alarm relay output Yes 8
Power Split Yes
SM Support Yes 13 SM Units
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
54/63
Telecom Sales Training Sep 29
ACU Technical Data Part II
Function ACU
Temp charging Yes
Boost charging Yes
Battery current limitation Yes
Battery discharge test Const current/Volt level
Battery prediction Yes
Battery tables 10
Current walk in settings Yes
External alarm inputs 8
LVD 2
System Voltage Yes
Battery Currents Yes 2Battery Fuse Input 4
Distribution Alarm Inputs 10
Distribution Currents 1
Temperature Sensor 2
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
55/63
Telecom Sales Training Sep 29
Agenda
Small BTS Introduction
Large System Concept
Product Roadmap
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
56/63
Telecom Sales Training Sep 29
Road Map Micro / Mini
*
Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 H1 H2 H1 H2
GIE 4805/GIE 4815 5/15A
Mini48 300W 2x3U
Actura 48 201 (ph1) 400/800W 1x2U
Actura 48 201 (ph2)
Actura 48 101 300W 1.5x2UEN
P-AP
FY09FY05 FY06 FY07 FY08
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
57/63
Telecom Sales Training Sep 29
Mini System Lineup
ACTURA 48201
ACTURA 48101
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
58/63
Telecom Sales Training Sep 29
Roadmap - Small
Control Rect. Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 H1 H2 H1 H2
Actura Optima 48130 1200W
Menu 1500W 3x2U
PS 48300/ 48350/48160 25A
Actura Flex 48420 1700W 2x2U
PS 48120&300/1800 1740W 2x2U
PS 48100-2/25 1450W, 3x2U
PS 48300-3/30 1740W, 3x2U
PS 48120&300/1800 1740W 2x2U
LTB GBB avail. GBB system
ENPC
FY08Cost
ENP-AP
FY09FY05 FY06 FY07
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
59/63
Telecom Sales Training Sep 29
Small System Lineup
PS48120 / PS48300 Flex 48420
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
60/63
Telecom Sales Training Sep 29
Road Map Medium
Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 H1 H2 H1 H2
Actura 4827 2700W 2x19"
Actura F 2700W 2x19"
Silcar MPS/LPS 2700W 2x19"
PS48400/48600 50A
Actura Flex 48330 2900W 2x3U
PS48400/48600
Silcar MPS/LPS
Low Cost BTS
29000W 2x2U
LTB GBB avail. ENPC EES GBB system
FY09FY05 FY06 FY07 FY08
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
61/63
Telecom Sales Training Sep 29
Medium System Lineup
ACTURA Optima 48200
ACTURA Flex 48330
PS48600
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
62/63
Telecom Sales Training Sep 29
Control Rect. Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 Q1 Q2 Q3 Q4 H1 H2 H1 H2
Actura 4860 6000W 4x19" Partly replaced by 50A
PS 481500 5800W 2x19",
Flex 481000 100A 2x5,5U
PS481000-6/100 100A 2x5,5U
Cost FY09FY05 FY06 FY07 FY08
Roadmap - Large
8/3/2019 Sales Training Slides - NetSure 501 AC0 (Actura Flex 48420)
63/63
Large System Lineup
PS481000-6 New Large (AP)