HEAT LOAD FORM (computerized computation) Prepared by : Galang, John Martin L Date : October 30, 2015 Name of Job : S202 Prop. No. : : Space used for : Approve : Size ## 406.683 * 11.42 = 4644.31415 cu. ft. ITEM AREA OR QUANTITY FACTOR BTU/HOUR Estimate for local time Peak Load local ti Sun time sun tim SOLAR GAIN -LOSS Hours of Operation: 10 Hours GLASS 55.9444 SQ. FT. x 15.2 x 0.7605 646.69 CONDITIONS DB WB %RH DP GR/L GLASS SQ. FT. x x 0.00 F F % GLASS SQ. FT. x x 0.00 Outdoor (OA) 97 81 51 76 135 GLASS SQ. FT. x x 0.00 SKYLIGHT 0 SQ. FT. x x 0.00 Room (RM) 75 62.6 50 55 65 SOLAR & TRANS. GAIN - WALLS & ROOF Difference 22 XXX XXX XXX 70 NW WALLS 255.72916667 SQ. FT. x 23.1 9 x 0.47 3858.19 SW WALLS SQ. FT. x x 0.00 OUTDOOR AIR NE WALLS SQ. FT. x x 0.00 SE WALLS SQ. FT. x x 0.00 VENTI-LATION 30 PEOPLE x 15 CFM/PERSON = ROOF-SUN 0 SQ. FT. x x 0.00 SQ. FT. x CFM/SQ. FT = ROOF-SHADED 0 SQ. FT. x x 0.00 CFM VENTILATION = 450 TRANS. GAIN - EXCEPT WALLS & ROOF INFIL-TRATION CFM/PERSON = ALL GLASS 94.6944 SQ. FT. x 22 x 0.54 1124.97 PARTITION 300.89583 SQ. FT. x 17 x 0.4 2046.09 OPEN DOORS 0 0 CFM/DOOR = PARTITION 0 SQ. FT. x x 0.00 EXHAUST FAN 0 FLOOR SQ. FT. x x 0.00 CRACK 0 0 CFM/FEET = INFILTRATION 0 CFM x x 0.00 CFM INFILTRATION = 0 CFM OUTDOOR AIR THRU OPERATION = 450 CFM INTERNAL HEAT APPARATUS DEW POINT PEOPLE 30 PEOPLE 220.5 6615.00 ESHF = 19557.17 EFFECTIVE ROOM SENS. HEAT POWER 850 WATTS 3.41 2898.50 27234.17 EFFECTIVE ROOM TOTAL HEAT LIGHTS 448 WATTS 3.41 x 0.85 1298.53 ESHF = 0.7181 APPLIANCES ETC. 0.00 ADDITIONAL HEAT GAINS 0.00 ADP INDICATED ADP 46.5 SELECTED ADP = 46.5 SUBTOTAL 18487.97 STORAGE SQ. FT x ) 0.00 DEHUMIDIFIED AIR QUANTITY SUBTOTAL 18487.97 TEMP RISE ( 1 - 0.1) 75 46.5 F) = SAFETY FACTOR 0.00 ROOM SENSIBLE HEAT 18487.97 DEHUM CFM 19557.17 FECTIVE ROOM SENS. HE = 705.984 CFMda 0.00 1.08 x 25.65 + + 18487.97 ROOM SENSIBLE HEAT = 24.248 F(rm-outlet) 1.08 x 705.98 % % % OUTDOOR AIR 450 22 0.1 x 1.08 1069.20 SUPPLY AIR QUANTITY EFFECTIVE ROOM SENSIBLE HEAT 19557.17 LATENT HEAT SUPPLY CFM ROOM SENSIBLE HEAT = CFMsa 1.08 x INFILTRATION CFM Gr/lb x 0.00 PEOPLE 30 PEOPLE 184.5 5535.00 DEHUM CFM - = 0.000 STEAM LB-HR 0.00 APPLIANCES ETC. 0.00 RESULTING ENT. & LVG CONDITIONS AT APPARATUS ADDITIONAL HEAT GAINS 0.00 VAPOR TRANS SQ. FT x 0.001 x Gr/lbs x 0.00 EDB 75 + 450 x ( 97 - 75 SUBTOTAL 5535.00 705.98 CFM = 89.0229798 SAFETY FACTOR 0.00 LDB 46.5 + 0.1 x ( 89.0229798 - 46.5 ROOM LATENT HEAT 5535.00 = 50.752298 SUPPLY DUCT LEAKAGE % o FROM PSYCH. CHART: F F OUTDOOR AIR 450 70 Gr/lbs 0.1 0.68 2142.00 EFFECTIVE ROOM LATENT HEAT 7677.00 RC = GTH = 4.6779 tons EFFECTIVE ROOM TOTAL HEAT 27234.17 12000 OUTOOOR AIR HEAT SQ. FT = TOTAL AREA 406.6825 = 86.94 SENSIB 450 CFMx 22 F x ( 0.1 BF) x 1.08 9622.80 LB RC 4.6779 LATENT 450 CFMx 70 Gr/lb x ( 0.1 BF) x 0.68 19278.00 SUBTOTAL 28900.80 + + + 0.00 % % % GRAND TOTAL HEAT 56134.97 SUN GAIN OR Temp. diff. SWINGING REVOLVING DOORS E SENS. HEAT FACTOR SUPPL Y DUCT HEAT GAIN SUPP LY DUCT LEAK FAN H.P. OUTLET TEMP DIFF CFM x F x CFM x RETUR N DUCT HEAT GAIN RETUR N DUCT LEAK GAIN HP PUM P AN D PIP

S202 (4)

Embed Size (px)

DESCRIPTION

airocn

Citation preview

Page 1: S202 (4)

HEAT LOAD FORM (computerized computation)Prepared by : Galang, John Martin L Date : October 30, 2015

Name of Job : S202 Prop. No. : :

Space used for : Approve :

Size ### 406.683 * 11.42 = 4644.31415 cu. ft.

ITEM AREA OR QUANTITY FACTOR BTU/HOUR Estimate forlocal time

Peak Loadlocal time

Sun time sun time

SOLAR GAIN -LOSS Hours of Operation: 10 Hours

GLASS 55.9444 SQ. FT. x 15.2 x 0.7605 646.69CONDITIONS

DB WB %RH DPGR/LB

GLASS SQ. FT. x x 0.00 F F %GLASS SQ. FT. x x 0.00

Outdoor (OA) 97 81 51 76 135GLASS SQ. FT. x x 0.00

SKYLIGHT 0 SQ. FT. x x 0.00Room (RM) 75 62.6 50 55 65

SOLAR & TRANS. GAIN - WALLS & ROOFDifference 22 XXX XXX XXX 70

NW WALLS 255.72916667 SQ. FT. x 23.1 9 x 0.47 3858.19SW WALLS SQ. FT. x x 0.00 OUTDOOR AIRNE WALLS SQ. FT. x x 0.00SE WALLS SQ. FT. x x 0.00

VENTI-LATION

30 PEOPLE x 15 CFM/PERSON =ROOF-SUN 0 SQ. FT. x x 0.00 SQ. FT. x CFM/SQ. FT =

ROOF-SHADED 0 SQ. FT. x x 0.00 CFM VENTILATION = 450

TRANS. GAIN - EXCEPT WALLS & ROOF

INFIL-TRATION

CFM/PERSON =ALL GLASS 94.6944 SQ. FT. x 22 x 0.54 1124.97PARTITION 300.89583 SQ. FT. x 17 x 0.4 2046.09 OPEN DOORS 0 0 CFM/DOOR =PARTITION 0 SQ. FT. x x 0.00 EXHAUST FAN 0FLOOR SQ. FT. x x 0.00 CRACK 0 0 CFM/FEET =

INFILTRATION 0 CFM x x 0.00 CFM INFILTRATION = 0

CFM OUTDOOR AIR THRU OPERATION = 450 CFMINTERNAL HEAT

APPARATUS DEW POINT

PEOPLE 30 PEOPLE 220.5 6615.00

ESHF=

19557.17 EFFECTIVE ROOM SENS. HEATPOWER 850 WATTS 3.41 2898.50 27234.17 EFFECTIVE ROOM TOTAL HEATLIGHTS 448 WATTS 3.41 x 0.85 1298.53 ESHF = 0.7181APPLIANCES ETC. 0.00ADDITIONAL HEAT GAINS 0.00 ADP INDICATED ADP 46.5 SELECTED ADP = 46.5

SUBTOTAL 18487.97

STORAGE SQ. FT x ) 0.00 DEHUMIDIFIED AIR QUANTITYSUBTOTAL 18487.97 TEMP RISE ( 1 - 0.1) 75 46.5 F) =

SAFETY FACTOR 0.00

ROOM SENSIBLE HEAT 18487.97DEHUM CFM 19557.17EFFECTIVE ROOM SENS. HEAT = 705.984 CFMda

0.00

1.08 x 25.65

+ +

18487.97 ROOM SENSIBLE HEAT= 24.248 F(rm-outlet)

1.08 x 705.98

% % %

OUTDOOR AIR 450 22 0.1 x 1.08 1069.20SUPPLY AIR QUANTITY

EFFECTIVE ROOM SENSIBLE HEAT 19557.17

LATENT HEATSUPPLY CFM

ROOM SENSIBLE HEAT= CFMsa

1.08 xINFILTRATION CFM Gr/lb x 0.00PEOPLE 30 PEOPLE 184.5 5535.00 DEHUM CFM - = 0.000

STEAM LB-HR 0.00

APPLIANCES ETC. 0.00RESULTING ENT. & LVG CONDITIONS AT APPARATUSADDITIONAL HEAT GAINS 0.00

VAPOR TRANS SQ. FT x 0.001 x Gr/lbs x 0.00 EDB 75 + 450 x ( 97 - 75

SUBTOTAL 5535.00 705.98 CFM = 89.0229798

SAFETY FACTOR 0.00 LDB 46.5 + 0.1 x ( 89.0229798 - 46.5

ROOM LATENT HEAT 5535.00 = 50.752298SUPPLY DUCT LEAKAGE % o FROM PSYCH. CHART: F F

OUTDOOR AIR 450 70 Gr/lbs 0.1 0.682142.00

EFFECTIVE ROOM LATENT HEAT 7677.00RC =

GTH= 4.6779 tons

EFFECTIVE ROOM TOTAL HEAT 27234.17 12000

OUTOOOR AIR HEAT

SQ. FT=

TOTAL AREA 406.6825 = 86.94SENSIB 450 CFMx 22 F x ( 0.1 BF) x 1.08 9622.80 LB RC 4.6779LATENT 450 CFMx 70 Gr/lb x ( 0.1 BF) x 0.68 19278.00

SUBTOTAL 28900.80

+ ++ 0.00% % %

GRAND TOTAL HEAT 56134.97

SUN GAIN OR Temp. diff.

SWINGING REVOLVING DOORS

E SENS. HEAT FACTOR

SUPPLY DUCT HEAT GAIN

SUPPLY

DUCT LEAK

FAN H.P.

OUTLET TEMP DIFF

CFM

x

F x

CFM x

RETURN

DUCT HEAT GAIN

RETURN DUCT

LEAK GAIN

HP PUM

P

AND

PIP

Page 2: S202 (4)

HEAT LOAD FORM (computerized computation)

local time

sun time

Hours of Operation: 10 Hours

GR/LB

135

65

70

OUTDOOR AIR

4500

450

00

00

0

CFM

APPARATUS DEW POINT

EFFECTIVE ROOM SENS. HEATEFFECTIVE ROOM TOTAL HEAT

0.7181

F

DEHUMIDIFIED AIR QUANTITY25.65

CFMda

F(rm-outlet)

SUPPLY AIR QUANTITY

CFMsa

CFMda

RESULTING ENT. & LVG CONDITIONS AT APPARATUS

)

)

F

tons

sq. ft

ton