S102 Roles Inertia Fault Level Reactive Power

Embed Size (px)

Citation preview

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    1/29

    System Role of Generation

    Leslie Bryans & Alan Kennedy

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    2/29

    Generators contribute to

    System stability and power quality

    Inertia and fault level

    Reactive power balance SONI will discuss

    Active power balance

    SONI will discuss

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    3/29

    What is Inertia

    It is the energy stored in generators

    because they are rotating.

    They continue to rotate after

    the energy source is removed

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    4/29

    Inertia

    Large spinning machines provide stored energydue to the rotating mass of their rotor, drivingturbine shafts etc. Engineers model this as a

    number of rotating masses.

    When a disturbance occurs e.g. theunanticipated loss of a generator, the stored

    energy is released into the system and arreststhe rate at which the system speed or frequencychanges.

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    5/29

    Restorative power

    Without wind With wind

    smaller

    smaller

    System Frequency Issue

    Solutions wind farms to contribute to restorative power

    and system inertia?

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    6/29

    182MW loss 852MW system load

    0

    50

    100

    150

    200

    250

    300

    -10 -5 0 5 10 15 20 25 30

    Time (secs)

    MW

    48.4

    48.6

    48.8

    49

    49.2

    49.4

    49.6

    49.8

    50

    50.2

    Hz

    frequency

    unit1

    unit2

    Frequency trace

    NI system only - low inertia

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    7/29

    165MW loss 970MW system load

    0

    50

    100

    150

    200

    250

    -10 -5 0 5 10 15 20 25 30

    Time (secs)

    MW

    49

    49.1

    49.2

    49.3

    49.4

    49.5

    49.6

    49.749.8

    49.9

    50

    Hz

    unit1

    unit 2

    freq

    Frequency trace for the combined NI

    & RoI System - higher inertia

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    8/29

    Why is the rate of change of

    system frequency important? We need to understand this better as it

    likely to be a limiting factor in

    accommodating higher levels of wind. ROCOF protection

    Question could this become backup Loss of

    Mains protection? (DG&SEE with Prof. Jim

    McDonald)

    System effects e.g. traditional generation

    auxiliary plant trips; CCGT flame outs.

    Raised with DG&SEE as requiring investigation

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    9/29

    Wind turbines

    Fixed speed turbines seem to deliver an

    inertia of around 4.3MWs/MVA which is

    similar to traditional plant; so do not

    reduce system inertia.

    DFIGs and Fully converted wind farms are

    presently thought to deliver close to

    0MWs/MVA; so at present reduce systeminertia.

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    10/29

    Work done

    In order to understand the problem, wehave explored what happens to inertia andrate of change of frequency with very high

    levels of penetration of wind power on theisland of Ireland.

    This is to understand what we need totackle rather than alarm the presentposition.

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    11/29

    Inertia, Rate of change of

    frequency and frequency nadir

    80% wind operating

    (40% energy target)

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    12/29

    Inertia summer min (~ 80% wind)

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    13/29

    Inertia - winter (~ 80% wind)

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    14/29

    48.60

    48.80

    49.00

    49.20

    49.40

    49.60

    49.80

    50.00

    50.20

    0.0 2.0 4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0

    Hz

    No Wind

    WTGs lift 10% in 3 secs

    WTGs lift 10% in 6 secs

    WTGs lift 5% in 3 secs

    WTGs lift 5% in 6 secs

    WTGs don't lift

    0.14Hz/s

    400MW trip in Winter80% wind

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    15/29

    49.20

    49.30

    49.40

    49.50

    49.60

    49.70

    49.80

    49.90

    50.00

    50.10

    0.0 2.0 4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0

    Hz No Wind

    WTGs lift 10% in 3 secs

    WTGs lift 10% in 6 secs

    WTGs lift 5% in 3 secs

    WTGs lift 5% in 6 secs

    WTGs don't lift

    400MW trip in Summer80% wind

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    16/29

    49.20

    49.30

    49.40

    49.50

    49.60

    49.70

    49.80

    49.90

    50.00

    50.10

    0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

    Hz No Wind

    WTGs lift 10% in 3 secs

    WTGs lift 10% in 6 secs

    WTGs lift 5% in 3 secs

    WTGs lift 5% in 6 secs

    WTGs don't lift

    0.5Hz/sec

    Enlarged Graph section 400MW trip in summer80% wind

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    17/29

    Work by UMIST for DG&SEE

    DFIGs could deliver inertia as required but

    require control modifications

    Hardware transient loading is not anobstacle. ( Prof. Jenkins says that the

    transient loading on gearboxes, drive

    trains etc. falls well within that needed for

    dynamic braking of the turbines.)

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    18/29

    Our Proposal

    To seek a modification to the NI Grid Code

    to require wind turbines to provide inertia

    at 4 6MWs/MVA.

    This would need to be harmonised with an

    equivalent provision in the EirGrid Grid

    Code and Distribution Codes.

    This will be a world first and waiting does

    not seem an option.

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    19/29

    Fault level

    With wind farms

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    20/29

    What is Fault level?

    Fault level is measured in current or MVA.

    When a short circuit occurs a large current flows

    this causes the operation of protective devices

    (fuses and circuit breakers open) to isolate thefault.

    Protection systems are designed to isolate only

    the faulty section of network.

    Fault level is also a measure of system stiffness

    which determines power quality issues.

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    21/29

    High and Low fault level

    Too high fault currents can be hard tointerrupt.

    Too low and the protective devices maynot operate.

    The problem with high penetration of wind

    farms is too low fault levels.(Work is on-going with DG and SEE for the

    UK Grid. They are going to study NI aswell).

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    22/29

    Power quality

    Very low fault level results in excessive

    voltage dips when equipment is switched

    on.

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    23/29

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    24/29

    Our proposal

    To ensure that the fault level tools developed byDG&SEE (which assess fault level throughoutthe range of generation dispatches) are applied

    to the NI network and to consider what furtheraction may be needed. At the extremewe mayneed to convert the distance protection schemesto unit schemes which is very expensive.

    Also, DG&SEE have not considered the knock-on effect of low fault level on the distributionprotection systems. This may be more seriousand potentially intolerable. Further work isrequired.

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    25/29

    Reactive power

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    26/29

    Reactive Power BalanceStatic Balance

    To ensure an adequate voltage everywhere

    on the system and provide reactive power

    requirements to load More heavily loaded transmission system requires

    relatively more reactive power due to IX losses

    Reactive power doesnt travel well on a transmission

    system due to the high X/R ratio, but NI transmission

    system is small.

    Studying the reactive power balance is more

    complex when embedded generation is

    included

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    27/29

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    28/29

    Problem with Embedded Gen

    G

    P

    Q

    R XStep-downTransformer Gen Bus

    loadR X

    P & Q

    Voltage

    Max limit at EG

    Min limit at load

    Back-bonetransmissionnetwork

  • 8/6/2019 S102 Roles Inertia Fault Level Reactive Power

    29/29

    Static Reactive Power Balance

    - Within reason this could be achieved with suitably sited

    capacitors but there are technical difficulties with manycapacitors installed

    Dynamic Reactive Power Balance

    - Needed during and after system disturbances

    - Quantity depends on many factors but rule of thumb isdynamic = static

    - Synchronous generators can supply high levels ofdynamic reactive power

    - Reactive power output of DFIGs and fully-converted windturbines is limited to ~ rated MVA, but even this is of limiteduse on the transmission system

    - Need for alternative forms of dynamic reactive support on

    transmission system eg. SVC, STATCOM, synch-comp