Upload
homer-simp
View
227
Download
0
Embed Size (px)
Citation preview
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
1/29
System Role of Generation
Leslie Bryans & Alan Kennedy
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
2/29
Generators contribute to
System stability and power quality
Inertia and fault level
Reactive power balance SONI will discuss
Active power balance
SONI will discuss
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
3/29
What is Inertia
It is the energy stored in generators
because they are rotating.
They continue to rotate after
the energy source is removed
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
4/29
Inertia
Large spinning machines provide stored energydue to the rotating mass of their rotor, drivingturbine shafts etc. Engineers model this as a
number of rotating masses.
When a disturbance occurs e.g. theunanticipated loss of a generator, the stored
energy is released into the system and arreststhe rate at which the system speed or frequencychanges.
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
5/29
Restorative power
Without wind With wind
smaller
smaller
System Frequency Issue
Solutions wind farms to contribute to restorative power
and system inertia?
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
6/29
182MW loss 852MW system load
0
50
100
150
200
250
300
-10 -5 0 5 10 15 20 25 30
Time (secs)
MW
48.4
48.6
48.8
49
49.2
49.4
49.6
49.8
50
50.2
Hz
frequency
unit1
unit2
Frequency trace
NI system only - low inertia
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
7/29
165MW loss 970MW system load
0
50
100
150
200
250
-10 -5 0 5 10 15 20 25 30
Time (secs)
MW
49
49.1
49.2
49.3
49.4
49.5
49.6
49.749.8
49.9
50
Hz
unit1
unit 2
freq
Frequency trace for the combined NI
& RoI System - higher inertia
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
8/29
Why is the rate of change of
system frequency important? We need to understand this better as it
likely to be a limiting factor in
accommodating higher levels of wind. ROCOF protection
Question could this become backup Loss of
Mains protection? (DG&SEE with Prof. Jim
McDonald)
System effects e.g. traditional generation
auxiliary plant trips; CCGT flame outs.
Raised with DG&SEE as requiring investigation
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
9/29
Wind turbines
Fixed speed turbines seem to deliver an
inertia of around 4.3MWs/MVA which is
similar to traditional plant; so do not
reduce system inertia.
DFIGs and Fully converted wind farms are
presently thought to deliver close to
0MWs/MVA; so at present reduce systeminertia.
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
10/29
Work done
In order to understand the problem, wehave explored what happens to inertia andrate of change of frequency with very high
levels of penetration of wind power on theisland of Ireland.
This is to understand what we need totackle rather than alarm the presentposition.
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
11/29
Inertia, Rate of change of
frequency and frequency nadir
80% wind operating
(40% energy target)
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
12/29
Inertia summer min (~ 80% wind)
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
13/29
Inertia - winter (~ 80% wind)
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
14/29
48.60
48.80
49.00
49.20
49.40
49.60
49.80
50.00
50.20
0.0 2.0 4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0
Hz
No Wind
WTGs lift 10% in 3 secs
WTGs lift 10% in 6 secs
WTGs lift 5% in 3 secs
WTGs lift 5% in 6 secs
WTGs don't lift
0.14Hz/s
400MW trip in Winter80% wind
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
15/29
49.20
49.30
49.40
49.50
49.60
49.70
49.80
49.90
50.00
50.10
0.0 2.0 4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 20.0
Hz No Wind
WTGs lift 10% in 3 secs
WTGs lift 10% in 6 secs
WTGs lift 5% in 3 secs
WTGs lift 5% in 6 secs
WTGs don't lift
400MW trip in Summer80% wind
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
16/29
49.20
49.30
49.40
49.50
49.60
49.70
49.80
49.90
50.00
50.10
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
Hz No Wind
WTGs lift 10% in 3 secs
WTGs lift 10% in 6 secs
WTGs lift 5% in 3 secs
WTGs lift 5% in 6 secs
WTGs don't lift
0.5Hz/sec
Enlarged Graph section 400MW trip in summer80% wind
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
17/29
Work by UMIST for DG&SEE
DFIGs could deliver inertia as required but
require control modifications
Hardware transient loading is not anobstacle. ( Prof. Jenkins says that the
transient loading on gearboxes, drive
trains etc. falls well within that needed for
dynamic braking of the turbines.)
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
18/29
Our Proposal
To seek a modification to the NI Grid Code
to require wind turbines to provide inertia
at 4 6MWs/MVA.
This would need to be harmonised with an
equivalent provision in the EirGrid Grid
Code and Distribution Codes.
This will be a world first and waiting does
not seem an option.
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
19/29
Fault level
With wind farms
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
20/29
What is Fault level?
Fault level is measured in current or MVA.
When a short circuit occurs a large current flows
this causes the operation of protective devices
(fuses and circuit breakers open) to isolate thefault.
Protection systems are designed to isolate only
the faulty section of network.
Fault level is also a measure of system stiffness
which determines power quality issues.
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
21/29
High and Low fault level
Too high fault currents can be hard tointerrupt.
Too low and the protective devices maynot operate.
The problem with high penetration of wind
farms is too low fault levels.(Work is on-going with DG and SEE for the
UK Grid. They are going to study NI aswell).
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
22/29
Power quality
Very low fault level results in excessive
voltage dips when equipment is switched
on.
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
23/29
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
24/29
Our proposal
To ensure that the fault level tools developed byDG&SEE (which assess fault level throughoutthe range of generation dispatches) are applied
to the NI network and to consider what furtheraction may be needed. At the extremewe mayneed to convert the distance protection schemesto unit schemes which is very expensive.
Also, DG&SEE have not considered the knock-on effect of low fault level on the distributionprotection systems. This may be more seriousand potentially intolerable. Further work isrequired.
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
25/29
Reactive power
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
26/29
Reactive Power BalanceStatic Balance
To ensure an adequate voltage everywhere
on the system and provide reactive power
requirements to load More heavily loaded transmission system requires
relatively more reactive power due to IX losses
Reactive power doesnt travel well on a transmission
system due to the high X/R ratio, but NI transmission
system is small.
Studying the reactive power balance is more
complex when embedded generation is
included
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
27/29
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
28/29
Problem with Embedded Gen
G
P
Q
R XStep-downTransformer Gen Bus
loadR X
P & Q
Voltage
Max limit at EG
Min limit at load
Back-bonetransmissionnetwork
8/6/2019 S102 Roles Inertia Fault Level Reactive Power
29/29
Static Reactive Power Balance
- Within reason this could be achieved with suitably sited
capacitors but there are technical difficulties with manycapacitors installed
Dynamic Reactive Power Balance
- Needed during and after system disturbances
- Quantity depends on many factors but rule of thumb isdynamic = static
- Synchronous generators can supply high levels ofdynamic reactive power
- Reactive power output of DFIGs and fully-converted windturbines is limited to ~ rated MVA, but even this is of limiteduse on the transmission system
- Need for alternative forms of dynamic reactive support on
transmission system eg. SVC, STATCOM, synch-comp